1 Functional Requirements for Advanced Distribution Automation with DER (ADA-DER) 1 Descriptions of Function Function Name Function ID Brief Description Narrative Overview of ADA Functions Overview Diagrams Overall Preconditions Overview of Post Conditions Distribution Operation Modeling and Analysis () Modeling Transmission/Sub-Transmission Immediately Adjacent to Distribution Circuits Modeling Distribution Circuit Connectivity Modeling Distribution Nodal Loads Modeling Distribution Circuit Facilities Distribution Power Flow Evaluation of Transfer Capacity Power Quality Analysis Loss Analysis Fault Analysis Evaluation of Operating Conditions Fault Location, Isolation and Service Restoration (FLIR) Volume II D29-i Final Release

2 Fault Location Fault Isolation and Service Restoration Contingency Analysis (CA) Multi-level Feeder Reconfiguration (MFR) Relay Protection Re-coordination (RPR) Voltage and Var Control (VVC) Pre-arming of Remedial Action Schemes (RAS) Coordination of Emergency Actions Coordination of Restorative Actions Intelligent Alarm Processing Actor (Stakeholder) Roles exchanged Activities/Services Contracts/Regulations Step by Step Analysis of Function Distribution Operation Modeling and Analysis () Function Preconditions and Assumptions Steps Normal Sequence Data Conversion and Validation No Events Event Run Scheduled Run Study/Look-ahead Mode Volume II D29-ii Final Release

3 2.1.3 Steps Alternative / Exception Sequences Post-conditions and Significant Results Diagrams Fault Location, Isolation and Service Restoration (FLIR) Function FLIR Preconditions and Assumptions FLIR Steps Normal Sequence FLIR First Fault with Only Manual Switches FLIR Second Fault (Related to First Fault which is Not Resolved Yet) with Only Manual Switches FLIR Fault with Remotely-Controlled and Manual Switches FLIR Fault with Remotely-Controlled and Manual Switches and Distributed Intelligence (DIS) FLIR Fault with DER Connected to Healthy Section Post-conditions and Significant Results Diagrams Volt/Var Control (VVC) VVC Preconditions and Assumptions VVC Steps Normal Sequence VVC Function During Scheduled Run VVC Function During Event Run VVC Function Participation in Severe Emergency in Bulk Power with Intentional Islands Post-conditions and Significant Results Diagrams Architectural Issues in Interactions Current Implementation Status Volume II D29-iii Final Release

4 3 Auxiliary Issues References and Contacts Prior Published Work of UCI and UCI s Personnel Action Item List Revision History Volume II D29-iv Final Release

5 Functional Requirements for Advanced Distribution Automation with DER (ADA-DER) Advanced Distribution Automation with DER (ADA-DER) Function 1 Descriptions of Function Use Case Description 1 All prior work (intellectual property of the company or individual) or proprietary (non-publicly available) work should be so noted. 1.1 Function Name Function The (further referred as Function) is named Advanced Distribution Automation (ADA) Function. 1.2 Function ID identification number of the L-3,L-3.1,L-3.2,L-3.3,L-3.4,L-3.5,L-3.6,L-3.8,L Brief Description Describe briefly the scope, objectives, and rationale of the Function. Objective: The objective of Advanced Distribution Automation Function is to enhance the reliability of power system service, power quality, and power system efficiency, by automating the following three processes of distribution operation control: data preparation in near-real-time; optimal decision-making; and the control of distribution operations in coordination with transmission and generation systems operations. Scope: The AdvancedDistributionAutomation Function performs a) data gathering, along with data consistency checking and correcting; b) integrity checking of the distribution power system model; c) periodic and event-driven system modeling and analysis; d) current and predictive alarming; e) contingency analysis; f) coordinated volt/var optimization: g) fault location, isolation, and service restoration; h) multi-level feeder reconfiguration; i) pre-arming of RAS and coordination of emergency actions in distribution; j) pre-arming of restoration schemes and coordination of restorative actions in distribution, and k) logging and reporting. These processes are performed through direct interfaces with different databases and systems, (EMS, OMS, CIS, MOS, SCADA, 1 Background information includes prior UCI work Volume II D29-1 Final Release

6 AM/FM/GIS, AMS and WMS), comprehensive near real-time simulations of operating conditions, near real-time predictive optimization, and actual real-time control of distribution operations. Rationale: By meeting its objectives in near-real time, the Function makes a significant contribution to improving the power system operations through automation, which cannot be achieved using existing operational methods. Status: The methodology and specification of the Function for current power system conditions have been developed, and prototype (pilot) and system-wide project in several North-American utilities have been implemented by Utility Consulting International and its client utilities prior to the project. 1.4 Narrative A complete narrative of the Function from a Domain Expert s point of view, describing what occurs when, why, how, and under what conditions. This will be a separate document, but will act as the basis for identifying the Steps in Section Overview of ADA Functions The AdvancedDistributionAutomation Function operates via the following closely coordinated applications: Overview Diagrams Volume II D29-2 Final Release

7 1 SCADA/EMS/ OPERATOR Status 2 change Objective change Lockout Fault ind. Com. change Transmission overload Transmission Volt violation Energy Cost change Energy 2 Cost change 4 7 WACS Distribution Operation Model & Analysis Pseudomeasurements 4 Integrity check Volt violations 1 Overload Controllable kw& kvar 1 Bus load limits 1 Losses 8 Volt quality 8 Look-Ahead Contingency Analysis Predicted 7 overload 1 Contingency Power-flow 8 Predicted Unserved kw 8 Dropped sections 8 Deenergized customers 8 Emergency overload 8 Emergency Under-voltage 8 Restoration actions 5 8 Volt & Var Control Settings Of volt control 1 Status of capacitors 1 Expected results 1 Update model 2 Expected Results, if if overload Spare Spare Spare 7 Fault Location, Isolation & Restoration Switching orders Closed- loop control 1 Spare Spare Spare Spare Spare Spare Relay protection recoordination 1 7 Reconfiguration solutions 1 8 Logs, Reports, Other users Fig. 1 Coordination of ADA applications is accomplished through internal interfaces within the ADA and through the feedback from the power system. 9 Pre-arming of of (RAS) Coordination of of emergency actions Coordination of of restorative actions 11 4 Intelligent Alarm Processing 12 Volume II D29-3 Final Release

8 Fig. 2 {Not yet coordinated with the Use Case description} Volume II D29-4 Final Release

9 Overall Preconditions Actor//Contract DistributionSCADA AM_FM_GISDatabase CIS database SCADA/EnergyManagement ConversionValidationFunction ADADistributionOperationModeling and Analysis () AdvancedDistributionAutomation: Fault Location Isolation and Service Restoration (FLIR) AdvancedDistributionAutomation: Contingency Analysis (CA) AdvancedDistributionAutomation: Multi-level Feeder Reconfiguration (MFR) AdvancedDistributionAutomation: Relay Protection Re-coordination (RPR) Preconditions or Assumptions DistributionSCADA database is updated via remote monitoring and operator inputs. Required scope, speed, and accuracy of real-time measurements are provided, supervisory and closed-loop control is supported. AM/FM system contains the geographical information of the distribution power system circuit connectivity, as well as the parameters describing the power system facilities. Conceptually, the AM_FM_GISDatabase can contain transmission connectivity and facility data and relevant to distribution operations customer-related data. CIS contains load data for customers that is estimated for each nodal location on a feeder, based on billing data and time-of-day and day-of week load shapes for different load categories. EnergyManagement system contains the transmission power system model, and can provide the transmission connectivity information for facilities in the vicinity of the distribution power system facilities and with outputs from other EnergyManagement applications The C&V uses standard interface between AM_FM_GISDatabase and converts and validates information about incremental changes implemented in the field. Preconditions: DistributionSCADA with several IEDs along distribution feeders, reporting statuses of remotely controlled switches and analogs including Amps, kw, kvar, and kv. s ability for updating the SCADA database with statuses of switches not monitored remotely. Substation SCADA with analogs and statuses from CBs exists. EnergyManagement is interfaced with AdvancedDistributionAutomation. AdvancedDistributionAutomation database is updated with the latest AM/FM/GIS/CIS data and operators input. The options for performance are selected Fault Location Preconditions: DistributionSCADA with fault detectors, Distribution Operation Model and Analysis with fault analysis, fault location relays (schemes) including high impedance relays and Some Distributed Intelligence schemes and Trouble call system exist. Fault Isolation and Service Restoration Preconditions: DistributionSCADA with ability to control a defined number of switching devices, Fault Location, Distribution Operation Model and Analysis, Voltage and Var Control for adjusting voltage and var after reconfiguration. Supervisory and closed-loop control of switches are available. Some Distributed Intelligence schemes exist.. The AdvancedDistributionAutomation database is updated including the real-time state of communication with IEDs and the availability of switch control. The options for CA are selected. Preconditions: DistributionSCADA with ability to control a definite number of switching devices, Distribution Operation Model and Analysis, Voltage and Var Control for adjusting voltage and var after reconfiguration. Supervisory and closed-loop control of switches are available. The options for the application are selected. The settings and modes of operation of the switching devices are reported by SCADA and can be controlled via SCADA. Volume II D29-5 Final Release

10 Actor//Contract ADAVVCController AdvancedDistributionAutomation: Prearming of Remedial Action Schemes (RAS) ADAEmergencyCoordination (CEA) ADARestorationCoordination (CRA) AdvancedDistributionAutomation: Intelligent Alarm Processing (IAP) Distributed Intelligence Schemes LoadManagmentDevice (LMS) UFLS: Under-Frequency Load Shedding Schemes UVLS: Under-Voltage Load Shedding Schemes SLS: Special Load Shedding Schemes Preconditions or Assumptions Preconditions: DistributionSCADA, Distribution Operation Model and Analysis, capability to monitor and control all or a portion of voltage, capacitor, DER, and power electronic controllers in closedloop mode exist. Preconditions: AdvancedDistributionAutomation is interfaced with the RAS schemes with the capability of changing the priorities of RAS actions and settings Preconditions: AdvancedDistributionAutomation is interfaced with EnergyManagement and receives critical statuses, measurements, preventive and corrective actions Preconditions: AdvancedDistributionAutomation is interfaced with EnergyManagement and receives information about restoration conditions Preconditions: AdvancedDistributionAutomation receives synchronized (time stamped) status and analog data from IEDs including uploads from event recorders. Preconditions: Distribution Intelligence Schemes are equipped with pear-to-pear communications and interfaced with AdvancedDistributionAutomation for pre-arming and coordination. Preconditions: LMS is interfaced with AdvancedDistributionAutomation, can be prioritized by AdvancedDistributionAutomation Preconditions: UFLS is interfaced with AdvancedDistributionAutomation, can be prioritized and prearmed by AdvancedDistributionAutomation Preconditions: UVLS is interfaced with AdvancedDistributionAutomation, can be prioritized and pre-armed by AdvancedDistributionAutomation Preconditions: SLS is interfaced with AdvancedDistributionAutomation, can be prioritized and prearmed by AdvancedDistributionAutomation Overview of Post Conditions Actor/Activity Post-conditions Description and Results SCADA Distribution Works continuously ADADistributionOperationModel All details of the real-time unbalanced distribution power flow are available for engineering ing and Analysis review. The operator is provided with the summary of analysis. Other applications receive the pseudo-measurements for each distribution system element down to load centers in the secondaries practically replacing hundreds thousands of measurements. The database is updated via real-time topology data. The observability of distribution operating conditions is increased multifold. The dynamic voltage limits are calculated; aggregated load models for EnergyManagement are provided; dispatchable load is estimated. AdvancedDistributionAutomation Faulted section is identified. A solution for an optimal isolation of faulted portions of Volume II D29-6 Final Release

11 Actor/Activity : Fault Location Isolation and Service Restoration AdvancedDistributionAutomation : Contingency Analysis AdvancedDistributionAutomation : Multi-level Feeder Reconfiguration AdvancedDistributionAutomation : Relay Protection Recoordination AdvancedDistributionAutomation : Voltage and Var Control Post-conditions Description and Results distribution feeder and restoration of services to healthy portions is provided to the operator; closed-loop execution of switching orders is available; Outage time for the majority of customers is reduced to several minutes. Results of contingency analysis of the relevant portion of distribution system are provided for engineering review and for use by other applications. Expected overload is determined; solutions are recommended. Planned outages are better prepared. Optimal selection of feeder(s) connectivity for a given objective is provided to the operator; Closed-loop execution is available. Reliability is increased, losses are reduced, voltages are improved; room for voltage optimization is increased; utilization of distribution facilities is enhanced; Relay protection settings adjusted to the real-time conditions based on the preset rules are sent to relevant protective relaying. The relay coordination is adaptive to the real-time condition; the reliability of service is increased. Optimal voltage controller and DER controller settings and capacitor statuses for a given objective(s) are sent to respective devices. The power quality is enhanced; The distribution facilities are better utilized; the transmission and generation systems is better supported by volt and vars; the load management is less intrusive; the customers pay smaller bills Distribution Operation Modeling and Analysis () This application is based on a real-time unbalanced distribution power flow for dynamically changing distribution operating conditions. It analyzes the results of the power flow simulations and provides the operator with the summary of this analysis. It further provides other applications with pseudo-measurements for each distribution system element from within substations down to load centers in the secondaries. The model is kept up-to-date by real-time updates of topology, facilities parameters, load, and relevant components of the transmission system. The Distribution Operation Modeling and Analysis supports three modes of operation: 1. Real-time mode, which reflects present conditions in the power system. 2. Look-ahead mode, which reflects conditions expected in the near future (from one hour to one week ahead) 3. Study mode, which provides the capability of performing the what if studies. The key sub-s performed by the application are as follows: Volume II D29-7 Final Release

12 Modeling Transmission/Sub-Transmission Immediately Adjacent to Distribution Circuits This sub- provides topology and electrical characteristics of those substation transformers and transmission/sub-transmission portions of the system, where loading and voltage levels significantly depend on the operating conditions of the particular portion of the distribution system. The model also includes substation transformers and transmission/sub-transmission lines with load and voltage limits that should be respected by the application Modeling Distribution Circuit Connectivity This sub- provides a topological model of distribution circuits, starting from the distribution side of the substation transformer and ending at the equivalent load center on the secondary of each distribution transformer. A topological consistency check is performed every time connectivity changes. The model input comes from SCADA/EnergyManagement, DistributionSCADA, from field crews, from DISCO operator, from AM/FM/GIS, WorkManagement, and OutageManagement databases, and engineers. Data Management Issues between AM/FM/GIS and AdvancedDistributionAutomation Distribution Connectivity Database Standard interfaces between different AM_FM_GISDatabases, data converters, and AdvancedDistributionAutomation database are not developed yet for practical use. The AM_FM_GISDatabases were not designed for real-time operational use. They lack many objects and attributes needed for AdvancedDistributionAutomation. The population of the databases is not supported by an interactive consistency check. The existing extractors of data and the converters into AdvancedDistributionAutomation databases do not determine all data errors. The AdvancedDistributionAutomation applications must conduct additional data consistency checking and data corrections before recommendations and controls are issued. Typically utility do not have established procedures for regular update of the AM_FM_GISDatabases by the operation and maintenance personnel. Therefore many changes implemented in the field remain unnoticed by the databases. Synchronization of the field state with the AdvancedDistributionAutomation database is a challenge in modern utilities. Data Management Issues between CIS and AM/FM/GIS and AdvancedDistributionAutomation Distribution Connectivity Database For the AdvancedDistributionAutomation applications, the AM/FM/GIS data must be associated with the corresponding customer information data from the CIS database. This data include billing data and description of the customer specifics, such as rate schedule, customer code, meter number, address, etc. The critical information is the billing data. This data is updated based on metering cycles (typically one month) and is not well synchronized. In order to synchronize billing data an automated meter reading system should be implemented. In order to update the AdvancedDistributionAutomation databases more frequently, which would increase the resolution of AdvancedDistributionAutomation s to individual distribution transformers and even customers, a high capacity communication system should be introduced to gather the data from hundreds of thousands of meters at the same time. Some of the modern procedures enabled by AutomatedMeterReadingDevice conflict with the needs of AdvancedDistributionAutomation model.an example is the consolidated bills, where the individual load data of distribution transformers located in different sites of the consolidated company becomes unavailable for the external to CIS world. Volume II D29-8 Final Release

13 Modeling Distribution Nodal Loads This sub- provides characteristics of real and reactive load connected to secondary side of distribution transformer or to primary distribution circuit in case of primary meter customers. These characteristics are sufficient to estimate kw and kvars at a distribution node at any given time and day and include the load shapes and load-to-voltage sensitivities (for real and reactive power) of various load categories. In real-time mode, the nodal loads are balanced with real-time measurements obtained from corresponding primary circuits. A validity check is applied to real-time measurements. The load model input comes from DistributionSCADA, from CIS supported by AutomatedMeterReadingDevice and linked with AM/FM/GIS, and weather forecast systems Modeling Distribution Circuit Facilities This sub- models the following distribution circuit facilities: 1. Overhead and underground line segments 2. Switching devices 3. Substation and distribution transformers, including step-down transformers 4. Station and feeder capacitors and their controllers 5. Feeder series reactors 6. Voltage regulators (single- and three-phase) and their controllers 7. LTC s and their controllers 8. Distribution generators and synchronous motors 9. Load equivalents for higher frequency models All facilities should be modeled with sufficient details to support the required accuracy of Distribution Operation Modeling and Analysis application Distribution Power Flow The sub- models the power flow including the impact of automatically controlled devices (i.e., LTCs, capacitor controllers, voltage regulators), and solves both radial and meshed networks, including those with multiple supply busses (i.e. having Distributed Energy Resources (DER) interconnected to the power system) Evaluation of Transfer Capacity This sub- estimates the available bi-directional transfer capacity for each designated tie switch. The determined transfer capacity is such that the loading of a tie switch does not lead to any voltage or current violations along the interconnected feeders. Volume II D29-9 Final Release

14 Power Quality Analysis This sub- performs the power quality analysis by: 1. Comparing (actual) measured and calculated voltages against the limits 2. Determining the portion of time the voltage or imbalance are outside the limits 3. Determining the amount of energy consumed during various voltage deviations and imbalance 4. Recording the time when voltage violations occur 5. Performing modeling of higher harmonics propagation and resonant conditions based on information available from the sources of harmonic distortion 6. Performing modeling of rapid voltage changes based on information available from the sources of voltage distortion The sub- provides the ability to estimate the expected voltage quality parameters during the planned changes in connectivity and reactive power compensation Loss Analysis This sub- bases its analysis on technical losses (e.g., conductor I 2 R losses, transformer load and no-load losses, and dielectric losses) calculated for different elements of the distribution system (e.g., per feeder or substation transformer). For the defined area, these losses are accumulated for a given time interval (month, quarter, year, etc.). They are further compared with the difference between the energy input (based on measurements) into the defined area and the total of relevant billed kwh (obtained from the database), normalized to the same time interval. The result of the comparison is an estimate of commercial losses (e.g., metering errors and theft) Fault Analysis This sub- calculates three-phase, line-to-line-to-ground and line-to-ground fault currents for each protection zone associated with feeder circuit breakers and field reclosers. The minimum fault current is compared with protection settings while the maximum fault current is compared with interrupting ratings of breakers and reclosers. If the requirements are not met, a message is generated for the operator Evaluation of Operating Conditions This sub- determines the difference between the existing substation bus voltage and the substation bus voltages limits. The sub- also estimates the available dispatchable real and reactive load obtainable via volt/var control. The operator or other applications can use this information for selective load reduction. The sub- provides aggregated operational parameters for the transmission buses to be used in transmission operation models. Volume II D29-10 Final Release

15 1.4.3 Fault Location, Isolation and Service Restoration (FLIR) This application detects the fault, determines the faulted section and the probable location of fault, and recommends an optimal isolation of the faulted portions of the distribution feeder and the procedures for the restoration of services to its healthy portions. The key sub-s performed by the application are as follows: Fault Location This sub- is initiated by SCADA inputs, such as lockouts, fault indications/location, and, also, by inputs from OutageManagement, and, in the future, by inputs from fault-predicting devices. It determines the specific protective device, which has cleared the sustained fault, identifies the de-energized sections, and estimates the probable place of the actual or the expected fault. It distinguishes faults cleared by controllable protective devices from those cleared by fuses, and identifies momentary outages and inrush/cold load pick-up currents Fault Isolation and Service Restoration This sub- supports three modes of operation: 1. Closed-loop mode, in which the sub- is initiated by the Fault location sub-. It generates a switching order (i.e., sequence) for the remotely controlled switching devices to isolate the faulted section, and restore service to the nonfaulted sections. The switching order is automatically executed via SCADA.. 2. Advisory mode, in which the sub- is initiated by the Fault location sub-. It generates a switching order for remotely- and manually-controlled switching devices to isolate the faulted section, and restore service to the non-faulted sections. The switching order is presented to operator for approval and execution 3. Study mode, in which the sub- is initiated by the user. It analyzes a saved case modified by the user, and generates a switching order under the operating conditions specified by the user. If during execution, there is change in connectivity, the sub- interrupts the execution and re-optimizes the solution based on new conditions. If during service restoration, there is another fault, the sub- runs again considering a new fault scenario. When work is completed, the sub- is instructed to generate a switching order for restoration of the normal configuration. The generated switching orders are based on considering the availability of remotely controlled switching devices, feeder paralleling, creation of islands supported by distributed energy resources, and on cold-load pickup currents Contingency Analysis (CA) This application performs an N-m contingency analysis in the relevant portion of distribution. The runs in the following manners: 1. Periodically Volume II D29-11 Final Release

16 2. By event (topology change, load change, availability of control change) 3. Study mode, in which the conditions are defined and the application is started by the user. The application informs the operator on the status of real-time distribution system reliability Multi-level Feeder Reconfiguration (MFR) This application recommends an optimal selection of feeder(s) connectivity for different objectives. It supports three modes of operation: 1. Closed-loop mode, in which the application is initiated by the Fault Location, Isolation and Service Restoration application, unable to restore service by simple (one-level) load transfer, to determine a switching order for the remotelycontrolled switching devices to restore service to the non-faulted sections by using multi-level load transfers.. 2. Advisory mode, in which the application is initiated by SCADA alarms triggered by overloads of substation transformer, segments of distribution circuits, or by detecting an overload, or by operator who would indicate the objective and the reconfiguration area. In this mode, the application recommends a switching order to the operator. 3. Study mode, in which the application is initiated and the conditions are defined by the user. The application performs a multi-level feeder reconfiguration to meet one of the following objectives: a. Optimally restore service to customers utilizing multiple alternative sources. The application meets this objective by operating as part of Fault Location, Isolation and Service Restoration. b. Optimally unload an overloaded segment. This objective is pursued if the application is triggered by the overload alarm from SCADA, or from the Distribution Operation Modeling and Analysis, or from Contingency analysis. These alarms are generated by overloads of substation transformer or segments of distribution circuits, or by operator demand. c. Minimize losses d. Minimize exposure to faults e. Equalize voltages The last three objectives are selected by engineer/planner Relay Protection Re-coordination (RPR) This application adjusts the relay protection settings to real-time conditions based on the preset rules. This is accomplished through analysis of relay protection settings and operational mode of switching devices (i.e., whether the switching device is in a switch or in a recloser mode), while considering the real-time connectivity, tagging, and weather conditions. The application is called to perform after feeder reconfiguration, and, in case, when conditions are changed and fuse saving is required. Volume II D29-12 Final Release

17 1.4.7 Voltage and Var Control (VVC) This application calculates the optimal settings of voltage controller of LTCs, voltage regulators, DERs, power electronic devices, and capacitor statuses optimizing the operations by either following different objectives at different times, or considering conflicting objectives together in a weighted manner. It supports three modes of operation: 1. Closed-loop mode, in which the application runs either periodically (e.g., every 15 min) or is triggered by an event (i.e., topology or objective change), based on real-time information. The application s recommendations are executed automatically via SCADA control commands. 2. Study mode, in which the application performs what-if studies, and provides recommended actions to the operator. 3. Look-ahead mode, in which conditions expected in the near future can be studied (from 1 hour through 1 week) by the operator. The following objectives, which could be preset for different times of the day and overwritten by operator if need to, are supported by the application: a. Minimize kwh consumption at voltages beyond given voltage quality limits (i.e., ensure standard voltages at customer terminals) b. Minimize feeder segment(s) overload c. Reduce load while respecting given voltage tolerance (normal and emergency) d. Conserve energy via voltage reduction e. Reduce or eliminate overload in transmission lines f. Reduce or eliminate voltage violations on transmission lines g. Provide reactive power support for transmission/distribution bus h. Provide spinning reserve support i. Minimize cost of energy j. Provide compatible combinations of above objectives If, during optimization or execution of the solution, the circuit status changes, the application is interrupted and solution is reoptimized. If, during execution, some operations are unsuccessful, solution is re-optimized without involving the maling devices. If some of the controllable devices are unavailable for remote control, solution does not involve these devices but takes into account their reaction to changes in operating conditions Pre-arming of Remedial Action Schemes (RAS) This application receives pre-arming signals from an upper level of control and changes the settings (tuning parameters) of distribution-side remedial action schemes (RAS), e.g., load-shedding schemes (a component of self-healing grid) or intentional DER islanding. Volume II D29-13 Final Release

18 1.4.9 Coordination of Emergency Actions This application recognizes the emergency situation based on changes of the operating conditions or on reaction of some RAS to operational changes and coordinates the objectives, modes of operation, and constraints of other AdvancedDistributionAutomation applications. For example, Under-frequency Load Shedding Schemes trigger emergency load reduction mode of volt/var control, or the under-frequency protection of DER triggers the pre-armed intentional islanding Coordination of Restorative Actions This application coordinates the restoration of services after the emergency conditions are eliminated. For example, AdvancedDistributionAutomation changes the order of feeder re-connection based on current customer priorities or inhibits return to normal voltage until there are disconnected feeders Intelligent Alarm Processing This application analyzes SCADA and -generated alarms and other rapid changes of the operational parameters in distribution and transmission and summarizes the multiple alarms into one massage defining the root cause of the alarms. For example, multiple sudden voltage violations along a distribution feeder and overloads of some feeder segments may be caused by a loss of DER excitation, or successful reclosing of a portion of feeder with loss of significant load may be caused by miss-coordination of the recloser settings and a particular fuse protecting a loaded lateral. 1.5 Actor (Stakeholder) Roles Describe all the people (their job), systems, databases, organizations, and devices involved in or affected by the Function (e.g. operators, system administrators, technicians, end users, service personnel, executives, SCADA system, real-time database, RTO, RTU, IED, power system). Typically, these actors are logically grouped by organization or al boundaries or just for collaboration purpose of this use case. We need to identify these groupings and their relevant roles and understand the constituency. The same actor could play different roles in different Functions, but only one role in one Function. If the same actor (e.g. the same person) does play multiple roles in one Function, list these different actor-roles as separate rows. Grouping (Community), Group Description Actor Name Actor Type (person, device, system Actor Description etc.) DisCos Person in charge of distribution operations during the shift DistributionSC ADA Distribution Supervisory Control and Data Acquisition Volume II D29-14 Final Release

19 Grouping (Community), Group Description Actor Name ConversionVali dationfunction ADADataChec ker ADADispatchin g ADATopology Update ADADistributio noperationmod el and Analysis () ADAVVCContr oller (VVC) AdvancedDistri butionautomati on: Fault location AdvancedDistri butionautomati on: Fault Isolation and Service Restoration (FLIR) AdvancedDistri butionautomati Actor Type (person, device, system etc.) Actor Description The C&V uses standard interface between AM_FM_GISDatabase and converts and validates information about incremental changes implemented in the field. The ADADataChecker monitors data entered into SCADA database and detects changes. When pre-defined changes are detected, the data checker triggers the ADADispatching. The ADADispatching starts corresponding AdvancedDistributionAutomation s based on pre-defined periodicity and events detected by the ADADataChecker. The ADATopologyUpdate updates the AdvancedDistributionAutomation topology model based on status changes detected by the data checker Calculation and Analysis of power flow/state estimation results AdvancedDistributionAutomation Voltage and Var Controller: Coordinated optimal control of voltage and var in distribution for different system-wide objectives Fault detection and location in distribution Isolation of faulted portions of distribution feeders and restoration of services to healthy portions Optimal selection of feeder connectivity for different objectives Volume II D29-15 Final Release

20 Grouping (Community), Group Description Actor Name on: Feeder Reconfiguration (FR) AdvancedDistri butionautomati on: Relay protection coordination AdvancedDistri butionautomati on: Prearming of Remedial Action Schemes (RAS) ADAEmergenc ycoordinations ystem ADARestoratio ncoordinations ystem AdvancedDistri butionautomati on: Intelligent Alarm Processing Actor Type (person, device, system etc.) Actor Description Adjustment of relay protection settings and operational modes of switches to provide a coordinated relay protection under real-time configuration Change of RAS settings in anticipation of a probable emergency Change of action priorities during the emergency state of the system Controlling the priorities of actions during the restorative state of the system Summarizing multiple alarms into one descriptive message. Volume II D29-16 Final Release

21 Grouping (Community), Group Description Actor Name Actor Type (person, device, system Actor Description etc.) LoadManagmen tdevice Controlling cycles of cyclic electric appliances (direct load control-dlc), interruptible and curtainable loads UFLS: Under- Shedding load based on frequency conditions Frequency Load Shedding Schemes UVLS: Under- Shedding load based on voltage conditions Voltage Load Shedding Schemes SLS: Special Shedding load based on specific operating conditions Load Shedding Schemes OutageManage Trouble call processing, troubleshoot crew dispatch ment WorkManagem Maintenance management in distribution ent FieldPersonnel Manual operations of field devices, repair and construction work FieldDevice Local intelligence for monitoring and control of automated devices in distribution, communicates with SCADA Distributed Intelligence Schemes Distributed Intelligence Schemes (DIS) - Performs operations in a localized distribution area based on local information and on data exchange between members of the group. Can communicate with SCADA. IEDs of DIS IEDs grouped in a Distributed Intelligence Scheme members DEROwner Maintenance and operations of DERs TransCOs Transmission of energy from generation to distribution within distributiondefined constraints/contracts EnergyManage Transmission and generation management system providing Volume II D29-17 Final Release

22 Grouping (Community), Group Description Actor Name Actor Type (person, device, system Actor Description etc.) ment AdvancedDistributionAutomation with transmission/generationrelated objectives, constraints, and input data RTO/ISO Wide-area power system control center providing high-level load management and other signals for DisCos MarketOperatio n Wide-area energy market management system providing high-level market signals for DisCos Major Major users of DisCo s services according to regulatory and contract rules customers CustomerServic Intermediary entity between DisCos and group of customers erepresentative AM_FM_GISD atabase Repository of distribution system assets, their relationships (connectivity), ownerships, and activities CustomerInfor Repository of customer information related to DisCos services mation AutomatedMete Automated Meter Reading interfaced with CIS and AM_FM_GISDatabases rreadingdevice AssetManagem Asset Management s interfaced with AM/FM/GIS ent Remedial Action Scheme Remedial Action Scheme performs local emergency operations based on local information, pre-armed settings and external signals. Can adapt to the changing local operating conditions. ADADatabase ADADatabase contains information on the current connectivity, operational parameters, electrical, economic and other relevant characteristics of the distribution power system ADAHistoricDa tabase ADATestDatab ase Environmental Volume II D29-18 Final Release

23 Grouping (Community), Actor Name daily data collector ITPersonnel LoadForecaster DMS SCADA Database Prearming of RAS schemes Fault isolation and service restoration sub AdvancedDistri butionautomati on load management s Actor Type (person, device, system etc.) Replicate this table for each logic group. Group Description Actor Description Including ADAVVCController 1.6 exchanged Describe any information exchanged in this template. Object Name See individual steps AM_FM_GISDatabases Object Description Nominal connectivity, electrical parameters, and geographic locations of distribution and transmission Volume II D29-19 Final Release

24 Object Name CIS database Outage management system DMS/SCADA database EnergyManagement/SCAD A Engineering databases Object Description facilities Customer information including billing data, customer types, links to distribution circuits Trouble call information, crew activity information. Real-time data from field IEDs and output of ADAapplications Real-time data from transmission field IEDs, output from EnergyManagement applications, information support from AdvancedDistributionAutomation applications Planning and design data for future facilities Volume II D29-20 Final Release

25 What Do We Need to Know to Optimally Control Distribution? G Volt Violation? Congestion? Insufficient Reserve? Real-time Prices? Stage of Power Alert? N.O. Status? Load? ~ DER state? R-T transfer capacity? Voltage imbalance? Harmonics? Voltage? Available? Voltage impact? Distribution and Transmission Facility Parameters and Customer Data Volume II D29-21 Final Release

26 ADA INFORMATION FLOW FOR COMPUTING APPLICATIONS Distributed Intelligence DER OMS WMS AMR DSM FR AM/FM/GIS/CIS SCADA/EMS SCADA-ADA-SCADA INTERFACES DISPATCHING ROUTINE VVO DOAN SR TM LM DPF FM DISPATCHER INTERFACE ENGINEER INTERFACE FltLct ENGINEERS VVO - VOLT/VAR CONTROL; DOAN - DISTRIBUTION OPERATINO ANALYSIS; FltLct- FAULT LOCATION; SR-ISOLATION AND SERVICE RESTORATION; DPF - DISTRIBUTION POWER FLOW; TM - TOPOLOGY MODEL; LM -LOAD MODEL; FM -FACILITY MODELS Volume II D29-22 Final Release

27 1.7 Activities/Services Describe or list the activities and services involved in this Function (in the context of this Function). An activity or service can be provided by a computer system, a set of applications, or manual procedures. These activities/services should be described at an appropriate level, with the understanding that sub-activities and services should be described if they are important for operational issues, automation needs, and implementation reasons. Other sub-activities/services could be left for later analysis. Activity/Service Name : AdvancedDistributionAutomationSyste m updates power system model and analyzes distribution operations FLIR: AdvancedDistributionAutomationSyste m performs fault location, fault isolation, and service restoration Activities/Services Provided Update of a) topology model b) facilities model c) load model d) relevant transmission model Analysis of real-time operating conditions using distribution power flow/state estimation Evaluation of system transfer capacity based on real-time measurements Issue of alarming/warning messages to the operator Generation of distribution operation reports and logs AdvancedDistributionAutomation indicates faults cleared by controllable protective devices by distinguishing between: a) faults cleared by fuses b) momentary outages c) inrush/cold load current AdvancedDistributionAutomation determines the faulted sections based on SCADA fault indications and protection lockout signals AdvancedDistributionAutomation estimates the probable fault locations based on SCADA fault current measurements and real-time fault analysis AdvancedDistributionAutomation determines the fault-clearing non-monitored protective device based on trouble call inputs and dynamic connectivity model AdvancedDistributionAutomation generates switching orders for fault isolation, service restoration, and return to normal (taking into account the availability of remotely controlled switching devices, feeder paralleling, and cold-load pickup): a) executes switching orders by using SCADA b) authorizes AdvancedDistributionAutomation application to execute switching orders in closed-loop mode AdvancedDistributionAutomation isolates the fault and restores service automatically by-passing the operator based on operator s authorization in advance AdvancedDistributionAutomation pre-arms Distributed Intelligence schemes Volume II D29-23 Final Release

28 Activity/Service Name MFR: AdvancedDistributionAutomationSyste m performs multi-level feeder reconfiguration for different objectives RPR: AdvancedDistributionAutomationSyste m performs relay protection recoordination VVC: AdvancedDistributionAutomationSyste m optimally controls volt/var by changing the states of voltage controllers, shunts, and distributed resources in a coordinated manner for different objectives under normal and emergency conditions CEA: Protection equipment performs system protection actions under emergency conditions IAP: Intelligent alarm processing SCADA: system performs disturbance monitoring Op Dispatch: s dispatch field crews to troubleshoot power system and customer power problems Activities/Services Provided AdvancedDistributionAutomation considers creation of islands supported by distributed resources for service restoration > Service restoration > Overload elimination > Loss minimization > Voltage balancing > Reliability improvement AdvancedDistributionAutomation changes relay protection settings and modes of operation of switching devices after feeder reconfiguration AdvancedDistributionAutomation changes relay protection setting in case of changed conditions for fuse saving Power quality improvement Overload elimination/reduction Load management Transmission operation support in accordance with T&D contracts Loss minimization in distribution and transmission Based on real-time distribution system connectivity, current composition of customers, and signals from an upper level of control, AdvancedDistributionAutomation provides protection system with information needed for properly performing under-frequency and under-voltage load shedding. Alarms, measurements, and messages produced by SCADA and AdvancedDistributionAutomation are processed by IAP to determine the root cause of the problem and deliver the summary message to the appropriate recipients of this information. Fault current recording Fault location Event recording Disturbance analysis s perform emergency switching operations to rapidly restore normal operating conditions by dispatching crews using Mobile radio system Mobile computing LMS: s performs intrusive load s or planners identify critical loads (hospitals, etc.) in advance Volume II D29-24 Final Release

29 Activity/Service Name management activities s enable emergency (major event) mode of operations for maintenance personnel and major event emergency mode of operation of AdvancedDistributionAutomationSyste m Outage management systems collect trouble calls, generate outage information, arrange work for troubleshooting Interactive utility-customer systems inform the customers about the progress of events AdvancedDistributionAutomationSyste m performs in major event emergency mode Activities/Services Provided ΑDA system locks out load shedding of critical loads s activate direct load control, prioritized by AdvancedDistributionAutomation s activate load curtailment, prioritized by AdvancedDistributionAutomation s apply load interruption, prioritized by AdvancedDistributionAutomation s enable emergency load reduction via AdvancedDistributionAutomation volt/var control s apply manual rolling blackouts Prepare personnel and automated system for actions under severe emergency conditions. Expedite fault location based on customer call-in information by using dynamic connectivity models Timely customers update about the progress of service restoration Automated messaging based on service restoration progress and association of customers communication nodes with the faulted area Automated data preparation, optimal decision making, and control of distribution operations in a coordinated with other systems manner under conditions of major events with more challenging safety and timing requirements Pre-arming of automatic/automated systems for operations under major event conditions and fast acting fault location, isolation, service restoration, feeder reconfiguration, volt/var control, and operation analysis 1.8 Contracts/Regulations Identify any overall (human-initiated) contracts, regulations, policies, financial considerations, engineering constraints, pollution constraints, and other environmental quality issues that affect the design and requirements of the Function. Contract/Regulation Contract between DISCO and TRANSCO Impact of Contract/Regulation on Function Operational boundaries. If the boundaries are at the circuit breaker level, then AdvancedDistributionAutomation has no direct access to substation capacitors and voltage regulators within the substation fence. In order to execute coordinated Volt/Var control, feeder reconfiguration, service restoration, AdvancedDistributionAutomation needs information about the substation connectivity, substation transformer loading, state of voltage regulators and capacitors, and their controllers. Furthermore, Volume II D29-25 Final Release

30 Contract/Regulation Contracts between DISCO and DEROwner Contracts between Disco and Customers Impact of Contract/Regulation on Function AdvancedDistributionAutomation should have capabilities for controlling these devices in a closed-loop mode. If the boundaries are at the high-voltage side of the substation transformer, then AdvancedDistributionAutomation has access to the substation devices and corresponding information. Volt/Var Agreement. Defines the voltage limits at the transmission side and reactive power requirements for distribution side. If the contractual parameters are not respected, the Volt/Var application may not meet its objectives, and the voltage limits at the customer side may be violated. Schedules. Defines amount of kw generated by DER at different times and constraints for power flow at PCC. Deviation from schedules must be timely detected and compensated by other reserve capabilities of the distribution system. Volt/Var control agreement. Defines modes of DER operation and setting for Volt/Var control. Defines rules for changes of modes of operation and setting (local/remote, DER/EPS). Deviation from agreement must be timely detected and compensated by other reserve capabilities of the distribution system. Standard Defines rules for interconnection between DER and DISCO (EPS). Deviation from the rules may result in violation of power quality limits, delays in service restoration, damage of DER equipment. Deviation from the standard must be timely detected and remedial actions must be implemented. Standard 519. Defines power quality requirements at customer terminals. AdvancedDistributionAutomation s are designed to respect these requirements. AdvancedDistributionAutomation must be capable of monitoring or accurately estimating the power quality parameters at the customer terminals, report and eliminate (or significantly reduce) the violations. Performance based rates. Defines the target level of service reliability. The distribution system and the AdvancedDistributionAutomation should be design to meet the target. Reliability guarantees. AdvancedDistributionAutomation should distinguish the customers with reliability guarantees from those without and focus the service restoration solution on meeting the guarantees, while providing other customers with target service reliability. Load management agreements. Defines the conditions, amount, and frequency of direct load control, load curtailment, interruption, and shedding. Policy From Actor May Shall Not Shall Description (verb) To Actor Volume II D29-26 Final Release

31 Constraint Type Description Applies to Volume II D29-27 Final Release

32 2 Step by Step Analysis of Function Describe steps that implement the. If there is more than one set of steps that are relevant, make a copy of the following section grouping (Preconditions and Assumptions, Steps normal sequence, and Steps alternate or exceptional sequence, Post conditions) 2.1 Distribution Operation Modeling and Analysis () Function this sequence Preconditions and Assumptions Describe conditions that must exist prior to the initiation of the Function, such as prior state of the actors and activities Identify any assumptions, such as what systems already exist, what contractual relations exist, and what configurations of systems are probably in place Identify any initial states of information exchanged in the steps in the next section. For example, if a purchase order is exchanged in an activity, its precondition to the activity might be filled in but unapproved. Actor///Contract AM_FM_GISDatabase CIS system (or proxy for CIS data) EnergyManagement SCADA DMS SCADA database ConversionValidationFunction Environmental daily data collector LoadForecaster ADADataChecker ADADispatching Preconditions or Assumptions AM/FM database contains the geographical information of the distribution power system circuit connectivity, as well as the parameters describing the power system facilities. Conceptually, the AM_FM_GISDatabase can contain transmission connectivity and facility data and relevant to distribution operations customer-related data. CIS contains load data for customers that is estimated for each nodal location on a feeder, based on billing data and time-of-day and day-of week load shapes for different load categories. EnergyManagement system contains the transmission power system model, and can provide the transmission connectivity information for facilities in the vicinity of the distribution power system facilities and with outputs from other EnergyManagement applications DistributionSCADA database is updated via remote monitoring and operator inputs.. Required scope, speed, and accuracy of real-time measurements are provided, supervisory and closed-loop control is supported. The C&V extracts incremental changes from AM/FM/GIS/Customer and converts it into AdvancedDistributionAutomation database format Collects environmental data One who makes decisions on operation of the power system Load forecasting system ADADataChecker frequently checks the changes in SCADA database ADADispatching is designed to coordinate the AdvancedDistributionAutomation s in a pre-defined manner Volume II D29-28 Final Release

33 Actor///Contract ADATopologyUpdate ITPersonnel ADATopologyUpdate ADATestDatabase ADADistributionOperationModeling and Analysis () Preconditions or Assumptions Checks the topology of the distribution system Field IT support ADATopologyUpdate reconfigures connectivity models in seconds Database containing test data values Preconditions: DistributionSCADA with several IEDs along distribution feeders, reporting statuses of remotely controlled switches and analogs including Amps, kw, kvar, and kv. s ability for updating the SCADA database with statuses of switches not monitored remotely. Substation SCADA with analogs and statuses from CBs exists. EnergyManagement is interfaced with AdvancedDistributionAutomation. AdvancedDistributionAutomation database is updated with the latest AM/FM and CIS data and operators input. The options for performance are selected Steps Normal Sequence Describe the normal sequence of events, focusing on steps that identify new types of information or new information exchanges or new interface issues to address. Should the sequence require detailed steps that are also used by other s, consider creating a new sub, then referring to that subroutine in this. Remember that the focus should be less on the algorithms of the applications and more on the interactions and information flows between entities, e.g. people, systems, applications, data bases, etc. There should be a direct link between the narrative and these steps. The numbering of the sequence steps conveys the order and concurrency and iteration of the steps occur. Using a Dewey Decimal scheme, each level of nested procedure call is separated by a dot.. Within a level, the sequence number comprises an optional letter and an integer number. The letter specifies a concurrent sequence within the next higher level; all letter sequences are concurrent with other letter sequences. The number specifies the sequencing of messages in a given letter sequence. The absence of a letter is treated as a default 'main sequence' in parallel with the lettered sequences. Sequence 1: Sequence 2: Do step 1 1.2A.1 - In parallel to activity 2 B do step 1 1.2A.2 - In parallel to activity 2 B do step 2 1.2B.1 - In parallel to activity 2 A do step 1 1.2B.2 - In parallel to activity 2 A do step Do step nested step nested step 3.2 Volume II D29-29 Final Release

34 2.1 - Do step Do step Data Conversion and Validation # Event Primary Actor Process/Activit y Info # Triggering event: Identify the name of the event Data conversion and validation What other actors are primarily responsible for the. Actors are defined in section1.5. ADADatabase Administrator, ConversionVali dationfunction Label that would appear in a process diagram. Use action verbs when naming activity. Extraction, conversion & validation Describe the actions that take place in active and present tense. The step should be a descriptive noun/verb phrase that portrays an outline summary of the step. If Then Else scenarios can be captured as multiple Actions or as separate steps. ADADatabase Administrator authorizes the Conversion and Validation to extract, convert and validate circuit connectivity and distribution transformer loading data. This is referred to as Stage 1 validation. What other actors are primarily responsible for Producing the information.actors are defined in section1.5. ADADatabas e Administrator What other actors are primarily responsible for Receiving the information Actors are defined in section1.5. (Note May leave blank if same as Primary Actor) ConversionV alidationfunc tion the information object. objects are defined in section 1.6 Authorization to start Stage 1 validation Elaborate architectural issues using attached spreadsheet. Use this column to elaborate details that aren t captured in the spreadsheet. Reference the applicable Environment containing this data exchange. Only one environment per step. 2 Note A triggering event is not necessary if the completion of the prior step leads to the transition of the following step. Volume II D29-30 Final Release

35 Process/Activit y Info DMS SCADA database, Checking real-time data The data in the latest download of DMS SCADA data is checked by for changes in topology and used to obtain the latest relevant analog data. DMS SCADA database DMS real-time analog, status & TLQ data 1.1.3, ADATopologyU pdate Connectivit y change ADATopologyUpdat e prepares changes in connectivity based on the latest DMS SCADA data for updating AdvancedDistributio nautomation database ADATopolog yupdatesyste m Changes in connectivity ADATopologyU pdate, ADADatabase Advanced Distributio nautomati on database update ADATopologyUpdat e updates AdvancedDistributio nautomation database ADATopolog yupdatesyste m ADADatabas e AdvancedDistrib utionautomation database update AM/FM/GIS Database, ConversionVali dationfunction Extraction, conversion & validation Conversion and Validation receives initial (before any corrections) connectivity, billing and facility parameter data. AM_FM_GIS Database ConversionV alidationfunc tion Initial connectivity, billing and facility parameter data Volume II D29-31 Final Release

36 1.1.6 ConversionVali dationfunction, ADADatabase Administrator ADADatabase Administrator Process/Activit y Issuing initial Stage 1 report Stage 1 corrections ITPersonnel Stage 1 corrections AM_FM_GISD atabase, ConversionVali dationfunction Extraction, conversion & validation After Conversion and Validation completes Stage 1 analysis it issues a report with incorrect circuit connectivity and transformer loading After reviewing the Stage 1 report, the ADADatabase Administrator issues an authorization to perform Stage 1 corrections. AM_FM_GISDataba se is corrected based on the Stage 1 report after ADADatabase Administrator authorized the procedure. Conversion and Validation receives connectivity, billing and facility parameter data after Stage 1 corrections have been implemented. ConversionV alidationfunc tion ADADatabas e Administrator ITPersonnel AM_FM_GIS Database ADADatabas e Administrator ITPersonnel AM_FM_GIS Database ConversionV alidationfunc tion Info Report with incorrect circuit connectivity and transformer loading Authorization to perform Stage 1 corrections Stage 1 corrections Connectivity, billing and facility parameter data after Stage 1 User Interface User Interface Volume II D29-32 Final Release

37 ConversionVali dationfunction, ADADatabase Administrator ConversionVali dationfunction, ADATestDataba se Process/Activit y Issuing report requiring no database corrections after Stage 1 Update of Advanced Distributio nautomati on Test Database after Stage 1 corrections After Conversion and Validation completes Stage 1 analysis it issues a report showing that no further corrections associated with connectivity, billing or facility parameter data are required. After Stage 1 corrections produce a report with no connectivity and transformer loading problems, the Conversion and Validation updates the AdvancedDistributio nautomation Test Database which sets the stage for Stage 2 validation. ConversionV alidationfunc tion ConversionV alidationfunc tion ADADatabas e Administrator ADATestDat abase Info Report showing that circuit connectivity and transformer loading require no corrections Update of AdvancedDistrib utionautomation Test Database User Interface Volume II D29-33 Final Release

38 ADADatabase Administrator, ConversionVali dationfunction ConversionVali dationfunction, ADATestDataba se Process/Activit y Load Flow and Load Transfer Analyses Load Flow and Load Transfer Analyses ADADatabase Administrator authorizes the Conversion and Validation to validate facility parameters via load flow and load transfer analyses. This is referred to as Stage 2 validation. Conversion and Validation receives excerpts from AdvancedDistributio nautomation Test Database (after they were updated with Stage 1 corrections) to perform Stage 2 analyses. ADADatabas e Administrator ADATestDat abase ConversionV alidationfunc tion ConversionV alidationfunc tion Info Authorization to start Stage 2 validation Excerpts from AdvancedDistrib utionautomation Test Database after Stage 1 corrections Volume II D29-34 Final Release

39 ConversionVali dationfunction, ADADatabase ConversionVali dationfunction, ADADatabase Administrator ADADatabase Administrator Process/Activit y Load Flow and Load Transfer Analyses Load Flow and Load Transfer Analyses Stage 2 corrections Conversion and Validation receives latest statuses and measurements from ADADatabase (which in turn are updated by DMS SCADADatabase) to perform Stage 2 analyses. After performing Stage 2 analyses, Conversion and Validation issues a report for ADADatabase Administrator. After reviewing the Stage 2 report, the ADADatabase Administrator issues an authorization to perform Stage 2 corrections. ADADatabas e ConversionV alidationfunc tion ADADatabas e Administrator ConversionV alidationfunc tion ADADatabas e Administrator ITPersonnel Info Latest statuses and measurements from ADADatabase Report on unreasonable load and voltage violations, corresponding facility parameters, results of comparative analyses and correction of inconsistencies Authorization to perform Stage 2 corrections User Interface User Interface Volume II D29-35 Final Release

40 ADADatabase Administrator, AM/FM/GIS Database AM/FM/GIS Database, ConversionVali dationfunction ConversionVali dationfunction, ADATestDataba se Process/Activit y Stage 2 corrections Extraction, conversion & validation Update of Advanced Distributio nautomati on Test Database after Stage 2 corrections AM_FM_GISDataba se is corrected based on the Stage 2 report after ADADatabase Administrator authorized the procedure. Conversion and Validation receives connectivity, billing and facility parameter data after Stage 2 corrections have been implemented. The Conversion and Validation updates the AdvancedDistributio nautomation Test Database. ITPersonnel AM_FM_GIS Database ConversionV alidationfunc tion AM_FM_GIS Database ConversionV alidationfunc tion ADATestDat abase Info Stage 2 corrections Connectivity, billing and facility parameter data after Stage 2 Update of AdvancedDistrib utionautomation Test Database User Interface Volume II D29-36 Final Release

41 ConversionVali dationfunction, ADATestDataba se ConversionVali dationfunction, ADADatabase Process/Activit y Load Flow and Load Transfer Analyses Load Flow and Load Transfer Analyses Conversion and Validation receives excerpts from AdvancedDistributio nautomation Test Database (after they were updated with Stage 2 corrections) to perform the next round of Stage 2 analyses. Conversion and Validation receives latest statuses and measurements from ADADatabase (which in turn are updated by DMS SCADADatabase) to perform the next round of Stage 2 analyses. ADATestDat abase ADADatabas e ConversionV alidationfunc tion ConversionV alidationfunc tion Info Excerpts from AdvancedDistrib utionautomation Test Database after Stage 2 corrections Latest statuses and measurements from ADADatabase Volume II D29-37 Final Release

42 ConversionVali dationfunction, ADADatabase Administrator ADADatabase Administrator Process/Activit y Issuing report requiring no database corrections after Stage 2 Update of ADADatab ase After Conversion and Validation completes Stage 2 analysis it issues a report showing that no further corrections associated with unreasonable load and voltage violations, or corresponding facility parameters are required. After reviewing the Stage 2 report requiring no further corrections, ADADatabase Administrator authorizes the update of AdvancedDistributio nautomation database. ConversionV alidationfunc tion ADADatabas e Administrator ADADatabas e Administrator ITPersonnel Info Report showing that no further corrections associated with unreasonable load and voltage violations, or corresponding facility parameters are required. Authorization to update AdvancedDistrib utionautomation database User Interface User Interface Volume II D29-38 Final Release

43 ITPersonnel, ADATestDataba se ITPersonnel, ADADatabase Process/Activit y Update of ADADatab ase Update of ADADatab ase After permission to update AdvancedDistributio nautomation database is given, ITPersonnel receives the needed update from AdvancedDistributio nautomation Test database. ITPersonnel updates AdvancedDistributio nautomation database ADATestDat abase ITPersonnel ITPersonnel ADADatabas e Info AdvancedDistrib utionautomation database update AdvancedDistrib utionautomation database update User Interface User Interface No Events # Event Primary Actor Process/Activit y Info # Triggering event: Identify the name of the event. 3 What other actors are primarily responsible for the. Actors are defined in section1.5. Label that would appear in a process diagram. Use action verbs when naming activity. Describe the actions that take place in active and present tense. The step should be a descriptive noun/verb phrase that portrays an outline summary of the step. If Then Else scenarios can be captured as multiple Actions or as separate steps. What other actors are primarily responsible for Producing the information.actors are defined in section1.5. What other actors are primarily responsible for Receiving the information Actors are defined in section1.5. (Note May leave blank if same as Primary Actor) the information object. objects are defined in section 1.6 Elaborate architectural issues using attached spreadsheet. Use this column to elaborate details that aren t captured in the spreadsheet. Reference the applicable Environment containing this data exchange. Only one environment per step. 3 Note A triggering event is not necessary if the completion of the prior step leads to the transition of the following step. Volume II D29-39 Final Release

44 1.2.1 No Events DMS SCADA database, EnergyManage ment SCADA database, Checking real-time data Checking real-time data Checking real-time data status verification receives the latest scan of DMS SCADA database to be checked for relevant changes or events. receives the latest scan of EnergyManagementSys tem SCADA database to be checked for relevant changes or events. determines that no changes or events are present in SCADA scan. status is verified (on/off) for reporting it to the. DMS SCADA database EnergyManag ement SCADA database DMS real-time analog, status, TLQ data EnergyManagem ent realtime analog, status, TLQ data No changes or events are detected. status User Interface Volume II D29-40 Final Release

45 Event Run # Event Primary Actor Process/Activit y Info # Triggering event: Identify the name of the event Event Run What other actors are primarily responsible for the. Actors are defined in section1.5. DMS SCADA database, EnergyManage ment SCADA database, Label that would appear in a process diagram. Use action verbs when naming activity. Checking real-time data Checking real-time data Describe the actions that take place in active and present tense. The step should be a descriptive noun/verb phrase that portrays an outline summary of the step. If Then Else scenarios can be captured as multiple Actions or as separate steps. receives the latest scan of DMS SCADA database to be checked for relevant changes or events. receives the latest scan of EnergyManagementS ystem SCADA database to be checked for relevant changes or events. What other actors are primarily responsible for Producing the information.actors are defined in section1.5. DMS SCADA database EnergyManag ement SCADA database What other actors are primarily responsible for Receiving the information Actors are defined in section1.5. (Note May leave blank if same as Primary Actor) the information object. objects are defined in section 1.6 DMS real-time analog, status, TLQ data EnergyManagem ent realtime analog, status, TLQ data Elaborate architectural issues using attached spreadsheet. Use this column to elaborate details that aren t captured in the spreadsheet. Reference the applicable Environment containing this data exchange. Only one environment per step. 4 Note A triggering event is not necessary if the completion of the prior step leads to the transition of the following step. Volume II D29-41 Final Release

46 Process/Activit y Info Checking real-time data, after detecting changes in connectivity, transfers relevant data to ADATopologyUpdat e. ADATopolog yupdatesyste m Changes in connectivity ADATopologyU pdate, ADADatabase Advanced Distributio nautomati on database update ADATopologyUpdat e updates AdvancedDistributio nautomation database with detected changes in connectivity detected by and with latest analog measurements. ADATopolog yupdatesyste m ADADatabas e Changes in connectivity and latest analog measurements ADATopologyU pdate, Checking distribution model integrity ADATopologyUpdat e gives permission to to analyze the distribution model integrity after AdvancedDistributio nautomation database is updated with latest changes. ADATopolog yupdatesyste m Permission to analyze distribution model integrity Volume II D29-42 Final Release

47 Process/Activit y Info ADADatabase, Checking distribution model integrity receives the data from AdvancedDistributio nautomation database needed for integrity check. ADADatabas e Excerpts from AdvancedDistrib utionautomation database 1.3.7a Checking distribution model integrity The distribution model integrity is confirmed and gives the permission for performing state estimation and power flow calculations. Permission for performing state estimation and power flow calculations 1.3.8a ADADatabase, State estimation and power flow calculation s receives the data from AdvancedDistributio nautomation database needed for state estimation and power flow calculations. ADADatabas e Excerpts from AdvancedDistrib utionautomation database Volume II D29-43 Final Release

48 Process/Activit y Info 1.3.9a, FLIR State estimation and power flow calculation s Upon completion of state estimation and power flow calculations, makes the connectivity, facility (including controllers), load and transmission data available to FLIR. FLIR Connectivity, facility (including controllers), load and transmission data a, ADAVVCContr oller State estimation and power flow calculation s Upon completion of state estimation and power flow calculations, makes the connectivity, facility (including controllers), load and transmission data available to ADAVVCController. ADAVVCCo ntroller Connectivity, facility (including controllers), load and transmission data a Analysis of distribution state estimation and power flow results makes results of power flow calculations available for analysis. Results of power flow calculations Volume II D29-44 Final Release

49 Process/Activit y Info a, ADAHistoricDa tabase Analysis of distribution state estimation and power flow results issues a report with results of analysis of state estimation and power flow calculations for storage in historic AdvancedDistributio nautomation database. ADAHistoric Database Power flow results, dispatchable kw & kvar, bus voltage limits, customer extreme voltages, segment and xmfr overloads, imbalances, load transfer capacity for selected ties, losses, quality and fault analyses, alarms (if any) about load/voltage violations and from fault analysis, logs Volume II D29-45 Final Release

50 Process/Activit y Info a, Analysis of distribution state estimation and power flow results Selected results of analysis of state estimation and power flow calculations are made available for the, EnergyManagementS ystem, and distributed intelligence schemes., EnergyManag ement status, dispatchable kw & kvar, bus voltage limits, aggregated load characteristics, transfer capacity, customer extreme voltages and imbalances, alarms (if any) about load/voltage violations and from fault analysis a, ADAVVCContr oller Analysis of distribution state estimation and power flow results If analysis of state estimation and power flow calculations detect a voltage or overload violation, VVC is initiated ADAVVCCo ntroller Initiation of VVC Volume II D29-46 Final Release

51 Process/Activit y Info 1.3.7b, ADADatabase Checking distribution model integrity If checking the distribution model integrity identifies a model inconsistency, a message describing the inconsistency is issued for storage in AdvancedDistributio nautomation database. ADADatabas e Message describing distribution model inconsistency 1.3.8b, Checking distribution model integrity If checking the distribution model integrity identifies a model inconsistency, a message describing the inconsistency is issued for the. Message describing distribution model inconsistency User Interface 1.3.9b, ADAVVCContr oller Checking distribution model integrity If checking the distribution model integrity identifies a model inconsistency, a command to switch VVC to default settings is issued. ADAVVCCo ntroller Command to switch ADAVVCContr oller to default settings Volume II D29-47 Final Release

52 Process/Activit y Info b, FLIR Checking distribution model integrity If checking the distribution model integrity identifies a model inconsistency, a command to switch FLIR to default settings is issued. FLIR Command to switch FLIR to default settings Scheduled Run # Event Primary Actor Info # Triggering event: Identify the name of the event. 5 What other actors are primarily responsible for the. Actors are defined in section1.5. Label that would appear in a process diagram. Use action verbs when naming activity. Describe the actions that take place in active and present tense. The step should be a descriptive noun/verb phrase that portrays an outline summary of the step. If Then Else scenarios can be captured as multiple Actions or as separate steps. What other actors are primarily responsible for Producing the information.actors are defined in section1.5. What other actors are primarily responsible for Receiving the information Actors are defined in section1.5. (Note May leave blank if same as Primary Actor) the information object. objects are defined in section 1.6 Elaborate architectural issues using attached spreadsheet. Use this column to elaborate details that aren t captured in the spreadsheet. Reference the applicable Environment containing this data exchange. Only one environment per step Scheduled Run DMS SCADA database, Checking real-time data receives the latest scan of DMS SCADA database to be checked for relevant changes or events. DMS SCADA database DMS real-time analog, status, TLQ data 5 Note A triggering event is not necessary if the completion of the prior step leads to the transition of the following step. Volume II D29-48 Final Release

53 Info EnergyManage ment SCADA database, Checking real-time data Checking real-time data ADADatabase, 1.4.5, FLIR State estimation and power flow calculations State estimation and power flow calculations receives the latest scan of EnergyManagementS ystem SCADA database to be checked for relevant changes or events. determines that no changes or events are present in SCADA scan. receives the data from AdvancedDistributio nautomation database needed for state estimation and power flow calculations. Upon completion of state estimation and power flow calculations, makes the connectivity, facility (including controllers), load and transmission data available to FLIR. EnergyManag ement SCADA database ADADatabas e FLIR EnergyManagem ent realtime analog, status, TLQ data No changes or events are detected. Excerpts from AdvancedDistrib utionautomation database Connectivity, facility (including controllers), load and transmission data Volume II D29-49 Final Release

54 Info 1.4.6, ADAVVCContr oller State estimation and power flow calculations Analysis of distribution state estimation and power flow results Upon completion of state estimation and power flow calculations, makes the connectivity, facility (including controllers), load and transmission data available to ADAVVCController. makes results of power flow calculations available for analysis. ADAVVCCo ntroller Connectivity, facility (including controllers), load and transmission data Results of power flow calculations Volume II D29-50 Final Release

55 Info 1.4.8, ADAHistoricDa tabase Analysis of distribution state estimation and power flow results issues a report with results of analysis of state estimation and power flow calculations for storage in historic AdvancedDistributio nautomation database. ADAHistoric Database Power flow results, dispatchable kw & kvar, bus voltage limits, customer extreme voltages, segment and xmfr overloads, imbalances, load transfer capacity for selected ties, losses, quality and fault analyses, alarms (if any) about load/voltage violations and from fault analysis, logs Volume II D29-51 Final Release

56 Info 1.4.9, , distributed intelligence schemes , ADAVVCContr oller Analysis of distribution state estimation and power flow results Analysis of distribution state estimation and power flow results Analysis of distribution state estimation and power flow results Selected results of analysis of power flow calculations are made available for the and EnergyManagementS ystem. Analysis of power flow results includes transfer capacity of selected ties, which is transmitted to distributed intelligence schemes. If analysis of power flow calculations detect a voltage or overload violation, VVC is initiated, EnergyManag ement Distributed intelligence schemes ADAVVCCo ntroller status, dispatchable kw & kvar, bus voltage limits, customer extreme voltages and imbalances, alarms (if any) about load/voltage violations and from fault analysis Transfer capacity of selected ties Initiation of VVC Study/Look-ahead Mode Volume II D29-52 Final Release

57 Info # Triggering event: Identify the name of the event Study/Look Ahead Mode What other actors are primarily responsible for the. Actors are defined in section1.5. AM_FM_GIS Database, ConversionVali dationfunction ConversionVali dationfunction, ADADatabase Label that would appear in a process diagram. Use action verbs when naming activity. Data conversion and validation Data conversion and validation Describe the actions that take place in active and present tense. The step should be a descriptive noun/verb phrase that portrays an outline summary of the step. If Then Else scenarios can be captured as multiple Actions or as separate steps. Conversion and validation receives the latest database download to extract, convert and validate circuit connectivity and transformer loading data (Stage 1) as well as to validate facility parameters via load flow and load transfer analyses (Stage 2). Conversion and validation updates AdvancedDistribution Automation database with the latest changes in AM_FM_GISDatabas e. What other actors are primarily responsible for Producing the information.actors are defined in section1.5. AM_FM_GIS Database ConversionVa lidationfuncti on What other actors are primarily responsible for Receiving the information Actors are defined in section1.5. (Note May leave blank if same as Primary Actor) ConversionV alidationfunc tion ADADatabas e the information object. objects are defined in section 1.6 Connectivity, billing and facility parameters Update of AdvancedDistrib utionautomation database Elaborate architectural issues using attached spreadsheet. Use this column to elaborate details that aren t captured in the spreadsheet. Reference the applicable Environment containing this data exchange. Only one environment per step. 6 Note A triggering event is not necessary if the completion of the prior step leads to the transition of the following step. Volume II D29-53 Final Release

58 Info ADADispatchi ng, 1.5.4, WorkManagem ent, Environmental daily data collector, ADADatabase Preparation of distribution system states as input for Preparation of distribution system states as input for Preparation of distribution system states as input for AdvancedDi stributionau tomationsys tem database update ADADispatchingSyste m, responsible, among other things, for triggering scheduled runs of various AdvancedDistribution Automation s, issues a command to initiate the look-ahead mode. gives the command to initiate the study mode. receives information about the outages: present and future, which is reflected in preparation of distribution system state. Environmental data for DER operation forecasting is updated in AdvancedDistribution Automation database. ADADispatch ing WorkManage ment Environmental daily data collector ADADatabas e Command to initiate lookahead mode. Command to initiate study mode. Schedules presently active or authorized for future outages Environmental data for DER load and schedule forecast User Interface Volume II D29-54 Final Release

59 Info ADADatabase, load forecaster LoadForecaster, ADADatabase, Preparation of distribution system states as input for Preparation of distribution system states as input for Preparation of distribution system states as input for LoadForecaster receives distribution transformer daily loading data and environmental data for DER load to be used in preparation of distribution system state. receives the distribution transformer loading and DER operational forecasts needed for preparation of distribution system states to be studied in the study and lookahead modes. receives the excerpts from AdvancedDistribution Automation database needed for preparation of distribution system states. ADADatabase LoadForecaste r ADADatabase LoadForecast er Distribution transformers daily loading, environmental data for DER load and schedule forecasts Distribution transformer loading and DER operational forecasts Excerpts from AdvancedDistrib utionautomation database Volume II D29-55 Final Release

60 Info , ADAHistoricD atabase Preparation of distribution system states as input for Checking distribution system state Performing distribution state estimation and power flow calculations Analysis of distribution power flow calculations results Statuses and analogs associated with the given distribution system state are made available for study and look-ahead modes. The given distribution system state is checked for inconsistencies. performs distribution power flow calculations making the results available for analyses. Analysis of the results of the distribution power flow calculations are made available for archiving. ADAHistoric Database Statuses and analogs Input data for a given distribution system state Results of distribution state estimation and power flow calculations Power flow results, dispatchable kw and kvar, bus voltage limits, customer extreme voltages and imbalances, losses, quality and fault analyses, alarms about load/voltage violations, logs. Volume II D29-56 Final Release

61 Info , Analysis of distribution power flow calculations results Preparation of distribution system states as input for Analysis of the results of the distribution power flow calculations are made available for the. Upon completion of analysis of the results of the distribution power flow calculations issues a command to start the study of the next distribution system state. status, dispatchable kw and kvar, bus voltage limits, customer extreme voltages and imbalances, alarms about load/voltage violations. Command to start the study of the next distribution system state. User Interface Steps Alternative / Exception Sequences Describe any alternative or exception sequences that may be required that deviate from the normal course of activities. Note instructions are found in previous table. Volume II D29-57 Final Release

62 Info Post-conditions and Significant Results Describe conditions that must exist at the conclusion of the Function. Identify significant items similar to that in the preconditions section. Describe any significant results from the Function Actor/Activity in real-time mode in look-ahead and study modes Diagrams Post-conditions Description and Results generates pseudo-measurements for all distribution elements, reveals operational violations, aggregates operational parameters at the demarcation points between distribution and transmission, provides information for pre-arming of distributed intelligence schemes, determines currently available demand response including DER dispatch, prepares model updates for other AdvancedDistributionAutomation-DER s. predicts operational parameters for all distribution elements under expected in near-future and study conditions, operational violations, aggregates operational parameters at the demarcation points between distribution and transmission, determines available in near-future demand response including DER dispatch, prepares model for other AdvancedDistributionAutomation-DER s in study and look-ahead modes. For clarification, draw (by hand, by Power Point, by UML diagram) the interactions, identifying the Steps where possible. Volume II D29-58 Final Release

63 Volume II D29-59 Final Release

64 Volume II D29-60 Final Release

65 Volume II D29-61 Final Release

66 Volume II D29-62 Final Release

67 Volume II D29-63 Final Release

68 2.2 Fault Location, Isolation and Service Restoration (FLIR) Function this sequence FLIR Preconditions and Assumptions Describe conditions that must exist prior to the initiation of the Function, such as prior state of the actors and activities Identify any assumptions, such as what systems already exist, what contractual relations exist, and what configurations of systems are probably in place Identify any initial states of information exchanged in the steps in the next section. For example, if a purchase order is exchanged in an activity, its precondition to the activity might be filled in but unapproved. Actor///Contract Preconditions or Assumptions The same as for The same as for AdvancedDistributionAutomation: Fault Location Preconditions: DistributionSCADA with fault detectors, Distribution Fault Location Isolation and Service Operation Model and Analysis with fault analysis, fault location relays (schemes) including high Restoration (FLIR) impedance relays and Some Distributed Intelligence schemes and Trouble call system exist. Fault Isolation and Service Restoration Preconditions: DistributionSCADA with ability to control a defined number of switching devices, Fault Location, Distribution Operation Model and Analysis, Voltage and Var Control for adjusting voltage and var after reconfiguration. Supervisory and closed-loop control of switches are available. Some Distributed Intelligence schemes exist. OutageManagement Outage Management is interfaced with SCADA and AdvancedDistributionAutomation and supports a dynamic topology model. EnergyManagement (WAMACS) EnergyManagement is interfaced with WAMACS and AdvancedDistributionAutomation and provides phasor data for all distribution (reference) buses. has AdvancedDistributionAutomation GUI and uses it for supervisory control of switches, for entering pseudo-scada statuses, selecting isolation and restoration alternatives, etc. The operator also has the ability to communicate with the field crews via mobile communications and computing. FieldPersonnel Distributed Intelligence Schemes AdvancedDistributionAutomationSyst em: Prearming of Remedial Action Schemes application Historic DB FieldPersonnels are able to communicate with the operator via mobile communications and computing DIS team members are able to operate in a coordinated manner based on peer-to-peer communications or based on operational parameters, and DIS team masters are able to communicate via fast peer-topeer communications The pre-arming application downloads operating conditions to DIS masters based on results Historic database is able to store large amount of data about outages, which will be used by the outage Volume II D29-64 Final Release

69 Actor///Contract Environmental daily data collector ADATopologyUpdate Fault location Preconditions or Assumptions statistic application and other users. Environmental daily data collector collects environmental data used for DER schedule forecast. ADATopologyUpdate changes connectivity in AdvancedDistributionAutomation database based on changes detected in real-time DMS and EnergyManagement SCADA. Fault-locating provides distances to fault location, which are used by operator or FLIR, along with other relevant data, to guide activities of field crews FLIR Steps Normal Sequence Describe the normal sequence of events, focusing on steps that identify new types of information or new information exchanges or new interface issues to address. Should the sequence require detailed steps that are also used by other s, consider creating a new sub, then referring to that subroutine in this. Remember that the focus should be less on the algorithms of the applications and more on the interactions and information flows between entities, e.g. people, systems, applications, data bases, etc. There should be a direct link between the narrative and these steps. The numbering of the sequence steps conveys the order and concurrency and iteration of the steps occur. Using a Dewey Decimal scheme, each level of nested procedure call is separated by a dot.. Within a level, the sequence number comprises an optional letter and an integer number. The letter specifies a concurrent sequence within the next higher level; all letter sequences are concurrent with other letter sequences. The number specifies the sequencing of messages in a given letter sequence. The absence of a letter is treated as a default 'main sequence' in parallel with the lettered sequences. Sequence 1: Sequence 2: Do step 1 1.2A.1 - In parallel to activity 2 B do step 1 1.2A.2 - In parallel to activity 2 B do step 2 1.2B.1 - In parallel to activity 2 A do step 1 1.2B.2 - In parallel to activity 2 A do step Do step nested step nested step 3.2 Volume II D29-65 Final Release

70 2.1 - Do step Do step FLIR First Fault with Only Manual Switches # Event Primary Actor Info # Triggering event? Identify the name of the event. 7 What other actors are primarily responsible for the? Actors are defined in section1.5. Label that would appear in a process diagram. Use action verbs when naming activity. Describe the actions that take place in active and present tense. The step should be a descriptive noun/verb phrase that portrays an outline summary of the step. If Then Else scenarios can be captured as multiple Actions or as separate steps. What other actors are primarily responsible for Producing the information? Actors are defined in section1.5. What other actors are primarily responsible for Receiving the information? Actors are defined in section1.5. (Note May leave blank if same as Primary Actor) the information object. objects are defined in section 1.6 Elaborate architectural issues using attached spreadsheet. Use this column to elaborate details that aren t captured in the spreadsheet. Reference the applicable Environment containing this data exchange. Only one environment per step FLIR first fault with only manual switches DMS SCADA database, EnergyManage ment SCADA database, Checking real-time data Checking real-time data receives the scan of DMS SCADA data to be checked for changes in topology. It also provides the latest relevant analog data. receives the scan of EnergyManagementS ystem SCADA data to be checked for relevant changes or events. DMS SCADA database EnergyManag ement SCADA database DMS real-time analog, status & TLQ data EnergyManagem ent realtime analog, status, TLQ data 7 Note A triggering event is not necessary if the completion of the prior step leads to the transition of the following step. Volume II D29-66 Final Release

71 Info Environmental daily data collector, OutageManage ment, 2.1.5, ADATopologyU pdate Checking real-time data Checking real-time data ADATopolog yupdatesyste m changes connectivity receives the scan of environmental data to be checked for changes affecting DER performance forecast. receives the scan of latest schedules of presently active or authorized for future outages to be checked for changes during the time of repair. After detects fault in distribution, relevant information is provided to topology. Environmental daily data collector OutageManag ement ADATopolog yupdatesyste m Real-time environmental data for DER schedule forecast Schedules of presently active or authorized for future outages Circuit breaker lockouts, inputs from OutageManagem ent ADATopologyU pdate, ADADatabase ADATopolog yupdatesyste m changes connectivity After fault is detected, AdvancedDistributio nautomation database is updated. ADATopolog yupdatesyste m ADADatabas e Update of AdvancedDistrib utionautomation database Volume II D29-67 Final Release

72 Info ADATopologyU pdate, FLIR ADADatabase, FLIR FLIR, Fault location, Fault location sub- identifies fault-related protective devices and de-energized sections Fault location sub- identifies fault-related protective devices and de-energized sections Fault location sub- identifies fault-related protective devices and de-energized sections Faultlocation relay informs Topology initiates fault location sub- of the FLIR. Fault location sub receives the needed data from AdvancedDistributio nautomation database after it was updated with fault information. Fault location sub provides the with information needed for him to make operational decisions, i.e., dispatching the field crew, etc. receives distances to fault location provided by the fault location relay. ADATopolog yupdatesyste m ADADatabase FLIR Fault location FLIR FLIR Fault location sub- initiation Excerpts from AdvancedDistrib utionautomation database updated after fault detection Circuit breaker lockouts, inputs from OutageManagem ent, faultrelated deenergized sections Distances to fault location User Interface User Interface Volume II D29-68 Final Release

73 Info , field crew informs field crew authorizes to patrol the faulted line to locate fault and perform binary search if needed. FieldPersonn el Authorization to patrol faulted line User Interface FieldPersonnel, , FieldPersonn el informs Entering status of switches and faulted section into AdvancedDis tributionauto mationsyste m database After locating the fault, the crew informs the about the status of switches involved in initial fault isolation. The enters status of switches (pseudostatuses) involved in initial fault isolation and the faulted section into AdvancedDistributio nautomation database. FieldPersonne l ADADatabas e Status of switches involved in initial fault isolation AdvancedDistrib utionautomation database update after initial fault isolation User Interface User Interface Volume II D29-69 Final Release

74 Info , FLIR ADADatabase, FLIR FLIR, ADAHistoricDa tabase Fault isolation and service restoration sub- generates list of recommende d switching orders Fault isolation and service restoration sub- generates list of recommende d switching orders Fault isolation and service restoration sub- generates list of recommende d switching orders By entering the faulted section into the AdvancedDistributio nautomation database, the initiates fault isolation and service restoration sub-. Fault isolation and service restoration sub- receives AdvancedDistributio nautomation database excerpts updated after initial fault isolation. FLIR issues a report for archiving in AdvancedDistributio nautomation historic database ADADatabase FLIR FLIR FLIR ADAHistoric Database Initiation of fault isolation and service restoration sub AdvancedDistrib utionautomation database excerpts updated after initial fault isolation Report including interrupted, unserved and restored load, and number of customers User Interface Volume II D29-70 Final Release

75 Info FLIR, , field crew Fault isolation and service restoration sub- generates list of recommende d switching orders informs field crew A generated list of recommended switching orders is presented to the. selects a switching order and authorizes its implementation. FLIR FieldPersonn el List of recommended switching orders Switching order authorized for implementation User Interface User Interface FieldPersonnel, FieldPersonn el informs Upon final isolation and service restoration to healthy sections, the field crew informs the about final status of relevant switches (cuts). FieldPersonne l Status of switches involved in final fault isolation and service restoration to healthy sections. User Interface Volume II D29-71 Final Release

76 Info , Entering status of switches involved in final fault isolation and service restoration to healthy sections into AdvancedDis tributionauto mationsyste m database FLIR FLIR updates the switching order in accord with the final fault isolation The enters status of switches/cuts (pseudo-statuses) involved in final fault isolation and service restoration to healthy sections into AdvancedDistributio nautomation database receives the final switching order from FLIR and dispatched the crew to implement it FLIR, ADADatabas e, FieldPersonn el AdvancedDistrib utionautomation database update after final fault isolation and service restoration Switching order, instructions to the crew User Interface User Interface FLIR Second Fault (Related to First Fault which is Not Resolved Yet) with Only Manual Switches Volume II D29-72 Final Release

77 Process/Activit y Info # Triggering event? Identify the name of the event. 8 What other actors are primarily responsible for the? Actors are defined in section1.5. Label that would appear in a process diagram. Use action verbs when naming activity. Describe the actions that take place in active and present tense. The step should be a descriptive noun/verb phrase that portrays an outline summary of the step. If Then Else scenarios can be captured as multiple Actions or as separate steps. What other actors are primarily responsible for Producing the information? Actors are defined in section1.5. What other actors are primarily responsible for Receiving the information? Actors are defined in section1.5. (Note May leave blank if same as Primary Actor) the information object. objects are defined in section 1.6 Elaborate architectural issues using attached spreadsheet. Use this column to elaborate details that aren t captured in the spreadsheet. Reference the applicable Environment containing this data exchange. Only one environment per step FLIR second fault (related to first fault which is not resolved yet) with only manual switches DMS SCADA database, EnergyManage ment SCADA database, Checking real-time data Checking real-time data receives the scan of DMS SCADA data to be checked for changes in topology. It also provides the latest relevant analog data. receives the scan of EnergyManagementSys tem SCADA data to be checked for relevant changes or events. DMS SCADA database EnergyManag ement SCADA database DMS real-time analog, status & TLQ data at time of first fault EnergyManagem ent realtime analog, status, TLQ data at time of first fault 8 Note A triggering event is not necessary if the completion of the prior step leads to the transition of the following step. Volume II D29-73 Final Release

78 2.2.3 Environmental daily data collector, OutageManage ment, 2.2.5, ADATopologyU pdate Process/Activit y Checking real-time data Checking real-time data ADATopol ogyupdate changes connectivit y receives the scan of environmental data to be checked for changes affecting DER performance forecast. receives the scan of latest schedules of presently active or authorized for future outages to be checked for changes. After detects first fault in distribution, relevant information is provided to topology. Environmental daily data collector OutageManag ement ADATopolog yupdatesyste m Info Real-time environmental data for DER schedule forecast at time of first fault Schedules of presently active or authorized for future outages at time of first fault First fault: circuit breaker lockouts, inputs from OutageManagem ent ADATopologyU pdate, ADADatabase ADATopol ogyupdate changes connectivit y After first fault is detected, AdvancedDistributionA utomation database is updated. ADATopolog yupdatesyste m ADADatabas e Update of AdvancedDistrib utionautomation database after first fault detection Volume II D29-74 Final Release

79 2.2.7 ADATopologyU pdate, FLIR ADADatabase, FLIR Process/Activit y Fault location sub identifies faultrelated protective devices and deenergized sections Fault location sub identifies faultrelated protective devices and deenergized sections After the first fault is detected, topology initiates fault location sub- of the FLIR. Fault location sub receives the needed data from AdvancedDistributionA utomation database after it was updated with the first fault information. ADATopolog yupdatesyste m ADADatabase FLIR FLIR Info Fault location sub- initiation after first fault Excerpts from AdvancedDistrib utionautomation database updated after first fault detection Volume II D29-75 Final Release

80 2.2.9 FLIR, , field crew Process/Activit y Fault location sub identifies faultrelated protective devices and deenergized sections informs field crew Fault location sub provides the with information on the first fault needed for him to make operational decisions, i.e., dispatching the field crew, etc. authorizes to patrol the faulted line to locate first fault and perform binary search if needed. FLIR FieldPersonn el Info First fault: circuit breaker lockouts, inputs from OutageManagem ent, faultrelated deenergized sections Authorization to patrol faulted line to locate first fault User Interface User Interface FieldPersonnel, FieldPerso nnel informs After locating the first fault, the crew informs the about the status of switches involved in initial fault isolation. FieldPersonne l Status of switches involved in initial first fault isolation User Interface Volume II D29-76 Final Release

81 2.2.12, , FLIR Process/Activit y Entering status of switches and faulted section into Advanced Distributio nautomati on database Fault isolation and service restoration sub generates list of recommend ed switching orders The enters status of switches (pseudostatuses) involved in initial first fault isolation and the faulted section into AdvancedDistributionA utomation database. By entering the faulted section, associated with first fault, into the AdvancedDistributionA utomation database, the initiates fault isolation and service restoration sub-. ADADatabas e FLIR Info AdvancedDistrib utionautomation database update after initial isolation of first fault Initiation of fault isolation and service restoration sub User Interface User Interface Volume II D29-77 Final Release

82 ADADatabase, FLIR FLIR, ADAHistoricDa tabase Process/Activit y Fault isolation and service restoration sub generates list of recommend ed switching orders Fault isolation and service restoration sub generates list of recommend ed switching orders Fault isolation and service restoration sub receives AdvancedDistributionA utomation database excerpts updated after initial first fault isolation. FLIR issues a report after the first fault for archiving in AdvancedDistributionA utomation historic database ADADatabase FLIR FLIR ADAHistoric Database Info AdvancedDistrib utionautomation database excerpts updated after initial isolation of first fault Report including interrupted, unserved and restored load, and number of customers after first fault Volume II D29-78 Final Release

83 Process/Activit y Info FLIR, Fault isolation and service restoration sub generates list of recommend ed switching orders A generated list of recommended switching orders related to first fault is presented to the. FLIR List of recommended switching orders related to first fault User Interface FLIR second fault (related to first fault which is not resolved yet) with only manual switches DMS SCADA database, Checking real-time data receives the scan of DMS SCADA data to be checked for changes in topology. It also provides the latest relevant analog data. DMS SCADA database DMS real-time analog, status & TLQ data at time of second fault EnergyManage ment SCADA database, Checking real-time data receives the scan of EnergyManagementSys tem SCADA data to be checked for relevant changes or events. EnergyManag ement SCADA database EnergyManagem ent realtime analog, status, TLQ data at time of second fault Volume II D29-79 Final Release

84 Environmental daily data collector, OutageManage ment, , ADATopologyU pdate Process/Activit y Checking real-time data Checking real-time data ADATopol ogyupdate changes connectivit y receives the scan of environmental data to be checked for changes affecting DER performance forecast. receives the scan of latest schedules of presently active or authorized for future outages to be checked for changes. After detects second fault in distribution, relevant information is provided to topology. Environmental daily data collector OutageManag ement ADATopolog yupdatesyste m Info Real-time environmental data for DER schedule forecast at time of second fault Schedules of presently active or authorized for future outages at time of second fault Second fault: circuit breaker lockouts, inputs from OutageManagem ent ADATopologyU pdate, ADADatabase ADATopol ogyupdate changes connectivit y After second fault is detected, AdvancedDistributionA utomation database is updated. ADATopolog yupdatesyste m ADADatabas e Update of AdvancedDistrib utionautomation database after second fault detection Volume II D29-80 Final Release

85 ADATopologyU pdate, FLIR ADADatabase, FLIR Process/Activit y Fault location sub identifies faultrelated protective devices and deenergized sections Fault location sub identifies faultrelated protective devices and deenergized sections After the second fault is detected, topology initiates fault location sub- of the FLIR. Fault location sub receives the needed data from AdvancedDistributionA utomation database after it was updated with the second fault information. ADATopolog yupdatesyste m ADADatabase FLIR FLIR Info Fault location sub- initiation after second fault Excerpts from AdvancedDistrib utionautomation database updated after second fault detection Volume II D29-81 Final Release

86 Process/Activit y FLIR Fault isolation and service restoration sub determines whether second fault impacts switching for first fault FLIR Fault isolation and service restoration sub determines whether second fault impacts switching for first fault Fault isolation and service restoration sub determines whether second fault impacts switching for first fault. Fault isolation and service restoration sub cancels the previous switching order if it needs to. FLIR FLIR FLIR Info Second fault: circuit breaker lockouts, inputs from OutageManagem ent, faultrelated deenergized sections Cancellation of first-fault-related switching order User Interface Volume II D29-82 Final Release

87 2.2.28, field crew Process/Activit y informs field crew authorizes to patrol the faulted line to locate second fault and perform binary search if needed. FieldPersonn el Info Authorization to patrol faulted line to locate second fault User Interface FieldPersonnel, , FieldPerso nnel informs Entering status of switches and faulted section into Advanced Distributio nautomati on database After locating the second fault, the crew informs the about the status of switches involved in initial second fault isolation. The enters status of switches (pseudostatuses) involved in initial second fault isolation and the faulted section into AdvancedDistributionA utomation database. FieldPersonne l ADADatabas e Status of switches involved in initial second fault isolation AdvancedDistrib utionautomation database update after initial isolation of second fault User Interface User Interface Volume II D29-83 Final Release

88 2.2.32, FLIR ADADatabase, FLIR Process/Activit y Fault isolation and service restoration sub generates list of recommend ed switching orders Fault isolation and service restoration sub generates list of recommend ed switching orders By entering the faulted section, associated with second fault, into the AdvancedDistributionA utomation database, the initiates fault isolation and service restoration sub- for both faults. Fault isolation and service restoration sub receives AdvancedDistributionA utomation database excerpts updated after initial second fault isolation. ADADatabase FLIR FLIR Info Initiation of fault isolation and service restoration sub AdvancedDistrib utionautomation database excerpts updated after initial isolation of second fault User Interface Volume II D29-84 Final Release

89 FLIR, ADAHistoricDa tabase FLIR, , field crew Process/Activit y Fault isolation and service restoration sub generates list of recommend ed switching orders Fault isolation and service restoration sub generates list of recommend ed switching orders informs field crew FLIR issues a report after the second fault for archiving in AdvancedDistributionA utomation historic database A generated list of recommended switching orders related to both faults is presented to the. selects a switching order and authorizes its implementation. FLIR FLIR ADAHistoric Database FieldPersonn el Info Report including interrupted, unserved and restored load, and number of customers after second fault List of recommended switching orders related to second fault Switching order authorized for implementation after second fault User Interface User Interface Volume II D29-85 Final Release

90 FieldPersonnel, , Process/Activit y FieldPerso nnel informs Entering status of switches involved in final fault isolation and service restoration to healthy sections into Advanced Distributio nautomati on database Upon final isolation and service restoration to healthy sections, the field crew informs the about final status of relevant switches for the second fault. The enters status of switches (pseudostatuses) involved in final fault isolation and service restoration to healthy sections into AdvancedDistributionA utomation database FieldPersonne l ADADatabas e Info Status of switches involved in final fault isolation and service restoration to healthy sections after second fault. AdvancedDistrib utionautomation database update after final fault isolation and service restoration User Interface User Interface Volume II D29-86 Final Release

91 FLIR FLIR updates the switching order in accord with the final isolation of both faults Process/Activit y receives the final switching order from FLIR and dispatched the crew to implement it FLIR, FieldPersonn el Info Switching order, instructions to the crew User Interface FLIR Fault with Remotely-Controlled and Manual Switches # Event Primary Actor Process/Activit y Info # Triggering event? Identify the name of the event. 9 What other actors are primarily responsible for the? Actors are defined in section1.5. Label that would appear in a process diagram. Use action verbs when naming activity. Describe the actions that take place in active and present tense. The step should be a descriptive noun/verb phrase that portrays an outline summary of the step. If Then Else scenarios can be captured as multiple Actions or as separate steps. What other actors are primarily responsible for Producing the information? Actors are defined in section1.5. What other actors are primarily responsible for Receiving the information? Actors are defined in section1.5. (Note May leave blank if same as Primary Actor) the information object. objects are defined in section 1.6 Elaborate architectural issues using attached spreadsheet. Use this column to elaborate details that aren t captured in the spreadsheet. Reference the applicable Environment containing this data exchange. Only one environment per step. 9 Note A triggering event is not necessary if the completion of the prior step leads to the transition of the following step. Volume II D29-87 Final Release

92 Process/Activit y Info FLIR fault with remotelycontrolled and manual switches DMS SCADA database, EnergyManage ment SCADA database, Environmental daily data collector, OutageManage ment, Checking real-time data Checking real-time data Checking real-time data Checking real-time data receives the scan of DMS SCADA data to be checked for changes in topology. It also provides the latest relevant analog data. receives the scan of EnergyManagementSys tem SCADA data to be checked for relevant changes or events. receives the scan of environmental data to be checked for changes affecting DER performance forecast. receives the scan of latest schedules of presently active or authorized for future outages to be checked for changes. DMS SCADA database EnergyManag ement SCADA database Environmental daily data collector OutageManag ement DMS real-time analog, status & TLQ data EnergyManagem ent realtime analog, status, TLQ data Real-time environmental data for DER schedule forecast Schedules of presently active or authorized for future outages Volume II D29-88 Final Release

93 2.3.5 Fault location, Process/Activit y Checking real-time data receives the distance to fault location, which is provided by Fault location in the presence of the fault. Fault location Info Distance to fault location 2.3.6, ADATopologyU pdate ADATopol ogyupdate changes connectivit y After detects fault in distribution, relevant information is provided to topology. ADATopolog yupdatesyste m Circuit breaker lockouts, inputs from OutageManagem ent ADATopologyU pdate, ADADatabase ADATopol ogyupdate changes connectivit y After fault is detected, AdvancedDistributionA utomation database is updated. ADATopolog yupdatesyste m ADADatabas e Update of AdvancedDistrib utionautomation database Volume II D29-89 Final Release

94 2.3.8 ADATopologyU pdate, FLIR ADADatabase, FLIR Process/Activit y Fault location sub identifies faultrelated protective devices and deenergized sections Fault location sub identifies faultrelated protective devices and deenergized sections Topology initiates fault location sub- of the FLIR. Fault location sub receives the needed data from AdvancedDistributionA utomation database after it was updated with fault information. ADATopolog yupdatesyste m ADADatabase FLIR FLIR Info Fault location sub initiation Excerpts from AdvancedDistrib utionautomation database updated after fault detection Volume II D29-90 Final Release

95 Process/Activit y FLIR Fault isolation and service restoration sub generates list of recommend ed switching orders ADADatabase, FLIR Fault isolation and service restoration sub generates list of recommend ed switching orders Fault location sub initiates fault isolation and service restoration sub of the FLIR. Fault isolation and service restoration sub receives AdvancedDistributionA utomation database excerpts updated with fault information. Fault location ADADatabase Fault isolation and service restoration sub FLIR Info Fault isolation and service restoration sub initiation, probable fault location with alternatives AdvancedDistrib utionautomation database excerpts Volume II D29-91 Final Release

96 FLIR, ADAHistoricDa tabase a FLIR, Process/Activit y Fault isolation and service restoration sub generates list of recommend ed switching orders Fault isolation and service restoration sub generates list of recommend ed switching orders FLIR issues a report for archiving in AdvancedDistributionA utomation historic database. A list of recommended switching orders using remotely controlled switches is presented to the. FLIR FLIR ADAHistoric Database Info Report including interrupted, unserved and restored load, and number of customers before additional fault isolation List of switching orders recommended after fault detection User Interface Volume II D29-92 Final Release

97 Process/Activit y b FLIR Fault isolation and service restoration sub generates list of recommend ed switching orders a, DMS SCADA database SO execution In advisory mode, considers the list of switching order alternatives and selects the best SO based on predefined criteria In the advisory mode, the, after reviewing SO, issues supervisory commands to execute it. FLIR DMS SCADA database Info List of switching orders recommended after fault detection Supervisory command to execute SO issued after fault detection User Interface User Interface b FLIR, DMS SCADA database SO execution In the closed-loop mode, FLIR issues command to execute the best SO. FLIR DMS SCADA database Supervisory command to execute SO issued after fault detection Volume II D29-93 Final Release

98 2.3.15, field crew FieldPersonnel, , , ADADatabase Process/Activit y informs field crew FieldPerso nnel informs Entering status of switches and faulted section into Advanced Distributio nautomati on database authorizes to patrol the faulted section to accurately locate the fault and perform binary search if needed. After accurately locating the fault, the crew informs the about the status of switches involved in additional switching to isolate the smallest possible faulted section. The enters status of switches (pseudostatuses) involved in finall fault isolation and the faulted section into AdvancedDistributionA utomation database. FieldPersonne l FieldPersonn el ADADatabas e Info Authorization to patrol faulted line Status of switches involved in isolating the smallest possible faulted section AdvancedDistrib utionautomation database update additional fault isolation User Interface User Interface User Interface Volume II D29-94 Final Release

99 2.3.19, FLIR ADADatabase, FLIR Process/Activit y Entering status of switches and faulted section into Advanced Distributio nautomati on database Fault isolation and service restoration sub generates list of recommend ed switching orders Entering the faulted section into AdvancedDistributionA utomation database initiates FLIR for generating final SO Fault isolation and service restoration sub receives AdvancedDistributionA utomation database excerpts updated after additional fault isolation. Info ADADatabase FLIR Fault isolation and service restoration sub initiation after additional fault isolation ADADatabase FLIR AdvancedDistrib utionautomation database excerpts Volume II D29-95 Final Release

100 FLIR, ADAHistoricDa tabase a FLIR, a, DMS SCADA database Process/Activit y Fault isolation and service restoration sub generates list of recommend ed switching orders Fault isolation and service restoration sub generates list of recommend ed switching orders SO execution FLIR issues a report for archiving in AdvancedDistributionA utomation historic database. A list of recommended final switching orders is presented to the. In the advisory mode, the, after reviewing SO, issues supervisory commands to execute it. FLIR FLIR ADAHistoric Database DMS SCADA database Info Report including interrupted, unserved and restored load, and number of customers after additional fault isolation List of switching orders recommended after additional fault isolation Supervisory command to execute SO issued after additional fault isolation User Interface User Interface Volume II D29-96 Final Release

101 2.3.23b FLIR, DMS SCADA database Process/Activit y SO execution In the closed-loop mode, FLIR issues commands to execute SO. FLIR DMS SCADA database Info Supervisory command to execute SO issued after additional fault isolation FLIR Fault with Remotely-Controlled and Manual Switches and Distributed Intelligence (DIS) # Event Primary Actor Process/Activit y Info # Triggering event? Identify the name of the event. 10 What other actors are primarily responsible for the? Actors are defined in section1.5. Label that would appear in a process diagram. Use action verbs when naming activity. Describe the actions that take place in active and present tense. The step should be a descriptive noun/verb phrase that portrays an outline summary of the step. If Then Else scenarios can be captured as multiple Actions or as separate steps. What other actors are primarily responsible for Producing the information? Actors are defined in section1.5. What other actors are primarily responsible for Receiving the information? Actors are defined in section1.5. (Note May leave blank if same as Primary Actor) the information object. objects are defined in section 1.6 Elaborate architectural issues using attached spreadsheet. Use this column to elaborate details that aren t captured in the spreadsheet. Reference the applicable Environment containing this data exchange. Only one environment per step. 10 Note A triggering event is not necessary if the completion of the prior step leads to the transition of the following step. Volume II D29-97 Final Release

102 Process/Activit y Info 2.4.1a Fault with remotelycontrolled and manual switches and with DIS IEDs of DIS members, Distributed Intelligence Schemes DIS identifies relevant protective device, deenergized sections and probable fault location and finds service restoration solution Distributed Intelligence (DIS) receives the real-time local status and analog data. IEDs of DIS members Distributed Intelligence Schemes Real-time local status and analog data 2.4.2a Distributed Intelligence Schemes, IEDs of DIS members DIS identifies relevant protective device, deenergized sections and probable fault location and finds service restoration solution DIS communicates to DIS members the switching instructions for fault isolation and service restoration. Distributed Intelligence Schemes IEDS of DIS members Command to isolate fault and restore service to healthy sections. Volume II D29-98 Final Release

103 Process/Activit y Info 2.4.3a Distributed Intelligence Schemes, DMS SCADA database DIS identifies relevant protective device, deenergized sections and probable fault location and finds service restoration solution Changes in connectivity implemented by DIS are downloaded into DMS SCADA database. Distributed Intelligence Schemes DMS SCADA database Changes in connectivity implemented by DIS 2.4.4a DMS SCADA database, Checking real-time data receives the scan of DMS SCADA data to be checked for changes in topology. It also receives the latest relevant analog data. DMS SCADA database DMS real-time analog, status & TLQ data, phasor data from WAMACS 2.4.5a, topology update Checking real-time data ADATopologyUpdateSys tem receives the changes in connectivity implemented by DIS ADATopolog yupdatesyste m Changes in connectivity implemented by DIS 2.4.6a ADATopology Update, ADADatabase ADATopol ogyupdate changes connectivit y AdvancedDistributionAut omation database is updated with changes in connectivity implemented by DIS ADATopolog yupdatesyste m ADADatabas e Changes in connectivity implemented by DIS Volume II D29-99 Final Release

104 Process/Activit y Info 2.4.1b IEDs of DIS members, Distributed Intelligence Schemes DIS identifies relevant protective device, deenergized sections and probable fault location and can not find service restoration solution Distributed Intelligence (DIS) receives real-time local status and analog data. IEDs of DIS members Distributed Intelligence Schemes Real-time status and analog data 2.4.2b Distributed Intelligence Schemes, DMS SCADA database DIS identifies relevant protective device, deenergized sections and probable fault location and can not find service restoration solution Indication of DIS inability to find a solution is downloaded into DMS SCADA database. Distributed Intelligence Schemes DMS SCADA database Indication of DIS inability to find a solution Volume II D Final Release

105 Process/Activit y Info 2.4.3b DMS SCADA database, Checking real-time data Due to DIS inability to find a solution, AdvancedDistributionAut omation is initiated. DMS SCADA database Command to initiate AdvancedDistrib utionautomation, DMS real-time analog, status & TLQ data 2.4.4b OutageManage ment, Checking real-time data receives the scan of latest schedules of presently active or authorized for future outages to be checked for changes. OutageManag ement Schedules of presently active or authorized for future outages 2.4.5b EnergyManage ment SCADA database, Checking real-time data receives the scan of EnergyManagementSyste m SCADA data to be checked for relevant changes or events. EnergyManag ement SCADA database EnergyManagem ent realtime analog, status, TLQ data 2.4.6b Environmental daily data collector, Checking real-time data receives the scan of environmental data to be checked for changes affecting DER schedule forecast. Environmental daily data collector Real-time environmental data for DER schedule forecast Volume II D Final Release

106 2.4.7b Fault location, Process/Activit y Checking real-time data receives the distance to fault location, which is provided by fault-locating relay in the presence of the fault. Fault location Info Distance to fault location 2.4.8b, ADATopology Update ADATopol ogyupdate changes connectivit y After detects fault in distribution, relevant information is provided to topology. ADATopolog yupdatesyste m Circuit breaker lockouts, inputs from OutageManagem ent 2.4.9b ADATopology Update, ADADatabase ADATopol ogyupdate changes connectivit y After fault is detected, AdvancedDistributionAut omation database is updated. ADATopolog yupdatesyste m ADADatabas e Update of AdvancedDistrib utionautomation database b ADATopology Update, FLIR Fault location sub identifies faultrelated protective devices and deenergized sections Topology initiates fault location sub- of the FLIR. ADATopolog yupdatesyste m FLIR Fault location sub initiation Volume II D Final Release

107 2.4.11b ADADatabase, FLIR Process/Activit y Fault location sub identifies faultrelated protective devices and deenergized sections b FLIR Fault isolation and service restoration sub generates list of recommend ed switching orders Fault location sub receives the needed data from AdvancedDistributionAut omation database after it was updated with fault information. Fault location sub initiates fault isolation and service restoration sub- of the FLIR. ADADatabase Fault location FLIR Fault isolation and service restoration sub Info Excerpts from AdvancedDistrib utionautomation database updated after fault detection Fault isolation and service restoration sub initiation, probable fault location with alternatives Volume II D Final Release

108 2.4.13b ADADatabase, FLIR b FLIR, ADAHistoricD atabase Process/Activit y Fault isolation and service restoration sub generates list of recommend ed switching orders Fault isolation and service restoration sub generates list of recommend ed switching orders Fault isolation and service restoration sub receives AdvancedDistributionAut omation database excerpts updated with fault information. FLIR issues a report for archiving in AdvancedDistributionAut omation historic database. ADADatabase FLIR FLIR ADAHistoric Database Info AdvancedDistrib utionautomation database excerpts Report including interrupted, unserved and restored load, and number of customers before additional fault isolation Volume II D Final Release

109 2.4.15b FLIR, b, DMS SCADA database Process/Activit y Fault isolation and service restoration sub generates list of recommend ed switching orders SO execution A list of recommended switching orders is presented to the. In the advisory mode, the, after reviewing SO, issues a supervisory command to execute it. FLIR DMS SCADA database Info List of switching orders recommended after fault detection Supervisory command to execute SO issued after fault detection User Interface User Interface b, field crew informs field crew authorizes to patrol the faulted line to accurately locate fault. FieldPersonn el Authorization to patrol faulted line User Interface Volume II D Final Release

110 2.4.18b FieldPersonnel, b, b, ADADatabase b, FLIR Process/Activit y FieldPerso nnel informs Entering status of switches and faulted section into Advanced Distributio nautomati on database Entering status of switches and faulted section into Advanced Distributio nautomati on database After locating the fault, the crew informs the about the status of switches involved in additional switching to isolate the smallest possible faulted section. The enters status of switches (pseudostatuses) involved in final fault isolation and the faulted section into AdvancedDistributionAut omation database. Entering the faulted section into AdvancedDistributionAut omation database initiates FLIR FieldPersonne l ADADatabas e Info Status of switches involved in isolating the smallest possible faulted section AdvancedDistrib utionautomation database update additional fault isolation ADADatabase FLIR Fault isolation and service restoration sub initiation after additional fault isolation User Interface User Interface Volume II D Final Release

111 2.4.22b ADADatabase, FLIR b FLIR, ADAHistoricD atabase Process/Activit y Fault isolation and service restoration sub generates list of recommend ed switching orders Fault isolation and service restoration sub generates list of recommend ed switching orders Fault isolation and service restoration sub receives AdvancedDistributionAut omation database excerpts updated after additional fault isolation. FLIR issues a report for archiving in AdvancedDistributionAut omation historic database. ADADatabase FLIR FLIR ADAHistoric Database Info AdvancedDistrib utionautomation database excerpts Report including interrupted, unserved and restored load, and number of customers after additional fault isolation Volume II D Final Release

112 2.4.24b FLIR, b, DMS SCADA database Process/Activit y Fault isolation and service restoration sub generates list of recommend ed switching orders SO execution A list of recommended switching orders is presented to the. The, after reviewing SO, issues a supervisory command to execute it, if remotely controlled switches are used. If manual switches are involved, the dispatches the crew to implement the switching order. FLIR DMS SCADA database Info List of switching orders recommended after additional fault isolation Supervisory command to execute SO issued after additional fault isolation; instructions for the crew. User Interface User Interface FLIR Fault with DER Connected to Healthy Section Volume II D Final Release

113 Info # Triggering event? Identify the name of the event. 11 What other actors are primarily responsible for the? Actors are defined in section1.5. Label that would appear in a process diagram. Use action verbs when naming activity. Describe the actions that take place in active and present tense. The step should be a descriptive noun/verb phrase that portrays an outline summary of the step. If Then Else scenarios can be captured as multiple Actions or as separate steps. What other actors are primarily responsible for Producing the information? Actors are defined in section1.5. What other actors are primarily responsible for Receiving the information? Actors are defined in section1.5. (Note May leave blank if same as Primary Actor) the information object. objects are defined in section 1.6 Elaborate architectural issues using attached spreadsheet. Use this column to elaborate details that aren t captured in the spreadsheet. Reference the applicable Environment containing this data exchange. Only one environment per step Fault in a circuit with DER connected to healthy section cleared by fast circuit breaker trip and by reverse protection from DER fault injection creating a selfsufficient island DMS SCADA database, relay protection schemes, historic database Unintentional self-sufficient island is created receives the scan of DMS SCADA data and historic load data to be checked for changes in topology and loading during the time of repair. DMS SCADA database DMS real-time analog, status & TLQ data, phasor data from WAMACS 11 Note A triggering event is not necessary if the completion of the prior step leads to the transition of the following step. Volume II D Final Release

114 Info 2.5.2a Checking the sufficiency of the island during the time of repair determines the sufficiency of the island during the time of repair and enables FLIR for location of the fault within the deenergized section. FLIR Instructions to FLIR 2.5.2b Checking the sufficiency of the island during the time of repair determines the insufficiency of the island during the portion of time of repair and enables FLIR for location of the fault within the de-energized section and solving restoration for the customers connected to the island. FLIR Instructions to FLIR Volume II D Final Release

115 Info Fault in a circuit with DER connected to healthy section cleared by fast circuit breaker trip and by reverse protection from DER fault injection, creating an insufficien t island DMS SCADA database, relay protection schemes, historic database Unintentional insufficient island is created, DER is separated with or without balanced load receives the scan of DMS SCADA data and historic load data to be checked for changes in topology and loading during the time of repair. DMS SCADA database DMS real-time analog, status & TLQ data, phasor data from WAMACS Checking the sufficiency of the island during the time of repair determines the insufficiency of the island during the time of repair and enables FLIR for location of the fault within the deenergized section and solving restoration for the de-energized customers connected to the island. FLIR Instructions to FLIR Volume II D Final Release

116 Info Fault in a circuit with DER connected to healthy section cleared by circuit breaker and by relay protection of DER at the PCC DMS SCADA database, relay protection schemes, historic database The feeder is deenergized, DER is separated with or without balanced load receives the scan of DMS SCADA data and historic load data to be checked for changes in topology and loading during the time of repair. DMS SCADA database DMS real-time analog, status & TLQ data, phasor data from WAMACS Checking the topology to ensure that DER is sepaarted determines the after-fault topology, the loading during the time of repair, and enables FLIR for location of the fault and solving isolation of the fault and restoration for the de-energized customers connected to the healthy portions of the feeder. FLIR Instructions to FLIR Volume II D Final Release

117 2.3.1 Post-conditions and Significant Results Actor/Activity AdvancedDistributionAutomationSy stem: Fault location, Isolation and Restoration Post-conditions Description and Results Faulted section is identified. A solution for an optimal isolation of faulted portions of distribution feeder and restoration of services to healthy portions is provided to the operator; closed-loop execution of switching orders is available; outage time for the majority of customers is reduced to several minutes Diagrams Volume II D Final Release

118 Volume II D Final Release

119 Volume II D Final Release

120 Volume II D Final Release

121 Volume II D Final Release

122 Volume II D Final Release

123 2.3 Volt/Var Control (VVC) VVC Preconditions and Assumptions Describe conditions that must exist prior to the initiation of the Function, such as prior state of the actors and activities Identify any assumptions, such as what systems already exist, what contractual relations exist, and what configurations of systems are probably in place Identify any initial states of information exchanged in the steps in the next section. For example, if a purchase order is exchanged in an activity, its precondition to the activity might be filled in but unapproved. Actor///Contract Preconditions or Assumptions EnergyManagement SCADA EnergyManagement system contains the transmission power system model, and can provide the transmission connectivity information for facilities in the vicinity of the distribution power system facilities and with outputs from other EnergyManagement applications DMS SCADA database DistributionSCADA database is updated via remote monitoring and operator inputs.. Required scope, speed, and accuracy of real-time measurements are provided, supervisory and closed-loop ADADistributionOperationModeling and Analysis () control is supported. Preconditions: DistributionSCADA with several IEDs along distribution feeders, reporting statuses of remotely controlled switches and analogs including Amps, kw, kvar, and kv. s ability for updating the SCADA database with statuses of switches not monitored remotely. Substation SCADA with analogs and statuses from CBs exists. EnergyManagement is interfaced with AdvancedDistributionAutomation. AdvancedDistributionAutomation database is updated with the latest AM/FM and CIS data and operators input. The options for performance are selected AdvancedDistributionAutomation: Fault Location Preconditions: DistributionSCADA with fault detectors, Distribution Fault Location Isolation and Service Operation Model and Analysis with fault analysis, fault location relays (schemes) including high Restoration (FLIR) impedance relays and Some Distributed Intelligence schemes and Trouble call system exist. Fault Isolation and Service Restoration Preconditions: DistributionSCADA with ability to control a defined number of switching devices, Fault Location, Distribution Operation Model and Analysis, Voltage and Var Control for adjusting voltage and var after reconfiguration. Supervisory and closed-loop control of switches are available. Some Distributed Intelligence schemes exist. OutageManagement Outage Management is interfaced with SCADA and AdvancedDistributionAutomation EnergyManagement (WAMACS) and supports a dynamic topology model. EnergyManagement is interfaced with WAMACS and AdvancedDistributionAutomation and provides phasor data for all distribution (reference) buses. has AdvancedDistributionAutomation GUI and uses it for supervisory control of switches, for entering pseudo-scada statuses, selecting isolation and Volume II D Final Release

124 Actor///Contract AdvancedDistributionAutomationSyst em: Prearming of Remedial Action Schemes ADAHistoricDatabase AdvancedDistributionAutomation: MFR Preconditions or Assumptions restoration alternatives, etc. The operator also has the ability to communicate with the field crews via mobile communications and computing. AdvancedDistributionAutomation is interfaced with the RAS schemes with the capability of changing the priorities of RAS actions and settings. Historic database is able to store large amount of data about outages, which will be used by the outage statistic application and other users. Multi-feeder reconfiguration with ability to optimally select feeder(s) connectivity for a given objective VVC Steps Normal Sequence Describe the normal sequence of events, focusing on steps that identify new types of information or new information exchanges or new interface issues to address. Should the sequence require detailed steps that are also used by other s, consider creating a new sub, then referring to that subroutine in this. Remember that the focus should be less on the algorithms of the applications and more on the interactions and information flows between entities, e.g. people, systems, applications, data bases, etc. There should be a direct link between the narrative and these steps. The numbering of the sequence steps conveys the order and concurrency and iteration of the steps occur. Using a Dewey Decimal scheme, each level of nested procedure call is separated by a dot.. Within a level, the sequence number comprises an optional letter and an integer number. The letter specifies a concurrent sequence within the next higher level; all letter sequences are concurrent with other letter sequences. The number specifies the sequencing of messages in a given letter sequence. The absence of a letter is treated as a default 'main sequence' in parallel with the lettered sequences. Sequence 1: Sequence 2: Do step 1 1.2A.1 - In parallel to activity 2 B do step 1 1.2A.2 - In parallel to activity 2 B do step 2 1.2B.1 - In parallel to activity 2 A do step 1 1.2B.2 - In parallel to activity 2 A do step Do step nested step nested step 3.2 Volume II D Final Release

125 2.1 - Do step Do step VVC Function During Scheduled Run # Event Primary Actor Info # Triggering event? Identify the name of the event. 12 What other actors are primarily responsible for the? Actors are defined in section1.5. Label that would appear in a process diagram. Use action verbs when naming activity. Describe the actions that take place in active and present tense. The step should be a descriptive noun/verb phrase that portrays an outline summary of the step. If Then Else scenarios can be captured as multiple Actions or as separate steps. What other actors are primarily responsible for Producing the information? Actors are defined in section1.5. What other actors are primarily responsible for Receiving the information? Actors are defined in section1.5. (Note May leave blank if same as Primary Actor) the information object. objects are defined in section 1.6 Elaborate architectural issues using attached spreadsheet. Use this column to elaborate details that aren t captured in the spreadsheet. Reference the applicable Environment containing this data exchange. Only one environment per step Time for ADAVVC Controller scheduled run DMS SCADA database, Checking real-time data receives the scan of DMS SCADA data to be checked for changes in topology. It also receives the latest relevant analog data. DMS SCADA database DMS real-time analog, status & TLQ data, status of voltage controllers, DER modes of operation, and settings 12 Note A triggering event is not necessary if the completion of the prior step leads to the transition of the following step. Volume II D Final Release

126 Info EnergyManage ment SCADA database, 3.1.3, ADAVVCContr oller ADADatabase, ADAVVCContr oller ADAVVCContr oller, Checking real-time data VVC performs optimization according to current objective VVC performs optimization according to current objective VVC performs optimization according to current objective receives the scan of EnergyManagementSy stem SCADA data to be checked for relevant changes or events. The fact that no events and changes in connectivity are detected is communicated to ADAVVCController. ADAVVCController is triggered by the time schedule. VVC receives the excerpts from AdvancedDistribution Automation database. Relevant results of VVC optimization are displayed for the. EnergyManag ement SCADA database ADAVVCCo ntroller ADADatabase ADAVVCCo ntroller ADAVVCCon troller EnergyManagem ent realtime analog, status, TLQ data No events or changes in connectivity detected, command to start scheduled run Excerpts from AdvancedDistrib utionautomation database VVC status, present and recommended bus kv, benefits, expected lowest and highest load voltage User Interface Volume II D Final Release

127 Info ADAVVCContr oller, DMS SCADA database ADAVVCContr oller, ADAHistoricDa tabase VVC performs optimization according to current objective VVC performs optimization according to current objective Relevant results of VVC optimization are sent to controllers in the field. Relevant results of VVC optimization are stored in AdvancedDistribution Automation historic database. ADAVVCCon troller ADAVVCCon troller DMS SCADA database ADAHistoric Database Recommended settings to relevant voltage and power electronic controllers, DER modes of operation and settings, capacitor status VVC and LTC states and settings; VVC limits and benefits; losses, voltage, objective and total demand before and after optimization, logs DMS SCADA database, Checking real-time data receives the scan of DMS SCADA data to be checked for changes in topology and confirmation of execution of VVC commands. It also provides the latest relevant analog data. DMS SCADA database DMS real-time analog, status & TLQ data, status of voltage controllers, confirmation of execution of VVC commands Volume II D Final Release

128 Info DMS SCADA database, ADAVVCContr oller for s display is regularly updated with data associated with LTC and VVC performance. DMS SCADA database ADAVVCCo ntroller VVC: status, integrity, settings, limits, bandcenter, objective; LTC: status, position; bus voltage limits VVC Function During Event Run # Event Primary Actor Info # Triggeri ng event? Identify the name of the event. 13 What other actors are primarily responsible for the? Actors are defined in section1.5. Label that would appear in a process diagram. Use action verbs when naming activity. Describe the actions that take place in active and present tense. The step should be a descriptive noun/verb phrase that portrays an outline summary of the step. If Then Else scenarios can be captured as multiple Actions or as separate steps. What other actors are primarily responsible for Producing the information? Actors are defined in section1.5. What other actors are primarily responsible for Receiving the information? Actors are defined in section1.5. (Note May leave blank if same as Primary Actor) the information object. objects are defined in section 1.6 Elaborate architectural issues using attached spreadsheet. Use this column to elaborate details that aren t captured in the spreadsheet. Reference the applicable Environment containing this data exchange. Only one environment per step. 13 Note A triggering event is not necessary if the completion of the prior step leads to the transition of the following step. Volume II D Final Release

129 Info ADA VVC Contr oller during event run , , , , DMS SCADA database, SCADA EnergyManage ment database, , ADAVVCContr oller detects load voltage or overload violation Checking real-time data Checking real-time data Changing current objective to load reduction within normal limits due to high energy price detects load voltage or overload violation and initiates ADAVVCController. checks the real-time data for changes, alarms. checks the real-time data for changes, alarms. detects high-energy price and issues command to change VVC objective. DMS SCADA database SCADA EnergyManag ement database ADAVVCCo ntroller ADAVVCCo ntroller Command to initiate VVC DMS real-time analog, status, TLQ data, confirmation of execution of VVC commands, status of voltage controllers EnergyManagem ent realtime analog, status, TLQ data Command to change optimization objective Volume II D Final Release

130 Info , ADAVVCContr oller ADAVVCContr oller, ADADatabase ADAVVCContr oller, ADAVVCContr oller, DMS SCADA database VVC performs optimization according to current objective VVC performs optimization according to current objective VVC performs optimization according to current objective VVC performs optimization according to current objective issues command to initiate VVC. ADAVVCController receives excerpt from AdvancedDistributionA utomation database updated with latest SCADA scan. VVC issues information relevant for. DMS SCADA database receives results of optimization. ADADatabase ADAVVCCon troller ADAVVCCon troller ADAVVCCo ntroller ADAVVCCo ntroller DMS SCADA database Command to initiate VVC AdvancedDistrib utionautomation database excerpt VVC status, present and recommended bus kv, benefits, expected lowest and highest load voltages Recommended settings to relevant voltage and power electronic controllers, DER modes of operation and settings, capacitor status User Interface Volume II D Final Release

131 Info ADAVVCContr oller, ADAHistoricDa tabase ADAVVCContr oller, 3.2.7, VVC performs optimization according to current objective VVC performs optimization according to current objective performs analysis Selected results are archived in ADAHistoricDatabase. ADAVVCController initiates after confirmation of execution is received., after detecting a violation present during the afteroptimization conditions, sends alarm to. ADAVVCCon troller ADAVVCCon troller ADAHistoric Database VVC and LTC states and settings; VVC limits and benefits; losses, voltage, objective and total demand before and after optimization, logs Command to initiate Alarm for User Interface Volume II D Final Release

132 Info 3.2.8, Remedial Action Scheme, DMS SCADA database, 3.3.1, ADAVVCContr oller ADADatabase, ADAVVCContr oller Prearming RAS adjusts settings of relevant groups of load shedding Data for VVC determines violation can not be eliminated through optimization VVC determines violation can not be eliminated through optimization, after detecting that optimization has not eliminated transmission violation, sends an alarm to the and triggers pre-arming of RAS. Relevant for VVC and LTC settings, limits and statuses are displayed. detects load voltage or voltage violation. VVC receives excerpts from AdvancedDistributionA utomation database updated with latest SCADA scan. DMS SCADA database ADADatabase Remedial Action Scheme, ADAVVCCo ntroller ADAVVCCo ntroller for prearming Remedial Action Scheme VVC: status, integrity, settings, limits, bandcenter, objective LTC: status, position Command to initiate VVC Excerpts from AdvancedDistrib utionautomation database User Interface User Interface Volume II D Final Release

133 Info ADAVVCContr oller, MFR ADAVVCContr oller, ADAHistoricDa tabase 3.4.1, ADAVVCContr oller ADAVVCContr oller, DMS SCADA database VVC determines violation can not be eliminated through optimization VVC determines violation can not be eliminated through optimization detects distribution model inconsistency VVC switches to default settings for portions of distribution system with inconsistent model VVC initiates MFR to eliminate the violation. AdvancedDistributionA utomation historic database receives logs issued by VVC. After detecting distribution model inconsistency, sets an inconsistency flag to put VVC in a default mode. The fact that the VVC is switched to default setting has been issued is received by DMS SCADA database. ADAVVCCon troller ADAVVCCon troller ADAVVCCon troller MFR ADAHistoric Database ADAVVCCo ntroller DMS SCADA database Command to initiate MFR Logs Distribution model inconsistency flag Fact that VVC is switched to default setting Volume II D Final Release

134 Info ADAVVCContr oller, AdvancedDistri butionautomati on historic database DMS SCADA database, SCADA EnergyManage ment database, 3.5.3, ADAVVCContr oller VVC switches to default settings for portions of distribution system with inconsistent model Checking real-time data Checking real-time data VVC determines there is room for optimization and performs optimization within emergency limits Log is stored in AdvancedDistributionA utomation historic database. checks the real-time data for changes, alarms. checks the real-time data for changes, alarms. detects transmission emergency limit violation and issues a command to initiate VVC. ADAVVCCon troller DMS SCADA database SCADA EnergyManag ement database ADAHistoric Database ADAVVCCo ntroller Log DMS real-time analog, status, TLQ data, confirmation of execution of VVC commands, status of voltage controllers EnergyManagem ent realtime analog, status, TLQ data Command to initiate VVC Volume II D Final Release

135 Info ADADatabase, ADAVVCContr oller ADAVVCContr oller, ADAVVCContr oller, DMS SCADA database VVC determines there is room for optimization and performs optimization within emergency limits VVC determines there is room for optimization and performs optimization within emergency limits VVC determines there is room for optimization and performs optimization within emergency limits VVC receives excerpts from AdvancedDistributionA utomation database updated with latest SCADA scan. Selected optimization results are displayed for the. DMS SCADA database receives relevant optimization results. ADADatabase ADAVVCCon troller ADAVVCCon troller ADAVVCCo ntroller DMS SCADA database Excerpts from AdvancedDistrib utionautomation database VVC status, present and recommended bus kv, expected lowest and highest load V, flag of using emergency limits Recommended settings to relevant voltage and power electronic controllers, DER modes of operation and settings, capacitors status User Interface Volume II D Final Release

136 Info ADAVVCContr oller, ADAHistoricDa tabase ADAVVCContr oller, 3.5.9, VVC determines there is room for optimization and performs optimization within emergency limits VVC determines there is room for optimization and performs optimization within emergency limits performs analysis Selected results are archived in AdvancedDistributionA utomation historic database. ADAVVCController initiates after confirmation of execution is received., after detecting a violation present during the afteroptimization conditions, sends alarm to. ADAVVCCon troller ADAVVCCon troller ADAHistoric Database VVC and LTC states and settings; VVC limits and benefits; losses, voltage, objective and total demand before and after optimization, logs Command to initiate Alarm for User Interface Volume II D Final Release

137 Info , Prearming of RAS schemes DMS SCADA database, Prearming RAS adjusts settings of relevant groups of load shedding Data for, after detecting that optimization has not eliminated transmission violation, sends an alarm to pre-arming RAS. Relevant for VVC and LTC settings, limits, and statuses are displayed. DMS SCADA database Prearming of RAS schemes Alarm for prearming RAS VVC: status, integrity, settings, limits, bandcenter, objective LTC: status, position User Interface VVC Function Participation in Severe Emergency in Bulk Power with Intentional Islands # Event Primary Actor Info # Triggering event? Identify the name of the event. 14 What other actors are primarily responsible for the? Actors are defined in section1.5. Label that would appear in a process diagram. Use action verbs when naming activity. Describe the actions that take place in active and present tense. The step should be a descriptive noun/verb phrase that portrays an outline summary of the step. If Then Else scenarios can be captured as multiple Actions or as separate steps. What other actors are primarily responsible for Producing the information? Actors are defined in section1.5. What other actors are primarily responsible for Receiving the information? Actors are defined in section1.5. (Note May leave blank if same as Primary Actor) the information object. objects are defined in section 1.6 Elaborate architectural issues using attached spreadsheet. Use this column to elaborate details that aren t captured in the spreadsheet. Reference the applicable Environment containing this data exchange. Only one environment per step. 14 Note A triggering event is not necessary if the completion of the prior step leads to the transition of the following step. Volume II D Final Release

138 Info The bulk power system is separated in nearbalanced islands to prevent wide-area blackout. The load shedding schemes operated Remedial Action Scheme, intentional islanding, Underfrequency load shedding (UFLS), Undervoltage load shedding, Special load shedding schemes Creating transmission islands, and load-shedding by fast acting schemes The conditions of capacity deficit are detected by EnergyManagement /SCADA and submitted to VVC as a trigger for changing the objective and perform in emergency mode. Transmission EnergyManag ement, Remedial Action Scheme. AdvancedDis tributionauto mationsyste m load management s Command to initiate VVC in load reduction mode; commands from VVC to IEDs and DERs SCADA EnergyMan agementsy stem database Contingency in bulk power system creates transmission islands SCADA EnergyManagement receives status of switches (circuit breakers) in transmission affected by contingency. Transmission EnergyManag ement, Remedial Action Scheme. SCADA EnergyMana gementsyste m database Status of switches Volume II D Final Release

139 Info UFLS, DMS SCADA database UFLS balances load and generation and changes distribution circuits connectivity DMS SCADA database receives status of switches affected by load shedding. FieldDevice DMS SCADA database Status of switches DMS SCADA database, Update of the topology and load models receives the latest scan of DMS SCADA database and adjusts the distribution operation model for VVC to perform in emergency load reduction mode.. DMS SCADA database DMS real-time analog, status, TLO data, status of voltage controllers , ADAVVC Controller Changing VVC current objective to load reduction within emergency limits issues a command to change VVC objective and initiate optimization. ADAVVCCo ntroller Command to change VVC objective and optimization Volume II D Final Release

140 Info ADAVVC Controller VVC performs optimization with emergency load reduction objective VVC performs reduction of load not affected by loadshedding schemes to create capacity reserves and restore a portion of shed loads. ADAVVCCon troller DMS SCADA database Settings for voltage controllers, statuses of capacitors, power electronics statuses of DER, modes of operation and settings of DER controllers Post-conditions and Significant Results Describe conditions that must exist at the conclusion of the Function. Identify significant items similar to that in the preconditions section. Describe any significant results from the Function Actor/Activity Post-conditions Description and Results AdvancedDistributionAutomationSy Optimal voltage controller settings, capacitor statuses and DER modes of operation and settings, stem: Volt-var Control for a given objective(s) are sent to respective controllers. The power quality is enhanced. The distribution facilities are better utilized; the transmission and generation systems are better supported by volt and vars; the load management is less intrusive; the customers pay smaller bills. Volume II D Final Release

141 2.3.4 Diagrams Volume II D Final Release

142 Volume II D Final Release

143 Volume II D Final Release

1 Description of Methodology for Volt / Var Optimization

1 Description of Methodology for Volt / Var Optimization Methodology for Volt / Var Optimization on a Substation Basis May 13th, 2011 Version 1.7 1 Methodology for Volt / Var Optimization (VVO) on a Substation Basis This use case discusses how the utility will

More information

HIGH LEVEL REQUIREMENTS OF FAST SIMULATION AND MODELLING SUITE OF TOOLS FOR FUTURE SELF-HEALING DISTRIBUTION POWER SYSTEM

HIGH LEVEL REQUIREMENTS OF FAST SIMULATION AND MODELLING SUITE OF TOOLS FOR FUTURE SELF-HEALING DISTRIBUTION POWER SYSTEM HIGH LEVEL REQUIREMENTS OF FAST SIMULATION AND MODELLING SUITE OF TOOLS FOR FUTURE SELF-HEALING DISTRIBUTION POWER SYSTEM A. Valenti* I Bel ** S. Lee *EDF **EPRI E2I ConEdison France USA USA arnaud.valenti@edf.fr

More information

SurvalentONE Distribution Management System

SurvalentONE Distribution Management System SurvalentONE Distribution Management System Analyze & Optimize Critical Grid Functions for Advanced System Monitoring & Control SurvalentONE ADMS The SurvalentONE ADMS platform is a fully integrated SCADA,

More information

BC Hydro s Voltage and VAR Optimization Program IEEE PES JTCM VVC TF - 13 Jan 2010

BC Hydro s Voltage and VAR Optimization Program IEEE PES JTCM VVC TF - 13 Jan 2010 BC Hydro s Voltage and VAR Optimization Program IEEE PES JTCM VVC TF - 13 Jan 2010 Prepared by: Valentina Dabic P.Eng, Distribution Operations Planning Cheong Siew P.Eng, Smart Grid Development BC Hydro

More information

Smart Distribution Technology

Smart Distribution Technology Smart Distribution Technology Presentation Agenda Alabama Power Company, A Southern Company Distribution Automation Supervisory Control And Data Acquisition (SCADA) Multiple Address System (MAS) communications

More information

Sacramen Sacr t amen o t Municipal Utility Dis t Dis rict t SMUD May Ma 10,

Sacramen Sacr t amen o t Municipal Utility Dis t Dis rict t SMUD May Ma 10, Sacramento Municipal Utility District SMUD May 10, 2010 1 SMUD Facts and Figures 900 Sq. Miles Service Area 585,500 Customers 1.4 million Area Population 10 Bulk Substations 473 Miles of Transmission Lines

More information

USE CASE 14 CONTROLLED ISLANDING

USE CASE 14 CONTROLLED ISLANDING I USE CASE 14 CONTROLLED ISLANDING Use Case Title Centralized application separates grid into islands to prevent blackout Use Case Summary Controlled islanding is a method that can significantly improve

More information

Volt/VAR Control Options and How to Leverage AMI Data

Volt/VAR Control Options and How to Leverage AMI Data By Tom Helmer, Executive Consultant and Joseph Sottnik, P.E., Project Manager, Black & Veatch Published in the August 2012 issue of PowerGrid International Energy efficiency and operational optimization

More information

What You Should Know About Communication Systems: Business Strategies and Options

What You Should Know About Communication Systems: Business Strategies and Options Doug Voda, PPMV Global Segment Leader for Smart Grid February 2015 NRECA TechAdvantage What You Should Know About Communication Systems: Business Strategies and Options The visionary Smart Grid Five Pillars

More information

EMS / DMS. DISTRIBUTION MANAGEMENT SYSTEM- Functional Description

EMS / DMS. DISTRIBUTION MANAGEMENT SYSTEM- Functional Description EMS / DMS DISTRIBUTION MANAGEMENT SYSTEM- Content 1. INTRODUCTION... 4 2. MODES OF INTERACTION WITH THE SCADA SYSTEM... 5 2.1 Simulation Mode... 5 2.2 State Estimation Mode (See functional description

More information

This webinar brought to you by the Relion product family

This webinar brought to you by the Relion product family This webinar brought to you by the Relion product family Relion. Thinking beyond the box. Designed to seamlessly consolidate functions, Relion relays are smarter, more flexible and more adaptable. Easy

More information

Small Generator Interconnection System Impact Study Report. Completed For Q0047

Small Generator Interconnection System Impact Study Report. Completed For Q0047 Small Generator Interconnection Completed For Q0047 Proposed Interconnection PacifiCorp s Existing Goshen Rigby 69 kv Line March 7, 2005 1.0 Description of the Generation Facility Q0047 ( Interconnection

More information

OC IEEE IAS/PES Meeting February 21, 2013

OC IEEE IAS/PES Meeting February 21, 2013 San Diego International Airport: Building For The Future, Through Underground Distribution Automation and SCADA OC IEEE IAS/PES Meeting February 21, 2013 1 Presenter: Randy Denton, PE Under Ground Utility

More information

IntelliTeam II Automatic Restoration System

IntelliTeam II Automatic Restoration System No system is too complex to automate with... IntelliTeam II Automatic Restoration System Introduced in 1997, the IntelliTeam Automatic Restoration System was the first product of its kind. Using peer-to-peer

More information

EPRI GIS Interest Group GIS Data Correction

EPRI GIS Interest Group GIS Data Correction EPRI GIS Interest Group GIS Data Correction The Southern Company Serve 4.4 Million Retail Customers Generating Capacity : 42,000 MW 120,000 Square Miles Alabama Power Company Serves 1,431,334 Customers

More information

EPRI Research Plan for Advanced Distribution Automation. Mark McGranaghan Vice President EPRI Solutions, Inc

EPRI Research Plan for Advanced Distribution Automation. Mark McGranaghan Vice President EPRI Solutions, Inc Photo EPRI Research Plan for Advanced Distribution Automation Mark McGranaghan Vice President EPRI Solutions, Inc Frank R. Goodman, Jr. Technical Lead: Distribution Automation Electric Power Research Institute

More information

MONITORING AND CONTROL REQUIREMENTS FOR DISTRIBUTED GENERATION FACILITIES

MONITORING AND CONTROL REQUIREMENTS FOR DISTRIBUTED GENERATION FACILITIES MONITORING AND CONTROL REQUIREMENTS FOR DISTRIBUTED GENERATION FACILITIES 1. Introduction Real time monitoring and control is necessary to ensure public and employee safety and to protect the integrity

More information

FAULT DETECTION ISOLATION AND RESTORATION ON THE FEEDER (FDIR): PICK YOUR TECHNOLOGY

FAULT DETECTION ISOLATION AND RESTORATION ON THE FEEDER (FDIR): PICK YOUR TECHNOLOGY FAULT DETECTION ISOLATION AND RESTORATION ON THE FEEDER (FDIR): PICK YOUR TECHNOLOGY Fahrudin Mekic Ken Alloway Cleber Angelo Robert Goodin ABB Inc. USA ABB Inc. USA ABB Inc. USA ABB Inc. USA fahrudin.mekic@us.abb.com.ken.alloway@us.abb.com

More information

WECC Criterion MOD-(11 and 13)-WECC-CRT-1.1

WECC Criterion MOD-(11 and 13)-WECC-CRT-1.1 WECC Criterion MOD-(11 and 13)-WECC-CRT-1.1 A. Introduction 1. Title: Steady State and Dynamic Data Requirements 2. Number: MOD-(11 and 13)-WECC-CRT-1.1 3. Purpose: To establish the consistent data requirements

More information

Status and Next Steps NARUC Electricity Committee Hank Courtright, Senior VP July 15, 2014

Status and Next Steps NARUC Electricity Committee Hank Courtright, Senior VP July 15, 2014 Status and Next Steps NARUC Electricity Committee Hank Courtright, Senior VP July 15, 2014 2014 Electric Power Research Institute, Inc. All rights reserved. Meet the Challenge An Integrated Grid 2 Interconnected

More information

SOUTH TEXAS ELECTRIC COOPERATIVE, INC.

SOUTH TEXAS ELECTRIC COOPERATIVE, INC. SOUTH TEXAS ELECTRIC COOPERATIVE, INC. P.O. Box 119 Nursery, Texas 77976 (361) 575-6491 Fax (361) 576-1433 Transmission Interconnection Requirements Table of Contents I. Introduction II. Interconnection

More information

Pepco s Plans for Smart Grid. Rob Stewart Blueprint Technology Strategist

Pepco s Plans for Smart Grid. Rob Stewart Blueprint Technology Strategist Pepco s Plans for Grid Rob Stewart Blueprint Technology Strategist 0 Pepco s Grid Vision Through the Grid, customers will become empowered to make choices regarding their use and cost of energy. It will

More information

A Data Approach to Advanced Distribution Management Systems. L. WILKE, B. WALL POWER Engineers USA

A Data Approach to Advanced Distribution Management Systems. L. WILKE, B. WALL POWER Engineers USA 21, rue d Artois, F-75008 PARIS CIGRE US National Committee http : //www.cigre.org 2017 Grid of the Future Symposium A Data Approach to Advanced Distribution Management Systems L. WILKE, B. WALL POWER

More information

Evolution of Control for the Power Grid

Evolution of Control for the Power Grid Evolution of Control for the Power Grid Anjan Bose Washington State University Pullman, WA, USA PaiFest In Honor of Prof. M. A. Pai Urbana-Champaign, IL October 15, 2015 The Past (before 1960s) Hard

More information

Network Planning for Smart Grid

Network Planning for Smart Grid Network Planning for Smart Grid UTC Telecom 2009 June 3, 2009 David Boroughs Experience you can trust. Objectives Smart Grid Architecture Overview Network Planning & Dimensioning Aspects Network Performance

More information

The various functions of an energy control center can be enumerated as under: 1. Load forecasting 6. Automatic generation control

The various functions of an energy control center can be enumerated as under: 1. Load forecasting 6. Automatic generation control ENERGY CONTROL CENTERS To generated, Transmission and Distribution system, Number of customers and Total investment. Installed capacity in India exceeds 206 GW with annual energy generated energy exceeding

More information

DISRIBUTED AUTOMATION FOR BACK-FEED NETWORK POWER RESTORATION

DISRIBUTED AUTOMATION FOR BACK-FEED NETWORK POWER RESTORATION DISRIBUTED AUTOMATION FOR BACK-FEED NETWORK POWER RESTORATION Fahrudin Mekic Zhenyuan Wang Vaibhav Donde Fang Yang James Stoupis ABB Inc. USA ABB Inc. USA ABB Inc. USA ABB Inc. USA ABB Inc. USA fahrudin.mekic@us.abb.com

More information

SDG&E s EPIC Demonstration Projects on Emerging Communication Standards. IEC Europe 2017 Conference. Frank Goodman, SDG&E EPIC Program Manager

SDG&E s EPIC Demonstration Projects on Emerging Communication Standards. IEC Europe 2017 Conference. Frank Goodman, SDG&E EPIC Program Manager SDG&E s EPIC Demonstration Projects on Emerging Communication Standards Frank Goodman, SDG&E EPIC Program Manager IEC 61850 Europe 2017 Conference September 26-28, 2017 2017 San Diego Gas & Electric Company.

More information

Blackout 101. Dr. B. Don Russell Texas A&M University. Dr. Bruce Wollenberg University of Minnesota. Mr. John McDonald KEMA, Inc.

Blackout 101. Dr. B. Don Russell Texas A&M University. Dr. Bruce Wollenberg University of Minnesota. Mr. John McDonald KEMA, Inc. Blackout 101 Dr. B. Don Russell Texas A&M University Dr. Bruce Wollenberg University of Minnesota Mr. John McDonald KEMA, Inc. Dr. Pete Sauer University of Illinois at Urbana-Champaign An Electric Power

More information

Monitor Your Distribution Grid

Monitor Your Distribution Grid Connected Energy Grid Management Improve reliability measures (SAIDI, SAIFI, CAIDI) Focus reliability improvements where they are needed most Improve volt/var control Optimize voltage for CVR Reduce outage

More information

Approval...6. Current Revision...7. Introduction... 8 About PJM Manuals... 8 About This Manual... 8 Using This Manual...9

Approval...6. Current Revision...7. Introduction... 8 About PJM Manuals... 8 About This Manual... 8 Using This Manual...9 PJM Manual 07: PJM Protection Standards Revision: 3 Effective Date: May 24, 2018 Prepared by System Planning Division Transmission Planning Department PJM 2018 Table of Contents Table of Contents Approval...6

More information

AUTOMATION OF POWER DISTRIBUTION USING SCADA

AUTOMATION OF POWER DISTRIBUTION USING SCADA 1 2 ABSTRACT In every substation certain measurements, supervision, control, operation and protection functions are necessary. Traditionally these functions were performed manually by system operator from

More information

Vermont Outage Coordination and Planning

Vermont Outage Coordination and Planning Vermont Outage Coordination and Planning Objectives Convey VELCO s role within NE and VT for outage coordination Review VELCO and VT utility outage coordination process Identify outage scheduling challenges,

More information

Maximizing protection coordination with self-healing technology

Maximizing protection coordination with self-healing technology Supersedes December 2011 Daniel P. Roth, Distribution Automation Technical Manager, Eaton s Cooper Power Systems Abstract Much of the Smart Grid initiative includes the installation of new recloser and

More information

Network Configuration Document Selection for New Substations Framework

Network Configuration Document Selection for New Substations Framework Network Configuration Document Selection for New Substations Current version: 20/06/2018 EXTERNAL USE Page 1 of 14 Table of contents 1. Introduction... 3 1.1 Purpose... 3 1.2 Scope... 3 1.3 References...

More information

IMS INTERFACE MARKET PROCEDURE NETWORK OPERATORS AND AEMO

IMS INTERFACE MARKET PROCEDURE NETWORK OPERATORS AND AEMO IMS INTERFACE MARKET PROCEDURE NETWORK OPERATORS AND AEMO PREPARED BY: System Management (WA) DOCUMENT REF: SO_OP_WA_3805 VERSION: 1.0 EFFECTIVE DATE: 13/10/2017 STATUS: FINAL Approved for distribution

More information

Concept White Paper. Concepts for Proposed Content of Eventual Standard(s) for Project : Real-Time Monitoring and Analysis Capabilities

Concept White Paper. Concepts for Proposed Content of Eventual Standard(s) for Project : Real-Time Monitoring and Analysis Capabilities Concept White Paper Concepts for Proposed Content of Eventual Standard(s) for Project 2009-02: Real-Time Monitoring and Analysis Capabilities Real-time Monitoring and Analysis Capabilities Standard Drafting

More information

Shabnam Rukhsar Electrical Engineering Department, Anjuman College of Engineering and Technology.India

Shabnam Rukhsar Electrical Engineering Department, Anjuman College of Engineering and Technology.India SCADA in Transmission Line Shabnam Rukhsar Electrical Engineering Department, Anjuman College of Engineering and Technology.India ABSTRACT: Transmission line equivalent circuit parameters are often 25%

More information

Glencoe Light and Power

Glencoe Light and Power Glencoe Light and Power REQUIREMENTS FOR GENERATION, TRANSMISSION, AND END-USER FACILITY INTERCONNECTIONS 1 Table of Contents Page I. INTRODUCTION...5 A. Authority... 5 B. Objectives...5 C. Interconnection

More information

2018 General Rate Case. Transmission & Distribution (T&D) Volume 3 R System Planning

2018 General Rate Case. Transmission & Distribution (T&D) Volume 3 R System Planning Application No.: Exhibit No.: Witnesses: A.1-0- SCE-0, Vol. 0 R E. Takayesu A (U -E) 01 General Rate Case Transmission & Distribution (T&D) Volume R System Planning Before the nd Errata Public Utilities

More information

Smart Grid Operations - Combining the Power of Smart Meters and The Control Room ADMS

Smart Grid Operations - Combining the Power of Smart Meters and The Control Room ADMS Smart Grid Operations - Combining the Power of Smart Meters and The Control Room ADMS United Energy case study Andrew Steer Manager - Network Control Centre Support United Energy Bradley Williams, P.E.

More information

Distribution Management System Open++ Opera v.3.3. User Manual

Distribution Management System Open++ Opera v.3.3. User Manual Distribution Management System Open++ Opera v.3.3 User Manual 1MRS 751464-MUM Issued: 31.12.1999 Version: D/29.8.2003 Program Revision: 3.3D We reserve the right to change data without prior notice. User

More information

SCADA and Central Applications An introduction

SCADA and Central Applications An introduction SCADA and Central Applications An introduction Course map Outline of the lecture Power System Operation - Centralised Control Applications SCADA - SCADA architecture & Components - SCADA system functions

More information

Advanced Protection and Control Technologies for T&D Grid Modernization

Advanced Protection and Control Technologies for T&D Grid Modernization Advanced Protection and Control Technologies for T&D Grid Modernization i-pcgrid Workshop San Francisco, CA March 31, 2016 Jeff Shiles, Principal Manager Protection & Automation Engineering Southern California

More information

Automation in Large Urban Power Distribution System. Dr. K Rajamani CENTRAL TECHNICAL SERVICES, RELIANCE ENERGY LIMITED, MUMBAI

Automation in Large Urban Power Distribution System. Dr. K Rajamani CENTRAL TECHNICAL SERVICES, RELIANCE ENERGY LIMITED, MUMBAI Automation in Large Urban Power Distribution System Dr. K Rajamani CENTRAL TECHNICAL SERVICES, RELIANCE ENERGY LIMITED, MUMBAI Need for Automation and Current trends Automation Systems and Functionality

More information

Southern Company Smart Grid

Southern Company Smart Grid Southern Company Smart Grid Smart Grid Investment Grant Update July 25, 2011 Southern Company Southern Company is one of the nations largest generators of electricity Has 4.4 million retail customers across

More information

Chapter 2 State Estimation and Visualization

Chapter 2 State Estimation and Visualization Chapter 2 State Estimation and Visualization One obvious application of GPS-synchronized measurements is the dynamic monitoring of the operating conditions of the system or the dynamic state estimation

More information

Solutions for transmission network management

Solutions for transmission network management EM SG SOLutions Solutions for transmission network management Energy Management Smart Grid Solutions Solutions for Transmission Network Management Overview Operator Training Simulator Blackout Prevention

More information

Application of Distributed Intelligence to Automatic Distribution Reconfiguration for Reliability Improvement

Application of Distributed Intelligence to Automatic Distribution Reconfiguration for Reliability Improvement Application of Distributed Intelligence to Automatic Distribution Reconfiguration for Reliability Improvement Doug Staszesky Director Product Management Automation Systems Division S&C Electric Company

More information

Small Generator Interconnection Facilities Study Report. Completed for Q0314 ( Interconnection Customer ) A Qualified Facility

Small Generator Interconnection Facilities Study Report. Completed for Q0314 ( Interconnection Customer ) A Qualified Facility Small Generator Interconnection Completed for Q0314 ( Interconnection Customer ) A Qualified Facility Proposed Interconnection PacifiCorp s 34.5-kV West Cedar Substation December 29, 2010 TABLE OF CONTENTS

More information

ONLINE CLOSED-LOOP OPTIMIZATION OF DISTRIBUTION NETWORKS

ONLINE CLOSED-LOOP OPTIMIZATION OF DISTRIBUTION NETWORKS ONLINE CLOSED-LOOP OPTIMIZATION OF DISTRIBUTION NETWORKS Werner FEILHAUER Michael HEINE Andreas SCHMIDT PSI AG, EE DE PSI AG, EE DE PSI AG, EE - DE wfeilhauer@psi.de mheine@psi.de aschmidt@psi.de ABSTRACT

More information

Introduction: Model Relationships Network Model Overview Example Commercial Model Overview Component Hierarchy & Definitions Example of Structure

Introduction: Model Relationships Network Model Overview Example Commercial Model Overview Component Hierarchy & Definitions Example of Structure 1 2 3 Introduction: Model Relationships Network Model Overview Example Commercial Model Overview Component Hierarchy & Definitions Example of Structure MISO Functions Served by the Network Model by the

More information

Substation SCADA Monitoring

Substation SCADA Monitoring Substation SCADA Monitoring Contact us Today for a FREE quotation to deliver this course at your company?s location. https://www.electricityforum.com/onsite-training-rfq Substations are a critical component

More information

ELG4125: System Protection

ELG4125: System Protection ELG4125: System Protection System Protection Any power system is prone to 'faults', (also called short-circuits), which occur mostly as a result of insulation failure and sometimes due to external causes.

More information

Loop Automation. Technical Manual for the ADVC Controller Range

Loop Automation. Technical Manual for the ADVC Controller Range Loop Automation Technical Manual for the ADVC Controller Range Contents List of Figures 5 List of Tables 7 Acronyms 7 Symbols 7 Introduction 8 About this Manual 8 ADVC Controller Firmware Version 9 WSOS

More information

High and Medium Voltage Substation Design, Testing and Maintenance. KSA, Jeddah, Holiday Inn Jeddah Gateway Hotel.

High and Medium Voltage Substation Design, Testing and Maintenance. KSA, Jeddah, Holiday Inn Jeddah Gateway Hotel. Training Course : High and Medium Voltage Substation Design, Testing and Maintenance Training Course For One Week In KSA, Jeddah, Holiday Inn Jeddah Gateway Hotel Which Be Held As Under Details : Tel.

More information

Siemens FuseSaver New half-cycle circuit breaker for rural smart grids to minimize operating costs of feeder and spur lines

Siemens FuseSaver New half-cycle circuit breaker for rural smart grids to minimize operating costs of feeder and spur lines Siemens FuseSaver New half-cycle circuit breaker for rural smart grids to minimize operating costs of feeder and spur lines Authors: Dr. Brett Watson, Siemens Ltd., PO Box 4833, Loganholme, QLD 4129, Australia

More information

Smart Solutions Smarter Grid

Smart Solutions Smarter Grid Smart Solutions Smarter Grid Optimizing Efficiency, Productivity, and Reliability Stef.Budai@CooperIndustries.com Consultant Grid Automation FECA Conference 2012 Contents Why the Smart Grid? Utility Industry

More information

Disclaimer Executive Summary Introduction Overall Application of Attachment Generation Transmission...

Disclaimer Executive Summary Introduction Overall Application of Attachment Generation Transmission... CIP-002-4 Cyber Security Critical Cyber Asset Identification Rationale and Implementation Reference Document September, 2010 Table of Contents TABLE OF CONTENts Disclaimer... 3 Executive Summary... 4 Introduction...

More information

Digital Transformation of Power Delivery

Digital Transformation of Power Delivery Digital Transformation of Power Delivery Keynote Speech Professor Saifur Rahman, PhD Virginia Tech, USA IEEMA Engineer Infinite Conference, Delhi NCR, India, 14 March 2018 Traditional Electricity Delivery

More information

Standard Development Timeline

Standard Development Timeline Standard Development Timeline This section is maintained by the drafting team during the development of the standard and will be removed when the standard becomes effective. Description of Current Draft

More information

DUKE ENERGY OHIO SMART GRID / GRID MODERNIZATION. Don Schneider GM, Smart Grid Field Deployment May 24, 2012

DUKE ENERGY OHIO SMART GRID / GRID MODERNIZATION. Don Schneider GM, Smart Grid Field Deployment May 24, 2012 DUKE ENERGY OHIO SMART GRID / GRID MODERNIZATION Don Schneider GM, Smart Grid Field Deployment May 24, 2012 FACTS ABOUT DUKE ENERGY 150+ years of service 4 million customers Fortune 500 $50 billion in

More information

EMS-LECTURE 2: WORKING OF EMS

EMS-LECTURE 2: WORKING OF EMS EMS-LECTURE 2: WORKING OF EMS Introduction: Energy Management systems consists of several applications programs which are used by the operator in a control centre for effective decision making in the operation

More information

g Energy Multilin Voltage Regulator Controller DGCV KEy BENEFITS APPLICATIONS FEATURES Metering & Monitoring Voltage Regulation Communications

g Energy Multilin Voltage Regulator Controller DGCV KEy BENEFITS APPLICATIONS FEATURES Metering & Monitoring Voltage Regulation Communications Multilin Voltage Regulator DGCV KEy BENEFITS Increases grid efficiency by optimizing voltage regulation Through deployment of the Volt/VAR system, the Multilin DGCV: - Enables up to a 6% reduction in energy

More information

November 29, ECE 421 Session 28. Utility SCADA and Automation. Presented by: Chris Dyer

November 29, ECE 421 Session 28. Utility SCADA and Automation. Presented by: Chris Dyer ECE 421 Session 28 November 29, 2018 Utility SCADA and Automation Presented by: Chris Dyer Utility SCADA & Automation Chris Dyer, P.E. BSEE University of Idaho, 1997 SCADA & Automation Engineer POWER Engineers,

More information

SPECIFIC INTERCONNECTION PROTECTION REQUIREMENTS... 5

SPECIFIC INTERCONNECTION PROTECTION REQUIREMENTS... 5 Central Hudson Gas & Electric Corporation (CHG&E) Interconnection Protection Requirements for Distributed Generators of Greater than 300 kva Connected in Parallel with the CHG&E Electrical Delivery System

More information

Distributor Thoughts on Smart Grid

Distributor Thoughts on Smart Grid Distributor Thoughts on Smart Grid Sylvia Smith Budget & Rates Manager Tony Richman Meter Services Manager-Smart Grid 1 Agenda Introduction Smart Grid Program Strategy & Technical Aspects Financial Considerations

More information

MONTANA-DAKOTA UTILITIES REQUIREMENTS FOR GENERATION, TRANSMISSION, AND END-USER FACILITY INTERCONNECTIONS

MONTANA-DAKOTA UTILITIES REQUIREMENTS FOR GENERATION, TRANSMISSION, AND END-USER FACILITY INTERCONNECTIONS MONTANA-DAKOTA UTILITIES REQUIREMENTS FOR GENERATION, TRANSMISSION, AND END-USER FACILITY INTERCONNECTIONS Table of Contents I. Introduction... 5 A. Authority... 5 B. Objectives... 5 C. Interconnection

More information

Small Generator Interconnection Facilities Study Report. Completed for. ( Interconnection Customer ) Proposed Interconnection Pavant substation

Small Generator Interconnection Facilities Study Report. Completed for. ( Interconnection Customer ) Proposed Interconnection Pavant substation Small Generator Interconnection Facilities Study Report Completed for ( Interconnection Customer ) Proposed Interconnection Pavant substation Original report dated February 17, 2016 Revised March 11, 2016

More information

IMPROVING POWER SYSTEM RELIABILITY USING MULTIFUNCTION PROTECTIVE RELAYS

IMPROVING POWER SYSTEM RELIABILITY USING MULTIFUNCTION PROTECTIVE RELAYS IMPROVING POWER SYSTEM RELIABILITY USING MULTIFUNCTION PROTECTIVE RELAYS Armando Guzmán Schweitzer Engineering Laboratories, Inc. Pullman, WA 99163 A reliable power system maintains frequency and voltage

More information

CIP Cyber Security Critical Cyber Asset Identification. Rationale and Implementation Reference Document

CIP Cyber Security Critical Cyber Asset Identification. Rationale and Implementation Reference Document CIP-002-4 Cyber Security Critical Cyber Asset Identification Rationale and Implementation Reference Document NERC Cyber Security Standards Drafting Team for Order 706 December 2010 This document provides

More information

ITC Facility Connection Requirements for Generation, Transmission and End-User Facilities Connected to the ITC Holdings Transmission Systems

ITC Facility Connection Requirements for Generation, Transmission and End-User Facilities Connected to the ITC Holdings Transmission Systems ITC Facility Connection Requirements for Generation, Transmission and End-User Facilities Connected to the ITC Holdings Transmission Systems Category: Planning Type: Policy Eff. Date/Rev. # 06/19/2017

More information

BEFORE THE ARKANSAS PUBLIC SERVICE COMMISSION

BEFORE THE ARKANSAS PUBLIC SERVICE COMMISSION BEFORE THE ARKANSAS PUBLIC SERVICE COMMISSION IN THE MATTER OF THE FORMULA ) RATE PLAN FILINGS OF OKLAHOMA GAS ) GAS AND ELECTRIC COMPANY ) DOCKET NO. -0-FR PURSUANT TO APSC DOCKET ) NO. -0-U ) Direct

More information

REAL-TIME MONITORING DATA SPECIFICATION

REAL-TIME MONITORING DATA SPECIFICATION REAL-TIME MONITORING DATA SPECIFICATION Version 1 December 9, 2016 Revision History Version Date Reviewer Revisions 1 11/1/16 Mansion Hudson Initial document 1 Contents 1. DOCUMENT REVIEW... 3 2. DEFINITIONS...

More information

Real-time Power System Operation. Energy Management Systems. Introduction

Real-time Power System Operation. Energy Management Systems. Introduction 1 Real-time Power System Operation Energy Management Systems Introduction The time frame for Power Systems Operation varies from a few seconds to a week. To assist with the operation of the system, modern

More information

DNP Points List and Implementation

DNP Points List and Implementation S&C IntelliRupter PulseCloser Fault Interrupter Outdoor Distribution (15.5 kv, 27 kv, and 38 kv) DNP Points List and Implementation Table of Contents Section Page Section Page Introduction...1 Status Points...2

More information

INTEGRATION OF RECLOSERS INTO SCADA SYSTEMS

INTEGRATION OF RECLOSERS INTO SCADA SYSTEMS INTEGRATION OF RECLOSERS INTO SCADA SYSTEMS Konstantine Kolevatov, AS Tavrida Electric Export It has become a major task to provide uninterrupted electricity supply to customers and minimize the outage

More information

Proposal for Development and Use of Node- Breaker Topology Representations for Offline and Real-time Study Models November 12, 2013

Proposal for Development and Use of Node- Breaker Topology Representations for Offline and Real-time Study Models November 12, 2013 Proposal for Development and Use of Node- Breaker Topology Representations for Offline and Real-time November 12, 2013 Rationale Background Interconnection wide powerflow and dynamics cases are currently

More information

SIGMA. Advanced Generator Protection and Control. Short Form Catalogue

SIGMA. Advanced Generator Protection and Control. Short Form Catalogue Short Form Catalogue SIGMA Advanced Generator Protection and Control Generator protection, synchronizing and load sharing Power management system Easy to install and commission Control most governors/avrs

More information

AUTOMATION OF DISTRIBUTION KIOSKS TECHNICAL AND FINANCIAL EVALUATION - "TYPICAL CASE STUDY"

AUTOMATION OF DISTRIBUTION KIOSKS TECHNICAL AND FINANCIAL EVALUATION - TYPICAL CASE STUDY AUTOMATION OF DISTRIBUTION KIOSKS TECHNICAL AND FINANCIAL EVALUATION - "TYPICAL CASE STUDY" Mohamed Khaled El-Sayed Alexandria Electricity Distribution Company - AEDC Egypt khaled_mks@hotmail.com 1-INTRODUCTION

More information

Smart Grid Vision DRAFT FOR DISCUSSION PURPOSES ONLY

Smart Grid Vision DRAFT FOR DISCUSSION PURPOSES ONLY Smart Grid Vision Vision Statement PG&E s vision for the Smart Grid: Smart Grid will leverage advanced communications and control technology to transform the operation of our electric network, from generation

More information

Standard Development Timeline

Standard Development Timeline Standard Development Timeline This section is maintained by the drafting team during the development of the standard and will be removed when the standard becomes effective. Description of Current Draft

More information

Interconnection and Transmission

Interconnection and Transmission Interconnection and Transmission Gary L. Brown, P.E. Director of Energy Development Gary@ZGlobal.biz 916-985-9461 Kevin Coffee Energy Management Committee Meeting Irvine, California August 26, 2015 Interconnection

More information

Supplemental Information

Supplemental Information Retirement of NPCC Directory# 3 Supplemental Information On April 1, 2015, NPCC Directory# 3 was retired upon the effective date of PRC-005-2 Protection System Maintenance which is subject to a 12 year

More information

Flexible High-Speed Load Shedding Using a Crosspoint Switch

Flexible High-Speed Load Shedding Using a Crosspoint Switch Flexible High-Speed Load Shedding Using a Crosspoint Switch Will Allen and Tony Lee Schweitzer Engineering Laboratories, Inc. Published in Wide-Area Protection and Control Systems: A Collection of Technical

More information

PRC Coordination of Protection Systems for Performance During Faults

PRC Coordination of Protection Systems for Performance During Faults PRC-027-1 Coordination of Protection Systems for Performance During Faults A. Introduction 1. Title: Coordination of Protection Systems for Performance During Faults 2. Number: PRC-027-1 3. Purpose: To

More information

October 05, ECE 421 Session 12. Utility SCADA and Automation. Presented by: Chris Dyer

October 05, ECE 421 Session 12. Utility SCADA and Automation. Presented by: Chris Dyer ECE 421 Session 12 October 05, 2017 Utility SCADA and Automation Presented by: Chris Dyer Utility SCADA & Automation Chris Dyer, P.E. BSEE University of Idaho, 1997 SCADA & Automation Engineer POWER Engineers,

More information

Evolution of Control for the Power Grid

Evolution of Control for the Power Grid Evolution of Control for the Power Grid Anjan Bose Washington State University Pullman, Washington, USA University of Seville Seville, Spain June 17, 2016 THE INTERCONNECTED GRID Economics Transfer electric

More information

Data Concentration of 7000 Distribution Devices to Facilitate Asset Optimization with the PI System

Data Concentration of 7000 Distribution Devices to Facilitate Asset Optimization with the PI System Data Concentration of 7000 Distribution Devices to Facilitate Asset Optimization with the PI System Presented by Alan Lytz System Architect PPL Electric Utilities HQ: Allentown Pennsylvania USA 1.4 million

More information

IMS INTERFACE MARKET PROCEDURE NETWORK OPERATORS AND AEMO

IMS INTERFACE MARKET PROCEDURE NETWORK OPERATORS AND AEMO IMS INTERFACE MARKET PROCEDURE NETWORK OPERATORS AND AEMO PREPARED BY: System Management (WA) DOCUMENT REF: SO_OP_WA_3805 VERSION: 1.0 EFFECTIVE DATE: 13/10/2017 STATUS: DRAFT FOR CONSULTATION Approved

More information

Generation, Transmission, and End User Facilities

Generation, Transmission, and End User Facilities Procedures for Interconnection of Generation, Transmission, and End User To the Grand River Dam Authority Transmission System Table of Contents GRDA/SPP Interaction... 3 Standards... 3 Generation... 3

More information

Residential/Commercial/Industrial

Residential/Commercial/Industrial Thank You For Purchasing the BASIC POWER UNIT from the team! 120 Marshalls Creek Road East Stroudsburg, PA 18302 570-872-9666 Residential/Commercial/Industrial IF YOU EXPERIENCE A PROBLEM WITH YOUR PURCHASE,

More information

Revised Generation Interconnection Impact Study Report. For. Queue Position 31 ( Interconnection Customer )

Revised Generation Interconnection Impact Study Report. For. Queue Position 31 ( Interconnection Customer ) Revised Generation Interconnection Impact Study Report For Queue Position 31 ( Interconnection Customer ) September 22, 2004 1 Generation Interconnection System Impact Study Report I. Revision of Original

More information

Toronto Hydro-Electric System Limited EB Exhibit G1 Tab 1 Schedule 1 ORIGINAL Page 1 of 15 SMART GRID PLAN

Toronto Hydro-Electric System Limited EB Exhibit G1 Tab 1 Schedule 1 ORIGINAL Page 1 of 15 SMART GRID PLAN EB-00-0 Exhibit G Tab Schedule Page of 0 SMART GRID PLAN INTRODUCTION This Exhibit presents THESL s plans for development of the smart grid in keeping with the Green Energy and Green Economy Act, 00 (

More information

Data and Forecasting Summary

Data and Forecasting Summary Data and Forecasting Summary This article highlights the need for more integrated and aligned data systems within WPD and improved interfaces within the industry. It also looks at the increased need for

More information

Road Map to Grid Modernization

Road Map to Grid Modernization Road Map to Grid Modernization APIC, University of Alberta May 5 th, 2016 Presenter: Chris Chapelsky, MSc., P.Eng. Operations 1 Engineer About EPCOR Water & Power Transmission & Distribution in Edmonton

More information

System Engineer Configures IEC Gateway to DNP3 Substation

System Engineer Configures IEC Gateway to DNP3 Substation 1 Description of Function 1.1 Function Name System Configures to DNP3 System Configures to DNP3 1.2 Function ID DNP3-IEC6850-2 1.3 Brief Description Given DNP-XML Device Profiles for a substation automation

More information

Fortum SGEM Program Presentation of ongoing research activities

Fortum SGEM Program Presentation of ongoing research activities Fortum SGEM Program Presentation of ongoing research activities MV and LV Network Automation Solutions in EU Benchmarking Research 1 Existing Distribution Grid Little change in the past few decades Mostly

More information

Awareness of the Situation

Awareness of the Situation 17/11/21 Situational Awareness UPDEA - Workshop Awareness of the Situation 25,623 Alarms in 8 ours 53 Alarms / min (average) 8% Are consequential Things 1 to keep in mind during a disturbance - Analog

More information

Transmission Register PTO Admin User Manual. Version 1.0

Transmission Register PTO Admin User Manual. Version 1.0 Transmission Register PTO Admin User Manual Version 1.0 Table of Contents 1. INTRODUCTION... 3 1.1. Purpose...3 1.2. Scope...3 1.3. Definitions...3 2. COMPONENTS HOMEPAGE... 6 2.1. Find Components...6

More information