Installation and Operation Guide
|
|
- Laurel Dickerson
- 5 years ago
- Views:
Transcription
1 Installation and Operation Guide KMD 1162 NetSensor Contents Specifications... 2 Network Cable Preparation... 4 Rough-in preparation... 5 Installing the NetSensor... 5 Operation... 6 Maintenance... 7 Programming a NetSensor
2 KMC Controls Specifications Display Compatibility LCD, 2-character, 7-segment, 056. in. high. KMD 5800 series controllers KMD 7000 series controllers BAC 5800 series BACnet controllers BAC 7000 series BACnet controllers Connection Connector type Maximum cable length RJ 12 connects data and power to KMC Tier 2 or BACnet controller. 75 feet (22.9 meters) Power Mounting Weight Material 5 volts DC supplied from connected controller Surface mount directly to any flat surface or to a 2 x 4 inch or 4 x 4 inch handy-box. Mounting on a 4 x 4 inch box requires a mounting backplate. 2.8 ounces (80 grams) Light almond or white ABS UL Flame Class 94HB Accessories Mounting backplate, 4 x 4 inch Almond HMO 1161 White HMO 1161W Replacement allen screw HPO 0044 Network cables 25 feet (7.6 meters) KMD feet (15.2 meters) KMD feet (22.9 meters) KMD 5692 Interface Cable KMD 5624 Gasket HPO
3 Sensor Type 10kΩ thermistor Accuracy ±2 F (±1.1 C) Operating range 47 to 97 F (8 to 36 C) Models Almond White KMD KMD 1162W10 Dimensions A B C D E A B C D E 3.25 in in in in in. 83 mm 116 mm 66 mm 83 mm 22 mm Environmental Limits Shipping temperature -40 to 140 F (-40 to 60 C) Humidity 0 95% relative humidity non-condensing 3
4 KMC Controls Network Cable Preparation Connecting a NetSensor to a KMC controller requires a six-wire cable with RJ-12 connectors on each end. Use either the KMC Controls ready-to-use cables or make cables to length when the NetSensor is installed. Cables made to length must meet the following requirements: Cable length is no longer than 75 feet (22.9 meters). Use cable with #24 AWG size conductors. Cable insulation must meet local building codes. Plenum rated cable is recommended. Connectors are appropriate for the cable in use and are installed following the connector manufactures instructions. RJ-12 CLOCK +5VDC A B GND DATA Cable Details 4
5 Rough-in preparation Complete rough-in wiring at each sensor location prior to sensor installation. This includes the following. Route the network cable from the NetSensor location to the controller to which it will connect. If required, install the appropriate mounting backplate. See Accessories on page 2 for model numbers. Mounting base RJ-12 cable Allen screws NetSensor mounting backplate Caution To prevent mounting screw heads from touching the circuit board in the NetSensor, use only the mounting screws supplied by KMC Controls. Using screws other than the type supplied will damage the NetSensor. Installing the NetSensor 1. Turn the Allen screws in the base of the NetSensor clockwise until they clear the cover. Swing the sensor away from the backplate to remove it. Turn clockwise to remove from base. Allen screws 2. Route the RJ-12 cable through the mounting base. 5
6 KMC Controls 3. Fasten the mounting base to the backplate or the outlet box with the Allen screws toward the floor. 4. Insert the RJ-12 cable coming from the base into the NetSensor. 5. Place the top of the NetSensor over the top of the mounting base and swing it down over the Allen screw brackets. Be careful not to pinch any wiring. 6. Back the Allen screws out of the brackets until they engage the NetSensor cover and hold it in place. Operation The following sections describe the controls and indicators found on the NetSensor. Setpoint buttons Fan speed Mode NetSensor button functions Display The display includes two 7-segment LCD digits that are visible across a normal size office. Room temperature is displayed until either setpoint button is pressed and then the display changes to setpoint mode. If the temperature remains out of the temperature operating range for more than 45 seconds, the KMD 1162 displays a set of dashes ( ). The NetSensor also sends 0 to the controller if the temperature is below 47 degrees Fahrenheit (8 degrees Celsius) and 120 if the temperature is above 97 degrees Fahrenheit (36 degrees Celsius). 6
7 Changing the setpoint Pressing either the up or down setpoint buttons changes the display from room temperature mode to setpoint mode. Pressing either button once displays the current setpoint for three seconds; each additional press increments or decrements the setpoint temperature by one degree Fahrenheit. Backlight When either setpoint button is pressed the backlight turns on and remains on for 10 seconds after the last button is released. PC port The NetSensor is equipped with a PC Port located at the bottom of the NetSensor housing. This port provides a temporary EIA 485 connection to the digital network for network setup. PC port Netsensor PC Port Location To use this port: 1. Connect the keyed, flat end of the KMD 5624 NetSensor Interface cable to the port on the NetSensor. 2. Connect the RJ-12 end of the cable to the interface device that converts the EIA 485 signal from the NetSensor into an EIA 232 signal. 3. The cable and interface required will vary between WinControl and BACstage. Cable and interface details are included in the installation guides for both programs. Maintenance Remove dust as necessary from holes in top and bottom. Clean the display with soft, damp cloth and mild soap. 7
8 KMC Controls Programming a NetSensor Program the KMD 1162 by associating each NetSensor button with a variable or value object in the controller to which the NetSensor is connected. See the illustration KMD 1162 button and function numbers on page 8 for the KMD 1162 button numbers. Table 3-1 lists the settings for programming a NetSensor with WinControl. Use the NetSensor dialog found under the Control Menu to configure each button. Table 3-2 lists settings for programming a NetSensor with BACstage. Use the NetSensor dialog in the Device Menu to configure each button. For additional instructions on programming a NetSensor with either WinControlXL or BACstage, use the on-line help system KMD 1162 button and function numbers 8
9 Table 3-1 WinControl settings NetSensor Variable Button Function Type Range 1 Temperature Analog F or C (Display only) Display Value Read Only Deg F Deg C Units Analog 2 Setpoint Analog 0 Decimal Read/Write Deg F Deg C Analog 3 Cool/Heat Digitial Cool/Heat Read/Write Cool/Heat Digital 4 Fan speed Digitial Off/on1/2/3 Read/Write Unused Analog Table 3-2 BACstage settings NetSensor Value object Units Type Permission Display Format Assignment Function Button 1 Temperature AV F or C Read Only AV F or C 2 Setpoint AV 0 Read/Write AV F or C 3 Cool/Heat BV Cool/Heat Read/Write BV Cool/Heat 4 Fan speed AV Off/On1/2/3 Read/Write AV No-units 9
10 KMC Controls Temperature The space temperature sensor inside of the NetSensor displays room temperature. Configure the temperature sensor with an analog variable in WinControl or an analog value object in BACstage. Temperature is always programmed in the Button 1 position. Setpoint Button 2 is associated with an analog variable in WinControl or an analog value object in BACstage. The WinControl Range or BACstage Display Format must be set to 0. The NetSensor limits the setpoint values to a range between 47 and 97 degrees Fahrenheit (8 to 36 degrees Celsius.) Operators can view and change the setpoint by first touching Button 2 and then pressing an up or down arrow button. Write a Control Basic to control equipment based on the conditions of the setpoint. 10 IF VAR2 < VAR1 THEN START OUT6 Cool/Heat Button 3 is associated with a digital variable in WinControl or a binary value object in BACstage. When Button 3 is set to Off, the button value remains at the last Button 3 setting. Fan speed Button 4 is associated with an analog variable in WinControl or an analog value object in BACstage. The WinControl Range or BACstage Display Format must be set to 0. When Button 3 is set to Off, the value for Button 4 is set to 0. For the Button 4 positions LOW, MED, and HIGH, the button value is 1, 2, and 3 respectively. Verifying a functioning NetSensor To check if a functioning NetSensor is present, use the Control Basic function NETSENSOR-STATUS. 10 IF NOT NETSENSOR-STATUS THEN STOP OUT1 10
11 11
12 KMC Controls Important notices The KMC logo, WinControlXL and NetSensor are trademarks of KMC Controls, Inc. 2005, KMC Controls, Inc. All rights reserved. No part of this publication may be reproduced, transmitted, transcribed, stored in a retrieval system, or translated into any language in any form by any means without the written permission of KMC Controls, Inc. Printed in U.S.A. Disclaimer The material in this manual is for information purposes only. The contents and the product it describes are subject to change without notice. KMC Controls, Inc. makes no representations or warranties with respect to this manual. In no event shall KMC Controls, Inc. be liable for any damages, direct or incidental, arising out of or related to the use of this manual. 12 KMC Controls. Inc Industrial Drive New Paris, IN TEL: FAX: info@kmccontrols.com
Installation Guide. Room Temperature Sensors. Mounting. Location and Cover Removal (All) STE-6011 Only. STE-6010/6013/6015 Only
Room Temperature Sensors STE-6010/6011/6013/6015 Mounting Location and Cover Removal (All) Install the sensor on an inside wall where it can sense the average room temperature and be away from direct sunlight,
More informationInstallation Guide max. Modular RJ-45 Jack. Four-pin EIA-485 PC Data Port
Room Temperature Sensors (with Rotary Dials) STE-6014/6017/6018/6019/6020 Mounting 2.250 All dimensions are in inches.643.422 Installation Guide.475 max. Modular RJ-45 Jack 2.438 R.187 R 3.094 STE-6019/6020
More informationInstallation & Operation Guide
Installation & Operation Guide Direct Digital VAV Controllers KMD-7001/7051 - VAV Terminal Units KMD-7002/7052 - Dual Duct VAV Units KMD-7003/7053 - Fan Induction Units 907-019-01C 1 Introduction This
More informationInstallation & Operation Guide
Installation & Operation Guide (Shown with optional Override Board Cover) KMD-5831 Programmable Loop Controller PLC-28 Direct Digital Controller 902-019-04B 1 Introduction This section provides a brief
More informationInstallation and Operation Guide. KMD 5559 CommTalk
Installation and Operation Guide Contents KMD 5559 CommTalk Description...3 Models...3 Specifications...3 Accessories...4 Mounting...5 Connecting the KMD 5559...5 Connecting power...9 Operation...9 Using
More informationInstallation and Operation Guide
Installation and Operation Guide Network -Isolator Contents Introduction...3 Installation...3 Mounting...3 Wiring and Terminal locks...4 Network Connections...4 Configuration/...7 Power Connection...7
More informationApplication Engineering
Application Engineering Application Engineering Commercial Comfort Controller (543-0175-00) Installation Guide May 2012 Contents Mounting... 1 Connections and Wiring... 1 Wiring Considerations... 1 Input
More informationInstallation Guide (3/6 Outputs)
BAC-12xx36/13xx36/14xx36 Series FlexStat 3 Relays, 6 Analog s, 6 External Inputs Quick Start Installation Guide (3/6 s) This document is for 3-relay, 6-analog-output, 6-external-input BAC-12xx36/13xx36/14xx36
More informationInstallation & Operation Guide
& Operation Guide KMD-7301/7301C Direct Digital Controller For Air Handling Applications 880-019-02C KMD 7301 and KMD 7301C Direct Digital Controller & Operation Guide Introduction This section provides
More informationThe KMC Converge BACnet module User Guide
The KMC Converge BACnet module User Guide Revision B KMC Controls, Inc. Important notices 2015, KMC Controls, Inc. KMC Converge and KMC Converge GFX are trademarks of KMC Controls, Inc. NetSensor, WinControl,
More information7" Touch Screen Display
7" Touch Screen Display Installation Guide Contents Minimum Requirements...1 Select a Location...1 Initial Setup...2 Unboxing...2 Installation...3 Prepare the Panel...3 Install the Mounting Plate...3 Mount
More informationSingle Setpoint for STE-9xxx NetSensor
Single Setpoint for STE-9xxx NetSensor Application Guide SETPOINT Contents STE-9000 Series NetSensor Setpoints...1 Procedure...1 Control Basic Code (Reference)...7 NetSensor Menus...8 Handling Precautions...8
More informationBAC-9000 Series VAV Controller Installation Guide
BAC-9000 Series VAV Controller Installation Guide CONTENTS Introduction... 1 Set Drive Hub (45/60 ) Rotation Limit... 1 Mount Controller... 2 Connect Sensors and Equipment... 3 Connect (Optional) Pressure
More informationMobile App User Guide. (for Apple and Android Phones)
KMC Connect Lite Mobile App User Guide (for Apple and Android Phones) KMC Controls, 19476 Industrial Drive, New Paris, IN 46553 / 877-444-5622 / Fax: 574-831-5252 / www.kmccontrols.com Contents Important
More informationBA/BS4S Temperature Sensor Installation & Operating Instructions
Product Overview and Identification The BAPI-Stat 4 room temperature sensor features a large format LCD and slider setpoint adjustment. Additional options include button override and communication jack.
More informationMobile App User Guide
KMC Connect Lite Mobile App User Guide KMC Controls, 19476 Industrial Drive, New Paris, IN 46553 / 877-444-5622 / Fax: 574-831-5252 / www.kmccontrols.com CONTENTS Important Notices...4 Support...4 About
More informationEP/2 Installation Instructions
1 2 3 4 7 ENTER 0 5 6 8 9 CLEAR + - LOGIC ONE EP/2 EP/2 Installation Instructions DOC. #569011000 A 7/30/04 PRINTED IN U.S.A. Regulatory Compliance Safety This device has been tested and found to be in
More informationReference to KMC BACnet Module. for Niagara AX
Reference to KMC BACnet Module for Niagara AX Includes installation instructions Revision E KMC BACnet Module Important notices Disclaimer 2012, KMC Controls, Inc. WinControl, NetSensor, and the KMC logo
More informationBAC-5000 BACstage Operator Workstation
BAC-5000 BACstage Operator Workstation Reference Guide and Operating Instructions For version 2.4 902-019-63M BAC 5000 Reference Guide 2012, KMC Controls, Inc. WinControl, NetSensor, and the KMC logo are
More informationApplications Guide BAC-5051E router Includes installation, operation, and maintenance instructions
Applications Guide BAC-5051E router Includes installation, operation, and maintenance instructions Revision J Copyrights and trademarks 2018, KMC Controls, Inc. NetSensor, WinControl, and the KMC logo
More informationclarity 3 Programmable Controller
clarity 3 Programmable Controller BACnet General Purpose Controllers (B-AAC) DESCRIPTION Taco Clarity 3 FPC series controllers are designed to control building systems and HVAC equipment. The integrated
More informationT7560A1036 Digital Wall Module
T7560A1036 Digital Wall Module HONEYWELL EXCEL 5000 OPEN SYSTEM BEFORE INSTALLATION All wiring must comply with local electrical codes and ordinances or as specified on installation wiring diagrams. T7560A1036
More informationHT Series Wall Mount with Analog Setpoints, LCD, and Humidistat and Thermostat Control
Wall Mount with Analog Setpoints, LCD, and Humidistat and Thermostat Control NOTICE This product is not intended for life or safety applications. Do not install this product in hazardous or classified
More informationHWS Series Wall Mount with Relay Setpoints, LCD, and Humidistat Control
Wall Mount with Relay Setpoints, LCD, and Humidistat Control NOTICE This product is not intended for life or safety applications. Do not install this product in hazardous or classified locations. Read
More informationInstallation and Operation Guide. BAC-5841/5842 UFAD and BAC / VAV Advanced Application Controllers, 8 x 8
Installation and Operation Guide BAC-58/58 UFAD and BAC-58-6/58-6 VAV Advanced Application Controllers, 8 x 8 NOTE: Download these additional documents from the Partners web site! To install and properly
More informationInstallation Guide. Carbon Dioxide (CO 2. ) Detectors. General Information. Mounting WARNING CAUTION. SAE-1011/1012 Space Mount SAE-1011/1012/1062
General Information WARNING Do not use in an explosive or hazardous environment, with combustible or flammable gases, as a safety or emergency stop device, or in any other application where failure of
More informationInfosystem Remote Touchscreen Installation Instructions
Infosystem Remote Touchscreen Installation Instructions DOC. #569102100 A 7/30/04 PRINTED IN U.S.A. Regulatory Compliance Safety This device has been tested and found to be in compliance with the requirements
More informationCustom Controller Installation Instructions
MODEL CUSTOM CONTROLLER HARDWARE CODE MAX ALLOWABLE AMBIENT TEMP: 70 C (158 F) THIS DEVICE COMPLIES WITH PART 15 OF THE FCC RULES. OPERATION IS SUBJECT TO THE FOLLOWING TWO CONDITIONS: 1) THIS DEVICE MAY
More informationHT Series Wall Mount with Relay Setpoints, LCD, and Humidistat and Thermostat Control
Wall Mount with Relay Setpoints, LCD, and Humidistat and Thermostat Control NOTICE This product is not intended for life or safety applications. Do not install this product in hazardous or classified locations.
More informationZone Pressure Touch (ZPT) Sensor with Attached Tube (-AT) - Low Pressure Range Unit Installation and Operation Instructions
Product Identification BAPI s Touch Low Range Pressure Sensor with Attached Static Pressure Probe is an accurate, rugged and economical solution for measuring and reporting duct/building static pressure,
More informationAEXX-349 SERIES REMOTE DISPLAYS
FN:349MAN1.DOC AEXX-349 SERIES REMOTE DISPLAYS DESCRIPTION AEXX-349 Series Remote Displays are available with 1, 2.3, 4, 8, or 12 high digits, visible from 5 feet to 500 feet away. They are available in
More informationZone Pressure Touch (ZPT) Sensor - Standard Range
Product Identification BAPI s Touch Pressure Sensor is an accurate, rugged and economical solution for measuring and reporting duct/ building static pressure, room-to-room differential pressure or air
More informationJunos WebApp Secure 5.0 Hardware Guide
Junos WebApp Secure 5.0 Hardware Guide Junos WebApp Secure 5.0 Hardware Guide This document contains a specification for the MWS1000 hardware appliance, as well as instructions for installation into a
More informationZone Pressure Touch Sensor - Standard Range
Overview The Zone Pressure Touch (ZPT) Sensor is an accurate, rugged and economical solution for measuring and reporting duct/ building static pressure, room-to-room differential pressure or air velocities/volumes.
More informationVT8600 Series Installation Guide. Rooftop Unit, Heat Pump and Indoor Air Quality Controller
VT8600 Series Installation Guide Rooftop Unit, Heat Pump and Indoor Air Quality Controller 2 Installation Guide VT8600 Series If replacing an existing Room Controller, label wires before removal of Controller.
More informationDWYER INSTRUMENTS, INC. Series AVUL Air Velocity Transmitter. Specifications - Installation and Operating Instructions.
Series AVUL Air Velocity Transmitter Specifications - Installation and Operating Instructions Bulletin P-AVUL 3-49/64 [95.71] 2-43/64 [67.92] 1/2 NPS 3-3/16 [80.81] 1-19/32 [40.59] 31/32 24.58 3-33/64
More informationCC186 AND CC186/2 STAND-ALONE OR SYSTEM CLOCK
FN:CC186M2.DOC CC186 AND CC186/2 STAND-ALONE OR SYSTEM CLOCK DESCRIPTION The CC186 is a single sided clock with six, 1.8 inch high digits. The CC186/2 is a double sided clock with six, 1.8 inch high digits
More informationUser's Guide. Extech AM A AC Analog Clamp Meter
User's Guide Extech AM300 300A AC Analog Clamp Meter Introduction Congratulations on your purchase of the Extech AM300 Analog Clamp Meter. This device measure AC Voltage and Current, DC Voltage, and Resistance.
More informationCTR21, CTR22, CTR23, and CTR24 Wall Modules
CTR21, CTR22, CTR23, and CTR24 Wall Modules FEATURES SPECIFICATION DATA The CTR21, CTR22, CTR23, and CTR24 family of wall modules include: Models with setpoint adjustment. Models with occupied/unoccupied
More informationFor Powerful Digital Marketing and Total Multimedia Solution DV-6664 & DV-6664T. User s Guide version 1.0
For Powerful Digital Marketing and Total Multimedia Solution DV-6664 & DV-6664T User s Guide version 1.0 Acknowledgements The MedeaWiz logo and DV-6664 are trademarks of MedeaWiz Corporation. All other
More informationETT 352 Touch Operating Panel
ETT 352 Touch Operating Panel Date of creation: 11.08.2014 Version date: 03.03.2017 Article number: 07-230-352-1-E Publisher: SIGMATEK GmbH & Co KG A-5112 Lamprechtshausen Tel.: 06274/4321 Fax: 06274/4321-18
More informationUSER MANUAL. DV-HAS HDMI Audio Separator LIT Bergen Boulevard, Woodland Park, NJ Tel FAX Web:
USER MANUAL DV-HAS HDMI Audio Separator 244 Bergen Boulevard, Woodland Park, NJ 07424 Tel 973-785-4347 FAX 973-785-3318 Web: www.fsrinc.com LIT1460 Proprietary Information All information in this manual
More informationTracer VM Bluetooth Interface
Tracer Bluetooth Interface Model number BTI-102 Operating Instructions General The Bluetooth Interface collects, transmits and saves data from Base Flowmeters installed in injection mold cooling circuits.
More informationSERVICE MANUAL MODEL SSW-321-X
SSW-321-X-ISSUE 4.0 SERVICE MANUAL FOR MODEL SSW-321-X STAINLESS STEEL WALL TELEPHONE Serving the Telephone Industry Since 1930 Communication Equipment 519 W South Park Street & Engineering Company Okeechobee,
More informationAE21 SERIES DISPLAY CONTROL TERMINAL
FN:AE21MAN1.DOC AE21 SERIES DISPLAY CONTROL TERMINAL DESCRIPTION The AE21 Series Display Control Terminal is used for implementing various display functions. It consists of a control terminal, the AE21,
More informationFor Powerful Digital Marketing and Total Multimedia Solution DV & DV-66104T. User s Guide version 2
For Powerful Digital Marketing and Total Multimedia Solution DV-66104 & DV-66104T User s Guide version 2 Acknowledgements The MedeaWiz logo and DV-66104 are trademarks of MedeaWiz Corporation. All other
More informationUCU Room Display. Operation Modes. Features. Applications DATASHEET
DATASHEET UCU Room Display The UCU Room Display provides dedicated visually appealing Room Control display for use with UCU10FC/K Unitary Controller. The display allows the user to view and adjust selected
More informationOmniSmart 1500VA 2U Rack/Tower Line-Interactive 120V UPS with LCD display and USB port
OmniSmart 1500VA 2U Rack/Tower Line-Interactive 120V UPS with LCD display and USB port MODEL NUMBER: OMNI1500LCD Highlights 1500VA / 1.5kVA 2U rack/tower 120V line interactive UPS with LCD display Corrects
More informationSimplyVAV Application and Installation Guide
SimplyVAV Application and Installation Guide Revision C SimplyVAV 2014, KMC Controls, Inc. SimplyVAV and the SimplyVAV logo are trademarks of KMC Controls, Inc. All rights reserved. No part of this publication
More informationHZS 352 Touch Room Unit
HZS 352 Touch Room Unit Date of creation: 25.04.2014 Version date: 25.03.2016 Article number: 06-895-352-E Publisher: SIGMATEK GmbH & Co KG A-5112 Lamprechtshausen Tel.: 06274/4321 Fax: 06274/4321-18 Email:
More informationTPE 1464 Series Pressure Transducer
TPE 1464 Series Pressure Transducer Description The KMC TPE 1464 series of pressure transducers incorporate a gauge pressure transmitter featuring low hysteresis, excellent repeatability, and longterm
More informationDMC-1000 Chassis-Based Media Converter
DMC-1000 Chassis-Based Media Converter User s Guide Rev. 01 (Jan. 2002) 6012-9600131 (1907MCR11616000) Printed In Taiwan RECYCLABLE i TABLE OF CONTENTS TABLE OF CONTENTS... II PREFACE... 3 19 MEDIA CONVERTER
More informationEthernet Adapter Installation Instructions
Ethernet Adapter Installation Instructions DOC. #569040000 A 7/30/04 PRINTED IN U.S.A. Disclaimer Logic One is a registered trademark of Novar Controls Corporation. The material in this manual is for information
More informationclarity 3 VAV Programmable Controller
clarity 3 VAV Programmable Controller BACnet VAV Controller-Actuators (B-AAC) DESCRIPTION Taco Clarity3 series controller-actuators are designed to operate VAV (Variable Air Volume) terminal units. The
More informationTRC-190 User s Manual
User s Manual Edition 3.2, May 2017 www.moxa.com/product 2017 Moxa Inc. All rights reserved. User s Manual The software described in this manual is furnished under a license agreement and may be used only
More informationFree Energy Band RCC30U Room Temperature Controller for Four-pipe Fan Coil Unit
Document No. 155-324 Free Energy Band RCC30U Room Temperature Controller for Four-pipe Fan Coil Unit Description Features Application Product Number Room temperature controller for four-pipe fan coil units.
More informationrcc.1081 Installation Instructions
rcc.1081 Installation Instructions Table of Contents Introduction...1 Specifications...2 Mounting...3 Wiring...5 Wiring Method...7 BACnet Network Wiring...8 Setting BACnet Address...9 Setting the BACnet
More informationMondo TC. Quick Reference & Setup Guide
Mondo TC Quick Reference & Setup Guide 2791 Circleport Drive, Erlanger, KY 41018, USA. Americas: +1 859-282-7303 EMEA: +44 (0) 1843 873322 Email: tech.usa@tvone.com www.tvone.com CSG-MONDO-TC Version 1.0
More informationUser s Guide. 600A True RMS AC/DC Clamp Meter. Model 38389
User s Guide 600A True RMS AC/DC Clamp Meter Model 38389 Safety International Safety Symbols This symbol, adjacent to another symbol or terminal, indicates the user must refer to the manual for further
More informationDIGITAL PANEL THERMOMETER
Love Controls DIGITAL PANEL THERMOMETER LCI108-2x LCI108J-2x INSTRUCTIONS MANUAL EDITION: February 2001 INTRODUCTION TO THE LOVE CONTROLS LCI108 SERIES This manual does not constitute a formal agreement.
More informationUser's Guide. Model High Precision Quad Output DC Power Supply
User's Guide Model 382270 High Precision Quad Output DC Power Supply Introduction Congratulations on your purchase of the Extech 382270 DC Power Supply. The Model 382270 can be used for many applications
More informationAEXX-273 SERIES WIRELESS CONTROLLED PACE CLOCKS
FN:273MAN1.DOC AEXX-273 SERIES WIRELESS CONTROLLED PACE CLOCKS DESCRIPTION AEXX-273 Series Wireless Controlled Pace Clocks are available in with 1", 2.3", 4", 8", or 12" high digits, visible from 5 feet
More informationTRC-190 User s Manual
First Edition, November 2008 www.moxa.com/product 2008 Moxa Inc. All rights reserved. Reproduction without permission is prohibited. The software described in this manual is furnished under a license agreement
More informationToll Free: Tel: Fax:
Toll Free: 1-888-865-6888 Tel: 510-226-8368 Fax: 510-226-8968 Email: sales@rackmountmart.com User Manual LCDK 1070 DVI-D KVM Legal Information First English printing, October 2002 Information in this document
More informationDIGITAL PANEL THERMOMETER
Love Controls DIGITAL PANEL THERMOMETER LCI108-1x LCI108J-1x INSTRUCTION MANUAL EDITION: January 2001 INTRODUCTION TO THE LOVE CONTROLS LCI108 SERIES This manual does not constitute a formal agreement.
More informationETT 312 Build-In Touch Terminal
ETT 312 Build-In Touch Terminal Date of creation: 01.02.2016 Version date: 23.01.2017 Article number: 01-230-312-E Publisher: SIGMATEK GmbH & Co KG A-5112 Lamprechtshausen Tel.: 06274/4321 Fax: 06274/4321-18
More informationDM-170/SRM-170/SRM-170A. User Manual. Version 3.2
DM-170/SRM-170/SRM-170A User Manual Version 3.2 May 8, 2003 Copyright Notice Copyright 2003 by ICP Electronics Inc. All Rights Reserved. The information in this document is subjected to change without
More informationPLEASE READ INSTRUCTIONS CAREFULLY BEFORE INSTALLATION!
TUC2 / TUCH2 Model Series Installation Instructions PLEASE READ INSTRUCTIONS CAREFULLY BEFORE INSTALLATION! APPLICATION The TUC2 provides temperature space monitoring with a backlit LCD. The TUCH2 provides
More informationLCD-1 Peripheral Board Technical Manual
LCD-1 Peripheral Board Technical Manual Document Revision: 1.03 Date: 22 April, 2003 BiPOM Electronics, Inc. 16301 Blue Ridge Road, Missouri City, Texas 77489 Telephone: 1-713-283-9970. Fax: Fax: 1-281-416-2806
More informationKMD Modbus Interface
Technical Bulletin (TB0405A-RevB) KMD-5540-005 Modbus Interface Issued 8 July 2013 Issue Setup and configuration of the KMD-5540-005 ModBus Interface Instructions This version of the KMD-5540 Series CommTalk
More informationON/OFF HUMIDIFIER CONTROL (ROOM 0R DUCT SENSOR) WITH OUTDOOR TEMPERATURE RESET OVERVIEW WALL CONTROLLER INSTALLATION (TCY-BH-T-U)
(ROOM 0R DUCT SENSOR) WITH OUTDOOR TEMPERATURE RESET TCY-BH-T-U Wall controller with sensor TDC-BH-T-U Duct controller with sensor SOA-Tn10 Outdoor temperature sensor (Optional) OVERVIEW For wall applications
More informationPROJECT: SPECIFIER: TYPE: QTY: OUTPUT LEVEL: COLOR: LENGTH X WIDTH: MOUNTING: DIMMING/CONTROLS:
PROJECT: SPECIFIER: TYPE: QTY: Available in 5 output levels of Static White at 24 Volts RGB and RGBW available at 24 Volts Tunable White and Double Sided available Great for creating Luminous Ceilings
More informationBTU-4D/BTU-4D-I Digital Temperature Unit & Sensors. Installation and Operation Manual
BTU-4D/BTU-4D-I Digital Temperature Unit & Sensors Installation and Operation Manual BTU-4D/BTU-4D-I Installation and Operation Manual Rev E Table of Contents Introduction... 1 TEMP OUTDOOR Sensor... 1
More informationLCD240-xHxx. INSTALLATION MANUAL LCD240 Horizontal Graphic LCD Display Device for Lifts. Part No.
Part No. -xhxx Description Horizontal Graphic LCD Display Device for Lifts Software 5.9 Documentation Rev. 2.8 Vuolas Electronics Oy Ltd. Kunnansarka 2 FIN-37150 Nokia, Finland Tel. +358 (0)3 342 6900
More informationZone Manager INSTALLATION MANUAL 40KMC KMQ QNC QNQ
40KMC------301 40KMQ------301 40QNC------3 40QNQ------3 INSTALLATION MANUAL Installation manual This control system only operates with indoor units of the following models: 40KMC------301 and 40KMQ------301
More informationT7560A,B,C Digital Wall Module
T7560A,B,C Digital Wall Module INSTALLATION INSTRUCTIONS CAUTION: This equipment generates, uses, and can radiate radio frequency energy and, if not installed and used in accordance with the Installation
More informationF1000 User's Manual. (Version: V1.01)
(Version: V1.01) Contents Chapter 1 Overview... 2 Chapter 2 Installation... 3 2.1 Installation guide... 3 2.1.1 Installation position... 3 2.1.2 NEMA4 standard installation... 3 2.1.3 Environment precautions...
More informationTM-2100 Series Room Command Module
TM-2100 Series Room Command Module Product Bulletin Code No. 21.144 E Issued 02 2011 The TM-2100 series of Room Command Modules are designed for use with the FCC series of DDC terminal unit controllers.
More informationEMC1600 Series Media Converter and Ethernet Extender Chassis
EMC1600 Series Media Converter and Ethernet Extender Chassis User s Manual Preface This manual describes how to install and use the 16-Bay Media Converter and Ethernet Extender Chassis. This chassis is
More informationMultiVOIP SIP Gateways
MultiVOIP SIP Gateways MultiVOIP Analog Models MultiVOIP SS Models MultiVOIP FX Models Cabling Guide Copyright and Technical Support Cabling Guide MultiVOIP SIP Gateway MultiVOIP FX Models MVP210-FX, MVP410-FX
More informationSmartOnline 208/120V or 240/120V 16kVA 11.2kW On-Line Double-Conversion UPS, Extended Run, SNMP, Webcard, 8U Rack/Tower, USB, DB9 Serial
SmartOnline 208/120V or 240/120V 16kVA 11.2kW On-Line Double-Conversion UPS, Extended Run, SNMP, Webcard, 8U Rack/Tower, USB, DB9 Serial MODEL NUMBER: SU16000RT4U Description Tripp Lite 16kVA SmartOnline
More informationOilCop Component Wiring Installation Manual
OilCop Component Wiring Installation Manual This info sheet contains important information. READ AND KEEP FOR REFERENCE. 2311 S. Edwards Wichita, KS 67213 TEL: 316-943-5477 FAX: 316-943-4760 TOLL FREE:
More informationOZONE SWITCH Model OS-6. OS-6 Features
USER MANUAL OZONE SWITCH Model OS-6 OS-6 Features The OS-6 is an industrial grade ozone controller and monitor. The OS-6 design is optimized for accuracy and ease of installation, setup and operation.
More informationSER8300 Series Line Voltage Room Controller with Optional PIR Sensor Installation Guide
Line Voltage Room Controller with Optional PIR Sensor Commercial and Hotel/Lodging HVAC Fan Coil Applications CONTENTS Installation 3 Location 3 Installation 3 Terminal, Identification and Function 4 Communication
More informationCOGNEX. Checker SensorView. Quick Reference Guide
COGNEX Checker SensorView Quick Reference Guide 890 SensorView 890 Overview SensorView 890 provides self-contained IP-65 touchscreen configuration, control, and monitoring of one or more Checker 4G series
More informationSmartPro LCD 120V 1.5kVA 900W Line-Interactive UPS, AVR, 2U Rack/Tower, LCD Display, USB, DB9 Serial
SmartPro LCD 120V 1.5kVA 900W Line-Interactive UPS, AVR, 2U Rack/Tower, LCD Display, USB, DB9 Serial MODEL NUMBER: SMART1500LCD Highlights 1500VA / 1.5kVA 2U rack/tower 120V line interactive UPS with LCD
More informationOmnitron Systems Technology, Inc. 1. iconverter. 19-Module Managed Power Chassis User s Manual
Omnitron Systems Technology, Inc. 1 iconverter 19-Module Managed Power Chassis User s Manual 27 Mauchly, #201, Irvine, CA 92618 Phone: (949) 250-6510; Fax: (949) 250-6514 2 Omnitron Systems Technology,
More informationUser s Guide. 600A AC Clamp Meter. Model 38387
User s Guide 600A AC Clamp Meter Model 38387 Safety International Safety Symbols This symbol, adjacent to another symbol or terminal, indicates the user must refer to the manual for further information.
More informationMulti-Point Gas Detection and Control System
Multi-Point Gas Detection and Control System DESCRIPTION Wall mounted, microprocessor-based, multi-point, analog electronic control system for various gas, temperature and humidity detection, control and
More informationVADDIO /CANON BU-SERIES PTZ CAMERAS
Camera and Electronic Products for Integrators Installation and User Guide VADDIO /CANON BU-SERIES PTZ CAMERAS Canon BU-45H Outdoor & BU-50H Indoor PTZ Cameras including Vaddio accessories for easy integration
More informationDVI KVM. Extra Long Range Extender Over One CAT5. User Manual EXT-DVIKVM-ELR. Release A8
DVI KVM Extra Long Range Extender Over One CAT5 EXT-DVIKVM-ELR User Manual Release A8 Important Safety Instructions 1 Read these instructions 2 Keep these instructions 3 Heed all warnings 4 Follow all
More informationHZS 351 Room Touch Control Panel
HZS 351 Room Touch Control Panel Date of creation: 13.03.2014 Version date: 25.03.2016 Article number: 06-895-351-E Publisher: SIGMATEK GmbH & Co KG A-5112 Lamprechtshausen Tel.: 06274/4321 Fax: 06274/4321-18
More informationOV-MCR116. Media Converter Chassis System. User s Manual
OV-MCR116 Media Converter Chassis System User s Manual FCC Class B Certification This equipment has been tested and found to comply with the regulations for a Class B digital device, pursuant to Part 15
More informationAllure EC-Smart-Comfort Series
Datasheet Allure EC-Smart-Comfort Series Communicating sensors with Smart-Light and Smart-Blind add-on modules Overview Features & Benefits The Allure EC-Smart-Comfort Series are versatile communicating
More informationTM-2100 Series Room Command Module
TM-2100 Series Room Command Module Product Bulletin Code No. 21.144 E Rev. B Issued 02 2007 The TM-2100 series of Room Command Modules are designed for use with the FCC series of DDC terminal unit controllers.
More information* * Agilent Power Distribution Unit (PDU) Installation Guide
Agilent Power Distribution Unit (PDU) Installation Guide For use with Agilent PDU kits and PDU installation kits for Agilent instrument racks June 2008 Edition 7 E0608 *5000-0039* 5000-0039 Notice The
More informationHardware Installation. Tracer MP581 Programmable Controller CNT-SVN01C-EN
Hardware Installation Tracer MP581 Programmable Controller CNT-SVN01C-EN Hardware Installation Tracer MP581 Programmable Controller CNT-SVN01C-EN November 2005 Tracer MP581 Programmable Controller Hardware
More informationEZ Switch EZ Connect N SMCFS1601/SMCFS2401
EZ Switch EZ Connect N Draft 16/24-Port 11n Wireless Fast Ethernet USB2.0 Adapter Switch SMCFS1601/SMCFS2401 COPYRIGHT & TRADEMARKS Specifications are subject to change without notice. is a registered
More informationEcoFlex LED Neon Manual
Manual Part number: LN-ECO-XXXX-10m from Environmental Lights is one of the most flexible and cost-effective members of our line of LED Neon products. It allows you to achieve the creative potential of
More informationDual-Feed 80A Auto Low Voltage Disconnect Panel - 80LVD02
Dual-Feed 80A Auto Low Voltage Disconnect Panel - 80LVD02 User Manual 1.1 Overview Telect s 80A, -48 Vdc Low-Voltage Disconnect (LVD) panel is a rack-mounted component with coil-operated contactors. These
More information