Rack Centric - High Voltage Distribution

Size: px
Start display at page:

Download "Rack Centric - High Voltage Distribution"

Transcription

1 Rack Centric - High Voltage Distribution Randy Malik Senior Technical Staff Member Research Triangle Park Raleigh, North Carolina Rmalik@us.ibm.com Data Center Application

2 Typical Data Center Energy End Use Chiller 100 Units CRAC 35 Units PDU UPS 33 Units Delivered IT Racks 2 10/18/2007

3 Some Facts about a Typical Data Center Consumption: 10 to 100 times more energy per square foot than a typical office building Electricity Used: 45 billion kwh in 2005 about 1.2% of all retail U.S. Electricity Consumption Power Demand : Expected to double in 10 years Average Utilization : 20 25% of the capacity Overall Efficiency = IT Power / Power Input = 30% Carbon Footprint: Coal Fired Plants = 2 Lbs/KWh Natural Gas = 1 Lb/KWh Diesel = 2.19 Lbs/KWh Source: Emerson Corporation 3 10/18/2007

4 Energy Consumption by Office and Telecom Equipment in Commercial Buildings Servers Routers Storage WAN Switches 2.3 LAN Switches 1.6 HUBs Electricity Use TWh/year Source: Roth K. Goldstein, F. Kleinman J(2002) Energy Consumption by Office and Telecommunication Equipment in Commercial Buildings 4 10/18/2007

5 Data Center Efficiency considering NCPI Losses Data Center Power Path to IT UPS PDU Cabling Switches Power to IT Power to Data Center Cooling IT Equipment Useful Output Power To Lights Secondary Support Generator Switchgear NCPI Data Center Efficiency = Power to IT Data Center Power IN 5 10/18/2007

6 Power Consumption in a Data Center PDU, 3% IT, 25% UPS, 9% Lighting, 1% Wiring, 1% CRAC, 9% Humidifier, 1% Power Supplies, 23% Chiller, 28% UPS PDU Lighting Wiring CRAC Humidifier Chiller Power Supplies IT 6 10/18/2007

7 Power Pathway to Data Center Efficiency Create a strategy for enhancing Tech utilization 1.Server consolidation and virtualization 2.Grid Computing 3.High Efficiency Processors 4.High Efficiency Server Power Supplies Size the Power System for Optimum Efficiency 1. Modular Approach Consider alternate distribution methods V AC to 208V AC to the racks V AC direct to the racks V AC to 240V AC to the racks V AC to 380VDC within the racks 7 10/18/2007

8 Efficiency of A typical Data Center Efficiency % 10% 20% 30% 40% 50% 60% 70% 80% 90% 100% Fraction of the Power Capacity Used Efficiency 8 10/18/2007

9 Efficiency of UPS & Power System as a function of Load Efficiency % 10% 20% 30% 40% 50% 60% 70% 80% 90% 100% % Load of Full Power Rating UPS Power System UPS Source : Eaton Corporation 9 10/18/2007

10 Power Consumption by a Processor during Active and Idle Mode 150 Modified Power Consumption Power Consumption Watts Processor Activity Note: Lower Activity by the processor does not mean lower power consumption 10 10/18/2007

11 A typical Work Load for a Data Center for a 24 hour period Time of Day Work load % Traffic Source: 2006/2007 Discussions with several NYC Financial Services firms 11 10/18/2007

12 Electrical Energy Cost of Powering a Data Center Annual Electrical Cost of a 1 MW data center ( $0.10/kWh) Annual Electrical Cost (M$) NCPI Load IT Load 0% 10% 20% 30% 40% 50% 60% 70% 80% 90% 100% Fraction of Power Capacity Used Annual IT Electrical Cost Annual NCPI Electrical Cost Source: APC 12 10/18/2007

13 Drivers for Rack Centric - High Voltage Distribution Efficiency No UPS Cost High Voltage Drivers No PDU Cooling Modularity 13 10/18/2007

14 Power Path for IT Racks in a Typical Data Center 9% 3% IT Racks PDU 208 /120V UPS 480V AC IT PDU 208 /120V 14 10/18/2007

15 Typical Power Distribution for Blade Server Racks Server Blade Chassis System Rack +12V-A AC - DC PSU 3 PSU 1 PSU 3 PSU1 +12V-B +12V-A +12V-B PSU 4 PSU 2 PSU 4 PSU 2 AC Distribution Box PDU - 1 PDU V AC 208V AC 15 10/18/2007

16 High Voltage DC Distribution in a Data Center Rectifier 480V AC Rectifier 380V DC Rectifier Battery Plant Rectifier IT Racks Source: Lawrence Berkley National Laboratory 16 10/18/2007

17 High Voltage DC Distribution in the Rack 3 Phase 480V AC 480 AC 208/120 AC UPS = 9% PDU = 3% 1% IT Rack 1% 380V 12V Plug in Module Server Blade Chassis 3 Phase 480V AC 3 Phase 480V AC AC DC Rectifier AC DC 380V DC Server Blade Chassis Server Blade Chassis Data Flow Rectifier Server Blade Chassis IT Rack Arrangement 17 10/18/2007

18 Three Phase Single Stage Series Resonant Cyclo Converter Source: Tomasz Kotula Eaton Development Centre 18 10/18/2007

19 380V - 12V Regulator Source: Vicor Corporation, Andover, USA Power Density = 1000W/in 3 EMC Filter + Boost + Bulk Cap Chopper up HDD Plug in Module 380V 12V VRD up Memory 380V 12V DC = 100W/in 3 Source: Astec/Artesyn Server Blade 19 10/18/2007

20 Rack Centric High Voltage Distribution Bus Proposal System Rack Server Blade Chassis Server Blade Chassis 380V DC Bus A AC DC Rectifiers Server Blade Chassis Blade Server 380V DC Bus B Battery Back Up 3 Phase 480V AC1 AC DC Rectifiers AC DC Rectifiers 3 Phase 480V AC /18/2007

21 Lower Overall Cost Higher Overall Efficiency IT, 25% UPS, 9% PDU, 3% Lighting, 1% Wiring, 1% Lighting, Wiring, 1% CRAC, 9% Humidifier, 1% CRAC, 9% IT, 38% Humidifier, 1% Chiller, 28% Power Supplies, 23% Chiller, 28% Power Supplies, 23% UPS PDU Lighting Wiring CRAC Humidifier Chiller Power Supplies IT Lighting Wiring CRAC Humidifier Chiller Power Supplies IT 21 10/18/2007

Pros and Cons of Various DC Distribution Architectures

Pros and Cons of Various DC Distribution Architectures Pros and Cons of Various DC Distribution Architectures Source: Solar Powered Datacenter by Google Randy Malik Power Technology And Qualification IBM RTP Raleigh NC Rick Fishbune Power Technology And Qualification

More information

7 Best Practices for Increasing Efficiency, Availability and Capacity. XXXX XXXXXXXX Liebert North America

7 Best Practices for Increasing Efficiency, Availability and Capacity. XXXX XXXXXXXX Liebert North America 7 Best Practices for Increasing Efficiency, Availability and Capacity XXXX XXXXXXXX Liebert North America Emerson Network Power: The global leader in enabling Business-Critical Continuity Automatic Transfer

More information

Green Data Centers A Guideline

Green Data Centers A Guideline Green Data Centers A Guideline Sekhar Kondepudi Ph.D Associate Professor Smart Buildings & Smart Cities Vice Chair Focus Group on Smart Sustainable Cities ITU-TRCSL Workshop on Greening the Future: Bridging

More information

Data Centre Energy & Cost Efficiency Simulation Software. Zahl Limbuwala

Data Centre Energy & Cost Efficiency Simulation Software. Zahl Limbuwala Data Centre Energy & Cost Efficiency Simulation Software Zahl Limbuwala BCS Data Centre Simulator Overview of Tools Structure of the BCS Simulator Input Data Sample Output Development Path Overview of

More information

Why Not Operate Data Centers & Telecom Central Offices at 400 VDC???

Why Not Operate Data Centers & Telecom Central Offices at 400 VDC??? Why Not Operate Data Centers & Telecom Central Offices at 400 VDC??? Dennis P. Symanski Senior Project Manager 2009 IBM Power and Cooling Technology Symposium 20-21OCT2009 Rochester, MN Data Center Energy

More information

Power Consumption in the Data Center. Green Concepts

Power Consumption in the Data Center. Green Concepts Power Consumption in the Data Center Green Concepts What is your Energy Saving Strategy? Buying Energy Efficient Equipment (EEE) 46% Say Yes to Green Technology Information Week Research Green Data Center

More information

Energy efficiency within data centers Is your IT organization capitalizing on the latest technology options and best practices?

Energy efficiency within data centers Is your IT organization capitalizing on the latest technology options and best practices? This is a photographic template your photograph should fit precisely within this rectangle. Energy efficiency within data centers Is your IT organization capitalizing on the latest technology options and

More information

Compute Engineering Workshop March 9, 2015 San Jose

Compute Engineering Workshop March 9, 2015 San Jose Compute Engineering Workshop March 9, 2015 San Jose Compute Engineering Workshop Microsoft OCS Distributed Local Battery Energy Power System Shaun L. Harris Director of Hardware Engineering Windows Cloud

More information

Highly Efficient Power Protection for High Density Computing Applications

Highly Efficient Power Protection for High Density Computing Applications Highly Efficient Power Protection for High Density Computing Applications IB Power and Cooling Symposium Lennart Jonsson Eaton Corporation 2007 Eaton Corporation. All rights reserved. Impact of High Density

More information

Increasing Data Center Efficiency by Using Improved High Density Power Distribution

Increasing Data Center Efficiency by Using Improved High Density Power Distribution Increasing Data Center Efficiency by Using Improved High Density Power Distribution By Neil Rasmussen White Paper #128 Revision 1 Executive Summary A new approach to power distribution for high density

More information

MSYS 4480 AC Systems Winter 2015

MSYS 4480 AC Systems Winter 2015 MSYS 4480 AC Systems Winter 2015 Module 12: DATA CENTERS By Satwinder Singh 14/05/2015 1 Data Centers Data Centers are specialized environments that safeguard your company's most valuable equipment and

More information

380VDC Data Center Duke Energy Charlotte, NC

380VDC Data Center Duke Energy Charlotte, NC 380VDC Data Center Duke Energy Charlotte, NC Dennis P. Symanski EPRI - Senior Project Manager Silicon Valley Leadership Group 2011 Data Center Efficiency Summit 18NOV2011 IBM - San Jose, CA 380VDC Data

More information

Cooling on Demand - scalable and smart cooling solutions. Marcus Edwards B.Sc.

Cooling on Demand - scalable and smart cooling solutions. Marcus Edwards B.Sc. Cooling on Demand - scalable and smart cooling solutions Marcus Edwards B.Sc. Schroff UK Limited Data Centre cooling what a waste of money! A 1MW data center needs 177,000,000 kwh in its lifetime of 10

More information

A Computer Scientist Looks at the Energy Problem

A Computer Scientist Looks at the Energy Problem A Computer Scientist Looks at the Energy Problem Randy H. Katz University of California, Berkeley EECS BEARS Symposium February 12, 2009 Energy permits things to exist; information, to behave purposefully.

More information

ENERGY STAR for Data Center Products: UPS plus Servers, Storage, and more April 24, 2012

ENERGY STAR for Data Center Products: UPS plus Servers, Storage, and more April 24, 2012 ENERGY STAR for Data Center Products: UPS plus Servers, Storage, and more April 24, 2012 Robert (RJ) Meyers Data Center Products Lead ENERGY STAR Program US Environmental Protection Agency 1 Overview Main

More information

Data Center Assessment Helps Keep Critical Equipment Operational. A White Paper from the Experts in Business-Critical Continuity TM

Data Center Assessment Helps Keep Critical Equipment Operational. A White Paper from the Experts in Business-Critical Continuity TM Data Center Assessment Helps Keep Critical Equipment Operational A White Paper from the Experts in Business-Critical Continuity TM Executive Summary The IT infrastructure within many companies has evolved

More information

High Voltage Direct Current Power Solutions for Data Centers

High Voltage Direct Current Power Solutions for Data Centers High Voltage Direct Current Power Solutions for Data Centers Professor: Dr. Danny Silver Acadia University Student Name: Jim Nasium Published: April 10 th, 2011 1. Introduction As the demand on data centers

More information

Cisco CRS 16-Slot Chassis Power Systems

Cisco CRS 16-Slot Chassis Power Systems This chapter includes the following sections: Power specifications are provided in Technical Specifications Power Systems Overview, on page 1 Power Component Information Common to the Two Types of Power

More information

Making the impossible data center a reality.

Making the impossible data center a reality. United Nations ITU WSIS 2016 WINNER E-Environment Malaysia s First Win 2015 ASIA PACIFIC WINNER 2015 Best of Sustainability and Environmental Technology WINNER 2015 Best of Sustainability and Environmental

More information

Green IT and Green DC

Green IT and Green DC Green IT and Green DC Alex SL Tay Regional Service Product Line Manager Site & Facilities Services, IBM ASEAN 1 What our clients are telling us We are running out of space in our data center We have environmental

More information

Liebert NX Series. 30kVA to 200kVA. AC Power for Business-Critical Continuity TM

Liebert NX Series. 30kVA to 200kVA. AC Power for Business-Critical Continuity TM Liebert NX Series 30kVA to 200kVA AC Power for Business-Critical Continuity TM Anticipating Technology Changes Through Adaptive Architecture Today, you need a power infrastructure that can work across

More information

Environmental & Efficiency Trends in Enterprise Computing. John Sheehy Systems Architect

Environmental & Efficiency Trends in Enterprise Computing. John Sheehy Systems Architect Environmental & Efficiency Trends in Enterprise Computing John Sheehy Systems Architect jes@e-techservices.com Cost of Energy is Increasing But Inversely Correlated with US Dollar Without the 45-point

More information

Systems and Technology Group. IBM Technology and Solutions Jan Janick IBM Vice President Modular Systems and Storage Development

Systems and Technology Group. IBM Technology and Solutions Jan Janick IBM Vice President Modular Systems and Storage Development Systems and Technology Group IBM Technology and Solutions Jan Janick IBM Vice President Modular Systems and Storage Development Power and cooling are complex issues There is no single fix. IBM is working

More information

Data Centre Energy Efficiency. Duncan Clubb EMEA Data Centre Practice Director CS Technology

Data Centre Energy Efficiency. Duncan Clubb EMEA Data Centre Practice Director CS Technology Data Centre Energy Efficiency Duncan Clubb EMEA Data Centre Practice Director CS Technology Key Messages No more silos energy efficiency only comes from a holistic approach to DC design and operation If

More information

SCE Energy Conservation Series. Computing The Benefits: Solutions for Creating Energy-Efficient Data Centers. Powerful Insights

SCE Energy Conservation Series. Computing The Benefits: Solutions for Creating Energy-Efficient Data Centers. Powerful Insights SCE Energy Conservation Series Computing The Benefits: Solutions for Creating Energy-Efficient Data Centers Changes in equipment, facility layout and procedures can have a big impact on energy costs. Computers

More information

Efficiency of Data Center cooling

Efficiency of Data Center cooling Efficiency of Data Center cooling Comparison of data room layouts and cooling systems Bohumil Cimbal Product manager for Cooling Systems in CONTEG Company Objective Basic questions between investor and

More information

Universal, Scalable Factorized Power Architecture for New Processors and Memory Loads

Universal, Scalable Factorized Power Architecture for New Processors and Memory Loads Universal, Scalable Factorized Power Architecture for New Processors and Memory Loads Uptime Institute, New York, NY, May 2010 Abstract: HPC (High Performance Computing) processors and memory loads continue

More information

18 th National Award for Excellence in Energy Management. July 27, 2017

18 th National Award for Excellence in Energy Management. July 27, 2017 18 th National Award for Excellence in Energy Management July 27, 2017 ICICI Bank, Data Centre, August Hyderabad 30 & 31, 2017 ICICI Bank - Revolution in Digital Banking Over 100,000 Digital POS in 4 months

More information

Future of Cooling High Density Equipment. Steve Madara Vice President and General Manager Liebert Precision Cooling Business Emerson Network Power

Future of Cooling High Density Equipment. Steve Madara Vice President and General Manager Liebert Precision Cooling Business Emerson Network Power Future of Cooling High Density Equipment Steve Madara Vice President and General Manager Liebert Precision Cooling Business Emerson Network Power Agenda Issues facing the Data Center Managing the explosive

More information

MEASURE MONITOR UNDERSTAND

MEASURE MONITOR UNDERSTAND MEASURE MONITOR UNDERSTAND Presented by Alistair Hunt Energy Monitoring, Measurement metrics Where and What 1 History & Background Company Timeline 18 Years Comrac & Sinetica founded 15 Years Raritan Integration

More information

E f f i c i e n c y b e y o n d t h e A C b a s e d d a t a c e n t e r d e s i g n s ; V D C p o w e r f e e d s o l u t i o n

E f f i c i e n c y b e y o n d t h e A C b a s e d d a t a c e n t e r d e s i g n s ; V D C p o w e r f e e d s o l u t i o n E f f i c i e n c y b e y o n d t h e A C b a s e d d a t a c e n t e r d e s i g n s ; 4 0 0 V D C p o w e r f e e d s o l u t i o n Juha Klemola / HW Architect / Nokia Introduction to the challenge Datacenter

More information

Extending Energy Efficiency. From Silicon To The Platform. And Beyond Raj Hazra. Director, Systems Technology Lab

Extending Energy Efficiency. From Silicon To The Platform. And Beyond Raj Hazra. Director, Systems Technology Lab Extending Energy Efficiency From Silicon To The Platform And Beyond Raj Hazra Director, Systems Technology Lab 1 Agenda Defining Terms Why Platform Energy Efficiency Value Intel Research Call to Action

More information

POWERING TECHNOLOGY. Reliably powering your business. Solving your power needs. DC POWER SYSTEMS

POWERING TECHNOLOGY. Reliably powering your business. Solving your power needs. DC POWER SYSTEMS POWERING TECHNOLOGY Reliably powering your business. Solving your power needs. DC POWER SYSTEMS P O W E R I N G T E C H N O L O G Y UNIPOWER Systems today incorporates products from the former Power-One

More information

Server Technology Inc.

Server Technology Inc. Server Technology Inc. Power Efficiency Gains by Deploying 415 VAC Power Distribution in North American Data Centers White Paper STI-100-008 2011-Sept-22 Headquarters Server Technology, Inc. 1040 Sandhill

More information

Liebert NXr Series 15KVA to 90KVA (208V/220V) AC Power for Business-Critical Continuity

Liebert NXr Series 15KVA to 90KVA (208V/220V) AC Power for Business-Critical Continuity Liebert NXr Series 15KVA to 90KVA (208V/220V) AC Power for Business-Critical Continuity Anticipating Technology Changes Through Adaptive Architecture Today, you need a power infrastructure that can work

More information

1.0 Executive Summary. 2.0 Available Features & Benefits

1.0 Executive Summary. 2.0 Available Features & Benefits Statement Of Work Energy Management Services Table of Contents 1.0 Executive Summary 2.0 Available Features & Benefits 3.0 Assessment Deliverables Selection 4.0 On Site Assessment Activities 5.0 Exclusions

More information

Maximise Data Center Value

Maximise Data Center Value Maximise Data Center Value with Higher Density Infrastructure Dramatic cost savings enabled; Requires solving unique electrical + cooling challenges; 08 December 2015 Speaker gokhan.gulal@4g.net.tr Genel

More information

High-Voltage DC-DC Power Module Development. Public Review

High-Voltage DC-DC Power Module Development. Public Review High-Voltage DC-DC Power Module Development Public Review DC-DC Power Module Phase 1 (Spec Development) Project Problem statement: A modular DC-DC power supply is needed to provide low cost, higher efficiency

More information

THE ROLE OF INFRARED TESTING AT DATA CENTERS

THE ROLE OF INFRARED TESTING AT DATA CENTERS THE ROLE OF INFRARED TESTING AT DATA CENTERS By: Eric R. Stockton CompuScanIR Division Stockton Infrared Thermographic Services, Inc. www.compuscanir.com 800-248-7226 Introduction Data centers and other

More information

Energy Logic: Emerson Network Power. A Roadmap for Reducing Energy Consumption in the Data Center. Ross Hammond Managing Director

Energy Logic: Emerson Network Power. A Roadmap for Reducing Energy Consumption in the Data Center. Ross Hammond Managing Director Energy Logic: A Roadmap for Reducing Energy Consumption in the Data Center Emerson Network Power Ross Hammond Managing Director Agenda Energy efficiency Where We Are Today What Data Center Managers Are

More information

Kifer Industrial Park

Kifer Industrial Park FEATURES ±56,358 SF Data Center / Lab / Manufacturing Building The entire facility is built-out with raised floor data center and data center support space Heavy Power Multiple telecom providers Pre-action

More information

Meeting the Energy Efficiency and Financial Challenges in IT. Liam Newcombe BCS Data Centre Specialist Group Secretary

Meeting the Energy Efficiency and Financial Challenges in IT. Liam Newcombe BCS Data Centre Specialist Group Secretary Meeting the Energy Efficiency and Financial Challenges in IT Liam Newcombe BCS Data Centre Specialist Group Secretary Meeting the Energy and Financial Challenges in IT Recognising the Problem Recognising

More information

AC, DC and Custom Power Supplies

AC, DC and Custom Power Supplies AC, DC and Custom Power Supplies High Efficiency Power Solutions DC-DC CONVERTERS Range Power Amps Max / Outputs Input Range Output (VDC) Dimensions H x W x D mm (inches) F501 500W 40 36-75 48, 28, 24,

More information

Product Brochure Eaton 93PR UPS kw

Product Brochure Eaton 93PR UPS kw Product Brochure Eaton 93PR UPS 25-200 kw For more than 50 years, Eaton has been safeguarding the critical systems of businesses across the globe. Whether protecting a single desktop or the largest data

More information

IBM eserver Total Storage, On Demand

IBM eserver Total Storage, On Demand IBM eserver Total Storage, On Demand Bill Ott, Vice President, eserver xseries & IntelliStation Development Systems and Technology Group 10/7/2005 IBM 2Q 2005 Business Status Key Accomplishments Operational

More information

SIFMA Technology Management Conference. Data Center Efficiency

SIFMA Technology Management Conference. Data Center Efficiency SIFMA Technology Management Conference June 20, 2007 Data Center Efficiency Presented by Julius Neudorfer In deciding how to best implement a strategy for supporting critical data systems, Data Center

More information

IXcellerate Moscow One Datacentre - Phase 1 & 2 Overview

IXcellerate Moscow One Datacentre - Phase 1 & 2 Overview Contents 1. Document Purpose... 2 2. Facility Overview... 2 2.1 Technical Space... 2 2.2 Load Density... 2 2.3 Resilience... 2 2.4 Engineering Plant Maintenance & Service Restoration... 3 3. Engineering

More information

DC Energy, Efficiency Challenges

DC Energy, Efficiency Challenges DC Energy, Efficiency Challenges Choosing a density strategy Implementing a high density environment Maximizing the efficiency benefit Anticipating the dynamic data center Key points on energy usage in

More information

Measurement and Management Technologies (MMT)

Measurement and Management Technologies (MMT) IBM Systems Lab Services and Training Measurement and Management Technologies (MMT) Data Center Solutions for a Smarter Planet AGENDA IBM Energy Efficiency Program & Accomplishments IBM CO2 Reduction Commitment

More information

Description & Installation Guide

Description & Installation Guide VIPAC TM Family of Power Systems 0 to 900 Watt Description & Installation Guide Product Description Vicor s VIPAC is a new type of integrated power system leveraging the latest advances in DC-DC converter

More information

Towards the Green Data Centre. Lex Coors Vice President Data Center Technology & Engineering Group

Towards the Green Data Centre. Lex Coors Vice President Data Center Technology & Engineering Group Towards the Green Data Centre Lex Coors Vice President Data Center Technology & Engineering Group DC Emissions: We Have Lift-Off! Data Centre Greenhouse Gas Emissions are projected to quadruple by 2020

More information

DC POWER OVERVIEW BROCHURE Powerful Solutions for Critical Data and Telecom Applications

DC POWER OVERVIEW BROCHURE Powerful Solutions for Critical Data and Telecom Applications DC POWER OVERVIEW BROCHURE Powerful Solutions for Critical Data and Telecom Applications DC POWER OVERVIEW BROCHURE NETSURE APPLICATIONS yradio Base Station / Microwave Site ywireless & Wireline Access

More information

3300 kw, Tier 3, Chilled Water, 70,000 ft 2

3300 kw, Tier 3, Chilled Water, 70,000 ft 2 [Reference Design 22] 3300 kw, Tier 3, Chilled Water, 70,000 ft 2 DESIGN OVERVIEW Data Center IT Capacity 1100 kw per Data Hall 3 Independent Data Halls Design Application Range This design can be applied

More information

E3T Energy. Information Technology and Data Centers (Webinar 1) Emerging Technologies Showcase IT Equipment & Power Management

E3T Energy. Information Technology and Data Centers (Webinar 1) Emerging Technologies Showcase IT Equipment & Power Management Information Technology and Data Centers (Webinar 1) Showcase IT Equipment & Power Management November 20, 2013 Welcome. Today s webinar is being recorded and will be posted at: www.e3tnw.org www.conduitnw.org

More information

Data Center Infrastructure Management (DCIM) By Jesse Zhuo

Data Center Infrastructure Management (DCIM) By Jesse Zhuo Data Center Infrastructure Management (DCIM) By Jesse Zhuo Agenda The Evolution of DCIM Users Perspectives Management Methodology by Delta DCIM The Evolution of DCIM What is DCIM DCIM is software for Data

More information

HP BladeSystem c-class enclosures

HP BladeSystem c-class enclosures Family data sheet HP BladeSystem c-class enclosures Tackle your infrastructure s cost, time, and energy issues HP BladeSystem c3000 Platinum Enclosure (rack version) HP BladeSystem c7000 Platinum Enclosure

More information

24/48V Battery Bank Ah High Cycling Long Life

24/48V Battery Bank Ah High Cycling Long Life Outdoor Power Cabinets, 48V DC Free Cooled with Combined Air-Con. PreFactory assembled with 19 inch Power sub rack, 2 or 4 battery Shelf s, 3U DCAC Panel combined with rectifiers 2U or 4U Power Module

More information

Topics Covered in this Presentation

Topics Covered in this Presentation DATA CENTER DESIGN CONSIDERATIONS AND TRENDS MUSIC CITY POWER QUALITY GROUP May 5, 2009 Daniel L. Ellis - Eaton 2008 Eaton Corporation. All rights reserved. Topics Covered in this Presentation Economic

More information

Case study on Green Data Center. Reliance Jio Infocomm Limited

Case study on Green Data Center. Reliance Jio Infocomm Limited Case study on Green Data Center 2 What is data center? Use and functions of Data Center. Basic Infrastructure requirement for data center. Energy consumption heads in data center. 3 What is Data Center

More information

Calculating Total Power Requirements for Data Centers

Calculating Total Power Requirements for Data Centers Calculating Total Power Requirements for Data Centers White Paper 3 Revision 1 by Victor Avelar > Executive summary Part of data center planning and design is to align the power and cooling requirements

More information

PROCESS & DATA CENTER COOLING. How and Why To Prepare For What s To Come JOHN MORRIS REGIONAL DIRECTOR OF SALES

PROCESS & DATA CENTER COOLING. How and Why To Prepare For What s To Come JOHN MORRIS REGIONAL DIRECTOR OF SALES PROCESS & DATA CENTER COOLING How and Why To Prepare For What s To Come JOHN MORRIS REGIONAL DIRECTOR OF SALES CONGRATULATIONS 2 BOLD PREDICTION 3 Where We Are TODAY Computer Technology NOW advances more

More information

SmartPro UPS System Intelligent, line-interactive battery backup and network power management

SmartPro UPS System Intelligent, line-interactive battery backup and network power management SmartPro UPS System Intelligent, line-interactive battery backup and network power management Model #: SMART2200VS 2200VA line interactive tower UPS system Enhanced communication ports (2 USB / 2 DB9),

More information

<Insert Picture Here> Austin Data Center 6Sigma DC CFD Model

<Insert Picture Here> Austin Data Center 6Sigma DC CFD Model Austin Data Center 6Sigma DC CFD Model Keith Ward Keith Ward Data Center Facilities Engineering and Logistics Design Austin Data Center Statistics - Space Original AT&T Designed and

More information

Converged Power Solutions. Data center power reinvented

Converged Power Solutions. Data center power reinvented Converged Power Solutions Data center power reinvented always on anywhere anytime With Eltek s Converged Power Solutions, the next generation power solution for data centers is here. It offers unmatched

More information

Power & Cooling Considerations for Virtualized Environments

Power & Cooling Considerations for Virtualized Environments Power & Cooling Considerations for Virtualized Environments Cisco Data Center Day 2008 31-01-2008 APC-MGE Vision & Mission OUR VISION APC-MGE products ensure availability wherever data is created, transmitted

More information

The Future of DATA CENTER CRITICAL POWER

The Future of DATA CENTER CRITICAL POWER The Future of DATA CENTER CRITICAL POWER DOES ENERGY USE IN YOUR DATA CENTER KEEP YOU UP AT NIGHT? It should. Your customers rely on you to keep networks flowing and transactions moving 24 hours a day,

More information

380VDC Data Center At Duke Energy

380VDC Data Center At Duke Energy 380VDC Data Center At Duke Energy Dennis P. Symanski EPRI - Senior Project Manager Curtis Watkins Duke Energy - Senior Project Manager Emerging Technology (ET) Summit November 9, 2010 Sacramento, CA From

More information

Datacenter Efficiency Trends. Cary Roberts Tellme, a Microsoft Subsidiary

Datacenter Efficiency Trends. Cary Roberts Tellme, a Microsoft Subsidiary Datacenter Efficiency Trends Cary Roberts Tellme, a Microsoft Subsidiary Power Slashing Tools P3 Kill-A-WATT Measures min, max, and instantaneous voltage and current draw Calculates power (watts), kilowatt

More information

UPS. centric Hot scalable modular 3-phase UPS Delivers 25 up to 200 kva/kw INFINITE POWER. Mission Critical Applications

UPS. centric Hot scalable modular 3-phase UPS Delivers 25 up to 200 kva/kw INFINITE POWER. Mission Critical Applications INFINITE POWER Mission Critical Applications UPS UNINTERRUPTIBLE POWER SUPPLY centric Hot scalable modular 3-phase UPS Delivers 25 up to 200 kva/kw Rack-mountable modules designed for blades, data-center,

More information

Smart Data Centres. Robert M Pe, Data Centre Consultant HP Services SEA

Smart Data Centres. Robert M Pe, Data Centre Consultant HP Services SEA Smart Data Centres Robert M Pe, Data Centre Consultant Services SEA 2006 Hewlett-Packard Development Company, L.P. The information contained herein is subject to change without notice Content Data center

More information

How Liquid Cooling Helped Two University Data Centers Achieve Cooling Efficiency Goals. Michael Gagnon Coolcentric October

How Liquid Cooling Helped Two University Data Centers Achieve Cooling Efficiency Goals. Michael Gagnon Coolcentric October How Liquid Cooling Helped Two University Data Centers Achieve Cooling Efficiency Goals Michael Gagnon Coolcentric October 13 2011 Data Center Trends Energy consumption in the Data Center (DC) 2006-61 billion

More information

Newave s approach for protecting mission critical application

Newave s approach for protecting mission critical application ABB Technology Show, May 2013 Newave s approach for protecting mission critical application May 13, 2013 Slide 1 Contents Newave s company overview Electricity environment and trend Data Centre environment

More information

Energy efficiency management and environmental impact assessment for ICTs

Energy efficiency management and environmental impact assessment for ICTs http://eustandards.in/ Energy efficiency management and environmental impact assessment for ICTs Beniamino Gorini (ETSI TC-EE chairman) 2 Contents What is required to define sustainable ICT products/networks/services

More information

VIPAC Array Family. of DC-DC Converters Up to 750 Watts. Description & Installation Guide. Product Description

VIPAC Array Family. of DC-DC Converters Up to 750 Watts. Description & Installation Guide. Product Description 2 VIPAC Array Family of DC-DC Converters Up to 70 Watts Description & Installation Guide Product Description The VIPAC Array is a highly flexible system of DC input, power building-blocks that can be configured

More information

Nominee: Prefabricated, Pre Assembled Data Centre Modules by Schneider Electric

Nominee: Prefabricated, Pre Assembled Data Centre Modules by Schneider Electric Nominee: Prefabricated, Pre Assembled Data Centre Modules by Schneider Electric Nomination title: Schneider Electric Prefabricated, Pre Assembled Data Centre Modules Schneider Electric has introduced a

More information

DC Power for Improved Data Center Efficiency

DC Power for Improved Data Center Efficiency DC Power for Improved Data Center March 2008 My Ton Ecos Consulting Brian Fortenbery EPRI William Tschudi Lawrence Berkeley National Laboratory DC Power for Data Center 1 The work described in this report

More information

2007 Power Symposium Where are we going?

2007 Power Symposium Where are we going? 2007 Power Symposium Where are we going? October 4, 2007 v Steven Barthel IBM Power Procurement Program Director AGENDA A Vision from the past The New things important to our customers Efficiency The Vision

More information

Tel: AC Power for Business-Critical Continuity TM

Tel: AC Power for Business-Critical Continuity TM Tel: +852-2690-4118 AC Power for Business-Critical Continuity TM Anticipating Technology Changes Through Adaptive Architecture Today, you need a power infrastructure that can work across your enterprise

More information

Inside the Data Center: Opportunities for Energy Efficiency

Inside the Data Center: Opportunities for Energy Efficiency Pacific Gas and Electric Company Presented to Technologies and Practices for Efficient & Reliable Data Centers Inside the Data Center: Opportunities for Energy Efficiency Mark Bramfitt Sunnyvale, California

More information

Thermal management. Thermal management

Thermal management. Thermal management Thermal management Thermal management Managing thermal loads is a major challenge for all Data Centre operators. Effecting proper control of the thermal environment drives energy consumption and ultimately

More information

Basic Methods for DTE Power Delivery

Basic Methods for DTE Power Delivery Basic Methods for DTE Power Delivery Ed Walker TI Technical Staff Analog Field Applications Cary, NC Design Example attempt to show Methods of implementation for power, isolation and output control leverage

More information

Optical Components. A Customers Perspective. Finisar Analyst and Investor Meeting October 7, Adam Carter Director Transceiver Module Group Cisco

Optical Components. A Customers Perspective. Finisar Analyst and Investor Meeting October 7, Adam Carter Director Transceiver Module Group Cisco Optical Components A Customers Perspective Adam Carter Director Transceiver Module Group Cisco Finisar Analyst and Investor Meeting October 7, 2008 1 Agenda Network Trends Network Traffic Forecast Growth

More information

TSC Schneider-PDI Agenda

TSC Schneider-PDI Agenda TSC Schneider-PDI Agenda General Electrical Power Layouts and Equipment Single Phase UPS s Three Phase UPS s Trends In Data Center Power Distribution Data Center Cooling Trends and Products Jim Tubbesing

More information

How green is green? The environmental benefits of using Diesel Rotary UPS systems to support critical loads in the datacenter. Summary.

How green is green? The environmental benefits of using Diesel Rotary UPS systems to support critical loads in the datacenter. Summary. How green is green? The environmental benefits of using Diesel Rotary UPS systems to support critical loads in the datacenter Summary Diesel Rotary UPS (DRUPS) systems are best in class regarding energy

More information

Beyond BREEAM Excellent DCs. Cobalt Data Centre Campus

Beyond BREEAM Excellent DCs. Cobalt Data Centre Campus Beyond BREEAM Excellent DCs Cobalt Data Centre Campus Campus Location - Newcastle Campus Site Plan Data Centre 2 Data Centre 1 Data Centre 3 Cobalt Business Park Power Delivery to Site National Grid Tynemouth

More information

November/December 2011

November/December 2011 November/December 2011 Company is justifiably proud of its new facilities Helping companies plan, design, operate, and eventually refresh or repurpose their data centers more efficiently and effectively

More information

Commercial Projects. Data Centres & IT. Alternative Energy Generation. Manufacturing & Service

Commercial Projects.   Data Centres & IT. Alternative Energy Generation. Manufacturing & Service Commercial Projects Data Centres & IT Alternative Energy Generation Manufacturing & Service www.silcar.com.au 02 Silcar designs, constructs, operates, manages and maintains critical infrastructure assets

More information

Modius OpenData v3.3. Product Overview of Modius OpenData for Unified Data Center Monitoring & Analysis

Modius OpenData v3.3. Product Overview of Modius OpenData for Unified Data Center Monitoring & Analysis Modius OpenData v3.3 Product Overview of Modius OpenData for Unified Data Center Monitoring & Analysis Modius Inc. 832 Folsom, Suite 1001 San Francisco, CA 94107 888.323.0066 info@modius.com www.modius.com

More information

PRODUCT FEATURES AND ADVANTAGES

PRODUCT FEATURES AND ADVANTAGES Flatpack2 24/1800 HE 24VDC Rectifier/Converter Modules The combination of innovative design, efficiency and reliability makes the Flatpack2 HE stand out. With efficiency up to 96.2%, the losses have been

More information

Mid-Sized Data Center UPS Solutions Overview

Mid-Sized Data Center UPS Solutions Overview Mid-Sized Data Center UPS Solutions Overview 2008 2008 Eaton Eaton Corporation. Corporation. All All rights rights reserved. reserved. Mid-Range System Concerns IT / ENGINEERS / BUYERS Cooling Designs

More information

Drives and motors. A guide to using variable speed drives and motors in data centres Meeting your Carbon Reduction Commitment (CRC)

Drives and motors. A guide to using variable speed drives and motors in data centres Meeting your Carbon Reduction Commitment (CRC) Drives and motors A guide to using variable speed drives and motors in data centres Meeting your Carbon Reduction Commitment (CRC) The power behind the data Private and public businesses, from banks to

More information

E-Series Site Preparation Guide

E-Series Site Preparation Guide E-Series Site Preparation Guide September 2017 215-11797_A0 doccomments@netapp.com Table of Contents 3 Contents Deciding whether to use this guide... 10 Specifications of the model 3040 40U cabinet...

More information

SmartAisle Intelligent, Integrated Infrastructure Using Row-based Building Blocks. Solutions For Business-Critical Continuity

SmartAisle Intelligent, Integrated Infrastructure Using Row-based Building Blocks. Solutions For Business-Critical Continuity SmartAisle Intelligent, Integrated Infrastructure Using Row-based Building Blocks Solutions For Business-Critical Continuity Deploy An Efficient and Flexible Row-Based Infrastructure Efficiency. Capacity.

More information

EP s approach to Power & Energy efficiency in DCs & paradigms

EP s approach to Power & Energy efficiency in DCs & paradigms DG for Innovation and Technological Support EP s approach to Power & Energy efficiency in DCs & paradigms Presentation Presentation subtitle subtitle or lead-in or lead-in that says that what says what

More information

30 th September Always Right Size Modular Data Centres. Cannon Technologies Ltd (2015)

30 th September Always Right Size Modular Data Centres. Cannon Technologies Ltd (2015) 30 th September 2015 Glenn Conlon Always Right Size Modular Data Centres Traditional DC Build: Image courtesy of ENP Traditional DC: IRO 20 million + @ T2/3 Image courtesy of ENP DC Halls x 2, 500 Cabinets

More information

District Cooling Marches on in Dubai The Emirates Towers Case Study

District Cooling Marches on in Dubai The Emirates Towers Case Study District Cooling Marches on in Dubai The Emirates Towers Case Study RETROFITTING JUMEIRAH EMIRATES TOWERS with DISTRICT COOLING Presented by: Samer Khoudeir Chief Sales & Marketing Officer Empower Tariq

More information

Green Computing: Datacentres

Green Computing: Datacentres Green Computing: Datacentres Simin Nadjm-Tehrani Department of Computer and Information Science (IDA) Linköping University Sweden Many thanks to Jordi Cucurull For earlier versions of this course material

More information

A Scalable, Reconfigurable, and Efficient Data Center Power Distribution Architecture

A Scalable, Reconfigurable, and Efficient Data Center Power Distribution Architecture A Scalable, Reconfigurable, and Efficient Data Center Power Distribution Architecture White Paper 129 Revision 1 by Neil Rasmussen > Executive summary Significant improvements in efficiency, power density,

More information

HVDC Innovation, XECHNO Power & Fresh HVDC

HVDC Innovation, XECHNO Power & Fresh HVDC 1 HVDC Innovation, XECHNO Power & Fresh HVDC Energy Saving Technology for the Data Center Green Consulting Business Unit Solution Business Division NTT DATA INTELLILINK Corp. Problems facing data centers:

More information

MGE Galaxy /900 kva

MGE Galaxy /900 kva MGE Galaxy 9000 800/900 kva Data centers are becoming increasingly large, Blade Servers are demanding more power, and there is increasing demand from semi conductors for the digital economy. The MGE Galaxy

More information