FPD-7024 Fire Alarm Control Panel Version 1.03

Size: px
Start display at page:

Download "FPD-7024 Fire Alarm Control Panel Version 1.03"

Transcription

1 FPD-7024 Fire Alarm Control Panel Version 1.03 Program Record Sheet Account Information: Account: Date: Name: Address: Panel Phone #: Contact Phone #: Contact Person: Comments: Panel Location: Notes: Program Time Default values are in bold. System Date and Time Auto Test 1) Test Time: 0200 (24-hour military format) 2) Test Frequency (Circle one): 1-4 hours 2-12 hours 3-24 hours 4-7 days 5-28 days 3) Daylight Savings Time: 1) DISABLE 2) ENABLE

2 Security User PINS Worksheet (User 0 to 69) User # 0 is the Programmer PIN. User # 1 is the panel default PIN. Authority Key: 0 = none; 1 = maximum; 2 = medium; 3 = minimum User # PIN Authority User Name User # PIN Authority User Name F01U Page Bosch Security Systems, Inc.

3 User PINS Worksheet (User 70 to 99) User # Authority Key: 0 = none; 1 = maximum; 2 = medium; 3 = minimum PIN Authority User Name User # PIN Authority User Name Program System Timers Default values are in Bold. Smoke Reset 6 sec (1-16 seconds) AC Fail Delay 6 hours (0-24 hours, or wait for DC) Auto Silence 0 min (5-99 minutes) Display Rate 4=1 sec (1-16 ¼ seconds) AC Line Sync 1) 50Hz 2) 60Hz (circle one) Option Bus, # of Keypads 0 (1-4) PIN Required, Local 1) YES 0) NO (circle one) PIN Required, Remote 1) YES 0) NO (circle one) NAC SIL MODE 1) AUDIBLE ONLY 2) AUDI & VISI (circle one) Remote Program 1) ENABLE 0) DISABLE (circle one) 2012 Bosch Security Systems, Inc. Page 3 F01U

4 Program Inputs Input Point Worksheet (Points 1 to 25) Point Number Points 4-8 require a 4-Point Expander Module. Points are available only with a Multiplex Expansion Module. See the Point Function Worksheet on Page 6 when filling in the Point Function column. Use the MUX Device Type Key when filling in the MUX Device Type column. Photocopy the blank table on Page 5 for Point Numbers Point Function (see p. 6) Alarm/ Trouble on Open Zone Verification Latching MUX Device Type 0 No Device 2 Single Input 3 I/O Module 4 MUX Smoke 5 Smoke w/frz 6 Dual Input 7 Octal Input Mux Device Type Key Text (write in description) =alarm =no 0=no see key 2=trouble 1=yes 1=yes F01U Page Bosch Security Systems, Inc.

5 Point Input Worksheet (Point to ) Point Number Photocopy this page for Point Numbers See the Point Function Worksheet on Page 6 when filling in the Point Function column. Use the MUX Device Type Key when filling in the MUX Device Type column. Point Function (see p. 6) Alarm/ Trouble on Open Zone Verification Latching MUX Device Type Text (write in description) =alarm =no 0=no see key 2=trouble 1=yes 1=yes * zone default for points 20-39=10, 40-59=11, 60-79=12, and so on Bosch Security Systems, Inc. Page 5 F01U

6 Point Function Worksheet The default values are shown. 1 Fire 2 Waterflow 3 Supervisory 4 (reserved) 5 Reset 6 Silence Parameters 7 AC Fault Function Configure Key Point Function Configure Local Only Silenceable Loop Response see key 0=no 0=no 1=fast 1=yes 1=yes 2=programmable 1 1-fire 0-no 0-no 1-fast 2 1-fire 0-no 0-no 1-fast 3 1-fire 0-no 0-no 1-fast 4 2-waterflow 0-no 0-no 2-16 sec. 5 1-fire 0-no 0-no 1-fast 6 1-fire 0-no 0-no 1-fast 7 1-fire 0-no 0-no 1-fast 8 1-fire 0-no 0-no 1-fast 9 1-fire 0-no 0-no 1-fast 10 1-fire 0-no 0-no 1-fast 11 3-supervisory 0-no 0-no 1-fast 12 1-fire 0-no 0-no 1-fast 13 1-fire 0-no 0-no 1-fast 14 1-fire 0-no 0-no 1-fast 15 1-fire 0-no 0-no 1-fast 16 1-fire 0-no 0-no 1-fast F01U Page Bosch Security Systems, Inc.

7 Program s (NACs and Relays) Default values are shown. Configuration Zone A Parameters Zone B Zone C Onboard and Expansion NACs NAC NAC Remote NAC Module 1- requires a Remote NAC Power Supply Remote NAC Module 2 requires a Remote NAC Power Supply Remote NAC Module 3 requires a Remote NAC Power Supply Remote NAC Module 4 requires a Remote NAC Power Supply Local Relays Local Relay Local Relay Local Relay Remote Relay Module 1- requires an Octal Relay Module Relay Relay Relay Relay Relay Relay Relay Relay Remote Relay Module 2 - requires an Octal Relay Module Relay Relay Relay Relay Relay Relay Relay Relay Zone D 1 Steady 2 Pulsing 3 California March 4 Temporal 5 Wheelock 6 Gentex 7 System Sensor Configuration Key ( Pattern) 63 General alarm (does not 62 General trouble 61 General waterflow (does not 60 No AC 59 Alarm verification 58 General supervisory alarm (does not 57 Communication trouble 56 General waterflow (silencing) 55 General supervisory (silencing) 54 Activates for ground start 53 General fire 52 General fire (does not 51 (reserved) 1-50 User assigned to inputs Zone Key 2012 Bosch Security Systems, Inc. Page 7 F01U

8 Program s (Mux s) Multiplex outputs are not supported by all panels. Photocopy the blank table on Page 9 for Point Numbers Device Address Zone A Parameters Zone B Zone C Zone D 63 General alarm (does not 62 General trouble 61 General waterflow (does not 60 No AC 59 Alarm verification 58 General supervisory alarm (does not 57 Communication trouble 56 General waterflow (silencing) 55 General supervisory (silencing) 54 Activates for ground start 53 General fire 52 General fire (does not 51 (reserved) 1-50 User assigned to inputs Zone Key For MUX relay outputs, be sure to carefully select an appropriate output zone, or 0, for each output zone entry. The defaults supplied by the panel assume that an input is installed at the address, and are not appropriate when output modules are installed instead. F01U Page Bosch Security Systems, Inc.

9 MUX Worksheet (MUX to ) Photocopy this page for MUX outputs Use the MUX Device Type Key when filling in the MUX Device Type column. Device Address Zone A Parameters Zone B Zone C Zone D 63 General alarm (does not 62 General trouble 61 General waterflow (does not 60 No AC 59 Alarm verification 58 General supervisory alarm (does not 57 Communication trouble 56 General waterflow (silencing) 55 General supervisory (silencing) 54 Activates for ground start 53 General fire 52 General fire (does not 51 (reserved) 1-50 User assigned to inputs Zone Key 2012 Bosch Security Systems, Inc. Page 9 F01U

10 Program Accounts Default values are in Bold. Phone Numbers Worksheet Fill in the information on the lines provided. Phone Number or IP address 1: Port Number 1: Account Number 1: Phone Number or IP address 2: Port Number 2: Account Number 2: Computer Phone or IP Address: Press See Action [TEST] 1 * Touch Tone * [TEST] 2 # Touch Tone # [TEST] 3 / 3 second delay [TEST] 4 > Wait for dial tone Special Phone Number Characters Phone 1 (Circle the desired setting) Format: (0) DISABLE (1) 3/1 (2) 4/2 (3) BFSK (4) SIA 110 (5) CONTACT ID (6) SIA 300 (7) Modem IIIa 2 Tone: (1) 19D, 14A, 10PS (2) 18D, 23A, 10PS (3) 19D, 14A, 20PS (4) 18D, 23A, 20PS (5) 19D, 14A, 40PS (6) 18D, 23A, 40PS Phone 2 (Circle the desired setting) Format: (0) DISABLE (1) 3/1 (2) 4/2 (3) BFSK (4) SIA 110 (5) CONTACT ID (6) SIA 300 (7) Modem IIIa 2 Tone: (1) 19D, 14A, 10PS (2) 18D, 23A, 10PS (3) 19D, 14A, 20PS (4) 18D, 23A, 20PS (5) 19D, 14A, 40PS (6) 18D, 23A, 40PS Phone Control Worksheet Circle the desired setting. Line 1 Line 2 Monitor Line: (1) YES (0) NO (1) YES (0) NO Dialing Type: (1) PULSE ONLY (2) TONE/PULSE (3) TONE ONLY (1) PULSE ONLY (2) TONE/PULSE (3) TONE ONLY Report Steering Worksheet Circle the desired setting. 1) Non-supervisory Alarm (1) Phone 1 (2) Phone 2 (3) Phones 1 and 2 (4) Phone 2 Backup (5) No Report 2) Supervisory Alarm 3) Non-supervisory Restoral 4) Supervisory Restoral (1) Phone 1 (2) Phone 2 (3) Phones 1 and 2 (4) Phone 2 Backup 5) No Report (1) Phone 1 (2) Phone 2 (3) Phones 1 and 2 (4) Phone 2 Backup 5) No Report (1) Phone 1 (2) Phone 2 (3) Phones 1 and 2 (4) Phone 2 Backup 5) No Report 5) Trouble (1) Phone 1 (2) Phone 2 (3) Phones 1 and 2 (4) Phone 2 Backup 5) No Report 6) Tests (1) Phone 1 (2) Phone 2 (3) Phones 1 and 2 (4) Phone 2 Backup 5) No Report 7) Silence (1) Phone 1 (2) Phone 2 (3) Phones 1 and 2 (4) Phone 2 Backup 5) No Report 8) Reset (1) Phone 1 (2) Phone 2 (3) Phones 1 and 2 (4) Phone 2 Backup 5) No Report 9) Fire Drill (1) Phone 1 (2) Phone 2 (3) Phones 1 and 2 (4) Phone 2 Backup 5) No Report F01U Page Bosch Security Systems, Inc.

11 Ring Count Ring Count Default : 00 ALTER COMM 0 = Network 1 = Serial Communicator Tries Communicator Tries Default : 10 Answering Machine Bypass 1) YES 2) NO Program Formats Default values are in Bold. Data range is 0-9, A-F. 4/2 Point Reports Worksheet Fill in the desired setting in the User Setting column. Report Digit 1 Default Value Digit 1 User Setting Report Digit 2 Default Value User Setting Fire Alarm 0 Point 1 1 Fire Restore 3 Point 2 2 Waterflow 0 Point 3 3 Supervise 0 Point 4 4 Trouble 6 Point 5 5 Trouble Restl 3 Point 6 6 Disable B Point 7 7 Disable Restl 3 Point 8 8 Point 9 9 Point /2 General Report Codes Worksheet Fill in the desired setting in the User Setting column. Data range is 00-FF. Report Digit 1 Default Value Digit 1 User Setting Report Digit 2 Default Value User Setting System in Test F1 AC Fail Restore EA System Test Rstl E1 Test Report EE Silence 9F Off Normal Test FD Fire Drill F2 Phone 1 Trbl FB Fire Drill Restl E2 Phone 1 Trbl Rstl EB Open Rst Report 9F Phone 2 Trbl FC Low Batt F9 Phone 2 Trbl Rstl EC Low Batt Restore E9 System Trbl FD AC Fail FA System Trbl Rstl ED 2012 Bosch Security Systems, Inc. Page 11 F01U

12 BFSK Reporting Codes Worksheet (for special reports) Fill in the desired setting in the User Setting column. Data range is 00-FF. BFSK Reporting Codes Default Value User Setting Off Normal Test Open/Reset Silence Fire Drill Fire Drill Restl FD FD FD FD ED Program Mux Mux Bus type (1) CLASS A (2) CLASS B Notes 2012 Bosch Security Systems, Inc. 130 Perinton Parkway, Fairport, NY USA (800) F01U Program Record Sheet 7/12 FPD-7024 FACP Page 12 of 12

Fire Communicator (DACT)

Fire Communicator (DACT) Fire Communicator (DACT) 1.0 Account Information Account: Name: Address: System Phone Number: Contact Person: Date: Contact Phone: Comments: Communicator Location: Notes: Note: All default values are shown

More information

Control Panel D9112. Release Notes for Version 7.00 March Introduction. 2.0 Requirements. 4.0 Previous Version 6.

Control Panel D9112. Release Notes for Version 7.00 March Introduction. 2.0 Requirements. 4.0 Previous Version 6. Control Panel D9112 Release for Version 7.00 March 2007 1.0 Introduction Although the D9112 (expanded version) Control Panel is no longer manufactured (replaced by the D9412G), Firmware Update Kits (P/N:

More information

Control Panel D9124. Release Notes for Version 7.00 March Introduction. 2.0 Requirements. 4.0 Previous Version 6.

Control Panel D9124. Release Notes for Version 7.00 March Introduction. 2.0 Requirements. 4.0 Previous Version 6. Control Panel Release for Version 7.00 March 2007 1.0 Introduction Firmware Update Kits (P/N: D9499-0700) are available for this product. Refer to the D9412G/D7412G Program Entry Guide (P/N: 47775D or

More information

Property of Monitronics Inc

Property of Monitronics Inc Enter Program (Locations 034 to 410) 1. Press Program Button on main panel 2. At keypad press 9 + Program Code (9 8 7 6 5) or 1. Power down with black switch on bottom left of panel 2. Power up while holding

More information

VISTA-128BP/VISTA-250BP Programming Form

VISTA-128BP/VISTA-250BP Programming Form VISTA-128BP/VISTA-250BP Programming Form Some fields are programmed for each partition (shown as shaded fields). If you are programming a multiple-partition system, see the Partition-Specific Fields section

More information

*00 INSTALLER CODE Enter 4 digits, 0-9 [4140] *28 POWER UP IN PREVIOUS STATE [1=yes] 0=no; "1" for UL.

*00 INSTALLER CODE Enter 4 digits, 0-9 [4140] *28 POWER UP IN PREVIOUS STATE [1=yes] 0=no; 1 for UL. 4140XMPT2 PROGRAMMING FORM Some fields are programmed for each partition (shown as shaded fields). See the PARTITION-SPECIFIC section for programming these fields. Standard default (*97) values are shown

More information

1HWZRU;1;( Table of Contents. General Description...2. Ordering Information...2. Feature Definitions...3. Programming the LED Keypads...

1HWZRU;1;( Table of Contents. General Description...2. Ordering Information...2. Feature Definitions...3. Programming the LED Keypads... HWZRU;;( Control/Communicator Installation Manual Table of Contents General Description... Ordering Information... Feature Definitions... Programming the LED Keypads... Programming the NX-E...9 Types of

More information

XR500/XR100 Command Processor Review. a) Zone expanders c) Output expanders b) All of these d) Single point detectors

XR500/XR100 Command Processor Review. a) Zone expanders c) Output expanders b) All of these d) Single point detectors Name Answer Key Company Address City, State, Zip Instructor Date Your email User Name = Password = XR500/XR100 Command Processor Review 1. may be connected to the LX-Bus. a) Zone expanders c) Output expanders

More information

Control Panel. D9412GV4/D7412GV4/D7212GV4 v1.xx. Release Notes

Control Panel. D9412GV4/D7412GV4/D7212GV4 v1.xx. Release Notes Control Panel D9412GV4/D7412GV4/D7212GV4 v1.xx en Release Notes Control Panel Table of contents en 3 Table of contents 1 Introduction 4 1.1 About documentation 4 1.1.1 Bosch Security Systems, Inc. product

More information

Commercial Fire and Burglary Partitioned Security System with Scheduling. Programming Guide. K0376PRV5 2/11 Rev. A

Commercial Fire and Burglary Partitioned Security System with Scheduling. Programming Guide. K0376PRV5 2/11 Rev. A VISTA-128FBP VISTA-250FBP Commercial Fire and Burglary Partitioned Security System with Scheduling Programming Guide K0376PRV5 2/11 Rev. A Table of Contents Programming Field Settings for UL864 Compliance

More information

MCM Electronics MCM Electronics MCM Electronics. The Icon Series. Installation and Programming Information. Icon 8 Version 5.0

MCM Electronics MCM Electronics MCM Electronics. The Icon Series. Installation and Programming Information. Icon 8 Version 5.0 MCM Electronics MCM Electronics MCM Electronics The Icon Series Installation and Programming Information Icon 8 Version 5.0 TABLE OF CONTENTS 1. 2. 3. Panel Hardware Page 2 Physical Layout. Inputs. Outputs.

More information

FOCUS 200 PLUS A CCC #: _ / / _ / ( _ ) _ - 35(/,0,1$5< -8/< Security Services CUSTOMER CONTROL UNIT TELEPHONE NUMBER:

FOCUS 200 PLUS A CCC #: _ / / _ / ( _ ) _ - 35(/,0,1$5< -8/< Security Services CUSTOMER CONTROL UNIT TELEPHONE NUMBER: CMP-DF2V1 7/01 Security Services SALES REPS: PLEASE FILL IN ALL WHITE AREAS. FOCUS 200 PLUS A CUSTOMER SYSTEM INVENTORY AND DATA ENTRY FORMS CCC #: _ / / _ / CUSTOMER CONTROL UNIT TELEPHONE NUMBER: ( _

More information

4140XMPT2 PROGRAMMING FORM

4140XMPT2 PROGRAMMING FORM 414XMPT2 PROGRAMMING FORM Some fields are programmed for each partition (shown as shaded fields). See the PARTITION-SPECIFIC section for programming these fields. Standard default (*97) values are shown

More information

D1265. Installation Guide. Touchscreen Keypad

D1265. Installation Guide. Touchscreen Keypad D1265 EN Installation Guide Touchscreen Keypad D1265 Installation Guide 1.0 Introduction Contents 1.0 Introduction...3 1.1 Overview...3 1.2 Graphical Buttons...3 1.3 Audible Tones...4 1.4 Supervision...4

More information

Property of Monitronics Inc

Property of Monitronics Inc Enter Program 1. Master Code + 8 + 0 + 0 (Display should show 20) or Power down then back up and press * and # within 1 minute (If exiting programming you can re-enter within 1 minute by pressing * and

More information

Property of Monitronics Inc

Property of Monitronics Inc Enter Program 1. 4112 + 8 + 0 + 0 (Display should show 20) or Power down then back up and press * and # within 1 minute (If exiting programming you can re-enter within 1 minute by pressing * and #) Exit

More information

PFC-6006 Reporting Codes Summary

PFC-6006 Reporting Codes Summary Report by Point The following table identifies the reporting codes generated for specific panel events when reporting by point. Report By Point SIA Format Contact ID Format System Power Up RR 1 305 00

More information

Intrusion Control Panels Quick Guide. May 2015

Intrusion Control Panels Quick Guide. May 2015 Intrusion Control Panels Quick Guide May 2015 Control Panels B Series Commercial Type Number B3512 B4512 B5512 Applications Type Residential, Small Commercial Residential, Small Commercial Residential,

More information

R A D I O N I C S. D7212B Control/Communicator Program Entry Guide C 9/95

R A D I O N I C S. D7212B Control/Communicator Program Entry Guide C 9/95 R A D I O N I C S D7212B Control/Communicator Program Entry Guide 74-06915-000-C 9/95 Notice The material and instructions covered in this manual have been carefully checked for accuracy and are presumed

More information

RANGER 9000E DOWNLOADABLE CONTROL COMMUNICATOR INSTALLATION MANUAL

RANGER 9000E DOWNLOADABLE CONTROL COMMUNICATOR INSTALLATION MANUAL RANGER 9000E DOWNLOADABLE CONTROL COMMUNICATOR INSTALLATION MANUAL TABLE OF CONTENTS GENERAL DESCRIPTION... 2 STANDARD AND OPTIONAL PARTS LIST... 2 FEATURE DEFINITIONS... 3 TERMINAL DRAWING AND SPECIAL

More information

Ademco Vista-20SE/First Alert FA-162C Program Sheet

Ademco Vista-20SE/First Alert FA-162C Program Sheet Enter Program 1. 4112 + 8 + 0 + 0 (Display should show 20) or Power down then back up and press * and # within 1 minute (If exiting programming you can re-enter within 1 minute by pressing * and #) Exit

More information

Control Panel ICP-SOL2-P/ICP-SOL3-P. en Quick Reference Guide

Control Panel ICP-SOL2-P/ICP-SOL3-P. en Quick Reference Guide Control Panel ICP-SOL2-P/ICP-SOL3-P en Quick Reference Guide Control Panel Table of Contents en 3 Table of contents 1 Introduction 6 2 Programming 7 2.1 ICON LCD Codepad Programming 7 2.2 TEXT LCD Codepad

More information

Control Panel DS7400XiV4-EXP

Control Panel DS7400XiV4-EXP Control Panel DS7400XiV4-EXP Release Notes January 2005 Release Notes for Firmware Version 4.10 Trademarks Cobox is a trademark of Lantronix. 1.0 Remote Programming Compatibility Use RPS-INT L version

More information

Ademco/Protection One 250P1-1 Programming Form

Ademco/Protection One 250P1-1 Programming Form Ademco/Protection One 250P1-1 Programming Form Local programming requires the use of a 2-line Alpha keypad connected to the keypad terminals on the control. Field Function Programmed Values [ ] = Default

More information

VISTA-50P VISTA-50PUL

VISTA-50P VISTA-50PUL VISTA-50P VISTA-50PUL PARTITIONED SECURITY SYSTEM with SCHEDULING Quick Start Step-by-Step Programming Procedure Single And Multiple Partition Programming Forms System Worksheets VISTA50P-PR 8/95 (See

More information

CUSTOMER INFORMATION

CUSTOMER INFORMATION CUSTOMER INFORMATION COMPANY NAME & ADDRESS: CONTACT: PHONE: FAX: NOTES: DATE ENTERED: DATE MODIFIED: 11/2/2010 12:41 P 11/2/2010 12:47 P USER_DEFINED_FIELD1: USER_DEFINED_FIELD2: Vista15PSIA-3 PROGRAMMING

More information

SOFTWARE VERSION 3.10

SOFTWARE VERSION 3.10 738PEP-03 SOFTWARE VERSION 3.10 HEXA PROGRAMMING: Addresses 000 to 043 and 300 to 527 are programmed using the Hexa Programming method. In this mode, you can enter any hexa-digit from 0-F where keys [1]

More information

Digiplex EVO High Security and Access System What s New EVO192 V2.7

Digiplex EVO High Security and Access System What s New EVO192 V2.7 Digiplex EVO High Security and Access System What s New EVO192 V2.7 Overview New zone programming and additional zone/system/anti-mask options EN 50131 compliancy Now supports automatic label broadcast

More information

MTGW. Installation Guide. CAN-RS-485 BUS Gateway

MTGW. Installation Guide. CAN-RS-485 BUS Gateway MTGW EN Installation Guide CAN- BUS Gateway MTGW Installation Instructions 1.0 Overview Trademarks Microsoft Windows 98/2000/XP are registered trademarks of Microsoft Corporation in the United States and

More information

FA168CPS / FA168CPSSIA FA148CP / FA148CPSIA

FA168CPS / FA168CPSSIA FA148CP / FA148CPSIA MAX INSTANT READY R BYPASS AWAY ARMED READY 1 OFF MAX INSTANT READY R 2 AWAY 3 STAY BYPASS FA168CPS / FA168CPSSIA FA148CP / FA148CPSIA Security Systems Programming Guide ARMED READY A B C D 7 4 1 OFF FA260

More information

High Security and Access System EVO48 V2.1 EVO192 V2.1

High Security and Access System EVO48 V2.1 EVO192 V2.1 High Security and Access System EVO48 V2.1 EVO192 V2.1 Programming Guide Includes LCD Keypad Programming We hope this product performs to your complete satisfaction. Should you have any questions or comments,

More information

Programming Worksheets

Programming Worksheets Now classified in accordance with ANSI/SIA CP-01-2000 (SIA-FAR) Programming Worksheets PC1555 CP-01 PC1555 CP-01 version 3.2 DLS2002 and higher Page references below are to the accompanying Installation

More information

Telephone and Reporting Setup in ElkRP

Telephone and Reporting Setup in ElkRP Telephone and Reporting Setup in ElkRP 1. To add a telephone, right click on Telephones under Folder items on the left side of the screen. Then select New Telephone. 2. On the New Telephone IDs screen,

More information

VISTA-20SEa. 3-Partition Security System. Programming Form. V20SEaPRV1 9/98

VISTA-20SEa. 3-Partition Security System. Programming Form.   V20SEaPRV1 9/98 VISTA-20SEa 3-Partition Security System New style cover to be used Programming Form V20SEaPRV1 9/98 Local programming requires the use of a 2-line Alpha keypad connected to Partition 1 keypad terminals

More information

D1260/D1260B. Owner's Manual. Keypad

D1260/D1260B. Owner's Manual. Keypad D1260/D1260B EN Owner's Manual Keypad D1260/D1260B Owner's Manual This system includes a telephone line seizure feature. The system may be programmed to communicate with a central monitoring station to

More information

&RPPHUFLDO)LUHDQG%XUJODU\ 3DUWLWLRQHG6HFXULW\6\VWHP ZLWK6FKHGXOLQJ

&RPPHUFLDO)LUHDQG%XUJODU\ 3DUWLWLRQHG6HFXULW\6\VWHP ZLWK6FKHGXOLQJ 9,67$)% &RPPHUFLDO)LUHDQG%XUJODU\ 3DUWLWLRQHG6HFXULW\6\VWHP ZLWK6FKHGXOLQJ 4XLFN6WDUW*XLGH FIRE FIRE * PULL V128FB-PRV1 10/98 2 Table Of Contents RECOMMENDED PROGRAMMING PROCEDURE... 4 PROGRAM FIELD CATEGORIES...

More information

MG/SP Series (V4.9/V5.1) What s New

MG/SP Series (V4.9/V5.1) What s New MG/SP Series (V4.9/V5.1) What s New Firmware: SP4000 and SP5 version 5.1 SP5500, SP000, SP7000, and MG5050 version 4.9 (SP5500 pictured) Overview: New Programming Sections New Events New Trouble Display

More information

Property of Monitronics Inc

Property of Monitronics Inc Enter Program Master Code + 8 + 0 + 0 (Display should show 20) or Power down then back up and press * and # within 1 minute (If exiting programming you can re-enter within 1 minute by pressing * and #)

More information

DAYLIGHT SAVINGS TIME START/END MONTH [ 0 ]0 = Disabled; 1 = Enabled. 1 Start End

DAYLIGHT SAVINGS TIME START/END MONTH [ 0 ]0 = Disabled; 1 = Enabled. 1 Start End RcvrAcct#: Test Date: May, ::PM SYSTEM ENTRY DELAY# [ ] = None, = secs, = secs, = secs, = secs, = secs, = mins [UL installations: The Entry Delay must be set for a maximum of seconds] ENTRY DELAY# [ ]

More information

EA500. Installation Instructions Transponder

EA500. Installation Instructions Transponder EA500 EN Installation Instructions Transponder EA500 Installation Instructions 1.0 Overview EN 2 1.0 Overview The EA500 Transponder is the Security Escort module that provides communications between the

More information

Installer Notes 4110DL/XM, Vista 10, Vista-20, Via-30PSE

Installer Notes 4110DL/XM, Vista 10, Vista-20, Via-30PSE Installer Notes 4110DL/XM, Vista 10, Vista-20, Via-30PSE 1. Programming can only be done with a 6139 Alpha Keypad on Vista-10/20/30PSE models. 2. When entering programming for the first time during Installations

More information

VISTA 12a / 48a TECHNICAL TRAINING. The Best in Security plus Everyday Convenience & Control

VISTA 12a / 48a TECHNICAL TRAINING. The Best in Security plus Everyday Convenience & Control VISTA 12a / 48a TECHNICAL TRAINING The Best in Security plus Everyday Convenience & Control Version #.007 7th June 2005 VISTA 12a / 48a Training Guide Index 1. Vista Family Features....... p. 3 2. Wiring

More information

3 6HFXULW\6\VWHP 3URJUDPPLQJ)RUP K4332 9/99 BYPASS NOT READY ARMED READY 4 MAX 5 TEST 6 BYPASS 7INSTANT 8 CODE 9CHIME READY ARMED

3 6HFXULW\6\VWHP 3URJUDPPLQJ)RUP K4332 9/99 BYPASS NOT READY ARMED READY 4 MAX 5 TEST 6 BYPASS 7INSTANT 8 CODE 9CHIME READY ARMED 3 6HFXULW\6\VWHP 3URJUDPPLQJ)RUP ARMED READY 1 OFF 2 AWAY 3 STAY 4 MAX 5 TEST 6 BYPASS 7INSTANT 8 CODE 9CHIME READY 0 # * NIGHT NO AC AWAY PHONE TEST BYPASS NOT READY ALARM STAY CHIME BAT FIRE CHECK INSTANT

More information

3DUWLWLRQHG6HFXULW\6\VWHPV ZLWK6FKHGXOLQJ

3DUWLWLRQHG6HFXULW\6\VWHPV ZLWK6FKHGXOLQJ )$&&$&% )LUHDQG%XUJODU\ 3DUWLWLRQHG6HFXULW\6\VWHPV ZLWK6FKHGXOLQJ **** **** ARMED READY A B C D FIRE FIRE First Alert OFF AWAY STAY 1 2 3 4 5 6 7 8 9 MAXIMUM TEST BYPASS INSTANT CODE CHIME READY * 0 #

More information

Safecom Solution-16 Quick Reference Guide ISSUE 1.10

Safecom Solution-16 Quick Reference Guide ISSUE 1.10 Safecom Solution-16 Quick Reference Guide ISSUE 1.10 2 Solution-16 Safecom Quick Reference Guide Safecom Solution-16 Quick Reference Guide Copyright 1998 by, SYDNEY, AUSTRALIA Document Part Number MA8016Q

More information

Control Panel Solution 2000 / 3000

Control Panel Solution 2000 / 3000 Control Panel Solution 2000 / 3000 en Quick Reference Guide Control Panel Table of contents en 3 Table of contents 1 Introduction 6 2 Programming 7 2.1 Alphanumeric Codepad Menu Programming 7 2.2 ICON

More information

VISTA-20BAY PROGRAMMING GUIDE SECURITY SYSTEM SINCE 1946

VISTA-20BAY PROGRAMMING GUIDE SECURITY SYSTEM SINCE 1946 VISTA-20BAY SECURITY SYSTEM PROGRAMMING GUIDE SINCE 1946 N7526-4PR 03/98 File No: S1632 Local programming requires the use of a 2-line alpha keypad connected to the keypad terminals on the control. Field

More information

INPUTS: Are 10K end of line monitored, with a response time of 300 ms. Alarm triggers SIREN, STROBE and REPORTING (depending on setup)

INPUTS: Are 10K end of line monitored, with a response time of 300 ms. Alarm triggers SIREN, STROBE and REPORTING (depending on setup) INPUTS: All inputs: Inputs 1 to 24: Tamper: Panic: Fire: Keyswitch: 16-18VAC: Are 10K end of line monitored, with a response time of 300 ms. Alarm triggers SIREN, STROBE and REPORTING (depending on setup)

More information

PROGRAMMING HELP GUIDE

PROGRAMMING HELP GUIDE DIGIPLEX EVO48-192 PROGRAMMING HELP GUIDE Entering Programming Mode 1) Press and hold the [0] key 2) Enter your [Installer Code] (default-000000) 3) Enter 4-digit [section] you wish to program 4) Enter

More information

EVOHD. Programming Guide. Version

EVOHD. Programming Guide. Version EVOHD Programming Guide Version 1.11 www.paradox.com Warranty For complete warranty information on this product please refer to the Limited Warranty Statement found on our Web site: www.paradox.com. Your

More information

I-NX8V2-IM Rev F Dec NetworX Series NX-8V2 Control Panel Installation and Setup

I-NX8V2-IM Rev F Dec NetworX Series NX-8V2 Control Panel Installation and Setup I-NXV-IM Rev F Dec 00 NetworX Series NX-V Control Panel Installation and Setup Copyright Disclaimer Trademarks and patents Copyright 00, GE Security Inc. All rights reserved. This document may not be copied

More information

First Alert FA160C/162C Installer Notes M. Leuck

First Alert FA160C/162C Installer Notes M. Leuck First Alert FA160C/162C Installer Notes M. Leuck 1. Programming can only be done by 6139 Alpha keypads, standard 6128 keypad cannot be used to program zones 2. Enter programming: Master Code + 8 + 0 +

More information

ENABLE / DISABLE: ZONES, DEVICES, CIRCUITS, COMMUNICATION SENSE, RESET HI-LO LEVELS, WALKTEST DIAGNOSTICS

ENABLE / DISABLE: ZONES, DEVICES, CIRCUITS, COMMUNICATION SENSE, RESET HI-LO LEVELS, WALKTEST DIAGNOSTICS Cheetah Manual #06-148 page 55 CHAPTER 10 Operation (level 2 password) Menu options available under this level of access are: HISTORY: ALARM, EVENT, ZONE, CURRENT LEVEL PASSWORD: (ENTRY) 1 SPECIAL: LEVELS,

More information

D1260/D1260B. Installation Guide. Keypads

D1260/D1260B. Installation Guide. Keypads D1260/D1260B EN Installation Guide Keypads D1260/D1260B Installation Guide Trademarks Trademarks Microsoft, Windows, Windows NT are either registered trademarks or trademarks of Microsoft Corporation in

More information

Control Panels B5512/B4512. en UL Installation Instructions

Control Panels B5512/B4512. en UL Installation Instructions Control Panels B551/B451 en UL Installation Instructions Control Panels Table of Contents en 3 Table of contents 1 Introduction 4 1.1 About documentation 4 1.1.1 Related documentation 4 1. Bosch Security

More information

FPA-1000-V2 Network Cards FPE-1000-NE, FPE-1000-NF, and FPE-1000-NW

FPA-1000-V2 Network Cards FPE-1000-NE, FPE-1000-NF, and FPE-1000-NW FPA-1000-V2 Network Cards FPE-1000-NE, FPE-1000-NF, and FPE-1000-NW en Installation manual FPA-1000-V2 Network Cards Table of contents en 3 Table of contents 1 General Information 4 1.1 Safety 4 1.2 Network

More information

Commercial Burglary Partitioned Security System With Scheduling. Programming Guide. K5894PRV4 6/04 Rev A

Commercial Burglary Partitioned Security System With Scheduling. Programming Guide. K5894PRV4 6/04 Rev A ADEMCO VISTA SERIES VISTA-128BP/VISTA-250BP/ VISTA-128SIA Commercial Burglary Partitioned Security System With Scheduling Programming Guide K5894PRV4 6/04 Rev A Table of Contents Recommended Programming

More information

2 IDS LCD Keypad User Manual C Issued March 2009

2 IDS LCD Keypad User Manual C Issued March 2009 2 3 4 Contents 1. Introduction to the IDS LCD Digital Keypad...8 2. Arming the Control Panel...8 2.1 Away Arming...8 2.1.1 How to Away Arm...8 2.1.2 Quick Away Arm Shortcut Key...8 2.2 Stay Arming...9

More information

TABLE OF CONTENTS. Notice...i How to Use This Program Entry Guide...i About the Type Styles That We Use in the Text...i D5200 Key Descriptions...

TABLE OF CONTENTS. Notice...i How to Use This Program Entry Guide...i About the Type Styles That We Use in the Text...i D5200 Key Descriptions... TABLE OF CONTENTS Notice...i How to Use This Program Entry Guide...i About the Type Styles That We Use in the Text...i D5200 Key Descriptions...ii PROGRAMMING THE D6500...1 LINE CARD Create Custom Programs

More information

SOFTWARE VERSION 3.20

SOFTWARE VERSION 3.20 48EPEP-00 SOFTWARE VERSION 3.20 HEXA PROGRAMMING: Addresses 000 to 043 and 300 to 527 are programmed using the Hexa Programming method. In this mode, you can enter any hexa-digit from 0-F where keys [1]

More information

Series. NX-8-EUR Control Panel. Installation manual

Series. NX-8-EUR Control Panel. Installation manual g GE Security NetworX TM Series NX-8-EUR Control Panel Installation manual NX-8-EUR Installation manual Page 2 23/12/04 CONTENTS CONTENTS...3 GENERAL INFORMATION...5 ORDERING INFORMATION...5 FEATURE DEFINITIONS...6

More information

Metasys Integrator Northern Application

Metasys Integrator Northern Application Metasys Connectivity Technical Manual 629.5 Metasys Integrator Section Application Note Issue Date 0900 APPLICATION NOTE Metasys Integrator Northern Application lntroduction Page *3 Application Details

More information

IDS1200 INSTALLER MANUAL. Summary of Operation 2 IDS1200 INSTALLER MANUAL - NO B ISSUED AUGUST 2002 VER 1.18

IDS1200 INSTALLER MANUAL. Summary of Operation 2 IDS1200 INSTALLER MANUAL - NO B ISSUED AUGUST 2002 VER 1.18 IDS12 INSTALLER MANUAL Summary of Operation A rm/ disarm [#] + [USER CODE] Quick Away Arm Quick Stay Arm Quick Stay Arm & Go H old down [ 1] for 1 second H old down [ 5] for 1 second H old down [ 6] for

More information

Modules Programming Guide

Modules Programming Guide Modules Programming Guide Programming Methods The modules can be programmed using the following methods: 1) Through the WinLoad Security Management Software. The modules can be programmed at 19,200 baud

More information

Modules Programming Guide. paradox.com

Modules Programming Guide. paradox.com Keypad Modules Annunciator Module Motion Detector Modules Zone Expansion Modules Access Control Module Voice Assisted Modules Accessory Modules Integration Module Internet Module Modules Programming Guide

More information

Remote Programming Software

Remote Programming Software Remote Programming Software RPS Release Notes for Version 5.14 November 2011 1.0 Release Notes for RPS 1.1 Version 5.14 Compatibility RPS is intended for use with the following control panels: D2000 Series

More information

Use this manual with the following Analogue Fire control panels: FC200/S - 2 Loop Master panel with 2.5 A Switching power supply

Use this manual with the following Analogue Fire control panels: FC200/S - 2 Loop Master panel with 2.5 A Switching power supply SOFTWARE MANUAL Use this manual with the following Analogue Fire control panels: FC200-2 Loop Master panel with 4 A Linear power supply FC200/S - 2 Loop Master panel with 2.5 A Switching power supply FC200/SL

More information

SOFTWARE VERSION 3.10

SOFTWARE VERSION 3.10 728PEP-03 SOFTWARE VERSION 3.10 HEXA PROGRAMMING: Addresses 000 to 043 and 300 to 527 are programmed using the Hexa Programming method. In this mode, you can enter any hexa-digit from 0-F where keys [1]

More information

XT30/XT50 PROGRAMMING PART 1. Slide 1. Slide 2. Slide 3. Objectives. XT30/XT50 Basic Training Programming- Part 1. Accessing the Programmer

XT30/XT50 PROGRAMMING PART 1. Slide 1. Slide 2. Slide 3. Objectives. XT30/XT50 Basic Training Programming- Part 1. Accessing the Programmer Slide 1 XT30/XT50 Basic Training Programming- Part 1 Slide 2 Objectives After completing this course you will: 1) Understand how to prepare the panel for programming and how to access the built-in programmer.

More information

ICP-SDI Installation Instructions. SDI Splitter

ICP-SDI Installation Instructions. SDI Splitter ICP-SDI-9114 EN Installation Instructions SDI Splitter ICP-SDI-9114 Installation Instructions Listings and Approvals Listings and Approvals UL UL 65 Police Station Burglar Alarm Units and Systems UL 609

More information

NetworX Series NX-8V2 Control Panel Installation and Startup

NetworX Series NX-8V2 Control Panel Installation and Startup NetworX Series NX-V Control Panel Installation and Startup 00 GE Security All rights reserved. These instructions do not purport to cover all details or variations in equipment nor to provide every possible

More information

4+2 Pulse Comms Task Format. CT001 Client Code: CT001 PABX No.-> None. CT001 PABX No.-> TN000. CT001 1st No.-> None. CT001 2nd No.

4+2 Pulse Comms Task Format. CT001 Client Code: CT001 PABX No.-> None. CT001 PABX No.-> TN000. CT001 1st No.-> None. CT001 2nd No. MODEL 3000 / ACCESS 4000 Programmer s Manual - Rev 3.00 4+2 Pulse Comms-19-1 4+2 Pulse Comms Task Format The 4+2 Pulse format transmits 4 client code and 2 alarm digits to a Central Station using bursts

More information

Conettix Ethernet Communication Module

Conettix Ethernet Communication Module Conettix Ethernet Communication B426 en Release Notes Conettix Ethernet Communication Table of Contents en 3 Table of contents 1 Introduction 4 1.1 Requirements 4 1.2 About documentation 5 2 Version 3.05

More information

RPS. Remote Programming Software. Release Notes for Version 5.13 November Release Notes for US Versions of RPS

RPS. Remote Programming Software. Release Notes for Version 5.13 November Release Notes for US Versions of RPS Remote Programming Software RPS Release Notes for Version 5.13 November 2010 1.0 Release Notes for US Versions of RPS 1.1 Version 5.13 Compatibility The US version of RPS is intended for use with the following

More information

Table of Contents. HILLS COMNAV INSTALLATION MANUAL V1.3

Table of Contents. HILLS COMNAV INSTALLATION MANUAL V1.3 Table of Contents Introduction... 3 Feature & Benefits... 4 1. Phone Line connection... 4 2. Phone Line connection, and network connection...5 3. Phone Line connection, network connection and integrated

More information

Installation Instructions

Installation Instructions NX-148E-RF LCD Touchpad w/receiver 466-2198 Rev. B May 2005 Product summary The NX-148E-RF Touchpad w/receiver combines touchpad and receiver capabilities into a single device for use with NetworX NX-4,

More information

Quick Start: 2. Connect AC power first and then the battery. 3. Configure the keypad (see page 44).

Quick Start: 2. Connect AC power first and then the battery. 3. Configure the keypad (see page 44). R R R HARDWIRE WIRELESS Quick Start:. Refer to the wiring diagram, connect siren, aux. power, pgm. output, remote bus, earth ground, zone and telephone wiring. NOTE: See Installation Instructions (WI99)..

More information

AMAX panel. AMAX panel 2100 AMAX panel 3000 AMAX panel 3000 BE AMAX panel en Operation Manual

AMAX panel. AMAX panel 2100 AMAX panel 3000 AMAX panel 3000 BE AMAX panel en Operation Manual AMAX panel AMAX panel 2100 AMAX panel 3000 AMAX panel 3000 BE AMAX panel 4000 en Operation Manual AMAX panel Table of Contents en 3 Table of contents 1 Safety 5 2 Short information 6 2.1 Introduction

More information

Model Number(s): D7000, D9000 Series Panels, D7000/9000V2 Panels

Model Number(s): D7000, D9000 Series Panels, D7000/9000V2 Panels Manufacturer: Bosch / Radionics Integration Note Model Number(s): D7000, D9000 Series Panels, D7000/9000V2 Panels Core Module Version: Comments: Tested Firmware Revisions: 6.80, 7.07 Document Revision

More information

Created by: Alarm System Store Quick Start Guide. for Interlogix NetworX NX4, NX6 & NX8

Created by: Alarm System Store   Quick Start Guide. for Interlogix NetworX NX4, NX6 & NX8 Quick Start Guide for Interlogix NetworX NX4, NX6 & NX8 Programming Code = 9713 Master User Code=1234 Program Mode= *8 + 9713 To exit programming hit the Exit key until you reach the home screen If this

More information

GEM-P9600 CONTROL PANEL/COMMUNICATOR

GEM-P9600 CONTROL PANEL/COMMUNICATOR R R R R PROGRAMMING INSTRUCTIONS HARDWIRE WIRELESS GEM-P9600 CONTROL PANEL/COMMUNICATOR GEMINI ARMED STATUS SYSTEM ARMED 0/0/00 0/0/97 :00AM NEXT/YES A 3 D E PRIOR/NO B 56 F AREA C 790G GEMINI SYSTEM ARMED

More information

PC3K User s Manual. Part # Revision 1.0 May Zeta Alarm Systems Ltd. A Division of GLT Exports Ltd

PC3K User s Manual. Part # Revision 1.0 May Zeta Alarm Systems Ltd. A Division of GLT Exports Ltd PC3K User s Manual Part # 3000-0002 Revision 1.0 May 2002 Zeta Alarm Systems Ltd A Division of GLT Exports Ltd 72-78 Morfa Road Swansea SA1 2EN U.K. http://www.zeta-alarms.co.uk nrpj@zeta-alarms.fsworld.co.uk

More information

Conettix Universal Dual Path Communicator B465

Conettix Universal Dual Path Communicator B465 Conettix Universal Dual Path Communicator B465 en Release Notes Conettix Universal Dual Path Communicator Table of contents en 3 Table of contents 1 Introduction 4 1.1 Requirements 4 2 Version 2.00.000

More information

Autodialer ADC Series

Autodialer ADC Series Advanced Life Safety Solutions Autodialer ADC Series Telephone Access System 3 4 5 7 8 9 0 User s Guide LT-883 Rev. 0 April 2005 Autodialer ADC Series Telephone Access System User Guide Contents Introduction...

More information

Conettix ITS-D6686-UL PRELIMINARY. Installation Guide. Ethernet Network Adapter

Conettix ITS-D6686-UL PRELIMINARY. Installation Guide. Ethernet Network Adapter Conettix ITS-D6686-UL EN Installation Guide Ethernet Network Adapter Conettix ITS-D6686-UL Installation Guide Contents Contents 1.0 Introduction... 3 1.1 Network Interface... 3 1.2 Serial Interface...

More information

Conettix ITS-D6686-UL

Conettix ITS-D6686-UL Conettix ITS-D6686-UL EN Installation Guide Ethernet Network Adapter Conettix ITS-D6686-UL Installation Guide Contents Contents 1.0 Introduction... 3 1.1 Network Interface... 3 1.2 Serial Interface...

More information

4. Specifications and Additional Information

4. Specifications and Additional Information 4. Specifications and Additional Information AGX52004-1.0 8B/10B Code This section provides information about the data and control codes for Arria GX devices. Code Notation The 8B/10B data and control

More information

FieldServer Driver - Serial FS Fire Control Instruments - FCI 7100 Series

FieldServer Driver - Serial FS Fire Control Instruments - FCI 7100 Series Driver Version: 1.01 Document Revision: 1 Description FieldServer Driver - Serial FS-8700-112 Fire Control Instruments - FCI 7100 Series The FCI 7100 Series System Control Units are manufactured by Fire

More information

Remote Programming Software LITE (RPS LITE)

Remote Programming Software LITE (RPS LITE) Remote Programming Software LITE (RPS LITE) D5500CU LITE, v6.06.016 en Release Notes Remote Programming Software LITE (RPS-LITE) Introduction en 3 1 Introduction RPS-LITE version 6.06.016 Release Notes.

More information

Control panels. G Series: B9512G, B8512G. Release notes

Control panels. G Series: B9512G, B8512G. Release notes Control panels G Series: B9512G, B8512G en Release notes Control panels Table of contents en 3 Table of contents 1 Introduction 4 1.1 About documentation 4 1.2 Requirements 5 2 Firmware version 3.07 8

More information

Section 1 Introduction

Section 1 Introduction Section 1 Introduction The Model 4824 Serial/Parallel Module provides one RS232 serial port and one parallel printer port. Eight 4824s could be used per system. You can use the 4824 for a variety of purposes,

More information

Remote Programming Software LITE (RPS-LITE) D5500CU-LITE, v6.05

Remote Programming Software LITE (RPS-LITE) D5500CU-LITE, v6.05 Remote Programming Software LITE (RPS-LITE) D5500CU-LITE, v6.05 en Release Notes Remote Programming Software LITE (RPS-LITE) Introduction en 3 1 Introduction RPS-LITE version 6.05 Release Notes Remote

More information

Control Panels. D9412GV4/D7412GV4 v en Release Notes

Control Panels. D9412GV4/D7412GV4 v en Release Notes Control Panels D9412GV4/D7412GV4 v2.03.018 en Release Notes Control Panels Table of Contents en 3 Table of contents 1 Introduction 5 1.1 Requirements 5 1.2 About documentation 5 1.2.1 Related documentation

More information

FSK TX CELLULAR PLUS. Installation and Programming Guide. Tel:

FSK TX CELLULAR PLUS. Installation and Programming Guide. Tel: FSK TX CELLULAR PLUS Installation and Programming Guide Tel: 0861 105 962 www.fsk.co.za INTRODUCTION The FSK TX Cellular Plus (TXC+) is a highly featured GSM based unit which is used for the transmission

More information

NX-2192E PINPOINT SYSTEM

NX-2192E PINPOINT SYSTEM NX-9E PINPOINT SYSTEM INSTALLATION MANUAL TABLE OF CONTENTS. GENERAL DESCRIPTION.... INSTALLATION.... DEVICE ADDRESS CONFIGURATION.... TERMINAL DESCRIPTIONS.... WIRING DIAGRAM.... MAXIMUM NUMBER OF DEVICES

More information

AV-4000 GSM AV-4000 DVR

AV-4000 GSM AV-4000 DVR E a s y L o a d e r AV-4000 GSM AV-4000 DVR (for LED keypads) Integrated Alarm Control panel & Communicator Series 4000 Appendix for GSM Alarm Panels Version 1.05 Edition I This product is subject to continuous

More information

DAS 250L CONTROL COMMUNICATOR INSTALLATION MANUAL

DAS 250L CONTROL COMMUNICATOR INSTALLATION MANUAL DAS 250L CONTROL COMMUNICATOR INSTALLATION MANUAL TABLE OF CONTENTS 1. GENERAL DESCRIPTION... P.2 2. STANDARD AND OPTIONAL PARTS LIST..... P.2 3. FEATURE DEFINITIONS... P.3 4. TERMINAL DRAWING AND SPECIAL

More information

WARNING: Remove all power sources to the panel before installation. Leave the external and main power OFF until installation is complete.

WARNING: Remove all power sources to the panel before installation. Leave the external and main power OFF until installation is complete. 9 Columbia Way Baulkham Hills, NSW 2153 PH 02-9894-1444 FAX 02-9894-4193 www.notifier.com.au AFP-3030 CPU Assembly Installation Sheet (AUS) - Released 24/10/2014 Rev A DOC-03-085 1 Product Overview The

More information

FPP-RNAC-8A-4C. Operation and Installation Guide. Remote NAC Power Supply

FPP-RNAC-8A-4C. Operation and Installation Guide. Remote NAC Power Supply F-RAC-8A-C E peration and Installation Guide Remote AC ower Supply F-RAC-8A-C peration and Installation Guide otice to sers, Installers, Authorities Having Jurisdiction, and other involved parties: his

More information

Conettix ITS-D6686-INTL

Conettix ITS-D6686-INTL Conettix ITS-D6686-INTL EN Installation Guide Ethernet Network Adapter Conettix ITS-D6686-INTL Installation Guide Contents Contents 1.0 Introduction... 3 1.1 Network Interface... 3 1.2 Serial Interface...

More information