Cabling for Data Centres. Andrew Sedman RCDD/NTS Technical Director MEA Reichle & DeMassari
|
|
- Elizabeth Rich
- 6 years ago
- Views:
Transcription
1 Cabling for Data Centres Andrew Sedman RCDD/NTS Technical Director MEA Reichle & DeMassari
2 Data Center Definition is a facility used to house computer systems and associated components, such as telecommunications and storage systems Source: Wikipedia DC = Computer Room? DC = Equipment Room or Telecommunications Room? No single official definition
3 Data Center Definition Assume no direct cabling to office Assume all services sent out via carrier networks Can be manned or lights-out Cabling requirements differ from DC to DC
4 Dependent upon Business model Investment Building Size Use DC Differences
5 Data Center Types Defined for cabling in terms of use: Co-location/Managed Services data center Private data center Similar systems in each: SANs Core & Distribution Switches Firewalls Servers
6 Co-Location Facilities Space and service providers to those that wish to locate data equipment off-site Multiple Independent Facilities Segregation Security No Central Distribution Multiple Links to ENIs Localised Cabling Shorter Links Cable Density Lower
7 Private Facilities Individual company to provide services to: Their Clients Large internal organisation Variations: Size Purpose Equipment Redundancy Standards concept (ENI, MD, ZD etc.)
8 Private Facilities Potential for large scale cabling requirements Typically higher density requirements Greater need for security on connectivity Large part of continued investment in MACs
9 Standards Overview ISO/IEC (Feb 2010) CENELEC EN (2007) EIA/TIA 942 (2005)
10 US Data Center Standards Released in 2005 New version in progress (942-A) TIA/EIA 942 Telecommunication Infrastructure for Data Center Cabling Pathways and Spaces Administration Grounding and Bonding OSP Cabling TIA/EIA 568-C 1 TIA/EIA 569-B TIA/EIA 606-A TIA/EIA-J- 607 TIA/EIA 758-A TIA/EIA 568-C 2 TIA/EIA 568-C 3
11 European Data Centre Standard EN : Information technology Generic cabling General requirements EN : Office premises EN : Industry premises EN : Homes EN : Data centres
12 International Data Centre Standards Approved Feb. 2010
13 Data Centre Structure (Acc ISO 24764) Interfaces to other networks Copper classes D,E,E A,F,F A Fibre OM3 minimum Fibre connectivity LC APC SM at ENI Actual Data Centre Copper classes E A,F,F A Fibre OM3 minimum Fibre connectivity MPO LC
14 Investment in DC passive Infrastructure (Ex. USA) The investment in the passive infrastructure is significantly larger during operation than during the installation.
15 Growth/Expansion Main Distribution Horizontal Distribution Equipment Distribution OM3 Cat6/6 A Switch Switch Switch Server OM3 Storage Switch Low / medium / high density Switch Backbone fixed installation Horizontal Cabling modular / generic / flexible SAN fixed installation
16 Needs of the Infrastructure Due to the ongoing investment after the initial DC build Cable systems need: Flexibility Modularity Scalability Design must: Allow for reasonable expansion: Space Administration Allow backward compatibility
17 Category 6 A vs Category 6A Cat 6 A provides: Greater headroom Provision for on-site environment Potential future applications ISO/IEC Cat 6 A vs. TIA Cat 6A Connecting Hardware NEXT Values 40.0 Starting at 250 MHz: Cat 6A: 40dB slope Cat 6 A : 30dB slope At 500 MHz difference of 3dB in NEXT ISO/IEC TIA TIA ISO/IEC
18 Category 6 A vs Category 6A Category 6 A The last 8P8C (RJ45 style) connector Specified up to 500 MHz Versions: Shielded Unshielded To ensure stable performance of 10GbE up to 100m
19 Category 7/7 A Connectors Category 7 & 7 A fully shielded systems Two forms recognised IEC (GG45) Principal connector IEC Category 7 A IEC (Tera) Allowed when other factors (BCT) outweigh the need for backwards compatibility Can cater for Category 7 & 7 A
20 Common Cabling Practices Fibre Systems MPO/MTP Fibre solutions (OM3/OM4) LC fibre connectors Raceways SAN links Copper Systems Category 6A/ A Pre-term solutions Switch links for core and access switches
21 MPO/MTP Fibre Solution 12 cores in 1 connector MM and SM fibre options Plug and Play solution Fan-out possible Made to Order (not field terminable)
22 MPO/MTP Fibre Solution Allows for future 40GbE connectivity Single port for 40GbE 4 x 10GbE Tx 4 x 10GbE Rx 4 x Spare (Management)
23 Convenient containment system Fibre only Scaleable Flexible Modular Raceways
24 SAN Links Direct connection links Live ports at distribution frame Security Management
25 Plug and Play solution Made to Order Pre-Tested Installation time minimised Quality controlled Pre-Term Copper
26 Copper Switch Links RJ45 Jack to Plug Active ports at distribution frame Management Security
27 Design Warning - Density Increasing need for density Manufacturers: Angled panel 1 48 port panel 2 42U cab/frame = or cables 100mm 100mm
28 Helping Energy Efficiency Considerable overhead for active equipment is DSP for noise cancellation Theory: Quality shielded cable system requires less noise cancellation Less noise cancellation = less electronics Less electronics = less heat Less heat = less cooling.etc.
29 Thank you Andrew Sedman RCDD/NTS Technical Director MEA Reichle & DeMassari MEA
How to Decide on Optical Fibre Termination Options. Thomas Ko, RCDD Product Manager Tyco Electronics / AMP NetConnect
How to Decide on Optical Fibre Termination Options Thomas Ko, RCDD Product Manager Tyco Electronics / AMP NetConnect Termination Choices Optical Fiber Cabling in Data Center Options available Traditional
More informationDATA CENTRE CABLING STANDARDS and NEW TECHNOLOGY OVERVIEW for 2005
DATA CENTRE CABLING STANDARDS and NEW TECHNOLOGY OVERVIEW for 2005 Mike Gilmore Managing Director, e-ready Building Convenor CENELEC TC215 WG1 Mike Gilmore Standards Activities Member JTC1 SC25 WG3: Generic
More informationCopper Cabling Standards
Copper Cabling Standards White paper White Paper Copper Cabling Standards v2.0 EN 1 Introduction Standard specifications are the foundation upon which most cabling and networking projects are built. Professionals
More informationBICSI NxtGEN & Global Data Center Standards Update
BICSI NxtGEN & Global Data Center Standards Update Bob Faber, RCDD/NTS Siemon Global Accounts Manager Chair NEMA High Performance Wire & Cable Chair BICSI Standards Committee Vice Chair BICSI TI&M Committee
More informationApplication Note. Data Center Standards and Layouts
Application Note Data Center Standards and Layouts 1. Data Center Standards In earlier times, a room in which one or more servers, a telephone system and active network components were located was often
More informationCopper Cabling from 10G to 400G, and back down to 10Mbps, but on 1 pair only
1 Copper Cabling from 10G to 400G, and back down to 10Mbps, but on 1 pair only Gautier Humbert, RCDD Standards Coordinator Digital Infrastructures Legrand District Chair Mainland Europe BICSI 2 Agenda
More informationHistory of Standards
History of Standards From 10Mbps to 100Gbps Ethernet 12 th May 2014 Gautier Humbert, RCDD Business Development Manager Legrand East and Central Europe Agenda 1- Current standards and their structures
More informationStandards Update. Mylaraiah J N, RCDD Member, BICSI India Steering Committee
Standards Update Mylaraiah J N, RCDD Member, BICSI India Steering Committee Standards Update International Standards Interrelations Reference Guide Standard ISO/IEC CENELEC TIA/EIA Performance / Generic
More informationTrends in Data Centre
Trends in Data Centre The impact on the IT infrastructure Thomas Ko Product Manager Market Situation Standards Update and Topology 40G and 100G Ethernet - Impact on IT Cabling Migration Options with Fiber
More informationDesign of the Physical Layer
Design of the Physical Layer Critical Choices for Today's Data Centres The Siemon Company: The partner of choice for your Global Data Centers Alberto Zucchinali RCDD Senior Technical Manager EMEA DC Solutions
More informationIndustry Standards in ICT Enabled Projects Reading and Applying the "Fine Print"
Industry Standards in ICT Enabled Projects Reading and Applying the "Fine Print" Gautier Humbert, RCDD Standards Coordinator Legrand Digital Infrastructures Gautier Humbert, RCDD BICSI District Chair Mainland
More informationAnticipating Cat 8 Agenda. Cat 8 Overview Cat 8 Customer Design Considerations Testing Procedures and Standards
Anticipating Cat 8 Agenda Cat 8 Overview Cat 8 Customer Design Considerations Testing Procedures and Standards What is Cat 8? Next Generation Copper Cabling 25G and 40G data rates over twisted pair copper
More informationIntroduction to Key Principles of Telecommunications Cabling
Introduction to Key Principles of Telecommunications Cabling Dimitris Filippou Technical Director, Ltd. IEEE Member, BICSI Country Chair, ELOT Technical Committee TC93 Member, CENELEC TC215 Delegate of
More informationTesting Considerations for Beyond 10Gigabit Ethernet. Erin Hallett
Testing Considerations for Beyond 10Gigabit Ethernet Erin Hallett JDSU Agenda Intro Need for Speed Growth of IP traffic Fiber vs. Copper Fiber Tightening requirements Testing considerations and practices
More informationDC Center Copper Cabling up to 40Gbase-T. Halim Senjaya
DC Center Copper Cabling up to 40Gbase-T Halim Senjaya CTDC CTIA Data Center Expert Datwyler Singapore Diploma in Eng ng in Physics Bandung IT Diploma in Cloud DC Technologies - NP MBA Middlebury Institute
More informationStandards Update. by Paul Kish NORDX/CDT
Standards Update by Paul Kish NORDX/CDT Standards overview Category 5e cabling new transmission parameters patch cord return loss Category 6 cabling cable choices backwards compatibility Summary Outline
More informationDATA CENTER CABLING DESIGN FUNDAMENTALS
White Paper DATA CENTER CABLING DESIGN FUNDAMENTALS Telecommunications Cabling Infrastructure Requirements according the Availability Classes I-IV of Introduction With the completion by end of Q1 2016,
More informationComplex networks in Plug & Play
tml tde Modular Link System Complex networks in Plug & Play tml tde Modular Link System The number of network connections in a Data Center is increasing constantly, due to the ever greater demands made
More information(Data Center Networks & Cloud Computing Security)
BPSDC (Data Center Networks & Cloud Computing Security) Lecture 3 Data Center Standars Service Level Agreement 2 Building a Data Center is just a Start What is Service Level Agreement (SLA)? An official
More informationAMP ACT 1 INSTALLING PREMISES CABLING SYSTEM. Welcome!!! Instructor : Nicholas Yeo
AMP ACT 1 INSTALLING PREMISES CABLING SYSTEM Welcome!!! Instructor : Nicholas Yeo AMP ACT 1 INSTALLING PREMISES CABLING SYSTEM Welcome!!! 2 Standards ISO CENELEC AS/NZS ANSI IEC CSA TIA EIA EN50173 AS/NZS
More information10G the Next Generation Structured Cabling. Technology Paper 002
Technology Paper 002 10G the Next Generation Structured Cabling Workspace Technology Limited Technology House, PO BOX 11578, Sutton Coldfield West Midlands B72 1ZB Telephone: 0121 354 4894 Facsimile: 0121
More informationFTTE Revisited for New Technologies
FTTE Revisited for New Technologies A new look into FTTE design to allow great flexibility as well as compliance to the latest 40G and 100G. Gautier Humbert, RCDD, CDCDP Business Development Manager Eastern
More informationData Center & Cloud Computing Infrastructure Solutions DATASHEET. MTP/MPO-LC/SC Cassette High-density Pre-terminated Modular Cassette System
Data Center & Cloud Computing Infrastructure Solutions DATASHEET MTP/MPO-LC/SC Cassette High-density Pre-terminated Modular Cassette System REV.1.0 2018 MTP MPO Cassette 01 Description FS.COM Fiber Optic
More informationNZQA unit standard version 3 Page 1 of 5. Demonstrate knowledge for telecommunications premises network cablers
Page 1 of 5 Title Demonstrate knowledge for telecommunications premises network cablers Level 2 Credits 2 Purpose This unit standard is for people installing and maintaining telecommunications cables on
More information1 of 5 12/31/2008 8:41 AM
1 of 5 12/31/2008 8:41 AM SAVE THIS EMAIL THIS Close All multimode fiber is not created equal By Robert Reid Bandwidth, reach, and cost are among the key factors you ll need to weigh. Multimode fiber cabling
More informationCable Sharing: An ANSI & ISO Recognized Solution for High Density, Low-Speed Applications. Robert Y. Faber Jr., RCDD/NTS.
Cable Sharing: An ANSI & ISO Recognized Solution for High Density, Low-Speed Applications Broadband High-Speed LAN Voice Robert Y. Faber Jr., RCDD/NTS Minimum Port Recommendations TIA/EIA-568-B.1 2 outlets
More informationUniprise Structured Cabling Solutions Guide
Uniprise Structured Cabling Solutions Guide Exceptional value, proven reliability You re not unrealistic. You re simply looking for a reliable and affordable structured cabling solution; a single portfolio
More informationPANGEN INDUSTRIAL AUTOMATION SYSTEM WARRANTY
PANGEN INDUSTRIAL AUTOMATION SYSTEM WARRANTY WARRANTY GUIDE PANGEN INDUSTRIAL AUTOMATION SYSTEM WARRANTY WARRANTY GUIDE PROGRAM OUTLINE TABLE OF CONTENTS: MATERIALS PAGE # Program Outline 2 Table of Contents
More informationINTERNATIONAL STANDARD
INTERNATIONAL STANDARD ISO/IEC 15018 First edition 2004-06 Information technology Generic cabling for homes ISO/IEC 2004 All rights reserved. Unless otherwise specified, no part of this publication may
More informationLAN Standards, News & Trends Update 2017 June 15, 2017
LAN Standards, News & Trends Update 2017 June 15, 2017 Greg Olson Jtech Systems, Inc Infrastructure Specialist Greg@jtechreps.com 425-437-1962 Our Objectives Review new & ongoing applications work in IEEE
More informationOptimization and Speed: Two Critical Standards Enabling Next Generation Networks. Stephanie Montgomery, TIA Brett Lane, Panduit
Optimization and Speed: Two Critical Standards Enabling Next Generation Networks Stephanie Montgomery, TIA Brett Lane, Panduit Structure of TIA Standards 2 A family of Standards ANSI/TIA-942-A Telecommunications
More informationCertification for 10G copper cabling
Certification for 10G copper cabling Presented by Eric Lie, Sales Manager 1 Introduction This presentation is intended to provide an overview of the 10GBASE-T requirements for cabling The applicable standards
More information10 Gigabit Ethernet and Future Cabling for Offices + Data Centres
10 Gigabit Ethernet and Future Cabling for Offices + Data Centres Presentation at Nexans Seminar Scandinavia, May 2006 Dr Alan Flatman Principal Consultant LAN Technologies Topics 1. 10 Gig over optical
More informationLX3 High Density LGX 1U Patch Panel
LX3 High Density LGX 1U Patch Panel An innovative 1U, 19 rack mountable patch panel, designed for use in high density applications. It offers management of up to 144 fibres using MTP optical cassette modules
More informationProduct information Patch Cord Cat. 6A, S/FTP, 4P, LSFRZH, gray, RJ45/s- RJ45/s, 1.0 m
Product information Patch Cord Cat. 6A, S/FTP, 4P, LSFRZH, gray, RJ45/s- RJ45/s, 1.0 m R509858 101376015 10 pcs Cable identification: S/FTP Outer jacket: LSFRZH Conductor diameter copper strand: AWG 26/7
More informationISO/IEC SC25 WG3. Who are they & what can they do for 802.3cg? Alan Flatman. Principal Consultant LAN Technologies.
1 ISO/IEC SC25 WG3 Who are they & what can they do for 802.3cg? Alan Flatman Principal Consultant LAN Technologies Email: a_flatman@tiscali.co.uk 2 Who are ISO/IEC SC25 WG3? Ø International systems group
More informationProduct information 19" 3U Global Patch Panel 48xRJ45/u, Cat. 6, partly populated R302361
Product information 19" 3U Global Patch Panel 48xRJ45/u, Cat. 6, partly populated R302361 1 Pcs. 19" 3U Global patch panel/u incl. cable tie shelf 12 connection module holders Global/u 3 Global blind covers
More informationDr. Paulo Marin, EE/BSc, MSc, PhD. Electrical Engineer, ICT Consultant
Is Cable Balancing Efficient i Enough for EMI Mitigation in Data Centers? Dr. Paulo Marin, EE/BSc, MSc, PhD. Electrical Engineer, ICT Consultant What are You going to Learn? What are the potential sources
More informationOvercoming the Testing Challenges of 40G and Beyond. Eric Farst Channel Sales Manager
Overcoming the Testing Challenges of 40G and Beyond Eric Farst Channel Sales Manager Agenda Introduction Increased demand for speed & capacity in the Enterprise/Data Center How Enterprises/Data Centers
More informationISO/IEC TR Guidance on 40GBASE-T T Cabling
1 ISO/IEC TR 11801-99 99-1 Guidance on 40GBASE-T T Cabling - a tutorial - Alan Flatman Principal Consultant LAN Technologies Email: a_flatman@tiscali.co.uk 2 Content 1. introduction to ISO/IEC SC25 WG3
More informationFMT4S. High Density Connectivity Solution
FMT4S High Density Connectivity Solution 2 FMT4S Solution Illustration FMT4S Optical Distribution Frame (ODF) FMT4S series is an advanced ODF series offering premium quality Data Center connectivity solution.
More informationHDCi LX3 High Density 4U Patch Panel
HDCi LX3 High Density 4U Patch Panel An innovative 4U, 19 rack mountable patch panel, designed for use in high density applications. It offers management of up to 576 fibres using MTP optical cassette
More informationV-Built Custom Preconfigured Solutions
WWW.SIEMON.COM V-Built Custom Preconfigured Solutions 8 One Part Number, One Price Ready to Roll Available with any Siemon cabinet, rack or enclosure, Siemon s V-Built Custom Preconfigured Solutions are
More information9/27/04 cci Cablecom Inc. 1
cci Cablecom Inc. 1 CCI Cablecom Inc. is a privately held, women owned corporation headquartered in Aurora, CO. We manufacture a variety of voice and datacom products. Cable applications Include: Local
More informationTelecommunication Cabling Standards to address IoT and power delivery. 5 October
Telecommunication Cabling Standards to address IoT and power delivery 1 5 October 2018 www.vti.net.au In a nut shell Out for comment NOW AS/NZS 11801.1 (General requirements) AS 11801.2 (Office) AS 11801.3
More informationLANmark-7A H i g H - S p e e d C O p p e R S O l u t i O n F O R 4 0 g i g a b i t a p p l i C a t i O n S
LANmark-7A High-Speed COPPER Solution For 40 Gigabit Applications LANmark-7A High-Speed Copper Solution For 40 Gigabit and Beyond LANmark-7A copper cabling is able to support higher bandwidths and faster
More informationData center cabling design fundamentals
White paper Data center cabling design fundamentals Telecommunications cabling infrastructure requirements according the availability classes I-IV of EN 50600-2-4 www.commscope.com 1 Introduction With
More informationHDCi LX3 High Density 1U Patch Panel
HDCi LX3 High Density 1U Patch Panel An innovative 1U, 19 rack mountable patch panel, designed for use in high density applications. It offers management of up to 144 fibres using MTP optical cassette
More informationThe module for the highest standards, guarantees the best performance in the 10 Gigabit Ethernet cabling.
This is my title your first subtitle saecond subtitle Product information Connection Module Cat. 6A, 1x/s, 10x R509504 966733885 10 Stk. The module for the highest standards, guarantees the best performance
More informationVF-45 TM (SG) Ferrule-Less Interconnect Proposal
VF-45 TM (SG) Ferrule-Less Interconnect Proposal IEEE 802.5 Token Ring. November 10-12, 1998 Tad Szostak - 3M Telecom Systems Division 512-984-3847; tszostak1@mmm.com www.3m.com/volition Plug and Socket
More informationNETCONNECT. Structured Cabling Solutions Guide. Asia-Pacific Region
NETCONNECT Structured Cabling Solutions Guide Asia-Pacific Region NETCONNECT STRUCTURED CABLING SOLUTIONS GUIDE EXCEPTIONAL VALUE, PROVEN RELIABILITY FROM COMMSCOPE You re not unrealistic. You re simply
More informationSTAR. Data Center High Density Connectivity Solution
STAR Data Center High Density Connectivity Solution 2 STAR Solution Illustration Reach for the STAR: Data Center Connectivity that achieves new heights! Fibernet is proud to introduce the new STAR series,
More informationViable Options for Data Center Solutions. By Ning Liu Offering Group Panduit APJ
Viable Options for Data Center Solutions By Ning Liu Offering Group Panduit APJ Agenda Market Overview Data Center Challengers Business Drivers Data Center Standards Data Center Technologies Panduit Solutions
More informationHI-DEX is an ultra high-performance, pre-terminated and modular optical fibre cabling system based on MT ferrule connector technology.
APPLICATION HI-DEX is an ultra high-performance, pre-terminated and modular optical fibre cabling system based on MT ferrule connector technology. This product set is designed for installation in the data
More informationNovember 2010 IEEE 802.3
TIA TR-42 Liaison to IEEE 802.3 Valerie Maguire Vice Chair, TIA TR-42 Vice Chair, TIA TR-42.7 November, 2010 Dallas, TX 1 Introduction to TIA Telecommunications Industry Association www.tiaonline.org TR-42:
More informationMANAGING THE COMPLEXITY.
AS A SERVICE MANAGING THE COMPLEXITY. HOW WILL YOU SIMPLIFY ESN MIGRATION? Control room IT solutions play a vital role in incident management. Technologies such as Integrated Communications Control Systems
More informationNewark, Delaware Architectural Engineering Senior Thesis Portfolio
Telecommunications System Design The represents the advancement of solar design in our world today. The building itself is an example of this. A Headquarters this dedicated to moving into the future should
More informationCONNECTOR SOLUTIONS. FASTConnect FUSEConnect Field Master
CONNECTOR SOLUTIONS FASTConnect Provide some of the fastest terminations in the industry Does not require a crimp or special assembly tools Mechanical, true no epoxy/no polish (NENP) connectors FUSEConnect
More informationDATA CENTER SOLUTIONS TM. Fiber Flex
DATA CENTER SOLUTIONS TM Fiber Flex We help reach your mission-critical objectives!! Olabs develops superior products and solutions in close collaboration with our customers. Our fiber optic structured
More informationCERTIFICATION PLUS SM
CERTIFICATION PLUS SM SYSTEM WARRANTY PROGRAM Panduit Warranty Guide PROGRAM OUTLINE TABLE OF CONTENTS: MATERIALS PAGE # Program Outline 2 Table of Contents Warranty Information 3 Introduction & Installation
More informationDATWYLER SYSTEM WARRANTY
DATWYLER SYSTEM WARRANTY Copper Cabling System Appendix A1 Systems Covered by the Warranty Juli 2014 Appendix A1_Systems Covered by Warranty Cu_July_2014_V01_EN.docx Page 1/9 Contents 1. Systems covered
More informationNew standards that have led to higher speeds and new cable categories. Mike Gengler Sales Area VP, Asia/Pac & Japan Fluke Networks
New standards that have led to higher speeds and new cable categories Mike Gengler Sales Area VP, Asia/Pac & Japan Fluke Networks Three Realities of Networking #1 - Networks Never Go Slower Plan for higher
More informationPsiber Data WireXpert P R O F E S S I O N A L N E T W O R K T E S T I N G & P R O T O C O L A N A L Y S I S
Psiber Data WireXpert Agenda Psiber Data WireXpert Introduction Company Presentation Why Cable Certification? Universal Structured Cabling or The Network Standards The WireXpert Page 2 Psiber Data Company
More informationField-terminated RJ45 connector with housing. Color housing: gray (RAL 7042). Color termination block: red.
FM45 Connector Cat. 6 A IP20, 4P, TIA 568-A/B, 10x R815651 966704105 10 Stk. 090.7437 / ähnliche Abbildung Instruction manual Field-terminated connector with housing. Color housing: gray (RAL 7042). Color
More informationIndustrial 5-Port Fast Ethernet Switches. with SFP Slot and optional 4 PoE PSE Ports. Basic Model: KSD-541. PoE Model: KSD-541-HP. Installation Guide
Industrial 5-Port Fast Ethernet Switches with SFP Slot and optional 4 PoE PSE Ports Basic Model: KSD-541 PoE Model: KSD-541-HP Installation Guide DOC.141201-1- (C) 2014 KTI Networks Inc. All rights reserved.
More informationMPO LGX Cassette Module
DATASHEET Product updated on March 13, 2018 MPO LGX Cassette Module MPO LGX Cassette Modules provide secure transition between MPO and LC or SC discrete connectors. They are used to interconnect MPO backbones
More informationLANmark-7A HIGH-SPEED COPPER SOLUTION FOR 40 GIGABIT APPLICATIONS
LANmark-7A HIGH-SPEED COPPER SOLUTION FOR 40 GIGABIT APPLICATIONS LANmark-7A High-Speed Copper Solution For 40 Gigabit and Beyond LANmark-7A copper cabling is able to support higher bandwidths and faster
More informationThe following pages contain a guide for the installation
INDEX The goal of this section is to illustrate how Siemon Company products can be used to support some of the most popular and emerging networks on the market. Section Contents 100Base-T....................................
More informationCabling Infrastructure
Introduction Ethernet Banking on Structured Cabling Technology Drivers Classification of Cables Fibre-optic cable Cables in building Cabling Infrastructure Cabling systems address the networking requirements
More informationConnectix Specification Guide for Category 6 U/UTP and Optical Fibre Cabling System Architecture
Connectix Specification Guide for Category 6 U/UTP and Optical Fibre Cabling System Architecture Issue Document Status Date: Prepared: Checked: 6 Cat 6 U/UTP, Optical Fibre and MER/SER Guidelines 29/03/2018
More informationFrequently Asked Questions (FAQs) Siemon 10G ip Solutions
Frequently Asked Questions (FAQs) Siemon 10G ip Solutions The world of enterprise cabling is evolving rapidly. Emerging, high-bandwidth services and the adoption of higher speed Ethernet standards, like
More information40 Gigabit over copper - Thorsten Punke Marketing Manager ANZ TE Connectivity
40 Gigabit over copper - 40GBase-T Thorsten Punke Marketing Manager ANZ TE Connectivity IEEE 802.3 Ethernet Update 40GBase-T The history The technical truth The technical history More speed equals to more
More informationIndustrial 5-Port Fast Ethernet Switches with SFP Slot and optional 4 PoE PSE Ports. Basic Model: KSD-541 PoE Model: KSD-541-P. Installation Guide
Industrial 5-Port Fast Ethernet Switches with SFP Slot and optional 4 PoE PSE Ports Basic Model: KSD-541 PoE Model: KSD-541-P Installation Guide DOC.080104-1- (C) 2008 KTI Networks Inc. All rights reserved.
More informationWirewerks Datacenters Becoming More Common in Our Workplace, Next Step Solution
Wirewerks Datacenters Becoming More Common in Our Workplace, Next Step Solution 1 2 Agenda 1. Wirewerks introduction 2. Wirewerks products overview Data Center: Next Step TM Confidential Information Wirewerks
More informationOptical Fiber Premises Standards News & Trends
1 Optical Fiber Premises Standards News & Trends Herb Congdon Tyco Electronics Updated: October 2005 hvcongdon@tycoelectronics.com 2 IEEE Ten Gigabit Ethernet (10GBASE-F) Published as IEEE802.3ae in June
More informationTarleton State University. Specifications
Tarleton State University Campus Communication Infrastructure Specifications Cabling Standards Summary This document identifies Tarleton State University communication infrastructure standards. The communication
More informationBICSI Northeast Regional Meeting June 17, Storrs CT. Considerations in Data Center Design. Thomas McNamara, RCDD
BICSI Northeast Regional Meeting June 17, Storrs CT Considerations in Data Center Design Thomas McNamara, RCDD AGENDA Purpose is to allow the ITS professional to be aware of the issues and therefore pose
More informationINTERNATIONAL STANDARD
ISO/IEC 11801-4 INTERNATIONAL STANDARD Edition 1.0 2017-11 Information technology Generic cabling for customer premises Part 4: Single-tenant homes INTERNATIONAL ELECTROTECHNICAL COMMISSION ICS 35.200
More informationARISTA 7500R/7500E/7300X Connectivity Guide CABLExpress 1. ARISTA 7500R/7500E/7300X Connectivity Guide
ARISTA 7500R/7500E/7300X Connectivity Guide CABLExpress 1 ARISTA 7500R/7500E/7300X Connectivity Guide How do you protect and improve the functionality of your critical processes? You have to Respect Layer
More informationBusiness Customer Demarcation Information
Business Customer Demarcation Information The intent of this document is to clearly define Communications terminology and deployment with reference to business data customers and services. 1. What is a
More informationHome Networks. Principles, Applications and Desirability
Home Networks Principles, Applications and Desirability Index 1. Introduction 2. Why the demand? 3. Technologies 4. Cat5e UTP structured wiring 5. Modular concept 6. Typical applications 7. Technical information
More informationMTP Multi Lite Trunk Assemblies
MTP Multi Lite Trunk Assemblies MTP Multi-Lite Trunk assemblies are a neat solution for providing up to four MTP -MTP links within a compact, high density ruggedised cable. The cable construction consists
More informationNZQA registered unit standard version 2 Page 1 of 7. Demonstrate basic knowledge of electronic security data protocols and cabling
Page 1 of 7 Title Demonstrate basic knowledge of electronic security data protocols and cabling Level 3 Credits 15 Purpose This unit standard is for electronic security installers engaged in the installation
More informationCloud Computing & The Data Centre Lee Funnell, EMEA Technical Manager September 2015
Cloud Computing & The Data Centre Lee Funnell, EMEA Technical Manager September 2015 Lee Funnell EMEA Technical Manager British Standards Institute - Premises Cabling Experts Panel Data Centre Alliance
More informationPower Over Ethernet with Panduit Copper Cabling. How To Create More Meaningful Connections With The Highest Performing Infrastructure
Power Over Ethernet with Panduit Copper Cabling How To Create More Meaningful Connections With The Highest Performing Infrastructure Introduction Increasing usage of Power over Ethernet (PoE) represents
More informationHUBER+SUHNER DCCT Training
HUBER+SUHNER DCCT Training DCCT training The following topics are covered throughout the 2 course: Fiber optic fundamentals This is an optional section of the training which covers the basics about fiber
More informationBend, Bandwidth or Both: enterprise networks. Ravi Yekula
Bend, Bandwidth or Both: Making the right choice for enterprise networks Ravi Yekula Corning Optical Fiber Agenda Multimode fiber remains the most cost-effective choice for enterprise networks Multimode
More informationDemonstrate and apply knowledge of computer networking infrastructure principles
Demonstrate and apply knowledge of computer networking infrastructure principles 22713 version 1 Page 1 of 5 Level 4 Credits 15 Purpose This unit standard covers the necessary introductory skills required
More informationData sheet C6 A modul 1 port 180 M AP pure white
Illustrations Dimensional drawing Page 1/7 See enlarged drawings at the end of document Product specification surface-mount termination unit with C6modul 180 certified to GHMT Cat.6 re-embedded PVP component
More informationNZQA unit standard version 2 Page 1 of 5
Page 1 of 5 Title Demonstrate knowledge of installation practices and procedures for telecommunications network equipment Level 3 Credits 10 Purpose This unit standard covers the installation of basic
More informationWelcome. BICSI And BICSI Standards, An Overview. Presented by: Greg Sherry RCDD/NTS/WD BICSI European Region Director
Welcome BICSI And BICSI Standards, An Overview July 12 th 2007 Presented by: Greg Sherry RCDD/NTS/WD BICSI European Region Director Greg Sherry, Qualitas Ltd 1976 - Started in the IT industry Various roles
More informationFAS-NET MPO Solution. Benefits of FAS-NET MPO Fiber Optic Solution:
Stable and Reliable Data Communication Solutions from Infinique Infinique has designed and developed quality product with affordable pricing for communication infrastructure solutions. This position has
More informationRecent Changes to the Physical Layer (Chapter 8) for DeviceNet and EtherNet/IP Brad Woodman Molex
Recent Changes to the Physical Layer (Chapter 8) for DeviceNet and EtherNet/IP Brad Woodman Molex www.odva.org Technical Track Agenda Introduction DeviceNet Chapter 8 Changes Cable profiles updated for
More informationMigratable cabling in computer centres for all data rates from Mbit/s to 100Gbit/s (DClink)
Introduction Computer centres must be reliable and available around the clock even during conversion work. Data rates are increasing constantly, and the FO cabling which only recently supported all applications
More informationKeeping up to Speed with High Data Rate Fiber Solutions. Eric Leichter Manager, Training and Technology
Keeping up to Speed with High Data Rate Fiber Solutions Eric Leichter Manager, Training and Technology Keeping up to Speed with High Data Rate Fiber Solutions Global Standards Update OM4 Optical Fiber
More informationOverview of the Cisco 2524 and Cisco 2525 Routers
CHAPTER 1 Overview of the Cisco 2524 and Cisco 2525 Routers The Cisco 2524 and Cisco 2525 routers provide LAN and WAN access in a low-cost modular router platform that can grow with your internetworking
More informationPANGEN SYSTEM WARRANTY. Warranty Guide
PANGEN SYSTEM WARRANTY Warranty Guide C2-10270 PANGEN SYSTEMWARRANTY GUIDE PROGRAM OUTLINE TABLE OF CONTENTS: MATERIALS PAGE # Program Outline 2 Table of Contents Warranty Information 3 Introduction &
More informationWhich networks do we need in the 2020s`? Selection criteria for structured copper cabling. Zoran Borcic Product Manager Copper Datacom
Which networks do we need in the 2020s`? Selection criteria for structured copper cabling Zoran Borcic Product Manager Copper Datacom Utilities T&I Industrial Energy Projects Telecom 50 COUNTRIES 112 PLANTS
More informationBalanced single-pair cabling channel specifications
Balanced single-pair cabling channel specifications IEEE P802.3cg 10SPE Task Force July 9, 2018 Dave Hess, CORD DATA 07/09/2018 hess_3cg_01_0718 1 Overview This contribution reflects the views of the presenter
More informationDATA CENTER SYMPOSIUM
DATA CENTER SYMPOSIUM Dynamic Changes in Data Center Optic Transmissions & The Impact to Structured Fiber Cabling Rick Dallmann CABLExpress Years of Experience CABLExpress is a manufacturer of custom built
More information