Metasys BACnet System Integrator (BSI) Monitoring

Size: px
Start display at page:

Download "Metasys BACnet System Integrator (BSI) Monitoring"

Transcription

1 Metasys Connectivity Technical Manual Metasys BACnet System Integrator Section Issue Date 73 TECHNICAL BULLETIN Metasys BACnet System Integrator (BSI) Monitoring Monitoring the BSI Communicator...2 Introduction... 2 Key Concepts... 3 Software Architecture Review... 3 BSI Viewer Menu Bar and Toolbar... 4 BACnet Communicator Application Statistics... 7 Datalink Statistics... 9 Object Mapping PC Protocol Engine Statistics... 2 Notification Class Objects (NCOs) Procedure Overview Detailed Procedures Viewing Mapped BACnet Object Cache Data Viewing BACnet Communicator Application Statistics Viewing Datalink Statistics Viewing PC Protocol Engine Statistics Viewing Notification Class Object Data Troubleshooting... 3 Error Log File... 3 Enable Debug Johnson Controls, Inc. Code No. LIT

2 2 Metasys BACnet System Integrator Monitoring the BSI Communicator Introduction Monitoring involves viewing communication statistics stored within the Metasys BACnet System Integrator (BSI) Communicator by accessing the various screens of the BSI Viewer. The BSI Viewer provides the means to verify that communication is taking place between the Metasys and BACnet systems; therefore, it can only be accessed if the BSI Communicator is running. The BSI Viewer aids in troubleshooting by displaying possible communication inconsistencies. BACnet data that appears in the BSI Viewer and also in the NCM means that communication between the systems is successful and that information is being relayed. This document describes how to: view mapped BACnet object cache data view BACnet Communicator Application Statistics view Datalink Statistics view PC Protocol Engine Statistics view Notification Class Object (NCO) data

3 Metasys BACnet System Integrator (BSI) Monitoring 3 Key Concepts Software Architecture Review The BSI software consists of the BSI Communicator, the BSI Configurator, and the BSI Viewer. As the main component of the BSI software, the BSI Communicator relays and translates information between the Metasys system and the BACnet system. The BSI Configurator is a software support tool for the BSI Communicator. It is used for initial BSI Communicator setup, which includes: defining which Metasys points will be available to foreign BACnet devices defining which BACnet points will be available to the Metasys system setting system parameters in the Metasys device object mapping priority differences between Metasys and BACnet systems establishing a data table for the different ways Engineering units are represented in Metasys and BACnet systems configuring the BSI Communicator s broadcast management feature setting up BACnet event notification for Metasys points The BSI Configurator provides separate user screens for each of these aspects. Data entered on these screens build databases that the BSI Communicator uses when communicating between Metasys and BACnet systems. For more information regarding the BSI Configurator refer to the Metasys BACnet System Integrator (BSI) Commissioning Technical Bulletin (LIT ) in the Metasys Connectivity Technical Manual (FAN 629.5).

4 4 Metasys BACnet System Integrator The BSI Viewer is another software support tool for the BSI Communicator. It provides the means to verify that communication is taking place between the Metasys and BACnet systems. This is done by allowing data about the communication process, stored within the BSI Communicator, to be viewed. The viewable data includes: information relating to the interaction between databases and the creation of original read and write messages information regarding the transmitting and receiving of messages runtime point statistics of the BSI Communicator s cache of BACnet points mapped into Metasys information relating to the acknowledging of messages information on the BSI Notification Class Objects (NCOs) BSI Viewer Menu Bar and Toolbar Each screen of the BSI Viewer has a Menu bar. Options to select the screen type and write a database to disk exist on the File menu. Only the Object Mapping screen has an active toolbar because multiple pieces of information can be viewed from that screen. Table 1 describes the available features and the method to access them. Table 1: Viewer Feature Options Task File Menu Option Menu Bar Option Select screen type. Type - - Write a running database. Write - - Exit the Viewer. Exit - - Rebind a BACnet object. - Rebind - Go to the first BACnet point in the database. - - Toolbar Button First Go to the previous BACnet point in the database. Continued on next page First Prev Prev

5 Metasys BACnet System Integrator (BSI) Monitoring 5 Task (Cont.) Go to the next BACnet point in the database. Go to the last BACnet point in the database. File Menu Option Menu Bar Option Toolbar Button Next Next Last Search backward in the database. - - Search forward in the database. - - Last? Find FindL Find? FindR Write Command On the File menu, the Write submenu lists the different databases used by the BSI Communicator. Choosing one of the databases from this list tells the BSI Communicator to write the current runtime database to the directory determined by the Metasys.ini FMSDATA parameter setting, where it overwrites the existing database file. When the system is running well and all points are online with valid data, use the Write command to save the images of the databases at the current state. The BSI Communicator can use the saved images of the databases to restart quickly with valid default data.

6 6 Metasys BACnet System Integrator Rebind Command The Rebind command applies to only the BACnet object being viewed last in the Viewer and tells the BSI Communicator to do three things: Remember the information specified in the BSI Configurator for the object being viewed in the BSI Viewer. Eliminate any information it might have found in the initial (or subsequent) auto-configuration for the object being viewed in the BSI Viewer (e.g., BSI Configurator fields marked Find from name ). Re-interrogate the system to relearn the information not supplied in the BSI Configurator for the object being viewed in the BSI Viewer. By asking the BSI Communicator to relearn unspecified data fields with the Rebind command, changes in point information are reflected in the running database. To make these changes permanent, perform the Write command for BACnet Object Mapping after Rebinding (relearning) is complete. Clear Stats and Done Command A Done button, Clear Stats button, or both appear on most of the BSI Viewer screens. The Done button closes the current display and redisplays the Object Mapping screen. Clicking the Clear Stats button zeros (clears) the information from the fields within the BSI Communicator. Use this button in a situation where statistics need to be collected from a known point in time (e.g., over a 24-hour period, overnight, or when certain events occur). This eliminates the need of writing down prior values and subtracting them from the new values. In addition, if the commissioning of the BSI Communicator results in numerous errors, the user may want to clear those error counts from the BSI Viewer afterward and then verify the information in the BSI Viewer once the system is running.

7 Metasys BACnet System Integrator (BSI) Monitoring 7 BACnet Communicator Application Statistics The statistics on the BACnet Communicator Application Statistics screen (Figure 1) show the interaction between databases and information relating to the creation of original read and write messages. Table 2 describes this screen s fields. BACnet Communicator Application Statistics - BACnet System Integrator File Rebind View Help First Prev Next Last? Find Find? BACNet Communicator Summary Status Last Scan 1/7/98 9:17:51 Prev Scan 1/7/98 9:17:18 Last Cleared 1/5/ :22:7 Metasys Communication Summary Read Requests Failed Read Req Write Requests Failed Write Req Read Requests Failed Read Req Write Requests Failed Write Req BACNet Communication Summary Failed Cmds Msg Decode Errors Objects Not Found Unsup. Properties Failed Read Prop. Msg Decode Errors Objects Not Found Unsup. Properties 'Other' Failures Clear Stats Done Ready NUM CAS Figure 1: BACnet Communicator Application Statistics BACnet System Integrator Screen

8 8 Metasys BACnet System Integrator Table 2: Field Descriptions - BACnet Communicator Application Statistics Section Field Name Description BACnet Communicator Summary Status Metasys Communication Summary BACnet Communication Summary Last Scan Prev Scan Last Cleared Read Requests Failed Read Req Write Requests Failed Write Req Failed Cmds Msg Decode Errors Objects Not Found Unsup. Properties Read Requests Failed Read Req Write Requests Failed Write Req Failed Read Prop. Msg Decode Errors Objects Not Found Unsup. Properties Other Failures Time stamp of last request to complete a scan of BACnet points. Last time stamp before update appeared in Last Scan. Difference between Last Scan and Prev Scan should be close to the Min Polling Time Interval on the System Setup screen in the BSI Configurator. Time stamp when these statistics were last cleared. Number of BACnet reads sent to the Metasys system. Number of BACnet reads sent to the Metasys system that failed. Number of Metasys writes and commands attempted. Number of Metasys write attributes sent that came back with an error or attempts to write attributes that are read only. Number of failed Metasys commands. Number of BACnet messages sent to Metasys points that could not be decoded. Number of times a BACnet message referenced a Metasys object that the BSI Communicator could not locate in the BSI database. Number of errors from attempts to read an unsupported property. Number of BACnet reads sent. Number of BACnet reads that came back with an error. Number of BACnet writes sent. Number of BACnet writes that came back with an error. Number of individual BACnet property read that failed. Number of BACnet replies to BSI Communicator requests that could not be decoded. Number of times a BACnet message sent from the BSI Communicator referenced an object that the BACnet device could not locate. Number of attempts by the BSI Communicator to read an unsupported property on a BACnet object. Can also occur while the BSI Communicator is learning which optional properties are supported by each BACnet object. Miscellaneous BACnet errors.

9 Metasys BACnet System Integrator (BSI) Monitoring 9 Datalink Statistics The Datalink puts BACnet message packets on and or takes them off the Ethernet card, if they arrive or need to be sent. There are two BACnet Datalink Statistics screens (Figure 2 and Figure 3), and you choose the appropriate screen from the Type submenu on the File menu according to the type of transport protocol used on the BACnet network (Raw Ethernet ISO or BACnet/IP). Each screen shows information regarding the transmitting and receiving of BACnet message packets. Each BACnet message can consist of one or more packets depending on its size. Note that the two screens are the same except for the additional section on the Raw Ethernet ISO screen. Table 3 describes the fields on these screens. BACnet Datalink Statistics - BACnet System Integrator File Rebind View Help First Prev Next Last? Find Find? Datalink Summary Status Last Cleared 1/5/ :22:12 Base Datalink Summary Msg Transmits Msg Received Broadcast Msg Transmits Broadcast Msg Received Retries Transmit Failures Datalink 8823 Summary DLC Xmit Frames DLC Recv Frames Buffers Free Now Least Buffers Free Recv Data Lost Ethernet Errors Discarded Frames Critical Exceptions DLC Data Lost Segments Lost Before Signup Clear Stats Done Ready NUM DS Figure 2: BACnet Datalink Statistics BACnet System Integrator Screen

10 1 Metasys BACnet System Integrator BACnet/IP Datalink Statistics - BACnet System Integrator File Rebind View Help First Prev Next Last? Find Find? Datalink Summary Status Last Cleared 5/ 1/ 2 14:22:12 Base Datalink Summary Msg Transmits Msg Received Broadcast Msg Transmits Broadcast Msg Received Retries Transmit Failures Clear Stats Done Ready NUM DS_BACIP Figure 3: BACnet/IP Datalink Statistics BACnet System Integrator Screen Note: If you display the wrong screen for the type of transport protocol used on the BACnet network, all of the statistics fields contain zeros ().

11 Metasys BACnet System Integrator (BSI) Monitoring 11 Table 3: Field Descriptions - Datalink Statistics Section Field Name Description Datalink Summary Last Cleared Time stamp when these statistics were last cleared. Status Base Datalink Msg Transmits Number of message packets transmitted. Summary Msg Received Number of message packets received. Broadcast Msg Transmits Number of broadcast message packets sent. Broadcast Msg Received Number of broadcast message packets received. Retries Number of retries (not used for Ethernet). Transmit Failures Number of failures in message packet transmits. Datalink 8823 DLC Xmit Frames Number of DLC Xmit frames put on the Ethernet card. Summary DLC Recv Frames Number of DLC Recv frames taken off the Ethernet card. Buffers Free Now Number of empty receive buffers available at current time. Least Buffers Free Lowest number of empty receive buffers reached since the statistics were last cleared. Recv Data Lost Indicates how many received data frames were lost. Ethernet Errors Number of errors indicated by the Ethernet card. Discarded Frames Number of frames that the Ethernet card eliminated. Critical Exceptions Emergency alarm - Any number besides zero in this field indicates a major communication problem occurred. DLC Data Lost Indicates how many data frames were lost. Segments Lost Before Signup The number of message frames the datalink did not know where to relay because initialization was not complete when they arrived. These were discarded.

12 12 Metasys BACnet System Integrator Object Mapping After accessing the BSI Viewer, the BACnet Object Mapping screen may be displayed. This screen provides a view of the BSI Communicator s cache of BACnet points mapped into the Metasys system. The various points can be moved through using the buttons on the toolbar. The screen changes according to the different types of points (device object, analog, binary, and multistate) being viewed. The first point is a dummy device object entry. It is used as a placeholder and always has the reference number of zero. Figures 4 through 7 show the various screen types. Tables 4 through 7 list descriptions of the various fields on each screen. Note: BACnet Object Mapping - BACnet System Integrator File Rebind View Help First Prev Next Last? Find Find? Initially, a blank white screen appears. Bypass this screen by using the toolbar buttons to begin moving through the viewable points. BACNet Device Object Configuration Object ID 8:5 Ref. No. 1 Name MACCR Metasys Configuration System MACCR Information Object Name Offline Expanded ID Last Update 1/7/98 8:29:1 Offline [no. of no-replies] 3 Segmentation Support 3 Max. No. of Segments 4 Max. APDU Seg. Size 1476 Address / Network No. 28 / 2 Object No. First Point 2 Status Code Total No. of No-replies Device Service Values Known Supports (who-has and who-is) User Specified Max. Msg. Size Object Types Supported Analog Value Analog Output Analog Input Ready Services Supported Auto Write File Write Property Write Property Mult Delete Object Create Object Remove List Element Add List Element Auto Read File Read Property Read Property Mult Read Property Cond Get Enrollment Summary Get Alarm Summary Subscribe COV Binary Value Binary Output Binary Input Config COV Notification Config Text Message Config Private Transfer Config Event Notification vt Data vt Open vt Close Notification Class Multistate Output Multistate Input Loop Group File Unconfig COV Notification Unconfig Text Message Unconfig Private Transfer Unconfig Event Notification Reinitialize Device Device Comm Control Acknowledge Alarm Command Calendar Schedule Device Program Event Enrollment I Have I Am Who Is Who Has Request Key Authenticate Time Synchronization Done NUM OMDO Figure 4: BACnet Object Mapping (Device Object) BACnet System Integrator Screen

13 Metasys BACnet System Integrator (BSI) Monitoring 13 Table 4: Field Descriptions - Device Object Section Field Name Description BACnet Device Object Configuration Metasys Configuration Information Services Supported Object Types Supported Object ID Ref. No. Name System Object Name Expanded ID Offline Last Update Offline (no. of no-replies) Segmentation Support Max. No. of Segments Max. APDU Seg. Size Address/Network No. Object No. of First Point Status Code Total No. of No-replies Device Service Values Known Supports (who-has and who-is) User Specified Max. Msg. Size See Figure 4. See Figure 4. The number to the left of the decimal point is the BACnet code for the object type. The number to the right of the decimal point is the BACnet code for the instance number. Internal index number used to identify the object entry in the BSI Communicator error log files. BACnet object name. Metasys system name where the mapped BACnet point resides. Metasys object name for the mapped BACnet object. Metasys expanded ID derived from BACnet object. Indicates if the BSI Communicator thinks this object is offline. Time stamp of when the value was last successfully read. Number of unsuccessful reads before the device object and associated points are flagged offline. BACnet code for segmentation level supported. Number of segments that can combine to determine the maximum message size (if message segmentation is supported). Maximum size a single message segment can be. MAC address/bacnet network number for the BACnet device object. Reference number of the first point associated with this device. BACnet device status returned by this device object. Number of failures to get a valid reply since last valid reply. Indicates if the Services Supported section has been successfully read from the device. Indicates if this device supports Who-has and Who-is. If checked, indicates that the Max. APDU Seg. Size was entered by the person configuring the system. If not checked, indicates the Max. APDU Seg. Size that can be handled by the device object. List of standard services in BACnet object. Ones checked are services that the device object says it can handle. List of standard object types for BACnet. Ones checked are object types that the device object says it can handle. Those not checked are not supported.

14 14 Metasys BACnet System Integrator BACnet Object Mapping - BACnet System Integrator File Rebind View Help First Prev Next Last? Find Find? BACNet Analog Object Configuration Object ID :1 Ref. No. 2 Name Room_Temperature Metasys Configuration System MACCR Unit 64 Object Name Expanded ID M_RT_ Room_Temperature Status Offline Last Update 1/7/98 8:34:41 Present Value High Alarm Limit. Low Alarm Limit. Relinquish Default. In Alarm Unreliable In Override Done Ready Figure 5: BACnet Object Mapping (Analog Object) BACnet System Integrator Screen NUM OMAO

15 Metasys BACnet System Integrator (BSI) Monitoring 15 Table 5: Field Descriptions - Analog Object Section Field Name Description BACnet Analog Object Configuration Metasys Configuration Status Object ID Ref. No. Name System Object Name Expanded ID Unit Offline Last Update Present Value High Alarm Limit Low Alarm Limit Relinquish Default In Alarm Unreliable In Override The number to the left of the decimal point is the BACnet code for the object type. The number to the right of the decimal point is the BACnet code for the instance number. Internal index number used to identify the object entry in the BSI Communicator error log files. BACnet object name. Metasys system name where the mapped BACnet point resides. Metasys object name for the mapped BACnet object. Metasys expanded ID derived from BACnet object. BACnet enumeration number for the BACnet unit used by this Analog point. Indicates if the BSI Communicator thinks this object is offline. Time stamp of when the present value was last successfully read. Present value last read. High alarm limit properties last read, if any. Low alarm limit properties last read, if any. Last relinquish default read, if any. Indicates if the BACnet point status is reporting alarm. Indicates unreliable status determined by BACnet object. Indicates if the BACnet point is in override.

16 16 Metasys BACnet System Integrator BACnet Object Mapping - BACnet System Integrator File Rebind View Help First Prev Next Last? Find Find? BACNet Binary Object Configuration Object ID 3:2 Ref. No. 22 Name Valve_Jam_Alarm Metasys Configuration System MACCR Object Name Expanded ID H_VJA Valve_Jam_Alarm Status Offline Last Update 1/7/98 8:37:1 Delay Value Units Text 1 Units Text 2 OFF ON Value Alarm State Polarity Relinquish Default In Alarm Unreliable In Override Done Ready Figure 6: BACnet Object Mapping (Binary Object) BACnet System Integrator Screen NUM OMBO

17 Metasys BACnet System Integrator (BSI) Monitoring 17 Table 6: Field Descriptions - Binary Object Section Field Name Description BACnet Binary Object Configuration Metasys Configuration Status Object ID Ref. No. Name System Object Name Expanded ID Offline Last Update Delay Value Units Text 1 Units Text 2 Value Alarm State Polarity Relinquish Default In Alarm Unreliable In Override The number to the left of the decimal point is the BACnet code for the object type. The number to the right of the decimal point is the BACnet code for the instance number. Internal index number used to identify the object entry in the BSI Communicator error log files. BACnet object name. Metasys system name where the mapped BACnet point resides. Metasys object name for the mapped BACnet object. Metasys expanded ID derived from BACnet object. Indicates if the BSI Communicator thinks this object is offline. Time stamp of when the present value was last successfully read. BACnet alarm delay value, if there is one. BACnet point inactive (State) text. BACnet point active (State1) text. Checkmark indicates point is active (State1). No checkmark indicates point is inactive (State). Indicates if point is in alarm state at BACnet object. Indicates reverse action on means off. Default inactive/active state when all priorities are released. Indicates if the BACnet point status is reporting alarm. Indicates unreliable status determined by BACnet object. Indicates if the BACnet point is in override.

18 18 Metasys BACnet System Integrator BACnet Object Mapping - BACnet System Integrator File Rebind View Help First Prev Next Last? Find Find? BACnet Multistate Object Configuration Object ID Name 13:1 Ref. No. 88 MODE Metasys Configuration System Object Name Expanded ID XL MODE Chiller Mode Status Offline Last Update 1/7/98 8:1:15 Delay Value 1 Units Text 1 OFF Present Value 2 Relinquish Default 1 Units Text 2 Units Text 3 RUN STDBY In Alarm Unreliable In Override Feedback Value 2 Units Text 4 No of States 3 Ready... NUM OMMS Figure 7: BACnet Object Mapping (Multistate Object) BACnet System Integrator Screen

19 Metasys BACnet System Integrator (BSI) Monitoring 19 Table 7: Field Descriptions - Multistate Object Section Field Name Description BACnet Multistate Object Object ID The number to the left of the decimal point is the BACnet code for the object type. The number to the right of the decimal point is the BACnet code for the instance number. Configuration Ref. No. Internal index number used to identify the object entry in the BSI Communicator error log files. Name BACnet object name. Metasys System Metasys system name where the mapped BACnet point resides. Configuration Object Name Metasys object name for the mapped BACnet object. Expanded ID Metasys expanded ID derived from BACnet object. Status Offline Indicates if the BSI Communicator thinks this object is offline. Last Update Time stamp of when the present value was last successfully read. Delay Value BACnet alarm delay value, if there is one. Present Value Present value of state the BACnet point is in. Relinquish Indicates default inactive/active state when all priorities are released. Default Feedback Value Indicates associated feedback with this point, if there is any. No of States Indicates the number of states that this multistate claims it can have. Units Text 1 Indicates text for State 1. Units Text 2 Indicates text for State 2. Units Text 3 Indicates text for State 3. Units Text 4 Indicates text for State 4. In Alarm Indicates if the BACnet point status is reporting alarm. Unreliable Indicates unreliable status determined by BACnet object. In Override Indicates if the BACnet point is in override.

20 2 Metasys BACnet System Integrator PC Protocol Engine Statistics The BACnet PC Protocol Engine screen (Figure 8) shows information about acknowledging BACnet messages. The Application Layer section shows data regarding the creation and analysis of BACnet messages. The BACNL section shows data pertaining to BACnet datalink tasks. Table 8 describes this screen s fields. BACnet PC Protocol Engine - BACnet System Integrator File Rebind View Help First Prev Next Last? Find Find? PC Protocol Engine Summary Status Last Cleared 1/ :22:12 Application Layer Transmit Confirmed Reqs 9625 Segment Reqs Complex Acks Seg Complex Acks Simple Acks Receive Confirmed Reqs Segment Reqs Complex Acks Seg Complex Acks Segment Acks Unconfirms 1 Errors Rejects Aborts Simple Acks Segment Acks Unconfirms Errors 33 Segments Local Aborts Request Retries 7129 Segment Retries Rejects Aborts Segments BACNL Datalink Msg Rcv Datalink Msg Txt Unknown Routes 1142 Unknown Msg Rcv Rejects Rcv Route Busy 9988 Clear Stats Done Ready NUM Figure 8: BACnet PC Protocol Engine BACnet System Integrator Screen PCProto

21 Metasys BACnet System Integrator (BSI) Monitoring 21 Table 8: Field Descriptions PC Protocol Engine Section Field Name Description PC Protocol Engine Last Cleared Time stamp when these statistics were last cleared. Summary Status Application Layer Transmit Confirmed Reqs Number of confirmed requests transmitted. Segment Reqs Number of segmented confirmed requests transmitted. Complex Acks Number of acknowledgements sent with reply data included. BACNL Seg Complex Acks Simple Acks Segment Acks Unconfirms Errors Rejects Aborts Segments Local Aborts Number of segmented acknowledgements sent with reply data included. Number of transmitted acknowledgements with no reply data. Number of acknowledgements sent to Segment Reqs or Seg Complex Acks. Number of unconfirmed requests transmitted. Indicates an error with a valid confirmed (seg) request. Indicates the number of times that the BACnet device rejected messages even though the messages may have been valid. Indicates the number of times that the processing of messages was aborted even though the messages may have been valid. Total number of message segments transmitted. The number of aborts generated as a result of a local protocol error usually due to timeouts. Number of retries due to no acknowledgment of requests. Number of retries due to no acknowledgement of segments. Request Retries Segment Retries Receive Confirmed Reqs Number of confirmed requests received. Segment Reqs Number of segmented confirmed requests received. Complex Acks Number of acknowledgements received with reply data included. Seg Complex Acks Simple Acks Segment Acks Unconfirms Errors Rejects Aborts Segments Datalink Msg Rcv Datalink Msg Txt Unknown Routes Unknown Msg Rcv Rejects Rcv Route Busy Number of segmented acknowledgments received with reply data included. Number of received acknowledgements with no reply data. Number of acknowledgements received for Segment Reqs or Seg Complex Acks. Number of unconfirmed requests received. Indicates an error with a valid confirmed (seg) request. Indicates the number of times that the BACnet device rejected messages even though the messages may have been valid. Indicates the number of times that the processing of messages was aborted even though the messages may have been valid. Total number of message segments received. Number of messages received from the datalink. Number of messages transmitted to the datalink. Number of messages that destination cannot be found because BACnet routing is unknown. Number of BACnet Network layer messages received that are not valid. Number of messages rejected at the BACnet Network Layer. Route to known destination network unavailable due to lost connection.

22 22 Metasys BACnet System Integrator Notification Class Objects (NCOs) BACnet Notification Class - Recipient List File Rebind View Help The BACnet Notification Class screen (Figure 9) shows information about the ten Notification Class Objects implemented in the BSI. These objects determine how alarm event messages from Metasys points are routed to BACnet devices, such as BACnet workstations. Table 9 describes the fields on this screen. First Prev Next Last? Find Find? BACnet Notification Class Object Notification Class Object Name 1 NCO_1 Description NCO_1_TEST Priority Ack_Required TO-OFFNORMAL 11 TO-FAULT 12 Recipient List [IP]1:13::45 [Port]4788 [Net#]1 [ProcessID]1 [Seg]1476 [Confirmed]F [mon]t [tue]t [wed]t [thu]t [fri]t [sat]t [sun]t [TIME]::. - 23:59:59.99 [offnormal]t [fault]t [normal]t TO-NORMAL 13 Refresh Done Ready NUM NCO Figure 9: BACnet Notification Class Recipient List Screen

23 Metasys BACnet System Integrator (BSI) Monitoring 23 Table 9: Field Descriptions - Notification Class Objects Section Field Name Description BACnet Notification Class Object Priority Ack_Required Notification Class Object Name Description TO-OFFNORMAL TO-FAULT TO-NORMAL Instance number from 1 to 1 of the Notification Class Object. Use the toolbar buttons to move through the ten objects. User-defined name of the NCO. User-defined description of the NCO. Priority, and whether operator acknowledgment is required, for messages indicating change to alarm state. Priority, and whether operator acknowledgment is required, for messages indicating change to fault state. Priority, and whether operator acknowledgment is required, for messages indicating change to normal state. Recipient List Recipient List List showing the destination device or devices for event messages from points assigned to this NCO. Further information includes the time schedule during which the destination is active. The Recipient List must be defined at a BACnet workstation.

24 24 Metasys BACnet System Integrator Procedure Overview Table 1: Monitoring the BSI Communicator To Do This View Mapped BACnet Object Cache Data (for device, analog, binary, and multi-state) View BACnet Communicator Application Statistics View Datalink Statistics View PC Protocol Engine Statistics View Notification Class Object Data Follow These Steps: With the BSI Communicator running, open the BSI Viewer. Move through the viewable points or search for a particular point using the toolbar buttons. Look at the information and check for inconsistencies and/or alarms. If no inconsistencies or alarms are found, click Done and from the File menu, select Exit to exit the BSI Viewer. If an inconsistency is found, continue. Open the BSI Configurator to verify how the point was configured. Compare the point configuration in the BSI Configurator with the appearance of the point in the third-party BACnet system. If necessary, check the error log file. Make any necessary changes in the BSI Configurator. Make any necessary changes in the BACnet system. If desired, recheck the data in the BSI Viewer. With the BSI Communicator running, open the BSI Viewer. From the File menu, point to Type and select Communicator Application Statistics. Look at the information and check for indications of problems. If no problems are indicated, click Done and from the File menu, select Exit to exit the BSI Viewer. If a problem is found, continue. Open the BSI Configurator to verify addressing information and to check for misnamed points, or point information that is obsolete. Make any necessary changes in the BSI Configurator or elsewhere. If desired, recheck the data in the BSI Viewer. With the BSI Communicator running, open the BSI Viewer. From the File menu, point to Type and select either Raw Ethernet (ISO 882.3) Datalink Statistics or BACnet/IP Datalink Statistics, depending on the type of transport protocol used on the BACnet network. Look at the information and check for indications of problems. If no problems are indicated, click Done and from the File menu, select Exit to exit the BSI Viewer. If a problem is found, continue. Look for and correct any Windows network driver problems, network errors, bad network card or misconfigured card problems. If desired, recheck the data in the BSI Viewer. With the BSI Communicator running, open the BSI Viewer. From the File menu, point to Type and select PC Protocol Engine Statistics. Look at the information and check for indications of problems. If no problems are indicated, click Done and from the File menu, select Exit to exit the BSI Viewer. If a problem is found, continue. Open the BSI Configurator to verify BACnet network addresses and Ethernet network information, and to check for slow responding devices and traffic overload. Make any necessary changes in the BSI Configurator or elsewhere. If desired, recheck the data in the BSI Viewer. With the BSI Communicator running, open the BSI Viewer. From the File menu, point to Type and select Notification Class Object. Use the toolbar buttons to move through the ten NCOs implemented in the BSI. Look at the information and check for indications of problems. If no problems are indicated, click Done and from the File menu, select Exit to exit the BSI Viewer. If a problem is found, continue. Open the BSI Configurator to correct Priority and Ack_Required settings. Use a BACnet workstation to correct the Recipient List. Make any necessary changes in the BSI Configurator or elsewhere. If desired, recheck the data in the BSI Viewer.

25 Metasys BACnet System Integrator (BSI) Monitoring 25 Detailed Procedures Viewing Mapped BACnet Object Cache Data To view mapped BACnet object cache data: 1. With the BSI Communicator running, open the BSI Viewer. The Object Mapping screen (internal list of BACnet points) appears. 2. Move through the viewable points or search for a particular point using the toolbar buttons. The screen s appearance will change according to the point type being viewed (Figures 4 through 7). 3. Look at the information and check for inconsistencies and/or alarms. Data on this screen may change as it is being viewed. 4. If no inconsistencies or alarms are found, click Done and from the File menu, select Exit to exit the BSI Viewer. If an inconsistency is found, continue with Step 5. Otherwise, the procedure is complete. 5. Open the BSI Configurator to verify how the point was configured. 6. Compare the point configuration in the BSI Configurator with the appearance of the point in the third-party BACnet system. 7. If necessary, check the error log file (BGATEERR.TXT) using any ASCII readable program. Refer to the Troubleshooting section of this document. 8. Make any necessary changes in the BSI Configurator. Refer to the Metasys BACnet System Integrator (BSI) Commissioning Technical Bulletin (LIT ) in the Metasys Connectivity Technical Manual (FAN-629.5). 9. If database changes are made with the BSI Configurator, be sure to restart Person-Machine Interface (PMI) or Metasys Application Enabler (MAE). 1. Make any necessary changes in the BACnet system. 11. If desired, recheck the data in the BSI Viewer. Note: An error occurs if the BSI Viewer is started without the BSI Communicator running.

26 26 Metasys BACnet System Integrator Viewing BACnet Communicator Application Statistics To view BACnet Communicator Application Statistics: 1. With the BSI Communicator running, open the BSI Viewer. The Object Mapping screen (internal list of BACnet points) appears. 2. From the File menu, point to Type and select Communicator Application Statistics. The BACnet Communicator Application Statistics screen appears (Figure 1). 3. Look at the information and check for indications of problems. Data on this screen may change as it is being viewed. 4. If no problems are indicated, click Done and from the File menu, select Exit to exit the BSI Viewer. If a problem is found, continue with Step 5. Otherwise, the procedure is complete. 5. Open the BSI Configurator to verify addressing information and to check for misnamed points, or point information that is obsolete. 6. Make any necessary changes in the BSI Configurator or elsewhere. Refer to the Metasys BACnet System Integrator (BSI) Commissioning Technical Bulletin (LIT ) in the Metasys Connectivity Technical Manual (FAN-629.5). 7. If database changes are made with the BSI Configurator, be sure to restart Person-Machine Interface (PMI) or Metasys Application Enabler (MAE). 8. If desired, recheck the data in the BSI Viewer. Note: An error occurs if the BSI Viewer is started without the BSI Communicator running.

27 Metasys BACnet System Integrator (BSI) Monitoring 27 Viewing Datalink Statistics To view Datalink Statistics: 1. Open the BSI Viewer. The Object Mapping screen (internal list of BACnet points) appears. 2. From the File menu, point to Type and select either Raw Ethernet (ISO 882.3) Datalink Statistics or BACnet/IP Datalink Statistics, depending on the type of transport protocol used on the BACnet network. The corresponding BACnet Datalink Statistics screen appears (Figure 2 or Figure 3). 3. Look at the information and check for indications of problems. Data on this screen may change as it is being viewed. 4. If no problems are indicated, click Done and from the File menu, select Exit to exit the BSI Viewer. If a problem is found, continue with Step 5. Otherwise, the procedure is complete. 5. Look for and correct any Windows network driver problems, network errors, bad network card or misconfigured card problems. 6. If desired, recheck the data in the BSI Viewer. Note: An error occurs if the BSI Viewer is started without the BSI Communicator running.

28 28 Metasys BACnet System Integrator Viewing PC Protocol Engine Statistics To view PC Protocol Engine Statistics: 1. Open the BSI Viewer. The Object Mapping screen (internal list of BACnet points) appears. 2. From the File menu, point to Type and select PC Protocol Engine Statistics. The BACnet PC Protocol Engine screen appears (Figure 8). 3. Look at the information and check for indications of problems. Data on this screen may change as it is being viewed. 4. If no problems are indicated, click Done and from the File menu, select Exit to exit the BSI Viewer. If a problem is found, continue with Step 5. Otherwise, the procedure is complete. 5. Open the BSI Configurator to verify BACnet network addresses and Ethernet network information, and to check for slow responding devices and traffic overload. 6. Make any necessary changes in the BSI Configurator or elsewhere. Refer to the Metasys BACnet System Integrator (BSI) Commissioning Technical Bulletin (LIT ) in the Metasys Connectivity Technical Manual (FAN-629.5). 7. If database changes are made with the BSI Configurator, be sure to restart PMI or MAE. 8. If desired, recheck the data in the BSI Viewer. Note: An error occurs if the BSI Viewer is started without the BSI Communicator running.

29 Metasys BACnet System Integrator (BSI) Monitoring 29 Viewing Notification Class Object Data To view Notification Class Object data: 1. With the BSI Communicator running, open the BSI Viewer. The Object Mapping screen (internal list of BACnet points) appears. 2. From the File menu, point to Type and select Notification Class Object. The BACnet Notification Class screen appears (Figure 9). 3. Use the toolbar buttons to move through the ten Notification Class Objects implemented in the BSI. 4. Look at the information and check for indications of problems. Data on this screen may change as it is being viewed. 5. If no problems are indicated, click Done and from the File menu, select Exit to exit the BSI Viewer. If a problem is found, continue with Step 6. Otherwise, the procedure is complete. 6. Open the BSI Configurator to correct Priority and Ack_Required settings. Use a BACnet workstation to correct the Recipient List. 7. If desired, recheck the data in the BSI Viewer. Note: An error occurs if the BSI Viewer is started without the BSI Communicator running.

30 3 Metasys BACnet System Integrator Troubleshooting Table 11: Monitoring Error Messages Throughout the monitoring process, error messages may appear. Table 11 lists the possible error messages, problems, and solutions. Error Message Problem Solution Object number: [number], classid = [number], objtyp_name = [text] - Metasys type is invalid. Object number: [number], type: [text], not implemented yet. OSRegisterTask, ID = [number] was unsuccessful. Metasys point object type is not valid. May be caused by incomplete binding to NCM data point (offline NCM, missing Metasys point) or unsupported Metasys point type. Metasys point object type is not handled by BSI Viewer. Fatal error - Unable to communicate with BSI Communicator. Likely to be caused by BSI Communicator not running or an install problem. Ignore Done button and go on to the next point. Check mapped Metasys point to make sure it exists as named. Verify database for this point. Make sure the BSI Communicator/Metasys PMI or MAE is running. Error Log File Enable Debug BSI Communicator information and error messages are written to an error log file, BGATEERR.TXT, found in the directory determined by the Metasys.ini ERRORLOGPATH parameter setting. Error messages are only added to the error log when the BSI Communicator is running or attempting to run. When the file reaches approximately.5 MB, it is renamed to BGATEERR.OLD, any existing BGATEERR.OLD file is deleted, and a new BGATEERR.TXT is started. Table 12 lists possible error messages, explanations, and solutions. The selection of the Enable Debug field during System Setup of the BSI Configurator affects messages written to the BGATEERR.TXT error log file. During commissioning, selecting this field results in all of the information being written to this error log file as installation and testing aids and as error messages. When this field is deselected, only error messages are written. Once commissioning is complete and the system is performing as desired, deselect Enable Debug on the Device Object screen of the BSI Configurator to avoid excessive disk activity and the loss of possible error messages. Refer to the Metasys BACnet System Integrator (BSI) Commissioning Technical Bulletin (LIT ) in the Metasys Connectivity Technical Manual (FAN 629.5) for more information.

31 Metasys BACnet System Integrator (BSI) Monitoring 31 Table 12: Runtime Troubleshooting Guide Problem Explanation Solution Asking Metasys attributes Information Debug only BSI Communicator is as: [request text] sending request for Metasys attributes. BACnet device index mismatch on point index=[number], scanning device ndx=[number], real dev ndx=[number] BACnet object no reply yet at index = [number] BACnet object scan time remaining after all requests sent = [number] BACnet Object Table Corrupted BACnet object table overflow Bad Data Type = [BACnet data type] Bad Error Type in message = [number] hex Can t decode I-HAVE message, address NETDEVINFO structure follows Can t decode WHO-HAS message, address NETDEVINFO structure follows Can t decode WHO-IS message, address NETDEVINFO structure follows Can t send WHO-HAS message on BACnet point ndx = [number], not enough info Continued on next page... Error BSI Communicator database corruption where device object is inconsistent for a BACnet point. Information Debug only BACnet object in BSI Communicator database at reference number has not received a reply since the last data request message was sent even though it is due to be polled again. This BACnet object is slow to reply or is offline, or the polling rate is too fast. Information Debug only Useful for setting the minimum scan time in the system information data. Tells how much time is left to complete the scan after all BACnet points have been scanned. If there is no time left or it runs over, (zero) is printed. After the BSI Communicator is up and running, this log should record at least 2% of the minimum scan time in order to have a predictable scan rate. Fatal Error BSI Communicator BACnet object database is corrupt, linkages or object types are not consistent. Error Could not add required BACnet device object information to BSI Communicator database due to database being full. Error BACnet data type not supported for read of Metasys points. Error BACnet object sent nonstandard error message that could not be decoded. Error BSI Communicator could not decode I-HAVE message from address structure printed in the next error log message. Error BSI Communicator could not decode WHO-HAS message from address structure printed in the next error log message. Error WHO-IS message from BACnet device could not be decoded. Address structure is printed in the next error log entry. Information Debug only There is not enough information to send a needed WHO-HAS message to the BACnet point at BSI Communicator database reference. Rebuild BSI Communicator BACnet object mapping database. Rebuild BSI Communicator BACnet object database. Too many BACnet points in BSI Communicator database. BSI Communicator database error or internal error. Check BACnet devices for nonstandard error message types. BACnet device sending nonstandard message. BACnet device sending nonstandard message. BACnet device sending nonstandard message.

32 32 Metasys BACnet System Integrator Problem (Cont.) Explanation Solution Can t send WHO-IS message on BACnet device ndx = [number], not enough info Information Debug only There is not enough information to send a needed WHO-IS message to the BACnet point at BSI Communicator database reference. Can t write to BACnet read only obj ndx [number] (not write enabled) Clock call returned invalid data Closing BACnet System Integrator Corrupted [file name] file Could not get memory, operation failed! Could not get message from NCM Could not read details of object = [Object name] Could not read details of system = [system name] Could not save NCM name in [message] Could not save net name Could not save object name Could not save object type for [object name] Could not save system name Continued on next page... Error Attempt to write to BACnet object that is not write enabled in the BSI Communicator BACnet object database. Error BSI Communicator internal clock read failed. Information Debug Only BSI Communicator received a request to shut down. Fatal Error Format of database file listed is incorrect. Error BSI Communicator is out of memory and cannot operate properly. Error Message from BACnet NCM to BSI PC could not be received at BSI Communicator. Error Metasys object data could not be read from NCM. Fatal Error BSI Communicator startup failure reading information about the BACnet NCM designated in the BSI Communicator system information. or Metasys point auto-configuration failed when data could not be extracted from a database read message. Fatal Error Metasys startup failed when unable to read NCM name from database read message. or Metasys point auto-configuration failed when data could not be extracted from a database read message. Fatal Error Metasys point auto-configuration failed when data could not be extracted from a database read message. Fatal Error Metasys point auto-configuration failed when data could not be extracted from a database read message. Error Metasys point information could not be extracted from read message. Fatal Error Could not read Metasys system name from database read message during Metasys point auto-configuration. Application error or update BSI Communicator database to allow writing. Windows problem. BSI Communicator database file has been corrupted or version is incorrect and it needs to be rebuilt. Check Windows resources. Install problem, Windows resources. BSI Communicator database problem or Metasys object does not exist or is not downloaded. Installation problem or Metasys system not operating correctly or BSI Communicator databases not correct or inconsistent (mapped BACnet points must be specified if a BACnet NCM is specified). Installation problem or Metasys system not operating correctly or BSI Communicator database incorrect. Installation problem or Metasys system not operating correctly. Installation problem or Metasys system not operating correctly. Metasys system not operating correctly or unsupported Metasys point type or BSI Communicator database error. Installation problem or Metasys system not operating correctly.

33 Metasys BACnet System Integrator (BSI) Monitoring 33 Problem (Cont.) Explanation Solution Could not set thread Error Could not control priority of parallel Windows problem. priority process in BSI Communicator. Could not start BACnet polling thread Could not start IAPI thread Data link task ID [number] is not supported Error BACnet mapped system not in specified NCM: [NCM text] Error BACnet Multistate Feedback over 4 on index [number] Error BACnet Multistate Number of States over 4 on index [number] Error BACnet Multistate Relinquish Default over 4 on index [number] Error BACnet Multistate Value over 4 on index [number] Error BACnet write service not supported by device at index = [number] Error Bad NCM COS report alarm type text=[cos text] Error Bot entry for system [system name] object [object name] ndx [number] no type (for writing) Error Can t find property [number] in PC table for BACnet obj ndx [number] Error Can t write when device unknown, BACnet point index = [number] Error COS signup string [command text] failed with status [number] Error Illegal bot index = [number] Continued on next page... Fatal Error BACnet polling could not be started. Fatal Error BSI Communicator process that communicates with Metasys system could not be started. Fatal Error The Data Link Task ID number entered at the BSI Configurator System Setup screen (Metasys Device Object) is not supported by BSI Communicator. Fatal Error BSI Communicator BACnet object database does not match actual NCM addressing structure. Error BACnet multistate point has feedback state with value having a higher state than Metasys system supports. Error BACnet multistate point has number of states greater than supported by Metasys system. Error BACnet multistate point has relinquish default with value having a higher state than Metasys system supports. Error BACnet multistate point has value with higher state than Metasys system supports. Error Attempt to write to BACnet object that does not support the write service as defined by BACnet. Error COS message for BACnet NCM has status that does not match strings in BGLANGTX.DAT. This is usually ONLINE or OFFLINE. Error Attempt to write mapped BACnet point while the BSI Communicator database does not have all of the required information in place. Error Unsupported property cannot be located in the supported property list. Error Attempt to write to BACnet point with unknown BACnet address. Fatal Error Unable to signup to receive Metasys COS messages for BACnet NCM on/offline detection. Error BSI Communicator BACnet object mapping database does not have a point at this index. Installation problem or insufficient Windows resources. Windows resources or installation problem. Choose a supported Data Link Task ID number code at the BSI Configurator System Setup screen (Metasys Device Object). Make BSI Communicator database and Metasys database match. Cannot map this point. Cannot map this point. Cannot map this point. Cannot map this point. Application error or improper use of BACnet device. BGLANGTX.DAT needs updating or Metasys system is not operating properly. Wait for BSI Communicator to finish database binding or correct BSI Communicator database. BACnet device may be sending nonstandard messages. Startup initialization may not be complete yet or BSI Communicator database may not be complete. Installation problem or BSI Communicator database problem. Internal error or corrupt BSI Communicator database.

N2 Binary Output/ BACnet Binary Output

N2 Binary Output/ BACnet Binary Output Object Dictionary 1 N2 Binary Output/ BACnet Binary Output Introduction Note: The Johnson Controls Binary Output object is considered a BACnet Binary Output object because it supports BACnet functionality.

More information

BACnet/IP Driver PTC Inc. All Rights Reserved.

BACnet/IP Driver PTC Inc. All Rights Reserved. 2017 PTC Inc. All Rights Reserved. 2 Table of Contents 1 Table of Contents 2 6 Overview 7 Setup 8 Channel Properties 8 Channel Properties General 8 Channel Properties Ethernet Communications 9 Channel

More information

N2 Analog Input/ BACnet Analog Input

N2 Analog Input/ BACnet Analog Input Object Dictionary 1 N2 Analog Input/ BACnet Analog Input Introduction Note: The Johnson Controls N2 Analog Input object is considered a BACnet Analog Input object because it supports BACnet functionality.

More information

N2 Multistate Output/ BACnet Multistate Output

N2 Multistate Output/ BACnet Multistate Output Object Dictionary 1 N2 Multistate Output/ BACnet Multistate Output Introduction Note: The Johnson Controls N2 Multistate Output object is considered a BACnet Multistate Output object because it supports

More information

Multistate Value/ BACnet Multistate Value

Multistate Value/ BACnet Multistate Value Object Dictionary 1 Multistate Value/ BACnet Multistate Value Introduction Note: The Johnson Controls Multistate Value object is considered a BACnet Multistate Value object because it supports BACnet functionality.

More information

N2 Binary Input/ BACnet Binary Input

N2 Binary Input/ BACnet Binary Input Object Dictionary 1 N2 Binary Input/ BACnet Binary Input Introduction Note: The Johnson Controls Binary Input object is considered a BACnet Binary Input object, because it supports BACnet functionality.

More information

Delta Controller Engine (DCE) Firmware

Delta Controller Engine (DCE) Firmware Date: August 22, 2011 Vendor Name: Delta Controls Inc. Product Name: Delta Controller Engine Product Model Number: DCE Product Version: 3.40 Firmware BACnet Protocol Revision: 6 Product Description The

More information

ICC. BACnet MS/TP Server Driver Manual INDUSTRIAL CONTROL COMMUNICATIONS, INC Industrial Control Communications, Inc.

ICC. BACnet MS/TP Server Driver Manual INDUSTRIAL CONTROL COMMUNICATIONS, INC Industrial Control Communications, Inc. INDUSTRIAL CONTROL COMMUNICATIONS, INC. BACnet MS/TP Server Driver Manual August 17, 2017 2017 Industrial Control Communications, Inc. TABLE OF CONTENTS 1 BACnet MS/TP Server... 2 1.1 Overview... 2 1.2

More information

BACnet Controller Integration with NAE/NCE/ODS Technical Bulletin

BACnet Controller Integration with NAE/NCE/ODS Technical Bulletin BACnet Controller Integration with NAE/NCE/ODS Technical Bulletin Code No. LIT-1201531 Software Release 9.0 Issued August 2017 Refer to the QuickLIT website for the most up-to-date version of this document.

More information

Object Dictionary 1. Pager. Introduction

Object Dictionary 1. Pager. Introduction Object Dictionary 1 Pager Introduction The Pager object provides alarm notifications via pager to personnel at a remote location who would otherwise not be aware of the alarm coming into a workstation

More information

entelibus CPU Engine (eb-eng) Firmware

entelibus CPU Engine (eb-eng) Firmware Date: March 27 th, 2017 Vendor Name: Delta Controls Inc. Product Name: entelibus CPU Engine Product Model Number: eb-eng Product Version: 3.40 Firmware BACnet Protocol Revision: 6 Product Description The

More information

Ethernet IP Datalink. Introduction

Ethernet IP Datalink. Introduction Object Dictionary 1 Ethernet IP Datalink Introduction The Ethernet Internet Protocol (IP) Datalink object manages the Ethernet communications bus and the messages transmitted on it. This object allows

More information

Fisher ROC Plus Serial Driver Help Kepware, Inc.

Fisher ROC Plus Serial Driver Help Kepware, Inc. Fisher ROC Plus Serial Driver Help 2015 Kepware, Inc. 2 Table of Contents Table of Contents 2 5 Overview 5 Channel Setup 7 Device Setup 13 Scan Mode 15 Timings and Timeouts 16 Automatic Demotion 17 Automatic

More information

Delta Control Unit (DCU) 3.30 BACNET PROTOCOL IMPLEMENTATION CONFORMANCE STATEMENT

Delta Control Unit (DCU) 3.30 BACNET PROTOCOL IMPLEMENTATION CONFORMANCE STATEMENT Date: August 14, 2003 Vendor Name: Delta Controls Inc. Product Name: Delta Control Unit Product Model Number: DSC-1616EX, DCU-050, DSM-050 Product Version: 3.30 BACnet Protocol Revision: 3 Product Description:

More information

BACnet Protocol Implementation Conformance Statement Automated Logic Corporation LGR25, LGR250, LGR1000

BACnet Protocol Implementation Conformance Statement Automated Logic Corporation LGR25, LGR250, LGR1000 Date: 9/18/2008 Vendor Name: Automated Logic Corporation Product Name: LGR Product Model Number: LGR25, LGR250, LGR1000 Applications Software Version: ExecB ME-LGR-melgr Firmware Revision: 2.18 BACnet

More information

Delta ORCAview Date: August 5, 2009 Vendor Name: Delta Controls Inc. Product Name:

Delta ORCAview Date: August 5, 2009 Vendor Name: Delta Controls Inc. Product Name: Date: August 5, 2009 Vendor Name: Delta Controls Inc. Product Name: ORCAview Product Model Number: DOW-340 Product Version: 3.40 BACnet Protocol Revision: 6 Product Description: ORCAview is an industry

More information

DNP3 Master Serial Driver PTC Inc. All Rights Reserved.

DNP3 Master Serial Driver PTC Inc. All Rights Reserved. 2018 PTC Inc. All Rights Reserved. 2 Table of Contents 1 Table of Contents 2 9 Overview 9 Setup 9 Channel Properties General 10 Channel Properties Serial Communications 11 Channel Properties Write Optimizations

More information

Fisher ROC Plus Ethernet Driver Help Kepware, Inc.

Fisher ROC Plus Ethernet Driver Help Kepware, Inc. Fisher ROC Plus Ethernet Driver Help 2015 Kepware, Inc. 2 Table of Contents Table of Contents 2 5 Overview 5 Channel Setup 7 Device Setup 13 Scan Mode 15 Timings and Timeouts 16 Automatic Demotion 17 Automatic

More information

Fisher ROC Plus Serial Driver Help Kepware Technologies

Fisher ROC Plus Serial Driver Help Kepware Technologies Fisher ROC Plus Serial Driver Help 2014 Kepware Technologies 2 Table of Contents Table of Contents 2 5 Overview 5 Channel Setup 6 Device Setup 7 Tag Import Settings 7 Address Specification 8 Operator Identification

More information

BACnet Protocol Implementation Conformance Statement OEMPrtl Pro

BACnet Protocol Implementation Conformance Statement OEMPrtl Pro Date: 12/13/2011 Vendor Name: OEMCtrl Product Name: Product Model Number: Applications Software Version: Firmware Revision: 4.02 BACnet Protocol Revision: 9 Product Description: The is

More information

Trend Log/BACnet Trend Log

Trend Log/BACnet Trend Log Object Dictionary 1 Trend Log/BACnet Trend Log Introduction Notes: The Johnson Controls Trend Log object is considered a BACnet Trend Log object because it supports BACnet functionality. In addition, this

More information

DNP3 Master Ethernet Driver PTC Inc. All Rights Reserved.

DNP3 Master Ethernet Driver PTC Inc. All Rights Reserved. 2018 PTC Inc. All Rights Reserved. 2 Table of Contents 1 Table of Contents 2 10 Overview 10 Setup 11 Channel Properties General 11 Channel Properties Ethernet Communications 12 Channel Properties Write

More information

Honeywell ComfortPoint TM Open Plant Controller Protocol Implementation Conformance Statement (PICS)

Honeywell ComfortPoint TM Open Plant Controller Protocol Implementation Conformance Statement (PICS) July 2017 Honeywell ComfortPoint TM Open Plant Controller Protocol Implementation Conformance Statement (PICS) Topic: BACnet Protocol Implementation Conformance Statement (PICS) Date: 13 st September 2017

More information

NB-ASC Family Protocol Implementation Conformance Statement (PICS)

NB-ASC Family Protocol Implementation Conformance Statement (PICS) Vendor Name: American Auto-Matrix Product Name: NB-ASC Family Product l Number: NB-ASC, NB-ASCe, NB-Rooftop, NB-Heat Pump, NB-Fancoil Firmware Revision: 6.03 BACnet Protocol Revision: 4 Product Description:

More information

Site Book User s Guide

Site Book User s Guide Issue Date 11/01/01 USER S GUIDE...3 Introduction... 3 Key Concepts... 5 Related Documentation...5 Communications Options...5 N30 Supervisory Controller...5 Project Builder...6 N30 Upgrade Utility...6

More information

Error code. Description of the circumstances under which the problem occurred. Less than 200. Linux system call error.

Error code. Description of the circumstances under which the problem occurred. Less than 200. Linux system call error. Error code Less than 200 Error code Error type Description of the circumstances under which the problem occurred Linux system call error. Explanation of possible causes Countermeasures 1001 CM_NO_MEMORY

More information

Honeywell ComfortPoint TM Open Plant Controller Protocol Implementation Conformance Statement (PICS)

Honeywell ComfortPoint TM Open Plant Controller Protocol Implementation Conformance Statement (PICS) August 2012 Honeywell ComfortPoint TM Open Plant Controller Protocol Implementation Conformance Statement (PICS) Topic: BACnet Protocol Implementation Conformance Statement (PICS) Date: 27 th August 2012

More information

NB-V3Tb Protocol Implementation Conformance Statement (PICS)

NB-V3Tb Protocol Implementation Conformance Statement (PICS) NB-V3Tb Vendor Name: American Auto-Matrix Product Name: NB-V3Tb Product Model Number: NB-V3Tb Firmware Revision: 6.03 BACnet Protocol Revision: 4 Product Description: NB-V3Tb is a full-featured VVT system

More information

BACnet Protocol Implementation Conformance Statement

BACnet Protocol Implementation Conformance Statement BACnet Protocol Implementation Conformance Statement Date: December 1 st, 2015 Vendor Name: Danfoss A/S Product Name: VLT HVAC Drive FC-102 Product Model Number: FC-102 Applications Software Version: 1.6

More information

BACnet Protocol Implementation Conformance Statement Unitary Protocol Converter (UPC)

BACnet Protocol Implementation Conformance Statement Unitary Protocol Converter (UPC) Date: 10/05/2016 Vendor Name: OEMCtrl Product Name: Unitary Protocol Converter Product Model Number: UPC Applications Software Version: Firmware Revision: 6.00a BACnet Protocol

More information

MatrixBBC. Protocol Implementation Conformance Statement (PICS) Product Description: BACnet Standardized Device Profile:

MatrixBBC. Protocol Implementation Conformance Statement (PICS) Product Description: BACnet Standardized Device Profile: Vendor Name: American Auto Matrix Product Name: BACnet Building Controller Product Model Number: x BBC y (x indicating target model; y feature) Firmware Revision: Target using BBC module v1.1.56 or later

More information

Using Dial-Up with the NDM

Using Dial-Up with the NDM Operator Workstation User s Manual 16-1 Chapter 16 Using Dial-Up with the NDM Introduction This section describes using the Dial-Up feature to connect to remote devices via the N2 Dialer Module (NDM).

More information

NB-VAV Family Protocol Implementation Conformance Statement (PICS)

NB-VAV Family Protocol Implementation Conformance Statement (PICS) Vendor Name: American Auto-Matrix Product Name: NB-VAV Family Product Model Number: NB-VAVta, NB-VAVtf, NB-VAVra, NB-VAVrf, NB-VAVr, NB-VAVta-IAQ, NB-VAVtf-IAQ Firmware Revision: 6.03 BACnet Protocol Revision:

More information

BACnet OPC Server User s Manual

BACnet OPC Server User s Manual BACnet OPC Server User s Manual Contents Introduction... 4 Installation... 8 System Requirements... 8 Install... 9 Installed Files... 11 Application Data... 12 Uninstall... 12 Getting Started... 13 Start

More information

History Page. Barracuda NextGen Firewall F

History Page. Barracuda NextGen Firewall F The Firewall > History page is very useful for troubleshooting. It provides information for all traffic that has passed through the Barracuda NG Firewall. It also provides messages that state why traffic

More information

Maintenance Tasks CHAPTER

Maintenance Tasks CHAPTER CHAPTER 5 These topics describe the Maintenance tasks of Element Manager: Viewing Basic System Information, page 5-2 Configuring Basic System Information, page 5-3 Configuring Date and Time Properties,

More information

N1 Migration with the NIE

N1 Migration with the NIE Technical Bulletin Issue Date April 29, 2003 N1 Migration with the NIE N1 Migration with the NIE...3 Introduction... 3 Key Concepts... 4 N1 Migration Overview... 4 N1 Migration Flowchart... 5 Metasys N1

More information

Kepware Technologies Differences Between 4x and 5x for DNP Drivers

Kepware Technologies Differences Between 4x and 5x for DNP Drivers Kepware Technologies Differences Between 4x and 5x for DNP Drivers June, 2010 V 1.000 Kepware Technologies Table of Contents 1. General... 1 2. Changes in Channel Properties... 1 2.1 DNP Master Ethernet...

More information

Device Diagnostic. Introduction

Device Diagnostic. Introduction Object Dictionary 1 Device Diagnostic Introduction The Device Diagnostic object supports various diagnostic functions of the device and monitors the device for an overload condition. This object allows

More information

Maintenance Tasks CHAPTER

Maintenance Tasks CHAPTER CHAPTER 5 These topics describe the Maintenance tasks of Element Manager: Viewing Basic System Information, page 5-2 Configuring Basic System Information, page 5-4 Configuring Date and Time Properties,

More information

Schedule/BACnet Schedule

Schedule/BACnet Schedule Object Dictionary 1 Schedule/BACnet Schedule Introduction Note: The Johnson Controls Schedule object is considered a BACnet Schedule object because it supports BACnet functionality. In addition, this object

More information

SAUTER BACnet PICS EY-modulo 5 ecos504/505 BACnet Protocol Implementation Conformance Statement

SAUTER BACnet PICS EY-modulo 5 ecos504/505 BACnet Protocol Implementation Conformance Statement BACnet Protocol Implementation Conformance Statement D100275255-05 Content Note: This statement corresponds to the ANSI/ASHRAE 135-2012 release. Changes are taking place constantly, without prior notification.

More information

Memory may be insufficient. Memory may be insufficient.

Memory may be insufficient. Memory may be insufficient. Error code Less than 200 Error code Error type Description of the circumstances under which the problem occurred Linux system call error. Explanation of possible causes Countermeasures 1001 CM_NO_MEMORY

More information

6800 Series Data Log Messages

6800 Series Data Log Messages ACW 130B SW1 Neutral Fault Detected Current Over Threshold for Duration Threshold ACW 1307 SW1 Neutral Overcurrent End Current Below Threshold ACW 1303 SW1 Neutral Overcurrent Start Current Over Threshold

More information

Runtime Totalization. Introduction

Runtime Totalization. Introduction Object Dictionary 1 Runtime Totalization Introduction The Runtime Totalization object tracks the time that elapses while a designated input, such as a binary or multistate value, matches a specified state.

More information

NB-GPC Family Protocol Implementation Conformance Statement (PICS)

NB-GPC Family Protocol Implementation Conformance Statement (PICS) Vendor Name: American Auto-Matrix Product Name: NB-GPC Family Product Model Number: NB-GPC1, NB-GPC2, NB-GPC3, NB-GPC4 Firmware Revision: 2.00 BACnet Protocol Revision: 4 Product Description: NB-GPC controllers

More information

APPLICATION NOTE JC/85

APPLICATION NOTE JC/85 Metasys Network Technical Manual 636 App. Notes: Network Communications Section Application Note Issue Date 0401 APPLICATION NOTE JC/85 Gateway Introduction Page 3 Application Details *3 Hardware and Software

More information

Installation Manual. DZK BACnet

Installation Manual. DZK BACnet Installation Manual DZK BACnet InterfacepbilCodarPageNumber TABLE OF CONTENTS Page Overview... 5 Outline and Features... 5 System outline... 5 Specifications and device elements... 6 Functional specifications...

More information

DNP Master Ethernet Driver Help Kepware Technologies

DNP Master Ethernet Driver Help Kepware Technologies DNP Master Ethernet Driver Help 2012 Kepware Technologies 2 Table of Contents Table of Contents 2 9 Overview 9 Channel Setup 10 Communications General 10 Timing 10 Device Setup 12 Communications 12 Polling

More information

Ping Driver PTC Inc. All Rights Reserved.

Ping Driver PTC Inc. All Rights Reserved. 2017 PTC Inc. All Rights Reserved. 2 Table of Contents 1 Table of Contents 2 3 Overview 4 Channel Properties General 4 Channel Properties Ethernet Communications 5 Channel Properties Write Optimizations

More information

ETH-1000 Version Info

ETH-1000 Version Info ETH-1000 Version Info 01.05.2018 Main CPU Firmware V5.600 Metasys, FLN release Added ability to release an object s value to Metasys N2 Master. Added ability to release a point s value to Siemens FLN Master.

More information

LonWorks Network Integration with NAE and LCS Technical Bulletin

LonWorks Network Integration with NAE and LCS Technical Bulletin LONWORKS Network Integration with NAE and LCS Technical Bulletin Code No. LIT-1201668 Software Release 8.0 Issued June 2016 Refer to the QuickLIT website for the most up-to-date version of this document.

More information

Source OID Message Severity Cause Action

Source OID Message Severity Cause Action 13 CHAPTER This section describes the Prime Network system events. System events appear in the Prime Network Events System tab. They include a variety of events pertaining to the system activities, from

More information

Bristol/IP Driver PTC Inc. All Rights Reserved.

Bristol/IP Driver PTC Inc. All Rights Reserved. 2017 PTC Inc. All Rights Reserved. 2 Table of Contents 1 Table of Contents 2 4 Overview 4 BSAP Networks 5 Channel Setup 6 Channel Properties - General 6 Channel Properties - Ethernet Communications 7 Channel

More information

Fisher ROC Serial Driver Help Kepware Technologies

Fisher ROC Serial Driver Help Kepware Technologies Fisher ROC Serial Driver Help 2012 Kepware Technologies 2 Table of Contents Table of Contents 2 4 Overview 4 Channel Setup 5 Device Setup 6 Tag Import Settings 6 Address Specification 7 Operator Identification

More information

Procon BAC-A/50. Installation Instructions MITSUBISHI ELECTRIC

Procon BAC-A/50. Installation Instructions MITSUBISHI ELECTRIC Installation Instructions Procon BAC-A/50 MITSUBISHI ELECTRIC BACnet TM is a registered trademark of ASHRAE (American Society of Heating, Refrigerating and Air- Conditioning Engineers, Inc.) 1. Product

More information

BACnet Protocol Implementation Conformance Statement Automated Logic G5RE

BACnet Protocol Implementation Conformance Statement Automated Logic G5RE Date: 6/1/2017 Vendor Name: Automated Logic Product Name: G5RE Product Model Number: G5RE Applications Software Version: N/A Firmware Revision: 100.02.2018 BACnet Protocol Revision: 9 Product Description:

More information

Appendix. Web Command Error Codes. Web Command Error Codes

Appendix. Web Command Error Codes. Web Command Error Codes Appendix Web Command s Error codes marked with * are received in responses from the FTP server, and then returned as the result of FTP command execution. -501 Incorrect parameter type -502 Error getting

More information

Using the Cable Monitor Tool

Using the Cable Monitor Tool APPENDIX B This appendix describes the Cisco ubr905 and Cisco ubr925 cable access routers Cable Monitor tool. The Cable Monitor is part of the router s onboard software that provides a web-based diagnostic

More information

Table of Contents. NBC User's Manual

Table of Contents. NBC User's Manual User's Manual User's Manual Table of Contents 1. Connections and Power... 3 1.1. Connections and Power for WSXXXX_BR products... 3 2. Initial Configuration... 4 2.1. NBC Network Configuration... 4 2.2.

More information

DNP Master Serial Driver Help Kepware Technologies

DNP Master Serial Driver Help Kepware Technologies DNP Master Serial Driver Help 2013 Kepware Technologies 2 Table of Contents Table of Contents 2 8 Overview 8 Channel Setup 9 Timing 9 Device Setup 10 Communications 10 Polling 13 Unsolicited Messaging

More information

Downloading Metasys Integrator 300 Series Code

Downloading Metasys Integrator 300 Series Code M-Tool Manual 693 System Tools Applications Section Issue Date 0101 APPLICATION NOTE Downloading Metasys Integrator 300 Series Code Downloading Metasys Integrator 300 Series Code...3 Introduction...3 Key

More information

BrightCore BACnet Lookout V2.2 Product Family

BrightCore BACnet Lookout V2.2 Product Family Page 1 BrightCore BACnet Lookout User Guide Essential, Standard and Extended v.2.2 Page 2 Copyright 2013 by ELMA Kurtalj ltd. All rights reserved. The contents of this documentation are taken in part from

More information

REPLACING A PEERLINK NETWORK WITH 2572-A / 2572-B ETHERNET

REPLACING A PEERLINK NETWORK WITH 2572-A / 2572-B ETHERNET REPLACING A PEERLINK NETWORK WITH 2572-A / 2572-B ETHERNET This is an example of how 2572-A / 2572-B Ethernet Modules may be used share data among multiple PLC s using the IP Multicast feature. The purpose

More information

Configuring Dynamic ARP Inspection

Configuring Dynamic ARP Inspection 21 CHAPTER This chapter describes how to configure dynamic Address Resolution Protocol inspection (dynamic ARP inspection) on the Catalyst 3560 switch. This feature helps prevent malicious attacks on the

More information

GE Ethernet Global Data Driver Help Kepware Technologies

GE Ethernet Global Data Driver Help Kepware Technologies GE Ethernet Global Data Driver Help 2012 Kepware Technologies 2 Table of Contents Table of Contents 2 4 Overview 4 Device Setup 5 Name Resolution 6 Exchange Configuration 7 Data Types Description 11 Address

More information

Configuring the Management Interface and Security

Configuring the Management Interface and Security CHAPTER 5 Configuring the Management Interface and Security Revised: February 15, 2011, Introduction This module describes how to configure the physical management interfaces (ports) as well as the various

More information

Defining Devices. Introduction

Defining Devices. Introduction Operator Workstation User s Manual 3-1 Chapter 3 Defining Devices Introduction Devices include NCMs, OWSs (PCs or portable computers), and printers. Each network has a system called Devices, which contains

More information

Enron Modbus Driver PTC Inc. All Rights Reserved.

Enron Modbus Driver PTC Inc. All Rights Reserved. 2017 PTC Inc. All Rights Reserved. 2 Table of Contents 1 Table of Contents 2 5 Overview 5 Channel Setup 6 Channel Properties - General 6 Channel Properties - Serial Communications 7 Channel Properties

More information

WT-BAC-IP Gateway Protocol Implementation Conformance Statement

WT-BAC-IP Gateway Protocol Implementation Conformance Statement WT-BAC-IP Gateway Protocol Implementation Conformance Statement Technical Bulletin WT-BAC-IP Code No. LIT-12011936 Issued June 2017 Refer to the QuickLIT Web site for the most up-to-date version of this

More information

Yokogawa HR Driver PTC Inc. All Rights Reserved.

Yokogawa HR Driver PTC Inc. All Rights Reserved. 2017 PTC Inc. All Rights Reserved. 2 Table of Contents 1 Table of Contents 2 3 Overview 3 Setup 4 Channel Properties - General 4 Channel Properties - Serial Communications 5 Channel Properties - Write

More information

N1 Migration with the NIE Technical Bulletin

N1 Migration with the NIE Technical Bulletin MS-NIE55xx-x, MS-NxE85SW-0, MS-NIE8500-x Code No. LIT-20535 Software Release 9.0 Issued August 207 Refer to the QuickLIT website for the most up-to-date version of this document. Document Introduction...3

More information

Building Product CCM08 Series BACnet Central Control Module User Manual

Building Product CCM08 Series BACnet Central Control Module User Manual Building Product CCM08 Series BACnet Central Control Module User Manual 2007.10 1 1. connect diagrammatic sketch (1)CCM08 interfaces diagrammatic sketch An Ethernet interface connected to BACnet/IP network.

More information

Partitioning and Internet Broker Error Messages

Partitioning and Internet Broker Error Messages MSE Technical Bulletin Partitioning and Internet Broker Error Messages Preface: The aim of this tech bulletin is to provide a list of the broker error messages in the partitioning and Internet environments

More information

BACnet Simulator User s Manual

BACnet Simulator User s Manual BACnet Simulator User s Manual Contents Introduction... 3 Installation... 4 System Requirements... 4 Install... 4 Installed Files... 6 Application Data... 7 Uninstall... 7 Getting Started... 8 Start the

More information

Teldat Router. ARP and InARP Protocol

Teldat Router. ARP and InARP Protocol Teldat Router ARP and InARP Protocol Doc. DM701-I Rev. 10.00 November, 2002 INDEX Chapter 1 Introduction...1 1. ARP Protocol... 2 2. InARP Protocol... 3 Chapter 2 Configuration...4 1. ARP Protocol Configuration

More information

Mitsubishi FX Net Driver PTC Inc. All Rights Reserved.

Mitsubishi FX Net Driver PTC Inc. All Rights Reserved. 2017 PTC Inc. All Rights Reserved. 2 Table of Contents 1 Table of Contents 2 3 Overview 3 Device Setup 4 Channel Properties 5 Channel Properties - General 5 Channel Properties - Serial Communications 6

More information

LonWorks Network Integration with NAE and LCS Technical Bulletin

LonWorks Network Integration with NAE and LCS Technical Bulletin LONWORKS Network Integration with NAE and LCS Technical Bulletin Code No. LIT-1201668 Software Release 9.0 Issued August 2017 Refer to the QuickLIT website for the most up-to-date version of this document.

More information

ESAC ebacgw SNMP. Date: Mar 08,2009. Product Model Number: Product Version: 1.0 BACnet Protocol Revision: 3. Product Description:

ESAC ebacgw SNMP. Date: Mar 08,2009. Product Model Number: Product Version: 1.0 BACnet Protocol Revision: 3. Product Description: Date: Mar 08,2009 Vendor Name: ESAC srl Product Name: ebacgw-snmp Product Model Number: Product Version: 1.0 BACnet Protocol Revision: 3 Product Description: ebacgw is a BACnet gateway to SNMP (simple

More information

MODBUS Protocol for MiCOM P30 Series

MODBUS Protocol for MiCOM P30 Series MODBUS Protocol for MiCOM P30 Series Substation Protocols Technical Documentation This document does not replace the Technical Manual Version: MiCOM P30, MODBUS Index: B Release: 08 / 2011 MODBUS Protocol

More information

PowerLink Host Data Manager User Guide

PowerLink Host Data Manager User Guide PowerLink Host Data Manager User Guide Last Updated: July 2009 Version: 2.06014 Contents Contents... 2 Introduction... 4 Quick Start... 5 Enable File Monitoring... 7 Enabling Attaché 7 File Monitoring

More information

Working with Objects and the M-View Screen

Working with Objects and the M-View Screen Project Builder User s Guide 6-1 Chapter 6 Working with Objects and the M-View Screen Introduction The Project Builder uses a variety of objects to configure controllers and perform tasks. This chapter

More information

NS Series CO 2 Network Zone Sensors Protocol Implementation Conformance Statement

NS Series CO 2 Network Zone Sensors Protocol Implementation Conformance Statement NS Series CO 2 Network Zone Sensors Protocol Implementation Conformance Statement NS-BCN7004-0, NS-BCN7004-2 Code No. LIT-12011581 Issued November 9, 2011 Supersedes April 12, 2011 Refer to the QuickLIT

More information

Reliance. Johnson Controls communication driver version 1.5.4

Reliance. Johnson Controls communication driver version 1.5.4 Reliance Johnson Controls communication driver version 1.5.4 CONTENT 1. Introduction... 3 1.1. Fundamental Terms... 3 2. Johnson Controls Communication driver... 4 2.1 Basic characteristics... 4 Starting

More information

Ciphermail Webmail Messenger Administration Guide

Ciphermail Webmail Messenger Administration Guide CIPHERMAIL EMAIL ENCRYPTION Ciphermail Webmail Messenger Administration Guide October 27, 2017, Rev: 8630 Copyright 2013-2017, ciphermail.com. CONTENTS CONTENTS Contents 1 Introduction 4 2 Admin login

More information

Data Exchange 3. The easy way to turn your data into valuable information. VERSION 3.0

Data Exchange 3. The easy way to turn your data into valuable information. VERSION 3.0 Data Exchange 3 The easy way to turn your data into valuable information. VERSION 3.0 12-21-2017 DATA EXCHANGE 3 1 TABLE OF CONTENTS SECTION 1. Overview... 6 1.1. MAIN GOALS...6 1.2. How it Works...6 Data

More information

Bridging Transmitting Non-IP Traffic or Merging Two Networks

Bridging Transmitting Non-IP Traffic or Merging Two Networks 10 Bridging Transmitting Non-IP Traffic or Merging Two Networks Contents Overview..................................................... 10-3 Transmitting Non-IP Traffic..................................

More information

APPLICATION NOTE. N2 Dial Application. Using N2 Dial...3. Introduction...3. Key Concepts...4

APPLICATION NOTE. N2 Dial Application. Using N2 Dial...3. Introduction...3. Key Concepts...4 FANs 637.5, 1637.5 N2 Dial Section Issue Date 0400 APPLICATION NOTE N2 Dial Application Using N2 Dial...3 Introduction...3 Key Concepts...4 N2 Dial Configuration... 4 Downloading with N2 Dial...*6 Dial-in

More information

With 802.1X port-based authentication, the devices in the network have specific roles.

With 802.1X port-based authentication, the devices in the network have specific roles. This chapter contains the following sections: Information About 802.1X, page 1 Licensing Requirements for 802.1X, page 9 Prerequisites for 802.1X, page 9 802.1X Guidelines and Limitations, page 9 Default

More information

BEAAquaLogic. Service Bus. MQ Transport User Guide

BEAAquaLogic. Service Bus. MQ Transport User Guide BEAAquaLogic Service Bus MQ Transport User Guide Version: 3.0 Revised: February 2008 Contents Introduction to the MQ Transport Messaging Patterns......................................................

More information

N30 Supervisory Controller Quick Start

N30 Supervisory Controller Quick Start Issue Date June 30, 2004 TECHNICAL BULLETIN N30 Supervisory Controller Quick Start N30 Supervisory Controller Quick Start...2 Introduction... 2 Key Concepts... 3 Using This Document... 3 Related Information...

More information

Metasys Integrator Caterpillar Application

Metasys Integrator Caterpillar Application Application Note Issue Date May, 00 APPLICATION NOTE Metasys Integrator Caterpillar Application Introduction Application Details Component Requirements Vendor Contact Information Design Considerations

More information

Project Builder User s Guide

Project Builder User s Guide M-Tool Manual 693 Project Builder Section Issue Date 0401 Table of Contents Project Builder User s Guide Table of Contents...1 Chapter 1 Using This Guide...1-1 Introduction... 1-1 Key Concepts... 1-2 User

More information

PROMISE ARRAY MANAGEMENT ( PAM) FOR FastTrak S150 TX2plus, S150 TX4 and TX4000. User Manual. Version 1.3

PROMISE ARRAY MANAGEMENT ( PAM) FOR FastTrak S150 TX2plus, S150 TX4 and TX4000. User Manual. Version 1.3 PROMISE ARRAY MANAGEMENT ( PAM) FOR FastTrak S150 TX2plus, S150 TX4 and TX4000 User Manual Version 1.3 Promise Array Management Copyright 2003 Promise Technology, Inc. All Rights Reserved. Copyright by

More information

CLI Error Messages. CLI Error Messages APPENDIXD

CLI Error Messages. CLI Error Messages APPENDIXD APPENDIXD This appendix lists the CLI error messages and CLI validation error messages. It contains the following sections:, page D-1 CLI Validation Error Messages, page D-5 describes CLI error messages.

More information

Appendix A: N1 OPC Data Access Server

Appendix A: N1 OPC Data Access Server Issue Date July 14, 2003 TECHNICAL BULLETIN Appendix A: N1 OPC Data Access Server Appendix A: N1 OPC Data Access Server...3 Introduction... 3 Key Concepts... 4 N1... 4 OLE... 4 OPC... 4 Site... 4 N1 OPC

More information

Modbus ASCII Driver PTC Inc. All Rights Reserved.

Modbus ASCII Driver PTC Inc. All Rights Reserved. 2017 PTC Inc. All Rights Reserved. 2 Table of Contents 1 Table of Contents 2 4 Overview 5 Setup 6 Channel Setup 6 Channel Properties General 6 Channel Properties Serial Communications 7 Channel Properties

More information

DOC. #TD /20/06 PRINTED IN U.S.A. Lingo XE Touchscreen & Web Browser User s Guide

DOC. #TD /20/06 PRINTED IN U.S.A. Lingo XE Touchscreen & Web Browser User s Guide DOC. #TD-0465 10/20/06 PRINTED IN U.S.A. Lingo XE Touchscreen & Web Browser User s Guide Logic One, Lingo, and iscope are registered trademarks of Novar. Ethernet os a registered trademark of Xerox Corporation.

More information

Communication 7. What's in this Chapter? This chapter contains the following sections:

Communication 7. What's in this Chapter? This chapter contains the following sections: Communication 7 What's in this Chapter? This chapter contains the following sections: Section Topic Page 7.1 Modbus Protocol 170 7.2 IEC 60870-5-103 protocol 190 SEPED307003 02/2008 169 7.1 Modbus Protocol

More information

Configuring DHCP Features and IP Source Guard

Configuring DHCP Features and IP Source Guard CHAPTER 21 This chapter describes how to configure DHCP snooping and option-82 data insertion, and the DHCP server port-based address allocation features on the switch. It also describes how to configure

More information