Implementation of Online ABT monitoring System In The TATA Power Co. Ltd. Mumbai. S. G. Patki, S. C. Dhapre, S. G. Joshi, S. A.

Size: px
Start display at page:

Download "Implementation of Online ABT monitoring System In The TATA Power Co. Ltd. Mumbai. S. G. Patki, S. C. Dhapre, S. G. Joshi, S. A."

Transcription

1 1 Implementation of Online ABT monitoring System In The TATA Power Co. Ltd. Mumbai S. G. Patki, S. C. Dhapre, S. G. Joshi, S. A. Wangade

2 2 Topics Discussed Metering system between TPC & MSETCL. Need for change in metering system. Salient features of online monitoring system. Implementation of online monitoring system. Experience during installation & commissioning. Future needs.

3 3 Introduction TATA Power Company is the largest private sector utility in India in the field of generation, transmission and distribution of electricity. It owns and operates thermal generating stations at Trombay,Jojobera, and Belgaum with total installed capacity of 1858 MW. It has also set up hydro generating plants at Bhira, Bhivpuri and Khopoli in the Raigad district of Maharashtra with a combined installed capacity of 480 MW. TPC distributes electricity in Mumbai directly and also through its licensees REL and BEST.

4 4 TPC-MSETCL Interconnection TPC network is interconnected by 220 KV lines to MSETCL at Trombay, Kalwa & Borivli. TPC has provided several 22 KV outlets to MSEDCL from its receiving stations at Kalyan, Ambarnath, Salsette, Kolshet and Panvel. MSETCL wheels power to MSEDCL through 22 KV outlets provided by TPC. TPC also feeds some direct consumers of MSEDCL at Saki and Khopoli. Totally, there are about 24 metering points between MSETCL and TPC, which are spread over a distance of 100 KM. Static HT Trivector meters with TOD features are deployed at above points. Meter data is collected jointly and processed for calculating net interchange between TPC and MSEB used for billing.

5

6 Typical TOD Meter

7 7 Modification in metering scheme In May, 2004, TPC started supplying power to utilities outside Maharashtra, as per availability, using transmission network of MSETCL. ABT tariff was applicable for such transactions and TPC was required to schedule and monitor net interchange with MSETCL on fifteen-minute time slot basis. TOD tariff was still applicable for normal power transactions between TPC and MSETCL. Existing TOD meters were not suitable for this application. It was decided to install new SEMs in series with the existing meters & also provide necessary remote communication system to monitor the net exchange between TPC and MSETCL on a real time basis.

8 ABT & Revenue meter at MSEDCL point of supply

9 9 Procurement of ABT meters Salient features included in meter specifications The meter should be compatible with TOD as well as ABT requirements simultaneously. Meter should have two independent auxiliary supplies for better reliability. Meter should be suitable for remote communication on real time basis. Meter should transfer tamper events / abnormalities immediately to server through the same communication port used for on line monitoring.

10 ABT Meter Procured by TPC

11 11 Procurement of software Salient features specified for UI Monitoring software. On line monitoring software should collect data from all the connected meters on real time basis and compute net interchange between MSETCL and TPC every minute. Software should provide user-friendly screens for continuous monitoring of net exchange. Monitoring screen should change the color when unscheduled interchange is resulting into net loss to TPC. Events & Communication failures should be annunciated immediately.

12 12 Procurement of software Salient features specified for UI Monitoring software. It should be possible to prepare daily schedule and or FAX the same to RLDC. System should generate user defined MIS reports such as monthly UI report highlighting periods of high-unscheduled interchange TPC procured new meters and on line monitoring software in May The server and Software installation at Trombay,and necessary remote communication set up was completed in November-2004.

13 ABT meter with online monitoring software

14 14 The Online monitoring scheme The meter works on serial RS-232 at a baud rate of 1200 bps. The communication protocol is kept proprietary for data security. To get data from connected meters within an interval of maximum 58 seconds, special devices called Net Box (NB-Repeaters) & Data Communication Unit (DCU-Amplifiers) are provided at both ends. Since UI between TPC & MSETCL is calculated by integrating data of all the meters, it was absolutely essential to synchronize their RTCs. A GPS clock is connected to the server, which in turn synchronizes individual meter clocks periodically and ensures time synchronization.

15 The NET BOX Line Driver & Multiplexer

16 DCU The Signal Booster

17 NB DCU Connections

18

19 19 Installation & Commissioning Metering points are geographically spread. Out of the total 24 metering points, only 13 were measuring significant interchange of power with MSETCL. 11 metering points were located in consumer premises and their combined consumption was insignificant. A summation meter was installed in TPC substation to record their combined consumption and the same was included in on line monitoring scheme. Getting data at central location on real time basis required very reliable communication network. Dedicated communication network of TPC (MW/FOP) was used for the scheme. Leased lines were used where TPC network was not available

20 20 Installation & Commissioning Communication configurations were chosen based on availability & reliability. FOP was a preferred media, where available. Out of the 13 major points, connectivity to TPC s own Fiber optic network was available for 8 points located in TPC receiving stations at Salsette, Kalyan, Saki & Kolshet respectively. To optimize the usage of fiber channels, a data bus was formed at Salsette for all the meters connected to FOP network.

21 Optical Fibre Guard Wire (OPGW on top of the transmission tower)

22 Fibre Cable Guard Wire Optical Fibre & Guard Wire Separation

23 Typical Fiber Optic Exchange (FOX)

24 Typical Fiber Optic Exchange (FOX)

25 Typical Fiber Optic Exchange (FOX)

26 Data Bus Formation at Salsette

27 Data Bus Formation at Salsette

28 28 Installation & Commissioning Three metering points located at Kalwa and Borivli stations of MSETCL did not have FOP connectivity and required some other media to establish communication with the Server. Leased Telephone Line was used at Kalwa. Combination of Leased telephone line and TPC Fiber network was used at Borivali. FOP network point was available about 2 Km away from the meter. The data is transferred up to FOP point using leased line and further up to Data Acquisition Server ( DAS ) through FOP.

29 29 Installation & Commissioning TPC Microwave system (Operating frequency 2.4 GHz) was used for two meters at Ambernath as FOP network and leased line were not available. The meter data is transferred directly to DAS through MW system. As some of the metering installations are located in 220kV / 100 kv switchyards, armored, shielded, four pair, CAT-5 cables were used for data communication to avoid electro-magnetic interference. Two meters at Trombay were connected directly to DAS using CAT-5 cables, as they were located close to the server room.

30 The Microwave Tower

31 The Microwave Antenna

32 ABT Meter-1 NB DCU Modem MW MW ABT Meter-2 NB Salsette HUB Ambernath ABT Meter-3 NB DCU FOX - 20 FOX - 20 DCU NBR FOX U SAL Modem GPS ABT Meter-4 Kalyan ABT Meter-5 Saki ABT Meter-6 NB NB NB DCU DCU FOX - 20 FOX - 20 FOX - 20 FOX - 20 NBR NBR FOX U LDD STARS DAS STARS Client Trombay LDD DCU Kolsheth ABT Meter-7 NB DCU FOX - 20 NBR ABT Meter-8 Salsette NB LLM FOX - 20 FOX - 20 NBR LLM Salsette FOP ABT Meter-12 NB ABT Meter-9 LLM DCU LLM Trombay 100kV Borivali ABT Meter-10 NB Kalwa 100kV NBR Leased Line DCU ABT Meter-13 NB Microwave NBR Trombay 220kV Fiber Optic CAT-5 Cable ABT Meter-11 Kalwa 220kV NB ABT Communication Architecture

33 33 On line monitoring Software Online monitoring scheme works on client-server architecture. The data acquisition server collects & stores data of each meter & the client machine provides online monitoring screens & user-defined reports. Oracle is used for data base management & SQL is used for Server-Client communication on LAN. Meter master data such as Meter Serial number, Meter ID, Multiplication Factor and Installation master data such as Generating station, Virtual meter definition, frequency steps, and UI Rates etc.is configured in Client machine.

34 Data Acquisition Server

35 Meter Data on Client Screen

36 36 On line monitoring Software Software was originally designed for a Generating station and only export scheduling was provided. TPC, being an integrated utility, was required to schedule supply as well as purchase of power and thus needed both import and export scheduling feature. This feature was added later. The software was initially designed to provide only two monitoring screens. UI monitoring screen Graphical screen. Toggle between two screens was inconvenient to our Load dispatch staff. The software was modified and the two screens were merged into a single screen titled Online UI, & graphical screen.

37 Online UI Screen Last Minute Data

38 Online Graphical Display

39 39 On line monitoring Software Merged screen was found very convenient by load dispatcher to monitor real time data such as a) Block time b) Scheduled interchange c) Current interchange d) Average frequency of current interval. e) Interchange since start of block. (Actual Interchange) f) Projected interchange at the end of the block g) Desired interchange to avoid unscheduled interchange h) UI in MW i) Loss or Gain in Rupees j) Alarms.

40 Online UI & Graphical Display

41 41 Problems during commissioning During communication trials, it was observed that indigenous RJ-45 & RJ-11 connectors used for terminations on NBs, DCUs & Modems were not getting latched properly resulting into frequent communication failure due to loose contact. Imported connectors were then used to overcome this problem. The data bus formed at Salsette for six meters was intermittently failing to communicate. Investigations revealed that the leased line modems were introducing an extra character in the data string, which was causing CRC failure & pulling the entire data bus down. New MODEM and DCU was put at Borivli to overcome this problem. The leased line at Kalwa was found to be unreliable & communication used to fail frequently. Hence TPC Microwave network was used instead of leased line. Microwave communication was found to be more reliable than the leased line. However, due to external Radio Frequency Interference (RFI), occasional failure was observed on microwave channels also.

42 42 Conclusion. FOP is found to be the most reliable communication media for such critical schemes. Leased line and Microwave media were not found to be very reliable. When communication with one meter fails, UI report for this period is not available. It should be possible to collect meter data manually and upload the same in the server so that UI report is available for entire month. It should be possible to export interval data and reports in EXCEL format. This will help generate other MIS reports. The billing data, frozen readings, tamper events etc registered by connected meters are not captured by the online integration software. This would be a useful feature. Additional communication channel is necessary to collect load survey data from connected meters. This is unnecessary duplication.

43 43 Future Needs Of Utility Industry. Power sector in India has a huge investment backlog, but is bridging the gap rapidly due to reforms. Large Business houses like TATA, Reliance, Essar, L & T, Torrent have big investment plans. TATA,s are in fact planning to go global and seeking opportunities in South Africa, Bangladesh, Australia, Latin America etc. These corpoates would need following information on real time basis at their corporate head quarter for smart decisions. 1. Net Generation from each plant,/each unit and Generation cost data. 2. Net sales from each Discom and Genco. 3. Net power purchase / Net power traded 4. Off take /Demands of key customers across the country.

44 44 Future Needs Of Utility Industry. This will need convergence of IT, communication and Metering technologies. May call for using Internet for meter data collection and transfer. There will be a need for end to end solution providers / service providers. How to cover areas which are remote and lack infrastructure in integrated data management. This will be a challenge. Key concerns will be time, data security, integrity, & system reliability. Can Indian power sector and IEEMA take the bet? Together, we can!

45 45 Our Contacts Thank you for patient hearing! Please send your queries by We will be pleased to respond.

Message Box ( Arial, Font size 18 Bold)

Message Box ( Arial, Font size 18 Bold) ed Operational Presentation Excellence through Title ( Arial, Automation Font size 28 ) Date, Venue, etc..( Arial, Font size 18 ) Jacob Joseph 02 nd Nov 2012 CII conference, New Delhi Outline Tata Power

More information

ENGINEERING SOLUTIONS INDIA PVT. LTD.

ENGINEERING SOLUTIONS INDIA PVT. LTD. Company Profile Company Overview P I N N A C L E ENGINEERING SOLUTIONS INDIA PVT. LTD. is founded in beginning of the first decade of 2000. The company is founded by Mr. Praphullachandra Ohol who has 20

More information

Simulation of Power System Faults for Protection Performance Analysis -Case Studies of Tata Power

Simulation of Power System Faults for Protection Performance Analysis -Case Studies of Tata Power Simulation of Power System Faults for Protection Performance Analysis -Case Studies of Tata Power By S G Patki M V Kini P K Jain G T Jawale Presented at: International Conference on Power System Protection,

More information

AMR and SCADA in Outage Management System for MSEDCL Sangita B. Patil 1, Bapu K. Patil 2

AMR and SCADA in Outage Management System for MSEDCL Sangita B. Patil 1, Bapu K. Patil 2 e-issn: 2349-9745 p-issn: 2393-8161 Scientific Journal Impact Factor (SJIF): 1.711 International Journal of Modern Trends in Engineering and Research www.ijmter.com AMR and SCADA in Outage Management System

More information

TECHNICAL SPECIFICATION OF GPRS based MODEM (Part 1)

TECHNICAL SPECIFICATION OF GPRS based MODEM (Part 1) TECHNICAL SPECIFICATION OF GPRS based MODEM (Part 1) 1. SCOPE: The scope of work is on turn-key basis covering modem supplies, solution engineering. Supply of GPRS Modems for data acquisition from HT/

More information

Automation in Large Urban Power Distribution System. Dr. K Rajamani CENTRAL TECHNICAL SERVICES, RELIANCE ENERGY LIMITED, MUMBAI

Automation in Large Urban Power Distribution System. Dr. K Rajamani CENTRAL TECHNICAL SERVICES, RELIANCE ENERGY LIMITED, MUMBAI Automation in Large Urban Power Distribution System Dr. K Rajamani CENTRAL TECHNICAL SERVICES, RELIANCE ENERGY LIMITED, MUMBAI Need for Automation and Current trends Automation Systems and Functionality

More information

A Case Study: SCADA Implementation in KPTCL

A Case Study: SCADA Implementation in KPTCL A Case Study: SCADA Implementation in KPTCL Vinuta V Koluragi M.Tech(Power and Energy Systems) Assisstant Professor B.L.D.E.A s V P Dr P. G. Halakatti College of Engg. & Tech., Bijapur. Abstract: Development

More information

INTERNET DELIVERY - REVISITED PART II - THE DISTRIBUTION SYSTEM

INTERNET DELIVERY - REVISITED PART II - THE DISTRIBUTION SYSTEM INTERNET DELIVERY - REVISITED PART II - THE DISTRIBUTION SYSTEM The concluding second part of this series provides details of the distribution system necessary to provide LAN connectivity to computers

More information

LANs do not normally operate in isolation. They are connected to one another or to the Internet. To connect LANs, connecting devices are needed.

LANs do not normally operate in isolation. They are connected to one another or to the Internet. To connect LANs, connecting devices are needed. LAN interconnecting devices INTRODUCTION LANs do not normally operate in isolation. They are connected to one another or to the Internet. To connect LANs, connecting devices are needed. Connecting devices

More information

Project Features. Power Sector Improvement Project (RRP KGZ ) $ 44.8 million (62.7% grant % loan) ADF amount:

Project Features. Power Sector Improvement Project (RRP KGZ ) $ 44.8 million (62.7% grant % loan) ADF amount: Power Sector Improvement Project (RRP KGZ 43456-02) Project Concept Outline Project Features ADF amount: ADF Country allocation: ADF Regional allocation: PPTA Budget (TASF IV): Sector (subsectors): Themes:

More information

Generation Interconnection Impact Study Report. For. Interconnection Customer Q0022

Generation Interconnection Impact Study Report. For. Interconnection Customer Q0022 Generation Interconnection Impact Study Report For Interconnection Customer Q0022 Prepared by: PacifiCorp Date: 10/29/2003 Generation Interconnection System Impact Study Report Interconnection Customer

More information

Energy Management System with ABT Optimization Engine

Energy Management System with ABT Optimization Engine Energy Management System with ABT Optimization Engine A White Paper Kalki Communication Technologies Limited #147, 5 th Main, HSR Layout, Sector 7 Bangalore 560102, INDIA E-mail: info@kalkitech.com Phone:

More information

Chapter 9 Introduction to Networks

Chapter 9 Introduction to Networks Chapter 9 Introduction to Networks 9.1 Uses of a network Networks are used in many situations. We can see networks in places like offices, airports and factories. In fact we use networks in many situations

More information

Reliance Infrastructure Limited

Reliance Infrastructure Limited Reliance Infrastructure Limited Reg. : H Block, 1 st Floor, Dhirubhai Ambani Knowledge City, Navi Mumbai 400 710 Website: www.rinfra.com PUBLIC NOTICE Objections / suggestions on Reliance Infrastructure

More information

Automation System Solutions

Automation System Solutions Automation System Solutions Automation Systems for Power Grid, Power Plant and Industries NR Electric Corporation Automation for Power Grid Substation Automation System Conventional Substation Automation

More information

Wireless IoT Sensing Solutions

Wireless IoT Sensing Solutions Wireless IoT Sensing Solutions Modularized and Ready-to-Use Solutions High Adaptability for IoT Sensing IoT Sensing Applications LPWAN and Wireless Ethernet IoT Architecture IoT Technology Product Highlights

More information

PRYSM ADVANCED METERING INFRASTRUCTURE. Intelligent Digital Solutions for a Smarter India

PRYSM ADVANCED METERING INFRASTRUCTURE. Intelligent Digital Solutions for a Smarter India PRYSM ADVANCED METERING INFRASTRUCTURE Intelligent Digital Solutions for a Smarter India VELANKANI SMART GRID PRODUCTS DRIVING INNOVATIVE ENERGY EFFICIENT SOLUTIONS Smart metering essentially involves

More information

Deploying Digital Substations: Experience with a Digital Substation Pilot in North America. Harsh Vardhan, R Ramlachan GE Grid Solutions, USA

Deploying Digital Substations: Experience with a Digital Substation Pilot in North America. Harsh Vardhan, R Ramlachan GE Grid Solutions, USA Deploying Digital Substations: Experience with a Digital Substation Pilot in North America Harsh Vardhan, R Ramlachan GE Grid Solutions, USA Wojciech Szela, Edward Gdowik PECO, USA SUMMARY Though IEC 61850

More information

Cyan Technology Ltd. Smart energy solutions. Meeting the challenges of smart metering in emerging regions

Cyan Technology Ltd. Smart energy solutions. Meeting the challenges of smart metering in emerging regions Cyan Technology Ltd Smart energy solutions Meeting the challenges of smart metering in emerging regions Dr Sean Cochrane Strategic Marketing Director Cyan Technology, UK May 2013 Cyan introduction 2 Smart

More information

COMPANY PROFILE LIPA MAJI NA

COMPANY PROFILE LIPA MAJI NA COMPANY PROFILE LIPA MAJI NA Smart (Prepaid) Water Metering Solutions Welcome to SwissQuest Water Supplies Company Ltd. SwissQuest Water Supplies is a Utilities Technology Company that specializes inthe

More information

Conference on Telecom Needs in Power Sector. Session Focus on Transmission

Conference on Telecom Needs in Power Sector. Session Focus on Transmission Conference on Telecom Needs in Power Sector Session Focus on Transmission 30-05-2012 POWERGRID- Business Segments Generation Linked (carries 51% of Nation s electric power) Grid Strengthening Inter-Regional

More information

AMI in Smart Substation Pilot Project

AMI in Smart Substation Pilot Project AMI in Smart Substation Pilot Project Knathip Spuntupong Metropolitan Electricity Authority Metering, Billing, CRM Asia 2013 22-23 May 2013 Bangkok Convention Centre at CentralWorld, Thailand Presentation

More information

Computers Are Your Future Tenth Edition

Computers Are Your Future Tenth Edition Computers Are Your Future Tenth Edition Chapter 3: Wired & Wireless Communication Copyright 2009 Pearson Education, Inc. Publishing as Prentice Hall 1 All rights reserved. No part of this publication may

More information

WATER TELEMETRY SYSTEM

WATER TELEMETRY SYSTEM WATER TELEMETRY SYSTEM v1.04 1 SkyΜeter Hydro edition (SM-HL) The SkyMeter is installed in the water supply and offer the following capabilities: Latest technology Highly accurate metering R160 Feature

More information

Cyan Technology Ltd. Delivering Smart Metering Benefits to the Indian Utilities. Dr. Sean Cochrane Strategic Marketing Manager, Cyan Technology

Cyan Technology Ltd. Delivering Smart Metering Benefits to the Indian Utilities. Dr. Sean Cochrane Strategic Marketing Manager, Cyan Technology Cyan Technology Ltd Delivering Smart Metering Benefits to the Indian Utilities Dr. Sean Cochrane Strategic Marketing Manager, Cyan Technology 4th Annual Smart Grids & Cleanpower 2012 Conference 14 June

More information

Accessories / 7XV5820

Accessories / 7XV5820 Accessories / XV0 XV0 industrial modem and modem-router with switch LSP.tif LSP.tif LSP.tif Modem k / ISDN TA Modem /ISDN Router Pocket Modem / ISDN Fig. / Industrial modems Depending on the available

More information

TYPES OF COMPUTER NETWORKS

TYPES OF COMPUTER NETWORKS TYPES OF COMPUTER NETWORKS What is a Network? A network consists of two or more computers that are linked in order to share resources (such as printers and CDs), exchange files, or allow electronic communications.

More information

INFRASTRUCTURE SHARING- An Indian Experience

INFRASTRUCTURE SHARING- An Indian Experience INFRASTRUCTURE SHARING- An Indian Experience Telecom Regulatory Authority of India New Delhi 20.05.2008 TRAI 1 Background TELECOM GROWTH IN INDIA 1991- Teledensity less than 1% 1991- Telecom sector opened

More information

multi-utility metering a total systems approach

multi-utility metering a total systems approach intelligent. multi-utility metering a total systems approach cost effective solutions for: sub-metering to help you understand energy and utility consumption and assist with sustainability and compliance

More information

Computers: Tools for an Information Age. Chapter 7 Networking: Computer Connections

Computers: Tools for an Information Age. Chapter 7 Networking: Computer Connections Computers: Tools for an Information Age Chapter 7 Networking: Computer Connections Objectives Describe the basic components of a network Explain the methods of data transmission, including types of signals,

More information

Small Generator Interconnection System Impact Study Report. Completed For Q0047

Small Generator Interconnection System Impact Study Report. Completed For Q0047 Small Generator Interconnection Completed For Q0047 Proposed Interconnection PacifiCorp s Existing Goshen Rigby 69 kv Line March 7, 2005 1.0 Description of the Generation Facility Q0047 ( Interconnection

More information

Meter Bus. Intelligent Communication

Meter Bus. Intelligent Communication Meter Bus Intelligent Communication Data Transmission System The M-Bus system (Meter Bus) is a data transmission system for acquiring, evaluating, optimizing and controlling energy and process data (e.g.

More information

The GCC Interconnection Grid

The GCC Interconnection Grid GCC Interconnection Authority The GCC Interconnection Grid ME Power & Water Conference Abu Dhabi, UAE Nabeel H. Al-Maskati, PhD Hassan K. Al-Asaad, Asaad, MBA March 2007 Background Gulf Cooperation Council

More information

TELECOM & ENERGY «Collaborating to Power the Smart Grids for Digital Growth«

TELECOM & ENERGY «Collaborating to Power the Smart Grids for Digital Growth« REPUBLIC OF ALBANIA ELECTRONIC AND POSTAL COMMUNICATIONS AUTHORITY - AKEP TELECOM & ENERGY «Collaborating to Power the Smart Grids for Digital Growth« SUMMARY What is Smart Grid Communications Networks

More information

DATASHEET ULTRASONIC COMPACT ENERGY METER MODEL 773

DATASHEET ULTRASONIC COMPACT ENERGY METER MODEL 773 APPLICATION Static compact energy meter using ultrasonic technology Highly accurate recording of all billing data in local and district heating and cooling systems FEATURES 1st. approval in Europe for

More information

Documentation. M-Bus 130-mbx

Documentation. M-Bus 130-mbx Documentation M-Bus 130-mbx Introduction The Istec M-Bus module is part of the Smart Slot communications family. With the integrated SmartSlot technology, Istec offers automatic consumer data read-out

More information

Communications is integral to modern electrical power system management

Communications is integral to modern electrical power system management Communications offers solutions for all communications requirements in the transmission and distribution networks of power utilities and industries. Communications Communications is integral to modern

More information

Wireless Solutions. 5.1 Wireless LAN & Wireless Modem. Wireless Modems. Intelligent GPRS/GSM Modules. Mini-Programmable Automation Controllers

Wireless Solutions. 5.1 Wireless LAN & Wireless Modem. Wireless Modems. Intelligent GPRS/GSM Modules. Mini-Programmable Automation Controllers Wireless Solutions. Wireless LAN & Wireless Modem P-- Wireless LAN Wireless Modems P--3 P--.2 GPRS/GSM Wireless Products P-2- Modems Intelligent GPRS/GSM Modules Mini-Programmable Automation Controllers

More information

Southern Avionics Company

Southern Avionics Company Southern Avionics Company Ethernet Connection Options - NAVTEX SPECIFICATION SHEET 5055 Belmont, Beaumont, TX 77707 Phone +409.842.1717/1.800.648.6158 (Toll Free in the US) Fax +409.842.2987 sales@southernavionics.com

More information

An update of the AMR project at Tshwane

An update of the AMR project at Tshwane An update of the AMR project at Tshwane Vincent Baloyi Chief Engineer : Metering, City of Tshwane, Gauteng, South Africa City of Tshwane We are the same July 2008 Automated Metering Infrastructure (AMI)

More information

Features. ! Single vector/bi vector/tri vector measurement! Time of day metering with maximum demand registration

Features. ! Single vector/bi vector/tri vector measurement! Time of day metering with maximum demand registration Sprint 350 Direct connected three-phase energy meter Sprint 350 is an enhanced metering solution for three-phase direct-connected installations. It is suitable for domestic, industrial and commercial applications.

More information

Introduction to Computer Networks INTRODUCTION TO COMPUTER NETWORKS

Introduction to Computer Networks INTRODUCTION TO COMPUTER NETWORKS INTRODUCTION TO COMPUTER NETWORKS Computer Networks Computer network connects two or more autonomous computers. The computers can be geographically located anywhere. LAN, MAN & WAN Network in small geographical

More information

INTELLIGENT ENERGY MANAGEMENT SYSTEM Shivani Sharma, Dr. Priyanka Sharma

INTELLIGENT ENERGY MANAGEMENT SYSTEM Shivani Sharma, Dr. Priyanka Sharma INTELLIGENT ENERGY MANAGEMENT SYSTEM Shivani Sharma, Dr. Priyanka Sharma Review Article Address for Correspondence Design Engineer (Electrical Dept), Reliance Engg Associated (P) Ltd., Jamnagar, Gujarat

More information

Utility Communications North- and South Asia

Utility Communications North- and South Asia Utility s North- and South Asia 1. März 2010 Slide 51 Utility s, Australia Customer: Western Power, Perth (Australia) of voice, SCADA and protection signals through-out the 220kV transmission line on the

More information

Developing an Operational Automated Real Time Tunnel Monitoring System

Developing an Operational Automated Real Time Tunnel Monitoring System Developing an Operational Automated Real Time Tunnel Monitoring System G. H. Tan SysEng (S) Pte Ltd K. G. Chua Wisescan Engineering Services Pte Ltd ABSTRACT: In cities with tunnel networks and adjacent

More information

Hot pluggable communication modules

Hot pluggable communication modules precision metering series in-built IEC 61850 support Best in class accuracy User friendly multilingual display Field con gurable for various installations Hot pluggable communication modules Prometer 100,

More information

CASE STUDY. Wind Farm in Mexico Completes First Successful IEC Application With Multivendor Interoperability

CASE STUDY. Wind Farm in Mexico Completes First Successful IEC Application With Multivendor Interoperability CASE STUDY La Venta II Wind Farm Oaxaca, Mexico Wind Farm in Mexico Completes First Successful IEC 61850 Application With Multivendor Interoperability Comisión Federal de Electricidad (CFE) is Mexico s

More information

TITLE SHEET FURNISHED BY ACCESS FIBER GROUP, INC.

TITLE SHEET FURNISHED BY ACCESS FIBER GROUP, INC. Cover TITLE SHEET RULES, REGULATIONS, AND SCHEDULE OF RATES AND CHARGES APPLICABLE TO LOCAL EXCHANGE SERVICE WITHIN THE STATE OF MISSOURI MISSOURI PUBLIC SERVICE COMMISSION TELECOMMUNICATIONS TARIFF FURNISHED

More information

Navpreet Singh INTRODUCTION TO COMPUTER NETWORKS. Computer Centre Indian Institute of Technology Kanpur Kanpur INDIA

Navpreet Singh INTRODUCTION TO COMPUTER NETWORKS. Computer Centre Indian Institute of Technology Kanpur Kanpur INDIA INTRODUCTION TO COMPUTER NETWORKS Navpreet Singh Computer Centre Indian Institute of Technology Kanpur Kanpur INDIA (Ph : 2597371, Email : navi@iitk.ac.in) About Myself About Myself I am Network Manager

More information

Tata Power Company Ltd. TATA POWER

Tata Power Company Ltd. TATA POWER Tata Power Company Ltd. IT Policy- E-mail, Internet Browsing, and VPN Access TATA POWER Information Technology Division March 2004 1 Creation Date March 2003 First Revision Due on March 2004 Second Revision

More information

CASE STUDY: NHAI DEPLOYS AN IT HIGHWAY AN IT HIGHWAY FOR INDIAN ROADS

CASE STUDY: NHAI DEPLOYS AN IT HIGHWAY AN IT HIGHWAY FOR INDIAN ROADS Business Solutions CASE STUDY: NHAI DEPLOYS AN IT HIGHWAY AN IT HIGHWAY FOR INDIAN ROADS In the age of convergence, the obvious choice is to drive voice, video, and data through a single network. We knew

More information

Why Wireless? Training materials for wireless trainers

Why Wireless? Training materials for wireless trainers Why Wireless? Training materials for wireless trainers Goals Understand why we use wireless, and how it fits into your existing network Realize the limits of what wireless can achieve See some examples

More information

EMPOWERING YOUR DIGITAL OILFIELD

EMPOWERING YOUR DIGITAL OILFIELD EMPOWERING YOUR DIGITAL OILFIELD FOR CUSTOMER CARE QUERIES, PLEASE WRITE TO THE CUSTOMER CARE CENTER: CUSTOMER.CARE@THURAYA.COM DIAL 100 FROM A THURAYA PHONE, OR +88216 100 100 FROM OTHER NETWORKS. YOU

More information

Networks. Computer Technology

Networks. Computer Technology Networks Computer Technology Network Two or more computers and other devices (printers or scanners) that are connected, for the purpose of sharing data and programs Advantages of Networks Communication

More information

Access Solution. Radio Wire less Fiber Optic Virtual Private Network (VPN)

Access Solution. Radio Wire less Fiber Optic Virtual Private Network (VPN) Multi Operator In-Building Solution (MOiBS) 2008 Jakarta, June 21, 2009 Ability Access Solution Internet Radio Wire less Fiber Optic Virtual Private Network (VPN) IT/IS Planning (IT System Blue Print /

More information

Revolutionary metering management in Romania

Revolutionary metering management in Romania Landis+Gyr@work Revolutionary metering management in Romania In 2002 Landis+Gyr was awarded a contract by the European Bank of Reconstruction and Development (EBRD). The EBRD was financing a metering system

More information

Small Generator Interconnection Tier 4 Facilities Study Report. Completed for. ( Interconnection Customer ) A Qualifying Facility Q0662

Small Generator Interconnection Tier 4 Facilities Study Report. Completed for. ( Interconnection Customer ) A Qualifying Facility Q0662 Small Generator Interconnection Tier 4 Facilities Study Report Completed for ( Interconnection Customer ) A Qualifying Facility Q0662 Proposed Interconnection Klamath Falls-Fishhole 69 kv line at approximately

More information

MRI,BCS and Meter Information Integration by Vivek Pathak

MRI,BCS and Meter Information Integration by Vivek Pathak MRI,BCS and Meter Information Integration by Vivek Pathak A specifically designed programme for Da Afghanistan Breshna Sherkat (DABS) Afghanistan 1 Technologies have evolved over a period of time and so

More information

A network is two or more computers, or other electronic devices, connected together so that they can exchange data.

A network is two or more computers, or other electronic devices, connected together so that they can exchange data. Computer Networks What is a Network? A network is two or more computers, or other electronic devices, connected together so that they can exchange data. For example; a network allows computers to share

More information

November 29, ECE 421 Session 28. Utility SCADA and Automation. Presented by: Chris Dyer

November 29, ECE 421 Session 28. Utility SCADA and Automation. Presented by: Chris Dyer ECE 421 Session 28 November 29, 2018 Utility SCADA and Automation Presented by: Chris Dyer Utility SCADA & Automation Chris Dyer, P.E. BSEE University of Idaho, 1997 SCADA & Automation Engineer POWER Engineers,

More information

Communication with EuroProt-IED Multifunctional intelligent devices

Communication with EuroProt-IED Multifunctional intelligent devices Communication with EuroProt-IED Multifunctional intelligent devices The intelligent multifunctional EuroProt devices made by Protecta - parallel to the development in the power system protection and the

More information

THE INTERCONNECTED NETWORK

THE INTERCONNECTED NETWORK THE INTERCONNECTED NETWORK The Interconnected Network The number of applications / Services on a network increases from year to year. New applications are permanently in preparation. Server and Server

More information

Brief Summary of the Chapter: CHAPTER 1 NETWORKING AND OPEN STANDARDS In this chapter we are going to study about computer Networks, associated terminology and related concept along with network devices.

More information

Technical Spotlight DEMO6-S6

Technical Spotlight DEMO6-S6 Technical Spotlight DEMO6-S6 Spotlight on BPL communication implemented in DEMO6 This project has received funding from the European Union s Seventh Framework Programme for research, technological development

More information

Substation to substation (ss2ss) GOOSE exchange for critical relay operations

Substation to substation (ss2ss) GOOSE exchange for critical relay operations CIGRÉ Canada 21, rue d Artois, F-75008 PARIS (CIGRE-130) Conference on Power Systems http : //www.cigre.org Vancouver, October 17-19, 2010 Substation to substation (ss2ss) GOOSE exchange for critical relay

More information

How smart can the grid really be?

How smart can the grid really be? How smart can the grid really be? by Dale Pudney, HVT Power Systems and Luo Wei, NR Electric With the improvement of electronic communications and computing technology, it becomes possible to integrate

More information

The Challenge of Legacy Assets

The Challenge of Legacy Assets The Impact of the Internet of Things on our Lives. The Challenge of Legacy Assets Richard Lucas, BSc(Eng) MBA MD of ASH Wireless ASH Wireless is an electronics design consultancy Specialising in wireless

More information

October 05, ECE 421 Session 12. Utility SCADA and Automation. Presented by: Chris Dyer

October 05, ECE 421 Session 12. Utility SCADA and Automation. Presented by: Chris Dyer ECE 421 Session 12 October 05, 2017 Utility SCADA and Automation Presented by: Chris Dyer Utility SCADA & Automation Chris Dyer, P.E. BSEE University of Idaho, 1997 SCADA & Automation Engineer POWER Engineers,

More information

Network Development in Mumbai City Area The Tata Power Company Ltd. (Distribution Business)

Network Development in Mumbai City Area The Tata Power Company Ltd. (Distribution Business) Network Development in Mumbai City Area The Tata Power Company Ltd. (Distribution Business) TABLE OF CONTENTS 1 INTRODUCTION... 5 1.1 Background... 5 1.2 EXISTING NETWORK OF TATA POWER IN MUMBAI CITY AREA...

More information

M-Bus Central Unit. Use

M-Bus Central Unit. Use 6 M-Bus Central Unit OZW The M-bus central unit is used for the remote readout, remote operation and supervision of an M-bus plant with a maximum of consumption meters and controllers featuring an M-bus

More information

RMS AUTOMATION SYSTEMS LTD.

RMS AUTOMATION SYSTEMS LTD. RMS AUTOMATION SYSTEMS LTD. SMART PRODUCTS DEVELOPMENT THROUGH SMARTER TECHNOLOGY Page No.1 Load monitoring & APFC monitoring with GSM communication. GSM-SMS-Server. Master Station With Modem & Antennae.

More information

Small Generator Interconnection Facilities Study Report. Completed for. ( Interconnection Customer ) Proposed Interconnection Pavant substation

Small Generator Interconnection Facilities Study Report. Completed for. ( Interconnection Customer ) Proposed Interconnection Pavant substation Small Generator Interconnection Facilities Study Report Completed for ( Interconnection Customer ) Proposed Interconnection Pavant substation Original report dated February 17, 2016 Revised March 11, 2016

More information

Sichuan Telecom. All-seeing with all-optical. Winners

Sichuan Telecom. All-seeing with all-optical. Winners Sichuan Telecom All-seeing with all-optical Sichuan Telecom s all-optical network has slashed OPEX, lowered broadband prices, and solved the problem of running multiple parallel networks. The China Telecom

More information

Maxwell Dondo PhD PEng SMIEEE

Maxwell Dondo PhD PEng SMIEEE Maxwell Dondo PhD PEng SMIEEE 1 Evolution of grid automation SCADA introduction SCADA Components Smart Grid SCADA Security 2 Traditionally power delivery was unsophisticated Generation localised around

More information

HARDWARE OF SUPERVISORY CONTROL & DATA ACQUISITION SYSTEM

HARDWARE OF SUPERVISORY CONTROL & DATA ACQUISITION SYSTEM Chapter 3 HARDWARE OF SUPERVISORY CONTROL & DATA ACQUISITION SYSTEM Dr. H.K. VERMA Distinguished Professor Department of Electrical and Electronics Engineering School of Engineering and Technology SHARDA

More information

ITP 140 Mobile Applications Technologies. Networks

ITP 140 Mobile Applications Technologies. Networks ITP 140 Mobile Applications Technologies Networks A First Look Under the Hood 2 3 Communication Channels Mediums for transporting data from one system to another Physical Twisted Pair (CAT-3, CAT-5/6)

More information

Chapter 2 Research of Optical Fiber Communication in Relay Protection

Chapter 2 Research of Optical Fiber Communication in Relay Protection Chapter 2 Research of Optical Fiber Communication in Relay Protection Zhan Guo and Zu-ming Xiao Abstract With the development of large grid, distributed, heterogeneous complex power network, the power

More information

BSES Smart Grid Road Map

BSES Smart Grid Road Map BSES Smart Grid Road Map Rajesh Bansal, Head (Network Operations), BSES Delhi BSES Delhi Discoms A Synopsis NDPL BRPL BYPL Reliance Infrastructure Ltd. acquired 51% stake in July 2002 in two Discoms MES

More information

ANSI/TIA/EIA-568-B Cabling Standard

ANSI/TIA/EIA-568-B Cabling Standard 83 Pair Numbers and Color Coding The conductors in a UTP cable are twisted in pairs and color coded so that each pair of wires can be easily identified and quickly terminated to the appropriate pin on

More information

AUTOMATION OF POWER DISTRIBUTION USING SCADA

AUTOMATION OF POWER DISTRIBUTION USING SCADA 1 2 ABSTRACT In every substation certain measurements, supervision, control, operation and protection functions are necessary. Traditionally these functions were performed manually by system operator from

More information

Small Generator Interconnection Facilities Study Report. Completed for Q0314 ( Interconnection Customer ) A Qualified Facility

Small Generator Interconnection Facilities Study Report. Completed for Q0314 ( Interconnection Customer ) A Qualified Facility Small Generator Interconnection Completed for Q0314 ( Interconnection Customer ) A Qualified Facility Proposed Interconnection PacifiCorp s 34.5-kV West Cedar Substation December 29, 2010 TABLE OF CONTENTS

More information

IEEE 1588v2 Time Synchronization in Energy Automation Applications Case Studies from China

IEEE 1588v2 Time Synchronization in Energy Automation Applications Case Studies from China IEEE 1588v2 Time Synchronization in Energy Automation Applications Case Studies from China Real Time Communications Symposium Munich, January 2012 Maciej Goraj maciejgoraj@ruggedcom.com 1 Who is RuggedCom?

More information

ET4254 Communications and Networking 1

ET4254 Communications and Networking 1 Topic 10:- Local Area Network Overview Aims:- LAN topologies and media LAN protocol architecture bridges, hubs, layer 2 & 3 switches 1 LAN Applications (1) personal computer LANs low cost limited data

More information

COMPUTER SKILLS COMP101

COMPUTER SKILLS COMP101 COMPUTER SKILLS COMP101 Chapter 4 Introduction to Computer Networks Definitions and Terminologies Computer Network A network consists of two or more computers that are linked in order to share resources

More information

Mohamed Al-Shaikh, BSc MSc CEng MIET Manager, Maintenance - GCCIA

Mohamed Al-Shaikh, BSc MSc CEng MIET Manager, Maintenance - GCCIA Mohamed Al-Shaikh, BSc MSc CEng MIET Manager, Maintenance - GCCIA OVERVIEW INTRODUCTION PROJECT DESCRIPTION PROJECT STATUS LEGAL AND ORGANIZATIONAL DEVELOPMENT PROSPECTS CONCLUSIONS Power Demand in GCC

More information

Data Center Integrated solutions

Data Center Integrated solutions Data Center Integrated solutions PERFORMANCE AND RELIABILITY AT THE HEART OF DATA CENTERS 01 The growing number of business and technical demands placed on data centers today are becoming increasingly

More information

Mark Scheme (Results) January 2008

Mark Scheme (Results) January 2008 Mark Scheme (Results) January 2008 GCE GCE Applied Information & Communication Technology (6959/01) Edexcel Limited. Registered in England and Wales No. 4496750 Registered Office: One90 High Holborn, London

More information

Data Center Integrated solutions

Data Center Integrated solutions Data Center Integrated solutions PERFORMANCE AND RELIABILITY AT THE HEART OF DATA CENTERS The growing number of business and technical demands placed on data centers today are becoming increasingly critical:

More information

IT Facts in Bangladesh

IT Facts in Bangladesh Telecommunication Needs for the Internet Infrastructure in Bangladesh Presentation at the Workshop on Nationwide Internet Access & Online Applications Dhaka, Bangladesh 23 May 2004 Professor Saifur Rahman,

More information

Shabnam Rukhsar Electrical Engineering Department, Anjuman College of Engineering and Technology.India

Shabnam Rukhsar Electrical Engineering Department, Anjuman College of Engineering and Technology.India SCADA in Transmission Line Shabnam Rukhsar Electrical Engineering Department, Anjuman College of Engineering and Technology.India ABSTRACT: Transmission line equivalent circuit parameters are often 25%

More information

Modernization of the National Wide Dispatch Centers of CADAFE - Venezuela

Modernization of the National Wide Dispatch Centers of CADAFE - Venezuela 1 Modernization of the National Wide Dispatch Centers of CADAFE - Venezuela R. Pirela, R. Pargas, and R. Céspedes, Senior Member, IEEE Abstract-- The Compañía Anónima de Administración y Fomento Eléctrico

More information

Due Diligence Services for Global Investment Agency to Assess the Business Case of Offshore Wind Plant Installations in India

Due Diligence Services for Global Investment Agency to Assess the Business Case of Offshore Wind Plant Installations in India Due Diligence Services for Global Investment Agency to Assess the Business Case of Offshore Wind Plant s in India join the Future now Copyright 2016 ENINCON LLP, All rights reserved Opportunity Assessment

More information

The current state of the electrical grid And the technologies that will enable its transformation

The current state of the electrical grid And the technologies that will enable its transformation ABB POWER GRIDS The current state of the electrical grid And the technologies that will enable its transformation IEEE POWER & ENERGY SOCIETY - SUBSTATIONS COMMITTEE May 7-11 th Agenda State of the Industry

More information

LRS-12. "Last Mile" SNMP Modem Rack FEATURES

LRS-12. Last Mile SNMP Modem Rack FEATURES "Last Mile" SNMP Modem Rack FEATURES Accommodates any combination of 12 HDSL, copper or fiber optic modem cards SNMP management agent Supports modems with or without integrated SNMP agent Management running

More information

1 Introduction to the software

1 Introduction to the software 1 Introduction to the software mk:@msitstore:d:\winpower%20net\helpeng.chm::/introduction%20to%20softw... 1/2 1 Introduction to the software The monitoring software is matched with our company controller.

More information

Chapter 3. Wired and Wireless Communication. What You Will Learn... Computers Are Your Future. What You Will Learn...

Chapter 3. Wired and Wireless Communication. What You Will Learn... Computers Are Your Future. What You Will Learn... What You Will Learn... Computers Are Your Future Chapter 3 The definition of bandwidth The bandwidth needs of a typical user How modems change digital signals into analog Transmission media and methods

More information

The data transmission mode describes the direction of data flow. It is either simplex, half duplex or full duplex.

The data transmission mode describes the direction of data flow. It is either simplex, half duplex or full duplex. Data transmission Data transmission on a network involves serial transmission. It transfers data by sending one bit at a time through a single line. All data on a network is transferred using a data transmission

More information

Data Communication. Introduction of Communication. Data Communication. Elements of Data Communication (Communication Model)

Data Communication. Introduction of Communication. Data Communication. Elements of Data Communication (Communication Model) Data Communication Introduction of Communication The need to communicate is part of man s inherent being. Since the beginning of time the human race has communicated using different techniques and methods.

More information

Application RTU560 RJ45 RJ45. Management. Switch RJ45 RJ45. Switch 560NMS34 SDSL. Data Sheet Switch 560NMS34. Port 1. Port 2. Port 3.

Application RTU560 RJ45 RJ45. Management. Switch RJ45 RJ45. Switch 560NMS34 SDSL. Data Sheet Switch 560NMS34. Port 1. Port 2. Port 3. Switch 560NMS34 Application The RTU component 560NMS34 is a managed plug and play Layer2-switch providing four Fast auto-negotiating RJ45-ports with auto MDI/X (Automatic Crossover Detection and Correction)

More information

Discovering Computers Chapter 9 Communications and Networks

Discovering Computers Chapter 9 Communications and Networks Discovering Computers 2009 Chapter 9 Communications and Networks Chapter 9 Objectives Discuss the components required for successful communications Identify various sending and receiving devices Describe

More information