CHAPTER 7 Copper Cable Testing

Size: px
Start display at page:

Download "CHAPTER 7 Copper Cable Testing"

Transcription

1 CHAPTER 7 Copper Cable Testing Lesson Objective After completing this lesson, you should be able to: i. Explain the various terms and instruments used to test copper cabling system. Cable Testing Cables can be tested with many different types of testing devices. The most common type of device to perform complete testing is a certification field tester. Certification field testers are the most common testing devices for certifying cabling systems. These testing devices are useful in the identification of improperly installed or terminated communication cables like continuity tester. A certification field tester is a comprehensive testing and certification device. It can perform basic continuity testing, and it can also perform more comprehensive performance testing. A certification field tester is used to certify installed cabling links to ensure that these cabling links will support high speed networks. EC2023PA: Cabling Technology Page1 1

2 Why need to test cable? Cable testing is an organized and systematic process of verifying that communication cables are installed and terminated correctly. Cable testing is performed with cable testing devices to confirm that the installation complies with the projects requirements and industry cabling standards. Cable testing is required to confirm that the installation was performed correctly and that the installed cables will provide reliable operation. Cable testing confirms that current applications will successfully work over the new cable system. It also provides performance specifications that will verify that the cables will support future applications as well. The process of testing communication cables includes: Visual inspection of the cables and the cable termination. Continuity testing Performance testing Wire Map test Attenuation test Visual Inspection The visual testing is the first step in testing a newly installed cabling system. The cabling system must be visually inspected after the installation is completed, to verify that the communication cables are installed in the cable pathways correctly. The cables must be supported properly in the cable pathways. The cables terminations must be visually inspected. The visual inspection must confirm that the cables are terminated in the correct location. It must also confirm that the correct color code was followed and the correct termination technique was used for the installation. Continuity Testing The second phase of testing the cabling system is performing complete continuity testing. Communication cables must have continuity to complete an electrical path for communication signals to flow between communication system devices. Communication cables are usually multi pair cables. Each cable pair is terminated to different pairs of a connecting hardware component to conform to a specific modular outlet configuration. EC2023PA: Cabling Technology Page1 2

3 Continuity testing will check the electrical path from one end of the cable to the other. A continuity test will also check to verify that the wires are terminated in the correct position and in the correct order. Performance Testing The last phase of testing the newly installed cabling is to conduct performance testing on all of the communication cables. Performance testing will determine if the installed communication cables will exhibit low attenuation and low crosstalk resistance. Performance testing will confirm that the correct components and the proper installation techniques were used during the installation. Performance test characterize the installed cable. They provide an indication of whether the installed communication cables provide a reliable transmission path for communication signals. EC2023PA: Cabling Technology Page1 3

4 Wire Map test Security Technology Department Chapter 7 The first requirement for the successful transmission of communication signals over communication cables is end to end continuity of the cable pairs. Correct continuity of the communication cable pairs requires that the pairs are strictly connected across the cable link. This means that the wire connected to pin 1 should be connected to pin 1 on the patch panel in the telecommunications room. Wire Map Open An open is a condition where a single wire or multiple wires do not provide continuity from one end of a link to the other. This condition is normally signified by an O next to a pin on a wire map graphic. EC2023PA: Cabling Technology Page1 4

5 Twisted pair cables should have complete continuity for all eight conductors (four pairs) across the cable link. If an open condition is identified for one wire of a twisted pair cable, check all the connection points for the wire showing open. If all wires of the cable are showing open condition, verify that the correct cable is being tested. Wire Map Short A short is a condition where two or more wires from a cable are connected ahead of where they should normally be connected in the circuit. This condition is normally identified by a line showing more than one pin of the outlet being electrically connected together. Twisted pair horizontal cables should not have any shorts in the cable link. If a short condition is identified by the testing device, check the terminations at the patch panel and work area outlets. Two wires may be terminated in the same termination slot. If the problem cannot be identified in the terminations, visually inspect the horizontal cable and all the patch cables in the link. Your visual inspection may identify that a cable s jacket may be torn or pinched. If this is the case, the damaged cable should be damaged. Wire Map Reversed Pair A reversed pair is a condition where the two wires of a pair are connected to the wrong pins. A reversed pair condition would mean that a signal transmitted on pin 1 would end up on pin 2 on the opposite end of the cable. The cable tester would show two lines crossed. EC2023PA: Cabling Technology Page1 5

6 Wire Map Crossed pair Security Technology Department Chapter 7 A crossed pair is a condition where the wires of a pair are connected to the wrong location on a modular outlet. The tester would show the two lines of a cable pair being terminated on different pins on the opposite end of the link. Attenuation Test Attenuation is defined as the reduction of transmitted signal due to the resistance encountered by the signal as it is traveling down a cable. An attenuation test is a measure of the amount of signal loss in the cable and connecting hardware of a cable link. Attenuation causes signals to shrink as they travel along a cable. Attenuation is measured in decibels (dabs). The dbs rating is specified per unit length of cable (usually 100m). The higher the attenuation db value, the greater the attenuation (signal loss) and the weaker the received signal. When measuring for attenuation, the lower the db values the better. The two primary causes of attenuation on a twisted pair cables are the Length of the cable Frequency of the transmitted signal over the cable Troubleshooting Failed Cables When a communicating cable is tested and the test result is a failure, the cause of the failure must be identified and corrected. Many times the cause of a failure for a cable performance test is the result of using an incorrect quality component. Another common cause of cable test failures is untwisting cable pairs. EC2023PA: Cabling Technology Page1 6

7 The following steps should be followed for troubleshooting communication cables. 1. Determine the exact cabling problem and verify if it is actually cable related. 2. Perform a visual inspection looking for anything unusual. 3. Use the cable testing devices and perform tests. 4. Break the cable segments into smaller parts and test each part. 5. Verify the correct cable and connectors were used. 6. Check for improper installation practices. 7. Replace suspect equipment or work area patch cords. 8. Look out for any damaged cable. 9. Look for any sources of interference close to the cable. 10. Check if there are any excessive cable distances. EC2023PA: Cabling Technology Page1 7

ANSI/TIA-568-C Cat 6A Field Test Specifications

ANSI/TIA-568-C Cat 6A Field Test Specifications This document has been prepared to aid consultants or engineers in developing contractual specifications covering the certification of Category 6A Permanent Links. It is offered as a general guide. Suitability

More information

ANSI/TIA-568-C Cat 6 Field Test Specifications

ANSI/TIA-568-C Cat 6 Field Test Specifications This document has been prepared to aid consultants or engineers in developing contractual specifications covering the certification of Category 6 Permanent Links. It is offered as a general guide. Suitability

More information

SECTION TELECOMMUNICATIONS TESTING AND DOCUMENTATION

SECTION TELECOMMUNICATIONS TESTING AND DOCUMENTATION SECTION 17045 TELECOMMUNICATIONS TESTING AND DOCUMENTATION PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including Facilities Management Design and Construction

More information

PANGEN SYSTEM WARRANTY. Warranty Guide

PANGEN SYSTEM WARRANTY. Warranty Guide PANGEN SYSTEM WARRANTY Warranty Guide C2-10270 PANGEN SYSTEMWARRANTY GUIDE PROGRAM OUTLINE TABLE OF CONTENTS: MATERIALS PAGE # Program Outline 2 Table of Contents Warranty Information 3 Introduction &

More information

Cabling Infrastructure

Cabling Infrastructure Introduction Ethernet Banking on Structured Cabling Technology Drivers Classification of Cables Fibre-optic cable Cables in building Cabling Infrastructure Cabling systems address the networking requirements

More information

ISO/IEC 11801: (E)

ISO/IEC 11801: (E) ISO/IEC 11801:2002-09 (E) Information technology_- Generic cabling for customer premises CONTENTS FOREWORD...10 INTRODUCTION...11 1 Scope...13 2 Normative references...13 3 Definitions, abbreviations and

More information

Cable Certification. General Testing Criteria (Applies to all cable certification testing) Attachment F Cable Certification

Cable Certification. General Testing Criteria (Applies to all cable certification testing) Attachment F Cable Certification General Testing Criteria (Applies to all cable certification testing) 1. RCIT reserves the right to be present during any or all cable testing procedures. The Contractor shall obtain authorization from

More information

CERTIFICATION PLUS SM

CERTIFICATION PLUS SM CERTIFICATION PLUS SM SYSTEM WARRANTY PROGRAM Panduit Warranty Guide PROGRAM OUTLINE TABLE OF CONTENTS: MATERIALS PAGE # Program Outline 2 Table of Contents Warranty Information 3 Introduction & Installation

More information

Copper Riser And Intrabuilding Cabling

Copper Riser And Intrabuilding Cabling Copper Riser And Intrabuilding Cabling PART 1: GENERAL The Contractor is held responsible to be familiar with the provisions contained herein and with other Sections of this Specification as applicable

More information

CTS2134 Introduction to Networking. Module : Troubleshooting

CTS2134 Introduction to Networking. Module : Troubleshooting CTS2134 Introduction to Networking Module 10.1 10.3: Troubleshooting Troubleshooting Methodology Facts 1. Identify the symptoms and potential causes. 2. Identify the affected area and determine how large

More information

Course Outline 11/6/ Santa Teresa Blvd Gilroy, CA COURSE: CSIS 274 DIVISION: 50 ALSO LISTED AS: SHORT TITLE: TELECOM/NETWK CABLE

Course Outline 11/6/ Santa Teresa Blvd Gilroy, CA COURSE: CSIS 274 DIVISION: 50 ALSO LISTED AS: SHORT TITLE: TELECOM/NETWK CABLE 5055 Santa Teresa Blvd Gilroy, CA 95020 Course Outline COURSE: CSIS 274 DIVISION: 50 ALSO LISTED AS: TERM EFFECTIVE: Fall 2011 Inactive Course SHORT TITLE: TELECOM/NETWK CABLE LONG TITLE: Telecommunication

More information

Chapter 3 Certifying Twisted Pair Cabling

Chapter 3 Certifying Twisted Pair Cabling Chapter 3 Certifying Twisted Pair Cabling Setting the Reference The reference procedure sets a baseline for insertion loss, ELFEXT, and dc resistance measurements. Run the tester s reference procedure

More information

ANSI/TIA/EIA-568-B Cabling Standard

ANSI/TIA/EIA-568-B Cabling Standard 83 Pair Numbers and Color Coding The conductors in a UTP cable are twisted in pairs and color coded so that each pair of wires can be easily identified and quickly terminated to the appropriate pin on

More information

Physical Layer V What does the physical layer provide?

Physical Layer V What does the physical layer provide? SEMESTER 1 Chapter 8 Physical Layer V 4.0 90 Points 8.1.1 What does the physical layer provide? What are the four elements of delivering frames across the media? 8.1.2 What are the three basic forms of

More information

Appendix 1 to the R&Mfreenet Warranty Program

Appendix 1 to the R&Mfreenet Warranty Program Appendix 1 to the R&Mfreenet Warranty Program 1 R&M Certification Process The R&Mfreenet certification process is three pillars: a) Adherence to applicable standards, both for products and installations;

More information

PANGEN INDUSTRIAL AUTOMATION SYSTEM WARRANTY

PANGEN INDUSTRIAL AUTOMATION SYSTEM WARRANTY PANGEN INDUSTRIAL AUTOMATION SYSTEM WARRANTY WARRANTY GUIDE PANGEN INDUSTRIAL AUTOMATION SYSTEM WARRANTY WARRANTY GUIDE PROGRAM OUTLINE TABLE OF CONTENTS: MATERIALS PAGE # Program Outline 2 Table of Contents

More information

CNE301 Network I Lab 04 Building a cross-over cable and configuring back2back network.

CNE301 Network I Lab 04 Building a cross-over cable and configuring back2back network. CNE301 Network I Lab 04 Building a cross-over cable and configuring back2back network. # Student ID Student Name Grade (10) 1-1 / 10 - Build a Crossover Cable Objective Build a Category 5 or Category 5e

More information

REPORT INTERTEK TESTING SERVICES, INC.

REPORT INTERTEK TESTING SERVICES, INC. REPORT INTERTEK TESTING SERVICES, INC. 3933 US ROUTE 11, CORTLAND, NEW YORK 13045 ORDER NO.: J20042193-406 DATE: March 19, 2001 REPORT NO.: J20042193-004 RENDERED TO: Tyco Electronics 3700 Reidsville Rd.

More information

Standards Update. by Paul Kish NORDX/CDT

Standards Update. by Paul Kish NORDX/CDT Standards Update by Paul Kish NORDX/CDT Standards overview Category 5e cabling new transmission parameters patch cord return loss Category 6 cabling cable choices backwards compatibility Summary Outline

More information

1. Which layer of the OSI model is responsible for specifying the encapsulation method used for specific types of media?

1. Which layer of the OSI model is responsible for specifying the encapsulation method used for specific types of media? CCNA 1 Chapter 4 v5.0 Exam Answers 2015 (100%) 1. Which layer of the OSI model is responsible for specifying the encapsulation method used for specific types of media? application transport data link physical

More information

Enterprise Network Test Strategies for Network Availability and Performance. A Sitaramaiah Director Fluke Networks India

Enterprise Network Test Strategies for Network Availability and Performance. A Sitaramaiah Director Fluke Networks India Enterprise Network Test Strategies for Network Availability and Performance A Sitaramaiah Director Fluke Networks India 1 Why is Enterprise Network Testing becoming increasingly important? IT is increasingly

More information

Family of Cords SYSTIMAX. Structured Cabling Systems. Quality Stranded and Solid Cords That Connect Data and Voice Circuits

Family of Cords SYSTIMAX. Structured Cabling Systems. Quality Stranded and Solid Cords That Connect Data and Voice Circuits SYSTIMAX Structured Cabling Systems Family of Cords Quality Stranded and Solid Cords That Connect Data and Voice Circuits Lucent Technologies Family of Stranded Cords includes 110 patch, modular and adapter

More information

Common Mistakes Made in Certification Specifications and Testing. Jim Davis Regional Marketing Engineer Fluke Networks

Common Mistakes Made in Certification Specifications and Testing. Jim Davis Regional Marketing Engineer Fluke Networks Common Mistakes Made in Certification Specifications and Testing Jim Davis Regional Marketing Engineer Fluke Networks Common Mistake #1 Failing to specify a Permanent Link test #1 Permanent Link or Channel?

More information

ANSI/TIA/EIA-568-B A P P E N D I X TECHNICAL INFORMATION. Contents ANSI/TIA/EIA-568-B. anixter.com

ANSI/TIA/EIA-568-B A P P E N D I X TECHNICAL INFORMATION. Contents ANSI/TIA/EIA-568-B. anixter.com A The urpose: stablish a generic telecommunications cabling standard that will support a multivendor environment nable the planning and installation of a structured cabling system for commercial buildings

More information

COMPUTER ENGINEERING AND INFORMATION TECHNOLOGY DEPARTMENT NETWORK LABORATORY. Ethernet Cabling

COMPUTER ENGINEERING AND INFORMATION TECHNOLOGY DEPARTMENT NETWORK LABORATORY. Ethernet Cabling Experiment number :(1) Ethernet Cabling Introduction:- The EIA/TIA (Electronic Industries Association and the newer Telecommunications Industry Alliance) is the standards body that creates the Physical

More information

White Paper: Installing Data Networks Using LinkWare Live SaaS

White Paper: Installing Data Networks Using LinkWare Live SaaS White Paper: Installing Data Networks Using LinkWare Live SaaS White Paper: Installing Data Networks Using LinkWare Live SaaS Software as a Service (SaaS) continues to grow in popularity across a wide

More information

T-Monitor E-Monitor TABLE OF CONTENTS SECTION 1 - DESCRIPTION...2 SECTION 2 - SPECIFICATIONS...3 SECTION 3 - INSTALLATION...5

T-Monitor E-Monitor TABLE OF CONTENTS SECTION 1 - DESCRIPTION...2 SECTION 2 - SPECIFICATIONS...3 SECTION 3 - INSTALLATION...5 T-Monitor E-Monitor TABLE OF CONTENTS SECTION - DESCRIPTION... SECTION - SPECIFICATIONS...3 SECTION 3 - INSTALLATION... SECTION - FRONT PANEL INDICATORS...7 SECTION - INTERFACE SIGNALS AND CABLES...8 SECTION

More information

Tarleton State University. Specifications

Tarleton State University. Specifications Tarleton State University Campus Communication Infrastructure Specifications Cabling Standards Summary This document identifies Tarleton State University communication infrastructure standards. The communication

More information

SECTION COMMON WORK RESULTS FOR COMMUNICATIONS

SECTION COMMON WORK RESULTS FOR COMMUNICATIONS PART 1 - GENERAL SECTION 270500 - COMMON WORK RESULTS FOR COMMUNICATIONS 1.1 RELATED SECTIONS A. All division 27 work shall, in addition to all division 1 specification sections, comply with all of the

More information

COMMON WORK RESULTS FOR COMMUNICATIONS

COMMON WORK RESULTS FOR COMMUNICATIONS SECTION 270500 - COMMON WORK RESULTS FOR COMMUNICATIONS PART 1 - GENERAL 1.1 RELATED SECTIONS A. All division 27 work shall, in addition to all division 1 specification sections, comply with all of the

More information

ANSI/TIA/EIA-568-B Cabling Standard

ANSI/TIA/EIA-568-B Cabling Standard 73 ANSI/TIA/EIA-568-B Cabling Standard In the mid-1980s, consumers, contractors, vendors, and manufacturers became concerned about the lack of specifications relating to telecommunications cabling. Before

More information

10GBASE-T and. Copper Cabling Choices

10GBASE-T and. Copper Cabling Choices 10GBASE-T and Copper Cabling Choices Agenda Cabling infrastructure planning recommendations Introduction to 10GBASE-T Evaluation of critical parameters What is Siemon 10G ip? Copper cabling recommendations

More information

Cables and Connectors

Cables and Connectors Module 2 Cables and Connectors Twisted Pair Two wires that carry the data signals (one conductor carries a positive signal; one carries a negative signal). Two wires are twisted to reduce the effects of

More information

The High Cost of a Low-Cost Cable Certification Tester

The High Cost of a Low-Cost Cable Certification Tester The High Cost of a Low-Cost Cable Certification Tester Our thanks to Fluke Networks for allowing us to reprint the following article. How much does it cost? That is typically the first question a cabling

More information

[0.057] 5.8 [0.23]

[0.057] 5.8 [0.23] Product Specification 7 March 13 Rev A1 SL Series Jacks, Category 6 1. SCOPE 1.1 Content This specification covers performance, tests and quality requirements for AMP NETCONNECT*, Category 6 SL Jacks used

More information

Dial Pulse Originating (DPO) Channel Unit Installation Guide

Dial Pulse Originating (DPO) Channel Unit Installation Guide Telecommunications Group Section 365 501 306 Equipment Issue 6 Third Printing, April 2001 3655-01 Dial Pulse Originating (DPO) Channel Unit Installation Guide CONTENTS PAGE Part 1. GENERAL.............................................................................

More information

Qualified Partner Programme QPP. Installation Practice Felice Guarna Wetzikon, July 2001

Qualified Partner Programme QPP. Installation Practice Felice Guarna Wetzikon, July 2001 Qualified Partner Programme QPP Installation Practice Felice Guarna Wetzikon, Why installation quality Product performance must be preserved by an accurate installation Long term warranty requires design

More information

Dr. Paulo Marin, EE/BSc, MSc, PhD. Electrical Engineer, ICT Consultant

Dr. Paulo Marin, EE/BSc, MSc, PhD. Electrical Engineer, ICT Consultant Is Cable Balancing Efficient i Enough for EMI Mitigation in Data Centers? Dr. Paulo Marin, EE/BSc, MSc, PhD. Electrical Engineer, ICT Consultant What are You going to Learn? What are the potential sources

More information

07. har-link Interface Connectors

07. har-link Interface Connectors . Interface Connectors The highest data rates in combination with perfect shielding characterize the connector. This way data can be passed on optimally within the control cabinet. The locking mechanism

More information

3 Chapter Introduction. 3.2 Copper Cable

3 Chapter Introduction. 3.2 Copper Cable 3 Chapter 3 3.1 Introduction The Network Media is the device that physically carries the data from computer to computer. The three major types of network media are: Copper Cable Fiber-Optic Cable Wireless

More information

Technical Committee. Addendum to ATM Physical Medium Dependent Interface Specification for 155 Mb/s Over Twisted Pair Cable (af-phy-0015.

Technical Committee. Addendum to ATM Physical Medium Dependent Interface Specification for 155 Mb/s Over Twisted Pair Cable (af-phy-0015. Technical Committee Addendum to ATM Physical Medium Dependent Interface Specification for 155 Mb/s Over Twisted Pair Cable (af-phy-0015.000) af-phy-0053.000 January 1996 af-phy-053.000 ATM Forum Technical

More information

Chapter 4: Network Access. Introduction to Networks v5.1

Chapter 4: Network Access. Introduction to Networks v5.1 Chapter 4: Network Access Introduction to Networks v5.1 4.0 Introduction 4.1 Physical Layer Protocols 4.2 Network Media 4.3 Data Link Layer Protocols 4.4 Media Access Control 4.5 Summary 2013 Cisco and/or

More information

White paper. Field Testing of Direct Attach Modified Permanent Links. occfiber.com

White paper. Field Testing of Direct Attach Modified Permanent Links. occfiber.com The dramatic growth of high-bandwidth wireless access points and other IP-enabled devices, such as surveillance cameras and building automation equipment has resulted in the practice of installing direct

More information

The six major components of a structured wiring system are:

The six major components of a structured wiring system are: OBJECTIVES 1. Describe various ANSI/TIA/EIA standards for commercial buildings and residential settings. 2. Discuss the specific Technical Systems Bulletins that can affect telecommunications installations.

More information

[0.057] 5.8 [0.23]

[0.057] 5.8 [0.23] Product Specification 7 June 13 Rev B SL Series Jacks, Category 6 1. SCOPE 1.1 Content This specification covers performance, tests and quality requirements for AMP NETCONNECT*, Category 6 SL Jacks used

More information

ELECTRICAL SUPPLY TROUBLESHOOTING QUICK GUIDE SAFETY PRECAUTIONS

ELECTRICAL SUPPLY TROUBLESHOOTING QUICK GUIDE SAFETY PRECAUTIONS ELECTRICAL SUPPLY TROUBLESHOOTING QUICK GUIDE 1. Circuit Breaker Tripping 2. Circuit Overload 3. Short Circuit 4. Ground Fault 5. Ground Fault Circuit Interrupter (GFCI) Tripping SAFETY PRECAUTIONS Basic

More information

GROUND FAULT CIRCUIT INTERUPTERS

GROUND FAULT CIRCUIT INTERUPTERS Title: GFCI Effective Date: 11/14/2014 Control Number: THG_0031 Revision Number: 1 Date: 10/21/2015 Annual Review Completed: 5/13/2015 GROUND FAULT CIRCUIT INTERUPTERS CONTENTS I. PURPOSE II. GENERAL REQUIREMENTS

More information

Installing The Loop Start Line Board In The FX Series Digital Communications System

Installing The Loop Start Line Board In The FX Series Digital Communications System R In The FX Series Digital Communications System Introducing The Loop Start Line Board Defining Loop Start The line board signals for the host system to complete a line connection by sending a supervisory

More information

07. har-link INTERFACE CONNECTORS

07. har-link INTERFACE CONNECTORS . INTERFACE CONNECTORS The highest data rates in combination with perfect shielding characterize the connector. This way data can be passed on optimally within the control cabinet. The locking mechanism

More information

USB 2.0 DIGI-USB2 1-Port USB m Category 5e/6/6a/7 Extender Set with Flexible Power. User Manual. Revision

USB 2.0 DIGI-USB2 1-Port USB m Category 5e/6/6a/7 Extender Set with Flexible Power. User Manual. Revision USB 2.0 DIGI-USB2 1-Port USB 2.0 100m Category 5e/6/6a/7 Extender Set with Flexible Power User Manual Revision 171213 Thank you for purchasing the USB 2.0 DIGI-USB2. Please read this guide thoroughly.

More information

Your Global Automation Partner. Bonded Pair Cable: Does it Have a Place in Factory Automation? White Paper - W1001

Your Global Automation Partner. Bonded Pair Cable: Does it Have a Place in Factory Automation? White Paper - W1001 Your Global Automation Partner Bonded Pair Cable: Does it Have a Place in Factory Automation? White Paper - W1001 As the manufacturing industry continues to become more communication-centric, it is relying

More information

Certification for 10G copper cabling

Certification for 10G copper cabling Certification for 10G copper cabling Presented by Eric Lie, Sales Manager 1 Introduction This presentation is intended to provide an overview of the 10GBASE-T requirements for cabling The applicable standards

More information

Artisan Technology Group is your source for quality new and certified-used/pre-owned equipment

Artisan Technology Group is your source for quality new and certified-used/pre-owned equipment Artisan Technology Group is your source for quality new and certified-used/pre-owned equipment FAST SHIPPING AND DELIVERY TENS OF THOUSANDS OF IN-STOCK ITEMS EQUIPMENT DEMOS HUNDREDS OF MANUFACTURERS SUPPORTED

More information

NGEAB-T Use Cases. Berlin, Germany February Chris DiMinico MC Communications/Panduit

NGEAB-T Use Cases. Berlin, Germany February Chris DiMinico MC Communications/Panduit NGEAB-T Use Cases Berlin, Germany February 2015 Chris DiMinico MC Communications/Panduit cdiminico@ieee.org 1 Scope Next Generation Enterprise Access BASE-T PHY Study Group to define use cases and deployment

More information

Copper Cabling Standards

Copper Cabling Standards Copper Cabling Standards White paper White Paper Copper Cabling Standards v2.0 EN 1 Introduction Standard specifications are the foundation upon which most cabling and networking projects are built. Professionals

More information

Please use the Q & A utility to ask us any questions concerning the material being presented.

Please use the Q & A utility to ask us any questions concerning the material being presented. Webinar Notes Please use the Q & A utility to ask us any questions concerning the material being presented. Please contact Brittany Socha on the chat line or email Brittany.socha@ikonixusa.com if you would

More information

COPPER-T EXTENDER TABLE OF CONTENTS SECTION 1 - DESCRIPTION SECTION 2 - SPECIFICATIONS... SECTION 3 - INSTALLATION

COPPER-T EXTENDER TABLE OF CONTENTS SECTION 1 - DESCRIPTION SECTION 2 - SPECIFICATIONS... SECTION 3 - INSTALLATION COPPER-T EXTENDER TABLE OF CONTENTS SECTION - DESCRIPTION...... SECTION - SPECIFICATIONS...... 3 SECTION 3 - INSTALLATION...... SECTION - FRONT PANEL INDICATORS... 7 SECTION - INTERFACE SIGNALS AND CABLES...

More information

12382 South Gateway Park Place, 700 Draper, UT

12382 South Gateway Park Place, 700 Draper, UT I N S T A L L A T I O N G U I D E AN-300 Structured Wiring Distribution Panel 12382 South Gateway Park Place, 700 Draper, UT 84020 1.801.617.3100 www.futuresmart.com Description Features The AN-300 Structured

More information

Connecting cables for valves, plug pattern ZC, metric screw Type codes

Connecting cables for valves, plug pattern ZC, metric screw Type codes Type codes NEBV Z4 WA 2 L R E 5 N M8 G 3 S1 Function NEBV Connecting cables for valves Connection technology on left, field device side Z4 Socket, plug pattern ZC, metric screw Cable outlet left WA Angled

More information

GSW-2453 Gigabit Chassis switch. User Guide

GSW-2453 Gigabit Chassis switch. User Guide GSW-2453 Gigabit Chassis switch User Guide Contents 1. INTRODUCTION... 1 Features... 1 Package Contents... 2 Ethernet Switching Technology... 2 2. HARDWARE DESCRIPTION... 4 Physical Dimension... 4 Front

More information

Introduction. Standards

Introduction. Standards Introduction LAN cable certifiers have been the go-to method of testing twisted pair cabling for nearly a quarter century, since the advent of 10Base-T on Class C/category 3 cabling to 10 MHz. This article

More information

With the publication. Make the right connection: Bonding a shielded system. installation

With the publication. Make the right connection: Bonding a shielded system. installation Make the right connection: Bonding a shielded system installation With the publication of the IEEE 802.3an 10GBase-T standard in 2006, Augmented Category 6 (i.e., Category 6A) cabling systems are being

More information

Communication Wiring Color Codes

Communication Wiring Color Codes Communication Wiring Color Codes Cat 5 & 5e Network Color Codes for RJ-45 Ethernet Plug Eight-conductor data cable (Cat 3 or Cat 5) contains 4 pairs of wires. Each pair consists of a solid color wire and

More information

INTERNATIONAL STANDARD

INTERNATIONAL STANDARD INTERNATIONAL TANDARD IEC 9- First edition 00-0 Generic cabling systems pecification for the testing of balanced communication cabling in accordance with IO/IEC 0 Part : Patch cords and work area cords

More information

JR3 EXTERNAL SENSOR ELECTRONICS WITH SERIAL DATA OUTPUT. JR3, Inc. 22 Harter Ave. Woodland, CA 95776

JR3 EXTERNAL SENSOR ELECTRONICS WITH SERIAL DATA OUTPUT. JR3, Inc. 22 Harter Ave. Woodland, CA 95776 JR3 EXTERNAL SENSOR ELECTRONICS WITH SERIAL DATA OUTPUT JR3, Inc. 22 Harter Ave. Woodland, CA 95776 5963B 13 October, 2003 TABLE OF CONTENTS CHAPTER 1 OVERVIEW General...1-1 Sensor...1-1 Electronic System...1-1

More information

BLACKBOX NETWORK SERVICES. one source for worldwide infrastructure services

BLACKBOX NETWORK SERVICES. one source for worldwide infrastructure services BLACKBOX NETWORK SERVICES one source for worldwide infrastructure services 24 Port 10/100Mbps plus 2 Gigabit TX/FX Auto-MDIX Modular Gigabit Ethernet Switch User s Manual FCC Warning This device has been

More information

Link Segment IEEE Mb/s Single Twisted Pair Ethernet Study Group Chris DiMinico MC Communications/Panduit

Link Segment IEEE Mb/s Single Twisted Pair Ethernet Study Group Chris DiMinico MC Communications/Panduit Link Segment IEEE 802.3 10 Mb/s Single Twisted Pair Ethernet Study Group hris DiMinico M ommunications/panduit cdiminico@ieee.org 1 Purpose Scope Initiate discussion(s) on 10 Mb/s Single Twisted Pair Ethernet

More information

Cable Sharing: An ANSI & ISO Recognized Solution for High Density, Low-Speed Applications. Robert Y. Faber Jr., RCDD/NTS.

Cable Sharing: An ANSI & ISO Recognized Solution for High Density, Low-Speed Applications. Robert Y. Faber Jr., RCDD/NTS. Cable Sharing: An ANSI & ISO Recognized Solution for High Density, Low-Speed Applications Broadband High-Speed LAN Voice Robert Y. Faber Jr., RCDD/NTS Minimum Port Recommendations TIA/EIA-568-B.1 2 outlets

More information

A FLUKE networks DTX 1800 Cable Analyzer és DTX Fiber Modules

A FLUKE networks DTX 1800 Cable Analyzer és DTX Fiber Modules A FLUKE networks DTX 1800 Cable Analyzer és DTX Fiber Modules Rövidített leírás és kezelési utasítás The DTX Series CableAnalyzers are rugged, hand-held instruments used to certify, troubleshoot, and document

More information

07. har-link Interface Connectors

07. har-link Interface Connectors . Interface Connectors The highest data rates in combination with perfect shielding characterize the connector. This way data can be passed on optimally within the control cabinet. The locking mechanism

More information

Ronald Tellas, Technology and Applications Manager, Enterprise Networking

Ronald Tellas, Technology and Applications Manager, Enterprise Networking Direct Connect Testing Guidelines Ronald Tellas, Technology and Applications Manager, Enterprise Networking Introduction Direct Connect is a viable option for the Digital Building that is being deployed

More information

Ethernet and PoE Operation Over Single Pair Twisted-Pair Copper Cabling (SPE) Chris DiMinico AEM Technical Sales Test and Measurement

Ethernet and PoE Operation Over Single Pair Twisted-Pair Copper Cabling (SPE) Chris DiMinico AEM Technical Sales Test and Measurement Ethernet and PoE Operation Over Single Pair Twisted-Pair Copper Cabling (SPE) Chris DiMinico AEM Technical Sales Test and Measurement Overview SPE is poised to enable a new class of low power devices that

More information

HCI 2017 Products Catalogue

HCI 2017 Products Catalogue HCI 27 Products Catalogue Publisher HSING CHAU INDUSTRIAL CO., LTD. 9Fl., No.39, Lane 53, Ruiguang Rd., Neihu District, Taipei City 492, Taiwan Tel: +886-2-8797- Fax: +886-2-8797-2388 Website: www.hci.com.tw

More information

10G Ethernet Over Structured Copper Cabling

10G Ethernet Over Structured Copper Cabling I T I n f r a s t r u c t u r e S o l u t i o n s Note: The following technical article was current at the time it was published. However, due to changing technologies and standards updates, some of the

More information

USB 2.0 RG2304GE-LAN. 4-Port USB 2.0 Gigabit Ethernet LAN Extender System. User Guide

USB 2.0 RG2304GE-LAN. 4-Port USB 2.0 Gigabit Ethernet LAN Extender System. User Guide USB 2.0 RG2304GE-LAN 4-Port USB 2.0 Gigabit Ethernet LAN Extender System User Guide Thank you for purchasing the USB 2.0 RG2304GE-LAN. Please read this guide thoroughly. This document applies to Part Numbers:

More information

INSTALLATION INSTRUCTIONS. ACB-100 Audio Control Board. This document describes the installation procedure for the ACB-100 Audio Control Board.

INSTALLATION INSTRUCTIONS. ACB-100 Audio Control Board. This document describes the installation procedure for the ACB-100 Audio Control Board. INSTALLATION INSTRUCTIONS MicroComm DXI -00 Audio Control Board. Intent & Scope This document describes the installation procedure for the -00 Audio Control Board. 2. Description The -00 Audio Control

More information

The AMP NETCONNECT Category 6 Cabling System

The AMP NETCONNECT Category 6 Cabling System The AMP NETCONNECT Category 6 Cabling System 2 Table of Contents TABLE OF CONTENTS...3 PERSPECTIVE...4 WHY INSTALL NEXT GENERATION CABLING SYSTEMS?...4 MEGAHERTZ VS. MEGABITS...4 PLANNING FOR THE FUTURE...5

More information

Optical Multiplexer. Quick Start Guide

Optical Multiplexer. Quick Start Guide Optical Multiplexer Quick Start Guide Part Number: 07M1195-QS, Rev. A Revised: February 12, 2009 Sales Office: +1 (301) 975-1000 Technical Support: +1 (301) 975-1007 E-mail: support@patton.com WWW: www.patton.com

More information

TO THE BID PACKAGE FOR COUNTY OF INYO NETWORK PROJECT. This addendum is being issued to modify portions of the Bid Package for the Project entitled:

TO THE BID PACKAGE FOR COUNTY OF INYO NETWORK PROJECT. This addendum is being issued to modify portions of the Bid Package for the Project entitled: ADDENDUM NO. 2 TO THE BID PACKAGE FOR February 6, 2006 This addendum is being issued to modify portions of the Bid Package for the Project entitled: Receipt of this Addendum should be acknowledged by inserting

More information

CATEGORY 6 PATCH BY EXCEPTION SOLUTION (PBE) Modules Frames and Covers Labelling and Accessories Patch Leads Cable Management

CATEGORY 6 PATCH BY EXCEPTION SOLUTION (PBE) Modules Frames and Covers Labelling and Accessories Patch Leads Cable Management CATEGORY 6 PATCH BY EXCEPTION SOLUTION (PBE) Modules Frames and Covers Labelling and Accessories Patch Leads Cable Management CLIPSAL DATACOMMS CATEGORY 6 PATCH BY EXCEPTION INTRODUCTION Category 6 Patch

More information

Jamey Calloway, RCDD Product Management Specialist Optical Cable Corporation

Jamey Calloway, RCDD Product Management Specialist Optical Cable Corporation Testing and deployment of direct attach and the impact of category 8 Thursday, 10 August 2017, 3:50-4:40 P.M. Jamey Calloway, RCDD Product Management Specialist Optical Cable Corporation Overview Traditional

More information

TABLE OF CONTENTS 1. Safety Instructions 2. Technical Specifications 3. Installation 4. How to Connect the Fixture 5. DMX512 Connections 6.

TABLE OF CONTENTS 1. Safety Instructions 2. Technical Specifications 3. Installation 4. How to Connect the Fixture 5. DMX512 Connections 6. TABLE OF CONTENTS 1. Safety Instructions 2. Technical Specifications 3. Installation 4. How to Connect the Fixture 5. DMX512 Connections 6. How to Set the Unit 7. DMX Configuration 8. IR Remote Control

More information

ADSL Loop Extender AER800-24P

ADSL Loop Extender AER800-24P Please read this document carefully before installation! ADSL Loop Extender AER800-24P (For AER800- C1P / C1PL) Installation Manual Version 3.0 Widearea Telecommunication Technology Co., Ltd Add: 2 nd,3

More information

TET TOKYO ELETECH CORPORATION. Instruction for use. - Small Interface Cable Adapter - SICA14C20Z-GA101

TET TOKYO ELETECH CORPORATION. Instruction for use. - Small Interface Cable Adapter - SICA14C20Z-GA101 Instruction for use - Small Interface Cable Adapter - 14C20Z-GA101 1. Product Overview By using this adaptor to place a pad near the micro controller, it is expected to reduce the area related to tool

More information

HANDBOOK OF CABLE TESTING

HANDBOOK OF CABLE TESTING Testing and Measurement Technology Fault Analysis Documentation and Reporting HANDBOOK OF CABLE TESTING Wire pert Cable Certifier WX4500 Best-in-Class Certifier for today and tomorrow. CAT 8 Ready! CAT8

More information

Lantech. IPES /100TX with 4 PoE Injectors 24~48VDC Industrial Switch. User Manual

Lantech. IPES /100TX with 4 PoE Injectors 24~48VDC Industrial Switch. User Manual Lantech IPES-0008-4 8 10/100TX with 4 PoE Injectors 24~48VDC Industrial Switch User Manual V1.00 Jun 2010 FCC Warning This Equipment has been tested and found to comply with the limits for a Class-A digital

More information

SYSTIMAX SCS Power Sum Solution

SYSTIMAX SCS Power Sum Solution SYSTIMAX SCS Power Sum Solution Superior Performance for CAT 5 Networks Realize the Full Potential of Your CAT 5 Network... You ve made a significant investment in your data network. Every component meets

More information

Start Here. Features. Model DS108 Dual Speed Hub Installation Giude

Start Here. Features. Model DS108 Dual Speed Hub Installation Giude Start Here The NETGEAR Model DS108 Dual Speed Hub is a network hub that enables users to mix and match 10 and 100 megabits per second (Mbps) devices on the same network. This capability eliminates the

More information

USB 2.0 RG2304 Network Series

USB 2.0 RG2304 Network Series USB 2.0 RG2304 Network Series 4-Port USB 2.0 Gigabit Ethernet LAN Extender Systems User Guide Thank you for purchasing the USB 2.0 RG2304N, 2304S or 2304GE-LAN. Please read this guide thoroughly. This

More information

Domestic Installation Manual

Domestic Installation Manual Domestic Installation Manual Chapter 5 Return Path Installation Implementation Approval Adam Brown Field Operations Quality Manager Documentation Owner Customer Installations ISSUE: V 5.3.1 IMPLEMENTATION

More information

Termination for 568A and 568B pin configurations.

Termination for 568A and 568B pin configurations. 1 Termination for 568A and 568B pin configurations. The four twisted pairs in Unshielded Twisted Pair (UTP) cabling terminate in eight-pin modular jacks. There are two different pin configurations permitted

More information

The advantages of the 6-connector channel

The advantages of the 6-connector channel APRIL 2007 The advantages of the 6-connector channel The advantage of sticking to standardised rules such as ISO11801 (that define the performance of the components, the performance of the whole cable

More information

Copper Certification Testing Best Practices Pocket Guide

Copper Certification Testing Best Practices Pocket Guide Copper Certification Testing Best Practices Pocket Guide Cabling certification is a best practice of world class installers because it shows the true quality of the installation and reduces the risk of

More information

Transmission Media :- It can be broadly classified into two types

Transmission Media :- It can be broadly classified into two types Transmission Media :- It can be broadly classified into two types - Guided Transmission Media:- in this type of media, a physical path is established between source and destination. The signal or electrical

More information

Your wiring expert NF-868

Your wiring expert NF-868 NF-868 Multipurpose LCD Display Cable Test & Inspection Instrument INSTRUCTION MANUAL Please read and learn safety instructions before use or maintain the equipment The tester uses 9V battery for power

More information

QuickLAN 6050 & Easy instrument for a preliminary LAN test

QuickLAN 6050 & Easy instrument for a preliminary LAN test QuickLAN 6050 & 6055 Easy instrument for a preliminary LAN test DESCRIPTION QuickLAN 6050 QuickLAN 6050 is ideal for all installers who need an easy instrument for a preliminary LAN test QuickLAN 6050

More information

Tone Generator and Probe

Tone Generator and Probe Tone Generator and Probe JUNE 2001 TS141A-R2 CUSTOMER SUPPORT INFORMATION Order toll-free in the U.S. 24 hours, 7 A.M. Monday to midnight Friday: 877-877-BBOX FREE technical support, 24 hours a day, 7

More information

Application & Electrical Performance. Category 5e Silver Solution

Application & Electrical Performance. Category 5e Silver Solution Application & Electrical Performance Category 5e Silver Solution CONTENTS Page No. Scope 3 Executive Summary 4 Transmission Test Method and Results 5-7 Electrical Test Method and Results 8-11 Definitions

More information

IBDN 110 Cross-Connect System

IBDN 110 Cross-Connect System IBDN 110 Cross-Connect System Connecting & Wiring Blocks Cross-Connect Kits Wall Mount Frame Kits Patch Cords Labels & Management Accessories For For A Complete End-to-End 110 Solution what s coming next.

More information

Deviser Part No.: TC500-DL Deviser Instruments, Inc. All rights reserved.

Deviser Part No.: TC500-DL Deviser Instruments, Inc. All rights reserved. TC500 Ethernet Cabling Certifier Operation Manual Version 1.13 Deviser Part No.: TC500-DL Deviser Instruments, Inc. All rights reserved. Warranty This instrument is guaranteed for a period of 2 years

More information