BACnet Gateway V0CTRL86P Lennox VRF, Mini-VRF and Mini-Split
|
|
- Erika Hicks
- 5 years ago
- Views:
Transcription
1 Installation and Application Guide 2017 Lennox Industries Inc. Dallas, Texas, USA BACnet Gateway V0CTRL86P Lennox VRF, Mini-VRF and Mini-Split CNTRLS /2017
2 THIS MANUAL MUST BE LEFT WITH THE WNER FR FUTURE REFERENCE Equipment List Package 1 of 1 consists of: 1 - BACnet gateway 1 - Instruction and Application Guide General The Lennox VRF, Mini-VRF and Mini-Split BACnet Gateway allows connection of those systems to a building management system (BMS) using BACnet protocols. Contents Equipment List General Network Setting Security Specifi cations System Connections BACnet bject Points List Indoor Unit Instance Number Description Indoor Unit Points utdoor Unit Instance Number Description utdoor Unit Points Appendix A. BACnet Protocol bserved Appendix B. Indoor Unit Detailed Points Appendix C. utdoor Unit Detailed Points WARNING Improper installation, adjustment, alteration, service or maintenance can cause property damage, personal injury or loss of life. Installation and service must be performed by a licensed professional HVAC installer or equivalent, service agency, or the gas supplier. WARNING Do not operate device with wet hands. CAUTIN Before attempting to perform any service or maintenance, turn the electrical power to unit FF at disconnect switch. CAUTIN Do not install device in areas where heavy oil, vapor, or gases containing sulfur may exist or the controller may be damaged. CAUTIN Clean device using a clean, damp cloth. Do not spray cleanser on or around device. IMPRTANT These instructions are intended as a general guide and do not supersede local codes in any way. Consult authorities having jurisdiction before installation. Read all of the information in this manual before operating this equipment. Network Setting There is an Ethernet interface in the device (Eth0). The factory-set device address is Security Default Admin User Name: admin Default Admin Password: Specifications Function Input Supply Power BACnet Connection I/ perating Temperature Range perating Humidity Range (Rh) Dimensions Description 24VAC BACnet/IP 4 port 485 interface 32 F ~ 122 F (0 C ~ 50 C) 25% ~ 90% 10-1/2 in. X 10 in. X 2-3/8 in. (26 cm X 25 cm X 6 cm) NTE - utdoor unit control & monitoring points are not available for Mini-Split systems. -1P Mini-VRF systems require the Mini-VRF Control Interface V0CTRL00P-1. 2
3 System Connections The BACnet instance number is a four-digit number that identifi es the BACnet gateway bus (port), the type of unit (indoor unit or outdoor unit) and the unit s address. Device ID = XXXX X X X X BACnet Bus (Port) Number Unit Type Unit Address 0 Indoor Unit (Indoor Unit 0-63) (0-3) 1 utdoor Unit (utdoor Unit 0-31) Example indicates BACnet device number 0, indoor unit type, indoor unit number 01. Ethernet Connection Bus 0 Bus 1 Bus 2 Bus 3 Figure 1. VRF BACnet Gateway Connection Points 3
4 XYE Indoor Unit VRF Heat Pump System BACnet Gateway K1K2E utdoor Unit XYE Indoor Unit BACnet/IP Network K1K2E utdoor Unit VRF Heat Pump System BMS NTE - Maximum 96 outdoor units per device. Up to 24 DUs (K1K2E connection required) per bus. (VRF & Mini-VRF Systems only) Maximum 256 indoor units per device. Up to 64 IDUs per bus. (All Systems) NTE - Field-supplied communication wiring - 18 GA., stranded, 3-conductor, shielded control wire (polarity sensitive). All shields of shielded cable connect to GRUND terminal, not to E. NTE - VRF Heat Pump wiring configuration shown. XYE wiring configuration is same for VRF Heat Pump and VRF Heat Recovery systems. No monitoring points are available for MS Boxes. NTE - Each VRF Refrigerant system is limited to 63 IDUs. Figure 2. VRF System Indoor and utdoor Unit Monitoring 4
5 XYE Indoor Unit BACnet Gateway VRF Heat Pump System XYE VRF Heat Pump System XYE XYE VRF Heat Pump System BACnet/IP Network VRF Heat Pump System BMS NTE - Maximum 96 outdoor units per device. Up to 24 DUs (K1K2E connection required) per bus. (VRF & Mini-VRF Systems only) Maximum 256 indoor units per device. Up to 64 IDUs per bus. (All Systems) NTE - Field-supplied communication wiring - 18 GA., stranded, 3-conductor, shielded control wire (polarity sensitive). All shields of shielded cable connect to GRUND terminal, not to E. NTE - VRF Heat Pump wiring configuration shown. XYE wiring configuration is same for VRF Heat Pump and VRF Heat Recovery systems. No monitoring points are available for MS Boxes. NTE - Each VRF Refrigerant system is limited to 63 IDUs. Figure 3. VRF System Indoor Unit nly Monitoring 5
6 BACnet Gateway BACnet/IP Network BMS XYE Indoor Unit VRF Heat Recovery System K1K2E utdoor Unit XYE Indoor Unit K1K2E utdoor Unit VRF Heat Recovery System NTE - Maximum 96 outdoor units per device. Up to 24 DUs (K1K2E connection required) per bus. (VRF & Mini-VRF Systems only) Maximum 256 indoor units per device. Up to 64 IDUs per bus. (All Systems) NTE - Field-supplied communication wiring - 18 GA., stranded, 3-conductor, shielded control wire (polarity sensitive). All shields of shielded cable connect to GRUND terminal, not to E. NTE - VRF Heat Recovery wiring configuration shown. XYE wiring configuration is same for VRF Heat Pump and VRF Heat Recovery systems. No monitoring points are available for MS Boxes. NTE - Each VRF Refrigerant system is limited to 63 IDUs. Figure 4. VRF Heat Recovery System Indoor and utdoor Unit Monitoring 6
7 BACnet Gateway BACnet/IP Network XYE Indoor Unit -1P Mini-VRF System XYE Indoor Unit -1P Mini-VRF System XYE Indoor Unit XYE Indoor Unit -1P Mini-VRF System -1P Mini-VRF System NTE - Maximum 96 outdoor units per device. Up to 24 DUs (K1K2E connection required) per bus. (VRF & Mini-VRF Systems only) Maximum 256 indoor units per device. Up to 64 IDUs per bus. (All Systems) NTE - Field-supplied communication wiring - 18 GA., stranded, 3-conductor, shielded control wire (polarity sensitive). All shields of shielded cable connect to GRUND terminal, not to E. NTE - utdoor unit control & monitoring points for -1P Mini-VRF systems require the Mini-VRF Control Interface V0CTRL00P-1. Figure 5. -1P or -2P Mini-VRF System Indoor Unit nly Monitoring 7
8 BACnet Gateway BACnet/IP Network BMS XYE Indoor Unit -2P Mini-VRF System K1K2E utdoor Unit K1K2E utdoor Unit XYE Indoor Unit -2P Mini-VRF System NTE - Maximum 96 outdoor units per device. Up to 24 DUs (K1K2E connection required) per bus. (VRF & Mini-VRF Systems only) Maximum 256 indoor units per device. Up to 64 IDUs per bus. (All Systems) NTE - Field-supplied communication wiring - 18 GA., stranded, 3-conductor, shielded control wire (polarity sensitive). All shields of shielded cable connect to GRUND terminal, not to E. NTE - utdoor unit control & monitoring points for -1P Mini-VRF systems require the Mini-VRF Control Interface V0CTRL00P-1. Figure 6. -2P Mini-VRF System Indoor and utdoor Unit Monitoring 8
9 BACnet Gateway BACnet/IP Network Cat. 5 Ethernet Cable Field Supplied to desired location BMS XYE Indoor Unit Lennox Mini-Split Single Zone System Lennox Mini-Split Single Zone System Lennox Mini-Split Single Zone System Lennox Mini-Split Single Zone System NTE - Maximum 96 outdoor units per device. Up to 24 DUs (K1K2E connection required) per bus. (VRF & Mini-VRF Systems only) Maximum 256 indoor units per device. Up to 64 IDUs per bus. (All Systems) NTE - Field-supplied communication wiring - 18 GA., stranded, 3-conductor, shielded control wire (polarity sensitive). All shields of shielded cable connect to GRUND terminal, not to E. NTE - MWMA Mini-split wall-mounted indoor units are shipped with a cable for use with connecting to XYE terminal. Do not discard cable. NTE - utdoor unit control & monitoring points are not available for Mini-Split systems. Figure 6. Mini-Split Single Zone System Indoor Unit nly Monitoring 9
10 BACnet Gateway BACnet/IP Network Cat. 5 Ethernet Cable Field Supplied to desired location BMS XYE Indoor Unit Mini-Split Multi-Zone System Four-zone system shown XYE Indoor Unit Mini-Split Multi-Zone System Four-zone system shown XYE Indoor Unit Mini-Split Multi-Zone System Four-zone system shown NTE - Maximum 96 outdoor units per device. Up to 24 DUs (K1K2E connection required) per bus. (VRF & Mini-VRF Systems only) Maximum 256 indoor units per device. Up to 64 IDUs per bus. (All Systems) NTE - Field-supplied communication wiring - 18 GA., stranded, 3-conductor, shielded control wire (polarity sensitive). All shields of shielded cable connect to GRUND terminal, not to E. NTE - MWMA Mini-split wall-mounted indoor units are shipped with a cable for use with connecting to XYE terminal. Do not discard cable. NTE - utdoor unit control & monitoring points are not available for Mini-Split systems. Mini-Split Multi-Zone System Four-zone system shown Figure 7. Mini-Split Multi-Zone System Indoor Unit nly Monitoring 10
11 XYE Indoor Unit K1K2E utdoor Unit VRF System BACnet Gateway XYE Indoor Unit BACnet/IP Network XYE Indoor Unit -1P Mini-VRF System Mini-Split Single-Zone System BMS NTE - Maximum 96 outdoor units per device. Up to 24 DUs (K1K2E connection required) per bus. (VRF & Mini-VRF Systems only) Maximum 256 indoor units per device. Up to 64 IDUs per bus. (All Systems) NTE - Field-supplied communication wiring - 18 GA., stranded, 3-conductor, shielded control wire (polarity sensitive). All shields of shielded cable connect to GRUND terminal, not to E. NTE - MWMA Mini-split wall-mounted indoor units are shipped with a cable for use with connecting to XYE terminal. Do not discard cable. NTE - utdoor unit control & monitoring points are not available for Mini-Split systems. -1P Mini-VRF systems require the Mini-VRF Control Interface V0CTRL00P-1. NTE - VRF Heat Pump wiring configuration shown. XYE wiring configuration is same for VRF Heat Pump and VRF Heat Recovery systems. No monitoring points are available for MS Boxes. NTE - Each VRF Refrigerant system is limited to 63 IDUs. Figure 8. Multiple Lennox System Types Using ne BACnet Gateway Device 11
12 XYE Indoor Unit VRF System BACnet Gateway K1K2E utdoor Unit -2P Mini-VRF System BACnet/IP Network -1P Mini-VRF System Mini-Split Single-Zone System Mini-Split Multi-Zone System Four-zone system shown BMS NTE - Maximum 96 outdoor units per device. Up to 24 DUs (K1K2E connection required) per bus. (VRF & Mini-VRF Systems only) Maximum 256 indoor units per device. Up to 64 IDUs per bus. (All Systems) NTE - Field-supplied communication wiring - 18 GA., stranded, 3-conductor, shielded control wire (polarity sensitive). All shields of shielded cable connect to GRUND terminal, not to E. NTE - MWMA Mini-split wall-mounted indoor units are shipped with a cable for use with connecting to XYE terminal. Do not discard cable. NTE - utdoor unit control & monitoring points are not available for Mini-Split systems. -1P Mini-VRF systems require the Mini-VRF Control Interface V0CTRL00P-1. NTE - VRF Heat Pump wiring configuration shown. XYE wiring configuration is same for VRF Heat Pump and VRF Heat Recovery systems. No monitoring points are available for MS Boxes. NTE - Each VRF Refrigerant system is limited to 63 IDUs. Figure 9. Multiple Lennox System Types Daisy Chained Together (Two Bus Used) 12
13 BACnet Gateway BACnet/IP Network BMS utdoor unit address setting under one EXE/ K1K2E port ENC1 (NUM_S) Valid range ENC4 (NET_AD- DRESS) Valid range The actual network address of outdoor unit in LVM/BACnet* Up to 8 Systems XYE K1K2E Refrigerant System 1 ENC4 0 ENC1 0 ENC4 0 ENC1 1 ENC4 0 ENC1 2 Refrigerant System 2 ENC4 1 ENC1 0 ENC4 1 ENC1 1 ENC4 1 ENC1 2 Refrigerant System 3 ENC4 2 ENC1 0 ENC4 2 ENC1 1 ENC4 2 ENC1 2 Refrigerant System 4 ENC4 3 ENC1 0 ENC4 3 ENC1 1 ENC4 3 ENC1 2 K1K2E K1K2E K1K2E K1K2E Refrigerant System 1 Refrigerant System 2 Refrigerant System 3 Refrigerant System *4+0=0 0*4+1=1 0*4+2=2 0*4+4=4 0*4+5=5 0*4+6=6 0*4+8=8 0*4+9=9 0*4+10=10 0*4+12=12 0*4+13=13 0*4+14=14 *The actual network address of the outdoor unit in LVM/BACnet = ENC4*4 + ENC1. Figure 10. utdoor Unit Addressing ENC Setting Example 13
14 BACnet bject Points List Item Function Identifier bject Name Indoor Unit Point List bject Type 1 Mode ModeSetting M Heating Cooling 2 Mode Status QueryMode MI Heating Cooling Possible ptions Dehumidify (Dry) Dehumidify (Dry) 3 Fan Speed FANSpeed M High Medium Low Stop Fan Speed Status QueryFANSpeed MI High Medium Low Stop FF 5 Setpoint TempSetting A F Setpoint Status QueryTempSetting AI F Room Temperature ITempIndoor AI F Swing Swing B Inactive Active 9 Error Code IMalfunction MI 10 Protection Code IProtect MI Remote Control Lock Turn Indoor Unit N/FF Turn All Indoor Units N/FF Fan only Fan only FF FF See "Indoor Unit Table 9. Error Code" on page 18 See "Indoor Unit Table 10. Protection Code" on page 19 Remote_Control_lock B Inactive Active Turnnff B Inactive Active ALL_nff B --- Active Item Function Identifier bject Name utdoor Unit Point List bject Type Possible ptions 1 peration Mode IperationMode MI Heating Cooling Stop Condenser Fan Speed IFANSpeed MI High Medium Low Ambient Temperature ITemputdoor AI F Indoor Quantity ITotalACs AI Number of indoor units 5 Compressor 1 ICom1Current AI Current in Amps 6 Compressor 2 ICom2Current AI Current in Amps 7 Compressor 3 ICom3Current AI Current in Amps 8 Error Code IMalfunction MI 9 Protection Code IProtect MI See "utdoor Unit Table 8. Error Code" on page 25 See "utdoor Unit Table 9. Protection Code" on page 26 NTE - utdoor unit control & monitoring points are not available for Mini-Split systems. -1P Mini-VRF systems require the Mini-VRF Control Interface V0CTRL00P-1. 14
15 Indoor Unit Instance Number Description Port No. Indoor unit address Parent bject Device* analog-input,4 Sub jbects analoginput,1 analoginput,2 analoginput,3 analogoutput,1 binaryoutput,1 binaryoutput,2 00 indoor_0_ Port 1 01 indoor_0_ ITempIndoor InTime IffTime QueryTempSetting TempSetting swing ElecHeat 63 indoor_1_ indoor_1_ Port 2 01 indoor_1_ ITempIndoor InTime IffTime QueryTempSetting TempSetting swing ElecHeat 63 indoor_1_ indoor_2_ Port 3 01 indoor_2_ ITempIndoor InTime IffTime QueryTempSetting TempSetting swing ElecHeat 63 indoor_2_ indoor_3_ Port 4 01 indoor_3_ ITempIndoor InTime IffTime QueryTempSetting TempSetting swing ElecHeat 63 indoor_3_ "* - Left two digits Virtual BACnet Network number = 19(default), can be changed on confi guration web page. Right four digits Device ID=""BTXX"";. ""B"" is the bus Number 0-3; ""T"" means type 0-indoor unit,1-outdoor unit; ""XX"" is the indoor unit Number 0-63 or utdoor unit actual network address 0-31(outdoor unit address + outdoor unit network address * 4);" multi-stateinput,1 Imalfunction Imalfunction Imalfunction Imalfunction multistateinput,2 Iprotect Iprotect Iprotect Iprotect multi-stateinput,3 QueryMode QueryMode QueryMode QueryMode multi-stateinput,4 QueryFanSpeed QueryFanSpeed QueryFanSpeed QueryFanSpeed multi-stateoutput,1 ModeSetting ModeSetting ModeSetting ModeSetting multi-stateoutput,2 FanSpeed FanSpeed FanSpeed FanSpeed 15
16 Indoor Unit Points Indoor Unit Table 1. Mode Attribute Identifier Data Type Attribute value Meaning Read/Write bject Identifi er BACnetbjectIdentifi er MultiState-output 1 - R bject Name CharacterString ModeSetting - R bject Type BACnetbjectType MultiState-output - R/W Description CharacterString peration mode setting - 1 Heat ptions Integer 2 3 Cool Dry 4 Fan Indoor Unit Table 2. Mode Status Attribute identifier Data type Attribute value Read/ Write bject Identifi er BACnetbjectIdentifi er MultiState-input 3 R bject Name CharacterString QueryMode R bject Type BACnetbjectType MultiState-input R Description CharacterString QueryMode Status Text BACnet ARRAY[N] CharacterString { Heat, Cool, Dry, Fan only, Stop } Indoor Unit Table 3. Fan Speed Attribute Identifier Data type Attribute value Meaning Read/ Write bject Identifi er BACnetbjectIdentifi er MultiState-output 2 - R bject Name CharacterString FanSpeed - R bject Type BACnetbjectType MultiState-output - R/W Description CharacterString Fan Speed Setting - ptions Integer High Medium Low Indoor Unit Table 4. Fan Speed Status Attribute identifier Data type Attribute value Read/Write bject Identifi er BACnetbjectIdentifi er MultiState-input 4 R bject Name CharacterString QueryFanSpeed R bject Type BACnetbjectType MultiState-input R Description CharacterString QueryFanSpeed Status Text BACnet ARRAY[N] CharacterString {"High","Middle","Low", Stop } 16
17 Indoor Unit Table 5. Setpoint Attribute Identifier Data type Attribute value Read/Write bject Identifi er BACnetbjectIdentifi er Analog-output 1 R bject Name CharacterString TempSetting R bject Type BACnetbjectType Analog-output R/W Description CharacterString Setpoint Unit BACnetEngineering Units Degree-Fahrenheit R NTE - All values are degrees Fahrenheit ( F). You must send degrees Fahrenheit ( F) values and you will receive degrees Fahrenheit ( F). Range: 61 F - 90 F (16 C - 32 C). Indoor Unit Table 6. Setpoint Status Attribute identifier Data type Attribute value Read/Write bject identifi er BACnetbjectIdentifi er Analog-input 4 R bject name CharacterString QueryTempSetting R bject type BACnetbjectType Analog-input R Current value REAL 0 R Description CharacterString QueryTempsetting Unit BACnetEngineering Units Degree-Fahrenheit R NTE - The sent value is degrees Fahrenheit ( F). Indoor Unit Table 7. Room Temperature Attribute Identifier Data Mode Attribute value Read/Write bject Identifi er BACnetbjectIdentifi er Analog-input 1 R bject Name CharacterString ITempIndoor R bject Type BACnetbjectType Analog-input R Description CharacterString Indoor Temperature Unit BACnetEngineering Units Degree-Fahrenheit R NTE - The received value is degrees Fahrenheit ( F). Indoor Unit Table 8. Swing Attribute Identifier Data type Attribute value Read/Write bject Identifi er BACnetbjectIdentifi er Binary-output 1 R bject Name CharacterString Swing R bject Type BACnetbjectType Binary-output R/W Description CharacterString Swing Setting Inactive Text CharacterString Turn off Active Text CharacterString Turn on NTE - inactive means swing FF, active means swing N. 17
18 Indoor Unit Table 9. Error Code Attribute Identifier Data Mode Attribute value Read/ Write bject Identifi er BACnetbjectIdentifi er MultiState-input 1 R bject Name CharacterString IMalfunction R bject Type BACnetbjectType MultiState-input R Description CharacterString Malfunction Status E1 E2 E3 E4 E5 E6 E7 BACnet ARRAY[N] Status Text E8 CharacterString E9 EA EB EC ED EE EF No NTE - Refer to the Lennox VRF Mobile App for error code descriptions. E0 18
19 Indoor Unit Table 10. Protection Code Attribute Identifier Data Mode Attribute value Read/ Write bject Identifi er BACnetbjectIdentifi er MultiState-input 2 R bject Name CharacterString IProtect R bject Type BACnetbjectType MultiState-input R Description CharacterString Protection Status P1 P2 P3 P4 BACnet ARRAY[N] Status text P5 CharacterString P6 P7 P8 PF No NTE - Refer to the Lennox VRF Mobile App for error code descriptions. P0 19
20 Indoor Unit Table 11. Remote Control Lock Attribute Identifier Data Mode Attribute value Read/ Write bject Identifi er BACnetbjectIdentifi er Binary-output 4 R/W bject Name CharacterString Remote_Control_lock R bject Type BACnetbjectType Binary-output R Description CharacterString Lock/Unlock remote control Inactive text CharacterString unlock remote control Active text CharacterString lock remote control NTE - Refer to the Lennox VRF Mobile App for error code descriptions. NTE - Lock All Functions of Wireless Remote Controller V0STAT52P-1. Indoor Unit Table 12. Turn Indoor Unit N/FF Attribute Identifier Data Mode Attribute value Read/ Write bject Identifi er BACnetbjectIdentifi er Binary-output 3 R/W bject Name CharacterString Turnnff R bject Type BACnetbjectType Binary-output R Description CharacterString Turn n/ff the AC Inactive text CharacterString Turn off Active text CharacterString Turn on NTE - Refer to the Lennox VRF Mobile App for error code descriptions. Indoor Unit Table 13. Turn All Indoor Units N/FF Attribute Identifier Data Mode Attribute value Read/ Write bject Identifi er BACnetbjectIdentifi er Binary-output 5 R/W bject Name CharacterString ALL_nff R bject Type BACnetbjectType Binary-output R Description CharacterString turn on/turn off ac all the bus Inactive text CharacterString Active text CharacterString turn off ac all the bus NTE - Refer to the Lennox VRF Mobile App for error code descriptions. 20
21 utdoor Unit Instance Number Description utdoor unit actual network address Parent bject Device* Multistateiutput,2 Multistateinput,1 Analogiutput,1 Analogiutput,2 Sub bjects Analogiutput,3 Analogiutput,4 Analogiutput,5 Multistateinput,3 Multistateinput,4 Port No. Refrigerant system utdoor unit address (Dip switch on outdoor unit board) utdoor unit network address(dip switch on outdoor unit board) *4=0 outdoor_0_0_ Sys *4=1 outdoor_0_0_ *4=2 outdoor_0_0_ Port 1 Sys *4=4 outdoor_0_1_ *4=5 outdoor_0_1_ *4=6 outdoor_0_1_ IperationMode IFanSpeed ITemputoor *4=28 outdoor_0_7_ Sys *4=28 outdoor_0_7_ *4=30 outdoor_0_7_ *4=0 outdoor_1_0_ Sys *4=1 outdoor_1_0_ *4=2 outdoor_1_0_ Port 2 Sys *4=4 outdoor_1_1_ *4=5 outdoor_1_1_ *4=6 outdoor_1_1_ IperationMode IFanSpeed ITemputoor *4=28 outdoor_1_7_ Sys *4=28 outdoor_1_7_ *4=30 outdoor_1_7_ "* - Left two digits Virtual BACnet Network number = 19(default), can be changed on confi guration web page. Right four digits Device ID=""BTXX"";. ""B"" is the bus Number 0-3; ""T"" means type 0-indoor unit,1-outdoor unit; ""XX"" is the indoor unit Number 0-63 or utdoor unit actual network address 0-31(outdoor unit address + outdoor unit network address * 4);" ITotalACs ITotalACs ICom1Current ICom2Current ICom1Current ICom2Current ICom3Current ICom3Current AC _ Ioutmalfunction AC _ Ioutmalfunction AC _Iutprotect AC _Iutprotect 21
22 utdoor unit actual network address Parent bject Device* Multistateiutput,2 Multistateinput,1 Analogiutput,1 Analogiutput,2 Sub bjects Analogiutput,3 Analogiutput,4 Analogiutput,5 Multistateinput,3 Multistateinput,4 Port No. Refrigerant system utdoor unit address (Dip switch on outdoor unit board) utdoor unit network address(dip switch on outdoor unit board) *4=0 outdoor_2_0_ Sys *4=1 outdoor_2_0_ *4=2 outdoor_2_0_ Port 3 Sys *4=4 outdoor_2_1_ *4=5 outdoor_2_1_ *4=6 outdoor_2_1_ IperationMode IFanSpeed ITemputoor *4=28 outdoor_2_7_ Sys *4=28 outdoor_2_7_ *4=30 outdoor_2_7_ *4=0 outdoor_3_0_ Sys *4=1 outdoor_3_0_ *4=2 outdoor_3_0_ Port 4 Sys *4=4 outdoor_3_1_ *4=5 outdoor_3_1_ *4=6 outdoor_3_1_ IperationMode IFanSpeed ITemputoor *4=28 outdoor_3_7_ Sys *4=28 outdoor_3_7_ *4=30 outdoor_3_7_ "* - Left two digits Virtual BACnet Network number = 19(default), can be changed on confi guration web page. Right four digits Device ID=""BTXX"";. ""B"" is the bus Number 0-3; ""T"" means type 0-indoor unit,1-outdoor unit; ""XX"" is the indoor unit Number 0-63 or utdoor unit actual network address 0-31(outdoor unit address + outdoor unit network address * 4);" ITotalACs ITotalACs ICom1Current ICom2Current ICom1Current ICom2Current ICom3Current ICom3Current AC _ Ioutmalfunction AC _ Ioutmalfunction AC _Iutprotect AC _Iutprotect 22
23 utdoor Unit Points NTE - utdoor unit control & monitoring points are not available for Mini-Split systems. -1P Mini-VRF systems require the Mini-VRF Control Interface V0CTRL00P-1. utdoor Unit Table 1. peration Mode Attribute Identifier Data Mode Attribute value Meaning Read/Write bject Identifi er BACnetbjectIdentifi er MultiState-input 1 R bject Name CharacterString IperationMode R bject Type BACnetbjectType MultiState-input R Description CharacterString peration mode Status text 1 Heat BACnet ARRAY [N] 2 Cool CharacterString 3 Stop utdoor Unit Table 2. Condenser Fan Speed Attribute Identifier Data Mode Attribute value Meaning Read/Write bject Identifi er BACnetbjectIdentifi er MultiState-input 2 R bject Name CharacterString IFanSpeed R bject Type BACnetbjectType MultiState-input R Description CharacterString Fan Speed 1 High 2 Medium ptions Integer 3 Low 4 Stop utdoor Unit Table 3. Ambient Temperature Attribute Identifier Data type Attribute value Read/Write bject Identifi er BACnetbjectIdentifi er Analog-input 1 R bject Name CharacterString ITemputoor R bject Type BACnetbjectType Analog-input R Description CharacterString utdoor Temperature Unit BACnetEngineering Units Degree-Fahrenheit R NTE - The received value is degrees Fahrenheit ( F). utdoor Unit Table 4. Indoor Quantity Attribute Identifier Data Mode Attribute value Read/Write bject Identifi er BACnetbjectIdentifier Analog-input 2 R bject Name CharacterString ITotalACs R bject Type BACnetbjectType Analog-input R Description CharacterString Indoor unit qty peration instruction The CURRENT VALUE attribute of the selected object refl ects the current INDR UNIT QUANTITY (Read only). 23
24 utdoor Unit Table 5. Compressor 1 Attribute Identifier Data type Attribute value Read/Write bject Identifi er BACnetbjectIdentifier Analog-input 3 R bject Name CharacterString ICom1Current R bject Type BACnetbjectType Analog-input R Current Value REAL 0 R Description CharacterString Compressor 1 current Unit BACnetEngineering Units Amperes R peration Instruction The CURRENT VALUE attribute of the selected object refl ects the CMPRESSR 1 ELECTRIC CURRENT (Read only). utdoor Unit Table 6. Compressor 2 Attribute Identifier Data type Attribute value Read/Write bject Identifi er BACnetbjectIdentifi er Analog-input 4 R bject Name CharacterString ICom2Current R bject Type BACnetbjectType Analog-input R Current Value REAL 0 R Description CharacterString Compressor 2 current Unit BACnetEngineering Units Amperes R peration Instruction The CURRENT VALUE attribute of the selected object refl ects the CMPRESSR 2 ELECTRIC CURRENT (Read only). utdoor Unit Table 7. Compressor 3 Attribute Identifier Data type Attribute value Read/Write bject Identifi er BACnetbjectIdentifi er Analog-input 5 R bject Name CharacterString ICom3Current R bject Type BACnetbjectType Analog-input R Description CharacterString Compressor 3 current Unit BACnetEngineering Units Amperes R peration Instruction The CURRENT VALUE attribute of the selected object refl ects the CMPRESSR 3 ELECTRIC CURRENT (Read only). 24
25 utdoor Unit Table 8. Error Code Attribute Identifier Data type Attribute value Read/ Write bject Identifi er BACnetbjectIdentifier MultiState-input 3 R bject Name CharacterString IMalfunction R bject Type BACnetbjectType MultiState-input R Description CharacterString Malfunction Status E1 E2 E3 E4 E5 E6 E7 BACnet ARRAY[N] Status Text E8 CharacterString E9 EA EB EC ED EE EF No NTE - Refer to the Lennox VRF Mobile App for error code descriptions. E0 25
26 utdoor Unit Table 9. Protection Code Attribute Identifier Data Mode Attribute value Read/ Write bject Identifi er BACnetbjectIdentifi er MultiState-input 4 R bject Name CharacterString IProtect R bject Type BACnetbjectType MultiState-input R Description CharacterString Protect Status P1 P2 P3 P4 P5 P6 P7 BACnet ARRAY[N] Status Text P8 CharacterString P9 PA PB PC PD PE PF No NTE - Refer to the Lennox VRF Mobile App for error code descriptions. P0 26
27 Appendix A. BACnet Protocol bserved Supportive bject Type bject Type Supported Dynamic Established or Not Dynamic Deleted or Not Analog Input bject Type X X X Analog utput bject Type X X X Analog Value bject Type X X X Binary Input bject Type X X X Binary utput bject Type X X X Binary Value bject Type X X X Device bject Type X X X Multi-Status Input bject Type X X X Multi-Status utput bject Type X X X Application Services of Supplied BACnet Application Services Read Property Read Property Multiple Write Property Write Property Multiple Request Start Request Preformed X Who-Has X X Who-Is I-Am X ption of Data Link Layer IS ,10BASE5 IS ,10BASE2 IS ,10BASET X X X Abbreviation R W R/W I BI B AI A MI M Legend Meaning Read Write Read/Write Input utput Binary Input Binary utput Analog Input Analog utput Multistate Input Multistate utput Supportive Character Set ANSI X3.4 IBMTM/Microsoft TM IS 10646(UCS2)T Subsection request support Subsection respond support Special Function Yes No X X window size:1476 window size:
28 Appendix B. Indoor Unit Detailed Points Indoor Unit Table 1. Mode Attribute Identifier Data type Attribute value Meaning Read/Write bject Identifi er BACnetbjectIdentifi er MultiState-output 1 R bject Name CharacterString ModeSetting R bject Type BACnetbjectType MultiState-output R Description CharacterString peration mode setting Current Value REAL 0 W Status Flags BACnetStatusFlags F F F F R Event Status BACnet EventStatus Normal R Take ff Service BLEAN F R Status Number Unsigned 6 R 1 Heat ptions Integer 2 3 Cool Dry 4 Fan Priority Array BACnetPriorityArra NULL R Release Default Unsigned 0 R Publicly Type Unsigned 1701 Feedback Value Unsigned 6 Event Enable BACnetEventTransitionBits T T T Affi rm Transform BACnetEventTransitionBits T T T Notify Type BACnetNotifyType Alarm Indoor Unit Table 2. Mode Status Attribute identifier Data type Attribute value Read/ Write bject Identifi er BACnetbjectIdentifi er MultiState-input 3 R bject Name CharacterString QueryMode R bject Type BACnetbjectType MultiState-input R Description CharacterString QueryMode Status Text BACnet ARRAY[N] CharacterString { Heat, Cool, Dry, Fan only, Stop } 28
29 Indoor Unit Table 3. Fan Speed Attribute Identifier Data type Attribute value Meaning Read/ Write bject Identifi er BACnetbjectIdentifi er MultiState-output 2 R bject Name CharacterString FanSpeed R bject Type BACnetbjectType MultiState-output R Description CharacterString Fan Speed Setting Current Value Unsigned 0 W Status Flags BACnetStatusFlags F F F F R Event Status BACnet EventStatus Normal R Take ff Service BLEAN F R Status Number Unsigned 6 R ptions Integer High Medium Low Priority Array BACnetPriorityArra NULL R Release Default Unsigned 0 Time Delay Unsigned 1 Publicly Type Unsigned 1701 Feedback Value Unsigned 6 Event Enable BACnetEventTransitionBits T T T Affi rm Transform BACnetEventTransitionBits T T T Notify Type BACnetNotifyType event Indoor Unit Table 4. Fan Speed Status Attribute identifier Data type Attribute value Read/Write bject Identifi er BACnetbjectIdentifi er MultiState-input 4 R bject Name CharacterString QueryFanSpeed R bject Type BACnetbjectType MultiState-input R Description CharacterString QueryFanSpeed Status Text BACnet ARRAY[N] CharacterString {"High","Middle","Low", Stop } 29
30 Indoor Unit Table 5. Setpoint Attribute Identifier Data type Attribute value Read/Write bject Identifi er BACnetbjectIdentifi er Analog-output 1 R bject Name CharacterString TempSetting R bject Type BACnetbjectType Analog-output R Description CharacterString Setpoint Status Flags BACnetStatusFlags F F F F R Current value REAL Temperature Value W Event Status BACnet EventStatus Normal R Take ff Service BLEAN F R Unit BACnetEngineering Units Degree-Fahrenheit R Minimum REAL 62 F (17 C) Maximum REAL 86 F (30 C) Distinguishability REAL 1 Priority Array Value BACnetPriorityArra NULL R Default Release REAL 0 R Distinguishability REAL 1 Cov Increment REAL 1 Low Valve Value REAL 62 F (17 C) High Valve Value REAL 86 F (30 C) Width Valve Value REAL 1 Enable Valve Value BACnetLimitEnable T T Event Enable BACnetEventTransitionBits T T T Notify Type BACnetNotifyType Alarm Publicly Type Unsigned 1701 Time Delay Unsigned 1 Affi rm Transform BACnetEventTransitionBits T T T NTE - All values are degrees Fahrenheit ( F). You must send degrees Fahrenheit ( F) values and you will receive degrees Fahrenheit ( F). Range: 61 F - 90 F (16 C - 32 C).. Indoor Unit Table 6. Setpoint Status Attribute identifier Data type Attribute value Read/Write bject Identifi er BACnetbjectIdentifi er Analog-input 4 R bject Name CharacterString QueryTempSetting R bject Type BACnetbjectType Analog-input R Current Value REAL 0 R Description CharacterString QueryTempsetting Unit BACnetEngineering Units Degree-Fahrenheit R NTE - The sent value is degrees Fahrenheit ( F). 30
31 Indoor Unit Table 7. Room Temperature Attribute Identifier Data Mode Attribute value Read/Write bject Identifi er BACnetbjectIdentifi er Analog-input 1 R bject Name CharacterString ITempIndoor R bject Type BACnetbjectType Analog-input R Current Value REAL 0 R Description CharacterString Indoor Temperature Unit BACnetEngineering Units Degree-Fahrenheit R Status Flags BACnetStatusFlags F F F F R Event Status BACnet EventStatus Normal R Reliablity BACnetReliability N-FAULT-DETECTED R Take ff Service BLEAN F R Unit BACnetEngineering Units Degree-Fahrenheit R Minimum REAL 0 F (-18 C) Maximum REAL 200 F (93 C) Distinguishability REAL 1 Time Delay Unsigned 1 Publicly Type Unsigned 1701 Low Valve Value REAL 0 F (-18 C) High Valve Value REAL 200 F (93 C) Width Valve Value REAL 1 Enable Valve Value BACnetLimitEnable F T Event Enable BACnetEventTransitionBits T T T Notify Type BACnetNotifyType event NTE - The received value is degrees Fahrenheit ( F). 31
32 Indoor Unit Table 8. Swing Attribute Identifier Data type Attribute value Read/Write bject Identifi er BACnetbjectIdentifi er Binary-output 1 R bject Name CharacterString Swing R bject Type BACnetbjectType Binary-output R Current Value BACnetBinaryPV inactive W Description CharacterString Swing Setting Status Flags BACnetStatusFlags F F F F R Event Status BACnet EventStatus Normal R Take ff Service BLEAN F R Polarity BACnetPolarity Normal R Inactive Text CharacterString Turn off Active Text CharacterString Turn on Time Delay Unsigned 1 Status Change Time BACnetDateTime Status Change Times Unsigned Change Time To 0 BACnetDateTime Publicly Type Unsigned 1701 Feedback Value BACnetBinaryPV inactive Event Enable BACnetEventTransitionBits T T T R Affi rm Transform BACnetEventTransitionBits T T T Priority Array BACnetPriorityArra NULL R Default Release BACnetBinaryPV inactive R Notify Type BACnetNotifyType Alarm NTE - Inactive means swing FF, active means swing N. 32
33 Indoor Unit Table 9. Error Code Attribute Identifier Data Mode Attribute value Read/Write bject Identifi er BACnetbjectIdentifi er MultiState-input 1 R bject Name CharacterString IMalfunction R bject Type BACnetbjectType MultiState-input R Description CharacterString Malfunction Status Current Value Unsigned 0 R Status Flags BACnetStatusFlags F F F F R Event Status BACnet EventStatus Normal R Take ff Service BLEAN F R Status Number Unsigned 11 R E0 E1 E2 E3 E4 E5 E6 Status Text E7 BACnet ARRAY[N] E8 CharacterString E9 EA EB EC ED EE EF No Time Delay Unsigned 1 Publicity Type Unsigned 1701 Event Enable BACnetEventTransitionBits T T T Affi rm Transform BACnetEventTransitionBits T T T Notify Type BACnetNotifyType Alarm NTE - Refer to the Lennox VRF Mobile App for error code descriptions. 33
34 Indoor Unit Table 10. Protection Code Attribute Identifier Data Mode Attribute value Read/ Write bject Identifi er BACnetbjectIdentifi er MultiState-input 2 R bject Name CharacterString IProtect R bject Type BACnetbjectType MultiState-input R Description CharacterString Protect Status Current Value Unsigned 0 R Status Flags BACnetStatusFlags F F F F R Event Status BACnet EventStatus Normal R Take ff Service BLEAN F R Status Number Unsigned 11 R P1 P2 P3 Status Text P4 BACnet ARRAY[N] P5 CharacterString P6 P7 P8 PF No Time Delay Unsigned 1 Publicly Type Unsigned 1701 Event Enable BACnetEventTransitionBits T T T Affi rm Transform BACnetEventTransitionBits T T T Notify Type BACnetNotifyType Alarm NTE - Refer to the Lennox VRF Mobile App for error code descriptions. P0 34
35 Indoor Unit Table 11. Remote Control Lock Attribute Identifier Data Mode Attribute value Read/ Write bject Identifi er BACnetbjectIdentifi er Binary-output 4 R/W bject Name CharacterString Remote_Control_lock R bject Type BACnetbjectType Binary-output R Current Value BACnetBinaryPV inactive W Description CharacterString Lock/Unlock remote control Status Flags BACnetStatusFlags F F F F R Event Status BACnet EventStatus Normal R Take ff Service BLEAN F R Polarity BACnetPolarity Normal R Inactive text CharacterString unlock remote control Active text CharacterString lock remote control Time Delay Unsigned 1 Status Change Time BACnetDateTime Status Change Times Unsigned Change Time To 0 BACnetDateTime Publicly Type Unsigned 1701 Feedback Value BACnetBinaryPV inactive Event Enable BACnetEventTransitionBits T T T R Affi rm Transform BACnetEventTransitionBits T T T Priority Array BACnetPriorityArra NULL R Default Release BACnetBinaryPV inactive R Notify Type BACnetNotifyType Alarm NTE - Refer to the Lennox VRF Mobile App for error code descriptions. NTE - Lock All Functions of Wireless Remote Controller V0STAT52P-1. NTE - Inactive means unlock remote control, active means lock remote control. 35
36 Indoor Unit Table 12. Turn Indoor Unit N/FF Attribute Identifier Data Mode Attribute value Read/ Write bject Identifi er BACnetbjectIdentifi er Binary-output 3 R/W bject Name CharacterString Turnnff R bject Type BACnetbjectType Binary-output R Current Value BACnetBinaryPV inactive W Description CharacterString Turn n/ff the AC Status Flags BACnetStatusFlags F F F F R Event Status BACnet EventStatus Normal R Take ff Service BLEAN F R Polarity BACnetPolarity Normal R Inactive text CharacterString Turn off Active text CharacterString Turn on Time Delay Unsigned 1 Status Change Time BACnetDateTime Status Change Times Unsigned Change Time To 0 BACnetDateTime Publicly Type Unsigned 1701 Feedback Value BACnetBinaryPV inactive Event Enable BACnetEventTransitionBits T T T R Affi rm Transform BACnetEventTransitionBits T T T Priority Array BACnetPriorityArra NULL R Default Release BACnetBinaryPV inactive R Notify Type BACnetNotifyType Alarm NTE - Refer to the Lennox VRF Mobile App for error code descriptions. NTE - Inactive means indoor unit turned off, active means indoor unit turned on. 36
37 Indoor Unit Table 13. Turn All Indoor Units N/FF Attribute Identifier Data Mode Attribute value Read/ Write bject Identifi er BACnetbjectIdentifi er Binary-output 5 R/W bject Name CharacterString ALL_nff R bject Type BACnetbjectType Binary-output R Current Value BACnetBinaryPV inactive W Description CharacterString turn on/turn off ac all the bus Status Flags BACnetStatusFlags F F F F R Event Status BACnet EventStatus Normal R Take ff Service BLEAN F R Polarity BACnetPolarity Normal R Inactive text CharacterString Active text CharacterString turn off ac all the bus Time Delay Unsigned 1 Status Change Time BACnetDateTime Status Change Times Unsigned Change Time To 0 BACnetDateTime Publicly Type Unsigned 1701 Feedback Value BACnetBinaryPV inactive Event Enable BACnetEventTransitionBits T T T R Affi rm Transform BACnetEventTransitionBits T T T Priority Array BACnetPriorityArra NULL R Default Release BACnetBinaryPV inactive R Notify Type BACnetNotifyType Alarm NTE - Refer to the Lennox VRF Mobile App for error code descriptions. NTE - Active means turn off all indoor units. 37
38 Appendix C. utdoor Unit Detailed Points NTE - utdoor unit control & monitoring points are not available for Mini-Split systems. -1P Mini-VRF systems require the Mini-VRF Control Interface V0CTRL00P-1. utdoor Unit Table 1. peration Mode Attribute Identifier Data Mode Attribute value Meaning Read/ Write bject Identifi er BACnetbjectIdentifi er MultiState-input 1 R bject Name CharacterString IperationMode R bject Type BACnetbjectType MultiState-input R Description CharacterString peration mode Current Value REAL 0 R Status Flags BACnetStatusFlags F F F F R Event Status BACnet EventStatus Normal R Take ff Service BLEAN F R Status Number Unsigned 3 R Status Text 1 Heat BACnet ARRAY [N] 2 Cool CharacterString 3 Stop Time Delay Unsigned 1 Publicly Type Unsigned 1701 Event Enable BACnetEventTransitionBits T T T Affi rm Transform BACnetEventTransitionBits T T T Notify Type BACnetNotifyType Alarm 38
39 utdoor Unit Table 2. Condenser Fan Speed Attribute Identifier Data Mode Attribute value Meaning Read/Write bject Identifi er BACnetbjectIdentifi er MultiState-input 2 R bject Name CharacterString IFanSpeed R bject Type BACnetbjectType MultiState-input R Description CharacterString Fan Speed Current Value Unsigned 0 R Status Flags BACnetStatusFlags F F F F R Event Status BACnet EventStatus Normal R Take ff Service serviceblean F R Status Number Unsigned 4 R ptions Integer 1 High 2 3 Medium Low Time Delay Unsigned 1 Publicly Type Unsigned 1701 Event Enable BACnetEventTransitionBits T T T Affi rm Transform BACnetEventTransitionBits T T T Notify Type BACnetNotifyType event 39
40 utdoor Unit Table 3. Ambient Temperature Attribute Identifier Data type Attribute value Read/ Write bject Identifi er BACnetbjectIdentifi er Analog-input 1 R bject Name CharacterString ITemputoor R bject Type BACnetbjectType Analog-input R Current Value REAL 0 R Description CharacterString utdoor Temperature Status Flags BACnetStatusFlags F F F R Event Status BACnet EventStatus Normal R Take ff Service BLEAN F R Unit BACnetEngineering Units Degree-Fahrenheit R Minimum REAL 0 F (-18 C) Maximum REAL 200 F (93 C) Time Delay Unsigned 1 Publicly Type Unsigned 1701 Low Valve Value REAL 0 F (-18 C) High Valve Value REAL 200 F (93 C) Width Valve Value REAL 1 Enable Valve Value BACnetLimitEnable F T Event Enable BACnetEventTransitionBits T T T Notify Type BACnetNotifyType event NTE - The received value is degrees Fahrenheit ( F). 40
41 utdoor Unit Table 4. Indoor Quantity Attribute Identifier Data Mode Attribute value Read/Write bject Identifi er BACnetbjectIdentifi er Analog-input 2 R bject Name CharacterString ITotalACs R bject Type BACnetbjectType Analog-input R Current Value REAL 0 R Description CharacterString Indoor unit qty Status Flags BACnetStatusFlags F F F F R Event Status BACnet EventStatus Normal R Take ff Service BLEAN F R Unit BACnetEngineering Units R Minimum REAL 0 Maximum REAL 250 Time Delay Unsigned 1 Publicly Type Unsigned 1701 Low Valve Value REAL 0 High Valve Value REAL 250 Width Valve Value REAL 1 Enable Valve Value BACnetLimitEnable F T Event Enable BACnetEventTransitionBits T T T Notify Type BACnetNotifyType Alarm peration Instruction The CURRENT VALUE attribute of the selected object refl ects the current INDR UNIT QUANTITY (it s read only). 41
42 utdoor Unit Table 5. Error Code Compressor 1 Attribute Identifier Data type Attribute value Read/Write bject Identifi er BACnetbjectIdentifi er Analog-input 3 R bject Name CharacterString ICom1Current R bject Type BACnetbjectType Analog-input R Current Value REAL 0 R Description CharacterString Compressor 1 current Status Flags BACnetStatusFlags F F F F R Event Status BACnet EventStatus Normal R Take ff Service BLEAN F R Unit BACnetEngineering Units Amperes R Minimum REAL 0 Maximum REAL 200 Time Delay Unsigned 1 Publicly Type Unsigned 1701 Low Valve Value REAL 0 High Valve Value REAL 200 Width Valve Value REAL 1 Enable Valve Value BACnetLimitEnable F T Notify Type BACnetNotifyType Alarm peration Instruction The CURRENT VALUE attribute of the selected object refl ects the CMPRESSR 1 ELECTRIC CURRENT (Read only). 42
43 utdoor Unit Table 6. Error Code Compressor 2 Attribute Identifier Data type Attribute value Read/Write bject Identifi er BACnetbjectIdentifi er Analog-input 4 R bject Name CharacterString ICom2Current R bject Type BACnetbjectType Analog-input R Current Value REAL 0 R Description CharacterString Compressor 2 current Status Flags BACnetStatusFlags F F F F R Event Status BACnet EventStatus Normal R Take ff Service BLEAN F R Unit BACnetEngineering Units Amperes R Minimum REAL 0 Maximum REAL 200 Time Delay Unsigned 1 Publicly Type Unsigned 1701 Low Valve Value REAL 0 High Valve Value REAL 200 Width Valve Value REAL 1 Enable Valve Value BACnetLimitEnable F T Event Enable BACnetEventTransitionBits T T T Notify Type BACnetNotifyType Alarm peration Instruction The CURRENT VALUE attribute of the selected object refl ects the CMPRESSR 2 ELECTRIC CURRENT (Read only). 43
44 utdoor Unit Table 7. Error Code Compressor 3 Attribute Identifier Data type Attribute value Read/Write bject Identifi er BACnetbjectIdentifi er Analog-input 5 R bject Name CharacterString ICom3Current R bject Type BACnetbjectType Analog-input R Description CharacterString Compressor 3 current Current Value REAL 0 R Status Flags BACnetStatusFlags F F F F R Event Status BACnet EventStatus Normal R Take ff Service BLEAN F R Unit BACnetEngineering Units Amperes R Minimum REAL 0 Maximum REAL 200 Time Delay Unsigned 1 Publicly Type Unsigned 1701 Low Valve Value REAL 0 High Valve Value REAL 200 Width Valve Value REAL 1 Enable Valve Value BACnetLimitEnable F T Event Enable BACnetEventTransitionBits T T T Notify Type BACnetNotifyType Alarm peration Instruction The CURRENT VALUE attribute of the selected object refl ects the CMPRESSR 3 ELECTRIC CURRENT (Read only). 44
45 utdoor Unit Table 8. Error Code Attribute Identifier Data type Attribute value Read/ Write bject Identifi er BACnetbjectIdentifi er MultiState-input 3 R bject Name CharacterString IMalfunction R bject Type BACnetbjectType MultiState-input R Description CharacterString Malfunction Status Current Value Unsigned 0 R Status Flags BACnetStatusFlags F F F F R Event Status BACnet EventStatus Normal R Take ff Service BLEAN F R Status Number Unsigned 17 R E1 E2 E3 E4 E5 E6 Status Text E7 BACnet ARRAY[N] E8 CharacterString E9 EA EB EC ED EE EF No Time Delay Unsigned 1 Publicly Type Unsigned 1701 Event Enable BACnetEventTransitionBits T T T Affi rm Transform BACnetEventTransitionBits T T T Notify Type BACnetNotifyType Alarm NTE - Refer to the Lennox VRF Mobile App for error code descriptions. E0 45
46 utdoor Unit Table 9. Protection Code Attribute Identifier Data Mode Attribute value Read/ Write bject Identifi er BACnetbjectIdentifi er MultiState-input 4 R bject Name CharacterString IProtect R bject Type BACnetbjectType MultiState-input R Description CharacterString Protect Status Current value Unsigned 0 R Status Flags BACnetStatusFlags F F F F R Event Status BACnet EventStatus Normal R Take ff Service BLEAN F R Status Number Unsigned 17 R P1 P2 P3 P4 P5 P6 Status Text P7 BACnet ARRAY[N] P8 CharacterString P9 PA PB PC PD PE PF No Time Delay Unsigned 1 Publicly Type Unsigned 1701 Event Enable BACnetEventTransitionBits T T T Affi rm transform BACnetEventTransitionBits T T T Notify Type BACnetNotifyType Alarm NTE - Refer to the Lennox VRF Mobile App for error code descriptions. P0 46
Building Product CCM08 Series BACnet Central Control Module User Manual
Building Product CCM08 Series BACnet Central Control Module User Manual 2007.10 1 1. connect diagrammatic sketch (1)CCM08 interfaces diagrammatic sketch An Ethernet interface connected to BACnet/IP network.
More informationOWNER S MANUAL. Building Gateways MD-CCM08/E (K01-BACNET)
OWNER S MANUAL Building Gateways MD-CCM08/E (K01-BACNET) Thank you very much for purchasing our air conditioner, please read this owner's manual carefully before using your air conditioner. CATALOGUE 1.
More informationLVM Touch Screen Centralized Controller
User Manual 2016 Lennox Industries Inc. Dallas, Texas, USA LVM Touch Screen Centralized Controller CONTROLS 507584-02 02/2016 THIS MANUAL MUST BE LEFT WITH THE OWNER FOR FUTURE REFERENCE Equipment List
More informationOPERATION INSTRUCTIONS
2018 Lennox Industries Inc. Dallas, Texas, USA OPERATION INSTRUCTIONS V0STAT52 Wireless Indoor Unit Controller CONTROLS 507459-04 05/2018 This manual must be left with the owner for future reference. IMPORTANT
More informationDaikin HVAC Controls Guide Specification
VARIABLE REFRIGERANT VOLUME (VRV) HVAC SYSTEM Building Management System Integration (Open Protocol Interface) Part 1 - General 1.01. Physical characteristics A. General: The VRV Controls Network shall
More informationInstallation Manual. DZK BACnet
Installation Manual DZK BACnet InterfacepbilCodarPageNumber TABLE OF CONTENTS Page Overview... 5 Outline and Features... 5 System outline... 5 Specifications and device elements... 6 Functional specifications...
More informationHVAC TECHNICAL BULLETIN
Date: 07/19/2017 Subject: CAC Wall Mount Units - Emergency Temperature utput (ET) setting Models: AC0**MNADCH/AA, AC0**MNTDCH/AA CAC Wall Mount Units - Emergency Temperature utput (ET) Setting Concept
More informationUSER'S MANUAL. IntesisBox KNX K01-KNX-1B/16/64 v1.0. r1 eng Issue Date: 2014/06
USER'S MANUAL IntesisBox KNX K01-KNX-1B/16/64 v1.0 r1 eng Issue Date: 2014/06 Interface for integration of Kaysun air conditioners into KNX TP-1 (EIB) control systems. Compatible with VRF air conditioners
More informationDaikin HVAC Controls Guide Specification
Part 1 - General VARIABLE REFRIGERANT VOLUME (VRV) HVAC SYSTEM Advanced Multi-zone Controller 1.01. Physical characteristics A. General: The advanced multi-zone controller shall be made from plastic materials
More informationIntesisBox. v.0.1. User Manual Issue Date: 12/2017 r1.3 EN
IntesisBox HS-RC-MBS-1 v.0.1 Modbus RTU (EIA-485) Interface for Hisense air conditioners. Compatible with commercial line of air conditioners commercialized by Hisense. User Manual Issue Date: 12/2017
More informationInstallation, Start-up and Operating Instructions
Installation, Start-up and Operating Instructions EVOLUTION SMART SENSOR FOR ZONING Cancels: NEW II ZONESMS-0-1 7-04 NOTE: Read the entire instruction manual before starting the installation. This symbol
More informationDaikin HVAC Controls Guide Specification
Part 1 - General VARIABLE REFRIGERANT VOLUME (VRV) HVAC SYSTEM Advanced Multi-zone Controller 1.01. Physical characteristics A. General: The advanced multi-zone controller shall be made from plastic materials
More informationPoolPak MPK with CommandPak Control System CPCS BACnet /IP User s Guide DOCUMENT #: SVW07-MPKBACNIP
PoolPak MPK with CommandPak Control System CPCS BACnet /IP User s Guide DOCUMENT #: SVW07-MPKBACNIP-20171020 UPDATED: OCTOBER 2017 INTRODUCTION PoolPak dehumidifiers equipped with an CommandPak Control
More informationIntesisBox TO-RC-MBS-1
IntesisBox TO-RC-MBS-1 v.1.5 MODBUS RTU (EIA485) Interface for Toshiba air conditioners from the Digital Inverter & VRF lines. User Manual Issue Date: 01/2014 Order Codes: TO-RC-MBS-1 Intesis Software
More informationSubmittal Data Sheet intelligent Touch Manager DCM601A71
For use with the following VRV Models: FXAQ, FXDQ, FXEQ, FXFQ, FXHQ, FXLQ, FXMQ, FXMQ_MF, FXNQ, FXTQ, FXUQ, FXZQ, VAM For use with the following Daikin SkyAir Models: FAQ, FBQ, FCQ, FHQ, FTQ Capacity:
More informationViconics VT76x6W Water-source Heat Pump Controllers Engineering Guide Specification
Viconics VT76x6W Water-source Heat Pump Controllers Engineering Guide Specification General The VT76xxW series is designed for single-stage and multi-stage control of water source heat pumps with dedicated
More informationSER8300 Series Line Voltage Room Controller with Optional PIR Sensor Installation Guide
Line Voltage Room Controller with Optional PIR Sensor Commercial and Hotel/Lodging HVAC Fan Coil Applications CONTENTS Installation 3 Location 3 Installation 3 Terminal, Identification and Function 4 Communication
More informationV0STAT51P-2 Programmable Wired Controller
PRODUCT SPECIFICATIONS VARIABLE REFRIGERANT FLOW SYSTEMS VRF V0STAT51P-2 Programmable Wired Controller Bulletin No. 210766 March 2016 Grouping - Controller can control up to 16 indoor units on the same
More informationOwner's Manual. BACnet Gateway. Original Instructions. Commercial Air Conditioners. Models: ME30-24/D4(B)
Owner's Manual Original Instructions Commercial Air Conditioners BACnet Gateway Models: ME30-24/D4(B) User Notice Dear customer: Please read this manual carefully prior to installation and operation and
More informationIntesisBox PA-AC-MBS-1
IntesisBox PA-AC-MBS-1 v.2.3 Modbus RTU (EIA-485) Interface for Panasonic air conditioners. Compatible with Etherea line air conditioners commercialized by Panasonic. User s Manual Issue Date: 11/2017
More informationSER8300 Series Line Voltage Room Controller with Optional PIR Sensor Installation Guide
Line Voltage Room Controller with Optional PIR Sensor Commercial and Hotel/Lodging HVAC Fan Coil Applications CONTENTS Installation 3 Location 3 Installation 3 Terminal, Identification and Function 4 Communication
More informationBACnet MS/TP Interface User s Guide
PoolPak MPK with CommandPak Control System CPCS BACnet MS/TP Interface User s Guide DOCUMENT #: SVW07-BACNET-MSTP-20171020 UPDATED: OCTOBER 2017 INTRODUCTION PoolPak dehumidifiers equipped with an CommandPak
More informationTEMPERATURE CONTROLLER 2 HEAT/ 2 COOL with Digital Room Temperature Display. Made in Australia 100% Australian Owned Company
TEMPERATURE CONTROLLER 2 HEAT/ 2 COOL with Digital Room Temperature Display HTC 5 Features Australian Made and designed Power can be either 24V or 240V AC 10 Amp (Resistive) Potential free relay contacts
More informationProcon BAC-A/50. Installation Instructions MITSUBISHI ELECTRIC
Installation Instructions Procon BAC-A/50 MITSUBISHI ELECTRIC BACnet TM is a registered trademark of ASHRAE (American Society of Heating, Refrigerating and Air- Conditioning Engineers, Inc.) 1. Product
More informationIntesisBox. v.2.5. User Manual Issue Date: 12/2017 r1.9 EN. Modbus RTU (EIA-485) Interface for Fujitsu air conditioners.
IntesisBox FJ-RC-MBS-1 v.2.5 Modbus RTU (EIA-485) Interface for Fujitsu air conditioners. User Manual Issue Date: 12/2017 r1.9 EN Order Codes: FJ-RC-MBS-1: Modbus RTU Interface for Fujitsu air conditioners
More informationINTERFACE SPECIFICATION
INTERFACE SPECIFICATION MODBUS CONVERTOR UTY-VMGX PART NO. 9708438030 Modbus is registered trademarks of Schneider Electric SA. LONWORKS is registered trademark of Echelon Corporation in the United States
More informationFailure to follow WARNING is very likely to result in such grave consequences as death or serious injury
Warning Read these Safety Precautions carefully to ensure correct installation. This manual classifies precautions into WARNING and CAUTION. Failure to follow WARNING is very likely to result in such grave
More informationIntesisBox DK-RC-MBS-1 v.0.2
IntesisBox DK-RC-MBS-1 v.0.2 MODBUS RTU (RS-485) Interface for Daikin air conditioners. Compatible with VRV and SKY line air conditioners commercialized by Daikin. User Manual Issue Date: 2011/05/05 Order
More informationRTD-NET Installation Instructions
LED3 SW1 LED4 RTD-NET Installation Instructions 0V +V POWER 15-24VDC English RTD-NET Installation Instructions 100.00 RTD-NET Control Interface realtime Control Systems REMC P1 P2 RS485 D-BUS DB DA GND
More informationIntesisBox ModBus RTU Fujitsu Air Conditioning
IntesisBox ModBus RTU Fujitsu Air Conditioning Compatible with Domestic and VRF line air conditioners commercialized by Fujitsu User Manual 03/2019 r1.0 eng Intesis Software S.L.U. 2019 All Rights Reserved.
More informationModbus RTU (EIA-485) Interface for Panasonic and Sanyo air conditioners. Compatible with ECOi and PACi line models.
IntesisBox PA-RC2-MBS-1 v.2.3 Modbus RTU (EIA-485) Interface for Panasonic and Sanyo air conditioners. Compatible with ECOi and PACi line models. User Manual Issue Date: 11/2017 r2.3 EN Order Codes: PA-RC2-MBS-1:
More informationINSTALLATION INSTRUCTIONS LonWorks Interface Model No. CZ-CLNC1U
INSTALLATIN INSTRUCTINS LonWorks Interface Model No. CZCLNCU Contents. LonWorks Interface verview Product verview System Diagram Functions. Installation Instructions of LonWorks Interface 4 Safety Precautions
More informationRTD-RA. realtime. Installation Instructions. English A B. Installation Instructions Control Systems LEDS ALL DIMENSIONS IN MM
RTD-RA Installation Instructions 37.50 LEDS 4 3 2 1 D English Installation Instructions 80.00 80.00 ALL DIMENSIS IN MM C realtime Control Systems A B LEDS 4 3 2 1 D S21 J3 J6 1 2 3 4 J5 5 6 7 0V S1 0V
More informationCONTROLLER INSTALLATION OPERATION & QUICK START
CONTROLLER INSTALLATION OPERATION & QUICK START Controller: 8403-066 ECU Series Controller Manual: 2100-559 Supersedes: NEW File: Tab 19 Date: 05-02-11 Page 1 of 6 TABLE OF CONTENTS Installation Note...
More informationCoolPlug CooLinkHub HVAC Bridge. Quick Installation Guide
CoolPlug CooLinkHub HVAC Bridge Quick Installation Guide Warning Read and understand the following Safety Guidelines and Warnings to ensure a safe installation Failure to follow WARNING may result in
More informationProdigy Control System Premium Rooftop Unit Control
CONTROLS Prodigy Control System Premium Rooftop Unit Control Bulletin No. 210537 February 2010 Supersedes January 2010 L E N N O X L E N N O X L E N N O X OVERVIEW The Prodigy Control System intelligently
More informationBrivis. Ducted Reverse Cycle Inverter. Wired Programmable Controller OWNERS MANUAL
Brivis Brivis Australia 6 Malcolm Rd Braeside Victoria 95 For all your Sales and Service enquiries call us on 00 BRIVIS (00 74 847) Australia 00 BRIVIS (00 74 847) Fax: +6 (0) 964 9400 www.brivis.com.au
More informationDual Digital Module Technical Guide
Factory Packaged Controls Coil Products Dual Digital Module Table of Contents OVERVIEW... 3 INSTALLATION AND WIRING... 4 Environmental Requirements...4 Mounting...4 Power Supply and Communications...4
More informationIntesisBox DK-RC-MBS-1 v.0.8
IntesisBox DK-RC-MBS-1 v.0.8 MODBUS RTU (RS-485) Interface for Daikin air conditioners. Compatible with VRV and SKY line air conditioners commercialized by Daikin. User Manual Issue Date: 2013/02/26 Order
More informationCOND. A ENABLE RELAY CONTACT COOLA ENABLE 24 VAC. RATING IS 1 AMP COND. B ENABLE COOL B ENABLE.
Factory Packaged Controls Coil Products Two Head Pressure Module Orion No.:OE370-23-HP2C 1 2 3 4 www.aaon.com www.orioncontrols.com Circuit A1 TRANSDUCER #1 Circuit A2 TRANSDUCER #2 Circuit B1 TRANSDUCER
More informationMXB-50 BACnet Interface for Mitsubishi Air-Conditioning
MXB-50 BACnet Interface for Mitsubishi Air-Conditioning Installation and User Guide www.microtrol.co.uk BACnet TM is a registered trademark of ASHRAE (American Society of Heating, Refrigerating and Air-
More informationWireless General Purpose Adapter (WGA100) Installation Instructions
(WGA100) Installation Instructions Daintree s WGA100 DT111 forms (Rev. part 12.8.17) of the Daintree ControlScope control solution for commercial and industrial buildings. It transmits and receives messages
More informationIntroduction. To use Carrier wireless sensors, you must have: A i-vu v6.5 or later system v6-00 or later drivers
Wireless Sensor CARRIER CORPORATION 2017 A member of the United Technologies Corporation family Stock symbol UTX Catalog No. 11-808-583-01 6/2/2017 Verify that you have the most current version of this
More informationFCU-4 FAN COIL CONTROLLER
FCU-4 FAN COIL CONTROLLER BACnet Enabled Description The FCU-4 is designed to provide complete control of fan coil units. The FCU-4 incorporates all the inputs and outputs to ensure that this advanced
More informationVC3000 Series Line Voltage Switching Relay Pack Controllers Installation Guide
Beyond Comfort VC3000 Series Line Voltage Switching Relay Pack Controllers Installation Guide August 10 th, 2010 (For Commercial and Lodging HVAC Fan Coil Applications) 028-0296-R1-LIT-VC3000-E01 Index
More informationUNT1100 Series. Binary Output Jumpers AO2 AO1 AO3 AO4 AOCM AOCM AOCM AOCM AO1. AI Switches Job Information N2 Address. Ref N2+ N2- ADDR 0 = ALL OPEN
1 2 8 4 AI6 R R Installation Bulletin UNT1100 Issue Date 0309 UNT1100 Series Introduction The Unitary (UNT) controller (UNT1100 Series) is a digital controller with applications for air handling units,
More informationStarzone 4000 Master Control Panel Figure 2.1 Master Control Panel
Starzone 4000 Master Control Panel Figure 2.1 Master Control Panel The heart of the Starzone 4000 system is the Starzone Master controller (SZM-4000). Each AHU that is to be zoned will have its own SZM-4000
More informationIntesisBox. v.1.3. User Manual Issue Date: 04/2016. IntesisBox PA-RC2-MBS-4
IntesisBox PA-RC2-MBS-4 v.1.3 MODBUS RTU (EIA485) Interface for Panasonic and Sanyo air conditioners. Compatible with ECOi and PACi line models. User Manual Issue Date: 04/2016 Order Codes: PA-RC2-MBS-4
More informationBM ADAPTER BAC-HD150. Air-conditioner Control System. Instruction Book. Contents
Air-conditioner Control System BM ADAPTER BAC-HD150 Instruction Book Contents BACnet is a registered trade mark of ASHRAE (American Society of Heating, Refrigerating, and Air-Conditioning Engineers, INC.).
More informationBACnet Flow Controller for Fan Filter Units
MANUAL SERVICE + INSTALLATION BACnet Flow Controller for Fan Filter Units BFC Series v300 Issue Date: 08/23/17 2017 Price Industries Limited. All rights reserved. TABLE OF CONTENTS Product Overview General
More informationWARNING. KMC BACnet Module Kits IMPORTANT! CONTROLS KITS AND ACCESSORIES
CONTROL KIT AND ACCEORIE 507042-01 6/2013 upersedes 2/2013 Litho U..A. KMC BACnet Module Kits Installation Instructions for BACnet Module Kits (96W14, 96W15 and 96W16) used with KG/KC/KH Rooftop Units
More informationREMOTE CONTROLLER RG57 Function Selection Manual
REMTE CNTRLLER RG57 Function Selection Manual www.mundoclima.com Thank you very much for purchasing our products. Please read this manual carefully before using the remote controller. RG57B2/BGE CL94774
More informationMVS RAIL ELECTRONIC FAN SPEED CONTROLLER. Mounting and operating instructions
DIN RAIL ELECTRONIC FAN SPEED Mounting and operating instructions Table of contents SAFETY AND PRECAUTIONS 3 PRODUCT DESCRIPTION 4 ARTICLE CODES 4 INTENDED AREA OF USE 4 TECHNICAL DATA 4 STANDARDS 5 WIRING
More informationIntesisBox KNX - BACnet/IP Client
IntesisBox KNX - BACnet/IP Client Gateway for integration of BACnet/IP devices into KNX control systems. Integrate Daikin VRV Air Conditioners into your KNX system. Daikin VRV system must be equipped with
More information76 F. Ductless Split Air Conditioner. YR-E16b Wired Controller User Manual WARNING
Ductless Split Air Conditioner YR-E16b Wired Controller User Manual Set temp. 76 F Indoor temp. 70 F Indoor humidity 32%RH Qty. online Standby Defrost Master Outdoor temp. 36 F Outdoor humidity 32%RH Mode
More informationRegister Map: Ecoflair Indirect Air Economizer
Register Map: Ecoflair Indirect Air Economizer Notes: 1. 16-bit registers (INT16, UINT16, ENUM) are transmitted MSB first (i.e., big-endian). 2. INT32 and UINT32 are most-significant word in n+0, least
More informationCRAGG RAILCHARGER Instruction Manual for 10DTC-12V 20DTC-12V 30DTC-24V 40DTC-12V 60DTC-12V
CRAGG RAILCHARGER for 10DTC-12V 20DTC-12V 30DTC-24V 40DTC-12V 60DTC-12V Contents 1 Warnings, Cautions, and Notes... 1 2 Description... 2 3 Features... 2 3.1 STANDARD FEATURES... 2 3.2 CHARGER REGULATION...
More informationtsense User Manual CO 2 -, temperature- and relative humidity transmitter Gas and Air Sensors
Gas and Air Sensors User Manual tsense CO 2 -, temperature- and relative humidity transmitter Table of contents General. 1 Display menu... 2 Measured values.. 2 CO 2 /Temperature/Humidity... 2 Limit settings.
More informationBACnet Protocol Implementation Conformance Statement
BACnet Protocol Implementation Conformance Statement Date: December 1 st, 2015 Vendor Name: Danfoss A/S Product Name: VLT HVAC Drive FC-102 Product Model Number: FC-102 Applications Software Version: 1.6
More informationSER8300 / SE8300 Series BACnet Integration Terminal Equipment Controller
1 BACnet Integration Terminal Equipment Controller Commercial and Lodging HVAC Applications BACnet CONTROLLER 2 BACnet Integration Manual SER8300 AND SE8300 SERIES PROTOCOL IMPLEMENTATION CONFORMANCE STATEMENT
More informationBB5-Lite TECHNICAL MANUAL
BB5-Lite TECHNICAL MANUAL Product Support 1800 354 434 CC - BB5 - LITE LITE with Plug & Play technology www.blackbox.net.au Designed by IAS in Brisbane Made in Australia Product Support 1800 354 434 www.ias.net.au
More informationIntesisBox PA-AW-MBS-1 v.2.0
IntesisBox PA-AW-MBS-1 v.2.0 Modbus RTU (EIA485) Interface for Panasonic Aquarea series. User Manual Issue Date: 08/2014 r2.0 Order Code: PA-AW-MBS-1: Modbus RTU Interface for Panasonic Aquarea series
More informationQUICK SETUP GUIDE. BCM2 Series Branch Circuit Monitors. Safety Information. Equipment Maintenance and Service. Product Overview. Raritan DANGER!
QUICK SETUP GUIDE BCM2 Series Branch Circuit Monitors Safety Information DANGER! HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH Follow safe electrical work practices. See NFPA 70E in the USA, or applicable
More informationInstallation, operating and maintenance ADALINK II. Web solution for LENNOX units supervision ADALINK II-IOM-1401-E. lennoxemeia.
Installation, operating and maintenance ADALINK II Web solution for LENNOX units supervision ADALINK II-IOM-1401-E lennoxemeia.com CONTENT 1 INTRODUCTION 1.1 - ADALINK II system description... 3 2 INSTALLATION
More informationSEZ7656R1045B / SEZ7656H1045B
SEZ7656R1045B / SEZ7656H1045B Installation Guide f BACnet MS-TP RTU / HP Room Controllers F Commercial Zoning Systems CONTENTS Installation 2 Location 2 Installation 2 BACnet System Overview 3 Terminal,
More informationBACnet-over-Ethernet (BACnet TCP/IP) Gateways for Modbus RTU Devices
Issue Date March 1, 2018 BMGE Series BACnet-over-Ethernet (BACnet TCP/IP) Gateways for Modbus RTU Devices General The BMGE Series BACnet-over-Ethernet (BACnet TCP/IP) gateways, which route communication
More informationAdditional features include: Slab Minimum and Slab Maximum Temperature Control. Test Sequence to Ensure Proper Component Operation
LR 58233 E150539 LR 58233 E150539 70 70 WWSD - Data Brochure Zone ontrol 369 D 369 10/00 The Zone ontrol 369 is designed to control the temperature in up to six heating zones using Room Temperature Units
More informationVTR8300 / VT8300 Series BACnet Integration Terminal Equipment Controller
BACnet Integration Terminal Equipment Controller Commercial and Lodging HVAC Applications BACnet CONTROLLER 2 BACnet Integration Manual VTR8300 and VT8300 series Protocol Implementation Conformance Statement
More informationENERGY-INTELLIGENT TECHNOLOGY HEATING AND COOLING SYSTEMS INTELLIGENT TOUCH MANAGER ONE FOR ALL ADVANCED MULTI-ZONE CONTROLLER
ENERGY-INTELLIGENT TECHNOLOGY HEATING AND COOLING SYSTEMS 08.16 INTELLIGENT TOUCH MANAGER ONE FOR ALL ADVANCED MULTI-ZONE CONTROLLER Intelligent Touch Manager The intelligent Touch Manager (itm) is an
More informationInstallation Instructions. Procon IP-32M wir-1_ MITSUBISHI ELECTRIC
Installation Instructions Procon IP-32M 2371-wir-1_2-0204 MITSUBISHI ELECTRIC Procon IP-32M Overview The Procon IP-32M unit provides an interface between a Mitsubishi City-Multi G50A controller with up
More informationCentral Controller Operation & Installation Manual
Central Controller Operation & Installation Manual YCZ-A004 CONTENT Function introduction of central controller... 1 Part info for central controller... 2 Page & Key Explanation... 4 Address Setting When
More informationintelligent TOUCH MANAGER ONE FOR ALL ADVANCED MULTI-ZONE CONTROLLER
intelligent TOUCH MANAGER ONE FOR ALL ADVANCED MULTI-ZONE CONTROLLER intelligent Touch Manager 2+ The intelligent Touch Manager (itm) is an advanced multi-zone controller that controls and monitors the
More informationMANUAL INSTALLATION. Multi-Variable Monitor. MVM Series. Issue Date: 02/07/ Price Industries Limited. All rights reserved.
MANUAL INSTALLATION Multi-Variable Monitor MVM Series Issue Date: 02/07/18 2018 Price Industries Limited. All rights reserved. TABLE OF CONTENTS Product Overview General...1 MVM Specifications...1 Included
More informationKNX is a European Standard Protocol used for household and industrial Buliding Management System (BMS).
PRODUCT NEWS Products News: New HC-A16KNX PAGE 1 / 8 Summary 1. This advanced product news introduces the new product HC-A16KNX. 2. The details are indicated in the description. Description 1. Applicable
More informationRXTP ROOM TEMPERATURE
ROOM TEMPERATURE CONTROLLER WITH PI CONTROL Mounting and operating instructions Table of contents SAFETY AND PRECAUTIONS 3 PRODUCT DESCRIPTION 4 ARTICLE CODES 4 INTENDED AREA OF USE 4 TECHNICAL DATA 4
More informationOWNER S MANUAL WIRE CONTROLLER OF AIR CONDITIONER. MODEL: KJR-12B/DPBG(T)-E Brivis Part No:B026000
OWNER S MANUAL WIRE CONTROLLER OF AIR CONDITIONER MODEL: KJR-12B/DPBG(T)-E Brivis Part No:B026000 Brivis Climate Systems Pty Ltd Tel:1300 BRIVIS brivis.com.au Thank you very much for purchasing our product.
More informationFrigoPack FU+ New Generation of Intelligent Refrigeration Inverters
FU+ New Generation of Intelligent Refrigeration Inverters Efficient and Energy-saving Control of Refrigeration Compressors and Condenser Fans www.frigokimo.com Effective speed control saves energy and
More informationVRF Control System. Judy Ouyang Technical Support Engineer
VRF Control System Judy Ouyang Technical Support Engineer Individual Centralized BMS Gateway Intelligent Control PC/Network 1 Individual control 2 Centralized control 1.1 Wireless controllers 1.2 Wired
More informationDTS 310. DIN Rail Mounted, Indoor Rated Revenue Grade Electrical Sub-meter. Page 1. Measurlogic MQ A
DTS 310 DIN Rail Mounted, Indoor Rated Revenue Grade Electrical Sub-meter Page 1 1 PRODUCT OVERVIEW... 3 1.1 SUPPLIED ITEMS... 3 1.2 DOCUMENT CONVENTIONS... 4 1.3 PRODUCT SPECIFICATION... 4 1.3.1 Current
More informationBACnet P.I.C.S. For RDT900 configurable controllers. Protocol Implementation Conformance Statement
BACnet P.I.C.S. Protocol Implementation Conformance Statement For RDT900 configurable controllers ENGLISH Code 148RDT900SAU page 1 of 28 page 2 of 28 Important Read this document thoroughly before installation
More informationSystem Controls Suggested Specification
1. Description A. Rooftop Unit Controller The Rooftop Unit Controller shall come equipped with a proportional-integral (PI) controller for accurate temperature control. The rooftop unit controller shall
More informationTC-9102 Terminal Controller
Metasys Network Sales Resource Manual 635 Application Specific Controllers Section Product Bulletin Issue Date 1095 TC-9102 Terminal Controller The TC-9102 Terminal Controller, the latest addition to the
More informationCoolPlug CooLinkHub HVAC Bridge. Quick Installation Guide
Bridge Quick Installation Guide Warning Read and understand the following Safety Guidelines and Warnings to ensure a safe installation Failure to follow WARNING may result in injury or death. This equipment
More informationCDD3 Duct Carbon Dioxide Detector with BACnet
Mounting The duct type sensor installs on the outside of a return air duct with the sampling tube inserted into the duct. Use the included foam plug to prevent air from entering the enclosure through the
More informationTracer Controls. Tracer ZN517 Unitary Controller BAS-PRC012-EN
Tracer Controls Tracer Unitary Controller 7 April 2003 BAS-PRC012-EN Introduction The Tracer unitary controller provides digital control that is similar to that of a wall thermostat. It supports the following
More informationBACnet MS/TP Gateways for Mega Controls Modbus RTU Networking Devices
BMG Series Issue Date March 1, 2018 BACnet MS/TP Gateways for Mega Controls Modbus RTU Networking Devices General The BMG Series is a BACnet network gateway which routes communication traffic between BACnet
More informationCDD3 Space Carbon Dioxide Detector with BACnet
Mounting The room type sensor installs directly on a standard electrical box and should be mounted five feet from the floor of the area to be controlled. Do not mount the sensor near doors, opening windows,
More informationRTD-W Installation Instructions
RTD-W Installation Instructions 0V +V POWER 15-24VDC 0V S1 S2 S3 0V S4 S5 S6 English RTD-W Installation Instructions 100.00 RTD-W Control Interface realtime Control Systems 24VAC/30VDC, 1A REMC P1 P2 RS485
More informationCommandCenter Operator Panel
CommandCenter Operator Panel Introduction This document describes the different features of the Operator Panel (local or remote) that is used with the Seresco units. Startup Screens When the unit start
More informationS66 Series Electronic Fan Speed Control
FANs 121, 125, 1628.3 Product/Technical Bulletin S66 Issue Date 0918 S66 Series Electronic Fan Speed Control The S66 Series Electronic Fan Speed Control is designed to modulate the speed of single-phase,
More informationVT8600 Series Installation Guide. Rooftop Unit, Heat Pump and Indoor Air Quality Controller
VT8600 Series Installation Guide Rooftop Unit, Heat Pump and Indoor Air Quality Controller 2 Installation Guide VT8600 Series If replacing an existing Room Controller, label wires before removal of Controller.
More informationOperation Guide CT100
Operation Guide CT100 PG 1 The CT100 communicating Z-Wave thermostat operates via a high-quality, easy-to-use touch screen. To set or adjust your CT100, simply touch your finger firmly to the screen. The
More informationQUICK SETUP GUIDE. BCM2 Series Branch Circuit Monitors. Safety Information. Equipment Maintenance and Service. Raritan DANGER!
QUICK SETUP GUIDE BCM2 Series Branch Circuit Monitors Safety Information DANGER! HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH Follow safe electrical work practices. See NFPA 70E in the USA, or applicable
More informationBCM2 Series Branch Circuit Monitors Quick Setup Guide
BCM2 Series Branch Circuit Monitors Quick Setup Guide Safety Information DANGER! HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH Follow safe electrical work practices. See NFPA 70E in the USA, or applicable
More informationMODBUS AND BACNET COMMUNICATION INSTRUCTIONS
100275719_2000534455_Rev A MODBUS AND BACNET COMMUNICATION INSTRUCTIONS Power-Fin Models: 2500-5000 WARNING This manual must only be used by a qualified heating installer / service technician. Read all
More informationSeries P215PR/RM Direct- and Remote-Mount Pressure-Actuated Condenser Fan Speed Controllers for Single-Phase Motors
European Refrigeration Controls Catalogue Catalogue Section 4 Product Bulletin P215PR/RM Issue August 2016 Series P215PR/RM Direct- and Remote-Mount Pressure-Actuated Condenser Fan Speed Controllers for
More informationInstallation Manual INTELLIGENT SERVER. Model name: BMS-LSV6UL
Model name: BMS-LSV6UL INTELLIGENT SERVER Thank you very much for purchasing this TOSHIBA INTELLIGENT SERVER. Please read this manual carefully beforehand for proper installation of the SERVER. NOTE This
More informationDWYER INSTRUMENTS, INC. Series AVUL Air Velocity Transmitter. Specifications - Installation and Operating Instructions.
Series AVUL Air Velocity Transmitter Specifications - Installation and Operating Instructions Bulletin P-AVUL 3-49/64 [95.71] 2-43/64 [67.92] 1/2 NPS 3-3/16 [80.81] 1-19/32 [40.59] 31/32 24.58 3-33/64
More informationWireless Remote Controller Kit
INSTALLATION MANUAL Wireless Remote Controller Kit LS BRC4C8 Read these instructions carefully before installation. Keep this manual in a handy place for future reference. This manual should be left with
More informationCOMFORT CONTROL CENTER SERVICE INSTRUCTIONS
USA SERVICE OFFICE Dometic Corporation 2320 Industrial Parkway Elkhart, IN 46516 574-294-2511 CANADA Dometic Corporation 46 Zatonski, Unit 3 Brantford, ON N3T 5L8 CANADA 519-720-9578 For Service Center
More information