A36D/TPSD DNP 3.0 & Modbus SCADA INTERFACE

Size: px
Start display at page:

Download "A36D/TPSD DNP 3.0 & Modbus SCADA INTERFACE"

Transcription

1 SCADA INTERFACE INSTRUCTIONS - OPTION 21P / 21Q - FOR A36D/TPSD SYSTEMS A36D/TPSD DNP 3.0 & Modbus SCADA INTERFACE OPTION 21P / 21Q INSTRUCTIONS This manual is only valid for A36D/TPSD Chargers equipped with P60-205TS control cards with software version series 0100 and 1100 and P60-302S Communications Board with software version series 0600 CPN ISSUE DATE: ECN /10 ECN/DATE 106 BRADROCK DRIVE DES PLAINES, IL (847) FAX: (847) / / /10 INSTRUCTION DRAWING NUMBER: P25-LOPT21PQ-A36D-TPSD-9

2 Default Settings The LaMarche Communications Card is shipped with the following default settings; Protocol: Set per customer order (DNP 3.0, Modbus ASCII, Modbus RTU, Modbus TCP) Default: DNP 3.0 Comm Port: RS232 (J2) Baud Rate: 9600 Data Bits: Fixed at 8 Stop Bits: Fixed at 1 Parity: Fixed at None Flow Control: Fixed at None Node Address: 4 (0100 Series Software), 90 (1100 Series Software) IP Address: Netmask: Gateway: TCP Port Number: Fixed at for DNP, Fixed at 502 for Modbus Changing the Settings In all likelihood it will be necessary to change the settings from the factory default settings to properly integrate a new charger into your SCADA Network. To change the above settings one must enter the "Customer Calibration" mode. This is accomplished by pressing the switch that activates Equalize and holding it in the "up" position for 5 seconds. When the control card enters the Customer Cal mode the display will show "CAL" for 2 seconds. During the time the display shows "CAL" release the switch. The purpose of the Customer Cal is to allow one to change settings in the field. The following setting changes are allowed in the following order: Low DC Current Alarm Threshold Low DC Current Alarm Reset Threshold Low Voltage 1 Alarm Voltage Threshold High Voltage Alarm Voltage Threshold Equalize Timer Mode Equalize Cycle Time High Voltage Shutdown Alarm Voltage Threshold Temperature Compensation Enable Modbus Address Scada Remote Configuration Mode Scada Protocol Scada Node Address (MSB, B4) Scada Node Address (B3) Scada Node Address (B2 Scada Node Address (B1) Scada Node Address (LSB, B0) Scada Comm Port Scada Baud Rate (Only when Scada Comm Port is either RS232 or RS485) Scada IP Address Quad 3 (Only when the Comm Port is set to TCP) Scada IP Address Quad 2 (Only when the Comm Port is set to TCP) Page 2 of 26

3 Scada IP Address Quad 1 (Only when the Comm Port is set to TCP) Scada IP Address Quad 0 (Only when the Comm Port is set to TCP) Scada Netmask Quad 3 (Only when the Comm Port is set to TCP) Scada Netmask Quad 2 (Only when the Comm Port is set to TCP) Scada Netmask Quad 1 (Only when the Comm Port is set to TCP) Scada Netmask Quad 0 (Only when the Comm Port is set to TCP) Scada Gateway Quad 3 (Only when the Comm Port is set to TCP) Scada Gateway Quad 2 (Only when the Comm Port is set to TCP) Scada Gateway Quad 1 (Only when the Comm Port is set to TCP) Scada Gateway Quad 0 (Only when the Comm Port is set to TCP) Scada Diagnostics Mode The control card when it enters the Customer Cal mode will display "CAL" for 2 seconds, then automatically move to display the first setting which will be the Low DC Current Alarm Threshold. While each setting is displayed, you have the option of changing it by pressing the "EQ" switch "UP" or "Down". "UP" is used to increase setting values and "DOWN" will decrease the settings. To advance to the next setting you must press the HVSD Reset Button. Setting the Modbus Address The following setting are used to set the Modbus Address so the communications card can communicate with the controller card: Modbus Address An Alternating display showing "Addr" for 1 second then the modbus address for 1 second. Hold the down switch until the display shows ALL. The ALL setting sets the controller card up so it will accept commands from the communications card. It also activates the following calibration settings. When the modbus address is not set to all the controller card may not be able to communicate with the communications card. To advance to the next setting you must press the HVSD Reset Button. Setting the Remote Configuration Mode This setting when set to YES places the communications card into a mode where it is then possible to set the card up using a configuration program supplied by LaMarche. This capability has been added in recognition of the shortcomings associated with showing characters on a 7 segment display. Please contact LaMarche if you are interested in using this as a configuration option. The default selection for this setting is NO (displayed as no). Setting this to YES causes the calibration sequence to jump to the end as it is expected the settings will be transmitted to the card using the software utility.. PLEASE NOTE YOU MUST RETURN TO THE CAL SEQUENCE TO DEACTIVATE THIS MODE OR RESET THE CONTROLLER CARD. To advance to the next setting you must press the HVSD Reset Button. Page 3 of 26

4 Setting the Scada Protocol The communications card is equipped with 4 methods of communicating, DNP 3.0, Modbus ASCII, Modbus RTU and Modbus TCP. The following setting is used to set the Scada Protocol: Protocol Each protocol setting is displayed using an alternating "SCdA" for 1 second followed by either " dnp", " ASCi", rtu or " tcp". To change the protocol from DNP to Modbus TCP, press the EQ switch "UP" until the display shows an alternating "SCdA" followed by " tcp". To advance to the next setting you must press the HVSD Reset Button. Setting the Scada Node Address The following settings are used to set the Scada Node Address: Scada Node Address (4), MSB Scada Node Address (3) Scada Node Address (2) Scada Node Address (1) Scada Node Address (0), LSB Each of these settings is displayed as follows: An Alternating display showing "Addr" for 1 second then "AX Y" for 1 second. The X represents the place of the address digit displayed and will be either 4,3,2,1,0. The Y is a single digit representing the actual address digit and will be either 9,8,7,6,5,4,3,2,1,0. Please note the highest possible address is thus the MSB will not increase beyond 6. It is your responsibility to make sure the address you set in is at or below For example: You would like to change the Node Address from the default setting of 4 to When the display is alternating between "Addr" and "A4 0" you would press the EQ switch and increase the setting until the display showed an alternating "Addr" and A4 1". When the display is alternating between "Addr" and "A3 0" you would press the EQ switch and increase the setting until the display showed an alternating "Addr" and A3 2". When the display is alternating between "Addr" and "A2 0" you would press the EQ switch and increase the setting until the display showed an alternating "Addr" and "A2 3". When the display is alternating between "Addr" and A1 0" you would press the EQ switch and increase the setting until the display showed an alternating "Addr" and A1 1". When the display is alternating between "Addr" and "A0 0" you would press the SELECT switch and decrease the setting until the display showed an alternating "Addr" and A0 0". The Node Address is now set to To advance to the next setting you must press the HVSD Reset Button. Page 4 of 26

5 Setting the Scada Comm Port The communications card is equipped with 3 methods of communicating, RS232, RS485 and TCP. NOTE: THIS SETTING IS SKIPPED IF YOU SELECT MODBUS TCP AS THE PROTOCOL. The following setting is used to set the Scada Comm Port: Scada Comm Port Each Comm Port setting is displayed using an alternating "POrt" for 1 second followed by either " 232", " 485" or " tcp". To change the Comm Port from RS232 to RS485, press the EQ switch "UP" until the display shows an alternating "POrt" followed by " 485". To change the Comm Port from RS232 to TCP, press the EQ switch "UP" until the display shows an alternating "POrt" followed by " tcp". To advance to the next setting you must press the HVSD Reset Button. Setting the Scada Baud Rate NOTE: THIS SETTING IS SKIPPED IF THE SELECTED COMM PORT IS TCP. The communications Card may be set to communicate over an RS232 or RS485 network at the following Baud Rates: 1200, 4800, 9600 The following setting is used to set the Baud Rate: Scada Baud Rate Each Baud Rate setting is displayed using an alternating "baud" followed by the baud rate "XXXX". To change the baud rate, press the EQ switch "UP" and increase the setting until the desired baud rate is shown. For example: to set the baud rate at 1200, hold the switch "Down" until the display shows "baud" and "1200", then release the switch. To advance to the next setting you must press the HVSD Reset Button. Setting the Scada IP Address NOTE: THIS SETTING WILL NOT APPEAR IN THE SEQUENCE IF THE COMMUNICATION PORT HAS BEEN SET TO RS232 OR RS485. The IP address in quad format is defined as follows Q3.Q2.Q1.Q0 where Q3, Q2, Q1 and Q0 may be represented by a 1 to 3 digit number thus the default IP of may be broken down as follows; Q3=192, Q2=168, Q1=0, Q0=6. The following settings are used to set the IP Address: Scada IP Address Quad 3, Q3 Scada IP Address Quad 2, Q2 Scada IP Address Quad 1, Q1 Scada IP Address Quad 0, Q0 Page 5 of 26

6 Each of these settings is displayed as follows: An Alternating display showing "IP X" for 1 second then a 1 to 3 digit number. The X will be either 3,2,1 or 0 and tells you which quad is being shown. The 1 to 3 digit number is the setting for that quad. For example: You would like to change the IP Address from the default setting of to When the display is alternating between "IP 3" and " 192" you would press the SELECT switch and decrease the setting until the display showed an alternating "IP 3" and 190. When the display is alternating between "IP 2" and " 168" you would press the SELECT switch and decrease the setting until the display showed an alternating "IP 2" and 160 ". When the display is alternating between "IP 1" and " 0" you would press the EQ switch and increase the setting until the display showed an alternating "IP 1" and " 10". When the display is alternating between "IP 0" and 6" you would press the SELECT and decrease the setting until the display showed an alternating "IP 0" and 3". The IP Address is now set to To advance to the next setting you must press the HVSD Reset Button. Setting the Scada Netmask NOTE: THIS SETTING WILL NOT APPEAR IN THE SEQUENCE IF THE COMMUNICATION PORT HAS BEEN SET TO RS232 OR RS485. The Netmask like the IP Address discussed above is defined as follows Q3.Q2.Q1.Q0 where Q3, Q2, Q1 and Q0 may be represented by a 1 to 3 digit number thus the default Netmask of may be broken down as follows; Q3=255, Q2=255, Q1=255, Q0=0. The following settings are used to set the Netmask: Scada Netmask Quad 3, Q3 Scada Netmask Quad 2, Q2 Scada Netmask Quad 1, Q1 Scada Netmask Quad 0, Q0 Each of these settings is displayed as follows: An Alternating display showing "Sn X" for 1 second then a 1 to 3 digit number. The X will be either 3,2,1 or 0 and tells you which quad is being shown. The 1 to 3 digit number is the setting for that quad. For example: You would like to change the netmask from the default setting of to When the display is alternating between "Sn 3" and " 255" you do nothing and wait for the cal sequence to auto advance. When the display is alternating between "Sn 2" and " 255" you do nothing and wait for the cal sequence to auto advance. When the display is alternating between "Sn 1" and " 255" you would press the SELECT switch and decrease the setting until the display showed an alternating "Sn 1" and 0. When the display is alternating between Sn 0 and 0 you would do nothing. Page 6 of 26

7 The Netmask is now set to To advance to the next setting you must press the HVSD Reset Button. Setting the Scada Gateway NOTE: THIS SETTING WILL NOT APPEAR IN THE SEQUENCE IF THE COMMUNICATION PORT HAS BEEN SET TO RS232 OR RS485. The Gateway like the IP Address discussed above is defined as follows Q3.Q2.Q1.Q0 where Q3, Q2, Q1 and Q0 may be represented by a 1 to 3 digit number thus the default Netmask of may be broken down as follows; Q3=000, Q2=000, Q1=000, Q0=000. NOTE: A Gateway setting of is equivalent to not having a Gateway Setting. Thus if you are not sure if you need to set the Gateway then leave it at the default of The following settings are used to set the Gateway: Scada Gateway Quad 3, Q3 Scada Gateway Quad 2, Q2 Scada Gateway Quad 1, Q1 Scada Gateway Quad 0, Q0 Each of these settings is displayed as follows: An Alternating display showing "rs X" for 1 second then a 1 to 3 digit number. The X will be either 3,2,1 or 0 and tells you which quad is being shown. The 1 to 3 digit number is the setting for that quad. For example: You would like to change the gateway from the default setting of to When the display is alternating between "rs 3" and " 0" you would press the EQ switch and increase the setting until the display showed an alternating "rs 3" and 192. When the display is alternating between "rs 2" and " 0" you would press the EQ switch and increase the setting until the display showed an alternating "rs 2" and 168. When the display is alternating between "rs 1" and " to auto advance. 0" you do nothing and wait for the cal sequence When the display is alternating between "rs 0" and " 0" you would press the EQ switch and increase the setting until the display showed an alternating "Sn 0" and 11. The Gateway is now set to To advance to the next setting you must press the HVSD Reset Button. Setting the Scada Diagnostics Mode This setting when set to YES places the communications card into a mode where it is then possible to utilize a program such a hyperterminal to check communications. This capability has been added in recognition that not all installers will have a software program capable of simulating a master station with the selected protocol. The default selection for this setting is NO (displayed as no). Setting this to YES places the communications card into a mode where you can confirm communications using hyperterminal. In this mode the communication board will send out an ascii character message that says Press a key The characters will be sent out using communications parameters you have entered. When you see this message you are confirming that the communications card is capable of transmitting Page 7 of 26

8 on the port using the settings you have selected. When you press a key the communications card will reply saying You pressed the X key where X is the key you pressed. If you see this then the card is transmitting and receiving properly. PLEASE NOTE YOU MUST RETURN TO THE CAL SEQUENCE TO DEACTIVATE THIS MODE OR RESET THE CONTROLLER CARD. To advance to the next setting you must press the HVSD Reset Button At this point the controller card will exit the calibration sequence and return to normal operation. Page 8 of 26

9 RS232 Port Connection RS232, RS485 & TCP Connection Information RS232 communications are accomplished through J2. The RS232 Port is a galvanically isolated interface. The RS232 interface is configured as DTE. The default settings are 9600 baud, 8 Bits, No Parity, 1 stop bit and no flow control. Page 9 of 26

10 RS485 Port Connection (s) For RJ11/Phone Jack Equipped Cards The RS485 (J3, J4) ports are parallel RJ11 jacks. Thus you may connect to either J3 or J4. The RS485 Ports are galvanically isolated. The RS485 interface is "two wire" thus no handshaking takes place. The default connection would be 9600 baud, 8 Bits, No Parity, 1 stop bit and no flow control. The RS485 interface may require configuration of jumpers JP1/JP2, JP3/JP4, JP5/JP6 on the P60-302S card. JP1/JP2, JP3/JP4 serve as biasing loads. JP5/JP6 serve as a terminating load. Each jumper is marked with RIN (the jumper position places the load resistor in the circuit) or ROUT (the jumper position places the load resistor out of the circuit). The positioning of these jumpers will depend on the configuration of your RS485 network. Typically a network using a device like B&B Electronics RS232 to RS485 converter (Part Number 485SD9RJ) would not require the use of the biasing load resistors thus the jumpers configuration for JP1/JP2 & JP3/JP4 would be to position the shorting jumpers on JP1 and JP3 for all P60-302S cards placed on this network. If you do not have these biasing resistors already somewhere on the RS485 network then you will need to place the shorting jumpers on JP2 and JP4, JP5/JP6 will need to be placed on JP6 for P60-302S's that are in the first and last position on the RS485 network. The B&B device I have mentioned above does not provide a terminating resistor. The RS485 jacks on the P60-302S board are 6 position RJ11 jacks. Only positions 2,4,5 have connections. Pin 2 is Data A (-), Pin 5 is Data B (+) and Pin 4 is the Signal Ground. RJ11 jacks are configured such that when you face them (looking into the jack) Pin 1 is left most position and Pin 6 is the right most. For good signal quality it is advisable to use shielded twisted pair cable in your RS485 network (B&B Electronics, Part Number ETC8504 or ETC8505). Page 10 of 26

11 RS485 Port Connection (s) for Terminal Strip Equipped Cards The RS485 (TS1) port is a 3 pin terminal strip. The RS485 Ports are galvanically isolated. The RS485 interface is "two wire" thus no handshaking takes place. The default connection would be 9600 baud, 8 Bits, No Parity, 1 stop bit and no flow control. The RS485 interface may require configuration of jumpers JP1/JP2, JP3/JP4, JP5/JP6 on the P60-302S card. JP1/JP2, JP3/JP4 serve as biasing loads. JP5/JP6 serves as a terminating load. Each jumper is marked with RIN (the jumper position places the load resistor in the circuit) or ROUT (the jumper position places the load resistor out of the circuit). The positioning of these jumpers will depend on the configuration of your RS485 network. Typically a network using a device like B&B Electronics RS232 to RS485 converter (Part Number 485SD9TB) would not require the use of the biasing load resistors thus the jumper s configuration for JP1/JP2 & JP3/JP4 would be to position the shorting jumpers on JP1 and JP3 for all P60-302S cards placed on this network. If you do not have these biasing resistors already somewhere on the RS485 network then you will need to place the shorting jumpers on JP2 and JP4, JP5/JP6 will need to be placed on JP6 for P60-302S's that are in the first and last position on the RS485 network. The B&B device I have mentioned above does not provide a terminating resistor. The RS485 jacks on the P60-302S board is a 3 position terminal strip. Pin 1 is Data A (+), Pin 3 is Data B (-) and Pin 2 is the Signal Ground. The terminal strip is positioned such that when you face it (looking directly into the strip) Pin 1 is the left most position and Pin 3 is the right most. For good signal quality it is advisable to use shielded twisted pair cable in your RS485 network (B&B Electronics, Part Number ETC8504 or ETC8505). Page 11 of 26

12 TCP Port Connection The TCP Interface will require the use of a Cross-over cable if you are going to connect the P36-302S card directly to a NIC on a PC. If you connect through a hub a straight through cable should suffice. The Ethernet Port on the P60-302S is 10/100 Base-T compatible. The TCP Connection is accomplished through a single RJ45 jack that is mounted to a daughter board on the P60-302S. Page 12 of 26

13 DNP V3.0 DEVICE PROFILE DOCUMENT Vendor Name: LaMarche Manufacturing Company Device Name: LaMarche Charger to DNP 3.0 Interface Module Remote Highest DNP Level Supported: For Requests: Level 1 For Responses: Level 1 Device Function: _ Master X Slave Notable objects, functions, and/or qualifiers supported in addition to the Highest DNP Levels Supported (the complete list is described in the attached table): Maximum Data Link Frame Size (octets): Transmitted: 292 Received 292 Maximum Data Link Re-tries: X None Fixed at 3 _ Configurable from to Maximum Application Fragment Size (octets): Transmitted: 256 Received 256 Maximum Application Layer Re-tries: X None _ Configurable Requires Data Link Layer Confirmation: X Never _ Always _ Sometimes _ Configurable as: Requires Application Layer Confirmation: Never _ Always _ When reporting Event Data (Slave devices only) X When sending multi-fragment responses (Slave devices only) _ Sometimes _ Configurable as: Page 13 of 26

14 DNP V3.0 DEVICE PROFILE DOCUMENT Timeouts while waiting for: Data Link Confirm: None X Fixed at 2000ms _ Variable _ Configurable. Complete Appl. Fragment: X None _ Fixed at _ Variable _ Configurable Application Confirm: None X Fixed at 10000ms _ Variable _ Configurable. Complete Appl. Response: X None _ Fixed at _ Variable _ Configurable Others: Link Status Period when using TCP Fixed at 20000ms Sends/Executes Control Operations: WRITE Binary Outputs _ Never X Always _ Sometimes _ Configurable SELECT/OPERATE _ Never X Always _ Sometimes _ Configurable DIRECT OPERATE _ Never X Always _ Sometimes _ Configurable DIRECT OPERATE NO ACK _ Never X Always _ Sometimes _ Configurable Count > 1 X Never _ Always _ Sometimes _ Configurable Pulse On X Never _ Always _ Sometimes _ Configurable Pulse Off X Never _ Always _ Sometimes _ Configurable Latch On _ Never X Always _ Sometimes _ Configurable Latch Off _ Never X Always Sometimes _ Configurable Queue X Never _ Always _ Sometimes _ Configurable Clear Queue X Never _ Always _ Sometimes _ Configurable Attach explanation if 'Sometimes' or 'Configurable' was checked for any operation. Reports Binary Input Change Events when no specific variation requested: X Never _ Only time-tagged _ Only non-time-tagged _ Configurable to send one or the other Reports time-tagged Binary Input Change Events when no specific variation requested: X Never _ Binary Input Change With Time _ Binary Input Change With Relative Time _ Configurable Sends Unsolicited Responses: X Never _ Configurable _ Only certain objects _ Sometimes (attach explanation) _ ENABLE/DISABLE UNSOLICITED Function codes supported Sends Static Data in Unsolicited Responses: X Never _ When Device Restarts _ When Status Flags Change No other options are permitted. Page 14 of 26

15 DNP V3.0 DEVICE PROFILE DOCUMENT Default Counter Object/Variation: X No Counters Reported _ Configurable _ Default Object Default Variation: _ Point-by-point list attached Counters Roll Over at: X No Counters Reported _ Configurable (attach explanation) _ 16 Bits _ 32 Bits _ Other Value: Point-by-point list attached Sends Multi-Fragment Responses: X Yes No Sequential File Transfer Support: Append File Mode _ Yes X No Custom Status Code Strings _ Yes X No Permissions Field _ Yes X No File Events Assigned to Class _ Yes X No File Events Send Immediately _ Yes X No Multiple Blocks in a Fragment _ Yes X No Max Number of Files Open 0 Page 15 of 26

16 DNP V3.0 Implementation Table The following table identifies which object variations, function codes, and qualifiers are supported in both request messages and in response messages. In the table below, text shaded as 00, 01 (start stop) indicates Subset Level 3 functionality (beyond Subset Level 2). In the table below, text shaded as 07, 08 (limited qty) indicates functionality beyond Subset Level 3. Object Number Variation Number OBJECT REQUEST RESPONSE Description Function Codes (dec) 1 0 Binary Input Any Variation 1 (read) 22 class) (assign 1 1 (default see note 1) Qualifier Codes (hex) 00, 01 (start-stop) 06 (no range, or all) 07, 08 (limited qty) 17, 27, 28 (index) Binary Input 1 (read) 00, 01 (start-stop) 06 (no range, or all) 07, 08 (limited qty) 17, 27, 28 (index) 1 2 Binary Input with Status 1 (read) 00, 01 (start-stop) 06 (no range, or all) 07, 08 (limited qty) 17, 27, 28 (index) 10 0 Binary Output Any Variation 1 (read) 00, 01 (start-stop) 22 (assign 06 (no range, or all) class) 07, 08 (limited qty) 17, 27, 28 (index) 10 1 Binary Output 1 (read) 00, 01 (start-stop) 06 (no range, or all) 07, 08 (limited qty) 17, 27, 28 (index) 1 (write 00, 01 (start-stop) 10 2 (default see note 1) Binary Output Status 1 (read) 00, 01 (start-stop) 06 (no range, or all) 07, 08 (limited qty) 17, 27, 28 (index) 12 0 Control Relay Output Block 22 (assign class) 12 1 Control Relay Output Block 3 (select) 4 (operate) 5 (direct op) 6 (dir. op, noack) 30 0 Analog Input - Any Variation 1 (read) 22 (assign class) 00, 01 (start-stop) 06 (no range, or all) 07, 08 (limited qty) 17, 27, 28 (index) Function Codes (dec) Qualifier Codes (hex) 129 (response) 00, 01 (start-stop) 17, 28 (index see note 2) 129 (response) 00, 01 (start-stop) 17, 28 (index see note 2) 129 (response) 00, 01 (start-stop) 17, 28 (index see note 1) 129 (response) 00, 01 (start-stop) 17, 28 (index see note 2) 17, 28 (index) 129 (response) echo of request 00, 01 (start-stop) 06 (no range, or all) 07, 08 (limited qty) 17, 27, 28 (index) Bit Analog Input 1 (read) 00, 01 (start-stop) 06 (no range, or all) 07, 08 (limited qty) 17, 27, 28 (index) 30 4 (default see note 1) 16-Bit Analog Input without Flag 1 (read) 00, 01 (start-stop) 06 (no range, or all) 07, 08 (limited qty) 17, 27, 28 (index) 40 0 Analog Output Status 1 (read) 22 class) (assign 00, 01 (start-stop) 06 (no range, or all) 07, 08 (limited qty) 17, 27, 28 (index) 129 (response) 00, 01 (start-stop) 17, 28 (index see note 2) 129 (response) 00, 01 (start-stop) 17, 28 (index see note 2) Page 16 of 26

17 Object Number Variation Number 40 2 (default see note 1 OBJECT REQUEST RESPONSE Description Function Codes (dec) Qualifier Codes (hex) 16-Bit Analog Output Status 1 (read) 00, 01 (start-stop) 06 (no range, or all) 07, 08 (limited qty) 17, 27, 28 (index) Function Codes (dec) Qualifier Codes (hex) 129 (response) 00, 01 (start-stop) 17, 28 (index see note 2) 41 0 Analog Output Block 22 (assign 00, 01 (start-stop) class) 06 (no range, or all) 07, 08 (limited qty) 17, 27, 28 (index) Bit Analog Output Block 3 (select) 17, 28 (index) 129 (response) echo of request 4 (operate) 27 (index) 5 (direct op) 6 (dir. op, noack) 60 1 Class 0 Data 1 (read) 06 (no range, or all) 80 1 Internal Indications 1 (read) 00, 01 (start-stop) 129 (response) 00, 01(start-stop) 2 (write) (see note 3) 00 (start-stop) index=4 or 7 Note 1: A Default variation refers to the variation responded when variation 0 is requested and/or in class 0, 1, 2, or 3 scans. Default variations are indicated in the table above. Note 2: For static (non-change-event) objects, qualifiers 17 or 28 are only responded when a request is sent with qualifiers 17 or 28, respectively. Otherwise, static object requests sent with qualifiers 00, 01, 06, 07, or 08, will be responded with qualifiers 00 or 01. Note 3: Writes of Internal Indications are only supported for index 7 (Restart IIN1-7) DNP V3.0 Point List The tables below identify all the data points provided by the implementation. Binary Input Points Static (Steady-State) Object Number: 1 Static Variation reported when variation 0 requested: 1 (Binary Input 2 without status) Point Index Name/Description 0 AC Alarm Indicator (FAILURE=1) 1 Low Voltage 1 Alarm Indicator (FAILURE=1) 2 High Voltage Alarm Indicator (FAILURE=1) 3 High Voltage Shutdown Alarm Indicator (FAILURE=1) 4 Low Current Alarm Indicator (FAILURE=1) 5 Ground Detection Enabled (ENABLED=1) Positive Ground Alarm Indicator (FAILURE=1). 6 Point will always read 0 when Ground Detection Enabled (Binary Input Point 5) is 0. Negative Ground Alarm Indicator (FAILURE=1). 7 Point will always read 0 when Ground Detection Enabled (Binary Input Point 5) is 0. 8 Summary Alarm Indicator (FAILURE=1) Blown DC Protection Indicator (FAILURE=1). 9 Point will always read 0 when Ground Detection Enabled (Binary Input Point 5) is Internal Temperature Probe In Use (TRUE=1). 11 External Temperature Probe In Use (TRUE=1). 12 Float/EQ Mode Indicator (FLOAT=0, EQUALIZE=1) Page 17 of 26

18 Binary Input Points Static (Steady-State) Object Number: 1 Static Variation reported when variation 0 requested: 1 (Binary Input 2 without status) Point Index Name/Description 13 Temperature Compensation Enable (ENABLED=1). Binary Output Status Points Object Number: 10 Default Variation reported when variation 0 requested: 2 (Binary Output Status) Control Relay Output Blocks Object Number: 12 Point Index Name/Description 0 Float/EQ Mode Indicator (FLOAT=0, EQUALIZE=1) 1 Temperature Compensation Enable (ENABLED=1). Note for Control Relay Output Blocks: Use Latch On to place point in a 1 state and Latch Off to place point in a 0 state. Analog Inputs Static (Steady-State) Object Number: 30 Static Variation reported when variation 0 requested: 4 (16-Bit Analog Input w/o Flag) Point Index Description, Units Scale Factor 0 Board Number. Will read 205 for 205T card. None 1 Software Version, Version of software on 205T card. None 2 Voltage, Volts Current, Amps Equalize Cycle Time Hours Remaining, Hours, Minutes Note: The last two digits are the minutes. None 5 Auto Equalize Timer, Days None 6 Auto Equalize Timer, Hours, Minutes Note: The last two digits are the minutes. None 7 Low DC Current Alarm Low Limit, Amps. Setting the Low DC Current Alarm below this will result in disabling the Low DC 0.1 Current Alarm Status Indicator. 8 Local Temperature Probe Reading, Degrees C Note: A shorted probe will give a reading of 273 and an open None probe will give a reading of Equalize Cycle Time Hours Remaining, Hours Note: A shorted probe will give a reading of 273 and an open probe will give a reading of+273 None Page 18 of 26

19 Analog Outputs Static (Steady-State) Object Number: 40 Static Variation reported when variation 0 requested: 2 (16-Bit Analog Output Status) Point Index Description, Units, Valid Settings/Range Scale Factor 0 Equalize Timer Mode (0,1 2,3,4) None 1 Equalize Timer Setting (0 to 144) None 2 Low Voltage 1 Alarm Threshold, Volts (0 to 2000) High Voltage Alarm Threshold, Volts (0 to 2000) High Voltage Shutdown Alarm Threshold, Volts (0 to 2000) Low DC Current Alarm Threshold, Amps (0 to 60000) Low DC Current Alarm Recovery Threshold, Amps (Low DC Current Alarm Threshold to 60000) 0.1 Page 19 of 26

20 LaMarche Modbus Implementation Default Communication Settings Channel Type: RS232 Flow Control: Fixed at None Baud Rate: 9600 Data Bits: Fixed at 8 Stop Bits: Fixed at 1 Parity: Fixed at None Supported Modbus Types ASCII (Default Modbus Type) RTU TCP Supported Modbus Function Codes 01 Read Coil Status (0X) 02 Read Discrete Input Registers (1X) 03 Read Holding Registers (4X) 04 Read Input Registers (3X) 05 Write Single Coil 06 Write Single Register 01 - Coils Address Name/Description Float/EQ Mode Indicator (FLOAT=0, EQUALIZE=1) Temperature Compensation Enable (ENABLED=1) Discrete Inputs Address Name/Description AC Alarm Indicator (FAILURE=1) Low Voltage 1 Alarm Indicator (FAILURE=1) High Voltage Alarm Indicator (FAILURE=1) High Voltage Shutdown Alarm Indicator (FAILURE=1) Low Current Alarm Indicator (FAILURE=1) Ground Detection Enabled (ENABLED=1) Positive Ground Alarm Indicator (FAILURE=1). Point will always read 0 when Ground Detection Enabled (Discrete Input Point 5) is Negative Ground Alarm Indicator (FAILURE=1). Point will always read 0 when Ground Detection Enabled (Discrete Input Point 5) is Summary Alarm Indicator (FAILURE=1) Blown DC Protection Indicator (FAILURE=1). Point will always read 0 when Ground Detection Enabled (Discrete Input Point 5) is Internal Temperature Probe In Use (TRUE=1) External Temperature Probe In Use (TRUE=1). Page 20 of 26

21 03 - Holding Registers Address Description, Units, Valid Settings/Range Scale Factor Equalize Timer Mode (0,1 2,3,4) None Equalize Timer Setting (0 to 144) None Low Voltage 1 Alarm Threshold, Volts (0 to 2000) High Voltage Alarm Threshold, Volts (0 to 2000) High Voltage Shutdown Alarm Threshold, Volts (0 to 2000) Low DC Current Alarm Threshold, Amps (0 to 60000) Low DC Current Alarm Recovery Threshold, Amps (Low DC Current Alarm Threshold to 60000) Input Registers Address Description, Units Scale Factor Heartbeat This register increases once per second and may be used to None determine if communications are still occurring Board Number. Will read 205 for 205T card. None Software Version, Version of software on 205T card. None Voltage, Volts Current, Amps Equalize Cycle Time Hours Remaining, Hours, Minutes Note: The last two digits are the minutes. None Auto Equalize Timer, Days None Auto Equalize Timer, Hours, Minutes Note: The last two digits are the minutes. None Low DC Current Alarm Low Limit, Amps. Setting the Low DC Current Alarm below this will result in disabling the Low DC 0.1 Current Alarm Status Indicator Local Temperature Probe Reading, Degrees C Note: A shorted probe will give a reading of 273 and an open None probe will give a reading of Equalize Cycle Time Hours Remaining, Hours Note: A shorted probe will give a reading of 273 and an open probe will give a reading of+273 None Page 21 of 26

22 La Marche Communications Board Troubleshooting Guide 1) Verify operation of RED LED on 302S Board. The communications board (ECN and above) are equipped with a Red LED (LED1). This LED indicates the following: OFF: The board is not being powered or has failed. Check to see the cable is properly connected to the 3-pin connector J5 on the communications card. FLASHING: A problem with communications between the 302S and the 205T has occurred. If the charger is equipped with a 205T check to see if the 10-pin ribbon cable is connecting J1 (Slave Port) on the 302S is connected to J2 on the 205T. A flashing LED can indicate the cable is bad. This LED will also flash when the 205T are in either the Factory or Customer calibration modes. ON: This indicates the 302S and 205T are communicating properly. 2) Confirm proper configuration of 302S card for customer s application. The 302S card is shipped with the following default settings: Comm Port: RS232 (J2) Baud Rate: 9600 Data Bits: 8 Stop Bit: 1 Parity: None Flow Control: None Node Address: These settings may not be what are desired and the only way to change them is to enter the customer calibration routine. The settings displayed in the customer cal routine should be checked to make sure they coincide with the customer s application. 3) Confirm the correct type of cable is connecting the 302S to the customer s application. Refer to LaMarche 302S Cabling Guide Section in the 302S Card Manual for details. 4) Is the 302S card being used on an RS485 Network? For an RS485 Network to function properly it must be properly biased and terminated. The 302S card is equipped with 3 configuration jumpers. JP5 removes the termination resistor. JP6 adds in the termination resistor. JP1 & JP3 remove the biasing resistors. JP4 & JP6 add in the biasing resistors. Common practice with RS485 networks is to configure the last device in a network (the device furthest from the master) with a termination resistor and the device closest to the master or sometimes the master has the biasing resistors. Problems often occur when devices are added and removed from a RS485 network without reconfiguring/checking the termination and biasing resistor arrangement. 5) Testing Method. The 302S cards are tested at the LaMarche factory prior to shipment using the Triangle MicroWorks Test Harness software program. Each of the ports (RS232, RS485 and Ethernet) is tested. The next several pages show actual screenshots from a DNP Session that may assist in troubleshooting as they depict the actual settings that were required to test the board. Page 22 of 26

23 Screenshots showing setup of a DNP Session over the RS232 Port Page 23 of 26

24 Screenshots showing setup of a DNP Session over the TCP Port Page 24 of 26

25 Screenshots showing setup of a Modbus RTU Session over the RS232 Port Page 25 of 26

26 Screenshots showing setup of a Modbus TCP Session over the Ethernet Port Page 26 of 26

DNP 3.0 & Modbus SCADA INTERFACE INSTRUCTIONS FOR 205T BASED SYSTEMS

DNP 3.0 & Modbus SCADA INTERFACE INSTRUCTIONS FOR 205T BASED SYSTEMS DNP 3.0 & Modbus SCADA INTERFACE INSTRUCTIONS - OPTION 21PQ - FOR 205T BASED SYSTEMS DNP 3.0 & Modbus SCADA INTERFACE OPTION 21PQ INSTRUCTIONS FOR 205T BASED SYSTEMS CPN114830 ECN/DATE ISSUE DATE: ECN

More information

DNP 3.0 Serial (RS232/RS485) and Ethernet (TCP/IP) SCADA Interface for TPSD/A36D Chargers with S2A-205T Option 21P or 57T or 57U. Setup Instructions

DNP 3.0 Serial (RS232/RS485) and Ethernet (TCP/IP) SCADA Interface for TPSD/A36D Chargers with S2A-205T Option 21P or 57T or 57U. Setup Instructions La Marche Manufacturing Company www.lamarchemfg.com DNP 3.0 Serial (RS232/RS485) and Ethernet (TCP/IP) SCADA Interface for TPSD/A36D Chargers with S2A-205T Option 21P or 57T or 57U Setup Instructions This

More information

A12B DNP 3.0 SERIAL & ETHERNET (TCP/IP) SCADA INTERFACE

A12B DNP 3.0 SERIAL & ETHERNET (TCP/IP) SCADA INTERFACE A12B DNP 3.0 SERIAL & ETHERNET (TCP/IP) SCADA INTERFACE OPTION 21P INSTRUCTIONS This manual is only valid for A12B units equipped with a S2A-225C control module and a S2A-383S-3X20 communications card.

More information

Setup Instructions. This manual is only valid for A12B Chargers equipped with the following: S2A-225C card with software version P225C0630

Setup Instructions. This manual is only valid for A12B Chargers equipped with the following: S2A-225C card with software version P225C0630 La Marche Manufacturing Company www.lamarchemfg.com DNP 3.0 Serial (RS232/RS485) and Ethernet (TCP/IP) or Fiber SCADA Interface for A12B Chargers Option 21P Option 57T Option 57U Setup Instructions This

More information

SOFTWARE DOCUMENTATION. DNP3 Configuration / Interoperability Guide for the DATRAN XL4 DNP3 RTU

SOFTWARE DOCUMENTATION. DNP3 Configuration / Interoperability Guide for the DATRAN XL4 DNP3 RTU SOFTWARE DOCUMENTATION DNP3 Configuration / Interoperability Guide for the DATRAN XL4 DNP3 RTU Table of Contents 1 DNP V3.0 DEVICE PROFILE... 3 2 DNP V3.0 IMPLEMENTATION TABLE... 6 3 DNP V3.0 POINT LIST...

More information

SOFTWARE DOCUMENTATION. DNP3 Configuration / Interoperability Guide for the DATRAN II excel DNP3 RTU

SOFTWARE DOCUMENTATION. DNP3 Configuration / Interoperability Guide for the DATRAN II excel DNP3 RTU SOFTWARE DOCUMENTATION DNP3 Configuration / Interoperability Guide for the DATRAN II excel DNP3 RTU QTech Data Systems Ltd Unit 6 Amuri Park 404 Barbadoes Street Christchurch New Zealand Phone: +64 3 3663713

More information

EVO AT SERIES BATTERY CHARGER AT SERIES BATTERY CHARGER COMMUNICATIONS MANUAL. EVO - Microprocessor Controlled Float Battery Charger JA

EVO AT SERIES BATTERY CHARGER AT SERIES BATTERY CHARGER COMMUNICATIONS MANUAL. EVO - Microprocessor Controlled Float Battery Charger JA EVO P R O D U C T COMMUNICATIONS MANUAL EVO - Microprocessor Controlled Float Battery Charger JA5011-54 NOTICE! WARNING Table of Contents - ATevo TABLE OF CONTENTS 1. INTRODUCTION.....................................................

More information

GE MDS, LLC. NETio Series. Protocol Communications Supplement. March 2013 Part No A01, Rev. C

GE MDS, LLC. NETio Series. Protocol Communications Supplement. March 2013 Part No A01, Rev. C GE MDS, LLC. NETio Series Protocol Communications Supplement March 2013 Part No. 05-4672A01, Rev. C Modbus Protocol NETio Architectural Implementation As described in detail below, the Modbus RTU protocol

More information

DNP 3.0 Serial (RS232/RS485) and Ethernet (TCP/IP) SCADA Interface for A31 Inverters with S2A-383S Option 21P. Setup Instructions

DNP 3.0 Serial (RS232/RS485) and Ethernet (TCP/IP) SCADA Interface for A31 Inverters with S2A-383S Option 21P. Setup Instructions La Marche Manufacturing Company www.lamarchemfg.com DNP 3.0 Serial (RS232/RS485) and Ethernet (TCP/IP) SCADA Interface for A31 Inverters with S2A-383S Option 21P Setup Instructions This manual is valid

More information

Campbell Scientific Australia DNP3 DEVICE PROFILE

Campbell Scientific Australia DNP3 DEVICE PROFILE S.UTLEY 1 1 Campbell Scientific Australia DNP3 DEVICE PROFILE Real-time monitoring and Control Systems S.UTLEY 1 2 DNP3 v.28 Device Profile Document Vendor name: Campbell Scientific, Inc. Device Name:

More information

DNP 3.0 device profile for AQ (5) DNP 3.0 device profile for AQ 200

DNP 3.0 device profile for AQ (5) DNP 3.0 device profile for AQ 200 DNP 3.0 device profile for AQ 200 1 (5) DNP 3.0 device profile for AQ 200 DNP 3.0 device profile for AQ 200 2 (5) Revision: 4.0 Date: October 2018 Changes: - Added Counter support Checked By: DNP 3.0 device

More information

Device Profile Document

Device Profile Document Voltage Regulators CL-6A Regulator Control DNP3 Device Profile Document Reference Information R225-90-11 Device Profile Document For Communications Protocol DNP3 For Use With Cooper Power Systems CL-6A

More information

DNP Points List and Implementation

DNP Points List and Implementation S&C IntelliCap Plus Automatic Capacitor Control DNP Points List and Implementation Table of Contents Section Page Section Page DNP Points List for IntelliCap Plus Controls...1 Status Points....2 Analog

More information

DNP3 V3.00 DEVICE PROFILE DOCUMENT

DNP3 V3.00 DEVICE PROFILE DOCUMENT DNP3 V3.00 DEVICE PROFILE DOCUMENT Vendor Name: DAQ Electronics. Device Name: DNP3 Master Station Server in the Callisto Computer. Date: June 8, 2000 Highest DNP Level Supported: For Requests: DNP-L3.

More information

DNP3 Communication User's manual

DNP3 Communication User's manual MV Network Management Fault tracking Monitoring and Control Merlin Gerin Easergy Range T200 P, T200 I DNP3 Communication User's manual Summary General...2 Functionnalities...2 Characteristics...2 Connection

More information

PXM 4/6/8K DNP3 PXM 4/6/8K DNP3 Ethernet Communications User Manual

PXM 4/6/8K DNP3 PXM 4/6/8K DNP3 Ethernet Communications User Manual PXM 4/6/8K DNP3 PXM 4/6/8K DNP3 Ethernet Communications User Manual Contents Contents 1. INTRODUCTION... 1 2. DNP3 PROTOCOL PRIMER... 1 2.1 Why DNP3?...1 2.2 Link Layer Responsibility...5 2.3 Static and

More information

DNP Points List and Implementation for the 6802 Vista Control

DNP Points List and Implementation for the 6802 Vista Control S&C 6800 Series Automatic Switch Control DNP Points List and Implementation for the 6802 Vista Control Table of Contents Section Page Section Page DNP Points List for 6802 Vista Control...1 6802 Status

More information

The Multilin DGCV Voltage Regulator Controller

The Multilin DGCV Voltage Regulator Controller GE Digital Energy The Multilin DGCV Voltage Regulator Controller Multilin DGCV Revision: 1.10 Manual P/N: 1601-0263-A1 GE publication code: GEK-113581 Copyright 2011 GE Digital Energy Communications Guide

More information

SCADA Controlled LOR/ER - DNP3.0 Communications Protocol - TECHNICAL MANUAL ES-SLOR-1

SCADA Controlled LOR/ER - DNP3.0 Communications Protocol - TECHNICAL MANUAL ES-SLOR-1 SCADA Controlled LOR/ER - DNP3.0 Communications Protocol - TECHNICAL MANUAL ES-SLOR-1 Telephone: 781-335-5200 fax: 781-335-4253 180 King Avenue Weymouth, MA 02188 www.electroswitch.com 1 Introduction...

More information

Protection Terminal REF 54_ Protection Relay REX 521

Protection Terminal REF 54_ Protection Relay REX 521 Protection Terminal Protection Relay 1MRS755260 Issued: 02.04.2004 Version: C/22.06.2004 Protection Terminal Protection Relay Contents 1. About this manual...4 1.1. Copyrights...4 1.2. Trademarks...4

More information

RS485 MODBUS Module 8AO

RS485 MODBUS Module 8AO Version 1.3 12/02/2013 Manufactured for Thank you for choosing our product. This manual will help you with proper support and proper operation of the device. The information contained in this manual have

More information

Control Indicator Module (CIM) - DNP3 Communications Protocol - TECHNICAL MANUAL

Control Indicator Module (CIM) - DNP3 Communications Protocol - TECHNICAL MANUAL Control Indicator Module (CIM) - DNP3 Communications Protocol - TECHNICAL MANUAL Page 1 of 35 Introduction...4 Basic Operation...5 Front Panel Controls and Indicators...5 Real Time Clock Battery Back Up...7

More information

INTEGRATED SYSTEMS AND CONTROL, INC. User s Hardware Manual. PCMNET V 7. xx

INTEGRATED SYSTEMS AND CONTROL, INC. User s Hardware Manual. PCMNET V 7. xx INTEGRATED SYSTEMS AND CONTROL, INC. User s Hardware Manual PCMNET V 7. xx INTEGRATED SYSTEMS AND CONTROLS, INC. PCMNET Users Manual Revised 2/4/2005 2003-2005 Integrated Systems and Control. Inc. PO Box

More information

RS485 MODBUS Module 6RO

RS485 MODBUS Module 6RO Version 2.0 12/02/2013 Manufactured for Thank you for choosing our product. This manual will help you with proper support and proper operation of the device. The information contained in this manual have

More information

Product Specification for SAB-S-MODBUS

Product Specification for SAB-S-MODBUS SAB-S-MODBUS May 9, 2011 Product Specification for SAB-S-MODBUS The SAB-S-MODBUS is a two-channel module that measures single or multiple magnet transducer position and returns this information to a host

More information

FLITE 395-GPRS-DNP3. DNP 3.0 communication Appendix to the User Manual. Easergy range. MV electrical network management

FLITE 395-GPRS-DNP3. DNP 3.0 communication Appendix to the User Manual. Easergy range. MV electrical network management MV electrical network management Easergy range FLITE 395-GPRS-DNP3 MV substation remote monitoring Directional FPI DNP 3.0 communication Appendix to the User Manual Summary SUMMARY...3 COMMISSIONING...4

More information

Installation and Programming Manual. Niobrara Research & Development Corporation P.O. Box 3418 Joplin, MO USA

Installation and Programming Manual. Niobrara Research & Development Corporation P.O. Box 3418 Joplin, MO USA DUCM DF1 Manual DUCM DF1 Installation and Programming Manual This manual describes the DUCM application for interfacing DF1 slaves to a Modbus or RNIM serial network. Effective: February 16, 2017 Niobrara

More information

QUCM Limitorque Controller

QUCM Limitorque Controller QUCM Limitorque Valve Controller Application Manual QUCM Limitorque Controller Installation and Programming Manual This Manual describes the QUCM application for interfacing Limitorque Valve Actuators

More information

350 Feeder Management System

350 Feeder Management System Title page GE Digital Energy Multilin 350 Feeder Management System Feeder Protection and Control Communications Guide SR350 revision: 1.20 Manual P/N: 1601-9087-A2 GE publication code: GEK-113511B Copyright

More information

IFC 100 Supplementary instructions

IFC 100 Supplementary instructions IFC 100 Supplementary instructions Signal converter for electromagnetic flowmeters Description of Modbus interface Electronic Revision: ER 3.0.xx Modbus version: 1.0.xx KROHNE CONTENTS IFC 100 1 Important

More information

345 Transformer Protection System

345 Transformer Protection System GE Digital Energy 345 Transformer Protection System Transformer protection and control GE Digital Energy 650 Markland Street Markham, Ontario Canada L6C 0M1 TELEPHONE: Worldwide +1 905 927 7070 Europe/Middle

More information

NOTE The documentation and/or manuals provided by the IEDs vendors must be read and understood thoroughly prior to configuration.

NOTE The documentation and/or manuals provided by the IEDs vendors must be read and understood thoroughly prior to configuration. ConfigWiz Addendum This is the DNP3.0 client addendum. This addendum describes the pop-up window tabs, fields, and ranges of valid parameters for entry in those fields. NOTE The documentation and/or manuals

More information

ATK3 I/O Module (Modbus Slave)

ATK3 I/O Module (Modbus Slave) ATK3 I/O Module (Modbus Slave) 2011-01-13 The ATK3 I/O Module by ElectroCom Table of contents 2011-01-13...1 The ATK3 I/O Module by ElectroCom...1 1 Hardware...2 1.1 Inputs...3 1.2 Outputs...3 1.2.1 Relay...3

More information

IEC Protocol Interoperability List

IEC Protocol Interoperability List IEC 60870-5-104 Protocol Interoperability List Network configuration Point-to-point Multiple point-to-point Multipoint-party line Multipoint-star Physical layer Transmission speed (control direction) Unbalanced

More information

DNP3 Device Profile Based on DNP XML Schema version Showing both the Device's Capabilities and its Current Configuration

DNP3 Device Profile Based on DNP XML Schema version Showing both the Device's Capabilities and its Current Configuration Page 1 of 17 DNP3 Device Profile Based on DNP XML Schema version 2.11.00 Document Name: MHT410 XML File Document Description: Device Profile for the MHT410 Showing both the Device's and its Current Configuration

More information

AL2-MBU Advanced Manual

AL2-MBU Advanced Manual AL2-MBU Advanced Manual REVISION 003.08 December 2008 REVISION LIST 001.08 January 2008 Preliminary version 002.08 June 2008 First official release 003.08 December 2008 New feature: Force Multiple Coils

More information

DNP3 Field Device Profile. for

DNP3 Field Device Profile. for DNP3 Field Device Profile for Document Name: Eaton DNP3 XML File Revision History Date Time ion Reason for change Edited by 2012-01-11 2015-04-16 1 Initial ion Joerg Katzer 15:00:00 2 First updates Joerg

More information

SDM-8AO. Expansion Module 8 analog outputs. Manufactured for

SDM-8AO. Expansion Module 8 analog outputs. Manufactured for Version 1.0 16.05.2014 Manufactured for Thank you for choosing our product. This manual will help you with proper support and proper operation of the device. The information contained in this manual have

More information

DNP V3.00 Protocol Assignments

DNP V3.00 Protocol Assignments E Electro Industries / GaugeTech "The Leader in Web Accessed Power Monitoring and Control" DNP V3.00 Protocol Assignments For Nexus 1250, 120 and 1270 Power Monitors Revision 1.5 November 7, 2002 Doc #

More information

MB40 & MB45 MODBUS TCP/IP Gateway Handbook

MB40 & MB45 MODBUS TCP/IP Gateway Handbook MB40 & MB45 MODBUS TCP/IP Gateway Handbook Version 1.2 29 July 2014 Environdata Australia Pty Ltd 42-44 Percy Street Warwick Queensland 4370 Australia Phone: (07) 4661 4699 Fax: (07) 4661 2485 International

More information

Voltage regulator TAPCON 260

Voltage regulator TAPCON 260 Voltage regulator TAPCON 260 Supplement 2532010/00 Protocol description DNP3 All rights reserved by Maschinenfabrik Reinhausen Copying and distribution of this document and utilization and communication

More information

RS485 MODBUS Module 16I-M

RS485 MODBUS Module 16I-M Version 2.0 12/02/2013 Manufactured for Thank you for choosing our product. This manual will help you with proper support and proper operation of the device. The information contained in this manual have

More information

Voltage regulator TAPCON 240

Voltage regulator TAPCON 240 Voltage regulator TAPCON 240 Supplement 2398461/01 Protocol description DNP3 All rights reserved by Maschinenfabrik Reinhausen Copying and distribution of this document and utilization and communication

More information

SDM-6RO. Expansion Module 6 relay outputs. Manufactured for

SDM-6RO. Expansion Module 6 relay outputs. Manufactured for Version 1.0 5.02.2014 Manufactured for Thank you for choosing our product. This manual will help you with proper support and proper operation of the device. The information contained in this manual have

More information

CAS IKS Gateway (Modbus RTU/TCP and HTML) Manual

CAS IKS Gateway (Modbus RTU/TCP and HTML) Manual CAS-2700-42 IKS to Modbus RTU Gateway CAS 2700-42 IKS Gateway (Modbus RTU/TCP and HTML) Manual CAS 2700-42 IKS Gateway Manual Page 1 of 34 BLANK PAGE CAS 2700-42 IKS Gateway Manual Page 2 of 34 Contents

More information

iopro Mirrored IO System

iopro Mirrored IO System Ph: (877) 343-8467 Fax: (800) 303-5381 Email: info@ioselect.com iopro Mirrored IO System Quick Start Guide (Ver. 6) www.ioselect.com Page 1 Introduction This document will cover how to use the iopro family

More information

Serial Connection of HC900 Hybrid Controller to 900CS Control Station

Serial Connection of HC900 Hybrid Controller to 900CS Control Station Note: Ethernet connections will provide faster performance than RS-485 HC900 1. Remove HC900 CPU and set S2 Dip Switches for RS-485 unterminated Replace CPU & follow instructions per Installation and User

More information

EasyIO FC20 User Reference v1.3. EasyIO FC 20 DDC User Reference V1.3

EasyIO FC20 User Reference v1.3. EasyIO FC 20 DDC User Reference V1.3 EasyIO FC 20 DDC User Reference V1.3 Document Change Log 1 st April 2013 Document created. 13 th July 2013 Software configurations added. 27 th Sept 2014 FC now support pulse input. 6 th June 2015 Serial

More information

TRAINING GUIDE LEVEL 3 MODBUS WRITE IMPORT COMMAND

TRAINING GUIDE LEVEL 3 MODBUS WRITE IMPORT COMMAND OleumTechTM TRAINING GUIDE LEVEL 3 MODBUS WRITE IMPORT COMMAND MUST BE FAMILIAR WITH LEVEL 1 TRAINING MATERIALS BEFORE MOVING FORWARD Doc ID# 80-6010-001b TABLE OF CONTENTS 1. WHAT IS NEW WRITE IMPORT

More information

A12B / A46 SMNP V3 SCADA INTERFACE INSTRUCTIONS

A12B / A46 SMNP V3 SCADA INTERFACE INSTRUCTIONS A12B / A46 SMNP V3 SCADA INTERFACE OPTION 21X INSTRUCTIONS This manual is only valid for A12B and A46 Chargers equipped with S2A-225C control cards with P225C-0630 software and the S2A-389S communications

More information

INSTRUCTION MANUAL STATION CONTROLLER SC1000 MOTOR PROTECTION ELECTRONICS, INC.

INSTRUCTION MANUAL STATION CONTROLLER SC1000 MOTOR PROTECTION ELECTRONICS, INC. INSTRUCTION MANUAL STATION CONTROLLER SC1000 MOTOR PROTECTION ELECTRONICS, INC. 2464 Vulcan Road, Apopka, Florida 32703 Phone: (407) 299-3825 Fax: (407) 294-9435 Revision Date: 9-11-08 Applications: Simplex,

More information

RS 485 Mini Modbus 1AO

RS 485 Mini Modbus 1AO RS 485 Mini Modbus 1AO Version 1.0 14/08/2014 Manufactured for Thank you for choosing our product. This manual will help you with proper support and proper operation of the device. The information contained

More information

mbc082 Bus Converter

mbc082 Bus Converter BUS CONVERTER RS485 TO 1-WIRE BUS mbc082 mbc082 Bus Converter Document. 10910, Revision - February 2007 2007 CMC Industrial Electronics Ltd. This page intentionally left blank. mbc082 Bus Converter Technical

More information

R1M-GH THERMOCOUPLE & DC INPUT MODULE MODEL. Remote I/O R1M Series. (16 points)

R1M-GH THERMOCOUPLE & DC INPUT MODULE MODEL. Remote I/O R1M Series. (16 points) Remote I/O R1M Series THERMOCOUPLE & DC INPUT MODULE (16 points) MODEL MODEL & SUFFIX CODE SELECTION R1MGH2T MODEL Modbus protocol I/O TYPE GH2 : Thermocouple or DC input, 16 points FIELD TERMINAL TYPE

More information

INTRINSICALLY SAFE DUPLEXER PROTECTION. ELECTRONICS, INC Vulcan Road Apopka, Florida MOTOR INSTRUCTION MANUAL

INTRINSICALLY SAFE DUPLEXER PROTECTION. ELECTRONICS, INC Vulcan Road Apopka, Florida MOTOR INSTRUCTION MANUAL INTRINSICALLY SAFE DUPLEXER INSTRUCTION MANUAL MOTOR PROTECTION ELECTRONICS, INC. 2464 Vulcan Road Apopka, Florida 32703 Phone: Website: (407) 299-3825 www.mpelectronics.com Operating Program Revision:

More information

KTA-250 Anemometer Alarm Card

KTA-250 Anemometer Alarm Card Connects to Davis Instruments DS7911 Anemometer Monitor both the wind speed and direction Interface to PLCs using the Modbus protocol Communicate via RS232 or 2-wire RS485 Interface to PLCs/Instruments

More information

Advantage CT/LTC Protocol Manual

Advantage CT/LTC Protocol Manual Advantage CT/LTC Protocol Manual Manual Part Number PMG8T200 Revision 2, November, 2004 16900 FOLTZ PARKWAY, CLEVELAND, OHIO 44149 440/238-2550, FAX 440/238-0660 e-mail: sales@weschler.com Table of Contents

More information

Intech Micro 2300-RO4 analogue input station MODBUS RTU slave application supplementary manual.

Intech Micro 2300-RO4 analogue input station MODBUS RTU slave application supplementary manual. Intech Micro 2300-RO4 analogue input station MODBUS RTU slave application supplementary manual. MODBUS supplementary manual to the 2300-RO4 Installation Guide. The 2300 series stations are designed to

More information

isma-b-mg-ip User Manual Global Control 5 Sp. z o.o. Poland, Warsaw

isma-b-mg-ip User Manual Global Control 5 Sp. z o.o. Poland, Warsaw isma-b-mg-ip User Manual Global Control 5 Sp. z o.o. Poland, Warsaw www.gc5.pl Table of content 1 Introduction... 4 1.1 Revision history... 5 1.2 Safety rules... 5 1.3 Technical specifications... 6 1.4

More information

Getting Started with your D3000M Series Module

Getting Started with your D3000M Series Module Getting Started with your D3000M Series Module This document contains step-by-step instructions to quickly connect and communicate with your D3000M modules. The modules require a one-time configuration

More information

CAN-Transceiver Data Register Map MODBUS Slave RTU

CAN-Transceiver Data Register Map MODBUS Slave RTU MODBUS Slave RTU V1.40 Table of Contents INTRODUCTION... 3 CAN TRANSCEIVER GLOBAL DATA... 3 OPTIONAL DIGITAL INPUTS... 3 AVC (TR CONTROL) REGISTER BASE ADDRESSES... 3 AVC MODBUS REGISTER DEFINITION...

More information

User Manual A08. User Manual

User Manual A08. User Manual A08 TABLE OF CONTENTS TABLE OF CONTENTS... 1 1. INTRODUCTION... 2 1.1. Key Features... 3 1.2. OS Requirement... 4 1.3. Specification... 4 1.4. Packing List... 4 2. OVERVIEW... 5 2.1. LED Definition...

More information

REL 512 Connectivity With A Harris Westronics RTU Using DNP 3.0

REL 512 Connectivity With A Harris Westronics RTU Using DNP 3.0 ABB Application Note Substation Automation and Protection Division REL 512 AN-45A-99 REL 512 Connectivity With A Harris Westronics RTU Using DNP 3.0 ABSTRACT: DNP 3.0 is a popular communication protocol

More information

DNP3 Device Profile. Device Profile Template. Data Dictionary. Release 2.0. January 30, 2001

DNP3 Device Profile. Device Profile Template. Data Dictionary. Release 2.0. January 30, 2001 Reclosers Kyle Form 4C Recloser Control Serial Communications Reference Information R280-90-1 DNP3 Device Profile Device Profile Template Data Dictionary Release 2.0 January 30, 2001 For Use With Cooper

More information

Lufkin Modbus Serial Driver Help Kepware Technologies

Lufkin Modbus Serial Driver Help Kepware Technologies Lufkin Modbus Serial Driver Help 2012 Kepware Technologies 2 Table of Contents Table of Contents 2 3 Overview 3 Channel Setup 4 Device Setup 5 Cable Diagram 5 Modem Setup 6 Block Sizes 6 Framing 7 Error

More information

RTU560 Connections and Settings DIN Rail RTU 560CIG10

RTU560 Connections and Settings DIN Rail RTU 560CIG10 Connections and Settings DIN Rail RTU 560CIG10 Application, characteristics and technical data have to be taken from the hardware data sheet: 560CIG10 1KGT 150 719 Operation The 560CIG10 is a DIN rail

More information

D-100 FLOW DISPLAY MODBUS Network Interface Installation Guide

D-100 FLOW DISPLAY MODBUS Network Interface Installation Guide MODBUS D-100 FLOW DISPLAY MODBUS Network Interface Installation Guide 11451 Belcher Road South, Largo, FL 33773 USA Tel +1 (727) 447-6140 Fax +1 (727) 442-5699 www.onicon.com sales@onicon.com 03-18 0657-9

More information

InstrumentationTools.com

InstrumentationTools.com Author: Instrumentation Tools Categories: Communication Difference between Modbus and DNP3 Communication Protocols Overview Modbus and DNP are both byte-oriented protocols. Modbus is an application layer

More information

MOD-MUX MODBUS TCP I/O PRODUCTS

MOD-MUX MODBUS TCP I/O PRODUCTS MOD-MUX MODBUS TCP I/O PRODUCTS Catalog and Design Guide P.O.Box 24 Stanfield 3613 SOUTH AFRICA Tel: +27 (031) 7028033 Fax: +27 (031) 7028041 Email: proconel@proconel.com Web: www.proconel.com 22/09/2009

More information

CURRENT PROTECTION RELAY SMPR-1

CURRENT PROTECTION RELAY SMPR-1 CURRENT PROTECTION RELAY SMPR-1 1.- ORION ITALIA SERIES MODBUS PROTOCOL. The ORION ITALIA SERIES implement a subset of the AEG Modicon Modbus serial communication standard. Many devices support this protocol

More information

XL200 Series PLC Interface

XL200 Series PLC Interface Copyright 2010 AMS Controls, Inc. All rights reserved. The information contained in this document is proprietary to AMS Controls, Inc., and is not to be reproduced in any form without the specific written

More information

Intech Micro 2300-A8VI analogue input station MODBUS RTU slave application supplementary manual.

Intech Micro 2300-A8VI analogue input station MODBUS RTU slave application supplementary manual. Intech Micro 2300-A8VI analogue input station MODBUS RTU slave application supplementary manual. MODBUS supplementary manual to the 2300-A8VI Installation Guide. The 2300 series stations are designed to

More information

RS485 MODBUS Module 8I8O

RS485 MODBUS Module 8I8O Expansion Module 8 digital inputs, 8 digital outputs Version 2.2 12/01/2014 Manufactured for Thank you for choosing our product. This manual will help you with proper support and proper operation of the

More information

Model IR4000M. HART Field Device Specification Multi-Point Monitor. Instruction Manual 07-08

Model IR4000M. HART Field Device Specification Multi-Point Monitor. Instruction Manual 07-08 Model IR4000M HART Field Device Specification Multi-Point Monitor The information and technical data disclosed in this document may be used and disseminated only for the purposes and to the extent specifically

More information

MX200 SERIES Modbus Card 50P GE Zenith Controls. Operation and Maintenance Manual 50R-2200B 12/00

MX200 SERIES Modbus Card 50P GE Zenith Controls. Operation and Maintenance Manual 50R-2200B 12/00 g MX200 SERIES Modbus Card 50P-1105 GE Zenith Controls 50R-2200B 12/00 Operation and Maintenance Manual Table of Contents Overview...01 Page LED Indicator...02 Installation...03 Installing the Network

More information

Tongta Inverter TDS-F8

Tongta Inverter TDS-F8 Tongta Inverter TDS-F8 MODBUS Communication Application Manual Please ensure the user gets this manual, for the optimal use of this device. 1. Introduction: TEK-DRIVE / TDS-F8 INVERTER MODBUS Communication

More information

Installation & Operation Guide

Installation & Operation Guide Installation & Operation Guide (Shown with optional Override Board Cover) KMD-5831 Programmable Loop Controller PLC-28 Direct Digital Controller 902-019-04B 1 Introduction This section provides a brief

More information

Industrial Serial Device Server

Industrial Serial Device Server 1. Quick Start Guide This quick start guide describes how to install and use the Industrial Serial Device Server. Capable of operating at temperature extremes of -10 C to +60 C, this is the Serial Device

More information

MODBUS RTU I/O Expansion Modules - Models C267, C277, and C287. Installation and Operations Manual Section 50

MODBUS RTU I/O Expansion Modules - Models C267, C277, and C287. Installation and Operations Manual Section 50 MODBUS RTU I/O Expansion Modules - Models C267, C277, and C287 Installation and Operations Manual 00-02-0651 09-01-09 Section 50 In order to consistently bring you the highest quality, full featured products,

More information

Modbus Communications Board

Modbus Communications Board - Modbus Communications Board (RS-485) User Manual Document No. 360-0099-01 (Revision G) Sensidyne, LP. 1000 112 th Circle N, Suite 100 St. Petersburg, Florida 33716 USA 800-451-9444 +1 727-530-3602 +1

More information

Intelligent Devices IDI 1100 Series Technical Manual

Intelligent Devices IDI 1100 Series Technical Manual Intelligent Devices IDI 1100 Series 4411 Suwanee Dam Road, Suite 510 Suwanee, GA 30024 T: (770) 831-3370 support@intelligentdevicesinc.com Copyright 2011, Intelligent Devices, Inc. All Rights Reserved

More information

MODEL: R3-NE1. Remote I/O R3 Series. ETHERNET INTERFACE MODULE (Modbus/TCP) 27.5 (1.08)

MODEL: R3-NE1. Remote I/O R3 Series. ETHERNET INTERFACE MODULE (Modbus/TCP) 27.5 (1.08) MODEL: R-NE Remote I/O R Series ETHERNET INTERFACE MODULE (Modbus/TCP) 7. (.8) 9 (.9) (.) mm (inch) MODEL: R-NE-[][] ORDERING INFORMATION Code number: R-NE-[][] Specify a code from below for each [] and

More information

VD SERIES CONTROLLERS (VERSION4.0) RS-485 COMMUNICATION INSTRUCTION MANUAL MODBUS Protocol Reference Guide

VD SERIES CONTROLLERS (VERSION4.0) RS-485 COMMUNICATION INSTRUCTION MANUAL MODBUS Protocol Reference Guide VD SERIES CONTROLLERS (VERSION4.0) RS-485 COMMUNICATION INSTRUCTION MANUAL MODBUS Protocol Reference Guide 1. COMMUNICATION FUNCTIONS 1.1 General -----------------------------------------------------------------------------------------1

More information

T1K MODBUS Base Controller Specifications

T1K MODBUS Base Controller Specifications Base Controller 1 2 In This Chapter.... Base Controller Setting the DIP Switches Setting the Rotary Address Switches Port Pin out and Wiring RJ12 Serial Port Pin out and Wiring 2 2 Base Controller General

More information

Golander Peristaltic Pump MODBUS Communication Instruction

Golander Peristaltic Pump MODBUS Communication Instruction Golander Peristaltic Pump MODBUS Communication Instruction 1 Introduction... 1 2 Modbus Protocol... 2 2.1 Modbus Protocol Model... 2 2.2 Byte Format... 2 2.3 MODBUS Message Timing... 2 2.4 Field... 3 2.5

More information

BCT SERIES CONTROLLERS (VERSION 3.0) RS-485 COMMUNICATION INSTRUCTION MANUAL MODBUS Protocol Reference Guide

BCT SERIES CONTROLLERS (VERSION 3.0) RS-485 COMMUNICATION INSTRUCTION MANUAL MODBUS Protocol Reference Guide BCT SERIES CONTROLLERS (VERSION 3.0) RS-485 COMMUNICATION INSTRUCTION MANUAL MODBUS Protocol Reference Guide 1. COMMUNICATION FUNCTIONS 1.1 General -----------------------------------------------------------------------------------------

More information

DATRAN XL4 PLUS RTU Quick Start Guide

DATRAN XL4 PLUS RTU Quick Start Guide DOC-QSG-XL4-PLUS-RTU DATRAN XL4 PLUS RTU Quick Start Guide Configuring the XL4 Plus RTU The XL4 Plus RTU is configured using software called QTech Workbench. Connection to your PC is via a USB cable (Type

More information

General Specifications

General Specifications General Specifications GS 34P02P22-02E DNP3 Communication Portfolio (FCN-500/FCN-RTU) GENERAL This General Specifications document describes the Distributed Network Protocol (DNP3) Communication Portfolio

More information

SmartMod DC Digital Input Module HE359DIM610 12/24VDC Negative Logic

SmartMod DC Digital Input Module HE359DIM610 12/24VDC Negative Logic MAN0842-02 DIM610 PAGE 1 of 6 SmartMod DC Digital Input Module HE359DIM610 12/24VDC Negative Logic 1 SPECIFICATIONS Number of Channels Input Ranges DIM610 12 PLC Update Rate 12/24 VDC Terminal Type DIM610

More information

NF760 Batch Controller

NF760 Batch Controller NF760 Batch Controller Overview The NF760 Batch Controller is suited to flow applications where precise measurement and control of batch quantities is required. Batch total, flow rate, accumulated total

More information

D115 The Fast Optimal Servo Amplifier For Brush, Brushless, Voice Coil Servo Motors

D115 The Fast Optimal Servo Amplifier For Brush, Brushless, Voice Coil Servo Motors D115 The Fast Optimal Servo Amplifier For Brush, Brushless, Voice Coil Servo Motors Ron Boe 5/15/2014 This user guide details the servo drives capabilities and physical interfaces. Users will be able to

More information

4511 MODBUS RTU. Configuration Manual. Pulse isolator. No. 9202MCM101(1707) For 4511 devices from ser. no:

4511 MODBUS RTU. Configuration Manual. Pulse isolator. No. 9202MCM101(1707) For 4511 devices from ser. no: 4511 MODBUS RTU Configuration Manual Pulse isolator No. 9202MCM101(1707) For 4511 devices from ser. no: 141590001 9202 CONTENTS Introduction...3 Modbus basics...3 Modbus RTU...3 4511 Supported Modbus Function

More information

4511 MODBUS RTU. Configuration Manual. HART transparent driver. No. 9107MCM102(1739) For 4511 devices from ser. no:

4511 MODBUS RTU. Configuration Manual. HART transparent driver. No. 9107MCM102(1739) For 4511 devices from ser. no: 4511 MODBUS RTU Configuration Manual HART transparent driver No. 9107MCM102(1739) For 4511 devices from ser. no: 141590001 9107 CONTENTS Introduction... 3 Modbus basics... 3 Modbus RTU... 3 4511 Supported

More information

DUAL LOOP DETECTOR WITH MODBUS COMMUNICATIONS

DUAL LOOP DETECTOR WITH MODBUS COMMUNICATIONS LD220 DUAL LOOP DETECTOR WITH MODBUS COMMUNICATIONS USER MANUAL P.O.Box 24 STANFIELD 3613 SOUTH AFRICA Tel: +27 (031) 7028033 Fax: +27 (031) 7028041 Email: proconel@proconel.com Web: www.proconel.com 18/08/2005

More information

SC2000 MOTOR PROTECTION ELECTRONICS, INC. INSTRUCTION MANUAL. (407) Phone: Website:

SC2000 MOTOR PROTECTION ELECTRONICS, INC. INSTRUCTION MANUAL. (407) Phone: Website: SC2000 INSTRUCTION MANUAL MOTOR PROTECTION ELECTRONICS, INC. 2464 Vulcan Road Apopka, Florida 32703 Phone: Website: (407) 299-3825 www.mpelectronics.com Operating Program Revision: 12 Revision Date: 8-27-14

More information

The following simple procedures should be performed prior to testing the 289H M relay card:

The following simple procedures should be performed prior to testing the 289H M relay card: 289H M LSS Installation & Operations Manual Start Up & Test Procedures Chapter 5 INTRODUCTION The information in this section of the manual provides the step by step procedures for conducting any testing

More information

General Specifications

General Specifications General Specifications DNP3 Communication Portfolio GS 34P02P22-01E GENERAL This General Specifications document describes the Distributed Network Protocol (DNP3) Communication Portfolio for STARDOM. The

More information

Operator Manual for Profibus

Operator Manual for Profibus PROCESS ANALYSERS SERVOPRO MultiExact Operator Manual for Profibus Part Number: Revision: Language: 05410007A 0 UK English This page intentionally blank LIST OF CONTENTS Section Page 1. DESCRIPTION AND

More information

How to set-up and read MOBBUS

How to set-up and read MOBBUS How to set-up and read MOBBUS Before anything can be read from the RTU, the meter must be programmed. During programming up to 16 of the thousands of displays in the meter can be assigned to the RTU. The

More information

DNP3 Device Profile Document For ARE-M Series Float Chargers Single-Phase Input

DNP3 Device Profile Document For ARE-M Series Float Chargers Single-Phase Input DNP3 Device Profile Document For ARE-M Series Float Chargers Single-Phase Input PM990.1072.00, Issue 6 UNIPOWER, LLC 3900 Coral Ridge Drive Coral Springs, FL 33065 Phone: +1-954-346-2442 Toll Free: 1-800-440-3504

More information