1 AIR CONDITIONER Duct type DESIGN & TECHNICAL MANUAL INDOOR ARYG72LHTA ARYG90LHTA OUTDOOR AOYG72LRLA AOYG90LRLA DR_AR012EF_

2 Notices: Product specifications and design are subject to change without notice for future improvement. For further details, please check with our authorized dealer. Copyright 2017 Fujitsu General Limited. All rights reserved.

3 CONTENTS Part 1. INDOOR UNIT Product features System outline Specifications Dimensions Models: ARYG72LHTA and ARYG90LHTA Installation space requirement Maintenance space requirement Wiring diagrams Model: ARYG72LHTA Model: ARYG90LHTA Capacity table Cooling capacity Heating capacity Fan performance Fan performance curve Airflow Operation noise (sound pressure) Noise level curve Sound level check point Electrical characteristics Safety devices External input and output External input External output Combination of external input and output Details of function Remote controller Wired remote controller Function settings Function settings on indoor unit Function settings by using remote controller Accessories Optional parts Controllers Others... 51

4 CONTENTS (continued) Part 2. OUTDOOR UNIT Specifications Dimensions Models: AOYG72LRLA and AOYG90LRLA Installation space Models: AOYG72LRLA and AOYG90LRLA Refrigerant circuit Models: AOYG72LRLA and AOYG90LRLA Wiring diagrams Models: AOYG72LRLA and AOYG90LRLA Capacity compensation rate for pipe length and height difference Model: AOYG72LRLA Model: AOYG90LRLA Additional charge calculation Model: AOYG72LRLA Model: AOYG90LRLA Airflow Model: AOYG72LRLA Model: AOYG90LRLA Operation noise (sound pressure) Noise level curve Sound level check point Electrical characteristics Safety devices External input and output External input External output Function settings Local setting switch buttons Local setting procedure Check and test Test run Error code Pump down Accessories Optional parts...85

5 Part 1. INDOOR UNIT DUCT TYPE: ARYG72LHTA ARYG90LHTA

6 DUCT TYPE 1. Product features 1-1. System outline Indoor unit Outdoor unit 2 4 Circuit breaker (over current) 5 Power supply φ1 230V 50Hz Earth leakage breaker 1 3 Power supply φ3 400V 50Hz Circuit breaker (over current) Earth leakage breaker 1: Power supply [Outdoor Unit] ( ) 2: Piping ( ) 3: Transmission line [O.U. - I.U] ( ) 4: Power supply [Indoor Unit] ( ) 5: Remote controller line [I.U. - R.C.] ( ) - 2 -

7 2. Specifications Type Duct Inverter heat pump Model name ARYG72LHTA ARYG90LHTA Power supply 230 V ~ 50 Hz Available voltage range V Capacity Cooling Rated kw Btu/h 64,800 75,000 Min. Max. kw Btu/h 28,600 71,300 35,100 82,500 Heating Rated kw Btu/h 76,400 92,100 Min. Max. kw Btu/h 24,500 83,900 29, ,300 Cooling Rated kw Heating HIGH Input power MED Fan W LOW QUIET Current Cooling Rated A Heating Power factor Cooling % Heating EER Cooling kw/kw COP Heating Moisture removal L/h (pints/h) 4.5 (7.92) 6.0 (10.56) Maximum operating current *1 Cooling A Heating HIGH 4,300 4,300 Cooling MED 3,900 3,900 LOW 3,450 3,450 Fan QUIET Airflow rate m 3 3,000 3,000 /h HIGH 4,300 4,300 MED 3,900 3,900 Heating LOW 3,450 3,450 QUIET 3,000 3,000 Type Q'ty Sirocco fan 2 Motor output W 750 1,070 Static pressure range Pa 50 to 150 (Standard: 72) 50 to 200 (Standard: 72) HIGH Cooling MED LOW Sound pressure level *2 QUIET db (A) HIGH Heating MED LOW QUIET Sound power level Cooling db (A) Heating Main: 546 1, Dimensions (H W D) 546 1, Sub: (252 1, ) 2 mm Main: 1.3 Fin pitch 1.3 Sub: 1.45 Heat exchanger type Main: 3 26 Rows Stages 3 26 Sub: (1 12) 2 Pipe type Copper Fin type Aluminium Enclosure Material Steel Color Dimensions Net 360 1, mm (H W D) Gross 460 1,640 1,030 Weight Net kg Gross Liquid Ø (Ø 1/2) Size mm (in) Connection pipe Gas Ø (Ø 1) Method Brazing Drain hose Material PVC Size mm Ø 24.4 (I.D.), Ø 32 (O.D.) (VP25) C 18 to 32 Cooling Operation range %RH 80 or less Heating C 16 to 30 Remote controller type Wired NOTES: Specifications are based on the following conditions: Cooling: Indoor temperature of 27 CDB/19 CWB, and outdoor temperature of 35 CDB/24 CWB. Heating: Indoor temperature of 20 CDB/15 CWB, and outdoor temperature of 7 CDB/6 CWB. Pipe length: 7.5 m, Height difference: 0 m. (Between outdoor unit and indoor unit.). Protective function might work when using it outside the operation range. *1: Maximum current: The maximum value when operated within the operation range. The total current of indoor unit and outdoor unit. *2: Sound pressure level: Measured values in manufacturer s anechoic chamber. Because of the surrounding sound environment, the sound levels measured in actual installation conditions might be higher than the specified values here. DUCT TYPE - 3 -

8 DUCT TYPE 3. Dimensions 3-1. Models: ARYG72LHTA and ARYG90LHTA Unit: mm Control box Gas pipe Liquid pipe Drain port Air Side view (L) Top view Side view (R) Front view Rear view - 4 -

9 3-2. Installation space requirement Provide sufficient installation space for product safety. Models: ARYG72LHTA and ARYG90LHTA DUCT TYPE Installation by which service space is made on top of the unit (recommended): Unit: mm 450 or more 150 or more 20 or more 500 or more 2,500 or more (When no ceiling) Installation by which service is carried out from the bottom of the unit: Unit: mm 20 or more 150 or more 20 or more 500 or more 2,500 or more (When no ceiling) - 5 -

10 DUCT TYPE 3-3. Maintenance space requirement For future maintenance and service access, provide sufficient maintenance space. NOTE: Do not place any wiring or illumination in the maintenance space, as they will impede service. Models: ARYG72LHTA and ARYG90LHTA Unit: mm Bottom view AIR Service access 500 or more Control box 700 or more 700 or more Bottom view Unit: mm AIR Service access 500 or more or more 2,000 or more - 6 -

11 4. Wiring diagrams 4-1. Model: ARYG72LHTA DUCT TYPE I/O PCB, WLAN adapter, Converter etc

12 DUCT TYPE 4-2. Model: ARYG90LHTA I/O PCB, WLAN adapter, Converter etc

13 5. Capacity table Capacity tables show each of following values calculated based on the outdoor temperature and the indoor temperature, under given Airflow Rate (AFR): For cooling capacity: Total Capacity (TC), Sensible Heat Capacity (SHC), and Input Power (IP) For heating capacity: Total Capacity (TC) and Input Power (IP) DUCT TYPE 5-1. Cooling capacity Model: ARYG72LHTA AFR m 3 /h 4,300 Outdoor temperature Indoor temperature CDB CWB CDB TC SHC IP TC SHC IP TC SHC IP TC SHC IP TC SHC IP TC SHC IP TC SHC IP kw kw kw kw kw kw kw Model: ARYG90LHTA AFR m 3 /h 4,300 Outdoor temperature Indoor temperature CDB CWB CDB TC SHC IP TC SHC IP TC SHC IP TC SHC IP TC SHC IP TC SHC IP TC SHC IP kw kw kw kw kw kw kw

14 DUCT TYPE 5-2. Heating capacity NOTE: Values mentioned in the table are calculated based on the maximum capacity. Model: ARYG72LHTA AFR m 3 /h 4,300 Outdoor temperature Indoor temperature CDB CDB CWB TC IP TC IP TC IP TC IP TC IP kw kw kw kw kw Model: ARYG90LHTA AFR m 3 /h 4,300 Outdoor temperature Indoor temperature CDB CDB CWB TC IP TC IP TC IP TC IP TC IP kw kw kw kw kw

15 6. Fan performance 6-1. Fan performance curve Model: ARYG72LHTA 300 Fan performance curve_1 DUCT TYPE External Static Pressure [Pa] Normal SP upper limit Qu (SP mode15) SP mode15 upper limit Qu (Normal SP) 20 Normal SP 0 lower limit 2,000 2,500 3,000 3,500 4,000 4,500 5,000 [m 3 /h] ,111 1,250 1,389 [l/s] 300 Airflow SP mode15 lower limit Fan performance curve_2 (For function setting by remote controller) Hi (SP mode15) Hi (Normal SP) External Static Pressure [Pa] Hi (SP mode13,14,15) Hi (SP mode12) Hi (SP mode11) Hi (SP mode10) Hi (SP mode09) Hi (SP mode08) Hi (Normal SP) Hi (SP mode07) Hi (SP mode06) Hi (SP mode05) 0 2,000 2,500 3,000 3,500 4,000 4,500 5,000 [m 3 /h] ,111 1,250 1,389 [l/s] Airflow

16 DUCT TYPE NOTES: Setting of the external static pressure is switchable into modes by using the remote controller. According to the resistance of the connecting duct, perform the setting of the external static pressure with referring Fan performance curve_2 above. The default setting is set at "Normal SP". Characteristics of air volume and capacity Cooling 105 Capacity [%] 100 Heating 95 2,000 2,500 3,000 3,500 4,000 4,500 5,000 [m 3 /h] ,111 1,250 1,389 [l/s] Airflow 105 Capacity [%] ,000 2,500 3,000 3,500 4,000 4,500 5,000 [m 3 /h] ,111 1,250 1,389 [l/s] Airflow

17 Model: ARYG90LHTA Fan performance curve_1 DUCT TYPE External Static Pressure [Pa] Qu (SP mode20) Normal SP upper limit SP mode20 upper limit Hi (SP mode20) SP mode20 lower limit Hi (Normal SP) 40 Qu (Normal SP) 20 Normal SP 0 lower limit 2,000 2,500 3,000 3,500 4,000 4,500 5,000 [m 3 /h] ,111 1,250 1,389 [l/s] Airflow Fan performance curve_2 (For function setting by remote controller) External Static Pressure [Pa] Hi (SP mode20) Hi (SP mode19) Hi (SP mode18) Hi (SP mode17) Hi (SP mode16) Hi (SP mode15) Hi (SP mode14) Hi (SP mode13) Hi (SP mode12) Hi (SP mode11) Hi (SP mode10) Hi (SP mode09) Hi (SP mode08) Hi (Normal SP) Hi (SP mode07) Hi (SP mode06) Hi (SP mode05) 0 2,000 2,500 3,000 3,500 4,000 4,500 5,000 [m 3 /h] ,111 1,250 1,389 [l/s] Airflow NOTES: Setting of the external static pressure is switchable into modes by using the remote controller. According to the resistance of the connecting duct, perform the setting of the external static pressure with referring Fan performance curve_2 above. The default setting is set at "Normal SP"

18 DUCT TYPE Characteristics of air volume and capacity Cooling 105 Capacity [%] 100 Heating 95 2,000 2,500 3,000 3,500 4,000 4,500 5,000 [m 3 /h] ,111 1,250 1,389 [l/s] Airflow 105 Capacity [%] ,000 2,500 3,000 3,500 4,000 4,500 5,000 [m 3 /h] ,111 1,250 1,389 [l/s] Airflow Automatic airflow adjustment procedures 1. To start the auto setting, use No.32 of setting value in Function Number Run the air conditioner on fan mode (High). * For instructions on how to operate the air conditioner, refer to the operation manual of the remote controller. During automatic airflow adjustment, the mode will be fixed at fan (High). When this function is active, do not operate the outdoor unit. 3. The air conditioner will run for about 1 to 8 min then stop automatically. * Do not change the throttles of the inlet and outlet ports during operation. When used in a group control system, the setting will take about 10 min. 4. Turn the air conditioner off and on again. 5. Check the setting value of Function 26. * If the setting value has not changed, repeat the procedure from step 2. CAUTION When the duct or outlet installations are changed after the Automatic airflow adjustment is completed, repeat the procedure from step

19 6-2. Airflow Model: ARYG72LHTA Cooling DUCT TYPE Fan speed HIGH MED LOW QUIET Airflow m 3 /h 4,300 l/s CFM 2,531 m 3 /h 3,900 l/s 1,083 CFM 2,296 m 3 /h 3,450 l/s 958 CFM 2,031 m 3 /h 3,000 l/s 833 CFM 1,766 Heating Fan speed HIGH MED LOW QUIET Airflow m 3 /h 4,300 l/s CFM 2,531 m 3 /h 3,900 l/s 1,083 CFM 2,296 m 3 /h 3,450 l/s 958 CFM 2,031 m 3 /h 3,000 l/s 833 CFM 1,

20 DUCT TYPE Model: ARYG90LHTA Cooling Heating Fan speed HIGH MED LOW QUIET Airflow m 3 /h 4,300 l/s CFM 2,531 m 3 /h 3,900 l/s 1,083 CFM 2,296 m 3 /h 3,450 l/s 958 CFM 2,031 m 3 /h 3,000 l/s 833 CFM 1,766 Fan speed HIGH MED LOW QUIET Airflow m 3 /h 4,300 l/s CFM 2,531 m 3 /h 3,900 l/s 1,083 CFM 2,296 m 3 /h 3,450 l/s 958 CFM 2,031 m 3 /h 3,000 l/s 833 CFM 1,

21 7. Operation noise (sound pressure) 7-1. Noise level curve Model: ARYG72LHTA Cooling Heating DUCT TYPE Octave band sound pressure level, db: (0 db= µbar) Quiet High NC-65 NC-60 NC-55 NC-50 NC-45 NC-40 NC-35 NC-30 NC-25 NC-20 NC-15 Octave band sound pressure level, db: (0 db= µbar) Quiet High NC-65 NC-60 NC-55 NC-50 NC-45 NC-40 NC-35 NC-30 NC-25 NC-20 NC ,000 2,000 4,000 8,000 Octave band center frequency, Hz ,000 2,000 4,000 8,000 Octave band center frequency, Hz Model: ARYG90LHTA Cooling 80 Heating 80 Octave band sound pressure level, db: (0 db= µbar) Quiet High NC-65 NC-60 NC-55 NC-50 NC-45 NC-40 NC-35 NC-30 NC-25 NC-20 NC-15 Octave band sound pressure level, db: (0 db= µbar) Quiet High NC-65 NC-60 NC-55 NC-50 NC-45 NC-40 NC-35 NC-30 NC-25 NC-20 NC ,000 2,000 4,000 8,000 Octave band center frequency, Hz ,000 2,000 4,000 8,000 Octave band center frequency, Hz

22 DUCT TYPE 7-2. Sound level check point 2 m 1 m Air Product Measuring duct (Set the static pressure as rating in this area.) 1.5 m Measuring duct Microphone Microphone Front view Side view

23 8. Electrical characteristics Model name ARYG72LHTA ARYG90LHTA Power supply Voltage V 230 ~ Frequency Hz 50 Max operating current A Circuit breaker current A 15 Power cable mm Wiring spec. *1 Connection cable *2 mm Limited wiring length m 101 DUCT TYPE *1: Selected sample based on Japan Electrotechnical Standards and Codes Committee E0005. As the regulations of wire size and circuit breaker differ in each country or region, select appropriate devices complied to the regional standard. *2: Limit voltage drop to less than 2%. Increase conductor size if voltage drop is 2% or more

24 DUCT TYPE 9. Safety devices Type of protection Protection form ARYG72LHTA Model ARYG90LHTA 250 V, 3.15 A Circuit protection Current fuse (PCB*) 250 V, 10 A 250 V, 20 A Fan motor protection Current protection 12.9 A 19.3 A *: Printed Circuit Board

25 10. External input and output CN71 (Drain pump) CN9 (Float switch) CN47 (External out) CN8 (Remote sensor) CN65 (External in/out PCB) CN48 (IR receiver) Rotary switch SW2 SW1 Fig. External input and output PCB DUCT TYPE Y1 Y2 Y3 1 2 Terminal (External in) Fig. Indoor unit PCB PCB External input External output Connector Input select Indoor unit External input and output (UTY-XCSX) Operation/Stop Forced stop Operation/Stop - Forced thermostat off - Operation status Error status Indoor unit fan operation status External heater output Operation status Error status Indoor unit status External heater output Input signal External connect kit (Optional parts) - Terminal Dry contact Edge - - CN UTY-XWZXZG Input 1/ Input 2 Input 1 Output 1 Output 2 Output 3 Dry contact/ Apply voltage Edge/ Pulse Edge

26 DUCT TYPE External input Operation/Stop mode or "Forced stop" mode can be selected with function setting of indoor unit. A twisted pair cable (22AWG) should be used. Maximum length of cable is 150 m. The wire connection should be separate from the power cable line. Indoor unit Indoor unit functions such as Operation/Stop can be done by using indoor unit terminals. Terminal 1 2 *1: The switch can be used on the following condition: DC 12 V to 24 V, 1 ma to 15 ma. External input and output PCB The indoor unit Operation/Stop can be set by using the input terminal on the PCB. Input select Use either one of these types of terminals according to the application. (Both types of terminals cannot be used simultaneously.) Dry contact In case of internal power supply, set the slide switch of SW1 to "NON VOL" side. Input 1 Input PCB 1 2 C Connected unit *1: The switches can be used on the following condition: DC 12 V to 24 V, 1 ma to 15 ma. Apply voltage In case of external power supply, set the slide switch of SW1 to "VOL" side. PCB - Input 1 Input 2 Power supply C Connected unit *1: The switches can be used on the following condition: DC 12 V to 24 V, 1 ma to 15 ma. *2: Make the power supply DC 12 V to 24 V 10 ma or more

27 10-2. External output Use an external output cable with appropriate external dimension, depending on the number of cables to be installed. Indoor unit A twisted pair cable (22AWG) should be used. Maximum length of cable is 25 m. Output voltage: High DC 12 V ± 2 V, Low 0 V. Permissible current: 50 ma For details, refer to Chapter "Combination of external input and output" on page 24. DUCT TYPE When indicator, etc. are connected directly Example: Function setting 60 is set to "00" PCB LED Resistor CN47 Connected unit When connecting with a device equipped with a power supply Example: Function setting 60 is set to "00" + Connected device (Operation status) - PCB 1 2 CN47 Connected unit Relay External input and output PCB A twisted pair cable (22AWG) should be used. Permissible voltage and current: DC 5 V to 30 V / 3 A, AC 30 V to 250 V / 3 A For details, refer to Chapter "Combination of external input and output" on page 24. Example PCB Connected device 1 (Operation status) Connected device 2 (Error status) Connected device 3 (Indoor unit fan operation status) Power supply Power supply Power supply

28 DUCT TYPE Combination of external input and output By combining the function setting of the indoor unit and rotary switch setting of the External input and output PCB, you can select various combinations of functions. Combination examples of external input and output are as follows: Mode Function setting External input and output PCB (Rotary SW) Indoor unit Input Operation/Stop Operation/Stop to External input External input and output PCB Terminal Input 1 Input 2 Signal type Operation/Stop Not available Edge Operation Stop Pulse Forced Thermostat OFF Not available Edge 3-9, A (Setting prohibited) B Operation/Stop C Operation/Stop D Operation/Stop Mode Function setting External input and output PCB (Rotary SW) Indoor unit Output Forced Thermostat OFF Forced Thermostat OFF Forced Thermostat OFF External output Not available Not available Not available External input and output PCB Edge Edge Edge CN47 Output 1 Output 2 Output Operation/Stop Operation/Stop Error status Operation/Stop Error status to Indoor unit fan operation status 3-9, A (Setting prohibited) B Error status Operation/Stop C D Indoor unit fan operation status External heater output Operation/Stop Operation/Stop Indoor unit fan operation status Error status Indoor unit fan operation status NOTE: Input of Operation/Stop depends on the setting of function setting : Operation/Stop mode 1 (R.C. enabled) 01: (Setting prohibited) 02: Forced stop 03: Operation/Stop mode 2 (R.C. disabled) Indoor unit fan operation status External heater output External heater output External heater output Error status

29 Input signal type Indoor unit Input signal type is only "Edge". Edge DUCT TYPE External input and output PCB The input signal type can be selected. Signal type (edge or pulse) can be switched by the DIP switch 2 (SW2) on the External input and output PCB. Edge The width of pulse must be longer than 200 msec. Pulse

30 DUCT TYPE Details of function Control input function When function setting is "Operation/Stop" mode 1 In the case of "Edge" input Function setting / Rotary SW of External input and output PCB - Input of indoor unit Terminal / 1 External input Input signal Command External input and output PCB Input 1 Off On On Off Off On On Off Operation Stop Operation Stop Input On Off Indoor unit Operation Stop Remote controller On In the case of "Pulse" input Function setting / Rotary SW of External input and output PCB / 1 External input Input signal Command External input and output PCB Input 1 Pulse Operation Input 2 Pulse Stop Input 1 On Off Input 2 On Off Indoor unit Operation Stop Remote controller On NOTES: The last command has priority. The indoor units within the same remote controller group operates in the same mode

31 When function setting is "Forced stop" mode In the case of "Edge" input Function setting / Rotary SW of External input and output PCB - Input of indoor unit Terminal / 1 External input Input signal Command External input and output PCB Input 1 Off On On Off Off On On Off Forced stop Normal Forced stop Normal DUCT TYPE Input On Off Forced stop Normal Indoor unit Operation Stop Remote controller On On On In the case of "Pulse" input Function setting / Rotary SW of External input and output PCB / 1 External input Input signal Command External input and output PCB Input 1 Pulse Forced stop Input 2 Pulse Normal Input 1 Input 2 On Off On Off Forced stop Normal Indoor unit Operation Stop Remote controller On On On NOTES: When the forced stop is triggered, indoor unit stops and Operation/Stop operation by the remote controller is restricted. When forced stop function is used with forming a remote controller group, connect the same equipment to each indoor unit within the group

32 DUCT TYPE When function setting is "Operation/Stop" mode 2 In the case of "Edge" input Function setting / Rotary SW of External input and output PCB - Input of indoor unit Terminal / 1 External input Input signal Command External input and output PCB Input 1 Off On On Off Off On On Off Operation Stop (R.C. disabled) Operation Stop (R.C. disabled) Input On Off Operation Indoor unit Stop (R.C. disabled) In the case of "Pulse" input Remote controller On Off On Function setting / Rotary SW of External input and output PCB / 1 External input Input signal Command External input and output PCB Input 1 Pulse Operation Input 2 Pulse Stop (R.C. disabled) Input 1 On Off Input 2 On Off Operation Indoor unit Stop (R.C. disabled) Remote controller On Off On NOTES: When "Operation/Stop" mode 2 function is used with forming a remote controller group, connect the same equipment to each indoor unit within the group

33 Forced thermostat off function Function setting / Rotary SW of External input and output PCB / / B / C / D External input Input signal Command External input and output PCB Input 1 Off On On Off Thermostat off Normal operation DUCT TYPE Input On Off Compressor On Off Room temp. Set temp. Control output function Function setting / Rotary SW of External input and output PCB External output / 1, 2 Output of indoor unit CN / / B / C / D External input and output PCB Output 1 Output signal Low High High Low Off On On Off Command Operation Stop Operation Stop The output is low when the unit is stopped. Operation Indoor unit Stop CN47 High Low On Output 1 Off

34 DUCT TYPE Error status Function setting / Rotary SW of External input and output PCB External output Output signal Command / B Output of indoor unit CN47 Low High Error High Low Normal / 2 Output 1 Off On Error On Off Normal / 1 External input and output Off On Error Output / C PCB On Off Normal / D Output 3 Off On Error On Off Normal The output is ON when an error is generated for the indoor unit. Error Indoor unit Normal CN47 High Low On Output 1, 2, 3 Off Indoor unit fan operation status Function setting / Rotary SW of External input and output PCB External output / C Output of indoor unit CN / / B Output 2 External input and output / D PCB / 1 Output 3 Output signal Low High High Low Off On On Off Off On On Off Command Fan run Fan stop Fan run Fan stop Fan run Fan stop Output signal On Low High Off High Low Condition The indoor unit fan is operating. The fan is stopped or during cold air prevention. During thermostat off when in dry mode operation. Indoor unit CN47 Output 2, 3 Fan run Fan stop High Low On Off

35 External heater output Function setting / Rotary SW of External input and output PCB External output Output signal Command Low High Heater on / D Output of indoor unit CN47 High Low Heater off / 2 External input and output Off On Heater on / B Output 3 PCB / C On Off Heater off DUCT TYPE Output signal Low High Off On High Low On Off Condition Heater turns on as shown in diagram of heating temperature Heater turns off as shown in diagram of heating temperature Other than Heating mode Error occurred Forced thermo off Fan stop protection Specifications of the signal output performance are as shown as follows: Example: When set temperature (Ts) is set at 22 C; And room temperature (Tr) increase above 12 C, signal output is on. And Tr increase above 21 C, signal output is off. And Tr decrease below 19 C, signal output is on. And Tr decrease below 10 C, signal output is off. Tr-Ts Tr-Ts=-1 C Tr-Ts=-10 C Off On Off Tr-Ts=-3 C Tr-Ts=-12 C The output also turns off in defrost operation

36 DUCT TYPE 11. Remote controller Wired remote controller Overview j i h g f Display panel o k l Monitor mode screen a b c d e m n a LED lamp (Operation indicator) Lights while the indoor unit is operating. Blinks when an error occurred. b FAN button Each time the button is pressed, fan speed switches as follows: Auto High Med Low Quiet c +, - buttons (Set temperature buttons) Used to adjust temperature in Monitor mode screen. + button: Raise - button: Lower In Setting screen, used to select the setting items. NOTE: When the operation mode is set to FAN, the temperature cannot be adjusted. d ENTER button Used to enter setting items and settings. e Room temperature sensor (inside) Senses ambient temperature of unit. f <, > buttons Used to select setting items during the setting item selection screen is displayed. g MENU button Used to display the setting item selection screen. h MODE button Each time the button is pressed, operation mode switches as follows: Auto Cool Dry Fan Heat NOTE: Setting screen (Example: Airflow direction setting) For individual icons in Setting screen and related functions, refer to the operation manual. i On/Off button Starts or stops the operation. NOTE: On/Off button cannot be operated at screens other than the Monitor mode screen. j Display panel Displays Monitor mode screen or Setting screen. Monitor mode screen is home screen of this controller, and the basic operation is performed in this screen. In Setting screen, several settings are adjustable. k Temperature indicator l Fan speed indicator m Clock indicator n Airflow direction indicator o Operation mode indicator

37 System diagram 1 remote controller: Indoor unit 2 remote controllers: Indoor unit DUCT TYPE A B C A, B, C: Remote controller cable A 500 m;b + C 500 m Primary Secondary Remote controller Remote controllers Electrical wiring 1 remote controller: 2 remote controllers: Y1 Y2 Y3 Indoor unit Y1 Y2 Y3 Indoor unit When there is a functional grounding Y1 Y2 Remote controller When there is a functional grounding Y1 Y2 Y1 Y2 Remote controller Remote controller Group control: When there is a functional grounding Indoor units Y1 Y2 Y3 Y1 Y2 Y3 Y1 Y2 Y3 Y1 Y2 Y3 Y1 Y2 Remote controller NOTES: Group connection with simultaneous multi system is not allowed. Group control with Polar 3-wired remote controller is not allowed

38 DUCT TYPE Specifications Dimensions and other specifications on the wired remote controller are as follows. Unit: mm Hole: Front view Side view Hole: Hole: Rear view Size (H W D) mm Weight g 170 Power V 12 Wiring specifications Use Cable size Wire type Remarks Remote controller cable 0.33 to 1.25 mm 2 Non-polar 2-core, Twisted pair Use sheathed PVC cable

39 12. Function settings To adjust the functions of this product according to the installation environment, various types of function settings are available. NOTE: Incorrect settings can cause a product malfunction. DUCT TYPE Function settings on indoor unit Models: ARYG72LHTA and ARYG90LHTA By using some components on the PCB, you can change the function settings. Related components on the PCB and the applicable settings DIP switch100 DIP switch101 Component Setting content 1 2 Remote controller address setting Setting change prohibited 2 Setting change prohibited 3 Fan delay setting Component location Components on the indoor unit main PCB used for the function settings are located as shown in the following figure. SW100 SW

40 DUCT TYPE DIP switch setting Remote controller address setting (SW100) When operating a number of indoor units by using a wired remote controller, DIP switch setting for assigning unit number to each indoor unit is required. DIP switches are normally set to make the unit number 00. Remote controller address DIP switch number Factory setting 00 OFF OFF OFF OFF 01 ON OFF OFF OFF 02 OFF ON OFF OFF 03 ON ON OFF OFF 04 OFF OFF ON OFF 05 ON OFF ON OFF 06 OFF ON ON OFF 07 ON ON ON OFF 08 OFF OFF OFF ON 09 ON OFF OFF ON 10 OFF ON OFF ON 11 ON ON OFF ON 12 OFF OFF ON ON 13 ON OFF ON ON 14 OFF ON ON ON 15 ON ON ON ON Indoor unit Remote controller address Remote controller Switch 1: Setting change prohibited (SW101) Switch 2: Setting change prohibited (SW101) Switch 3: Fan delay setting (SW101) When the indoor unit is stopped while operating in conjunction with auxiliary heater, the indoor unit fan operation will continue for 1 minute. Switch 3 Fan delay Factory setting ON Enabled OFF Disabled

41 12-2. Function settings by using remote controller Some function settings can be changed on the remote controller. After confirming the setting procedure and the content of each function setting, select appropriate functions for your installation environment. DUCT TYPE NOTE: Incorrect settings can cause a product malfunction. Remote controller address setting Remote controller address confirmation NOTE: The address of this remote controller is set automatically. Do not change the indoor unit remote controller address from the factory setting "0". (Verify that the address is "0".) 1. To activate the address setting mode, hold down the three buttons of MENU, <, and EN- TER at the same time for 2 seconds or longer. Menu 2 setting screen is displayed. 2. Select the 15 in Menu 2 settings. Then press the ENTER button. 3. The address of this unit is displayed on the screen. is displayed: Address automatically allocated Not displayed: Address manually allocated Remote controller address 01 to 32 Press the ENTER button to return to the Menu 2 item selection screen

42 DUCT TYPE Setting the remote controller address manually NOTES: Perform manual address setting only when setting the address with an arbitrary number. Indoor unit remote controller address setting is necessary. Set the remote controller address of indoor units connected by the same remote controller cable within a range of 1 to 9 and A (10) to F (15) so that there is no duplication. (Do not set to "0".) The address of this unit is set within a range of 1 to 32, but set it so that it does not duplicate the remote controller address of an indoor unit connected by the same remote controller cable. 1. To activate the address setting mode, hold down the three buttons of MENU, <, and EN- TER at the same time for 2 seconds or longer. Menu 2 setting screen is displayed. 2. Select the 15 in Menu 2 settings. Then press the ENTER button. 3. The address of this unit is displayed on the screen. Set the unit number with the + or - buttons. System number cannot be changed. is displayed: Address automatically allocated Not displayed: Address manually allocated Remote controller address 01 to 32 Press the ENTER button to return to the Menu 2 item selection screen

43 Resetting the manual address setting number 1. To activate the address setting mode, hold down the three buttons of MENU, <, and EN- TER at the same time for 2 seconds or longer. Menu 2 setting screen is displayed. DUCT TYPE 2. Select the 14 in Menu 2 settings. Then press the ENTER button. 3. To reset address, select 1: Reset with the + or - buttons. If not resetting, press the MENU button to the Menu 2 item selection screen. is displayed: Address automatically allocated Not displayed: Address manually allocated : Not reset : Reset Press the ENTER button to return to the Menu 2 item selection screen

44 DUCT TYPE Remote controller master/slave setting NOTE: Set only one Master remote controller. 1. To activate the address setting mode, hold down the three buttons of MENU, <, and EN- TER at the same time for 2 seconds or longer. Menu 2 setting screen is displayed. 2. Select the 06 in Menu 2 settings. Then press the ENTER button. 3. Select the 0: Master or the 1: Slave with the + or - buttons. : Master : Slave 4. Press the "ENTER" button. If there is no problem, return to Menu 2 items selection screen. In the case of settings at initial booting, "Monitor mode screen" is displayed. There's 0 or more than 2 "Master" units: The number will be displayed. "Master" is 0: Press the "ENTER" button to return to the Menu 2 item selection screen. "Master" is more than 2: Press the "ENTER" button to return to the screen of step 2. "Master" is 0 or more than 2: Press the "MENU" button to return to the Menu 2 item selection screen. Number of Master units

45 Setting procedure by using wired remote controller The function number and the associated setting value are displayed on the LCD of the remote controller. Follow the instructions written in the local setup procedure supplied with the remote controller, and select appropriate setting according to the installation environment. Before connecting the power supply of the indoor unit, reconfirm following items: Piping air tight test and vacuuming have been performed firmly. There is no wiring mistake. 1. Connect the power supply. 2. To activate the address setting mode, hold down the three buttons of MENU, <, and EN- TER at the same time for 2 seconds or longer. Menu 2 setting screen is displayed. DUCT TYPE 3. Select the 13 in Menu 2 settings. Then press the ENTER button. 4. Pressing the "+" or "-" button, select a remote controller address (select the indoor unit you want to operate). Then press the "ENTER" button. Remote controller address Example: When remote controller address 01 is selected

46 DUCT TYPE 5. Pressing the "+" or "-" button, to select the function number. Then press the "ENTER" button. Function number 6. Pressing the "+" or "-" button, to select the setting number. Then press the "ENTER" button. Setting number Example: Function number 30 Setting number 01 Error Good When the data was not set up on the indoor unit ( -- is displayed.) When the data was normally set up on the indoor unit. Set up the data again. Pressing the "ENTER" button to return to the address selection screen. If setting has been completed, pressing the "MENU" button to return to the Menu 2 item selection screen

47 Contents of function setting Each function setting listed in this section is adjustable in accordance with the installation environment. NOTE: Setting will not be changed if invalid numbers or setting values are selected. DUCT TYPE Function setting list Function no. Functions 1) 11 Filter sign 2) 26 Static pressure 3) 30/31 Room temperature control for indoor unit sensor 4) 35/36 Room temperature control for wired remote controller sensor 5) 40 Auto restart 6) 42 Room temperature sensor switching 7) 43 Cold air prevention 8) 44 Remote controller custom code 9) 46 External input control 10) 48 Room temperature sensor switching (Aux.) 11) 49 Indoor unit fan control for energy saving for cooling 12) 60 Switching functions for external output terminal 1) Filter sign Select appropriate intervals for displaying the filter sign on the indoor unit according to the estimated amount of dust in the air of the room. If the indication is not required, select "No indication" (03). Function number Setting value Setting description Factory setting Standard (2,500 hours) 01 Long interval (4,400 hours) 02 Short interval (1,250 hours) 03 No indication

48 DUCT TYPE 2) Static pressure Select the appropriate static pressure according to the installation conditions. Function number Setting value Setting description Factory setting Pa Pa Pa Pa Pa Pa Pa Pa Pa Pa Pa Pa Pa Pa Pa Pa 31 Standard (72 Pa) 32 Automatic airflow adjustment NOTE: Range of static pressure is different by model. Type name Setting of static pressure range 72 type 50 to 150 Pa 90 type 50 to 200 Pa 3) Room temperature control for indoor unit sensor Depending on the installed environment, correction of the room temperature sensor may be required. Select the appropriate control setting according to the installed environment. The temperature correction values show the difference from the Standard setting "00" (manufacturer s recommended value). Function number Setting value Setting description 30 (For cooling) 31 (For heating) Factory setting 00 Standard setting 01 No correction 0.0 C C C C C C C C C C C C C C C C C More cooling Less heating Less cooling More heating

49 4) Room temperature control for wired remote controller sensor Depending on the installed environment, correction of the wire remote temperature sensor may be required. Select the appropriate control setting according to the installed environment. To change this setting, set Function 42 to Both 01. Ensure that the Thermo Sensor icon is displayed on the remote controller screen. DUCT TYPE Function number Setting value Setting description 35 (For cooling) 36 (For heating) Factory setting 00 No correction 01 No correction 0.0 C C C C C C C C C C C C C C C C C More cooling Less heating Less cooling More heating 5) Auto restart Enables or disables automatic restart after a power interruption. Function number Setting value Setting description Factory setting Enable 01 Disable NOTE: Auto restart is an emergency function such as for power outage etc. Do not attempt to use this function in normal operation. Be sure to operate the unit by remote controller or external device. 6) Room temperature sensor switching (Only for wired remote controller) When using the wired remote controller temperature sensor, change the setting to "Both" (01). Function number Setting value Setting description Factory setting Indoor unit 01 Both 00: Sensor on the indoor unit is active. 01: Sensors on both indoor unit and wired remote controller are active. NOTE: Remote controller sensor must be turned on by using the remote controller

50 DUCT TYPE 7) Cold air prevention This setting is to disable the cold air prevention function during heating operation. When disabled, the fan setting will always follow the setting on the remote controller. (Excluding defrost mode) Function number Setting value Setting description Factory setting Enable 01 Disable 8) Remote controller custom code (Only for wireless remote controller) The indoor unit custom code can be changed. Select the appropriate custom code. Function number Setting value Setting description Factory setting A 01 B 02 C 03 D 9) External input control "Operation/Stop" mode or "Forced stop" mode can be selected. Function number Setting value Setting description Factory setting Operation/Stop mode 1 01 (Setting prohibited) 02 Forced stop mode 03 Operation/Stop mode 2 10) Room temperature sensor switching (Aux.) To use the temperature sensor on the wired remote controller only, change the setting to "Wired remote controller" (01). This function will only work if the function setting 42 is set at "Both" (01). When the setting value is set to "Both" (00), more suitable control of the room temperature is possible by setting function setting 30 and 31 too. Function number Setting value Setting description Factory setting Both 01 Wired remote controller

51 11) Indoor unit fan control for energy saving for cooling Enables or disables the power-saving function by controlling the indoor unit fan rotation when the outdoor unit is stopped during cooling operation. Function number Setting value Setting description Factory setting Disable 01 Enable 02 Remote controller DUCT TYPE 00: When the outdoor unit is stopped, the indoor unit fan operates continuously following the setting on the remote controller. 01: When the outdoor unit is stopped, the indoor unit fan operates intermittently at a very low speed. 02: Enable or disable this function by remote controller setting. NOTES: As the factory setting, this setting is initially inactivated. Set to "00" or "01" when connecting a remote controller that cannot set the Fan control for energy saving function or connecting a network converter. To confirm if the remote controller has this setting, refer to the operating manual of each remote controller. 12) Switching functions for external output terminal Functions of the external output terminal can be switched. For details, refer to External input and output. Function number Setting value Setting description Factory setting Operation status (Setting prohibited) 09 Error status 10 Indoor unit fan operation status 11 External heater

52 DUCT TYPE 13. Accessories Part name Exterior Q ty Part name Exterior Q ty Operating manual (For indoor unit) 1 Coupler heat insulation (small) 1 Operating manual (CD-ROM) 1 Cable tie (large) 4 Operating manual (For remote controller) 1 Cable tie (medium) 1 Installation manual (For indoor unit) 1 Cable tie (small) 1 Installation manual (For remote controller) 1 Remote controller 1 Special nut A (large flange) 4 Remote controller accessories 1 set Special nut B (small flange) 4 Drain hose insulation 1 Washer 8 Drain hose 1 Coupler heat insulation (large) 1 Hose band

53 14. Optional parts Controllers DUCT TYPE Exterior Part name Model name Summary Wired remote controller UTY-RNRYZ* Easy finger touch operation with LCD panel. Backlit LCD enables easy operation in a dark room. Wire type: Non-polar 2-wire Wired remote controller UTY-RLRY High visibility and easy operation. Room temperature can be accurately controlled using the built-in thermo sensor. Wire type: Non-polar 2-wire Simple remote controller UTY-RSRY Compact remote controller concentrates on the basic functions such as Start/Stop, fan control, temperature setting, and operation mode. Wire type: Non-polar 2-wire Simple remote controller UTY-RHRY Compact remote controller concentrates on the basic functions such as Start/Stop, fan control, and temperature setting. Wire type: Non-polar 2-wire Wired remote controller UTY-RVNYM Large and full-dot liquid crystal screen, wide and large keys easy to press, user-intuitive arrow key. Wire type: Polar 3-wire Wired remote controller UTY-RNNYM Room temperature can be controlled by detecting the temperature accurately with built-in thermo sensor. Wire type: Polar 3-wire Simple remote controller UTY-RSNYM Compact remote controller concentrates on the basic functions such as Start/Stop, fan control, temperature setting, and operation mode. Wire type: Polar 3-wire

54 DUCT TYPE Exterior Part name Model name Summary IR receiver kit with wireless remote controller UTY-LBTYM Unit control is performed by wireless remote controller. NOTE: Available functions may differ by the remote controller. For details, refer to the operation manual

55 14-2. Others Exterior Part name Model name Summary Remote sensor unit UTY-XSZX New amenity space can be offered by installing Remote sensor unit in the remote controller. DUCT TYPE Long-life filter UTD-LFKA Long-life filter can be mounted to the indoor unit. Drain pump unit UTZ-PX1NAB Optional drain lift up mechanism allows more flexible installation. External connect kit UTY-XWZXZG Use to connect with various peripheral devices and air conditioner PCB. For control output port. External input and output PCB UTY-XCSX Use to connect with external devices and air conditioner PCB. Wireless LAN adapter UTY-TFSXZ1 Remotely manage an air conditioning system using mobile devices such as smartphones and tablets. MODBUS converter UTY-VMSX For connection between an air conditioner and a MODBUS open network. KNX converter UTY-VKSX For connection between an air conditioner and a KNX network. Split system converter UTY-VTGX This converter is required when connecting single split system to VRF network system

56 DUCT TYPE Exterior Part name Model name Summary Split system converter (AC power supply) UTY-VTGXV This converter is required when connecting single split system to VRF network system. External switch controller UTY-TERX Air conditioner switching can be controlled by connecting other external sensor switches. NOTE: Combined use of External input and output PCB, MODBUS converter, KNX converter, and Wireless LAN adapter is not allowed

R410A D2D_AU019E/

R410A D2D_AU019E/ R41A 2. : AUU18RCLX AUU24RCLX D2D_AU19E/ 27.6.11 2-1. FEATURE MODELS : AUU18RCLX / AOU18RLX AUU24RCLX / AOU24RLX FEATURES Easy maintenance The control box is easily accessible for maintenance work Wide

More information

INTERFACE SPECIFICATION

INTERFACE SPECIFICATION INTERFACE SPECIFICATION MODBUS CONVERTOR UTY-VMGX PART NO. 9708438030 Modbus is registered trademarks of Schneider Electric SA. LONWORKS is registered trademark of Echelon Corporation in the United States

More information

SINGLE. Technical Data Book. Big Duct for EU (R410A, 50Hz, HP) Model : IDU : AC***KNHPKH/EU ODU : AC***KXAPNH/EU

SINGLE. Technical Data Book. Big Duct for EU (R410A, 50Hz, HP) Model : IDU : AC***KNHPKH/EU ODU : AC***KXAPNH/EU SINGLE Technical Data Book Big Duct for EU (R4A, 0Hz, HP) Model : IDU : AC***KNHPKH/EU ODU : AC***KXAPNH/EU History Version Modification Date Remark Ver 1.0 Release SINGLE Big Duct for EU (R4A, 0Hz, HP)

More information

Slim Ducted type. Contents MMD-AP 4SPH2UL MMD-AP0094SPH2UL MMD-AP0124SPH2UL MMD-AP0154SPH2UL MMD-AP0184SPH2UL

Slim Ducted type. Contents MMD-AP 4SPH2UL MMD-AP0094SPH2UL MMD-AP0124SPH2UL MMD-AP0154SPH2UL MMD-AP0184SPH2UL E5-3I D-AP 4SP2U Slim Ducted type D-AP0074SP2U D-AP0094SP2U D-AP024SP2U D-AP054SP2U D-AP084SP2U Contents. Specifications 2. Dimensions 3. Center of gravity 4. Piping diagram 5. Wiring diagram 6. Electrical

More information

Slim duct (AMTTTFNLDEH ) Indoor units

Slim duct (AMTTTFNLDEH ) Indoor units Slim duct (AMTTTFNLDEH ) Slim duct. Specifications 1) Technical specifications Model AM22FNLDEH AM28FNLDEH AMFNLDEH AM4FNLDEH AMFNLDEH Power Supply Ø, #, V, Hz 1,2,22-24, 1,2,22-24, 1,2,22-24, 1,2,22-24,

More information

VRF. Technical Data Book. Slim duct for America (R410A, 60Hz, HP) Model : AM***FNLDCH***

VRF. Technical Data Book. Slim duct for America (R410A, 60Hz, HP) Model : AM***FNLDCH*** VRF Technical Data Book Slim duct for America (R41A, 6Hz, HP) Model : AM***FNLDCH*** History Version Modification Date Remark Ver.1. Release Slim duct for America (R41A, 6Hz, HP) 1.11.4 - Ver.1.1 1.12.28

More information

SERVICE Manual DUCT TYPE AIR CONDITIONER. (Cool) OUTDOOR UNIT INDOOR UNIT TYPE UDH4400G DH44ZAX IDH4400A DH44ZA1(A2) ADH4400G DH44ZA1(A2)

SERVICE Manual DUCT TYPE AIR CONDITIONER. (Cool) OUTDOOR UNIT INDOOR UNIT TYPE UDH4400G DH44ZAX IDH4400A DH44ZA1(A2) ADH4400G DH44ZA1(A2) DUCT TYPE AIR CONDITIONER (Cool) TYPE ADH4400G DH44ZA(A2) INDOOR UNIT IDH4400A DH44ZA(A2) OUTDOOR UNIT UDH4400G DH44ZAX SERVICE Manual AIR CONDITIONER CONTENTS. Product Specifications 2. Installation 3.

More information

SINGLE. Technical Data Book. 4Way Cassette S for (Inv, R410A,

SINGLE. Technical Data Book. 4Way Cassette S for (Inv, R410A, SINGLE Technical Data Book 4Way Cassette S for (Inv, R410A, 1 Ver.1.0 Release Single 4Way Cassette S for USA (Inv, R410A, 60Hz, HP) TDB 15.02.05 - Ver.1. 5.0.09 Ver.1..0.0 Ver.1..0. Index 1 Nomenclature

More information

INSTALLATION MANUAL For authorized service personnel only.

INSTALLATION MANUAL For authorized service personnel only. AIR CONDITIONER SIMPLE REMOTE CONTROLLER (WIRED TYPE) UTY-RSNUM INSTALLATION MANUAL For authorized service personnel only. English Français Español Contents. SAFETY PRECAUTIONS...2 2. ACCESSORIES...2 3.

More information

U-Match Series DC Inverter Service Manual PRODUCT

U-Match Series DC Inverter Service Manual PRODUCT PRODUCT 1 PRODUCT 1 MODELS LIST 1.1 Outdoor Unit Name Product Code Power Supply (V, Ph, Hz) Appearance GUHD24NS3GO CF090W0800 220-240V~ 50/60Hz GUHD36NS3GO CF090W0860 220-240V~ 50/60Hz GUHD42NS3GO CF090W0870

More information

IntesisBox. v.0.1. User Manual Issue Date: 12/2017 r1.3 EN

IntesisBox. v.0.1. User Manual Issue Date: 12/2017 r1.3 EN IntesisBox HS-RC-MBS-1 v.0.1 Modbus RTU (EIA-485) Interface for Hisense air conditioners. Compatible with commercial line of air conditioners commercialized by Hisense. User Manual Issue Date: 12/2017

More information

Wireless Remote Controller Kit

Wireless Remote Controller Kit INSTALLATION MANUAL Wireless Remote Controller Kit LS BRC4C8 Read these instructions carefully before installation. Keep this manual in a handy place for future reference. This manual should be left with

More information

MCFCW-08-4LS-1 (4-Pipe) Low Static Chilled/Hot Water Ceiling Concealed Cased Fan Coil 208/230V 4-Pipe Heating & Cooling Fan Coil 24,000 BTUH

MCFCW-08-4LS-1 (4-Pipe) Low Static Chilled/Hot Water Ceiling Concealed Cased Fan Coil 208/230V 4-Pipe Heating & Cooling Fan Coil 24,000 BTUH MCFCW-08-4LS-1 (4-Pipe) Low Static Chilled/Hot Water Ceiling Concealed Cased Fan Coil 208/230V 4-Pipe Heating & Cooling Fan Coil 24,000 BTUH 1 Chilled and Hot Water Fan Coil Low Static 4-Pipe Nominal Size:

More information

KNX is a European Standard Protocol used for household and industrial Buliding Management System (BMS).

KNX is a European Standard Protocol used for household and industrial Buliding Management System (BMS). PRODUCT NEWS Products News: New HC-A16KNX PAGE 1 / 8 Summary 1. This advanced product news introduces the new product HC-A16KNX. 2. The details are indicated in the description. Description 1. Applicable

More information

IntesisBox PA-AW-MBS-1 v.2.0

IntesisBox PA-AW-MBS-1 v.2.0 IntesisBox PA-AW-MBS-1 v.2.0 Modbus RTU (EIA485) Interface for Panasonic Aquarea series. User Manual Issue Date: 08/2014 r2.0 Order Code: PA-AW-MBS-1: Modbus RTU Interface for Panasonic Aquarea series

More information

IntesisBox ModBus RTU Fujitsu Air Conditioning

IntesisBox ModBus RTU Fujitsu Air Conditioning IntesisBox ModBus RTU Fujitsu Air Conditioning Compatible with Domestic and VRF line air conditioners commercialized by Fujitsu User Manual 03/2019 r1.0 eng Intesis Software S.L.U. 2019 All Rights Reserved.

More information

Two remote controller system with one Lossnay Basic System (Refer to page C-10) Multiple Lossnay units with one remote controller.

Two remote controller system with one Lossnay Basic System (Refer to page C-10) Multiple Lossnay units with one remote controller. Control CHAPTER 1 System Design 1. System Examples One with one remote Multiple units with one remote Two remote system with one Basic System (Refer to page C-10) Non-polar Two wires Power supply Remote

More information

Lossnay Remote Controller

Lossnay Remote Controller Remote Controller . Summary Technical manual detailing the control and operation of commercial-type units (LGH-RX5-E Series). Possible System Configurations () When using only the remote. (2) Linking

More information

MCFCW-20-4HS-1 (4-Pipe) High Static Chilled/Hot Water Ceiling Concealed Cased Fan Coil 208/230V 4-Pipe Heating & Cooling Fan Coil 60,000 BTUH

MCFCW-20-4HS-1 (4-Pipe) High Static Chilled/Hot Water Ceiling Concealed Cased Fan Coil 208/230V 4-Pipe Heating & Cooling Fan Coil 60,000 BTUH MCFCW-20-4HS-1 (4-Pipe) High Static Chilled/Hot Water Ceiling Concealed Cased Fan Coil 208/230V 4-Pipe Heating & Cooling Fan Coil 60,000 BTUH 1 Chilled and Hot Water Fan Coil High Static 4-Pipe Nominal

More information

7. PCB AND FUNCTIONS

7. PCB AND FUNCTIONS Contents. PCB AND FUNCTIS. Outdoor Unit Control PCB... - -. Outdoor Unit Control PCB CR-C0DXH... - -. Outdoor Unit FAN PCB FAN-C00DXH... - -. Outdoor Unit FAN PCB FAN-C0DXH... - -. Outdoor Unit Filer PCB

More information

IntesisBox. v.2.5. User Manual Issue Date: 12/2017 r1.9 EN. Modbus RTU (EIA-485) Interface for Fujitsu air conditioners.

IntesisBox. v.2.5. User Manual Issue Date: 12/2017 r1.9 EN. Modbus RTU (EIA-485) Interface for Fujitsu air conditioners. IntesisBox FJ-RC-MBS-1 v.2.5 Modbus RTU (EIA-485) Interface for Fujitsu air conditioners. User Manual Issue Date: 12/2017 r1.9 EN Order Codes: FJ-RC-MBS-1: Modbus RTU Interface for Fujitsu air conditioners

More information

PLXRMM1605. Wall Mounted. FT-A Series. COOLING ONLY [50Hz] V

PLXRMM1605. Wall Mounted. FT-A Series. COOLING ONLY [50Hz] V PLXRMM1605 Wall Mounted FT-A Series COOLING ONLY [50Hz] 220-240V COMFORT 1 Daikin s FT-A series A simple, stylish and sleek wall mounted air conditioner that blends into any environment, providing the

More information

MCFCW-06-4HS-1 (4-Pipe) High Static Chilled/Hot Water Ceiling Concealed Cased Fan Coil 208/230V 4-Pipe Heating & Cooling Fan Coil 18,000 BTUH

MCFCW-06-4HS-1 (4-Pipe) High Static Chilled/Hot Water Ceiling Concealed Cased Fan Coil 208/230V 4-Pipe Heating & Cooling Fan Coil 18,000 BTUH MCFCW-06-4HS-1 (4-Pipe) High Static Chilled/Hot Water Ceiling Concealed Cased Fan Coil 208/230V 4-Pipe Heating & Cooling Fan Coil 18,000 BTUH 1 Chilled and Hot Water Fan Coil High Static 4-Pipe Nominal

More information

Single phase. Technical Support Division

Single phase. Technical Support Division Single phase Technical Support Division 2014.12 CMV MINI VRF System - Control System 1 1. Outdoor Unit and Indoor Unit PCB 2. Communication System 3. Controllers 2 CMV MINI VRF System - Control System

More information

Non-communicating room controllers

Non-communicating room controllers 3 882 DESIGO RXA Non-communicating room controllers RXA29.1 For fan-coil systems The RXA29.1 room controller are used for temperature control in individual rooms. For 2-pipe or 4-pipe fan-coil systems,

More information

VRF Technical Data Book

VRF Technical Data Book VRF Technical Data Book Wind-Free 4Way Cassette for North America (R4A, HP) Model : AM***NN4DCH/** History Version Modification Date Remark Ver.1. Released VRF Wind-Free 4Way Cassette for north America

More information

Super Digital Inverter / RAV Series 2010 Technical training

Super Digital Inverter / RAV Series 2010 Technical training Super Digital Inverter / RAV Series 2010 Technical training 1 PRESENTATION CONTENT Features Operation Safeties 2 FEATURES CONTENT System Line up & Model Numbers System Performance Operating envelope Electrical

More information

TECHNICAL MANUAL (CONTROLS) Models. Lossnay Unit. Lossnay Remote Controller LGH-150RX3-E LGH-25RX3-E LGH-35RX3-E LGH-50RX3-E LGH-80RX3-E LGH-100RX3-E

TECHNICAL MANUAL (CONTROLS) Models. Lossnay Unit. Lossnay Remote Controller LGH-150RX3-E LGH-25RX3-E LGH-35RX3-E LGH-50RX3-E LGH-80RX3-E LGH-100RX3-E TECHNICAL MANUAL (CONTROLS) Models Unit LGH-15RX3-E LGH-25RX3-E LGH-35RX3-E LGH-50RX3-E LGH-80RX3-E LGH-100RX3-E LGH-150RX3-E LGH-200RX3-E Remote Controller PZ-41SLB-E PZ-52SF-E CONTENTS 1. Summary...............................................................................

More information

Air Conditioning Technical Data FVA-A > FVA71AMVEB > FVA100AMVEB > FVA125AMVEB > FVA140AMVEB

Air Conditioning Technical Data FVA-A > FVA71AMVEB > FVA100AMVEB > FVA125AMVEB > FVA140AMVEB Air Conditioning Technical Data FVA-A > FVA71AMVEB > FVA0AMVEB > FVA1AMVEB > FVA1AMVEB Indoor Unit FVA-A TABLE OF CONTENTS FVA-A 1 Features.............................................................

More information

Millenium II +: general characteristics

Millenium II +: general characteristics Millenium II +: general characteristics Starter kit Blind Temperature sensors Special starter kits Bare board Power supply Level detection Local extensions Accessories Standard Expandable Adjacent extensions

More information

Non-communicating room controllers

Non-communicating room controllers 3 881 DESIO RXA on-communicating room controllers For fan-coil systems RXA20.1 RXA21.1 RXA22.1 The RXA20.1, RXA21.1 and RXA22.1 room controllers are used for temperature control in individual rooms. For

More information

VRF. Technical Data Book. DVM S Eco 8, 9 HP

VRF. Technical Data Book. DVM S Eco 8, 9 HP VRF Technical Data Book DVM S Eco 8, 9 HP Version Modification Date Remark Ver.1.0 Released DVM S Eco 8,9HP TDB.06.26 Ver.1.1 Max pipe length modified(equivalent length) : 0 -> 130m 15.04.07 Nomenclature

More information

1:1 Model Connection Interface

1:1 Model Connection Interface Air Conditioner Installation Manual 1:1 Model Connection Interface Model name: TCB-PCNT31TLUL Installation Manual Digital Inverter Air Conditioner 1 English Manuel d installation Climatiseur inverseur

More information

Installation Instructions

Installation Instructions 50ES, 50EZ, 50GL, 50GS, 50GX, 50JS, 50JX, 50JZ, 50SD, 50SZ, 50VL, 50VT, 50XP, 50XZ 601A, 602A, 602B, 604A, 604B, 604D, 607C, 701A, 702A, 702B, 704A, 704B, 704D, 707C PA1P, PA2P, PA3P, PH1P, PH2P, PH3P

More information

Mitsubishi Electric Air-conditioner Network System

Mitsubishi Electric Air-conditioner Network System Mitsubishi Electric Air-conditioner Network System Central Controller Model: GB-50A Installation Manual Contents 1. Safety Precautions to be Observed without Fail...1 2. Confirmation of Parts...3 3. Product

More information

RTD-NET Installation Instructions

RTD-NET Installation Instructions LED3 SW1 LED4 RTD-NET Installation Instructions 0V +V POWER 15-24VDC English RTD-NET Installation Instructions 100.00 RTD-NET Control Interface realtime Control Systems REMC P1 P2 RS485 D-BUS DB DA GND

More information

HITACHI. EH-150 series PLC EH-RTD8 Resistance Temperature Detective input module Instruction manual. Safety precautions

HITACHI. EH-150 series PLC EH-RTD8 Resistance Temperature Detective input module Instruction manual. Safety precautions HITACHI EH-150 series PLC Resistance Temperature Detective input module Instruction manual Thank you for purchasing a Hitachi Programmable Logic Controller. To operate it safely, please read this instruction

More information

4-step Chiller and Heat Pump Controller

4-step Chiller and Heat Pump Controller 4-step Chiller and Heat Pump Controller Technical Data Sheet GENERAL DESCRIPTION MODELS CODE MODEL DESCRIPTION MW324000 ECH 420 HEAT PUMP WITH 4 STEPS/ 2 CIRCUITS + MODBUS MW324005 ECH 420/V WITH SCREW

More information

IntesisBox PA-AC-MBS-1

IntesisBox PA-AC-MBS-1 IntesisBox PA-AC-MBS-1 v.2.3 Modbus RTU (EIA-485) Interface for Panasonic air conditioners. Compatible with Etherea line air conditioners commercialized by Panasonic. User s Manual Issue Date: 11/2017

More information

Pocket Quick Reference Guide On the TOSHIBA

Pocket Quick Reference Guide On the TOSHIBA Pocket Quick Reference Guide On the TOSHIBA RBC-AMS51E / RBC-AMS54E Remote Controller Quick Reference Guide To assist service engineers working on Toshiba air conditioning equipment, there is a large quantity

More information

INSTALLATION INSTRUCTIONS

INSTALLATION INSTRUCTIONS INSTALLATION INSTRUCTIONS Adaptor Model No. CZ-CFUNC1U For your safety Read the following instructions carefully, and carry out secure installation and electrical work. The precautions given in this manual

More information

TPE, TPED Series 2000

TPE, TPED Series 2000 GRUNDFOS INSTRUCTIONS TPE, TPED Series 2000 Installation and operating instructions English (GB) English (GB) Installation and operating instructions Original installation and operating instructions. CONTENTS

More information

Temperature controller Ducted systems

Temperature controller Ducted systems 2 725 Temperature controller Ducted systems Standard model without zoning functions RRV851 Multifunctional controller used for central control of ducted HVAC systems in combination with a QAX850 master

More information

Modbus RTU/TCP GOLD RX/PX/CX/SD, GENERATION C/D Applicable to program version 1.05 and newer versions

Modbus RTU/TCP GOLD RX/PX/CX/SD, GENERATION C/D Applicable to program version 1.05 and newer versions Modbus RTU/TCP GOLD RX/PX/CX/SD, GENERATION C/D Applicable to program version 1.05 and newer versions Overview ModBus can access single addresses or multiple addresses simultaneously; either reading or

More information

HIGH EFFICIENCY 15 and 17 SEER TWO STAGE HEAT PUMP ENVIRONMENTALLY SOUND R 410A REFRIGERANT. Min. Circuit Ampacity

HIGH EFFICIENCY 15 and 17 SEER TWO STAGE HEAT PUMP ENVIRONMENTALLY SOUND R 410A REFRIGERANT. Min. Circuit Ampacity ENVIRONMENTALLY SOUND REFRIGERANT C4H(5, 7) Product Specifications HIGH EFFICIENCY 15 and 17 TWO STAGE HEAT PUMP ENVIRONMENTALLY SOUND R 410A REFRIGERANT 2, 3, 4, and 5 TONS SPLIT SYSTEM 208 / 230 Volt,

More information

Ostar Eye K6. Beam and Kaleido Effects. User manual. Please read the instructions carefully before use

Ostar Eye K6. Beam and Kaleido Effects. User manual. Please read the instructions carefully before use Ostar Eye K6 Beam and Kaleido Effects User manual Please read the instructions carefully before use TABLE OF CONTENTS 1. Safety Instructions... 2 2. Technical Specifications... 4 3. How To Control The

More information

Owner s Manual RBC-AX32U(W)-E RBC-AX32U(WS)-E AIR CONDITIONER (SPLIT TYPE) Wireless remote controller kit. Model name: English.

Owner s Manual RBC-AX32U(W)-E RBC-AX32U(WS)-E AIR CONDITIONER (SPLIT TYPE) Wireless remote controller kit. Model name: English. AIR CDITIER (SPLIT TYPE) Owner s Manual Wireless remote controller kit Model name: RBC-AX3U(W)-E RBC-AX3U(WS)-E Generic model name RBC-AX3U(W)-E Wireless remote controller model name WH-LSE Signal receiving

More information

SAMURAI SCAN 50 LED-SC50D. User Guide. Innovation, Quality, Performance. Professional Entertainment Technology 19-

SAMURAI SCAN 50 LED-SC50D. User Guide. Innovation, Quality, Performance. Professional Entertainment Technology 19- SAMURAI SCAN 50 LED-SC50D Innovation, Quality, Performance User Guide Professional Entertainment Technology 19- EC Declaration of Conformity We declare that our products (lighting equipments) comply with

More information

Features. Line Regulation. Load Regulation. Safety. Cooling. Input Connectors. Output Connectors. Overvoltage Protection. Over Temperature Protection

Features. Line Regulation. Load Regulation. Safety. Cooling. Input Connectors. Output Connectors. Overvoltage Protection. Over Temperature Protection Specifications: Input Voltage ( 3 phase ) No of Phases Input Frequency 208VAC ( 170 ~ 265 ) Code: 3P208 415VAC ( 342 ~ 460 ) Code: 3P400 Wye or Delta, 4 wire 3phase and one protective earth. 47 ~ 63Hz

More information

DUCTED SPLIT SYSTEMS With Scroll compressors

DUCTED SPLIT SYSTEMS With Scroll compressors DUCTED SPLIT SYSTEMS With Scroll compressors 2 Benefits TOTAL COMFORT ON WIDE AREAS The Ducted Blower Split Systems for light commercial applications of DXDXT-M/K series are the ideal solution for keeping

More information

RTD-W Installation Instructions

RTD-W Installation Instructions RTD-W Installation Instructions 0V +V POWER 15-24VDC 0V S1 S2 S3 0V S4 S5 S6 English RTD-W Installation Instructions 100.00 RTD-W Control Interface realtime Control Systems 24VAC/30VDC, 1A REMC P1 P2 RS485

More information

Professional Entertainment Technology. imove 50SR. Innovation, Quality, Performance 21-

Professional Entertainment Technology. imove 50SR. Innovation, Quality, Performance 21- Innovation, Quality, Performance 21- imove 50SR User Guide Professional Entertainment Technology EC Declaration of Conformity We declare that our products (lighting equipments) comply with the following

More information

CHILLED WATER. HIGH PRECISION AIR CONDITIONERS, FROM 7 TO 211 kw

CHILLED WATER. HIGH PRECISION AIR CONDITIONERS, FROM 7 TO 211 kw IT COOLING CLOSE CONTROL AIR CONDITIONERS CHILLED WATER HIGH PRECISION AIR CONDITIONERS, FROM 7 TO 211 kw 3 Versions available Single chilled water coil Double chilled water coil High temperature IT COOLING

More information

Modbus RTU (EIA-485) Interface for Panasonic and Sanyo air conditioners. Compatible with ECOi and PACi line models.

Modbus RTU (EIA-485) Interface for Panasonic and Sanyo air conditioners. Compatible with ECOi and PACi line models. IntesisBox PA-RC2-MBS-1 v.2.3 Modbus RTU (EIA-485) Interface for Panasonic and Sanyo air conditioners. Compatible with ECOi and PACi line models. User Manual Issue Date: 11/2017 r2.3 EN Order Codes: PA-RC2-MBS-1:

More information

INDOOR UNIT CONTROLLER (IUC) Operation Manual

INDOOR UNIT CONTROLLER (IUC) Operation Manual INDOOR UNIT CONTROLLER (IUC) Operation Manual Date: 9 June 2015 Issue: 4 Note: Information in this document applies to IUC controllers programmed with software version 1.5. Page 1 of 11 Contents 1. Introduction...

More information

RS-485 FClink Networking Room Thermostats with LCD for Fan Coil Units

RS-485 FClink Networking Room Thermostats with LCD for Fan Coil Units NT10 Series Revision Date April 16, 2014 RS-485 FClink Networking Room Thermostats with LCD for Fan Coil Units Features Ultra slim wall-mount unit to match any decor Supports standalone operation on RS

More information

R1M-GH BEFORE USE... POINTS OF CAUTION INSTRUCTION MANUAL PC RECORDER MODEL. (thermocouple or DC input, 16 points)

R1M-GH BEFORE USE... POINTS OF CAUTION INSTRUCTION MANUAL PC RECORDER MODEL. (thermocouple or DC input, 16 points) INSTRUCTION MANUAL PC RECORDER (thermocouple or DC input, points) MODEL RM-GH BEFORE USE... Thank you for choosing M-System. Before use, please check contents of the package you received as outlined below.

More information

OPERATION INSTRUCTIONS

OPERATION INSTRUCTIONS 2018 Lennox Industries Inc. Dallas, Texas, USA OPERATION INSTRUCTIONS V0STAT52 Wireless Indoor Unit Controller CONTROLS 507459-04 05/2018 This manual must be left with the owner for future reference. IMPORTANT

More information

DESIGO RX Individual room controllers. for fan-coil systems, chilled ceilings and radiators, with LONMARK-compatible bus communications

DESIGO RX Individual room controllers. for fan-coil systems, chilled ceilings and radiators, with LONMARK-compatible bus communications 3 834 DESIO RX Individual room controllers for fan-coil systems, chilled ceilings and radiators, with MARK-compatible bus communications RXC20.1 RXC21.1 The RXC20.1 and RXC21.1 controllers are used for

More information

Ostar Eye K18. Beam and Kaleido Effects. User manual. 6. Fixture Cleaning. Please read the instructions carefully before use

Ostar Eye K18. Beam and Kaleido Effects. User manual. 6. Fixture Cleaning. Please read the instructions carefully before use 6. Fixture Cleaning The cleaning of internal and external optical lenses and/or mirrors must be carried out periodically to optimize light output. Cleaning frequency depends on the Ostar Eye K18 Beam and

More information

Hyamaster r SPS. Intelligent single and multiple pump control system with continuous speed control by frequency inverter, with PLC SIMATIC r S7

Hyamaster r SPS. Intelligent single and multiple pump control system with continuous speed control by frequency inverter, with PLC SIMATIC r S7 Type Series Booklet 1964.5/2-10 Hyamaster r SPS Intelligent single and multiple pump control system with continuous speed control by frequency inverter, with PLC SIMATIC r S7 Fields of Application Industry:

More information

R1M-GH BEFORE USE... POINTS OF CAUTION INSTRUCTION MANUAL PC RECORDER MODEL. (thermocouple or DC input, 16 points)

R1M-GH BEFORE USE... POINTS OF CAUTION INSTRUCTION MANUAL PC RECORDER MODEL. (thermocouple or DC input, 16 points) INSTRUCTION MANUAL PC RECORDER (thermocouple or DC input, points) MODEL BEFORE USE... Thank you for choosing M-System. Before use, please check contents of the package you received as outlined below. If

More information

300 WATT, PFC, OPEN FRAME POWER SUPPLIES TABLE 1. OUTPUT RATINGS AND SPECIFICATIONS, RMW 300W SERIES

300 WATT, PFC, OPEN FRAME POWER SUPPLIES TABLE 1. OUTPUT RATINGS AND SPECIFICATIONS, RMW 300W SERIES INSTRUCTION MANUAL KEPCO An ISO 9001 Company. 300 WATT, PFC, OPEN FRAME POWER SUPPLIES RMW 300W SERIES I INTRODUCTION SCOPE OF MANUAL. This instruction manual covers the installation and operation of the

More information

RTD-RA. realtime. Installation Instructions. English A B. Installation Instructions Control Systems LEDS ALL DIMENSIONS IN MM

RTD-RA. realtime. Installation Instructions. English A B. Installation Instructions Control Systems LEDS ALL DIMENSIONS IN MM RTD-RA Installation Instructions 37.50 LEDS 4 3 2 1 D English Installation Instructions 80.00 80.00 ALL DIMENSIS IN MM C realtime Control Systems A B LEDS 4 3 2 1 D S21 J3 J6 1 2 3 4 J5 5 6 7 0V S1 0V

More information

SINGLE. Technical Data Book Zone Control Systems

SINGLE. Technical Data Book Zone Control Systems SINGLE Technical Data Book Zone Control Systems Zone control system 2 I. Zone control system 1 Zone controller & remote temperature sensor 1. MWRZS00 / MWRZS10 / MRWTS 1) Features.... 4 2) Product specification...

More information

STRA-17 Room controller. Installation and maintenance manual. Content

STRA-17 Room controller. Installation and maintenance manual. Content Content Installation preparations... Wiring diagram...3 Display handling...5 Technical data...6 Configuration...7 Operating modes...7 Controller modes...7 Activation operating modes...7 Control states...8

More information

METASYS N2 open GOLD RX/PX/CX/SD, GENERATION C/D Applicable to program version 1.05 and newer versions

METASYS N2 open GOLD RX/PX/CX/SD, GENERATION C/D Applicable to program version 1.05 and newer versions METASYS N2 open GOLD RX/PX/CX/SD, GENERATION C/D Applicable to program version 1.05 and newer versions Metasys N2 open Metasys nodes contains up to 256 Virtual Objects. These virtual objects can be either

More information

Supplementary operating instructions for your air curtain system Controller TMC 500

Supplementary operating instructions for your air curtain system Controller TMC 500 Supplementary operating instructions for your air curtain system Controller TMC 500 (Translation of the original) Serial number: Year: Please quote this number when contacting customer service! Date 08.04.2016

More information

FEATURES AND BENEFITS. Installation and operation. Controller

FEATURES AND BENEFITS. Installation and operation. Controller DFC 350 & 450 DISPLACEMENT FREE COOLING Function The Dantherm Displacement Free Cooling (DFC) unit is a slim, passive cooling solution designed to remove excess heat from rooms with sensitive equipment.

More information

ERV Control Interface Installation / Operation manual. TCB-IFVN1UL ERV Control Interface ENGLISH

ERV Control Interface Installation / Operation manual. TCB-IFVN1UL ERV Control Interface ENGLISH ERV Control Interface Installation / Operation manual Model name: For Commercial Use TCB-IFVN1UL ERV Control Interface ENGLISH Thank you for purchasing TOSHIBA / Carrier ERV Control Interface. This manual

More information

HPS-M -2 DIFFERENTIAL PRESSURE TRANSMITTER. Mounting and operating instructions

HPS-M -2 DIFFERENTIAL PRESSURE TRANSMITTER. Mounting and operating instructions DIFFERENTIAL PRESSURE Mounting and operating instructions Table of contents SAFETY AND PRECAUTIONS 3 PRODUCT DESCRIPTION 4 ARTICLE CODES 4 INTENDED AREA OF USE 4 TECHNICAL DATA 4 STANDARDS 5 OPERATIONAL

More information

RS-485 Modbus RTU Networking Room Thermostats with LCD for Fan Coil Units

RS-485 Modbus RTU Networking Room Thermostats with LCD for Fan Coil Units NT10 Series Issue Date February 21, 2016 RS-485 Modbus RTU Networking Room Thermostats with LCD for Fan Coil Units Features Ultra slim wall-mount unit to match any decor Supports standalone operation on

More information

REMOTE CONTROLLER (WIRED TYPE) INSTALLATION MANUAL. For authorized service personnel only. PART No

REMOTE CONTROLLER (WIRED TYPE) INSTALLATION MANUAL. For authorized service personnel only. PART No REMOTE CONTROLLER (WIRED TYPE) INSTALLATION MANUAL For authorized service personnel only. PART No. 938007-0 INSTALLATION MANUAL PART No. 938007-0 REMOTE CONTROLLER (WIRED TYPE) Contents. SAFETY PRES....

More information

NT50 Series RS485 Modbus RTU Networking LCD Fan Coil Thermostat

NT50 Series RS485 Modbus RTU Networking LCD Fan Coil Thermostat NT50 Series RS485 Modbus RTU Networking LCD Fan Coil Thermostat Features Modern Appearance Stylish rotary dial and buttons Large LCD with backlight Support Modbus RTU protocol Support standalone operation

More information

RCF-230CD. Communicating room thermostat for fan-coil applications with on/off outputs

RCF-230CD. Communicating room thermostat for fan-coil applications with on/off outputs revision 11 2013 RCF-230CD Communicating room thermostat for fan-coil applications with on/off outputs RCF-230CD intended to control heating and/or cooling in 2- or 4-pipe installations. Setpoint and fan

More information

RCF-230CAD. Room controller with communication for fancoil applications with two analogue V DC outputs

RCF-230CAD. Room controller with communication for fancoil applications with two analogue V DC outputs revision 04 2016 RCF-230CAD Room controller with communication for fancoil applications with two analogue 0...10 V DC outputs Intended to control heating and/or cooling in 2- or 4-pipe installations. Setpoint

More information

FPS SERIES Super Slim Ceiling Mount Air Handling Units

FPS SERIES Super Slim Ceiling Mount Air Handling Units About Multistack 19, Multistack is well-known in the international air conditioning industry by its invention of modular chiller. Today, Multistack has grown into an international refrigeration & air conditioning

More information

OPERATING INSTRUCTIONS PA AMPLIFIER P-1812

OPERATING INSTRUCTIONS PA AMPLIFIER P-1812 OPERATING INSTRUCTIONS PA AMPLIFIER P-1812 Please follow the instructions in this manual to obtain the optimum results from this unit. We also recommend that you keep this manual handy for future reference.

More information

CTXA-AS/AT/AW, FTXA-AS/AT/AW

CTXA-AS/AT/AW, FTXA-AS/AT/AW Split Air Conditioning Technical Data CTXA-AS/AT/AW, FTXA-AS/AT/AW > CTXAA2V1BS > CTXAA2V1BT > CTXAA2V1BW > FTXAA2V1BS > FTXAA2V1BT > FTXAA2V1BW > FTXAA2V1BS > FTXAA2V1BT > FTXAA2V1BW > FTXAA2V1BS > FTXAA2V1BT

More information

IntesisBox. v.1.3. User Manual Issue Date: 04/2016. IntesisBox PA-RC2-MBS-4

IntesisBox. v.1.3. User Manual Issue Date: 04/2016. IntesisBox PA-RC2-MBS-4 IntesisBox PA-RC2-MBS-4 v.1.3 MODBUS RTU (EIA485) Interface for Panasonic and Sanyo air conditioners. Compatible with ECOi and PACi line models. User Manual Issue Date: 04/2016 Order Codes: PA-RC2-MBS-4

More information

UTY-RVNUM. INSTALLATION MANUAL For authorized service personnel only. MANUEL D'INSTALLATION Pour le personnel agréé uniquement.

UTY-RVNUM. INSTALLATION MANUAL For authorized service personnel only. MANUEL D'INSTALLATION Pour le personnel agréé uniquement. REMOTE CONTROLLER (WIRED TYPE) INSTALLATION MANUAL For authorized service personnel only. English UTY-RVNUM MANUEL D'INSTALLATION Pour le personnel agréé uniquement. Français MANUAL DE INSTALACIÓN Sólo

More information

Switching Power Supply

Switching Power Supply Switching Power Supply Highly Reliable and Full-functioned 1-year Life Expectancy, 12, 1, or 24 V output voltages, and 30, 60, 0, or 10 W power ratings. 8 to 132 VAC or 170 to 264 VAC switchable input

More information

User's manual. GREE AHU kit. Type: U-Match Version: 1.02

User's manual. GREE AHU kit. Type: U-Match Version: 1.02 User's manual GREE AHU kit Type: U-Match Version: 1.02 Thank you for choosing AHU com, please read this user's manual carefully before operation and keep it for further reference. If you have lost the

More information

IntesisBox TO-RC-MBS-1

IntesisBox TO-RC-MBS-1 IntesisBox TO-RC-MBS-1 v.1.5 MODBUS RTU (EIA485) Interface for Toshiba air conditioners from the Digital Inverter & VRF lines. User Manual Issue Date: 01/2014 Order Codes: TO-RC-MBS-1 Intesis Software

More information

Quick Start Installation and User Manual

Quick Start Installation and User Manual 1 Quick Start Installation and User Manual Contents 1. Overview 2. Technical Specifications 3. Installation Mounting Electrical Installation Clamp Installation Wiring Diagrams 4. Installation Settings

More information

technical data Systems Individual control systems

technical data Systems Individual control systems technical data Systems Individual control systems Individual control systems 17 1 Possible individual control systems...2 2 BRC2A51 - Simplified remote control Explanation of buttons and functions... 3

More information

Features. Conducted Emission. Radiated Emission. Line Regulation. Load Regulation. Safety. Cooling. Input Connectors.

Features. Conducted Emission. Radiated Emission. Line Regulation. Load Regulation. Safety. Cooling. Input Connectors. Specifications: Input Voltage ( 1 phase ) ( 3 phase ) No of Phases Input Frequency 230VAC ( 170 ~ 265 ) Code: 1P200 208VAC ( 170 ~ 265 ) Code: 3P208 415VAC ( 342 ~ 460 ) Code: 3P400 1phase or 3phase Wye

More information

Product Brochure DENCO Close Control Units Row-DENCO. High Density Cooling for Data Centres

Product Brochure DENCO Close Control Units Row-DENCO. High Density Cooling for Data Centres Product Brochure DENCO Close Control Units Row-DENCO High Density Cooling for Data Centres Data Centre Cooling Through a history in close control, we have developed a broad and deep understanding of how

More information

Pocket Quick. Reference Guide. On the TOSHIBA RBC-AMS51E. Remote Controller

Pocket Quick. Reference Guide. On the TOSHIBA RBC-AMS51E. Remote Controller Pocket Quick Reference Guide On the TOSHIBA RBC-AMS51E Remote Controller Quick Reference Guide To assist service engineers working on Toshiba air conditioning equipment, there is a large quantity of data

More information

RCF-230CTD. Room controller for fan-coil applications with outputs for two thermal or one 3-position actuator or function for an electric heater

RCF-230CTD. Room controller for fan-coil applications with outputs for two thermal or one 3-position actuator or function for an electric heater revision 03 2012 RCF-230CTD Room controller for fan-coil applications with outputs for two thermal or one 3-position actuator or function for an electric heater RCF-230CTD is a room controller intended

More information

Features. Conducted. Emission. Line Regulation. Load Regulation. Safety. Cooling. Input Connectors. Overvoltage Protection. Phase Loss.

Features. Conducted. Emission. Line Regulation. Load Regulation. Safety. Cooling. Input Connectors. Overvoltage Protection. Phase Loss. Features Specifications: High Power Density 3.3KW in 2U 1 phase 240vac input 3 phase input 208VAC / 415VAC options Power Factor Correction Output voltage up to 600V, current up to 400A Built-in RS232 /

More information

Suitable for detecting transparent films or transparent bottles

Suitable for detecting transparent films or transparent bottles Ultrasonic Sensor Suitable for detecting transparent films or transparent bottles Reliable detection of transparent objects The sensor reliably detects transparent films or transparent objects. Only 16

More information

PLC-24V10AL(-PT/-TH) Quick Start Manual (Rev.1.10)

PLC-24V10AL(-PT/-TH) Quick Start Manual (Rev.1.10) TEC (Peltier) Controller PLC-24V10AL(-PT/-TH) Quick Start Manual (Rev.1.10) Thank you for purchasing the TEC (Peltier) Controller PLC-24V10AL. Read these operating instructions carefully to ensure effective

More information

NIR Moisture Analyzer KB-30

NIR Moisture Analyzer KB-30 NIR Moisture Analyzer KB-30 Operation Manual Safety Precautions FPL950701 Improper use of the NIR moisture analyzer in violation of the following safety notes may result in death, injury or damage to property

More information

TOP - 1. Instruction Manual. Version 1.0 Produced in Jan. 2004

TOP - 1. Instruction Manual. Version 1.0 Produced in Jan. 2004 Version 1.0 Produced in Jan. 2004 Instruction Manual LCD monitor IV-08MP Thank you for purchasing the SHARP IV-08MP LCD monitor. Read this introductory instruction manual carefully to thoroughly familiarize

More information

Chiller. CG 010 to 130. Remote Air Cooled Condensers Engineering Data Manual. 9.4 to 131 kw

Chiller. CG 010 to 130. Remote Air Cooled Condensers Engineering Data Manual. 9.4 to 131 kw Chiller CG 010 to 130 Remote Air Cooled Condensers Engineering Data Manual 9.4 to 131 kw Specifications Unit identification CG. O. O55. FSC. R407C LN Configuration Refrigerant rpm fans Size Air flow Remote

More information

HCS-3600 / 3602 / 3604 Laboratory Grade & High RFI Immunity Switching Mode Power Supply with Rotary Encoder Control

HCS-3600 / 3602 / 3604 Laboratory Grade & High RFI Immunity Switching Mode Power Supply with Rotary Encoder Control HCS-3600 / 3602 / 3604 Laboratory Grade & High RFI Immunity Switching Mode Power Supply with Rotary Encoder Control 1. INTRODUCTION User Manual This family of efficient, upgraded SMPS with small form factor,

More information

WIRED REMOTE CONTROLLER

WIRED REMOTE CONTROLLER WIRED REMOTE CONTROLLER INSTALLER REFERENCE GUIDE Be sure to read these installation instructions before conducting the installation of this product. Contents Contents 1. Safety Precautions... 2 2. Accessories...

More information

Lossnay Energy Recovery Ventilator

Lossnay Energy Recovery Ventilator Energy Recovery Ventilator MODELS: LGH-5RVX-E, LGH-5RVX-E, LGH-35RVX-E LGH-5RVX-E, LGH-65RVX-E, LGH-8RVX-E LGH-RVX-E, LGH-5RVX-E, LGH-RVX-E Installation Instructions (For use by dealer/contractor) English

More information

The PanasonicVRF Driver

The PanasonicVRF Driver The PanasonicVRF Driver The PanasonicVRF driver interfaces to a Panasonic or Sanyo variable refrigerant flow (VRF) air conditioning system. Compatible VRF systems include Panasonic ECOi, ECO G, and Sanyo

More information