1 cod. 9IS42075 rel. 4/06 -GB- *If the conditions for defrosting are not present, or if parameter OdO<>0, the display will blink three times, to indicate that the operation will not be performed. ID 974 DCC electronic controllers for forced air refrigeration units with deep cooling cycle Eliwell Electronic controller for forced air refrigeration units: the ID974 DCC is also suitable for mixed refrigeration systems that perform a blast chilling cycle and subsequent storage of foodstuffs. At the end of the blast chilling cycle the controller automatically switches to storage mode. 2 NTC/PTC probes 3 relays TTL serial 230V SETTING THE SET POINT - MACHINE STATUS MENU a) Press the button and release it to access the machine status menu. In normal conditions, the labels for the Set point value is found in the menu. Once the SEt label has been displayed, press the button to display the Setpoint value. The Setpoint value appears on the display. UP Scrolls through the menu items Increases the values Activates manual defrost function DOWN Scrolls through the menu items Decreases the values fnc (press once) fnc ESC function (quit) (hold down) Enable manually DCC function (par. H33) (press once) Accesses the point Displays the alarms (if active) Displays Pb1 and Pb2 (see) (hold down) Accesses the parameter programming menus To change the Set point value, use the UP and DOWN buttons within 15 seconds. If you press the button again, when the fnc button is pressed or 15 seconds elapse, the last value displayed will be stored and the SEt label will reappear on the display. b) If alarms are present, the AL label appears. By using the UP and DOWN buttons, you can scroll through all the folders in the menu: BUTTONS AND LEDS Deep Cooling Cycle (Blast Chiller) Function (DCC) The instrument automatically inhibits defrosting and manages alarms during the blast chilling function. The blast chilling cycle can be activated by pressing the fnc key Compressor ON when the compressor is started up; blinking in case of delay, protection or blocked enabling Defrost ON when defrosting; blinking in case of manual enabling -AL: alarm folder (if alarms present, except for faulty probes/probe errors; -SEt: Set point ting folder see pt. a) -Pb1: probe 1 value folder; -Pb2: probe 2 value folder - if present - c) If an alarm condition exists when the Machine Status menu is accessed, the AL folder label appears. Alarm ON when the alarm is enabled; blinking when the alarm is silenced Fans ON when the fan is working (example: when maximum and minimum temperature alarms are present) Use the UP and DOWN buttons to scroll through the list of active alarms and press to display the selected alarm. The menu is divided into 2 levels once users have pressed the button for 5 seconds, they can access the user level folders (1) Navigation at user level(1): By using the UP / DOWN buttons you can scroll through all the folders in the programming menu that only contain user level parameters (1) How to access the installer level (2): By using the UP / DOWN buttons, scroll through the user level folders (1) until the folder with the CnF label is displayed. Then press to access the parameters contained in it. By using the UP / DOWN all the parameters in the user level (1) in CnF are displayed, continue until the PA2 label is not longer displayed and press. By pressing the button next to PA2 the first folder containing installer level parameters will be displayed and then the CP folder. PROGRAMMING MENU Navigation at installer level(2): By using the UP / DOWN buttons you can scroll through all the folders in the programming menu that only contain installer level parameters (2) How to modify the parameter value (on both levels): When the button is pressed, the first folder in the menu is displayed. (e.g.: CP folder) By using the UP / DOWN buttons you can scroll through all the folders in current level. By pressing the button next to the selected folder (in this case AL ) the first parameter in the current level will be displayed. Select the desired parameter using the UP / DOWN keys. By pressing the button the value of the selected parameter is displayed and by using the UP and DOWN buttons, it can be modified.
2 Access to parameter handling both at user level and installer level can be limited by using passwords. The passwords can be enabled by ting the PA1 (user password) and PA2 (installer password) in the dis folder. The passwords are enabled if the value of the 2 parameters PA1 and PA2 is not 0. To access the Programming menu hold down the button for more than 5 seconds. If specified, the user level(1) access PASS- the CnF folder is displayed. Press the button to enter the CnF folder where the PA2 label is present. Scroll through the folder parameters and press the button next to the PA2 label, 0 will appear on the display. PASSWORD WORD will be requested If password 1 is enabled (not 0) you will be asked to enter it. Perform the operation by selected the correct value using the UP e DOWN keys and press the button to confirm. Installer level (2) parameters In the programming menu scroll through the folders containing the user level parameters using the UP and DOWN buttons until Use the UP / DOWN buttons to select the correct value of the installer password and then press the button to access the installer level parameters (2). If the password is not entered correctly, the device will display the PA2 label again and the operation will have to be repeated. The Copy Card is an accessory connected to the TTL serial port used for quick programming of the unit parameters (upload and download parameter map to one or more units of the same type). upload (UL label), download (dl label) and copy card formatting (Fr label) operations are performed in the following way: The FPr folder contains the commands necessary for use of the Copy Card. Press to access the functions. Use the UP / DOWN buttons to display the required function. Press the and uploading (or downloading) will be performed. If the operation is successful y will be displayed, if it is not successful, n will be displayed. COPY CARD Download from re Connect the copy card when the instrument is OFF. The programming parameters are downloaded when the device is switched on. At the end of the lamp test, the following messages are displayed for about 5 seconds: dly label if copy operation is successful DLn label if operation fails DOWNLOAD UPLOAD NOTE: after the parameters have been downloaded, the device uses the downloaded parameter map tings. see FPr folder in Parameter Table and Description of parameters At each level in both menus, when the fnc button is pressed or the 15 second time out elapses, you are taken back to the higher display level and the last value on the display is stored. MAX-MIN ALARMS Temperature expressed as an absolute value (par Att =0) Abs(olute) 1 Temperature in relation to point (par Att =1) rel(ative) 2 Off Minimum temperature alarm Maximum temperature alarm Minimum temperature alarm back swing Maximum temperature alarm back swing LAL Temperature lower than or equal to LAL (LAL with sign) Temperature greater than or equal to HAL (HAL with sign) Temperature higher than or equal to LAL+ Temperature lower than or equal to HAL- HAL SP1+ LAL/SP2 + LAL SP1+ HAL/SP2 + HAL Temperature lower than or equal to point +LAL (LAL positive only) Temperature greater than or equal to point +HAL (HAL positive only) Temperature greater than or equal to point + LAL + point - LAL + Temperature lower than or equal to point+hal- if Att=reL(ative) LAL must be negative: therefore point+lal< point because point+(- LAL )=- LAL ID DCC 2/6
3 DEEP COOLING CYCLE (DCC) The Deep Cooling Cycle Function (DCC) is enabled by H01 parameter. When DCC is activated the compressor works on dcs point with dif differential: time is by tdc parameter (blast chiller cycle). defrost Stop temperature (par. dst) At DCC activation interval between two defrost is re, and defrost is disabled. After DCC cycle and after a time by dcc a defrost is forced - delay between defrosts is re-enabled (see dit). Temperature Alarms are disabled during DCC cycle - except for LAL if Att=1 (relative to point). After DCC cycle Alarms management is restored. In case of faulty probe and/or blackout DCC cycle stops. If dcs, tdc and dcc parameters are changed by the user during the DCC cycle this will be re-calculate with new parameters tings. DCC (par. DCS) compressor key DCC timeout (par. tdc) delay defrost after DCC par. dcc defrost timeout (par. det) defrost ALARMS LABEL E1 ALARM Probe 1(control) faulty CAUSE measuring of values outside the nominal reading range control probe faulty/shorted/open probe EFFECTS E1 label appears on display; Controller enabled as indicated by the On1 and OF1 parameters if programmed for the Duty Cycle Resolving problems check the probe wiring replace the probe NOTES E2 Probe 2 (evaprator) faulty measuring of values outside the nominal reading range control probe faulty/shorted/open probe E2 label appears on display; check the probe wiring replace the probe AH1 High temperature alarm value read by probe 1 > HAL after time equal to tao. (see MIN MAX ALARMS and description of HAL, Att and tao parameters) Alarms created in the AL folder with the AH1/AH2 label Wait for temperature value read by probe 1 to fall below HAL AL1 Low temperature alarm value read by probe 1 < LAL after time equal to tao. (see MIN MAX ALARMS and description of LAL, Att and tao parameters) Alarms created in the AL folder with the AL1/AL2 label Wait for temperature value read by probe 1 to go above LAL Ad2 End of defrost due to time-out If defrost ends because of a timeout (instead of being caused by a defrost end temperature detected by the defrosting probe), an alarm is generated an the icon is turned on consequently. Alarms created in the AL folder with the Ad2 label ALL see Alarm LED Automatic back swing occurs when the next defrost starts By pressing any key during the alarm condition, the signal light disappears. In order to really erase the alarm you must wait the next defrost. ALL Manual silencing by pressing button ALL If there are alarm exclusion times (see parameter table AL folder) the alarm will not be signalled. ID DCC 3/6
4 The instrument includes a facility for disabling the keyboard: using the keys (pressing UP+DOWN simultaneously for 2 seconds; see KEYS AND LEDS) by programming the Loc parameter (see folder with dis label). KEYBOARD LOCKING PARAMETERS TABLE If the keyboard is locked, you can access the Programming Menu by pressing the key. The Setpoint can also be viewed. PAR. RANGE ELIWELL U.M. LEVEL DEFAULT/ PAR. RANGE ELIWELL U.M. LEVEL DEFAULT/ SETPOINT SEt LSE...HSE -22 C/ F 1 CP FOLDER dif C/ F 1 HSE LSE C/ F 2 LSE HSE C/ F 2 * dcs C/ F 2 * tdc min*10 2 * dcc min 2 Ont min 2 OFt min 2 don sec 2 dof sec 2 dbi sec 2 OdO sec 2 DEF Folder dty 0/1/2 0 num 2 dit h 1 dct 0/1/2 1 num 2 doh min 2 det min 1 dst C/ F 1 dpo n/y 0 C/ F 2 FAn Folder FSt C/ F 1 FAd C/ F 2 Fdt min 2 dt min 2 dfd n/y y flag 2 FCO n/y/dc y num 2 * DCC parameters AL Folder Att 0/1 1 flag C/ F 2 HAL LAL C/ F 2 LAL HAL C/ F 2 PAO h 2 dao min 2 tao min 2 dis Folder LOC n/y n flag 2 PA num 2 PA num 2 ndt n/y y flag 2 CA C/ F 2 CA C/ F 2 ddl 0/1/2 1 num 2 dro 0/1 0 flag 2 CnF Folder ** H00 0/1 1 flag 2 * H01 n/y y flag 2 H num 2 H42 n/y y flag 2 rel / / / / tab / / / / Fpr Folder UL / / / / dl / / / / Fr / / / / **Check the NTC/PTC default probe type installed (see label) LEVEL column: indicates the visibility level of parameters accessed using a PASSWORD (see relevant paragraph). If one or more parameters are modified, it is suggested to the switch off the controller after the modification and then switched back on. MECHANICAL ASSEMBLY The unit has been designed for panel-mounting: Drill a 29x71 mm hole, insert a tool and fix it in place with the brackets provided. Do not assemble the instrument in excessively humid or dirty locations since it is designed to be used in locations with normal pollution levels. Always make sure that the area next to the cooling openings of the tool is adequately ventilated. ELECTRICAL CONNECTIONS Warning! Always switch off machine before working on electrical connections. The instrument has screw terminals for connecting electrical cables with a maximum diameter of 2.5 mm 2 (only one conductor per terminal for power connections): for terminal capacity, see instrument label.the relay contacts are voltage-free. Do not exceed the maximum current allowed. For higher loads, use a suitable contactor. Make sure that the power voltage complies with the device voltage. The sensor has no connection polarity and can be extended using an ordinary bipolar cable (note that extending the probe may affect the electromagnetic compatibility (EMC) of the instrument: special care must be used when wiring). Probe cables, power supply cables and the TTL serial cable should be kept separate from power cables. ID DCC 4/6
5 DESCRIPTION OF PARAMETERS dif HSE LSE *dcs *tdc *dcc COMPRESSOR CONTROL (folders with label CP ) Compressor relay activation differential: the compressor stops on reaching the Setpoint value (as indicated by the adjustment probe) and restarts at a temperature value equal to the Setpoint plus the value of the differential. Note: the value 0 cannot be assumed. Maximum possible point value. Minimum possible point value. NOTE: The two s are interdependent: HSE (maximum ) cannot be less than LSE (minimum ) and vice versa Deep Cooling Setpoint Time Out Deep Cooling Cycle Delay Defrost after Deep Cooling Cycle *see DCC description and diagram page 3 Ont Compressor activation time in the event of a faulty probe. If to 1 with Oft to 0, the compressor is always on, while with OFt >0 it operates in duty cycle mode. OFt Compressor off time in the event of a faulty probe. If to 1 with Ont at 0, the compressor is always off, while with Ont>0 it operates in duty cycle mode. don Starting delay. The parameter indicates that a protection is active on the relay actuations of the generic compressor. Between the request and effective activation of the compressor relay, at least the specified time must elapse. dof Delay after switching off. The parameter indicates that the protection is active on compressor relay actuations. At least the indicated time must elapse between switch-off of the compressor relay and the successive switch-on. dbi Delay between switch-ons. The indicated time must elapse between two subsequent switch-ons of the compressor. OdO Delay time in activating the outputs after switch-on of the instrument or after a power failure. 0= not active. DEFROSTING CONTROL (folders with labels def ) dty dit dct doh dst det dpo FSt FAd Fdt dt dfd FCO DEFROSTING CONDITIONS The instrument allows defrosting to be performed in the following conditions: the evaporator temperature is lower than the defrost end temperature by the dst parameter; manual defrosting is not already activated (see); in this case the request for automatic defrosting will be cancelled. Automatic defrosting In this case, defrosting takes place at time intervals by parameter dit (=0 defrosting will not take place at all). As mentioned above, if the parameter dit> 0 and defrosting conditions apply (see parameter dst), defrosting will take place at fixed intervals and according to the parameter dct Type of defrost. 0 = electrical defrosting; 1 = cycle inversion defrosting (hot gas); 2 = Free mode defrost (independent of compressor). Interval between the start of two subsequent defrosting operations. 0= the function is disabled (defrosting is NEVER performed) Selection of count mode for the defrosting interval. 0 = compressor hours of operation (DIGIFROST method); Defrosting active ONLY with the compressor on. NOTE: compressor time of operation is counted regardless of the evaporator probe (counting is active if evaporator probe is absent or faulty). 1 = hours of appliance operation. Defrost counting is always active when the machine is on and starts at each power-on. 2 = compressor stop. Every time the compressor stops, a defrosting cycle is performed according to parameter dty Defrost start delay time from start up of instrument. Defrosting end temperature (determined by the evaporator probe). Defrost time-out: determines the maximum duration of defrosting. Determines whether the instrument must enter defrosting at start-up (if the temperature measured by the evaporator allows this operation). y = yes, starts defrosting at start-up; n = no, does not start defrosting at start-up. FAN CONTROL (folder with FAn label) Fan lock temperature: if the evaporator probe reads a higher value than the value, the fans are stopped. The value is positive or negative and, depending on parameter FPt, can represent the temperature as an absolute value or relative to the Setpoint. Fan activation intervention differential (see par. FSt ). Delay time at fan activation after a defrosting cycle. Dripping time. Allows exclusion of the evaporator fans to be selected or not selected during defrosting. y = yes (fans excluded); n = no. It allows the fan lock to be selected or not when the compressor is OFF. y = fans active (with thermostat; depending on the value read by the defrosting probe, see FSt parameter); n = fans off; dc = duty cycle. FOd Att AFt HAL LAL PAO dao tao Allows fan lock to be selected when the door is open and fan restart when the door is shut (if they were active). n=fan lock; y=fans unchanged ALARMS (folder with AL label) Parameter HAL and LAL modes, as temperature absolute value or as differential relative to the Setpoint. 0 = absolute value; 1 = relative value. Alarm differential. Maximum temperature alarm. Temperature value (understood as distance from the Setpoint or as an absolute value based on Att) which if exceeded in an upward direction triggers the activation of the alarm signal. See Max/Min. Alarm Diagram. Minimum temperature alarm. Temperature value (understood as distance from the Setpoint or as an absolute value based on Att) which if exceeded in a downward direction triggers the activation of the alarm signal. See Max/Min. Alarm Diagram. Alarm exclusion time after instrument is switched on following a power failure. Alarm exclusion time after defrost. Temperature alarm signal delay time. DISPLAY (folder with dis label) LOC Keyboard locking. It is still possible to enter parameter programming and modify the parameters, including the status of this parameter, in order to allow keyboard unlocking. y = yes (keyboard locked); n = no. PA1 When enabled (value other than 0), it constitutes the access key for level 1 parameters. ndt View with decimal point. y = yes (view with decimal point); n = no (only integers). CA1/CA2 Calibration 1/2. Positive or negative temperature value added to the value read by probe 1/2 ddl Viewing mode during defrosting. 0 = shows the temperature read by the thermostat probe; 1 = locks the reading at the temperature value read by thermostat probe when defrosting starts and until the next time the Setpoint value is reached; 2 = displays the label def during defrosting and until the next time the Setpoint value is reached. dro Select C or F for displaying the temperature read by the probe. 0 = C, 1 = F. PLEASE NOTE: switching between C and F or vice versa DOES NOT modify the point, differential, etc. (for example =10 C become 10 F). H00 H01 H33 H42 rel tab UL dl Fr CONFIGURATION (folder with CnF label) Selection of probe type. 0 = PTC; 1 = NTC. Enable Deep Cooling Cycle Function (y= yes, n= no) Configurability FNC key (ESC function) 0 = disabled; 1 = defrost; 2 = auxiliary; 3 = reduced (economy); 4 = DCC function Evaporator probe presence. n= not present; y= present. Device version: read only parameter. Reserved: read-only parameter. COPY CARD (folder with label Fpr ) - (see Copy Card section) Upload. Programming parameter transfer from instrument to Copy Card. Download. Programming parameter transfer from Copy Card to instrument. Format. Erasing all parameters in the key. PLEASE NOTE: using the Fr parameter (key formatting) results in permanent loss of data inserted in key. The operation cannot be cancelled. CONDITIONS OF USE PERMITTED USE For safety reasons the instrument must be installed and used in accordance with the instructions supplied. Users must not be able to access parts with dangerous voltage levels under normal operating conditions. The device must be suitably protected from water and dust according to the specific application and only be accessible using special tools (except for the front keypad). The device can be fitted to equipment for household use and/or similar use in the refrigeration sector and has been tested with regard to safety in accordance with the European harmonized reference standards: It is classified as follows: as an automatic electronic control device to be integrated as regards its construction; as a 1 B type operated control device as regards its automatic operating features; as a Class A device in relation to the category and structure of the software. UNPERMITTED USE The use of the unit for applications other than those described above is forbidden. It should be noted that the relay contacts supplied with the device are functional and therefore exposed to potential faults. Any protection devices required to comply with product requirements or dictated by common sense due to obvious safety reasons should be installed externally. ID DCC 5/6
6 TECHNICAL DATA ID DCC WIRING DIAGRAM Front protection Casing Dimensions Assembly Operating temperature Storage temperature Ambient operating and storage humidity Display range Analogue input Serial Digital outputs (configurable) Buzzer Measurement range Accuracy Resolution Power consumption Power supply IP65 PC+ABS UL94 V-0 resin plastic body, polycarbonate front, thermoplastic resin buttons. front panel 74x32 mm, depth 59 mm (terminals excluded). on panel, with drilling template 71x29 mm (+0.2/-0.1 mm) C C % RH (non-condensing). NTC probe: C ( F); PTC probe: C ( F) on display 3 1/2 digits + sign. 2 PTC or NTC input (parameter selectable). TTL for connection to Copy Card 3 outputs on relays: (A) 1 output on SPDT relay 8(3)A 1/2 hp 250Va, (B) 1 output on SPST relay 8(3)A 1/2 hp 250Va, (C) 1 output on SPST relay 5(2)A 1/4 hp 250Va (for relay capacity, see instrument label). if present from -55 a 140 C. better than 0.5% of bottom scale + 1 digit. 0.1 C (0.1 F up to F; 1 F above). 3 VA max 230Va ±10% 50/60 Hz PLEASE NOTE: please refer to label on the instrument for relay capacity, power supply and terminals layout. TERMINALS 1 Common relay contact 2 N.O. defrost relay (A) 3 N.C. defrost relay (A) 4 Compressor relay output (B) 5 Fan relay output (C) 6-7 Power supply 8-9 Probe 2 input (evaporator) 8-10 Probe 1 input (thermostat) A TTL input for Copy Card ID V (A) (B) (C) Supply A Pb2 10 Pb1 The technical characteristics in this document concerning measurements (range, accuracy, resolution, etc.) refer to the instrument in the strictest sense and not to any accessories provided such as probes, for example. This means, for example, that an error introduced by the probe is added to any error that is typical of the instrument. RESPONSIBILITY AND RESIDUAL RISKS Eliwell shall not be liable for any damages deriving from: - installation/use other than that prescribed and, in particular, which does not comply with the safety standards specified in the regulations and/or those given herein; - use on boards which do not guarantee proper protection against electric shock, water or dust when assembled; - use on boards which allow dangerous parts to be accessed without the use of tools; - tampering with and/or alteration of the product; - installation/use on boards that do not comply with the standards and regulations in force. DISCLAIMER 4/2006 -GBcod. 9IS42075 This document is exclusive property of Eliwell and cannot be reproduced and circulated unless expressly authorized by Eliwell. Although Eliwell has taken all possible measures to guarantee the accuracy of this document, it declines any responsibility for any damage arising out of its use. The same applies to any person or company involved in preparing and writing this document. Eliwell reserves the right to make any changes or improvements without prior notice and at any time. ID DCC 6/6
EZ-HT / EZ-MT / EZ-LT. Electronic controllers for refrigeration units
EZ-HT / EZ-MT / EZ-LT EN Electronic controllers for refrigeration units EZ-HT / EZ-MT / EZ-LT USER INTERFACE UP Press and release Scroll menu items Increases values Press for at least 5 sec Activates the
More informationEWPlus 961 EO Dispenser
EWPlus 961 EO Dispenser Electronic controllers for refrigeration units NOTE: When the controller is powered on it performs a lamp test, during which time the display and LEDs will flash for several seconds
More informationIDPLUS 902/961/971/974. Electronic controllers for refrigeration units
IDPLUS 902/961/971/974 GB Electronic controllers for refrigeration units CONTENTS ID PLUS 902/961 USER INTERFACE (KEYS AND LEDS)... 4 ID PLUS 971/974 USER INTERFACE (KEYS AND LEDS)... 6 ID PLUS 902/961
More informationENGLISH EW961/971/974
EN ENGLISH EW961/971/974 Electronic controllers for refrigeration units EN UP Press and release Scrolls through menu items Increases values Press for at least 5 secs Activates the Manual Defrost function
More informationIDPLUS 978. Electronic controllers for refrigeration units
IDPLUS 978 EN Electronic controllers for refrigeration units USER INTERFACE IDPLUS 978 UP Press and release Scroll menu items Increases values Press for at least 5 sec Activates the Manual Defrost function
More informationEMPlus 600. Electronic digital indicator
EMPlus 600 EN Electronic digital indicator USER INTERFACE UP Press and release Scroll menu items Increases values DOWN Press and release Scroll menu items Decrease values KEYS EMPlus 600 STAND-BY (ESC)
More informationEWRC 300/500 NT QUICK START. Controllers for static and ventilated cold rooms. English
EWRC 300/500 NT Controllers for static and ventilated cold rooms QUICK START INTRODUCTION The Coldface EWRC 300/500 NT series controls the temperature of a static or ventilated cold room. The instrument
More informationICPlus 902. Electronic controller with 1 intervention point
ICPlus 902 EN Electronic controller with 1 intervention point USER INTERFACE UP Press and release Scroll menu items Increases values Press for at least 5 sec Function can be configured by the user (H31)
More informationEWPLUS 902/961 EWPLUS 971/974
ENGLISH Electronic controllers for refrigeration units EN EWPLUS 902/961 EWPLUS 971/974 UP Press and release Scrolls through menu items Increases values Press for at least 5 secs Activates the Manual Defrost
More informationInterLink ECM20/ECL60 EC Series Installation and Operation Manual
Commercial Refrigeration Parts InterLink ECM20/ECL60 EC Series Installation and Operation Manual Commercial Refrigeration Parts ECM20/ECL60 Installation and Operation Manual Contents User Interface 3 Keys
More informationID985/V. Electronic controllers for ventilated refrigeration units with electronic expansion valve management
ID985/V GB Electronic controllers for ventilated refrigeration units with electronic expansion valve management SUMMARY MECHANICAL ASSEMBLY...3-GB ELECTRICAL CONNECTIONS...3-GB ELECTRICAL DIAGRAM...4-GB
More informationID 985/S/E/CK - ID985/E LX electronic controllers for ventilated refrigeration units
cod. 9IS23080 rel. 4/08 -GB- ID 985/S/E/CK - ID985/E LX electronic controllers for ventilated refrigeration units with RS485 on board (ID985/S/E/CK) and remote display BUTTONS AND DISPLAY UP button Scrolls
More informationID 985/S/E/CK - ID 985/E LX
ID 985/S/E/CK - ID 985/E LX Electronic controllers for ventilated refrigeration units with RS485 on board (ID985/S/E/CK) and remote display BUTTONS Scrolls through the menu items Increases values Activates
More informationEWPC 901/A rel. 6/96 ing
EWPC 91A rel. 696 ing temperature controller with alarm output WHAT IT IS The EWPC 91A is a temperature controller specifically designed for refrigeration applications. The instrument includes a 1 Vdc
More informationEWTS LX programmable electronic timers
cod. 9IS43096 rel. 7/06 -GB- EWTS 950-990 LX programmable electronic timers LEDs cnt slow flashing for parameter programming fast flashing when counting in progress permanently on when counting stopped
More informationIC 915 (LX) Alarm ON for active alarm; blinking when a silenced alarm is still present
IC 95 (LX) GB cod. 9IS37 rel. 4 electronic controller with points and differential point adjustment USER INTERFACE The user has a display and four buttons for controlling instrument status and programg.
More information4-step Chiller and Heat Pump Controller
4-step Chiller and Heat Pump Controller Technical Data Sheet GENERAL DESCRIPTION MODELS CODE MODEL DESCRIPTION MW324000 ECH 420 HEAT PUMP WITH 4 STEPS/ 2 CIRCUITS + MODBUS MW324005 ECH 420/V WITH SCREW
More informationEWPlus 961/971/974 EO LVD
EWPlus 961/971/974 EO LVD Versatile high-performance controllers thanks to the new Energy Saving algorithms for plug-in refrigerated cabinets. USER INTERFACE EWPLUS EO LVD NOTE When switched on, the device
More informationID974E electronic controllers for ventilated refrigeration units
cod. 9IS448- rel. 7-8 -GB- ID974E electronic controllers for ventilated refrigeration units USER INTERFCE The user has a displa and four kes for controlling status and programg of the instrument. KEYS
More informationEWCH 485 Electronic Pulse Counter
Electronic Pulse Counter Technical Data Sheet INSTRUMENT DESCRIPTION GENERAL DESCRIPTION is a programmable microprocessor based counter with 1or 2 outputs. The instrument offers the possibility to program:
More informationICPlus 915. Electronic controller with 2 intervention points
ICPlus 915 EN Electronic controller with 2 intervention points USER INTERFACE UP Press and release Scroll menu items Increases values Press for at least 5 sec Function can be configured by the user (H31)
More informationPROGRAMMING CONTROLLER ELIWELL IC-915 DUAL CONTROLLER
PROGRAMMING CONTROLLER ELIWELL IC-915 DUAL CONTROLLER Programming Manual Release Date: July 5, 2006 Publication Number: 33319INS Revision Date: April 03, 2014 Revision: C Visit the Cornelius web site at
More informationMECHANICAL INSTALLATION
Controllers for freezer cabinet and cold rooms with built-in compressor. Panel-mounted Energy Saving algorithms and optimised defrost control 8 preloaded applications efrost at single/double evaporator
More informationID-Digifrost Line ID-DIGIFROST LINE BROCHURE
IDDigifrost Line IDDIGIFRT LINE BRCHURE Table of Contents General Description Icon pecifications election Guide ID 96(), 96 L 3 ID 970, 970 L 4 ID 97, 97 L temperature (PtcNtc) 5 ID 974, 974 L 6 ID 975
More informationGCI-5K INSTALLATION AND OPERATOR S MANUAL
GCI-5K INSTALLATION AND OPERATOR S MANUAL Grid-tied inverter for wind Ningbo Ginlong Technologies 1 INTRODUCTION 2 SAFETY GUIDELINES AND WARNINGS 3 INSTALLATION 3.1 Selecting a location for the inverter
More informationEWCM Compact controller for compressor plants
EN EWCM 4120-4150-4180 e Compact controller for compressor plants 1 Summary INTRODUCTION - CHaracteristics...4 CONDITIONS OF USE...4 MECHANICAL ASSEMBLY...7 WIRING DIAGRAMS...7 CONNECTION DIFFERENCES BETWEEN
More informationControllers for static or ventilated refrigeration units up to 2HP. Innovative Solutions for Cold Rooms. Technology & Evolution
Controllers for static or ventilated refrigeration units up to 2HP Innovative Solutions for Cold Rooms Technology & Evolution MasterCella is the new series of controllers for cold rooms that joins the
More informationXEV EX48 Superheat Controller
Instruction Sheet PA-00369 January 2014 XEV EX48 Superheat Controller XEV EX48 Superheat Controller with ModBus Communication Capability XEV EX48 Driver for Emerson EX4,5,6,7,8 Electronic Stepper Expansion
More informationWING REFRIGERATION CONTROLLERS
SECTION INDEX FUNCTIONS MODELS - NT, MT AND LT APPLICATIONS COMPACT/SPLIT FORMAT Thermostats and off cycle defrost multifunction controllers XW10L - XW10V- - XW20L - XW20LS - XW20V - XW20VS Multifunction
More informationTLZ10 DIGITAL ELECTRONIC THERMOCONTROLLER. toll-free 1(866) (603) ADVANCED THERMOELECTRIC PO Box 1003, WRJ, VT 05001
TLZ0 DIGITAL ELECTRIC THERMOCTROLLER ADVANCED THERMOELECTRIC PO Box 003, WRJ, VT 000 toll-free (8) -434 (03) 888-47 sales@electracool.com The Z3 Series became the replacement for the TLZ0 and TDH-0 Series
More informationElectronic controllers for small centralised air-conditioning units
FLEX Electronic controllers for small centralised air-conditioning units General Description Eliwell, a leading manufacturer for over a decade of control equipment for small and medium-size air conditioning
More informationDESIGO RX Individual room controllers. for fan-coil systems, chilled ceilings and radiators, with LONMARK-compatible bus communications
3 834 DESIO RX Individual room controllers for fan-coil systems, chilled ceilings and radiators, with MARK-compatible bus communications RXC20.1 RXC21.1 The RXC20.1 and RXC21.1 controllers are used for
More informationOEM. Room unit QAA822 with2- wire interface. Building Technologies CLIMATIX TM. For use with Climatix controllers
OEM CLIMATIX TM Room unit QAA822 with2- wire interface For use with Climatix controllers Remote control of air conditioning unit Mandík Measurement of the room temperature Buttons for starting, setting
More informationField module for cold locations for installation in refrigerators for direct control of a pulsed expansion valve
FKE003 Field module for cold locations for installation in refrigerators for direct control of a pulsed expansion valve Features Operation of electronic expansion valves pulsed via integrated electronic
More informationUser Guide. Multipipe Units CMAA / RTMA CNT-SVU004B-GB
User Guide Multipipe Units CMAA / RTMA CNT-SVU004B-GB USER GUIDE WARNING Supply the unit at least 24 hours before the initial startup to heat the compressor oil. In conditions of low water temperature,
More informationLOGIC CONTROLLER INSTALLATION MANUAL NTR 756 B /E
LOGIC CONTROLLER INSTALLATION MANUAL NTR 756 B /E Table of contents 1. INTRODUCTION...1 2. HARDWARE DESCRIPTION...2 3. INSTALLATION...6 4. CONNECTION...8 5. USER SAFETY AND PROTECTION OF THE EQUIPMENT...11
More informationRoom unit with PPS2 interface
1 626 Room unit with PPS2 interface for use with: controllers with a PPS2 interface QAA88.3 Room temperature measurement Key buttons for adjustment of the room temperature setpoint Key buttons for operating
More informationEVF305 Product specifications - Version 1.02 EVCO S.p.A. Evco S.p.A. Product specifications EVF305
Evco S.p.A. Product specifications EVF305 Digital controllers for the management of the rotisserie with capacitive type user interface Drawn-up by Name and surname Date November 2012 page 1 of 14 1. REVISIONS
More informationDC Cooling Unit MODEL : TDC 500A / TDC 300A
DC Cooling Unit MODEL : TDC 500A / TDC 300A DC Cooling unit Instruction Manual Contents 1. DC Cooling unit...3 2. Technical Specifications...4 3. Installation procedure. 5 4. Operation/Working... 6 5.
More informationERC 21X Modbus parameter
Programming Guide ERC 21X Modbus parameter Copyright Danfoss Produced by ZA 2015.02 Programming guide ERC21X Modbus parameter DKRCC.EZ.RL0.A1.02 / 520H9702 1 ERC 211-1 relay Software version: 4.13 Configuration
More informationNon-communicating room controllers
3 882 DESIGO RXA Non-communicating room controllers RXA29.1 For fan-coil systems The RXA29.1 room controller are used for temperature control in individual rooms. For 2-pipe or 4-pipe fan-coil systems,
More informationUser Guide. For controller on CXAO / RTXB heat pumps CGCM / CXCM 2 circuit units. CNT-SVU005C-GB Original instructions
User Guide For controller on CXAO / RTXB heat pumps CGCM / CXCM 2 circuit units CNT-SVU005C-GB Original instructions Table of contents Advanced electronics... 3 Technical Specifications... 4 Display description...
More informatione30v DIGITAL ELECTRONIC THERMOMETER OPERATING INSTRUCTIONS Index
e30v DIGITAL ELECTRONIC THERMOMETER OPERATING INSTRUCTIONS Vr. 01 (ENG) - 18/01 - cod.: ISTR-Me30V-ENG01 ASCON TECNOLOGIC S.rl. Viale Indipendenza 56, 27029 - VIGEVANO (PV) ITALY Tel.: +39 0381 69871 -
More informationProduct and functional description
Product and functional description The RS 520/23 shutter / blind actuator is a KNX device with one relay output. The device is installed in an AP 118 Control Module Box or an AP 641 Room Control Box. The
More informationSTRA-17 Room controller. Installation and maintenance manual. Content
Content Installation preparations... Wiring diagram...3 Display handling...5 Technical data...6 Configuration...7 Operating modes...7 Controller modes...7 Activation operating modes...7 Control states...8
More informationON/OFF HUMIDIFIER CONTROL (ROOM 0R DUCT SENSOR) WITH OUTDOOR TEMPERATURE RESET OVERVIEW WALL CONTROLLER INSTALLATION (TCY-BH-T-U)
(ROOM 0R DUCT SENSOR) WITH OUTDOOR TEMPERATURE RESET TCY-BH-T-U Wall controller with sensor TDC-BH-T-U Duct controller with sensor SOA-Tn10 Outdoor temperature sensor (Optional) OVERVIEW For wall applications
More informationRack Input Module Installation Instructions
Rack Input Module Installation Instructions DOC. #560105000 A 7/30/04 PRINTED IN U.S.A. Regulatory Compliance Safety This device has been tested and found to be in compliance with the requirements set
More informationTemperature controller Ducted systems
2 725 Temperature controller Ducted systems Standard model without zoning functions RRV851 Multifunctional controller used for central control of ducted HVAC systems in combination with a QAX850 master
More informationQuick Start Installation and User Manual
1 Quick Start Installation and User Manual Contents 1. Overview 2. Technical Specifications 3. Installation Mounting Electrical Installation Clamp Installation Wiring Diagrams 4. Installation Settings
More informationEnergy ST 500 Electronic controllers for centralised air-conditioning units
Energy ST 500 Electronic controllers for centralised air-conditioning units GB Invensys Controls Europe An Invensys Company UP+DOWN Manual reset ST500 MENU LAYOUT Manual defrost UP DOWN Switch on/off Change
More informationTECHNICAL MANUAL WATER 300 C 5300 CV/06-00 GB
T E C H N I C A L M A N U A L TECHNICAL MANUAL C 5300 CV/06-00 GB GB The information contained in this document may be modified without prior notice and is in no way binding, even implicitly, for CLIMAVENETA.
More informationControllers for compressor racks with advanced energy saving. PN08 September 2016
page 1 / 16 XC400/600 for small/medium compressor rack management Dixell introduces the new compact parametric controllers for compressor rack with. Dixell presents the XC400/600 series, dedicated to the
More informationES 4000 STANDARD. 1 General information Document Overview General description Introduction... 4
Controller Instruction 1 General information ES 4000 STANDARD Printed Matter Number : 2946 7002 09 Applicable to : MB compressors Preliminary Operations: : Safety Instructions : General Persons Required
More informationManual Simatek Control Unit GFC 32
Manual Simatek Control Unit GFC 32 Original instructions 1400004_GB Ver. 2014.01.09 Index 1. Main features 3 2. Technical features 3 3. Installation guidelines 4 4. Preliminary checks 5 5. Electrical connections
More informationSuitable for a wide range of installations with wall-mount, flush-mount and hand-held remote control options.
TUC03 Configurable Terminal Unit Controller Product Bulletin The TUC03 Configurable Terminal Unit Controller is designed specifically to provide direct digital control of terminal unit applications with
More informationESM-3711-CL 77 x 35 DIN Size, Minimum & Maximum Temperature Record, Digital, ON / OFF Cooling Controller
ESM-3711-CL 77x35 DIN Size Cooling Controller Internal Buzzer ESM-3711-CL 77 x 35 DIN Size, imum & imum Temperature Record, Digital, ON / OFF Cooling Controller - 3 Digits display - NTC input or, PTC input
More informationOP10. Pre-programmed, configurable controller for simple applications
revision 10 2013 OP10 Pre-programmed, configurable controller for simple applications The Optigo OP10 range of controllers can be set to handle everything from temperature or humidity control to control
More informationManual Control Unit GFC 32
Manual Control Unit 1400004_EN/05.2017 Index 1. Main features 3 2. Technical features 3 3. Installation guidelines 4 4. Preliminary checks 5 5. Electrical connections 5 6. Settings 6 7. Remote control
More informationNon-communicating room controllers
3 881 DESIO RXA on-communicating room controllers For fan-coil systems RXA20.1 RXA21.1 RXA22.1 The RXA20.1, RXA21.1 and RXA22.1 room controllers are used for temperature control in individual rooms. For
More informationInstallation, Start-up and Operating Instructions
Installation, Start-up and Operating Instructions EVOLUTION SMART SENSOR FOR ZONING Cancels: NEW II ZONESMS-0-1 7-04 NOTE: Read the entire instruction manual before starting the installation. This symbol
More informationRTD-NET Installation Instructions
LED3 SW1 LED4 RTD-NET Installation Instructions 0V +V POWER 15-24VDC English RTD-NET Installation Instructions 100.00 RTD-NET Control Interface realtime Control Systems REMC P1 P2 RS485 D-BUS DB DA GND
More informationRoom Temperature Controllers
3 021 Room Temperature Controllers for two-pipe fan coil units RCC10 Output for on / off valve actuator Outputs for three-speed fan Control depending on the room or return air temperature (RCC10) Automatic
More informationpco 3 Controller User Manual ASPX Digital Scroll, Air Packaged Chiller For Version MCDSV_A02
pco 3 Controller User Manual ASPX Digital Scroll, Air Packaged Chiller For Version MCDSV_A02 pco 3 Controller User Manual Introduction The Airstack Chiller is a modular air-cooled chiller composed of
More informationML Twin Compressor Controller Installation & User Guide
ML Controller PR0123-TWI ML Twin Compressor Controller Installation & User Guide For Products: - PR0710, PR0711, PR0720, PR0721 Resource Data Management Ltd 80 Johnstone Avenue, Hillington Industrial Estate,
More informationQXA2000 QXA2001. Condensation Monitor QXA2001 QXA2000 AQX2000
1 542 1542P03 1542P01 1542P02 QXA2001 QXA2000 AQX2000 Condensation Monitor QXA2000 QXA2001 The QXA2000 condensation monitor is used to avoid damage due to condensation on chilled ceilings and in HVAC plant.
More informationZelio Control-modular measurement and control relays 1
Presentation, description 1 106439 RM35 TM111MW Presentation Motor temperature measurement and 50MW and RM35 TM250MW monitor the following, on 3-phase supplies: correct sequencing of phases L1, L2 and
More informationControl Cube T Digital Temperature Controller Operating Manual
Control Cube T Digital Temperature Controller Operating Manual Specifications Willhi WH7016+ digital thermostatic controller; 110vac; 30A relay Dual mode (heating or cooling) 13A maximum current rating
More informationMiG2 CONTROLLERS. 2 & 4 Stage General Purpose Controllers, with Air-conditioning Facilities
MiG2 CONTROLLERS 2 & 4 Stage General Purpose Controllers, with Air-conditioning Facilities The MiG2 controllers incorporate: 2 Inputs (Configurable as Resistive, 0 10V, 0 20mA or 4 20mA) 2 or 4 Relay Outputs
More informationpowersplit...the network evolution!
powersplit...the network evolution! Technology & Evolution PST00VR100, PST00SR300, PJC 2 Hp PJS,Y 2 Hp PTS00LR200 powersplit is the new controller for multiplexed showcases with on-board compressors. Thanks
More informationSERIES 59. Microprocessor Temperature Controller with Digital Display and RTD, Thermistor or Thermocouple Sensing
SERIES 59 Microprocessor Temperature Controller with Digital Display and RTD, Thermistor or Thermocouple Sensing FEATURES Microprocessor-based no cumbersome menus Large 3-digit LED display permits easy
More informationMulti Units Humidity/Temperature Transmitter. HygroViewer Model JW300 User Manual
Multi Units Humidity/Temperature Transmitter HygroViewer Model JW300 User Manual 1. Electrical Wired & Installation The power cord is a one-meter length, 22 AWG, 7 different colors for recognition. Please
More informationField selectable application type and room module series, via dip-switches on controller
TUC03 Plus Configurable Terminal Unit Controller Product bulletin The TUC03 Plus configurable Terminal Unit Controller is specifically designed to provide an improved BACnet integration. It allows the
More informationLED W RGBA User Manual
LED- 245-1W RGBA User Manual Please read the instructions carefully before use CONTENTS 1. Safety Instructions...2 2. Technical Specifications...3 3. How To Set The Unit...4 3.1 Control Panel...4 3.2 Main
More informationApplication Engineering
Application Engineering Application Engineering Commercial Comfort Controller (543-0175-00) Installation Guide May 2012 Contents Mounting... 1 Connections and Wiring... 1 Wiring Considerations... 1 Input
More informationXVD Driver for bipolar electronic expansion stepper valves
Driver for bipolar electronic expansion stepper valves EN User and Installation manual CONTENTS 1 Introduction... 4 1.1 USING THE MANUAL... 4 1.2 General Description... 4 1.2.1 Main functions:... 5 1.3
More informationLXM32AD18N4 motion servo drive - Lexium 32 - three-phase supply voltage 208/480V kw
Characteristics motion servo drive - Lexium 32 - three-phase supply voltage 208/480V - 1.8 kw Complementary Switching frequency Overvoltage category Leakage current Output voltage Electrical isolation
More informationRCF-230CAD. Room controller with communication for fancoil applications with two analogue V DC outputs
revision 04 2016 RCF-230CAD Room controller with communication for fancoil applications with two analogue 0...10 V DC outputs Intended to control heating and/or cooling in 2- or 4-pipe installations. Setpoint
More informationJUMO ecotrans ph 03 Microprocessor transmitter/ switching device for ph/redox voltage and temperature
Page 1/7 JUMO ecotrans 03 Microprocessor transmitter/ switching device for /Redox voltage and temperature with a 2-line LCD for mounting on a 35 mm DIN rail Brief description Depending on the configuration,
More informationFCU-4 FAN COIL CONTROLLER
FCU-4 FAN COIL CONTROLLER BACnet Enabled Description The FCU-4 is designed to provide complete control of fan coil units. The FCU-4 incorporates all the inputs and outputs to ensure that this advanced
More informationSupplementary operating instructions for your air curtain system Controller TMC 500
Supplementary operating instructions for your air curtain system Controller TMC 500 (Translation of the original) Serial number: Year: Please quote this number when contacting customer service! Date 08.04.2016
More informationS66 Series Electronic Fan Speed Control
FANs 121, 125, 1628.3 Product/Technical Bulletin S66 Issue Date 0918 S66 Series Electronic Fan Speed Control The S66 Series Electronic Fan Speed Control is designed to modulate the speed of single-phase,
More informationElectronic controllers for centralised air-conditioning units
Energy Flex Electronic controllers for centralised air-conditioning units General Description Eliwell, a leading manufacturer for over a decade of control equipment for small and medium-size air conditioning
More informationProduct and Applications Description. Example of Operation. Installation Instructions WARNING. Note. Application Programs
Product and Applications Description Example of Operation dimmer UP 525/11 load circuit AC 230 V L1 N The dimmer UP 525/11 is a dimming actuator for mounting in box mounts (a.o. 60 mm Ø, 60 mm depth).
More informationXR-CHC and XRB-CHC Refrigeration controllers with Bluetooth connectivity
XR-CHC and XRB-CHC Refrigeration controllers with Bluetooth connectivity PN 13/18 September Dixell introduces its new XR-CHC and XRB-CHC controllers with Bluetooth connectivity for refrigerated applications.
More informationMicro-Ohmmeter Model 6292
Micro-Ohmmeter Model 6292 Quick Start Guide ENGLISH www.aemc.com CHAUVIN ARNOUX GROUP Statement of Compliance Chauvin Arnoux, Inc. d.b.a. AEMC Instruments certifies that this instrument has been calibrated
More informationAUDIO AND VIDEO DOOR ENTRY SYSTEM WITH NEXA CODED PANEL
AUDIO AND VIDEO DOOR ENTRY SYSTEM WITH NEXA CODED PANEL 2 INTRODUCTION First and foremost we would like to thank you for purchasing this product. Our commitment to satisfying our customers can be seen
More informationPressure switch RE B/ Type HEDE10.../1/ Operating instructions
Pressure switch Type HEDE10.../1/ RE 30276-B/10.10 Replaces: 06.10 Operating instructions 2/20 Bosch Rexroth AG HEDE10.../1/ RE 30276-B/10.10 Contents 1 Overview of menu...3 2 Safety note... 4 3 Operating
More informationRoom unit with PPS2 interface
s 1 640 1640P01 Desigo RX Room unit with PPS2 interface For use with: QAX34.3 Equipment from the RXC, RXB, RXL and RXA (PPS2) ranges Desigo PX automation stations 1) Devices with a PPS2 interface Measurement
More informationFCA THE SOLLATEK FREOCOM
FCA THE SOLLATEK FREOCOM the Intelligent Controls Temperature control, energy saving and voltage protection for all fridges, freezers and coolers. As the problems associated with global warming become
More informationManual Control Unit GFCD 16
Manual Control Unit 1400002_EN/04.2017 Index 1. Main features 3 2. Technical features 3 3. Installation guidelines 4 4. Preliminary checks 5 5. Electrical connections 5 6. Filter taps 5 7. Settings 6 8.
More informationCustom Controller Installation Instructions
MODEL CUSTOM CONTROLLER HARDWARE CODE MAX ALLOWABLE AMBIENT TEMP: 70 C (158 F) THIS DEVICE COMPLIES WITH PART 15 OF THE FCC RULES. OPERATION IS SUBJECT TO THE FOLLOWING TWO CONDITIONS: 1) THIS DEVICE MAY
More informationASI Systems ML5740A Series
ML5740A Series Electric Linear Valve Actuators Non-Spring Return APPLICATION The ML5740A series actuators operate standard ASI Systems valves in heating, ventilating and air conditioning (HVAC) applications.
More informationEE360. High-End Moisture in Oil Transmitter. Typical applications. Features EE360 EE360. (+34)
is dedicated for reliable monitoring of lubrication, hydraulic and insulation oils as well as diesel fuel. In addition to highly accurate measurement of water activity (a w ) and temperature (T), calculates
More informationLXM32SD18M2 motion servo drive - Lexium 32-single phase supply voltage 115/230V - 0.5/1.kW
Product data sheet Characteristics LXM32SD18M2 motion servo drive - Lexium 32-single phase supply voltage 115/230V - 0.5/1.kW Main Range of product Lexium 32 Product or component type Device short name
More informationAV24-MFT AV24-MFT2 AV24-MFT2-C105. Power consumption In operation For wire sizing N 1700 N Control Control signal Y Operating range
echnical data sheet AV4-MF()(-C105) Multi-functional linear actuators for -way and 3-way globe valves Actuating force 500 N Nominal voltage AC/DC 4 V Control: modulating DC 0 10 V Position feedback DC
More informationECON-ZIP-BASE. ZIP Economizer Base Module
ECON-ZIP-BASE ZIP Economizer Base Module You can mount the ZIP Economizer in any orientation; it is recommended that you mount it in a position that will allow full utilization of the LCD and key pad and
More informationRXL24.1. Room controller RXL. Communicating controller for chilled ceiling and radiator applications CC-02
s 3 878 RXL Room controller RXL24.1 Communicating controller for chilled ceiling and radiator applications CC-02 The RXL24.1 room controller is used for temperature control in individual rooms. For chilled
More informationProgrammable controller MCX06C
MAKING MODERN LIVING POSSIBLE Technical brochure Programmable controller MCX06C Danfoss range of universal MCX programmable controllers offers the functionality and reliability you need to get the best
More informationGRUNDFOS INSTRUCTIONS. Control MPC. Installation and operating instructions
GRUNDFOS INSTRUCTIONS Control MPC Installation and operating instructions English (GB) English (GB) Installation and operating instructions Original installation and operating instructions CONTENTS Page
More informationCurrentWatch Current Sensors. EGF Series Ground Fault Sensors. Ground Fault Sensors with Solid-State or Mechanical Relay Outputs.
CurrentWatch Current Sensors Ground Fault Sensors with Solid-State or Mechanical Relay s 1 Contents Overview.................... 1 Model Selection, Switches...... 2 Model Selection, Accessories... 3 Wiring
More information