Common Departures Interconnecting Facilities Requirements
|
|
- Blaze Chambers
- 6 years ago
- Views:
Transcription
1 Welcome to our e-rew Express. In our last issue, we discussed the common departures on metering installation requirements. This time, we would like to discuss the common departures on the customer low voltage main switch and interconnecting facilities requirements. We hope you can avoid these departures when you prepare your installation for connection of supply. We hope you will find the information of this e-rew Express useful and handy. If you have any suggestion, please send an to us at or contact our Customer Installation Section at so that we can further improve our service. Common Departures on Customer Low Voltage Main Switch and Interconnecting Facilities Requirements 1. Main Incomers i. Protection Scheme The time-current curve of overcurrent protection of customer main incomer directly connected to transformer cannot grade with HK Electric infeed protection. The type and setting of customer main incomer s protective devices shall be graded properly with HK Electric infeed protection.
2 ii. Switches Directly Connected to Transformer Main Incomer Essential Main Switch 35kA 45kA The short circuit breaking capacity of the switch directly connected to transformer is inadequate. Short circuit breaking capacity of the switch directly connected to transformer shall exceed 40kA. The switch directly connected transformer shall not be of fixed type. to Draw-out type or plug-in type circuit breaker shall be used. 2
3 iii. Undervoltage Protection Undervoltage Protective Device Undervoltage Protective Device Undervoltage protective devices should not be installed at main switches or switches affecting more than one customer / equipment. Undervoltage protective devices should be installed at the load side only in order to avoid unnecessary supply interruption to other equipment / customers. 2. Customer Main Switch i. Main Switch Position A customer main switch shall not be installed after HK Electric s meter. A customer main switch shall be installed and connected immediately before HK Electric s meter. 3
4 ii. Single Phase Installation A single pole switch cannot be used as a main switch for single phase installation. A main switch for single phase installation shall be of double-pole type interrupting live and neutral. iii. 3-phase Installation Neutral Link Neutral link in the neutral conductor of a 3-pole main switch for 3-phase installation has not been provided. A main switch for 3-phase installation shall be of 4-pole or TPN switch. If 3-pole linked switch or circuit breaker is used, a link shall be inserted in the neutral conductor and securely fixed by bolts or screws. iv. Temporary Installation or Overhead Line Supply A MCB shall not be used as the main switch for the installation which is supplied from an overhead line installation or for temporary installation. A RCD shall be used as the main switch for the installation which is supplied from an overhead line installation or for temporary installation. 4
5 3. Riser Switch Earth fault relay associated with protection C.T.s could be used to achieve automatic disconnection within 5 seconds during an earth fault. 4. An instantaneous trip RCD should not be used as riser switch or cutout of multi- customer premises. Interconnecting Circuit Breakers Between Two or More Supply Sources i. Section Switch Overcurrent protection of the section switch has not been provided. With Overcurrent Protection The section switch shall be provided with proper overcurrent protection. ii. Changeover Switch A 3-pole changeover switch shall not be used for interconnecting the normal and standby sources. 5 A mechanically and electrically interlocked 4-pole changeover switch should be used for interconnecting the normal and standby sources to ensure that neutral unbalance and fault currents return to the correct source of supply.
6 iii. LV Service Cables No interconnecting facilities between HK Electric s LV service cables are allowed. We are pleased to provide advisory services to REC/REW regarding the customer low voltage main switch and interconnecting facilities arrangement. Please provide us with the schematicc wiring diagram. We will study and feedback our comment or suggestion to you. 6
Wiring diagrams. Content. Information for reading and graphic symbols... 5/2. Wiring diagrams of the circuit-breakers... 5/3
Wiring diagrams Content Information for reading and graphic symbols... 5/2 Wiring diagrams of the circuit-breakers... 5/3 Electrical accessories... 5/4 5/1 Information for reading and graphic symbols State
More informationDocument C0. Use for:
Date: July 27, 2015 Document C0 Use for: Connection of Electric Generation that will operate with an Open Transition (Category 1) between the Ameren System and the Generator or operate with a Synchronized
More informationSECTION DISCONNECT SWITCHES
SECTION 16440 DISCONNECT SWITCHES PART 1 - GENERAL 1.01 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and other Division 01 Specification
More informationDIN Series MINIATURE CIRCUIT BREAKERS, RESIDUAL CURRENT CIRCUIT BREAKERS. Introducing the DIN Series High-quality, high-performance circuit breakers
DIN Series MINIATURE CIRCUIT BREAKERS, RESIDUAL CURRENT CIRCUIT BREAKERS Introducing the DIN Series High-quality, high-performance circuit breakers Features (1) All models fully comply with IEC regulations
More informationRCDs RCBOs MCBs Isolating Switches Switchboards
RCDs RCBOs MCBs Isolating Switches Switchboards 1300 722 275 F: 1300 738 717 RCD 4 Pole 6KA RCDs monitors at all times the current flow and will cut the electrical supply in case of an imbalance. Suitable
More informationMiCOM P122C Time-Overcurrent Protection
Protection Relays 01 MiCOM P122C Time-Overcurrent Protection Customer Benefits 1A/5A software setting 4 function keys Compact unit for flush and wall-surface mounting Comprehensive measurements Disturbance
More informationC C CIRCUIT-BREAKERS Moulded-case (MCCB), general. 1. Introduction. 2. General description
CIRCUIT-BREAKERS C C81-21 CIRCUIT-BREAKERS - Contents 1. Introduction 2. General description 3. Rated voltages 3.1 Rated operational voltage (U e ) 3.2 Rated impulse withstand voltage (U imp ) 3.3 Rated
More informationBLUE 3 INSTALLATION GUIDE
BLUE 3 INSTALLATION GUIDE CATCH Power BLUE 3 Installation manual - Page 1 IMPORTANT This product must be installed by a licensed electrician. This product must be installed according to the AS3000 Australian
More informationMG24434 Supplementary Protector SUPPLEMENTARY PROTECTOR, 240VAC, 16A, CIRCUIT BREAKER TYPE: STANDARD
United States MG24434 Supplementary Protector SUPPLEMENTARY PROTECTOR, 240VAC, 16A, CIRCUIT BREAKER TYPE: STANDARD Product Information Features and Specifications For Use With: OEM Panels Approvals: UL
More informationSwitchgear FEATURE. Basler Electric Company
Switchgear LIFe ExtenSIon: Replacement of electromechanical Overcurrent Relaying By Todd Martin, Basler Electric Company Chemical Facility U p d at i n g S w i t c h g e a r R e l ay s Electromechanical
More informationMULTI 9 System Catalog UL Recognized C60N Supplementary Protectors
UL Recognized C60N Supplementary Protectors B Curve C60N Supplementary Protectors 1 MG24110 MG24125 MG24140 MG24155 15 MG17406 MG17436 MG17461 1.2 MG17402 MG17432 16 MG24118 MG24133 MG24148 MG24163 1.5
More informationApplication Techniques CENTERLINE 2100 Motor Control Centers
POWER SYSTEM CONSIDERATIONS FOR PRODUCT SELECTION Application Techniques CENTERLINE 2100 Motor Control Centers Power System Considerations for Product Selection i Power System Considerations for Product
More informationEnhancing Reliability of Legacy Systems with New Generation Low-Voltage Circuit Breaker Upgrades
Enhancing Reliability of Legacy Systems with New Generation Low-Voltage Circuit Breaker Upgrades May 2012 / 1910DB1202 by Hal Theobald, Product Manager, Schneider Electric Services and Reza Tajali, P.E.,
More informationEDS LONDON 33KV DISTRIBUTION NETWORK DESIGN AND CUSTOMER SUPPLIES
Network(s): Summary: ENGINEERING DESIGN STANDARD EDS 08-0150 LONDON 33KV DISTRIBUTION NETWORK DESIGN AND CUSTOMER SUPPLIES LPN This standard provides guidelines for the development of the 33kV distribution
More informationMiCOM P521. Fast Feeder Differential Protection
01 Fast Feeder Differential Protection The relay provides high-speed two-ended current differential unit protection of overhead lines and underground cables in applications such as ring mains and parallel
More informationIssued February DATA SHEET 5SX2 MCB. Based on Siemens Industrial Control Catalog
Issued February 2011 DATA SHEET 5SX2 MCB Based on Siemens Industrial Control Catalog General Data Trip characteristics Tripping characteristics acc. to EN 60 898 Tripping characteristic A, -5 Type A characteristic
More informationB60 Domestic Voltage Optimisation Unit. Installation Manual
Govna B60PVM Voltage Optimisation Unit Govna B60PVM Voltage Optimisation Unit B60 Domestic Voltage Optimisation Unit Web: www.renewableenergyhub.co.uk Email: info@renewableenergyhub.co.uk Phone: 0845 862
More informationSACE Emax 2 Specification guide
SACE Emax 2 Specification guide Specification Number: 26 01 20.17 Product Name: LOW VOLTAGE POWER CIRCUIT BREAKERS PART 1 GENERAL NOTE: ( ) Indicates option or a selection is to be made for quantity or
More informationSECTION ENCLOSED SWITCHES AND CIRCUIT BREAKERS
SECTION 262816 - ENCLOSED SWITCHES AND CIRCUIT BREAKERS PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division
More informationCDW7. Standard: IEC Application. Standard and certification. International standard: IEC Approved certification: CB, CE, KEMA
Application Applied to power distribution of AC Hz/60Hz, rated operational voltage 400/ 690V, rated current 200A~6300A and lower For power distribution and protecting circuit and power supply equipment
More information4.3. Switchboards. Contents Description Pow-R-Line Drawout Molded Case Circuit Breaker Switchboards Product Selection...
.3 Product Description Drawout molded case circuit breaker switchboard Front accessible Front connected Through-the-door design drawout mechanism through 600A Insulated case UL 89 breakers up to 200A Visual
More informationB60 Domestic Voltage Optimisation Unit
B60 Domestic Voltage Optimisation Unit Installation Manual V1.2 Nov 2013 1 P a g e PRODUCT ADVISORY NOTICE This product must be installed by a competent person in accordance with the IEE Wiring Regulations,
More informationTP&N DISTRIBUTION BOARD TYPE B RANGE
GROUP Now included in the range: Extension Boxes Metering Kits Surge Suppression and more! TP&N DISTRIBUTION BOARD TYPE B RANGE A comprehensive distribution board range for modern commercial & industrial
More informationSENTRON. Protective devices Selectivity for 3VA molded case circuit breakers. Introduction. Selectivity - terms and definitions
Introduction 1 Selectivity - terms and definitions 2 SENTRON Methods of implementing selectivity using circuit breakers 3 Protective devices Selectivity for 3VA molded case circuit breakers Configuration
More informationTransfer Switches 5.1 Transfer Switch Equipment Product Selection Guide... Product Description... Application Description...
.1 Transfer Switch Equipment Product Selection Guide.................................... Product Description....................................... Application Description......................................2
More informationMULTI 9 System Catalog UL Recognized NC100H Supplementary Protectors
B Curve NC100H Supplementary Protectors Rating 1P 2P 3P 4P 80 MG27164 MG27175 MG27186 MG27197 MULTI 9 System Catalog UL Recognized NC100H Supplementary Protectors C Curve NC100H Supplementary Protectors
More informationMiniature. Circuit Breakers. reliable solutions for protection of installations against over-current phenomenon. Advantages for you : Technical data :
Miniature Circuit Breakers reliable solutions for protection of installations against over-current phenomenon Advantages for you : Bi-connect terminals for simultaneous termination of bus bar & wires Unique
More informationBulletin Installation of solar photovoltaic systems Rules , , , , and
Bulletin 64-5-0 Installation of solar photovoltaic systems Rules 64-060, 64-200, 64-214, 84-020, 84-024 and 84-030 Scope (1) Introduction (2) Disconnecting means (a) Disconnecting means for solar photovoltaic
More informationSentron 3VT circuit breakers Simply Smart: First choice for power distribution
s Sentron 3VT circuit breakers Simply Smart: First choice for power distribution www.siemens.com/industry Sentron 3VT Molded Case Circuit-Breakers - 10-1600Amperes With the standard line of 3VT molded-case
More informationMiCOM P521. Fast feeder differential protection
01 Fast feeder differential protection The relay provides high-speed two-ended current differential unit protection of overhead lines and underground cables in applications such as ring mains and parallel
More informationPowerPact Q-Frame Molded Case Circuit Breakers and Switches (Types QB, QD, QG and QJ)
PowerPact Q-Frame Molded Case Circuit Breakers and Switches (Types QB, QD, QG and QJ) Catalog Class 0CT00R/0 0 CONTENTS Description..............................................Page Description.............................................
More informationSPM Series Plug-in Surge Protection
SPM Series Plug-in Surge Protection The SPM series of modular surge protection devices provides protection of equipment connected to incoming low voltage AC power supplies against the damaging effects
More informationJtec 10kA Miniature Circuit Breaker
Jtec 0kA Miniature Circuit Breaker EN 60898 The Jtec range has been enthusiastically adopted by a diverse range of customers seeking a cost effective 0kA performance. Jtec MCBs are available in a wide
More informationSpectra RMS Circuit Breakers with microentelliguard Trip Units
GE Energy Industrial Solutions Spectra RMS Circuit Breakers with microentelliguard Trip Units Greater system coordination, arc flash protection and reliability for new equipment and retrofit applications
More information60103 Circuit Breaker
6003 Circuit Breaker United States MINIATURE CIRCUIT BREAKER, 20/240VAC, 2A, CIRCUIT BREAKER TYPE: STANDARD Image not available Product Information Features and Specifications Circuit Breaker Type: Standard
More informationPROCEDURE FOR TESTING P122 THREE PHASE OVERCURRENT & EARTH FAULT PROTECTION RELAY S.E.P TRAINING CENTRE
PROCEDURE FOR TESTING P122 THREE PHASE OVERCURRENT & EARTH FAULT PROTECTION RELAY INDEX CHAPTER 1: 1. INTERFACING PC WITH RELAY 2. EXTRACTING SETTINGS FROM THE RELAY CHAPTER 2: 1. SETTING VALUES AS PER
More informationPRC Coordination of Protection Systems for Performance During Faults
PRC-027-1 Coordination of Protection Systems for Performance During Faults A. Introduction 1. Title: Coordination of Protection Systems for Performance During Faults 2. Number: PRC-027-1 3. Purpose: To
More informationIMP/ 001 / 014 Policy for the Protection of Distribution Networks
Version:- 1.1 Date of Issue:- July 2016 Page 1 of 39 IMP/ 001 / 014 Policy for the Protection of Distribution Networks 1. Purpose The purpose of this document is to detail the network protection philosophy
More information24973 Circuit Breaker MINIATURE CIRCUIT BREAKER, 440VAC, 10A, CIRCUIT BREAKER TYPE: STANDARD
United States 24973 Circuit Breaker MINIATURE CIRCUIT BREAKER, 440VAC, 10A, CIRCUIT BREAKER TYPE: STANDARD Image not available Product Information Features and Specifications Approvals: IEC 60947-2 Rated
More informationNPW800R RETROFITTING. Power and Volatge Protection Relay
RETROFITTING Power and Volatge Protection Relay NPW800R (R3 case) is dedicated to the refurbishment of CEE WTG 7000 relays (R3 case) providing the measurement of apparent (S), active (P) and reactive (Q)
More informationMiCOM P111. Three phase and earth fault overcurrent relays
Three phase and earth fault overcurrent relays The relays are suitable for all the application where overcurrent and/or earth-fault protection are required. Thanks to its favorable price vs technical features
More informationThe City of Winnipeg Dry Type Transformers up to 600 V Primary Section Bid Opportunity No Page 1 of 2
The City of Winnipeg Dry Type Transformers up to 600 V Primary Section 26121601 Bid Opportunity No. 1196-2014 Page 1 of 2 Part 1 General 1.1 RELATED REQUIREMENTS.1 Section 26 05 01 - Common Work Results
More informationElectrical Service Change-Tn Neenah
Electrical Service Change-Tn Neenah Permit # Owners name Project address Contractors name Contractors address Fax #: Type of occupancy Job description New construction Main panel Single phase Additional
More information3 Design of the electrical installation protection system
J - Protection against voltage surges in LV 3 Design of the electrical To protect an electrical installation in a building, simple rules apply for the choice of b (s); b its protection system. 3.1 Design
More informationPower systems 5: Protection
Power systems 5: Protection Introduction In this series of articles, we will be looking at each of the main stages of the electrical power system in turn. As you will recall from our Introduction to Electrical
More information(Above 100km Distance) (Streetlight Pole) (Above 100km Distance) (Streetlight Pole)
Part 9 Miscellaneous Drawing Register Number Description M1-1 SSN Network Device with LV Aerial Supply (ABC) Arrangement M1-2 SSN Network Device with LV Aerial Supply Arrangement M1-3 SSN Network Device
More informationMemshield Overcurrent Protection Relay (AOR1B)
(AOB) Multi-function Protection Device Local and remote trip indication AO-B type OCs are available with trip indications. Two types of trip indication function are available: single contact type and individual
More informationStandard Development Timeline
Standard Development Timeline This section is maintained by the drafting team during the development of the standard and will be removed when the standard becomes effective. Description of Current Draft
More informationCoordination of Surge protection devices
Coordination of Surge protection devices Design guide Surge arresters for commercial and industrial buildings Surge protection devices: how to choose them? coordination How to choose surge protection devices?
More informationmcbs, EQUIPMENT NEW PRODUCTS 2014 Voltage surge protectors & other control and signalling devices Time & light sensitive switches
NEW P. 4 RX3 MCBs 63 A 4500 & 6000 prong type busbar MCBs, RCDs, add-on modules & accessories P. 9 DX3 RCBOs 63 A 6000 / 10 ka AC, A & Hpi type prong & fork type busbar P. 16 DX3 MCBs 63 A 50 ka mcbs,
More informationSPECIFIC INTERCONNECTION PROTECTION REQUIREMENTS... 5
Central Hudson Gas & Electric Corporation (CHG&E) Interconnection Protection Requirements for Distributed Generators of Greater than 300 kva Connected in Parallel with the CHG&E Electrical Delivery System
More informationPower-Style QED-2, Series 2 Low Voltage Switchboards
Power-Style QED-2, Series 2 Low Voltage Switchboards Catalog 2742CT1001 (Addendum to 2742CT9501R12/09) 2010 Class 2742 CONTENTS Description............................................. Page Features...................................................
More informationMPSC Microprocessor-based protection and metering devices for low voltage power circuit breakers. ABB Power Distribution
MPSC-2000 Microprocessor-based protection and metering devices for low voltage power circuit breakers ABB Power Distribution Introduction For circuit breaker protection, metering and communications, the
More information7000 SERIES Power Switching Solutions. Closed Transition Transfer Switching. Delayed Transition Transfer Switching
7000 SERIES Power Switching Solutions Fig. 2: Four pole, Closed Transition Switch rated 1000 Amperes in Type 1 enclosure. Closed Transition Switching Closed Transition Switches feature main contacts that
More informationMiniature Circuit-Breaker IEC Series 8562
> 1 to 3 pole versions > Rated current from 0.5... 40 A > 6 or 10 ka breaking capacity to DI VDE 0641, respectively E 60898 > Isolating Function to E 60947-2 > Permanently set thermal and magnetic trips
More information.2 Section General Commissioning (Cx) Requirements. .3 Section Common Work Requirements - Electrical
Issued for Review Section 26 28 16.01 Air Circuit Breakers Page 1 of 7 PART 1 GENERAL 1.1 GENERAL.1 This specification serves to define requirements for a replacement of low voltage circuit breaker of
More informationSubstation Automation Products. Line differential protection RED670 Relion 670 series
Substation Automation Products Line differential protection RED670 Relion 670 series For maximum reliability of your power system The RED670 IED (Intelligent Electronic Device) is designed for protection,
More informationElectrical Demand Specification (Reference SOP: )
Project: Equipment Description: Location: Equipment No.: Project No: Protocol No.: Content Index 1. GENERAL...3 Design Standards...3 1.1. Standards...3 2. DESIGN...3 2.1. Safety...3 2.2. Circuit protection...3
More informationPLT. Breaker-based transfer switch open, closed or soft transition amps. Specification sheet
Specification sheet PLT Breaker-based transfer switch open, closed or soft transition 800 3000 amps Description PLT breaker-based transfer switches are designed for operation and switching of electrical
More informationMiniature Circuit Breakers for Railway Applications
Siemens AG 00 for Railway Applications BETA Low-Voltage Circuit Protection The miniature circuit breakers are used in fixed railway systems and rolling stock for protecting system components against overcurrent
More informationPOWER GRID AUTOMATION. Pág.. n. RMU Automation
POWER GRID AUTOMATION RMU Automation Distribution Network Non-Controlled Secondary Distribution Systems Distribution Network RMU Automation - Levels RMU Automation - RTU / FRTU SMART CONTROLLER Monitoring
More informationSPM Series Plug-in Surge Protector Type 2/3 (Test Class II/III) Single & Three Phase Surge Arresters
The SPM series of modular surge protection devices provides protection of equipment connected to incoming low voltage AC power supplies against the damaging effects of transient over voltages caused by
More informationNew Functions and Integrated Communication Capability. The new SENTRON 3VL ETUs SENTRON 3VL. Answers for industry.
New Functions and Integrated Communication Capability The new SENTRON 3VL ETUs SENTRON 3VL Answers for industry. For 3VL2 and 3VL3, the tripping solenoid is integrated in the ETU Undervoltage release 3
More informationSurge Protective Device
SURGE PROTECTIVE DEVICE Surge Protective Device 20 R 320 Type Max. discharge current Imax/Iimp (ka) Number of poles (P) R: with alarm auxiliary contact Blank: without alarm auxiliary contact Max. continuous
More informationMasterpact NW Restricted Earth Fault Protection
Masterpact NW Restricted Earth Fault Protection Date: November 2011 Page 1 of 12 Contents Introduction 3 Principle of Operation 4 Equipment Required 5 Installation of the Neutral CT 5 Connection of the
More informationSection 4 Ground-Fault Protection Devices
Multi 9 System Catalog Section 4Ground-Fault Protection Devices Section 4Ground-Fault Protection Devices Selection Table The Multi 9 System includes one UL Listed and three IEC rated product families that
More informationUser Manual. AQ-F215 Simulator
User Manual AQ-F215 Simulator Instruction manual AQ-F215 Simulator 2 (28) Revision 1.00 Date 16.5.2014 Changes N/A Revision 1.01 Date 13.3.2018 Changes Updated visual look Readability improvements Instruction
More information5.1. Motor Protection and Monitoring. Contents. Product Overview. Monitoring Relays. D64R Series Digital Ground Fault Relays...
.1 Ground Fault Relays and Monitors Contents Description Current.................. Phase................... Voltage.................. Ground Fault Relays and Monitors D64R Series Digital Ground Fault Relays....
More informationvoltage surge protectors low voltage type 1 (class I / B) voltage surge protectors low voltage type 2 (class II / C) Distribution board protection
voltage surge protectors low voltage type 1 (class I / B) voltage surge protectors low voltage type 2 (class II / C) 030 23 030 28 039 21 039 33 039 34 Type 1 voltage surge protectors (V.S.P.) for main
More informationVAMP 221. Table of Contents
2 V221/EN M/E019 VAMP 221 Table of Contents Table of Contents 1. General... 7 1.1. VAMP 221 arc protection system components... 7 1.1.1. Central unit VAMP 221... 9 1.1.2. I/O units VAM 12L / VAM 12 LD,
More informationB60 PVM Domestic Voltage Optimisation Unit. Installation Manual
Installation Manual V2.2 November 2015 PRODUCT ADVISORY NOTICE This product must be installed by a competent person in accordance with the IEE Wiring Regulations, BS7671 (17th Edition or later) and current
More informationREL52002 Easergy P3U30, 4L, 4U, 16DI/8DO, Uaux: V, DI: V, RS-485
Characteristics Easergy P3U30, 4L, 4U, 16DI/8DO, Uaux: 48-230V, DI: 220-230V, RS-485 Main Range of product Product or component type Relay application Device short name [Us] rated supply voltage Type of
More informationGround Fault Current Protection Devices Prevent Costly Production Shutdowns
Ground Fault Current Protection Devices Prevent Costly Production Shutdowns Figure.1 Altech s three new series deliver multiple capabilities. In all three series, ground fault sensitivity levels range
More informationB60 Domestic Voltage Optimisation Unit. Installation Manual
Installation Manual V2.2 June 2015 PRODUCT ADVISORY NOTICE This product must be installed by a competent person in accordance with the IEE Wiring Regulations, BS7671 (17th Edition or later) and current
More informationElectrical Integration of PV Systems. Ridha Hamidi, Ph.D.
Electrical Integration of PV Systems Ridha Hamidi, Ph.D. 1 Many articles in the NEC are applicable to the electrical integration of a PV system, particularly Article 690. 2 The NEC defines the various
More informationResidual Current Devices. Residual Current Devices FRCmM-NA according to UL1053 & IEC/EN 61008
Residual Current Devices FRCmM-NA according to UL1053 & IEC/EN 61008 Wide range of compact types of RCDs serving as fault-current and additional protection according to UL1053 & IEC/EN 61008 standards,
More informationInstructions Order No. 3ZX1812-0WN60-0AC0 /
as copy and fax form Instructions Order. 3ZX1812-0WN60-0AC0 / 9239 9916 176 SIEMENS 3W... ID.:... OK! Caution! Dangerous high voltage! Dangerous storage spring! De-energize the equipment and secure against
More informationSR489 SR489. Generator Management Relay. Economical protection, metering, and monitoring functions for small and medium sized generators.
SR489 Generator Management Relay Economical protection, metering, and monitoring functions for small and medium sized generators. 1 Product Highlights Inputs / Outputs Generator Protection Power Metering
More informationINSTITUTE OF TESTING AND CERTIFICATION (INDIA) PVT. LTD.
(INDIA) VT. LTD. 5. INCOMING SULY CONDUCTOR TERMINATIONS AND DEVICES FOR DISCONNECTING AND SWITCHING OFF 5.1 Incoming supply conductor terminations The electrical equipment of the machine shall have only
More informationOTEC Miniature Circuit Breakers (MCB) OTEC Miniature Circuit Breakers (MCB) OTEC Miniature Circuit Breakers (MCB) Areas of Application
Miniature Circuit Breakers Areas of Application Miniature circuit breakers (MCBs) of the N-System primarily protect cables and conductors against overload and short circuit. Thus, they also protect electrical
More informationREL52001 Easergy P3U30, 4L, 4U, 16DI/8DO, Uaux: V, DI: V, 2 x RJ-45
Characteristics Easergy P3U30, 4L, 4U, 16DI/8DO, Uaux: 48-230V, DI: 220-230V, 2 x RJ-45 Main Range of product Product or component type Relay application Configuration type (Cortec) [Us] rated supply voltage
More informationSECTION TRANSIENT VOLTAGE SUPPRESSION FOR LOW-VOLTAGE ELECTRICAL POWER CIRCUITS
SECTION 264313 - TRANSIENT VOLTAGE SUPPRESSION FOR LOW-VOLTAGE ELECTRICAL POWER CIRCUITS PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and
More informationPowerpact 4 panelboards Panelboards and incoming devices Panelboards
Panelboards and incoming devices Panelboards Panelboards MG25C2 250A 13 way powerboard 506.76 MG25C4 250A 17 way powerboard 534.00 MG2C5 250A 5 way panelboard 620.33 MG2C7 250A 7 way panelboard 650.83
More informationRemote communication options include IEC Ethernet communications or Modbus (RS485).
2019 The MELPRO D series relay is suitable for feeder protection, motor protection and transformer protection applications. The relay offers multiple step time grading for over-current protection co-ordination.
More informationProducts Portfolio. Pole mounted Vacuum Recloser
Products Portfolio Pole mounted Vacuum Recloser Efacec Switchgear Efacec Switchgear is a leading company in Portugal and a worldwide reference in the development of solutions for power generation, transmission,
More information1. Distribution panelboards. 2. Lighting and appliance branch-circuit panelboards. 3. Load centers. 4. Electronic-grade panelboards.
SECTION 26 24 16 - PANELBOARDS PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification Sections,
More informationPower System Protection Training
Power System Protection Training Contact us Today for a FREE quotation to deliver this course at your company?s location. https://www.electricityforum.com/onsite-training-rfq Refresh your knowledge of
More informationSECTION DISTRIBUTION SWITCHBOARDS
PART 1 - GENERAL 1.1 DESCRIPTION: SECTION 26 24 11 This section specifies the furnishing, installation, and connection of the distribution switchboards. 1.2 RELATED WORK: A. Section 13 05 41, SEISMIC RESTRAINT
More information4. CIRCUIT BREAKERS. Functional Emergency Switching
4. CIRCUIT BREAKERS The circuit breaker/disconnector fulfils all of the basic switchgear functions, while, by means of accessories, numerous other possibilities exist. As shown in table H2-19 the circuit
More informationLiebert AccuVar (ACV Series) Surge Protective Device (SPD) (With Noise Filtering) GUIDE SPECIFICATIONS for a Parallel Surge Suppression System
Liebert AccuVar (ACV Series) Surge Protective Device (SPD) (With Noise Filtering) GUIDE SPECIFICATIONS for a Parallel Surge Suppression System Part 1 General 1.01 Summary A. These specifications describe
More information1510 MOTOR CONTROLLERS
SECTION 262913- MOTOR CONTROLLERS PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of contract, including general and supplementary conditions and Division 1 specification section,
More informationßCompliant with Amendment 3 ßBSEN for easy cabling. accommodate RCBOs. meeting current standards
CHINT EUROPE (UK) LTD Chint Metal Consumer Units ßCompliant with Amendment 3 of BS 7671 : 2008 Regulation 421.1.201 ßBSEN 61439-3 3 to 36 Ways are Standard Specials to Customer Requirements ß 1mm steel
More informationQUICK REFERENCE PRICE GUIDE JUNE 2016
QUICK REFERENCE PRICE GUIDE JUNE 2016 OUR CUSTOMER CARE COMMITMENTS Quality is Guaranteed All products supplied from this Quick Price Guide carry a guarantee against defects in materials and workmanship
More informationResidual Current Devices drcm Digital
Digital Line voltage independent RCCB for fault or additional protection with additional digital features. System Monitoring: Preventive information / warning before the RCD trips in case of leakage currents.
More informationZone-Selective Interlocking Field Testing and Commissioning
GE Energy Connections DEH-583 Instruction Guide Zone-Selective Interlocking Field Testing and Commissioning For EntelliGuard* and microentelliguard* Trip Units 2 Table of Contents 1. Overview... 4 2. ZSI
More informationPRC System Protection Coordination Supplementary Reference
PRC-001-2 System Protection Coordination Supplementary Reference Contents: Disclaimer... 2 Generator Protection Devices or Elements that May Require Coordination with Transmission or Distribution Protective
More informationTECHNICAL SPECIFICATION FOR MEDIUM VOLTAGE METAL-CLAD SWITCHGEAR (15 KV)
1.1 DESCRIPTIONS OF WORK A. The Bidder shall furnish and install the equipment as specified herein and as shown on the contract drawings. B. The switchgear and circuit breakers shall be manufactured by
More information11 kv Indoor Switchgear - SCADA Controlled
Specification 11 kv Indoor Switchgear - SCADA Controlled Important Warning This document is one of a set of standards developed solely and specifically for use on the rail network owned or managed by the
More informationDescription. Installation. Power supply
Air circuit breakers Special versions Series MEGT07 0V/500V/DC 50 up to 5000 A The air circuit breakers MEGT07 are suitable for use as disconnecting switch in DC distributions up to a rated voltage of
More information3- and 4-pole switching in UPS installation
Smart tricks to improve power supply reliability White paper series Power Distribution & UPS 3- and 4-pole switching in UPS installation Janne Paananen Technology Manager, Critical Power Solutions, Eaton
More information