1 DIGIPLEX EVO PROGRAMMING HELP GUIDE Entering Programming Mode 1) Press and hold the [0] key 2) Enter your [Installer Code] (default ) 3) Enter 4-digit [section] you wish to program 4) Enter required data While in a one can press CLEAR and you will move one step back in programming. You can now Enter any other or by pressing CLEAR again you will exit Programming Mode. Zone Programming Pg.9 [0400] is accessible only when using EVO641 and EVO641R keypads. Without section [0400], you can only program the first 96 zones of the system using sections [0001] to [0096] for the zone s serial number and input, sections [0101] to [0196] for zone parameters, sections [0201] to [0296] for report codes and sections [0301] to [0396] for zone labels. In addition, with a EVO48 panel, you can only program the first 48 zones with or without section [0400]. Enter [0400], then enter the number of the zone you want to program Zone 1 = 001 Enter the zone s 8-digit serial and 3-digit input number (The input number is not needed for module with only one input) Press [0] followed by [Enter] to clear a zone s serial number. Enter the zone s parameters (01) (*2*4***) default Enter the zone s report codes (00) (00) (00) (00) default Enter the zone s label Press [ENTER] to save and go to the next zone Pressing [CLEAR] twice will exit the zone programming menus. Press [ENTER] before pressing clear to save your modifications. Zone Definition Partition Zone Option Select one Select one (default) 1 - Entry Delay 1 Switch options 1 to 8 or 2 - Entry Delay Follow 1 - Assigned to Partition 1 [1] Auto Zone Shutdown 4 - Instant (default) [2] Bypass (default on) 5-24Hr Buzzer 2 - Assigned to Partition 2 [3] Stay Zone 6-24Hr Burglary 3 - Assigned to Partition 3 [4] Force Zone (default on) 7-24Hr Hold-up 4 - Assigned to Partition 4 [5] [6] Zone Alarm Type 8-24Hr Gas 5 - Assigned to Partition 5 off off Steady Alarm 9-24Hr Heat 6 - Assigned to Partition 6 off on Pulsed Alarm A - 24Hr Water 7 - Assigned to Partition 7 on off Silent Alarm B - 24Hr Freeze 8 - Assigned to Partition 8 on on Report Only C - Delayed 24Hr Fire [7] Intellizone D - Standard 24Hr Fire [8] Delay before Transmission E - Stay Delay 1 F -StayDelay2. In any Zone Programming option, pressing [ACC] will save the data and go to the next zone on the same option screen. Pressing [TRBL] will save the data and go to the previous zone on the same option screen. Alarm Report Code Device A Control Panel SN#:020000A2 Input Terminals Input 2 Device B Detector A: Device A: Device B: Device C: Alarm Restore Report Code Keypad Zone APR3-ZX8 Module SN#: Input 5 Input Terminals Zone# 1= 2= 3= 4= Keypad SN#: 1A Tamper Report Code Detector A SN#: COMMUNICATI CombusNETWORK # [0001] [0002] [0003] [0004] Serial# A A Tamper Restore Report Code / / / / Device C Input# N/A N/A Ademco slow, Silent Knight fast, SESCOA, Ademco express or Pager formats: Key-in desired 2-digit hex value FF for Contact ID (MEM-Key on LCD). Automatic Report Code Programming Pg. 50 Remember that the EVO panel does not have zones, but inputs. These inputs must be assigned to zones first. Example: The main panel has eight inputs. If you want zones 1 to 8 to be on the main panel you need to fill in the serial number of the main panel and input next to the zone assignment. Zones 1 to 8 does not have to be on the main panel though. Wireless Zones Wireless detectors all have a six digit serial number. These serial numbers need to be assigned to a MG-RTX3(tranceiver) as inputs. Each MG-RTX3 have 32 inputs, thus with each MG-RTX3 fitted to an EVO one can install 32 wireless zones (6 x MG-RTX3 = 192 zones). To assign wireless inputs to a MG-RTX one must enter Module Programming. ( the MG-RTX is a module) 1) Press and hold the [0]key 2) Enter your installer code (Default = ) 3) Enter section ) Enter the 8-digit MG-RTX serial number. (now you are in the module s programming) 5) Enter module section 101 for input 001 (to for input 032) 6) Fill in the 6-digit detector serial -or press the tamper switch on the wireless detector After the inputs have been created they can be assigned to zones the same as any other input. Now refer back to zone programming. Pg.1

2 Keyswitch Programming Pg.19 Keyswitch numbering [0501] to [0532] represent keyswitches 1 to 32 respectively. This feature allows you to assign a keyswitch to an addressable or hardwired detection device. Enter 3- digit [INPUT NUMBER] of Module to which keyswitch is connected. Enter 8- digit [SERIAL NUMBER] of Module to which keyswitch is connected. Keyswitch parameters [0601] to [0632] represent keyswitches 1 to 32 respectively. This feature defines the keyswitch s partition assigment and arming method. Keyswitch Partition Assignment 0 - Not assigned to a partition (default) 1 - Keyswitch Assignment to Partition Keyswitch Assignment to Partition Keyswitch Assignment to Partition Keyswitch Assignment to Partition Keyswitch Assignment to Partition Keyswitch Assignment to Partition Keyswitch Assignment to Partition Keyswitch Assignment to Partition 8 Keyswitch Definitions 0 - (default) 1 - Momentary Keyswitch (pulsed) 2 - Maintained Keyswitch (latched) 3 - Generates a Utility Event Event on Open 4 - Generates a Utility Event Event on Open and Close Keyswitch Options (default: all Off) [ 3] - Disarm Only [ 4] - Off = Disarm On = Disarm only if Stay/ Instant armed [ 5] - Arm Only [ 6] - * Stay Arming [ 7] - * Force Arming [ 8] - * Instant Arming * Select only one. If all Off Keyswitch will regular arm 8-digit Serial Number Input# Define Assign Keyswitch Options [0501] / / / / / / / / / [0601] [0502] / / / / / / / / / [0602] [0503] / / / / / / / / / [0603] (3035) will automatically fill in the report codes for Keyswitch Arm/Disarm or they could be filled in individually at sections (0701) to (0832).Pg.20 Panic Input The above mentioned KEYSWITCH inputs may be programmed as a Panic, Medical or Fire input. These inputs will follow the Auxiliary Panic inputs enabled as shown below. After assigning a input in any position at section (0501) to (0532) the Panics are defined at sections (0601) to (0632) as follow: Example: (0601) First Digit (5) Second Digit (1) Then enable Options 1 to 8 5-Always 1-Panic 2-Medical 3-Fire Select Partition Assignment [0601] [0602] Partition Panic Alarm Options NB! the below mentioned options must be enabled for the above mentioned input to work on the required partition. Partition 1 [3123] Partition 2 [3223] Partition 3 [3323] Partition 4 [3423] Partition 5 [3523] Partition 6 [3623] Partition 7 [3723] Partition 8 [3823] Option ( = Default Setting) [1] Panic 1 (Keys 1 & 3)Panic [2] Panic 2 (Keys 4 & 6)Medical [3] Panic 3 (Keys 7 & 9)Fire [4] Panic 1 Alarm Type ( = Report Only; = Audible Alarm) [5] Panic 2 Alarm Type ( = Report Only; = Audible Alarm) [6] Panic 3 Alarm Type ( = Report Only; = Fire Alarm) [7] Always Report Disarming ( = Always; = Only After Alarm) [8] Auto-Force on Regular Arming Remember to fill in the Special Reporting codes for reporting in sections (3930) to (3932). PGM Activation for Radio could be achieved with PGM Event group 030 (pg.24). Common Partition Timers Pg.43 Partition 1 Partition 2 Partition 3 Partition 4 Partition 5 Partition 6 Partition 7 Partition 8 1) Press and hold the [0] key. Decimal Values from 000 to 255 Data 2) Enter your INSTALLER CODE Exit Delay Timer 3) Enter the Timer SECTI NUMBER. (Data x 1 second; Default = 060 seconds) [3108] / / [3208] [3308] [3408] [3508] [3608] [3708] [3808] 4) Fill in desired 3 digit timer. Example Entry Delay for 30 seconds. When you fill in (Data x 1 second; Default = 030 seconds) [3111] / / [3211] [3311] [3411] [3511] [3611] [3711] [3811] the last digit the time will be saved Entry Delay 2 and the programming will move onto (Data x 1 second; Default = 060 seconds) [3112] / / [3212] [3312] [3412] [3512] [3612] [3712] [3812] the next section or ask you to fill in a Bell Cut-off Timer [3113] / / [3213] [3313] (Data x 1 minute; Default = 4 minutes) [3413] [3513] [3613] [3713] [3813] new section. One does not have to press ENTER after a time has been Special Arming Exit Delay [3130] / / [3230] [3330] [3430] [3530] [3630] [3730] [3830] (Keyswitch,auto arming,winload etc.) filled in. Dialer Timers Pg.39 Auto-Arm Times Pg. 42 No Movement Auto Arming Schedule Pg. 47 Timings Pg.2

3 Options 1) Press and hold the [0] key. 2) Enter your INSTALLER CODE (Default: ) 3) Enter the Option SECTI NUMBER. 4) Turn desired Options 1to8 or by pressing on that digit. The corresponding number will lite up on the Keypad. To Disable an Option press on a lit digit. 5) Press the ENTER key. You will automatically be in the next. Change the data or press CLEAR and enter another. Example: System Options Pg.36, 37 Dialer Options Pg.38 Other Options Pg Partition Options Pg = Default setting SECTI [3031] : Partition Options 1 SECTI [3032] : Partition Options 2 [1] Partition 1 [1] Bell/siren output in partition 1 [2] Partition 2 [2] Bell/siren output in partition 2 [3] Partition 3 [3] Bell/siren output in partition 3 [4] Partition 4 [4] Bell/siren output in partition 4 [5] Partition 5 (EVO192 only) [5] Bell/siren output in partition 5 [6] Partition 6 (EVO192 only) [6] Bell/siren output in partition 6 [7] Partition 7 (EVO192 only) [7] Bell/siren output in partition 7 [8] Partition 8 (EVO192 only) [8] Bell/siren output in partition 8 Programmable Outputs Pg.21 Event Group Feature Group Start # End # The PGMs are not Pre-Programmed PGM Programming Suggested PGM programming: PGM Activation PGM1 [0910] / / [0911] / / [0912] / / [0913] / / PGM1 Arm/Disarm LED( - trigger only) PGM2 [0920] / / [0921] / / [0922] / / [0923] / / PGM2 Radio Panic( - or + trigger ) PGM3 [0930] / / [0931] / / [0932] / / [0933] 0 / / 0 0 PGM3 Radio Burglary( - or + trigger ) PGM4 [0940] / / [0941] / / [0942] / / [0943] 0 / / 0 0 PGM4 Radio Open/Close( - or + trigger ) PGM5 [0950] / / [0951] / / [0952] / / [0953] / / PGM5 Onboard Relay PGM Deactivation PGM1 [0914] / / [0915] / / [0916] / / [0917] / / NB! Change Jumper (JP1) position for + or - trip for PGMs 2, 3 and4 PGM2 [0924] / / [0925] / / [0926] / / [0927] / / PGM3 [0934] / / [0935] / / [0936] / / [0937] / / PGM4 [0944] / / [0945] / / [0946] / / [0947] / / PGM5 [0954] / / [0955] / / [0956] / / [0957] / / Event Group Event Feature Group Feature Start # End # 023 Zone Bypassed 024 Zone in Alarm 000 Zone Numbers 025 Fire Alarm 255=anyZone# Check the PGM Programming list from page 22 to 27 Note! For Panic and Burglary Radio triggers you need PGMs to pulse, thus PGM 2 and 3 need to follow the PGM Timer and not the Deactivation Event. Go to sections [0929] and [0939] and turn Option 1 for each. PGM Options Option ( = Default Setting) Other Programming PGM1 [0919] PGM2 [0929] Data PGM1 Delay [0918] / / (001to255x1sec./mins.) PGM2 Delay [0928] / / (001to255x1sec./mins.) PGM3 Delay [0938] 0 / / (001to255x1sec./mins.) 0 2 PGM4 Delay [0948] / / (001to255x1sec./mins.) PGM5 Delay [0958] / / (001to255x1sec./mins.) PGM3 [0939] (1*******) PGM4 [0949] PGM5 [0959] [1] PGM Deactivation After ( = Deactivation Event; = PGM Timer) [2] PGM Base Time ( = Seconds; = Minutes) Setting the Time and Date: 1) Enter the [Master Code] (default-1234) 2) TBL] key 3) 8] key 4) Enter the Time and Date. Changing the Installer Code 1) Press and hold the [0] key 2) Enter your [Installer Code] (default ) 3) Enter section [1000] 4) Enter the new Installer Code Usefull s [4000] - Displays the serial numbers of Panel and all Modules connected to the panel, use [ ] and [ ] to scroll. [4001] - Reset a module s programming by entering its serial number. [4002] - Locate/Unlocate a module by entering the serial number the module s Locate LED will flash. [4003] - Module Programming Mode, by entering the serial number of a module one can program the module. [4004] - Module data broadcasting can be done from here. First enter the source module s serial number then the other same type and version modules serial number/s. Press [ACC] to start transfer. [4005] - Quick module scanning will erase any module removed from panel from its memory. [4006] - Module Scanning that is the same as above, but you can add modules newly connected to the bus. Installer Function Keys To access the installer functions, press and hold the [0] key, enter the [INSTALLER CODE], and then press the KEY below: [STAY ] Test Report: Sends the Test Report report code programmed in section [3902] to the monitoring station. [FORCE] Call WinLoad Software: Will dial the PC telephone number programmed in section [3010] in order to initiate communication with a computer using the WinLoad software. [ARM] Answer WinLoad Software: Will force the control panel to answer a call made by the Monitoring Station that is using the WinLoad software. [DISARM] Cancel Communication: Cancels all communication with the WinLoad software or with the Monitoring Station until the next reportable event. [MEM] Installer Test Mode: The installer test mode will allow you to perform walk tests where the bell or siren will squawk to indicate opened zones. MEM] button again to exit. Partitions cannot be armed if the Installer Test Mode is enabled. [TRBL] Start Module Scan: The keypad will display the serial number of each module on the combus. [ACC] Combus Voltmeter: To verify if the combus is supply ing sufficient power, press and hold the [0] key, enter the [INSTALLER CODE] and press the [ACC] button. A reading of 12.3V or lower at the panel s service ke ypad connector indicates that the voltage is too low. The voltage may drop during the control panel battery test. Pg.3

4 Dialer Settings To the Panel for telephone reporting you need to do the following: 1) While in Programming Option 3 in [3036]. 2) Then enter the client s Account number in [3061]. Note to enter the same account number in s [3062] to [3068] if more than 1 Partition is used. 3) Enter 5555 in section [3070] to make sure you are using the Contact ID format. Make sure the control room set the client up with the same format. 4) Enter the base telephone number in section [ 3071]. Press ENTER when you get to the last digit. 5) Go to section [4032] and then [4037]. This will fill in all the Zone and Trouble reporting codes. If it is a business, go to section [4033] and [ 4035] as well. Account Numbers MSTN = Monitoring Station Telephone Number Data - Hex Value ( FFFF) Default [3061] / / / (if less than 4 digits, press [ENTER]) ACCOUNT NUMBER 0000 [3062] Partition 2 [3063] Partition 3 [3064] Partition 4 [3065] Partition 5 [3066] Partition 6 [3067] Partition 7 [3068] Partition 8 Reporting Formats [3070] REPORTING FORMATS FOR TELEPHE NUMBERS 1 TO 4 0-Ademco slow/1-silent Knight fast/2-sescoa/3-ademco Express/5-Contact ID/6-SIA FSK/7-Pager Use the same format for each number. Only the pager format can be used with other reporting formats. Data (Press [ENTER] if less than 32 digits) [3071] / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / MITORING STATI /PAGER TELEPHE #1 [3072] Second Base Number [3073] Third Base Number [3074] Fourth Base Number Special Telephone Number Keys Function LCD Grafica Function LCD Grafica [STAY ] Clear [CLEAR] Left action key (Clear) * # [FORCE] [#] Delete [TRBL] Switch to Tone Dialing (T) [ARM] (press key until desired Delete from cursor to the end [ACC] Wait for second dial tone (W) [DISARM] letter/symbol appears) Insert space [ MEM] 4-second pause (P) [BYP] Dial 9 for outside line 9+[STAY ] Only the SIA format supports the [0} digit in its account numbers. Enter the [STAY]=A digit in its place. When using the SIA Format, and the Account Number Transmission (see option [6] in section [3045] on page 37 correspond tothe partition, the control panel only uses the Partition 1 Account Number programmed in section [3061], but the report code includes the account number Automatic Report Code Programming When using Contact ID or SIA Reporting formats (section [3070] on page 36), default report codes can be programmed automatically. After automatic defaults are set, they can be changed and the remaining report codes can be set manually. [4030] ALL REPORT CODES RESET TO 00 Resets all the report codes from sections [0201] to [0296], [0701] to [0832], [2001] to [2199] and [3900] to [3999] to 00. [4031] ALL REPORT CODES RESET TO FF [0201] to [0296], [0701] to [0832], [2001] to [2199] & [3900] to [3999] [4032] ZE ALARM/ALARM RESTORE AND ZE TAMPER/TAMPER [0201] to [0296] RESTORE REPORT CODES [4033] USER/KEYSWITCH ARMING &DISARMING REPORT CODES [0701] to [0832], and [2001] to [2199] [4034] SPECIAL CODES [3900] to [3909] [4035] SPECIAL ARMING/DISARMING REPORT CODES [3910] to [3929] [4036] SPECIAL ALARM REPORT CODES [3930] to [3939] [4037] TROUBLE &TROUBLE RESTORE REPORT CODES [3940] to [3999] 1 Functions 2 Telephone Numbers VDMP3 Voice dialer module Select the following options to enable voice reporting and arm/disarm function. [1] Arm/disarm (default 1 and 2 ) [3090] [2] Voice reporting Program up to 8 telephone numbers which will be called in sequence in the event of an alarm. Telephone numbers should be programmed in priority sequence as the VDMP3 will start with telephone number 1. For extra key functions, see Special Telephone Number Keys on page 40. [3091] [3091] Telephone number 1 [3095] Telephone number 5 to [3092] Telephone number 2 [3096] Telephone number 6 [3098] [3093] Telephone number 3 [3097] Telephone number 7 [3094] Telephone number 4 [3098] Telephone number 8 3 Numbers 5 Features (PGM) Choose which telephone numbers will be enabled for each partition in your system. Options [1] to [8] represent telephone numbers 1 through 8. (Default: Telephone number 1 is enabled for all partitions.) [3133] [3133] Partition 1 [1] to [8] [3533] Partition 5 [1] to [8] to [3233] Partition 2 [1] to [8] [3633] Partition 6 [1] to [8] [3833] [3333] Partition 3 [1] to [8] [3733] Partition 7 [1] to [8] [3433] Partition 4 [1] to [8] [3833] Partition 8 [1] to [8] Features in this section correspond to utility key PGMs in the EVO control panel. For more information, see Feature Activation (PGMs). [3087] Options [1] to [8] represent features 1 to 8 (default: ) Remote Control Programming 1) First assign the remote to a user in User Code Programming. 2) Go to section[2900] and choose your remote button functions: (18) (20) MG-REM1 MG-REM2 Default (1 B) (C 0) Button 1 Button 2 Button 3 Buttons 2+3 Disarm Regular Arm Utility Key 1 3) At [2940] enter (00). Utility Key Disarm: cannot be modified Choose 1 function for each button Entry Function Entry Function [0] Button [8] Panic 1 [1] Regular Arm [9] Panic 2 [2] Stay Arm A = [stay] Panic 3 [3] Instant Arm* B = [force] Utility Key 1 [4] Force Arm* C = [arm] Utility Key 2 [5] N/A D = [disarm] Utility Key 3 [6] N/A E = [byp] Utility Key 4 [7] N/A F = [mem] N/A Pg.4

5 User Code Programming Note: Each option is considered when the number appears within the brackets Enter the Master Code (Default:1234) Enter Programming Mode By Pressing [0) then [ACC] Select User (002 =user 2) Enter Desired User Code (Pin) User Options [1] [2] Master Feature Master - user can program user access codes only Full Master - user can program user access codes, options, and assignments [3] Duress [6]Stay & Instant Switch Options [4] Bypass [7]Force 1to8or On default all [5] Arm Only[8] = Access keypad s partitions users can = Access user s partitions Regular Arm * Note: all users can regular arm User Options User Area Assignment Access Level and Schedule Assignment Enter Digits Press [ENTER] here if you do not need to program Access Control. You will move to Step10 Switch Options 1to8or Make sure that the user has a Partition enabled or else the code will not work. Partition Assignment [1] User Code has Access to Partition 1 [2] User Code has Access to Partition 2 [3] User Code has Access to Partition 3 [4] User Code has Access to Partition 4 [5] User Code has Access to Partition 5 [6] User Code has Access to Partition 6 [7] User Code has Access to Partition 7 [8] User Code has Access to Partition 8 Access Level & Schedule Assignment First Brackets: Access Level Enter Level from 00 to 15 (00 = all doors) Second Brackets: Schedule Enter number from 00 to 15 (00 = all times) Access Control User Options Access Card Assignment Remote Control Assignment User Label Press [ ENTER] to advanced to save and advanced to next user If no Remote press [ENTER] for Label or [CLEAR] for next user If no Label press [ENTER] You must ENABLE option 1 for ACCESS Access Control Options CTROL [1] Access Control [2] Can Disarm with Access Card [3] Card with Door Unlocked Period Extension [4] [5]Feature off offcannot Arm with Card (armingdisabled) on offcan Regular Arm with Card off oncan Stay Arm with Card on oncan Force Arm with Card [6] Add Tolerance Window to Schedules [7] off = Code can arm, disarm & access anytime on = Code follows Schedule [8] off = Valid Card can be granted access and disarm partition on = Valid Card can be granted access, Access Card Assignment Enter Access Card's serial number manually or present Card to the reader. Remote Control Assignment* Enter remote control s serial number manually or press a remote button twice. Access Control (For ACCESS modules and READERS) Programming Overview: Steps 1, 2 and 6 are the MINIMUM requirement to program Access Control: 1. Access Control in section [3038] option [1]. 2. Assign the Doors in sections [2201] to [2232] by entering the DGP-ACM12 or access keypad s serial number for each door. 3. Optional: Create up to 15 Access Levels in sections [2601] to [2615]. Assign certain combinations of doors to a level or levels 01 to 15. These Access Levels could then be assigned to Users in User Code Programming( Step 7: Default = 00 = User have access to all doors). 4. Optional: Create up to 32 Access Schedules in sections [2401] to [2432]. Assign different time periods for access next to each schedule. These schedules could then be assigned to Users in the User Code Programming( Step 7: Default = 00 = User have access at all times). 5. Optional: Enter Holidays in sections [2710] to [2712], which will disallow access o those days unless (H) is selected next to the user s Level. 6. Program the User Codes( Pg.12 User manual or above in this guide steps 7 to 9). NB! The Access module is set to Partition 1 on default. To change this enter Module Programming (section [4003] Pg.3 in this guide) and change this in section [001]. Pg.5

High Security and Access System EVO48 V2.1 EVO192 V2.1

High Security and Access System EVO48 V2.1 EVO192 V2.1 High Security and Access System EVO48 V2.1 EVO192 V2.1 Programming Guide Includes LCD Keypad Programming We hope this product performs to your complete satisfaction. Should you have any questions or comments,

More information

Digiplex EVO High Security and Access System What s New EVO192 V2.7

Digiplex EVO High Security and Access System What s New EVO192 V2.7 Digiplex EVO High Security and Access System What s New EVO192 V2.7 Overview New zone programming and additional zone/system/anti-mask options EN 50131 compliancy Now supports automatic label broadcast

More information

EVOHD. Programming Guide. Version

EVOHD. Programming Guide. Version EVOHD Programming Guide Version 1.11 www.paradox.com Warranty For complete warranty information on this product please refer to the Limited Warranty Statement found on our Web site: www.paradox.com. Your

More information

Modules Programming Guide. paradox.com

Modules Programming Guide. paradox.com Keypad Modules Annunciator Module Motion Detector Modules Zone Expansion Modules Access Control Module Voice Assisted Modules Accessory Modules Integration Module Internet Module Modules Programming Guide

More information

Modules Programming Guide

Modules Programming Guide Modules Programming Guide Programming Methods The modules can be programmed using the following methods: 1) Through the WinLoad Security Management Software. The modules can be programmed at 19,200 baud

More information

MG/SP Series (V4.9/V5.1) What s New

MG/SP Series (V4.9/V5.1) What s New MG/SP Series (V4.9/V5.1) What s New Firmware: SP4000 and SP5 version 5.1 SP5500, SP000, SP7000, and MG5050 version 4.9 (SP5500 pictured) Overview: New Programming Sections New Events New Trouble Display

More information

(To modify t he installer code, ref er to section [ 1000], Installer Code Programming on page 21) 1234 or

(To modify t he installer code, ref er to section [ 1000], Installer Code Programming on page 21) 1234 or HIGH SECURITY AND ACCESS CONTROL SYSTEM (DGP-NE96) PROGRAMMING GUIDE Software Version V1.0 DG P-NE 96 DEFAULT INSTALLER CODE 000000 (To modify t he installer code, ref er to section [ 1000], Installer

More information

SOFTWARE VERSION 3.20

SOFTWARE VERSION 3.20 48EPEP-00 SOFTWARE VERSION 3.20 HEXA PROGRAMMING: Addresses 000 to 043 and 300 to 527 are programmed using the Hexa Programming method. In this mode, you can enter any hexa-digit from 0-F where keys [1]

More information

SOFTWARE VERSION 3.10

SOFTWARE VERSION 3.10 728PEP-03 SOFTWARE VERSION 3.10 HEXA PROGRAMMING: Addresses 000 to 043 and 300 to 527 are programmed using the Hexa Programming method. In this mode, you can enter any hexa-digit from 0-F where keys [1]

More information

1HWZRU;1;( Table of Contents. General Description...2. Ordering Information...2. Feature Definitions...3. Programming the LED Keypads...

1HWZRU;1;( Table of Contents. General Description...2. Ordering Information...2. Feature Definitions...3. Programming the LED Keypads... HWZRU;;( Control/Communicator Installation Manual Table of Contents General Description... Ordering Information... Feature Definitions... Programming the LED Keypads... Programming the NX-E...9 Types of

More information

RANGER 9000E DOWNLOADABLE CONTROL COMMUNICATOR INSTALLATION MANUAL

RANGER 9000E DOWNLOADABLE CONTROL COMMUNICATOR INSTALLATION MANUAL RANGER 9000E DOWNLOADABLE CONTROL COMMUNICATOR INSTALLATION MANUAL TABLE OF CONTENTS GENERAL DESCRIPTION... 2 STANDARD AND OPTIONAL PARTS LIST... 2 FEATURE DEFINITIONS... 3 TERMINAL DRAWING AND SPECIAL

More information

Property of Monitronics Inc

Property of Monitronics Inc Enter Program (Locations 034 to 410) 1. Press Program Button on main panel 2. At keypad press 9 + Program Code (9 8 7 6 5) or 1. Power down with black switch on bottom left of panel 2. Power up while holding

More information

SOFTWARE VERSION 3.10

SOFTWARE VERSION 3.10 738PEP-03 SOFTWARE VERSION 3.10 HEXA PROGRAMMING: Addresses 000 to 043 and 300 to 527 are programmed using the Hexa Programming method. In this mode, you can enter any hexa-digit from 0-F where keys [1]

More information

VISTA-128BP/VISTA-250BP Programming Form

VISTA-128BP/VISTA-250BP Programming Form VISTA-128BP/VISTA-250BP Programming Form Some fields are programmed for each partition (shown as shaded fields). If you are programming a multiple-partition system, see the Partition-Specific Fields section

More information

Property of Monitronics Inc

Property of Monitronics Inc Enter Program 1. Master Code + 8 + 0 + 0 (Display should show 20) or Power down then back up and press * and # within 1 minute (If exiting programming you can re-enter within 1 minute by pressing * and

More information

2 IDS LCD Keypad User Manual C Issued March 2009

2 IDS LCD Keypad User Manual C Issued March 2009 2 3 4 Contents 1. Introduction to the IDS LCD Digital Keypad...8 2. Arming the Control Panel...8 2.1 Away Arming...8 2.1.1 How to Away Arm...8 2.1.2 Quick Away Arm Shortcut Key...8 2.2 Stay Arming...9

More information

4140XMPT2 PROGRAMMING FORM

4140XMPT2 PROGRAMMING FORM 414XMPT2 PROGRAMMING FORM Some fields are programmed for each partition (shown as shaded fields). See the PARTITION-SPECIFIC section for programming these fields. Standard default (*97) values are shown

More information

Programming Worksheets

Programming Worksheets Now classified in accordance with ANSI/SIA CP-01-2000 (SIA-FAR) Programming Worksheets PC1555 CP-01 PC1555 CP-01 version 3.2 DLS2002 and higher Page references below are to the accompanying Installation

More information

Safecom Solution-16 Quick Reference Guide ISSUE 1.10

Safecom Solution-16 Quick Reference Guide ISSUE 1.10 Safecom Solution-16 Quick Reference Guide ISSUE 1.10 2 Solution-16 Safecom Quick Reference Guide Safecom Solution-16 Quick Reference Guide Copyright 1998 by, SYDNEY, AUSTRALIA Document Part Number MA8016Q

More information

IDS X-Series User Manual E Issued June 2013

IDS X-Series User Manual E Issued June 2013 1 2 Contents 1. Introduction to the IDS X-Series Panels... 6 2. Before Operating Your Alarm System... 6 3. Understanding the Keypad LEDs... 7 3.1 Viewing Data on an LED Keypad... 11 3.2 Entering Data on

More information

First Alert FA160C/162C Installer Notes M. Leuck

First Alert FA160C/162C Installer Notes M. Leuck First Alert FA160C/162C Installer Notes M. Leuck 1. Programming can only be done by 6139 Alpha keypads, standard 6128 keypad cannot be used to program zones 2. Enter programming: Master Code + 8 + 0 +

More information

Series. NX-8-EUR Control Panel. Installation manual

Series. NX-8-EUR Control Panel. Installation manual g GE Security NetworX TM Series NX-8-EUR Control Panel Installation manual NX-8-EUR Installation manual Page 2 23/12/04 CONTENTS CONTENTS...3 GENERAL INFORMATION...5 ORDERING INFORMATION...5 FEATURE DEFINITIONS...6

More information

Property of Monitronics Inc

Property of Monitronics Inc Enter Program 1. 4112 + 8 + 0 + 0 (Display should show 20) or Power down then back up and press * and # within 1 minute (If exiting programming you can re-enter within 1 minute by pressing * and #) Exit

More information

TM50 Touch Intuitive Touchscreen

TM50 Touch Intuitive Touchscreen TM50 Touch Intuitive Touchscreen Description With its bright color display, intuitive icons, and menu-driven interface, the TM50 Touch Intuitive Touchscreen reflects Paradox s commitment to user-centric

More information

Contents. 4. Disarming the Control Panel How to Disarm with a User Code How to Disarm using a Key-Switch or Remote...

Contents. 4. Disarming the Control Panel How to Disarm with a User Code How to Disarm using a Key-Switch or Remote... Contents 1. Introduction to the Watchguard WGAP864 LCD Digital Keypad... 6 2. Viewing Violated Zones... 6 3. Arming the Control Panel... 7 3.1 Away Arming... 7 3.1.1 How to Away Arm... 7 3.1.2 Quick Away

More information

*00 INSTALLER CODE Enter 4 digits, 0-9 [4140] *28 POWER UP IN PREVIOUS STATE [1=yes] 0=no; "1" for UL.

*00 INSTALLER CODE Enter 4 digits, 0-9 [4140] *28 POWER UP IN PREVIOUS STATE [1=yes] 0=no; 1 for UL. 4140XMPT2 PROGRAMMING FORM Some fields are programmed for each partition (shown as shaded fields). See the PARTITION-SPECIFIC section for programming these fields. Standard default (*97) values are shown

More information

Control Panel ICP-SOL2-P/ICP-SOL3-P. en Quick Reference Guide

Control Panel ICP-SOL2-P/ICP-SOL3-P. en Quick Reference Guide Control Panel ICP-SOL2-P/ICP-SOL3-P en Quick Reference Guide Control Panel Table of Contents en 3 Table of contents 1 Introduction 6 2 Programming 7 2.1 ICON LCD Codepad Programming 7 2.2 TEXT LCD Codepad

More information

Installer Notes 4110DL/XM, Vista 10, Vista-20, Via-30PSE

Installer Notes 4110DL/XM, Vista 10, Vista-20, Via-30PSE Installer Notes 4110DL/XM, Vista 10, Vista-20, Via-30PSE 1. Programming can only be done with a 6139 Alpha Keypad on Vista-10/20/30PSE models. 2. When entering programming for the first time during Installations

More information

Commercial Burglary Partitioned Security System With Scheduling. Programming Guide. K5894PRV4 6/04 Rev A

Commercial Burglary Partitioned Security System With Scheduling. Programming Guide. K5894PRV4 6/04 Rev A ADEMCO VISTA SERIES VISTA-128BP/VISTA-250BP/ VISTA-128SIA Commercial Burglary Partitioned Security System With Scheduling Programming Guide K5894PRV4 6/04 Rev A Table of Contents Recommended Programming

More information

Ademco/Protection One 250P1-1 Programming Form

Ademco/Protection One 250P1-1 Programming Form Ademco/Protection One 250P1-1 Programming Form Local programming requires the use of a 2-line Alpha keypad connected to the keypad terminals on the control. Field Function Programmed Values [ ] = Default

More information

VISTA-50P VISTA-50PUL

VISTA-50P VISTA-50PUL VISTA-50P VISTA-50PUL PARTITIONED SECURITY SYSTEM with SCHEDULING Quick Start Step-by-Step Programming Procedure Single And Multiple Partition Programming Forms System Worksheets VISTA50P-PR 8/95 (See

More information

DAS 250L CONTROL COMMUNICATOR INSTALLATION MANUAL

DAS 250L CONTROL COMMUNICATOR INSTALLATION MANUAL DAS 250L CONTROL COMMUNICATOR INSTALLATION MANUAL TABLE OF CONTENTS 1. GENERAL DESCRIPTION... P.2 2. STANDARD AND OPTIONAL PARTS LIST..... P.2 3. FEATURE DEFINITIONS... P.3 4. TERMINAL DRAWING AND SPECIAL

More information

Important Notice. Customer Information. 2 WisDom User Manual

Important Notice. Customer Information. 2 WisDom User Manual User Manual Important Notice This manual is delivered subject to the following conditions and restrictions: This manual contains proprietary information belonging to RISCO Group. The information is supplied

More information

Ademco Vista-20SE/First Alert FA-162C Program Sheet

Ademco Vista-20SE/First Alert FA-162C Program Sheet Enter Program 1. 4112 + 8 + 0 + 0 (Display should show 20) or Power down then back up and press * and # within 1 minute (If exiting programming you can re-enter within 1 minute by pressing * and #) Exit

More information

I-NX8V2-IM Rev F Dec NetworX Series NX-8V2 Control Panel Installation and Setup

I-NX8V2-IM Rev F Dec NetworX Series NX-8V2 Control Panel Installation and Setup I-NXV-IM Rev F Dec 00 NetworX Series NX-V Control Panel Installation and Setup Copyright Disclaimer Trademarks and patents Copyright 00, GE Security Inc. All rights reserved. This document may not be copied

More information

MCM Electronics MCM Electronics MCM Electronics. The Icon Series. Installation and Programming Information. Icon 8 Version 5.0

MCM Electronics MCM Electronics MCM Electronics. The Icon Series. Installation and Programming Information. Icon 8 Version 5.0 MCM Electronics MCM Electronics MCM Electronics The Icon Series Installation and Programming Information Icon 8 Version 5.0 TABLE OF CONTENTS 1. 2. 3. Panel Hardware Page 2 Physical Layout. Inputs. Outputs.

More information

IDS. Users Guide to Keypad Functions S E C U R I T Y MANUAL NO D ISSUED NOVEMBER 2002 VERSION 2.

IDS.  Users Guide to Keypad Functions S E C U R I T Y MANUAL NO D ISSUED NOVEMBER 2002 VERSION 2. INHEP DIGITAL IDS S E C U R I T Y Users Guide to Keypad Functions MANUAL NO. 700-146-01D ISSUED NOVEMBER 2002 VERSION 2.17 Summary of Operation A rm/ disarm [#] + [USER CODE] Quick Quick Quick Away Arm

More information

Telephone and Reporting Setup in ElkRP

Telephone and Reporting Setup in ElkRP Telephone and Reporting Setup in ElkRP 1. To add a telephone, right click on Telephones under Folder items on the left side of the screen. Then select New Telephone. 2. On the New Telephone IDs screen,

More information

Commercial Fire and Burglary Partitioned Security System with Scheduling. Programming Guide. K0376PRV5 2/11 Rev. A

Commercial Fire and Burglary Partitioned Security System with Scheduling. Programming Guide. K0376PRV5 2/11 Rev. A VISTA-128FBP VISTA-250FBP Commercial Fire and Burglary Partitioned Security System with Scheduling Programming Guide K0376PRV5 2/11 Rev. A Table of Contents Programming Field Settings for UL864 Compliance

More information

IDS1200 INSTALLER MANUAL. Summary of Operation 2 IDS1200 INSTALLER MANUAL - NO B ISSUED AUGUST 2002 VER 1.18

IDS1200 INSTALLER MANUAL. Summary of Operation 2 IDS1200 INSTALLER MANUAL - NO B ISSUED AUGUST 2002 VER 1.18 IDS12 INSTALLER MANUAL Summary of Operation A rm/ disarm [#] + [USER CODE] Quick Away Arm Quick Stay Arm Quick Stay Arm & Go H old down [ 1] for 1 second H old down [ 5] for 1 second H old down [ 6] for

More information

Property of Monitronics Inc

Property of Monitronics Inc Enter Program Master Code + 8 + 0 + 0 (Display should show 20) or Power down then back up and press * and # within 1 minute (If exiting programming you can re-enter within 1 minute by pressing * and #)

More information

DAYLIGHT SAVINGS TIME START/END MONTH [ 0 ]0 = Disabled; 1 = Enabled. 1 Start End

DAYLIGHT SAVINGS TIME START/END MONTH [ 0 ]0 = Disabled; 1 = Enabled. 1 Start End RcvrAcct#: Test Date: May, ::PM SYSTEM ENTRY DELAY# [ ] = None, = secs, = secs, = secs, = secs, = secs, = mins [UL installations: The Entry Delay must be set for a maximum of seconds] ENTRY DELAY# [ ]

More information

VISTA-20BAY PROGRAMMING GUIDE SECURITY SYSTEM SINCE 1946

VISTA-20BAY PROGRAMMING GUIDE SECURITY SYSTEM SINCE 1946 VISTA-20BAY SECURITY SYSTEM PROGRAMMING GUIDE SINCE 1946 N7526-4PR 03/98 File No: S1632 Local programming requires the use of a 2-line alpha keypad connected to the keypad terminals on the control. Field

More information

SECURITY MODULE CG3 User Manual

SECURITY MODULE CG3 User Manual SECURITY MODULE CG3 User Manual Security system can be managed with Paradox K636, K10 LED, K32 LED and Protegus SK130 LED Control by the keypad Paradox 1. Full arming the security system (when the security

More information

AMAX panel. AMAX panel 2100 AMAX panel 3000 AMAX panel 3000 BE AMAX panel en Operation Manual

AMAX panel. AMAX panel 2100 AMAX panel 3000 AMAX panel 3000 BE AMAX panel en Operation Manual AMAX panel AMAX panel 2100 AMAX panel 3000 AMAX panel 3000 BE AMAX panel 4000 en Operation Manual AMAX panel Table of Contents en 3 Table of contents 1 Safety 5 2 Short information 6 2.1 Introduction

More information

LCD User Station User Manual

LCD User Station User Manual LCD User Station User Manual PUBLICATION INFORMATION 504A R Final Release CONTENTS 1.0 INTRODUCTION... 4 1.1 Legend... 2.2 Terminology... 2.0 OPERATION... 8 2.1 Indicator Lights... 2.2 Visual Display...

More information

FSK TX CELLULAR PLUS. Installation and Programming Guide. Tel:

FSK TX CELLULAR PLUS. Installation and Programming Guide. Tel: FSK TX CELLULAR PLUS Installation and Programming Guide Tel: 0861 105 962 www.fsk.co.za INTRODUCTION The FSK TX Cellular Plus (TXC+) is a highly featured GSM based unit which is used for the transmission

More information

CUSTOMER INFORMATION

CUSTOMER INFORMATION CUSTOMER INFORMATION COMPANY NAME & ADDRESS: CONTACT: PHONE: FAX: NOTES: DATE ENTERED: DATE MODIFIED: 11/2/2010 12:41 P 11/2/2010 12:47 P USER_DEFINED_FIELD1: USER_DEFINED_FIELD2: Vista15PSIA-3 PROGRAMMING

More information

Created by: Alarm System Store Quick Start Guide. for Interlogix NetworX NX4, NX6 & NX8

Created by: Alarm System Store   Quick Start Guide. for Interlogix NetworX NX4, NX6 & NX8 Quick Start Guide for Interlogix NetworX NX4, NX6 & NX8 Programming Code = 9713 Master User Code=1234 Program Mode= *8 + 9713 To exit programming hit the Exit key until you reach the home screen If this

More information

PCS200 Communicator Module V2.2

PCS200 Communicator Module V2.2 PCS200 Communicator Module V2.2 Reference and Installation Manual Warranty For complete warranty information, please visit www.paradox.com/terms. Your use of the Paradox product signifies your acceptance

More information

VISTA 12a / 48a TECHNICAL TRAINING. The Best in Security plus Everyday Convenience & Control

VISTA 12a / 48a TECHNICAL TRAINING. The Best in Security plus Everyday Convenience & Control VISTA 12a / 48a TECHNICAL TRAINING The Best in Security plus Everyday Convenience & Control Version #.007 7th June 2005 VISTA 12a / 48a Training Guide Index 1. Vista Family Features....... p. 3 2. Wiring

More information

3 6HFXULW\6\VWHP 3URJUDPPLQJ)RUP K4332 9/99 BYPASS NOT READY ARMED READY 4 MAX 5 TEST 6 BYPASS 7INSTANT 8 CODE 9CHIME READY ARMED

3 6HFXULW\6\VWHP 3URJUDPPLQJ)RUP K4332 9/99 BYPASS NOT READY ARMED READY 4 MAX 5 TEST 6 BYPASS 7INSTANT 8 CODE 9CHIME READY ARMED 3 6HFXULW\6\VWHP 3URJUDPPLQJ)RUP ARMED READY 1 OFF 2 AWAY 3 STAY 4 MAX 5 TEST 6 BYPASS 7INSTANT 8 CODE 9CHIME READY 0 # * NIGHT NO AC AWAY PHONE TEST BYPASS NOT READY ALARM STAY CHIME BAT FIRE CHECK INSTANT

More information

INPUTS: Are 10K end of line monitored, with a response time of 300 ms. Alarm triggers SIREN, STROBE and REPORTING (depending on setup)

INPUTS: Are 10K end of line monitored, with a response time of 300 ms. Alarm triggers SIREN, STROBE and REPORTING (depending on setup) INPUTS: All inputs: Inputs 1 to 24: Tamper: Panic: Fire: Keyswitch: 16-18VAC: Are 10K end of line monitored, with a response time of 300 ms. Alarm triggers SIREN, STROBE and REPORTING (depending on setup)

More information

Quick Start: 2. Connect AC power first and then the battery. 3. Configure the keypad (see page 44).

Quick Start: 2. Connect AC power first and then the battery. 3. Configure the keypad (see page 44). R R R HARDWIRE WIRELESS Quick Start:. Refer to the wiring diagram, connect siren, aux. power, pgm. output, remote bus, earth ground, zone and telephone wiring. NOTE: See Installation Instructions (WI99)..

More information

DSC programming for the Alexor and Impassa

DSC programming for the Alexor and Impassa DSC programming for the Alexor and Impassa THERE IS NO REASON TO BE IN ANY SECTION OF YOUR SYSTEM UNLESS IT IS ON THIS QUICK START GUIDE. If you do not see it here, please question if you should be doing

More information

Programming Default Tables

Programming Default Tables Lynx Plus Control Defaults Lynx Plus Series Installation and Setup Guide *20 Installer code 4112 4112 4112 4112 *21 Quick arm enable 1 1 1 1 *22 Keypad backlight timeout 0 0 0 0 *23 Forced bypass 0 0 0

More information

NetworX Series NX-8V2 Control Panel Installation and Startup

NetworX Series NX-8V2 Control Panel Installation and Startup NetworX Series NX-V Control Panel Installation and Startup 00 GE Security All rights reserved. These instructions do not purport to cover all details or variations in equipment nor to provide every possible

More information

&RPPHUFLDO)LUHDQG%XUJODU\ 3DUWLWLRQHG6HFXULW\6\VWHP ZLWK6FKHGXOLQJ

&RPPHUFLDO)LUHDQG%XUJODU\ 3DUWLWLRQHG6HFXULW\6\VWHP ZLWK6FKHGXOLQJ 9,67$)% &RPPHUFLDO)LUHDQG%XUJODU\ 3DUWLWLRQHG6HFXULW\6\VWHP ZLWK6FKHGXOLQJ 4XLFN6WDUW*XLGH FIRE FIRE * PULL V128FB-PRV1 10/98 2 Table Of Contents RECOMMENDED PROGRAMMING PROCEDURE... 4 PROGRAM FIELD CATEGORIES...

More information

ATLAS 8 PLUSTM USER GUIDE LED & LCD. Rins 160 Issue 2

ATLAS 8 PLUSTM USER GUIDE LED & LCD. Rins 160 Issue 2 ATLAS 8 PLUSTM USER GUIDE LED & LCD The equipment has been approved to CTR21for pan-european single terminal connection to the Public Switched Telephone Network (PSTN). However, due to differences between

More information

3DUWLWLRQHG6HFXULW\6\VWHPV ZLWK6FKHGXOLQJ

3DUWLWLRQHG6HFXULW\6\VWHPV ZLWK6FKHGXOLQJ )$&&$&% )LUHDQG%XUJODU\ 3DUWLWLRQHG6HFXULW\6\VWHPV ZLWK6FKHGXOLQJ **** **** ARMED READY A B C D FIRE FIRE First Alert OFF AWAY STAY 1 2 3 4 5 6 7 8 9 MAXIMUM TEST BYPASS INSTANT CODE CHIME READY * 0 #

More information

GEM-P9600 CONTROL PANEL/COMMUNICATOR

GEM-P9600 CONTROL PANEL/COMMUNICATOR R R R R PROGRAMMING INSTRUCTIONS HARDWIRE WIRELESS GEM-P9600 CONTROL PANEL/COMMUNICATOR GEMINI ARMED STATUS SYSTEM ARMED 0/0/00 0/0/97 :00AM NEXT/YES A 3 D E PRIOR/NO B 56 F AREA C 790G GEMINI SYSTEM ARMED

More information

PCS200 GPRS Communicator Module V1.0

PCS200 GPRS Communicator Module V1.0 PCS200 GPRS Communicator Module V1.0 Installation and User Manual Warranty For complete warranty information on this product please refer to the Limited Warranty Statement found on the website www.paradox.com/

More information

FOCUS 200 PLUS A CCC #: _ / / _ / ( _ ) _ - 35(/,0,1$5< -8/< Security Services CUSTOMER CONTROL UNIT TELEPHONE NUMBER:

FOCUS 200 PLUS A CCC #: _ / / _ / ( _ ) _ - 35(/,0,1$5< -8/< Security Services CUSTOMER CONTROL UNIT TELEPHONE NUMBER: CMP-DF2V1 7/01 Security Services SALES REPS: PLEASE FILL IN ALL WHITE AREAS. FOCUS 200 PLUS A CUSTOMER SYSTEM INVENTORY AND DATA ENTRY FORMS CCC #: _ / / _ / CUSTOMER CONTROL UNIT TELEPHONE NUMBER: ( _

More information

INSTALLATION MANUAL. Table of Contents. General Description Position Dip Switch Settings Enrolling the NX216-E Expander...

INSTALLATION MANUAL. Table of Contents. General Description Position Dip Switch Settings Enrolling the NX216-E Expander... INSTALLATION MANUAL Table of Contents Page General Description... -Position Dip Switch Settings... Enrolling the NX-E Expander... Wiring the NX-E... Terminal Description... Wiring Diagram... Default Zone

More information

Control Panel Solution 2000 / 3000

Control Panel Solution 2000 / 3000 Control Panel Solution 2000 / 3000 en Quick Reference Guide Control Panel Table of contents en 3 Table of contents 1 Introduction 6 2 Programming 7 2.1 Alphanumeric Codepad Menu Programming 7 2.2 ICON

More information

VISTA-20SEa. 3-Partition Security System. Programming Form. V20SEaPRV1 9/98

VISTA-20SEa. 3-Partition Security System. Programming Form.   V20SEaPRV1 9/98 VISTA-20SEa 3-Partition Security System New style cover to be used Programming Form V20SEaPRV1 9/98 Local programming requires the use of a 2-line Alpha keypad connected to Partition 1 keypad terminals

More information

Solution 16 plus. User Guide Security System

Solution 16 plus. User Guide Security System Solution 16 plus EN Security System Copyright Notice Unless otherwise indicated, this publication is the copyright of Bosch Security Systems Pty Ltd ( Bosch ). All rights are reserved.you may download

More information

D1260/D1260B. Owner's Manual. Keypad

D1260/D1260B. Owner's Manual. Keypad D1260/D1260B EN Owner's Manual Keypad D1260/D1260B Owner's Manual This system includes a telephone line seizure feature. The system may be programmed to communicate with a central monitoring station to

More information

ELECTRONIC ENGINEERING LTD. OLED Keypad. User s Guide. P/N: Doc Rev-A SW Ver /08/10

ELECTRONIC ENGINEERING LTD. OLED Keypad. User s Guide. P/N: Doc Rev-A SW Ver /08/10 ELECTRONIC ENGINEERING LTD. OLED Keypad User s Guide P/N: 7103670 Doc Rev-A SW Ver-0.65 05/08/10 Crow Limited Warranty Crow warrants this product to be free from defects in materials and workmanship under

More information

ATLAS 8 PLUSTM USER GUIDE LED & LCD. Intelligent Security & Fire Ltd Rins 160 Issue 6

ATLAS 8 PLUSTM USER GUIDE LED & LCD. Intelligent Security & Fire Ltd Rins 160 Issue 6 ATLAS 8 PLUSTM USER GUIDE LED & LCD 8! INSTALLER DETAI LS: 1 3 4 2 5 6 7 8 9 0 OR SET TELEPHO NE: The equipment has been approved to CTR21for pan-european single terminal connection to the Public Switched

More information

Installation Instructions

Installation Instructions NX-148E-RF LCD Touchpad w/receiver 466-2198 Rev. B May 2005 Product summary The NX-148E-RF Touchpad w/receiver combines touchpad and receiver capabilities into a single device for use with NetworX NX-4,

More information

Installation Quick Start Guide

Installation Quick Start Guide Installation Quick Start Guide For detailed information please refer to the full Agility 3 Installer Manual provided on our website: www.riscogroup.com Table of Contents 1. INSTALL THE MAIN UNIT... 3 2.

More information

GSM AD05 Slave GSM Auto Dialer- Instruction Manual

GSM AD05 Slave GSM Auto Dialer- Instruction Manual GSM AD05 Slave GSM Auto Dialer- Instruction Manual Please read these instructions before you start the installation Features LCD display Programmable 9 x 32 digit phone numbers for each trigger. 10 second

More information

Colour Graphic Terminal User Manual. Rev 3.1

Colour Graphic Terminal User Manual. Rev 3.1 Integriti. Colour Graphic Terminal User Manual. 1 Colour Graphic Terminal User Manual. Rev 3.1 2013-2014. Inner Range Pty. Ltd. Part Number: 636000U 2 Integriti. Revision 3.1 June 2014. SYSTEM DETAILS

More information

Challenger Version 8 Programming Macro Logic.

Challenger Version 8 Programming Macro Logic. Challenger Version 8 Programming Macro Logic. This document provides details of the requirements for planning and programming Macro Logic in a Version 8 Challenger System for use in Alarm Control and/or

More information

* * ARM MONITOR EXCLUDE MEMORY. HomeSafe Security Panel 5400/16CB. Programming Manual C-Bus Supplement

* * ARM MONITOR EXCLUDE MEMORY. HomeSafe Security Panel 5400/16CB. Programming Manual C-Bus Supplement * * ARM 1 2 3 MONITOR 4 5 6 EXCLUDE 7 8 9 MEMORY P 0 E HomeSafe Security Panel 5400/16CB Programming Manual C-Bus Supplement Contents 1.0 Product Range...3 2.0 Features...3 2.1 Control Panel Features...3

More information

Integriti User Manual. Elite / EliteX LCD Terminal Keypads

Integriti User Manual. Elite / EliteX LCD Terminal Keypads Integriti User Manual Elite / EliteX LCD Terminal Keypads INNER RANGE recommends that all INTEGRITI systems are installed & maintained by FACTORY CERTIFIED TECHNICIANS. For a list of Accredited Dealers

More information

SUPERPLEX. User s Manual. High performance, simplified wireless home security controller. Products that work. Software Release: V2.

SUPERPLEX. User s Manual. High performance, simplified wireless home security controller. Products that work. Software Release: V2. SUPERPLEX User s Manual Products that work Software Release: V2.5 KE-MOBILEHQ-12- High performance, simplified wireless home security controller Thank you for purchasing this Kingdom Electronics product.

More information

FA168CPS / FA168CPSSIA FA148CP / FA148CPSIA

FA168CPS / FA168CPSSIA FA148CP / FA148CPSIA MAX INSTANT READY R BYPASS AWAY ARMED READY 1 OFF MAX INSTANT READY R 2 AWAY 3 STAY BYPASS FA168CPS / FA168CPSSIA FA148CP / FA148CPSIA Security Systems Programming Guide ARMED READY A B C D 7 4 1 OFF FA260

More information

SUPERPLEX 2. User s Manual. High performance, simplified wireless home security controller. Products that work. Software Release: V2.

SUPERPLEX 2. User s Manual. High performance, simplified wireless home security controller. Products that work. Software Release: V2. SUPERPLEX 2 User s Manual Products that work Software Release: V2.0 KE-MOBILEHQ-12- High performance, simplified wireless home security controller Thank you for purchasing this Kingdom Electronics product.

More information

Emergency Dialer DIAL-ALERT MODEL: AD-433S.

Emergency Dialer DIAL-ALERT MODEL: AD-433S. www.skylinkhome.com Emergency Dialer TM DIAL-ALERT MODEL: AD-433S 101A118 FEB, 2000 SKYLINK TECHNOLOGIES INC., 2213 Dunwin Drive, Mississauga, Ontario L5L 1X1 CANADA Tel : (905) 608-9223 (800) 304-1187

More information

_A_en_LED63VG VOICE GUIDE KEYPAD LED63VG

_A_en_LED63VG VOICE GUIDE KEYPAD LED63VG 18020502_A_en_LED6VG VOICE GUIDE KEYPAD LED6VG Disclaimer While every effort has been made to ensure that the information in this manual is accurate and complete, no liability can be accepted for any errors

More information

Keypad LCD (software version 3.10) CA-10 plus

Keypad LCD (software version 3.10) CA-10 plus PROGRAMMING AND INSTALLATION MANUAL Keypad LCD (software version 3.10) CA-10 plus GDAŃSK ca10plci_e 09/03 WARNING Due to safety reasons, alarm system should be installed by qualified personnel only. Because

More information

Wireless Alarm System User Guide

Wireless Alarm System User Guide Wireless Alarm System User Guide Alarm Panel Time 10:09 c RINS1902 Document SAP: 102015108-03 Contents ProControl+ 4 Setting Devices 5 The Wireless Panel Keypad 5 Wireless Keyfobs 5 Locking the Keyfob

More information

Dialler HA2000 RTC. Installation & Operating Manual

Dialler HA2000 RTC. Installation & Operating Manual Dialler HA2000 RTC Installation & Operating Manual The easiest way to get to know the system and get it up and running quickly is to get all the devices and accessories programmed on a tabletop before

More information

USER MANUAL TP TP TP Expandable serial alarm systems. Release: 3.1

USER MANUAL TP TP TP Expandable serial alarm systems. Release: 3.1 USER MANUAL Expandable serial alarm systems TP0- - TP8-88 - TP0-0 Release:. Models: TP0- - TP8-88 - TP0-0 Programming SW version:.9 Update: 0/06 Language: English CONFORMITY The present equipment is in

More information

NX-148 LCD KEYPAD INSTALLATION MANUAL

NX-148 LCD KEYPAD INSTALLATION MANUAL NX-148 LCD KEYPAD INSTALLATION MANUAL Table of Contents Entering the Program Mode... 2 Selecting the Module to Program... 2 Programming a Location... 2 NX-148 Library... 3 Loading Factory Defaults... 3

More information

EUROPLEX TECHNOLOGIES. WARNING. Copyright. Disclaimer

EUROPLEX TECHNOLOGIES. WARNING. Copyright. Disclaimer EUROPLEX TECHNOLOGIES. Company Web Site address: www.europlex.com Europlex Technologies [Ireland] Ltd. Clonshaugh Industrial Estate, Clonshaugh, Dublin 17, Ireland. Tel: +353-1 - 8485111 Fax: +353-1 -

More information

Agility Installation Quick Start Guide 1

Agility Installation Quick Start Guide 1 Agility Installation Quick Start Guide Thank you for purchasing the Agility Flexible Wireless Solution from RISCO Group. This quick start guide will describe the main steps for installing and programming

More information

THE OPERATOR INTRODUCTION 2 ACCESSING YOUR SYSTEM 2 FUNCTIONS OF THE "OPERATOR" 3 PROGRAMMING/CHANGING ACCESS CODES 12 ACTIVATING EMERGENCY ALARMS 13

THE OPERATOR INTRODUCTION 2 ACCESSING YOUR SYSTEM 2 FUNCTIONS OF THE OPERATOR 3 PROGRAMMING/CHANGING ACCESS CODES 12 ACTIVATING EMERGENCY ALARMS 13 THE OPERATOR INTRODUCTION 2 ACCESSING YOUR SYSTEM 2 FUNCTIONS OF THE "OPERATOR" 3 SECTION I. CHECKING SYSTEM STATUS 3 SECTION II. USING THE MENU 4 SECTION III. ARMING YOUR SECURITY SYSTEM 5 SECTION IV.

More information

ADEMCO VISTA-48A Security Systems

ADEMCO VISTA-48A Security Systems ADEMCO VISTA-48A Security Systems Programming Guide K0749-1ENPRV1 10/05 Rev. A APPLICABILITY: VISTA-48A controls with microprocessor version 2.2 or higher. TO START PROGRAM MODE, use method A or B (must

More information

Includes: 413oxM 513oxM 414oxM 414oxMP

Includes: 413oxM 513oxM 414oxM 414oxMP Includes: 413oxM 513oxM 414oxM 414oxMP Chris Martin Jan, 1992 Ademco Technical Support EXPLANATION: Contact ID Reporting provides faster transmission speed and very specific event code reporting, resulting

More information

DAS LCD ALPHA NUMERIC CODEPAD

DAS LCD ALPHA NUMERIC CODEPAD DAS LCD ALPHA NUMERIC CODEPAD Table of Contents 1. LCD Codepad Diagram... 2 2. Introduction... 3 3. Understanding Your LCD Codepad... 4-7 4. Changing User Codes... 8-9 5. Special Function Keys..... 10

More information

PROGRAMMING AND INSTALLATION MANUAL

PROGRAMMING AND INSTALLATION MANUAL PROGRAMMING AND INSTALLATION MANUAL Keypad LCD-S (software version 3.10) CA-10 plus GDAŃSK ca10plci_s_e 09/03 WARNING Due to safety reasons, alarm system should be installed by qualified personnel only.

More information

USER MANUAL. Alarm Control Panels. SATEL sp. z o.o. ul. Budowlanych Gdańsk POLAND tel Firmware version 1.

USER MANUAL. Alarm Control Panels. SATEL sp. z o.o. ul. Budowlanych Gdańsk POLAND tel Firmware version 1. Alarm Control Panels Firmware version 1.15 USER MANUAL integra_u_en 04/16 SATEL sp. z o.o. ul. Budowlanych 66 80-298 Gdańsk POLAND tel. + 48 58 320 94 00 www.satel.eu WARNING Before you start using the

More information

Keypad LCD-L (software version 3.10) CA-10 plus

Keypad LCD-L (software version 3.10) CA-10 plus PROGRAMMING AND INSTALLATION MANUAL Keypad LCD-L (software version 3.10) CA-10 plus GDAŃSK ca10plci_l_e 09/03 WARNING Due to safety reasons, alarm system should be installed by qualified personnel only.

More information

Developer s Guide. PC54O1 Serial Interface Module Version 1.0

Developer s Guide. PC54O1 Serial Interface Module Version 1.0 Developer s Guide PC54O1 Serial Interface Module Version 1.0 IMPORTANT This manual contains information on limitations regarding product use and function and information on the limitations as to liability

More information

NetworX Series. NX-507E RELAY EXPANDER NX-508E OUTPUT EXPANDER Installation and Startup

NetworX Series. NX-507E RELAY EXPANDER NX-508E OUTPUT EXPANDER Installation and Startup NetworX Series NX-0E RELAY EXPANDER NX-0E OUTPUT EXPANDER Installation and Startup NX-0E / NX-0E AUXILIARY MODULES TABLE OF CONTENTS I. GENERAL DESCRIPTION... II. WIRING INFORMATION... III. NX-0E TERMINAL

More information

Control Panels D9412GV4/D7412GV4. en Owner's Manual

Control Panels D9412GV4/D7412GV4. en Owner's Manual Control Panels D9412GV4/D7412GV4 en Owner's Manual Control Panels Table of Contents en 3 Table of contents 1 Introduction 8 1.1 About documentation 9 2 Keypads overview 11 2.1 Identify your keypad style

More information

CP150B Vandal & Weather Resistant Keypad Security Systems

CP150B Vandal & Weather Resistant Keypad Security Systems Vandal & Weather Resistant Keypad Security Systems EN Security System CP150B - Vandal & Weather Resistant Keypad The CP150B keypad provides alarm and or access control functionality when used on selected

More information