How new testing standards affect you Singapore, Nov 2009
|
|
- Eugene Norman
- 6 years ago
- Views:
Transcription
1 How new testing standards affect you Singapore, Nov 2009 Adrian Young Sr. Customer Support Engineer
2 In this presentation, we will cover How ANSI/TIA-568-C.2 has consolidated all the different test plugs defined in the past to one single test plug and how that affects your test results Alien Crosstalk testing strategy and basic troubleshooting 1 jumper vs 3 jumper reference found in IEC Optical Time Domain Reflectometry testing as found in ANSI/TIA-568-C.0 and IEC
3 Permanent Link test lead Ever swapped your test leads around and got a different result? It can t be the tester, it s the same tester you are using May be it s the test lead.. well kind off.. It s that RJ45 plug on the end of the lead that is causing it to change. ANSI/TIA-568-C.2 states:? The plug is terminated by hand, the variation of performance can be wide spread.
4 Test leads/plugs cause the biggest uncertainty If the performance of your plug changes, so does your NEXT margin It s the placing of the twisted pairs that affects it s performance It is a real struggle to create a test plug One solution remove the twisted pairs in the RJ45 plug
5 Test leads & plugs are critical for Category 5e, 6 and 6A Up until recently, there were three different test plugs specified for testing Category 5e, 6 and 6A ANSI/TIA/EIA-568-B.2 defined a test plug for Cat 5e ANSI/TIA/EIA-568-B.2-1 defined a test plug for Cat 6 ANSI/TIA-568-B.2-10 defined a test plug for Cat 6A With ANSI/TIA-568-C.2 there is now only one test plug for Cat 5e, 6 and 6A which is the same test plug found in ANSI/TIA-568-B.2-10 This is fantastic news for the entire industry. Connector vendors only have to worry about one test plug to tune their connectors to Cat 5e, 6 and 6A. For installers now, they can optimize their test results by using a test lead with an RJ45 plug that meets the requirements of ANSI/TIA-568-C.2
6 Test plug requirements ANSI/TIA-568-C.2 defines the test plug for NEXT FEXT Return Loss Laboratory technicians can spend weeks trying to make a test plug that meets the requirements it s generally understood that this is not practical In Annex C of ANSI/TIA-568-C.2 it talks about using a PCB (Printed Circuit Board) style RJ45 plug It is easier to produce a compliant test plug using a PCB substrate according to Annex E.2 of ANSI/TIA-568-C.2 1) Its properties have been designed to comply with electrical properties of the test plug described in clause C ) The construction is repeatable and consistent. 3) It is mounted to the test fixture without the use of twisted wire test leads, yielding a more consistent measurement result.
7 How a connector is tested in the laboratory ANSI/TIA-568-C.2 defines the test plug for NEXT, FEXT and Return Loss C Test plug construction for return loss testing NOTES, Plugs of this type may be obtained from: Fluke Networks, Everett, WA or SMP Data Communcations, Swannanoa, NC. Alternative equivalent components may also be used. The closer your test plug is to the standard, the better your result
8 Alien Crosstalk (AxTalk) testing Values are found in ANSI/TIA-568-C.2 for the Perm. Link and Channel Methodology is found in the new ANSI/TIA-1152 Myth: You do not have to do Alien Crosstalk testing if it is a shielded cabling system Fact: Neither standard makes a distinction between UTP/FTP/STP when it comes to Alien Crosstalk testing Experience: Our experience shows that shielded cabling systems can fail Alien Crosstalk requirements if not installed correctly AxTalk is a sample test of the installation ANSI/TIA does not specify the sampling plan IEC no longer specifies 1% or 5 links whichever is the greatest Sampling instructions can be found in the new IEC
9 How is it measured? A Disturber cable is picked (which one?) ANSI/TIA-568-C.2 and TIA-1152 give little guidance; short and long link IEC provides better information: Selection of disturbing links Disturbing links shall include both of the following:» all of the links that are in the same cable bundle or the most consistently positioned relative to the disturbed link as disturbing links;» those that occupy adjacent positions to the left, right, above and below connections on the disturbed link on patch panels or multiple outlets. Let s take a look at a real world example:
10 Picking the Disturbed (Victim) link We know that the connectors contribute most of the PS ANEXT for Category 6A and Class E A cabling systems Do not pick the links/connectors at the end of a patch panel, since there are no adjacent connectors Do not pick the links/connectors at the end or a row/group for the same reason
11 Picking the Disturbed (Victim) link In the results software, we identified this link as one of our shortest links It is not at the end of the patch panel or group of connectors There are connectors/links above and below This truly is worst case
12 Picking the Disturber links Identify the bundle this Disturbed (Victim) link can be found in, shown in blue below This installation used bundles of 12 cables. We know that Alien Crosstalk between bundles is not significant, so we can focus on just the cables in the bundle
13 Picking the Disturber links We already know that the connectors contribute most of the PS ANEXT for Category 6A and Class E A cabling systems So you need to pick the connectors above and below Selection of disturbing links Disturbing links shall include both of the following:» all of the links that are in the same cable bundle or the most consistently positioned relative to the disturbed link as disturbing links;» those that occupy adjacent positions to the left, right, above and below connections on the disturbed link on patch panels or multiple outlets.
14 The Alien Crosstalk Measurement (PS ANEXT)
15 Troubleshooting Alien Crosstalk Failures Disturber Ranking Here we see the Alien Crosstalk is coming from the adjacent links, we therefore know this is a connector issue and not a cable issue
16 ANSI/TIA-568-C.0 Fiber Testing (Tier 1) General Link attenuation is measured using the reference methods specified by TIA A for multimode and TIA for single-mode. The one cord reference method is preferred for both multimode and single-mode. Other methods as detailed in the above standards may be applied. Test documentation should include the test method applied. Let s take an example to understand how this is done:
17 ANSI/TIA-568-C.0 Fiber Testing (1 jumper reference) The test reference cord is removed from the Input, this is ok You must NEVER remove the cord from the output (source)
18 ANSI/TIA-568-C.0 Fiber Testing (1 jumper reference) A known good test reference cord is connected to the Input port
19 ANSI/TIA-568-C.0 Fiber Testing (1 jumper reference) And then connect to the link to be tested 100 m Loss Budget = 1.85 db 0.75 db db db
20 IEC Three Jumper Reference The reference is set (cords zeroed out)
21 IEC Three Jumper Reference The middle test reference cord is removed
22 IEC Three Jumper Reference And then connect to the link to be tested Loss Budget for multimode is calculated as follows: Loss of fiber under test + Loss of Splices + Loss of Connectors db db db db 100 m Loss Budget = 0.75 db 0.35 db db db db db
23 ANSI/TIA-568-C.0 Fiber Testing (Tier 2) OTDR (Optical Time Domain Reflectometer) is now part of 568-C.0 OTDR testing was specified in TIA TSB-140 Feb 2004 (not a standard)
24 Thank you for your time Questions?
Certification for 10G copper cabling
Certification for 10G copper cabling Presented by Eric Lie, Sales Manager 1 Introduction This presentation is intended to provide an overview of the 10GBASE-T requirements for cabling The applicable standards
More informationCommon Mistakes Made in Certification Specifications and Testing. Jim Davis Regional Marketing Engineer Fluke Networks
Common Mistakes Made in Certification Specifications and Testing Jim Davis Regional Marketing Engineer Fluke Networks Common Mistake #1 Failing to specify a Permanent Link test #1 Permanent Link or Channel?
More informationANSI/TIA-568-C Cat 6A Field Test Specifications
This document has been prepared to aid consultants or engineers in developing contractual specifications covering the certification of Category 6A Permanent Links. It is offered as a general guide. Suitability
More informationAnticipating Cat 8 Agenda. Cat 8 Overview Cat 8 Customer Design Considerations Testing Procedures and Standards
Anticipating Cat 8 Agenda Cat 8 Overview Cat 8 Customer Design Considerations Testing Procedures and Standards What is Cat 8? Next Generation Copper Cabling 25G and 40G data rates over twisted pair copper
More informationNew standards that have led to higher speeds and new cable categories. Mike Gengler Sales Area VP, Asia/Pac & Japan Fluke Networks
New standards that have led to higher speeds and new cable categories Mike Gengler Sales Area VP, Asia/Pac & Japan Fluke Networks Three Realities of Networking #1 - Networks Never Go Slower Plan for higher
More informationANSI/TIA-568-C Cat 6 Field Test Specifications
This document has been prepared to aid consultants or engineers in developing contractual specifications covering the certification of Category 6 Permanent Links. It is offered as a general guide. Suitability
More informationEnterprise Network Test Strategies for Network Availability and Performance. A Sitaramaiah Director Fluke Networks India
Enterprise Network Test Strategies for Network Availability and Performance A Sitaramaiah Director Fluke Networks India 1 Why is Enterprise Network Testing becoming increasingly important? IT is increasingly
More informationSECTION TELECOMMUNICATIONS TESTING AND DOCUMENTATION
SECTION 17045 TELECOMMUNICATIONS TESTING AND DOCUMENTATION PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including Facilities Management Design and Construction
More informationDatasheet: DSX CableAnalyzer Series
Datasheet: DSX CableAnalyzer Series Datasheet: DSX CableAnalyzer Series The DSX CableAnalyzer Series is the copper certification solution of the Versiv cabling certification product family. The DSX Series
More informationTIA TR-42 Liaison to IEEE
TIA TR-42 Liaison to IEEE Val Rybinski Vice-Chair, TR-42.7 May 2005 Austin, TX Impact of PHY Capabilities Extended frequency characterization required Alien crosstalk limits and test methods required Strategies
More informationCopper Certification Testing Best Practices Pocket Guide
Copper Certification Testing Best Practices Pocket Guide Cabling certification is a best practice of world class installers because it shows the true quality of the installation and reduces the risk of
More informationStandards Update. by Paul Kish NORDX/CDT
Standards Update by Paul Kish NORDX/CDT Standards overview Category 5e cabling new transmission parameters patch cord return loss Category 6 cabling cable choices backwards compatibility Summary Outline
More informationTO THE BID PACKAGE FOR COUNTY OF INYO NETWORK PROJECT. This addendum is being issued to modify portions of the Bid Package for the Project entitled:
ADDENDUM NO. 2 TO THE BID PACKAGE FOR February 6, 2006 This addendum is being issued to modify portions of the Bid Package for the Project entitled: Receipt of this Addendum should be acknowledged by inserting
More informationCable Certification. General Testing Criteria (Applies to all cable certification testing) Attachment F Cable Certification
General Testing Criteria (Applies to all cable certification testing) 1. RCIT reserves the right to be present during any or all cable testing procedures. The Contractor shall obtain authorization from
More informationNGEAB-T Use Cases. Berlin, Germany February Chris DiMinico MC Communications/Panduit
NGEAB-T Use Cases Berlin, Germany February 2015 Chris DiMinico MC Communications/Panduit cdiminico@ieee.org 1 Scope Next Generation Enterprise Access BASE-T PHY Study Group to define use cases and deployment
More informationPerformance specification for the Fluke DSP Fluke Corporation
Performance specification for the Fluke Fluke Corporation 1. Summary This document contains the performance specifications in terms of requirements per draft TIA and IEC specifications. Since requirements
More informationLargest Cat 6A Installation in Midwest Pushes Frontiers of Networking Technology
Largest Cat 6A Installation in Midwest Pushes Frontiers of Networking Technology At a Glance Customer: Terrance Electric and Technology Company for HSBC Industry: Banking/Finance Location: Mettawa, Illinois
More informationThe High Cost of a Low-Cost Cable Certification Tester
The High Cost of a Low-Cost Cable Certification Tester Our thanks to Fluke Networks for allowing us to reprint the following article. How much does it cost? That is typically the first question a cabling
More informationJamey Calloway, RCDD Product Management Specialist Optical Cable Corporation
Testing and deployment of direct attach and the impact of category 8 Thursday, 10 August 2017, 3:50-4:40 P.M. Jamey Calloway, RCDD Product Management Specialist Optical Cable Corporation Overview Traditional
More informationLanTEK III FiberTEK III. Certifier for Copper and Fibre Cabling. Proof of Performance
LanTEK III FiberTEK III Certifier for Copper and Fibre Cabling Proof of Performance LanTEK III FiberTEK III The LanTEK III is an easy to use cable certifier that meets existing TIA and ISO/IEC performance
More informationPCS PATCH CORD SOLUTIONS PATCH CORD SOLUTIONS
Structured Cabling Solutions PCS PATCH CORDS. HiPerlink 6 Colored Patch Cords- 35,36 HiPerlink 1000 Category 5e Colored Patch Cords- 35,36 Snap-in Icons 36 ScTP Category 5 Patch Cord 37 Category 5 Colored
More informationLanTEK III FiberTEK III. Certifier for Copper and Fibre Cabling. Proof of Performance
LanTEK III FiberTEK III Certifier for Copper and Fibre Cabling Proof of Performance LanTEK III FiberTEK III The LanTEK III is an easy to use cable certifier that meets existing TIA and ISO/IEC performance
More informationHistory Channel. 10G Ethernet on Copper
10G Ethernet on Copper History Channel Category Cable by Supported Technology Cat 1 - Telephone cable, ISDN Cat 3-10BaseT Cat 5-100BaseTX Cat 5e - 1000BaseT Cat 6-1000BaseT, but what about 10 Gigabit???
More informationDTX CableAnalyzerTM Accessories Guide
NETWORKSUPERVISION DTX CableAnalyzerTM Accessories Guide See how Fluke Networks options and accessories can easily enhance your investment. Smart Remotes Contents Smart Remotes................. 2 DTX 10
More informationChapter 4: Network Access. Introduction to Networks v5.1
Chapter 4: Network Access Introduction to Networks v5.1 4.0 Introduction 4.1 Physical Layer Protocols 4.2 Network Media 4.3 Data Link Layer Protocols 4.4 Media Access Control 4.5 Summary 2013 Cisco and/or
More informationPANGEN SYSTEM WARRANTY. Warranty Guide
PANGEN SYSTEM WARRANTY Warranty Guide C2-10270 PANGEN SYSTEMWARRANTY GUIDE PROGRAM OUTLINE TABLE OF CONTENTS: MATERIALS PAGE # Program Outline 2 Table of Contents Warranty Information 3 Introduction &
More informationWhite Paper: Choosing the RIght OTDR for your Datacenter
White Paper: Choosing the RIght OTDR for your Datacenter To ensure that fiber in datacenters is reliable, network professionals need a more accurate, easier, and faster methodology for assessing the integrity
More informationIndependent Testing - For End User Confidence
Independent Testing - For End User Confidence QUALIFICATION TESTING OF SCREENED CATEGORY 6 A ISO/IEC, CENELEC & TIA CONNECTING HARDWARE ACCORDING TO REQUIREMENTS OF EDITION 2.2 OF ISO/IEC 11801, CENELEC
More informationTesting Considerations for Beyond 10Gigabit Ethernet. Erin Hallett
Testing Considerations for Beyond 10Gigabit Ethernet Erin Hallett JDSU Agenda Intro Need for Speed Growth of IP traffic Fiber vs. Copper Fiber Tightening requirements Testing considerations and practices
More informationLink Segment IEEE Mb/s Single Twisted Pair Ethernet Study Group Chris DiMinico MC Communications/Panduit
Link Segment IEEE 802.3 10 Mb/s Single Twisted Pair Ethernet Study Group hris DiMinico M ommunications/panduit cdiminico@ieee.org 1 Purpose Scope Initiate discussion(s) on 10 Mb/s Single Twisted Pair Ethernet
More informationApplication Note: Mode Conversion Testing Prevents Your Network from Hanging in the Balance
Application Note: Mode Conversion Testing Prevents Your Network from Hanging in the Balance Application Note: Mode Conversion Testing Prevents Your Network from Hanging in the Balance There is a reason
More informationCategory 8 paves the way for IEEE 40GBASE-T. David Hughes RCDD/DCDC/NTS Senior Technical Manager MEA CommScope
Category 8 paves the way for IEEE 40GBASE-T David Hughes RCDD/DCDC/NTS Senior Technical Manager MEA CommScope Agenda Market need for 40 G over balanced twisted pair cabling Standards ISO/IEC 11801-99-1
More informationMosaic TM LCS2 Cat. 6 RJ 45 socket
870 LIMOGES Cedex Telephone : + 33 0 5 55 06 87 87 - Fax: + 33 0 5 55 06 88 88 Mosaic TM LCS2 Cat. 6 Page 765 61 765 44 765 94 1. General characteristics...1 2. Presentation...2 3. Installation....2 4.
More informationANSI/TIA/EIA-568-B Cabling Standard
73 ANSI/TIA/EIA-568-B Cabling Standard In the mid-1980s, consumers, contractors, vendors, and manufacturers became concerned about the lack of specifications relating to telecommunications cabling. Before
More informationThe advantages of the 6-connector channel
APRIL 2007 The advantages of the 6-connector channel The advantage of sticking to standardised rules such as ISO11801 (that define the performance of the components, the performance of the whole cable
More informationDatasheet: DSX-5000 CableAnalyzer
Datasheet: DSX-5000 CableAnalyzer The DSX-5000 CableAnalyzer is the copper certification solution and is part of the Versiv cabling certification product family. The Versiv line also includes fiber OLTS
More informationMosaic TM LCS2 Cat. 6 RJ 45 socket
870 LIMOGES Cedex Telephone : + 33 0 5 55 06 87 87 - Fax: + 33 0 5 55 06 88 88 Mosaic TM LCS2 Cat. 6 Page 765 61 765 44 765 94 1. General characteristics....1 2. Presentation...2 3. Installation...2 4.
More informationCat.8 Shielded Field Termination Plug Description
Description RiT s CAT8 Shielded field termination plug are cost-effective building blocks for your cabling system. Meticulously engineered to deliver exceptional performance while streamlining installations.
More informationRonald Tellas, Technology and Applications Manager, Enterprise Networking
Direct Connect Testing Guidelines Ronald Tellas, Technology and Applications Manager, Enterprise Networking Introduction Direct Connect is a viable option for the Digital Building that is being deployed
More informationWhite Paper: Installing Data Networks Using LinkWare Live SaaS
White Paper: Installing Data Networks Using LinkWare Live SaaS White Paper: Installing Data Networks Using LinkWare Live SaaS Software as a Service (SaaS) continues to grow in popularity across a wide
More informationProvided by
Provided by www.aaatesters.com Datasheet: DSX-5000 CableAnalyzer The DSX-5000 CableAnalyzer is the copper certification solution and is part of the Versiv cabling certification product family. The Versiv
More informationWhite paper. Field Testing of Direct Attach Modified Permanent Links. occfiber.com
The dramatic growth of high-bandwidth wireless access points and other IP-enabled devices, such as surveillance cameras and building automation equipment has resulted in the practice of installing direct
More informationCable Sharing: An ANSI & ISO Recognized Solution for High Density, Low-Speed Applications. Robert Y. Faber Jr., RCDD/NTS.
Cable Sharing: An ANSI & ISO Recognized Solution for High Density, Low-Speed Applications Broadband High-Speed LAN Voice Robert Y. Faber Jr., RCDD/NTS Minimum Port Recommendations TIA/EIA-568-B.1 2 outlets
More informationAMP-TWIST* Modular Jack, UTP, Category 6A
Product Specification 5 July 13 Rev A AMP-TWIST* Modular Jack, UTP, Category 6A 1. SCOPE 1.1 Content This specification covers performance, tests and quality requirements for TE Connectivity*, 6A UTP AMP-
More informationOpen System Architecture Selecting the Right Cable and Connectivity for Your Application
Open System Architecture Selecting the Right Cable and Connectivity for Your Application Kenneth Cornelison Industry Consultant Wire and Cable Technology Engineering Resources Key Discussion Points TIA
More informationINSTALLATION INSTRUCTIONS. ACB-100 Audio Control Board. This document describes the installation procedure for the ACB-100 Audio Control Board.
INSTALLATION INSTRUCTIONS MicroComm DXI -00 Audio Control Board. Intent & Scope This document describes the installation procedure for the -00 Audio Control Board. 2. Description The -00 Audio Control
More informationAMENDED FINAL REPORT FOR:
731 Enterprise Drive Lexington, KY 40510 Telephone: 859-226-1000 Facsimile: 859-226-1040 www.intertek-etlsemko.com AMENDED FINAL REPORT FOR: CUSTOMER NAME: PRODUCT NAME: Leviton 2222 222nd St. SE Bothell,
More informationDC Center Copper Cabling up to 40Gbase-T. Halim Senjaya
DC Center Copper Cabling up to 40Gbase-T Halim Senjaya CTDC CTIA Data Center Expert Datwyler Singapore Diploma in Eng ng in Physics Bandung IT Diploma in Cloud DC Technologies - NP MBA Middlebury Institute
More informationMORE ETHERNET ON THE HORIZON WHO NEEDS 2.5G AND 5G ETHERNET? Krzysztof Ojdana, Product Manager WHITE PAPER. Molex Connected Enterprise Solutions
MORE ETHERNET ON THE HORIZON WHO NEEDS 2.5G AND 5G ETHERNET? Krzysztof Ojdana, Product Manager WHITE PAPER Molex Connected Enterprise Solutions EXECUTIVE SUMMARY Ethernet seems to be one of the fastest
More informationIndustry Standards in ICT Enabled Projects Reading and Applying the "Fine Print"
Industry Standards in ICT Enabled Projects Reading and Applying the "Fine Print" Gautier Humbert, RCDD Standards Coordinator Legrand Digital Infrastructures Gautier Humbert, RCDD BICSI District Chair Mainland
More informationAppendix 1 to the R&Mfreenet Warranty Program
Appendix 1 to the R&Mfreenet Warranty Program 1 R&M Certification Process The R&Mfreenet certification process is three pillars: a) Adherence to applicable standards, both for products and installations;
More informationTarleton State University. Specifications
Tarleton State University Campus Communication Infrastructure Specifications Cabling Standards Summary This document identifies Tarleton State University communication infrastructure standards. The communication
More informationAMP-TWIST* 6S Series SL Jack
Product Specification 108-93003 16/Mar/2011 Rev E AMP-TWIST* 6S Series SL Jack 1. SCOPE 1.1 Content This specification covers performance, tests and quality requirements for AMP NETCONNECT*, AMP- TWIST*
More informationGet ready to overachieve.
Datasheet: DSX-5000 CableAnalyzer The DSX-5000 CableAnalyzer is the copper certification solution and is part of the Versiv cabling certification product family. The Versiv line also includes fiber OLTS
More informationPANGEN INDUSTRIAL AUTOMATION SYSTEM WARRANTY
PANGEN INDUSTRIAL AUTOMATION SYSTEM WARRANTY WARRANTY GUIDE PANGEN INDUSTRIAL AUTOMATION SYSTEM WARRANTY WARRANTY GUIDE PROGRAM OUTLINE TABLE OF CONTENTS: MATERIALS PAGE # Program Outline 2 Table of Contents
More informationChapter 3 Certifying Twisted Pair Cabling
Chapter 3 Certifying Twisted Pair Cabling Setting the Reference The reference procedure sets a baseline for insertion loss, ELFEXT, and dc resistance measurements. Run the tester s reference procedure
More informationIntroduction to Key Principles of Telecommunications Cabling
Introduction to Key Principles of Telecommunications Cabling Dimitris Filippou Technical Director, Ltd. IEEE Member, BICSI Country Chair, ELOT Technical Committee TC93 Member, CENELEC TC215 Delegate of
More information"IL CABLAGGIO IN RAME DI CATEGORIA 6 E LA CERTIFICA SUL CAMPO DEI PARAMETRI TRASMISSIVI FINO A 250 MHZ"
"IL CABLAGGIO IN RAME DI CATEGORIA 6 E LA CERTIFICA SUL CAMPO DEI PARAMETRI TRASMISSIVI FINO A 250 MHZ" Gli standard per la categoria 6 e i nuovi strumenti di misura maurizio.malinconi@flukenetworks.com
More informationCERTIFICATION PLUS SM
CERTIFICATION PLUS SM SYSTEM WARRANTY PROGRAM Panduit Warranty Guide PROGRAM OUTLINE TABLE OF CONTENTS: MATERIALS PAGE # Program Outline 2 Table of Contents Warranty Information 3 Introduction & Installation
More informationDatasheet: DSX-5000 CableAnalyzer
Datasheet: DSX-5000 CableAnalyzer The DSX-5000 CableAnalyzer is the copper certification solution and is part of the Versiv cabling certification product family. The Versiv line also includes fiber OLTS
More informationISO/IEC 11801: (E)
ISO/IEC 11801:2002-09 (E) Information technology_- Generic cabling for customer premises CONTENTS FOREWORD...10 INTRODUCTION...11 1 Scope...13 2 Normative references...13 3 Definitions, abbreviations and
More informationCat.8 Shielded Keystone Jack Description
Description RiT s CAT8 Shielded Keystone Jacks are cost-effective building blocks for your cabling system. Meticulously engineered to deliver exceptional performance while streamlining installations. Phosphor
More informationAdvances in Fiber Tier 2 Enterprise & Data Center Testing
Advances in Fiber Tier 2 Enterprise & Data Center Testing As the volume of fibers deployed into enterprise increases significantly, fiber cabling advances like multi-fiber (MPO) connectors and interfaces
More informationDatasheet: DSX CableAnalyzer Series
Datasheet: DSX CableAnalyzer Series The DSX CableAnalyzer Series is the copper certification solution of the Versiv cabling certification product family. The DSX Series includes the DSX-8000, which can
More informationDatasheet: DSX CableAnalyzer Series
Datasheet: DSX CableAnalyzer Series Datasheet: DSX CableAnalyzer Series The DSX CableAnalyzer Series is the copper certification solution of the Versiv cabling certification product family. The DSX Series
More informationCertificate bundle. KELine components Cat.6 A, Cat.7, Cat.7 A. from independent testing laboratories. for KELine Structured Cabling
Certificate bundle from independent testing laboratories for KELine Structured Cabling KELine components Cat.6 A, Cat.7, Cat.7 A Certificate verification step by step On the website of the testing laboratories*:
More informationLANcat System 6 with C5e Performance Module. User Manual Addendum
LANcat System 6 with C5e Performance Module User Manual Addendum Datacom Textron may make improvements or additions to this publication or their products at any time without notice. Datacom Textron shall
More informationAnixter Standards Reference Guide
Anixter: The Cabling System Experts Anixter is a leading global supplier of communications and security products, electrical and electronic wire and cable, fasteners and other small components. We help
More informationFrequently Asked Questions (FAQs) Siemon 10G ip Solutions
Frequently Asked Questions (FAQs) Siemon 10G ip Solutions The world of enterprise cabling is evolving rapidly. Emerging, high-bandwidth services and the adoption of higher speed Ethernet standards, like
More information10G Ethernet Over Structured Copper Cabling
I T I n f r a s t r u c t u r e S o l u t i o n s Note: The following technical article was current at the time it was published. However, due to changing technologies and standards updates, some of the
More informationPhysical Layer V What does the physical layer provide?
SEMESTER 1 Chapter 8 Physical Layer V 4.0 90 Points 8.1.1 What does the physical layer provide? What are the four elements of delivering frames across the media? 8.1.2 What are the three basic forms of
More informationFiber Management Systems
FIBER OPTIC PRODUCTS CATALOG OF ALL PRODUCTS WWW..COM Fiber Management Systems Wall Mount Fiber Management System Stand Alone Floor Mount Fiber Rack Mount Fibre Management System Fixed Type ODF Sliding
More informationDTX-PCU6S. Users Manual. Patch Cord Adapters
DTX-PCU6S Patch Cord Adapters Users Manual November 2004 2004 Fluke Corporation. All rights reserved. All product names are trademarks of their respective companies. LIMITED WARRANTY & LIMITATION OF LIABILITY
More informationCabling to support ac and beyond. Nate Herring Sr. Product Manager Hubbell Premise Wiring
Cabling to support 802.11ac and beyond Nate Herring Sr. Product Manager Hubbell Premise Wiring IP Traffic Continues to Increase Globally, IP traffic will grow 3-fold from 2014 to 2019, a compound annual
More informationPower Over Ethernet with Panduit Copper Cabling. How To Create More Meaningful Connections With The Highest Performing Infrastructure
Power Over Ethernet with Panduit Copper Cabling How To Create More Meaningful Connections With The Highest Performing Infrastructure Introduction Increasing usage of Power over Ethernet (PoE) represents
More informationThe Impact of Internet of Things (IoT) on Cable Certification
The Impact of Internet of Things (IoT) on Cable Certification Simon Harrison General Manager Softing Singapore Pte Ltd November 2017 Agenda Review of traditional structured cabling configurations Special
More informationR&Mfreenet Advanced Cat 6A Shielded Connection Module
R&Mfreenet Advanced R&Mfreenet Advanced Cat 6A Connection Module The R&Mfreenet Cat 6A shielded connection modules, part of the Advanced cabling system, are ideal for voice, fast data transmissions and
More informationPhysical Layer changes coming to a network near you, soon! Wayne Allen Regional Marketing Engineer Fluke Networks
Physical Layer changes coming to a network near you, soon! Wayne Allen Regional Marketing Engineer Fluke Networks Agenda New ISO/IEC 11801 Standard New Fibre standards and encoding methods Higher speeds,
More informationNGEAB-T Use Case ad hoc February 6, 2015
NGEAB-T Use Case ad hoc February 6, 2015 Chris DiMinico MC Communications/Panduit cdiminico@ieee.org 1 Agenda Agenda February 6, 2015 (1)Review patent policy (2) Review contributions NGEAB-T Use Case Ad
More informationDatasheet: DSX CableAnalyzer Series
Datasheet: DSX CableAnalyzer Series The DSX CableAnalyzer Series is the copper certification solution of the Versiv cabling certification product family. The DSX Series includes the DSX-8000, which can
More informationSPOS (Station Point of Sale) 200. SFTP (Station Fare Transaction Processor) 35. CQD (Card Query Device) 35. HCR (Handheld Card Reader) Cradles 120
DESIGN GUIDELINES PRESTO INSTALLATION & CONNECTIVITY PAGE 1 of 4 ELECTRICAL CONNECTIVITY AND WIRING Communications Conduits Conduits designated for Presto equipment data wiring shall be clearly identified
More informationCabling Infrastructure
Introduction Ethernet Banking on Structured Cabling Technology Drivers Classification of Cables Fibre-optic cable Cables in building Cabling Infrastructure Cabling systems address the networking requirements
More informationIntroduction. Standards
Introduction LAN cable certifiers have been the go-to method of testing twisted pair cabling for nearly a quarter century, since the advent of 10Base-T on Class C/category 3 cabling to 10 MHz. This article
More informationLAN Standards, News & Trends Update 2017 June 15, 2017
LAN Standards, News & Trends Update 2017 June 15, 2017 Greg Olson Jtech Systems, Inc Infrastructure Specialist Greg@jtechreps.com 425-437-1962 Our Objectives Review new & ongoing applications work in IEEE
More informationor go home GO SMALL SEPTEMBER 2015 FOR PROFESSIONALS MANAGING THE CABLE AND WIRELESS SYSTEMS THAT ENABLE CRITICAL COMMUNICATIONS STANDARDS
SEPTEMBER 2015 FOR PROFESSIONALS MANAGING THE CABLE AND WIRELESS SYSTEMS THAT ENABLE CRITICAL COMMUNICATIONS GO SMALL or go home STANDARDS PAGE 17 WBMMF on the fast track NETWORK MANAGEMENT PAGE 31 Quicken
More informationLos Angeles Community College District Design Standards
LACCD Facilities Design Standards - Structural Cabling and Telecommunications Room Facilities Ver Approved: DTC February 0, 0 LACCD has developed the following Districtwide standard for IT infrastructure
More informationOvercoming the Testing Challenges of 40G and Beyond. Eric Farst Channel Sales Manager
Overcoming the Testing Challenges of 40G and Beyond Eric Farst Channel Sales Manager Agenda Introduction Increased demand for speed & capacity in the Enterprise/Data Center How Enterprises/Data Centers
More informationNew Standardized Cabling Options for NBASE-T Devices
New Standardized Cabling Options for NBASE-T Devices Webinar Speakers Tom Baum Sr. Product Manager, Panduit tmba@panduit.com Peter Jones Chairman, NBASE-T Alliance Distinguished Engineer, Cisco chairman@nbaset.org
More informationAMENDED FINAL REPORT FOR:
731 Enterprise Drive Lexington, KY 40510 Telephone: 859-226-1000 Facsimile: 859-226-1040 www.intertek.com AMENDED FINAL REPORT FOR: CUSTOMER NAME: PRODUCT NAME: Leviton Manufacturing Co. 417 Stone Drive
More informationDTX-PCxxS. Users Manual. Patch Cord Test Adapters
DTX-PCxxS Patch Cord Test Adapters Users Manual January 2011 2011 Fluke Corporation. All rights reserved. Printed in USA. All product names are trademarks of their respective companies. LIMITED WARRANTY
More informationCHAPTER 7 Copper Cable Testing
CHAPTER 7 Copper Cable Testing Lesson Objective After completing this lesson, you should be able to: i. Explain the various terms and instruments used to test copper cabling system. Cable Testing Cables
More informationTraining Offer. Catalogue
Training Offer Catalogue docnr. 3.0 rev.date: 04 August 2008 2/13 Introduction, "The transmission quality of a cabling installation depends on the cabling system used, as well as the installation itself."
More informationNGBASE-T Cabling Requirements
NGBASE-T Cabling Requirements Dr. T. C. Tan, DMTS, CommScope Labs B.Sc (Eng), DIC, PhD, CEng, FIET White paper www.commscope.com Contents Contents Contents 2 1.0 Introduction 3 2.0 IEEE 802.3 NGBASE-T
More informationLANmark-6 10G LANmark-6 A
Field-testing procedure of LANmark-6 10G LANmark-6 A Cabling System Technical Paper Nexans Cabling Solutions March 2006 - Revision 1.1 Table of Contents 1 Introduction 3 2 How to proceed? 4 2.1 Introduction
More informationEthernet and PoE Operation Over Single Pair Twisted-Pair Copper Cabling (SPE) Chris DiMinico AEM Technical Sales Test and Measurement
Ethernet and PoE Operation Over Single Pair Twisted-Pair Copper Cabling (SPE) Chris DiMinico AEM Technical Sales Test and Measurement Overview SPE is poised to enable a new class of low power devices that
More informationThe AMP NETCONNECT Category 6 Cabling System
The AMP NETCONNECT Category 6 Cabling System 2 Table of Contents TABLE OF CONTENTS...3 PERSPECTIVE...4 WHY INSTALL NEXT GENERATION CABLING SYSTEMS?...4 MEGAHERTZ VS. MEGABITS...4 PLANNING FOR THE FUTURE...5
More informationConflicts in Data Center Fiber Structured Cabling Standards
Conflicts in Data Center Fiber Structured Cabling Standards By Dave Fredricks, CABLExpress Data Center Infrastructure Architect Various telecommunications and data center (DC)-specific standards are commonly
More informationDeploying NBASE-TTM 2.5G/5GBASE-T Technologies
Deploying NBASE-TTM 2.5G/5GBASE-T Technologies George A. Zimmerman, Ph.D., CME Consulting Board of Directors, NBASE-T Alliance Peter Jones, Cisco Systems Chairman, NBASE-T Alliance Masood Shariff, CommScope
More informationCATEGORY 6 PATCH BY EXCEPTION SOLUTION (PBE) Modules Frames and Covers Labelling and Accessories Patch Leads Cable Management
CATEGORY 6 PATCH BY EXCEPTION SOLUTION (PBE) Modules Frames and Covers Labelling and Accessories Patch Leads Cable Management CLIPSAL DATACOMMS CATEGORY 6 PATCH BY EXCEPTION INTRODUCTION Category 6 Patch
More informationIEEE Ethernet Working Group TIA TR-42 Liaison to IEEE 802.3
IEEE 802.3 Ethernet Working Group TIA TR-42 Liaison to IEEE 802.3 Valerie Maguire The Siemon Company Dallas, TX November 9, 2015 Page 1 Introduction to TIA Telecommunications Industry Association www.tiaonline.org
More information