Data Center Trends and Challenges
|
|
- Jonathan Davidson
- 6 years ago
- Views:
Transcription
1 Data Center Trends and Challenges, IBM Fellow Chief Engineer - Data Center Energy Efficiency
2 Customers challenges are driven by the following Increasing IT demand Continued cost pressure Responsive to change 6x 69x 85% Growth in server and storage shipments this decade. Of distributed computing capacity sits idle. 18% 75% Increase in data center energy costs in next year. Of CIO s anticipate a strongly centralized infrastructure in 5 years. 20x 71% 5-60% Technology density increase in servers this decade. Of data centers > 7 years old. Of IT workloads may be cloud-enabled.
3 Everyone Has A Computer Room Branch Office Enterprise Data Center
4 Data centers use electricity How much? More video was uploaded to YouTube in the past 2 months than if ABC, CBS and NBC had been airing content 24/365 since 1948 Nov, 2012
5 Typical Data Center Energy End Use 100 Units 35 Units Power Conversions Data Center Energy& Breakdown Distribution Power 16.7% 30 Units Cooling Equipment Cooling 33.3% Server Load /Computing Operations X86 average utilization 5 12% IT Equipment 50.0% 33 Units Delivered Power Usage Effectiveness(PUE) = (Infrastructure Power + IT Power)/IT Power = 2
6 Data Center Energy Use Trends
7 Total Electricity Usage by State (MkWhr/year) World Data Centers US Data Centers
8 Information Technology is becoming more energy efficient at a furious pace The computer in your cell phone today is a million times cheaper, and a thousand times more powerful and about a hundred thousand time smaller than the one computer installed at MIT in 1965 Nov, 2012
9 Incredible performance improvements Incredible performance improvements Energy per Transistor goes DOWN Number of transistors ~ 1 Million Factor Reduction In Energy/Transistor Over 30+ Years
10 Moore s Law: Delivering DC Performance power5 575 power6 575 power TFlops 118 racks 10,000 ft MW TFlops 9 racks 300 ft MW TFlops 1 racks 30 ft MW
11 Overview of ASHRAE s Thermal Guidelines Book third edition Chapter 1 Introduction Chapter 2 Air Cooled Equipment Environmental Specifications Chapter 3 Liquid Cooled Equipment Environmental Specifications Chapter 4 Facility Temperature & Humidity Measurement Chapter 5 Equipment Placement & Airflow Patterns Chapter 6 Equipment Manufacturers Heat & Airflow Reporting Appendices A - J Can obtain
12 IT Equipment Environment Measurement at Inlet Four Key Environmental Requirements 1. Inlet Air Temperature 2. Inlet Humidity 3. Inlet Particulate Contamination 4. Inlet Gaseous Contamination AIR INLET to datacom equipment IS the important specification to meet. OUTLET temperature is NOT important to datacom equipment.
13 Thermal Guidelines Third Edition (2011) Drivers for Updated Thermal Guidelines Improve Energy Efficiency Expand use of the allowable range - Reduce chiller hours Expand the limits of the allowable range - Enable greater economizer usage ASHRAE TC 9.9 Response Create Opportunity for Innovation Defined two new classes with wider environmental envelopes Created guidance to evaluate operation outside existing recommended range - Educate users on reliability, IT equipment power consumption and other factors
14 IT Equipment Environmentals ASHRAE Psychrometric Chart 2011 New Classes A1 and A2 are EXACTLY the SAME as previous Classes 1 & 2 Classes A1 and A2 apply to new and legacy equipment New Classes A3 and A4 do NOT include legacy equipment These are the IT Equipment inlet requirements!!
15 Overview of ASHRAE s Power Trends & Cooling Book Chapter 1 Introduction Chapter 2 Background Chapter 3 Component Power Trends Chapter Load Trends and Their Application Chapter 5 Air Cooling of Computer Equipment Chapter 6 Liquid Cooling of Computer Equipment Chapter 7 Practical Application of Trends to Data Center Design Appendices A C ASHRAE TC 9.9 Website
16 Volume Server Power Trends to 2020 Market Requirements force IT manufacturers to maximize performance/volume creating high heat load/rack These rack heat loads will result in increased focus on improving data center ventilation solutions and localized liquid cooling solutions
17 Leibniz Rechenzentrum, Garching, Germany SuperMUC: Warm-Water Cooled 3 PFLOPS System 1Q12 2Q12: ~10000 IBM System x idataplex Water Cooled dx360 M4
18 dx360 M4 - Water Cooling design Hot Water Cooled Node with 90% heat recovery. Power advantage over air cooled node by 5-7%. {Due to lower CPU temps and absence of fans} Water inlet 18 C to 0.5 liters/min per Node {37 liters/min Rack} idataplex Rack w/ water cooled nodes
19 2nd Day of Power Failures Cripples Wide Swath of India The world s largest blackout ever crippled much of northern India for a second consecutive day on Tuesday(July 31, 2012), spreading across 22 of 28 states, an area of 670 million people(10% of the planet). An estimated 32 gigawatts was taken off line.
20 Sandy's mammoth wake: millions without power, transit A half dozen nuclear power plants were shut down or otherwise affected, while the nation's oldest facility declared a rare "alert" after the record storm surge pushed flood waters high enough to endanger a key cooling system. More than 6.6 million homes and businesses were without electricity, about two-thirds of them in New York and New Jersey.
21 Energy Savings from Tri/Co-Generation 100 Units INPUT 100% USEFUL ENERGY 74.2% 35 Units ELECTRICAL OUTPUT 29.7% LOSSES 25.8% OTHER LOSSES 4.8% 30 Units Delivered EXHAUST LOSSES 21% THERMAL OUTPUT 44.5% Offset building thermal loads by recycling the waste heat energy available at site Reduces costs and increases reliability Increases efficiency and reduces fossil fuel combustion
22 Syracuse University Green Data Center Green Data Center Facility Micro-Turbines Water cooled raised floor Absorption Chillers
23 Big Issues IT demand continues to grow rapidly IT energy efficiency continues to dramatically improve Low IT equipment utilization Low infrastructure efficiency improvements remain Energy cost will continue to be #1 business concern
24 Thank you for your attention Nov, 2012
Mission Critical Facilities & Technology Conference November 3, 2011 Cooling 101. Nick Gangemi Regional Sales Manager Data Aire
Mission Critical Facilities & Technology Conference November 3, 2011 Cooling 101 Nick Gangemi Regional Sales Manager Data Aire Agenda Exactly what are we talking about ASHRAE TC 9.9 Design best practices
More informationMSYS 4480 AC Systems Winter 2015
MSYS 4480 AC Systems Winter 2015 Module 12: DATA CENTERS By Satwinder Singh 14/05/2015 1 Data Centers Data Centers are specialized environments that safeguard your company's most valuable equipment and
More informationCHILLED WATER. HIGH PRECISION AIR CONDITIONERS, FROM 7 TO 211 kw
IT COOLING CLOSE CONTROL AIR CONDITIONERS CHILLED WATER HIGH PRECISION AIR CONDITIONERS, FROM 7 TO 211 kw 3 Versions available Single chilled water coil Double chilled water coil High temperature IT COOLING
More informationSession 6: Data Center Energy Management Strategies
Session 6: Data Center Energy Management Strategies Data Center Energy Use and Opportunities: Applying Best Practices to meet Executive Order Requirements Dale Sartor, PE Lawrence Berkeley National Laboratory
More informationCooling. Highly efficient cooling products for any IT application. For More Information: (866) DATA CENTER SOLUTIONS
Cooling > Highly efficient cooling products for any IT application. DATA CENTER SOLUTIONS For More Information: (866) 787-3271 Sales@PTSdcs.com End-to-End Cooling Solutions from the Closet to the Data
More informationIntroducing the Heat Wheel to the Data Center
Introducing the Heat Wheel to the Data Center Robert (Dr. Bob) Sullivan, Ph.D. Data Center Infrastructure Specialist KyotoCooling International Critical Facilities Round Table 1 A New Free Cooling Technique
More informationHow Liquid Cooling Helped Two University Data Centers Achieve Cooling Efficiency Goals. Michael Gagnon Coolcentric October
How Liquid Cooling Helped Two University Data Centers Achieve Cooling Efficiency Goals Michael Gagnon Coolcentric October 13 2011 Data Center Trends Energy consumption in the Data Center (DC) 2006-61 billion
More informationReducing Data Center Cooling Costs through Airflow Containment
FEATURE Reducing Data Center Cooling Costs through Airflow Containment Implementing a containment solution in the data center costs much less than the alternatives of adding air handlers or other supplemental
More informationFuture of Cooling High Density Equipment. Steve Madara Vice President and General Manager Liebert Precision Cooling Business Emerson Network Power
Future of Cooling High Density Equipment Steve Madara Vice President and General Manager Liebert Precision Cooling Business Emerson Network Power Agenda Issues facing the Data Center Managing the explosive
More informationRecapture Capacity for Existing. and Airflow Optimization
Recapture Capacity for Existing Data Centers Through Cooling and Airflow Optimization Introduction Challenges and Trends Agenda Cooling & Airflow Optimization Takeaways Learning Objectives Recognize opportunities
More informationScalable, Secure. Jason Rylands
Energy Efficient, Modular, Scalable, Secure Jason Rylands The planning, construction and operation of IT infrastructure for mission critical applications in reliable Datacentres represents a real challenge.
More informationASHRAE s Energy Efficiency Technical Guidance
ASHRAE s Energy Efficiency Technical Guidance Tom Watson, P.E. Fellow ASHRAE, Life Member ASHRAE President ASHRAE Energy Efficiency Standards Agenda Standards & Guidelines Research Projects Design Guidance
More informationCombining Cold Aisle Containment with Intelligent Control to Optimize Data Center Cooling Efficiency
A White Paper from the Experts in Business-Critical Continuity TM Combining Cold Aisle Containment with Intelligent Control to Optimize Data Center Cooling Efficiency Executive Summary Energy efficiency
More informationData Center Energy and Cost Saving Evaluation
Available online at www.sciencedirect.com ScienceDirect Energy Procedia 75 (2015 ) 1255 1260 The 7 th International Conference on Applied Energy ICAE2015 Data Center Energy and Cost Saving Evaluation Z.
More informationHot vs Cold Energy Efficient Data Centers. - SVLG Data Center Center Efficiency Summit
Hot vs Cold Energy Efficient Data Centers - SVLG Data Center Center Efficiency Summit KC Mares November 2014 The Great Debate about Hardware Inlet Temperature Feb 2003: RMI report on high-performance data
More informationIs Data Center Free Cooling Feasible in the Middle East? By Noriel Ong, ASEAN Eng., PMP, ATD, PQP
Is Data Center Free Cooling Feasible in the Middle East? By Noriel Ong, ASEAN Eng., PMP, ATD, PQP This case study will evaluate the feasibility of data center free cooling in the Middle East using indirect
More informationPROCESS & DATA CENTER COOLING. How and Why To Prepare For What s To Come JOHN MORRIS REGIONAL DIRECTOR OF SALES
PROCESS & DATA CENTER COOLING How and Why To Prepare For What s To Come JOHN MORRIS REGIONAL DIRECTOR OF SALES CONGRATULATIONS 2 BOLD PREDICTION 3 Where We Are TODAY Computer Technology NOW advances more
More informationOptimization in Data Centres. Jayantha Siriwardana and Saman K. Halgamuge Department of Mechanical Engineering Melbourne School of Engineering
Optimization in Data Centres Jayantha Siriwardana and Saman K. Halgamuge Department of Mechanical Engineering Melbourne School of Engineering Outline Background and Motivation Overview and scale of data
More informationGreen IT and Green DC
Green IT and Green DC Alex SL Tay Regional Service Product Line Manager Site & Facilities Services, IBM ASEAN 1 What our clients are telling us We are running out of space in our data center We have environmental
More informationLRZ SuperMUC One year of Operation
LRZ SuperMUC One year of Operation IBM Deep Computing 13.03.2013 Klaus Gottschalk IBM HPC Architect Leibniz Computing Center s new HPC System is now installed and operational 2 SuperMUC Technical Highlights
More informationCooling on Demand - scalable and smart cooling solutions. Marcus Edwards B.Sc.
Cooling on Demand - scalable and smart cooling solutions Marcus Edwards B.Sc. Schroff UK Limited Data Centre cooling what a waste of money! A 1MW data center needs 177,000,000 kwh in its lifetime of 10
More informationBENEFITS OF ASETEK LIQUID COOLING FOR DATA CENTERS
BENEFITS OF ASETEK LIQUID COOLING FOR DATA CENTERS Asetek has leveraged its expertise as the world-leading provider of efficient liquid cooling systems to create its RackCDU and ISAC direct-to-chip liquid
More informationGreen Data Centers A Guideline
Green Data Centers A Guideline Sekhar Kondepudi Ph.D Associate Professor Smart Buildings & Smart Cities Vice Chair Focus Group on Smart Sustainable Cities ITU-TRCSL Workshop on Greening the Future: Bridging
More informationMeasurement and Management Technologies (MMT)
IBM Systems Lab Services and Training Measurement and Management Technologies (MMT) Data Center Solutions for a Smarter Planet AGENDA IBM Energy Efficiency Program & Accomplishments IBM CO2 Reduction Commitment
More informationSmart Data Centres. Robert M Pe, Data Centre Consultant HP Services SEA
Smart Data Centres Robert M Pe, Data Centre Consultant Services SEA 2006 Hewlett-Packard Development Company, L.P. The information contained herein is subject to change without notice Content Data center
More informationEnergy Efficiency and WCT Innovations
Energy Efficiency and WCT Innovations Zeeshan Kamal Siddiqi HPC Leader Middle East, Turkey and Africa (META) Lenovo 2017 Lenovo. All rights reserved. Why do we have a problem? Higher TDP Processors Data
More informationData center cooling evolution. The hottest way to save energy. Lucio Bustaffa: Product Development Manager BlueBox Group
Data center cooling evolution. The hottest way to save energy Lucio Bustaffa: Product Development Manager BlueBox Group Data Center overview What s happening in the web? 2 Data Center overview What s happening
More informationPower & Cooling Considerations for Virtualized Environments
Power & Cooling Considerations for Virtualized Environments Cisco Data Center Day 2008 31-01-2008 APC-MGE Vision & Mission OUR VISION APC-MGE products ensure availability wherever data is created, transmitted
More information7 Best Practices for Increasing Efficiency, Availability and Capacity. XXXX XXXXXXXX Liebert North America
7 Best Practices for Increasing Efficiency, Availability and Capacity XXXX XXXXXXXX Liebert North America Emerson Network Power: The global leader in enabling Business-Critical Continuity Automatic Transfer
More informationData Center Temperature Design Tutorial. Ian Seaton Chatsworth Products
Data Center Temperature Design Tutorial Ian Seaton Chatsworth Products What are we going to do today? Explore a process for determining what data center operating temperature will deliver the best total
More informationDATA CENTER AIR HANDLING COOLING SOLUTIONS
DATA CENTER AIR HANDLING COOLING SOLUTIONS World-class performance and reliability from YORK As data storage and protection needs grow, so can costs and complexity. That s why having the right partner
More informationA global technology leader approaching $42B in sales with 57,000 people, and customers in 160+ countries LENOVO. ALL RIGHTS RESERVED
A global technology leader approaching $42B in sales with 57,000 people, and customers in 160+ countries. 2 Lenovo s Performance Lenovo WW PC Market Share 19.7% 2014 13.1% 2013 2012 9.6% 8.2% 2011 6.5%
More informationPower and Cooling for Ultra-High Density Racks and Blade Servers
Power and Cooling for Ultra-High Density Racks and Blade Servers APC White Paper #46 Richard L. Sawyer Director of Data Center Technology American Power Conversion Company 2005 APC corporation What has
More informationInnovative Data Center Energy Efficiency Solutions
Innovative Data Center Energy Efficiency Solutions Dr. Hendrik F. Hamann IBM T.J. Watson Research Center 2/8/2009 2007 IBM Corporation A holistic Challenge: Energy & Thermal Management Energy / thermal
More informationInternet-Scale Datacenter Economics: Costs & Opportunities High Performance Transaction Systems 2011
Internet-Scale Datacenter Economics: Costs & Opportunities High Performance Transaction Systems 2011 James Hamilton, 2011/10/24 VP & Distinguished Engineer, Amazon Web Services email: James@amazon.com
More informationHigh Efficient Data Center Cooling
Nordborg High Efficient Data Center Cooling Copenhagen Center on Energy Efficiency webinar 12. July 2017 Jörg Saar, Danfoss Cooling 1 Danfoss Cooling Contents 1. Short intro to Danfoss Cooling 2. Introduction
More informationMoving Containment Inside the Enclosure. Jeff Markle Great Lakes Case & Cabinet
Moving Containment Inside the Enclosure Presented by Jeff Markle Great Lakes Case & Cabinet Containment Containment : To put constraint upon; to restrain; to confine; to keep within bounds Containment
More informationCase study on Green Data Center. Reliance Jio Infocomm Limited
Case study on Green Data Center 2 What is data center? Use and functions of Data Center. Basic Infrastructure requirement for data center. Energy consumption heads in data center. 3 What is Data Center
More informationLCP Hybrid Efficient performance with heat pipe technology
LCP Hybrid Efficient performance with heat pipe technology 2 LCP Hybrid The whole is more than the sum of its parts The same is true of "Rittal The System." With this in mind, we have bundled our innovative
More informationHigh Density Cooling Solutions that work from Knurr Kris Holla
High Density Cooling Solutions that work from Knurr Kris Holla The Heat Goes On Ó by Knürr A An International Company Ranked #3 in the world Founded 1931 Strong international setting in over 32 countries
More informationThe Efficient Enterprise. All content in this presentation is protected 2008 American Power Conversion Corporation
Ee The Efficient Enterprise All content in this presentation is protected 2008 American Power Conversion Corporation Keystrokes Kilowatts Heat OUT Electricity IN Need for bandwidth exploding Going hyperbolic!
More informationPlanning a Green Datacenter
Planning a Green Datacenter Dr. Dominique Singy Contribution to: Green IT Crash Course Organisator: Green IT Special Interest Group of the Swiss Informatics Society ETH-Zurich / February 13, Green Data
More informationCooling Solutions & Considerations for High Performance Computers
Cooling Solutions & Considerations for High Performance Computers White Paper 6 Revision 1 By Rich Whitmore Executive summary The recent advances in high performance computing have driven innovations not
More informationDATA CENTER EFFICIENCY: Data Center Temperature Set-point Impact on Cooling Efficiency
DATA CENTER EFFICIENCY: Data Center Temperature Set-point Impact on Cooling Efficiency September 27 th, 2013 Tejas Desai, PE CEM CEA LEED AP Sameer Behere, PE CEM LEED AP Agenda Problem: Quick fixes can
More informationENCLOSURE HEAT DISSIPATION
ENCLOSURE HEAT DISSIPATION DATA CENTER SOLUTIONS A White Paper by Great Lakes Case & Cabinet Company www.werackyourworld.com 814.734.7303 Page 2 Introduction Dangerous heat levels inside an enclosure threaten
More informationEnergy Engineering: Tools and Trends
Energy Engineering: Tools and Trends AEE Northeast Ohio Chapter Meeting March 27, 2008 1 Introduction Background and Experience Energy Engineer for Trane 20 years in HVAC Industry Equipment design and
More informationFREECOOLING, EVAPORATIVE AND ADIABATIC COOLING TECHNOLOGIES IN DATA CENTER. Applications in Diverse Climates within Europe, Middle East and Africa
FREECOOLING, EVAPORATIVE AND ADIABATIC COOLING TECHNOLOGIES IN DATA CENTER Applications in Diverse Climates within Europe, Middle East and Africa Freecooling, Evaporative and Adiabatic Cooling Technologies
More informationASHRAE Data Center Standards: An Overview
Mission Critical Facilities ASHRAE Data Center Standards: An Overview 10012 North Dale Mabry Highway Suite 109 Tampa, FL 33618 813-792-6009 www.pergravis.com Presenter: Steve Ritzi, CDCE Pergravis is a
More informationEnergy Logic: Emerson Network Power. A Roadmap for Reducing Energy Consumption in the Data Center. Ross Hammond Managing Director
Energy Logic: A Roadmap for Reducing Energy Consumption in the Data Center Emerson Network Power Ross Hammond Managing Director Agenda Energy efficiency Where We Are Today What Data Center Managers Are
More informationData Center Trends: How the Customer Drives Industry Advances and Design Development
Bablu Kazi, PE MORRISON HERSHFIELD MISSION CRITICAL Data Center Trends: How the Customer Drives Industry Advances and Design Development What does the Customer Need? Scalability P U E Latest Technology
More informationECOBAY: Closed loop water cooled server cabinet for data centers
ECOBAY: Closed loop water cooled server cabinet for data centers ELECTRONICS MANUFACTURING SERVICES Communications Computing Multimedia & Consumer Industrial & Semiconductor Defense & Aerospace Medical
More informationFundamentals of CFD and Data Center Cooling Amir Radmehr, Ph.D. Innovative Research, Inc.
Minneapolis Symposium September 30 th, 2015 Fundamentals of CFD and Data Center Cooling Amir Radmehr, Ph.D. Innovative Research, Inc. radmehr@inres.com Learning Objectives 1. Gain familiarity with Computational
More informationTWO FINANCIAL IMPACT STUDIES. Seal IT Equipment Cabinets for Significant Annual Cost Savings and Simple Payback in a Few Short Months
TWO FINANCIAL IMPACT STUDIES Seal IT Equipment Cabinets for Significant Annual Cost Savings and Simple Payback in a Few Short Months TWO FINANCIAL IMPACT STUDIES Seal IT Equipment Cabinets for Significant
More informationLANL High Performance Computing Facilities Operations. Rick Rivera and Farhad Banisadr. Facility Data Center Management
Slide-1 LANL High Performance Computing Facilities Operations Rick Rivera and Farhad Banisadr Facility Data Center Management Division Slide-2 Outline Overview - LANL Computer Data Centers Power and Cooling
More informationNext Generation Cooling
Next Generation Cooling Server Manufacturer Perspective Practical and Cost Effective David Moss Data Center Strategist Dell 1 Why Chip, Row, or Rack? Density? Energy Don t be scared; I don t see 50kW/rack
More informationResults of Study Comparing Liquid Cooling Methods
School of Mechanical Engineering FACULTY OF ENGINEERING Results of Study Comparing Liquid Cooling Methods Dr Jon Summers (J.L.Summers@Leeds.Ac.UK) Institute of ThermoFluids (itf) 54th HPC User Forum, September
More informationCurrent Data Center Design. James Monahan Sept 19 th 2006 IEEE San Francisco ComSoc
Current Data Center Design James Monahan Sept 19 th 2006 IEEE San Francisco ComSoc What is the biggest facility problem in your data center? 35% 30% 25% 20% 15% Series1 10% 5% 0% Excessive heat Insufficient
More informationData centers control: challenges and opportunities
1 Data centers control: challenges and opportunities Damiano Varagnolo Luleå University of Technology Aug. 24th, 2015 First part: what is a datacenter and what is its importance in our society Data centers
More informationUsing ASHRAE s Books to Save Energy. Presented by Don Beaty President DLB Associates ASHRAE Technical Committee TC 9.9
Using ASHRAE s Books to Save Energy Presented by Don Beaty President DLB Associates ASHRAE Technical Committee TC 9.9 1 Agenda Opening Comments Part 1 Introduction Part 2 TIPS 1 to 8 Closing Comments 2
More informationSurvey Highlights Need for Better Server Energy Efficiency
Survey Highlights Need for Better Server Energy Efficiency DATA CENTER INEFFICIENCIES RAISE IT COSTS AND RISKS CIOs and other IT leaders have probably had their fill of hearing from corporate executives
More informationVirtualization and consolidation
Virtualization and consolidation Choosing a density strategy Implementing a high-density environment Maximizing the efficiency benefit Anticipating the dynamic data center Schneider Electric 1 Topical
More informationNREL Validates LCS Technology. PRESENTED BY Herb Zien CEO, LiquidCool Solutions
NREL Validates LCS Technology PRESENTED BY Herb Zien CEO, LiquidCool Solutions Learning Objectives As much as 40% of data center power is used to circulate air, and fans in a typical 30-megawatt data center
More informationTechnology for Constructing Environmentally Friendly Data Centers and Fujitsu s Approach
Technology for Constructing Environmentally Friendly Data Centers and Fujitsu s Approach Hiroshi Nagazono In recent years, IT devices such as servers have come to have high performance and be highly integrated
More informationReducing Energy Consumption with
Reducing Energy Consumption with Passive Cooling Ian Cathcart, RCDD Technical Support Manager Technical Support Manager Chatsworth Products, Inc. Thermal Management: Mission Critical Data center heat loads
More information<Insert Picture Here> Austin Data Center 6Sigma DC CFD Model
Austin Data Center 6Sigma DC CFD Model Keith Ward Keith Ward Data Center Facilities Engineering and Logistics Design Austin Data Center Statistics - Space Original AT&T Designed and
More informationEvaporative free air cooling technology Providing evaporative free air cooling solutions.
Evaporative free air cooling technology Providing evaporative free air cooling solutions. Creating an effective workspace environment data centre free air cooling technology FreeCool - Evaporative Free
More informationPassive RDHx as a Cost Effective Alternative to CRAH Air Cooling. Jeremiah Stikeleather Applications Engineer
Passive RDHx as a Cost Effective Alternative to CRAH Air Cooling Jeremiah Stikeleather Applications Engineer Passive RDHx as a Cost Effective Alternative to CRAH Air Cooling While CRAH cooling has been
More informationOptimizing Cooling Performance Of a Data Center
ASHRAE www.ashrae.org. Used with permission from ASHRAE Journal. This article may not be copied nor distributed in either paper or digital form without ASHRAE s permission. For more information about ASHRAE,
More information18 th National Award for Excellence in Energy Management. July 27, 2017
18 th National Award for Excellence in Energy Management July 27, 2017 ICICI Bank, Data Centre, August Hyderabad 30 & 31, 2017 ICICI Bank - Revolution in Digital Banking Over 100,000 Digital POS in 4 months
More informationRunning Your Data Center Under Ideal Temperature Conditions
TECHNICAL BRIEF Mastering Data Center Environmental Controls to Help Drive Your Bottom Line Running Your Data Center Under Ideal Temperature Conditions Challenge Many data centers waste energy using inefficient
More informationA Data Center Heat Removal System That Saves... 80% Discover Inertech s Award-winning Data Center Heat Removal System
A Data Center Heat Removal System That Saves... Infrastructure Power Water up to 40% up to 80% up to 85% Discover Inertech s Award-winning Data Center Heat Removal System A Cool Solution; A Breakthrough
More informationHow High Temperature Data Centers & Intel Technologies save Energy, Money, Water and Greenhouse Gas Emissions
Intel Intelligent Power Management Intel How High Temperature Data Centers & Intel Technologies save Energy, Money, Water and Greenhouse Gas Emissions Power savings through the use of Intel s intelligent
More informationWhere s the Heat Coming From. Leland Sparks Global Account Technical Consultant Belden
Where s the Heat Coming From Leland Sparks Global Account Technical Consultant Belden What is the greatest DC challenge you face? Air Flow to Heat Load Relation Server Inlet Fans Chips Outlet LOAD Dell
More informationUsing CFD Analysis to Predict Cooling System Performance in Data Centers Ben Steinberg, P.E. Staff Applications Engineer
Using CFD Analysis to Predict Cooling System Performance in Data Centers Ben Steinberg, P.E. Staff Applications Engineer Agenda What is CFD? Applications of CFD Applicability to the Data Center How it
More informationSMART SOLUTIONS TM INTELLIGENT, INTEGRATED INFRASTRUCTURE FOR THE DATA CENTER
SMART SOLUTIONS TM INTELLIGENT, INTEGRATED INFRASTRUCTURE FOR THE DATA CENTER Enabling Tomorrow s CRITICAL EDGE INFRASTRUCTURE We helped some of the largest names in the industry bring new capacity online
More informationReclaim Wasted Cooling Capacity Now Updated with CFD Models to Support ASHRAE Case Study Data
White Paper EC9005A Reclaim Wasted Cooling Capacity Now Updated with CFD Models to Support ASHRAE Case Study Data Peer reviewed case study data from ASHRAE now updated with CFD model analysis revealing
More informationWater-Cooling and its Impact on Performance and TCO
Water-Cooling and its Impact on Performance and TCO Matthew T. Ziegler Director, HPC and AI WW BU System Strategy and Architecture mziegler@lenovo.com 2016 Lenovo Internal. All rights reserved. 1 Agenda
More informationGoogle s Green Data Centers: Network POP Case Study
Google s Green Data Centers: Network POP Case Study Table of Contents Introduction... 2 Best practices: Measuring. performance, optimizing air flow,. and turning up the thermostat... 2...Best Practice
More informationThe End of Redundancy. Alan Wood Sun Microsystems May 8, 2009
The End of Redundancy Alan Wood Sun Microsystems May 8, 2009 Growing Demand, Shrinking Resources By 2008, 50% of current data centers will have insufficient power and cooling capacity to meet the demands
More informationSolutions for the Crossroads:
Solutions for the Crossroads: Energy Optimization from Plant to Plug Aaron Davis, Chief Marketing Officer Philippe Delorme, EVP Strategy & Innovation Solutions of the past are simply not sufficient for
More informationApplication of TileFlow to Improve Cooling in a Data Center
Case Study Application of TileFlow to Improve Cooling in a Data Center 3025 Harbor Lane North, Suite 300 Plymouth, MN 55447 USA Copyright 2004 Innovative Research, Inc. 2 Introduction A large insurance
More informationINNOVATE DESIGN APPLY.
INNOVATE DESIGN APPLY By A whole new cooling experience The Motivair ChilledDoor Rack Cooling System targets the critical cooling requirements of today s modern server rack designs. As technology continues
More informationData Center Design and. Management. Steve Knipple. August 1, CTO / VP Engineering & Operations
Data Center Design and Energy Management Steve Knipple CTO / VP Engineering & Operations August 1, 2013 Agenda Introduction to EasyStreet Speaker Bio EasyStreet Sustainability Data Center 1 (Retrofit completed
More informationINNOVATE DESIGN APPLY.
INNOVATE DESIGN APPLY By A whole new cooling experience The Motivair ChilledDoor Rack Cooling System targets the critical cooling requirements of today s modern server rack designs. As technology continues
More informationHPC Solutions in High Density Data Centers
Executive Report HPC Solutions in High Density Data Centers How CyrusOne s Houston West data center campus delivers the highest density solutions to customers With the ever-increasing demand on IT resources,
More informationThe Energy Challenge in HPC
ARNDT BODE Professor Arndt Bode is the Chair for Computer Architecture at the Leibniz-Supercomputing Center. He is Full Professor for Informatics at TU Mü nchen. His main research includes computer architecture,
More informationServer room guide helps energy managers reduce server consumption
Server room guide helps energy managers reduce server consumption Jan Viegand Viegand Maagøe Nr. Farimagsgade 37 1364 Copenhagen K Denmark jv@viegandmaagoe.dk Keywords servers, guidelines, server rooms,
More informationProduct Guide. Direct Contact Liquid Cooling Industry leading data center solutions for HPC, Cloud and Enterprise markets.
Product Guide Direct Contact Liquid Cooling Industry leading data center solutions for HPC, Cloud and Enterprise markets. www.coolitsystems.com Phone: +1 403.235.4895 The Future of Data Center Cooling
More informationWhy would you want to use outdoor air for data center cooling?
Dell Fresh Air 2.0: Frequently Asked Questions Achieve improved data center efficiency and powerful enterprise performance you have come to expect from Dell, by deploying Dell Fresh Air hardware. Competitively
More informationHow High-Density Colocation and Enhanced Visibility Improve Business Performance
How High-Density Colocation and Enhanced Visibility Improve Business Performance Steven So Vice President Data Center Business Cloud Business Division NTT Com Asia Limited 11 Sep 2015 NTT Communications
More informationINT 492 : Selected Topic in IT II (Data Center System Design) 3(3-0-6)
INT 492 : Selected Topic in IT II (Data Center Design) 3(3-0-6) การออกแบบระบบศ นย สารสนเทศ Overview The American Society of Heating, Refrigeration and Air-Conditioning Engineers (ASHRAE) Technical Committee
More informationImproving Rack Cooling Performance Using Blanking Panels
Improving Rack Cooling Performance Using Blanking By Neil Rasmussen White Paper #44 Revision 1 Executive Summary Unused vertical space in open frame racks and rack enclosures creates an unrestricted recycling
More informationCLOSE CONTROL AIR CONDITIONERS DATA CENTERS DESIGN SIDE NOTES
CLOSE CONTROL AIR CONDITIONERS DATA CENTERS DESIGN SIDE NOTES DATA CENTER NEEDS A MINUTE IN THE LIFE OF INTERNET Evolving technology has created the necessity for ever greater exchange of data, increasing
More informationWhite Paper - Infrastructure in an energy-efficient data centre
White Paper - Infrastructure in an energy-efficient data centre Verena Schwalfenberg Dipl.-Ing. Markus Schmidt Copyright 2008 All rights reserved. Rittal GmbH & Co. KG Auf dem Stützelberg D-35745 Herborn
More informationReliable Power and Thermal Management in The Data Center
Reliable Power and Thermal Management in The Data Center Deva Bodas Corporation April 19, 2004 Deva.Bodas@.com 1 Agenda 2 Data center manageability challenges & trends Current state of power & thermal
More informationA) Differences between Precision and Comfort Cooling Here are the major differences exist between precision air conditioning and comfort systems.
DATA CENTRE COOLING SYSTEM A) Differences between Precision and Comfort Cooling Here are the major differences exist between precision air conditioning and comfort systems. 1. Cooling Optimized to Electronic
More informationPlanning for Liquid Cooling Patrick McGinn Product Manager, Rack DCLC
Planning for Liquid Cooling -------------------------------- Patrick McGinn Product Manager, Rack DCLC February 3 rd, 2015 Expertise, Innovation & Delivery 13 years in the making with a 1800% growth rate
More informationDigital Realty Data Center Solutions Digital Chicago Datacampus Franklin Park, Illinois Owner: Digital Realty Trust Engineer of Record: ESD Architect
Digital Realty Data Center Solutions Digital Chicago Datacampus Franklin Park, Illinois Owner: Digital Realty Trust Engineer of Record: ESD Architect of Record: SPARCH Project Overview The project is located
More informationRF Code Delivers Millions of Dollars in Annual Power & Cooling Savings for CenturyLink
INDUSTRIAL INTERNET IN ACTION CASE STUDY RF Code Delivers Millions of Dollars in Annual Power & Cooling Savings for CenturyLink CLIENT PROFILE CenturyLink Technology Solutions is the second largest telecommunications
More informationSystems and Technology Group. IBM Technology and Solutions Jan Janick IBM Vice President Modular Systems and Storage Development
Systems and Technology Group IBM Technology and Solutions Jan Janick IBM Vice President Modular Systems and Storage Development Power and cooling are complex issues There is no single fix. IBM is working
More information