Energy Usage in Cloud Part2. Salih Safa BACANLI

Size: px
Start display at page:

Download "Energy Usage in Cloud Part2. Salih Safa BACANLI"

Transcription

1 Energy Usage in Cloud Part2 Salih Safa BACANLI

2 Cooling Virtualization Energy Proportional System Conclusion

3 Cooling After servers, the second largest consumer of power in a data center is the cooling system.(kava, 2012) This cloud-computing hardware must be cooled by something, regardless of the hardware s location or owner. Required cooling infrastructure depends on the computing resources power density and layout.(infotech,2011)

4 Air cooling is popular, inexpensive,simple to scale to fit room needs. Fine for systems up to 15 KW You need to move the air through the equipment (air s heat transfer coefficient is nearly constant). Ventilation air and natural winds OR You need to cool the air in the cloud room.

5 Raised Floor The equipments (racks) are put on a platform higher than the ground. The area is used for air space or water cooling pipes.

6 For systems who energy consumption is bigger than 15 KW/rack you need to use liquid. Moving large volumes of air can be very expensive for very-high-density racks. Mineral oil and water can be used for liquid.

7 Virtualization as solution? Virtualization is nice if used properly. Having many computers in the same hardware. Scaling: Horizontal: Increasing VM Vertical:increase resource allocation of current VMs (increase their CPU share) (Paya & Marinescu, 2013)

8 Disadvantageous Virtualization 1) The rise of high density Higher power density is likely to result from virtualization, at least in some racks. Areas of high density can pose cooling challenges that, if left unaddressed, could threaten the reliability of the overall data center. 2) Reduced IT load can affect PUE After virtualization, the data center s power usage effectiveness (PUE) is likely to worsen. This is despite the fact that the initial physical server consolidation results in lower overall energy use. If the power and cooling infrastructure is not right-sized to the new lower overall load, physical infrastructure efficiency measured as PUE will degrade.

9 3) Dynamic IT loads Virtualized IT loads, particularly in a highly virtualized, cloud data center, can vary in both time AND location. In order to ensure availability in such a system, it s critical that rack-level power and cooling health be considered before changes are made. 4)Lower redundancy requirements are possible A highly virtualized data center designed and operated with a high level of IT fault-tolerance may reduce the necessity for redundancy in the physical infrastructure. This effect could have a significantly positive impact on data center planning and capital costs.

10

11 To improve post-virtualization PUE, the data center s infrastructure efficiency curve must be improved (lowered) by optimizing power and cooling systems to reduce the waste of oversizing and better align capacity with the new, lower load. In addition to improving efficiency, optimized power and cooling will directly impact the electric bill by reducing the power consumed by unused power and cooling capacity.

12

13 Energy proportional system Normal System

14 For normal server Utilization is measure of application perfomance like requests per second on a web server

15 Energy efficiency of servers have increased as the time passed.

16 For Energy Proportional Server

17 Conclusion The introduction of more efficient CPUs based on chip multiprocessing has also contributed positively toward more energy-efficient servers. However, long-term technology trends invariably indicate that higher performance means increased energy usage. As a result, energy efficiency must improve as fast as computing performance to avoid a significant growth in computers energy footprint. (Barroso & Hölzle, 2007)

18 To a first-order approximation, both cooling and provisioning costs are proportional to the average energy that servers consume, therefore energy efficiency improvements should benefit all energy dependent components

19

20 References N.A (2011).Cooling the Cloud,Infotech. [ONLINE] Retrived from [ ] Kava,J. (2012). Cooling the cloud: A look inside Google s Hot Huts.Google Green Blog[ONLINE]Retrieved from [ ] Barroso,L.A. & Hölzle,U. (2007). The case for energy proportional computing.computer,december 2007, Schneider Electricity-Data Center Science [ONLINE] Retrieved from [ ] Paya, A. & Marinescu, D.C.(2013). Energy-aware Application Scaling on a Cloud.Arxiv.org[ONLINE] Retrieved from [ ]

Virtualization and consolidation

Virtualization and consolidation Virtualization and consolidation Choosing a density strategy Implementing a high-density environment Maximizing the efficiency benefit Anticipating the dynamic data center Schneider Electric 1 Topical

More information

Power & Cooling Considerations for Virtualized Environments

Power & Cooling Considerations for Virtualized Environments Power & Cooling Considerations for Virtualized Environments Cisco Data Center Day 2008 31-01-2008 APC-MGE Vision & Mission OUR VISION APC-MGE products ensure availability wherever data is created, transmitted

More information

Cooling on Demand - scalable and smart cooling solutions. Marcus Edwards B.Sc.

Cooling on Demand - scalable and smart cooling solutions. Marcus Edwards B.Sc. Cooling on Demand - scalable and smart cooling solutions Marcus Edwards B.Sc. Schroff UK Limited Data Centre cooling what a waste of money! A 1MW data center needs 177,000,000 kwh in its lifetime of 10

More information

How Liquid Cooling Helped Two University Data Centers Achieve Cooling Efficiency Goals. Michael Gagnon Coolcentric October

How Liquid Cooling Helped Two University Data Centers Achieve Cooling Efficiency Goals. Michael Gagnon Coolcentric October How Liquid Cooling Helped Two University Data Centers Achieve Cooling Efficiency Goals Michael Gagnon Coolcentric October 13 2011 Data Center Trends Energy consumption in the Data Center (DC) 2006-61 billion

More information

Overcoming the Challenges of Server Virtualisation

Overcoming the Challenges of Server Virtualisation Overcoming the Challenges of Server Virtualisation Maximise the benefits by optimising power & cooling in the server room Server rooms are unknowingly missing a great portion of their benefit entitlement

More information

Current Data Center Design. James Monahan Sept 19 th 2006 IEEE San Francisco ComSoc

Current Data Center Design. James Monahan Sept 19 th 2006 IEEE San Francisco ComSoc Current Data Center Design James Monahan Sept 19 th 2006 IEEE San Francisco ComSoc What is the biggest facility problem in your data center? 35% 30% 25% 20% 15% Series1 10% 5% 0% Excessive heat Insufficient

More information

84 kw, Tier 3, Direct Expansion, 937 ft 2

84 kw, Tier 3, Direct Expansion, 937 ft 2 [Reference Design 42] 84 kw, Tier 3, Direct Expansion, 937 ft 2 DESIGN OVERVIEW Data Center IT Capacity 84 kw Target Availability Tier 3 Annualized PUE at 100% Load 1.712 Total Racks and Average Density

More information

The Efficient Enterprise. All content in this presentation is protected 2008 American Power Conversion Corporation

The Efficient Enterprise. All content in this presentation is protected 2008 American Power Conversion Corporation Ee The Efficient Enterprise All content in this presentation is protected 2008 American Power Conversion Corporation Keystrokes Kilowatts Heat OUT Electricity IN Need for bandwidth exploding Going hyperbolic!

More information

Future of Cooling High Density Equipment. Steve Madara Vice President and General Manager Liebert Precision Cooling Business Emerson Network Power

Future of Cooling High Density Equipment. Steve Madara Vice President and General Manager Liebert Precision Cooling Business Emerson Network Power Future of Cooling High Density Equipment Steve Madara Vice President and General Manager Liebert Precision Cooling Business Emerson Network Power Agenda Issues facing the Data Center Managing the explosive

More information

MSYS 4480 AC Systems Winter 2015

MSYS 4480 AC Systems Winter 2015 MSYS 4480 AC Systems Winter 2015 Module 12: DATA CENTERS By Satwinder Singh 14/05/2015 1 Data Centers Data Centers are specialized environments that safeguard your company's most valuable equipment and

More information

Passive RDHx as a Cost Effective Alternative to CRAH Air Cooling. Jeremiah Stikeleather Applications Engineer

Passive RDHx as a Cost Effective Alternative to CRAH Air Cooling. Jeremiah Stikeleather Applications Engineer Passive RDHx as a Cost Effective Alternative to CRAH Air Cooling Jeremiah Stikeleather Applications Engineer Passive RDHx as a Cost Effective Alternative to CRAH Air Cooling While CRAH cooling has been

More information

Green Computing: Datacentres

Green Computing: Datacentres Green Computing: Datacentres Simin Nadjm-Tehrani Department of Computer and Information Science (IDA) Linköping University Sweden Many thanks to Jordi Cucurull For earlier versions of this course material

More information

Data Center Trends: How the Customer Drives Industry Advances and Design Development

Data Center Trends: How the Customer Drives Industry Advances and Design Development Bablu Kazi, PE MORRISON HERSHFIELD MISSION CRITICAL Data Center Trends: How the Customer Drives Industry Advances and Design Development What does the Customer Need? Scalability P U E Latest Technology

More information

Green Computing: Datacentres

Green Computing: Datacentres Green Computing: Datacentres Simin Nadjm-Tehrani Department of Computer and Information Science (IDA) Linköping University Sweden Many thanks to Jordi Cucurull For earlier versions of this course material

More information

White Paper - Infrastructure in an energy-efficient data centre

White Paper - Infrastructure in an energy-efficient data centre White Paper - Infrastructure in an energy-efficient data centre Verena Schwalfenberg Dipl.-Ing. Markus Schmidt Copyright 2008 All rights reserved. Rittal GmbH & Co. KG Auf dem Stützelberg D-35745 Herborn

More information

Data center cooling evolution. The hottest way to save energy. Lucio Bustaffa: Product Development Manager BlueBox Group

Data center cooling evolution. The hottest way to save energy. Lucio Bustaffa: Product Development Manager BlueBox Group Data center cooling evolution. The hottest way to save energy Lucio Bustaffa: Product Development Manager BlueBox Group Data Center overview What s happening in the web? 2 Data Center overview What s happening

More information

BENEFITS OF ASETEK LIQUID COOLING FOR DATA CENTERS

BENEFITS OF ASETEK LIQUID COOLING FOR DATA CENTERS BENEFITS OF ASETEK LIQUID COOLING FOR DATA CENTERS Asetek has leveraged its expertise as the world-leading provider of efficient liquid cooling systems to create its RackCDU and ISAC direct-to-chip liquid

More information

Warehouse-Scale Computers to Exploit Request-Level and Data-Level Parallelism

Warehouse-Scale Computers to Exploit Request-Level and Data-Level Parallelism Warehouse-Scale Computers to Exploit Request-Level and Data-Level Parallelism The datacenter is the computer Luiz Andre Barroso, Google (2007) Outline Introduction to WSCs Programming Models and Workloads

More information

Trends and legislations in the data center industry. Pär Åberg - Business Development Manager - Swegon

Trends and legislations in the data center industry. Pär Åberg - Business Development Manager - Swegon Trends and legislations in the data center industry Pär Åberg - Business Development Manager - Swegon DC Fastest growing industry in the world 2 Fast and furious 3 IT services in the driving seat of the

More information

7 Best Practices for Increasing Efficiency, Availability and Capacity. XXXX XXXXXXXX Liebert North America

7 Best Practices for Increasing Efficiency, Availability and Capacity. XXXX XXXXXXXX Liebert North America 7 Best Practices for Increasing Efficiency, Availability and Capacity XXXX XXXXXXXX Liebert North America Emerson Network Power: The global leader in enabling Business-Critical Continuity Automatic Transfer

More information

Avoiding Costs From Oversizing Datacenter Infrastructure

Avoiding Costs From Oversizing Datacenter Infrastructure Avoiding Costs From Oversizing Datacenter Infrastructure White Paper # 37 Executive Summary The physical and power infrastructure of data centers is typically oversized by more than 100%. Statistics related

More information

Distributed Pervasive Systems

Distributed Pervasive Systems Distributed Pervasive Systems CS677 Guest Lecture Tian Guo Lecture 26, page 1 Outline Distributed Pervasive Systems Popular Application domains Sensor nodes and networks Energy in Distributed Systems (Green

More information

DATA CENTER COLOCATION BUILD VS. BUY

DATA CENTER COLOCATION BUILD VS. BUY DATA CENTER COLOCATION BUILD VS. BUY Comparing the total cost of ownership of building your own data center vs. buying third-party colocation services Executive Summary As businesses grow, the need for

More information

Smart Data Centres. Robert M Pe, Data Centre Consultant HP Services SEA

Smart Data Centres. Robert M Pe, Data Centre Consultant HP Services SEA Smart Data Centres Robert M Pe, Data Centre Consultant Services SEA 2006 Hewlett-Packard Development Company, L.P. The information contained herein is subject to change without notice Content Data center

More information

Mission Critical Facilities & Technology Conference November 3, 2011 Cooling 101. Nick Gangemi Regional Sales Manager Data Aire

Mission Critical Facilities & Technology Conference November 3, 2011 Cooling 101. Nick Gangemi Regional Sales Manager Data Aire Mission Critical Facilities & Technology Conference November 3, 2011 Cooling 101 Nick Gangemi Regional Sales Manager Data Aire Agenda Exactly what are we talking about ASHRAE TC 9.9 Design best practices

More information

Combining Cold Aisle Containment with Intelligent Control to Optimize Data Center Cooling Efficiency

Combining Cold Aisle Containment with Intelligent Control to Optimize Data Center Cooling Efficiency A White Paper from the Experts in Business-Critical Continuity TM Combining Cold Aisle Containment with Intelligent Control to Optimize Data Center Cooling Efficiency Executive Summary Energy efficiency

More information

2016 COOLING THE EDGE SURVEY. Conducted by Vertiv Publication Date: August 30, 2016

2016 COOLING THE EDGE SURVEY. Conducted by Vertiv Publication Date: August 30, 2016 2016 COOLING THE EDGE SURVEY Conducted by Vertiv Publication Date: August 30, 2016 TWO STAGE POWER DISTRIBUTION Table of Contents Section I: Methodology Section II: Key Findings 1. Strategic Importance

More information

MEASURE MONITOR UNDERSTAND

MEASURE MONITOR UNDERSTAND MEASURE MONITOR UNDERSTAND Presented by Alistair Hunt Energy Monitoring, Measurement metrics Where and What 1 History & Background Company Timeline 18 Years Comrac & Sinetica founded 15 Years Raritan Integration

More information

Powering Change in the Data Center. A White Paper from the Experts in Business-Critical Continuity TM

Powering Change in the Data Center. A White Paper from the Experts in Business-Critical Continuity TM Powering Change in the Data Center A White Paper from the Experts in Business-Critical Continuity TM Executive Summary Increases in data center density and diversity are driving change in the power and

More information

How High Temperature Data Centers & Intel Technologies save Energy, Money, Water and Greenhouse Gas Emissions

How High Temperature Data Centers & Intel Technologies save Energy, Money, Water and Greenhouse Gas Emissions Intel Intelligent Power Management Intel How High Temperature Data Centers & Intel Technologies save Energy, Money, Water and Greenhouse Gas Emissions Power savings through the use of Intel s intelligent

More information

Optimization in Data Centres. Jayantha Siriwardana and Saman K. Halgamuge Department of Mechanical Engineering Melbourne School of Engineering

Optimization in Data Centres. Jayantha Siriwardana and Saman K. Halgamuge Department of Mechanical Engineering Melbourne School of Engineering Optimization in Data Centres Jayantha Siriwardana and Saman K. Halgamuge Department of Mechanical Engineering Melbourne School of Engineering Outline Background and Motivation Overview and scale of data

More information

3300 kw, Tier 3, Chilled Water, 70,000 ft 2

3300 kw, Tier 3, Chilled Water, 70,000 ft 2 [Reference Design 22] 3300 kw, Tier 3, Chilled Water, 70,000 ft 2 DESIGN OVERVIEW Data Center IT Capacity 1100 kw per Data Hall 3 Independent Data Halls Design Application Range This design can be applied

More information

Close Coupled Cooling for Datacentres

Close Coupled Cooling for Datacentres Close Coupled Cooling for Datacentres Dr Fathi Tarada Mosen Ltd fathi.tarada@mosenltd.com www.mosenltd.com Agenda Increasing Power Densities Raised Floor Limitations Hot and Cold Aisle Enclosures Close

More information

DC Energy, Efficiency Challenges

DC Energy, Efficiency Challenges DC Energy, Efficiency Challenges Choosing a density strategy Implementing a high density environment Maximizing the efficiency benefit Anticipating the dynamic data center Key points on energy usage in

More information

Survey and Audit Service Schedule. Airflow and Thermal Imaging Survey Service Schedule. Data Centre Solutions Expertly Engineered

Survey and Audit Service Schedule. Airflow and Thermal Imaging Survey Service Schedule. Data Centre Solutions Expertly Engineered Survey and Audit Service Schedule Airflow and Thermal Imaging Survey Service Schedule Data Centre Solutions Expertly Engineered Consult optimisation, audit and survey services Data Centre Services Workspace

More information

Continuity Insights Chicago: Evolving Data Center Trends & Design Standards. 19 June Jose Hernandez, 30+ years of design/build experience

Continuity Insights Chicago: Evolving Data Center Trends & Design Standards. 19 June Jose Hernandez, 30+ years of design/build experience Continuity Insights Chicago: Evolving Data Center Trends & Design Standards Technology Management, Inc. 1911 Rohlwing Rd., Suite E Rolling Meadows, IL 60008 847 394 8900 19 June 2013 www.tmiamerica.com

More information

How much power?! Data Centre Efficiency. How much Money?! Carbon Reduction Commitment (CRC)

How much power?! Data Centre Efficiency. How much Money?! Carbon Reduction Commitment (CRC) How much power?! Data Centre Efficiency The US EPA found in 2006 data centres used 1.5% of total US consumption (5) For Bangor University data centres use approximately 5-10% of the total university electricity

More information

NREL Validates LCS Technology. PRESENTED BY Herb Zien CEO, LiquidCool Solutions

NREL Validates LCS Technology. PRESENTED BY Herb Zien CEO, LiquidCool Solutions NREL Validates LCS Technology PRESENTED BY Herb Zien CEO, LiquidCool Solutions Learning Objectives As much as 40% of data center power is used to circulate air, and fans in a typical 30-megawatt data center

More information

Data Center Design: Power, Cooling & Management

Data Center Design: Power, Cooling & Management Presents Data Center Design: Power, Cooling & Management The Legacy Data Center Large (oversized) UPS Systems Large Power Distribution Systems N, N+1, 2N, 2(N+1) UPS topologies Large Free standing

More information

PROCESS & DATA CENTER COOLING. How and Why To Prepare For What s To Come JOHN MORRIS REGIONAL DIRECTOR OF SALES

PROCESS & DATA CENTER COOLING. How and Why To Prepare For What s To Come JOHN MORRIS REGIONAL DIRECTOR OF SALES PROCESS & DATA CENTER COOLING How and Why To Prepare For What s To Come JOHN MORRIS REGIONAL DIRECTOR OF SALES CONGRATULATIONS 2 BOLD PREDICTION 3 Where We Are TODAY Computer Technology NOW advances more

More information

White paper adaptive IT infrastructures

White paper adaptive IT infrastructures Contents Executive summary... 4 Introduction... 5 Reference architecture... 6 Objective of a comprehensive regulation system... 8 First objective: optimal energy operating point... 8 Second objective:

More information

Rittal Cooling Solutions A. Tropp

Rittal Cooling Solutions A. Tropp 1 Rittal Cooling Solutions Presented by Adam Tropp 2 Agenda Cooling Strategies Aisle Containment Chimney Solution Airstream Management Rittal Liquid Cooling Packages Data Monitoring 3 Cooling strategies.

More information

Energy Efficient Data Centers

Energy Efficient Data Centers IBM Systems and Technology Group Lab Services Energy Efficient Data Centers Steven Ahladas IBM Corp ahladas@us.ibm.com Keeping our clients in the race. All trends going the same way. IT Servers were an

More information

Increasing Data Center Efficiency by Using Improved High Density Power Distribution

Increasing Data Center Efficiency by Using Improved High Density Power Distribution Increasing Data Center Efficiency by Using Improved High Density Power Distribution By Neil Rasmussen White Paper #128 Revision 1 Executive Summary A new approach to power distribution for high density

More information

Systems and Technology Group. IBM Technology and Solutions Jan Janick IBM Vice President Modular Systems and Storage Development

Systems and Technology Group. IBM Technology and Solutions Jan Janick IBM Vice President Modular Systems and Storage Development Systems and Technology Group IBM Technology and Solutions Jan Janick IBM Vice President Modular Systems and Storage Development Power and cooling are complex issues There is no single fix. IBM is working

More information

Application of TileFlow to Improve Cooling in a Data Center

Application of TileFlow to Improve Cooling in a Data Center Case Study Application of TileFlow to Improve Cooling in a Data Center 3025 Harbor Lane North, Suite 300 Plymouth, MN 55447 USA Copyright 2004 Innovative Research, Inc. 2 Introduction A large insurance

More information

Newave s approach for protecting mission critical application

Newave s approach for protecting mission critical application ABB Technology Show, May 2013 Newave s approach for protecting mission critical application May 13, 2013 Slide 1 Contents Newave s company overview Electricity environment and trend Data Centre environment

More information

Data Center Energy and Cost Saving Evaluation

Data Center Energy and Cost Saving Evaluation Available online at www.sciencedirect.com ScienceDirect Energy Procedia 75 (2015 ) 1255 1260 The 7 th International Conference on Applied Energy ICAE2015 Data Center Energy and Cost Saving Evaluation Z.

More information

SIX Trends in our World

SIX Trends in our World Data Center Infrastructure for Cloud and Energy Efficiency SIX Trends in our World Connectivity Simplicity StruxureWare TM for data centers TuanAnh Nguyen, Solution Engineer Manager, Vietnam Schneider

More information

Efficiency of Data Center cooling

Efficiency of Data Center cooling Efficiency of Data Center cooling Comparison of data room layouts and cooling systems Bohumil Cimbal Product manager for Cooling Systems in CONTEG Company Objective Basic questions between investor and

More information

Data Center Design: Power, Cooling & Management

Data Center Design: Power, Cooling & Management Presents Data Center Design: Power, Cooling & Management The Legacy Data Center Large (oversized) UPS Systems Large Power Distribution Systems N, N+1 UPS topologies Large Free standing Static Switches

More information

9.6 MW, Traditional IT and OCP-compatible, Indirect Air Economizer, m 2

9.6 MW, Traditional IT and OCP-compatible, Indirect Air Economizer, m 2 [Reference esign 62] 9.6 MW, Traditional IT and OC-compatible, Indirect Air Economizer, 16970 m 2 ESIGN OVERVIEW ata Center IT Capacity 9.6 MW Target Availability Tier III with 2N power distribution and

More information

Datacenter Efficiency Trends. Cary Roberts Tellme, a Microsoft Subsidiary

Datacenter Efficiency Trends. Cary Roberts Tellme, a Microsoft Subsidiary Datacenter Efficiency Trends Cary Roberts Tellme, a Microsoft Subsidiary Power Slashing Tools P3 Kill-A-WATT Measures min, max, and instantaneous voltage and current draw Calculates power (watts), kilowatt

More information

Maximise Data Center Value

Maximise Data Center Value Maximise Data Center Value with Higher Density Infrastructure Dramatic cost savings enabled; Requires solving unique electrical + cooling challenges; 08 December 2015 Speaker gokhan.gulal@4g.net.tr Genel

More information

Cooling. Highly efficient cooling products for any IT application. For More Information: (866) DATA CENTER SOLUTIONS

Cooling. Highly efficient cooling products for any IT application. For More Information: (866) DATA CENTER SOLUTIONS Cooling > Highly efficient cooling products for any IT application. DATA CENTER SOLUTIONS For More Information: (866) 787-3271 Sales@PTSdcs.com End-to-End Cooling Solutions from the Closet to the Data

More information

5.2 MW, Pod-based build, Chilled Water, ft 2

5.2 MW, Pod-based build, Chilled Water, ft 2 [Reference Design 65] 5.2 MW, Pod-based build, hilled Water, 85000 ft 2 DESIGN OVERVIEW Data enter apacity 5.2 MW Target Availability Tier III with 2N power distribution and less-redundant generator configuration

More information

Energy Logic: Emerson Network Power. A Roadmap for Reducing Energy Consumption in the Data Center. Ross Hammond Managing Director

Energy Logic: Emerson Network Power. A Roadmap for Reducing Energy Consumption in the Data Center. Ross Hammond Managing Director Energy Logic: A Roadmap for Reducing Energy Consumption in the Data Center Emerson Network Power Ross Hammond Managing Director Agenda Energy efficiency Where We Are Today What Data Center Managers Are

More information

EP s approach to Power & Energy efficiency in DCs & paradigms

EP s approach to Power & Energy efficiency in DCs & paradigms DG for Innovation and Technological Support EP s approach to Power & Energy efficiency in DCs & paradigms Presentation Presentation subtitle subtitle or lead-in or lead-in that says that what says what

More information

Lecture 20: WSC, Datacenters. Topics: warehouse-scale computing and datacenters (Sections )

Lecture 20: WSC, Datacenters. Topics: warehouse-scale computing and datacenters (Sections ) Lecture 20: WSC, Datacenters Topics: warehouse-scale computing and datacenters (Sections 6.1-6.7) 1 Warehouse-Scale Computer (WSC) 100K+ servers in one WSC ~$150M overall cost Requests from millions of

More information

IT Air Conditioning Units

IT Air Conditioning Units IT Air Conditioning Units Modern Flexible Effective Energy Saving CoolTeg Plus and CoolTop overview CoolTeg Plus CW CoolTeg Plus DX CoolTeg Plus XC CoolTop Installation Between IT racks On top of IT rack

More information

> Executive summary. Virtualization: Optimized Power and Cooling to Maximize Benefits. White Paper 118 Revision 2. Contents.

> Executive summary. Virtualization: Optimized Power and Cooling to Maximize Benefits. White Paper 118 Revision 2. Contents. Virtualization: Optimized Power and Cooling to Maximize Benefits White Paper 118 Revision 2 by Suzanne Niles Click on a section to jump to it > Executive summary Data centers are routinely and unknowingly

More information

How to Increase Data Center Efficiency

How to Increase Data Center Efficiency How to Increase Data Center Efficiency Shivani Shukla Potkar Product Marketing Manager Pentair Electronics Protection High cooling efficiency & and reduced power consumption enhances the balance between

More information

PowerWAVE 9000DPA Designed to meet the requirements of today and tomorrow

PowerWAVE 9000DPA Designed to meet the requirements of today and tomorrow PowerWAVE 9000DPA Designed to meet the requirements of today and tomorrow PowerWAVE 9000DPA: Delivers class-leading Six Nines (99.9999%) power availability. PowerWAVE 9000DPA Up to 250 kva (200 kva N+1)

More information

Data Center Trends and Challenges

Data Center Trends and Challenges Data Center Trends and Challenges, IBM Fellow Chief Engineer - Data Center Energy Efficiency Customers challenges are driven by the following Increasing IT demand Continued cost pressure Responsive to

More information

Ecolibrium. Cloud control. Keeping data centres cool. OCTOBER 2018 VOLUME 17.9 RRP $14.95 PRINT POST APPROVAL NUMBER PP352532/00001

Ecolibrium. Cloud control. Keeping data centres cool. OCTOBER 2018 VOLUME 17.9 RRP $14.95 PRINT POST APPROVAL NUMBER PP352532/00001 Ecolibrium OCTOBER 2018 VOLUME 17.9 RRP $14.95 PRINT POST APPROVAL NUMBER PP352532/00001 Cloud control Keeping data centres cool. COVER FEATURE Cloud control Such is the growth in data centres globally

More information

Data Center Infrastructure Management (D.C.I.M.)

Data Center Infrastructure Management (D.C.I.M.) Data Center Infrastructure Management (D.C.I.M.) Garies Chong, RCDD, DCDC. BICSI Southeast Asia District Chair Managing Director of EMS Wiring Systems Pte Ltd Data Center Infrastructure Management (D.C.I.M.)

More information

Industry leading low energy evaporative fresh air cooling.

Industry leading low energy evaporative fresh air cooling. Industry leading low energy evaporative fresh air cooling. Freecool Evaporative Free Air Cooling by Workspace Technology delivers innovative low energy cooling for a range of applications including data

More information

Next Generation Cooling

Next Generation Cooling Next Generation Cooling Server Manufacturer Perspective Practical and Cost Effective David Moss Data Center Strategist Dell 1 Why Chip, Row, or Rack? Density? Energy Don t be scared; I don t see 50kW/rack

More information

SMART SOLUTIONS TM INTELLIGENT, INTEGRATED INFRASTRUCTURE FOR THE DATA CENTER

SMART SOLUTIONS TM INTELLIGENT, INTEGRATED INFRASTRUCTURE FOR THE DATA CENTER SMART SOLUTIONS TM INTELLIGENT, INTEGRATED INFRASTRUCTURE FOR THE DATA CENTER Enabling Tomorrow s CRITICAL EDGE INFRASTRUCTURE We helped some of the largest names in the industry bring new capacity online

More information

Cooling Solutions & Considerations for High Performance Computers

Cooling Solutions & Considerations for High Performance Computers Cooling Solutions & Considerations for High Performance Computers White Paper 6 Revision 1 By Rich Whitmore Executive summary The recent advances in high performance computing have driven innovations not

More information

Using CFD Analysis to Predict Cooling System Performance in Data Centers Ben Steinberg, P.E. Staff Applications Engineer

Using CFD Analysis to Predict Cooling System Performance in Data Centers Ben Steinberg, P.E. Staff Applications Engineer Using CFD Analysis to Predict Cooling System Performance in Data Centers Ben Steinberg, P.E. Staff Applications Engineer Agenda What is CFD? Applications of CFD Applicability to the Data Center How it

More information

PEX+ High Efficiency, Low Operating Cost Precision Solution for Data Centers

PEX+ High Efficiency, Low Operating Cost Precision Solution for Data Centers TM PEX+ High Efficiency, Low Operating Cost Precision Solution for Data Centers WE ARE VERTIV Vertiv, formerly Emerson Network Power, designs, builds, and services mission critical technologies that enable

More information

LCS Value Proposition November 2014

LCS Value Proposition November 2014 LCS Value Proposition November 2014 Data Center Trends 2014 Improving Data Center Power Efficiency & Reducing Carbon Footprint Initiatives for raising data center temperatures Data center upgrades for

More information

Cloud environment. dr inż. Piotr Boryło , Kraków

Cloud environment. dr inż. Piotr Boryło , Kraków Cloud environment dr inż. Piotr Boryło 7.03.2018, Kraków Agenda Cloud fundamentals Greening the cloud Intercloud Fog/Edge Computing Network Function Virtualization SDN for clouds Testing the cloud vs cloud

More information

Commercialization of the Cloud Platform Suite and Endeavors toward a High-Efficiency Server

Commercialization of the Cloud Platform Suite and Endeavors toward a High-Efficiency Server Commercialization of the Cloud Platform Suite and Endeavors toward a High-Efficiency Server SUZUKI Kumiko, MATSUMOTO Shintaro, YOSHIZAWA Kentarou OCHI Ichiro, SHIMADA Hiroshi, KOGUCHI Kazuto Abstract This

More information

ABB Automation & Power World: April 18-21, 2011 CLP CEU Myth Busting: The Truth behind Data Center Marketing Trends

ABB Automation & Power World: April 18-21, 2011 CLP CEU Myth Busting: The Truth behind Data Center Marketing Trends ABB Automation & Power World: April 18-21, 2011 CLP-101-1-CEU Myth Busting: The Truth behind Data Center Marketing Trends May 10, 2011 Slide 1 CLP-101-1-CEU Myth Busting: The Truth behind Data Center Marketing

More information

PowerWave 9000DPA Designed to meet the requirements of today and tomorrow

PowerWave 9000DPA Designed to meet the requirements of today and tomorrow PowerWave 9000DPA Designed to meet the requirements of today and tomorrow PowerWAVE 9000DPA: Delivers class-leading Six Nines (99.9999%) power availability. PowerWAVE 9000DPA Up to 250 kva (200 kva N+1)

More information

A) Differences between Precision and Comfort Cooling Here are the major differences exist between precision air conditioning and comfort systems.

A) Differences between Precision and Comfort Cooling Here are the major differences exist between precision air conditioning and comfort systems. DATA CENTRE COOLING SYSTEM A) Differences between Precision and Comfort Cooling Here are the major differences exist between precision air conditioning and comfort systems. 1. Cooling Optimized to Electronic

More information

How to improve efficiency in Data Processing Centres (DPCs) The importance of knowing the PUE. center DPC

How to improve efficiency in Data Processing Centres (DPCs) The importance of knowing the PUE. center DPC 12 Technology for energy efficiency www.circutor.com Technical article Francisco Domínguez Network Quality Division How to improve efficiency in Data Processing Centres (DPCs) The importance of knowing

More information

Data Center Fundamentals: The Datacenter as a Computer

Data Center Fundamentals: The Datacenter as a Computer Data Center Fundamentals: The Datacenter as a Computer George Porter CSE 124 Feb 10, 2017 Includes material from (1) Barroso, Clidaras, and Hölzle, as well as (2) Evrard (Michigan), used with permission

More information

HPC Solutions in High Density Data Centers

HPC Solutions in High Density Data Centers Executive Report HPC Solutions in High Density Data Centers How CyrusOne s Houston West data center campus delivers the highest density solutions to customers With the ever-increasing demand on IT resources,

More information

Thermal management. Thermal management

Thermal management. Thermal management Thermal management Thermal management Managing thermal loads is a major challenge for all Data Centre operators. Effecting proper control of the thermal environment drives energy consumption and ultimately

More information

APC APPLICATION NOTE #74

APC APPLICATION NOTE #74 #74 Configuration of InfraStruXure for Data Centers to Support Dell PowerEdge 1855 Abstract Many companies are making plans to incorporate Dell PowerEdge Blade Servers into their data center applications.

More information

DCIM Solutions to improve planning and reduce operational cost across IT & Facilities

DCIM Solutions to improve planning and reduce operational cost across IT & Facilities DCIM Solutions to improve planning and reduce operational cost across IT & Facilities Presented by: Chi Sen, Director, Data Centre Software Solutions, APJ & EMEA Schneider Electric Data Center Solutions

More information

Green Cloud: Emerging trends and their Impacts

Green Cloud: Emerging trends and their Impacts Green : Emerging trends and their Impacts Miss.Swati S.Tawade Lecturer, Computer Engineering, Yadavrao Tasgaonkar Institute of Technology,Maharashtra,India --------------------------------------------------------------****---------------------------------------------------------------

More information

Reducing Data Center Cooling Costs through Airflow Containment

Reducing Data Center Cooling Costs through Airflow Containment FEATURE Reducing Data Center Cooling Costs through Airflow Containment Implementing a containment solution in the data center costs much less than the alternatives of adding air handlers or other supplemental

More information

Ten Cooling Solutions to Support High-density Server Deployment. Schneider Electric Data Center Science Center White Paper #42

Ten Cooling Solutions to Support High-density Server Deployment. Schneider Electric Data Center Science Center White Paper #42 Ten Cooling Solutions to Support High-density Server Deployment Schneider Electric Data Center Science Center White Paper #42 1 Introduction 2 Introduction This paper provides 10 approaches for increasing

More information

Predictive Resilience: Leveraging Integrated DCIM to Reduce Data Center Downtime

Predictive Resilience: Leveraging Integrated DCIM to Reduce Data Center Downtime July 17, 2013 Predictive Resilience: Leveraging Integrated DCIM to Reduce Data Center Downtime siemens.com/answers Predictive Resilience Table of content What is DCIM & Its Business Value Extract Maximum

More information

Liebert DCW CATALOGUE

Liebert DCW CATALOGUE Liebert DCW CATALOGUE Chilled Water-Based High Density Cooling For The Data Center LIEBERT DCW Flexible Approaches For Energy Efficient Cooling Save up to 70% in cooling energy usage Data center managers

More information

Charles Nolan. Do more with less with your data centre A customer s perspective. Director IT Infrastructure, UNSW. Brought to you by:

Charles Nolan. Do more with less with your data centre A customer s perspective. Director IT Infrastructure, UNSW. Brought to you by: Charles Nolan Director IT Infrastructure, UNSW Do more with less with your data centre A customer s perspective Brought to you by: Today s Enterprise Data Centre Doing more with less High Density Data

More information

The Evolving Data Center

The Evolving Data Center The Evolving Data Center Dominic Loh Product Manager, Power Quality, APAC Data Centers are enabling global growth Proliferation of mobile computing Digitalization of everything Big Data 2 Evolution of

More information

Avoidable Mistakes that Compromise Cooling Performance in Data Centers and Network Rooms

Avoidable Mistakes that Compromise Cooling Performance in Data Centers and Network Rooms Avoidable Mistakes that Compromise Cooling Performance in Data Centers and Network Rooms Problem Several cooling system mistakes are very common and avoidable Mistakes compromise availability and increase

More information

2000 kw, Tier 3, Chilled Water, Prefabricated, sq. ft.

2000 kw, Tier 3, Chilled Water, Prefabricated, sq. ft. [Reference Design 64] 2000 kw, Tier 3, Chilled Water, refabricated, 23700 sq. ft. DESIGN OVERVIEW Data Center IT Capacity 2000 kw Target Availability Tier 3 Annualized E at 100% Load 1.64 in Miami, FL

More information

Energy Efficiency and WCT Innovations

Energy Efficiency and WCT Innovations Energy Efficiency and WCT Innovations Zeeshan Kamal Siddiqi HPC Leader Middle East, Turkey and Africa (META) Lenovo 2017 Lenovo. All rights reserved. Why do we have a problem? Higher TDP Processors Data

More information

IBM eserver Total Storage, On Demand

IBM eserver Total Storage, On Demand IBM eserver Total Storage, On Demand Bill Ott, Vice President, eserver xseries & IntelliStation Development Systems and Technology Group 10/7/2005 IBM 2Q 2005 Business Status Key Accomplishments Operational

More information

The End of Redundancy. Alan Wood Sun Microsystems May 8, 2009

The End of Redundancy. Alan Wood Sun Microsystems May 8, 2009 The End of Redundancy Alan Wood Sun Microsystems May 8, 2009 Growing Demand, Shrinking Resources By 2008, 50% of current data centers will have insufficient power and cooling capacity to meet the demands

More information

ΕΠΛ372 Παράλληλη Επεξεργάσια

ΕΠΛ372 Παράλληλη Επεξεργάσια ΕΠΛ372 Παράλληλη Επεξεργάσια Warehouse Scale Computing and Services Γιάννος Σαζεϊδης Εαρινό Εξάμηνο 2014 READING 1. Read Barroso The Datacenter as a Computer http://www.morganclaypool.com/doi/pdf/10.2200/s00193ed1v01y200905cac006?cookieset=1

More information

1008 kw, Tier 2, Chilled Water, ft 2

1008 kw, Tier 2, Chilled Water, ft 2 [eference Design 81] 1008 kw, Tier 2, hilled Water, 18115 ft 2 DESIGN OVEVIEW Data enter IT apacity 1008 kw Adaptable from 200 kw to 3024 kw Target Availability Tier 2 Annualized PUE at 100% Load 1.65

More information

Delivering Next Generation DCIM for a Mobile Workforce

Delivering Next Generation DCIM for a Mobile Workforce Delivering Next Generation DCIM for a Mobile Workforce 1 About Optimum Path Optimum Path Inc. is a software company, headquartered in Florida, USA with locations in APAC and EMEA regions. We continue to

More information

Data center redundancy. Air traffic High-speed pipes. Training Design. Costs. Guy with a wrench. Terrorism

Data center redundancy. Air traffic High-speed pipes. Training Design. Costs. Guy with a wrench. Terrorism Data center redundancy Costs Training Design Air traffic High-speed High speed pipes Guy with a wrench Terrorism Fire Communications Backup and Network power Power di t ib ti distribution Security Governance

More information