Moving Containment Inside the Enclosure. Jeff Markle Great Lakes Case & Cabinet

Size: px
Start display at page:

Download "Moving Containment Inside the Enclosure. Jeff Markle Great Lakes Case & Cabinet"

Transcription

1 Moving Containment Inside the Enclosure Presented by Jeff Markle Great Lakes Case & Cabinet

2 Containment Containment : To put constraint upon; to restrain; to confine; to keep within bounds Containment in the data center is the isolation of conditioned air (hot or cold) The goal is to increase cooling efficiency, to ensure proper operational temperature of equipment, reduce operating costs, minimize the risk of down time or strains on the systems

3 Data Center - Worst Practices Hot Aisle / Cold Aisle Heat exhaust recirculation Heat exhaust recirculation Heat exhaust recirculation 85 F 29% Rh 60 F Perforated tile in hot aisle 70% Rh Perforated tile in hot aisle Uncontained Air Flow Paths - inefficient Rear cable cut outs Rear cable cut outs

4 Covering the Basics Preventing Bypass Seal the Gaps, for Conditioned Air Raised Floor Cable Access Grommets (qty-9 cut outs 8 x8 = one floor tile) Brush Grommet Kit Tool less Filler Panels Sealing access-holes in raised floor Maintains static pressure in raised floor and reduces amount of particulate build-up under raised floor Filler / Blanking Panels prevents re-circulation and by-pass air within the enclosure above & below the equipment Brush Grommet Kits Prevents by-pass airflow around the equipment within the enclosure by sealing the rails to the side panels & still have cable access

5 Airflow paths internal & external, with no Hot & Cold Air separation. No Aisle Containment options, Mesh Front door, where 30% of the door is still blocked Hot Air Returns are in the cold aisle Has to cool 28 cubic feet of air per cabinet before being drawn into enclosure by equipment.

6 ASHRAE TC9.9 New 2008 Recommended Environmental Envelope Version 2008 Version Low End Temp. 68 F (20 C) 64.4 F (18 C) High End Temp. 77 F (25 C) 80.6 F (27 C) Low end Moisture 40% RH 41.9 F D.P. (5.5 C) High End Moisture 55% RH 60% RH & 59 F D.P. (15 C) Allows you to raise your Temp. set point = cost reductions only when measures are taken to eliminate recirculation / bypass air flow

7 Standard Hot Aisle / Cold Aisle Front & Rear Vented Doors (Optional fan assisted.) F in Cold Aisle F at server intake F at server exhaust Approx.: 4 6 kw load / enclosure 1050 CFM thru the enclosure Recirculation from exhaust back to the intake causing the CRAC units to be less efficient as they have to cool all of the white space first

8 Containment There are a wide variety of products which offer containment across aisles, panels which mount to the top of the enclosures and containment curtains which hang from the ceiling * Sourced from InfoWorld.com

9 Containment Cold Aisle Contained with uncontained Hot Air return back to CRAC units

10 Containment Contained Cold Aisle Ducted hot air return to CRAC units via plenum and down flow chimneys. All air flow is separated but why build a room within a room?

11 Cold Aisle Containment / Ducted Exhaust Key Design Features: Concrete slab floor = save cost on raised floor & installation Overhead down draft Cold Aisle air delivery Ducted Exhaust back to CRAC unit. Passive Enc. Systems = no fan assist Overhead power & data, Cable management * Sourced from Computerworld.com

12 Ducted Exhaust is a form of Hot Aisle Containment. Standard Cold Aisle / Ducted Exhaust Front Vented Door / Solid Rear Door (Optional fan assisted) F in the Raised Floor F in Cold Aisle F at server intake F at server exhaust Approx.: 5-7 kw load / enclosure The return air temp is increased which increases the CRAC unit efficiency. The white space of the room does not get heated from the Hot aisle recirculation. Therefore the CRAC unit can run at a higher set point temperature (cost savings) and still achieve the same Cold Aisle temps Still have to cool the entire Cold Aisle before cooling the equipment

13 Containment moved into the enclosure via Air Manager & Chimney Data Center utilizing Chimney and Air Manager solution Air grates in floor are only for the comfort cooling of personnel working in the space Facility uses Air Side Economizers; freecooling and runs 90% on outside air Equipment is mixed Avaya, EMC, Dell, HP and Foundry Ducted return is Ducted return is plumbed back into facility HVAC for additional overall efficiency

14 Heat Load Dissipation of the Enclosure within a Data Center is directly Dependent upon the Cooling Capacity of the CRAC units and Method of the Delivery & Return Airflow. Cooling Efficiency is related to the separation of the Conditioned Air from the Hot Exhaust by various methods based upon the specific Data Center Environment. Also the elimination of Bypass Airflow of the Conditioned air will increase Cooling Efficiency. Air Manager (1 RMU) kw ratings are dependent upon the Data Center CRAC units in a Passive System Localized Optional Rack Fans can be installed for a Active System

15 Enclosure based Containment Plenum Air Manager / Ducted Exhaust Front Vented Door / Solid Rear Door F in white space (Optional fan assisted) F at server intake F at server exhaust Approx.: 8-12 kw load / enclosure The return air temp is increased which increases the CRAC unit efficiency. The white space of the room does not get heated from the Hot aisle recirculation. Therefore the CRAC unit can run at a higher set point temperature (cost savings) & still achieve the same Cold Aisle temps Less perf tiles are required to cool the white space only. The intake air is forced through an adjustable Air Manager directly from the CRAC Having an adjustable opening allows the raised floor pressure to be maintained throughout the Data Center Less perf tiles required = cost savings

16 AIR MANAGER Manages available conditioned air by directing it to the front of the equipment mounted within the enclosure. (Adjustability from 0-100%; uses bottom 1 RMU) Does not interfere with rear bottom cable access 42 & 48 deep enclosures

17 Rear view of enclosures; Ducted Return Typically would contain hot aisle with mesh doors for exhaust F in Aisle Spaces F 85 degree measured at chimney intake 2000 sq. ft. room, (2) 26 ton CRAC units Air side Economizers 8 to 10 kw load per Rack (208, 3 phase)

18 Rear View shows cable management does not interfere with exhaust airflow Zero U side EIA mounting. provides more networking mounting while not restricting exhaust air flow.

19 Uncontained Cold Aisle Cold Aisle in a cabinet based containment solution.

20 Containment via Ducting Ducted Intake / Ducted Exhaust Solid Front Door / Solid Rear Door F in white space 60 F at server intake F at server exhaust Approx.: 15 plus Kw. load / enclosure The return air temp is increased which increases the CRAC unit efficiency. The white space of the room does not get heated from the Hot aisle recirculation. Therefore the CRAC unit can run at a lower setting (cost savings) & achieve greater efficiency Even less perf tiles are required to cool the white space only. The intake air is completely contained and is able to be adjusted at the CRAC unit level This concept can be done on slab floor as well.

21 Containment via a Closed Loop Water Cooled System Closed-Loop Water-Cooled Enclosure 84 H x30 W x55 D : 30kW Capacity Manufactured as a specialty enclosure or an aftermarket accessory designed for installation in standard product CFM 30kW, 40 F T N+1 Variable Speed fans Offers a complete closed loop solution where heat is extracted from the rear of the enclosure via fans and channeled via a plenum to a heat exchanger mounted in the bottom of the enclosure. Cold water not only serves as a heat sink but as the fans drive the air across the heat exchanger, it becomes cooled and is then forced up a plenum chamber in the front of the enclosure to deliver conditioned air to the front of the servers and equipment mounted in the enclosure.

22 Cooling Considerations Closed-Loop Water- Cooled Enclosure 84 H x 30 W x 55 D 30kW Capacity

23 Cooling Considerations A Variable Density Closed Loop Water Cooled Solution Rack Size Heat Exchanging Unit (center). Up to 30kW cooling capacity divided equally across the Equipment Racks Chilled Air delivered via Plinth & Air Manager accessories Warm Exhaust Air return via Ducted Chimneys

24 Cooling Considerations A Variable Density Closed Loop Water Cooled Solution

25 Cooling Considerations A Variable Density Closed Loop Water Cooled Solution

26 A Variable Density Closed Loop Water Cooled Solution

27 Cooling Considerations A Variable Density Closed Loop Water Cooled Solution Allows for Greater Density in Minimum Space.

28 Key Points The enclosure must be an integral part of the Data Center design. It must not be thought of as an accessory to be purchased after the Data Center is designed or constructed. The goal of enclosure based containment is to cool the equipment first, not the Data Center floor space then the equipment second. You wouldn t try to cool the soda sitting on the kitchen counter by maximizing the air conditioner in your house. You would put it in the refrigerator! Thank you!

Data Center Enclosures Best Practices. Maximize the Efficiency of the Enclosure within a Data Center

Data Center Enclosures Best Practices. Maximize the Efficiency of the Enclosure within a Data Center Data Center Enclosures Best Practices Maximize the Efficiency of the Enclosure within a Data Center Things to ask before selecting Enclosures: Primary Use Severs or Patching, or both determines size. RMU

More information

Where s the Heat Coming From. Leland Sparks Global Account Technical Consultant Belden

Where s the Heat Coming From. Leland Sparks Global Account Technical Consultant Belden Where s the Heat Coming From Leland Sparks Global Account Technical Consultant Belden What is the greatest DC challenge you face? Air Flow to Heat Load Relation Server Inlet Fans Chips Outlet LOAD Dell

More information

ENCLOSURE HEAT DISSIPATION

ENCLOSURE HEAT DISSIPATION ENCLOSURE HEAT DISSIPATION DATA CENTER SOLUTIONS A White Paper by Great Lakes Case & Cabinet Company www.werackyourworld.com 814.734.7303 Page 2 Introduction Dangerous heat levels inside an enclosure threaten

More information

Variable Density, Closed-Loop, Water-Cooled Data Center Solution

Variable Density, Closed-Loop, Water-Cooled Data Center Solution Variable Density, Closed-Loop, Water-Cooled Data Center Solution Overview Great Lakes Case & Cabinet Co., Inc. has worked with Naissus Thermal Management Solutions, of Toronto, Ontario to develop one of

More information

A Green Approach. Thermal

A Green Approach. Thermal A Green Approach to Thermal Management Thermal Management - AGENDA Definitions & Thermal Facts Density Trends Rack Level Management Passive Solutions Thermal Sources & Green Solutions Data Center Layout

More information

Power and Cooling for Ultra-High Density Racks and Blade Servers

Power and Cooling for Ultra-High Density Racks and Blade Servers Power and Cooling for Ultra-High Density Racks and Blade Servers APC White Paper #46 Richard L. Sawyer Director of Data Center Technology American Power Conversion Company 2005 APC corporation What has

More information

Reducing Energy Consumption with

Reducing Energy Consumption with Reducing Energy Consumption with Passive Cooling Ian Cathcart, RCDD Technical Support Manager Technical Support Manager Chatsworth Products, Inc. Thermal Management: Mission Critical Data center heat loads

More information

Recapture Capacity for Existing. and Airflow Optimization

Recapture Capacity for Existing. and Airflow Optimization Recapture Capacity for Existing Data Centers Through Cooling and Airflow Optimization Introduction Challenges and Trends Agenda Cooling & Airflow Optimization Takeaways Learning Objectives Recognize opportunities

More information

Reclaim Wasted Cooling Capacity Now Updated with CFD Models to Support ASHRAE Case Study Data

Reclaim Wasted Cooling Capacity Now Updated with CFD Models to Support ASHRAE Case Study Data White Paper EC9005A Reclaim Wasted Cooling Capacity Now Updated with CFD Models to Support ASHRAE Case Study Data Peer reviewed case study data from ASHRAE now updated with CFD model analysis revealing

More information

Current Data Center Design. James Monahan Sept 19 th 2006 IEEE San Francisco ComSoc

Current Data Center Design. James Monahan Sept 19 th 2006 IEEE San Francisco ComSoc Current Data Center Design James Monahan Sept 19 th 2006 IEEE San Francisco ComSoc What is the biggest facility problem in your data center? 35% 30% 25% 20% 15% Series1 10% 5% 0% Excessive heat Insufficient

More information

Data center solutions for successful companies Cooling solutions

Data center solutions for successful companies Cooling solutions Data center solutions for successful companies Cooling solutions WeRackYourWorld.com great lakes cooling solutions Power and cooling are of prime importance to anyone working in a data center. As information

More information

Avoidable Mistakes that Compromise Cooling Performance in Data Centers and Network Rooms

Avoidable Mistakes that Compromise Cooling Performance in Data Centers and Network Rooms Avoidable Mistakes that Compromise Cooling Performance in Data Centers and Network Rooms Problem Several cooling system mistakes are very common and avoidable Mistakes compromise availability and increase

More information

Mission Critical Facilities & Technology Conference November 3, 2011 Cooling 101. Nick Gangemi Regional Sales Manager Data Aire

Mission Critical Facilities & Technology Conference November 3, 2011 Cooling 101. Nick Gangemi Regional Sales Manager Data Aire Mission Critical Facilities & Technology Conference November 3, 2011 Cooling 101 Nick Gangemi Regional Sales Manager Data Aire Agenda Exactly what are we talking about ASHRAE TC 9.9 Design best practices

More information

1.866.TRY.GLCC WeRackYourWorld.com

1.866.TRY.GLCC WeRackYourWorld.com cool it. 1.866.TRY.GLCC WeRackYourWorld.com In order to maximize space in the data center and accommodate for increased data, rack-mount enclosures are becoming populated with high-density servers and

More information

Cooling on Demand - scalable and smart cooling solutions. Marcus Edwards B.Sc.

Cooling on Demand - scalable and smart cooling solutions. Marcus Edwards B.Sc. Cooling on Demand - scalable and smart cooling solutions Marcus Edwards B.Sc. Schroff UK Limited Data Centre cooling what a waste of money! A 1MW data center needs 177,000,000 kwh in its lifetime of 10

More information

High Tech Getting Too Hot? High Density Environments Require A Different Cooling Approach

High Tech Getting Too Hot? High Density Environments Require A Different Cooling Approach High Tech Getting Too Hot? High Density Environments Require A Different Cooling Approach Proper airfl ow and thermal management are the most critical aspects of designing and operating your data center,

More information

Reducing Data Center Cooling Costs through Airflow Containment

Reducing Data Center Cooling Costs through Airflow Containment FEATURE Reducing Data Center Cooling Costs through Airflow Containment Implementing a containment solution in the data center costs much less than the alternatives of adding air handlers or other supplemental

More information

Impact of Air Containment Systems

Impact of Air Containment Systems White Paper June 2012 WP-20 Impact of Air Containment Systems Reducing Energy Consumption Introduction: The Importance of Maintaining Data Center Cooling Energy Efficiency Data centers are mission-critical

More information

Thermal management. Thermal management

Thermal management. Thermal management Thermal management Thermal management Managing thermal loads is a major challenge for all Data Centre operators. Effecting proper control of the thermal environment drives energy consumption and ultimately

More information

Great Lakes Product Solutions for Cisco Catalyst and Catalyst Switches: ESSAB14D Baffle for Cisco Catalyst 9513 Switch

Great Lakes Product Solutions for Cisco Catalyst and Catalyst Switches: ESSAB14D Baffle for Cisco Catalyst 9513 Switch Great Lakes Product Solutions for Cisco Catalyst and Catalyst Switches: ESSAB14D Baffle for Cisco Catalyst 9513 Switch Great Lakes Product Solutions for Cisco Catalyst and Catalyst Switches Table of Contents

More information

Effectiveness and Implementation of Modular Containment in Existing Data Centers

Effectiveness and Implementation of Modular Containment in Existing Data Centers WHITE PAPER Effectiveness and Implementation of Modular Containment in Existing Data Centers By Lars Strong, P.E., Upsite Technologies, Inc. Bruce Long, Upsite Technologies, Inc. 505.798.0200 upsite.com

More information

AisleLok Modular Containment vs. Legacy Containment: A Comparative CFD Study of IT Inlet Temperatures and Fan Energy Savings

AisleLok Modular Containment vs. Legacy Containment: A Comparative CFD Study of IT Inlet Temperatures and Fan Energy Savings WHITE PAPER AisleLok Modular Containment vs. : A Comparative CFD Study of IT Inlet Temperatures and Fan Energy Savings By Bruce Long, Upsite Technologies, Inc. Lars Strong, P.E., Upsite Technologies, Inc.

More information

<Insert Picture Here> Austin Data Center 6Sigma DC CFD Model

<Insert Picture Here> Austin Data Center 6Sigma DC CFD Model Austin Data Center 6Sigma DC CFD Model Keith Ward Keith Ward Data Center Facilities Engineering and Logistics Design Austin Data Center Statistics - Space Original AT&T Designed and

More information

Fundamentals of CFD and Data Center Cooling Amir Radmehr, Ph.D. Innovative Research, Inc.

Fundamentals of CFD and Data Center Cooling Amir Radmehr, Ph.D. Innovative Research, Inc. Minneapolis Symposium September 30 th, 2015 Fundamentals of CFD and Data Center Cooling Amir Radmehr, Ph.D. Innovative Research, Inc. radmehr@inres.com Learning Objectives 1. Gain familiarity with Computational

More information

Rittal White Paper 506: Cold Aisle Containment for Improved Data Center Cooling Efficiency By: Daniel Kennedy

Rittal White Paper 506: Cold Aisle Containment for Improved Data Center Cooling Efficiency By: Daniel Kennedy Rittal White Paper 506: Cold Aisle Containment for Improved Data Center Cooling Efficiency By: Daniel Kennedy Executive Summary Increasing power requirements for new servers have created the need to support

More information

Air Containment Design Choices and Considerations

Air Containment Design Choices and Considerations Air Containment Design Choices and Considerations Brad J. Murphy, A.Sc.T., ATS, DCDC, DCEP, Principal Racon Data Centres Introduction Introduction Air containment design must consider many different factors

More information

Rittal Cooling Solutions A. Tropp

Rittal Cooling Solutions A. Tropp 1 Rittal Cooling Solutions Presented by Adam Tropp 2 Agenda Cooling Strategies Aisle Containment Chimney Solution Airstream Management Rittal Liquid Cooling Packages Data Monitoring 3 Cooling strategies.

More information

A) Differences between Precision and Comfort Cooling Here are the major differences exist between precision air conditioning and comfort systems.

A) Differences between Precision and Comfort Cooling Here are the major differences exist between precision air conditioning and comfort systems. DATA CENTRE COOLING SYSTEM A) Differences between Precision and Comfort Cooling Here are the major differences exist between precision air conditioning and comfort systems. 1. Cooling Optimized to Electronic

More information

To Fill, or not to Fill Get the Most out of Data Center Cooling with Thermal Blanking Panels

To Fill, or not to Fill Get the Most out of Data Center Cooling with Thermal Blanking Panels To Fill, or not to Fill Get the Most out of Data Center Cooling with Thermal Blanking Panels The use of a hot aisle/cold aisle configuration in the data center has long been considered a best practice

More information

Reverse Flow Cabinet. ContraFlo Cabinet. Reverse Flow Cabinet for Raised Floor Data Centers

Reverse Flow Cabinet. ContraFlo Cabinet. Reverse Flow Cabinet for Raised Floor Data Centers Reverse Flow Cabinet ContraFlo Cabinet Reverse Flow Cabinet for Raised Floor Data Centers ContraFlo TM Cabinet Reverse Flow Cabinet The ContraFlo cabinet turns airflow upside down to offer an alternative

More information

COOLING SOLUTIONS. SmartRack Close-Coupled Cooling for IT Environments

COOLING SOLUTIONS. SmartRack Close-Coupled Cooling for IT Environments COOLING SOLUTIONS SmartRack Close-Coupled Cooling for IT Environments Efficient, flexible, manageable cooling reduces costs and simplifies installation. Efficient, flexible, manageable cooling for IT environments

More information

APC APPLICATION NOTE #74

APC APPLICATION NOTE #74 #74 Configuration of InfraStruXure for Data Centers to Support Dell PowerEdge 1855 Abstract Many companies are making plans to incorporate Dell PowerEdge Blade Servers into their data center applications.

More information

Introducing the Heat Wheel to the Data Center

Introducing the Heat Wheel to the Data Center Introducing the Heat Wheel to the Data Center Robert (Dr. Bob) Sullivan, Ph.D. Data Center Infrastructure Specialist KyotoCooling International Critical Facilities Round Table 1 A New Free Cooling Technique

More information

Evaporative free air cooling technology Providing evaporative free air cooling solutions.

Evaporative free air cooling technology Providing evaporative free air cooling solutions. Evaporative free air cooling technology Providing evaporative free air cooling solutions. Creating an effective workspace environment data centre free air cooling technology FreeCool - Evaporative Free

More information

Design and Installation Challenges: Aisle Containment Systems

Design and Installation Challenges: Aisle Containment Systems Design and Installation Challenges: Aisle Containment Systems 1 We all know the Benefits of Containment 1. Reduces Total Cost of Data Center Ownership 2. Eliminates hot spots 3. Supports higher heat and

More information

ENCLOSURE THERMAL TESTING HEAT REMOVAL IN THE REAL WORLD

ENCLOSURE THERMAL TESTING HEAT REMOVAL IN THE REAL WORLD R I T T A L T H E R M A L S E R I E S ENCLOSURE THERMAL TESTING HEAT REMOVAL IN THE REAL WORLD FRIEDHELM L O H GROUP I. INTRODUCTION As a leading manufacturer of enclosure solutions, Rittal is frequently

More information

Ten Cooling Solutions to Support High-density Server Deployment. Schneider Electric Data Center Science Center White Paper #42

Ten Cooling Solutions to Support High-density Server Deployment. Schneider Electric Data Center Science Center White Paper #42 Ten Cooling Solutions to Support High-density Server Deployment Schneider Electric Data Center Science Center White Paper #42 1 Introduction 2 Introduction This paper provides 10 approaches for increasing

More information

EF-Series EuroFrame Gen 2 Cabinet System

EF-Series EuroFrame Gen 2 Cabinet System Protecting your technology investment. EF-Series EuroFrame Gen 2 Cabinet System The new generation of EF-Series EuroFrame Cabinet is a reliable and economical cabinet solution that supports rack-mount

More information

Ten Cooling Solutions to Support High- Density Server Deployment

Ten Cooling Solutions to Support High- Density Server Deployment Ten Cooling Solutions to Support High- Density Server Deployment By Peter Hannaford White Paper #42 Revision 2 Executive Summary High-density servers offer a significant performance per watt benefit. However,

More information

MSYS 4480 AC Systems Winter 2015

MSYS 4480 AC Systems Winter 2015 MSYS 4480 AC Systems Winter 2015 Module 12: DATA CENTERS By Satwinder Singh 14/05/2015 1 Data Centers Data Centers are specialized environments that safeguard your company's most valuable equipment and

More information

CFD Modeling of an Existing Raised-Floor Data Center

CFD Modeling of an Existing Raised-Floor Data Center CFD Modeling of an Existing Raised-Floor Data Center Amir Radmehr 1, Brendan Noll 2, John Fitzpatrick 2, Kailash Karki 1 1. Innovative Research, Inc. 3025 Harbor Lane N, Suite 300, Plymouth, MN 2. University

More information

HIGHLY EFFICIENT COOLING FOR YOUR DATA CENTRE

HIGHLY EFFICIENT COOLING FOR YOUR DATA CENTRE HIGHLY EFFICIENT COOLING FOR YOUR DATA CENTRE Best practices for airflow management and cooling optimisation DC ASSESSMENT SERVICES AISLE CONTAINMENT AIRFLOW MANAGEMENT Achieving true 24/7/365 operation

More information

Next Generation Cooling

Next Generation Cooling Next Generation Cooling Server Manufacturer Perspective Practical and Cost Effective David Moss Data Center Strategist Dell 1 Why Chip, Row, or Rack? Density? Energy Don t be scared; I don t see 50kW/rack

More information

Energy Efficient Data Centers

Energy Efficient Data Centers IBM Systems and Technology Group Lab Services Energy Efficient Data Centers Steven Ahladas IBM Corp ahladas@us.ibm.com Keeping our clients in the race. All trends going the same way. IT Servers were an

More information

Passive RDHx as a Cost Effective Alternative to CRAH Air Cooling. Jeremiah Stikeleather Applications Engineer

Passive RDHx as a Cost Effective Alternative to CRAH Air Cooling. Jeremiah Stikeleather Applications Engineer Passive RDHx as a Cost Effective Alternative to CRAH Air Cooling Jeremiah Stikeleather Applications Engineer Passive RDHx as a Cost Effective Alternative to CRAH Air Cooling While CRAH cooling has been

More information

The Energy. David L. Moss Dell Data Center Infrastructure

The Energy. David L. Moss Dell Data Center Infrastructure The Energy Advantages of Containment Systems David L. Moss Dell Data Center Infrastructure www.dell.com/hiddendatacenter Summary The Uptime Institute estimates that the cost to build a new 20,000 square

More information

Data Center Airflow Management Basics: Comparing Containment Systems

Data Center Airflow Management Basics: Comparing Containment Systems WHITE PAPER Data Center Airflow Management Basics: Comparing Containment Systems Edited by David Knapp Product Marketing Manager Published: February 2017 US & Canada +1-800-834-4969 Toronto, Ontario, Canada

More information

Data center cooling evolution. The hottest way to save energy. Lucio Bustaffa: Product Development Manager BlueBox Group

Data center cooling evolution. The hottest way to save energy. Lucio Bustaffa: Product Development Manager BlueBox Group Data center cooling evolution. The hottest way to save energy Lucio Bustaffa: Product Development Manager BlueBox Group Data Center overview What s happening in the web? 2 Data Center overview What s happening

More information

Containment Accessories Floor Mounting Template

Containment Accessories Floor Mounting Template P R O D U C T A P P L I C AT I O N Frame Supported Hot Aisle Containment (HAC) Solution The Frame Supported Hot Aisle Containment (HAC) Solution by Chatsworth Products (CPI) features a frame supported

More information

Cabinet Level Containment. IsoFlo Cabinet. Isolated Airfl ow Cabinet for Raised Floor Data Centers

Cabinet Level Containment. IsoFlo Cabinet. Isolated Airfl ow Cabinet for Raised Floor Data Centers Cabinet Level Containment IsoFlo Cabinet Isolated Airfl ow Cabinet for Raised Floor Data Centers IsoFlo Cabinet Cabinet Level Containment Tate s IsoFlo cabinet completely isolates the IT cooling from the

More information

Google s Green Data Centers: Network POP Case Study

Google s Green Data Centers: Network POP Case Study Google s Green Data Centers: Network POP Case Study Table of Contents Introduction... 2 Best practices: Measuring. performance, optimizing air flow,. and turning up the thermostat... 2...Best Practice

More information

MS Noise 9210 Passive 24U Acoustic Rack

MS Noise 9210 Passive 24U Acoustic Rack MS Noise 9210 Passive 24U Acoustic Rack Acoustic Server Rack Enclosure with Silent Self-Venting Design The MSCT range of quiet rack enclosures has been designed to house noisy 19" rack-mounted equipment,

More information

How to Increase Data Center Efficiency

How to Increase Data Center Efficiency How to Increase Data Center Efficiency Shivani Shukla Potkar Product Marketing Manager Pentair Electronics Protection High cooling efficiency & and reduced power consumption enhances the balance between

More information

Using CFD Analysis to Predict Cooling System Performance in Data Centers Ben Steinberg, P.E. Staff Applications Engineer

Using CFD Analysis to Predict Cooling System Performance in Data Centers Ben Steinberg, P.E. Staff Applications Engineer Using CFD Analysis to Predict Cooling System Performance in Data Centers Ben Steinberg, P.E. Staff Applications Engineer Agenda What is CFD? Applications of CFD Applicability to the Data Center How it

More information

Improving Data Center Efficiency

Improving Data Center Efficiency Improving Data Center Efficiency Controlling Bypass Airflow in your Data Center Bypass airflow can have a significant impact on the cooling capacity and efficiency of any data center. One key part of

More information

Data Centre Products. Airflow Management Solutions

Data Centre Products. Airflow Management Solutions Data Centre Products Airflow Management Solutions Computational Fluid Dynamics (CFD) model of an optimised data centre illustrating cold-aisle isolation and Eaton s Heat Containment System (HCS). See CFD

More information

APC APPLICATION NOTE #146

APC APPLICATION NOTE #146 #146 Hot Aisle Containment Application Guidelines and Approved Configurations By Kevin Lemke Abstract The Hot Aisle Containment System (HACS) is a modular ceiling panel and door system for use in isolating

More information

Liebert DCW CATALOGUE

Liebert DCW CATALOGUE Liebert DCW CATALOGUE Chilled Water-Based High Density Cooling For The Data Center LIEBERT DCW Flexible Approaches For Energy Efficient Cooling Save up to 70% in cooling energy usage Data center managers

More information

MS Noise 9210 Active 24U Acoustic Rack

MS Noise 9210 Active 24U Acoustic Rack MS Noise 9210 Active 24U Acoustic Rack Acoustic Server Rack Enclosure with Assisted Cooling The MSCT range of quiet rack enclosures has been designed to house noisy 19" rack-mounted equipment, such as

More information

The Four 4R s. of Data Center Airflow Management. About Upsite Technologies

The Four 4R s. of Data Center Airflow Management. About Upsite Technologies About Upsite Technologies Upsite Technologies, Inc., a pioneer, and industry thought leader specializing in data center airflow management, provides a full suite of products and services designed to enable

More information

Combining Cold Aisle Containment with Intelligent Control to Optimize Data Center Cooling Efficiency

Combining Cold Aisle Containment with Intelligent Control to Optimize Data Center Cooling Efficiency A White Paper from the Experts in Business-Critical Continuity TM Combining Cold Aisle Containment with Intelligent Control to Optimize Data Center Cooling Efficiency Executive Summary Energy efficiency

More information

Server Room & Data Centre Energy Efficiency. Technology Paper 003

Server Room & Data Centre Energy Efficiency. Technology Paper 003 Technology Paper 003 Server Room & Data Centre Energy Efficiency Workspace Technology Limited Technology House, PO BOX 11578, Sutton Coldfield West Midlands B72 1ZB Telephone: 0121 354 4894 Facsimile:

More information

Rethinking Datacenter Cooling

Rethinking Datacenter Cooling Rethinking Datacenter Cooling www.sempertec.com SemperTec White Paper Rethinking Datacenter Cooling Contents Executive Summary Introduction Air Distribution: Three Cooling Design Considerations Cold Aisle

More information

DATA CENTER EFFICIENCY: Data Center Temperature Set-point Impact on Cooling Efficiency

DATA CENTER EFFICIENCY: Data Center Temperature Set-point Impact on Cooling Efficiency DATA CENTER EFFICIENCY: Data Center Temperature Set-point Impact on Cooling Efficiency September 27 th, 2013 Tejas Desai, PE CEM CEA LEED AP Sameer Behere, PE CEM LEED AP Agenda Problem: Quick fixes can

More information

Application of TileFlow to Improve Cooling in a Data Center

Application of TileFlow to Improve Cooling in a Data Center Case Study Application of TileFlow to Improve Cooling in a Data Center 3025 Harbor Lane North, Suite 300 Plymouth, MN 55447 USA Copyright 2004 Innovative Research, Inc. 2 Introduction A large insurance

More information

Liebert DCW Family Chilled Water-Based High Density Cooling For The Data Center. Precision Cooling For Business-Critical Continuity

Liebert DCW Family Chilled Water-Based High Density Cooling For The Data Center. Precision Cooling For Business-Critical Continuity Liebert DCW Family Chilled Water-Based High Density Cooling For The Data Center Precision Cooling For Business-Critical Continuity Flexible Approaches For Energy Efficient Cooling Save up to 70% in cooling

More information

survey, 71% of respondents listed Improving capacity planning as a top driver for buying DCIM 1.

survey, 71% of respondents listed Improving capacity planning as a top driver for buying DCIM 1. :: In a recent Uptime Institute survey, 71% of respondents listed Improving capacity planning as a top driver for buying DCIM 1. 2 Maintain Assess Control ROI Monitor Optimize The Need for a Better Approach

More information

A LAYMAN S EXPLANATION OF THE ROLE OF IT RACKS IN COOLING YOUR DATA CENTER

A LAYMAN S EXPLANATION OF THE ROLE OF IT RACKS IN COOLING YOUR DATA CENTER A LAYMAN S EXPLANATION OF THE ROLE OF IT RACKS IN COOLING YOUR DATA CENTER By David Moss Dell Data Center Infrastructure dell.com/hiddendatacenter Many people see an IT rack as a glorified shelving system.

More information

Temperature monitoring and CFD Analysis of Data Centre

Temperature monitoring and CFD Analysis of Data Centre Available online at www.sciencedirect.com Procedia Engineering 56 (2013 ) 551 559 5 th BSME International Conference on Thermal Engineering Temperature monitoring and CFD Analysis of Data Centre N.M.S.

More information

TWO FINANCIAL IMPACT STUDIES. Seal IT Equipment Cabinets for Significant Annual Cost Savings and Simple Payback in a Few Short Months

TWO FINANCIAL IMPACT STUDIES. Seal IT Equipment Cabinets for Significant Annual Cost Savings and Simple Payback in a Few Short Months TWO FINANCIAL IMPACT STUDIES Seal IT Equipment Cabinets for Significant Annual Cost Savings and Simple Payback in a Few Short Months TWO FINANCIAL IMPACT STUDIES Seal IT Equipment Cabinets for Significant

More information

Cooling. Highly efficient cooling products for any IT application. For More Information: (866) DATA CENTER SOLUTIONS

Cooling. Highly efficient cooling products for any IT application. For More Information: (866) DATA CENTER SOLUTIONS Cooling > Highly efficient cooling products for any IT application. DATA CENTER SOLUTIONS For More Information: (866) 787-3271 Sales@PTSdcs.com End-to-End Cooling Solutions from the Closet to the Data

More information

One Stop Cooling Solution. Ben Tam Business Development Manager

One Stop Cooling Solution. Ben Tam Business Development Manager One Stop Cooling Solution Ben Tam Business Development Manager Agenda One Stop Cooling Solution Challenges Customers Are Facing Today Rack / Row / Room Solution Keynotes New Product Launch Slide 2 2 One

More information

Close Coupled Cooling for Datacentres

Close Coupled Cooling for Datacentres Close Coupled Cooling for Datacentres Dr Fathi Tarada Mosen Ltd fathi.tarada@mosenltd.com www.mosenltd.com Agenda Increasing Power Densities Raised Floor Limitations Hot and Cold Aisle Enclosures Close

More information

Optimization in Data Centres. Jayantha Siriwardana and Saman K. Halgamuge Department of Mechanical Engineering Melbourne School of Engineering

Optimization in Data Centres. Jayantha Siriwardana and Saman K. Halgamuge Department of Mechanical Engineering Melbourne School of Engineering Optimization in Data Centres Jayantha Siriwardana and Saman K. Halgamuge Department of Mechanical Engineering Melbourne School of Engineering Outline Background and Motivation Overview and scale of data

More information

Data Center Racks. Vantage S2. Enclosure System. Switch N to Eaton.

Data Center Racks. Vantage S2. Enclosure System. Switch N to Eaton. Data Center Racks Vantage S2 Enclosure System Switch N to Eaton. The Lean Data Center Data center managers are constantly moving, adding and changing IT equipment and electrical circuits all while trying

More information

Running Your Data Center Under Ideal Temperature Conditions

Running Your Data Center Under Ideal Temperature Conditions TECHNICAL BRIEF Mastering Data Center Environmental Controls to Help Drive Your Bottom Line Running Your Data Center Under Ideal Temperature Conditions Challenge Many data centers waste energy using inefficient

More information

How to Sell APC s Cisco Approved Solution for Nexus 7018

How to Sell APC s Cisco Approved Solution for Nexus 7018 NetShelter SX Side Airflow Solution for Cisco Nexus 7018 How to Sell APC s Cisco Approved Solution for Nexus 7018 Objectives Explain Sales Strategy for the Side Airflow Solution for Nexus 7018 Explain

More information

Optimizing data centers for high-density computing

Optimizing data centers for high-density computing Optimizing data centers for high-density computing technology brief, 2nd edition Abstract... 2 Introduction... 2 Power consumption and heat load... 2 Power consumption... 2 Heat load... 5 The Need for

More information

Improving Rack Cooling Performance Using Blanking Panels

Improving Rack Cooling Performance Using Blanking Panels Improving Rack Cooling Performance Using Blanking By Neil Rasmussen White Paper #44 Revision 1 Executive Summary Unused vertical space in open frame racks and rack enclosures creates an unrestricted recycling

More information

or

or Infinite possibilities for your data center The F-Series TeraFrame T M Cabinet System The F-Series TeraFrame Cabinet System from Chatsworth Products, Inc. (CPI) provides configurable thermal management

More information

DATACOM CABINETS SOLUTION GUIDE

DATACOM CABINETS SOLUTION GUIDE DATACOM CABINETS SOLUTION GUIDE designed to be better. LEGRAND S CABINET OFFERING Legrand cabinets are designed with cable management, airflow management and effortless installation to meet all network

More information

Datacenter Efficiency Trends. Cary Roberts Tellme, a Microsoft Subsidiary

Datacenter Efficiency Trends. Cary Roberts Tellme, a Microsoft Subsidiary Datacenter Efficiency Trends Cary Roberts Tellme, a Microsoft Subsidiary Power Slashing Tools P3 Kill-A-WATT Measures min, max, and instantaneous voltage and current draw Calculates power (watts), kilowatt

More information

Total Modular Data Centre Solutions

Total Modular Data Centre Solutions Sector Data Centre Total Modular Data Centre Solutions www.airedale.com BRITISH MANUFACTURER ENERGY EFFICIENCY CONTROLS SERVICE TRAINING 01 Standardised Modular Designs to fit your needs Our modular system

More information

Improving Data Center Reliability and Efficiency by Recovering Cooling Capacity with KoldLok Raised Floor Grommets BUSINESS CASE ANALYSIS

Improving Data Center Reliability and Efficiency by Recovering Cooling Capacity with KoldLok Raised Floor Grommets BUSINESS CASE ANALYSIS BUSINESS CASE ANALYSIS Improving Data Center Reliability and Efficiency by Recovering Cooling Capacity with KoldLok Raised Floor Grommets by Daniel L. Gollahon, CDP Subject: This business case examines

More information

Product Brochure DENCO Close Control Units Row-DENCO. High Density Cooling for Data Centres

Product Brochure DENCO Close Control Units Row-DENCO. High Density Cooling for Data Centres Product Brochure DENCO Close Control Units Row-DENCO High Density Cooling for Data Centres Data Centre Cooling Through a history in close control, we have developed a broad and deep understanding of how

More information

TMS-08. Thermal. Management Solutions

TMS-08. Thermal. Management Solutions TMS-08 Thermal Management Solutions Contents Section Page Introduction 1 Flexibility on Demand 2 The Cabinet 3 Configuring a Cabinet for Thermal Loads 4 19 Blanking Panels 8 Front to Rear Blanking Panels

More information

Green Sustainable Data Centres. Checklist - EU Code of Conduct on Data Centres. Annex

Green Sustainable Data Centres. Checklist - EU Code of Conduct on Data Centres. Annex Green Sustainable Data Centres Checklist - EU Code of Conduct on Data Centres Annex This course is produced under the authority of e-infranet: http://e-infranet.eu/ Course team prof. dr. Colin Pattinson,

More information

A Data Center Heat Removal System That Saves... 80% Discover Inertech s Award-winning Data Center Heat Removal System

A Data Center Heat Removal System That Saves... 80% Discover Inertech s Award-winning Data Center Heat Removal System A Data Center Heat Removal System That Saves... Infrastructure Power Water up to 40% up to 80% up to 85% Discover Inertech s Award-winning Data Center Heat Removal System A Cool Solution; A Breakthrough

More information

Five Strategies for Cutting Data Center Energy Costs Through Enhanced Cooling Efficiency

Five Strategies for Cutting Data Center Energy Costs Through Enhanced Cooling Efficiency Five Strategies for Cutting Data Center Energy Costs Through Enhanced Cooling Efficiency A White Paper from the Experts in Business-Critical Continuity TM Executive Summary As electricity prices and IT

More information

Certified 1. AMCO Enclosures Containment Brochure. Hot/Cold Aisle Containment Solutions ACB3.0. Designed and Manufactured in the USA

Certified 1. AMCO Enclosures Containment Brochure. Hot/Cold Aisle Containment Solutions ACB3.0. Designed and Manufactured in the USA ACB3.0 Designed and Manufactured in the USA Hot/Cold Aisle Containment Solutions AMCO Enclosures Containment Brochure IMS Engineered Products is Certified 1 Aisle Containment Solutions AMCO Enclosures

More information

HP Modular Cooling System: water cooling technology for high-density server installations

HP Modular Cooling System: water cooling technology for high-density server installations HP Modular Cooling System: water cooling technology for high-density server installations technical brief Abstract... 2 Introduction... 2 Data center trends... 2 Increased power demands... 3 Increased

More information

LANL High Performance Computing Facilities Operations. Rick Rivera and Farhad Banisadr. Facility Data Center Management

LANL High Performance Computing Facilities Operations. Rick Rivera and Farhad Banisadr. Facility Data Center Management Slide-1 LANL High Performance Computing Facilities Operations Rick Rivera and Farhad Banisadr Facility Data Center Management Division Slide-2 Outline Overview - LANL Computer Data Centers Power and Cooling

More information

Intelligent Containment Systems

Intelligent Containment Systems Intelligent Containment Systems About Geist Geist designs and manufactures industry leading technology and software for powering, monitoring, cooling and managing critical data center infrastructure. We

More information

MEASURE MONITOR UNDERSTAND

MEASURE MONITOR UNDERSTAND MEASURE MONITOR UNDERSTAND Presented by Alistair Hunt Energy Monitoring, Measurement metrics Where and What 1 History & Background Company Timeline 18 Years Comrac & Sinetica founded 15 Years Raritan Integration

More information

A separate CRAC Unit plant zone was created between the external façade and the technical space.

A separate CRAC Unit plant zone was created between the external façade and the technical space. Nominee: FES Co Ltd Nomination title: HP Cold Cube The Doxford Facility is a highly secure Data Centre. The challenge was to take advantage of the previous investment in highly resilient infrastructure

More information

Schneider Electric Cooling Portfolio. Jim Tubbesing Heath Wilson APC/Schneider North Texas Rep Tubbesing Solutions

Schneider Electric Cooling Portfolio. Jim Tubbesing Heath Wilson APC/Schneider North Texas Rep Tubbesing Solutions Schneider Electric Cooling Portfolio Jim Tubbesing Heath Wilson APC/Schneider North Texas Rep Tubbesing Solutions Data Center Cooling Agenda 1. How to size data center, server rooms, IDF rooms, etc in

More information

Hassle-free equipment installation

Hassle-free equipment installation 22U 36in Knock-Down Server Rack Cabinet with Casters StarTech ID: RK2236BKF This server rack provides 22U of storage space in a sleek secure cabinet for storing EIA-310 compliant 19 rackmount devices such

More information

Trends in Data Center Energy Efficiency

Trends in Data Center Energy Efficiency Trends in Data Center Energy Efficiency Presented by: Todd Boucher Better Building by Design 2012 1 Efficiency Vermont is a Registered Provider with The American Institute of Architects Continuing Education

More information

Survey and Audit Service Schedule. Airflow and Thermal Imaging Survey Service Schedule. Data Centre Solutions Expertly Engineered

Survey and Audit Service Schedule. Airflow and Thermal Imaging Survey Service Schedule. Data Centre Solutions Expertly Engineered Survey and Audit Service Schedule Airflow and Thermal Imaging Survey Service Schedule Data Centre Solutions Expertly Engineered Consult optimisation, audit and survey services Data Centre Services Workspace

More information

Airflow Management s Role in Data Center Cooling Capacity

Airflow Management s Role in Data Center Cooling Capacity Airflow Management s Role in Data Center Cooling Capacity By Larry Mainers, CEO Subzero Engineering 2014 Subzero Engineering SUMMARY Airflow management (AFM) is changing the way data centers cool the IT

More information