IXcellerate Moscow One Datacentre - Phase 1 & 2 Overview

Size: px
Start display at page:

Download "IXcellerate Moscow One Datacentre - Phase 1 & 2 Overview"

Transcription

1 Contents 1. Document Purpose Facility Overview Technical Space Load Density Resilience Engineering Plant Maintenance & Service Restoration Engineering Systems Overview Power Supply Cooling Ventilation Safety and Security Systems Fire Suppression Systems Fire Alarm System Security Systems Security Controls Access Control System CCTV System Connectivity

2 1. Document Purpose This document gives an overview of the IXcellerate Moscow One DataCentre infrastructure and core services at the completion of the Phase 2 of the project. 2. Facility Overview IXcellerate Moscow One DataCentre is located in a warehouse building with the total area of about 6,000 m² in the industrial estate in the North of Moscow. The location is not in an active seismic area and has no hazards in the immediate locality. The site has an area of about 2 hectares and it is fully fenced. The building was constructed from steel and prefabricated panels and commissioned in The building is a single store warehouse with the height of 12 meters. It has two 2-floor annexes on the North and West side of the building with loading bays and technical plant room on the ground floor and office spaces on the first floor. 2.1 Technical Space 2.2 Load Density In phases 1 and 2 the total area of the white space is 1,420 m²: Phase 1 data hall 440 m²; constructed in 2012 Phase 2 data hall 980 m², constructed in 2015 Each data hall comprise a dedicated room with the wall and ceiling fire rating EI90. The floor has a load bearing capacity of 8000kg/ m². A 1,000mm high raised floor with the load bearing capacity of 1800 kg/ m² is installed in the data halls. The clear height in the data hall between the raised floor top level and the data hall roof structure is 4,000mm. Additional two more phases are planned to be added to the facility increasing the capacity up to a total of 6000 m². The facility is designed to provide 4kW per m² of power using room cooling and 12kW per m² using room and in-row cooling. The UPS and cooling systems installed are sized to deliver both the maximum average load density in kw and high-density power to racks where required. 2.3 Resilience The facility is built to offer a high degree of reliability and availability in respect of the critical building services offered to customers. The facility is designed and constructed to operate continuously delivering critical services to the required level of service 24 hours a day, 7 days a week, 52 weeks a year. This is achieved by using a combination of redundant and standby systems. The mechanical and electrical systems are arranged so that no single point of failure within the controls or plant could materially affect the output of that system. Fault tolerance has also been built into the systems so that predictable failure modes do not interrupt service to customers. 2

3 There are two fully separate dark fiber routes into the building and two separate meet-me and carrier rooms. The following table illustrates the resilience strategy for each of the critical systems: Distribution routes Electrical Mechanical Power streams Four independent streams CHW Pipework Two circuits with the ability to interconnect (at Phase 3) Plant Transformers Single TX per UPS string Chillers N+1 in circuit Generators Single unit per UPS string CRAC units N+1 UPS N+N strings Pumps N+1 in circuit Physical Separation UPS and switchgear Separate room AHUs Via use of fire dampers Transformers Separate rooms Chillers External Generators Separate external containers CHW pumps One set per compartment Concurrently maintainability Fault Tolerance (single event) All equipment Yes All equipment Yes UPS module on string Yes Pipework Yes Generator unit Yes Ductwork Yes HV/LV switchgear Yes Chiller unit Yes CRAC unit Yes The Tier classification is Tier 3+. The facility has been certified by IBM as Level 3, the certificate is given for the data centre project, construction and operation in the accordance with globally recognised IBM Reliability Rating System. The additional fault tolerance makes the site closer to Tier 4 than Tier Engineering Plant Maintenance & Service Restoration The engineering plant vendors used in IXcellerate Moscow One DataCentre not only provide high quality equipment, but also high levels of service. The equipment maintenance program is built from two key sources; firstly the equipment provider s specification, ensuring the equipment will deliver the specified level of availability. Secondly, a failure mode analysis of the systems is performed to ascertain what resources, training and spare parts are needed to be able to restore service within the SLAs provided to customers. The service level delivered by the combination of design, maintenance and service restoration capability, deliver a level of availability higher that the % availability promised to customers by the SLA. 3

4 3. Engineering Systems Overview 3.1 Power Supply Power supply is provided from four independent power streams with minimal points of failure. Power supply to the facility is from two independent transformer substations with the total electrical load of 5,000kVA: 2x1,000kVA transformers; and 2x1,600kVA transformers Each UPS string is fed by a dedicated transformer. UPS power supply is provided by four UPS strings as follows: 2 strings with 2x400kVA UPS in each string. Each UPS string will be fed by a dedicated 1,000kVA transformer; 2 strings with 2x300kVA UPS in each string. Each UPS string will be fed by a dedicated 1,600kVA transformer Total UPS power available after completion of Phase 2 will be 1,180kW following N+N redundancy (up to 1,760kW following distributed redundancy). Standby power is provided by a low voltage diesel-generator which will deliver power at low voltage (0.4kV) to each LV Switchboard (UPS string). Diesel generators are installed in containers on the site. Generator fuel is stored on site in containers and will be sufficient for 72 hours of operation. Additional fuel storage can be added if needed. Three suppliers provide refueling within eight hours of the request. 3.2 Cooling 3.3 Ventilation Cooling in the data hall is provided by a combination of: 4x100kW Emerson DX down flow CRAC units installed at Phase 1. Total cooling capacity of the DX units is 200kW (N+N redundancy); 2x400kW and 2x600kW air cooled Emerson chillers with free cooling (N+1 redundancy) N+1 capacity CRAH units in the data hall, > N+1 CRAH unit redundancy The system is designed to operate at +36 C (+45 C maximum) in accordance with ASHRAE. Total cooling capacity will be 1,400kW with the ability to upgrade capacity if needed to 2MW. A chilled mains loop is installed in Phase 2 hall with RAC connection branches and the ability to add in-row cooling for high-density racks. Humidity control is provided by steam humidifiers as part of CRAC units. All environmental conditions are monitored by an integrated building management system. Both data halls are equipped with mechanical air supply and extract ventilation system. Fresh air supply system is designed to provide 0.5 AC/hr. in the data hall. Positive air pressure is maintained in both data halls. 4

5 4. Safety and Security Systems 4.1 Fire Suppression Systems The data centre features a multi-level fire safety system combining prevention, early detection and focused response: Level 1: Keeping the data centre tidy and free of fire hazards. Level 2: Regular inspection of the data centre by maintenance staff. Level 3: VESDA smoke detection system monitoring the air in the server rooms and providing early warning. It detects fire hazard very early, before the emergence of smoke or fire. Level 4: An automatic fire notification system and fire alarm system. Level 5: Response by data centre staff using handheld fire extinguishers and water mist fire hoses. Level 6: Automatic fire suppression with HI-FOG water mist fire suppression. The Level 3 fire detection through VESDA is enhanced by positioning probes in the flow of the hot air return from the rows of racks so that a location of a possible fire is quickly identified. A Marioff HI-FOG fire suppression system protects the data halls and UPS rooms. HI-FOG sprinklers are installed both at high and low (floor void) levels. The HI-FOG system utilizes water mist as a fire agent. The HI-FOG system pipework installed in the data halls and UPS rooms are dry and pressurized so in normal conditions there is no water in the pipes. The operation of the HI-FOG system is triggers by a combination of: Disruption of the sprinkler thermal bulb by high temperature and an air pressure drop in the pipework; AND Fire alarm from the fire control system The dual action approach limits accidental discharge. 4.2 Fire Alarm System A dedicated analogue addressable fire alarm system is installed for protection of all IXcellerate Moscow One DataCentre premises. Optical analogue addressable smoke detectors are installed at high and low (floor void) levels in the data halls and UPS rooms. The fire alarm system is integrated with the data centre building management system which controls the following systems: Marioff HI-FOG fire suppression system; Access control system; Ventilation system The cooling system in the data hall remains in operation in case of a fire alarm. 4.3 Security Systems Security Controls Integrated procedures, systems and teams provide security. Two teams work closely together to deter, detect, deny, delay and defend all security threats as appropriate. The majority of the activity of the team is to ensure the existing defenses are in good repair to deter threats; detect threats through monitoring via multiple mechanisms such as visual inspection and cameras; access to all areas is denied to any person who does not have pre-authorisation to access the area; delaying threats is done through multiple layers of security as indicated below and defense is supported by a rapid armed response from local law enforcement. 5

6 4.3.2 Access Control System IXcellerate Moscow One DataCentre has the following levels of security: CCTV System Clear perimeter with wall and barbed wire fence, regularly patrolled Secured entrance gate to the site; Secured entrance to the building s entrance lobby with the use of intercom system; Secured entrance lobby with the turnstile controlled by the security guard, card reader and a biometric reader; Secured access to the data halls, UPS room and auxiliary with the use of card readers. Access doors to Phase 1 and 2 data halls are also equipped with biometric readers. Additional security can be provided for customers such as cages with biometric access control. All information from the access control system transmits to the data centre building management system. All premises of IXcellerate Moscow One Data Centre are equipped with the CCTV system. All entrance doors, corridors and premises are under CCTV system control. Data stored over 90 days. Additional CCTV cameras may be installed by the specific customer s demand. 5. Connectivity A structured cabling system is used by all customers and provides the ability for customers to connect to each other or telecoms carriers in the two meet-me rooms. Each cross-connect is installed and tested by our factory certified technicians. This structured approach enables changes, troubleshooting and repairs to be fast and efficient. Dual meet-me rooms and two separate cable entrances enable full redundancy of communication connections. A third meet-me room and cable entrance will be added in future phases. Private and public peering is available from Eurasia:peering and MSK-IX (Moscow Internet Exchange). More than thirty local and international carriers are present in the facility. 6

brightsolid Data Hall 1 Keysource Technical Specifications

brightsolid Data Hall 1 Keysource Technical Specifications brightsolid Data Hall 1 Keysource Technical Specifications Page 1 Introduction A Data Centre is a highly controlled environment that provides IT to external organisations seeking to outsource their requirements

More information

POWERING A CONNECTED ASIA. Pacnet Hong Kong DataSpace1 Technical Specifications. Advanced Data Center Facility for Multi-Site Enterprises

POWERING A CONNECTED ASIA. Pacnet Hong Kong DataSpace1 Technical Specifications. Advanced Data Center Facility for Multi-Site Enterprises POWERING A CONNECTED ASIA Pacnet Hong Kong DataSpace1 Technical Specifications Advanced Data Center Facility for Multi-Site Enterprises Pacnet Hong Kong DataSpce1 (HKDS1) provides an ideal environment

More information

Datacentre Newbridge Data sheet

Datacentre Newbridge Data sheet Datacentre Newbridge Data sheet Data sheet Datacentre Newbridge Find us 7 Claylands Road Edinburgh EH28 8LF Scotland With 10 datacentres, over 4,500 racks and a 10Gb resilient core network between our

More information

Datacentre Milton Keynes Hall C Data sheet

Datacentre Milton Keynes Hall C Data sheet Datacentre Milton Keynes Hall C Data sheet Data sheet Datacentre Milton Keynes Hall C Find us With 10 datacentres, over 4,500 racks and a 10Gb resilient core network between our datacentre locations, Pulsant

More information

Data Centre Stockholm II, Sweden Flexible, advanced and efficient by design.

Data Centre Stockholm II, Sweden Flexible, advanced and efficient by design. Data Centre Stockholm II, Sweden Flexible, advanced and efficient by design. TelecityGroup Kvastvägen 25-29 128 62 Sköndal Stockholm Sweden Tel: +46 (0) 8 799 3800 se.info@telecity.com www.telecitygroup.se

More information

Dude Solutions Business Continuity Overview

Dude Solutions Business Continuity Overview Dude Solutions Business Continuity Overview Table of Contents Overview.... 2 Primary and Disaster Recovery Data Centers.... 2 Network Infrastructure.... 3 Emergency Processes.... 3 Power and Cooling Systems....

More information

DATA CENTRE. JT Five Oaks. Facility Product Description. Data Centre Services

DATA CENTRE. JT Five Oaks. Facility Product Description. Data Centre Services JT Five Oaks DATA CENTRE Facility Product Description JT s Data Centre Hosting Service provides a secure computer room environment with protected and backup power, security and bandwidth. Data Centre specification

More information

PISCATAWAY, NEW JERSEY NJ1 DATA CENTERS POWERED BY TRUST

PISCATAWAY, NEW JERSEY NJ1 DATA CENTERS POWERED BY TRUST PISCATAWAY, NEW JERSEY NJ1 DATA CENTERS POWERED BY TRUST THE CENTER THAT NEVER SLEEPS The greater New York metro area is a pulsing capital of industry and finance alive 24 x 7 x 365 with critical transactions

More information

CenturyLink Data Center Services Omaha, Nebraska

CenturyLink Data Center Services Omaha, Nebraska CenturyLink Data Center Services Omaha, Nebraska HIGH AVAILABILITY ENTERPRISE COMPUTING Designed and equipped to meet the demands of enterprises, wholesale businesses and government agencies, CenturyLink

More information

Datacentre Milton Keynes Data sheet

Datacentre Milton Keynes Data sheet Datacentre Milton Keynes Data sheet Data sheet Datacentre Milton Keynes Find us With 10 datacentres, over 4,500 racks and a 10Gb resilient core network between our datacentre locations, Pulsant has the

More information

JT Rue Des Pres DATA CENTRE

JT Rue Des Pres DATA CENTRE JT Rue Des Pres DATA CENTRE Facility Product Description JT s Data Centre Hosting Service provides a secure computer room environment with protected and backup power, security and bandwidth. Data Centre

More information

WHITE PAPER. Solutions OnDemand Hosting Overview

WHITE PAPER. Solutions OnDemand Hosting Overview WHITE PAPER SAS Title Solutions OnDemand Hosting Overview ii Contents Overview... 1 Cary 1 (US) Facility Specifications...2 Cary 2 (US) Facility Specifications (SAS New Cloud Computing Center)...3 Charlotte

More information

COLOCATION 1/4 RACK RACK COLD AISLE CONTAINEMENT PRIVATE CAGE PRIVATE SUITE FLEXIBLE PRICING OPTIONS

COLOCATION 1/4 RACK RACK COLD AISLE CONTAINEMENT PRIVATE CAGE PRIVATE SUITE FLEXIBLE PRICING OPTIONS 1 COLOCATION Experience the most flexible datacenters for mission-critical infrastructure in a highly secure, efficient and reliable environment. Enjoy future-proof and agile colocation services that provide

More information

Datacentre Reading East 2 Data sheet

Datacentre Reading East 2 Data sheet Datacentre Reading East 2 Data sheet Data sheet Datacentre Reading East 2 Find us With 10 datacentres, over 4,500 racks and a 10Gb resilient core network between our datacentre locations, Pulsant has the

More information

Data Center NJ1. Piscataway, NJ

Data Center NJ1. Piscataway, NJ Data Center NJ1 Piscataway, NJ powerful/ efficient /reliable solutions > Data Center NJ1 ABOUT DUPONT FABROS TECHOLOGY (DFT) DFT is a leading owner, developer, operator and manager of wholesale data centers.

More information

Twin Core Data Center Munich

Twin Core Data Center Munich Twin Core Data Center Munich T-Systems Data Center Munich Sister Site, Back Up Location/Twin Core DC ALL (Allach) 1st Route: 13km DWDM System 2nd Route: 27km DC EIP (Euro Industrie Park) Point to Point

More information

Dazelidis Thanos - Product Manager Rittal Greece 1

Dazelidis Thanos - Product Manager Rittal Greece 1 Dazelidis Thanos - Product Manager Rittal Greece 1 Facility Location Lefdal Mine is located in the region Sogn og Fjordane between Måløy and Nordfjordeid. It is situated next to a deep, cold fjord with

More information

Tier IV Standards as Specified in the TIA 942 Document

Tier IV Standards as Specified in the TIA 942 Document S No Architectural Proximity of visitor parking to data 18.3 m / 60 ft minimum separation with physical barriers to prevent vehicles from 1 center perimeter building walls driving closer 2 Building Construction

More information

CARRIER NEUTRAL, PROVIDING ACCESS TO A RICH CONNECTIVITY AND CLOUD ECOSYSTEM

CARRIER NEUTRAL, PROVIDING ACCESS TO A RICH CONNECTIVITY AND CLOUD ECOSYSTEM CARRIER NEUTRAL, PROVIDING ACCESS TO A RICH CONNECTIVITY AND CLOUD ECOSYSTEM Amsterdam Technical Specification UNINTERRUPTED POWER BESPOKE SOLUTIONS NETWORK DENSE CLOUD CONNECTIVITY GLOBAL SWITCH Global

More information

NTT Communications data center services. Key european data centers

NTT Communications data center services. Key european data centers NTT Communications data center services Key european data centers NTT Communications can offer our customers the following data center services: Colocation pre-provisioned packages Colocation bespoke solutions

More information

BASELAYER CORE PA20 Power Module

BASELAYER CORE PA20 Power Module TM TM PA20 Power Module The CORE PC20 Power Module is a state of the art switchboard and UPS featuring modularized, critical components and delivers a configurable conditioned power supply. HIGHLIGHTS

More information

Data Center. Tai Po Data Center

Data Center. Tai Po Data Center Data Center Tai Po Data Center TAI PO DATA CENTER Nexcenter The Global Data Center Vision NTT Communications offers data center services at hundreds of locations worldwide under the brand name Nexcenter.

More information

DATA CENTRE. JT First Tower Lane. Facility Product Description. Data Centre Services

DATA CENTRE. JT First Tower Lane. Facility Product Description. Data Centre Services JT First Tower Lane DATA CENTRE Facility Product Description JT s Data Centre Hosting Service provides a secure computer room environment with protected incoming power supplies and a fully resilient network

More information

AVANTAGE DATA CENTER. The only ecological «green» data center in Russia with application of the best innovative technologies

AVANTAGE DATA CENTER. The only ecological «green» data center in Russia with application of the best innovative technologies AVANTAGE DATA CENTER The only ecological «green» data center in Russia with application of the best innovative technologies AVANTAGE 3 700 m 2 Administrative building 14 diesel-rotor uninterrupted power

More information

FACT SHEET: IBM NEW ZEALAND DATA CENTRE

FACT SHEET: IBM NEW ZEALAND DATA CENTRE FACT SHEET: IBM NEW ZEALAND DATA CENTRE IBM and the Data Centre IBM is the largest occupier of data centre space in the world and currently owns or occupies approximately one million square metres globally.

More information

Course Description. Audience. Prerequisites. : Course CTDC : Certified TIA-942 Design Consultant. Course Outline :: CTDC ::

Course Description. Audience. Prerequisites. : Course CTDC : Certified TIA-942 Design Consultant. Course Outline :: CTDC :: Module Title Duration : Course CTDC : Certified TIA-942 Design Consultant : 3 days Course Description Data centres are at the core of many organisations. Downtime of the data centre could lead to major

More information

Art and Science of Building NUS Data Centres

Art and Science of Building NUS Data Centres Art and Science of Building NUS Data Centres DATA CENTRE @ NUS Contents I. Nostalgia II. III. IV. Science of Elements in a Data Centre NUS DC Live Migration the Art and Challenges Milestones in Pictures

More information

MD-ALPHA DATA CENTER. Hagerstown, Maryland

MD-ALPHA DATA CENTER. Hagerstown, Maryland DATA CENTER Hagerstown, Maryland TM Capital Data Centers, Inc. Data Center Our Vision will provide its customers with affordable co-location and managed services solutions that stringently protect mission-critical

More information

Data Center SC1. Santa Clara, CA

Data Center SC1. Santa Clara, CA Data Center SC1 Santa Clara, CA powerful/ efficient /reliable solutions > Data Center SC1 ABOUT DUPONT FABROS TECHOLOGY (DFT) DFT is a leading owner, developer, operator and manager of wholesale data centers.

More information

RFP Annex A Terms of Reference UNHCR HQ Data Centre Colocation Service

RFP Annex A Terms of Reference UNHCR HQ Data Centre Colocation Service RFP 2017 845 Annex A Terms of Reference UNHCR HQ Data Centre Colocation Service Version 1 Contents Project objectives... 1 Background... 1 Scope... 1 Timeframe and Cost... 4 Stakeholders, roles and responsibilities...

More information

Kifer Industrial Park

Kifer Industrial Park FEATURES ±56,358 SF Data Center / Lab / Manufacturing Building The entire facility is built-out with raised floor data center and data center support space Heavy Power Multiple telecom providers Pre-action

More information

Colocation Checklist Not all data centers are created equal.

Colocation Checklist Not all data centers are created equal. Colocation Checklist Not all data centers are created equal. They vary in performance, reliability, control and security standards. Know what to look for in a colocation provider with this comprehensive

More information

2000 kw, Tier 3, Chilled Water, Prefabricated, sq. ft.

2000 kw, Tier 3, Chilled Water, Prefabricated, sq. ft. [Reference Design 64] 2000 kw, Tier 3, Chilled Water, refabricated, 23700 sq. ft. DESIGN OVERVIEW Data Center IT Capacity 2000 kw Target Availability Tier 3 Annualized E at 100% Load 1.64 in Miami, FL

More information

CenturyLink Data Center Services Herndon, Virginia

CenturyLink Data Center Services Herndon, Virginia CenturyLink Data Center Services Herndon, Virginia DATA CENTER SOLUTIONS TO SUPPORT GLOBAL ENTERPRISE IT The IT environment is rapidly changing. Organizations are expanding their IT infrastructure to accommodate

More information

The Region s Leading Data Center Developer, Manager and Operator

The Region s Leading Data Center Developer, Manager and Operator The Region s Leading Data Center Developer, Manager and Operator C O R P O R A T E P R O F I L E C O R P O R A T E P R O F I L E Overview CSF Group is principally engaged in the business of providing a

More information

Rack Colocation Hosting. Data Centre Solutions Expertly Engineered

Rack Colocation Hosting.   Data Centre Solutions Expertly Engineered Rack Colocation Hosting www.workspace-technology.com Data Centre Solutions Expertly Engineered We are committed to ensuring the very best data centre environment for your business Rack Colocation Hosting

More information

AMS6, Amstel Business Park Campus. Highly connected, Energy efficient data centre. Duivendrechtse kade 80A 1096 AH Amsterdam Netherlands

AMS6, Amstel Business Park Campus. Highly connected, Energy efficient data centre. Duivendrechtse kade 80A 1096 AH Amsterdam Netherlands AMS6, Amstel Business Park Campus Highly connected, Energy efficient data centre. Duivendrechtse kade 80A 1096 AH Amsterdam Netherlands Tel: +31 (0) 20 592 9263 Nl.info@telecity.com www.telecitygroup.nl

More information

DATACENTER COLOCATION. Flexible, Secure and Connected

DATACENTER COLOCATION. Flexible, Secure and Connected DATACENTER COLOCATION Flexible, Secure and Connected Flexible Solutions for Your Requirements Contents Your Goals 2 Compound and Buildings 4 Security 6 Infrastructure 8 Free Choice 10 Good Reasons 12 Our

More information

3300 kw, Tier 3, Chilled Water, 70,000 ft 2

3300 kw, Tier 3, Chilled Water, 70,000 ft 2 [Reference Design 22] 3300 kw, Tier 3, Chilled Water, 70,000 ft 2 DESIGN OVERVIEW Data Center IT Capacity 1100 kw per Data Hall 3 Independent Data Halls Design Application Range This design can be applied

More information

A next generation Colocation data centre for Birmingham city centre

A next generation Colocation data centre for Birmingham city centre A next generation Colocation data centre for Birmingham city centre Presenter: Russel Smith The Exponential Growth in Data BIG Data Social Networking Cloud Multi Media Device Apps SMART Cities High density,

More information

Data Centre Solutions. Data Centre Solutions Expertly Engineered

Data Centre Solutions.   Data Centre Solutions Expertly Engineered Data Centre Solutions www.workspace-technology.com Data Centre Solutions Expertly Engineered We will expertly deliver your data centre using our world-class skills and capabilities. Data Centre Solutions

More information

DATACENTER BERLIN Definitely a Good Perspective

DATACENTER BERLIN Definitely a Good Perspective DATACENTER BERLIN Definitely a Good Perspective We Do not Take any Chances: For the Security of Your IT Systems. Contents Your Goals 2 Compound and Buildings 4 Security 6 Infrastructure 8 Free Choice 14

More information

AT&T Enterprise Hosting Services

AT&T Enterprise Hosting Services AT&T Enterprise Hosting Services Irvine, CA Internet Data Center Last Update: 09.25.2008 2008 AT&T Intellectual Property. All rights reserved. AT&T and the AT&T logo are trademarks of AT&T Intellectual

More information

The Shared Data Centre Project

The Shared Data Centre Project David Birds - Data Centre Manager Oxford University Computing Services Networkshop 39 13 th April 2011 Why do we need it? 1. Additional data centre capacity. 2. The opportunity to provide a higher level

More information

MSYS 4480 AC Systems Winter 2015

MSYS 4480 AC Systems Winter 2015 MSYS 4480 AC Systems Winter 2015 Module 12: DATA CENTERS By Satwinder Singh 14/05/2015 1 Data Centers Data Centers are specialized environments that safeguard your company's most valuable equipment and

More information

ASCENT DATA CENTER. 30 MW Data Center Enterprise Grade Facility LEED Gold ATLANTA, GA ABOUT ASCENT CO LO CAT I O N SUI T E S AVAI LAB LE NO W!

ASCENT DATA CENTER. 30 MW Data Center Enterprise Grade Facility LEED Gold ATLANTA, GA ABOUT ASCENT CO LO CAT I O N SUI T E S AVAI LAB LE NO W! ASCENT DATA CENTER CO LO CAT I O N SUI T E S AVAI LAB LE NO W! ATLANTA, GA 30 MW Data Center Enterprise Grade Facility LEED Gold ABOUT ASCENT Ascent Data Center is located in the greater Atlanta, Georgia

More information

Access UK Ltd. Data centre Security. Data Centre Summary v.2.0 _ December Date: 12 th January Version: 1.1. Parkinson / Daniel Gould

Access UK Ltd. Data centre Security. Data Centre Summary v.2.0 _ December Date: 12 th January Version: 1.1. Parkinson / Daniel Gould Access UK Ltd Data centre Security Date: 12 th January 2017 Version: 1.1 Authors: Tracy Wiseman/ Rob Parkinson / Daniel Gould Table of Contents Table of Contents... 2 Introduction... 3 Our Certifications...

More information

DATA CENTRE & COLOCATION

DATA CENTRE & COLOCATION DATA CENTRE & COLOCATION RISING DEMAND FOR HOSTED SERVICES When it comes to hosted IT infrastructure, organisations are looking for highly resilient, highly available and highly scalable facilities at

More information

Thermal management. Thermal management

Thermal management. Thermal management Thermal management Thermal management Managing thermal loads is a major challenge for all Data Centre operators. Effecting proper control of the thermal environment drives energy consumption and ultimately

More information

World Class. Globally Certified. High Availability.

World Class. Globally Certified. High Availability. Intellicentre 2 World Class. Globally Certified. High Availability. Intellicentre 2 Macquarie Park, Sydney 2 Intellicentre 2 A new generation of data centre solutions. Australia s first showcase Tier III

More information

1.0 Executive Summary. 2.0 Available Features & Benefits

1.0 Executive Summary. 2.0 Available Features & Benefits Statement Of Work Energy Management Services Table of Contents 1.0 Executive Summary 2.0 Available Features & Benefits 3.0 Assessment Deliverables Selection 4.0 On Site Assessment Activities 5.0 Exclusions

More information

MINNEAPOLIS MARKET STREAM PRIVATE DATA CENTER CHASKA, MINNESOTA Ross Avenue, Suite 2800 Dallas, Texas 75201

MINNEAPOLIS MARKET STREAM PRIVATE DATA CENTER CHASKA, MINNESOTA Ross Avenue, Suite 2800 Dallas, Texas 75201 STREAM PRIVATE DATA CENTER MINNEAPOLIS MARKET CHASKA, MINNESOTA 2001 Ross Avenue, Suite 2800 Dallas, Texas 75201 www.streamdatacenters.com 866.301.0901 2 SECURE INDEPENDENT EFFICIENT SECURE Secured perimeter

More information

DATACENTER CAMPUS FRANKFURT. Plan for Every Second

DATACENTER CAMPUS FRANKFURT. Plan for Every Second DATACENTER CAMPUS FRANKFURT Plan for Every Second We Give All Our Energy and Dedication to Create Safe Environments by Making Risks Manageable Contents Your Goals 2 Compound and Buildings 4 Security 6

More information

RFP Questions Guideline For Data Center Buyers

RFP Questions Guideline For Data Center Buyers RFP Questions Guideline For Data Center Buyers Rev: 00W0052015 1 P a g e This guideline document is a supporting download for our webinar titled 5 RFP Questions Data Center Buyers Must Ask a Provider and

More information

CUS. Introducing New Zealand s most connected data centre. Albany, Auckland

CUS. Introducing New Zealand s most connected data centre. Albany, Auckland Introducing New Zealand s most connected data centre Albany, Auckland Superior connectivity Power density Premium performance High grade security V CUS communications Vocus new data centre is a premium

More information

KEEPING YOU OUT IN FRONT

KEEPING YOU OUT IN FRONT URBACON DATA CENTRE SOLUTIONS KEEPING YOU OUT IN FRONT A next generation data centre in the core of downtown Toronto DOWNTOWN DATA CENTRE 281 FRONT STREET TORONTO, ON 1 2 X URBACON BUILDING GROUP 70 Lake

More information

THE TELEPORT. Merrill Lynch Data Center. TELEHOUSE Center. Teleport I Teleport II AT&T / Globecast. Ariel view of the Teleport

THE TELEPORT. Merrill Lynch Data Center. TELEHOUSE Center. Teleport I Teleport II AT&T / Globecast. Ariel view of the Teleport THE TELEPORT Merrill Lynch Data Center TELEHOUSE Center Teleport I Teleport II AT&T / Globecast Ariel view of the Teleport THE TELEPORT Major Features: Front Entrance to the Teleport Established in 1985

More information

DUB4. An innovative data centre. Resilience. Power. Flexibility AT NORTHWEST BUSINESS PARK

DUB4. An innovative data centre. Resilience. Power. Flexibility AT NORTHWEST BUSINESS PARK DUB4 AT NORTHWEST BUSINESS PARK An innovative data centre Resilience. Power. Flexibility Unit 14 Northwest Business Park, Ballycoolin, Dublin 14 +353 1 4611200 ie.info@telecity.com www.telecity.ie Introducing

More information

Open Access. Definitions

Open Access. Definitions Open-IX Data Center Technical Standards Version 2.0, January 1, 2018 Questions: dc-group@open-ix.org The purpose of the Open- IX Data Center Technical Standards document is to establish a recommended standard

More information

1200 West 7th Street, Los Angeles, CA Smart.

1200 West 7th Street, Los Angeles, CA Smart. Overview 1200 West 7th Street, Los Angeles, CA 90017 West 7 Center is conveniently located at 1200 West 7th Street in downtown Los Angeles near the 10 and 110 freeway. This tier III datacenter facility

More information

Data Center Design and the ANSI/TIA-942 Standard

Data Center Design and the ANSI/TIA-942 Standard Data Center Design and the BICSI Regional Meeting Ellicott, MD Rick Foster RCDD,TLT Communications Infrastructure Group July 27, 2006 What is ANSI/TIA-942? Published by TIA in April 2005 Telecommunications

More information

INT 492 : Selected Topic in IT II (Data Center System Design) 3(3-0-6)

INT 492 : Selected Topic in IT II (Data Center System Design) 3(3-0-6) INT 492 : Selected Topic in IT II (Data Center Design) 3(3-0-6) การออกแบบระบบศ นย สารสนเทศ Overview The American Society of Heating, Refrigeration and Air-Conditioning Engineers (ASHRAE) Technical Committee

More information

200 kw, Tier 3, Chilled Water, 5250 ft 2

200 kw, Tier 3, Chilled Water, 5250 ft 2 [eference Design 4] 200 kw, Tier 3, Chilled Water, 5250 ft 2 DESIGN OVEVIEW Data Center IT Capacity 200 kw Adaptable from 50 kw to 600 kw Target Availability Tier 3 Annualized UE at 100% Load 1.67 in Miami,

More information

9.6 MW, Traditional IT and OCP-compatible, Indirect Air Economizer, m 2

9.6 MW, Traditional IT and OCP-compatible, Indirect Air Economizer, m 2 [Reference esign 62] 9.6 MW, Traditional IT and OC-compatible, Indirect Air Economizer, 16970 m 2 ESIGN OVERVIEW ata Center IT Capacity 9.6 MW Target Availability Tier III with 2N power distribution and

More information

STATE OF THE ART DATA CENTRES

STATE OF THE ART DATA CENTRES DATA CENTRES STATE OF THE ART DATA CENTRES In recent years, Data Centres have become increasingly important to businesses of all sizes as a higher volume of customers choose to host their servers with

More information

ENABLING DATA-DRIVEN PHILIPPINE ENTERPRISES VITRO DATA CENTER MAKATI A NEXCENTER-CERTIFIED FACILITY

ENABLING DATA-DRIVEN PHILIPPINE ENTERPRISES VITRO DATA CENTER MAKATI A NEXCENTER-CERTIFIED FACILITY ENABLING DATA-DRIVEN PHILIPPINE ENTERPRISES VITRO DATA CENTER MAKATI A NEXCENTER-CERTIFIED FACILITY TOTAL BUILDING AREA: TOTAL FLOOR AREA OF SERVER FARMS: RAISED FLOOR HEIGHT: 18,700SQM 6,800SQM 900MM

More information

Passive RDHx as a Cost Effective Alternative to CRAH Air Cooling. Jeremiah Stikeleather Applications Engineer

Passive RDHx as a Cost Effective Alternative to CRAH Air Cooling. Jeremiah Stikeleather Applications Engineer Passive RDHx as a Cost Effective Alternative to CRAH Air Cooling Jeremiah Stikeleather Applications Engineer Passive RDHx as a Cost Effective Alternative to CRAH Air Cooling While CRAH cooling has been

More information

Datacentres & Colocation

Datacentres & Colocation Datacentres & Colocation Connectivity without compromise Datacentres & Colocation Stability, security and privacy paramount to your business needs M24Seven Colocation allows customers to place their server(s)

More information

Total Modular Data Centre Solutions

Total Modular Data Centre Solutions Sector Data Centre Total Modular Data Centre Solutions www.airedale.com BRITISH MANUFACTURER ENERGY EFFICIENCY CONTROLS SERVICE TRAINING 01 Standardised Modular Designs to fit your needs Our modular system

More information

Modular & Mobile Data Centre Solutions. Data Centre Solutions Expertly Engineered

Modular & Mobile Data Centre Solutions.     Data Centre Solutions Expertly Engineered Modular & Mobile Data Centre Solutions www.workspace-technology.com www.mobiledatacentre.com Data Centre Solutions Expertly Engineered ...providing clients with complete agility, delivering a scalable

More information

Mission Critical Facilities & Technology Conference November 3, 2011 Cooling 101. Nick Gangemi Regional Sales Manager Data Aire

Mission Critical Facilities & Technology Conference November 3, 2011 Cooling 101. Nick Gangemi Regional Sales Manager Data Aire Mission Critical Facilities & Technology Conference November 3, 2011 Cooling 101 Nick Gangemi Regional Sales Manager Data Aire Agenda Exactly what are we talking about ASHRAE TC 9.9 Design best practices

More information

84 kw, Tier 3, Direct Expansion, 937 ft 2

84 kw, Tier 3, Direct Expansion, 937 ft 2 [Reference Design 42] 84 kw, Tier 3, Direct Expansion, 937 ft 2 DESIGN OVERVIEW Data Center IT Capacity 84 kw Target Availability Tier 3 Annualized PUE at 100% Load 1.712 Total Racks and Average Density

More information

An Adaptive Data Center for Dynamic IT Aligned Energy s Dallas-Plano Data Center

An Adaptive Data Center for Dynamic IT Aligned Energy s Dallas-Plano Data Center An Adaptive Data Center for Dynamic IT Aligned Energy s Dallas-Plano Data Center 2800 Summit Avenue Plano, TX 75074 800.232.2817 An adaptive data center Business needs and IT loads are moving targets.

More information

Data Center. Data Centers in Hong Kong

Data Center. Data Centers in Hong Kong Data Center Data Centers in Hong Kong DATA CENTERS IN HONG KONG Nexcenter The Global Data Center Vision NTT Communications offers data center services at hundreds of locations worldwide under the brand

More information

Industry leading low energy evaporative fresh air cooling.

Industry leading low energy evaporative fresh air cooling. Industry leading low energy evaporative fresh air cooling. Freecool Evaporative Free Air Cooling by Workspace Technology delivers innovative low energy cooling for a range of applications including data

More information

5.2 MW, Pod-based build, Chilled Water, ft 2

5.2 MW, Pod-based build, Chilled Water, ft 2 [Reference Design 65] 5.2 MW, Pod-based build, hilled Water, 85000 ft 2 DESIGN OVERVIEW Data enter apacity 5.2 MW Target Availability Tier III with 2N power distribution and less-redundant generator configuration

More information

Data Center and Colocation RFP Template

Data Center and Colocation RFP Template Data Center and Colocation RFP Template TABLE OF CONTENTS Client Organization Details... 3 Background Information... 3 Existing IT Infrastructure... 3 Business Requirements... 3 Vendor Corporate Profile...

More information

Introduction. Service and Support

Introduction. Service and Support We Do It Better. Contents Introduction... 3 Service and Support... 3 Data Center Details... 4 Security... 4 Location... 4 Power... 4 Humidification... 5 AC... 5 Cooling... 6 Datacenter Features... 6 SAS

More information

Data Center Facility Analysis Project. Final Presentation Wednesday, July 22, :30 3:30 PM

Data Center Facility Analysis Project. Final Presentation Wednesday, July 22, :30 3:30 PM Data Center Facility Analysis Project Final Presentation Wednesday, July 22, 2009 1:30 3:30 PM 1 Commonwealth Technology Center Conference Rooms 1 & 2 Enterprise Server Farm (ESF) Facility Data: 1 Technology

More information

TIER 3+ CARRIER NEUTRAL DATA CENTER TELEPOINT SOFIA EAST THE LATEST ADDITION TO OUR FAST-GROWING DATA CENTER LOCATIONS.

TIER 3+ CARRIER NEUTRAL DATA CENTER TELEPOINT SOFIA EAST THE LATEST ADDITION TO OUR FAST-GROWING DATA CENTER LOCATIONS. TIER 3+ CARRIER NEUTRAL DATA CENTER TELEPOINT SOFIA EAST THE LATEST ADDITION TO OUR FAST-GROWING DATA CENTER LOCATIONS www.telepoint.bg INTRODUCTION Telepoint is a TIER 3+ Carrier Neutral Data Center in

More information

Data Center Infrastructure Management (DCIM) By Jesse Zhuo

Data Center Infrastructure Management (DCIM) By Jesse Zhuo Data Center Infrastructure Management (DCIM) By Jesse Zhuo Agenda The Evolution of DCIM Users Perspectives Management Methodology by Delta DCIM The Evolution of DCIM What is DCIM DCIM is software for Data

More information

PEARL MANHATTAN, NY

PEARL MANHATTAN, NY FEATURES :: Power 40 MWs of high tension service :: Inter-connectivity 3 milliseconds to New York City s major exchanges :: Security New York Police Department is immediately adjacent; secured vehicular

More information

PRODUCTS & SERVICES. colocation services

PRODUCTS & SERVICES. colocation services PRODUCTS & SERVICES colocation services Equinix is the preferred destination for companies who control the world s most valued information assets. Our International Business Exchange (IBX ) centers are

More information

Fact sheet FRANKFURT DATA CENTRE CAMPUS. Connect, transact and grow

Fact sheet FRANKFURT DATA CENTRE CAMPUS. Connect, transact and grow Fact sheet FRANKFURT DATA CENTRE CAMPUS Connect, transact and grow WELCOME TO FRANKFURT On the infrastructure side, the location Frankfurt am Main is the backbone of the digital business in Germany. As

More information

7 Best Practices for Increasing Efficiency, Availability and Capacity. XXXX XXXXXXXX Liebert North America

7 Best Practices for Increasing Efficiency, Availability and Capacity. XXXX XXXXXXXX Liebert North America 7 Best Practices for Increasing Efficiency, Availability and Capacity XXXX XXXXXXXX Liebert North America Emerson Network Power: The global leader in enabling Business-Critical Continuity Automatic Transfer

More information

ANSI/BICSI Data Center Design and Implementation Best Practices

ANSI/BICSI Data Center Design and Implementation Best Practices ANSI/BICSI 002-2014 Data Center Design and Implementation Best Practices Risk, Reliability & Availability Selecting a Data Center Design Class Bob Camerino RCDD DCDC CT Vice Chair BICSI Mainland Europe

More information

Practical Lessons from Data Centre Design and Testing Zac Potts

Practical Lessons from Data Centre Design and Testing Zac Potts Practical Lessons from Data Centre Design and Testing Zac Potts Associate Director of Data Centre Design Introduction and Overview of Data Centre Design and Engineering Principles Tier Ratings and Standards

More information

THE ADVANTAGE MISSION CRITICAL JOKAKE CONSTRUCTION. INSPIRE. BUILD. PARTNER. INSPIRE. BUILD. PARTNER.

THE ADVANTAGE MISSION CRITICAL JOKAKE CONSTRUCTION. INSPIRE. BUILD. PARTNER.  INSPIRE. BUILD. PARTNER. THE ADVANTAGE JOKAKE CONSTRUCTION. INSPIRE. BUILD. PARTNER. INSPIRE. BUILD. PARTNER. MISSION CRITICAL WWW.JOKAKE.COM Everyone works from the Cloud. We work to maintain it. Over the last 31 years Jokake

More information

Fact sheet VIENNA DATA CENTRE CAMPUS. Connect, transact and grow

Fact sheet VIENNA DATA CENTRE CAMPUS. Connect, transact and grow Fact sheet VIENNA DATA CENTRE CAMPUS Connect, transact and grow WELCOME TO VIENNA Vienna is one of Europe s best connected cities, and is home to VIX, Austria s largest Internet exchange. In the North

More information

Fact sheet COPENHAGEN DATA CENTRE CAMPUS. Connect, transact and grow

Fact sheet COPENHAGEN DATA CENTRE CAMPUS. Connect, transact and grow Fact sheet COPENHAGEN DATA CENTRE CAMPUS Connect, transact and grow WELCOME TO COPENHAGEN Ranked by the World Bank as one of the best countries in the world to conduct business, Denmark boasts a forward-thinking

More information

1008 kw, Tier 2, Chilled Water, ft 2

1008 kw, Tier 2, Chilled Water, ft 2 [eference Design 81] 1008 kw, Tier 2, hilled Water, 18115 ft 2 DESIGN OVEVIEW Data enter IT apacity 1008 kw Adaptable from 200 kw to 3024 kw Target Availability Tier 2 Annualized PUE at 100% Load 1.65

More information

A separate CRAC Unit plant zone was created between the external façade and the technical space.

A separate CRAC Unit plant zone was created between the external façade and the technical space. Nominee: FES Co Ltd Nomination title: HP Cold Cube The Doxford Facility is a highly secure Data Centre. The challenge was to take advantage of the previous investment in highly resilient infrastructure

More information

ANSI/BICSI Data Center Design and Implementation Best Practices

ANSI/BICSI Data Center Design and Implementation Best Practices ANSI/BICSI 002-2014 Data Center Design and Implementation Best Practices Risk, Reliability & Availability Selecting a Data Center Design Class Bob Camerino RCDD DCDC CT Secretary BICSI Mainland Europe

More information

CHILLED WATER. HIGH PRECISION AIR CONDITIONERS, FROM 7 TO 211 kw

CHILLED WATER. HIGH PRECISION AIR CONDITIONERS, FROM 7 TO 211 kw IT COOLING CLOSE CONTROL AIR CONDITIONERS CHILLED WATER HIGH PRECISION AIR CONDITIONERS, FROM 7 TO 211 kw 3 Versions available Single chilled water coil Double chilled water coil High temperature IT COOLING

More information

Jack van der Horst, Regional Technology Manager, Asia Pacific. ABB

Jack van der Horst, Regional Technology Manager, Asia Pacific. ABB ABB DATA CENTER FORUM 2017, 11 JULY 2017, TUESDAY ABB Ability Data Center Automation Datacenter Automation for improved operations and reduced risks Jack van der Horst, Regional Technology Manager, Asia

More information

REPORT. Energy Efficiency of the San Diego Supercomputer Center and Distributed Data Centers at UCSD. Prepared for:

REPORT. Energy Efficiency of the San Diego Supercomputer Center and Distributed Data Centers at UCSD. Prepared for: REPORT Energy Efficiency of the San Diego Supercomputer Center and Distributed Data Centers at UCSD Prepared for: San Diego Supercomputer Center 10100 John J Hopkins Drive San Diego, CA 92037 May 11, 2009

More information

DATA CENTER SERVICES CONNECTIVITY: THE TRUE DIGITAL TRANSFORMATION

DATA CENTER SERVICES CONNECTIVITY: THE TRUE DIGITAL TRANSFORMATION DATA CENTER SERVICES CONNECTIVITY: THE TRUE DIGITAL TRANSFORMATION THE GREATEST NEUTRAL INTERCONNECTED PLATFORM IN SPAIN & PORTUGAL Companies from all kind of industries are adapting their business processes

More information

Cooling. Highly efficient cooling products for any IT application. For More Information: (866) DATA CENTER SOLUTIONS

Cooling. Highly efficient cooling products for any IT application. For More Information: (866) DATA CENTER SOLUTIONS Cooling > Highly efficient cooling products for any IT application. DATA CENTER SOLUTIONS For More Information: (866) 787-3271 Sales@PTSdcs.com End-to-End Cooling Solutions from the Closet to the Data

More information

Data Centre Security. Presented by: M. Javed Wadood Managing Director (MEA)

Data Centre Security. Presented by: M. Javed Wadood Managing Director (MEA) Data Centre Security Presented by: M. Javed Wadood Managing Director (MEA) EPI history and global locations UK origin, 1987 Singapore office, 1999 9 EPI offices worldwide Global partner network spanning

More information

Data Center. Hong Kong Financial Data Center

Data Center. Hong Kong Financial Data Center Data Center Hong Kong Financial Data Center NTT Communications Global Data Centers Nexcenter The Global Data Center Vision NTT Communications is one of the largest data center service providers in the

More information