VAM I/O units. Publication version: VIO/en M/D003. User Manual

Size: px
Start display at page:

Download "VAM I/O units. Publication version: VIO/en M/D003. User Manual"

Transcription

1 VAM I/O units Publication version: User Manual

2 Trace back information: Workspace Main version a Checked in 0-0- Skribenta version..

3 Table of Contents Table of Contents General.... Legal notice.... Safety information.... EU directive compliance... Introduction.... Purpose.... Main properties... User interface VAM L fiber sensor I/O unit.... VAM LX fiber sensor I/O unit.... VAM 0L point sensor I/O unit.... VAM 0LD point sensor I/O unit.... VAM L point sensor I/O unit.... VAM LD point sensor I/O unit.... VAM C current I/O unit VAM CD current I/O unit VAMP R trip multiplier relay... Programming switches.... Switches for arc sensor I/O units.... Switches for current I/O units... Adjusting the overcurrent setting... BI/BO connection... Connections VAM L / VAM LX interfaces VAM 0L interfaces.... VAM 0LD interfaces.... VAM L interfaces.... VAM LD interfaces.... VAM C interfaces.... VAM CD interfaces.... VAMP R interfaces... I/O Technical data.... Connections.... Auxiliary power supply Digital inputs Trip contacts Disturbance tests...

4 Table of Contents. Electrical safety tests.... Environmental conditions.... Package....9 Casing... 9 Construction Dimensional drawings VAM L / LX Din rail mounting VAM 0L Din rail mounting VAM 0LD Flush mounting VAM L Din rail mounting VAM LD Flush mounting VAM C Din rail mounting VAM CD Flush mounting VAMP R Din rail mounting VA DA VA EH VYX VYX I/O unit mounting and wiring VAM 0L, VAM L, VAM C, VAM L, VAM LX VAM 0LD, VAM LD, VAM CD Connecting the VAMP I/O units Connecting the secondary circuits of the current transformers (VAM C / VAM CD only) Connecting the trip circuits of the circuit breakers Connecting between the central unit and the I/O unit Connecting separate auxiliary supplies VAMP R Wiring multiple central units Arc sensors VA DA VA EH ARC-SLx VA DP... 0 Order information... Glossary

5 General General. Legal notice Copyright 0 Schneider Electric. All rights reserved. Disclaimer No responsibility is assumed by Schneider Electric for any consequences arising out of the use of this document. This document is not intended as an instruction manual for untrained persons. This document gives instructions on device installation, commissioning and operation. However, the manual cannot cover all conceivable circumstances or include detailed information on all topics. In the event of questions or specific problems, do not take any action without proper authorization. Contact Schneider Electric and request the necessary information. Contact information rue Joseph Monier 90 Rueil-Malmaison FRANCE Phone: + (0) Fax: + (0) Safety information Important Information Read these instructions carefully and look at the equipment to become familiar with the device before trying to install, operate, service or maintain it. The following special messages may appear throughout this bulletin or on the equipment to warn of potential hazards or to call attention to information that clarifies or simplifies a procedure. The addition of either symbol to a Danger or Warning safety label indicates that an electrical hazard exists which will result in personal injury if the instructions are not followed. This is the safety alert symbol. It is used to alert you to potential personal injury hazards. Obey all safety messages that follow this symbol to avoid possible injury or death.

6 . Safety information General DANGER DANGER indicates an imminently hazardous situation which, if not avoided, will result in death or serious injury. WARNING WARNING indicates a potentially hazardous situation which, if not avoided, can result in death or serious injury. CAUTI CAUTI indicates a potentially hazardous situation which, if not avoided, can result in minor or moderate injury. NOTICE NOTICE is used to address practices not related to physical injury. User qualification Electrical equipment should be installed, operated, serviced, and maintained only by trained and qualified personnel. No responsibility is assumed by Schneider Electric for any consequences arising out of the use of this material. A qualified person is one who has skills and knowledge related to the construction, installation, and operation of electrical equipment and has received safety training to recognize and avoid the hazards involved. Password protection Use the IED's password protection feature to protect untrained persons from interacting with this device. WARNING WORKING ENERGIZED EQUIPMENT Do not choose lower Personal Protection Equipment while working on energized equipment. Failure to follow these instructions can result in death or serious injury.

7 General. EU directive compliance. EU directive compliance EMC compliance 0/0/EU Compliance with the European Commission's EMC Directive. Product Specific Standards were used to establish conformity: EN 0-: 0 Product safety 0//EU Compliance with the European Commission's Low Voltage Directive. Compliance is demonstrated by reference to generic safety standards: EN0-:0

8 Introduction Introduction This User s Manual contains a functional description of the VAM I/O units and technical data.. Purpose The main purpose of the VAM I/O units is to detect arc light or short circuit current and deliver this information (zone information) to the arc protection central unit and the other VAM I/O units. Additionally VAM I/O units can be used for tripping appropriate circuit breakers. NOTE: For applications in the US, Canada and Mexico, use specific documents reviewed in line with the requirements of the relevant regulatory authorities. Please contact our local Schneider Electric office for assistance.. Main properties Arc flash protection system is a modular system consisting of a central unit, I/O units and arc sensors. Due to its modularity, the system is suitable for a range of arc protection applications, from simple systems with one central unit and one I/O unit to more complex solutions comprising several central units used for selective arc protection. The I/O unit VAM 0L / VAM 0LD, VAM L / VAM LD serves as link between the system s point sensors and the central unit. Each I/O unit has connections for ten arc sensors, one portable pin sensor and one trip output. The I/O unit VAM L/VAMLX serves as link between the system s fibre sensors and the central unit. Each I/O unit has connections for three arc sensors, one pin sensor and one trip output. The I/O unit VAM C / VAM CD serves as link between the system s current inputs and the central unit. Each I/O unit has connections for three current transformers and one trip output. The arc sensor VA DA is activated by strong light. The sensor transforms the light information into the current signal, which is forwarded through the I/O unit to the central unit. The arc sensor VA EH also operates on the same principle. The pin sensor VA DP has the same functions as an arc sensor but can be temporarily connected to an I/O unit. The sensor can be fixed to the breast pocket of a technician to improve safety when working with live switchgear.

9 Introduction. Main properties The door mounted VAM I/O units with the letter D in the type designations VAM 0LD, VAM LD and VAM CD are door mounted versions for the corresponding VAM 0L, VAM L and VAM C units. The functionality is exactly the same. 9

10 User interface User interface Usually, there is no need to touch the front panel during normal operation, since all the necessary information can be read from the central unit display. However, after a new installation or a system expand you will need to program certain functions (zone/address, trip output) in the I/O unit. NOTE: If you unfasten the terminal blocks during installation, remember to tighten the fixing screws after installation! Also tighten the screws even if you did not unfasten the blocks. 0

11 User interface. VAM L fiber sensor I/O unit. VAM L fiber sensor I/O unit VAML 0 9 X Zone SW OFF L>ext/Int Latch L+I/L SENSOR OK 9 ACT 0 TRIP SENSOR INPUTS CH CH CH R T R T R T Figure.: VAM L fiber sensor I/O unit front panel. Connection for portable arc sensor (VA DP). Programming switches. POWER indicator light, indicates that the supply voltages of each component are in order.. indicator light, lit when the central units and I/O units are communicating.. ERROR indicator light, indicates an internal fault detected by the component s self-diagnostics. Such faults include faulty arc sensor or changes in the amount of sensors.. Connector sockets for the VX00 modular cables. LED lights indicating sensor activation. Terminals for three fibre sensors 9. Portable arc sensor VA DP connected and operational 0. Portable arc sensor activated. I/O unit trip relay activated. Terminal block for external communication and BI/O channels and trip signal

12 . VAM LX fiber sensor I/O unit User interface. VAM LX fiber sensor I/O unit VAM LX 0 9 X L>ext/Int Latch L+I/L Zone SW OFF SENSOR OK 9 ACT 0 TRIP SENSOR INPUTS CH CH CH R T R T R T CH CH CH Adj Adj Adj Min. Max. Min. Max. Min. Max. Figure.: VAM LX fiber sensor I/O unit front panel. Connection for portable arc sensor (VA DP). Programming switches. POWER indicator light, indicates that the supply voltages of each component are in order.. indicator light, lit when the central units and I/O units are communicating.. ERROR indicator light, indicates an internal fault detected by the component s self-diagnostics. Such faults include faulty arc sensor or changes in the amount of sensors.. Connector sockets for the VX00 modular cables. LED lights indicating sensor activation. Terminals for three fibre sensors 9. Portable arc sensor VA DP connected and operational 0. Portable arc sensor activated. I/O unit trip relay activated. Terminal block for external communication and BI/O channels and trip signal. Sensitivity adjustments for each fibre sensor channels

13 User interface. VAM 0L point sensor I/O unit. VAM 0L point sensor I/O unit VAM 0L 0 9 X L> ext/int Latch L+I/L Zone SW OFF SENSOR OK 9 ACT 0 TRIP SENSOR INPUTS 9 0 X Figure.: VAM 0L point sensor I/O unit front panel. Connection for portable arc sensor (VA DP). Programming switches. POWER indicator light, indicates that the supply voltages of each component are in order.. indicator light, lit when the central unit and I/O units are communicating.. ERROR indicator light, indicates an internal fault detected by the component s self-diagnostics. Such faults include faulty arc sensor or changes in the amount of sensors.. Connector sockets for the VX00 modular cables. LED lights indicating sensor activation. Terminal block for ten arc sensors 9. Portable arc sensor VA DP connected and operational 0. Portable arc sensor activated. I/O unit trip relay activated. Terminal block for external communication and BI/O channels and trip signal

14 O N. VAM 0LD point sensor I/O unit User interface. VAM 0LD point sensor I/O unit VAM 0LD Point sensor I/O unit SENSOR INPUTS 9 0 ADDRESS NR 0. BB FEEDER. CB FEEDER TRIP. CC FEEDER. BB FEEDER. CB FEEDER. CC FEEDER. BB FEEDER 9. BB FEEDER 9 9. BB FEEDER 9 FRT PANEL 0. TIE BREAKER ID X SENSOR INPUTS SW 0 ACT 9 OK SENSOR Zone L/L+I Latch L> Int/ Ext BACK PANEL X 9 0 Figure.: VAM 0LD point sensor I/O unit front and back panel. Connection for portable arc sensor (VA DP). Programming switches. POWER indicator light, indicates that the supply voltages of each component are in order.. indicator light, lit when the central unit and I/O units are communicating.. ERROR indicator light, indicates an internal fault detected by the component s self-diagnostics. Such faults include faulty arc sensor or changes in the amount of sensors.. Connector sockets for the VX00 modular cables. LED lights indicating sensor activation. Terminal block for ten arc sensors

15 User interface. VAM 0LD point sensor I/O unit 9. Portable arc sensor VA DP connected and operational 0. Portable arc sensor activated. I/O unit trip relay activated. Terminal block for external communication and BI/O channels and trip signal. Text pocket for sensor specific labels.

16 . VAM L point sensor I/O unit User interface. VAM L point sensor I/O unit VAM L is primary design for selective feeder trip applications. The unit comprises electromechanical trip normally open contacts and one trip alarm change over contact. The unit has 0 Arc sensor inputs. Tree sensors (of the ten) inputs are dedicated, and are controlling their own trip relay. The unit is ideal for selective trip of cable compartment in case of an ARC fault. VAM L can selectively handle feeders. The rest of the sensors can then supervise the busbar and breaker compartments and will operate in the zone selected by the unit address switches. VAM L 0 9 X Addr SW OFF L>ext/int Latch L+I / L Zone SENSOR OK 9 ACT 0 TRIP SENSOR INPUTS 9 0 X Figure.: VAM L point sensor I/O unit fron panel. Connection for portable arc sensor (VA DP). Programming switches. POWER indicator light, indicates that the supply voltages of each component are in order.. indicator light, lit when the central unit and I/O units are communicating.. ERROR indicator light, indicates an internal fault detected by the component s self-diagnostics. Such faults include faulty arc sensor or changes in the amount of sensors.. Connector sockets for the VX00 modular cables. LED lights indicating sensor activation. Terminal block for ten arc sensors 9. Portable arc sensor VA DP connected and operational 0. Portable arc sensor activated. I/O unit trip relays activated. Terminal block for output relay

17 O N User interface. VAM LD point sensor I/O unit. VAM LD point sensor I/O unit VAM LD Point sensor I/O unit SENSOR INPUTS 9 0 ADDRESS NR 0. BB FEEDER. CB FEEDER TRIP. CC FEEDER. BB FEEDER. CB FEEDER. CC FEEDER. BB FEEDER 9. BB FEEDER 9 9. BB FEEDER 9 FRT PANEL 0. TIE BREAKER ID X SENSOR INPUTS SW 0 ACT 9 OK SENSOR Zone L/L+I Latch L> Int/ Ext BACK PANEL X 9 0 Figure.: VAM LD point sensor I/O unit front and back panel. Connection for portable arc sensor (VA DP). Programming switches. POWER indicator light, indicates that the supply voltages of each component are in order.. indicator light, lit when the central unit and I/O units are communicating.. ERROR indicator light, indicates an internal fault detected by the component s self-diagnostics. Such faults include faulty arc sensor or changes in the amount of sensors.. Connector sockets for the VX00 modular cables. LED lights indicating sensor activation. Terminal block for ten arc sensors

18 . VAM LD point sensor I/O unit User interface 9. Portable arc sensor VA DP connected and operational 0. Portable arc sensor activated. I/O unit trip relays activated. Terminal block for output relays. Text pocket for sensor specific labels.

19 User interface. VAM C current I/O unit. VAM C current I/O unit OFF Zone Zone Zone Zone VAMC SW X 0 9 X TRIP CURRENT TRANSFORMER L L L xin L/L L/Io 9 0 SW Latch A/A I>out I>in xin.0 L,L L/Io Figure.: VAM C current I/O unit front panel. Programming switches. POWER indicator light, indicates the supply voltages of each component are in order.. indicator light, lit when the central units and I/O units are communicating.. ERROR indicator light, indicates an internal fault detected by the component s self-diagnostics. Such faults include faulty current transformer or phase current unbalance.. Connector sockets for the VX00 modular cables. LED lights indicating that I> stage has started. Terminals for three current transformers. Current transformer programming switches 9. Overcurrent setting knob (I L, I L ), setting range 0. x I N 0. Overcurrent setting knob (I L, I 0 ), setting range 0.0 x I N. I/O unit trip relay activated. Terminal block for external communication and BI/O channels and trip signal. Indicator leds for current setting 9

20 O N. VAM CD current I/O unit User interface. VAM CD current I/O unit VAM CD Current I/O unit ---CURRENTTRANSFORMER--- L L L FEEDER: F0 ADDRESS: ZE: & I> PICK-UP: X In OTHER: I> EXT TRIP FRT PANEL 0 9 L/Io L/L SW xin 0 9 BACK PANEL X 9 0 X SW Zone Zone Zone Zone Figure.: VAM CD current I/O unit front and back panel. Programming switches. POWER indicator light, indicates the supply voltages of each component are in order.. indicator light, lit when the central units and I/O units are communicating.. ERROR indicator light, indicates an internal fault detected by the component s self-diagnostics. Such faults include faulty current transformer or phase current unbalance.. Connector sockets for the VX00 modular cables. LED lights indicating that I> stage has started. Terminals for three current transformers. Current transformer programming switches 0

21 User interface.9 VAMP R trip multiplier relay 9. Overcurrent setting knob (I L, I L ), setting range 0. x I N 0. Overcurrent setting knob (I L, I 0 ), setting range 0.0 x I N. I/O unit trip relay activated. Terminal block for external communication and BI/O channels and trip signal. Indicator leds for current setting. Text pocket.9 VAMP R trip multiplier relay VAMP R 9 X Power Trip Trip TRIP TRIP Vac/dc Vdc INPUTS + OUTPUT TRIPGROUP TRIPGROUP NO NC NO NC NO NC NO NC SF ALARM NO NC X VAMP R frontplate Figure.9: VAMP R trip multiplier relay front panel. POWER LED, indicates that the external operating voltage of + Vdc is connected.. Terminals for external operating voltage (+ Vdc). Can be supplied by central units or I/O units.. Terminals for incoming trip signal (e.g. Vdc from VAM I/O unit binary output, groups). Control voltage range is Vad/dc.. Terminals for outgoing trip signals ( potential-free contacts, normally open, normally closed).

22 Programming switches Programming switches Before system implementation, check the positions of the programming switches in accordance with the following basic principles: Each I/O unit connected to the communication bus has its own address (each I/O unit have an unique address). Set the programming switches before connecting the supply voltage. If you have to change the switch positions once the supply voltage has been connected, disconnect the supply voltage to the unit in question for the duration of the programming and re-configure the system. If position of the switch is changed, re-install the system again in the central unit.. Switches for arc sensor I/O units The programming switches of the I/O units are used to determine the unit address and trip relay function. The system accommodates up to units. Eight addresses are reserved for each protection zone: Zone addresses 0 Zone addresses Zone addresses Zone addresses The programming switches have different weight factors. To create an address for the I/O unit, turn switches with different values to the position and calculate the sum of their weight factors. The following table shows the weight factors of each programming switch. Table.: Programming switch weight factors, *) VAM 0L / VAM 0LD, VAM L / VAM LD, and VAM L / VAM LX only Switch No. *) Weight factor NOTE: Note the position of the VAM LD, VAM 0LD and VAM CD dip switches.

23 Programming switches. Switches for arc sensor I/O units VAML/VAMLX VAMLD/VAM0LD SW OFF L>ext/Int Latch L+I/L Zone SW OFF SENSOR OK ACT TRIP ACT OK SENSOR Zone L/L+I Latch L> ext/int VAM0L/VAML Zone SW OFF L>ext/int Latch L+I/L SENSOR OK ACT TRIP Figure.: Programming switches for VAM 0L, VAM 0LD, VAM L, VAM LD, VAM L and VAM LX VAM 0L / VAM 0LD, VAM L / VAM LX Switch determines which light activation activates the arc stage. When the switch position is, the arc stage only activates on the light information provided by the unit's own sensors. In OFF position the arc stage activates on the light information received from any unit in the same protection zone. Switch determines the trip relay latch. When the switch is in position the trip relay remains engaged after the arc trip until the fault is acknowledged at the central unit s panel. In the OFF position the trip relay follows the arc fault. Switch determines the arc trip criteria. When the switch is in position the trip is based on light information only; in OFF position both fault currents exceeding the current limit and light information are required.

24 . Switches for current I/O units Programming switches VAM L / VAM LD When the L>ext/int DIP switch is in L>int position, the output relays are only activated by dedicated sensors. SENSOR activates T. SENSOR activates T. SENSOR activates T. SENSORS to 0 are normally sending light information to system according to zone setting. If the switch is in L>ext position, all output relays are also controlled by the selected zone information. This activation source can be any sensor channel to 0 or from an external I/O unit configured to the same zone.. Switches for current I/O units The address range for current I/O units is (), -. Do not use address, because in this case the current I/O unit operates in CENTRAL UNIT mode and the actual central unit must be set to SUB-UNIT mode. To determine the address of a current I/O unit, add the sum of the weight factors to (for example, programming switch values total, address of the current I/O unit + = 9). NOTE: Do not use as the unit address if system have central unit. Other programming switches have different functions in different units, as described below.

25 Programming switches. Switches for current I/O units VAM C / VAM CD VAMC SW Zone Zone Zone Zone OFF TRIP SW Latch A/A I>out I>in L,L L/Io xin VAM CD SW OFF Zone Zone Zone Zone SW Latch A/A I>out I>in L,L M.0 L/Io xin Figure.: Programming switches of VAM C / VAM CD Table.: VAMC dipswitches weight factors SW NO: Weight factor

26 . Switches for current I/O units Programming switches Table.: SW switch settings Switch Definition Zone Zone Zone Zone Addr Addr Addr Addr Description System operating zone (light information) System operating zone (light information) System operating zone (light information) System operating zone (light information) Address weighting coefficient Address weighting coefficient Address weighting coefficient Address weighting coefficient Table.: SW switch settings Switch *) As in CT Definition Latch A / A * I> out I> in Description Position 0 (switch down): trip relay is only operational while the protection is activated Position (switch up): trip relay changes to latching status after trip Position 0 (switch down): rated secondary current of the current transformer is A Position (switch up): rated secondary current of the current transformer is A Position 0 (switch down): unit does not transmit the current criteria to other units Position (switch up): unit transmits the current criteria to other units Position 0 (switch down): unit does not receive the current criteria from other units Position (switch up): unit receives the current criteria from other units

27 Adjusting the overcurrent setting Adjusting the overcurrent setting The principles for changing the current setting in VAM C units are the same as for the central unit. You can see the estimated current setting from the led bar on the right side of the unit. The most accurate way of setting the current limit for the unit is as follows: Turn the potentiometer to the maximum value. Feed a test current corresponding to the required setting using a testing device. Lower the setting until the current activation indicator LED of the I/O unit and / or the I>ext indicator LED in VAMP the central unit are / is lit. 0 9 X VAMC SW Zone Zone Zone Zone TRIP CURRENT TRANSFORMER L L L xin POWER ERROR X L/L L/Io VAMc conn Figure.: Adjusting the current setting in VAM C

28 BI/BO connection BI/BO connection Each I/O unit also has a BI/O bus. The light I/O units (VAM 0L / VAM 0LD, VAM L / VAM LD, VAM L / VAM LX) can transmit trip signal to the central unit or current I/O unit. The current I/O unit (VAM C / VAM CD) can receive the light information and send the current information either to other I/O units or the multiplying relay. NOTE: The DI/DO on the VAM units are fast BI/BO signals. The following DI and DO connections are included in the standard delivery of VAM 0L and VAM L / VAM LX: DI GND Trip out GND X- X- X-0 X-9 Zone shift (, (, (, ( Trip signal, V dc Trip signal earth The following DI and DO connections are included in the standard delivery of VAM C units: L>in GND Trip out GND X- X- X-0 GND Light input, V dc Light input earth Trip signal Trip signal earth NOTE: L>in light input in VAM C / VAM CD (X- &X-) is master light input. This means that incoming light zone dip switch settings do not matter and unit trips when this input is active and there is current over the set limit.

29 Connections Connections Grounding of VAM I/O units must be made according to the Construction section in the document. ELECTRICAL SHOCK DANGER Always connect the protective grounding before connecting the power supply. Failure to follow these instructions can result in death or serious injury. 9

30 . VAM L / VAM LX interfaces Connections. VAM L / VAM LX interfaces VAML/LX 0 9 X L>ext/int Latch L+I/L Zone SW SENSOR OK ACT TRIP POWER ERROR SENSOR INPUTS CH CH CH R T R T R T X-R: X-T: X-R: X-T: X-R: X-T: Fiber receiver connection Fiber transmitter connection Fiber receiver connection Fiber transmitter connection Fiber receiver connection Fiber transmitter connection Channel Channel Channel X-: +V supply from master unit or external power supply X-: GND X-: X-: CAN-L CAN-H Zone information (L>, I>) =, X-: X-: Serial B Serial A master slave com X-: DI GND Zone change X-: DI (-Vdc) ( -> ; -> ; -> ; -> ) X-9: X-0: DO GND DO +Vdc Trip signal (DI&DO) X-: X-: + Temp sensor - Temp sensor Not in use X-: X-: X-: Trip relay (NO) X-: Trip relay (NO) 0

31 Connections. VAM 0L interfaces. VAM 0L interfaces VAM 0L 0 9 X L> ext/int Latch L+I/L Zone SW SENSOR OK ACT TRIP POWER ERROR SENSOR INPUTS 9 0 X VAM0L conn X-, : arc sensor channel X-, : arc sensor channel X-, : arc sensor channel X-, : arc sensor channel X-9, 0: arc sensor channel X-, : arc sensor channel X-, : arc sensor channel X-, : arc sensor channel X-, : arc sensor channel 9 X-9, 0: arc sensor channel 0 X-: +V supply from masterunit or external power supply X-: GND X-: X-: CAN-L CAN-H Zone information (L>, I>) =, X-: X-: Serial B Serial A Master slave com X-: DI GND Zone change X-: DI ( Vdc) ( -> ; ->; -> ; -> ) X-9: X-0: DO GND DO +Vdc Trip signal X-: X-: + Temp sensor - Temp sensor Not in use X-: X-: X-: Trip relay (NO) X-: Trip relay (NO)

32 O N. VAM 0LD interfaces Connections. VAM 0LD interfaces X SENSOR INPUTS SW ACT OK SENSOR Zone L/L+I Latch L> Int/ Ext X 9 0 X-, : arc sensor channel X-, : arc sensor channel X-, : arc sensor channel X-, : arc sensor channel X-9, 0: arc sensor channel X-, : arc sensor channel X-, : arc sensor channel X-, : arc sensor channel X-, : arc sensor channel 9 X-9, 0: arc sensor channel 0 X-: +V supply from masterunit or external power supply X-: GND X-: X-: CAN-L CAN-H Zone information (L>, I>) =, X-: X-: Serial B Serial A Master slave com X-: DI GND Zone change X-: DI (-Vdc) ( -> ; ->; -> ; -> ) X-9: X-0: DO GND DO +Vdc Trip signal X-: X-: + Temp sensor - Temp sensor Not in use X-: X-: X-: Trip relay (NO) X-: Trip relay (NO)

33 Connections. VAM L interfaces. VAM L interfaces VAM L 0 9 X SW OFF L> ext/int Latch L+I/L Zone SENSOR OK ACT TRIP POWER ERROR SENSOR INPUTS 9 0 X VAML conn X-, : X-, : X-, : X-, : X-9, 0: X-, : X-, : X-, : X-, : X-9, 0: X-: X-: arc sensor channel arc sensor channel arc sensor channel arc sensor channel arc sensor channel arc sensor channel arc sensor channel arc sensor channel arc sensor channel 9 arc sensor channel 0 +v supply from masterunit or external power supply GND X-: X-: X-: X-: X-: X-: X-9: X-0: X-: X-: X-: X-: X-: X-: NO NC Trip relay (NO) Trip relay (NO) Trip relay (NO) Trip relay (NO) Trip relay (NO) Trip relay (NO) Alarm

34 O N. VAM LD interfaces Connections. VAM LD interfaces X SENSOR INPUTS SW ACT OK SENSOR Zone L/L+I Latch L> Int/ Ext X 9 0 X-, : X-, : X-, : X-, : X-9, 0: X-, : X-, : X-, : X-, : X-9, 0: X-: X-: X-: X-: X-: X-: X-: X-: X-9: X-0: X-: X-: X-: X-: X-: X-: arc sensor channel arc sensor channel arc sensor channel arc sensor channel arc sensor channel arc sensor channel arc sensor channel arc sensor channel arc sensor channel 9 arc sensor channel 0 +v supply from masterunit or external power supply GND NO NC Trip relay (NO) Trip relay (NO) Trip relay (NO) Trip relay (NO) Trip relay (NO) Trip relay (NO) Alarm

35 Connections. VAM C interfaces. VAM C interfaces 0 9 X VAMC SW Zone Zone Zone Zone TRIP.0 POWER.0 xin.0 ERROR 0. CURRENT TRANSFORMER L L L 0. X L/L L/Io VAMc conn X-, : Current input IL X-, : Current input IL / Io X-9, : Current input IL X-: +V supply from master unit or external power supply X-: GND X-: X-: CAN-L CAN-H Zone information (L>, I>) =, X-: X-: Serial B Serial A master slave com X-: X-: DI GND DI (-Vdc) L> X-9: X-0: DO GND DO +Vdc TRIP X-: X-: X-: X-: X-: Trip relay (NO) X-: Trip relay (NO)

36 N. VAM CD interfaces Connections. VAM CD interfaces L/Io L/L SW 0 9 X.0.0 SW xin O Zone Zone Zone Zone X 9 0 X-, : Current input IL X-, : Current input IL / Io X-9, : Current input IL X-: +V supply from master unit or external power supply X-: GND X-: X-: CAN-L CAN-H Zone information (L>, I>) =, X-: X-: Serial B Serial A master slave com X-: X-: DI GND DI (-Vdc) L> X-9: X-0: DO GND DO +Vdc TRIP X-: X-: X-: X-: X-: Trip relay (NO) X-: Trip relay (NO)

37 Connections. VAMP R interfaces. VAMP R interfaces VAMP R 9 X Power Trip Trip TRIP TRIP Vac/dc Vdc INPUTS + OUTPUT TRIP GROUP TRIP GROUP NO NC NO NC NO NC NO NC SF ALARM NO NC X X-, : X-, : X-, : X-, : X-9, 0: X-, : X-, : X-, : X-: X-: X-9: X-0: X-: X-: X-: X-: X-: X-: X-: X-: X-9: X-0: X-: X-: Trip relay (NO), Trip group. Trip relay (NC), Trip group. Trip relay (NO), Trip group. Trip relay (NC), Trip group. Trip relay (NO), Trip group. Trip relay (NC), Trip group. Trip relay (NO), Trip group. Trip relay (NC), Trip group. NO NC Aux voltage supply +Vdc GND Aux voltage supply +Vdc GND Aux voltage supply +Vdc GND TRIP. Input Vac/dc TRIP. Input Vac/dc TRIP. Input Vac/dc TRIP. Input Vac/dc SF Alarm relay Trip group. Trip group.

38 I/O Technical data I/O Technical data. Connections Table.: VAM L Sensor connections fibre loop sensors (type ARC-SLx) portable arc sensor (type VA DP) Table.: VAM LX Sensor connections fibre loop sensors (type ARC-SLx) - sensitivity adjust range compared to L 0. (max). (min) portable arc sensor (type VA DP) Table.: VAM 0L, VAM 0LD, VAM L, VAM LD Sensor connections 0 arc sensors (type VA DA or VA EH) portable arc sensor (type VA DP) Terminal: - MSTB. -.0 Cross-section area of wire Maximum. mm ( AWG) Minimum. mm ( AWG) Table.: VAM C, VAM CD Rated current L / L - current measuring zone - thermal withstand capability - power consumption or A (optional) 0/0Hz 0 A (0 *I N [I N =A]); 0 0 A (0 * I N [I N =A]) 00 A (for s) 00 A (for 0s) 0 A (continuous) <0. VA Rated current L / I 0 - current measuring zone - thermal withstand capability - power consumption or A (optional) 0/0Hz 0 A (0 *I N [I N =A]); 0 0 A (0 * I N [I N =A]) 00 A (for s) 00 A (for 0s) 0 A (continuous) <0. VA Terminal: - single or multi-strand wire Cross-section area of wire Maximum mm ( AWG) Minimum. mm ( AWG)

39 I/O Technical data. Auxiliary power supply. Auxiliary power supply Table.: VAM 0L, VAM 0LD, VAM L, VAM LD, VAM C, VAM CD, VAM L, VAM LX Rated voltage U AUX Power consumption V dc < W (in normal mode) <. W (output relays activated) Terminal: - MSTB. -.0 ( RJ when supply from central unit) - Cross-section area of wire Maximum. mm ( AWG) Minimum. mm ( AWG) Table.: VAMP R Rated voltage U AUX Current consumption - one relay group activated - both relay groups activated V dc 0 ma stby 0 ma 0 ma Table.: VA DA, VA EH, VA DP Rated voltage U AUX Power consumption V dc (from I/O unit) < mw (in normal mode) < 0 mw (activated). Digital inputs No digital inputs available in VAM L and VAM LD Table.: VAM 0L, VAM 0LD, VAM L, VAM LX Number of inputs pcs I> in arc fault trip out Internal operating voltage V dc (BIO in) V dc (BIO out) Load capacity (max.) Terminal: - MSTB. -.0 ma Cross-section area of wire Maximum. mm ( AWG) Minimum. mm ( AWG) 9

40 . Trip contacts I/O Technical data Table.9: VAM C Number of inputs pcs L> in pcs I> out Internal operating voltage V dc (BIO in) V dc (BIO out) Load capacity (max.) Terminal: - MSTB. -.0 ma Cross-section area of wire Maximum. mm ( AWG) Minimum. mm ( AWG) Table.0: VAMP R Operating voltage Current consumption V ac/dc ma. Trip contacts Table.: VAM 0L, VAM 0LD, VAM L, VAM LD, VAM C, VAM CD, VAM L, VAM LX Number of contacts closing contact (relay T) for VAM 0L, VAM 0LD, VAM C, VAM CD, VAM L, VAM LX Number of contacts closing contacts (relay T) for VAM L, VAM LD Rated voltage Continuous withstand capacity Make and carry for 0.s Make and carry for s 0 V ac/dc A 0 A A Breaking capacity, dc(l/r=0 ms) At V dc: At 0 V dc: At 0 V dc: Relay material Terminal: - MSTB. -.0 A 0. A 0. A AgNi 90/0 Cross-section area of wire Maximum. mm ( AWG) Minimum. mm ( AWG) 0

41 I/O Technical data. Disturbance tests Table.: VAMP R N/O / N/C rated voltage Operation time (typical) Continuous withstand capacity Make and carry for 0.s Make and carry for s 0V ac/dc < 0 ms A 0 A A N/O breaking capacity dc (L/R=0ms) At V dc At 0 V dc At 0 V dc Contact material Terminal: - MSTB. -.0 A 0. A 0. A AgNi 90/0 Cross-section area of wire Maximum. mm ( AWG) Minimum. mm ( AWG). Disturbance tests Table.: Disturbance tests Test Emission - Conducted - Emitted Immunity - Mhz damped oscillatory wave - Static discharge (ESD) - Emitted HF field - Fast transients (EFT) - Surge - Conducted HF field - Power-frequency magnetic field - Pulse magnetic field Standard & Test class / level EN / IEC 0- EN 0, Class A / IEC 0- EN 0, Class A / IEC 0- EN / IEC 0- IEC 0-- EN Level / IEC 0-- Class EN Level / IEC 0-- EN Level / IEC 0-- Class A EN Level / IEC 0-- EN Level / IEC 0-- EN EN Level Test value MHz MHz ±.kvp CM, ±.0kVp DM kv contact, kv air 0-00 MHz, 0 V/m kv, /0 ns, khz kv,./0 µs, CM kv,./0 µs, DM MHz, 0 Vemf 00A/m (continuous), 000A/m - s 000A/m,./0 µs

42 . Electrical safety tests I/O Technical data. Electrical safety tests Table.: Electrical safety tests Test - Impulse voltage withstand - Dielectric test - Insulation resistance - Protective bonding resistance Standard & Test class / level EN 0-, Class III EN 0-, Class III EN 0- EN 0- Test value kv,./0 ms, 0. J kv, 0 Hz. Environmental conditions Table.: Environmental conditions Operating temperature range - Transport and storage temperature range - VAM I/O units - ARC SLm, VA xx sensors - Relative air humidity -0 C ( F) -0 0 C (-0 F) -0 C (-0 F) < % ( year, average) < 90% (0 days per year, condensation not allowed) Maximum operating altitude 000 m (. ft). Package Table.: Package Dimensions (WxHxD) VAMP R, VAM 0L, VAM C, VAM L, VAM LX Weight (unit, box and user instructions) VAMP R, VAM 0L, VAM C, VAM L, VAM LX - x 9 x mm /. x. x 0.9 in - 0. kg (.9 lb)

43 I/O Technical data.9 Casing.9 Casing Table.: VAM 0L, VAM C, VAMP R, VAM L, VAM LX Housing class (IEC 09) Housing class (NEMA) Housing class (UL 0) Dimensions (W x H x D) Material Weight Colour code IP NEMA Open type x 9 x mm /. x. x 0.9 in mm (0.09 in) steel plate 0. kg (. lb) RAL 0 (housing) / RAL 00 (back plate) Table.: VAM 0LD, VAM LD, VAM CD Housing class (IEC 09) Housing class (NEMA) IP Front: NEMA Rear: NEMA Housing class (UL 0) Front: Open type Rear: Open type Dimensions (W x H x D) Material Weight Colour code x 0 x mm /. x. x 0.9 in mm (0.09 in) steel plate 0.0 kg (. lb) RAL 0 (housing) / RAL 00 (back plate) Table.9: VA DA, VA EH, VA DP Housing class (IEC 09) Housing class (NEMA) Housing class (UL 0) Dimensions (W x H x D) IP NEMA Open type x x mm (VA DA) Φ x mm (VA EH) Φ0 x mm (VA DP) Material Weight Cable length Plastic 0.0 kg VA DA and VA EH: m or 0 m VA DP: m

44 9 Construction 9 Construction 9. Dimensional drawings 9.. VAM L / LX Din rail mounting VAM L/LX DIN RAIL MOUNTING mm in VAM L / LX 9.. L>ext/Int. VAM L / LX L>ext/Int 0.9 T max N m.-. lb-in V A M L / L X L>ext/Int mm /. in VAM L / LX L>ext/Int

45 9 Construction 9. Dimensional drawings 9.. VAM 0L Din rail mounting VAM 0L DIN RAIL MOUNTING mm in T max N m.-. lb-in mm /. in EN 00

46 9. Dimensional drawings 9 Construction 9.. VAM 0LD Flush mounting VAM 0LD FLUSH MOUNTING mm in T max N m.-. lb-in ø Ground screw terminal Min.. mm / Ø0.0 in (# - # AWG)

47 9 Construction 9. Dimensional drawings 9.. VAM L Din rail mounting VAM L DIN RAIL MOUNTING mm in T max N m.-. lb-in mm /. in EN 00

48 9. Dimensional drawings 9 Construction 9.. VAM LD Flush mounting VAM LD FLUSH MOUNTING mm in T max N m.-. lb-in ø Ground screw terminal Min.. mm / Ø0.0 in (# - # AWG)

49 9 Construction 9. Dimensional drawings 9.. VAM C Din rail mounting VAM C DIN RAIL MOUNTING mm in T max N m.-. lb-in mm /. in EN 00 9

50 9. Dimensional drawings 9 Construction 9.. VAM CD Flush mounting VAM CD FLUSH MOUNTING mm in T max N m.-. lb-in ø Ground screw terminal Min.. mm / Ø0.0 in (# - # AWG)

51 9 Construction 9. Dimensional drawings 9.. VAMP R Din rail mounting VAMP R DIN RAIL MOUNTING mm in. - Vac/dc Vac/dc 0.9 T max N m.-. lb-in mm /. in EN 00 - Vac/dc

52 Dimensional drawings 9 Construction 9..9 VA DA mm in VA EH mm in. 0. VAEH_mittakuva

53 9 Construction 9. Dimensional drawings 9.. VYX 00 mm in

54 9. Dimensional drawings 9 Construction 9.. VYX 00 mm in

55 9 Construction 9. I/O unit mounting and wiring 9. I/O unit mounting and wiring CAUTI Read this User's Manual carefully before undertaking any installation or wiring work. Safety instructions Always observe the national electrical safety regulations when working under live conditions. The unit manufacturer is not liable for damage due to incorrect working methods or failure to observe safety instructions. The correct handling of the unit under all mounting and operating conditions forms the foundation for its safe use. CAUTI Any separately marked notes and warnings must be observed. The wiring work must be performed according to national standards and any requirements specified by the customer. Do not connect the auxiliary supply voltage until the installation has been completed. Before installation Before installation, make sure the environmental conditions comply with the requirements specified in Chapter. CAUTI The unit contains components liable to damage if exposed to an electrostatic discharge (ESD). Do not open the unit unless you have taken appropriate protective measures against ESD. The manufacturer cannot guarantee operational safety in environments that do not satisfy the specified environmental conditions.

56 9. Connecting the VAMP I/O units 9 Construction 9.. VAM 0L, VAM L, VAM C, VAM L, VAM LX The units are designed for mounting on a DIN rail. Mount the units on the rail in such a way that the indicator lights on the front panel are visible and the sensor wiring can be made as easily as possible. 9.. VAM 0LD, VAM LD, VAM CD The units are designed for mounting on a door. Hence all indicators are clearly visible in normal operation. 9. Connecting the VAMP I/O units The I/O units can be connected to the components listed below: Enclosure current transformer secondary circuits (VAM C and VAM CD I/O units only) Circuit breaker trip circuits External auxiliary supply circuits Connections to the VAMP central unit or other I/O units (data communication and auxiliary supply) Connections to other central units or detection relays (digital input (DI) or digital output (DO) bus) 9. Connecting the secondary circuits of the current transformers (VAM C / VAM CD only) Connect the secondary circuits of the current transformers to the following screw connectors: X-, X- (L ) X-, X- (L /I 0 ) X-9, X- (L ) The arc protection system can also be single or two-phase connected. Three-phase connection is nevertheless recommended for optimal operating speed.

57 9 Construction 9. Connecting the secondary circuits of the current transformers (VAM C / VAM CD only) DANGER HAZARD OF ELECTRICAL SHOCK Do not open the secondary circuit of a live current transformer. Disconnecting the secondary circuit of a live current transformer may cause dangerous overvoltages. Failure to follow these instructions will result in death or serious injury. NOTE: The current measuring channels L and L must be used in connection with two-phase current measuring. Single-phase current or ground fault current must always be connected to the current measuring channel L /I 0 ; otherwise, an unbalance error will occur. The specified operating time can only be guaranteed for three-phase current measurement and with the proper voltage supply to all system components, minimum allowed auxiliary voltage is. Vdc. The VAM C overcurrent unbalance alarm settings recognizes if the two-phase or three-phase monitoring is being used based on the connections made to the unit and the overcurrent limits set for each connection. The two-phase connection monitoring is triggered when the L /I 0 connection overcurrent limit differs from the L /L overcurrent limit settings by 90% or more. This is because in the event two-phase monitoring is used, the L /I 0 connection is the connection used to monitor the ground current. Therefore, the current limit set for the L /I 0 connection should reflect limits associated with anticipated ground currents. The remaining L /L currents should be balanced, and overcurrent settings for the L /L connection should be reflected as such. The two-phase monitoring mode is also referred to as ground-fault mode. The three-phase monitoring is triggered when the L /I 0 and L /L overcurrent limit settings are similar, reflecting that each phase is understood to be in balance with the other two phases. If detected, the system gives an unbalance alarm after a 0-second delay time. The alarm does not affect other operations of the arc detection system. The phase discontinuity settings are non-adjustable since all the setting values have been programmed in the current-monitoring unit.

58 9. Connecting the trip circuits of the circuit breakers 9 Construction 9. Connecting the trip circuits of the circuit breakers Connect the circuit breaker s trip circuit to the following pins: TRIP: X-, X- For example, in the event of an arc fault, the output contact will close at specified time when three-phase current measurement is used. The output trip relay of the light I/O units (VAM 0L and VAM L) operates during faults in its own zone. In the current I/O unit (VAM C), select the protection zone controlling the I/O unit using the programming switches. If several trips are required, the multiplying relay VAMP R can be used. If VAMP R is used, make sure that proper voltage supply is connected to device. 9. Connecting between the central unit and the I/O unit Connect the central unit to the I/O units with a modular cable of type VX00. The modular cable carries all information between the central unit and I/O units, including data in serial form, arc fault messages and operating supply to the I/O units. Connect the VX00 cable to the arc I/O interface of the central units. Connect the cable to or on the first I/O unit. Route the cable from or on the first I/O unit to or in the next unit, etc. All the and interfaces are identical, i.e. the cable can always be connected to either interface. The maximum total length of the modular cable, taking into account all the I/O units connected to the central unit, is 00 m. NOTE: Use only star connection for I/O units. Maximum single bus cable length is 0 meters. CAUTI HAZARD OF EQUIPMENT DAMAGE Do not connect modular cables closed loop. Failure to follow these instructions can result in personal injury or equipment damage.

59 9 Construction 9. Connecting separate auxiliary supplies NOTICE HAZARD OF EQUIPMENT DAMAGE Only VAMP communication cable type VX00 shall be used. Modular cable wiring shall be placed on the control cabling trays as far from the primary cable, bus bar and bus ducts as possible. Do not connect Ethernet to ARC I/O Bus! Failure to follow these instructions can result in equipment damage. 9. Connecting separate auxiliary supplies When routing modular cables over long distances (0 meters of modular cabling) or when the system contains more than I/O units you should preferably use a separate auxiliary +Vdc voltage supply with output monitoring along with the modular bus cabling. Recommended types of power supplies with output monitoring:. Phaseo ABLRSM0 Vdc). Phaseo ABLRSM00 Vdc). or any equivalent type of power supply with above functionality NOTE: Use of power supplies without voltage monitoring is not recommended. Connect the auxiliary supply to the V terminals of the last I/O unit. Use at least.mm (AWG ) size twisted pair cable. NOTE: It is recommended to use external wiring to connect auxiliary supply to all units. Pay particular attention to the polarity of the wire and cable connections. Additional power supply cabling is recommended, min.. mm (AWG ) Power supply cabling, min.. mm (AWG ) Modular Arc I/O bus cable 9

60 9. Connecting separate auxiliary supplies 9 Construction Vdc ~ VAM X VAM R 0 9 0L X int L>ext/ Latch L+I/L Zone X TRIP int L>ext/ Latch L+I/L Zone 0 9 S R INPUT SENSO R ERROR OK ACT TRIP 9 S R INPUT SENSO X X X POWE ACT R SENSO O N ACT SW OK O N ERROR R SENSO SW TRIP 0L VAM R POWE ERROR OK O N int L>ext/ Latch L+I/L Zone Vamp L POWE R SENSO SW OK F F O I Figure 9.: External power supply wiring Vdc ~ VAM X VAM 0 9 0L X VAM 0 9 0L X VAM POWER 0 9 0L POWER X POWER L>ext/in Latch L+I/L Zone 0 9 R INPUTS SENSO TRIP 9 L>ext/in Latch L+I/L Zone 0 9 R INPUTS SENSO 9 0 t ERROR OK SENSOR SW ACT TRIP t L>ext/in Latch L+I/L Zone 0 9 R INPUTS SENSO OK ACT TRIP 0 R INPUTS SENSO 9 0 X X X SENSOR O N TRIP SW OK ACT O N ACT SENSOR O N t L>ext/in Latch L+I/L Zone O N Vamp 00 SW t ERROR ERROR ERROR OK 0L POWER SENSOR SW 9 0 X OK F F I O Vdc ~ VAM X 0 9 VAM X VAM 9 0 SENSOR SW OK ACT TRIP 9 R INPUTS SENSO 9 0 X t L>ext/in Latch L+I/L Zone 0 9 SENSOR 9 9 POWER R INPUTS SENSO 9 0 X ERROR t L>ext/in Latch L+I/L Zone 0 0 OK ACT TRIP 0 9 R INPUTS SENSO X X X SENSOR SW OK ACT TRIP 0L O N R INPUTS SENSO VAM O N t L>ext/in Latch L+I/L Zone 0 9 POWER ERROR SW 0 X ERROR L POWER ERROR ACT TRIP 0 9 0L OK O N SENSOR O N t L>ext/in Latch L+I/L Zone 0L POWER SW Two branch design, length of cabling must not exceed 00 m combine total in both branches. Figure 9.: Protection system wiring configuration 0 9 VAM X 0 9 VAM 0L X 0 9 0L R X 0 9 0L VAM R POWE POWE R X POWE 0 ACT TRIP X int L>ext/ Latch L+I/L Zone S R INPUT SENSO 9 0 X int L>ext/ Latch L+I/L Zone SW OK 9 OK SW ACT TRIP 0 S R INPUT SENSO X 9 0 R ERRO R SENSO int L>ext/ Latch L+I/L Zone R ERRO R SENSO OK O N TRIP SENSO O N OK ACT SW O N O N int L>ext/ Latch L+I/L Zone Vamp 00 ERRO R ERRO R SENSO R R R SW 0L VAM POWE ACT TRIP 0 9 S R INPUT SENSO X OK F F I O If four or less I/O units are used, total cable length is below 0 m. No power supply is needed. Figure 9.: Small protection system wiring configuration, one branch design 0

61 OK L>ext/int Latch L+I/L Zone SW O N X SENSOR OK ACT TRIP SENSOR INPUTS X POWER ERROR L>ext/int Latch L+I/L Zone SW O N X SENSOR OK ACT TRIP SENSOR INPUTS X POWER ERROR L>ext/int Latch L+I/L Zone SW O N X SENSOR OK ACT TRIP SENSOR INPUTS X POWER ERROR L>ext/int Latch L+I/L Zone SW O N X SENSOR OK ACT TRIP SENSOR INPUTS X POWER ERROR 9 Construction 9. VAMP R + Vdc ~ VAM 0L 0 9 VAM 0L 0 9 VAM 0L 0 9 VAM 0L 0 9 Vamp X X X X I O F F Systems having more than four I/O units must be equipped with separate auxiliary supply. Figure 9.: Protection system wiring configuration, one branch design 9. VAMP R - V ad/dc + Vdc :X VAMP R Group Group Self super vision alar m X: Figure 9.: VAMP R block diagram The multiplying relay VAMP R can be used when additional trip outputs are needed. VAMP R comprises N/O contacts and N/C contacts. They are divided into two separate groups which can be independently controlled by e.g. the binary output of the I/O units or the central unit. Attach the VAMP R unit to a DIN rail. Connect the auxiliary voltage ( +V ) to terminal X- (+) and X- (-). Terminals X- and X- are parallel inputs to X-(+). Terminals X- and X- are parallel inputs to X-(). The auxiliary voltage ( +V ) can be supplied from the central unit or nearest slave ( X- (+), X- (-)). Connect the required signal (- V ad/dc) to the trip control inputs. Input TRIP ( X-, X- ) is controlling the trip group. Input TRIP ( X-, X-9 ) is controlling the trip group. There are xn/c + xn/o contacts per trip group.

62 9.9 Wiring multiple central units 9 Construction If necessary, input TRIP and can be connected in parallel. Then all trip relays will operate simultaneously. 9.9 Wiring multiple central units A maximum of I/O units and/or central units in slave mode can be connected to one communication bus. In this case, the units can operate on a maximum of four protection zones (depending on their programming switches). The light and current signals given by the I/O units, including address information, are transferred to each central unit. If more than one central unit is to be connected to the same communication bus, one central unit must be in central unit mode and the other central units in sub-unit mode. In applications with multiple central units the central units can be interconnected also via BI/O connections (binary input/output). In this case, each part of the system can control four protection zones per system communication bus. In this case, arc and overcurrent information is transferred between the central units without address information. NOTE: When configurating Vamp arc protection system with multiple central units, disconnect I/O-units from central units in slave mode during their installation procedure. 9.0 Arc sensors Mount the sensors on the switchgear in such a way that they cover the protection zone as completely as possible. The line of sight must be free between the sensor and the supervised area. If point sensors are used in open compartments (such as bus-bar sections), there should be a sensor approximately every meters. Due to the wide detection range of the sensors and the light reflection inside the switchgear, the mounting position is not critical. Connecting sensors VA DA and VA EH to the I/O units The sensors are delivered with -metre standard cables or 0-metre shielded cables (to be specified in the order). After mounting the sensors, connect them to the I/O units as follows: Draw the wire to the nearest I/O unit using the shortest route possible and cut it to a suitable length. Connect the arc sensors to the screw terminals X- 0. The polarity of the arc sensor cables is not critical.

63 9 Construction 9.0 Arc sensors Connecting the ARC-SLx sensors to the I/O units The sensors are delivered in standard lengths (to be specified in the order) equipped with terminals compatible with VAM L units. After mounting the sensors, connect them to the I/O units as follows: Draw each end of the sensor to the I/O unit and carefully form a loop of the extra fibre. Connect the arc sensors to plug-in terminals X-R, T R, T. While the polarity of the arc sensors is not critical, you must connect each end of the fibre to the same channels. NOTE: Check that the sensor positioning has not changed during shipping and commissioning. Use a separate VAMP Arc Flash Protection Testing Manual for testing testing each sensor during commissioning VA DA You can be install the arc sensor onto the switchgear wall from the outside. Press the active part of the sensor through the 0-mm hole in the wall and fix it using a -mm screw. VADA_asennus Figure 9.: Mounting the arc sensor VA DA Active part of the sensor Cable clamp Fastening screw x mm Cable of sensor You can also surface mount the sensor to the wall using the mounting plates VYX0 or VYX0, available as additional parts.

64 9.0 Arc sensors 9 Construction NOTE: The sensor must not be exposed to direct sunlight or other strong light. Do not mount the sensor directly under a light source. Figure 9.: Arc sensor VA DA Figure 9.: Sensitivity of the arc sensor VA DA 9.0. VA EH You can be install the arc sensor onto the switchgear wall from the outside. Press the active part of the sensor through the 0.-mm hole in the wall. You can also surface mount the sensor. To do this, push the sensor into a plastic mounting tube and fix it with heat shrink tubing. NOTE: The sensor must not be exposed to direct sunlight or other strong light. Do not mount the sensor directly under a light source. Figure 9.9: Arc sensor VA EH

65 9 Construction 9.0 Arc sensors 9.0. ARC-SLx ARC-SLx is an fibre sensor that can be mounted on the switchgear to monitor several compartments simultaneously (various bus-bar compartmets, etc.). The fibre must not touch any live parts of the switchgear or other hot components, since too high temperatures may destroy the fibre. When mounting the sensor on the switchgear, ensure that the bending radius is long enough (min. 0 mm) and that it is safe from the sharp edges of the switchgear. NOTE: The sensor must not be exposed to direct sunlight or other strong light. Do not mount the sensor directly under a light source. To avoid false tripping, cover any unused channels of the I/O unit. Figure 9.0: ARC-SLx 9.0. VA DP The portable pin sensor can be temporarily connected to the I/O units. It is used to improve safety when working with live switchgear, for example, Attach the sensor close to the working area, for example in the breast pocket of the maintenance man. A pin sensor operates in the same way as a fixed arc sensor. The only difference is free mobility within the limits of the connecting cable. Figure 9.: Pin sensor VA DP

66 9.0 Arc sensors 9 Construction NOTE: To avoid faulty tripping, disconnect the pin sensor from the system immediately after use. DANGER HAZARD OF ELECTRIC SHOCK, ELECTRIC ARC OR BURNS Ensure that trip signal will control main breaker in case of Arc flash incident! Failure to follow these instructions will result in death or serious injury.

VAM I/O units. Publication version: VIOen M/A001. User manual

VAM I/O units. Publication version: VIOen M/A001. User manual Publication version: User manual Trace back information: Workspace Main version a Checked in 2012-10-1 Skribenta version 03 Contents Contents 1 This document... 1.1 Legal notice... 1.2 Safety information...

More information

VAMP 221. Table of Contents

VAMP 221. Table of Contents 2 V221/EN M/E019 VAMP 221 Table of Contents Table of Contents 1. General... 7 1.1. VAMP 221 arc protection system components... 7 1.1.1. Central unit VAMP 221... 9 1.1.2. I/O units VAM 12L / VAM 12 LD,

More information

ACCESS 9340/9360 Meter Input/Output Module

ACCESS 9340/9360 Meter Input/Output Module Installation Manual PMIM-IOMOD-0208 ACCESS 9340/9360 Meter Input/Output Module 9340-60-I/O2222 and 9340-60-I/O26 HAZARD CATEGORIES AND SPECIAL SYMBOLS Read these instructions carefully and look at the

More information

INSTRUCTION MANUAL TRIP CIRCUIT SUPERVISION RELAY GKAD1

INSTRUCTION MANUAL TRIP CIRCUIT SUPERVISION RELAY GKAD1 INSTRUCTION MANUAL TRIP CIRCUIT SUPERVISION RELAY GKAD1 TOSHIBA Corporation 2004 All Rights Reserved. ( Ver. 1.6 ) Safety Precautions Before using this product, please read this chapter carefully. This

More information

Sensitive Earth-fault Relay SPAJ 111 C. Product Guide

Sensitive Earth-fault Relay SPAJ 111 C. Product Guide Issued: April 1999 Status: Update Version: C/12.04.2006 Data subject to change without notice Features Sensitive low-set neutral overcurrent stage with definite time characteristic High-set neutral overcurrent

More information

Earth-fault Relay SPAJ 110 C. Product Guide

Earth-fault Relay SPAJ 110 C. Product Guide Issued: April 1999 Status: Updated Version: C/12.04.2006 Data subject to change without notice Features Low-set neutral overcurrent stage with definite time or inverse time characteristic High-set neutral

More information

ARCON 2.0 Arc protection system. Operation and configuration instructions Technical description.

ARCON 2.0 Arc protection system. Operation and configuration instructions Technical description. ARCON 2.0 Arc protection system Operation and configuration instructions Technical description Eaton Industries (Austria) GmbH, Eugenia 1, A-3943 Schrems www.eaton.eu/documentation 1 MA_Arcon_en.qd/04.2018b

More information

Feeder protection relay SPAA 121 C. Product Guide

Feeder protection relay SPAA 121 C. Product Guide Issued: April 1999 Status: Updated Version: C/06.03.2006 Data subject to change without notice Features Two-phase low-set phase overcurrent unit with definite time or inverse time characteristic Two-phase

More information

Residual overvoltage relay

Residual overvoltage relay Page 1 Issued: April 1999 Status: New Data subject to change without notice Features Definite-time residual overvoltage earthfault protection and supervision Two independent operation stages, e.g. one

More information

Combined Overcurrent and Earth-fault Relay SPAJ 140 C. Product Guide

Combined Overcurrent and Earth-fault Relay SPAJ 140 C. Product Guide Combined Overcurrent and Earth-fault Product Guide Issued: April 1999 Status: Updated Version: C/18.04.2006 Data subject to change without notice Features Three-phase, low-set phase overcurrent unit with

More information

Arc protection relay. Features Three-phase overcurrent function. Application

Arc protection relay. Features Three-phase overcurrent function. Application Arc protection relay REA 10_ Page 1 Issued: May 1999 Status: New Data subject to change without notice Features Three-phase overcurrent function Loop-type or radial sensor fibre for arc detection Two high-speed

More information

SIPROTEC easy 7SJ45 Numerical Overcurrent Protection Relay Powered by CTs

SIPROTEC easy 7SJ45 Numerical Overcurrent Protection Relay Powered by CTs SIPROTEC easy 7SJ4 Numerical Overcurrent Protection Relay Powered by CTs Function overview Fig. /1 Description The SIPROTEC easy 7SJ4 is a numerical overcurrent protection relay which is primarily intended

More information

Synchro-check relay. Application

Synchro-check relay. Application Issued: April 1999 Status: Updated Version: B/08.11.2001 Data subject to change without notice Features Two identical operation stages allowing the closing conditions of two separate circuit breakers to

More information

EH-RIO IP67 Profibus-DP I/O modules

EH-RIO IP67 Profibus-DP I/O modules Installation Instructions EH-RIO IP67 Profibus-DP I/O modules (RIO-PBXDP8M12, -PBXDP8M8, -PBYTP8M12, -PBYTP8M8, -PBXYP8M12, -PBXYP8M8) M12 Style Connectors M8 Style Connectors 43819 The EH-RIO IP67 Profibus-DP

More information

Voltage regulator. SPAU 341 C 1MRS MBG Issued: July 1998 Status: Revised Version: C/ Data subject to change without notice

Voltage regulator. SPAU 341 C 1MRS MBG Issued: July 1998 Status: Revised Version: C/ Data subject to change without notice Issued: July 1998 Status: Revised Version: C/08.10.2003 Data subject to change without notice Features Comprehensive voltage regulation for power transformers with on-load tapchangers in distribution substations

More information

Combined Overcurrent and Earth-fault Relay SPAJ 141 C. Product Guide

Combined Overcurrent and Earth-fault Relay SPAJ 141 C. Product Guide Combined Overcurrent and Earth-fault Product Guide Issued: April 1999 Status: Updated Version: C/19.04.2006 Data subject to change without notice Features Three-phase, low-set phase overcurrent unit with

More information

Feeder/ Motor Protection Relay VAMP 40

Feeder/ Motor Protection Relay VAMP 40 Feeder/ Motor Protection Relay Feeder/motor protection relay Main characteristics Complete protection Comprehensive selection of protection functions for distribution network overhead line feeders, cable

More information

CompactBlock Guard I/O EtherNet/IP Safety Modules

CompactBlock Guard I/O EtherNet/IP Safety Modules Installation Instructions CompactBlock Guard I/O EtherNet/IP Safety Modules Catalog Numbers 1791ES-IB8XOBV4, 1791ES-IB16 Topic Page Important User Information 2 North American Hazardous Location Approval

More information

FL MC 2000E (SM40) LC

FL MC 2000E (SM40) LC IEC 61850 fiber optic converter with LC fiber optic connection (1310 nm) to convert 100Base-Tx to single- or multi-mode fiber glass Data sheet 3205_en_C 1 Description PHOENIX CONTACT 2014-04-04 2 Features

More information

PowerLogic High Density Metering System 1-Meter Enclosure

PowerLogic High Density Metering System 1-Meter Enclosure PowerLogic High Density Metering System 1-Meter Enclosure Installation Guide 63230-508-211A1 Safety information PowerLogic High Density Metering System 1-Meter Enclosure Important information Read these

More information

Embedded I/O Expansion Board with 10 Outputs

Embedded I/O Expansion Board with 10 Outputs Installation Instructions Embedded I/O Expansion Board with 10 Outputs Catalog Number 1799-OQ10X Topic Page Important User Information 2 Environment and Enclosure 3 About the Board 4 Install the Board

More information

SCADAPack E 5405 Digital Input Hardware Manual

SCADAPack E 5405 Digital Input Hardware Manual SCADAPack E 5405 Digital Input Hardware Manual 2 SCADAPack E 5405 Digital Input Hardware Manual Table of Contents Part I 5405 Digital Input Module 3 1 Technical... Support 3 2 Safety... Information 4 3

More information

1S20. Arc Fault Monitor Relay. Features. Introduction. ARC Fault Protection

1S20. Arc Fault Monitor Relay. Features. Introduction. ARC Fault Protection Technical Bulletin Arc Fault Monitor Relay Features Compact, economic design Simple panel mounting for retrofit applications Two or three arc sensor inputs Two high speed tripping duty arc sense output

More information

REDUNDANCY MODULE TSP-REM360 AND TSP-REM600

REDUNDANCY MODULE TSP-REM360 AND TSP-REM600 REDUNDANCY MODULE TSP-REM360 AND TSP-REM600 Operating Instructions Seite 1 Dimensions drawings: TSP-REM360 Weight: 0.882lb Gewicht: 0.40kg Seite 2 Dimensions drawings: TSP-REM600 Bottom view Top view Side

More information

Sensitive definite time or inverse time earth-fault stage for back-up residual earthfault

Sensitive definite time or inverse time earth-fault stage for back-up residual earthfault Issued: April 1999 Status: Updated Version: B/09.11.2001 Data subject to change without notice Features Sensitive restricted earth-fault protection stage for fast, selective earth-fault protection Sensitive

More information

ekorrps MULTIFUNCTIONAL PROTECTION UNIT CONFIGURATION AND GENERAL CHARACTERISTICS LIB

ekorrps MULTIFUNCTIONAL PROTECTION UNIT CONFIGURATION AND GENERAL CHARACTERISTICS LIB MO-067-EN Operation Manual MULTIFUNCTIONAL PROTECTION UNIT CONFIGURATION AND GENERAL CHARACTERISTICS LIB Transformer Substations Secondary Distribution Switchgear Primary Distribution Switchgear Protection

More information

HITACHI. EH-150 series PLC EH-RTD8 Resistance Temperature Detective input module Instruction manual. Safety precautions

HITACHI. EH-150 series PLC EH-RTD8 Resistance Temperature Detective input module Instruction manual. Safety precautions HITACHI EH-150 series PLC Resistance Temperature Detective input module Instruction manual Thank you for purchasing a Hitachi Programmable Logic Controller. To operate it safely, please read this instruction

More information

Operating instructions. Switching amplifier DN0210 DN / / 2015

Operating instructions. Switching amplifier DN0210 DN / / 2015 Operating instructions Switching amplifier DN0210 DN0220 UK 80011079 / 00 01 / 2015 Contents 1 Preliminary note...4 1.1 Symbols used...4 1.2 Warning signs used...4 2 Safety instructions...5 2.1 General...5

More information

MultiTech Router Commissioning for Com X 200/210/510

MultiTech Router Commissioning for Com X 200/210/510 Knowledge Base 7EN42-0166 05/2017 MultiTech Router Commissioning for Com X 200/210/510 This document describes installation recommendations and how to commission a MultiTech rcell Series router for use

More information

PGR-4700 MANUAL SENSITIVE GROUND-FAULT RELAY

PGR-4700 MANUAL SENSITIVE GROUND-FAULT RELAY Tel: +1-800-832-3873 E-mail: techline@littelfuse.com www.littelfuse.com/pgr-4700 PGR-4700 MANUAL SENSITIVE GROUND-FAULT RELAY REVISION 2-B-032218 Copyright 2018 by Littelfuse, Inc. All rights reserved.

More information

Universal Power Supplies

Universal Power Supplies , Features Universal input: 90 264 VAC or 120 30 VDC Active power factor correction (>0.95) High efficiency up to 93% Load share function for up to 3 units in parallel Adjustable output voltage EMI/EMC

More information

SIMOCODE 3UF Motor Management and Control Devices

SIMOCODE 3UF Motor Management and Control Devices Technical specifications General data applicable to the basic units, current measuring modules, current/voltage measuring modules, expansion modules, decoupling module and operator panel Permissible ambient

More information

SINAMICS G130. Terminal Module 150 (TM150) Operating Instructions 03/2013 SINAMICS

SINAMICS G130. Terminal Module 150 (TM150) Operating Instructions 03/2013 SINAMICS SINAMICS G130 Operating Instructions 03/2013 SINAMICS s Safety information 1 General information 2 SINAMICS SINAMICS G130 Mechanical installation 3 Electrical installation 4 Technical specifications 5

More information

Feeder protection relay

Feeder protection relay Page 1 Issued: April 1999 Status: New Data subject to change without notice Features Comprehensive numerical feeder protection relay consisting of two multi-function protection relay modules and a flexible

More information

VAMP 57. Protection IED. Quick Start. Publication version: V57/en QS/A008

VAMP 57. Protection IED. Quick Start. Publication version: V57/en QS/A008 VAMP 57 Protection IED Publication version: Quick Start Trace back information: Workspace VAMP Range version a4 Checked in 2018-02-13 Skribenta version 5.2.027 Table of Contents Table of Contents 1 Legal

More information

RE17LAMW on-delay timing relay - 1 s..100 h V AC/ DC - solid state output

RE17LAMW on-delay timing relay - 1 s..100 h V AC/ DC - solid state output Characteristics on-delay timing relay - 1 s..100 h - 24..240 V AC/ DC - solid state output Main Range of product Product or component type Discrete output type Width Component name Time delay type Time

More information

Arc protection relay. Features Three-phase overcurrent function. Application

Arc protection relay. Features Three-phase overcurrent function. Application Arc protection relay REA 10_ Issued: May 1999 Status: Updated Version: B/12.11.2001 Data subject to change without notice Features Three-phase overcurrent function Loop-type or radial sensor fibre for

More information

MINI MCR-SL-PT100-UI(-SP)(-NC)

MINI MCR-SL-PT100-UI(-SP)(-NC) Configurable Temperature Transducer for PT100 Data Sheet 04/2005 Functions MINI MCR-SL-PT100-UI(-SP)(-NC) is a configurable 3-way isolated temperature measuring transducer. It is suitable for the connection

More information

Electrical network protection Sepam series 20 Sepam series 40 Quick start

Electrical network protection Sepam series 20 Sepam series 40 Quick start 03146790FE+01+NP00000000 Electrical network protection Sepam series 20 Sepam series 40 Quick start PE50465 Storage Sepam may be stored in its original packaging in a closed sheltered location: b ambient

More information

Digital ac/dc (24V) Input Module

Digital ac/dc (24V) Input Module Installation Instructions Digital ac/dc (24V) Input Module Catalog Number 1771-IND, Series C Topic Page Important User Information 2 Before You Begin 3 Power Requirements 3 Prevent Electrostatic Discharge

More information

Clipsal Bus Couplers. Two Channel (SLC5102BCLEDL) and Four Channel (SLC5104BCL) for Use with C-Bus Wired Systems

Clipsal Bus Couplers. Two Channel (SLC5102BCLEDL) and Four Channel (SLC5104BCL) for Use with C-Bus Wired Systems Clipsal Bus Couplers Two Channel (SLC5102BCLEDL) and Four Channel (SLC5104BCL) for Use with C-Bus Wired Systems Instruction Bulletin Retain for future use. Clipsal Bus Couplers 63249-420-236A2 Instruction

More information

RE22R2QGMR Star-Delta Timing Relay s 300h V AC/DC - 2C/O

RE22R2QGMR Star-Delta Timing Relay s 300h V AC/DC - 2C/O Characteristics Star-Delta Timing Relay - 0.05s 300h - 24 240V AC/DC - 2C/O Main Range of product Product or component type Discrete output type Device short name Nominal output current Complementary Contacts

More information

INSTALLATION DKM-409 NETWORK ANALYSER WITH HARMONIC MEASUREMENT AND SCOPEMETER. Before installation:

INSTALLATION DKM-409 NETWORK ANALYSER WITH HARMONIC MEASUREMENT AND SCOPEMETER. Before installation: DKM-409 NETWORK ANALYSER WITH HARMONIC MEASUREMENT AND SCOPEMETER The DKM-409 is a precision instrument designed for displaying various AC parameters in 3-phase distribution panels. Thanks to its isolated

More information

RE22R1QMQ star-delta timing relay - 230VAC/440VAC - 1 C/O

RE22R1QMQ star-delta timing relay - 230VAC/440VAC - 1 C/O Characteristics star-delta timing relay - 230VAC/440VAC - 1 C/O Main Range of product Product or component type Discrete output type Device short name Nominal output current Complementary Contacts type

More information

VAMP 57. Protection IED. Quick Start. Publication version: V57/en QS/A007

VAMP 57. Protection IED. Quick Start. Publication version: V57/en QS/A007 VAMP 57 Protection IED Publication version: Quick Start Trace back information: Workspace Main version a123 Checked in 2016-10-05 Skribenta version 4.6.006 Table of Contents Table of Contents 1 Legal notice...

More information

Operating instructions. Standstill monitor A / / 2011

Operating instructions. Standstill monitor A / / 2011 Operating instructions Standstill monitor A300 UK 1 2 3 4 5 6 7 8 7390337 / 01 02 / 2011 1 2 3 4 5 6 7 8 switchpoint min max pulse/min power Made in Germany ifm electronic gmbh D 45127 Essen func. I II

More information

Monitoring technique. VARIMETER Voltage relay MK 9064N, MH 9064

Monitoring technique. VARIMETER Voltage relay MK 9064N, MH 9064 Monitoring technique VARIMETER Voltage relay MK 9064N, MH 9064 0269462 Your Advantages Preventive maintenance For better productivity Quicker fault locating Precise and reliable Min-, Max. value or window

More information

High impedance protection relay

High impedance protection relay High impedance protection relay Page 1 Issued: April 1999 Status: New Data subject to change without notice Features High impedance type differential current earth-fault protection, so called restricted

More information

Feeder protection relay SPAA 341 C. Product Guide

Feeder protection relay SPAA 341 C. Product Guide Issued: April 1999 Status: Updated Version: D/07.03.2006 Data subject to change without notice Features Comprehensive numerical feeder protection relay consisting of two multi-function protection relay

More information

MINI-PS AC/10-15DC/8

MINI-PS AC/10-15DC/8 Primary-Switched Power Supply, Narrow Design Data Sheet 08/2004 MINI POWER provides: An extra narrow design, with widths of 22.5 mm, 45 mm, and 67.5 mm (0.886, 1.772, and 2.657 in.) Global use due to a

More information

RE17LCBM off-delay timing relay - control - 1 s..100 h V - solid state output

RE17LCBM off-delay timing relay - control - 1 s..100 h V - solid state output Characteristics off-delay timing relay - control - 1 s..100 h - 24..240 V - solid state output Main Range of product Product or component type Discrete output type Width Component name Time delay type

More information

Protection Relays PHASE & RESIDUAL OVERCURRENT

Protection Relays PHASE & RESIDUAL OVERCURRENT Protection Relays PHASE & RESIDUAL OVERCURRENT Application The relay type NA016 can be used in radial networks as feeder or power transformer protection. In solidly grounded systems the residual overcurrent

More information

Electronic timer CT-AHD.22

Electronic timer CT-AHD.22 2CDC 251 093 F0t06 a Rotary switch for the preselection of the time range b Potentiometer with direct reading scale for the fine adjustment of the time delay c U: green LED V control supply voltage applied

More information

Altivar 61/71 Adjustable Speed Drives Heatsink Fan Kits VZ3V1212 and VZ3V1216

Altivar 61/71 Adjustable Speed Drives Heatsink Fan Kits VZ3V1212 and VZ3V1216 Altivar 61/71 Adjustable Speed Drives Heatsink Fan Kits VZ3V1212 and VZ3V1216 Instruction Bulletin 30072-452-48 Retain for future use. 30072-452-48 Altivar 61/71 Heatsink Fan Kits VZ3V1212 and VZ3V1216

More information

Symmetra PX 160. Maintenance Bypass Enclosure. Installation 05/

Symmetra PX 160. Maintenance Bypass Enclosure. Installation 05/ Symmetra PX 160 Maintenance Bypass Enclosure Installation 05/2014 www.schneider-electric.com Legal Information The Schneider Electric brand and any registered trademarks of Schneider Electric Industries

More information

Rhino Redundancy Module PSM24-REM360S. Operating Instructions

Rhino Redundancy Module PSM24-REM360S. Operating Instructions Rhino Redundancy Module PSM4-REM360S Operating Instructions RHINO REDUNDANCY MODULE PSM4-REM360S Description With this module and two power supplies of the PSM series (78, 90, 56, 80 and 360 watt models),

More information

RE22R2AMR On-delay Timing Relay s 300h V AC/DC - 2C/O

RE22R2AMR On-delay Timing Relay s 300h V AC/DC - 2C/O Characteristics On-delay Timing Relay - 0.05s 300h - 24 240V AC/DC - 2C/O Main Range of product Product or component type Discrete output type Device short name Nominal output current Complementary Contacts

More information

RE22R2CMR Off-delay Timing Relay s 300h V AC/DC - 2C/O

RE22R2CMR Off-delay Timing Relay s 300h V AC/DC - 2C/O Characteristics Off-delay Timing Relay - 0.05s 300h - 24 240V AC/DC - 2C/O Main Range of product Product or component type Discrete output type Device short name Nominal output current Complementary Contacts

More information

RE17LAMW on-delay timing relay - 1 s..100 h V AC/DC - solid state output

RE17LAMW on-delay timing relay - 1 s..100 h V AC/DC - solid state output Characteristics on-delay timing relay - 1 s..100 h - 24..240 V AC/DC - solid state output Complementary Control type Voltage range Main Range of product Product or component type Discrete output type Width

More information

Electronic timer CT-SDD.22 Star-delta change-over with 2 n/o contacts

Electronic timer CT-SDD.22 Star-delta change-over with 2 n/o contacts Data sheet Electronic timer CT-SDD. Star-delta change-over with n/o contacts The CT-SDD. is an electronic time relay with star-delta change-over. It is from the CT-D range. With their MDRC profile and

More information

RAD-DOR4-IFS. I/O extension module, 4 digital relay outputs. INTERFACE Data sheet. 1 Description

RAD-DOR4-IFS. I/O extension module, 4 digital relay outputs. INTERFACE Data sheet. 1 Description I/O extension module, 4 digital relay outputs INTERFACE Data sheet 104834_en_01 PHOENIX CONTACT 2013-01-21 1 Description The RAD-DOR4-IFS I/O extension module can be used in conjunction with Radioline

More information

RE22R2QTMR Star-Delta Timing Relay s 300h V AC/DC - 2C/O

RE22R2QTMR Star-Delta Timing Relay s 300h V AC/DC - 2C/O Characteristics StarDelta Timing Relay 0.05s 300h 24 240V AC/DC 2C/O Main Range of product Product or component type Discrete output type Device short name Nominal output current Zelio Time Modular timing

More information

RE7RB13MW adjustable off-delay timing relay s V AC DC - 2OC

RE7RB13MW adjustable off-delay timing relay s V AC DC - 2OC Characteristics adjustable off-delay timing relay - 0.05..1 s - 240 V AC DC - 2OC Main Range of product Product or component type Contacts type and composition Component name Time delay type Time delay

More information

Output Voltage* (nom.)(adjustable)

Output Voltage* (nom.)(adjustable) Industrial Power Supplies TBLC Series, 6 90 W Low profile case, module depth only 59,5mm Suitable for mounting in domestic installation panels Low output ripples and spikes Fully compliance to ECO-Standard

More information

Allen-Bradley 1786-RPFRXL

Allen-Bradley 1786-RPFRXL Installation Instructions ControlNet Fiber-optic Ring Repeater Modules Catalog Numbers 1786-RPFRL/B, 1786-RPFRXL/B Topic Page Important User Information 2 Environment and Enclosure 3 North American Hazardous

More information

ArmorPoint I/O Field Potential Distributor, Series A

ArmorPoint I/O Field Potential Distributor, Series A Installation Instructions ArmorPoint I/O Field Potential Distributor, Series A (Cat. No. 1738-FPD) The field potential distributor (Cat. no. 1738-FPD) lets you change the field power distribution source

More information

Operating instructions. Speed monitor D / / 2014

Operating instructions. Speed monitor D / / 2014 Operating instructions Speed monitor D200 80005257 / 00 05 / 2014 Contents 1 Preliminary note...4 1.1 Symbols used...4 1.2 Warning signs used...4 2 Safety instructions...5 2.1 General...5 2.2 Target group...5

More information

INSTRUCTION SHEET. Eaton Logic Controller ELCB Controllers

INSTRUCTION SHEET. Eaton Logic Controller ELCB Controllers 2010-12-10 5011699201-PBB1 Eaton Logic Controller ELCB Controllers INSTRUCTION SHEET [Applicable Controllers] ELCB-PB10 ELCB-PB14 ELCB-PB20 ELCB-PB30 ELCB-PB40 IL05001005E 002-1310020-02 Thank you for

More information

RE22R2KMR Off-delay Timing Relay s 10min V AC/DC - 2C/O

RE22R2KMR Off-delay Timing Relay s 10min V AC/DC - 2C/O Characteristics Off-delay Timing Relay - 0.05s 10min - 24 240V AC/DC - 2C/O Main Range of product Product or component type Discrete output type Device short name Nominal output current Complementary Contacts

More information

RE48ATM12MW on-delay timing relay s..300 h V AC - 2 OC

RE48ATM12MW on-delay timing relay s..300 h V AC - 2 OC Characteristics on-delay timing relay - 0.02 s..300 h - 24..240 V AC - 2 OC Complementary Product front plate size Control type Housing material Main Range of product Product or component type Electrical

More information

RE22R1QMQ star-delta timing relay - 230VAC/440VAC - 1 C/ O

RE22R1QMQ star-delta timing relay - 230VAC/440VAC - 1 C/ O Characteristics star-delta timing relay - 230VAC/440VAC - 1 C/ O Main Range of product Product or component type Discrete output type Device short name Nominal output current Zelio Time Modular timing

More information

SoundwebTM. Installation Guide

SoundwebTM. Installation Guide 105 SoundwebTM Soundweb TM 9000 Installation Guide Soundweb TM Regulatory Information An example of this equipment has been tested and found to comply with the following European and international Standards

More information

PowerLogic ION7550 RTU option

PowerLogic ION7550 RTU option 70052-0213-02 PRODUCT OPTION 01/2011 PowerLogic ION7550 RTU option The PowerLogic ION7550 Remote Terminal Unit (RTU) option is designed for data acquisition from WAGES (water, air, gas, electricity, steam)

More information

Electronic timer CT-ERD.12

Electronic timer CT-ERD.12 2CDC 251 092 F0t06 a Rotary switch for the preselection of the time range b Potentiometer with direct reading scale for the fine adjustment of the time delay c U: green LED V control supply voltage applied

More information

Communication Gateway COM 610. Product Guide

Communication Gateway COM 610. Product Guide Communication Gateway COM 610 Product Guide Issued: September 2004 Status: Updated Version: D/17.10.2006 Data subject to change without notice Features Protocol conversion gateway for substation automation:

More information

Electronic timer CT-EBD.12 Flasher starting with ON with 1 c/o (SPDT) contact

Electronic timer CT-EBD.12 Flasher starting with ON with 1 c/o (SPDT) contact Data sheet Electronic timer CT-EBD.12 Flasher starting with ON with 1 c/o (SPDT) contact The CT-EBD.12 is an electronic time relay with the function flasher starting with ON. It is from the CT-D range.

More information

Bulletin 290/291 ArmorStart LT Distributed Motor Controllers Specifications

Bulletin 290/291 ArmorStart LT Distributed Motor Controllers Specifications Power Circuit Control Circuit (External Source) Control Circuit (Internal Source) Short Circuit Current Rating (SCCR) Application Electrical Ratings Three-phase Number of Poles 3 Input Power Terminals

More information

Output Voltage* (nom.)(adjustable)

Output Voltage* (nom.)(adjustable) Industrial Power Supplies TBLC Series, 6 90 W Low profile case, module depth only 55 mm Suitable for mounting in domestic installation panels Very high efficiency and low standby power -> compliance to

More information

EX-RC1 Remote I/O Adapter

EX-RC1 Remote I/O Adapter EX-RC1 Remote I/O Adapter The EX-RC1 interfaces between Unitronics Vision OPLCs and remote I/O Expansion Modules distributed throughout your system. The adapter is connected to a PLC via CANbus. Each adapter

More information

Acti 9 Communication System

Acti 9 Communication System Acti 9 Communication System Diagnostics User Manual 05/2012 DOCA0042EN-00 www.schneider-electric.com This document contains general descriptions and/or general technical specifications of the products

More information

Redundancy unit CP-A RU

Redundancy unit CP-A RU 2CDC 271 010 F0t06 Features Decoupling of CP power supply units with 2 inputs, each up to 20 A per input / channel Output up to 40 A True redundancy by 100 % decoupling of two parallel connected power

More information

RE22R2AMR On-delay Timing Relay s 300h V AC/DC - 2C/O

RE22R2AMR On-delay Timing Relay s 300h V AC/DC - 2C/O Characteristics Ondelay Timing Relay 0.05s 300h 24 240V AC/DC 2C/O Main Range of product Product or component type Discrete output type Device short name Nominal output current Zelio Time Modular timing

More information

Type MVTT 14 and MVTT 15: Static Digital Time delay relays

Type MVTT 14 and MVTT 15: Static Digital Time delay relays Type MVTT 4 and MVTT 5: Static Digital Time delay relays Features 000/ setting range Time settings easily selected by means of thumbwheel switches Provide time delayed pick-up, or drop-off Compact construction

More information

170 ADM to 60 VDC Module Base / 170 ADO Pt. Relay Out Module Base. Version 1.0

170 ADM to 60 VDC Module Base / 170 ADO Pt. Relay Out Module Base. Version 1.0 170 ADM 850 10 10 to 60 VDC Module Base / 170 ADO 830 30 6 Pt. Relay Out Module Base Version 1.0 31005197 00 Safety Information NOTICE Read these instructions carefully, and look at the equipment to become

More information

SINAMICS G130. Voltage Sensing Module 10 (VSM10) Operating instructions 03/2011 SINAMICS

SINAMICS G130. Voltage Sensing Module 10 (VSM10) Operating instructions 03/2011 SINAMICS SINAMICS G130 Operating instructions 03/2011 SINAMICS s Safety information 1 General 2 SINAMICS SINAMICS G130 Voltage Sensing Module 10 (VSM10) Mechanical installation 3 Electrical installation 4 Technical

More information

5401 and 5402 Digital I/O Modules

5401 and 5402 Digital I/O Modules 50 and 50 Digital I/O Modules Installation, Operation and Maintenance Setup Manual 5/9/0 Safety Information The information provided in this documentation contains general descriptions and/or technical

More information

Contact protection relay

Contact protection relay Contact protection relay Ordering details SVR 450 08 F0000 The protects sensitive control contacts from excessive load. It can be used with latching function or without. Bounce time of control contacts

More information

Operating instructions AS-i SmartLine module AC3200 AC /00 06/2016

Operating instructions AS-i SmartLine module AC3200 AC /00 06/2016 Operating instructions AS-i SmartLine module AC3200 AC3201 80237876/00 06/2016 Contents 1 Preliminary note...3 1.1 Symbols used...3 1.2 Warnings used...3 2 Safety instructions...3 2.1 General...3 2.2 Target

More information

Safety Standards. Model Number: Unit Weight:

Safety Standards. Model Number: Unit Weight: MEA-250A24C Highlights & Features Meet Efficiency Level VI Safety Approvals to IEC 60601-1 3.1 Ed. & IEC 60950-1 Compliant with IEC 60601-1-2 3 th and 4 th Ed. Requirements IP22 ingress protection rating

More information

Rhino Buffer Module PSM24-BFM600S. Operating Instructions

Rhino Buffer Module PSM24-BFM600S. Operating Instructions Rhino Buffer Module PSM24-BFM600S Operating Instructions RHINO BUFFER MODULE PSM24-BFM600S Description The PSM24-BFM600S Buffer Module will hold the output voltage of a 24 VDC power supply after brownouts

More information

High Impedance Protection Relay SPAE010, SPAE011. Product Guide

High Impedance Protection Relay SPAE010, SPAE011. Product Guide SPAE010, SPAE011 SPAE010, SPAE011 1MRS750383-MBG Issued: April 1999 Status: Updated Version: D/21.03.2006 Data subject to change without notice Features High impedance type differential current earth-fault

More information

NI REM Remote I/O Overview DATASHEET. Digital Input Module for Remote I/O

NI REM Remote I/O Overview DATASHEET. Digital Input Module for Remote I/O DATASHEET NI REM-11154 Digital Input Module for Remote I/O Read digital input frequencies up to 5 khz Adjustable filter time to improve measurement quality Spring-terminal connectors allow fast wiring

More information

Operating Manual UMB ISO Converter ISOCON Order Number: 8160.UISO

Operating Manual UMB ISO Converter ISOCON Order Number: 8160.UISO Order Number: 8160.UISO Status: V3; 17.09.2010c G. Lufft Mess- und Regeltechnik GmbH, Fellbach, Germany 1 TABLE OF CONTENTS PLEASE READ BEFORE USE... 3 DESCRIPTION... 5 UMB ISO CONVERTER ISOCON... 6 CONFIGURATION...

More information

RAD-DO8-IFS. I/O extension module, eight digital transistor outputs. Data sheet. 1 Description

RAD-DO8-IFS. I/O extension module, eight digital transistor outputs. Data sheet. 1 Description I/O extension module, eight digital transistor outputs Data sheet 105364_en_00 PHOENIX CONTACT 2013-03-26 1 Description The I/O extension module can be used in conjunction with Radioline wireless modules

More information

Safety Standards. Model Number:

Safety Standards. Model Number: PMC Highlights & Features Universal AC input range from 85Vac to 264Vac without power de-rating High operating ambient temperature, > 60 o C de-rating power High MTBF > 700,000 hrs. as per Telcordia SR-332

More information

MC 11 EB-2 Power supply cabinet with external bus, AC version

MC 11 EB-2 Power supply cabinet with external bus, AC version MC 11 EB-2 Power supply cabinet with external bus, AC version USER/MAINTENANCE MANUAL 1 SLOT 0 SLOT 1 SLOT 2 SLOT 3 SLOT 4 SLOT 5 SLOT 6 SLOT 7 SLOT 8 SLOT 9 SLOT 10 SLOT 11 EB-2 (a) MC11 (b) (c) Figures

More information

CliQ II DC-UPS Module 24V 40A / DRU-24V40ABN

CliQ II DC-UPS Module 24V 40A / DRU-24V40ABN Highlights & Features Full corrosion resistant Aluminium chassis Suitable for 24V system up to 40A Built-in diagnostic monitoring for DC OK, Discharge and Battery Fail by relay contacts LED indicator for

More information

RM22TG. Product data sheet Characteristics. three-phase control relay Vac, 2 C/O. Main. Complementary. Network number of phases

RM22TG. Product data sheet Characteristics. three-phase control relay Vac, 2 C/O. Main. Complementary. Network number of phases Characteristics three-phase control relay 183 528Vac, 2 C/O Main Range of product Product or component type Relay type Network number of phases Relay name Relay monitored parameters Time delay type Switching

More information

TRIO-DIODE/12-24DC/2X10/1X20

TRIO-DIODE/12-24DC/2X10/1X20 Redundancy module INTERFACE Data sheet 104278_en_00 1 Description PHOENIX CONTACT 20100423 Features TRIO DIODE is the DINrail mountable redundancy module from the TRIO POWER product range. Using the redundancy

More information

IRI1-ES Sensitive Earth Fault Current Relay. Manual IRI1-ES (Revision A)

IRI1-ES Sensitive Earth Fault Current Relay. Manual IRI1-ES (Revision A) IRI1-ES Sensitive Earth Fault Current Relay Manual IRI1-ES (Revision A) Woodward Manual IRI1-ES GB Woodward Governor Company reserves the right to update any portion of this publication at any time. Information

More information