Maximise Data Center Value
|
|
- Stephen Beasley
- 5 years ago
- Views:
Transcription
1 Maximise Data Center Value with Higher Density Infrastructure Dramatic cost savings enabled; Requires solving unique electrical + cooling challenges; 08 December 2015
2 Speaker Genel Müdür 4G İletişim Teknolojileri A.Ş.
3 Data Center Investments Keep Increasing Continued Infrastructure Growth Number of data centers increasing Average size of data centers also increasing Even though footprint of equipment is decreasing Driven by Underlying Storage and Compute Demand business intelligence / data mining e-commerce at every scale private cloud better & cheaper bandwidth RESULTS OpEx requirement (or CapEx for co-location) increasing; Budgets not keeping pace; Massive consolidation efforts and shift to co-location;
4 Even When Server Power Draw Decreasing Year Watts / U 2004 (DL360G3) 360 W 2008 (DL360G5) 238 W 2011 (DL360G7) 157 W 2013 (DL360G8) 170 W 2015 (DL360G9) 105W Source: Data Center Pulse. Wiersma, Jan. Where is the Rack Density Trend Going? ; HP QuickSpecs Combining major CPU improvements in power/mips better underlying h/w architecture e.g. High-efficiency PSUs e.g. Move to SSDs e.g. Improved front-side bus architectures (RAM) standard 1U / 2U servers are actually less power-hungry per U.
5 Customers Face Immense Upfront Costs: Infrastructure + Real Estate Air Handlers Switchgear Transformers Chillers / Economizers Generators CRAC / CRAH UPS RPP / Panel Board / Distribution Board Owner operated = CapEx Co-location facility = OpEx Before a single CPU is powered on, incredible investments must be made; Land and Building
6 Real Estate Prices Increasing Prohibitively In certain regions, no viable candidate sites available for data center development; e.g. Hong Kong (Google, other multinationals) Some companies convert commercial buildings into data center (limits space and usability) Real Estate Costs + Infrastructure Costs # of Cabinets Per rack investments are massive and fixed ; = fixed investment per rack Therefore, massive returns from increasing cabinet power density.
7 Increased Power Density Enables Consolidation Increase to 11KVA Add 7.5 KVA Avg load /rack = 3.5 KVA Rack 1 Rack 2 Rack 3 Rack 4 Rack 5 Rack 6 Rack 7 Rack KVA Reduce Racks Free Space
8 but Typically Requires Shift to 3ph Phase 16A 32A 63A 16A 32A 63A Single phase Single phase Single phase Three phase Three phase Three phase Input Voltage 230V 230V 230V 400V 400V 400V Output Voltage 230V 230V 230V 230V 230V 230V Active power 3.7 kw 7.4 kw 14.5 kw 11 kw 22.1kW 43.6 kw # of servers * 57 52* # of blades n/a 32 (2 chassis) 64 (4 chassis) 48 (3 chassis) 80* (5 chassis) * Could power more, but cannot fit in standard cabinet HP Proliant DL360pG8 1U server, 192 watts at 70% load HP Proliant C7000 w/ 16x Proliant BL460c Gen8, 3710 watts at 70% load
9 415v / 3ph : Dramatically Increases Density
10 But High Density Racks Face Unique Challenges Weight. Can cabinet handle increased static and dynamic load? Cooling. Can air handlers, chillers, etc. be scaled to exhaust increased heat? Power. Adequate UPS and other infrastructure? Understand complexities of branch circuit in cabinet? Known, proven solutions exist for all these challenges. Cost more per cabinet vs. lower density; But far outweighed by cost savings of increased utilization.
11 Proper Feed Sizing for High Density Blade Chassis Prevalence of blade servers increasing every year; Increased confusion regarding power interconnects required to maintain true 2N; Issue compounded when clients solely consider power capacity guidelines of RPP / distribution panel feed; e.g. Cisco UCS U height; ~1800W typical; ~2300W peak; 4x Power Supplies, up to 2500W each; e.g. 415V, 3phase WYE; 32a Supply 23,000VA / ~22,400 Watts; In theory, should support up to ( ) = 9 chassis; Let s try seven (48U rack)
12 Proper Feed Sizing for High Density Blade Chassis First Connect Six Chassis (14.2kVA) Peak = 4.9A per connection; Peak (Failure Mode) = on one plug
13 Proper Feed Sizing for High Density Blade Chassis Even with B-side down, each circuit breaker at 61% load. Very safe.
14 Proper Feed Sizing for High Density Blade Chassis Failure Mode: B-Side power down and some A-side power supplies fail. Still safe.
15 Proper Feed Sizing for High Density Blade Chassis Add 7 th Chassis. Need to share breakers.
16 Proper Feed Sizing for High Density Blade Chassis 14.7A Still safe so far. Two breakers load to 14.7A if B-side power down. 14.7A
17 Proper Feed Sizing for High Density Blade Chassis 14.7A 14.7A Not truly redundant! One bad power supply (during B-side maintenance) can shut down 3 chassis
18 Proper Feed Sizing for High Density Blade Chassis 14.7A 14.7A Not truly redundant! One bad power supply (during B-side maintenance) can shut down 3 chassis
19 Proper Feed Sizing for High Density Blade Chassis 14.7A Not truly redundant! One bad power supply (during B-side maintenance) can shut down 3 chassis
20 Proper Feed Sizing for High Density Blade Chassis 14.7A Not truly redundant! One bad power supply (during B-side maintenance) can shut down 3 chassis
21 Proper Feed Sizing for High Density Blade Chassis 14.7A Not truly redundant! One bad power supply (during B-side maintenance) can shut down 3 chassis
22 Proper Feed Sizing for High Density Blade Chassis 19.6A Not truly redundant! One bad power supply (during B-side maintenance) can shut down 3 chassis
23 Proper Feed Sizing for High Density Blade Chassis Not truly redundant! One bad power supply (during B-side maintenance) can shut down 3 chassis
24 Proper Feed Sizing for High Density Blade Chassis Not truly redundant! One bad power supply (during B-side maintenance) can shut down 3 chassis Violates best practice concept of isolated failure domains.
25 Proper Feed Sizing for High Density Blade Chassis Example Result: (One Possible Solution) This cabinet provides two redundant 23kVA power feeds. Does not necessarily translate into, Can implement 23kVA of load. 7 ~16.5kVA did not work! Apparent maximum = 6 36U (14.1kVA); Wastes 40% of power capacity; Wastes 25% of rack space (assuming 48U cabinet);
26 Thank You!
27
Server Technology Inc.
Server Technology Inc. Power Efficiency Gains by Deploying 415 VAC Power Distribution in North American Data Centers White Paper STI-100-008 2011-Sept-22 Headquarters Server Technology, Inc. 1040 Sandhill
More informationData Center Assessment Helps Keep Critical Equipment Operational. A White Paper from the Experts in Business-Critical Continuity TM
Data Center Assessment Helps Keep Critical Equipment Operational A White Paper from the Experts in Business-Critical Continuity TM Executive Summary The IT infrastructure within many companies has evolved
More informationDeploying High Power to IT Equipment Racks
1 Deploying High Power to IT Equipment Racks A White Paper from Raritan 2 Table of Contents Overview...3 Trends in Data Center Power Deployment...3 Drivers for High Power Racks...4 Data Center Power Distribution
More informationDeploying High Power to IT Equipment Racks
2012 Raritan Inc. Table of Contents Overview Page 3 Trends in Data Center Power Deployment Page 3 Drivers for High Power Racks Page 3 Data Center Power Distribution Around the World Page 4 What Is High
More informationPROCESS & DATA CENTER COOLING. How and Why To Prepare For What s To Come JOHN MORRIS REGIONAL DIRECTOR OF SALES
PROCESS & DATA CENTER COOLING How and Why To Prepare For What s To Come JOHN MORRIS REGIONAL DIRECTOR OF SALES CONGRATULATIONS 2 BOLD PREDICTION 3 Where We Are TODAY Computer Technology NOW advances more
More informationData Sheet FUJITSU Server PRIMERGY CX400 M1 Scale out Server
Data Sheet FUJITSU Server Scale out Server Data Sheet FUJITSU Server Scale out Server Scale-Out Smart for HPC, Cloud and Hyper-Converged Computing FUJITSU Server PRIMERGY will give you the servers you
More informationPassive RDHx as a Cost Effective Alternative to CRAH Air Cooling. Jeremiah Stikeleather Applications Engineer
Passive RDHx as a Cost Effective Alternative to CRAH Air Cooling Jeremiah Stikeleather Applications Engineer Passive RDHx as a Cost Effective Alternative to CRAH Air Cooling While CRAH cooling has been
More informationData Sheet FUJITSU Server PRIMERGY CX400 M4 Scale out Server
Data Sheet FUJITSU Server PRIMERGY CX400 M4 Scale out Server Data Sheet FUJITSU Server PRIMERGY CX400 M4 Scale out Server Workload-specific power in a modular form factor FUJITSU Server PRIMERGY will give
More informationThe HP BladeSystem p-class 1U power enclosure: hot-plug, redundant power for a server blade enclosure
The HP BladeSystem p-class 1U power enclosure: hot-plug, redundant power for a server blade enclosure technology brief Abstract... 3 Introduction... 3 Components of the enclosure... 3 Hot-plug, redundant
More informationCPS VS UPS FOR POWERING DATA CENTERS
CPS VS UPS FOR POWERING DATA CENTERS HOW THE ADVANTAGES OF A NO BREAK CONVERGED POWER SYSTEM (CPS) PROVIDED BETTER POWER RELIABILITY, SYSTEM AVAILABILITY AND REDUCED COSTS OVER A UNINTERRUPTABLE POWER
More informationEnergy efficiency within data centers Is your IT organization capitalizing on the latest technology options and best practices?
This is a photographic template your photograph should fit precisely within this rectangle. Energy efficiency within data centers Is your IT organization capitalizing on the latest technology options and
More informationProduct Guide. Direct Contact Liquid Cooling Industry leading data center solutions for HPC, Cloud and Enterprise markets.
Product Guide Direct Contact Liquid Cooling Industry leading data center solutions for HPC, Cloud and Enterprise markets. www.coolitsystems.com Phone: +1 403.235.4895 The Future of Data Center Cooling
More informationTwo-Stage Power Distribution: An Essential Strategy to Future Proof the Data Center
Two-Stage Power Distribution: An Essential Strategy to Future Proof the Data Center Adapting to Change Concern over the pace of technology change is increasing among data center managers. This was reflected
More informationPowerExecutive. Tom Brey IBM Agenda. Why PowerExecutive. Fundamentals of PowerExecutive. - The Data Center Power/Cooling Crisis.
PowerExecutive IBM Agenda Why PowerExecutive - The Data Center Power/Cooling Crisis Fundamentals of PowerExecutive 1 The Data Center Power/Cooling Crisis Customers want more IT processing cycles to run
More informationIncreasing Data Center Efficiency by Using Improved High Density Power Distribution
Increasing Data Center Efficiency by Using Improved High Density Power Distribution By Neil Rasmussen White Paper #128 Revision 1 Executive Summary A new approach to power distribution for high density
More informationMSYS 4480 AC Systems Winter 2015
MSYS 4480 AC Systems Winter 2015 Module 12: DATA CENTERS By Satwinder Singh 14/05/2015 1 Data Centers Data Centers are specialized environments that safeguard your company's most valuable equipment and
More informationPRODUCT & SYSTEM OFFERINGS
POWER DISTRIBUTION INC. PRODUCT & SYSTEM OFFERINGS For More Information Use your QR Reader integrates the data center floor. from local monitoring to central control of power to mission critical systems.
More informationRemote Management of Data Center White Space: What to Manage and How? Ashish Moondra Sr. Product Manager Chatsworth Products
Remote Management of Data Center White Space: What to Manage and How? Ashish Moondra Sr. Product Manager Chatsworth Products Learning Outcomes Need for Remote Management of Whitespace Understand Elements
More informationFREEING HPC FROM THE DATACENTRE
FREEING HPC FROM THE DATACENTRE ku:l sistem TM COOLING REDEFINED www.iceotope.com ku:l sistem removes the need for inefficient air cooling technologies FREEING HPC FROM THE DATACENTRE Iceotope s patented
More informationEnergy Logic: Emerson Network Power. A Roadmap for Reducing Energy Consumption in the Data Center. Ross Hammond Managing Director
Energy Logic: A Roadmap for Reducing Energy Consumption in the Data Center Emerson Network Power Ross Hammond Managing Director Agenda Energy efficiency Where We Are Today What Data Center Managers Are
More informationAPC by Schneider Electric Solutions for Cisco Unified Computing System (UCS) Blade Applications
APC by Schneider Electric Solutions for Cisco Unified Computing System (UCS) Blade Applications The Cisco Unified Computing System is a next-generation data center platform that unites compute, network,
More informationDatacenter Efficiency Trends. Cary Roberts Tellme, a Microsoft Subsidiary
Datacenter Efficiency Trends Cary Roberts Tellme, a Microsoft Subsidiary Power Slashing Tools P3 Kill-A-WATT Measures min, max, and instantaneous voltage and current draw Calculates power (watts), kilowatt
More informationFuture of Cooling High Density Equipment. Steve Madara Vice President and General Manager Liebert Precision Cooling Business Emerson Network Power
Future of Cooling High Density Equipment Steve Madara Vice President and General Manager Liebert Precision Cooling Business Emerson Network Power Agenda Issues facing the Data Center Managing the explosive
More informationHighly Efficient Power Protection for High Density Computing Applications
Highly Efficient Power Protection for High Density Computing Applications IB Power and Cooling Symposium Lennart Jonsson Eaton Corporation 2007 Eaton Corporation. All rights reserved. Impact of High Density
More informationBus Way vs. Cable: a CapEx comparison
Siemens.com/datacenters Bus Way vs. Cable: a CapEx comparison Positive economics characterize bus way based designs for Data Center critical power distribution White Paper November 2013 Traditionally,
More informationThe Virtualized Server Environment
CHAPTER 3 The Virtualized Server Environment Based on the analysis performed on the existing server environment in the previous chapter, this chapter covers the virtualized solution. The Capacity Planner
More informationPowering Change in the Data Center. A White Paper from the Experts in Business-Critical Continuity TM
Powering Change in the Data Center A White Paper from the Experts in Business-Critical Continuity TM Executive Summary Increases in data center density and diversity are driving change in the power and
More informationHow Liquid Cooling Helped Two University Data Centers Achieve Cooling Efficiency Goals. Michael Gagnon Coolcentric October
How Liquid Cooling Helped Two University Data Centers Achieve Cooling Efficiency Goals Michael Gagnon Coolcentric October 13 2011 Data Center Trends Energy consumption in the Data Center (DC) 2006-61 billion
More informationData Sheet FUJITSU Server PRIMERGY CX400 M4 Scale out Server
Data Sheet FUJITSU Server PRIMERGY CX400 M4 Scale out Server Workload-specific power in a modular form factor FUJITSU Server PRIMERGY will give you the servers you need to power any workload and changing
More informationPros and Cons of Various DC Distribution Architectures
Pros and Cons of Various DC Distribution Architectures Source: Solar Powered Datacenter by Google Randy Malik Power Technology And Qualification IBM RTP Raleigh NC Rick Fishbune Power Technology And Qualification
More informationSwitch to Perfection
Switch to Perfection Traditional Data Centre - Temperatures Ideal Air Temperature: 22 C Chilled Water: 7-9 C Heat Load per Rack: Up to 4,5 Chilling & Pump Set The challenge a thermal image Front View of
More informationTopics. CIT 470: Advanced Network and System Administration. Google DC in The Dalles. Google DC in The Dalles. Data Centers
CIT 470: Advanced Network and System Administration Data Centers Topics Data Center: A facility for housing a large amount of computer or communications equipment. 1. Racks 2. Power 3. PUE 4. Cooling 5.
More informationTWO FINANCIAL IMPACT STUDIES. Seal IT Equipment Cabinets for Significant Annual Cost Savings and Simple Payback in a Few Short Months
TWO FINANCIAL IMPACT STUDIES Seal IT Equipment Cabinets for Significant Annual Cost Savings and Simple Payback in a Few Short Months TWO FINANCIAL IMPACT STUDIES Seal IT Equipment Cabinets for Significant
More informationDCIM Data Center Infrastructure Management
DCIM Data Center Infrastructure Management Part 3 Operational Management Moves Adds and Changes & Electrical Infrastructure November 5, 2013 Presented by Julius Neudorfer Sponsored by Today s Topics Operational
More informationPRODUCT BROCHURE. Deploying effective power protection in data centers
PRODUCT BROCHURE Deploying effective power protection in data centers 2 D E P L OY I N G E F F E C T I V E P O W E R P R O T E C T I O N I N D ATA C E N T E R S The following document was written to serve
More informationSystems and Technology Group. IBM Technology and Solutions Jan Janick IBM Vice President Modular Systems and Storage Development
Systems and Technology Group IBM Technology and Solutions Jan Janick IBM Vice President Modular Systems and Storage Development Power and cooling are complex issues There is no single fix. IBM is working
More informationData Center Trends: How the Customer Drives Industry Advances and Design Development
Bablu Kazi, PE MORRISON HERSHFIELD MISSION CRITICAL Data Center Trends: How the Customer Drives Industry Advances and Design Development What does the Customer Need? Scalability P U E Latest Technology
More information1.0 Executive Summary. 2.0 Available Features & Benefits
Statement Of Work Energy Management Services Table of Contents 1.0 Executive Summary 2.0 Available Features & Benefits 3.0 Assessment Deliverables Selection 4.0 On Site Assessment Activities 5.0 Exclusions
More informationIBM Integrated Server Farm (ISF)
IBM Integrated Server Farm (ISF) TSS HW Services 05/04/2005 Data Centre Trends The density of computing power in a data centre environment has steadily increased in recent years. This trend is driven by
More informationDCIM Data Center Infrastructure Management Measurement is the first step
DCIM Data Center Infrastructure Management Measurement is the first step Presented by Julius Neudorfer Sponsored by DCIM Data Center Infrastructure Management Measurement is the first step Presented by
More informationELASTIC CLOUD STORAGE (ECS) APPLIANCE
Specification Sheet ELASTIC CLOUD STORAGE (ECS) APPLIANCE Dell EMC Elastic Cloud Storage (ECS ) Appliance is a multi-purpose, software-defined cloud-storage platform. This 3rd Generation object-based solution
More informationHP ProLiant BladeSystem Gen9 vs Gen8 and G7 Server Blades on Data Warehouse Workloads
HP ProLiant BladeSystem Gen9 vs Gen8 and G7 Server Blades on Data Warehouse Workloads Gen9 server blades give more performance per dollar for your investment. Executive Summary Information Technology (IT)
More informationPowerWAVE 8000DPA. (10 20 kva/kw) Parallelable up to 400 kva/kw
PowerWAVE 8000DPA (10 20 kva/kw) Parallelable up to 400 kva/kw Modular UPS designed for low and medium power applications. Key benefits Individual static switches per module Each module has its own display
More informationPRODUCT BROCHURE. Cyberex Remote Power Panel (RPP) Power distribution system
PRODUCT BROCHURE Cyberex Remote Power Panel (RPP) Power distribution system 2 CYBEREX RPP POWER DISTRIBUTION REMOTE POWER PANEL Cyberex power distribution Remote Power Panel (RPP) With constantly evolving
More informationMaking the impossible data center a reality.
United Nations ITU WSIS 2016 WINNER E-Environment Malaysia s First Win 2015 ASIA PACIFIC WINNER 2015 Best of Sustainability and Environmental Technology WINNER 2015 Best of Sustainability and Environmental
More informationMission Critical Facilities & Technology Conference November 3, 2011 Cooling 101. Nick Gangemi Regional Sales Manager Data Aire
Mission Critical Facilities & Technology Conference November 3, 2011 Cooling 101 Nick Gangemi Regional Sales Manager Data Aire Agenda Exactly what are we talking about ASHRAE TC 9.9 Design best practices
More informationData Sheet FUJITSU Server PRIMERGY CX400 S2 Multi-Node Server Enclosure
Data Sheet FUJITSU Server PRIMERGY CX400 S2 Multi-Node Server Enclosure Data Sheet FUJITSU Server PRIMERGY CX400 S2 Multi-Node Server Enclosure Scale-Out Smart for HPC and Cloud Computing with enhanced
More informationProduct brochure. Cyberex. Remote Power Panel (RPP) Power distribution system
Product brochure Cyberex Remote Power Panel (RPP) Power distribution system Cyberex power distribution Remote power panel (RPP) With constantly evolving demands and the increasing need to store critical
More informationA Green Approach. Thermal
A Green Approach to Thermal Management Thermal Management - AGENDA Definitions & Thermal Facts Density Trends Rack Level Management Passive Solutions Thermal Sources & Green Solutions Data Center Layout
More informationAPC APPLICATION NOTE #74
#74 Configuration of InfraStruXure for Data Centers to Support Dell PowerEdge 1855 Abstract Many companies are making plans to incorporate Dell PowerEdge Blade Servers into their data center applications.
More informationVirtualization and consolidation
Virtualization and consolidation Choosing a density strategy Implementing a high-density environment Maximizing the efficiency benefit Anticipating the dynamic data center Schneider Electric 1 Topical
More informationThermal management. Thermal management
Thermal management Thermal management Managing thermal loads is a major challenge for all Data Centre operators. Effecting proper control of the thermal environment drives energy consumption and ultimately
More informationData Sheet FUJITSU Server PRIMERGY CX420 S1 Out-of-the-box Dual Node Cluster Server
Data Sheet FUJITSU Server PRIMERGY CX420 S1 Out-of-the-box Dual Node Cluster Server Data Sheet FUJITSU Server PRIMERGY CX420 S1 Out-of-the-box Dual Node Cluster Server High availability for lower expertise
More informationRecapture Capacity for Existing. and Airflow Optimization
Recapture Capacity for Existing Data Centers Through Cooling and Airflow Optimization Introduction Challenges and Trends Agenda Cooling & Airflow Optimization Takeaways Learning Objectives Recognize opportunities
More informationHow High-Density Colocation and Enhanced Visibility Improve Business Performance
How High-Density Colocation and Enhanced Visibility Improve Business Performance Steven So Vice President Data Center Business Cloud Business Division NTT Com Asia Limited 11 Sep 2015 NTT Communications
More informationGlobal Networks and Data Centers Briefing. May 27, 2011
Global Networks and Data Centers Briefing May 27, 2011 Global Disaster Recovery Strategy Short to Mid-Term: Leverage Current Assets Long-Term: DR + SaaS growth Target State T ( ~ FY 13 ) Netherlands Metro-based
More informationClose Coupled Cooling for Datacentres
Close Coupled Cooling for Datacentres Dr Fathi Tarada Mosen Ltd fathi.tarada@mosenltd.com www.mosenltd.com Agenda Increasing Power Densities Raised Floor Limitations Hot and Cold Aisle Enclosures Close
More informationPower Management in Cisco UCS
Power Capping in Cisco UCS, page 2 Power Policy Configuration, page 3 Power Policy for Cisco UCS Servers, page 3 Configuring the Power Policy, page 3 Power Supply for Redundancy Method, page 4 Configuring
More informationHP Power Calculator Utility: a tool for estimating power requirements for HP ProLiant rack-mounted systems
HP Power Calculator Utility: a tool for estimating power requirements for HP ProLiant rack-mounted systems technology brief Abstract... 2 Introduction... 2 Key parameters... 2 Input line voltage... 2 Device
More informationZ8 G4 Site Prep Guide Table of contents
Z8 G4 Site Prep Guide Table of contents Introduction... 2 Power consumption and cooling considerations... 2 Power consumption limitations... 2 Uninterruptible power supply (UPS)... 3 Power consumption
More informationEnergy Usage in Cloud Part2. Salih Safa BACANLI
Energy Usage in Cloud Part2 Salih Safa BACANLI Cooling Virtualization Energy Proportional System Conclusion Cooling After servers, the second largest consumer of power in a data center is the cooling system.(kava,
More informationDominick Lovicott Enterprise Thermal Engineering. One Dell Way One Dell Way Round Rock, Texas
One Dell Way One Dell Way Round Rock, Texas 78682 www.dell.com DELL ENTERPRISE WHITEPAPER THERMAL DESIGN OF THE DELL POWEREDGE T610, R610, AND R710 SERVERS Dominick Lovicott Enterprise Thermal Engineering
More informationHot vs Cold Energy Efficient Data Centers. - SVLG Data Center Center Efficiency Summit
Hot vs Cold Energy Efficient Data Centers - SVLG Data Center Center Efficiency Summit KC Mares November 2014 The Great Debate about Hardware Inlet Temperature Feb 2003: RMI report on high-performance data
More information7 Best Practices for Increasing Efficiency, Availability and Capacity. XXXX XXXXXXXX Liebert North America
7 Best Practices for Increasing Efficiency, Availability and Capacity XXXX XXXXXXXX Liebert North America Emerson Network Power: The global leader in enabling Business-Critical Continuity Automatic Transfer
More informationDensity in the Data Center
Density in the Data Center INDUSTRY BRIEF Aug 2014 Density in the datacenter refers to the electric power consumed per square foot of floor space (or unit volume of space), number of servers, and the cooling
More informationSIFMA Technology Management Conference. Data Center Efficiency
SIFMA Technology Management Conference June 20, 2007 Data Center Efficiency Presented by Julius Neudorfer In deciding how to best implement a strategy for supporting critical data systems, Data Center
More informationData Sheet Fujitsu Server PRIMERGY CX400 M1 Compact and Easy
Data Sheet Fujitsu Server Compact and Easy Data Sheet Fujitsu Server Compact and Easy Scale-Out Smart for HPC, Cloud and Hyper-Converged Computing The Fujitsu Server helps to meet the immense challenges
More informationData Centre & Colocation in Birmingham. Flexible. Secure. Accredited.
Data Centre & Colocation in Birmingham Flexible. Secure. Accredited. Intercity - transforming your business Work Together. Work Anywhere. Work Securely. At Intercity Technology, we re driven by our people-first
More informationDCIM Data Center Infrastructure Management
DCIM Data Center Infrastructure Management Part 2 Implementation Challenges & Strategic Advantages - Predictive Analysis August 8, 2013 Presented by Julius Neudorfer Sponsored by Today s Topics Implementation
More informationManaging Power in Cisco UCS
Managing Power in Cisco UCS This chapter includes the following sections: Power Management in Cisco UCS, page 1 Configuring the Power Policy, page 1 Configuring the Global Cap Policy, page 2 Configuring
More informationCapacity and Power Management: The Forgotten Factors in Disaster Recovery Planning Presented by: Clemens Pfeiffer CTO Power Assure, Inc.
Capacity and Power Management: The Forgotten Factors in Disaster Recovery Planning Presented by: Clemens Pfeiffer CTO Power Assure, Inc. The Purpose of a Data Center Provide IT equipment a healthy environment
More informationPlanning for Liquid Cooling Patrick McGinn Product Manager, Rack DCLC
Planning for Liquid Cooling -------------------------------- Patrick McGinn Product Manager, Rack DCLC February 3 rd, 2015 Expertise, Innovation & Delivery 13 years in the making with a 1800% growth rate
More informationSystem Overview. Liquid Cooling for Data Centers. Negative Pressure Cooling Without Risk of Leaks
Liquid Cooling for Data Centers System Overview The Chilldyne Cool-Flo System is a direct-to-chip liquid cooling system that delivers coolant under negative pressure. Chilldyne s technologies were designed
More informationCooling on Demand - scalable and smart cooling solutions. Marcus Edwards B.Sc.
Cooling on Demand - scalable and smart cooling solutions Marcus Edwards B.Sc. Schroff UK Limited Data Centre cooling what a waste of money! A 1MW data center needs 177,000,000 kwh in its lifetime of 10
More informationAPMTM UPS 30kW - 300kW The Compact Row-Based UPS With Flexpower Technology
APM UPS 30kW - 300kW The Compact Row-Based UPS With Flexpower Technology T M LIEBERT APM UPS Anticipating Technology Changes Through Adaptive Architecture Today, you need a power infrastructure that can
More informationPhil Tuma, Application Development Engineer John Gross, Mechanical Engineering Director Kar-Wing Lau, CEO Charles Benge, Director Mission Critical
E n g i n e e r i n g W o r k s h o p : A d v a n c e d C o o l i n g S o l v i n g t h e E n e r g y C h a l l e n g e t h r o u g h I n n o v a t i o n s i n D a t a C e n t e r C o o l i n g 3m.com/immersion
More informationIT Level Power Provisioning Business Continuity and Efficiency at NTT
IT Level Power Provisioning Business Continuity and Efficiency at NTT Henry M.L. Wong Intel Eco-Technology Program Office Environment Global CO 2 Emissions ICT 2% 98% Source: The Climate Group Economic
More informationECS APPLIANCES. Specification Sheet
Specification Sheet ECS APPLIANCES This 3rd Generation object storage solution from Dell EMC, ECS is built for accelerating digital transformation by bridging both traditional and next generation applications.
More informationPowerWAVE 8000DPA Modular UPS designed for low and medium power applications
PowerWAVE 8000DPA Modular UPS designed for low and medium power applications PowerWAVE 8000DPA is ideal for low to medium, high density critical power protection applications. For more information call
More informationData Center Trends and Challenges
Data Center Trends and Challenges, IBM Fellow Chief Engineer - Data Center Energy Efficiency Customers challenges are driven by the following Increasing IT demand Continued cost pressure Responsive to
More informationPRODUCT BROCHURE. Conceptpower DPA V UL Modular UPS 20kW 600kW
PRODUCT BROCHURE Conceptpower DPA 120 208V UL Modular UPS 20kW 600kW 2 CONCEPTPOWER DPA 120 280V MODULAR UPS Today s data centers require continuous uptime. That target is why ABB s Conceptpower DPA 120
More informationConverged Power Solutions. Data center power reinvented
Converged Power Solutions Data center power reinvented always on anywhere anytime With Eltek s Converged Power Solutions, the next generation power solution for data centers is here. It offers unmatched
More informationPOWERMAX FAMILY. Appliance-based packaging. PowerMax 2000 and Specifications. Specification Sheet. PowerMax Arrays
Specification Sheet POWERMAX FAMILY PowerMax Arrays PowerMax 2000 and 8000 The new family of Dell EMC NVMe (Non-Volatile Memory Express) arrays resets the bar for enterprise storage with new levels of
More informationNimble Storage vs HPE 3PAR: A Comparison Snapshot
Nimble Storage vs HPE 3PAR: A 1056 Baker Road Dexter, MI 48130 t. 734.408.1993 Nimble Storage vs HPE 3PAR: A INTRODUCTION: Founders incorporated Nimble Storage in 2008 with a mission to provide customers
More informationINCREASE IT EFFICIENCY, REDUCE OPERATING COSTS AND DEPLOY ANYWHERE
www.iceotope.com DATA SHEET INCREASE IT EFFICIENCY, REDUCE OPERATING COSTS AND DEPLOY ANYWHERE BLADE SERVER TM PLATFORM 80% Our liquid cooling platform is proven to reduce cooling energy consumption by
More informationViable Options for Data Center Solutions. By Ning Liu Offering Group Panduit APJ
Viable Options for Data Center Solutions By Ning Liu Offering Group Panduit APJ Agenda Market Overview Data Center Challengers Business Drivers Data Center Standards Data Center Technologies Panduit Solutions
More informationDesign a Remote-Office or Branch-Office Data Center with Cisco UCS Mini
White Paper Design a Remote-Office or Branch-Office Data Center with Cisco UCS Mini June 2016 2016 Cisco and/or its affiliates. All rights reserved. This document is Cisco Public. Page 1 of 9 Contents
More informationProduct Overview >> Cisco R Series Racks: Make Your Infrastructure Highly Secure. Has an innovative design to deliver exceptional power, cooling, and cable management, as well as strength and stability
More informationLiebert DCW CATALOGUE
Liebert DCW CATALOGUE Chilled Water-Based High Density Cooling For The Data Center LIEBERT DCW Flexible Approaches For Energy Efficient Cooling Save up to 70% in cooling energy usage Data center managers
More informationUCS M-Series + Citrix XenApp Optimizing high density XenApp deployment at Scale
In Collaboration with Intel UCS M-Series + Citrix XenApp Optimizing high density XenApp deployment at Scale Aniket Patankar UCS Product Manager May 2015 Cisco UCS - Powering Applications at Every Scale
More informationTHE OFFICIAL TRADE JOURNAL OF BICSI
ICT TODAY THE OFFICIAL TRADE JOURNAL OF BICSI January/February 2017 Volume 38, Number 1 + PLUS + Information Security and ESS in the Age of the Internet of Things + Grounding System Design and Testing
More informationProduct brochure. Conceptpower DPA Modular UPS DPA 120 UL 208V: 20kW 600kW
Product brochure Conceptpower DPA Modular UPS DPA 120 UL 208V: 20kW 600kW 2 Product brochure Conceptpower DPA 120 UL UPS Conceptpower DPA 120 The modular UPS for small and medium-sized data centers UPS
More informationScaling to Petaflop. Ola Torudbakken Distinguished Engineer. Sun Microsystems, Inc
Scaling to Petaflop Ola Torudbakken Distinguished Engineer Sun Microsystems, Inc HPC Market growth is strong CAGR increased from 9.2% (2006) to 15.5% (2007) Market in 2007 doubled from 2003 (Source: IDC
More informationPower Consumption in the Data Center. Green Concepts
Power Consumption in the Data Center Green Concepts What is your Energy Saving Strategy? Buying Energy Efficient Equipment (EEE) 46% Say Yes to Green Technology Information Week Research Green Data Center
More informationDesign a Remote-Office or Branch-Office Data Center with Cisco UCS Mini
White Paper Design a Remote-Office or Branch-Office Data Center with Cisco UCS Mini February 2015 2015 Cisco and/or its affiliates. All rights reserved. This document is Cisco Public. Page 1 of 9 Contents
More informationPower and Cooling for Ultra-High Density Racks and Blade Servers
Power and Cooling for Ultra-High Density Racks and Blade Servers APC White Paper #46 Richard L. Sawyer Director of Data Center Technology American Power Conversion Company 2005 APC corporation What has
More informationFind the right platform for your server needs
Product family guide Find the right platform for your server needs HP ProLiant Gen8 model transition guide The next generation There are mounting business pressures to support more applications and users,
More informationTABLE OF CONTENTS. About ScaleMatrix... 3 ScaleMatrix vs. Traditional Data Center Comparison... Colocation Services...
COLOCATION E-BOOK TABLE OF CONTENTS About ScaleMatrix... 3 ScaleMatrix vs. Traditional Data Center Comparison... Colocation Services... 4 5 7 Challenges Facing Data Center Operators with HPC Requirements...
More informationCisco 4000 Series Integrated Services Routers: Architecture for Branch-Office Agility
White Paper Cisco 4000 Series Integrated Services Routers: Architecture for Branch-Office Agility The Cisco 4000 Series Integrated Services Routers (ISRs) are designed for distributed organizations with
More informationHP Modular Cooling System: water cooling technology for high-density server installations
HP Modular Cooling System: water cooling technology for high-density server installations technical brief Abstract... 2 Introduction... 2 Data center trends... 2 Increased power demands... 3 Increased
More information