ECP NORTROLL CABLETROLL 2350 FPI INSTALLATION AND COMMISSIONING PROCEDURE

Size: px
Start display at page:

Download "ECP NORTROLL CABLETROLL 2350 FPI INSTALLATION AND COMMISSIONING PROCEDURE"

Transcription

1 Network(s): Summary: ENGINEERING COMMISSIONING PROCEDURE ECP NORTROLL CABLETROLL 2350 FPI INSTALLATION AND COMMISSIONING PROCEDURE EPN, LPN, SPN This document details the installation, testing and commissioning procedures for the Nortroll CableTroll 2350 fault passage indicator. Owner: Kevin Burt Approved By: Steve Mockford Approved Date: 16/01/2015 This document forms part of the Company s Integrated Business System and its requirements are mandatory throughout UK Power Networks. Departure from these requirements may only be taken with the written approval of the Director of Asset Management. If you have any queries about this document please contact the author or owner of the current issue. Applicable To UK Power Networks All UK Power Networks Asset Management Capital Programme Connections HSS&TT Network Operations UK Power Networks Services Other External G81 Website Contractors ICPs/IDNOs Meter Operators THIS IS AN UNCONTROLLED DOCUMENT, THE READER MUST CONFIRM ITS VALIDITY BEFORE USE

2 Revision Record Version 6.0 Review Date 05/01/2019 Date 05/01/2015 Author Stephen Tucker Why has the document been updated: Document revised to incorporate revised settings for the LPN interconnected network following an incident investigation. The revised settings will enable operational restriction HSS 406-ORE-41 to be removed from sites where the updated settings are applied. Associated documents ECP a and 0521b updated accordingly with the update of this document. What has changed: Overcurrent setting disabled for LPN interconnected network (Clause 11.8). Test form ECP a and ECP b updated to incorporate the above change. Version 5.0 Review Date 30/09/2018 Date 09/10/2012 Author Stephen Tucker Dip-switch SW4-8 check added. Reviewed for G81 website Version 4.2 Review Date Date 08/07/2012 Author John Lowe Reclassification of document from Installation and Commissioning Manual 5.21 Version 4.1 Review Date Date 18/03/2011 Author Jerry Wells Document rebranded Version 4.0 Review Date Date 10/02/2010 Author Stephen Tucker General update to make the document more usable. Remote output settings updated for the Lucy Gemini 2 RTU. New test form for earth fault only units added Version 3.0 Review Date Date 17/11/2006 Author Stephen Tucker Remote output settings corrected. Primary and secondary injection tests modified Version 2.0 Review Date Date 24/10/2006 Author Stephen Tucker Default timer reset changed to 6 hours, mounting details enhanced and RTU test simulators added Version 1.0 Review Date Date 29/09/2006 Author Stephen Tucker Original UK Power Networks 2015 All rights reserved 2 of 20

3 Contents 1 Introduction Scope References Abbreviations and Definitions Description Installation Materials Test Equipment Installation of a CableTroll 2350 with a New Split Core-balance CT Installation of a CableTroll 2350 with an Existing Core-balance CT Installation of a CableTroll 2350 with Phase CTs Configuration Core-balance CT Tests Phase CT Tests Setup Primary Injection Earth Fault Test Secondary Injection Overcurrent Test On-Load Tests Final Checks Asset Data Test Equipment Certification Appendix A Dimensions Appendix B Schematics B.1 Typical Schneider RN2/6c FPI Connections B.2 Typical Lucy VRN2/6a FPI Connections UK Power Networks 2015 All rights reserved 3 of 20

4 Figures Figure 5-1 Notroll CableTroll 2350 Fault Passage Indicator... 6 Figure 8-1 CableTroll 2350 main PCB with Terminals and Dip Switches Shown... 8 Figure 8-2 Triplex Cable Cable Screen and Earth through Internal CT... 9 Figure 8-3 Triplex Cable Cable Screen and Earth through External CT... 9 Figure 8-4 Three-core Cable Cable Screen and Earth through External CT... 9 Figure 8-5 Three-core Cable Cable Screen terminated before CT and no Earth through CT... 9 Figure 8-6 Split CORE-balance CT Installation Figure 11-1 CableTroll 2350 Display Card Showing Connections and Dip Switches Figure 13-1 CT Shorting-link in Place Figure 13-2 CT Shorting-link Opened Figure 13-3 CT Wiring Lopped Together UK Power Networks 2015 All rights reserved 4 of 20

5 1 Introduction 1.1 This document details the installation, testing and commissioning procedures for the Nortroll CableTroll 2350 fault passage indicator (FPI). These tests shall be satisfied before the FPI can be accepted as fit for service and energisation. 1.2 This procedure shall be carried out by the Commissioning Engineer or his appointed representative, who shall be Competent Person having appropriate training and experience. 1.3 This procedure shall be carried out in accordance with the requirements of the UK Power Networks Distribution Safety Rules. 1.4 This procedure shall be carried out with regard to the requirements and recommendations of the manufacturer. If conflict exists between the requirements of the manufacturer and those of UK Power Networks the matter shall be referred to Asset Management (or your UK Power Networks nominated contact). 1.5 The results of all observations, tests, adjustments and all relevant remarks shall be recorded on the associated test form. 2 Scope 2.1 This procedure and the associated test form apply to the CableTroll 2350 fault passage indicator. The installation of a split core-balance current transformer (CT) is also covered. 2.2 This procedure is intended for use by UK Power Networks field staff, contractors and external connection providers. 3 References 3.1 This procedure should be read in conjunction with the following references: EOS Fault Passage Indicators. Nortroll CableTroll 2350 User Guide (available from Alfresco Engineering Library > Reference Library > Manufacturers > Nortroll). 3.2 This procedure should be used with the following test forms: ECP a Nortroll CableTroll 2350 FPI Overcurrent and Earth Fault Test Form. ECP b Nortroll CableTroll 2350 FPI Earth Fault Only Test Form. UK Power Networks 2015 All rights reserved 5 of 20

6 4 Abbreviations and Definitions 4.1 The following abbreviations and definitions are used throughout this procedure. Term Alfresco ART CT FPI RTU Definition UK Power Networks Document Library UK Power Networks Asset Registration Team Current Transformer Fault Passage Indicator Remote Terminal Unit 5 Description 5.1 The CableTroll 2350 (Figure 5-1) is a battery powered fault passage indicator for detecting overcurrent and earth faults on underground cable networks operating at voltages up to and including 36kV. It can be used with either three FPI phase CTs (fitted as standard in the left-hand cable box of all new ring main units) or, where phase CTs are not fitted, a core-balance CT can be used (but this will only provide an earth fault indication). Therefore the CableTroll 2350 is suitable as a replacement for older type earth fault indicators (EFI) using a core-balance CTs. Note: New core-balance CTs have a 60/1 ratio, however, existing core-balance CTs with a 60/1 or a 40/1 ratio can also be found on the networks. R CableTroll 2350 Earth Fault Test Made in Norway Over current Reset 0 Batt SN: Manufactured: Battery date: CE Figure 5-1 Notroll CableTroll 2350 Fault Passage Indicator UK Power Networks 2015 All rights reserved 6 of 20

7 5.2 The CableTroll 2350 includes the following functionality: Two high visibility LEDs for the indication of an overcurrent or earth fault. An output contact for remote indication. A self-reset. A local and remote reset. A local test facility. Built-in commissioning tests. 10 year battery life. 5.3 The CableTroll 2350 has two built in tests to assist with commissioning. The first test checks whether there is any zero sequence (residual) current flowing. Zero sequence current generally only flows during an earth fault; however, there will always be a low level of zero sequence current flowing due to network imbalance. This test determines whether the zero sequence current is above 15A. 5.4 The second test checks for load current (this test is only applicable if three 500/1 phase CTs are being used and the circuit load is above 15A per phase) and is an indication that the CTs are connected correctly. 6 Installation Materials 6.1 The following materials are required to undertake the installation of a CableTroll 2350 using a split core-balance CT: Nortroll CableTroll 2350 (14731H). Split core-balance CT (14733C). 1.5mm 2 2-core PVC insulated and PVC sheathed cable (BS 6500:1994 code 3182Y). 1.5mm 2 4-core PVC insulated and PVC sheathed cable - only required if remote indication/reset is used (BS 6500:1994 code 3184Y). 2 BA nuts, bolts and washers for securing the CableTroll Contact grease. Note: If the CableTroll 2350 is supplied with the switchgear these items are not required. 7 Test Equipment 7.1 The following test equipment is required to carry out the tests detailed in this procedure: Secondary Current Injection Test Set (range 0.1A to 100A). Injection device capable of injecting 60A (core-balance CT installations only). RTU simulator (LPN Remsdaq RTU only). UK Power Networks 2015 All rights reserved 7 of 20

8 8 Installation of a CableTroll 2350 with a New Split Core-balance CT 8.1 Connect a 1.5mm 2 2-core cable to the CT via the gland. 8.2 Separate the two halves of the CT by removing the stainless steel band. 8.3 Position the CT correctly around the cable, with particular reference to Paragraph Figure 8-2, Figure 8-3, Figure 8-4 and Figure 8-5. Fit the jubilee clip supplied with the CT loosely around the cable. 8.4 Fit the removable half of the CT in position and secure to the cable using the cable clamps and jubilee clip. 8.5 Remove the front cover of the CableTroll Mount the CableTroll 2350 on the switchgear supporting legs on the side nearest to where the CT will be installed. The CableTroll 2350 only requires two of the four fixings to be used to secure it in place. Note: The CableTroll 2350 box has four fixing holes, one in each corner with 110mm between vertical centres and 90mm between horizontal centres. Full dimensions are given in Appendix A. 8.7 Connect the CT to terminals J3/S1 and J3/S2 on the CableTroll 2350 (refer to Figure 8-1) via the gland, ensuring there is sufficient cable to reach the CT position. Display Card Connector PC Download Connector Battery Terminal 2: External Indication 3: External Indication J8 J2 J6 J1 S1 SW3SW4 J3 J4 S2: CT 1 S1: CT 1 S2: CT 2 S1: CT 2 500/1 60/1 40/1 500/1 1: External Reset 2: External Reset J5 S1: CT 3 S2: CT 3 500/1 Battery Reset Button Figure 8-1 CableTroll 2350 main PCB with Terminals and Dip Switches Shown 8.8 Before the other half of the CT is installed, wipe the contact faces to ensure they are clean and apply thin coating of contact grease to the faces. 8.9 Mate the two halves of the CT together ensuring the locating marks agree and that any neoprene washers are not trapped between the faces Tighten the stainless steel band securing the two halves of the CT. UK Power Networks 2015 All rights reserved 8 of 20

9 8.11 If the cable earth screen passes through the CT, the earth shall also pass through the CT. Refer to examples in Figure 8-2, Figure 8-3 and Figure 8-4. This is to ensure that currents in the screens are cancelled, and that the CT only measures the earth fault current in the cable cores. Note: On modern switchgear the switchgear earth stud is insulated from the gland plate and the cable screen is terminated onto the insulated earth stud, either inside or outside the cable box. Core-balance CT Insulated earth stud Insulated earth stud Core-balance CT Figure 8-2 Triplex Cable Cable Screen and Earth through Internal CT Figure 8-3 Triplex Cable Cable Screen and Earth through External CT Insulated cable gland Core-balance CT Insulated cable gland Core-balance CT Cable screen brought out for termination before CT Figure 8-4 Three-core Cable Cable Screen and Earth through External CT Figure 8-5 Three-core Cable Cable Screen terminated before CT and no Earth through CT UK Power Networks 2015 All rights reserved 9 of 20

10 8.12 If the cable earth screen does not pass through the CT, as shown in Figure 8-5, there is no need for the switchgear earth to pass through the CT Where the earth passes through the CT rotate the CT so that the edge of the removable part of the CT lines up with the edge of the earth as shown in Figure 8-6. This should make an angle of 70 between the earth and the terminal box for optimum performance. Removable part Neoprene washers Locating marks Earth Jubilee clip 70 degrees (angle for optimum performance) Figure 8-6 Split CORE-balance CT Installation 8.14 Adjust the CT support bracket(s) so that the cable is centrally positioned in the CT and re-tighten If required, connect the remote output and remote reset, from the RTU, to terminals J6 and J8 respectively (refer to Figure 8-1) using a 1.5mm 2 4-core cable Check all connections and glands are adequately tightened Commission and test CableTroll 2350 according to Sections 11 and 12. UK Power Networks 2015 All rights reserved 10 of 20

11 9 Installation of a CableTroll 2350 with an Existing Core-balance CT 9.1 Disconnect the CT from the old earth fault indicator. 9.2 Remove the front cover of the CableTroll Mount the CableTroll 2350 on the switchgear supporting legs on the side nearest to the CT. The CableTroll 2350 only requires two of the four fixings to be used to secure it in place. Note: The CableTroll 2350 box has four fixing holes, one in each corner with 110mm between vertical centres and 90mm between horizontal centres. Full dimensions are given in Appendix A. 9.4 Connect the CT to terminals J3/S1 and J3/S2 on the CableTroll 2350 (refer to Figure 8-1) via the gland, ensuring there is sufficient cable to reach the CT position. 9.5 If required, connect the remote output and remote reset, from the RTU; to terminals J6 and J8 respectively (refer to Figure 8-1). 9.6 Check all connections and glands are adequately tightened. 9.7 Commission and test CableTroll 2350 according to Sections 11 and Installation of a CableTroll 2350 with Phase CTs 10.1 Generally the CableTroll 2350 will have already been installed by the switchgear manufacturer and connected to the phase CTs in the cable box. However, if this is not the case follow the steps below Remove the front cover of the CableTroll Mount the CableTroll 2350 on the switchgear supporting legs on the side nearest to the CT, generally this will be adjacent to ring switch one. The CableTroll 2350 only requires two of the four fixings to be used to secure it in place. Note: The CableTroll 2350 box has four fixing holes, one in each corner with 110mm between vertical centres and 90mm between horizontal centres. Full dimensions are given in Appendix A Connect the CTs to terminals J3/S1, J3/S2, J4/S1, J4/S2, J5/S1 and J5/S2 on the CableTroll 2350 (refer to Figure 8-1) via the gland according to the schematics shown in Appendix B If required, connect the remote output and remote reset, from the RTU, to terminals J6 and J8 respectively (refer to Figure 8-1) according to the schematics shown in Appendix B Check all connections and glands are adequately tightened Commission and test CableTroll 2350 according to Sections 11 and 13. UK Power Networks 2015 All rights reserved 11 of 20

12 11 Configuration 11.1 Record the substation and CableTroll 2350 details on the relevant test form ECP a (overcurrent and earth fault) ECP b (earth fault only) Carry out a visual inspection of the CableTroll 2350 to check that it is undamaged and correctly mounted and secured Remove the front cover Connect the battery and press the Battery Reset button on PCB Press the Test button on the front of the unit. The earth fault and overcurrent LEDs should be illuminated in turn followed by LED 0 which should be green (if LED 0 is red the battery test has failed and the battery should be replaced) The CableTroll 2350 has a number of configurable settings. The default settings and the available settings are shown below. Parameter Default Dip-switch Options Overcurrent Threshold 625A SW3-1 = 0, SW3-2 = 0, SW3-3 = 1 OFF, 250A, 375A, 500A, 625A, 750A Earth Fault Threshold 50A SW3-6 = 0 OFF, 50A CT Type 500/1 SW3-8 = 0 500/1, 60/1 Earth Fault CT Type 60/1 SW3-7 = 0 60/1, 40/1 Timer Reset 6h SW3-4 = 0, SW3-5 = 1 OFF, 3h, 6h, 12h Remote Output Fleeting SW4-1 = 1 Fleeting, Latched Remote Reset Yes - None Output Relay H SW4-8=1 F, H 11.7 The settings can be changed using the dip-switches inside the unit. The function of each dip-switch is shown on the display card on the inside of the lid (refer to Figure 11-1). UK Power Networks 2015 All rights reserved 12 of 20

13 Figure 11-1 CableTroll 2350 Display Card Showing Connections and Dip Switches 11.8 Select the appropriate overcurrent setting according to the table below using dipswitches SW3-1, SW3-2 and SW3-3. Parameter Network Setting SW3-1 SW3-2 SW3-3 Overcurrent Threshold LPN Interconnected OFF LPN Non-interconnected 625A EPN, SPN 625A EPN, SPN beyond pole mounted reclosers where NOP fault level 25MVA 250A Note: If the CableTroll 2350 is only being used as an earth fault indicator set the overcurrent threshold to OFF Check that timer reset is set to 6 hours according to the table below using dipswitches SW3-4 and SW3-5. Parameter Setting SW3-4 SW3-5 Timer Reset 6h Check that the earth fault has been enabled according to the table below using dip-switch SW3-6. Parameter Setting SW3-6 Earth Fault Enable 0 UK Power Networks 2015 All rights reserved 13 of 20

14 11.11 Select the appropriate CT ratio according to the table below using dip-switches SW3-8 and SW3-7. FPI phase CTs have a 500/1 ratio and new core-balance CTs have a 60/1 CT ratio. Parameter Setting SW3-8 SW3-7 CT Ratio 500/ / / If the CableTroll 2350 is connected to an RTU select the appropriate remote output type according to the table below using dip-switch SW4-1. Parameter Setting SW4-1 Lucy Gemini 2 RTU Remote Output Latched 1 Remsdaq RTU Remote Output Latched Check that the output relay type is set correctly according to the table below using dip-switch SW4-8. This parameter was introduced on all units from September 2011 which is labelled with an H. This parameter should be correctly set in the factory. Parameter Setting SW4-8 Output relay type F (no H label fitted) Off 0 Output relay type H (H label fitted) On On completion of the configuration press the Reset button on the front of the unit Record the selected settings on the test form. UK Power Networks 2015 All rights reserved 14 of 20

15 12 Core-balance CT Tests 12.1 Carry out a primary injection test from the CT to test the earth fault threshold Connect the injection test set through the core-balance CT. Increase the injection current until earth fault LED on the CableTroll 2350 illuminates this should be around 60A for a 60/1 or 40/1 CT Record the actual current on the test form If applicable, confirm that the appropriate indication is shown on the RTU or RTU simulator Reset the CableTroll Disconnect the test set. UK Power Networks 2015 All rights reserved 15 of 20

16 13 Phase CT Tests 13.1 Setup Check the 500/1 phase CTs have been satisfactorily tested during the switchgear commissioning Check that any manual CT shorting-link has been opened or removed for the 500/1 phase CTs. An example is shown in Figure 13-1 and Figure Note: The CT shorting arrangement used will be dependent on the type of switchgear. Figure 13-1 CT Shorting-link in Place Figure 13-2 CT Shorting-link Opened Check that the CT (and, if fitted, the remote output and remote reset) wiring is correctly terminated in the CableTroll Note: If there are only four cores for the CT wiring, terminals J3/S2, J4/S2 and J5/S2 in the CableTroll 2350 must be looped together, an example is shown in Figure Figure 13-3 CT Wiring Lopped Together If appropriate, check that the RTU or RTU simulator (LPN only) is connected to the switchgear. UK Power Networks 2015 All rights reserved 16 of 20

17 13.2 Primary Injection Earth Fault Test Carry out a primary injection test from the relevant cable box to test the earth fault threshold Close the earth switch associated with the cable box under test Connect the injection test set between the L1 phase bushing in the cable box and switchgear earth. Increase the injection current until earth fault LED on the CableTroll 2350 illuminates this should be around 50-60A Record the actual current on the test form If applicable, confirm that the appropriate indication is shown on the RTU or RTU simulator Reset the CableTroll 2350 and repeat for phase L2 and L3. The earth fault threshold should be similar in all three tests Disconnect the test set Secondary Injection Overcurrent Test Carry out a secondary injection test from the CT terminal block on the switchgear to test overcurrent threshold Check that one side of each CT is connected together most switchgear is supplied with this configuration but if this is not the case use a shorting-link as necessary Connect the injection test set across the L1-L2 phase CT at the CT terminal block. Increase the injection current until overcurrent LED on the CableTroll 2350 illuminates this should operate according the values given in the table. Setting (A) Approx Secondary Operating Current (A) Record the actual current on the test form Reset the CableTroll 2350 and repeat for phase CTs L2-L3 and L3-L1. The overcurrent threshold should be similar in all three tests If applicable, remove the shorting link applied in step Disconnect the test set. UK Power Networks 2015 All rights reserved 17 of 20

18 13.4 On-Load Tests Carry out these tests with both ring switches closed after the switchgear is connected to the HV network and energised Press and hold the test button, press the reset button and then release both to initiate the built-in commissioning tests. LEDs 0, 1, 2, and 3 will light briefly and indicate the following: Zero sequence test if LED 0 is green the zero sequence current is below 15A and is okay. If LED 0 is red the zero sequence (earth fault) current is above 15A and indicates that there is a problem with the CTs or CT wiring or there is an earth fault on the network. This should be investigated further. Load current check if LED 1, 2 or 3 is yellow a load current above 25A is flowing in the respective phase. If the actual load at the site is expected to be above 25A on each phase and any of the LEDs 1, 2 or 3 are not illuminated then this indicates that the CTs are incorrectly connected or that there is a wiring fault between the CTs and the CableTroll This should be investigated further. 14 Final Checks 14.1 Check the CT shorting-link has been removed if applicable Check all connections secure Check front cover is secure. 15 Asset Data 15.1 Complete the asset data form and either send it to the Asset Registration Team (ART), it to the appropriate mailbox (ART.EPN@ukpowernetworks.co.uk, ART.LPN@ukpowernetworks.co.uk, ART.SPN@ukpowernetworks.co.uk) or send it to your UK Power Networks nominated contact. 16 Test Equipment 16.1 Record the purpose, make, type and serial number of all test equipment used during commissioning on the test form. 17 Certification 17.1 When all the tests have been satisfactorily completed, sign and date the test form. Place a copy of the test form on-site in a plastic wallet and in a secure location. UK Power Networks 2015 All rights reserved 18 of 20

19 Appendix A Dimensions A Section A-A A Cable Entry UK Power Networks 2015 All rights reserved 19 of 20

20 Appendix B Schematics Typical FPI connections for secondary switchgear are shown below. Refer to the switchgear commissioning procedures ECP and ECP for more detailed schematic drawings. B.1 Typical Schneider RN2/6c FPI Connections B.2 Typical Lucy VRN2/6a FPI Connections UK Power Networks 2015 All rights reserved 20 of 20

ECP SECONDARY SUBSTATION COMMISSIONING PROCEDURE

ECP SECONDARY SUBSTATION COMMISSIONING PROCEDURE Document Number: ECP 11-0501 Network(s): Summary: ENGINEERING COMMISSIONING PROCEDURE ECP 11-0501 SECONDARY SUBSTATION COMMISSIONING PROCEDURE EPN, LPN, SPN This procedure details the end-to-end process

More information

EOS SCHNEIDER RINGMASTER 'C' RANGE SWITCHGEAR

EOS SCHNEIDER RINGMASTER 'C' RANGE SWITCHGEAR Document Number: EOS 03-0018 Network(s): Summary: ENGINEERING OPERATION STANDARD EOS 03-0018 SCHNEIDER RINGMASTER 'C' RANGE SWITCHGEAR EPN, LPN, SPN This standard details the installation, commissioning

More information

EOS LUCY SABRE 'A' RANGE SWITCHGEAR

EOS LUCY SABRE 'A' RANGE SWITCHGEAR Document Number: EOS 03-0027 Network(s): Summary: ENGINEERING OPERATION STANDARD EOS 03-0027 LUCY SABRE 'A' RANGE SWITCHGEAR EPN, LPN, SPN This standard details the installation, commissioning and operation

More information

ECS LUCY GEMINI 3 CONFIGURATION PROCEDURE

ECS LUCY GEMINI 3 CONFIGURATION PROCEDURE Document Number: ECS 05-9541 Network(s): Summary: ENGINEERING CONSTRUCTION STANDARD ECS 05-9541 LUCY GEMINI 3 CONFIGURATION PROCEDURE EPN, LPN, SPN This document details the configuration procedure for

More information

EOS LUCY GEMINI 3 TYPE E RTU

EOS LUCY GEMINI 3 TYPE E RTU Document Number: EOS 05-9305 Network(s): Summary: ENGINEERING OPERATION STANDARD EPN, LPN, SPN EOS 05-9305 LUCY GEMINI 3 TYPE E RTU This standard details the application, installation and operation of

More information

EDS SCADA NUMBERING SYSTEM

EDS SCADA NUMBERING SYSTEM Document Number: EDS 05-9007 Network(s): Summary: EPN, LPN, SPN ENGINEERING DESIGN STANDARD EDS 05-9007 SCADA NUMBERING SYSTEM This standard describes the system for numbering SCADA wiring within switchgear

More information

EDS MW AND MVAR TRANSDUCER CONNECTION

EDS MW AND MVAR TRANSDUCER CONNECTION Document Number: EDS 05-5001 Network(s): Summary: ENINEERIN DESIN STANDARD EDS 05-5001 MW AND MVAR TRANSDUCER CONNECTION EPN, LPN, SPN This standard details the convention to be used when wiring MW and

More information

EOS REMSDAQ CALLISTO NX TYPE E RTU

EOS REMSDAQ CALLISTO NX TYPE E RTU Document Number: EOS 05-9306 Network(s): Summary: ENGINEERING OPERATING STANDARD EOS 05-9306 REMSDAQ CALLISTO NX TYPE E RTU EPN, LPN, SPN This standard details the application, installation and operation

More information

ECS TYPE E RTU AND ANCILLARY ITEMS INSTALLATION PROCEDURE

ECS TYPE E RTU AND ANCILLARY ITEMS INSTALLATION PROCEDURE Document Number: ECS 05-9540 Network(s): Summary: ENGINEERING CONSTRUCTION STANDARD ECS 05-9540 TYPE E AND ANCILLARY ITEMS INSTALLATION PROCEDURE EPN, LPN, SPN This procedure details the installation,

More information

EBB PILOT FOR THE LIVE CONNECTION OF UNMETERED EQUIPMENT TO OVERHEAD LINES

EBB PILOT FOR THE LIVE CONNECTION OF UNMETERED EQUIPMENT TO OVERHEAD LINES Network(s): Summary: ENGINEERING BULLETIN EBB 08-0061 PILOT FOR THE LIVE CONNECTION OF UNMETERED EQUIPMENT TO OVERHEAD LINES EPN, SPN This bulletin provides a framework for the pilot scheme for unmetered

More information

ECP GPRS/3G/4G COMMS DEVICE CONFIGURATION AND COMMISSIONING PROCEDURE

ECP GPRS/3G/4G COMMS DEVICE CONFIGURATION AND COMMISSIONING PROCEDURE Network(s): Summary: ENGINEERING COMMISSIONING PROCEDURE ECP 11-0601 GPRS/3G/4G COMMS DEVICE CONFIGURATION AND COMMISSIONING PROCEDURE EPN, LPN, SPN Configuration and commissioning procedure for the GPRS/3G/4G

More information

MESP TECHNICAL SPECIFICATION FOR A RECTIFIER UNIT CONTROL & PROTECTION SYSTEM FOR USE IN THE 1500V DC TRACTION SYSTEM

MESP TECHNICAL SPECIFICATION FOR A RECTIFIER UNIT CONTROL & PROTECTION SYSTEM FOR USE IN THE 1500V DC TRACTION SYSTEM Engineering Specification Electrical Networks TECHNICAL SPECIFICATION FOR A RECTIFIER UNIT CONTROL & PROTECTION SYSTEM FOR USE IN THE 1500V Version: 1 Issued: March 2014 Owner: Electrical Networks Asset

More information

EDS LONDON 33KV DISTRIBUTION NETWORK DESIGN AND CUSTOMER SUPPLIES

EDS LONDON 33KV DISTRIBUTION NETWORK DESIGN AND CUSTOMER SUPPLIES Network(s): Summary: ENGINEERING DESIGN STANDARD EDS 08-0150 LONDON 33KV DISTRIBUTION NETWORK DESIGN AND CUSTOMER SUPPLIES LPN This standard provides guidelines for the development of the 33kV distribution

More information

EDS KV, GRID AND PRIMARY SYSTEM PROTECTION AND CONTROL SCHEMES

EDS KV, GRID AND PRIMARY SYSTEM PROTECTION AND CONTROL SCHEMES Network(s): Summary: ENGINEERING DESIGN STANDARD EDS 05-0001 132KV, GRID AND PRIMARY SYSTEM PROTECTION AND CONTROL SCHEMES EPN, LPN, SPN This engineering design standard describes the requirements for

More information

EDS LV CUSTOMER UNMETERED SUPPLIES

EDS LV CUSTOMER UNMETERED SUPPLIES Document Number: EDS 08-2102 Network(s): Summary: ENGINEERING DESIGN STANDARD EDS 08-2102 LV CUSTOMER UNMETERED SUPPLIES EPN, LPN, SPN This standard details the requirements for unmetered single-phase

More information

INSTRUCTION MANUAL A141 High Level Audible Warning System

INSTRUCTION MANUAL A141 High Level Audible Warning System 24V DC (18V to 30V DC range) 115 or 230VAC (90V to 264V AC range) Operating Temp: -20 to +55 C IP Rating: IP65 Marking: 3) Installation Requirements 1) Introduction The A141 high level audible warning

More information

Independent Connections Provider (ICP) Unmetered Connections (UMC) Jointing to Services (UJ2S) Procedure

Independent Connections Provider (ICP) Unmetered Connections (UMC) Jointing to Services (UJ2S) Procedure Independent Connections Provider () Unmetered Connections (UMC) Jointing to Services (UJ2S) Procedure Owner Name Title Neil Clarke Head of Highway Services Signature Date 16 August 2018 Authoriser Name

More information

CABLETROLL 3 CABLETROLL CABLETROLL CABLETROLL CABLETROLL LED-2 5 CABLETROLL CABLETROLL REMOTE INDICATION 7

CABLETROLL 3 CABLETROLL CABLETROLL CABLETROLL CABLETROLL LED-2 5 CABLETROLL CABLETROLL REMOTE INDICATION 7 CABLETROLL 3 CABLETROLL 2310 4 CABLETROLL 2320 4 CABLETROLL 2330 5 CABLETROLL 2350 5 LED-2 5 CABLETROLL 2410 6 CABLETROLL 2440 6 REMOTE INDICATION 7 The CableTroll indicators are fault current detectors

More information

NPI800 NPI800R. First Handling Guide. Phase and earth overcurrent relay

NPI800 NPI800R. First Handling Guide. Phase and earth overcurrent relay Phase and earth overcurrent relay FOREWORD The aim of this handbook is to provide to the User information useful for the commissioning and the tests of NPI800 and NPI800R relays, multifunction digital

More information

GENERAL INFORMATION. The time it takes to find the fault The time it takes to repair the fault.

GENERAL INFORMATION. The time it takes to find the fault The time it takes to repair the fault. GENERAL INFORMATION Improve customer satisfaction Customer satisfaction is often difficult to measure. One of the key figures used to indicate the performance of a distribution network is SAIDI. SAIDI

More information

VAMP 221. Table of Contents

VAMP 221. Table of Contents 2 V221/EN M/E019 VAMP 221 Table of Contents Table of Contents 1. General... 7 1.1. VAMP 221 arc protection system components... 7 1.1.1. Central unit VAMP 221... 9 1.1.2. I/O units VAM 12L / VAM 12 LD,

More information

NPIH800 NPIH800R. First Handling Guide Earth overcurrent relay

NPIH800 NPIH800R. First Handling Guide Earth overcurrent relay Earth overcurrent relay FOREWORD The aim of this handbook is to provide to the User information useful for the commissioning and the tests of NPIH800 and NPIH800R relays, multifunction digital protections

More information

Source-Transfer Application Guide

Source-Transfer Application Guide S&C Model 6802 Automatic Switch Control Source-Transfer Application Guide Table of Contents Section Page Section Page Introduction Qualified Persons.... 2 Read this Instruction Sheet.... 2 Retain this

More information

SRI LANKA STANDARD CODE OF PRACTICE FOR GRID CONNECTED PHOTOVOLTAIC POWER SYSTEMS SLS 1522:2016

SRI LANKA STANDARD CODE OF PRACTICE FOR GRID CONNECTED PHOTOVOLTAIC POWER SYSTEMS SLS 1522:2016 SRI LANKA STANDARD CODE OF PRACTICE FOR GRID CONNECTED PHOTOVOLTAIC POWER SYSTEMS SLS 1522:2016 BY H S W Karunaratne Assistant Director - Engineering Sri Lanka Standards Institution. 1 DEFINITIONS Ac module:

More information

SOLARIMMERSION IV Advanced Installation Manual v1.9

SOLARIMMERSION IV Advanced Installation Manual v1.9 SOLARIMMERSION IV Advanced Installation Manual v1.9 1 Contents 1. Overview 2. Technical Specifications 3. Installation Mounting Electrical Installation Clamp Installation Wiring Diagrams 4. Installation

More information

IMPROVE CUSTOMER SATISFACTION 3 FUNCTIONAL DESCRIPTION 5 DETECTION PRINCIPLE 6 WHERE SHOULD INDICATORS BE INSTALLED AND WHAT MODEL SHOULD BE USED 7

IMPROVE CUSTOMER SATISFACTION 3 FUNCTIONAL DESCRIPTION 5 DETECTION PRINCIPLE 6 WHERE SHOULD INDICATORS BE INSTALLED AND WHAT MODEL SHOULD BE USED 7 IMPROVE CUSTOMER SATISFACTION 3 FUNCTIONAL DESCRIPTION 5 DETECTION PRINCIPLE 6 WHERE SHOULD INDICATORS BE INSTALLED AND WHAT MODEL SHOULD BE USED 7 LINETROLL 110Eµ 8 LINETROLL 111K 9 LINETROLL L400D 10

More information

MESP TECHNICAL SPECIFICATION FOR 22 kv METAL ENCLOSED SWITCHGEAR

MESP TECHNICAL SPECIFICATION FOR 22 kv METAL ENCLOSED SWITCHGEAR Engineering Specification Electrical Networks TECHNICAL SPECIFICATION FOR 22 kv Version: 2 Issued: 19 th December 2016 Owner: Chief Engineer Approved By: Andrew Russack Head of Engineering - Electrical

More information

OPERATING INSTRUCTIONS 7 SERIES STATIC GENERATORS

OPERATING INSTRUCTIONS 7 SERIES STATIC GENERATORS OPERATING INSTRUCTIONS 7 SERIES STATIC GENERATORS GB Contents Page 1 Introduction 4 2 Safety 5 3 Use 6 4 Checking on Delivered Equipment 6 5 General Specification and Dimensions 7 6 Positioning 10 7 Operating

More information

Operating and Maintenance Instructions

Operating and Maintenance Instructions Part No Description Dual EC Fan Controller Issue Date Bug no Comments 1 10 July 2012 1205 Signed CE front sheet & instructions clarified 2 28 Jan 2013 1205 Instructions clarified, identify Live & SELV

More information

CONTROL PANEL WIRING SPECIFICATIONS

CONTROL PANEL WIRING SPECIFICATIONS CONTROL PANEL WIRING ISSUE STATUS FIRST REV DESCRIPTION DATE 001 1 ST ISSUE 22/04/2014 002 1 ST AMMENDMENT 10/03/2017 003 2 ND AMMENDMENT 08/09/2017 THIS DOCUMENT IS DESIGNED TO COVER ALL APPLICATIONS,

More information

Company Directive ENGINEERING SPECIFICATION EE SPEC: 136

Company Directive ENGINEERING SPECIFICATION EE SPEC: 136 Company Directive ENGINEERING SPECIFICATION EE SPEC: 136 Ancillary Electrical Equipment for Use in Conjunction with Switchgear and Protection/Control Panels NOTE: The current version of this document is

More information

Recording and Reporting of High Voltage and Low Voltage Switching

Recording and Reporting of High Voltage and Low Voltage Switching 1 SCOPE This document details the procedures to be adopted prior to, during, and on completion of Switching operations, and details the manner in which HV and LV Switching shall be recorded in order to

More information

Rapier GX Gas Enclosed Load Break Switch and Sectionaliser up to 38kV with automation or remote control options ENGINEERING BRILLIANT SOLUTIONS

Rapier GX Gas Enclosed Load Break Switch and Sectionaliser up to 38kV with automation or remote control options ENGINEERING BRILLIANT SOLUTIONS Rapier GX Gas Enclosed Load Break Switch and Sectionaliser up to 38kV with automation or remote control options ENGINEERING BRILLIANT SOLUTIONS RAPIER GX Gas Enclosed Switch Our new RAPIER GX, pole-mounted

More information

EDS HV NETWORK DESIGN

EDS HV NETWORK DESIGN Document Number: EDS 08-3000 Network(s): Summary: EPN, LPN, SPN ENGINEERING DESIGN STANDARD EDS 08-3000 HV NETWORK DESIGN This standard details the guidelines for the design and development of the 11kV

More information

ECP REMSDAQ CALLISTO 1 CONTROL UNIT AND RTU INSTALLATION PROCEDURE

ECP REMSDAQ CALLISTO 1 CONTROL UNIT AND RTU INSTALLATION PROCEDURE Network(s): Summary: ENGINEERING CONSTRUCTION PROCEDURE ECP 05-9535 REMSDAQ CALLISTO 1 CONTROL UNIT AND RTU INSTALLATION PROCEDURE LPN This document details the installation procedure for the Remsdaq Callisto

More information

Distribution Substation Manual (DSM) Section 6: Miscellaneous

Distribution Substation Manual (DSM) Section 6: Miscellaneous Distribution Substation Manual (DSM) Section 6: Miscellaneous Standard Number: HPC-5DA-07-0006-2012 Document Control Author Name: Viswa Easwaran Position: Standards Engineer Document Owner Name: Justin

More information

From: Dan Toon, EXECUTIVE MANAGER COMMERCIAL SERVICES. Date: 15 August 2007 (Supersedes the 06 March 2007 issue)

From: Dan Toon, EXECUTIVE MANAGER COMMERCIAL SERVICES. Date: 15 August 2007 (Supersedes the 06 March 2007 issue) Memorandum To: Donna Ward, DEPOT FINANCIAL SERVICES SUPERVISOR From: Dan Toon, EXECUTIVE MANAGER COMMERCIAL SERVICES cc: Date: 15 August 2007 (Supersedes the 06 March 2007 issue) Re: Purchase Specification

More information

MESP TECHNICAL SPECIFICATION FOR SCADA CABLING IN SUBSTATIONS

MESP TECHNICAL SPECIFICATION FOR SCADA CABLING IN SUBSTATIONS Engineering Specification Electrical Networks MESP 081000-01 TECHNICAL SPECIFICATION FOR SCADA CABLING IN Version: 1 Issued: March 2014 Owner: Electrical Networks Asset Manager Approved By: George Marulli

More information

S Sectionalizers Types TVS15 and TVS27 Time Voltage Sectionalizer Installation and Operation Instructions. Contents

S Sectionalizers Types TVS15 and TVS27 Time Voltage Sectionalizer Installation and Operation Instructions. Contents Sectionalizers Types TVS15 and TVS27 Time Voltage Sectionalizer Installation and Operation Instructions Service Information S270-30-1 Figure 1. Kyle Type TVS Time-Voltage Sectionalizer. Contents 010032KM

More information

B. System Design and Performance Requirements

B. System Design and Performance Requirements Change History Date Description of Change Pages / Sections Modified Change Approver Initials 6/15/16 Updated division section from 16950 to 26 27 13, removed references to other section numbers 11/21/14

More information

SIGMA D++ / SIGMA D+ / SIGMA D Directional Fault Indicator

SIGMA D++ / SIGMA D+ / SIGMA D Directional Fault Indicator SIGMA D++ / SIGMA D+ / SIGMA D Directional Fault Indicator Product Features CT powered directional short-circuit and directional earth fault indicator for all distribution networks / neutral point treatments

More information

RCD Fused Connection Unit Model: RCD10WPV. RCD Double Sockets Models: RCD05WAV, RCD06WPV, RCD07MAV, RCD08MPV. Installation & Operating Instructions

RCD Fused Connection Unit Model: RCD10WPV. RCD Double Sockets Models: RCD05WAV, RCD06WPV, RCD07MAV, RCD08MPV. Installation & Operating Instructions RCD Fused Connection Unit Model: RCD10WPV RCD Double Sockets Models: RCD05WAV, RCD06WPV, RCD07MAV, RCD08MPV Installation & Operating Instructions General The Timeguard range of RCDs provides protection

More information

ST: TP14D/2 TEST SHEET COMBINED LV CT & METER CABINET INSTALLATIONS OFF-LOAD TESTING

ST: TP14D/2 TEST SHEET COMBINED LV CT & METER CABINET INSTALLATIONS OFF-LOAD TESTING COMBINED LV CT & METER CABINET INSTALLATIONS Summary This Test Sheet shall be employed during the off-load testing of Combined LV CT & Meter Cabinet Installations in accordance with Standard Technique

More information

Hydrastep 2468CA and 2468CC

Hydrastep 2468CA and 2468CC Operating Manual 24685033, Rev. AE June 2011 Hydrastep 2468CA and 2468CC Hydrastep 2468 Electronic Gauging System (Single Power Supply Version) www.emersonprocess.com CATEGORY SYMPTOM POSSIBLE CAUSES (See

More information

ABB Digital medium-voltage switchgear

ABB Digital medium-voltage switchgear NAMIBIA AMEU/AEDU MARCH 2018 ABB Digital medium-voltage switchgear Barry Addinall UniGear Digital Contents 1. Digital switchgear 2. Complexity of Distribution networks 3. New technologies using digital

More information

Electrical Demand Specification (Reference SOP: )

Electrical Demand Specification (Reference SOP: ) Project: Equipment Description: Location: Equipment No.: Project No: Protocol No.: Content Index 1. GENERAL...3 Design Standards...3 1.1. Standards...3 2. DESIGN...3 2.1. Safety...3 2.2. Circuit protection...3

More information

Loop Automation. Technical Manual for the ADVC Controller Range

Loop Automation. Technical Manual for the ADVC Controller Range Loop Automation Technical Manual for the ADVC Controller Range Contents List of Figures 5 List of Tables 7 Acronyms 7 Symbols 7 Introduction 8 About this Manual 8 ADVC Controller Firmware Version 9 WSOS

More information

Common Departures Interconnecting Facilities Requirements

Common Departures Interconnecting Facilities Requirements Welcome to our e-rew Express. In our last issue, we discussed the common departures on metering installation requirements. This time, we would like to discuss the common departures on the customer low

More information

1S20. Arc Fault Monitor Relay. Features. Introduction. ARC Fault Protection

1S20. Arc Fault Monitor Relay. Features. Introduction. ARC Fault Protection Technical Bulletin Arc Fault Monitor Relay Features Compact, economic design Simple panel mounting for retrofit applications Two or three arc sensor inputs Two high speed tripping duty arc sense output

More information

Remote units Hands free or telephone handset options available. Master to remote and remote to master calling

Remote units Hands free or telephone handset options available. Master to remote and remote to master calling (ORB/L/RS16 LOOP WIRED) Remote units Hands free or telephone handset options available Master to remote and remote to master calling Fully monitored for open and short circuit cable failures. Remotes connected

More information

Flexible Urban Networks Low Voltage Successful and safe installation, commissioning and operation of LV switches and circuit breakers on LV networks

Flexible Urban Networks Low Voltage Successful and safe installation, commissioning and operation of LV switches and circuit breakers on LV networks Flexible Urban Networks Low Voltage Successful and safe installation, commissioning and operation of LV switches and circuit breakers on LV networks (SDRC 9.2) Contents Executive Summary... 5 1. Introduction...

More information

Specification Voltage Limiting Device

Specification Voltage Limiting Device Engineering Specification Electrical Networks L1-CHE-SPE-152 Specification Voltage Limiting Device Version: 1 Issued: 20 th April 2018 Owner: Chief Engineer Approved By: Andrew Russack Head of Engineering,

More information

ASI Systems ML5740A Series

ASI Systems ML5740A Series ML5740A Series Electric Linear Valve Actuators Non-Spring Return APPLICATION The ML5740A series actuators operate standard ASI Systems valves in heating, ventilating and air conditioning (HVAC) applications.

More information

ASI Systems ML5720A Series

ASI Systems ML5720A Series ML5720A Series Electric Linear Valve Actuators Non-Spring Return APPLICATION The ML5720A series actuators operate standard ASI Systems valves in heating, ventilating and air conditioning (HVAC) applications.

More information

LIFEBUOY RELEASE SYSTEM - TECHNICAL PRODUCT SPECIFICATION AND INSTALLATION MANUAL

LIFEBUOY RELEASE SYSTEM - TECHNICAL PRODUCT SPECIFICATION AND INSTALLATION MANUAL LIFEBUOY RELEASE SYSTEM - TECHNICAL PRODUCT SPECIFICATION AND INSTALLATION MANUAL The LifeBuoy Remote Release System standard HM-0600 consists of the following parts: One GRP holder with pre-installed

More information

Operating Manual. icam100

Operating Manual. icam100 icam100 This page is intentionally left blank. Document Number 302803 (See Last Page for Revision Details) 2006 Extronics Limited. This document is Copyright Extronics limited. Extronics reserve the right

More information

MMLB 01/MMLB 02 Multi-finger Test Plug/ Single-finger Test Plug Technical Data MMLB_EN_TD_A

MMLB 01/MMLB 02 Multi-finger Test Plug/ Single-finger Test Plug Technical Data MMLB_EN_TD_A AUTOMATION MMLB 01/MMLB 02 Multi-finger Test Plug/ Single-finger Test Plug Technical Data MMLB_EN_TD_A GRID Note: The technical manual for this device gives instructions for its installation, commissioning,

More information

Session Five: IEC61850 Based Process Bus Protection Solution for Remote Located Power Transformers

Session Five: IEC61850 Based Process Bus Protection Solution for Remote Located Power Transformers Session Five: IEC61850 Based Process Bus Protection Solution for Remote Located Power 1. Abstract Dinesh Mithanthaya Design Manager, Horizon Power Higher capacity substation power transformers ( 5MVA),are

More information

SECTION ELECTRIC METERING

SECTION ELECTRIC METERING SECTION 26 27 13 ELECTRIC METERING SPEC WRITER NOTES: Use this section only for NCA projects Delete between //----// if not applicable to project. Also delete any other item or paragraph not applicable

More information

Hydrastep 2468CB and 2468CD

Hydrastep 2468CB and 2468CD Operating Manual 6850, Rev. AE June 0 Hydrastep 68CB and 68CD Hydrastep 68 Electronic Gauging System (Dual Power Supply Version) www.emersonprocess.com CATEGORY SYMPTOM POSSIBLE CAUSES (See Note ) SOLUTION

More information

SERIES SD3800 / SD3810 SPECIFICATION

SERIES SD3800 / SD3810 SPECIFICATION SERIES SD3800 / SD3810 SPECIFICATION SOLID DIELECTRIC SINGLE SIDED 15 KV & 25 KV PADMOUNTED VACUUM LOAD INTERRUPTERS AND VACUUM FAULT INTERRUPTERS WITH VISIBLE DISCONNECTS MANUALLY OPERATED / REMOTELY

More information

Ag Leader Technology Insight. Direct Command Installation Spra-Coupe 7000 Series

Ag Leader Technology Insight. Direct Command Installation Spra-Coupe 7000 Series Note: Indented items indicate parts included in an assembly listed above. Part Name / Description Part Number Quantity Direct Command Spra-Coupe 7000 Kit 4100531 1 Liquid Product Control Module 4000394

More information

Bulletin Installation of Solar Photovoltaic Systems Section 50; Rules: , , ; Tables 11 and 19 Issued July 2010

Bulletin Installation of Solar Photovoltaic Systems Section 50; Rules: , , ; Tables 11 and 19 Issued July 2010 Ontario Electrical Safety Code - Bulletins 50-1-0 Bulletin 50-1-0 Installation of Solar Photovoltaic Systems Section 50; Rules: 84-020, 84-024, 84-030; Tables 11 and 19 Issued July 2010 Scope (1) Introduction

More information

AC Immune DC Track Circuits Set-Up, Test and Certification

AC Immune DC Track Circuits Set-Up, Test and Certification Discipline: Engineering (Signalling) Category: Standard AC Immune DC Track Circuits Set-Up, Test and Certification SES 02 Applicability New South Wales RIC (NSW CRN) Primary Source RIC Standard SC 07 41

More information

The Exp-007 unit connects directly to Remote Status Indicator units to provide 2 programmable 1-Amp rated, volt free, clean contact outputs.

The Exp-007 unit connects directly to Remote Status Indicator units to provide 2 programmable 1-Amp rated, volt free, clean contact outputs. Relay Outputs The Exp-007 and Exp-008 are internal peripherals for use with the Ex3000 gas extinguishing system. The units are used to expand the number of outputs available on the system either local

More information

2 Check that Public Safety has been considered (e.g. cabinet secured and locked, trip hazards removed where applicable).

2 Check that Public Safety has been considered (e.g. cabinet secured and locked, trip hazards removed where applicable). NOTE: SAFETY: Tests must be carried out after the installation, alteration or repair and before putting back to service. At all times maintain suitable clearance to all other electrical equipment and verify

More information

3a. IEM Indoor Metal Clad Medium Voltage Switchgear 25KV a. Section INDOOR METAL CLAD MEDIUM VOLTAGE SWTICHGEAR (Std.

3a. IEM Indoor Metal Clad Medium Voltage Switchgear 25KV a. Section INDOOR METAL CLAD MEDIUM VOLTAGE SWTICHGEAR (Std. 3a. IEM Indoor Metal Clad Medium Voltage Switchgear 25KV 16346-1 3a. Section 16346 INDOOR METAL CLAD MEDIUM VOLTAGE SWTICHGEAR (Std. Relays) Part 1 General 1.1 CONDITIONS AND REQUIREMENTS: A. Refer to

More information

Company Directive STANDARD TECHNIQUE: TP18A/1. Application of Connection Control Panels for Soft Intertrip and/or Voltage Constraint Schemes

Company Directive STANDARD TECHNIQUE: TP18A/1. Application of Connection Control Panels for Soft Intertrip and/or Voltage Constraint Schemes Company Directive STANDARD TECHNIQUE: TP18A/1 Application of Connection Control Panels for Soft Intertrip and/or Voltage Constraint Schemes Summary This document provides guidance on the application of

More information

LineTroll User Manual

LineTroll User Manual LineTroll 3100 User Manual This document describes the Installation-, configuration and use of LineTroll 3100/3100K/3100T Revision 2a. Date:24.11.2006 Information about the Xenon-flash version added Ext

More information

Vibration Sensor Type 640

Vibration Sensor Type 640 Vibration Sensor Type 640 Standard Zone-1-21 Zone-2-22 Instruction Manual English Instruction Manual Vibration Sensor Type 640 Standard Zone-1-21 Zone-2-22 Edition: 12.04.10 Attention! Before Start-Up

More information

The Programmable 4-Way Relay Card is an optional peripheral unit that provides four individually programmable relay output circuits.

The Programmable 4-Way Relay Card is an optional peripheral unit that provides four individually programmable relay output circuits. Peripheral Relay The Programmable 4-Way Relay Card is an optional peripheral unit that provides four individually programmable relay output circuits. Up to 16 Cards can be connected to a multi-loop panel

More information

BlueWave ~ Intelligent Energy Control. Installation and User Manual for BW2/C and BW3/C versions. Quick Guide

BlueWave ~ Intelligent Energy Control. Installation and User Manual for BW2/C and BW3/C versions. Quick Guide BlueWave ~ Intelligent Energy Control Installation and User Manual for BW2/C and BW3/C versions Quick Guide Press button to override or activate Channel 1 Press button to override or activate Channel 2

More information

HST -M1 Switching element with locking mechanism (Translation of Original Manual)

HST -M1 Switching element with locking mechanism (Translation of Original Manual) Installation and Operating Manual for Components HST -M1 Switching element with locking mechanism (Translation of Original Manual) HST-M1 Ident. No.: 10213 HST-M1 Ident. No.: 10219 HST-M1, pictured Ident.

More information

Our Power & Control line of Business offers solutions that safely distribute power to your home or business. Our product range includes Low/Medium

Our Power & Control line of Business offers solutions that safely distribute power to your home or business. Our product range includes Low/Medium Our Power & Control line of Business offers solutions that safely distribute power to your home or business. Our product range includes Low/Medium Voltage Panels and Enclosures designed and built with

More information

Elastimold Molded Vacuum Recloser - MVR

Elastimold Molded Vacuum Recloser - MVR Subject: Elastimold Recloser Technical Specification Date: 4/24/12 File: MVR-RS-0412 Page: 1 of 6 1.0 SCOPE Elastimold Molded Vacuum Recloser - MVR 1.1 This specification covers electrical and mechanical

More information

SITRANS F Coriolis Flowmeters SITRANS FCT030 transmitter Quick Start

SITRANS F Coriolis Flowmeters SITRANS FCT030 transmitter Quick Start SITRANS F Coriolis Flowmeters Quick Start Before installing, including in hazardous areas, refer to the Operating Instructions on the internet or on the SITRANS F literature CD-ROM. They contain detailed

More information

Data Manager Installation Guide

Data Manager Installation Guide PR05XX Data Manager Installation Guide Resource Data Management Ltd 80 Johnstone Avenue, Hillington Industrial Estate, Glasgow, Scotland G52 4NZ UK +44(0)141 810 2828 Switchboard support@resourcedm.com

More information

DAC LIMITED. USER GUIDE Vandal Resistant Telephones 711 Autodial Telephone range

DAC LIMITED. USER GUIDE Vandal Resistant Telephones 711 Autodial Telephone range DAC LIMITED USER GUIDE Vandal Resistant Telephones 711 Autodial Telephone range CONTENTS Page 2 Page 4 Page 5 Page 6 Page 7 Page 8 Page 9 Page 10 Page 11 Installation Electrical Connection Approved Facilities

More information

Company Directive STANDARD TECHNIQUE: TP14J. Management of Metering CT & VT Test Certificates

Company Directive STANDARD TECHNIQUE: TP14J. Management of Metering CT & VT Test Certificates Company Directive STANDARD TECHNIQUE: TP14J Management of Metering CT & VT Test Certificates Summary This standard technique document details the process for managing metering CT and VT test certificates.

More information

USER MANUAL VIBRATION CONTROL RMA-POWER-BOX 107/230

USER MANUAL VIBRATION CONTROL RMA-POWER-BOX 107/230 USER MANUAL VIBRATION CONTROL Version 2.2 1 IMPORTANT NOTES Electrical danger within the meaning of this documentation or the warning labels on the product itself respectively means that death, serious

More information

POWER GRID AUTOMATION. Pág.. n. RMU Automation

POWER GRID AUTOMATION. Pág.. n. RMU Automation POWER GRID AUTOMATION RMU Automation Distribution Network Non-Controlled Secondary Distribution Systems Distribution Network RMU Automation - Levels RMU Automation - RTU / FRTU SMART CONTROLLER Monitoring

More information

AVC 2 AUTOMATIC VOLUME CONTROL USERS MANUAL

AVC 2 AUTOMATIC VOLUME CONTROL USERS MANUAL AVC 2 AUTOMATIC VOLUME CONTROL USERS MANUAL GENERAL DETAIL The AVC2 will control a stereo channel to a preset maximum output level allowing the maximum sound level of a system to be controlled. The AVC2

More information

DC Track Circuits Set-Up, Test and Certification

DC Track Circuits Set-Up, Test and Certification Discipline: Engineering (Signalling) Category: Standard DC Track Circuits Set-Up, Test and Certification SES 01 Applicability New South Wales CRIA (NSW CRN) Primary Source RIC Standard SC 07 41 00 01 WI

More information

ENGINEERING AND SERVICES FIRM THAT SPECIALIZES IN HYDROELECTRIC POWER AND CONTROL SYSTEM DESIGN, OUR TEAM OF PROFESSIONALS HAVE WORKED TOGETHER

ENGINEERING AND SERVICES FIRM THAT SPECIALIZES IN HYDROELECTRIC POWER AND CONTROL SYSTEM DESIGN, OUR TEAM OF PROFESSIONALS HAVE WORKED TOGETHER smallhydro PRIME ENGINEERING LIMITED IS AN ELECTRICAL ENGINEERING AND SERVICES FIRM THAT SPECIALIZES IN HYDROELECTRIC POWER AND CONTROL SYSTEM DESIGN, IMPLEMENTATION AND MAINTENANCE. OUR TEAM OF PROFESSIONALS

More information

DRS-LIGHT. Device Description DRS-LP824. Digital Unit Decoupling Relay Type DRS-LP824. Device Description DIL

DRS-LIGHT. Device Description DRS-LP824. Digital Unit Decoupling Relay Type DRS-LP824. Device Description DIL DRS-LIGHT Digital Unit Decoupling Relay Type DRS-LP824 Device Description Edition:09.05.2008 SLLR_LP824_e.doc Page 1 /10 CAUTION Installing, commissioning and operating of this product may be performed

More information

NEXT GENERATION NETWORK RESTORATION APPROACHES ON DISTRIBUTION FEEDERS

NEXT GENERATION NETWORK RESTORATION APPROACHES ON DISTRIBUTION FEEDERS NEXT GENERATION NETWORK RESTORATION APPROACHES ON DISTRIBUTION FEEDERS John DULLER Ahsan HALIM Gordon PATON UK Power Networks UK UK Power Networks UK General Electric - UK john.duller@ukpowernetworks.co.uk

More information

MRT1 Test Unit. Manual MRT1 (Revision A)

MRT1 Test Unit. Manual MRT1 (Revision A) MRT1 Test Unit Manual MRT1 (Revision A) Woodward Manual MRT1 GB Woodward Governor Company reserves the right to update any portion of this publication at any time. Information provided by Woodward Governor

More information

IO-INTERFACE. Procon. INSTALLATION MANUAL Version 1.01 MITSUBISHI ELECTRIC FOR INSTALLERS

IO-INTERFACE. Procon. INSTALLATION MANUAL Version 1.01 MITSUBISHI ELECTRIC FOR INSTALLERS Procon IO-INTERFACE FOR INSTALLERS INSTALLATION MANUAL Version 1.01 For safe and correct use, please read this installation manual thoroughly before installing the PROCON IO-INTERFACE. MITSUBISHI ELECTRIC

More information

Primary Injection Test Procedure

Primary Injection Test Procedure S&C IntelliRupter PulseCloser Fault Interrupter Outdoor Distribution (15.5 kv, 27 kv, and 38 kv) Primary Injection Test Procedure Table of Contents Section Page Section Page Introduction Qualified Persons....

More information

Test Report S

Test Report S Sunkom Pty Ltd FDX card s A101, A102, A104 and A108 Laboratory Details All tests were performed at : Comtest Laboratories Pty. Ltd. Unit 1 / 570 City Road South Melbourne Victoria 3205 Australia Telephone

More information

H704-42(H)(E), H704-42/1(H)(E)

H704-42(H)(E), H704-42/1(H)(E) POWER MONITORING INSTALLATION GUIDE H704-42(H)(E), H704-42/1(H)(E) Branch Current Monitor DANGER NOTICE Installer's Specifications General: Operating Temp. Range 0 to 60 C (32 to 140 F) (

More information

CROWN LINE Power Bus Bar Distribution System

CROWN LINE Power Bus Bar Distribution System COWN LINE Power Bus Bar Distribution System COWN LINE Power Bus Bar Distribution System The pluggable bus bar system Currents up to 300 Amps Up to 2 meters in length Pluggable breakers VDE finger proof

More information

E3S-A. Built-in Amplifier Photoelectric Sensor (Medium Size) Ordering Information. Built-in Amplifier Photoelectric Sensors. Horizontal. 7 m.

E3S-A. Built-in Amplifier Photoelectric Sensor (Medium Size) Ordering Information. Built-in Amplifier Photoelectric Sensors. Horizontal. 7 m. Built-in Amplifier (Medium Size) ES-A CSM_ES-A_DS_E Be sure to read Safety Precautions on page 0. Ordering Information Built-in Amplifier s Red light Infrared light Sensing method Appearance Connection

More information

Manual: Distribution Substation Manual (DSM) Section 4: Equipment Installation Guide

Manual: Distribution Substation Manual (DSM) Section 4: Equipment Installation Guide Manual: Distribution Substation Manual (DSM) Section 4: Equipment Installation Guide Standard Number: HPC-5DA-07-0004-2012 Document Control Author Name: Viswa Easwaran Position: Standards Engineer Document

More information

HST -M2 Switching element with locking mechanism (Translation of Original Manual)

HST -M2 Switching element with locking mechanism (Translation of Original Manual) Installation and Operating Manual for Components HST -M2 Switching element with locking mechanism (Translation of Original Manual) HST-M2 Ident.-No.: 10214 HST-M2 Ident.-No.: 10626 HST-M2 Ident.-No.: 10218

More information

PACSystems RX7i IC698CHS009/119

PACSystems RX7i IC698CHS009/119 January 2010 The RX7i rack can be used for all RX7i CPU and I/O configurations, Series 90-70 I/O, and VME modules. Backplane connectors are spaced on 0.8" (20.3mm) centers to accommodate single-width RX7i

More information

NU-LEC. Loop Automation. Reclosers & Sectionalizers

NU-LEC. Loop Automation. Reclosers & Sectionalizers NU-LEC Loop Automation Reclosers & Sectionalizers 1 NU-LEC LLC NU-LEC LLC is a wholly unit of NU-LEC Industries, Pty, Ltd. Sales and service center for United States, Canada, and the Caribbean. Warehouse

More information

(Above 100km Distance) (Streetlight Pole) (Above 100km Distance) (Streetlight Pole)

(Above 100km Distance) (Streetlight Pole) (Above 100km Distance) (Streetlight Pole) Part 9 Miscellaneous Drawing Register Number Description M1-1 SSN Network Device with LV Aerial Supply (ABC) Arrangement M1-2 SSN Network Device with LV Aerial Supply Arrangement M1-3 SSN Network Device

More information

SPI PowerNet requirements for the non-contestable Interface Works at Deer Park Terminal Station

SPI PowerNet requirements for the non-contestable Interface Works at Deer Park Terminal Station SPI PowerNet requirements for the non-contestable Interface Works at Deer Park Terminal Station SPI PowerNet Reference: ZD23 Version: 1.1 Issue date: 15 May 2014 Contents 1 Scope... 3 2 Deer Park Terminal

More information

COOPER POWER SERIES. RS-485 digital communications accessory board installation and operation instructions. Voltage Regulators MN225074EN

COOPER POWER SERIES. RS-485 digital communications accessory board installation and operation instructions. Voltage Regulators MN225074EN Voltage Regulators MN225074EN Effective March 2017 Supersedes January 2012 (S225-40-7) RS-485 digital communications accessory board installation and operation instructions COOPER POWER SERIES DISCLAIMER

More information