Non-Contact MPO Fiber Optic Connector
|
|
- Donna Peters
- 6 years ago
- Views:
Transcription
1 White Paper Non-Contact MPO Fiber Optic Connector Traditional MPO connectors require all fiber end faces to be in close physical contact at the same time. This is because of the fact that if there is an air gap, the light will be reflected between the end faces of the optical fiber (Fabry-Perot cavity) and seriously affects the stability of the signal. To ensure that all fiber end faces are in close contact at the same time, the fiber end face needs to protrude significantly from the surrounding surface, and a large working pressure is required on the optical fiber connector. ecause of the design, there are numerous problems with traditional MPO connectors. Figure 1. Non-contact MPO fiber connector (left) has an anti-reflective coating on the end face, compared to a conventional contact MPO connector (right) Non-contact MPO (NC-MPO) fiber connector has an optical fiber end face lower than the plastic ferrule surface, and an anti-reflection coating is on all the fiber end faces and the plastic ferrule surface (Fig. 1). When NC-MPO connectors are mated, there is a small air gap between all the fiber end faces. nti-reflection coating can prevent multiple reflection of light, while the lower fiber end face (Fig. 2) ensures that the mating fiber end face is not damaged. The working pressure on the NC-MPO connector is very small Figure 2. In a non-contact MPO fiber connector, the fiber end face is lower than the surrounding plastic ferrule surface (interferometer plot) The insertion loss test and return loss test reported in this paper are performed using test equipment model JGR-MS5.
2 Experiment 1: SM NC-MPO connector mated to SM NC-MPO connector side: 12-core SM NC-MPO connector (8 degree, coating); side: 12-core SM MPO physical contact connector (8 degree, no coating). NC-MPO connector under test: side: 12-core SM NC-MPO connector (8 degree, coating); -side: 12-core SM MPO physical contact connector (8 degree, no coating). Test method is shown below where the red part denotes anti-reflection coating on the ) Reference measurement: ) DUT measurement: DUT Due to the lack of reflection at the coated end face (see the next section), the insertion loss after mating needs to subtract.15 d from the test value. Pout = Pin (1-4%), Pout is the detection value of the photo detector, Pin is the actual insertion loss, loss of 4% is about.15d. Test procedure for connectors with coating t the reference measurement step, the end of the reference jumper is an -coated connector. s a result of the coating, the -side connector end face does not exhibit a 4% reflection loss. The photo detector receives power P out1 which is equal to the power P in1 at the output of the -side connector. P in1=pout1 t DUT test step, because the DUT's -side is a non-coated connector, the -side connector Pin1 Pout1
3 end face will have 4% reflection loss. The power received by the photo detector is P out2 = P in2 * (1-4%). DUT Pout2 Pin2 The final test result P out2 includes an extra 4% return loss in addition to the actual insertion loss P in2 of the DUT. This 4% (or.15d) needs to be subtracted from the measured insertion loss value. Test Result: Non-contact To Non-contact IL test Result For 12- core SM MPO(131nm) % % % %.% 5 6.% 5.% 4.% 3.% 2.% 1.%.%.% Non-contact To Non-contact IL test Result For 12- core SM MPO(155nm) % 3.21% % %.%.% 3 6.% 5.% 4.% 3.% 2.% 1.%.%
4 Experiment 2: SM NC-MPO connector mated to Special SM Uncoated MPO connector side: 12-core SM NC-MPO connector (8 degree, coating); -side: 12-core SM MPO physical contact connector (8 degree, no coating). MPO connector under test: -side: Special 12-core SM MPO connector (8 degree, no coating): fiber end is recessed from the ferrule surface, no coating. In other words, the fiber is recessed from the ferrule surface and will not cause damage to the coating on the opposing connector. -side: 12-core SM MPO physical contact connector (8 degree, no coating) Test method is shown below where the red part denotes anti-reflection coating on the ) Reference measurement ) DUT measurement DUT Pout = Pin (1-4%), Pout is the photo detector value, Pin is the actual insertion loss, again 4% loss is equivalent to.15d, which needs to be subtracted. Since the end of the DUT is a non-coated connector, a 4% loss is generated when the DUT -side is mated with the -side of the test jumper. Note this 4% loss is real. Therefore, the minimum loss in this case is.15 d. The loss distribution can be clearly shown in the following figure. Test Result:
5 Non-contact To Non-contact(uncoated) IL test Result For 12-core SM MPO(131nm) % 8.7% % % % 4.17%.% % 5.% 4.% 3.% 2.% 1.%.% Non-contact To Non-contact(uncoated) IL test Result For 12-core SM MPO(155nm).% 27.66% % % % 7 35.% 3.% 25.% 2.% 15.% 1.% 2.8%.% 5.% 1.% 12-core SM NC-MPO Performance Summary
6 12-core Singlemode NC-MPO Statistical results Non-Contact 8 ( coated mated to coated) Non-Contact 8 ( coated mated to uncoated) 131nm 155nm 131nm 155nm Insertion Loss Return Loss Experiment 3: Multimode NC-MPO Connector mated to Multimode NC-MPO Connector: end face degree -side: 12-core MM NC-MPO connector ( degree, coating); -side: 12-core MM MPO physical contact connector ( degree, no coating). MPO connector under test: -side: 12-core MM NC-MPO connector ( degree, coating); -side: 12-core MM MPO physical contact connector ( degree, no coating). Test method is shown below where the red part denotes anti-reflection coating on the Mean value.6d.6d.25d.23d Standard deviation % distribution.16d.15d.35d.35d Repeatability <.1d <.1d <.1d <.1d Maximum value.2d.19d.39d.39d Minimum value.1d.1d.17d.15d Mean value 77.92d 8.12d 75.7d 75.44d Standard deviation 4.89d 3.28d Maximum value 85.4d 83.6d 85.5d 83.7d Minimum value 69.9d 73.4d 65.1d 66.1d ) Reference measurement ) DUT measurement DUT Due to the lack of reflection at the coated end face, the insertion loss after mating needs to subtract.15 d from the test value. Test Result:
7 Non-contact To Non-contact IL test Result For 12-core MM MPO ( angle) % % % 1.35% 3.%.9% 2 45.% 4.% 35.% 3.% 25.% 2.% 15.% 1.% 5.%.%.%.% Experiment 4: Multimode NC-MPO Connector mated to Multimode NC-MPO Connector: end face 8 degree -side: 12-core MM NC-MPO connector (8 degree, coating); -side: 12-core MM MPO physical contact connector (8 degree, no coating) MPO connector under test: -side: 12-core MM NC-MPO connector (8 degree, coating) -side: 12-core MM MPO physical contact connector (8 degree, no coating) Test method is shown below where the red part denotes anti-reflection coating on the ) Reference measurement: ) DUT measurement: DUT
8 Due to the lack of reflection at the coated end face, the insertion loss after mating needs to subtract.15 d from the test value. Test Result: Non-contact To Non-contact IL test Result For 48- core MM MPO (8 angle) % % % 1.67%.56%.% % 6.% 5.% 4.% 3.% 2.% 1.%.% 12-core Multimode NC-MPO Performance Summary 12-core Multimode NC-MPO Statistical results From the test results, it can be seen that 12-core MM 8 angle NC-MPO has better performance than angle NC-MPO. Experiment 5: 48-core multimode NC-MPO Connector mated to 48-core multimode NC-MPO end face degree Insertion Loss Return Loss side: 48-core MM NC-MPO connector ( degree, coating); -side: 2 groups of 24-core MM MPO physical contact connector ( degree, no coating). MPO connector under test: Non-Contact ( coated mated to coated) side: 48-core MM NC-MPO connector ( degree, coating); Non-Contact 8 ( coated mated to coated) Wavelength: 85nm Mean value.5d.4d Standard deviation % distribution.15d.15d Repeatability <.1d <.1d Maximum value.28d.22d Minimum value.1d.1d Mean value 18.68d Standard deviation 2.3 Returned signal too small Maximum value 25.4d to detect. Minimum value 16.9d -side: 2 groups of 24-core MM MPO physical contact connector ( degree, no coating).
9 Test method is shown below where the red part denotes anti-reflection coating on the ) Reference measurement Dector ) DUT measurement DUT Dector Due to the lack of reflection at the coated end face, the insertion loss after mating needs to subtract.15 d from the test value. Test Result: Non-contact To Non-contact IL test Result For 48-core MM MPO ( angle) % % 24.24% 19.89% % % 2.84% 1.14%.38%.% % 25.% 2.% 15.% 1.% 5.%.%
10 Experiment 6: 48-core Multimode NC-MPO connector mated to 48-core Multimode NC-MPO end face 8 degree -side: 48-core MM NC-MPO connector (8 degree, coating); -side: 2 groups of 24-core MM MPO physical contact connector ( degree, no coating). MPO connector under test: -side: 48-core MM NC-MPO connector (8 degree, coating); -side: 2 groups of 24-core MM MPO physical contact connector ( degree, no coating). Test method is shown below where the red part denotes anti-reflection coating on the ) Reference measurement ) DUT measurement Dector DUT Due to the lack of reflection at the coated end face, the insertion loss after mating needs to subtract.15 d from the test value.
11 Test Result: Non-contact To Non-contact IL test Result For 48-core MM MPO (8 angle) % % 26.97% 15.73% 1.11% %.% 3 3.% 25.% 2.% 15.% 1.% 5.%.% 48-core Multimode NC-MPO Performance Summary: 48-core Multimode NC-MPO Statistical results Insertion Loss Return Loss From the test results, it can be seen that 48-core MM 8 angle NC-MPO has better performance than angle NC-MPO. Non-Contact ( coated mated to coated) Non-Contact 8 ( coated mated to coated) Wavelength 85nm Mean value.16d.13d Standard deviation % distribution.31d.25d Repeatability <.1d <.1d Maximum value.42d.29d Minimum value.1d.2d Mean value 24.42d Standard deviation Returned signal too Maximum value 27.1d small to detect. Minimum value 17.3d
Non-Contact MPO Fiber Optic Connector
White Paper Non-Contact MPO Fiber Optic Connector The traditional physical contact MPO fiber connector requires that all fiber end faces achieve physical contact at the same time. Otherwise, there will
More informationEmbedded Polymer Waveguide to Optical Fiber Interconnects Creating the Optimal Link
Embedded Polymer Waveguide to Optical Fiber Interconnects Creating the Optimal Link Dr. Blanca Ruiz, Marika Immonen, Dr. Andres Ferrer, Christian Gsell, Dr. Peter Cristea CTI Corporate Technology & Innovation
More informationApplications Engineering Notes. The US Conec MTP Multifiber Connector
Applications Engineering Notes Document Title Document Number The US Conec MTP Multifiber Connector AEN-1909 Revision Number Rev 2.0 Effective Date June 1, 2008 1.0 Document Purpose The purpose of this
More informationFlexAirConnecT Dust Insensitive Multi-Fiber Connector with Low Loss and Low Mating Force
INFOCOMMUNICATIONS FlexAirConnecT Dust Insensitive Multi-Fiber Connector with Low Loss and Low Mating Force Hajime ARAO*, Sho YAKABE, Fumiya UEHARA, Dai SASAKI, and Takayuki SHIMAZU ----------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------
More informationDIAMOND Fiber Optic Components
DIAMOND Fiber Optic Components CABLE ASSEMBLIES AND ADAPTERS MFS & Fan-Out cords PC/APC MULTIMODE PC The Diamond Multiple Fiber System (MFS)combines Diamond`s advanced polishing technology and the flexibility
More informationA wide range of connectors are available to fit very specific needs.
By Larry Johnson In all fiber optic systems, it is necessary to join two fibers together with low signal attenuation while maintaining low reflection levels depending upon the type of system used. Fiber
More informationOptical Component Environmental Test System OCETS Plus Series
COMMUNICATIONS TEST & MEASUREMENT SOLUTIONS Optical Component Environmental Test System OCETS Plus Series Key Features High Return Loss option (HiRL) monitors RL up to 70 db Up to 210 device channels (420
More information3 No Polish LC 50um Multimode Connector Environmental and Mechanical Test Report
January 009 No Polish LC 0um Multimode Connector Environmental and Mechanical Test Report Page Introduction The focus of this document is to report the results from a series of environmental and mechanical
More informationSC/APC Connector. CATV Active device Telecommunication. Metro Local Area Data processing
Introduction As the industry s leading supplier of single-mode cable assemblies, Optical Fiber offers the most complete line of connectors and factory-terminated cables. From single-fiber jumpers to high
More informationCable Assembly Test System. MS12001 System
Cable Assembly Test System KEY FEATURES MS10P is a powerful controller unit with 10 slots MS10E Expansion Chassis for up to 10 extra slots Remote control via Ethernet/GPIB card Turn-key software Local
More informationDIAMOND Fiber Optic Components
DIAMOND Fiber Optic Components CABLE ASSEMBLIES AND ADAPTERS E-2 Backplane PC/APC MULTIMODE PC Enthusiastic customers using the E-2 TM connector system on their equipment encouraged the development of
More informationLTK-400 Series Optical Sources, Meters and Kits Without Data Storage Capabilities
Features and Benefits High output power and calibrated wavelengths Easy to use, unparalleled performance Rugged handheld design Capable of enduring harsh testing environments Product warranty and calibration
More informationMAP-200 Power Meter Detector Adaptors
Selection Guide MAP-200 Power Meter Detector Adaptors VIAVI Solutions AC Detector Adaptors are designed for use with the VIAVI MAP-200 optical power meters (mopm), return loss meters (morl) and Swept Wavelength
More informationHigh spatial resolution measurement of volume holographic gratings
High spatial resolution measurement of volume holographic gratings Gregory J. Steckman, Frank Havermeyer Ondax, Inc., 8 E. Duarte Rd., Monrovia, CA, USA 9116 ABSTRACT The conventional approach for measuring
More informationLTS-1 LTS-1C LTS-2 LTS-5 LTS-6 LTS-7 LTS-10 LTS-11 LTS-12. Wilcom. Optical Loss Test Kits. Description LTS-2
Optical Loss Test Kits Description Fit your application to your budget. Our Optical Test Kits combine the dependability and accuracy of our hand-held optical sources and meters with a convenient carry
More informationLEAD Fiber Optics PRODUCT CATALOGUE
LEAD Fiber Optics PRODUCT CATALOGUE OPTICAL TERMINATOR TEL:+886-2-8672-2371 FAX:+886-2-8672-3275 Web:http:// Optical Terminator Optical Terminators are used to terminate unused fiber connector ports in
More informationFiber optic connector for space applications
Fiber optic connector for space applications The AVIM connector family, is designed to be used in high reliability space and aerospace programs. These connectors are designed as Single Terminus, Fiber
More informationOptical Switch
1 4 1 8 1 16 Optical Switch Features: Wide Wavelength Range Low Back Reflection High Reliability High dependability Simple control Unique Patented Technology No glue in the route Applications: Switching
More informationMulti-drop Profibus Fiber Optic Converter
Multi-drop Profibus Fiber Optic Converter User Manual Table of Contents 1. Overview...3 1.1 Introduction...3 1.2 Technical Specification....3 1.3 Warranty..........4 2. Installation...4 2.1 Package Contents.....5
More informationTest Port Adapters Reference Guide
Test Port Adapters Reference Guide TEST AND INSPECTION OTDRs Certification Test Kits Fiberscopes Loss Test Sets überreicht durch: Opternus GmbH Optische Spleiss- & Messtechnik Büro Süd: Bahnhofstr. 5 D-22941
More informationMT-RJ OPTICAL FIBER SYSTEMS TESTING. Field Testing Made Easy
MT-RJ OPTICL FIER SYSTEMS TESTING Field Testing Made Easy TLE of CONTENTS Introduction...3 Recommended Test Components...4 Testing With Dual Sources and Detectors...5 Testing with a One Port Test Set...9
More informationLTS-2A LTS-10 LTS-10C LTS-11 LTS-12
Optical Loss Test Kits LTS-2A LTS-10 LTS-10C LTS-11 LTS-12 Description Fit your application to your budget. Our Optical Loss Test Kits, and Fiber Test Kits combine the dependability and accuracy of our
More informationQUALITY ASSURANCE OF MULTIFIBER CONNECTORS
QUALITY ASSURANCE OF MULTIFIBER CONNECTORS Eric A. Norland/ Daniel Beerbohm Norland Products Inc. Cranbury, NJ 08512 ABSTRACT Industry requirements for compact, high fiber count connectors in both telecom
More informationLight-Source Mainframe
Light-Source SERIES Document Number: SGD-0908-001 Specification & User Manual Table of Contents Disclaimer... 3 Range Of Limitations... 3 Dimensions and Materials... 3 Features... 3 Specifications... 4
More informationUsing Low DMD, Laser Optimized Multimode Fiber to Expand 10-Gigabit Network Design Options
Using Low DMD, Laser Optimized Multimode Fiber to Expand 10-Gigabit Network Design Options Lisa Huff Technical Manager, Advanced Design & Applications Berk-Tek, a Nexans Company Adam Murano Fiber Engineering
More informationFC Type Connector. Standards YD/T IEC GR-326-CORE
FC Type Connector Product Introduction Optical Fiber Jumper is the cable with a connector installed on its each end respectively to make the jumping connection of light path. Features Standard metal parts,
More informationA Closer Look at Plug and Play MPO/MTP Assemblies
WP_MTPAssemblies_D.qxp_D 11/29/16 3:05 PM Page 1 A Closer Look at Plug and Play MPO/MTP Assemblies The Internet of Things (IoT) and Big Data are driving the need for more bandwidth and increased transmission
More informationDIAMOND Fiber Optic Components
DIAMOND Optic Components NETWORK ACCESSORIES Attenuators Family PC/APC MULTIMODE PC DESCRIPTION Attenuators are used to adapt the transmitted light power to the characteristics of the implanted receiver.
More informationAdrian Young Leviton Network Solutions
Adrian Young Leviton Network Solutions In This Session Multimode fiber types How many fibers do I need for my application? Future IEEE and non IEEE applications Will my existing fiber plant support these?
More informationOPTICAL CONNECTOR CONTAMINATION
OPTICAL CONNECTOR CONTAMINATION 6 What do the standards say? The test procedures specified by 568-C require tools and procedures for ensuring connector quality. End faces on cords and trunks shall be in
More informationHeat-Cure Single-Fiber Connectors A LANscape Solutions Product
Applications Field or factory installations requiring high optical performance Cable Assembly House, OEM and Manufacturing Environments Multiple terminations where material cost is the main consideration
More informationOptical Engine? What s That?
JANUARY 28-31, 2013 SANTA CLARA CONVENTION CENTER Advances in Onboard Optical Interconnects: A New Generation of Miniature Optical Engines Marc Verdiell CTO Samtec Optical Group Samtec, Inc. 01/29/2013
More informationSpecialized Solutions for Fiber Optic Testing
Specialized Solutions for Fiber Optic Testing www.optotest.com 1.805.987.1700 OP740 High-Speed Multichannel Optical Power Meter The OP740 offers a state-of-the-art solution for highspeed optical power
More informationE x Direction of Propagation. y B y
x E x Direction of Propagation k z z y B y An electromagnetic wave is a travelling wave which has time varying electric and magnetic fields which are perpendicular to each other and the direction of propagation,
More informationLEAD Fiber Optics PRODUCT CATALOGUE
LEAD Fiber Optics PRODUCT CATALOGUE BARE FIBER ADAPTER TEL:+886-2-8672-2371 FAX:+886-2-8672-3275 Web:http://www.twfiberoptic.com Bare Fiber Adapter Bare fiber adapters are used as the medium to link the
More informationDIAMOND Fiber Optic Components
DIAMOND Fiber Optic Components CABLE ASSEMBLIES AND ADAPTERS E-2000 Simplex PC/APC MULTIMODE PC Constant innovation in the field of fiber optics has created demand for products with ever increasing performance
More informationDIAMOND Fiber Optic Components
DIAMOND Fiber Optic Components E-2 Compact & Duplex CABLE ASSEMBLIES AND ADAPTES SINGLE MODE PC/APC MULTIMODE PC The E-2 COMPACT and DUPLEX combine the optical and mechanical performances of the E-2 simplex
More informationA Closer Look at Fiber Optic Cable Assemblies
A Closer Look at Fiber Optic Cable Assemblies Our thanks to Siemon for allowing us to reprint the following article Many network performance problems occurring at the physical layer are directly related
More informationMBR5 Multi-Output Backreflection Meter
MBR5 Multi-Output Backreflection Meter User Manual All information contained herein is believed to be accurate and is subject to change without notice. No responsibility is assumed for its use. JGR Optics
More informationAF-OLK5A Series Fiber Optic Test kit
AF-OLK5A Series Fiber Optic Test kit Description The AF-OLK5A series test kits are the complete solution necessary for the installer to test, terminate and trouble shoot fiber optic systems. These test
More informationFiber Channel / FICON Singlemode Recommendation for 8 APC connectivity systems
Fiber Channel / FICON Singlemode Recommendation for 8 APC connectivity systems WHITEPAPER Whitepaper: Lichtlauf Poarität - Codierung Autor: Harald Jungbäck Seite 1 von 5 Reflections: A singlemode (SM)
More informationQualified Partner Programme QPP. Fiber Optic Gigabit Ethernet Theory Felice Guarna
Qualified Partner Programme QPP Fiber Optic Gigabit Ethernet Theory Felice Guarna Applications The protocols used in LAN mostly base on Ethernet technology. In 1998 the IEEE 802.3z was passed (Gigabit
More informationMTP/MPO SOLUTIONS FIBERTRONICS. General Applications & Loss Specifications
MTP/MPO SOLUTIONS FIBERTRONICS Multifiber Push-On (MPO) connectors have answered the call for more bandwidth and more space efficiency. MPO connectors are able to provide up to 24 or more fibers in a single
More information1. Summary of configurations for end face geometry and measurement conditions. Configurations for End Face Geometry
31 October 2003 Guidance Document Guidance for Interferometer Inspection of Fiber Optic Ferrule, Fiber End Face Measurements, Ferrules with Domed End Faces 1. Summary of configurations for end face geometry
More informationProduct information 19" 1U UniRack2 24xLC-Duplex G.652.D, PC, ceramic, C/2 R819330
Product information 19" 1U UniRack2 24xLC-Duplex G.652.D, PC, ceramic, C/2 R819330 1 Pcs. 19" 1U slide-in unit, splice tray plate with 2 splice trays radius 40 mm, fastening material, labeling strips and
More informationChoosing MPO Connectors for the Data Center. Ken Hall, RCDD, NTS Data Center Architect CommScope
Choosing MPO Connectors for the Data Center Ken Hall, RCDD, NTS Data Center Architect CommScope Agenda Network Architecture changes Data Center & MPO Standards Application comparisons Additional considerations
More informationDevelopment of Cleanliness Specification for Expanded Beam Connectors Project. End of Project Brief. July 20, 2016
Development of Cleanliness Specification for Expanded Beam Connectors Project End of Project Brief July 20, 2016 Project Members Tatiana Berdinskikh Tom Coughlin Michael Kadar-Kallen, Mike Gurreri Christine
More informationPOL-001 Fiber-Optic In-Line Polarizer. Operation Manual
POL-001 Fiber-Optic In-Line Polarizer Operation Manual Feb. 18, 2002 General Photonics Corp. Ph: (909) 590-5473 5228 Edison Ave. Fax: (909) 902-5536 Chino, CA 91710 USA www.generalphotonics.com Document
More informationCubro OPTOSLIM TAPs Series (Upto 100 G)
Cubro OPTOSLIM TAPs Series (Upto 100 G) PRODUCT OVERVIEW Network TAPs At a glance Definition A network TAP (test access point) is an external monitoring device that mirrors the traffic that passes between
More informationField Installable LC Connector
Field Installable LC Connector Serin Tan 1, Terutake Kobayashi 2, Daigo Saito 2, Kazuhiro Takizawa 2 and Kazuya Ogata 2 To expand our range of field installable optical connectors, we have successfully
More informationEric Lindmark, Ph.D.
Theory and Practical Application Written by: Eric Lindmark, Ph.D. v061608 4611 Chatsworth Street Shoreview, Minnesota, 55126-5813, USA www.promet.net Introduction In theory, higher bit rate fiber optic
More informationZX-1 Array Plus Zoom Interferometer
ZX-1 Array Plus Zoom Interferometer Key Benefits: Single unit can measure multi-fibre MT, Mini-MT, MT-RJ, MPO, MPX and MTP array connectors AND single-fibre PC, APC connectors, ferrules and ferrule blanks
More informationMS12001 Cable Assembly Test System. User Guide
MS12001 Cable Assembly Test System User Guide Copyright 2011 JGR Optics Inc. All rights reserved. No part of this publication may be reproduced, stored in a retrieval system or transmitted in any form,
More informationFEATURED PRODUCTS SC & LC MINI BOOTS LC-HD TOP ADAPTER XP-SERIES LC SWITCHABLE UNIBOOT IP-SERIES LC-KEYED FLEX BOOTS PLC-WDM
LC-HD FEATURED PRODUCTS SC & LC MINI BOOTS SC & LC TOP ADAPTER IP-SERIES LC SWITCHABLE UNIBOOT XP-SERIES LC-KEYED SC & LC FLEX BOOTS PLC-WDM LC-HD CONNECTOR LC HD HIGH DENSITY CONNECTOR The SENKO LC-HD,
More informationDIAMOND Fiber Optic Components
DIAMOND Fiber Optic Components CABLE ASSEMBLIES AND ADAPTERS F-3 Simplex PC/APC MULTIMODE PC Telecommunications and Fiber Optics are developing at an incredible speed. To keep up with tomorrow s requirements
More informationOTS-400 Series Optical Sources, Meters, Testers and Kits with Data Storage Capabilities A LANscape Solutions Product
Applications Testing and troubleshooting of various telecommunication networks Description The Corning Cable Systems OTS-400 Series of intelligent and versatile optical meters, sources and testers offers
More informationFiber Optic Connectors
White Paper Fiber Optic Connectors Why expanded beam is essential in harsh environments Abstract Traditional physical contact fiber optic connectors have proved to be unreliable in harsh environment applications
More informationDevelopment of Optical Wiring Technology for Optical Interconnects
Development of Optical Wiring Technology for Optical Interconnects Mitsuhiro Iwaya*, Katsuki Suematsu*, Harumi Inaba*, Ryuichi Sugizaki*, Kazuyuki Fuse*, Takuya Nishimoto* 2, Kenji Kamoto* 3 We had developed
More informationAutofocus Video Inspection Probe G0382A. Product Introduction
focus Video Inspection Probe G0382A Product Introduction What is Video Inspection Probe? Scratches and stains to optic fiber ferrule endfaces are often said to have a negative impact on transmission quality.
More informationIntroduction to optical fibers and their applications
Introduction to optical fibers and their applications Felix Donkers Oct, 2008 (draft v0.1) Outline Introduction Optical fibers, patch cords and cables Optical fiber termination and alignment Application
More informationState-of-the-Art and direction for high density optical fiber interconnects
State-of-the-Art and direction for high density optical fiber interconnects Bill Blubaugh, Toshiaki Satake US Conec Ltd. April 18, 2007 We develop, manufacture and market high density optical interconnect
More informationLayered media and photonic crystals. Cord Arnold / Anne L Huillier
Layered media and photonic crystals Cord Arnold / Anne L Huillier Definition A photonic crystal is a periodic arrangement of a dielectric material that exhibits strong interaction with light Variation
More informationMPO LGX Cassette Module
DATASHEET Product updated on November 19, 2018 MPO LGX Cassette Module MPO LGX Cassette Modules provide secure transition between MPO and LC or SC discrete connectors. They are used to interconnect MPO
More informationLASER TO FIBER COUPLER WITH ADJUSTABLE FOCUS USA PATENT #
LASER TO FIBER COUPLER WITH ADJUSTABLE FOCUS USA PATENT #7431513 Features: Can handle powers up to 100 W CW Patented connector designs for precise coupling with focus adjustment Excellent coupling efficiency
More informationConnectorMax MPO Link Test Solution A COMPLETE MPO POLARITY, CONTINUITY AND CONNECTOR INSPECTION SOLUTION FOR SHORT FIBER LINKS (UP TO 5 KM)
A COMPLETE MPO POLARITY, CONTINUITY AND CONNECTOR INSPECTION SOLUTION FOR SHORT FIBER LINKS (UP TO 5 KM) All-in-one, easy-to-use solution to validate the polarity type, continuity and connector cleanliness
More informationOptical fibers. Biossensores, Mestrado Integrado em Engª. Electrónica e Telecomunicações)
Optical fibers Outline Fundamental Components and Concepts. Intensity Based and Fabry-Perot Interferometric Sensors. Applications of the Fiber Optic Sagnac Interferometer. The Mach-Zehnder and Michelson
More informationUniCam High-Performance Connectors, Multimode and Single-Mode
Features and Benefits Broad operating temperature (-40 to +75 C) Utility and flexibility Factory-polished end face Consistent optical performance Fast termination and no consumables Low installation cost
More informationFiberLink 6650 Series
MANUAL FiberLink 6650 Series Optical Power Meter Installation and Operations Manual WWW.ARTEL.COM Contents Contents Welcome... 3 Features... 3 Package Contents... 3 Technical Specifications... 4 Applications
More informationSerial to Fiber Optic Converter Technical Guide
Serial to Fiber Optic Converter Technical Guide TABLE OF CONTENTS OVERVIEW... 3 Introduction to Fiber Optics... 3 Fiber Optic System Overview... 4 INSTALLATION & WIRING... 5... 5 Setting the Dip-Switches...
More informationInstallation Guide. 100BASE-TX/100BASE-FX Fast Ethernet Media Converter NC-200FT/FC. -1-iIiNC-200FT/FC P/N:
Installation Guide 100BASE-TX/100BASE-FX Fast Ethernet Media Converter NC-200FT/FC -1-iIiNC-200FT/FC P/N:750-0166-001 Table le of Contents General Description...3 Specifications...4 Connectors & Cables...5
More informationWhite Paper. March Random mating IL vs. Ky Ly - Senior Staff Engineer
White Paper March 2012 Random mating IL vs. IL by Master Jumper Ky Ly - Senior Staff Engineer Random mating IL vs. IL by Master Jumper Contents 4 Introduction 4 Insertion Loss 5 Random Mating 5 Connector
More informationLEAD Fiber Optics PRODUCT CATALOGUE
LEAD Fiber Optics PRODUCT CATALOGUE FIBER OPTIC ATTENUATOR Fixed plug-in type TEL:+886-2-8672-2371 FAX:+886-2-8672-3275 Web:http://www.twfiberoptic.com Fixed plug in type Attenuator Fixed plug in fiber
More informationDC Network Connectivity
DC Network Connectivity Options & Optimizing TCO Rakesh SAMBARAJU - Application Engineer Nexans Data Center Solutions Agenda l Part I Ethernet Standards and Technologies Ø Current Ethernet Standards Ø
More informationPolymer Coated Fiber Cable (PCF)
Polymer Coated Fiber Cable (PCF) Panduit has introduced a Polymer Coated Fiber (PCF) to their fiber cable offering available in 50µm and 62.5µm core diameters. Along with this cable having a stronger durability
More informationProduct information 19" 1U UniRack 24xLC-Duplex OM4, PC, ceramic, Bm/3 R816749
Product information 19" 1U UniRack 24xLC-Duplex OM4, PC, ceramic, Bm/3 R816749 1 Pcs. Front panel with staggered arrangement of adapters. 19" 1U slide-in unit, splice tray plate with 2 splice trays radius
More informationSerial to Fiber Optic Converter
Serial to Fiber Optic Converter Preliminary - 2-9-2009 WattMaster Controls, Inc. 8500 NW River Park Drive Parkville, MO 64152 Toll Free PH: (866) 918-1100 PH: (816) 505-1100 FAX: (816) 505-1101 E-mail:
More informationLightBend TM Dual 2x2 Bypass Multimode Fiberoptic Switch
(Bidirectional) (Protected by U.S. patent 6823102 and pending patents) Features Low Optical Distortions 8 Ports Integration High Isolation High Reliability Fail-Safe Latching Epoxy-Free Optical Path Low
More informationPCS PATCH CORD SOLUTIONS PATCH CORD SOLUTIONS
Structured Cabling Solutions PCS PATCH CORDS. HiPerlink 6 Colored Patch Cords- 35,36 HiPerlink 1000 Category 5e Colored Patch Cords- 35,36 Snap-in Icons 36 ScTP Category 5 Patch Cord 37 Category 5 Colored
More information37 (19) - channel micromachined deformable mirror system: typical technical passport
F L E X I B L E Flexible Optical B.V. Adaptive Optics Optical Microsystems Wavefront Sensors O P T I C A L Oleg Soloviev Chief Scientist Röntgenweg 1 64 BD, Delft The Netherlands Tel: +31 1 1-4 Fax: +31
More informationFiber optic converter audio and CAN TA OPERATION MANUAL
Fiber optic converter audio and CAN TA-110.1 IOA110-1 March 2009 LANEX S.A., Technical support: tel. ul.ceramiczna 8, 20-150 Lublin tel. +48 81 443 96 36 Contents 1. General Characteristics.... 5 1.1.
More informationTrends in Testing Data Center Infrastructure. Ed Gastle VIAVI Solutions
Trends in Testing Data Center Infrastructure Ed Gastle VIAVI Solutions Agenda INTRODUCTION Modern Data Center Architecture Historically Enterprise has been a 3 tier topology Core, Aggregation, Access Cloud
More informationPre-polished Connector Insertion Loss and Termination Yield. Achieving High Termination Yields And Low Insertion Loss Values
Pre-polished Connector Insertion Loss and Termination Yield Achieving High Termination Yields And Low Insertion Loss Values White Paper 1/2004 Executive Summary Pre-polished connectors offer a quick and
More informationWhite Paper: BERT Baseline Polish versus Polishing Process 2
White Paper: BERT Baseline Polish versus Polishing Process 2 By Curtis Wright, ECE Electrical Engineer, R&D Introduction Bit Error Rate Testing (BERT) provides cabling and connectivity manufacturers with
More informationLC Connector. A High Density Fiber Optic Network Solution. Paul Kolesar Lucent Technologies, Bell Laboratories
A High Density Fiber Optic Network Solution Paul Kolesar Lucent Technologies, Bell Laboratories IEEE 802.3z Gigabit Ethernet March, 1997 Outline Design Background and Goals Product Family Overview Features
More informationDIAMOND Fiber Optic Components
DIAMOND Fiber Optic Components NETWORK ACCESSORIES Hybrid family PC/APC MULTIMODE PC DESCRIPTION In-line hybrid adapter are used to directly mate connectors with different mechanical interface. Their optical
More informationFUSION SPLICERS Splicing Made Easy and Affordable
PRODUCTS 2018 FUSION SPLICERS Splicing Made Easy and Affordable Ilsintech s fiber optic fusion splicers provide best-in-class optical performance with a simplistic design, making installs for any application
More informationCatalog Single-Mode Fiber Coupled Laser System. SingleMode Fiber Coupled Diode Laser System
SingleMode Fiber Coupled Diode Laser System 405nm,635nm,650nm,670nm,685nm,785nm, 830nm,850nm,880nm,1310nm,1550nm 1mW to 60mW Output Power PM fiber/sm fiber( MM fiber Optional) CW/TTL/Analog Modulation
More informationStudy of Mode Characteristics of Glass Optical Fibers LABORATORY MANUAL: TESTER MCS-04
Study of Mode Characteristics of Glass Optical Fibers LABORATORY MANUAL: TESTER MCS-04 1. Definition and Computation of Numerical Aperture 2. Definition and Computation of V Number & Computation 3. Specifications
More information3M Passive Optical Splitter Shelves and Modules
Communication Markets Division 3M Passive Optical Splitter Shelves and Modules 3M offers a robust portfolio of passive optical fiber splitter products made to enable easy configuration, design, ordering,
More informationArtisan Technology Group is your source for quality new and certified-used/pre-owned equipment
Artisan Technology Group is your source for quality new and certified-used/pre-owned equipment FAST SHIPPING AND DELIVERY TENS OF THOUSANDS OF IN-STOCK ITEMS EQUIPMENT DEMOS HUNDREDS OF MANUFACTURERS SUPPORTED
More informationAPPLICATION NOTE DD-100
O Z OPTICS LTD. C A N A D A OZ OPTICS LTD. APPLICATION NOTE DD-100 OZ OPTICS FAMILY OF OEM MOTOR DRIVEN ATTENUATORS The information/data furnished in this document shall not be duplicated, used or disclosed
More informationFlexNAP System Component Polarity
Engineering Services Department 800 17th St NW PO Box 489 Hickory, North Carolina 28603-0489 800 743-2671 f 828 901-5533 www.corning.com/opcomm FlexNAP System Component Polarity AEN111, Revision 2 The
More informationLensed Connector Cleanliness Specification Development
Lensed Connector Cleanliness Specification Development Presented by: Doug Wilson FiberQA Optical Interconnects 2016 May 10, 2016 San Diego, California Cleanliness Specification for Expanded Beam Connectors
More informationOverview of WT&T LED light sources (fiber-coupled and free-space) WT&T Inc. Contact:
Overview of WT&T LED light sources (fiber-coupled and free-space) WT&T Inc. Contact: sales@wttechnology.com 2005-2015 WT&T Inc, all rights reserved Compact, high power, single channel fiber-coupled LED
More informationFour opto-isolated signal channels: SD, RD, RTS, and CTS. Electrical compatibility with RS-485. A 5V DC/DC converter for power isolation
July 2000 RS-4 Port Isolator IC0ACC03 The IC0ACC03 RS-4 Port Isolator replaces the obsolete ICCMM0 Isolated Repeater/Converter (also known as the Brick ). This Port Isolator provides the basic functionality
More informationEC Series LC Connectors
EC Series LC Connectors Amphenol s data communications EC Series fiber optic LC small form factor (SFF) connectors utilize the familiar RJ-45 latching mechanism. The LC connector is almost half the size
More informationPretium EDGE HD Solutions A LANscape Pretium Solutions Product
Pretium EDGE HD Solutions for Enterprise Data Centers and Storage Area Networks Corning Pretium EDGE HD solutions create a fiber optic tip-to-tip solution for data centers and storage area networks (SANs)
More informationOSIS by Radiall One Step Interconnection Solution
FIBER OPTIC AND MULTISIGNAL APPLICATIONS OSIS by Radiall One Step Interconnection Solution Introduction The easiest outdoor interconnection solution: in only one click! To meet the requirements of telecommunication
More informationMEMS PACKAGES AND MOUNTS GUIDE
MEMS PACKAGES AND MOUNTS GUIDE Last Updated: 11/27/2017 Mirrorcle Technologies, Inc. Overview Mirrorcle Technologies Inc. ( MTI ) MEMS mirrors are available in the following standard ceramic packages:
More informationLight and refractive index
17 Fig. 7.1 shows a ray of light incident on a rectangular glass block at point X. W P X air glass Q R S Fig. 7.1 The ray of light is refracted at X. On Fig. 7.1, (a) draw the normal at X, [1] (b) draw
More information