SIL-A. Overcurrent and Earth Fault Relay for Primary and Secondary Distribution. Main characteristics
|
|
- Albert Oswald Douglas
- 5 years ago
- Views:
Transcription
1 SIL-A Overcurrent and Earth Fault Relay for Primary and Secondary Distribution Main characteristics The SIL-A is an overcurrent and earth fault protection relay for primary and secondary distribution with power supply Vdc/ 4-23 Vac. The current measurement is obtained either by standard Many protection functions: (Zone Selection Interlocking) To allow the relays have a communication port on the front of the equipment and
2 5 Oscillographic records, 2 fault reports and 2 events saved in non-volatile RAM memory with date/time, even without power supply, thanks to its internal RT (Real Time lock). Additional information to fault reports Technical specifications SIL-A Functions diagram SIL-A 52 5_1 5_2* 5/51 49* SHB* Hmi LD 2x2 7 keys+i/52+b79 RT (1 ms) LP 5BF* TB* 46 DFR 5 N/G_1 (1) 5 N/G_2* (1) 5/51 N/G Setting groups LDP 37* 74T* 46B* * optional 79 49T* 52 6* 74TS* 6* PG Test Out configurable Input configurable * available through programmable logic control (PG) tº IE * Modbus TP/IP* DNP3. TP/IP* IE 615* ModBus RTU* IE * ModBus RTU* DNP3. Serial* Leds configurable ModBus RTU. Tx, Rx Ethernet RS45 RS45 RS232 SIom Modem (1) Note:
3 5_1 5_2 5N/G_1(1) 5N/G_2(1) 5/51 5/51N/G(1) Technical specifications Technical parameters SIL-A urrent Tap:.1 to 3 xin (step.1) Time Delay: Adaptation B :.2 to 3 s (step.1 s) Adaptation :. to 3 s (step.1 s) Activation level 1% Deactivation level 95% Timing accuracy (greater of both): urrent Tap: Adaptation B :.1 to 3 xin (step.1) Adaptation :.5 to 3 xin (step.1) Time Delay: Adaptation B :.2 to 3 s (step.1 s) Adaptation :. to 3 s (step.1 s) Activation level 1% Deactivation level 95% Timing accuracy (greater of both): urrent Tap:.1 to 7 xin (step.1) urves IE and IEEE urve type: IE Inverse curve, IE very inverse curve, IE extremely inverse curve, IE long time inverse, IEEE Inverse curve, IEEE very inverse curve, IEEE extremely inverse curve, Defined time. Time delay: Adaptation B :.2 to 3 s (step.1) Adaptation :. to 3 s (step.1) Time Dial (TMS):.2 to 2.2 (step.1) urve, activation level 11% urve, deactivation level 1% Defined time, activation level 1% Defined time, deactivation level 95% Timing accuracy for IE and IEEE curves selection: ±3 ms or ±5% (greater of both). Timing accuracy for DT curve selection (greater of both): urrent Tap: Adaptation B :.1 to 7 xin (step.1) Adaptation :.5 to 7 xin (step.1) urves IE and IEEE urve type: IE Inverse curve, IE very inverse curve, IE extremely inverse curve, IE long time inverse, IEEE Inverse curve, IEEE very inverse curve, IEEE extremely inverse curve, Defined time. Time delay: Adaptation B :.2 to 3 s (step.1) Adaptation :. to 3 s (step.1) Time Dial (TMS):.2 to 2.2 (step.1) urve, activation level 11% urve, deactivation level 1% Defined time, activation level 1% Defined time, deactivation level 95% Timing accuracy for IE and IEEE curves selection: ±3 ms or ±5% (greater of both). Timing accuracy for DT curve selection (greater of both): 46 ircuit Breaker Monitoring 5BF(*) 79 74TS LP (1) Note: and 5/51N. are 5N/G(2) and 5/51N/G. (*) Note: urrent Tap:.1 to 7 xin (step.1) urves IE and IEEE urve type: IE Inverse curve, IE very inverse curve, IE extremely inverse curve IE, long time inverse, IEEE Inverse curve, IEEE very inverse curve, IEEE extremely inverse curve, Defined time. Time delay: Adaptation B :.2 to 3 s (step.1) Adaptation :. to 3 s (step.1) Time Dial (TMS):.2 to 2.2 (step.1) urve, activation level 11% urve, deactivation level 1% Defined time, activation level 1% Defined time, deactivation level 95% Timing accuracy for IE and IEEE curves selection: ±3 ms or ±5% (greater of both). Timing accuracy for DT curve selection (greater of both): Maximum number of openings: 1 to 1. (step 1) Maximum accumulated amps: to 1. (M(A²)) (step 1) Opening time:.2 to 3 s (step.1 s) losing time:.2 to 3 s (step.1 s) Excessive repeated openings: 1 to 1. (step 1) Repetitive openings/time: 1 to 3 min (step 1 min) Open circuit breaker activation threshold: % In Open circuit breaker reset threshold: 1% In Yes/No Time delay:.2 to 1. s (step.1 s) Open circuit breaker activation threshold: % In Open circuit breaker reset threshold: 1% In onfigurable function pickup Yes/No Hold enable: Yes/No/No time Number of reclosings: 1 to 5 Reclosing time 1, 2, 3, 4, 5 :.2 to 3 s (step.1 s) Hold time:.2 to 3 s (step.1 s) Reset time:,2 to 3 s (step,1 s) Safe time:.2 to 3 s (step.1 s) Locking possibilities: pulse inputs, level inputs, commands. Yes/No Time delay:.2 to 3 s (step.1 s) ontinuity in circuits A and B Inputs Adaptation B : onfigurable Digital Inputs Adaptation : Dedicated Digital Inputs Yes/No Settings groups: 1 to 4 (step 1) No load Time:.2 to 3 s (step.1 s) old load Time:.2 to 3 s (step.1 s) LP activation threshold: % In LP reset threshold: 1% In
4 Technical parameters SIL-A PG 6 49T OR4, OR4_LATH, OR4_PULSES, OR4_TIMERUP, OR4_ PULSE, NOR4, NOR4_LATH, NOR4_TIMERUP, NOR4_ PULSE, AND4, AND4_PULSES, AND4_TIMERUP, AND4_ PULSE, NAND4, NAND4_TIMERUP, NAND4_PULSE Allows to latch (lock out) the contact trip due to programmable logic (PG: LATH). Available through configurable inputs thanks to the programmable logic Yes/No urrent Tap:.1 to 2.4 xin (step.1) heating: 3 to 6 min (step 1 min) Load Data Profiling (LDP) Demand of current with the following characteristics: Sampling rate (interval): configurable through communications (1 6 min) Date/Time IMAX (in interval) IMAX (actual) IA IB I IN cooling: 1 to 6 heating (step 1) Same voltage as the auxiliary power supply 49(*) Alarm: 2 to 99 % (step 1%) Trip level: 1% Deactivation level: 95% of alarm level inputs 25 Vac A 3 Vdc 5 A Trip time accuracy: ± 5% over the theoretical value Outputs 4 configurable outputs Trip time curves are valid under 2 times the adjusted tap. With currents higher than 2 times the adjusted tap, trip time and thermal image value are truncated to 2 times the adjusted tap. Frequency 5/6 Hz selectable by general settings 74T(*) 37(*) 46B(*) SHB(*) TB(*) 6 Settings groups RT Events Disturbance Fault Recording (DFR) (1) Note: and 5/51N. Yes/No Time delay:.2 to 3 s (step.1 s) Timing accuracy: ±3 ms or ±.5% (greater of both) Function enable : Yes/No urrent Tap:.1 to 3 xin (step.1) Time delay:.2 to 3 s (step.1 s) Activation level: 1% Deactivation level: 15% Instantaneous reset Timing accuracy: ±3 ms or ±.5% (greater of both) Yes/No urrent Tap: 15 to 1% (step 1%) Time delay:. to 3 s (step.1 s) Timing accuracy (greater of both): If Time Delay, to,2 s, ±5 ms or ±.5% If Time Delay,2 to 3 s, ±3 ms or ±.5% Yes/No urrent Tap: 5 to 5% (step 1%) Reset time:. to 3 s (step.1 s) Block threshold:.1 to 3 x In (step.1) Yes/No urrent Tap: 1.5 to 2 x In (step.1) Available through configurable inputs and outputs thanks to programmable logic 4 settings groups Activated by inputs or by general settings. apacitor charge time: 1 minutes Operation with no auxiliary voltage: 72 hours 2 events 16 samples/cycle Fault start configurable 2 fault reports with 24 events each one 5 OMTRADE rec. (1 cycles): 3 pre postfault cycles OMTRADE IEEE analog channels and 4/35 digital channels (adapt. B/ ) urrent measurement ommunications Phase current (IA, IB, I), neutral (IN), positive sequence (I1), negative sequence(i2), maximum current (Imax) and thermal image (TI) Phase current (IA, IB, I), neutral (IN), positive sequence (I1), negative sequence(i2), phase second harmonic current (IA-2H, IB-2H and I-2H), maximum current (Imax) and thermal image (TI) Fundamental values (DFT) Sampling: 16 samples/cycle ±2% Accuracy over a band of ±2% over the nominal current and 4% over the rest of the range ±2% Accuracy over a band of ±2% over the nominal current and 4% or ±5 ma (greater of both) over the rest of the range Saturation limit: 3 times rated current LOAL OMMUNIATION 1 Local port RS232: ModBus RTU REMOTE OMMUNIATION (*) 1 remote port with the following options : 1 Remote port RS45: ModBus RTU, IE or DNP3. Serial (by model/settings) 1 Remote port RJ45: IE 615, DNP3. TP/IP, Modbus TP/IP or IE (by model/ settings) Auxiliary power Vac/dc (-2% / +1%) Operating temperature : -1 to 7º Environmental Storage temperature: -2 to º conditions Relative humidity: 95% Measurement 3 or 4 T /1 or /5 Transformers Measurement 3 LPT (current transformers with voltage output) Metallic box Panel mounted. Mechanical Height x Width: 177 x 17 mm haracteristics Depth: mm IP-54 on pannel Weight: 1,5 kg. are 5N/G(2) and 5/51N/G. (*) Note:
5 Technical specifications onnections diagram SIL-A 3 LPT Transformers 3 Standard urrent Transformers SILA Overcurrent & Earth Fault relay SILA Overcurrent & Earth Fault relay LPT 4 Standard urrent Transformers SILA Overcurrent & Earth Fault relay
6 onnections diagram SIL-A UTOUT Selection & Ordering data SIL-A SIL-A X S Overcurrent & Earth Fault Protection Relay for Primary & Secondary X S 2 4 A B D A B E PROTETION FUNTIONS 5_1 +5_2 + 5/51 + 5N/G_1 + 5N/G_2 + 5/51N/G BF TS + LP T PHASE MEASUREMENT LPT (Primary = 5 A) Standard: 1 A or 5 A Sensitive:.5 A or 2.5 A NEUTRAL MEASUREMENT LPT (Neutral internally calculated) Standard: 1 A (.1-3 A) or 5 A (.5-15 A) Sensitive:.1 A (.1-3 A) or.5 A (.5-15 A) NET FREQUENY Defined by General Setting POWER SUPPLY Vac/dc ADDITIONAL FUNTIONS T B + Trip Block B + SHB (available only for Adaptation ) REAR OMMUNIATIONS RS232 (Modbus RTU) + RS45 (Modbus RTU or IE ) RS232 (Modbus RTU) + RJ45 (IE 615) RS232 (Modbus RTU) + RJ45 (IE ) RS232 (Modbus RTU) + RS45 (Modbus RTU or DNP3. serial) RS232 (Modbus RTU) + RJ45 (Modbus TP/IP or DNP3. TP/IP) INPUTS-OUTPUTS 6 Inputs + 4 Outputs MEHANIS Vertical assembly LANGUAGE English, Spanish and German English, Spanish and Turkish English, Spanish and French English, Turkish and Russian ADAPTATION B - Without 5_2, 5N/G_2 and 5BF (74TS with dedicated DI) Example of ordering code: SIL A 2 A 1 2 B B SILA 2 A 1 2 B B
SIA-B. Overcurrent & Earth Fault Protection Relay for Secondary Distribution. Dual & Self Powered / Standard CTs. Main characteristics
SIA-B Overcurrent & Earth Fault Protection Relay for Secondary Distribution Dual & Self Powered / Standard CTs Main characteristics The SIA-B is an protection relay with self powered and dual powered (Self-powering
More informationFunction permission: yes/no. Operating range: 0.10 to 30 xin (step 0.01) Operating time: 0.02 to 300 s (step 0.01 s) Activation level 100%
Operating range: 0.10 to 30 xin (step 0.01) 50P(2) Activation level 100% Deactivation level 95% Timer accuracy: 30 ms Operating range: 0.10 to 30 xin (step 0.01) 50N/G(2) Activation level 100% Deactivation
More informationISO 9001:2000 SIL A. Overcurrent and Earth fault relay INSTALLATION GUIDE. Guia_SIL-A_Rev / 48
ISO 9001:2000 SIL A Overcurrent and Earth fault relay INSTALLATION GUIDE www.fanox.com Guia_SIL-A_Rev. 01 1 / 48 1.USER INTERFAE... 4 1.1. onfigurable LEDs... 4 1.2. Local communication port. RS232...
More informationSIA-C. Overcurrent and Earth Fault Protection Relay for Secondary Distribution. Dual & Self Powered. Main characteristics
SI Overcurrent and Earth Fault Protection Relay for Secondary Distribution Dual & Self Powered Main characteristics The SI is a overcurrent protection relay with self powered and dual powered (self auxiliary)
More informationSIA-C. Overcurrent and Earth Fault Protection Relay for Secondary Distribution. Dual & Self Powered. Main characteristics
SIA-C Overcurrent and Earth Fault Protection Relay for Secondary Distribution Dual & Self Powered Main characteristics The SIA-C is a overcurrent protection relay with self powered and dual powered (self
More informationSIA/SIL. Secondary and Primary Distribution Protection Relays. Specialized in self powered relays IEC 61850
Specialized in self powered relays SIA/SIL Secondary and Primary Distribution Protection Relays Dual & Self Powered Relays Overcurrent & Earth Fault Protection Relays Feeder Protection Relays IEC 68 Introduction
More informationINSTALLATION & COMMISIONING GUIDE
SIA C Self Power O/C & E/F Protection Relay INSTALLATION & COMMISIONING GUIDE www.fanox.com SIAC11500032AG_Rev. 12 1 / 32 1. RECEPTION & INSTALLATION... 3 1.1. Relay unpacking... 3 1.2. Relay verification...
More informationProtection relay for secondary distribution
Protection relay for secondary distribution Dual and Self powered Signalling with flag indicators High electromagnetic compatibility Events recorder and specific test menu Protection relay for secondary
More informationSIA B Self and Dual powered Overcurrent & Earth Fault Protection Relay USER S MANUAL L
SIA B Self and Dual powered Overcurrent & Earth Fault Protection Relay USER S MANUAL L 1. REEPTION, HANDLING & INSTALLATION... 5 1.1. Unpacking... 5 1.2. Reception of relays... 5 1.3. Handling electronic
More informationU lity network. system Q sys. Interconnected P sys. P load Q load. P gen Q gen. Generator network
SIL-G Feeder & Generator Protection Relay RC FLSH Main characteristics The SIL-G is a relay for primary distribution which can protect a feeder by means of current and voltage functions. It is also provided
More informationISO 9001:2000 SIL A. Overcurrent and Earth-Fault relay USER S MANUAL SER S MANUAL
SIL A Overcurrent and Earth-Fault relay USER S MANUAL SER S MANUAL 1. RECEPTION, HANDLING, INSTALLATION... 1 1.1. Unpacking... 1 1.2. Reception of relays... 1 1.3. Handling electronic equipment... 1 1.4.
More informationSIA C. Self-powered overcurrent relay USER MANUAL
SIA C Self-powered overcurrent relay USER MANUAL 1. RECEPTION, HANDLING, INSTALLATION... 9 1.1. Unpacking... 9 1.2. Reception of relays... 9 1.3. Handling electronic equipment... 9 1.4. Installation, commissioning
More informationINTRODUCTION. The PL-50 MO and PM-250 families represent the. PM-250-H: Horizontal box. PM-250-V: Vertical box
INTRODUCTION The PL-50 MO units are available in the next mechanical version: The PL-50 MO and PM-250 families represent the different solutions that Team Arteche offers for motor protection. Both families
More informationNPW800R RETROFITTING. Power and Volatge Protection Relay
RETROFITTING Power and Volatge Protection Relay NPW800R (R3 case) is dedicated to the refurbishment of CEE WTG 7000 relays (R3 case) providing the measurement of apparent (S), active (P) and reactive (Q)
More informationSIL. Protection relays for primary and secondary distribution
SIL Protection relays for primary and secondary distribution Reduced size and light weight Two protocols simultaneously: MODUS & IEC 60870-5-103 With auto-reclosing, trip circuit supervision and cold load
More informationBus Bar Protection Relay B-PRO 4000
Bus Bar Protection Relay B-PRO 4000 Product Overview The IEC 61850 station bus embedded B-PRO 4000 relay provides complete bus and substation differential protection (low impedance) with CT saturation
More informationSR489 SR489. Generator Management Relay. Economical protection, metering, and monitoring functions for small and medium sized generators.
SR489 Generator Management Relay Economical protection, metering, and monitoring functions for small and medium sized generators. 1 Product Highlights Inputs / Outputs Generator Protection Power Metering
More informationADDITIONAL INFORMATION MODBUS INSTRUCTION MANUAL. Request publication Request publication DNP 3.0 INSTRUCTION MANUAL
BE1-851E ENHANCED OVERCURRENT PROTECTION SYSTEM DEVICE FUNCTIONS 43 50 51 62 The BE1-851E is an enhanced overcurrent protection system based on the design of the BE1-851, a multifunction, numeric relay
More informationSEL-487B. A Powerful Solution for Busbar Differential Protection. Bus Differential and Breaker Failure Relay
Bus Differential and Breaker Failure Relay A Powerful Solution for Busbar Differential Protection Features and Benefits Select the for the differential protection of busbar systems with up to 18 terminals.
More informationSIA/SIL. Secondary and Primary Distribution Protection Relays. Specialized in self powered relays IEC 61850
Specialized in self powered relays SI/SIL Secondary and Primary Distribution Protection Relays Dual & Self Powered Relays Overcurrent & Earth Fault Protection Relays Feeder Protection Relays IEC 680 Introduction
More informationVIP 40/45 VIP 400/410
40/45 400/410 Selection guide 01 PM100573 40/45 PM100576 400/410 self-powered integrated protection relay Optimised performance for transformer, incomer, feeder and bus riser protection Complete engineered
More informationSYMAP R Plug in Variants FI, MI, 87M, TI Technical data
SYMAP R Plug in Variants FI, MI, 87M, TI Technical data 1 Product overview SYMAP R (Retrofit) is a digital protection relay for use in medium and high-voltage power systems. Because of its integrated protection
More informationIndex POWER T&D. SIA-B (Dual & Self powered) OC&EF Protection for Secondary Distribution with specific transformers... 20
POWER T&D Index What is SELF-POWER?... 6 Why is Fanox the world s leading manufacturer of SELF-POWERED Relays?... 9 Evolution of RMU s Protection Relays.... 1 Protection functions, common features and
More informationMiCOM P111. Three phase and earth fault overcurrent relays
Three phase and earth fault overcurrent relays The relays are suitable for all the application where overcurrent and/or earth-fault protection are required. Thanks to its favorable price vs technical features
More informationProtection Relays PHASE & RESIDUAL OVERCURRENT
Protection Relays PHASE & RESIDUAL OVERCURRENT Application The relay type NA016 can be used in radial networks as feeder or power transformer protection. In solidly grounded systems the residual overcurrent
More informationINTEGRATED SYSTEMS AND CONTROL, INC. User s Hardware Manual. PCMNET V 7. xx
INTEGRATED SYSTEMS AND CONTROL, INC. User s Hardware Manual PCMNET V 7. xx INTEGRATED SYSTEMS AND CONTROLS, INC. PCMNET Users Manual Revised 2/4/2005 2003-2005 Integrated Systems and Control. Inc. PO Box
More informationREL52001 Easergy P3U30, 4L, 4U, 16DI/8DO, Uaux: V, DI: V, 2 x RJ-45
Characteristics Easergy P3U30, 4L, 4U, 16DI/8DO, Uaux: 48-230V, DI: 220-230V, 2 x RJ-45 Main Range of product Product or component type Relay application Configuration type (Cortec) [Us] rated supply voltage
More informationMiCOM P124 T&D. Self and Dual Powered Overcurrent Relays
PROTECTION MiCOM P124 Self and Dual Powered Overcurrent Relays MiCOM P124 are numerical relays designed to offer complete overcurrent protection without requiring any external auxiliary supply. They can
More informationMiCOM P123R. Overcurrent Relays P123R/EN AD/A11. Upgrade Documentation
MiCOM P123R Overcurrent Relays Upgrade Documentation MiCOM P123R Page 1/14 CONTENTS MiCOM P123R ADDENDUM: MiCOM P12X UPDATE DOCUMENTATION 3 P12X/EN IT/EB6: INTRODUCTION 4 P12x/EN TD/Eb6: TECHNICAL DATA
More informationRequest publication Request publication DNP 3.0 INSTRUCTION MANUAL. Request publication
BE1-851 OVERCURRENT PROTECTION SYSTEM The BE1-851 is a multifunction, numeric relay that provides three phase, ground, and negative sequence overcurrent protection with four shot recloser, breaker failure,
More informationRemote communication options include IEC Ethernet communications or Modbus (RS485).
2019 The MELPRO D series relay is suitable for feeder protection, motor protection and transformer protection applications. The relay offers multiple step time grading for over-current protection co-ordination.
More informationREL52002 Easergy P3U30, 4L, 4U, 16DI/8DO, Uaux: V, DI: V, RS-485
Characteristics Easergy P3U30, 4L, 4U, 16DI/8DO, Uaux: 48-230V, DI: 220-230V, RS-485 Main Range of product Product or component type Relay application Device short name [Us] rated supply voltage Type of
More informationGENERAL CATALOGUE. Equipments. Devices. fanox.com
GENERAL CATALOGUE SELF-POWERED s Equipments Devices fanox.com years of protection Fanox designs and manufactures electronic protection relays for Low and Medium Voltage. Since it was founded in 1992, the
More informationMiCOM P122C Time-Overcurrent Protection
Protection Relays 01 MiCOM P122C Time-Overcurrent Protection Customer Benefits 1A/5A software setting 4 function keys Compact unit for flush and wall-surface mounting Comprehensive measurements Disturbance
More informationSACE Emax 2 Specification guide
SACE Emax 2 Specification guide Specification Number: 26 01 20.17 Product Name: LOW VOLTAGE POWER CIRCUIT BREAKERS PART 1 GENERAL NOTE: ( ) Indicates option or a selection is to be made for quantity or
More informationBF
BE1-11i INTERTIE PROTECTION SYSTEM DEVICE FUNCTIONS The BE1-11i Intertie Protection System is a multifunction numeric relay providing the protection and control requirements outlined in IEEE 1547-2003
More informationTransformer Protection and Control RET630 Numerical transformer protection in medium voltage networks
GUIDEFORM SPECIFICATION Transformer Protection and Control RET630 Numerical transformer protection in medium voltage networks The freely configurable relay is intended for protection, control, measurement
More informationEDR-3000 Eaton Distribution Relay
Supersedes November 2014 Contents Description Page General Description.... 2 Applications.... 3 Dimensions.... 5 Wiring Diagram.... 6 Specifications... 7 Ordering Information....11 Applications Provides
More informationMiCOM P521. Fast feeder differential protection
01 Fast feeder differential protection The relay provides high-speed two-ended current differential unit protection of overhead lines and underground cables in applications such as ring mains and parallel
More informationBF Option. BESTNet BESTNet BESTNet BESTNet BESTNet BE1-700C DIGITAL OVERCURRENT PROTECTIVE RELAY ADVANTAGES
Easy Ethernet or Modbus/TCP Available with BE1-700C BESTNet BESTNet BESTNet BESTNet BESTNet BE1-700C DIGITAL OVERCURRENT PROTECTIVE RELAY The BE1-700C is a compact multifunction, numeric relay that provides
More informationMiCOM P124. Self and Dual Powered Overcurrent Relays. Protection Relays
01 Self and Dual Powered Overcurrent Relays are numerical relays designed to offer complete overcurrent protection without requiring any external auxiliary supply. They can be applied to a wide variety
More informationOvercurrent and Arc Protection by Reyrolle Alexander Erokhin. 21, 2017 I Berlin
Overcurrent and Arc Protection by Reyrolle Alexander Erokhin VAR Partner Day September 20-21, 21, 2017 I Berlin Reyrolle Product Range by SIEMENS Challenges We Meet for our Customers Easy-to-use protection
More informationAdvanced distribution feeder solution with integrated protection, monitoring, and control
Protection System Advanced distribution feeder solution with integrated protection, monitoring, and control Achieve sensitive and secure fault detection using comprehensive protection functions. Keep track
More informationRelion 615 series Line Differential Protection and Control RED615 Ver. 2.0 Technical Presentation
Relion 615 series Line Differential Protection and Control RED615 Ver. 2.0 Technical Presentation ABB Oy Distribution Automation July 1, 2009 1MRS756504 B Slide 1 Contents RED615 Technical Presentation
More informationTRANSFORMER PROTECTION SYSTEM ADVANTAGES 87N
BE1-11t TRANSFORMER PROTECTION SYSTEM DEVICE FUNCTIONS The BE1-11t Transformer Protection System is a multifunction numeric relay designed with many features to address reliability issues that arise due
More informationQuantum III. Compact DC Drive Package. Slitter DC Drive Package. Quantum III
Compact DC Drive Package The delivers a DC drive package that integrates the intelligence of the Mentor II with a space saving design that incorporates many accessories typically required in the North
More informationCombined Overcurrent and Earth-fault Relay SPAJ 140 C. Product Guide
Combined Overcurrent and Earth-fault Product Guide Issued: April 1999 Status: Updated Version: C/18.04.2006 Data subject to change without notice Features Three-phase, low-set phase overcurrent unit with
More informationSection 4 Ground-Fault Protection Devices
Multi 9 System Catalog Section 4Ground-Fault Protection Devices Section 4Ground-Fault Protection Devices Selection Table The Multi 9 System includes one UL Listed and three IEC rated product families that
More informationEDR-3000 Eaton Distribution Relay
EDR-3000 Eaton Distribution Relay Technical Data New Information Description Page 1. General Description.......................... 2 2. Applications............................... 2 3. Drilling Pattern.............................
More informationGE Multilin 350 Feeder Protection Relay Specifications
GE Multilin 350 Feeder Protection Relay Specifications The feeder protection relay shall provide primary protection of medium voltage distribution feeders. The relay shall be equipped with the following
More informationMESP TECHNICAL SPECIFICATION FOR A RECTIFIER UNIT CONTROL & PROTECTION SYSTEM FOR USE IN THE 1500V DC TRACTION SYSTEM
Engineering Specification Electrical Networks TECHNICAL SPECIFICATION FOR A RECTIFIER UNIT CONTROL & PROTECTION SYSTEM FOR USE IN THE 1500V Version: 1 Issued: March 2014 Owner: Electrical Networks Asset
More informationMaximize process uptime with the SEL-patented motor thermal model.
SEL-710 Motor Protection Relay Maximize process uptime with the SEL-patented motor thermal model. Optimize motor performance with separate thermal models for the stator and rotor. Monitor stator and ambient
More informationEasy To Use OEMS Take Note
MA7200 Features Sensorless Vector Precise speed and torque control for the most demanding system performance. Simple set-up through autotuning function. The MA7200 can be operated in sensorless vector
More informationMULTIFUNCTION MICROPROCESSOR PROTECTION RELAY TYPE IM30-G DATA BASE
Pag. 1 of 6 MULTIFUNCTION MICROPROCESSOR PROTECTION RELAY TYPE DATA BASE Pag. 2 of 6 1 - Supported MODBUS functions. Both the communication ports support the following MODBUS RTU commands: - Read N words
More information7SR242 Duobias Multi-Function 2-Winding Transformer Protection Relay
7SR242 Duobias Multi-Function 2-Winding Transformer Protection Relay Document Release History This document is issue 2010/06. The list of revisions up to and including this issue is: 2010/06 Additional
More informationSORDS ELECTRIC ~ MA7200. Sensorless Vector AC Inverter.
www.sordselectric.com MA7200 Sensorless Vector AC Inverter Features and Benefits Sensorless Vector The MA7200 has precise speed and torque control for the most demanding system performance and simple set-up
More informationF650 Firmware Release Notes / History (Rev 10)
1.00 2.00 First version of the product (Basic Model F1G0) Full protection scheme F650BABF1G0HI August 30 th 2002 1.11 2.00 New model F2G0 (inputs and outputs board type 2) F650BABF2G0HI October 14 th 2002
More informationIED (Intelligent Electronic Device)
IED (Intelligent Electronic Device) Neopis IED (Intelligent Electronic Device) Intelligent Electronic Device Dynamic Characteristics PROMET 4300-F PROMET 4300-M Relay Type Setting Setting Range Setting
More informationBF 79 81
BE1-11f FEEDER PROTECTION SYSTEM The BE1-11f is a multifunction numeric relay that provides three phase, ground, and negative sequence directional or non-directional overcurrent protection with four shot
More informationMiCOM P12x/y. Three phase and earth fault overcurrent relays
01 Three phase and earth fault overcurrent relays The relays provides features for easy adaptation and are suitable for all applications where overcurrent and earth-fault protection are required. The MiCOM
More informationEarth-fault Relay SPAJ 110 C. Product Guide
Issued: April 1999 Status: Updated Version: C/12.04.2006 Data subject to change without notice Features Low-set neutral overcurrent stage with definite time or inverse time characteristic High-set neutral
More informationSIPROTEC 7SC80 Feeder Protection and Automation Answers for infrastructure and cities.
www.siemens.com/protection SIPROTEC 7SC80 Feeder Protection and Automation Answers for infrastructure and cities. designed for feeder automation applications This solution allows very fast fault detection
More informationTransformer Protection Relay
Transformer Protection Relay T-PRO Product Overview The IEC 61850 station bus embedded T-PRO relay provides complete three-phase multi-winding transformer protection and overload protection, DFR-quality
More informationGE Power Management. UR F60 Feeder Management Relay An integrated feeder protection and metering solution
UR An integrated feeder protection and metering solution Power to Manage your Facility Connectivity ModBus RTU MMS/UCA2 TM Protocols SI Compatibility Flexibility FlexCurves FlexLogic The first Relay designed
More informationMETERING INSTRUMENTS AND CURRENT TRANSFORMERS
Energy Meters p16-1 Data Concentrators p16-3 Digital Measuring Instruments p16-4 Expansion Modules and Accessories p16-15 Current Transformers p16-19 Software and Applications p16-22 Systems Management
More informationRTU560. CT/VT Interface 560CVT10. Meter Operation. Application. Characteristics. Data Sheet CT/VT Interface 560CVT10. Instantaneous Meter Values
CT/VT Interface 560CVT10 The fault current is measured up to 20 times nominal current. Therefore the current inputs withstand 50 times nominal current for 1 s. The CT/VT interface is equipped with one
More informationCURRENT PROTECTION RELAY SMPR-1
CURRENT PROTECTION RELAY SMPR-1 1.- ORION ITALIA SERIES MODBUS PROTOCOL. The ORION ITALIA SERIES implement a subset of the AEG Modicon Modbus serial communication standard. Many devices support this protocol
More informationTWO-WINDING TRANSFORMER DIFFERENTIAL
E3-TR PROTECTION WITH AUTOMATIC VOLTAGE Because of the control, measuring and monitoring functions implemented, the IED can also be used as a bay control unit. The EuroCAP configuration tool, which is
More informationBF 86 FEEDER PROTECTION SYSTEM ADVANTAGES
BE1-11f FEEDER PROTECTION SYSTEM (J) Panel Mount (H) Rack Mount The BE1-11f Feeder Protection System is a multifunction numeric relay designed with many features to address reliability issues that arise
More informationGRE130. Protection and Control for MV Systems
Protection and Control for MV Systems FEATURES Phase undervoltage protection with IDMTL or DTL(27). Phase overvoltage protection with IDMTL or DTL(59). Zero phase sequence overvoltage (neutral voltage
More informationFP-5000 Series Multi-functional Microprocessor-based Feeder Protective Relay
FP-5000 Series Multi-functional Microprocessor-based Feeder Protective Relay The power of fusion. 1874 1886 1893 1899 1906 1908 1911 1934 1962 1963 1976 1983 1990 1999 There s a certain energy at Eaton.
More informationRT4F-110V/25A RECTIFIER
The RT4F-110V/25A is a hot-pluggable switched mode rectifier (SMR) module designed to provide up to 25A of output current into a 110V nominal system. Examples of such systems are 60 cells lead acid (136V
More informationMetering Devices, Protective Relays, Software and Connectivity. Pre-Wired Control Power, Voltage and CT Inputs
.3 Features and Benefits Saves installation time and cost One part number to order; no need to worry that any part has been left out Pick the meter or meters you need as it is designed to fit various Eaton
More informationSensitive definite time or inverse time earth-fault stage for back-up residual earthfault
Issued: April 1999 Status: Updated Version: B/09.11.2001 Data subject to change without notice Features Sensitive restricted earth-fault protection stage for fast, selective earth-fault protection Sensitive
More informationRelion 615 series Transformer Protection and Control RET615 Ver. 2.0 Technical Presentation
Relion 615 series Transformer Protection and Control RET615 Ver. 2.0 Technical Presentation Distribution Automation May 13, 2010 1MRS756901 A Slide 1 Content RET615 Technical Presentation highlights May
More informationCombined Overcurrent and Earth-fault Relay SPAJ 141 C. Product Guide
Combined Overcurrent and Earth-fault Product Guide Issued: April 1999 Status: Updated Version: C/19.04.2006 Data subject to change without notice Features Three-phase, low-set phase overcurrent unit with
More informationRecloser Controller for feeder protection and automation siemens.com/distribution-automation
SIPROTEC 7SC80 Control Controller for feeder protection and automation siemens.com/distribution-automation SIPROTEC 7SC80 Control Designed for feeder automation applications This solution allows very fast
More informationFeeder Protection Relay REF 610. Product Guide
Product Guide Contents 1 Description.............................. 3 2 Protection functions....................... 3 3 Measurement............................ 4 4 Disturbance recorder......................
More informationFP-5000 Feeder Protection
Effective: April 2001 Page 1 New Information FP-00 Feeder Protection Contents Description Page FP-00 Description......... 2 Application Description...... 2 Features, Functions and Benefits..............
More informationNumerical motor protection in medium voltage networks Motor Protection and Control REM620
Guideform Specification 1MRS758530 A Numerical motor protection in medium voltage networks Motor Protection and Control REM620 The configurable motor management relay is intended for protection, control,
More informationDIGITAL RELAY OF PROTECTION AND AUTOMATION SERIES PC83 AND PC830
DIGITAL RELAY OF PROTECTION AND AUTOMATION SERIES PC83 AND PC830 PC83 and PC830 series devices are designed to perform the relay protection functions and 6-154 kv networks automation, have different functionality
More informationENhanced TEChnology. Solid insulated vacuum recloser for power distribution system thru 15kV, 27kV, 38kV. Ver.
ENhanced TEChnology www.entecene.co.kr Solid insulated vacuum recloser for power distribution system thru 15kV, 27kV, 38kV Ver. 081226 General features We, ENTEC introduce a Solid Insulated Vacuum Recloser
More informationMIN II. Complete numerical ground directional protection. Digital Energy Multilin. Protection and Control. Monitoring and Metering.
MIN II Key Benefits Reduce troubleshooting and maintenance cost - event recording, and analogy/digital oscillography Design flexibility - Easy to use programming logic Access to information - Modbus RTU
More informationPM800 series. Applications
Functions and characteristics PE86134 The PowerLogic meters offers many high-performance capabilities needed to meter and monitor an electrical installation in a compact 96 x 96 mm unit. All models include
More informationRELAYABLE POWER. AQ 200 series protection, control, measurement and monitoring IEDs
RELAYABLE POWER AQ 200 series protection, control, measurement and monitoring IEDs Contents AQ 200 series protection and control IEDs 3 AQ 200 benefits 3 AQ 200 protection functions 4 AQ 200 control and
More informationType SDR reclosers plus controllers and type B-2 recloser bypass switch assembly usa.siemens.com/mediumvoltage
Overhead solutions Type SDR reclosers plus controllers and type B-2 recloser bypass switch assembly usa.siemens.com/mediumvoltage Overhead switching products Brochure Your outdoor overhead distribution
More informationATV12H075M3 variable speed drive ATV kW - 1hp V - 3ph - with heat sink
Product datasheet Characteristics ATV12H075M3 variable speed drive ATV12-0.75kW - 1hp - 200..240V - 3ph - with heat sink Complementary Main Range of product Altivar 12 Product or component type Product
More informationProducts Portfolio. Pole mounted Vacuum Recloser
Products Portfolio Pole mounted Vacuum Recloser Efacec Switchgear Efacec Switchgear is a leading company in Portugal and a worldwide reference in the development of solutions for power generation, transmission,
More informationPROTECT Electronics Co. Ltd
Independent static overcurrent relay Document ID: 24-13-15848-00 Budapest, 2006 User s manual version information Version Datum Modification Compiled by.00 May 1995 First Hungarian version Póka.01 June
More informationThree phase and earth fault overcurrent relays
01 Three phase and earth fault overcurrent relays The relays provides features for easy adaptation and are suitable for all applications where overcurrent and earth-fault protection are required. The MiCOM
More informationSolid insulated vacuum recloser for power distribution system thru 15kV, 27kV, 38kV Version 3.3
www.entecene.co.kr Solid insulated vacuum recloser for power distribution system thru 15kV, 27kV, 38kV Version 3.3 General features We, ENTEC introduce a Solid Insulated Vacuum Recloser encapsulated with
More informationResidual overvoltage relay
Page 1 Issued: April 1999 Status: New Data subject to change without notice Features Definite-time residual overvoltage earthfault protection and supervision Two independent operation stages, e.g. one
More informationDNP3 Communications Protocol
Powermeter and Power Quality Analyzer PM174 DNP3 Communications Protocol Reference Guide BG0413 Rev. A3 Every effort has been made to ensure that the material herein is complete and accurate. However,
More informationwww. ElectricalPartManuals. com Protective Relays PROTECTION AND CONTROL FUNCTIONS ADVANCED CAPABILITIES
Protective Relays Electrical Apparatus Capacitor Bank Protection Relay 165-440-900 Figure 1: Edison Idea Relay The capacitor bank protection relay is a member of Cooper Power Systems Edison Idea TM line
More informationRelion 615 series. Feeder protection and control REF615 ANSI Product guide
Relion 615 series Feeder protection and control Product guide Contents 1 Description............................. 3 2 Standard configurations................ 4-5 3 Protection functions...................
More information7SR11 and 7SR12 Settings and Instruments
7SR11 and 7SR12 Settings and Instruments Document Release History This document is issue 2012/01. The list of revisions up to and including this issue is: 2012/01 Software Maintenance 2011/06 Software
More informationModbus Server SIEMENS Algorex (printer port)
IntesisBox Server SIEMENS (printer port) Gateway for the integration of Siemens fire detection panels into enabled control systems. Monitor your fire panels remoy from your Control Center using any commercial
More informationRELAYABLE POWER. AQ 200 series protection, control, measurement and monitoring IEDs
RELAYABLE POWER AQ 200 series protection, control, measurement and monitoring IEDs Contents AQ 200 series protection and control IEDs 3 AQ 200 benefits 3 AQ 200 protection functions 4 AQ 200 control and
More informationBus Differential and Breaker Failure Relay. Advanced bus protection with built-in breaker failure detection
SEL-487B Bus Differential and Breaker Failure Relay Advanced bus protection with built-in breaker failure detection Protect busbars with up to 21 terminals using high-speed, low-impedance bus differential
More informationEM-1000 /EM-2000/ EM-3000 Series Multifunction Power and Energy Meters
Power and Energy Meters Code No. LIT-1900845 Issued December 4, 2013 EM-1000 /EM-2000/ EM-3000 Series Multifunction Power and Energy Meters EM-1000 Series Meter Description The EM-1000 Series monitor is
More information