CONNECTING SENSORS TO DATA ACQUISITION SYSTEM ANALOG INPUTS

Size: px
Start display at page:

Download "CONNECTING SENSORS TO DATA ACQUISITION SYSTEM ANALOG INPUTS"

Transcription

1 CONNECTING SENSORS TO DATA ACQUISITION SYSTEM ANALOG INPUTS Properly connecting sensors to a data acquisition system is as crucial as selecting the proper sensor for the application, and there are multiple factors that need to be taken into consideration to ensure that stable measurements are acquired with minimal noise and effect on other components connected to the system. This white paper discusses the recommended methods for connecting sensors and/or external signals to +/-10V analog inputs that are provided on data acquisition systems for end user connection. A sensor that is wired to a system incorrectly can not only cause inaccurate measurements on that channel, it could possibly introduce problems on other channels including channels that had been working correctly previously. The following simplified schematic is representative of a single analog input connection provided in a Wineman Technology data acquisition system, and will be used as the basis for this paper. The analog input is configured as differential and is typical of that found on many of the National Instruments data acquisition modules across the PC, PXI, NI CompactDAQ, and CompactRIO platforms. Terminals or a bulkhead connector will be provided in a typical Wineman Technology design data acquisition system for connecting external sensors and will include the following connections:

2 One common misconception is that an analog input on a data acquisition system is similar to a digital multimeter (DMM). There have been cases where a sensor will read correctly with a DMM yet will not provide valid readings on a data acquisition system. Although an analog input appears to be like a DMM measuring voltage, it is not intended for measuring floating signals. Most data acquisition modules require that the signal have a common mode voltage of. Connecting 4-Wire Sensors Many of the sensors commonly used for data acquisition provide a 4-wire connection. The types of sensors that fall into this category include conditioned bridge-type transducers, such as pressure transducers, load cells, and torque transducers. For the purpose of this example, we will focus on strain-type devices; however the principals outlined below also apply to other sensor types. Many manufacturers of strain-type sensors provide options for including integrated signal conditioning in the sensor since it delivers a linearized, highlevel signal (+/-10V typically) to the data acquisition system, as opposed to providing signals at or below 50mV. Noise induced on higher-level signals will be less significant than if induced on a low-level signal. The following schematic provides the recommended wiring for connecting a 4- wire sensor to a data acquisition system.

3 Connecting 3-Wire Sensors Some sensors are provided with 3-wire connections and may include OEM-type pressure transducers as well as potentiometers. Connecting a 3-wire sensor to a data acquisition system is similar to the method used for connecting a 4-wire sensor, except the negative signal will be tied to the excitation common at the sensor. It is possible to wire a 3-wire sensor to the data acquisition system using a 3- conductor shielded cable and providing a jumper at the terminal between EXCand SIG- but the signal will be more susceptible to noise since it is not being transmitted on a differential pair. Connecting a Current Loop Sensor Transducers powered by current loops are also used on data acquisition systems and can be wired into a voltage analog input easily by adding a pull-down resistor (as shown below). Typically 500Ω resistors are used to create a 10V drop across the analog input, though 250Ω resistors can be used for creating a 5V drop instead. Any value of resistor can be used as long as it does not create more than a 10V drop at the full-scale output of the sensor. It is best practice to use

4 either a high-precision metal film or wire-wound resistor to provide an accurate, stable resistance with minimal drift. Connecting a Floating Sensor When it is necessary to connect a floating sensor to an analog input on a data acquisition system, a 1MΩ bias resistor will need to be installed in order to ensure that the signal is within the common-mode voltage range of the analog input. The resistor will provide the necessary reference while minimizing the current induced by connecting the two circuits. The following schematic provides an example of how to connect a batterypowered sensor to a data acquisition system. There are special cases when the sensor is a device powered by a separate circuit (i.e., the speed feedback from a variable frequency drive) where it would be best to install a signal isolator between the two circuits (this is covered in the next section). Terminating Shields There are three basic rules that should always be followed when terminating shields, though they frequently are overlooked.

5 1. The shield should be connected to the zero-signal reference potential of the signal contained within the cable. 2. The shield should be connected to the zero-signal reference potential at the signal-earth connection. 3. The shield should only be terminated at one end. As the cable increases in length between a data acquisition system and a sensor, the importance of terminating the shield properly increases. A properly terminated shield will create a low-pass filter that will become a high-pass filter if terminated at the other end. There are special cases where shields are terminated at both ends; however, this should be avoided as it introduces the chance of inducing current through the shield. This may happen due to potential differences between the ground planes at either end, creating what is commonly referred to as a ground loop. Cable Selection For optimal system performance, all sensors need to be connected to the data acquisition system using shielded twisted pair cabling. The shield, when properly terminated, will minimize voltage induced by outside electromagnetic sources which may include electric power transmission lines, load switching, fluorescent lighting, and/or radio signals. A twisted pair will cause any induced noise to be generated equally on both signal lines so that it can be eliminated by a differential analog input. When installing shielded twisted pair cabling, it is recommended that the length of exposed, unshielded wire be minimized to a length not exceeding 4 when terminated inside the data acquisition enclosure, and 2 if terminated outside the enclosure. There are a wide variety of vendors that provide twisted shielded cables intended for use in data acquisition systems. When selecting cable, it is preferred that each twisted pair be individually shielded in order to minimize any capacitive coupling between the excitation power and the measured signal. The following is a sample of some of the cables used by Wineman Technology when designing and building a data acquisition system. Belden 8723 Two Twisted Shielded Pair Cable with PVC Jacket

6 Belden 8451 One Twisted Shielded Pair Cable with PVC Jacket While wiring sensors to systems may seem mundane, research and planning can ensure a properly functioning system and can help avoid costly problems later in the project. There are many other wiring considerations that we didn t cover in this article; however, we are confident that the practices discussed above will help you on your next application. If you need additional help please do not hesitate to contact us at winemantech.com/contact.

Isolated Voltage Input 3B30 / 3B31 FEATURES APPLICATIONS PRODUCT OVERVIEW FUNCTIONAL BLOCK DIAGRAM

Isolated Voltage Input 3B30 / 3B31 FEATURES APPLICATIONS PRODUCT OVERVIEW FUNCTIONAL BLOCK DIAGRAM Isolated Voltage Input 3B30 / 3B31 FEATURES Interfaces, amplifies, & filtersanalog input voltages. Narrow-bandwidth (3Hz) single-channel single conditioning. Module provides simultaneous precision voltage

More information

Isolated Wideband Voltage Input 3B40 / 3B41 FEATURES APPLICATIONS PRODUCT OVERVIEW FUNCTIONAL BLOCK DIAGRAM

Isolated Wideband Voltage Input 3B40 / 3B41 FEATURES APPLICATIONS PRODUCT OVERVIEW FUNCTIONAL BLOCK DIAGRAM Isolated Wideband Voltage Input 3B40 / 3B41 FEATURES Interfaces, amplifies, protects& filters wide-bandwidth (h0 khz) single-channel analog voltage inputs. Module provides simultaneous precision voltage

More information

OBSOLETE. Isolated, Linearized, Thermocouple Input 3B47 FEATURES APPLICATIONS PRODUCT OVERVIEW FUNCTIONAL BLOCK DIAGRAM

OBSOLETE. Isolated, Linearized, Thermocouple Input 3B47 FEATURES APPLICATIONS PRODUCT OVERVIEW FUNCTIONAL BLOCK DIAGRAM FEATURES Interfaces, amplifies, filters, isolates, & linearizes analog input voltages from a J, K, T, E, R, S or B-type thermocouple Thermocouple input signal is internally linearized High accuracy internal

More information

Wide Bandwidth Strain Gage Input 3B18 FEATURES APPLICATIONS PRODUCT OVERVIEW FUNCTIONAL BLOCK DIAGRAM

Wide Bandwidth Strain Gage Input 3B18 FEATURES APPLICATIONS PRODUCT OVERVIEW FUNCTIONAL BLOCK DIAGRAM Wide Bandwidth Strain Gage Input 3B18 FEATURES Wideband (20 khz) single-channel signal conditioning module. Module Bandwidth is user-selectable between 20 khz and 100Hz, with user-supplied filter caps

More information

Strain gauge Measuring Amplifier GSV-1A8. Instruction manual GSV-1A8, GSV-1A8USB, GSV-1A16USB

Strain gauge Measuring Amplifier GSV-1A8. Instruction manual GSV-1A8, GSV-1A8USB, GSV-1A16USB Strain gauge Measuring Amplifier GSV-1A8 Instruction manual GSV-1A8, GSV-1A8USB, GSV-1A16USB GSV-1A8USB SubD1 (front side) GSV-1A8USB M12 (front side) GSV-1A16USB (rear side) GSV-1A8USB K6D (front side)

More information

Signal Connections CHAPTER

Signal Connections CHAPTER 2 CHAPTER 3 Signal Connections This chapter provides useful information on how to connect input and output signals to the USB-4704 via the I/O connectors. Sections include: Overview I/O Connectors Analog

More information

Isolated Linearized RTD Input 5B34 FEATURES APPLICATIONS PRODUCT OVERVIEW FUNCTIONAL BLOCK DIAGRAM

Isolated Linearized RTD Input 5B34 FEATURES APPLICATIONS PRODUCT OVERVIEW FUNCTIONAL BLOCK DIAGRAM Isolated Linearized RTD Input 5B34 FEATURES Amplifies, Protects, Filters, and Isolates Analog Input. Linearize a wide variety of 2 & 3 wire RTDs. (True 4-wire RTD measurements are provided by the 5B35).

More information

Delta Controls. Wiring and Installation Guidelines

Delta Controls. Wiring and Installation Guidelines Delta Controls Wiring and Installation Guidelines Copyright Information Document Title: Delta Controls Wiring and Installation Guidelines Edition: 1.5 Revised: June 2012 o part of this document may be

More information

Isolated Process Current Output 3B39 FEATURES APPLICATIONS PRODUCT OVERVIEW FUNCTIONAL BLOCK DIAGRAM

Isolated Process Current Output 3B39 FEATURES APPLICATIONS PRODUCT OVERVIEW FUNCTIONAL BLOCK DIAGRAM Isolated Process Current Output 3B39 FEATURES Interfaces, isolates, & filters a 0 to +10V or -10V to +10V input signal and provides an isolated process current output across loads of 0 to 850Ω.. Intended

More information

EVAL-INAMP-62RZ/82RZ/82RMZ

EVAL-INAMP-62RZ/82RZ/82RMZ Evaluation Boards for the AD620 Series and and the AD8220 Series Instrumentation Amplifiers EVAL-INAMP-62RZ/82RZ/82RMZ FEATURES 3 generic, easy-to-use PC boards Support several related in-amp products

More information

Techniques to Reduce Measurement Errors in Challenging Environments

Techniques to Reduce Measurement Errors in Challenging Environments Techniques to Reduce Measurement Errors in Challenging Environments Jon Semancik VTI Instruments Corp. 2031 Main Street Irvine, CA 92614 949-955-1894 jsemancik@vtiinstruments.com INTRODUCTION Test engineers

More information

Safety Barriers. CEAG safety barriers can be used for all kinds of instrumentation applications.

Safety Barriers. CEAG safety barriers can be used for all kinds of instrumentation applications. Safety Barriers Description Safety barriers limit the energy fed to an intrinsically safe circuit so that neither sparks nor thermal effects (hot surfaces) can cause an explosion. CEAG safety barriers

More information

Strain gauge Measuring Amplifier GSV-1A8. Instruction manual GSV-1A8, GSV-1A8USB, GSV-1A16USB

Strain gauge Measuring Amplifier GSV-1A8. Instruction manual GSV-1A8, GSV-1A8USB, GSV-1A16USB Strain gauge Measuring Amplifier GSV-A8 Instruction manual GSV-A8, GSV-A8USB, GSV-A6USB GSV-A8USB SubD5 (front side) GSV-A8USB M2 (front side) GSV-A6USB (rear side) GSV-A8USB K6D (front side) Version:

More information

UNIVERSAL MOTION INTERFACE (UMI) ACCESSORY

UNIVERSAL MOTION INTERFACE (UMI) ACCESSORY USER GUIDE UNIVERSAL MOTION INTERFACE (UMI) ACCESSORY Introduction This user guide describes how to use the UMI-A, UMI-Flex, and UMI-Flex accessories. The UMI products are connectivity accessories you

More information

LDD M SERIES INSTRUCTION MANUAL LDD M SERIES

LDD M SERIES INSTRUCTION MANUAL LDD M SERIES TM LDD M SERIES LDD M SERIES INSTRUCTION MANUAL P O Box Bozeman, MT 9 Phone (0) -90 Fax (0) -9 email sales@wavelengthelectronics.com www.wavelengthelectronics.com TABLE OF CONTENTS Features... Customer

More information

Electromagnetic Compatibility ( EMC )

Electromagnetic Compatibility ( EMC ) Electromagnetic Compatibility ( EMC ) ESD Strategies in IC and System Design 8-1 Agenda ESD Design in IC Level ( ) Design Guide Lines CMOS Design Process Level Method Circuit Level Method Whole Chip Design

More information

AWP-24 Wave Height Gauge. Acquiring Minimum Noise Data Application Note

AWP-24 Wave Height Gauge. Acquiring Minimum Noise Data Application Note AWP24 Wave Height Gauge Acquiring Minimum Noise Data Application Note Issue: 10 Status: Released 14September2009 Prepared by Akamina Technologies Inc Akamina Technologies 91 Norice St,Ottawa,OntarioK2G

More information

Integrity Instruments Application Notes. Release 1

Integrity Instruments Application Notes. Release 1 Integrity Instruments Application Notes Release 1 What is EIA/TIA/RS-485 What is EIA/TIA/RS-422 Half Duplex and Full Duplex Communication Asynchronous Communicatin Grounding EIA/TIA/RS-485/422 Shielding

More information

Isolated, Voltage or Current Input 7B30 FEATURES APPLICATIONS PRODUCT OVERVIEW FUNCTIONAL BLOCK DIAGRAM

Isolated, Voltage or Current Input 7B30 FEATURES APPLICATIONS PRODUCT OVERVIEW FUNCTIONAL BLOCK DIAGRAM Isolated, Voltage or Current Input 7B30 FEATURES Interfaces, amplifies and filters unipolar and bipolar millivolt and voltage inputs. Provides a protected precision output of either +1 V to +5 V or 0 V

More information

Data Acquisition Card or DMM: Which is Right for Your Application? By John Tucker and Joel Roop Keithley Instruments, Inc.

Data Acquisition Card or DMM: Which is Right for Your Application? By John Tucker and Joel Roop Keithley Instruments, Inc. Data Acquisition Card or DMM: Which is Right for Your Application? By John Tucker and Joel Roop Keithley Instruments, Inc. When automating voltage measurements, is it better to go with a programmable Digital

More information

SCXI OFFSET-NULL AND SHUNT-CALIBRATION HIGH-VOLTAGE TERMINAL BLOCK INSTALLATION GUIDE

SCXI OFFSET-NULL AND SHUNT-CALIBRATION HIGH-VOLTAGE TERMINAL BLOCK INSTALLATION GUIDE SCXI -1321 OFFSET-NULL AND SHUNT-CALIBRATION HIGH-VOLTAGE TERMINAL BLOCK INSTALLATION GUIDE Conventions This guide describes how to install and use the SCXI-1321 offset-null and shunt-calibration terminal

More information

User s Guide 200 ma Current Source Module CSM-39020

User s Guide 200 ma Current Source Module CSM-39020 User s Guide 200 ma Current Source Module CSM-39020 ILX Lightwave Corporation 31950 Frontage Road Bozeman, MT, U.S.A. 59715 U.S. & Canada: 1-800-459-9459 International Inquiries: 406-556-2481 Fax 406-586-9405

More information

Determination of Calibration Factors

Determination of Calibration Factors Determination of Calibration Factors Digital data acquisition system use analog-to-digital converters (ADCs) to convert analog voltages from sensors to digital, binary data. The most common ADCs used for

More information

JR3 EXTERNAL SENSOR ELECTRONICS WITH ANALOG OUTPUT. JR3, Inc. 22 Harter Ave. Woodland, CA 95776

JR3 EXTERNAL SENSOR ELECTRONICS WITH ANALOG OUTPUT. JR3, Inc. 22 Harter Ave. Woodland, CA 95776 JR3 EXTERNAL SENSOR ELECTRONICS WITH ANALOG OUTPUT JR3, Inc. 22 Harter Ave. Woodland, CA 95776 5962C 15 December, 2003 TABLE OF CONTENTS CHAPTER 1 OVERVIEW General...1-1 Sensor...1-1 Electronic System...1-1

More information

Agilent Strain Measurement Application Using Agilent U2300A Series Data Acquisition Devices With Agilent VEE Pro. Application Note

Agilent Strain Measurement Application Using Agilent U2300A Series Data Acquisition Devices With Agilent VEE Pro. Application Note Agilent Strain Measurement Application Using Agilent U2300A Series Data Acquisition Devices With Agilent VEE Pro Application Note Introduction This application note is designed for users who wish to test

More information

Lab 4: Introduction to ELVIS II+ Introduction to ELVIS II+

Lab 4: Introduction to ELVIS II+ Introduction to ELVIS II+ Page 1 of 12 Laboratory Goals Introduction to ELVIS Lab 4: Introduction to ELVIS Familiarize students with the National Instruments hardware ELVIS Identify the capabilities of ELVIS Make use of the built

More information

MDK. Accelnet Module DevKit. Provides Mounting & Connections for Accelnet CANopen Servoamplifiers FEATURES

MDK. Accelnet Module DevKit. Provides Mounting & Connections for Accelnet CANopen Servoamplifiers FEATURES Provides Mounting & Connections for Accelnet CANopen Servoamplifiers FEATURES Works with all Accelnet Models Develop & Debug Accelnet projects then transfer design to oem pc board. Dev Kit Model * Vdc

More information

EMC Installation Guide

EMC Installation Guide A P P E N D I X B EMC Installation Guide General Product Philosophy Meeting requirements for electromagnetic compatibility (EMC) compliance will require specific measures to be taken during installation

More information

GSV-1A4 M12/2 M12/2. Highlights

GSV-1A4 M12/2 M12/2. Highlights GSV-1A4 M12/2 M12/2 Highlights Input sensitivity: 2mV/V; 4mV/V, 2 mv/v, 1mV/V, 0.5mV/V configurable via jumpers Output signals ±10V AND 12mA+-8mA on 15 pin Sub-D Integrated half and quarter bridge completion

More information

BX8 8-Channel Digital Amplifier

BX8 8-Channel Digital Amplifier 8-Channel Digital Amplifier 8-Channel Synchronized Sampling Internal Calculation of Axis Load Values for 6-Axis Sensors Active Scaling of Analog Outputs according to Internal Calculations ±5V, ±10V, 4-20mA,

More information

UNIVERSAL MOTION INTERFACE (UMI) ACCESSORY

UNIVERSAL MOTION INTERFACE (UMI) ACCESSORY USER GUIDE UNIVERSAL MOTION INTERFACE (UMI) ACCESSORY Contents This user guide describes how to use the UMI-77, UMI-A, UMI-Flex, and UMI-Flex accessories. Introduction... What You Need to Get Started...

More information

D115 The Fast Optimal Servo Amplifier For Brush, Brushless, Voice Coil Servo Motors

D115 The Fast Optimal Servo Amplifier For Brush, Brushless, Voice Coil Servo Motors D115 The Fast Optimal Servo Amplifier For Brush, Brushless, Voice Coil Servo Motors Ron Boe 5/15/2014 This user guide details the servo drives capabilities and physical interfaces. Users will be able to

More information

Dept. of Electrical, Computer and Biomedical Engineering. Instrumentation for the data acquisition laboratory

Dept. of Electrical, Computer and Biomedical Engineering. Instrumentation for the data acquisition laboratory Dept. of Electrical, Computer and Biomedical Engineering Instrumentation for the data acquisition laboratory Purpose of the lab activity Design and make simple systems for data acquisition from detectors,

More information

ABB Drives. User s Manual Modbus Adapter Module FMBA-01

ABB Drives. User s Manual Modbus Adapter Module FMBA-01 ABB Drives User s Manual Modbus Adapter Module FMBA-01 Modbus Adapter Module FMBA-01 User s Manual 3AFE68586704 REV A EN EFFECTIVE: 27.06.2005 2005 ABB Oy. All Rights Reserved. 5 Safety instructions

More information

FEATURES DESCRIPTION MODEL 110B. Power Supply

FEATURES DESCRIPTION MODEL 110B. Power Supply FEATURES Extends wiring distance of FT-10 LonWorks Networks. (2) channels using a single Model 110B. Up to 10 channels using (5) Model 110B. Low cost alternative to routers configured as repeaters. Wring

More information

Temperature measurement board, optically isolated, 16/8/4 channels for thermocouples, Pt100, RTD, 18-bit

Temperature measurement board, optically isolated, 16/8/4 channels for thermocouples, Pt100, RTD, 18-bit Temperature measurement board, optically isolated, 16/8/ channels for thermocouples, Pt100, RTD, 18-bit APCI-3200 Up to 16 channels for thermocouples or 8 inputs for resistance temperature detectors (RTD)

More information

ALMEMO 202 ALMEMO professional measuring instrument, latest V7 generation with data logger function. ALMEMO V7 Measuring Instrument

ALMEMO 202 ALMEMO professional measuring instrument, latest V7 generation with data logger function. ALMEMO V7 Measuring Instrument ALMEMO V7 Measuring Instrument ALMEMO 202 ALMEMO professional measuring instrument, latest V7 generation with data logger function. Two measuring inputs for all digital ALMEMO D7 sensors. Special functions

More information

BE/EE189 Design and Construction of Biodevices Lecture 5. BE/EE189 Design and Construction of Biodevices - Caltech

BE/EE189 Design and Construction of Biodevices Lecture 5. BE/EE189 Design and Construction of Biodevices - Caltech BE/EE189 Design and Construction of Biodevices Lecture 5 LabVIEW Programming Data acquisition DAQ system Signals and signal conditioning Nyquist frequency NI ELVIS II NI-DAQmx and DAQ assistant LabVIEW

More information

Isolated Current Output 5B39 FEATURES APPLICATIONS PRODUCT OVERVIEW

Isolated Current Output 5B39 FEATURES APPLICATIONS PRODUCT OVERVIEW Isolated Current Output 5B39 FEATURES Converts a High-level analog input voltage into a floating proportional output current. Output current of 4 to 20 ma or 0 to 20 ma across loads from 0Ω to 750Ω. High

More information

Adapter Kit - QSI Electronics to G2 Meter Installation Instructions

Adapter Kit - QSI Electronics to G2 Meter Installation Instructions Adapter Kit - QSI Electronics to G2 Meter Installation Instructions These installation instructions cover the adapter kit installation of the QSI1, QSI2 and QSI3 versions of communications electronics

More information

NI REM Remote I/O Overview DATASHEET. Analog Output Module for Remote I/O

NI REM Remote I/O Overview DATASHEET. Analog Output Module for Remote I/O DATASHEET NI REM-11115 Analog Output Module for Remote I/O Four voltage output ranges to choose from (0 V to 10V, ±10V, 0 V to 5 V, and ±5V) Two current output ranges to choose from (0 ma to 20mA, 4 ma

More information

System StrainSmart Data Acquisition System. Micro-Measurements FEATURES DESCRIPTION MODEL 5100B SCANNER SPECIFICATIONS

System StrainSmart Data Acquisition System. Micro-Measurements FEATURES DESCRIPTION MODEL 5100B SCANNER SPECIFICATIONS FEATURES From 5 to 1200 input channels can be configured as needed at any time Inputs accepted from strain gages and strain-gagebased transducers (Model 5110A), thermocouples (Model 5120A), sensors with

More information

TM0-1 AMPLIFIER / CONDITIONER MODULE OPERATORS MANUAL. Transducer Techniques R

TM0-1 AMPLIFIER / CONDITIONER MODULE OPERATORS MANUAL. Transducer Techniques R TM0-1 AMPLIFIER / CONDITIONER MODULE OPERATORS MANUAL Transducer Techniques R 42480 RIO NEDO, TEMECULA, CA 92590 (909) 719-3965 FAX (909) 719-3900 URL: http://www.ttloadcells.com E-mail: tti@ttloadcells.com

More information

5B Series 16 Channel Backplane 5B01 FEATURES APPLICATIONS PRODUCT OVERVIEW FUNCTIONAL BLOCK DIAGRAM

5B Series 16 Channel Backplane 5B01 FEATURES APPLICATIONS PRODUCT OVERVIEW FUNCTIONAL BLOCK DIAGRAM 5B Series 16 Channel Backplane 5B01 FEATURES Mix and Match 5B Series I/O Module Capability Factory Mutual (FM) Approved Approved for Use in Class I, Division2, Groups A, B, C, and D Locations. CE Certified:

More information

The IQ240 panel mount load cell indicator is a precision digital indicator for load cell and strain gauge applications.

The IQ240 panel mount load cell indicator is a precision digital indicator for load cell and strain gauge applications. IQ240 Panel Mount Load Cell Indicator Data sheet English 1.01 Introduction The IQ240 panel mount load cell indicator is a precision digital indicator for load cell and strain gauge applications. The high

More information

General Specifications. P2-08THM Analog Input

General Specifications. P2-08THM Analog Input General Specifications Operating Temperature Storage Temperature Humidity Environmental Air Vibration Shock Field to Logic Side Isolation Heat Dissipation Enclosure Type Agency Approvals Module Keying

More information

EDX-10 Series. Compact Recording System

EDX-10 Series. Compact Recording System 3-51 EDX-10 Series Compact Recording System Compact & lightweight, with a simple configuration, all channels synchronous 20 khz high-speed sampling (For 4 channels) Control Unit EDX-10B A unit controls

More information

RPS-401A, RPS-426A Self-Contained Ultrasonic Sensor

RPS-401A, RPS-426A Self-Contained Ultrasonic Sensor Features Adjustable Zero & Span Sensing Range 8-80 in. Narrow Sensing Beam LED Strength Indicator Short Circuit Protected Wide Temperature Range Selectable Inverted & Non- Inverted Outputs Analog Current

More information

R Series for USB Multifunction RIO with Kintex-7 160T FPGA. ni.com/manuals. Electromagnetic Compatibility Guidelines

R Series for USB Multifunction RIO with Kintex-7 160T FPGA. ni.com/manuals. Electromagnetic Compatibility Guidelines USER MANUAL R Series for USB Multifunction RIO with Kintex-7 160T FPGA Français Deutsch 日本語한국어简体中文 ni.com/manuals This document provides compliance, pinout, connectivity, mounting, and power information

More information

This data sheet is only valid in association with the IL SYS INST UM E user manual.

This data sheet is only valid in association with the IL SYS INST UM E user manual. Inline analog input terminal, 4 inputs for connecting voltage signals Data sheet 8081_en_01_C01 PHOENIX CONTACT 2015-04-14 1 Description The terminal is designed for use within an Inline station. It is

More information

DECK All-In-One Enclosure. Quick Installation Guide for Field Installers

DECK All-In-One Enclosure. Quick Installation Guide for Field Installers DECK All-In-One Enclosure Quick Installation Guide for Field Installers 1 Contents Legal Statement... 2 Preliminary Considerations... 2 Required Installation Tools and Materials... 2 Networking Information...

More information

Isolated Voltage Input 7B31 FEATURES APPLICATIONS PRODUCT OVERVIEW FUNCTIONAL BLOCK DIAGRAM

Isolated Voltage Input 7B31 FEATURES APPLICATIONS PRODUCT OVERVIEW FUNCTIONAL BLOCK DIAGRAM Isolated Voltage Input 7B31 FEATURES Interfaces, amplifies, and filters unipolar and bipolar voltage inputs. Module provides a precision output of either +1 V to +5 V or 0 V to +10 V, linear with temperature.

More information

CheckSum. FUNC-2B Functional Test Module. The FUNC-2B features:

CheckSum. FUNC-2B Functional Test Module. The FUNC-2B features: CheckSum FUNC-2B Functional Test Module FUNC-2B Functional Test Module Made in U.S.A. The CheckSum Model FUNC-2B Functional Test System is designed to be used as an extension to a CheckSum ICT System.

More information

E2 Controller Wiring Practices Rev 4 19-APR-2010

E2 Controller Wiring Practices Rev 4 19-APR-2010 E2 Controller Wiring Practices 026-1903 Rev 4 19-APR-2010 1640 Airport Road Suite #104 Kennesaw, GA 30144 Phone 770-425-2724 Fax 770-425-9319 ALL RIGHTS RESERVED The information contained in this manual

More information

OBSOLETE. CanWorks itrax Two-Channel Control Unit Installation. Instruction Sheet P/N A

OBSOLETE. CanWorks itrax Two-Channel Control Unit Installation. Instruction Sheet P/N A Instruction Sheet P/N 1047805A CanWorks itrax Two-Channel Installation WARNING: Allow only qualified personnel to perform the following tasks. Follow the safety instructions in this document and all other

More information

GE Fanuc IC694ALG221. Rx3i PacSystem

GE Fanuc IC694ALG221. Rx3i PacSystem GE Fanuc IC694ALG221 http://www.pdfsupply.com/automation/ge-fanuc/rx3i-pacsystem/ic694alg221 Rx3i PacSystem Input module, analog 4 point current. IC694A IC694AL IC694ALG 919-535-3180 sales@pdfsupply.com

More information

MODEL 8000MP LEVEL SENSOR

MODEL 8000MP LEVEL SENSOR 1 MODEL 8000MP LEVEL SENSOR INSTRUCTIONS FOR INSTALLATION, OPERATION & MAINTENANCE VISIT OUR WEBSITE SIGMACONTROLS.COM 2 SERIES 8000MP LEVEL SENSOR 1. DESCRIPTION The Model 8000MP Submersible Level Sensor

More information

Appendix D. EMC Installation Guidelines. Safety Considerations. Ferrite Absorbers and P-Clips. General Product Philosophy

Appendix D. EMC Installation Guidelines. Safety Considerations. Ferrite Absorbers and P-Clips. General Product Philosophy Appendix D EMC Installation Guidelines General Product Philosophy The ZETA6xxx was not designed originally for EMC compliance. Therefore, it will require specific measures to be taken during installation.

More information

JR3 EXTERNAL SENSOR ELECTRONICS WITH SERIAL DATA OUTPUT. JR3, Inc. 22 Harter Ave. Woodland, CA 95776

JR3 EXTERNAL SENSOR ELECTRONICS WITH SERIAL DATA OUTPUT. JR3, Inc. 22 Harter Ave. Woodland, CA 95776 JR3 EXTERNAL SENSOR ELECTRONICS WITH SERIAL DATA OUTPUT JR3, Inc. 22 Harter Ave. Woodland, CA 95776 5963B 13 October, 2003 TABLE OF CONTENTS CHAPTER 1 OVERVIEW General...1-1 Sensor...1-1 Electronic System...1-1

More information

Quick Installation Guide for Field Installers

Quick Installation Guide for Field Installers 1 Quick Installation Guide for Field Installers 2 Contents Legal Statement 3 Required Installation Tools and Materials 3 Networking Information 3 Modbus Communication and Wiring 4 Modbus Network and Layout

More information

Adapter Kit - QSI Electronics to TM Meter Installation Instructions

Adapter Kit - QSI Electronics to TM Meter Installation Instructions Adapter Kit - QSI Electronics to TM Meter Installation Instructions These installation instructions cover the adapter kit installation of the QSI1, QSI2 and QSI3 versions of communications electronics

More information

GSV-3USBx2 3,5mV/V 4,2V

GSV-3USBx2 3,5mV/V 4,2V x2 3,5mV/V 4,2V Highlights Powered via USB port Sampling rate 10 khz Data rate 1...1000 Hz straingage quarter, half, full bridges Built-in bridge supplement 350 Ohm Optionally also for displacement transducers

More information

The 1784-KR is a half-slot module that resides in any available expansion slot in an IBM XT (except slot J8) or AT compatible computer.

The 1784-KR is a half-slot module that resides in any available expansion slot in an IBM XT (except slot J8) or AT compatible computer. This document shows you how to install the 1784-KR module. Do not attempt to install the module until you have read this document. It contains the following sections: The 1784-KR module provides an interface

More information

VibraLINK switchable junction boxes Installation and operating guide VLL series

VibraLINK switchable junction boxes Installation and operating guide VLL series VibraLINK switchable junction boxes Installation and operating guide VLL series Caution: This guide should be read carefully before installation Wilcoxon Sensing Technologies 8435 Progress Drive, Frederick,

More information

Agilent 3630A Triple DC Power Supply. Agilent 34401A Digital Multimeter (DMM)

Agilent 3630A Triple DC Power Supply. Agilent 34401A Digital Multimeter (DMM) Agilent E3630A Triple DC Power Supply and Agilent 34401A Digital Multimeter (DMM) Agilent 3630A Triple DC Power Supply The DC power supply used in this lab is the Agilent E3630A Triple DC power supply.

More information

7-4-2 CP1W-MAD11/CPM1A-MAD11 Analog I/O Units

7-4-2 CP1W-MAD11/CPM1A-MAD11 Analog I/O Units 7-4-2 CP1W-MAD11/CPM1A-MAD11 I/O Units Part Names CP1W-MAD11/CPM1A-MAD11 Each CP1W-MAD11/CPM1A-MAD11 I/O Unit provides 2 analog inputs and 1 analog output. The analog input range can be set to 0 to 5 VDC,

More information

PRODUCT SHEET INTERFACE MODULES

PRODUCT SHEET INTERFACE MODULES INTERFACE MODULES HLTC UIMC When connecting the analog output sourcing from external devices to the MP or MP, channel contention must be considered. To connect external device outputs to the MP or MP:

More information

IB ST 24 AO 4/EF. INTERBUS-ST analog output module, 4 outputs, 0-10 V, ±10 V, 0-20 ma, 4-20 ma. Data sheet. 1 Description

IB ST 24 AO 4/EF. INTERBUS-ST analog output module, 4 outputs, 0-10 V, ±10 V, 0-20 ma, 4-20 ma. Data sheet. 1 Description INTERBUS-ST analog output module, 4 outputs, 0-10 V, ±10 V, 0-20 ma, 4-20 ma Data sheet 105597_en_01 PHOENIX CONTACT 2014-10-24 1 Description The module is designed for use within an ST station. It is

More information

LGR-5327 Specifications

LGR-5327 Specifications s Revision 1.0, April, 2010 Copyright 2010, Measurement Computing Corporation All specifications are subject to change without notice. Typical for 25 C unless otherwise specified. s in italic text are

More information

GE Fanuc IC694ALG391. Rx3i PacSystem

GE Fanuc IC694ALG391. Rx3i PacSystem GE Fanuc IC694ALG391 http://www.pdfsupply.com/automation/ge-fanuc/rx3i-pacsystem/ic694alg391 Rx3i PacSystem Output module analog 2 points, current. IC694A IC694AL IC694ALG 919-535-3180 sales@pdfsupply.com

More information

SECTION 1 INTRODUCTION. Walt Kester

SECTION 1 INTRODUCTION. Walt Kester SECTION 1 INTRODUCTION Walt Kester This book deals with sensors and associated signal conditioning circuits. The topic is broad, but the focus of this book is to concentrate on circuit and signal processing

More information

SCXI -1313A Terminal Block

SCXI -1313A Terminal Block INSTALLATION GUIDE SCXI -1313A Terminal Block Conventions This guide describes how to install and use the SCXI-1313A terminal block with an SCXI-1125 module. The SCXI-1313A terminal block is shielded and

More information

EDX-10 Series. Compact Recording System

EDX-10 Series. Compact Recording System 3-49 EDX-10 Series Compact Recording System Compact, lightweight, with a simple configuration, all channels synchronous 20 khz high-speed sampling (For 4 channels) Control Unit EDX-10B A unit controls

More information

TBX-1316 High-Voltage Attenuator Terminal Block

TBX-1316 High-Voltage Attenuator Terminal Block INSTALLATION GUIDE TBX-1316 High-Voltage Attenuator Terminal Block This guide describes how to install and use the TBX-1316 high-voltage attenuator terminal block with the following modules: SCXI-1125

More information

INSTALLATION INSTRUCTIONS

INSTALLATION INSTRUCTIONS www.altroniccontrols.com INSTALLATION INSTRUCTIONS EXACTA 21 MONITORING AND CONTROL SYSTEM CAUTION: The EXACTA 21 CONTROL SYSTEM is CSA CERTIFIED FOR use in Class I, GROUPS C & D, Division 2 hazardous

More information

NT PRESSURE TRANSDUCER MODELS 4100, 4210, 4130, 4230

NT PRESSURE TRANSDUCER MODELS 4100, 4210, 4130, 4230 P/N 0-027289 (Rev. A 04/4) NT PRESSURE TRANSDUCER MODELS 400, 420, 430, 4230 User Guide Table of Contents Safety Alert Symbol... 2 Introduction... 3 Installation... 3 Mechanical Installation... 3 Electrical

More information

Advanced NI-DAQmx Programming Techniques with LabVIEW

Advanced NI-DAQmx Programming Techniques with LabVIEW Advanced NI-DAQmx Programming Techniques with LabVIEW Agenda Understanding Your Hardware Data Acquisition Systems Data Acquisition Device Subsystems Advanced Programming with NI-DAQmx Understanding Your

More information

Isolated Process Current Input 7B32 FEATURES APPLICATIONS PRODUCT OVERVIEW FUNCTIONAL BLOCK DIAGRAM

Isolated Process Current Input 7B32 FEATURES APPLICATIONS PRODUCT OVERVIEW FUNCTIONAL BLOCK DIAGRAM Isolated Process Current Input 7B32 FEATURES Interfaces, amplifies and filters a process-current input. Module provides a precision output of either +1 V to +5 V or 0 V to +10 V, linear with temperature.

More information

Measurement Systems Datascan Installation and User Guide

Measurement Systems Datascan Installation and User Guide Measurement Systems Datascan Installation and User Guide Supplied By Contents Contents 1. INTRODUCTION... 1 1.1 GENERAL... 1 1.2 DATASCAN MODULE RANGE... 1 1.2.1 Measurement Processors... 1 1.2.2 Analog

More information

3 Chapter Introduction. 3.2 Copper Cable

3 Chapter Introduction. 3.2 Copper Cable 3 Chapter 3 3.1 Introduction The Network Media is the device that physically carries the data from computer to computer. The three major types of network media are: Copper Cable Fiber-Optic Cable Wireless

More information

DC Circuit Simulation

DC Circuit Simulation Chapter 2 DC Circuit Simulation 2.1 Starting the Project Manager 1. Select Project Manager from the Start All Program Cadence Release 16.5 Project Manager. 2. Select Allegro PCB Designer (Schematic) from

More information

The following conventions appear in this document:

The following conventions appear in this document: CALIBRATION PROCEDURE NI PXI-4220 Conventions This document contains the information and instructions needed to calibrate the NI PXI-4220. You should calibrate the NI PXI-4220 at a regular interval as

More information

SCXI Contents CALIBRATION PROCEDURE

SCXI Contents CALIBRATION PROCEDURE CALIBRATION PROCEDURE SCXI -1122 Contents This document contains information and step-by-step instructions for calibrating the National Instruments SCXI-1122 module. Introduction... 2 What Is Calibration?...

More information

A S C O R I N C O R P O R A T E D VXI MODULES

A S C O R I N C O R P O R A T E D VXI MODULES A S C O R I N C O R P O R A T E D VXI MODULES General Purpose Switch Modules Most VXI test environments require general purpose switching capabilities to enable and disable particular I/O circuits, especially

More information

High-Precision Data Acquisition

High-Precision Data Acquisition NI PCI-435, NI PXI-435 Temperature and voltage loggers Accuracy 0.4 C for J-type thermocouples, 0.03 C for thermistors, 0. C for RTDs 6 voltage or thermocouple inputs; up to 60 readings/s 8 digital I/O

More information

Adapter Kit - QSI Electronics to G-Series Meter Installation Instructions

Adapter Kit - QSI Electronics to G-Series Meter Installation Instructions Adapter Kit - QSI Electronics to G-Series Meter Installation Instructions These installation instructions cover the adapter kit installation of the QSI1, QSI2 and QSI3 versions of communications electronics

More information

955 ebrik INSTALLATION MANUAL. Series ebrik ABSOLUTE PROCESS CONTROL KNOW WHERE YOU ARE... REGARDLESS LINEAR DISPLACEMENT TRANSDUCERS

955 ebrik INSTALLATION MANUAL. Series ebrik ABSOLUTE PROCESS CONTROL KNOW WHERE YOU ARE... REGARDLESS LINEAR DISPLACEMENT TRANSDUCERS Series ebrik INSTALLATION MANUAL LINEAR DISPLACEMENT TRANSDUCERS ABSOLUTE PROCESS CONTROL KNOW WHERE YOU ARE... REGARDLESS Introduction The is an accurate programmable, auto-tuning, noncontact, linear

More information

RS485 MODBUS Module 8AO

RS485 MODBUS Module 8AO Version 1.3 12/02/2013 Manufactured for Thank you for choosing our product. This manual will help you with proper support and proper operation of the device. The information contained in this manual have

More information

This Presentation Will

This Presentation Will Investigating Basic Circuits Pre-Activity Discussion Digital Electronics 2014 Project Lead The Way, Inc. This Presentation Will Introduce you to basic circuits and their symbols. Introduce you to components

More information

ZENSOL CIRCUIT BREAKER PERFORMANCE ANALYZER

ZENSOL CIRCUIT BREAKER PERFORMANCE ANALYZER ZENSOL AUTOMATION INC. COMPUTERIZED TEST EQUIPMENT ZENSOL CIRCUIT BREAKER PERFORMANCE ANALYZER CBA-32P Micro CBA MANUAL 1W E OPERATOR S GUIDE Version 1.70 January 2001 www.zensol.com Man-1we.doc Rév 5

More information

Analog Input/Output Modules

Analog Input/Output Modules User s Manual Analog Input/Output Modules Addendum Manual No. :IM 34M06H11-01E Manual Title :Analog Input/Output Modules Edition :1st Edition With the adoption of the CE Marking conformance declaration

More information

BSL Hardware Guide for MP35 and MP30-1 -

BSL Hardware Guide for MP35 and MP30-1 - BSL Hardware Guide for MP35 and MP30-1 - MP35/30 ACQUISITION UNIT The MP35/30 data acquisition unit is the heart of the Biopac Student Lab PRO System. The MP35/30 has an internal microprocessor to control

More information

OPERATION MANUAL - DS-MOD-

OPERATION MANUAL - DS-MOD- Description Characteristic features Transducer electronics with current output 4...20 ma or voltage output 0...10 V For ceramic pressure sensor series DS-KE or other bridge signals Adjustment over potentiometer

More information

IST ULTRASTAB Power Supply for high precision transducers

IST ULTRASTAB Power Supply for high precision transducers IST ULTRASTAB Power Supply for high precision transducers High performance 6-channel power supply for multi-channel laboratory measurement applications. Features Current output or ±0 V voltage output (see

More information

Characteristics and functioning

Characteristics and functioning Characteristics and functioning 1/27 enod4-c Characteristics and functioning NU-eNod4C-ETH-E-1014_216706-A 1 ENOD4 PRODUCT RANGE... 4 1.1 General presentation... 4 1.2 Versions and options... 4 1.2.1 Versions...

More information

-Camille Bauer Div. of Absolute Process Instruments, Inc. Phone: Fax: J-1

-Camille Bauer Div. of Absolute Process Instruments, Inc. Phone: Fax: J-1 Solving Your Y Application Challenges! Phone: 800-462-4040 Fax: 800-949-7502 www.apicb.com 1220 American Way Libertyville, IL 60048 USA Copyright Absolute Process Instruments, Inc. 02/03 CBSK2003A J-1

More information

ICA S & H Strain Gauge or Load Cell Embedded Analogue Amplifier. User Benefits. Ideal Applications

ICA S & H Strain Gauge or Load Cell Embedded Analogue Amplifier. User Benefits. Ideal Applications ICA S & H Strain Gauge or Load Cell Embedded Analogue Amplifier User Benefits A range of high performance robust signal conditioners in a miniature OEM format and designed specifically for fitting inside

More information

LGR-5325 Specifications

LGR-5325 Specifications s Revision 1.0, April, 2010 Copyright 2010, Measurement Computing Corporation s All specifications are subject to change without notice. Typical for 25 C unless otherwise specified. s in italic text are

More information

SCB-68 User Guide. 68-Pin Shielded Desktop Connector Block

SCB-68 User Guide. 68-Pin Shielded Desktop Connector Block SCB-6 User Guide 6-Pin Shielded Desktop Connector Block This guide describes how to connect and use the NI SCB-6 with 6-pin or 00-pin data acquisition (DAQ) devices and other NI products with a 6-pin SCSI

More information

R1M-GH THERMOCOUPLE & DC INPUT MODULE MODEL. Remote I/O R1M Series. (16 points)

R1M-GH THERMOCOUPLE & DC INPUT MODULE MODEL. Remote I/O R1M Series. (16 points) Remote I/O R1M Series THERMOCOUPLE & DC INPUT MODULE (16 points) MODEL MODEL & SUFFIX CODE SELECTION R1MGH2T MODEL Modbus protocol I/O TYPE GH2 : Thermocouple or DC input, 16 points FIELD TERMINAL TYPE

More information