APC InRow Cooler Prototype Initial Report - Test Setup Verification. H. Coles, S. Greenberg Contributing: J. Bean (APC) November 18, 2011
|
|
- Tyrone Fitzgerald
- 6 years ago
- Views:
Transcription
1 APC InRow Cooler Prototype Initial Report - Test Setup Verification H. Coles, S. Greenberg Contributing: J. Bean (APC) November 18,
2 Introduction Contents Technology Description/Attributes Installation Analysis Metrics, Methods, Metering, Test Description Results Next Steps Conclusions 2
3 Project funding Introduction California Energy Commission (CEC) APC: In-kind Funding LBNL Role - Identify and demonstrate new data center energy saving technologies Goal - Reduction or Elimination of Compressor Cooling Technology Selected: APC dual heat exchanger InRow Cooler Status: Initial trial setup and data collection completed 3
4 APC Unit Description Fans (3 EC type) Air to Water Heat Exchanger (chilled water) Cooled Air Leaving Air to Water Heat Exchanger ( treated water) Air to Water Hex (chilled) Chilled Water Modulating Valve Air to Water Hex (treated) IT Rack IT Rack Hot Aisle IT Rack IT Rack IT Rack IT Rack Treated Water Modulating Valve Chilled Water Connection treated Water Connection Hot Air Entering filter IT Rack IT Rack Cold Aisle IT Rack IT Rack Hot Aisle IT Rack IT Rack 4
5 Product Attributes Redundancy: dual water cooling loops and heat exchangers Self contained: additional CRAH/CRAC units not required Use min. chilled water use only where/when needed for data center hot spots Some additional plumbing required 5
6 APC Unit Installation Building 50 Data Center Rm 1275 Lawrence Berkeley National Laboratory Front Air Exit Cold Aisle Rear Air Entry Hot Aisle Front Door Display/Control Filter 6
7 COP Metric Definition COP [ kw thermal / kw elec. ] = cooling provided / power needed cooling provided (kw) = treated water cooling + chilled water cooling APC Unit Power power needed (kw) = (kw/ton * tons) + (kw/ton * tons) + APC Unit Power APC Unit Power 7
8 Electrical Power Needed (kw/ton) Plant Model ASHRAE 90.1 Code Minimum Water-Side Economizer Equipped Santa Clara CA Climate Year Average (Taylor Engineering) kw/ton vs. Chilled Water Temperature (CWT) distribution pumping included Santa Clara CA Year Average (CHWT) y = x x x Chilled Cooling Water Water Temperature ( F) Taylor Engineering Heavy Use of Chiller Little or No Chiller Use (water side economizer) aka treated 8
9 Test Methods Short duration preliminary tests Manual Mode Test 1: cooling tower only (single coil) Test 2: chilled water only (single coil) Test 3: chilled and treated water combined (both coils) Key Metric Coefficient of Performance (COP) 9
10 Synapsense Wireless Air Temperatures Air Temp. Sensors Metering Installed Power and Btu Meters Power Meter Ion Power Meter (APC Unit) Onicon Btu Meter (treated water) Cooling Tower ( treated ) Treated Water Btu Meter Air Temp. Sensors Chilled Water Btu Meter Chilled Cooling Water Onicon Btu Meter (chilled water) Flow Sensor Temperature Sensors Flow Sensor 10
11 Preliminary Results: Compare Cooling Modes (manual operation, valves 100% open, slow speed) Energy Rate (kw thermal, kw electrical) COP (kw/kw) Chilled Water Chilled Water Cooling Net Cooling APC Power Required COP 0.58 kw/ton Chilled+ Treated Water Treated H2O Cooling Chilled Water Cooling Net Cooling APC Power Required COP 0.46 kw/ton Treated H2O Cooling Treated Water Net Cooling APC Power Required COP 0.28 kw/ton Chilled Water Only Cooling Treated + Chilled Cooling Treated Water Only Cooling 11
12 Treated Compare Exit Temperature with Similar Inlet Temperature (manual mode) Test # F Air from Hot Aisle Entering APC Unit ( F) Air to Cold Aisle Leaving APC Unit ( F) Air Entering/Leaving APC InRow Unit Test # F Chilled Air from Hot Aisle Entering APC Unit ( F) Air to Cold Aisle Leaving APC Unit ( F) Air Entering/Leaving APC InRow Unit Test # F Treated and Chilled Air from Hot Aisle Entering APC Unit ( F) Air to Cold Aisle Leaving APC Unit ( F) Air Entering/Leaving APC InRow Unit SVLG 2011 Data Center Efficiency Summit - LBNL 12
13 CFM / kw Cooled COP (kw cooling / kw electrical) Performance (kw elec / ton ) Treated Water Cooling Metering Test COP Treated Water Cooling Only COP [kw/kw] = cooling / total electrical (plant + APC unit) needed Treated Water Cooling Performance (COP) Treated Only Coil Test - CFM per Net Cooled kw cfm per kw SVLG 2011 Data Center Efficiency Summit - LBNL 13
14 Next Steps Test control system temperature modulation, fan speed (data presented not typical in some cases manual mode) Test at various output set point temperatures Monitor cfm/kw supported Investigate power used and COP change at high fan speeds Longer term test Test performance when both coils use treated water Test with warmer air inlet Re-check air temperature sensor calibration 14
15 Conclusions Test setup working Efficiency Points Chilled water ~14kW cooling (4 tons) at COP =6 (0.58kW/ton) Treated water ~14kW cooling (4 tons) at COP =12 (0.28kW/ton) Unit appears to support typical server cfm/kw E.g. treated water test = ~1000cfm for ~5kW cooling ( cfm/kW) Compare to others Chilloff 2 Results (Row Coolers) SCOPc = ~6 using ~45 F cooling water COP this test = ~6 using 47 F cooling water 15
16 End Questions? 16
17 Appendix 17
18 Flow (gpm) Delta Temp. (F) Thermal Cooling (kw) Water Supply Temp. ( F) Test 1 Treated Water Only Cooling Cooling vs. Water Supply Temperature Treated Water- Manual Control, APC Fans at Low Speed Treated Water Supply Temperature ( F) Treated Water Cooling (kw) midnight noon midnight Time (hours) noon Air from Hot Aisle Entering APC Unit ( F) Air to Cold Aisle Leaving APC Unit ( F) Air Entering/Leaving APC InRow Unit Treated Water dt ( F) Treated Water Flow (gpm) Treated Coil Only Cooling - water delta temp. ( F), flow (gpm)
19 CFM / kw Cooled Air Flow (cfm) COP (kw cooling / kw electrical) Test 1 Treated Water Cooling Only (continued) 14.0 COP Treated Water Cooling Only COP [kw/kw] = cooling / total electrical (plant + APC unit) needed Treated Water Cooling Performance (COP) Treated Only Coil Test - Calculated air flow (cfm) calculated air flow cfm per kw Treated Only Coil Test - CFM per Net Cooled kw
20 Delta Temp. (F) Thermal Cooling (kw) Test 2 Chilled Water Only Cooling Flow (gpm) Water Supply Temp. ( F) 20 Cooling vs. Water Supply Temperature Chilled Coil Only - Manual Mode, CRAH Fans at Low Speed Chilled Water Supply Temperature ( F) Chilled Water Cooling (kw) noon Time (hours) midnight Air from Hot Aisle Entering APC Unit ( F) Air to Cold Aisle Leaving APC Unit ( F) Air Entering/Leaving APC InRow Unit Chilled Coil Cooling - water delta temp. ( F), flow (gpm) Chilled Water dt ( F) Chilled Water Flow (gpm)
21 cfm / kw cfm COP (kw cooling / kw electrical) Test 2 Chilled Water Only Cooling (continued) COP Chilled Water Cooling (manual mode) COP [kw/kw] = cooling / total electrical (plant + APC unit) needed Chilled Water Cooling Performance (COP) noon Time (hours) midnight Chilled Coil Only Test - Calculated Total CFM cfm Chilled Coil Only Test - CFM / kw Cooled cfm per kw 21
22 Flow (gpm) Delta Temp. (F) Thermal Cooling (kw) Water Supply Temp. ( F) Test 3 Chilled and Treated Cooling Combined (24 hour test, both coils at full water flow rate) Cooling vs. Water Supply Temperature Treated and Chilled Water Combined - CRAH Fans at Low Speed Treated Water Supply Temperature ( F) Chilled Water Supply Temperature ( F) Chilled Water Cooling (kw) Treated Water Cooling (kw) midnight Time (hours) noon Air from Hot Aisle Entering APC Unit ( F) Air to Cold Aisle Leaving APC Unit ( F) Air Entering/Leaving APC InRow Unit Both Coils Cooling - water delta temp. ( F), flow (gpm) Chilled Water dt ( F) Treated Water dt ( F) 27 Chilled Water Flow (gpm) Treated Water Flow (gpm)
23 cfm / kw cfm COP (kw cooling / kw electrical) Energy Use Efficiency COP and kw/ton Test 3 (both coil) continued 14.0 COP Treated, Chilled Water Cooling and Combination COP [kw/kw] = cooling (kw) / total electrical (plant + APC unit) needed (kw) Treated Water Cooling Performance (COP) Combined Cooling Performance (COP) Chilled Water Cooling Performance (COP) Treated and Chilled Coils Used - Total Cfm Time (hours) cfm Treated and Chilled Coils Used - Total Cfm / kw Cooled 10/04/ :00 10/05/ :00 cfm / kw Notes: both coils full flow ( ~ each), APC fans at low speed 23
24 cfm cfm Air Flow (cfm) Ave. Air Fans Test # F Initial Check Air Flow Using Energy Balance low? calculated air flow Cubic Feet per Minute Treated Only Coil Test - Calculated air flow (cfm) Test # F Chilled Coil Only Test - Calculated Total CFM cfm Test # F Treated and Chilled Coils Used - Total Cfm cfm Air CFM = f (net cooling, air delta temp.) 24
Data Center Energy Savings By the numbers
Data Center Energy Savings By the numbers Chris Kurkjian, PE HP Critical Facility Services provided by EYP Mission Critical Facilities 2008 Hewlett-Packard Development Company, L.P. The information contained
More informationPerformance Evaluation for Modular, Scalable Cooling Systems with Hot Aisle Containment in Data Centers. Final Report
Performance Evaluation for Modular, Scalable Cooling Systems with Hot Aisle Containment in Data Centers Final Report To The California Energy Commission May 2009 Tengfang Xu Environmental Energy Technologies
More informationSchneider Electric Cooling Portfolio. Jim Tubbesing Heath Wilson APC/Schneider North Texas Rep Tubbesing Solutions
Schneider Electric Cooling Portfolio Jim Tubbesing Heath Wilson APC/Schneider North Texas Rep Tubbesing Solutions Data Center Cooling Agenda 1. How to size data center, server rooms, IDF rooms, etc in
More informationDATA CENTER EFFICIENCY: Data Center Temperature Set-point Impact on Cooling Efficiency
DATA CENTER EFFICIENCY: Data Center Temperature Set-point Impact on Cooling Efficiency September 27 th, 2013 Tejas Desai, PE CEM CEA LEED AP Sameer Behere, PE CEM LEED AP Agenda Problem: Quick fixes can
More informationRetro-Commissioning Report
10 Retro-Commissioning Report Retro-Commissioning Retro-Commissioning is the process for identifying intrinsic operational and energy related issues in the facilities DDC system and providing a mechanism
More informationWhat s New for Data Centers in Title Jeff Stein, PE Taylor Engineering
What s New for Data Centers in Title 24-2013 Jeff Stein, PE Taylor Engineering SVLG Workshop November 14, 2013 About Jeff Stein Principal, Taylor Engineering 2000 - now Professional Experience Eley Associates,
More informationHot vs Cold Energy Efficient Data Centers. - SVLG Data Center Center Efficiency Summit
Hot vs Cold Energy Efficient Data Centers - SVLG Data Center Center Efficiency Summit KC Mares November 2014 The Great Debate about Hardware Inlet Temperature Feb 2003: RMI report on high-performance data
More informationCooling. Highly efficient cooling products for any IT application. For More Information: (866) DATA CENTER SOLUTIONS
Cooling > Highly efficient cooling products for any IT application. DATA CENTER SOLUTIONS For More Information: (866) 787-3271 Sales@PTSdcs.com End-to-End Cooling Solutions from the Closet to the Data
More informationA Data Center Heat Removal System That Saves... 80% Discover Inertech s Award-winning Data Center Heat Removal System
A Data Center Heat Removal System That Saves... Infrastructure Power Water up to 40% up to 80% up to 85% Discover Inertech s Award-winning Data Center Heat Removal System A Cool Solution; A Breakthrough
More informationREPORT. Energy Efficiency of the San Diego Supercomputer Center and Distributed Data Centers at UCSD. Prepared for:
REPORT Energy Efficiency of the San Diego Supercomputer Center and Distributed Data Centers at UCSD Prepared for: San Diego Supercomputer Center 10100 John J Hopkins Drive San Diego, CA 92037 May 11, 2009
More informationMission Critical Facilities & Technology Conference November 3, 2011 Cooling 101. Nick Gangemi Regional Sales Manager Data Aire
Mission Critical Facilities & Technology Conference November 3, 2011 Cooling 101 Nick Gangemi Regional Sales Manager Data Aire Agenda Exactly what are we talking about ASHRAE TC 9.9 Design best practices
More informationClose-coupled cooling
Close-coupled cooling Intelligently controlled high-performance InRow cooling for the IT environment APC TM by Schneider Electric close-coupled cooling products provide a modular, scalable, and predictable
More informationMSYS 4480 AC Systems Winter 2015
MSYS 4480 AC Systems Winter 2015 Module 12: DATA CENTERS By Satwinder Singh 14/05/2015 1 Data Centers Data Centers are specialized environments that safeguard your company's most valuable equipment and
More informationLANL High Performance Computing Facilities Operations. Rick Rivera and Farhad Banisadr. Facility Data Center Management
Slide-1 LANL High Performance Computing Facilities Operations Rick Rivera and Farhad Banisadr Facility Data Center Management Division Slide-2 Outline Overview - LANL Computer Data Centers Power and Cooling
More informationImplications of Current Thermal Guidelines
Copyright 2010, American Society of Heating, Refrigerating and Air-Conditioning Engineers, Inc. This posting is by permission from ASHRAE Journal/High Performing Buildings. This material may not be copied
More informationPassive RDHx as a Cost Effective Alternative to CRAH Air Cooling. Jeremiah Stikeleather Applications Engineer
Passive RDHx as a Cost Effective Alternative to CRAH Air Cooling Jeremiah Stikeleather Applications Engineer Passive RDHx as a Cost Effective Alternative to CRAH Air Cooling While CRAH cooling has been
More informationEvaluation and Modeling of Data Center Energy Efficiency Measures for an Existing Office Building
Evaluation and Modeling of Data Center Energy Efficiency Measures for an Existing Office Building Dhayanandh Murugan 1, Gabrielle Viola McMorrow 1, Dr.Liping Wang 1, Greenberg Steve 2 1 University of Wyoming,
More informationReducing Energy Consumption with
Reducing Energy Consumption with Passive Cooling Ian Cathcart, RCDD Technical Support Manager Technical Support Manager Chatsworth Products, Inc. Thermal Management: Mission Critical Data center heat loads
More informationThe Energy. David L. Moss Dell Data Center Infrastructure
The Energy Advantages of Containment Systems David L. Moss Dell Data Center Infrastructure www.dell.com/hiddendatacenter Summary The Uptime Institute estimates that the cost to build a new 20,000 square
More informationDatacenter Efficiency Trends. Cary Roberts Tellme, a Microsoft Subsidiary
Datacenter Efficiency Trends Cary Roberts Tellme, a Microsoft Subsidiary Power Slashing Tools P3 Kill-A-WATT Measures min, max, and instantaneous voltage and current draw Calculates power (watts), kilowatt
More informationDigital Realty Data Center Solutions Digital Chicago Datacampus Franklin Park, Illinois Owner: Digital Realty Trust Engineer of Record: ESD Architect
Digital Realty Data Center Solutions Digital Chicago Datacampus Franklin Park, Illinois Owner: Digital Realty Trust Engineer of Record: ESD Architect of Record: SPARCH Project Overview The project is located
More informationSwitch to Perfection
Switch to Perfection Traditional Data Centre - Temperatures Ideal Air Temperature: 22 C Chilled Water: 7-9 C Heat Load per Rack: Up to 4,5 Chilling & Pump Set The challenge a thermal image Front View of
More informationOne Stop Cooling Solution. Ben Tam Business Development Manager
One Stop Cooling Solution Ben Tam Business Development Manager Agenda One Stop Cooling Solution Challenges Customers Are Facing Today Rack / Row / Room Solution Keynotes New Product Launch Slide 2 2 One
More informationFt Worth Data Center Power Metering for Real Time PUE Calculation. Scope of Work
Ft Worth Data Center Power Metering for Real Time PUE Calculation Scope of Work Prepared for the General Services Administration By Lawrence Berkeley National Laboratory Rod Mahdavi December 13, 2010 Executive
More informationImpact of Air Containment Systems
White Paper June 2012 WP-20 Impact of Air Containment Systems Reducing Energy Consumption Introduction: The Importance of Maintaining Data Center Cooling Energy Efficiency Data centers are mission-critical
More informationFuture of Cooling High Density Equipment. Steve Madara Vice President and General Manager Liebert Precision Cooling Business Emerson Network Power
Future of Cooling High Density Equipment Steve Madara Vice President and General Manager Liebert Precision Cooling Business Emerson Network Power Agenda Issues facing the Data Center Managing the explosive
More informationRittal Cooling Solutions A. Tropp
1 Rittal Cooling Solutions Presented by Adam Tropp 2 Agenda Cooling Strategies Aisle Containment Chimney Solution Airstream Management Rittal Liquid Cooling Packages Data Monitoring 3 Cooling strategies.
More informationCisco Lab Setpoint Increase. Energy Efficient Data Center Demonstration Project
Cisco Lab Setpoint Increase Energy Efficient Data Center Demonstration Project About the Energy Efficient Data Center Demonstration Project The project s goal is to identify key technology, policy and
More informationCRAH Retrofit and Energy Savings Project
CRAH Retrofit and Energy Savings Project Danny Johnson Director, Technical Operations Silicon Valley Leadership Group - Data Center Efficiency Summit October 24, 2012 2260 E. El Segundo Boulevard - A Digital
More informationWelcome Association of Energy Engineers to the Microsoft Technology Center
Welcome Association of Energy Engineers to the Microsoft Technology Center Today s Agenda 10:00 10:30 What s new in data center energy efficiency planning and implementation? 10:30 11:00 ASHRAE data center
More informationRack cooling solutions for high density racks management, from 10 to 75 kw
Rack cooling solutions for high density racks management, from 10 to 75 Superior efficiency, high reliability, low energy consumption Modern data center are characterized by 24/7 operation all year long.
More informationDATA CENTER LIQUID COOLING
DATA CENTER LIQUID COOLING EFFICIENT, EFFECTIVE, SUSTAINABLE What is Liquid Cooling? Key Trends & Potential Inhibitors Why are Many Owner/Operators Making the Move? Types of Liquid Cooling Solutions Liquid
More information7 Best Practices for Increasing Efficiency, Availability and Capacity. XXXX XXXXXXXX Liebert North America
7 Best Practices for Increasing Efficiency, Availability and Capacity XXXX XXXXXXXX Liebert North America Emerson Network Power: The global leader in enabling Business-Critical Continuity Automatic Transfer
More informationScalable, Secure. Jason Rylands
Energy Efficient, Modular, Scalable, Secure Jason Rylands The planning, construction and operation of IT infrastructure for mission critical applications in reliable Datacentres represents a real challenge.
More informationProduct Brochure DENCO Close Control Units Row-DENCO. High Density Cooling for Data Centres
Product Brochure DENCO Close Control Units Row-DENCO High Density Cooling for Data Centres Data Centre Cooling Through a history in close control, we have developed a broad and deep understanding of how
More informationAPC APPLICATION NOTE #146
#146 Hot Aisle Containment Application Guidelines and Approved Configurations By Kevin Lemke Abstract The Hot Aisle Containment System (HACS) is a modular ceiling panel and door system for use in isolating
More informationClose Coupled Cooling for Datacentres
Close Coupled Cooling for Datacentres Dr Fathi Tarada Mosen Ltd fathi.tarada@mosenltd.com www.mosenltd.com Agenda Increasing Power Densities Raised Floor Limitations Hot and Cold Aisle Enclosures Close
More informationInRow Chilled Water. Up to 70kW. Close-coupled, chilled water cooling for medium to large data centers. Row-Based Cooling.
InRow Chilled Water Close-coupled, chilled water cooling for medium to large data centers Up to 0kW > Row-Based Cooling The InRow Chilled Water product design closely couples the cooling with the IT heat
More informationReducing Data Center Cooling Costs through Airflow Containment
FEATURE Reducing Data Center Cooling Costs through Airflow Containment Implementing a containment solution in the data center costs much less than the alternatives of adding air handlers or other supplemental
More informationWaterside Economizing in Data Centers: Design and Control Considerations
2009, American Society of Heating, Refrigerating and Air-Conditioning Engineers, Inc. (www.ashrae.org). Published in ASHRAE Transactions 2009, vol. 115, part 2. For personal use only. Additional reproduction,
More informationMoving Containment Inside the Enclosure. Jeff Markle Great Lakes Case & Cabinet
Moving Containment Inside the Enclosure Presented by Jeff Markle Great Lakes Case & Cabinet Containment Containment : To put constraint upon; to restrain; to confine; to keep within bounds Containment
More informationRear Door Heat Exchanger
Vinod Kamath Power and Thermal Engineering Sep 16, 2005 Problem Statement Rack Power loads are high due to increased compute density. The impact is seen in datacenters as high inlet air temperatures to
More informationHIGH DENSITY RACK COOLING CHOICES
WATERCOOLED HIGH PERFORMANCE COMPUTING SYSTEMS AQUILA WHITE PAPER HIGH DENSITY RACK COOLING CHOICES by Phil Hughes Reprinted with permission of Clustered Systems Company, Inc 1 THIS WHITE PAPER DISCUSSES
More informationAre All Servers Created Equal? Comparing Server Energy Use and Efficiency
Are All Servers Created Equal? Comparing Server Energy Use and Efficiency Henry Coles Lawrence Berkeley National Laboratory Nov. 5, 2014 SVLG Data Center Efficiency Summit Santa Clara University contact:
More informationEfficiency of Data Center cooling
Efficiency of Data Center cooling Comparison of data room layouts and cooling systems Bohumil Cimbal Product manager for Cooling Systems in CONTEG Company Objective Basic questions between investor and
More informationData Center Temperature Design Tutorial. Ian Seaton Chatsworth Products
Data Center Temperature Design Tutorial Ian Seaton Chatsworth Products What are we going to do today? Explore a process for determining what data center operating temperature will deliver the best total
More informationPower and Cooling for Ultra-High Density Racks and Blade Servers
Power and Cooling for Ultra-High Density Racks and Blade Servers APC White Paper #46 Richard L. Sawyer Director of Data Center Technology American Power Conversion Company 2005 APC corporation What has
More informationCase study: Energy efficiency improvements in a legacy data centre. Robert Tozer Director Opera>onal Intelligence
Case study: Energy efficiency improvements in a legacy data centre Robert Tozer Director Opera>onal Intelligence Objec>ves First improve air management Air supply temperature to servers Lower temperature
More informationIndustry leading low energy evaporative fresh air cooling.
Industry leading low energy evaporative fresh air cooling. Freecool Evaporative Free Air Cooling by Workspace Technology delivers innovative low energy cooling for a range of applications including data
More informationImpact of Hot and Cold Aisle Containment on Data Center Temperature and Efficiency
Impact of Hot and Cold Aisle Containment on Data Center Temperature and Efficiency White Paper 135 Revision 3 by John Niemann, Kevin Brown, and Victor Avelar Executive summary Both hot-air and cold-air
More informationCooling on Demand - scalable and smart cooling solutions. Marcus Edwards B.Sc.
Cooling on Demand - scalable and smart cooling solutions Marcus Edwards B.Sc. Schroff UK Limited Data Centre cooling what a waste of money! A 1MW data center needs 177,000,000 kwh in its lifetime of 10
More informationPROCESS & DATA CENTER COOLING. How and Why To Prepare For What s To Come JOHN MORRIS REGIONAL DIRECTOR OF SALES
PROCESS & DATA CENTER COOLING How and Why To Prepare For What s To Come JOHN MORRIS REGIONAL DIRECTOR OF SALES CONGRATULATIONS 2 BOLD PREDICTION 3 Where We Are TODAY Computer Technology NOW advances more
More informationInternational 6SigmaDC User Conference CFD Modeling for Lab Energy Savings DCSTG Lab Temperature Setpoint Increase
International 6SigmaDC User Conference CFD Modeling for Lab Energy Savings DCSTG Lab Temperature Setpoint Increase Chris Noland cnoland@cisco.com Vipha Kanakakorn vkanakak@cisco.com 3/4/2010 Goal & Limitations
More informationHVAC System Energy Savings Opportunities
HVAC System Energy Savings Opportunities Speaker Info M. Lant DuBose Energy Services ConEdison Solutions dubosem@conedsolutions.com (813)285-6340 Wholly owned subsidiary of ConEdison since 2007 Entered
More informationSilicon Valley Power Data Center Program Rebate Application
Contact Information Tax Status (check one) Sole Proprietor Contact Name Phone Corporation Partnership Company Email address Government Not-For-Profit Customer/Facility Information Company Name SVP Account
More informationTen Cooling Solutions to Support High-density Server Deployment. Schneider Electric Data Center Science Center White Paper #42
Ten Cooling Solutions to Support High-density Server Deployment Schneider Electric Data Center Science Center White Paper #42 1 Introduction 2 Introduction This paper provides 10 approaches for increasing
More information18 th National Award for Excellence in Energy Management. July 27, 2017
18 th National Award for Excellence in Energy Management July 27, 2017 ICICI Bank, Data Centre, August Hyderabad 30 & 31, 2017 ICICI Bank - Revolution in Digital Banking Over 100,000 Digital POS in 4 months
More informationOptimizing Chilled Water Plant Performance. David Herman, PE, LEED AP Principal EnerG Associates, LLC
Optimizing Chilled Water Plant Performance David Herman, PE, LEED AP Principal EnerG Associates, LLC Optimizing Chilled Water Plant Learning Objectives Performance Review the design and operating characteristics
More informationR4 Ventures LLC White Paper
R4 Ventures LLC PR ODUCT IN HARD COPY OR DIGITAL FORM. ALL OFFENDERS WILL BE SUED IN A COURT OF LAW. R4 Ventures LLC White Paper Comparison of energy consumption in kw per ton of cooling Real Time Data
More informationDEDICATED HEAT RECOVERY UNIT (DHRC)
DEDICATED HEAT RECOVERY UNIT (DHRC) AHRI CERTIFICATION Air-Conditioning, Heating, and Refrigeration Institute Multistack is AHRI Certified and continues to certify products as they are developed AHRI Certification
More informationHow much power?! Data Centre Efficiency. How much Money?! Carbon Reduction Commitment (CRC)
How much power?! Data Centre Efficiency The US EPA found in 2006 data centres used 1.5% of total US consumption (5) For Bangor University data centres use approximately 5-10% of the total university electricity
More informationAisleLok Modular Containment vs. Legacy Containment: A Comparative CFD Study of IT Inlet Temperatures and Fan Energy Savings
WHITE PAPER AisleLok Modular Containment vs. : A Comparative CFD Study of IT Inlet Temperatures and Fan Energy Savings By Bruce Long, Upsite Technologies, Inc. Lars Strong, P.E., Upsite Technologies, Inc.
More informationLiquid Cooling Package LCP Cooling Systems
Liquid Cooling Package LCP Cooling Systems 2 Rittal LCP The whole is more than the sum of its parts. The same is true of Rittal The System. With this in mind, we have bundled our innovative enclosure,
More informationRecapture Capacity for Existing. and Airflow Optimization
Recapture Capacity for Existing Data Centers Through Cooling and Airflow Optimization Introduction Challenges and Trends Agenda Cooling & Airflow Optimization Takeaways Learning Objectives Recognize opportunities
More informationHOURLY ANALYSIS PROGRAM v5.00 and v5.01
HOURLY ANALYSIS PROGRAM v and v5.01 Carrier Software Systems Carrier Corporation Syracuse, New York Rev. November 3, 2016 Copyright 2016 Carrier Corporation, All Rights Reserved Contents Chiller Features
More informationCleanroom Energy Benchmarking In High-Tech and Biotech Industries
ACEEE 2001 Paper #66 Cleanroom Energy Benchmarking In High-Tech and Biotech Industries William Tschudi; Lawrence Berkeley National Laboratory Kathleen Benschine, Stephen Fok; Pacific Gas and Electric Company
More informationData Center Temperature Rise During a Cooling System Outage
Data Center Temperature Rise During a Cooling System Outage White Paper 179 Revision 0 By Paul Lin Simon Zhang Jim VanGilder > Executive summary The data center architecture and its IT load significantly
More informationUsing CFD Analysis to Predict Cooling System Performance in Data Centers Ben Steinberg, P.E. Staff Applications Engineer
Using CFD Analysis to Predict Cooling System Performance in Data Centers Ben Steinberg, P.E. Staff Applications Engineer Agenda What is CFD? Applications of CFD Applicability to the Data Center How it
More informationCHILLED WATER. HIGH PRECISION AIR CONDITIONERS, FROM 7 TO 211 kw
IT COOLING CLOSE CONTROL AIR CONDITIONERS CHILLED WATER HIGH PRECISION AIR CONDITIONERS, FROM 7 TO 211 kw 3 Versions available Single chilled water coil Double chilled water coil High temperature IT COOLING
More informationLiebert. HPC-S Free Cooling Chiller Designed for the Efficient Cooling of Small Data Centers
Liebert HPC-S Free Cooling Chiller Designed for the Efficient Cooling of Small Data Centers Liebert HPC-S FREE COOLING CHILLER Getting To A PUE Of 1.2 Free cooling data center chillers are designed to
More informationEnergy Efficient Data Centers
IBM Systems and Technology Group Lab Services Energy Efficient Data Centers Steven Ahladas IBM Corp ahladas@us.ibm.com Keeping our clients in the race. All trends going the same way. IT Servers were an
More informationOptimiz Chilled January 25, 2013
Optimiz zing Existing Data Center Chilled Water Plants January 25, 2013 This White Paper describes factors to be consideredd when optimizing an existing data center chilledd water plant. Authored by Michael
More informationUC DAVIS THERMAL ENERGY STORAGE (TES) TANK OPTIMIZATION INVESTIGATION MATTHEW KALLERUD, DANNY NIP, MIANFENG ZHANG TTP289A JUNE 2012
UC DAVIS THERMAL ENERGY STORAGE (TES) TANK OPTIMIZATION INVESTIGATION MATTHEW KALLERUD, DANNY NIP, MIANFENG ZHANG TTP289A 004 11 JUNE 2012 TABLE OF CONTENTS Abstract...3 Introduction...3 Methodology...4
More informationModbus Register Map: InRow ACRD60x / ACRC60x
Modbus Map: InRow ACRD60x / ACRC60x Notes: 1. 16-bit registers (INT16, UINT16, ENUM) are transmitted MSB first (i.e., big-endian). 2. INT32 and UINT32 are most-significant word in n+0, least significant
More informationCurrent Data Center Design. James Monahan Sept 19 th 2006 IEEE San Francisco ComSoc
Current Data Center Design James Monahan Sept 19 th 2006 IEEE San Francisco ComSoc What is the biggest facility problem in your data center? 35% 30% 25% 20% 15% Series1 10% 5% 0% Excessive heat Insufficient
More informationANCIS I N C O R P O R A T E D
Thermal Design of Data Centers to Safeguard Electronic Equipment Presentation at the Thermal Design Center Santa Clara, CA, March 9, 2010 Magnus K. Herrlin, Ph.D. President Incorporated mherrlin@ancis.us
More informationAPC APPLICATION NOTE #114
APPLICATION NOT #4 Using the Rack Air Containment System with the InfraStruXure InRow SC By David Roden Abstract The InfraStruXure InRow SC (ACSC00 and ACSC0) is a self-contained air conditioner for server
More informationIBM Symposium Data Center Cooling. EC Systems for HVAC architecture and Direct air Cabinet Cooling
IBM Symposium 2008 Data Center Cooling EC Systems for HVAC architecture and Direct air Cabinet Cooling Presented by David J. Spofford Product Manager IT/Telecomm 1 Agenda Data Center trends for IT and
More informationGreen IT and Green DC
Green IT and Green DC Alex SL Tay Regional Service Product Line Manager Site & Facilities Services, IBM ASEAN 1 What our clients are telling us We are running out of space in our data center We have environmental
More informationIT Air Conditioning Units
IT Air Conditioning Units Modern Flexible Effective Energy Saving CoolTeg Plus and CoolTop overview CoolTeg Plus CW CoolTeg Plus DX CoolTeg Plus XC CoolTop Installation Between IT racks On top of IT rack
More informationHIGH DENSITY DATACOM INTEGRATED COOLING SYSTEM.
HIGH DENSITY DATACOM INTEGRATED COOLING SYSTEM. SYSTEM LOGICA is the most advanced alternative to the problem of cooling of server rooms MONTAIR is the trademark which represents excellence on the market
More information<Insert Picture Here> Austin Data Center 6Sigma DC CFD Model
Austin Data Center 6Sigma DC CFD Model Keith Ward Keith Ward Data Center Facilities Engineering and Logistics Design Austin Data Center Statistics - Space Original AT&T Designed and
More informationMotivair MLC-SC Air-Cooled Scroll Chillers Tons
INNOVATE DESIGN APPLY www.motivaircorp.com Motivair MLC-SC Air-Cooled Scroll Chillers 100 285 Tons OUR BUSINESS IS COOLING YOURS. When commercial grade isn t enough Businesses who function in today s advanced
More informationIT COOLING EVAPORATIVE COOLING SYSTEM. 2 STAGE INDIRECT ADIABATIC COOLING SYSTEM FOR LARGE DATA CENTERS FROM 80 TO 320 kw
IT COOLING EVAPORATIVE COOLING SYSTEM 2 STAGE INDIRECT ADIABATIC COOLING SYSTEM FOR LARGE DATA CENTERS FROM 8 TO 3 kw IT COOLING EVAPORATIVE COOLING SYSTEM ADIABATIC COOLING FOR HIGH EFFICIENCY - Variable
More informationIs Data Center Free Cooling Feasible in the Middle East? By Noriel Ong, ASEAN Eng., PMP, ATD, PQP
Is Data Center Free Cooling Feasible in the Middle East? By Noriel Ong, ASEAN Eng., PMP, ATD, PQP This case study will evaluate the feasibility of data center free cooling in the Middle East using indirect
More informationCooling Solutions & Considerations for High Performance Computers
Cooling Solutions & Considerations for High Performance Computers White Paper 6 Revision 1 By Rich Whitmore Executive summary The recent advances in high performance computing have driven innovations not
More informationDriving Proactive Facility Operations with Automated HVAC Diagnostics
Driving Proactive Facility Operations with Automated HVAC Diagnostics Turn HVAC Data into Actionable Information AKA Monitoring Based Commissioning Ongoing Commissioning Automated Fault Detection & Diagnostics
More informationIntroducing the Heat Wheel to the Data Center
Introducing the Heat Wheel to the Data Center Robert (Dr. Bob) Sullivan, Ph.D. Data Center Infrastructure Specialist KyotoCooling International Critical Facilities Round Table 1 A New Free Cooling Technique
More informationMEASURE MONITOR UNDERSTAND
MEASURE MONITOR UNDERSTAND Presented by Alistair Hunt Energy Monitoring, Measurement metrics Where and What 1 History & Background Company Timeline 18 Years Comrac & Sinetica founded 15 Years Raritan Integration
More informationglide glider kw R134a air cooled liquid chillers AND free cooling chillers FREE COOLING SHELL A C CLASS E C Energy Class RCGROUP SpA
99 glide air cooled liquid chillers ND free cooling chillers glider 178 1328 Energy Class More efficient + B C D E F G Less efficient R134a CLSS SHELL C E C FREE COOLING 100 air cooled liquid chiller and
More informationNext Generation Cooling
Next Generation Cooling Server Manufacturer Perspective Practical and Cost Effective David Moss Data Center Strategist Dell 1 Why Chip, Row, or Rack? Density? Energy Don t be scared; I don t see 50kW/rack
More informationDatacenter Cooling. DC Cooling Efficiency and Project experience. Osman Uzuner. Vakıfbank Central Systems Management Datacenter Operations
Datacenter Cooling DC Cooling Efficiency and Project experience Osman Uzuner Vakıfbank Central Systems Management Datacenter Operations Agenda Agenda and Intro About Vakıfbank DC Energy Consumption breakdown
More informationDesigning Ultra-Efficient Building Cooling Systems
Designing Ultra-Efficient Building Cooling Systems Design to Apply Effective Optimization Technologies To Chiller Plants and Air Systems ASHRAE Triangle Chapter Raleigh, NC November 16, 2016 Tom Hartman,
More informationReclaim Wasted Cooling Capacity Now Updated with CFD Models to Support ASHRAE Case Study Data
White Paper EC9005A Reclaim Wasted Cooling Capacity Now Updated with CFD Models to Support ASHRAE Case Study Data Peer reviewed case study data from ASHRAE now updated with CFD model analysis revealing
More information1.0 Executive Summary. 2.0 Available Features & Benefits
Statement Of Work Energy Management Services Table of Contents 1.0 Executive Summary 2.0 Available Features & Benefits 3.0 Assessment Deliverables Selection 4.0 On Site Assessment Activities 5.0 Exclusions
More informationINNOVATE DESIGN APPLY.
INNOVATE DESIGN APPLY By A whole new cooling experience The Motivair ChilledDoor Rack Cooling System targets the critical cooling requirements of today s modern server rack designs. As technology continues
More informationIT COOLING AIR CONDITIONERS FOR HIGH DENSITY RACKS AND BLADE SERVERS. RACK COOLING SOLUTIONS FOR HIGH DENSITY RACK MANAGEMENT, FROM 4 TO 75 kw
IT COOLING AIR CONDITIONERS FOR HIGH DENSITY RACKS AND BLADE SERVERS RACK COOLING SOLUTIONS FOR HIGH DENSITY RACK MANAGEMENT, FROM 4 TO 75 kw IT COOLING AIR CONDITIONERS FOR HIGH DENSITY RACKS AND BLADE
More informationChiller Replacement and System Strategy. Colin Berry Account Manager
Chiller Replacement and System Strategy Colin Berry Account Manager Current Situation 4 Existing RTAA chillers All units 23 years old Limited service history One unit MUST be replaced immediately One unit
More informationINNOVATE DESIGN APPLY.
INNOVATE DESIGN APPLY By A whole new cooling experience The Motivair ChilledDoor Rack Cooling System targets the critical cooling requirements of today s modern server rack designs. As technology continues
More informationSystem Overview. Liquid Cooling for Data Centers. Negative Pressure Cooling Without Risk of Leaks
Liquid Cooling for Data Centers System Overview The Chilldyne Cool-Flo System is a direct-to-chip liquid cooling system that delivers coolant under negative pressure. Chilldyne s technologies were designed
More information