1 Metasys Connectivity Technical Manual Metasys Integrator Section Application Note Issue Date 0496 APPLICATION NOTE Metasys Integrator Graham Application Introduction Page 3 Application Details 3 Component Requirements *5 Vendor Contact Information 6 Design Considerations 6 Cable Connections 7 Cable Pinouts *7 Connecting the Cable 7 Metasys Integrator Setup 9 Metasys Integrator Setup 9 Adjustable Frequency Drive Setup 10 Point Mapping Tables 11 Graham Model 1576 and 1703 Adjustable Frequency Drives 11 Graham Model 1703 Adjustable Frequency Drives 11 Metasys Network Setup 13 Mapping to a CS Object 13 * Indicates those sections where changes have occurred since the last printing Johnson Controls, Inc. 1 Code No. LIT
2 2 Metasys Integrator Metasys Integrator Graham Application
3 Introduction This document explains Metasys Integrator Graham Adjustable Frequency Drive applications. Use this document with the Metasys Integrator Technical Bulletin (FAN 629.5), which provides information on installing and commissioning Metasys Integrator. For information on Graham equipment, see Graham documentation (obtainable from a Graham representative). Application Details Metasys Integrator allows Graham Adjustable Frequency Drives to become an integral part of the Metasys and Metasys Companion Networks. Once the Johnson Controls RS-232 to RS-485 converter (MM-CVT101-0) is connected to a Metasys or Companion Network via the Metasys Integrator, and a Graham B&B MULTI/O MI485D Control Unit is connected to the Adjustable Frequency Drive, each drive can be accessed by the full complement of Metasys Facility Management System (FMS) features, including Change-of-State (COS) monitoring, alarm notification, scheduling, trend, and totalization. The RS-232 to RS-485 converter connects to Metasys Integrator through the RS-232 port. The B&B MULTI/O MI485D Control Unit is the interface between Graham equipment and non-graham devices (such as Metasys Integrator). Each Metasys Integrator vendor port can connect to one RS-485 converter. Each converter can connect to 31 B&B MULTI/O MI485D Control Units. Each control unit connects to one Adjustable Frequency Drive. Figure 1 shows Graham and Metasys integration, and Figure 2 shows Graham and Metasys Companion integration. Metasys Integrator supports two Graham drive models: Model 1576 and Model Metasys Integrator Metasys Integrator Graham Application 3
4 ump N1LAN Application Specific Controller B&B MI4850 MULTI/O Adjustable Frequency Drive Standard NCU RS-232 RS-232 to RS-485 Converter RS-485 (2-wire) Metasys Integrator B&B MI4850 MULTI/O Adjustable Frequency Drive UNT N2 Bus Application Specific Controller graham1 Figure 1: Graham and Metasys Integration PC-Version Panel Version/LTD or Converter Application Specific Controller B&B MI4850 MULTI/O Adjustable Frequency Drive RS-232 RS-232 to RS-485 Converter RS-485 (2-wire) Metasys Integrator B&B MI4850 MULTI/O Adjustable Frequency Drive UNT Application Specific Controller N2 Bus gracomp Figure 2: Graham and Metasys Companion Integration 4 Metasys Integrator Metasys Integrator Graham Application
5 Component Requirements Metasys Release Requirements Metasys Companion Release Requirements To integrate Graham equipment, you ll need: Johnson Controls RS-232 to RS-485 converter (Order Number MM-CVT101-0) Graham Adjustable Frequency Drives, each connected to a B&B MULTI/O MI485D Control Unit RS-232 cable for connecting the converter to Metasys Integrator RS wire cable (for connecting the converter to the control unit) Metasys Integrator N2 Bus (for connecting Metasys Integrator to the Metasys or Companion Network) portable PC for downloading vendor communication tables (.VCT files) and network setup information into Metasys Integrator, drive communication settings, and for running diagnostics Graham setup software (supplied by Graham; Graham representatives are responsible for the setup and operation of Graham equipment) cable for connecting portable PC to Metasys Integrator the correct vendor communication table (.VCT file) to download into Metasys Integrator (supplied on Metasys Integrator diskette) This document describes the RS-232 cable and the vendor communication tables. Graham documentation describes their equipment. The remaining components are described in the Metasys Integrator Technical Bulletin. To integrate Graham equipment into the Metasys Network, you ll need: Metasys OWS software Release 4.0 or higher Metasys Integrator software/firmware Release 4.0 or higher To integrate Graham equipment into the Metasys Companion Network, you ll need: Metasys Companion Release 4.0 or higher Metasys Integrator software/firmware Release 4.0 or higher Metasys Integrator Metasys Integrator Graham Application 5
6 Vendor Component Requirements Integration between Metasys Integrator and Graham has been tested with the equipment listed in Table 1. Changes to this equipment or integration of Graham products not discussed in this document will require additional software development and testing by Systems Products. For information on integrating other products, call Engineering Services in Milwaukee (extension 4357). Table 1: Graham Part and Software Version Numbers Graham Product Model Number Graham Adjustable Frequency Drive B&B MULTI/O Control Unit Setup Software 1576, Rev. 2.3 or higher 1703, Rev. 2.3 or higher MI485D RS-485S Vendor Contact Information Design Considerations Graham Company, Inc W. Bradley Road Milwaukee, WI Application Technical Support: Phone: (414) FAX: (414) When integrating Graham equipment, keep the following considerations in mind: Make sure all Graham equipment is set up, started, and running properly before attempting to integrate with the Metasys or Companion Network. (The Graham representative is responsible for operation of Graham equipment.) Make sure the Adjustable Frequency Drive baud rate is set to 9600 baud. (The Graham representative is responsible for setting the Adjustable Frequency Drive s baud rate.) RS-232 cable distance between Metasys Integrator and the RS-232 to RS-485 converter can be a maximum of 50 feet. Cable distance between the converter and the last Adjustable Frequency Drive can be a maximum of 10,000 feet (for 16 Adjustable Frequency Drives or less). If there are more than 16 drives (from 17 to 31), the maximum distance is 4000 feet. Since capacity control (which variable speed drives are often applied to) requires very fast control loops, this integration does not support output control. For output control, connect these drives to local controllers. 6 Metasys Integrator Metasys Integrator Graham Application
7 Cable Connections Cable Pinouts Use the following cable pinouts for the RS-232 connection between Metasys Integrator and the converter. Vendor Port A or B on Metasys Integrator DB-9 Female RS-232 Port on Converter DB-25 Male Signal Pin RS-232 Pin Signal RD TD GND RTS RD TD GND RTS (50 ft. maximum) graham2 Figure 3: Cable Pinouts Connecting the Cable Connect the female end of the RS-232 cable to either Vendor Port A or Vendor Port B on Metasys Integrator. Connect the male end of the cable to the RS-232 port on the RS-232 to RS-485 converter. Figure 4: Port to Port Connection Metasys Integrator Metasys Integrator Graham Application 7
8 8 Metasys Integrator Metasys Integrator Graham Application
9 Metasys Integrator Setup Metasys Integrator Setup To set up Metasys Integrator, you ll use a portable PC connected to Metasys Integrator Terminal Port. Metasys Integrator setup involves: downloading the correct vendor communication table (.VCT file) setting up the ports assigning network addresses to the controllers The following table provides setup information specific to Graham applications. For detailed procedures, see the Metasys Integrator Technical Bulletin. Table 2: Metasys Integrator Setup for Graham Applications Vendor Communication Table (.VCT File) Model 1576 Adjustable Frequency Drive Model 1703 Adjustable Frequency Drive Port Setup Baud Rate 9600 Word Length 8 Stop Bits 1 Parity Interface Network Setup Vendor Address Timeout Value Poll Delay NPA Address Network Port Address Performance Guide For a single N2 address GR_1576.VCT GR_1703.VCT None RS FF digital, 00-FF analog 1000 ms 0 ms Two addresses per unit: dd,aa where: dd=digital (binary) address aa=analog address Each address must be two digits. No spaces before or after comma. 32 analog and 32 digital address maximum. 1-2 seconds Metasys Integrator Metasys Integrator Graham Application 9
10 Adjustable Frequency Drive Setup Verify that the Adjustable Frequency Drive setup values are set to the factory defaults listed in Table 3. Table 3: Metasys Integrator Setup for Graham Applications Parameter Value Protocol Turnaround Delay 2 Step 10 ms Comm. Timer 0 10 Metasys Integrator Metasys Integrator Graham Application
11 Point Mapping Tables Graham Model 1576 and 1703 Adjustable Frequency Drives To get the hardware reference for mapping points to CS object attributes (via the software model), combine the NPT (Network Point Type) and NPA (Network Point Address). For example, the hardware reference for the Load point is AI2. Graham Model 1703 Adjustable Frequency Drives To get the hardware reference for mapping points to CS object attributes (via the software model), combine the NPT (Network Point Type) and NPA (Network Point Address). For example, the hardware reference for the Load point is AI2. The following table shows the points available for mapping in the Graham Adjustable Frequency Drives. Table 4: Graham Model 1576 Adjustable Frequency Drives NPT 1 NPA 2 Unit Description AI AI 1 2 % % Speed Load BI 1 Drive Fault BI 2 Run Mode BI 3 Current Fault BI 4 Over voltage Fault BI 5 Under Voltage Fault BI 6 Overload Fault 1 Network Point Type 2 Network Point Address 0=stopped 0-100% 0-100% 1=running The following table shows the points available for mapping in the Graham Adjustable Frequency Drives. Table 5: Graham Model 1703 Adjustable Frequency Drives NPT 1 NPA 2 Unit Description AI AI 1 2 % % Speed Load BI 1 Drive Fault BI 2 Run Mode BI 3 Current Fault BI 4 Over voltage Fault BI 5 Under Voltage Fault BI 6 Overload Fault 1 Network Point Type 2 Network Point Address 1=stopped 0-100% 0-100% 0=running Metasys Integrator Metasys Integrator Graham Application 11
12 12 Metasys Integrator Metasys Integrator Graham Application
13 Metasys Network Setup Metasys Network Setup is described in the Metasys Integrator Technical Bulletin. This section contains details specific to Graham applications. Mapping to a CS Object Table 6: Software Model and CS Object Definition Application Model 1576 Adjustable Frequency Drive Model 1703 Adjustable Frequency Drive Software Model (on Models diskette) GR_1576.DDL GR_1703.DDL Display Attribute (recommended) AI1 (speed) AI1 (speed) NT Command Attribute (recommended) AI1 (speed) AI1 (speed) Metasys Integrator Metasys Integrator Graham Application 13
14 14 Metasys Integrator Metasys Integrator Graham Application Notes
15 Notes Metasys Integrator Metasys Integrator Graham Application 15
16 Notes Controls Group FAN E. Michigan Street Metasys Connectivity Technical Manual P.O. Box 423 Metasys Integrator Release 6.0 Milwaukee, WI Printed in U.S.A. 16 Metasys Integrator Metasys Integrator Graham Application
Metasys Integrator Multistack Application
Metasys Connectivity Technical Manual 629.5 Metasys Integrator Section Application Note Issue Date 0998 APPLICATION NOTE Metasys Integrator Multistack Application lntroduction Page *3 Application Details
More informationMetasys Integrator Allen-Bradley Custom Application
Metasys Connectivity Technical Manual 629.5 Metasys Integrator Section Application Note Issue Date 0998 APPLICATION NOTE Metasys Integrator Allen-Bradley Custom Application Introduction Page 3 Application
More informationMetasys Integrator GE Lighting Application
Metasys Connectivity Technical Manual 629.5 Metasys Integrator Section Application Note Issue Date 0998 APPLICATION NOTE Metasys Integrator GE Lighting Application lntroduction Page 3 Application Details
More informationMetasys Integrator United Power Application
Metasys Connectivity Technical Manual 629.5 Metasys Integrator Section Application Note Issue Date 0998 APPLICATION NOTE Metasys Integrator United Power Application lntroduction Page 3 Application Details
More informationMetasys Integrator Powerware Application (previously the Exide Application)
Application Note Issue Date 11/01/01 APPLICATION NOTE Metasys Integrator Powerware Application (previously the Exide Application) lntroduction Page Application Details Component Requirements 4 Vendor Contact
More informationMetasys Integrator Northern Application
Metasys Connectivity Technical Manual 629.5 Metasys Integrator Section Application Note Issue Date 0900 APPLICATION NOTE Metasys Integrator Northern Application lntroduction Page *3 Application Details
More informationMetasys Integrator Caterpillar Application
Application Note Issue Date May, 00 APPLICATION NOTE Metasys Integrator Caterpillar Application Introduction Application Details Component Requirements Vendor Contact Information Design Considerations
More informationN2 Dialer Module. Features and Benefits
Metasys Network Sales Resource Manual 635 Application Specific Controllers Section Product Bulletin Issue Date 1194 N2 Dialer Module The N2 Dialer Module (NDM) provides a low-cost method of connecting
More informationDownloading Metasys Integrator 300 Series Code
M-Tool Manual 693 System Tools Applications Section Issue Date 0101 APPLICATION NOTE Downloading Metasys Integrator 300 Series Code Downloading Metasys Integrator 300 Series Code...3 Introduction...3 Key
More informationMetasys Integrator Cutler-Hammer Application
Application Note Issue Date May, 00 APPLICATION NOTE Metasys Integrator Cutler-Hammer Application Introduction Application Details Component Requirements 9 Vendor Contact Information Design Considerations
More informationMetasys and Companion
Metasys Network Technical Manual 636 App. Notes: Operator Devices Section Technical Bulletin Issue Date 0191 Metasys and Companion Application Page 3 Purpose of Application 3 Setting Up the Windows Terminal
More informationMetasys Integrator 300 Series Commissioning
Metasys Connectivity Technical Manual 629.5 Section Technical Bulletin Issue Date 0900 TECHNICAL BULLETIN 300 Series Commissioning 300 Series Commissioning...3 Introduction...3 Key Concepts...5 Related
More informationUsing Third-Party Remote Communications Software
Metasys Network Technical Manual 636 App. Notes: Third-Party Software Section Application Note Issue Date 0595 APPLICATION NOTE Using Third-Party Remote Communications Software Application Details Page
More informationXT-9100 Technical Bulletin
System 9100 Technical Manual 636.4 Technical Bulletins Section Technical Bulletin Issue Date 0896 XT-9100 Technical Bulletin XT-9100 Extension Module/XP-910x Expansion Modules Page 3 Introduction 3 SX
More informationAPPLICATION NOTE. N2 Dial Application. Using N2 Dial...3. Introduction...3. Key Concepts...4
FANs 637.5, 1637.5 N2 Dial Section Issue Date 0400 APPLICATION NOTE N2 Dial Application Using N2 Dial...3 Introduction...3 Key Concepts...4 N2 Dial Configuration... 4 Downloading with N2 Dial...*6 Dial-in
More informationICC. Metasys N2 Master Driver Manual INDUSTRIAL CONTROL COMMUNICATIONS, INC Industrial Control Communications, Inc.
INDUSTRIAL CONTROL COMMUNICATIONS, INC. Metasys N2 Master Driver Manual January 5, 2018 2018 Industrial Control Communications, Inc. TABLE OF CONTENTS 1 Metasys N2 Master... 2 1.1 Overview... 2 1.2 Connections...
More informationLab and Central Plant Controller
Metasys Network Sales Resource Manual 635 Application Specific Controllers Section Product Bulletin Issue Date 0290 Lab and Central Plant Controller The Metasys Lab and Central Plant (LCP) Controller is
More informationAPPLICATION NOTE JC/85
Metasys Network Technical Manual 636 App. Notes: Network Communications Section Application Note Issue Date 0401 APPLICATION NOTE JC/85 Gateway Introduction Page 3 Application Details *3 Hardware and Software
More informationFieldServer Driver - Serial FS Metasys N2
Driver Version: 1.02 Document Revision: 12 FieldServer Driver - Serial FS-8700-19 Metasys N2 Description The Metasys N2 network supports communications with a diverse range of devices. Many N2 compatible
More information1550-N2 Revision 1.7 A-B Drives Protocol Interface September 1999
1550-N2 Revision 1.7 A-B Drives Protocol Interface September 1999 ProSoft Technology, Inc 9801 Camino Media Suite 105 Bakersfield, CA 93311 (661) 664-7208 (661) 664-7233 Fax http://www.prosoft-technology.com
More informationTC-9102 Terminal Controller
Metasys Network Sales Resource Manual 635 Application Specific Controllers Section Product Bulletin Issue Date 1095 TC-9102 Terminal Controller The TC-9102 Terminal Controller, the latest addition to the
More informationExtended Digital Controller
The Metasys Extended Digital Controller Metasys Network Sales Resource Manual 635 Application Specific Controllers Section Product Bulletin Issue Date 1093 Extended Digital Controller (DX-9100) is the
More informationNDM Configurator. Introduction Page *3. Configuration Files 5. Downloading 17 APPLICATION NOTE
System 9100 Technical Manual 636.4 Network Communications Section Application Note Issue Date 0896 APPLICATION NOTE NDM Configurator Introduction Page *3 Configuration Files 5 Hardware Requirements *5
More informationPolling the N2 Network or Zone Bus for Devices
Metasys Checkout Tool User s Guide 3-1 Chapter 3 Polling the N2 Network or Zone Bus for Devices Introduction The first step in the checkout process is using the Metasys Checkout Tool to find and display
More informationDefining Points. Introduction
M-Series Workstation with Companion/Facilitator Manual 9-1 Chapter 9 Defining Points Introduction This chapter explains how to define software points. Points are software representations of input and output
More informationMetasys System Configuration Tool (SCT)
Product Bulletin Issue Date March 31, 2003 Metasys System Configuration Tool (SCT) As an integral part of the Metasys system extended architecture, the System Configuration Tool (SCT) supports the engineering,
More informationIntroduction to DX LCD Display
DX LCD Display User s Guide 2-1 Chapter 2 Introduction to DX LCD Display Introduction The DX LCD Display unit is a person/controller interface used with the DX-9100 series of controllers. The display can
More informationMetasys N2 Instruction Manual VLT Adjustable Frequency Drive. 12/ Revision B
Metasys N2 Instruction Manual VLT 6000 Adjustable Frequency Drive 12/99-6110-00 Revision B 2 Table of Contents Overview Page Introduction... 5 About this Manual... 5 References... 5 Instructions Abbreviations
More informationTECHNICAL BULLETIN. Using M-Authorize. Using M-Authorize...2. Introduction Key Concepts... 3
Issue Date May 31, 2002 TECHNICAL BULLETIN Using M-Authorize Using M-Authorize...2 Introduction... 2 Key Concepts... 3 Software Authorization... 3 Johnson Controls Software Authorization Form... 3 Detailed
More informationMODBUS/TCP TO SIEMENS G110/G120/MM440 APPLICATION
ICP PANEL-TEC MICROBRIDGE INSTALLATION AND OPERATION GUIDE MODBUS/TCP TO SIEMENS G110/G120/MM440 APPLICATION Revision History Revision Date Author Comments 000 02 June 2009 David Walker Initial release.
More informationSender Receiver Sender
EEE 410 Microprocessors I Spring 04/05 Lecture Notes # 19 Outline of the Lecture Interfacing the Serial Port Basics of Serial Communication Asynchronous Data Communication and Data Framing RS232 and other
More informationUNT1100 Series. Binary Output Jumpers AO2 AO1 AO3 AO4 AOCM AOCM AOCM AOCM AO1. AI Switches Job Information N2 Address. Ref N2+ N2- ADDR 0 = ALL OPEN
1 2 8 4 AI6 R R Installation Bulletin UNT1100 Issue Date 0309 UNT1100 Series Introduction The Unitary (UNT) controller (UNT1100 Series) is a digital controller with applications for air handling units,
More informationICP PANEL-TEC PEX3000 II
ICP PANEL-TEC PEX3000 II MODBUS PORT EXPANDER INSTALLATION AND OPERATION GUIDE REVISION HISTORY Revision Date Author Comments 000 29 Aug 2008 Keira Majors Initial release. 001 16 Sep 2008 David Walker
More informationIntegrity Instruments
Integrity Instruments P.O. Box 451 Order Phone 800-450-2001 Pine River Minnesota Fax Phone 218-587-3414 56474 USA Tech Phone 218-587-3120 http://www.integrityusa.com 485-25A High Speed RTS Enabled RS-232
More informationModular Room Control (MRC) Series Expansion Board
Installation Instructions Issue Date December 13, 2002 Modular Room Control (MRC) Series Expansion Board Application The Modular Room Control (MRC) system has the ability to expand its input/output capabilities
More informationMetasys N1 Network Integration
Product Bulletin Issue Date March 31, 2003 Metasys N1 Network Integration The Metasys N1 Network Integration solution connects existing Metasys N1 based building automation systems into the new generation
More informationMODBUS PLUS TO SIEMENS G110/G120/MM440 APPLICATION
ICP PANEL-TEC MICROBRIDGE INSTALLATION AND OPERATION GUIDE MODBUS PLUS TO SIEMENS G110/G120/MM440 APPLICATION Revision History Revision Date Author Comments 000 3 May 2010 David Walker Initial release.
More informationDisplay. Introduction
Object Dictionary 1 Display Introduction The Display object configures the display of a Local Display Terminal (LDT) in an N30 supervisory controller. Use Project Builder to create a Display object for
More informationFX Input/Output (I/O) Modules XM07 and XM14
Product Bulletin FX I/O Modules Issue Date July 6, 2009 FX Input/Output (I/O) Modules XM07 and XM14 The FX Input/Output (I/O) Modules provide additional physical input and output points for FX field controllers
More informationGuidelines and Recommendations for Better Graphics Performance with Integrated N1 Networks
M-Graphics User s Manual G-1 Appendix G Guidelines and Recommendations for Better Graphics Performance with Integrated N1 Networks Introduction This chapter discusses guidelines and recommendations for
More informationObject Dictionary 1. Pager. Introduction
Object Dictionary 1 Pager Introduction The Pager object provides alarm notifications via pager to personnel at a remote location who would otherwise not be aware of the alarm coming into a workstation
More informationLumio Release Note Lumio Multi-Touch Communication Protocol
Lumio Release Note Lumio Multi-Touch Communication Protocol Note Number RN00009 - Revision A0 Release Date Product Lumio Crystal Touch PCB Controller Abstract This note describes the Lumio Multi Touch
More informationA66N2 Installation and Programming Manual
A66N2 Manual A66N2 Installation and Programming Manual This Manual describes the A66N2 Communications Adapter for the Altivar 66 Variable Frequency Drive, its uses and set up. Effective: 14 February 2001
More informationWebinar Organizers. Ryan Shea. Bruce McDuffee. Joe Ryan. Webinar Moderator. Applications Specialist. Product Manager. Precision Digital Corporation
Webinar Organizers Joe Ryan Product Manager Precision Digital Corporation Ryan Shea Applications Specialist Precision Digital Corporation Bruce McDuffee Webinar Moderator Precision Digital Corporation
More informationTongta Inverter TDS-F8
Tongta Inverter TDS-F8 MODBUS Communication Application Manual Please ensure the user gets this manual, for the optimal use of this device. 1. Introduction: TEK-DRIVE / TDS-F8 INVERTER MODBUS Communication
More informationN2 Binary Output/ BACnet Binary Output
Object Dictionary 1 N2 Binary Output/ BACnet Binary Output Introduction Note: The Johnson Controls Binary Output object is considered a BACnet Binary Output object because it supports BACnet functionality.
More informationN30 Supervisory Controller Installation
Technical Bulletin Issue Date July 25, 2002 N30 Supervisory Controller Installation N30 Supervisory Controller Installation...2 Introduction... 2 Key Concepts... 3 Installation Site Considerations... 3
More informationN2 Binary Input/ BACnet Binary Input
Object Dictionary 1 N2 Binary Input/ BACnet Binary Input Introduction Note: The Johnson Controls Binary Input object is considered a BACnet Binary Input object, because it supports BACnet functionality.
More informationConnecting UniOP to the ABB 07KT97 Controllers
Connecting to the ABB 07KT97 Controllers This Technical Note contains the information needed to connect to the ABB 07 KT 97 controllers. The ABB 07 KT 97 supports communication via standard Modbus RTU
More informationMetasys Checkout Tool User s Guide
Table of Contents Metasys Checkout Tool User s Guide Chapter 1 Using This Guide...1-1 Introduction... 1-1 Key Concepts... 1-2 Chapter Organization...1-2 Chapter 2 Introduction to the Metasys Checkout Tool...2-1
More informationMultistate Value/ BACnet Multistate Value
Object Dictionary 1 Multistate Value/ BACnet Multistate Value Introduction Note: The Johnson Controls Multistate Value object is considered a BACnet Multistate Value object because it supports BACnet functionality.
More informationXTM Configurator. Introduction Page 3. Theory of Operation *3. Configuration Procedures 7
FANs 636.4, 1628.4 XTM/XPx Section Technical Bulletin Issue Date 0400 XTM Configurator Introduction Page 3 Theory of Operation *3 Configuration Procedures 7 Design Considerations 8 Start XTM Configurator
More informationOutput Relay Latched Function Module
Metasys Network Technical Manual 636 Function Modules Section Technical Bulletin Issue Date 0793 Output Relay Latched Function Module Introduction Page 3 Description 3 Application 4 Capabilities 4 Theory
More informationSeaLINK+8/USB. Sealevel Systems, Inc P.O. Box 830 Liberty, SC USA. Phone: (864) FAX: (864)
TM SeaLINK+8/USB Part # 280X Sealevel Systems, Inc P.O. Box 830 Liberty, SC 29657 USA Phone: (864) 843-4343 FAX: (864) 843-3067 www.sealevel.com Contents INTRODUCTION... 1 INSTALLATION INSTRUCTIONS...
More informationLN Series Input/Output (I/O) Extension Modules and LN Communicating Sensors Subnetwork for LN-VAVCF-12 and LN-PRGxxx-12 Application Note
LN Series Input/Output (I/O) Extension Modules and LN Communicating Sensors Subnetwork for LN-VAVCF-12 and LN-PRGxxx-12 Application Note LN-IOE400-0, LN-IOE410-0, LN-IOE420-0, LN-VAVCF-12, LN-PRGxxx-12
More informationMetasys Web Access System Overview
Technical Bulletin Issue Date February 18, 2003 Metasys Web Access System Overview Metasys Web Access System Overview...2 Introduction... 2 Key Concepts... 3 Related Information... 3 Hardware and Software
More informationFX Tools Express Software Package
Product Bulletin FX Tools Express Issue Date October 31, 2005 FX Tools Express Software Package FX Tools Express is a Windows based software package for configuring, downloading and commissioning of predefined
More informationPowerFlex 700H Drive Firmware (Revision )
Release Notes PowerFlex 700H Drive Firmware (Revision 67.001) These release notes correspond to revision 67.001 of firmware for PowerFlex 700H drives. This document describes the differences between firmware
More informationSeaLINK+8/USB. Sealevel Systems, Inc 155 Technology Place P.O. Box 830 Liberty, SC USA
TM SeaLINK+8/USB Part # 280X Sealevel Systems, Inc 155 Technology Place P.O. Box 830 Liberty, SC 29657 USA Phone: (864) 843-4343 FAX: (864) 843-3067 www.sealevel.com Contents INTRODUCTION... 1 OVERVIEW...1
More informationOutput Relay Electrical Function Module
Metasys Network Technical Manual 636 Function Modules Section Technical Bulletin Issue Date 0294 Output Relay Electrical Function Module Introduction Page 3 Description 3 Application 4 Capabilities 4 Theory
More informationIntroduction to the N30 Supervisory Controller
N30 Supervisory Controller User s Manual 2-1 Chapter 2 Introduction to the N30 Supervisory Controller Introduction This chapter describes the basic functions and operation of an N30 Supervisory Controller
More informationGeneral Specifications
General Specifications GS 48D50Z00-00E-N C0-950-00 Basic Communication System ProSafe-COM A major part of this functionality is mapped upon an industrial PC, thus representing ProSafe- COM. The basic hardware
More informationNetwork Port. Introduction Page 3. Engineering 9. Installation Procedures 13. Commissioning Procedures 17. Defining Objects 21
Metasys Connectivity Technical Manual 629.5 Network Port Section Technical Bulletin Issue Date 0401 Network Port Introduction Page 3 Description 3 Key Terms 4 Hardware 6 System Requirements 6 Communication
More informationREL 512 Connectivity With A Harris Westronics RTU Using DNP 3.0
ABB Application Note Substation Automation and Protection Division REL 512 AN-45A-99 REL 512 Connectivity With A Harris Westronics RTU Using DNP 3.0 ABSTRACT: DNP 3.0 is a popular communication protocol
More informationTechnical Manual for RT-EX-9017
Technical Manual for RT-EX-9017 Version 2.01 8 x Analog Input (16 bit) Introduction The EX9017 MODBUS I/O Expansion module is a high-quality and low-cost add-on data acquisition device that allows expanding
More informationS300-DIN-RDR2SA Address Mode Configuration
Technical Bulletin Issue Date August 17, 2010 S300-DIN-RDR2SA Address Mode Configuration The S300-DIN-RDR2SA (also referred to as ) can be addressed in two ways: legacy mode and physical address mode.
More informationNetwork Terminal. Features and Benefits. Metasys Network Sales Resource Manual 635 Operator Devices Section Product Bulletin Issue Date 0190
Metasys Network Sales Resource Manual 635 Operator Devices Section Product Bulletin Issue Date 0190 Network Terminal The Network Terminal (NT) can put the precise facility management capabilities of Metasys
More informationTrend Log/BACnet Trend Log
Object Dictionary 1 Trend Log/BACnet Trend Log Introduction Notes: The Johnson Controls Trend Log object is considered a BACnet Trend Log object because it supports BACnet functionality. In addition, this
More informationStatic Pressure High Limit
Metasys Network Technical Manual 636 Air Handlers Section Technical Bulletin Issue Date 0590 Static Pressure High Limit Static pressure high limit File Name Path Name Main Function Accessories How It Works
More informationPCI Hardware Installation
PCI Hardware Installation Product Overview The RocketPort PCI series multiport serial card fits into the PCI slot of a personal computer, and uses a 36 MHz processor that is specifically designed to process
More informationCDN220 HIGH DENSITY I/O ADAPTER USER GUIDE
CDN220 HIGH DENSITY I/O ADAPTER USER GUIDE 13022001 (c) Copyright DIP Inc., 1996 DIP Inc. P.O. Box 9550 MORENO VALLEY, CA 92303 714-924-1730 CONTENTS CDN220 PRODUCT OVERVIEW 1 CDN220 INSTALLATION 2 POWER
More informationVariable Air Volume Modular Assembly (VMA) 1400 Series
Product Bulletin Issue Date March 27, 2009 Variable Air Volume Modular Assembly (VMA) 1400 Series The Variable Air Volume Modular Assembly (VMA) Series is a family of configurable digital controllers.
More informationMetasys System Extended Architecture
Product Bulletin Issue Date March 31, 2003 Metasys System Extended Architecture The architecture of the Metasys building automation and facilities management system has been extended to be fully compatible
More informationAppendix C. Datum Systems PSM-4900 Satellite Modem. Cabling Specifications
DATUM SYSTEMS Appendix C Datum Systems PSM-4900 Satellite Modem Cabling Specifications PSM-4900 VSAT / SCPC - Cabling Specifications Revision History Rev 1.0 6-10-2000 Preliminary Release. Rev 1.1 8-1-2000
More informationM-Tool. Features and Benefits System Configuration and Project Management. Allows fast adjustment and commissioning of systems
Product Bulletin Issue Date July 6, 2006 Supersedes June 30, 2004 M-Tool M-Tool transforms the way you create control strategies by providing a suite of tools with an intuitive and efficient work environment.
More informationMetasys Installation and Platform Requirements
Issue Date June 1, 2002 TECHNICAL BULLETIN Metasys Installation and Platform Requirements Metasys Installation and Platform Requirements...2 Introduction... 2 Key Concepts... 3 Operating System Support...
More informationSoftware Details and Hardware Connections
GX-00 Software Configuration Tool User s Guide - Chapter Software Details and Hardware Connections Introduction This chapter describes the tasks you perform before using the GX Tool. This chapter describes:
More informationMetasys for Validated Environments (MVE) Installation and Platform Requirements
Issue Date 2/7/03 TECHNICAL BULLETIN Metasys for Validated Environments (MVE) Installation and Platform Requirements Metasys for Validated Environments (MVE) Installation and Platform Requirements...2
More informationN2 Analog Input/ BACnet Analog Input
Object Dictionary 1 N2 Analog Input/ BACnet Analog Input Introduction Note: The Johnson Controls N2 Analog Input object is considered a BACnet Analog Input object because it supports BACnet functionality.
More information1782-JDO DeviceNet-to-Optomux Gateway User s Manual
1782-JDO DeviceNet-to-Optomux Gateway User s Manual Western Reserve Controls, Inc. Although every effort has been made to insure the accuracy of this document, all information is subject to change without
More informationTitle: Using the AUX Port.
Title: Using the AUX Port. Article Number: 1090 Date: 03/15/05 Information in this article applies to: HMI Silver Series (Enhanced Versions OIT Product(s All Controller (PLC Product(s N/A Summary HMI generation
More informationWorking with Objects and the M-View Screen
Project Builder User s Guide 6-1 Chapter 6 Working with Objects and the M-View Screen Introduction The Project Builder uses a variety of objects to configure controllers and perform tasks. This chapter
More informationSCADALink IP100 SCADA Terminal Server QUICK START GUIDE Revision 1.42 June 19, 2012
SCADA Terminal Server QUICK START GUIDE Revision 1.42 June 19, 2012 www.scadalink.com INTRODUCTION Use this Quick Start Guide to configure a SCADALink IP100. Full documentation is found under the IP100
More information1. Safety Danger Warnings Earthing and earth fault protection... 4
vacon 1 INDEX Document: DPD00386A Version release date: 24.9.10 1. Safety... 2 1.1 Danger... 2 1.2 Warnings... 3 1.3 Earthing and earth fault protection... 4 2. Metasys N2 - general info... 5 3. N2 technical
More informationMiniature Asynchronous 4-Wire High Speed Modems
ME1862A-F ME1863A-F JULY 2003 ME1862A-M ME1863A-M Miniature Asynchronous 4-Wire High Speed Modems CUSTOMER SUPPORT INFORMATION Order toll-free in the U.S.: Call 877-877-BBOX (outside U.S. call 724-746-5500)
More informationMetasys Smoke Control Wiring
Metasys Network Technical Manual 636 Smoke Control Section Technical Bulletin Issue Date 1199 Metasys Smoke Control Wiring Metasys Smoke Control Wiring Page 3 Overview 3 References 4 Power Entry 5 Metasys
More informationRS-232 Fiber Link Card System
USER GUIDE The leader in rugged fiber optic technology. U-152 2018B-0406 Fiber Link Card System SYSTEM INSTALLATION INFORMATION Introduction The Fiber Link Card system transports a full 9-Pin copper signal
More informationELAN DIGITAL SYSTEMS LTD. CF232 COMPACT FLASH CF+ CARD USER S GUIDE
ELAN DIGITAL SYSTEMS LTD. LITTLE PARK FARM ROAD, SEGENSWORTH WEST, FAREHAM, HANTS. PO15 5SJ. TEL: (44) (0)1489 579799 FAX: (44) (0)1489 577516 e-mail: support@pccard.co.uk website: http://www.pccard.co.uk
More informationICN Mini Link/External. User s Guide. 1733N Model A Mini Link/EXT (Version 1) 1732N Model A ICN Interface Board (Version 1)
ICN Mini Link/External User s Guide 1733N Model A Mini Link/EXT (Version 1) 1732N Model A ICN Interface Board (Version 1) MicroMod Automation, Inc. The Company MicroMod Automation is dedicated to improving
More informationTroubleshooting the NAE/NIE
Technical Bulletin Issue Date March 31, 2003 Troubleshooting the NAE/NIE Troubleshooting the NAE/NIE...2 Introduction... 2 Key Concepts... 3 NAE... 3 Power-Up LED Sequence... 4 System RE-BOOT Switch...
More informationN1 Migration with the NIE
Technical Bulletin Issue Date April 29, 2003 N1 Migration with the NIE N1 Migration with the NIE...3 Introduction... 3 Key Concepts... 4 N1 Migration Overview... 4 N1 Migration Flowchart... 5 Metasys N1
More informationM-Bus Central Unit. Use
6 M-Bus Central Unit OZW The M-bus central unit is used for the remote readout, remote operation and supervision of an M-bus plant with a maximum of consumption meters and controllers featuring an M-bus
More informationUser's Manual PLC09 Modbus Converter for PAL-AT Leak Detection System
User's Manual PLC09 Modbus Converter for PAL-AT Leak Detection System PermAlert ESP, Inc. 7720 Lehigh Ave. Niles, IL 60714 847-966-2190 2 INDEX 1.0 Introduction 4 1.1 Features 4 2.0 Installation 4 2.1
More informationUSB-TTL-5 PRODUCT IS A COMBINATION OF PRODUCTS USB AND TTL-232-5P BOTH DATASHEETS ARE INCLUDED IN THIS PDF FILE
USB-TTL-5 PRODUCT IS A COMBINATION OF PRODUCTS USB-232-2 AND TTL-232-5P BOTH DATASHEETS ARE INCLUDED IN THIS PDF FILE USB-232-2 USB 2.0 To RS-232 Converter DB9 www.serialcomm.com Datasheet Revision 2.4
More informationEthernet IP Datalink. Introduction
Object Dictionary 1 Ethernet IP Datalink Introduction The Ethernet Internet Protocol (IP) Datalink object manages the Ethernet communications bus and the messages transmitted on it. This object allows
More informationDNP3 Communication User's manual
MV Network Management Fault tracking Monitoring and Control Merlin Gerin Easergy Range T200 P, T200 I DNP3 Communication User's manual Summary General...2 Functionnalities...2 Characteristics...2 Connection
More informationWrenchman, Inc Old Hwy. # 8 Suite # 122 New Brighton, Minnesota (651)
Wrenchman, Inc. 1801 Old Hwy. # 8 Suite # 122 New Brighton, Minnesota 55112 (651) 638-9012 468X Interface Cable Specifications The Interface Cable emulates the Async RS-232 logical interface supported
More informationSTEP X - Name of Step QUICK START GUIDE SP385A-R3, SP390A-R3 USB TO RS CONVERTER 24/7 TECHNICAL SUPPORT AT OR VISIT BLACKBOX.
STEP X - Name of Step QUICK START GUIDE SP385A-R3, SP390A-R3 USB TO RS CONVERTER 24/7 TECHNICAL SUPPORT AT 877.877.2269 OR VISIT BLACKBOX.COM STEP 1 - Package Includes/System Requirements PACKAGE INCLUDES
More informationInstalling the DX LCD Display
DX LCD Display User s Guide 3-1 Chapter 3 Installing the DX LCD Display Introduction Use the DX LCD Display as either a portable device, or permanently mount it in a panel or on the wall. For panel and
More informationSystem-10 BTU Meter BACnet Network Interface Installation Guide
BACnet ONICON Flow and Energy Measurement System-10 BTU Meter BACnet Network Interface Installation Guide 11451 Belcher Road South, Largo, FL 33773 USA Tel +1 (727) 447-6140 Fax +1 (727) 442-5699 0652-12
More information