CLIMATE. CUSTOMIZED. CyberHandler2 from 30KW to 520 KW. The indirect evaporative free-cooling Air Handling Unit

Size: px
Start display at page:

Download "CLIMATE. CUSTOMIZED. CyberHandler2 from 30KW to 520 KW. The indirect evaporative free-cooling Air Handling Unit"

Transcription

1 CLIMATE. CUSTOMIZED. CyberHandler2 from 30KW to 520 KW The indirect evaporative free-cooling Air Handling Unit

2 Flexible & Efficient 11 sizes from 30 kw up to 520 kw to fit your needs with maximum efficiency Typical ppue between 1.02&1.10 The CyberHandler2 offers you a wide range of capacities, from 30 kw to 520 kw, in 11 different sizes allowing you to find the best compromise cost/efficiency according to your specific requirements. Each size will be an optimized and customized solution that perfectly fit to your installation requirements with the maximum efficiency and flexibility. With an high efficient indirect evaporative free-cooling design and using the industry state-of-the-art components the CyberHandler2 minimizes the running costs and achieve ppue s down to 1,02. The unique STULZ C7000 controller specially designed for precision control of mission-critical environments, with a proven track record of success within this industry, makes this product the most energy efficient trusted option in the market. Operation Modes & Benefits operation modes based on ambient air temperatures: 0 / Dry Mode Top - Up Mode Wet Mode Dry Mode (free-cooling only): Adiabatics OFF Mechanical Cooling OFF Wet Mode (Adiabatic): Adiabatics ON Mechanical Cooling OFF Top-Up Mode (Mix Mode): Adiabatics ON Mechanical Cooling ON The benefits of the indirect evaporative cooling: Outdoor contamination free Evaporative cooling extends indirect free-cooling operation all year round Unbeatable energy efficiency levels with ppues in the range of Lower total cost of ownership (TCO): reduced CAPEX, OPEX, maintenance, infrastructure costs, etc Internal white space is reduced to a minimum, as the unit is installed externally Simplified installation: easier management of power cabling, pipes and water, not needed inside the white space Downsizing of the electrical infrastructure allows savings in CAPEX of 6-8% Faster return of investment

3 Installation Configurations 2 configurations available to adapt to your installation requirements Wall Configuration SH/RH * In this configuration the horizontal path of the IT room supply and return air allow the units to be installed directly in the wall of the building in a perimeter distribution. * SH: Supply Horizontal RH: Return Horizontal Roof Configuration SB/RB * This configuration allows the supply and return air to enter directly into the IT Room ceiling. No ductwork is needed on the roof. * SB: Supply Bottom RB: Return Bottom

4 Cooling Configurations Indirect evaporative free-cooling The ideal solution when the outdoor ambient conditions are suitable to reach the room supply temperature set point without the need of additional mechanical cooling. Only the adiabatic free-cooling system is enough to achieve the required cooling capacity. Indirect evaporative free-cooling with Top-Up integrated DX cooling system An integrated DX Top-Up cooling system helps the Air Handling Unit to achieve the required cooling capacity when the extreme outdoor ambient conditions are reached. The complete DX system (evaporator/ compressor/condenser) is inside the unit. The top-up DX system can reach up to 30% of the total required cooling capacity.

5 Indirect evaporative free-cooling with CW Coil Top-Up/Redundant cooling In case of extreme outdoor ambient conditions, the adiabatic cooling system is complemented by an integrated chilled water coil connected to a remote chiller. Options for the full CW coil redundancy or top-up are available. Indirect evaporative free-cooling with redundant DX cool. system In this configuration the Air Handling Unit is equipped with a DX coil (evaporator and compressors) which connects to an outdoor condensing unit allowing the system to reach 100% redundancy only with the DX system.

6 Components Overview Mechanical cooling options Chilled water coil (external chiller) DX coil (external condensor) Integrated DX cooling system (top-up) Compressor technology The latest EC compressor scroll inverter technology Additional tandem scroll compressors for higher capacities Maximum efficiency at partial loads Fans Exhaust Air Plug fan technology Latest technology of high efficient EC motors Reduce the noise level Outdoor or Air Filters Eurovent certified Meet the standard EN779:2012 Low pressure drop design Available in different classes (G4, M5, F7 and F9) Controller STULZ C7000 State-of-the-art intelligent control for IT cooling systems Designed specifically for precision control of mission-critical environments In-house development of hardware and software.

7 Air-to-air plate heat exchangers 100 % aluminium, epoxy painted, extra sealed 100% indirect heat recovery Eurovent certified Excellent relation efficiency vs pressure drop Double PHX for higher cooling recovery Return Air Dampers Supply Air 100 % aluminium and plastics (no corrosion issues) Low pressure drop design Different leakage classes available Special fire and smoke dampers (as optional) Water spray nozzles Full cone stainless steel nozzles Guarantees a full shower of the plate heat exchanger Non-clogging design Allows the use of demineralized water Water Pump High efficiency stainless steel circulation pump Allows the use of demineralized water Low pressure system Redundant pump as optional

8 Selection Tool The CyberHandler2 Select is a powerful software tool specially designed to allow an easy and friendly experience trough the selection of each Air Handling Unit. The user-friendly interface guides you through the optimization and customization of the unit that best fits the project requirements. As outputs the CyberHandler2 Select is able to deliver you the following documentation: Technical specification sheets 2D Drawings 3D image Quotation Life Cycle Cost (LCC) calculation ppue calculation (inbuilt the ASHRAE Weather Data Viewer version 5.0) The complete solution The CyberHandler2 is more than a product, we have a full range of services available to offer you a turnkey solution for the data center cooling: Life Cycle Cost/ ppue Calc. RO Water Treat. Syst. Warranty CyberHandler2 Commissioning Maintenance Software tools for the calculation of the Life Cycle Cost/pPUE Reverse Osmosis (RO) water treatment system Commissioning Maintenance Warranty

9 C7000 Controller C 7000 Electronic Controller: Intelligent Control for IT Cooling Systems Designed specifically for precision control of mission-critical environments Energy-efficient control concepts onboard (CW standby management, raised-floor pressure management, Indirect Dynamic Free Cooling) Preservation of parameters during firmware updates Onboard protocol Modbus RTU (customizing Modbus data point list) Freely configurable digital alarm inputs Integrated data logger Internal Modbus component communication bus Hardware periphery check after boot sequence The following BMS protocols are supported: BACnet IP, BACnet MS/TP, Modbus TCP, and LonWorks WIB 8000: The All-in-One Web Interface for Precision Air-Conditioning Systems. The WIB 8000 is user-friendly and highly functional, and it offers easy data exchange and monitoring with global adaptability. Functions and Monitoring Alert information via to up to five recipients Ongoing retrieval of data from the controller Monitoring of up to 32 units via Web browser Ethernet port Bus-independent zone operation Easy connection to existing building management system User-Friendly Works via HTTP and SNMP in parallel No JavaScript, no cookies Easy and quick configuration via Web page Easy to install and suitable for retrofitting (only one component to install!)

10 Main Features at a glance Cooling range from 30 kw to 520 kw 11 sizes Ready for roof and wall installation The best casing leak classification according to the standard EN1886 (L1/L1) Designed for minimum pressure losses STULZ C7000 controller designed especially for precision control of mission-critical environments Easy access for maintenance Several filter classes available: G4, M5, F7 and F9 Designed to fit standard transportation Flexible modular installation 3 cooling systems in 1: - Indirect free-cooling - Indirect evaporative cooling - Mechanical cooling (as top-up or redundancy) Customize it Customize the CyberHandler2 to your requirements with a wide range of options Dual power supply with automatic or manual switchover Ultrasonic humidifiers Fresh air damper for CO2 control Outdoor installation Damper (ambient side and DC room return) Silencers FAT Control systems UPS backed Fire and smoke dampers (Data Hall side) Different filter classes according the EN779: M5, F7, F9 RO water treatment system Anti-frost control Redundant adiabatic water pump Different power supply

11 Services on your doorstep STULZ is a global company with headquarters in Hamburg, Germany, 19 subsidiaries, 7 production sites and sales and service partners in more than 140 countries. In 1971 we began specializing in the development an production of precision air conditioning units and chi for data centers. That s a wealth of experience gathere over 40 years from many thousands of projects that we ve implemented worldwide. Technical development from Germany We put a great deal of experience and innovative spirit into our air conditioning systems. Engineers, specialist departments and sales employees work closely together and are involved through all stages of development, all the way to the finished product. We brook no compro - mise where the efficiency of our products is concerned, and cost-effective operation is at the heart of our endeavors. Test to your specifications In our state-of-the-art, 700-square-meter Test Center with its various climate chambers, we can perform a variety of tests on precision air conditioning systems and chillers. If you decide to purchase a STULZ solution, you can book a witness test in our Test Center. This allows you to have the desired air conditioning system tested for compliance with your exact specifications, creating transparency and providing you with information about the system s performance and energy consumption.

12

Air Handling Units. With Intelligence

Air Handling Units. With Intelligence Air Handling Units With Intelligence Production facility in India Services on your doorstep STULZ is a global company with headquarters in Hamburg, Germany. 19 Subsidiaries, 9 Production sites and Sales

More information

Precision Cooling Mission Critical Air Handling Units

Precision Cooling Mission Critical Air Handling Units M I S S I O N C R I T I CA L C O O L I N G Precision Cooling Mission Critical Air Handling Units Global Expertise for Precision Cooling Solutions STULZ is a privately owned, global manufacturer of highly

More information

CyberHandler 2 The Indirect Evaporative Free Cooling Air Handling Unit

CyberHandler 2 The Indirect Evaporative Free Cooling Air Handling Unit CyberHandler 2 The Indirect Evaporative Free Cooling Air Handling Unit Services on your doorstep For over 40 years we have been one of the world s leading manufacturers of air conditioning solutions for

More information

IT COOLING EVAPORATIVE COOLING SYSTEM. 2 STAGE INDIRECT ADIABATIC COOLING SYSTEM FOR LARGE DATA CENTERS FROM 80 TO 320 kw

IT COOLING EVAPORATIVE COOLING SYSTEM. 2 STAGE INDIRECT ADIABATIC COOLING SYSTEM FOR LARGE DATA CENTERS FROM 80 TO 320 kw IT COOLING EVAPORATIVE COOLING SYSTEM 2 STAGE INDIRECT ADIABATIC COOLING SYSTEM FOR LARGE DATA CENTERS FROM 8 TO 3 kw IT COOLING EVAPORATIVE COOLING SYSTEM ADIABATIC COOLING FOR HIGH EFFICIENCY - Variable

More information

Ecoflair Air Economizers

Ecoflair Air Economizers Ecoflair Air Economizers Cooling to maximize value for the cloud schneider-electric.com/ecoflair Life is On Schneider Electric 1 Ecoflair takes data center efficiency to new heights 2 Imagine cooling your

More information

Indirect Adiabatic and Evaporative Data Center Cooling

Indirect Adiabatic and Evaporative Data Center Cooling Indirect Adiabatic and Evaporative Data Center Cooling Developed in response to the broadening of the ASHRAE recommended server inlet temperature envelope in 2008, Excool represents the most advanced technology

More information

Indirect Adiabatic and Evaporative Data Centre Cooling

Indirect Adiabatic and Evaporative Data Centre Cooling Indirect Adiabatic and Evaporative Data Centre Cooling Developed in response to the broadening of the ASHRAE recommended server inlet temperature envelope in 2008, Excool represents the most advanced

More information

CHILLED WATER. HIGH PRECISION AIR CONDITIONERS, FROM 7 TO 211 kw

CHILLED WATER. HIGH PRECISION AIR CONDITIONERS, FROM 7 TO 211 kw IT COOLING CLOSE CONTROL AIR CONDITIONERS CHILLED WATER HIGH PRECISION AIR CONDITIONERS, FROM 7 TO 211 kw 3 Versions available Single chilled water coil Double chilled water coil High temperature IT COOLING

More information

IT Cooling Solutions. The Whole Range of. Data Center Cooling Solutions

IT Cooling Solutions. The Whole Range of. Data Center Cooling Solutions IT Cooling Solutions The Whole Range of Data Center Cooling Solutions DIRECT FREE COOLING ROOM COOLING HIGH DENSITY COOLING DATA CENTER COOLING INDIRECT FREE COOLING CHILLER UNITS AIR HANDLING UNITS MODULAR

More information

Aquaflair. BREC/F and BCEC/F kw

Aquaflair. BREC/F and BCEC/F kw Aquaflair Air-cooled chillers and free-cooling chillers with screw or oil-free centrifugal compressors equipped with adiabatic system BREC/F and BCEC/F 350-1350 kw Dualism for evolution: the combination

More information

Liebert. EFC from 100 to 350 kw. The Highly Efficient Indirect Evaporative Freecooling Unit

Liebert. EFC from 100 to 350 kw. The Highly Efficient Indirect Evaporative Freecooling Unit Liebert EFC from 100 to 350 kw The Highly Efficient Indirect Evaporative Freecooling Unit LIEBERT EFC from 100 to 350 kw Vertiv Vertiv designs, builds and services mission critical technologies that enable

More information

Product Brochure DENCO Close Control Units Row-DENCO. High Density Cooling for Data Centres

Product Brochure DENCO Close Control Units Row-DENCO. High Density Cooling for Data Centres Product Brochure DENCO Close Control Units Row-DENCO High Density Cooling for Data Centres Data Centre Cooling Through a history in close control, we have developed a broad and deep understanding of how

More information

Excool Indirect Adiabatic and Evaporative Data Centre Cooling World s Leading Indirect Adiabatic and Evaporative Data Centre Cooling

Excool Indirect Adiabatic and Evaporative Data Centre Cooling World s Leading Indirect Adiabatic and Evaporative Data Centre Cooling Excool Indirect Adiabatic and Evaporative Data Centre Cooling World s Leading Indirect Adiabatic and Evaporative Data Centre Cooling Data Centre Solutions Expertly Engineered Indirect Adiabatic and Evaporative

More information

HIGH EFFICIENCY Central Chiller

HIGH EFFICIENCY Central Chiller Blending Conveying Drying Process Cooling Heat Transfer Size Reduction HIGH EFFICIENCY Central Chiller Energy Efficient Modular & Expandable Virtually Eliminate Downtime Available in 20-60 ton single units,

More information

The new generation of dedicated HVAC drives

The new generation of dedicated HVAC drives The new generation of dedicated HVAC drives Contents Selection guides p. 8 Presentation p. 14 References p. 18 Bus and communication networks p. 26 Motor starters p. 28 Altivar 212 Orientated towards performance,

More information

Case Study The University of Warwick

Case Study The University of Warwick Data Centre Solutions...energy efficient by design Case Study The University of Warwick Workspace Technology deploys industry leading Indirect Fresh Air Cooling for the University of Warwick Workspace

More information

Aquaflair. Uniflair TRAC, TRAF and TRAH. Air-cooled chillers, free-cooling chillers and heat pumps with scroll compressors.

Aquaflair. Uniflair TRAC, TRAF and TRAH. Air-cooled chillers, free-cooling chillers and heat pumps with scroll compressors. Aquaflair Uniflair TRAC, TRAF and TRAH Air-cooled chillers, free-cooling chillers and heat pumps with scroll compressors 120-350kW Uniflair TRA ranges 115-350kW Air-cooled Chillers Cooling, Free cooling

More information

A Data Center Heat Removal System That Saves... 80% Discover Inertech s Award-winning Data Center Heat Removal System

A Data Center Heat Removal System That Saves... 80% Discover Inertech s Award-winning Data Center Heat Removal System A Data Center Heat Removal System That Saves... Infrastructure Power Water up to 40% up to 80% up to 85% Discover Inertech s Award-winning Data Center Heat Removal System A Cool Solution; A Breakthrough

More information

IT Air Conditioning Units

IT Air Conditioning Units IT Air Conditioning Units Modern Flexible Effective Energy Saving CoolTeg Plus and CoolTop overview CoolTeg Plus CW CoolTeg Plus DX CoolTeg Plus XC CoolTop Installation Between IT racks On top of IT rack

More information

AireFlow kW DX AIR. Data Centre Cooling Product of the Year. Indirect Adiabatic AHU

AireFlow kW DX AIR.   Data Centre Cooling Product of the Year. Indirect Adiabatic AHU IT Cooling Indirect Adiabatic AHU Data Centre Cooling Product of the Year AireFlow 100-440kW Indirect adiabatic cooling for resilient, optimised data centre cooling + Delivers all year round free-cooling*

More information

FREECOOLING, EVAPORATIVE AND ADIABATIC COOLING TECHNOLOGIES IN DATA CENTER. Applications in Diverse Climates within Europe, Middle East and Africa

FREECOOLING, EVAPORATIVE AND ADIABATIC COOLING TECHNOLOGIES IN DATA CENTER. Applications in Diverse Climates within Europe, Middle East and Africa FREECOOLING, EVAPORATIVE AND ADIABATIC COOLING TECHNOLOGIES IN DATA CENTER Applications in Diverse Climates within Europe, Middle East and Africa Freecooling, Evaporative and Adiabatic Cooling Technologies

More information

STULZ Micro DC. with Chip-to-Atmosphere TM Liquid to Chip Cooling

STULZ Micro DC. with Chip-to-Atmosphere TM Liquid to Chip Cooling STULZ Micro DC with Chip-to-Atmosphere TM Liquid to Chip Cooling STULZ Micro DC Data center professionals and communication service providers (CSPs) face an increasingly difficult world. The continued

More information

Industry leading low energy evaporative fresh air cooling.

Industry leading low energy evaporative fresh air cooling. Industry leading low energy evaporative fresh air cooling. Freecool Evaporative Free Air Cooling by Workspace Technology delivers innovative low energy cooling for a range of applications including data

More information

Total Modular Data Centre Solutions

Total Modular Data Centre Solutions Sector Data Centre Total Modular Data Centre Solutions www.airedale.com BRITISH MANUFACTURER ENERGY EFFICIENCY CONTROLS SERVICE TRAINING 01 Standardised Modular Designs to fit your needs Our modular system

More information

PROCESS & DATA CENTER COOLING. How and Why To Prepare For What s To Come JOHN MORRIS REGIONAL DIRECTOR OF SALES

PROCESS & DATA CENTER COOLING. How and Why To Prepare For What s To Come JOHN MORRIS REGIONAL DIRECTOR OF SALES PROCESS & DATA CENTER COOLING How and Why To Prepare For What s To Come JOHN MORRIS REGIONAL DIRECTOR OF SALES CONGRATULATIONS 2 BOLD PREDICTION 3 Where We Are TODAY Computer Technology NOW advances more

More information

Chilled Water Computer Room Air Handler (CRAH) Critical Infrastructure for the World s Leading Data Centers

Chilled Water Computer Room Air Handler (CRAH) Critical Infrastructure for the World s Leading Data Centers Chilled Water Computer Room Air Handler (CRAH) Critical Infrastructure for the World s Leading Data Centers DATA CENTER COOLING EXPERTISE Data Center managers have unique needs. Nortek Air Solutions listens

More information

Ecotel Free Cool 5-15kW

Ecotel Free Cool 5-15kW Precision Air Conditioning Free-cooling Ecotel Free Cool 5-15kW + + Self-contained compact outdoor cabin cooler + + 100% free-cooling + + -48V DC supply option + + Easy serviceability (front component

More information

Reducing Data Center Cooling Costs through Airflow Containment

Reducing Data Center Cooling Costs through Airflow Containment FEATURE Reducing Data Center Cooling Costs through Airflow Containment Implementing a containment solution in the data center costs much less than the alternatives of adding air handlers or other supplemental

More information

Liebert. PCW from 25 to 220 kw. Chilled Water Units Optimizing Data Center Efficiency

Liebert. PCW from 25 to 220 kw. Chilled Water Units Optimizing Data Center Efficiency Liebert PCW from 25 to 220 kw Chilled Water Units Optimizing Data Center Efficiency LIEBERT PCW from 25 to 220 kw Vertiv Vertiv designs, builds and services mission critical technologies that enable the

More information

7 Best Practices for Increasing Efficiency, Availability and Capacity. XXXX XXXXXXXX Liebert North America

7 Best Practices for Increasing Efficiency, Availability and Capacity. XXXX XXXXXXXX Liebert North America 7 Best Practices for Increasing Efficiency, Availability and Capacity XXXX XXXXXXXX Liebert North America Emerson Network Power: The global leader in enabling Business-Critical Continuity Automatic Transfer

More information

Control systems. Efficient room control

Control systems. Efficient room control Control systems Efficient room control AIRCONTROL Efficient room control with X-AIRCONTROL Humidity Occupancy Increasingly demanding requirements on energy efficiency as well as the latest EU regulations

More information

Liebert Economizer Cooling Solutions Reduce Cooling Costs by up to 50% Without Compromising Reliability

Liebert Economizer Cooling Solutions Reduce Cooling Costs by up to 50% Without Compromising Reliability Precision Cooling for Business-Critical Continuity TM Liebert Economizer Cooling Solutions Reduce Cooling Costs by up to 50% Without Compromising Reliability DATA CENTER SOLUTIONS For More Information:

More information

Data center cooling evolution. The hottest way to save energy. Lucio Bustaffa: Product Development Manager BlueBox Group

Data center cooling evolution. The hottest way to save energy. Lucio Bustaffa: Product Development Manager BlueBox Group Data center cooling evolution. The hottest way to save energy Lucio Bustaffa: Product Development Manager BlueBox Group Data Center overview What s happening in the web? 2 Data Center overview What s happening

More information

ICS COOL ENERGY THE TEMPERATURE CONTROL SPECIALISTS

ICS COOL ENERGY THE TEMPERATURE CONTROL SPECIALISTS ICS COOL ENERGY THE TEMPERATURE CONTROL SPECIALISTS GLOBAL PRESENCE, LOCAL SERVICE WHERE WE MAKE IT WORK WHO WE MAKE IT WORK FOR ACCREDITATIONS i-chiller -10 C to 30 C 1.7 TO 505kW i-chiller COMPACT

More information

Rack cooling solutions for high density racks management, from 10 to 75 kw

Rack cooling solutions for high density racks management, from 10 to 75 kw Rack cooling solutions for high density racks management, from 10 to 75 Superior efficiency, high reliability, low energy consumption Modern data center are characterized by 24/7 operation all year long.

More information

Liebert. PDX from 15 to 165 kw. Direct Expansion Solution for Small and Medium Data Centers

Liebert. PDX from 15 to 165 kw. Direct Expansion Solution for Small and Medium Data Centers Liebert PDX from 5 to 65 Direct Expansion Solution for Small and Medium Data Centers LIEBERT PDX from 5 to 65 Vertiv Vertiv designs, builds and services mission critical technologies that enable the vital

More information

Liebert. AFC from 500 to 1700 kw. The Adiabatic Freecooling Solution with Top-Tier Availability

Liebert. AFC from 500 to 1700 kw. The Adiabatic Freecooling Solution with Top-Tier Availability Liebert AFC from 500 to 1700 kw The Adiabatic Freecooling Solution with Top-Tier Availability Liebert AFC from 500 to 1700 kw Vertiv Vertiv designs, builds and services mission critical technologies that

More information

Your Solution For Energy and Cost Savings. McQuay Packaged Chiller Plant

Your Solution For Energy and Cost Savings. McQuay Packaged Chiller Plant Your Solution For Energy and Cost Savings McQuay Packaged Chiller Plant Innovative Solutions for Your Chiller Plant McQuay packaged chiller plants provide energy efficient chillers integrated with pumps,

More information

Mission Critical Facilities & Technology Conference November 3, 2011 Cooling 101. Nick Gangemi Regional Sales Manager Data Aire

Mission Critical Facilities & Technology Conference November 3, 2011 Cooling 101. Nick Gangemi Regional Sales Manager Data Aire Mission Critical Facilities & Technology Conference November 3, 2011 Cooling 101 Nick Gangemi Regional Sales Manager Data Aire Agenda Exactly what are we talking about ASHRAE TC 9.9 Design best practices

More information

Future of Cooling High Density Equipment. Steve Madara Vice President and General Manager Liebert Precision Cooling Business Emerson Network Power

Future of Cooling High Density Equipment. Steve Madara Vice President and General Manager Liebert Precision Cooling Business Emerson Network Power Future of Cooling High Density Equipment Steve Madara Vice President and General Manager Liebert Precision Cooling Business Emerson Network Power Agenda Issues facing the Data Center Managing the explosive

More information

IEC DATA CENTRE INDIRECT EVAPORATIVE COOLING SYSTEM

IEC DATA CENTRE INDIRECT EVAPORATIVE COOLING SYSTEM DATA CENTRE INDIRECT EVAPORATIVE COOLING SYSTEM THE GLOBAL DATA CENTRE MARKET The data centre air conditioning market is expected to grow with a CAGR (compound annual growth rate) of about 12% in the next

More information

Liebert PDX from 15 to 120 kw

Liebert PDX from 15 to 120 kw Liebert PDX from 5 to 0 kw The Thermal Management Solution for Small and Medium Data Centers Electronic Expansion Valve Efficiency Digital Scroll Partial Load icom Control TCO Optimization Integrated Solution

More information

Close-coupled cooling

Close-coupled cooling Close-coupled cooling Intelligently controlled high-performance InRow cooling for the IT environment APC TM by Schneider Electric close-coupled cooling products provide a modular, scalable, and predictable

More information

ASHRAE IRELAND HVAC FOR DATA CENTRES. Michael Geraghty Building Services Engineer (DipEng) Company owner and managing director

ASHRAE IRELAND HVAC FOR DATA CENTRES. Michael Geraghty Building Services Engineer (DipEng) Company owner and managing director ASHRAE IRELAND HVAC FOR DATA CENTRES Michael Geraghty Building Services Engineer (DipEng) Company owner and managing director michael@entropic.ie OVERVIEW OF THE MARKET SITUATION IN IRELAND Relative Data

More information

glide glider kw R134a air cooled liquid chillers AND free cooling chillers FREE COOLING SHELL A C CLASS E C Energy Class RCGROUP SpA

glide glider kw R134a air cooled liquid chillers AND free cooling chillers FREE COOLING SHELL A C CLASS E C Energy Class RCGROUP SpA 99 glide air cooled liquid chillers ND free cooling chillers glider 178 1328 Energy Class More efficient + B C D E F G Less efficient R134a CLSS SHELL C E C FREE COOLING 100 air cooled liquid chiller and

More information

Data Center Optimized Controls

Data Center Optimized Controls Data Center Optimized Controls Controls Agenda 30 min. Emerson Control Products icom (Dynamic Thermal Optimization) 20 min. Station Rotation Station 1: Controller Challenge Station 2: Wireless Demo 5 min.

More information

Liebert PDX from 15 to 120 kw

Liebert PDX from 15 to 120 kw Liebert PDX from 5 to 0 kw The Thermal Management Solution for Small and Medium Data Centers Electronic Expansion Valve Efficiency Digital Scroll Partial Load icom TM Control TCO Optimization Integrated

More information

Control system. Type FSL-CONTROL II. Modular, stand-alone room control system, specially for decentralised ventilation systems (with bus communication

Control system. Type FSL-CONTROL II. Modular, stand-alone room control system, specially for decentralised ventilation systems (with bus communication X X testregistrierung Control system Type Central BMS interface DCP-FSL II-Stand-alone Pressure independent control valve Straight-way valve Modular, stand-alone room control system, specially for decentralised

More information

Is Data Center Free Cooling Feasible in the Middle East? By Noriel Ong, ASEAN Eng., PMP, ATD, PQP

Is Data Center Free Cooling Feasible in the Middle East? By Noriel Ong, ASEAN Eng., PMP, ATD, PQP Is Data Center Free Cooling Feasible in the Middle East? By Noriel Ong, ASEAN Eng., PMP, ATD, PQP This case study will evaluate the feasibility of data center free cooling in the Middle East using indirect

More information

Aquaflair. BREC & BREF kW 380V/3ph/60Hz - 460V/3ph/60Hz. Air-cooled chillers and free-cooling chillers with double screw compressors

Aquaflair. BREC & BREF kW 380V/3ph/60Hz - 460V/3ph/60Hz. Air-cooled chillers and free-cooling chillers with double screw compressors Aquaflair Air-cooled chillers and free-cooling chillers with double screw compressors BREC & BREF 350-1200kW 380V/3ph/60Hz - 460V/3ph/60Hz The all-in-one solution for your business need Combining cutting-edge

More information

Air-Side Economizer Cycles Applied to the Rejection of Data Center Heat

Air-Side Economizer Cycles Applied to the Rejection of Data Center Heat Air-Side Economizer Cycles Applied to the Rejection of Data Center Heat B. Keith Dunnavant, P.E. Manager, Data Center Cooling Solutions Munters Corporation Founded in 1955 Manufacturing & Sales Locations

More information

Liebert AFC from 500 to 1450 kw. The Adiabatic Freecooling Solution with Top-Tier Availability

Liebert AFC from 500 to 1450 kw. The Adiabatic Freecooling Solution with Top-Tier Availability Liebert AFC from 500 to 1450 kw The Adiabatic Freecooling Solution with Top-Tier Availability Liebert AFC, the Ideal Adiabatic Chilled Water Solution for Top-Tier Data Centers Emerson Network Power delivers

More information

HIGH DENSITY DATACOM INTEGRATED COOLING SYSTEM.

HIGH DENSITY DATACOM INTEGRATED COOLING SYSTEM. HIGH DENSITY DATACOM INTEGRATED COOLING SYSTEM. SYSTEM LOGICA is the most advanced alternative to the problem of cooling of server rooms MONTAIR is the trademark which represents excellence on the market

More information

Precision Cooling for Business-Critical Continuity. Liebert HPC-S. Designed for the Efficient Cooling of Small Data Centers

Precision Cooling for Business-Critical Continuity. Liebert HPC-S. Designed for the Efficient Cooling of Small Data Centers Precision Cooling for Business-Critical Continuity Liebert HPC-S Designed for the Efficient Cooling of Small Data Centers Liebert HPC-S: Enhanced Efficiency Freecooling Chiller Higher energy costs, limited

More information

Thermal management. Thermal management

Thermal management. Thermal management Thermal management Thermal management Managing thermal loads is a major challenge for all Data Centre operators. Effecting proper control of the thermal environment drives energy consumption and ultimately

More information

Case Study: The design of a modern data centre Jeffrey Brindle Technical Director, HP Critical Facilities Services

Case Study: The design of a modern data centre Jeffrey Brindle Technical Director, HP Critical Facilities Services Case Study: The design of a modern data centre Jeffrey Brindle Technical Director, HP Critical Facilities Services EMEA Roll-out 2 Main Mirror UK Swindon/Newbury area (15,000m 2 ) Germany Russelsheim(main)/

More information

Liquid Cooling Package LCP Cooling Systems

Liquid Cooling Package LCP Cooling Systems Liquid Cooling Package LCP Cooling Systems 2 Rittal LCP Rittal The System. The whole is more than the sum of its parts. The same is true of Rittal The System. With this in mind, we have bundled our innovative

More information

Cooling. Highly efficient cooling products for any IT application. For More Information: (866) DATA CENTER SOLUTIONS

Cooling. Highly efficient cooling products for any IT application. For More Information: (866) DATA CENTER SOLUTIONS Cooling > Highly efficient cooling products for any IT application. DATA CENTER SOLUTIONS For More Information: (866) 787-3271 Sales@PTSdcs.com End-to-End Cooling Solutions from the Closet to the Data

More information

Munters Data Center Cooling Solutions. Simon Young & Craig MacFadyen Munters Data Centers

Munters Data Center Cooling Solutions. Simon Young & Craig MacFadyen Munters Data Centers Munters Data Center Cooling Solutions 1 Simon Young & Craig MacFadyen Munters Data Centers Introduction Vision Your Perfect Climate Mission Munters' mission is to be a globally leading supplier of energy

More information

Liebert DSE Precision Cooling System Industry-best efficiency. Increased capacity. Ensured availability. EFFICIENCY. CAPACITY. AVAILABILITY.

Liebert DSE Precision Cooling System Industry-best efficiency. Increased capacity. Ensured availability. EFFICIENCY. CAPACITY. AVAILABILITY. Liebert DSE Precision Cooling System Industry-best efficiency. Increased capacity. Ensured availability. EFFICIENCY. CAPACITY. AVAILABILITY. Liebert DSE High-Efficiency Precision Cooling System Room-Based

More information

Airedale International Air Conditioning Limited. Leeds Road, Rawdon Leeds, LS19 6JY, England

Airedale International Air Conditioning Limited. Leeds Road, Rawdon Leeds, LS19 6JY, England > For the latest information on our products please visit : www.airedale.com > Please refer to the technical manuals for more detailed information Your nearest Airedale distributor is: ISO 14001 EMS52086

More information

Trane Cold Generator TM. Scroll Chillers. Comfort and Process Cooling Solutions

Trane Cold Generator TM. Scroll Chillers. Comfort and Process Cooling Solutions Trane Cold Generator TM Scroll Chillers Comfort and Process Cooling Solutions Advanced Cooling Solutions The Trane Cold Generator family of scroll chillers is a broad line of comfort and process cooling

More information

M+W Group s Visionary Delta Datacenter

M+W Group s Visionary Delta Datacenter Region Central Europe M+W Germany GmbH A Company of the M+W Group 23 rd April 2014 M+W Group s Visionary Delta Datacenter IKS Data Center Design & Engineering Conference 2014 Moscow, Russia M+W Group at

More information

Efficiency of Data Center cooling

Efficiency of Data Center cooling Efficiency of Data Center cooling Comparison of data room layouts and cooling systems Bohumil Cimbal Product manager for Cooling Systems in CONTEG Company Objective Basic questions between investor and

More information

GP SERIES Packaged Chillers

GP SERIES Packaged Chillers Blending Conveying Drying Process Cooling Heat Transfer Size Reduction GP SERIES Packaged Chillers Comprehensive Flexible Versatile Compact unitary designs available in a variety of configurations from

More information

Blue e+ chillers with the principle

Blue e+ chillers with the principle Blue e+ chillers with the principle Blue e+ chillers The world s most efficient range of chillers. The principle: Efficient Energy savings of up to 70% thanks to DC inverter technology Flexible Worldwide

More information

Liebert PDX. The Cooling Solution for Small and Medium Data Centers. Digital Scroll. Part Load. Competent Partner Efficiency

Liebert PDX. The Cooling Solution for Small and Medium Data Centers. Digital Scroll. Part Load. Competent Partner Efficiency Liebert PDX The Cooling Solution for Small and Medium Data Centers Competent Partner Efficiency Digital Scroll Part Load icom Control TCO Optimization Integrated Solution Operational Cost Reduction New

More information

Introducing the Heat Wheel to the Data Center

Introducing the Heat Wheel to the Data Center Introducing the Heat Wheel to the Data Center Robert (Dr. Bob) Sullivan, Ph.D. Data Center Infrastructure Specialist KyotoCooling International Critical Facilities Round Table 1 A New Free Cooling Technique

More information

InPac 600 Series Fully configurable severe duty and explosion proof HVAC and building pressurization systems 2 5 ton ::

InPac 600 Series Fully configurable severe duty and explosion proof HVAC and building pressurization systems 2 5 ton :: Fully configurable severe duty and explosion proof HVAC and building pressurization systems 2 5 ton :: 7.0 17.5 kw Features and Benefits Built for critical applications Two-stages of cooling allows for

More information

Liquid Cooling Package LCP Cooling Systems

Liquid Cooling Package LCP Cooling Systems Liquid Cooling Package LCP Cooling Systems 2 Rittal LCP The whole is more than the sum of its parts. The same is true of Rittal The System. With this in mind, we have bundled our innovative enclosure,

More information

DESCRIPTION OF MODBUS CONNECTION

DESCRIPTION OF MODBUS CONNECTION DESCRIPTION OF MODBUS CONNECTION MODBUS CONNECTION There is a possibility to control Air Handling Unit (AHU) from external management system (BMS), which work with MODBUS data processing. For MODBUS connection

More information

Liebert AFC from 500 to 1450 kw. The Adiabatic Freecooling Solution with Top-Tier Availability

Liebert AFC from 500 to 1450 kw. The Adiabatic Freecooling Solution with Top-Tier Availability Liebert AFC from 500 to 1450 kw The Adiabatic Freecooling Solution with Top-Tier Availability Liebert AFC, the Ideal Adiabatic Chilled Water Solution for Top-Tier Data Centers Emerson Network Power delivers

More information

Liebert. DCL up to 35 kw. Modular Rack Cooling

Liebert. DCL up to 35 kw. Modular Rack Cooling Liebert DCL up to 35 kw Modular Rack Cooling LIEBERT DCL up to 35 kw Vertiv Vertiv designs, builds and services mission critical technologies that enable the vital applications for data centers, communication

More information

IT COOLING AIR CONDITIONERS FOR HIGH DENSITY RACKS AND BLADE SERVERS. RACK COOLING SOLUTIONS FOR HIGH DENSITY RACK MANAGEMENT, FROM 4 TO 75 kw

IT COOLING AIR CONDITIONERS FOR HIGH DENSITY RACKS AND BLADE SERVERS. RACK COOLING SOLUTIONS FOR HIGH DENSITY RACK MANAGEMENT, FROM 4 TO 75 kw IT COOLING AIR CONDITIONERS FOR HIGH DENSITY RACKS AND BLADE SERVERS RACK COOLING SOLUTIONS FOR HIGH DENSITY RACK MANAGEMENT, FROM 4 TO 75 kw IT COOLING AIR CONDITIONERS FOR HIGH DENSITY RACKS AND BLADE

More information

Liebert. AFC from 500 to 1450 kw. The Adiabatic Freecooling Solution with Top-Tier Availability CERTIFIED HVAC-HYGIENE.

Liebert. AFC from 500 to 1450 kw. The Adiabatic Freecooling Solution with Top-Tier Availability CERTIFIED HVAC-HYGIENE. Liebert AFC from 500 to 1450 kw The Adiabatic Freecooling Solution with Top-Tier Availability CERTIFIED HVAC-HYGIENE Conformity of the device Vertiv Liebert AFC with the hygiene requirements of the guideline

More information

Liebert. DCL up to 35 kw. Modular Rack Cooling

Liebert. DCL up to 35 kw. Modular Rack Cooling Liebert DCL up to 35 kw Modular Rack Cooling LIEBERT DCL up to 35 kw Vertiv Vertiv designs, builds and services mission critical technologies that enable the vital applications for data centers, communication

More information

Liebert DM. High Performance, Sensible Cooling for Small Computer Rooms and Network Closets

Liebert DM. High Performance, Sensible Cooling for Small Computer Rooms and Network Closets Liebert DM High Performance, Sensible Cooling for Small Computer Rooms and Network Closets Emerson Network Power, a business of Emerson (NYSE: EMR), is a worldwide leader in infrastructure solutions across

More information

How Green can you go?

How Green can you go? ASHRAE 90.1 2010 It s out..and should be our code in 3 years Work on sealing and testing building envelope, commissioning Cool Roofs..hey were already doing that Extensive Controls enhancements Equipment

More information

SmoothAir Modular Precision Cooling

SmoothAir Modular Precision Cooling TM SmoothAir Modular Precision Cooling ODM/OEM/Customization+ Specialist Support+ Modular Precision Cooling for Smart, Reliable and Green MDC Solution Why Choose Us Products Support Customization Products

More information

Precision Cooling. Precision Cooling Advantages

Precision Cooling. Precision Cooling Advantages Precision Cooling Today s computing technologies compound conventional cooling problems. Blade servers, communications switches and other electronics are being packed into tighter and tighter spaces. Computing

More information

INNOVATE DESIGN APPLY.

INNOVATE DESIGN APPLY. INNOVATE DESIGN APPLY By A whole new cooling experience The Motivair ChilledDoor Rack Cooling System targets the critical cooling requirements of today s modern server rack designs. As technology continues

More information

IXcellerate Moscow One Datacentre - Phase 1 & 2 Overview

IXcellerate Moscow One Datacentre - Phase 1 & 2 Overview Contents 1. Document Purpose... 2 2. Facility Overview... 2 2.1 Technical Space... 2 2.2 Load Density... 2 2.3 Resilience... 2 2.4 Engineering Plant Maintenance & Service Restoration... 3 3. Engineering

More information

Installation Service. 1.0 Executive Summary. Factory Trained Technician Train Customer Support Staff On Basic Operation Of The Equipment

Installation Service. 1.0 Executive Summary. Factory Trained Technician Train Customer Support Staff On Basic Operation Of The Equipment Installation Service Statement of Work Start-up Service for Cooling Start-up - 1 - Service for Cooling Service 1.0 Executive Summary Table of Contents 1.0 Executive Summary 2.0 Features & Benefits 3.0

More information

INNOVATE DESIGN APPLY.

INNOVATE DESIGN APPLY. INNOVATE DESIGN APPLY By A whole new cooling experience The Motivair ChilledDoor Rack Cooling System targets the critical cooling requirements of today s modern server rack designs. As technology continues

More information

Trailblazer AGZ-E air-cooled scroll chillers

Trailblazer AGZ-E air-cooled scroll chillers Trailblazer AGZ-E air-cooled scroll chillers 30 to 240 tons with Variable Speed Condenser Fan Technology The right features, the right value, right now Intelligent Equipment AGZ-E 30 to 161 RapidRestore

More information

VARIABLE REFRIGERANT FLOW SYSTEMS HITACHI SMARTFLEX VRF GEN II FLEXIBILITY, PERFORMANCE AND CONTROL

VARIABLE REFRIGERANT FLOW SYSTEMS HITACHI SMARTFLEX VRF GEN II FLEXIBILITY, PERFORMANCE AND CONTROL HITACHI SMARTFLEX VRF GEN II FLEXIBILITY, PERFORMANCE AND CONTROL Expanding the possibilities STATE-OF-THE-ART DESIGN TAKES PERFORMANCE TO NEW LEVELS Our re-engineered Outdoor Units boast an extended operating

More information

09LD/GD. Air-Cooled Condensers/Air-Cooled Fluid Coolers. Nominal cooling capacity kw 09LD/GD 09GD

09LD/GD. Air-Cooled Condensers/Air-Cooled Fluid Coolers. Nominal cooling capacity kw 09LD/GD 09GD Air-Cooled Condensers/Air-Cooled Fluid Coolers 09LD/GD 09GD 09LD/GD Nominal cooling capacity 281-987 kw The 09LD air-cooled condensers are designed for refrigeration plants where a halogenated hydrocarbon,

More information

RiMatrix S Make easy.

RiMatrix S Make easy. RiMatrix S Make easy. 2 RiMatrix S Rittal The System. The whole is more than the sum of its parts. The same is true of Rittal The System. With this in mind, we have bundled our innovative enclosure, power

More information

CONTENTS CONTROLLERS room controllers room units control units PRODUAL 3 CATALOGUE

CONTENTS CONTROLLERS room controllers room units control units PRODUAL 3 CATALOGUE Catalogue 207 CONTENTS CONTROLLERS... 4 room controllers... 5 room units... 29 control units... 24 PRODUAL 3 CATALOGUE T U R KU I C T C ON T R OL L E R S Multifunctional controllers for optimal performance

More information

FEATURES AND BENEFITS. Installation and operation. Controller

FEATURES AND BENEFITS. Installation and operation. Controller DFC 350 & 450 DISPLACEMENT FREE COOLING Function The Dantherm Displacement Free Cooling (DFC) unit is a slim, passive cooling solution designed to remove excess heat from rooms with sensitive equipment.

More information

ENCLOSURE HEAT DISSIPATION

ENCLOSURE HEAT DISSIPATION ENCLOSURE HEAT DISSIPATION DATA CENTER SOLUTIONS A White Paper by Great Lakes Case & Cabinet Company www.werackyourworld.com 814.734.7303 Page 2 Introduction Dangerous heat levels inside an enclosure threaten

More information

DATA CENTER AIR HANDLING COOLING SOLUTIONS

DATA CENTER AIR HANDLING COOLING SOLUTIONS DATA CENTER AIR HANDLING COOLING SOLUTIONS World-class performance and reliability from YORK As data storage and protection needs grow, so can costs and complexity. That s why having the right partner

More information

Digital Realty Data Center Solutions Digital Chicago Datacampus Franklin Park, Illinois Owner: Digital Realty Trust Engineer of Record: ESD Architect

Digital Realty Data Center Solutions Digital Chicago Datacampus Franklin Park, Illinois Owner: Digital Realty Trust Engineer of Record: ESD Architect Digital Realty Data Center Solutions Digital Chicago Datacampus Franklin Park, Illinois Owner: Digital Realty Trust Engineer of Record: ESD Architect of Record: SPARCH Project Overview The project is located

More information

18 th National Award for Excellence in Energy Management. July 27, 2017

18 th National Award for Excellence in Energy Management. July 27, 2017 18 th National Award for Excellence in Energy Management July 27, 2017 ICICI Bank, Data Centre, August Hyderabad 30 & 31, 2017 ICICI Bank - Revolution in Digital Banking Over 100,000 Digital POS in 4 months

More information

CASE STUDIES ENERGY EFFICIENT DATA CENTRES

CASE STUDIES ENERGY EFFICIENT DATA CENTRES CASE STUDIES ENERGY EFFICIENT DATA CENTRES Testimonials We are delighted that our PUE is less than 1.15 during the summer, achieving what we felt was a very ambitious programme of work with a targeted

More information

Data Centre Stockholm II, Sweden Flexible, advanced and efficient by design.

Data Centre Stockholm II, Sweden Flexible, advanced and efficient by design. Data Centre Stockholm II, Sweden Flexible, advanced and efficient by design. TelecityGroup Kvastvägen 25-29 128 62 Sköndal Stockholm Sweden Tel: +46 (0) 8 799 3800 se.info@telecity.com www.telecitygroup.se

More information

TWO FINANCIAL IMPACT STUDIES. Seal IT Equipment Cabinets for Significant Annual Cost Savings and Simple Payback in a Few Short Months

TWO FINANCIAL IMPACT STUDIES. Seal IT Equipment Cabinets for Significant Annual Cost Savings and Simple Payback in a Few Short Months TWO FINANCIAL IMPACT STUDIES Seal IT Equipment Cabinets for Significant Annual Cost Savings and Simple Payback in a Few Short Months TWO FINANCIAL IMPACT STUDIES Seal IT Equipment Cabinets for Significant

More information

DATACENTER CAMPUS FRANKFURT. Plan for Every Second

DATACENTER CAMPUS FRANKFURT. Plan for Every Second DATACENTER CAMPUS FRANKFURT Plan for Every Second We Give All Our Energy and Dedication to Create Safe Environments by Making Risks Manageable Contents Your Goals 2 Compound and Buildings 4 Security 6

More information

ZTE ZXCR Series DX In-Row Air Conditioning Product Description

ZTE ZXCR Series DX In-Row Air Conditioning Product Description ZTE ZXCR Series DX In-Row Air Conditioning Product Description Requirements & Challenges Due to the rapid development of telecommunication technology, the related IT equipment s power consumption is increase

More information

How to Increase Data Center Efficiency

How to Increase Data Center Efficiency How to Increase Data Center Efficiency Shivani Shukla Potkar Product Marketing Manager Pentair Electronics Protection High cooling efficiency & and reduced power consumption enhances the balance between

More information