Session 6: Data Center Energy Management Strategies

Size: px
Start display at page:

Download "Session 6: Data Center Energy Management Strategies"

Transcription

1 Session 6: Data Center Energy Management Strategies Data Center Energy Use and Opportunities: Applying Best Practices to meet Executive Order Requirements Dale Sartor, PE Lawrence Berkeley National Laboratory August 10, 2016 Rhode Island Convention Center Providence, Rhode Island

2 Obtaining CEUs and Certificates FEMP is accredited by the International Association for Continuing Education & Training (IACET) and has awarded: 0.2 CEUs for Sessions 1 7, CEUs for Session 8 To earn CEUs and a certificate of completion, participants must: Attend the entire session Access the assessment between August 19 September 23, 2016 Achieve 80% on the assessment and complete a brief evaluation by logging on to: Attendees will receive details for accessing the assessment by following the Energy Exchange. Note: Participants must register once with the National Institute of Building Sciences Whole Building Design Guide (WBDG.org) to complete the requirements and obtain their certificate. 2

3 US Data Center Energy Usage Reports (2007 & 2016) ~1.8% U.S. Electricity

4 Change in Server Shipments Nearly all server shipment growth since 2010 occurred in servers destined for large hyperscale data centers: Hyperscale data centers typically operate more efficiently Growing percentage of overall data center activity

5 Key Observations Servers are improving in power scaling ability Servers typically operate at 10 50% utilization Increased power scaling reduces average power demand Large reduction in physical server demand within data centers Increase virtualization and consolidation has tempered increase in annual server shipments SPEC workbook data

6 Energy Use Estimates Savings: 620 billion kwh

7 Efficiency Scenarios 7

8 Future Challenges & Opportunities Data center closet clunkers: Improving/removing closet and other poorly operated smaller data centers Beyond 2020: Established efficiency measures (consolidation, power scaling, low PUE) to eventually hit upper limit Computational/storage demand only increasing Computational efficiency growth starting to wane

9 Executive Order 13693: The New Driver In March 2015, the President issued Executive Order (EO) 13693, Planning for Federal Sustainability in the Next Decade. Specific goals for data centers Promote energy optimization, efficiency, and performance Install/monitor advanced energy meters in all data centers by FY2018 Establish a Power Usage Effectiveness (PUE) target - between 1.2 and 1.4 for new data centers - less than 1.5 for existing data centers Other related goals Reduce building energy 2.5% per year per sq. ft. thru 2025 Increase clean and renewable energy to 25% & 30% by 2020 & 2025 Reduce water consumption 2% per year per sq. ft. thru 2025 Make ENERGY STAR or FEMP designated acquisitions

10 Implementing Instructions for New Directive Ensuring the agency chief information officer (CIO) promotes data center energy optimization, efficiency, and performance Agencies are to have data center staff trained and certified in data center energy efficiency. All core data centers shall have at least one Data Center Energy Practitioner (DCEP) assigned to manage data center performance Agency CIO should develop, issue and implement policies, procedures and guidance.

11 Implementing Instructions for New Directive Installing and monitoring advanced energy meters in all data centers by fiscal year 2018 Advanced energy meters installed by agencies as appropriate in all data centers shall be meters that enable the active tracking of power usage effectiveness (PUE) for the data center, as well as promote implementation of Data Center Infrastructure Management (DCIM). All new data centers shall include advanced energy and water meters. Agencies shall evaluate consolidation/closure for existing data centers unable to cost effectively install meters by FY 2018

12 Implementing Instructions for New Directive Establishing a power usage effectiveness target of 1.2 to 1.4 for new data centers and less than 1.5 for existing data centers Agencies should adopt a cloud first policy when developing new systems. Agencies will evaluate existing data centers unable to achieve 1.5 for alternative solutions. Encourages use of shared service providers and contracted data center services. Procurement preference for data centers with the lowest demonstrated PUE. Power Usage Effectiveness (PUE) is a measure of how efficiently a computer data center infrastructure uses energy.

13 Other Federal Initiatives Federal Data Center Optimization Initiative (formerly Consolidation Initiative) Reduce the cost of data center hardware, software and operations Shift IT investments to more efficient computing platforms and technologies Better Buildings Data Center Partners (voluntary) Improve efficiency of data center s PUE 1 by at least 20% within 10 years Implement/Share best practices, innovative technologies, and strategies Metering required for tracking Technical & communication assistance

14 FEMP Technical Assistance FEMP has assembled numerous technical assistance resources, including best practice guides, case studies, technical bulletins, and training on data center energy efficiency Direct technical assistance is available through FEMP to agencies who join as a Better Buildings Data Center Partner For more information visit:

15 Benchmark Energy Performance Compare to peers: wide variation Identify best practices, ID opportunities Track performance: Can t manage what isn t measured The relative percentage of energy actually doing computing varies Office Space Conditioning 1% Lighting 2% Other 13% Computer Loads 67% Electrical Room Cooling 4% Cooling Tower Plant 4% Data Center Server Load 51% HVAC - Air Movement 7% Data Center CRAC Units 25% Lighting 2% HVAC - Chiller and Pumps 24%

16 High Level Metric: PUE Power Utilization Effectiveness (PUE) = Total Power/IT Power

17 Sample PUEs PUEs: Reported & Calculated PUE EPA ENERGY STAR Average 1.91 Intel Jones Farm, Hillsboro 1.41 T-Systems & Intel DC2020 Test Lab, Munich 1.24 Google 1.16 Leibniz Supercomputing Centre (LRZ) 1.15 National Center for Atmospheric Research (NCAR) 1.10 Yahoo, Lockport 1.08 Facebook, Prineville 1.07 National Renewable Energy Laboratory (NREL) 1.06 Source: Mike Patterson, Intel

18 Data Center Best Practices 1. Measure and Benchmark Energy Use 2. Identify IT Opportunities, and modify procurement processes to align with the procurement policy 3. Optimize Environmental Conditions 4. Manage Airflow (Air Management) 5. Evaluate Cooling Options 6. Improve Electrical Efficiency 7. Use IT to Control IT

19 1. Measure and Benchmark Energy Use Use metrics to measure efficiency Benchmark performance Establish continual improvement goals

20 2. Identify IT Opportunities Specify efficient servers (incl. power supplies) Virtualize Refresh IT equipment Turn off unused equipment Implement acquisition systems to assure efficient products are purchased

21 3. Optimize Environmental Conditions Follow ASHRAE guidelines or manufacturer specifications Operate near maximum of ASHRAE s recommended range Anticipate servers will occasionally operate in the allowable range Minimize or eliminate humidity control

22 4. Manage Airflow Implement hot and cold aisles Seal leaks and manage floor tiles Isolate hot and cold air/contain hot or cold aisle Control air flow (save energy with VSD on fans) ºF vs ºF (35 41ºC vs ºC) 70 80ºF vs ºF (21 27ºC vs. 7 13ºC)

23 5. Evaluate Cooling Options Use centralized cooling system Maximize central cooling plant efficiency Provide liquid based heat removal Compressorless cooling ( free cooling)

24 6. Improve Electrical Efficiency Select efficient UPS systems and topography Examine redundancy levels Consider redundancy in the network rather than in the data center (geographical redundancy) Increase voltage distribution and reduce conversions. Redundant Operation Source: LBNL Benchmarking study

25 7. Use IT to Control IT Energy Evaluate monitoring systems to enhance real time management and efficiency Use visualization tools (e.g., thermal maps) Install dashboards to manage and sustain energy efficiency

26 Most importantly Get IT and Facilities people talking and working together as a team!

27 DOE s Center of Expertise Datacenters.lbl.gov Datacenters.lbl.gov

28 Available Resources Profiling Tool Assessment Tools Best Practices Guide Benchmarking Guide Data Center Programming Guide Technology Case Study Bulletins Report Templates Process Manuals Quick-Start Guide Professional Certification (DCEP)

29 DOE s Better Buildings Program

30 Questions Dale Sartor, P.E. Lawrence Berkeley National Laboratory MS University of California Berkeley, CA (510)

Innovative Data Center Efficiency Techniques. Michael K Patterson, PhD PE Eco-technology Program Office Intel Corporation

Innovative Data Center Efficiency Techniques. Michael K Patterson, PhD PE Eco-technology Program Office Intel Corporation Innovative Data Center Efficiency Techniques Michael K Patterson, PhD PE Eco-technology Program Office Intel Corporation 1 Alternate titles.. Crisis or opportunity? Never build a new data center! Improve

More information

Energy Efficiency for Exascale. High Performance Computing, Grids and Clouds International Workshop Cetraro Italy June 27, 2012 Natalie Bates

Energy Efficiency for Exascale. High Performance Computing, Grids and Clouds International Workshop Cetraro Italy June 27, 2012 Natalie Bates Energy Efficiency for Exascale High Performance Computing, Grids and Clouds International Workshop Cetraro Italy June 27, 2012 Natalie Bates The Exascale Power Challenge Where do we get a 1000x improvement

More information

MSYS 4480 AC Systems Winter 2015

MSYS 4480 AC Systems Winter 2015 MSYS 4480 AC Systems Winter 2015 Module 12: DATA CENTERS By Satwinder Singh 14/05/2015 1 Data Centers Data Centers are specialized environments that safeguard your company's most valuable equipment and

More information

LANL High Performance Computing Facilities Operations. Rick Rivera and Farhad Banisadr. Facility Data Center Management

LANL High Performance Computing Facilities Operations. Rick Rivera and Farhad Banisadr. Facility Data Center Management Slide-1 LANL High Performance Computing Facilities Operations Rick Rivera and Farhad Banisadr Facility Data Center Management Division Slide-2 Outline Overview - LANL Computer Data Centers Power and Cooling

More information

18 th National Award for Excellence in Energy Management. July 27, 2017

18 th National Award for Excellence in Energy Management. July 27, 2017 18 th National Award for Excellence in Energy Management July 27, 2017 ICICI Bank, Data Centre, August Hyderabad 30 & 31, 2017 ICICI Bank - Revolution in Digital Banking Over 100,000 Digital POS in 4 months

More information

Green Data Centers A Guideline

Green Data Centers A Guideline Green Data Centers A Guideline Sekhar Kondepudi Ph.D Associate Professor Smart Buildings & Smart Cities Vice Chair Focus Group on Smart Sustainable Cities ITU-TRCSL Workshop on Greening the Future: Bridging

More information

Ft Worth Data Center Power Metering for Real Time PUE Calculation. Scope of Work

Ft Worth Data Center Power Metering for Real Time PUE Calculation. Scope of Work Ft Worth Data Center Power Metering for Real Time PUE Calculation Scope of Work Prepared for the General Services Administration By Lawrence Berkeley National Laboratory Rod Mahdavi December 13, 2010 Executive

More information

Server room guide helps energy managers reduce server consumption

Server room guide helps energy managers reduce server consumption Server room guide helps energy managers reduce server consumption Jan Viegand Viegand Maagøe Nr. Farimagsgade 37 1364 Copenhagen K Denmark jv@viegandmaagoe.dk Keywords servers, guidelines, server rooms,

More information

HPE Energy Efficiency Certification Service

HPE Energy Efficiency Certification Service Data sheet HPE Energy Efficiency Certification Service HPE Technology Consulting As power consumption and heat generation in the data center increase due to information explosion, big data, e-commerce,

More information

Cooling on Demand - scalable and smart cooling solutions. Marcus Edwards B.Sc.

Cooling on Demand - scalable and smart cooling solutions. Marcus Edwards B.Sc. Cooling on Demand - scalable and smart cooling solutions Marcus Edwards B.Sc. Schroff UK Limited Data Centre cooling what a waste of money! A 1MW data center needs 177,000,000 kwh in its lifetime of 10

More information

Data Center Trends and Challenges

Data Center Trends and Challenges Data Center Trends and Challenges, IBM Fellow Chief Engineer - Data Center Energy Efficiency Customers challenges are driven by the following Increasing IT demand Continued cost pressure Responsive to

More information

Addressing Data Center Efficiency Lessons Learned From Process Evaluations of Utility Energy Efficiency Programs

Addressing Data Center Efficiency Lessons Learned From Process Evaluations of Utility Energy Efficiency Programs Addressing Data Center Efficiency Lessons Learned From Process Evaluations of Utility Energy Efficiency Programs IEPEC Conference Session 16: Industrial Strength Evaluation June 10, 2010 AJ Howard Energy

More information

BAS Chillers 8/15/2016. Achieving Energy Savings with BAS and Data Analytics Guanjing Lin Lawrence Berkeley National Laboratory August 10, 2016

BAS Chillers 8/15/2016. Achieving Energy Savings with BAS and Data Analytics Guanjing Lin Lawrence Berkeley National Laboratory August 10, 2016 Session 7: Building Automation and Operation Tools Outline Analytics Tools to Supplement BAS Achieving Energy Savings with BAS and Data Analytics Guanjing Lin Lawrence Berkeley National Laboratory August

More information

PROCESS & DATA CENTER COOLING. How and Why To Prepare For What s To Come JOHN MORRIS REGIONAL DIRECTOR OF SALES

PROCESS & DATA CENTER COOLING. How and Why To Prepare For What s To Come JOHN MORRIS REGIONAL DIRECTOR OF SALES PROCESS & DATA CENTER COOLING How and Why To Prepare For What s To Come JOHN MORRIS REGIONAL DIRECTOR OF SALES CONGRATULATIONS 2 BOLD PREDICTION 3 Where We Are TODAY Computer Technology NOW advances more

More information

Data Center Energy Savings By the numbers

Data Center Energy Savings By the numbers Data Center Energy Savings By the numbers Chris Kurkjian, PE HP Critical Facility Services provided by EYP Mission Critical Facilities 2008 Hewlett-Packard Development Company, L.P. The information contained

More information

Data Centers. Powerful Solutions That Put You in Control. Energy Management Solutions. Where your energy dollars are used. 1

Data Centers. Powerful Solutions That Put You in Control. Energy Management Solutions. Where your energy dollars are used. 1 Energy for What s Ahead SM Energy Management Solutions Data Centers Powerful Solutions That Put You in Control Ready to take a byte out of your data center energy use and become more cost-effcient? Data

More information

Future of Cooling High Density Equipment. Steve Madara Vice President and General Manager Liebert Precision Cooling Business Emerson Network Power

Future of Cooling High Density Equipment. Steve Madara Vice President and General Manager Liebert Precision Cooling Business Emerson Network Power Future of Cooling High Density Equipment Steve Madara Vice President and General Manager Liebert Precision Cooling Business Emerson Network Power Agenda Issues facing the Data Center Managing the explosive

More information

Continuous Commissioning at Sandia National Laboratories

Continuous Commissioning at Sandia National Laboratories Session: Why On going Commissioning Can Lead to Better Performing Buildings Continuous Commissioning at Sandia National Laboratories Jack Mizner Sandia National Laboratories August 10, 2016 Sandia National

More information

Green IT Project: The Business Case

Green IT Project: The Business Case Green IT Project: The Business Case Indumathi Lnu University at Albany DATE We will discuss Identifying green IT projects Funding green IT projects Building the business case Case study: University at

More information

Reducing Data Center Cooling Costs through Airflow Containment

Reducing Data Center Cooling Costs through Airflow Containment FEATURE Reducing Data Center Cooling Costs through Airflow Containment Implementing a containment solution in the data center costs much less than the alternatives of adding air handlers or other supplemental

More information

MEASURE MONITOR UNDERSTAND

MEASURE MONITOR UNDERSTAND MEASURE MONITOR UNDERSTAND Presented by Alistair Hunt Energy Monitoring, Measurement metrics Where and What 1 History & Background Company Timeline 18 Years Comrac & Sinetica founded 15 Years Raritan Integration

More information

Energy Efficiency and CHP Opportunities for Data Centers

Energy Efficiency and CHP Opportunities for Data Centers Energy Efficiency and CHP Opportunities for Data Centers Webinar #2: Understanding Energy Efficiency Concepts and Technologies for Data Centers The 2nd in a 4-Part Series of Educational Webinars Targeting

More information

Inside the Data Center: Opportunities for Energy Efficiency

Inside the Data Center: Opportunities for Energy Efficiency Pacific Gas and Electric Company Presented to Technologies and Practices for Efficient & Reliable Data Centers Inside the Data Center: Opportunities for Energy Efficiency Mark Bramfitt Sunnyvale, California

More information

EP s approach to Power & Energy efficiency in DCs & paradigms

EP s approach to Power & Energy efficiency in DCs & paradigms DG for Innovation and Technological Support EP s approach to Power & Energy efficiency in DCs & paradigms Presentation Presentation subtitle subtitle or lead-in or lead-in that says that what says what

More information

Developing an Action Plan: Building Energy Metering and Beyond

Developing an Action Plan: Building Energy Metering and Beyond Developing an Action Plan: Building Energy Metering and Beyond Angela Lewis, PE, PhD, LEED AP, FMP Project Manager Facility Engineering Associates (FEA) MANAGING CEUs AND CFM MAINTENANCE POINTS You are

More information

BENEFITS OF ASETEK LIQUID COOLING FOR DATA CENTERS

BENEFITS OF ASETEK LIQUID COOLING FOR DATA CENTERS BENEFITS OF ASETEK LIQUID COOLING FOR DATA CENTERS Asetek has leveraged its expertise as the world-leading provider of efficient liquid cooling systems to create its RackCDU and ISAC direct-to-chip liquid

More information

May Hands-on Guidance. Measurable Results. SUPPLIER EFFICIENCY PROGRAM

May Hands-on Guidance. Measurable Results. SUPPLIER EFFICIENCY PROGRAM May 2015 Hands-on Guidance. Measurable Results. SUPPLIER EFFICIENCY PROGRAM REACHING OUTSIDE OUR WALLS WHAT A scalable education and training platform that helps suppliers reduce their energy use and costs

More information

Energy Action Plan 2015

Energy Action Plan 2015 Energy Action Plan 2015 Purpose: In support of the Texas A&M University Vision 2020: Creating a Culture of Excellence and Action 2015: Education First Strategic Plan, the Energy Action Plan (EAP) 2015

More information

7 Best Practices for Increasing Efficiency, Availability and Capacity. XXXX XXXXXXXX Liebert North America

7 Best Practices for Increasing Efficiency, Availability and Capacity. XXXX XXXXXXXX Liebert North America 7 Best Practices for Increasing Efficiency, Availability and Capacity XXXX XXXXXXXX Liebert North America Emerson Network Power: The global leader in enabling Business-Critical Continuity Automatic Transfer

More information

Welcome Association of Energy Engineers to the Microsoft Technology Center

Welcome Association of Energy Engineers to the Microsoft Technology Center Welcome Association of Energy Engineers to the Microsoft Technology Center Today s Agenda 10:00 10:30 What s new in data center energy efficiency planning and implementation? 10:30 11:00 ASHRAE data center

More information

LG CNS Global Cloud Data Center

LG CNS Global Cloud Data Center LG CNS Global Cloud Data Center Are your digital assets vital to your business growth? Then, let LG CNS manage it for you Solution For further information, please contact: datacenter@lgcns.com www.lgcns.com/en

More information

ESC Conference: Energy Savings and Performance-Based Contracting Investment Initiative Update. Timothy D. Unruh PhD, PE, CEM.

ESC Conference: Energy Savings and Performance-Based Contracting Investment Initiative Update. Timothy D. Unruh PhD, PE, CEM. ESC Conference: Energy Savings and Performance-Based Contracting Investment Initiative Update July 29, 2014 Timothy D. Unruh PhD, PE, CEM Program Manager DOE FEMP 1 Energy Efficiency and Renewable Energy

More information

Mission Critical Facilities & Technology Conference November 3, 2011 Cooling 101. Nick Gangemi Regional Sales Manager Data Aire

Mission Critical Facilities & Technology Conference November 3, 2011 Cooling 101. Nick Gangemi Regional Sales Manager Data Aire Mission Critical Facilities & Technology Conference November 3, 2011 Cooling 101 Nick Gangemi Regional Sales Manager Data Aire Agenda Exactly what are we talking about ASHRAE TC 9.9 Design best practices

More information

Ecolibrium. Cloud control. Keeping data centres cool. OCTOBER 2018 VOLUME 17.9 RRP $14.95 PRINT POST APPROVAL NUMBER PP352532/00001

Ecolibrium. Cloud control. Keeping data centres cool. OCTOBER 2018 VOLUME 17.9 RRP $14.95 PRINT POST APPROVAL NUMBER PP352532/00001 Ecolibrium OCTOBER 2018 VOLUME 17.9 RRP $14.95 PRINT POST APPROVAL NUMBER PP352532/00001 Cloud control Keeping data centres cool. COVER FEATURE Cloud control Such is the growth in data centres globally

More information

Passive RDHx as a Cost Effective Alternative to CRAH Air Cooling. Jeremiah Stikeleather Applications Engineer

Passive RDHx as a Cost Effective Alternative to CRAH Air Cooling. Jeremiah Stikeleather Applications Engineer Passive RDHx as a Cost Effective Alternative to CRAH Air Cooling Jeremiah Stikeleather Applications Engineer Passive RDHx as a Cost Effective Alternative to CRAH Air Cooling While CRAH cooling has been

More information

Annual Report for the Utility Savings Initiative

Annual Report for the Utility Savings Initiative Report to the North Carolina General Assembly Annual Report for the Utility Savings Initiative July 1, 2016 June 30, 2017 NORTH CAROLINA DEPARTMENT OF ENVIRONMENTAL QUALITY http://portal.ncdenr.org Page

More information

IT infrastructure Next level for data center. Rittal The System Yavor Panayotov Data center Day

IT infrastructure Next level for data center. Rittal The System Yavor Panayotov Data center Day IT infrastructure Next level for data center Rittal The System Yavor Panayotov Data center Day - 2018 1 Rittal The System - Solutions Enclosures Enclosures Small enclosures Command Panel & support arm

More information

How much power?! Data Centre Efficiency. How much Money?! Carbon Reduction Commitment (CRC)

How much power?! Data Centre Efficiency. How much Money?! Carbon Reduction Commitment (CRC) How much power?! Data Centre Efficiency The US EPA found in 2006 data centres used 1.5% of total US consumption (5) For Bangor University data centres use approximately 5-10% of the total university electricity

More information

Data Center Energy and Cost Saving Evaluation

Data Center Energy and Cost Saving Evaluation Available online at www.sciencedirect.com ScienceDirect Energy Procedia 75 (2015 ) 1255 1260 The 7 th International Conference on Applied Energy ICAE2015 Data Center Energy and Cost Saving Evaluation Z.

More information

Energy Logic: Emerson Network Power. A Roadmap for Reducing Energy Consumption in the Data Center. Ross Hammond Managing Director

Energy Logic: Emerson Network Power. A Roadmap for Reducing Energy Consumption in the Data Center. Ross Hammond Managing Director Energy Logic: A Roadmap for Reducing Energy Consumption in the Data Center Emerson Network Power Ross Hammond Managing Director Agenda Energy efficiency Where We Are Today What Data Center Managers Are

More information

Optimization in Data Centres. Jayantha Siriwardana and Saman K. Halgamuge Department of Mechanical Engineering Melbourne School of Engineering

Optimization in Data Centres. Jayantha Siriwardana and Saman K. Halgamuge Department of Mechanical Engineering Melbourne School of Engineering Optimization in Data Centres Jayantha Siriwardana and Saman K. Halgamuge Department of Mechanical Engineering Melbourne School of Engineering Outline Background and Motivation Overview and scale of data

More information

The Greening of Services

The Greening of Services The Greening of Services CYNET Presentation - Under the scope of GN3Plus Project / NA3-T3 Activity Special Scientists: Nikoletta Tsioroli, Petros Ioannou CYNET 2015 Agenda Introduction NA3-T3 Tasks - Quick

More information

Case Study: Energy Systems Integration Facility (ESIF)

Case Study: Energy Systems Integration Facility (ESIF) Case Study: Energy Systems Integration Facility (ESIF) at the U.S. Department of Energy s National Renewable Energy Laboratory (NREL) in Golden, Colorado OFFICE HIGH BAY LABORATORIES DATA CENTER 1 Case

More information

Energy Efficient Data Centers

Energy Efficient Data Centers IBM Systems and Technology Group Lab Services Energy Efficient Data Centers Steven Ahladas IBM Corp ahladas@us.ibm.com Keeping our clients in the race. All trends going the same way. IT Servers were an

More information

DC Energy, Efficiency Challenges

DC Energy, Efficiency Challenges DC Energy, Efficiency Challenges Choosing a density strategy Implementing a high density environment Maximizing the efficiency benefit Anticipating the dynamic data center Key points on energy usage in

More information

Data Center Lifecycle and Energy Efficiency

Data Center Lifecycle and Energy Efficiency Data Center Lifecycle and Energy Efficiency Lifecycle infrastructure management, power management, thermal management, and simulation solutions enable data center modernization. White Paper October 2014

More information

Green Computing: Datacentres

Green Computing: Datacentres Green Computing: Datacentres Simin Nadjm-Tehrani Department of Computer and Information Science (IDA) Linköping University Sweden Many thanks to Jordi Cucurull For earlier versions of this course material

More information

Optimizing Cooling Performance Of a Data Center

Optimizing Cooling Performance Of a Data Center ASHRAE www.ashrae.org. Used with permission from ASHRAE Journal. This article may not be copied nor distributed in either paper or digital form without ASHRAE s permission. For more information about ASHRAE,

More information

Green Computing: Datacentres

Green Computing: Datacentres Green Computing: Datacentres Simin Nadjm-Tehrani Department of Computer and Information Science (IDA) Linköping University Sweden Many thanks to Jordi Cucurull For earlier versions of this course material

More information

Efficiency of Data Center cooling

Efficiency of Data Center cooling Efficiency of Data Center cooling Comparison of data room layouts and cooling systems Bohumil Cimbal Product manager for Cooling Systems in CONTEG Company Objective Basic questions between investor and

More information

Trends in Data Center Energy Efficiency

Trends in Data Center Energy Efficiency Trends in Data Center Energy Efficiency Presented by: Todd Boucher Better Building by Design 2012 1 Efficiency Vermont is a Registered Provider with The American Institute of Architects Continuing Education

More information

INT 492 : Selected Topic in IT II (Data Center System Design) 3(3-0-6)

INT 492 : Selected Topic in IT II (Data Center System Design) 3(3-0-6) INT 492 : Selected Topic in IT II (Data Center Design) 3(3-0-6) การออกแบบระบบศ นย สารสนเทศ Overview The American Society of Heating, Refrigeration and Air-Conditioning Engineers (ASHRAE) Technical Committee

More information

Evaporative free air cooling technology Providing evaporative free air cooling solutions.

Evaporative free air cooling technology Providing evaporative free air cooling solutions. Evaporative free air cooling technology Providing evaporative free air cooling solutions. Creating an effective workspace environment data centre free air cooling technology FreeCool - Evaporative Free

More information

Data Center Trends: How the Customer Drives Industry Advances and Design Development

Data Center Trends: How the Customer Drives Industry Advances and Design Development Bablu Kazi, PE MORRISON HERSHFIELD MISSION CRITICAL Data Center Trends: How the Customer Drives Industry Advances and Design Development What does the Customer Need? Scalability P U E Latest Technology

More information

Recapture Capacity for Existing. and Airflow Optimization

Recapture Capacity for Existing. and Airflow Optimization Recapture Capacity for Existing Data Centers Through Cooling and Airflow Optimization Introduction Challenges and Trends Agenda Cooling & Airflow Optimization Takeaways Learning Objectives Recognize opportunities

More information

November/December 2011

November/December 2011 November/December 2011 Company is justifiably proud of its new facilities Helping companies plan, design, operate, and eventually refresh or repurpose their data centers more efficiently and effectively

More information

The Efficient Enterprise. All content in this presentation is protected 2008 American Power Conversion Corporation

The Efficient Enterprise. All content in this presentation is protected 2008 American Power Conversion Corporation Ee The Efficient Enterprise All content in this presentation is protected 2008 American Power Conversion Corporation Keystrokes Kilowatts Heat OUT Electricity IN Need for bandwidth exploding Going hyperbolic!

More information

CHAPTER 11 Data Centers and IT Equipment

CHAPTER 11 Data Centers and IT Equipment CHAPTER 11 Data Centers and IT Equipment OBJECTIVES Understand the linkages between data center efficiency and business profitability. Identify the major energy uses in data centers and the sources of

More information

Performance Evaluation for Modular, Scalable Cooling Systems with Hot Aisle Containment in Data Centers. Final Report

Performance Evaluation for Modular, Scalable Cooling Systems with Hot Aisle Containment in Data Centers. Final Report Performance Evaluation for Modular, Scalable Cooling Systems with Hot Aisle Containment in Data Centers Final Report To The California Energy Commission May 2009 Tengfang Xu Environmental Energy Technologies

More information

Comprehensive Energy Management & Utility Master Plan

Comprehensive Energy Management & Utility Master Plan Comprehensive Energy Management & Utility Master Plan OVERVIEW University of Utah & Health Science Campus Overview Campus Transformation Value Drivers and Challenges Integrated Energy Planning Approach

More information

Power and Cooling for Ultra-High Density Racks and Blade Servers

Power and Cooling for Ultra-High Density Racks and Blade Servers Power and Cooling for Ultra-High Density Racks and Blade Servers APC White Paper #46 Richard L. Sawyer Director of Data Center Technology American Power Conversion Company 2005 APC corporation What has

More information

IBM Corporation. Global Energy Management System Implementation: Case Study. Global

IBM Corporation. Global Energy Management System Implementation: Case Study. Global Energy Management System Implementation: Case Study IBM Corporation ISO 50001 Registration: Results and Benefits It takes a global team to drive real success. Business case for energy management IBM is

More information

Green IT and Green DC

Green IT and Green DC Green IT and Green DC Alex SL Tay Regional Service Product Line Manager Site & Facilities Services, IBM ASEAN 1 What our clients are telling us We are running out of space in our data center We have environmental

More information

1.0 Executive Summary. 2.0 Available Features & Benefits

1.0 Executive Summary. 2.0 Available Features & Benefits Statement Of Work Energy Management Services Table of Contents 1.0 Executive Summary 2.0 Available Features & Benefits 3.0 Assessment Deliverables Selection 4.0 On Site Assessment Activities 5.0 Exclusions

More information

Data Centre Stockholm II, Sweden Flexible, advanced and efficient by design.

Data Centre Stockholm II, Sweden Flexible, advanced and efficient by design. Data Centre Stockholm II, Sweden Flexible, advanced and efficient by design. TelecityGroup Kvastvägen 25-29 128 62 Sköndal Stockholm Sweden Tel: +46 (0) 8 799 3800 se.info@telecity.com www.telecitygroup.se

More information

Data Center Infrastructure Management (DCIM) By Jesse Zhuo

Data Center Infrastructure Management (DCIM) By Jesse Zhuo Data Center Infrastructure Management (DCIM) By Jesse Zhuo Agenda The Evolution of DCIM Users Perspectives Management Methodology by Delta DCIM The Evolution of DCIM What is DCIM DCIM is software for Data

More information

Alfonso Ortega Villanova University Site Director Associate Vice President Research and Graduate Programs James R. Birle Professor of Energy Technology Villanova University www.villanova.edu/es2 Villanova

More information

Virtualization and consolidation

Virtualization and consolidation Virtualization and consolidation Choosing a density strategy Implementing a high-density environment Maximizing the efficiency benefit Anticipating the dynamic data center Schneider Electric 1 Topical

More information

Excool Indirect Adiabatic and Evaporative Data Centre Cooling World s Leading Indirect Adiabatic and Evaporative Data Centre Cooling

Excool Indirect Adiabatic and Evaporative Data Centre Cooling World s Leading Indirect Adiabatic and Evaporative Data Centre Cooling Excool Indirect Adiabatic and Evaporative Data Centre Cooling World s Leading Indirect Adiabatic and Evaporative Data Centre Cooling Data Centre Solutions Expertly Engineered Indirect Adiabatic and Evaporative

More information

Smart Data Centres. Robert M Pe, Data Centre Consultant HP Services SEA

Smart Data Centres. Robert M Pe, Data Centre Consultant HP Services SEA Smart Data Centres Robert M Pe, Data Centre Consultant Services SEA 2006 Hewlett-Packard Development Company, L.P. The information contained herein is subject to change without notice Content Data center

More information

Next Generation Cooling

Next Generation Cooling Next Generation Cooling Server Manufacturer Perspective Practical and Cost Effective David Moss Data Center Strategist Dell 1 Why Chip, Row, or Rack? Density? Energy Don t be scared; I don t see 50kW/rack

More information

Liebert DCW CATALOGUE

Liebert DCW CATALOGUE Liebert DCW CATALOGUE Chilled Water-Based High Density Cooling For The Data Center LIEBERT DCW Flexible Approaches For Energy Efficient Cooling Save up to 70% in cooling energy usage Data center managers

More information

United States Data Center Energy Usage Report

United States Data Center Energy Usage Report United States Data Center Energy Usage Report ARMAN SHEHABI, SARAH SMITH, DALE SARTOR, RICHARD BROWN, MAGNUS HERRLIN ENVIRONMENTAL AND ENERGY IMPACT DIVISION, LAWRENCE BERKELEY NATIONAL LABORATORY JONATHAN

More information

Catch the Heat Avoid the Heat! How an integrated management approach helps to operate your data center energy efficient and reliable

Catch the Heat Avoid the Heat! How an integrated management approach helps to operate your data center energy efficient and reliable Catch the Heat Avoid the Heat! How an integrated management approach helps to operate your data center energy efficient and reliable Urs Iten, Director Global Portfolio Management Data Center siemens.com/datacenters

More information

Case study on Green Data Center. Reliance Jio Infocomm Limited

Case study on Green Data Center. Reliance Jio Infocomm Limited Case study on Green Data Center 2 What is data center? Use and functions of Data Center. Basic Infrastructure requirement for data center. Energy consumption heads in data center. 3 What is Data Center

More information

DCIM Data Center Infrastructure Management Measurement is the first step

DCIM Data Center Infrastructure Management Measurement is the first step DCIM Data Center Infrastructure Management Measurement is the first step Presented by Julius Neudorfer Sponsored by DCIM Data Center Infrastructure Management Measurement is the first step Presented by

More information

Cooling. Highly efficient cooling products for any IT application. For More Information: (866) DATA CENTER SOLUTIONS

Cooling. Highly efficient cooling products for any IT application. For More Information: (866) DATA CENTER SOLUTIONS Cooling > Highly efficient cooling products for any IT application. DATA CENTER SOLUTIONS For More Information: (866) 787-3271 Sales@PTSdcs.com End-to-End Cooling Solutions from the Closet to the Data

More information

1.0 Executive Summary

1.0 Executive Summary Statement of Work - 1 - Power and Cooling Assessment for Data Center Professional Services Service 1.0 Executive Summary Table of Contents 1.0 Executive Summary 2.0 Features & Benefits 3.0 Details of Service

More information

Hot vs Cold Energy Efficient Data Centers. - SVLG Data Center Center Efficiency Summit

Hot vs Cold Energy Efficient Data Centers. - SVLG Data Center Center Efficiency Summit Hot vs Cold Energy Efficient Data Centers - SVLG Data Center Center Efficiency Summit KC Mares November 2014 The Great Debate about Hardware Inlet Temperature Feb 2003: RMI report on high-performance data

More information

Optimizing the Existing Building Cx Process:

Optimizing the Existing Building Cx Process: Optimizing the Existing Building Cx Process: Integrating EBCx into ESPCs Lia Webster, P.E. Senior Engineer Portland Energy Conservation, Inc. AIA Quality Assurance Learning Objectives 1. Identify ways

More information

NREL Validates LCS Technology. PRESENTED BY Herb Zien CEO, LiquidCool Solutions

NREL Validates LCS Technology. PRESENTED BY Herb Zien CEO, LiquidCool Solutions NREL Validates LCS Technology PRESENTED BY Herb Zien CEO, LiquidCool Solutions Learning Objectives As much as 40% of data center power is used to circulate air, and fans in a typical 30-megawatt data center

More information

Federal Data Center Consolidation Initiative (FDCCI) Workshop I: Initial Data Center Consolidation Plan

Federal Data Center Consolidation Initiative (FDCCI) Workshop I: Initial Data Center Consolidation Plan Federal Data Center Consolidation Initiative (FDCCI) Workshop I: Initial Data Center Consolidation Plan June 04, 2010 FDCCI Workshop I Agenda for June 4, 2010 1. Welcome Katie Lewin GSA Director Cloud

More information

DATA CENTER AIR HANDLING COOLING SOLUTIONS

DATA CENTER AIR HANDLING COOLING SOLUTIONS DATA CENTER AIR HANDLING COOLING SOLUTIONS World-class performance and reliability from YORK As data storage and protection needs grow, so can costs and complexity. That s why having the right partner

More information

Reducing Energy Consumption with

Reducing Energy Consumption with Reducing Energy Consumption with Passive Cooling Ian Cathcart, RCDD Technical Support Manager Technical Support Manager Chatsworth Products, Inc. Thermal Management: Mission Critical Data center heat loads

More information

Recent Developments in Federal Electronics Stewardship

Recent Developments in Federal Electronics Stewardship Recent Developments in Federal Electronics Stewardship Why Focus on Electronics? Rapid advances in IT have resulted in: Increased sales of electronics worldwide Increased energy consumption A new stream

More information

Technology Changes in Data Centers

Technology Changes in Data Centers Technology Changes in Data Centers Mark Murrill Emerson Network Power TFI Conference, January 2014 Austin, TX 1 Agenda Market trends and impact on data center design Convergence around traditional telecom

More information

Maximising Energy Efficiency and Validating Decisions with Romonet s Analytics Platform. About Global Switch. Global Switch Sydney East

Maximising Energy Efficiency and Validating Decisions with Romonet s Analytics Platform. About Global Switch. Global Switch Sydney East Maximising Energy Efficiency and Validating Decisions with Romonet s Analytics Platform Case Study - Global Switch Sydney East About Global Switch Global Switch is a leading owner, operator and developer

More information

ANCIS I N C O R P O R A T E D

ANCIS I N C O R P O R A T E D Thermal Design of Data Centers to Safeguard Electronic Equipment Presentation at the Thermal Design Center Santa Clara, CA, March 9, 2010 Magnus K. Herrlin, Ph.D. President Incorporated mherrlin@ancis.us

More information

ASHRAE Data Center Standards: An Overview

ASHRAE Data Center Standards: An Overview Mission Critical Facilities ASHRAE Data Center Standards: An Overview 10012 North Dale Mabry Highway Suite 109 Tampa, FL 33618 813-792-6009 www.pergravis.com Presenter: Steve Ritzi, CDCE Pergravis is a

More information

EO and Smart Federal Government Data Center Management

EO and Smart Federal Government Data Center Management 1 Overview In fiscal year 2009, the U.S. government used an astounding 1,095.7 trillion BTUs of energy. This total included everything from keeping the lights on at the Lincoln Memorial to maintaining

More information

POWER AND THERMAL MANAGEMENT SOLUTIONS

POWER AND THERMAL MANAGEMENT SOLUTIONS POWER AND THERMAL MANAGEMENT SOLUTIONS Power has long been a critical public utility we depend on in our homes and daily lives. Companies are under pressure to provide the necessary hardware and software

More information

White Paper: Data Center Capacity Management Provides New Business Opportunities & Efficiency at State-of-the-Art One Wilshire June 8, 2017

White Paper: Data Center Capacity Management Provides New Business Opportunities & Efficiency at State-of-the-Art One Wilshire June 8, 2017 White Paper: Data Center Capacity Management Provides New Business Opportunities & Efficiency at State-of-the-Art One Wilshire June 8, 2017 As operators have demanded increasing levels of power density

More information

DATA CENTER COLOCATION BUILD VS. BUY

DATA CENTER COLOCATION BUILD VS. BUY DATA CENTER COLOCATION BUILD VS. BUY Comparing the total cost of ownership of building your own data center vs. buying third-party colocation services Executive Summary As businesses grow, the need for

More information

CLOSE CONTROL AIR CONDITIONERS DATA CENTERS DESIGN SIDE NOTES

CLOSE CONTROL AIR CONDITIONERS DATA CENTERS DESIGN SIDE NOTES CLOSE CONTROL AIR CONDITIONERS DATA CENTERS DESIGN SIDE NOTES DATA CENTER NEEDS A MINUTE IN THE LIFE OF INTERNET Evolving technology has created the necessity for ever greater exchange of data, increasing

More information

Air Containment Design Choices and Considerations

Air Containment Design Choices and Considerations Air Containment Design Choices and Considerations Brad J. Murphy, A.Sc.T., ATS, DCDC, DCEP, Principal Racon Data Centres Introduction Introduction Air containment design must consider many different factors

More information

IT Transformation Through ESPCs

IT Transformation Through ESPCs June 27, 2013 IT Transformation Through ESPCs Restricted Siemens AG 2013. All rights reserved. siemens.com/answers Contents Integration of IT with Facilities ESPCs as Related to Data Centers Measurement

More information

ASHRAE elearning Course Catalog

ASHRAE elearning Course Catalog ASHRAE elearning Course Catalog Web-based, On-Demand Training Corporate Discounts Available (see page 2) 5 Great Reasons to Use ASHRAE elearning: Easy Administration: No special software required. Transcripts

More information

Senate Comprehensive Energy Bill

Senate Comprehensive Energy Bill Senate Comprehensive Energy Bill Both the House and Senate energy committees are currently in the process of developing comprehensive energy bills. The Senate Energy and Natural Resources Committee released

More information

1/28/2013. ASHRAE Standard ASHRAE Standard Aiming at 50% Energy Savings For ASHRAE Standard 90.

1/28/2013. ASHRAE Standard ASHRAE Standard Aiming at 50% Energy Savings For ASHRAE Standard 90. -203-203 Stephen V. Skalko, P.E. Chair SSPC 90. Aiming at 50% Energy Savings For 90.-203 ASHRAE Winter Meeting January 28, 203 AIA Objectives for the Session Develop basic understanding of different formats

More information

Sustainable Business with Green Datacenter

Sustainable Business with Green Datacenter Site and Facilities Services Data Center Services Sustainable Business with Green Datacenter Prag, May 11th, 2010 Stephan Bhend, IBM Site and Facilities Services 2008 IBM Corporation Sustainable Business

More information