SLX Series. Application Specific Controllers (SLX-ASC-FCU-L, SLX-ASC-HPU-L, SLX-ASC-RTU-L, SLX-ASC-UV-L)

Size: px
Start display at page:

Download "SLX Series. Application Specific Controllers (SLX-ASC-FCU-L, SLX-ASC-HPU-L, SLX-ASC-RTU-L, SLX-ASC-UV-L)"

Transcription

1 SLX Series Document No Application Specific Controllers (SLX-ASC-FCU-L, SLX-ASC-HPU-L, SLX-ASC-RTU-L, SLX-ASC-UV-L) Free Programmable Controllers (SLX-PC-203, SLX-PC-300, SLX-PC-400, SLX-PC-500 ) 1. Product Description This document describes the hardware installation procedures for the SLX Series Application Specific Controller (ASC) and free Programmable Controller (PC). The ASC product line is designed to control and monitor HVAC equipment such as fan coil units, rooftop units, heat pump units and unit ventilators. This product line includes the following controllers: SLX-ASC-FCU-L, SLX-ASC-HPU-L, SLX-ASC- RTU-L and SLX-ASC-UV-L. The PC product line is designed to control and monitor various HVAC equipment such as rooftop units and air handling units, as well as chillers and boilers. Moreover, it is suitable for any lighting control and power measurement application. This product line includes the following controllers: SLX-PC- 203,SLX-PC-300, SLX-PC-400, SLX-PC-403 SLX-PC-410, SLX-PC-413, SLX-PC-500 and SLX-PC-510. These product lines are based on the LONWORKS technology for peer-to-peer communication between controllers and are LONMARK certified. All of these controllers are built on a similar platform, but have different numbers of inputs and outputs. Moreover, each individual model has different amounts of digital and/or universal outputs. For more information on the specific layout and functionality of each controller, please refer to their individual technical specification sheets. The following controllers are housed in small enclosures: SLX-ASC-FCU-L, SLX-ASC-HPU-L, SLX-ASC-RTU-L, SLX-ASC-UV-L, SLX-PC-203, and SLX-PC-300. The following controllers are housed in large enclosures: SLX-PC-400 models and SLX-PC- 500 models. Figure 1: (Top to Bottom) Large Enclosure with HOA Switches, Large Enclosure, and Small Enclosure. SLX Series Page 1 of 9

2 2. General Installation Requirements For proper installation and subsequent operation of each controller, pay special attention to the following recommendations: - It is recommended that the controller(s) be kept at room temperature for at least 24 hours before installation to allow any condensation that may have accumulated, due to low temperature during shipping/storage, to evaporate. - Upon unpacking the product, inspect the contents of the carton for shipping damages. Do not install damaged controllers. - Allow for proper clearance of controller enclosure, wiring terminals and service pin for easy access, hardware configuration and maintenance. Remember to record the Neuron ID located on both sides of the device (in text and barcode format) for later commissioning. - Each controller is designed to operate under the following environmental conditions: Ambient temperature from 32 F to 158 F (0 C to 70 C) Relative humidity from 0% to 90%, non-condensing - Ensure proper ventilation of each controller and avoid areas where corroding, deteriorating or explosive vapors, fumes or gases may be present. Each controller must be oriented with the ventilation slots and power supply/output terminal block connector towards the top to permit proper heat dissipation. - The plastic enclosure has a back plate that is separable from the front plate allowing the back plates (with the connectors) to be shipped directly to the installation site while all the engineering is done in the office. - If the controller is used and/or installed in a manner not specified, the functionality and the protection provided by the controller may be impaired. Any type of modification to any SLX Series product will void the product s warranty. Take special care to keep the front and back plate aligned when separating and joining them. Take reasonable precautions to prevent electrostatic discharges to each controller when installing, servicing or operating the controller. Discharge accumulated static electricity by touching your hand to a securely grounded object before working with each controller. 3. General Wiring Recommendations Turn off power before any kind of servicing. - All wiring must comply with electrical wiring diagrams as well as national and local electrical codes. - To connect the wiring to each controller, use the terminal connectors. It is recommended to remove the front plate from the back plate to facilitate the wiring process; however, it is possible to do all wiring with the front and back plates together. Use a small flat screwdriver to tighten the terminal connector screws once the wires have been inserted. - Power type cables (i.e. for power, 2- and 3-wire voltage and current inputs and outputs, as well as triac outputs) should be kept apart from other types of wiring to avoid any ambient noise transmission to other wires. - The board connectors accept wires or flat cables ranging from 22 to 14AWG (0.644 to 1.630mm diameter) per pole. However, power cables must remain between 18 and 14AWG (1.024 to 1.630mm diameter). - Do not connect the universal inputs, analog/digital outputs or common terminals to earth or chassis ground (unless stated otherwise). - The transformer powering each controller must be configured as a floating transformer (i.e. it should not be grounded). - Keep all wires away from high speed data transmission cables (ie. Ethernet, etc.). - Keep input and output wiring in conduits or trays, or close to the building frame if possible. 4. Mounting Instructions Each controller can be mounted on a DIN rail to speed up the installation procedure. The controllers are also equipped with two mounting holes of 0.25 (6.35mm) by (4.191mm). They can be mounted in a panel or on a wall by using appropriate screw types (use sheet metal, thread forming or self-tapping screws accordingly). DIN Rail-Mounted Installation 1. Make sure that the DIN rail is properly mounted on the wall. 2. Simply clip controller onto the DIN rail. Wall-Mounted Installation 1. Open the controller by separating the front and back plate using the side clips. 2. From within the back plate use the mounting holes to mark the location of any holes that need to be drilled. 3. Remove the back plate and drill holes. 4. Finally, clean the perforated surface and fasten the device using the appropriate screw types. Page 2 of 9 SLX Series

3 5. Controller Dimensions 6. Power Wiring Voltage: 24VAC/DC; ± 15%, Class 2 To conform to Class 2 requirements in the United States, use transformers of 100VA or less to power the controller. When powering one or multiple devices, use the following method to calculate the power requirements of the required transformer: - Add up the maximum power consumption of all controllers and multiply this sum by If the resulting number is higher than 100VA, consider using multiple transformers. Use an external fuse on the 24VAC/DC side (secondary side) of the transformer, as shown in Figure 3, to protect all controllers against power line spikes. Maintain consistent polarity when connecting controllers and devices to the transformer. That is, the COM terminal of each controller and each peripheral should be connected to the same terminal on the secondary side of the transformer. The controllers are half-wave rectified. Connecting two half-wave power supplies to the same transformer without maintaining polarity will cause a short circuit. Controller 1 24VAC/DC 24V COM Fuse 24VAC AC Controller 2 24VAC/DC 24V COM Transformer Figure 3: Power Wiring AC. Figure 4: Power Wiring DC. The COM terminals of the controller are internally wired to the 24V COM terminal of the power supply. Therefore, if powering peripherals and controllers with the same transformer, it is essential to maintain polarity. Failure to do so will result in a short circuit and/or a damaged controller. Figure 2: (Top to Bottom) Rear View of the Large Enclosure, Rear View of the Small Enclosure, and Side View of the Large and Small Enclosure. SLX Series Page 3 of 9

4 7. Input Wiring Each controller has physical connections for inputs that are software configurable from within the controller s LNS plug-in. Each input can be configured for digital, resistive, current or voltage signals. Input types must be configured properly with the LMT to ensure proper input readings. Before connecting any input equipment to the controller, refer to the installation guide of the equipment manufacturer. For a wire length less than 75 (23m), either a shielded or unshielded 18AWG wire may be used. For a wire length between 75 and 200 (23m to 61m), a shielded 18AWG wire is recommended. The wire should be shielded on the controller side and the shield length should be kept as short as possible. Wiring Digital Inputs This input configuration is used to monitor digital dry contacts, as well as pulsed contacts (PC models only). Figure 5: Digital Input Digital Dry Contact (NO and NC). Wiring Resistive Inputs This input configuration is used to monitor 100Ω and 1000Ω RTDs, 10kΩ type II and III thermistors, as well as 10kΩ and 100kΩ (PC models only) potentiometers. On the SLX-PC-400 models and SLX-PC-500 models, the onboard 15 VDC output can be used to supply the current loop shown in Figure 8. Refer to the transducer installation guide for further details. Connect the current input according to the following figure if a 3-wire, 4-20mA transducer is being used. Figure 9: Current Input 3-Wire Transducer. Connect the current input according to the following figure if the transducer is powered by its own power source. Figure 10: Current Input Transducer with its Own Power Source. Wiring Voltage Inputs Voltage inputs have a range of 0 to 10VDC. Connect the voltage input according to the following figure if a 3-wire 0-10V transducer is being used. Transducer + Common 24VAC 0-10V 24VAC UIx COM Figure 11: Voltage Input 3-Wire Transducer. Connect the voltage input according to the following figure if the transducer is powered by its own power source. Figure 6: Resistive Input RTD /Thermistor Input. Figure 12: Voltage input Transducer with its Own Power Source. 8. SLX-RTS/SLX-STAT Wiring Figure 7: Resistive Input 10kΩ Potentiometer Input. Page 4 of 9 The ASCs do not support 100Ω or 1000Ω inputs. When using a 100Ω input, the wire length should be kept short so as to avoid a possible temperature offset. For example, an 18AWG wire, 25 (7.6m) in length can create an offset of 2 F (1.1 C). Wiring Current Inputs Current inputs have a range of 4 to 20mA. Connect the current input according to the following figure if a 2-wire, 4-20mA transducer is being used. Figure 8: Current Input 2-Wire Transducer. Each controller is compatible with the SLX-RTS line of standard room sensors. Refer to the SLX-RTS and SLX-STAT installation instructions for wiring details. 9. Output Wiring Each controller has physical connections for triac outputs and/or universal outputs, depending on the type and model. These outputs are all software configurable. Controller Triac Outputs Universal Outputs SLX-ASC-FCU-L 5 2 SLX-ASC-HPU-L 5 2 SLX-ASC-RTU-L 5 2 SLX-ASC-UV-L 5 2 SLX-PC SLX-PC Jumper 0-10VDC/0-20mA SLX Series

5 Controller SLX-PC-4x0 SLX-PC-4x3 SLX-PC-500 Triac Universal Jumper Outputs Outputs 0-10VDC/0-20mA Before connecting any output equipment to the controller, refer to the installation guide of the equipment manufacturer. For a wire length less than 75 (23m), either a shielded or unshielded 18AWG wire may be used. For a wire length between 75 and 200 (23m to 61m), a shielded 18AWG wire is recommended. The wire should be shielded on the controller side, and the shield length should be kept as short as possible. Figure 15: Discrete 0 or 12VDC Universal Output Relay. Wiring Current Outputs The 0 to 20mA signal is configurable by jumper (available for SLX-PC-400 models and SLX-PC-500 models only). Figure 16: Current 0-20mA Universal Output and Jumper Configuration. Wiring Voltage Outputs Connect the 0 to 10VDC output according to the following figure. Wiring Triac Outputs Digital outputs are all made of triacs and there is no voltage present on the output terminals. Therefore, an external power source has to be added if necessary. To measure the state of a triac output, an external load must be connected. Connect the digital output according to the following figure if a relay is being controlled. Figure 17: Voltage 0-10VDC Universal Output. Connect the 0 to 10VDC output according to the following figure if an analog actuator is being controlled. Figure 18: Voltage 0-10VDC Universal Output Analog Actuator. Figure 13: Digital Triac Output Relay. Connect the digital output according to the following figure if a floating actuator is being controlled. Figure 14: Digital Triac Output Floating Actuator. Wiring Universal Outputs Universal outputs can be configured to provide either a discrete signal of 0 or 12VDC, a linear signal ranging from 0 to 10VDC or a 0 to 20mA signal (SLX-PC-400 models and SLX-PC-500 models). The discrete signal can be used to generate a pulse wave modulation (PWM) signal or a simple two-state signal. These outputs are protected by an autoreset fuse. Wiring Discrete Outputs When controlling a relay with a universal output, a diode must be connected in parallel to protect the controller from back-emf current, which occurs when the relay is turned off. It is recommended to use diodes that are part of the 1N400x family and they should be placed closer to the relay. 10. Communications Wiring The recommended cable type for LON communications is 22AWG (0.65 mm), twisted pair, unshielded. The LON communication wire is polarity insensitive and can be laid out in a bus, star, loop or free topology. For loop topology, polarity is important and special care must be taken when connecting the LON network to avoid a short circuit. It is recommended to use the bus topology network configuration for all LON communication wiring, as it allows for easy network troubleshooting. Connect both wires to the LON 1 or 2 terminals of the controller. If inserting multiple wires in the terminals, ensure that the wires are properly twisted together prior to inserting them in the terminal connectors. Figure 19: Communications Wiring. SLX Series Page 5 of 9

6 For more information and detailed explanations on network topology and wire length restrictions, refer to the Junction Box and Wiring Guideline for Twisted Pair LonWorks Networks, published by Echelon Corporation. It is important to use proper network terminators depending on the type of network topology used. Failure to do so can result in communication errors between controllers. Do not use multiple gauges of cable on the same communication bus, as this may also result in communication errors. Selecting Network Terminators Topology Part # Bus PDIDI-BT-TP10XX Free PDIDI-FT-TP10XX Figure 21: Memory Erase Jumper Location (J4) on SLX-PC-203 and SLX-PC-300. For a bus topology, two network terminators are required (one at each end of the bus topology channel). For a free topology, one network terminator is required, and it can be put anywhere on the channel. 11. Memory Erase Jumper Each controller features a memory erase jumper that can be used to erase the Neuron chip s memory. If an incorrect APB file is loaded into the controller, the Neuron chip's memory will be corrupted and no communication with the controller will be possible. The memory erase jumper can be used to correct this problem by resetting the Neuron chip s memory; the chip will then be in an application-less state. The memory erase jumper is labeled J2 on the ASCs, J4 on the SLX-PC-203 and SLX- PC-300, and J20 on the SLX-PC-400 models and SLX-PC-500 models. To erase the Neuron chip's memory using the memory erase jumper, do the following: 1. Disconnect the power to the controller. 2. Place a jumper on the proper pins on the controller. Figure 22: Memory Erase Jumper Location (J20) on SLX-PC-400 and SLX-PC Reconnect power to the controller. 4. The orange-colored service LED will blink rapidly indicating that it is erasing the Neuron chip's memory. When the service LED stops blinking and remains solid, the erase procedure is complete. The erase procedure typically takes between 2 and 10 seconds. 5. Disconnect the power to the controller and remove the jumper. 6. Reconnect the power. The service LED will blink twice and become solid indicating that the controller is applicationless. The proper APB (using the Commission or Load option in LNS, e.g. SLX Series LMT) can now be loaded into the controller. 12. Maintenance Turn off power before any kind of servicing. Figure 20: Memory Erase Jumper Location (J2) on SLX-ASC. Each controller requires minimal maintenance, but it is important to take note of the following: - If it is necessary to clean the outside of the front plate and/or the inside of the back plate, use a dry cloth. - Verify the tension of all wires and cables whenever the controller is serviced. Page 6 of 9 SLX Series

7 13. Disposal The Waste Electrical and Electronic Equipment (WEEE) Directive sets out regulations for the recycling and disposal of products. The WEEE2002/96/EG Directive applies to standalone products, ie. products that can function entirely on their own and are not a part of another system or piece of equipment. For this reason SLX Series products are exempt from the WEEE Directive. Nevertheless, they are marked with the WEEE symbol, indicating that disposal of the devices shall not be done together with municipal waste. Products must be disposed of at the end of their useful life according to local regulations and the WEEE Directive. SLX Series Page 7 of 9

8 14. Typical Rooftop Application Wiring Diagram Page 8 of 9 SLX Series

9 15. Troubleshooting Guide Controller is powered but does not turn on Fuse has blown (Auto-reset fuse) Disconnect the power, the input and the output terminals. Then wait a few seconds to allow the auto-reset fuse to cool down. Check the power supply and check input and output wiring. Reconnect the power. Power supply polarity Verify that consistent polarity is maintained between all controllers and the transformer. Ensure that the COM terminal of each controller is connected to the same terminal on the secondary side of the transformer. See Figure 3. Controller cannot communicate on a FTT network Absent or incorrect supply voltage 1. Check power supply voltage between 24VAC/DC ±15% and COM pins, and ensure that it is between acceptable limits. 2. Check for tripped fuse or circuit breaker. Overloaded power transformer Verify that the transformer used is powerful enough to supply all controllers. Network not wired properly Double check that the wire connections are correct. Absent or incorrect network termination Check the network termination(s). Incorrect APB file has been loaded Use the memory erase jumper to reset the Neuron chip's memory, then load the proper APB into the Service pin not working controller using a network management tool (e.g. LMT). Controller communicates well over a short network, but does not communicate on large network Network length Check that the total wire length does not exceed the specifications of the Junction Box and Wiring Guideline for Twisted Pair LonWorks Networks. Wire type Check that the wire type agrees with the specification of the Junction Box and Wiring Guideline for Twisted Pair LonWorks Networks. Network wiring problem Double check that the wire connections are correct. Absent or incorrect network termination Check the termination(s). Incorrect or broken termination(s) will make the communication integrity dependent upon a controller s position on the network. Extra capacitance Make sure that no extra capacitance is being connected to the network other than the standard FTT circuit, and a maximum of a 3 meter stub (in bus topology). Number of devices on network segment The number of controllers on a channel should never exceed 64. Use a router or a repeater in accordance exceeded to the Junction Box and Wiring Guideline for Twisted Pair LonWorks Networks. Network traffic Query node statistic to check errors. Use a LON protocol analyzer to check network traffic. Hardware input is not reading the correct value Input wiring problem Check that the wiring is correct according to this document and according to the peripheral device s manufacturer. Open circuit or short circuit Use a voltmeter to check the voltage on the input terminal. Short circuit (0V) and Open circuit (5V). Configuration problem Use the controller configuration plug-in to check the configuration of the input. Hardware output is not operating correctly Output wiring problem Check that the wiring is correct according to this document and according to the peripheral device s manufacturer. Configuration problem Use the controller configuration plug-in to check the configuration of the input.. Service LED (Orange Color) Off (does not apply to PC models) Repeated Blink (PC models only) On Slow Blink (1 sec. On, 1 sec. Off) Fast Blink (0.3 sec. On, 1 sec. Off) The controller is in normal operation. The controller is in normal operation. The LED will blink according to the controller code execution time. The controller is application-less. Appropriate action: Reload the APB. The controller is unconfigured. Appropriate action: Commission the controller. Watchdog time out. Application corrupted. Appropriate action: Use the memory erase jumper to reset the Neuron chip's memory, then load the proper APB into the controller using a network management tool (e.g. LMT). Information in this publication is based on current specifications. The company reserves the right to make changes in specifications and models as design improvements are introduced. Other product or company names mentioned herein may be the trademarks of their respective owners Siemens Building Technologies, Inc. Siemens Building Technologies, Inc Deerfield Parkway Buffalo Grove, IL U.S.A. Document No Country of Origin: US Page 9 of 9

Hardware Installation Guide

Hardware Installation Guide Hardware Installation Guide IO Extension Module for ECL600 and ECB600 Series Controllers: 1. Product Description This document describes the hardware installation procedures for the I/O Extension Modules.

More information

Content. Product Description

Content. Product Description EY-modulo 4 EY-RU482F001 Room Operating Unit with Display for Fan Coil applications EY-RU483F001 Room Operating Unit with Display for VAV applications en Guidelines for the electrician Content 1 Product

More information

Hardware Installation Guide

Hardware Installation Guide Hardware Installation Guide BACnet Application Specific controller: ECB-203, ECB-300 and ECB-400 1. Product Description This document describes the hardware installation procedures for the ECB-series BACnet

More information

LN Free Programmable PRG 600 Series Controllers

LN Free Programmable PRG 600 Series Controllers LN Free Programmable PRG 600 Series Controllers Installation Instructions LN-PRG600-2, LN-PRG610-2 Code No. LIT-12011691 Issued July 17, 2014 Refer to the QuickLIT website for the most up-to-date version

More information

LN Series Input/Output (I/O) Extension Modules

LN Series Input/Output (I/O) Extension Modules LN Series Input/Output (I/O) Extension Modules Installation Instructions LN-IOE400-0, LN-IOE410-0, LN-IOE420-0 Code No. LIT-12011693 Issued April 24, 2014 Supersedes January 30, 2013 Refer to the QuickLIT

More information

LN Application Specific, Remote I/O, and Free Programmable Controllers

LN Application Specific, Remote I/O, and Free Programmable Controllers LN Application Specific, Remote I/O, and Free Programmable Controllers Installation Instructions LN-RTUL-1, LN-FCUL-1, LN-UVL-1, LN-HPUL-1, LN-IOxxx-1, LN-PRG203-2, LN-PRG300-2, LN-PRG4x0-2, LN-PRG5x0-2

More information

LTEC Heat Pump DDC Controller

LTEC Heat Pump DDC Controller Document No. 09 Rev., May, 00 LTEC Heat Pump DDC Controller Product Description These instructions explain how to install or replace a LTEC (LonMark Terminal Equipment Controller) HP (Heat Pump) DDC Controller

More information

LX-Display. Installation Instructions LX-DSWSC1-0, LX-DSWSC2-0. Mounting. Applications. North American Emissions Compliance

LX-Display. Installation Instructions LX-DSWSC1-0, LX-DSWSC2-0. Mounting. Applications. North American Emissions Compliance LX-Display Installation Instructions LX-DSWSC1-0, LX-DSWSC2-0 Code No. LIT-12011572 Issued April 28, 2014 Supersedes August 6, 2009 Applications The LX-Display controllers have multifunction Liquid Crystal

More information

Hardware Installation Guide

Hardware Installation Guide Hardware Installation Guide LonMark Certified VAV/VVT Controllers: ECL-VAVS-O, ECL-VAVS, ECL-VAV, ECL-VVTS, ECL-VAV-N 10-Point LonMark Certified Programmable Controllers: ECL-103 1. Product escription

More information

LTEC Unit Ventilator DDC Controller

LTEC Unit Ventilator DDC Controller Document No. 09 Rev., May, 00 LTEC Unit Ventilator DDC Controller Product Description These instructions explain how to install or replace a LTEC (LonMark Terminal Equipment Controller) UV (Unit Vent)

More information

DESIGO RX Individual room controllers. for fan-coil systems, chilled ceilings and radiators, with LONMARK-compatible bus communications

DESIGO RX Individual room controllers. for fan-coil systems, chilled ceilings and radiators, with LONMARK-compatible bus communications 3 834 DESIO RX Individual room controllers for fan-coil systems, chilled ceilings and radiators, with MARK-compatible bus communications RXC20.1 RXC21.1 The RXC20.1 and RXC21.1 controllers are used for

More information

UNT1100 Series. Binary Output Jumpers AO2 AO1 AO3 AO4 AOCM AOCM AOCM AOCM AO1. AI Switches Job Information N2 Address. Ref N2+ N2- ADDR 0 = ALL OPEN

UNT1100 Series. Binary Output Jumpers AO2 AO1 AO3 AO4 AOCM AOCM AOCM AOCM AO1. AI Switches Job Information N2 Address. Ref N2+ N2- ADDR 0 = ALL OPEN 1 2 8 4 AI6 R R Installation Bulletin UNT1100 Issue Date 0309 UNT1100 Series Introduction The Unitary (UNT) controller (UNT1100 Series) is a digital controller with applications for air handling units,

More information

FEATURES DESCRIPTION MODEL 110B. Power Supply

FEATURES DESCRIPTION MODEL 110B. Power Supply FEATURES Extends wiring distance of FT-10 LonWorks Networks. (2) channels using a single Model 110B. Up to 10 channels using (5) Model 110B. Low cost alternative to routers configured as repeaters. Wring

More information

DS A 10/99 MN 500 I/A SERIES MICRONET MN 500 CONTROLLERS APPLICATION SPECIFICATION

DS A 10/99 MN 500 I/A SERIES MICRONET MN 500 CONTROLLERS APPLICATION SPECIFICATION DS 10.103A 10/99 MN 500 WIRING AND COMMISSIONING INFORMATION FOR I/A SERIES MICRONET MN 500 CONTROLLERS APPLICATION Order Type: MNN-50-100 MicroNet NCP 500 Controller I/A Series MicroNet 500 Series Controllers

More information

Hardware Installation. Tracer MP581 Programmable Controller CNT-SVN01C-EN

Hardware Installation. Tracer MP581 Programmable Controller CNT-SVN01C-EN Hardware Installation Tracer MP581 Programmable Controller CNT-SVN01C-EN Hardware Installation Tracer MP581 Programmable Controller CNT-SVN01C-EN November 2005 Tracer MP581 Programmable Controller Hardware

More information

TEC Unit Conditioner Controller

TEC Unit Conditioner Controller Document No. 540-1026 TEC Unit Conditioner Controller Generic Controller I/O Layout. See Wiring Diagram for application specific details. Control Applications 2040 and 2041 2050 through 2054 Product Description

More information

LX Series Remote Input/Output (I/O) Controller

LX Series Remote Input/Output (I/O) Controller LX Series Remote Input/Output (I/O) Controller Product Bulletin LX-IO520-1, LX-IO401-1, LX-IO301-1 Code No. LIT-12011491 Issued June 22, 2009 The LX Series Remote Input/Output (I/O) controller extends

More information

Non-communicating room controllers

Non-communicating room controllers 3 882 DESIGO RXA Non-communicating room controllers RXA29.1 For fan-coil systems The RXA29.1 room controller are used for temperature control in individual rooms. For 2-pipe or 4-pipe fan-coil systems,

More information

CDD4 Duct Carbon Dioxide Transmitter

CDD4 Duct Carbon Dioxide Transmitter Drill or punch a 1-1/8 or 1-1/4 hole in the duct at the preferred location and insert the probe into the hole to mark the enclosure mounting holes. Remove the unit and drill the four mounting holes. Clean

More information

RXC39.5. Room controller. Building Technologies. Desigo RXC. Communicating room controller for fan-coil applications

RXC39.5. Room controller. Building Technologies. Desigo RXC. Communicating room controller for fan-coil applications s 3 856 Desigo RXC Room controller RXC39.5 Communicating room controller for fan-coil applications The RXC39.5 room controller is used for temperature control in individual rooms. For fan-coil systems

More information

Excel Smart I/O Compact

Excel Smart I/O Compact HONEYWELL ECEL 5000 OPEN SYSTEM GENERAL INFORMATION LonWorks service LED LonWorks service button terminal assignment label BEFORE INSTALLATION IMPORTANT INSTALLATION INSTRUCTIONS It is recommended that

More information

NEUROLOGIC RESEARCH CORPORATION MODEL 2500

NEUROLOGIC RESEARCH CORPORATION MODEL 2500 NEUROLOGIC RESEARCH CORPORATION MODEL 2500 NETWORK HUMISTAT Compact, self-contained dehumidifier controller. 0.5 degrees C accuracy typical. RH sensor is digitally calibrated for 2% accuracy. Open communication

More information

BACnet PTEC Heat Pump Multi-Stage Controller. Control Applications. Product Description. Product Numbers. Warning/Caution Notation

BACnet PTEC Heat Pump Multi-Stage Controller. Control Applications. Product Description. Product Numbers. Warning/Caution Notation BACnet PTEC Heat Pump Multi-Stage Controller Generic Controller I/O Layout. See Wiring Diagram for application specific details. Control Applications 6673, 6674 Product Description These instructions explain

More information

DTS 310. DIN Rail Mounted, Indoor Rated Revenue Grade Electrical Sub-meter. Page 1. Measurlogic MQ A

DTS 310. DIN Rail Mounted, Indoor Rated Revenue Grade Electrical Sub-meter. Page 1. Measurlogic MQ A DTS 310 DIN Rail Mounted, Indoor Rated Revenue Grade Electrical Sub-meter Page 1 1 PRODUCT OVERVIEW... 3 1.1 SUPPLIED ITEMS... 3 1.2 DOCUMENT CONVENTIONS... 4 1.3 PRODUCT SPECIFICATION... 4 1.3.1 Current

More information

TEC Heat Pump Multi-Stage Controller. Control Applications. Accessories. Product Description. Product Numbers. Warning/Caution Notation

TEC Heat Pump Multi-Stage Controller. Control Applications. Accessories. Product Description. Product Numbers. Warning/Caution Notation Document No. 540-1024 TEC Heat Pump Multi-Stage Controller Generic Controller I/O Layout. See Wiring Diagram for application specific details. Control Applications 2273 and 2274 Product Description These

More information

TEC VAV with 0-10V AO Heat. Modulation and CO2 Monitoring. Controller. Control Applications. Product Description. Accessories.

TEC VAV with 0-10V AO Heat. Modulation and CO2 Monitoring. Controller. Control Applications. Product Description. Accessories. Document No. 540-1031 TEC VAV with 0-10V AO Heat Modulation and CO2 Monitoring Controller Generic Controller I/O Layout. See Wiring Diagram for application specific details. Control Applications 2843,

More information

TEC Terminal Box (VAV) Controller

TEC Terminal Box (VAV) Controller Document No. 540-1025 TEC Terminal Box (VAV) Controller Generic Controller I/O Layout. See Wiring Diagram for application specific details. Control Applications 2020 through 2027 Product Description These

More information

RXTP ROOM TEMPERATURE

RXTP ROOM TEMPERATURE ROOM TEMPERATURE CONTROLLER WITH PI CONTROL Mounting and operating instructions Table of contents SAFETY AND PRECAUTIONS 3 PRODUCT DESCRIPTION 4 ARTICLE CODES 4 INTENDED AREA OF USE 4 TECHNICAL DATA 4

More information

Non-communicating room controllers

Non-communicating room controllers 3 881 DESIO RXA on-communicating room controllers For fan-coil systems RXA20.1 RXA21.1 RXA22.1 The RXA20.1, RXA21.1 and RXA22.1 room controllers are used for temperature control in individual rooms. For

More information

Specification Sheet For electronically commutated motors

Specification Sheet For electronically commutated motors SC-VAV-N Specification Sheet For electronically commutated motors Used in constant pressure applications The SC-EFC is designed to control exhaust air in various building applications. The system includes

More information

Tempco Instruction Manual

Tempco Instruction Manual Tempco Instruction Manual 1/16 DIN Solid State Temperature Controller Relay Output Solid State Output For Heating Model Numbers: TEC-901, TEC-902, TEC-905 Temperature controls in this series are designed

More information

IQ-SBS LCU Series Installation Instructions

IQ-SBS LCU Series Installation Instructions Installation Instructions LCU-1 The IQ-SBS LCU-1 is a self-contained device for integrating control of facility lighting with IQ-SBS. The LCU-1 controls lighting zones, accepts input from override switches

More information

LN Series Remote Input/Output (I/O) Modules

LN Series Remote Input/Output (I/O) Modules LN Series Remote Input/Output (I/O) Modules Product Bulletin LN-IO301-1, LN-IO401-1, LN-IO520-1 Code No. LIT-12011316 Issued June 5, 2012 Supersedes November 9, 2007 The LN Series Remote Input/Output (I/O)

More information

INSTALLATION INSTRUCTIONS

INSTALLATION INSTRUCTIONS INSTALLATION INSTRUCTIONS LonWorks Communication Card RXRX-AY02 RECOGNIZE THIS SYMBOL AS AN INDICATION OF IMPORTANT SAFETY INFORMATION! WARNING THESE INSTRUCTIONS ARE INTENDED AS AN AID TO QUALIFIED, LICENSED

More information

Junos WebApp Secure 5.0 Hardware Guide

Junos WebApp Secure 5.0 Hardware Guide Junos WebApp Secure 5.0 Hardware Guide Junos WebApp Secure 5.0 Hardware Guide This document contains a specification for the MWS1000 hardware appliance, as well as instructions for installation into a

More information

Siemens TEC Extended I/O Controller

Siemens TEC Extended I/O Controller Document No. 540-1028 TEC Extended I/O Controller Generic Controller I/O Layout. See Wiring Diagram for application specific details. Control Applications 2497 Product Description These instructions explain

More information

BA/BS4S Temperature Sensor Installation & Operating Instructions

BA/BS4S Temperature Sensor Installation & Operating Instructions Product Overview and Identification The BAPI-Stat 4 room temperature sensor features a large format LCD and slider setpoint adjustment. Additional options include button override and communication jack.

More information

RTT2 ROOM TEMPERATURE SWITCH. Mounting and operating instructions

RTT2 ROOM TEMPERATURE SWITCH. Mounting and operating instructions Mounting and operating instructions Table of contents SAFETY AND PRECAUTIONS PRODUCT DESCRIPTION ARTICLE CODES INTENDED AREA OF USE TECHNICAL DATA STANDARDS OPERATIONAL DIAGRAMS WIRING AND CONNECTIONS

More information

ENCL-MZ800-WAL ENCL-MX800-PAN MNL TAC I/A Series MicroNet MN 800 Series Controller Installation Instructions. Application.

ENCL-MZ800-WAL ENCL-MX800-PAN MNL TAC I/A Series MicroNet MN 800 Series Controller Installation Instructions. Application. TAC 1354 Clifford Avenue P. O. Box 2940 Loves Park, IL 61132-2940 www.tac.com ENCL-MZ800-WAL ENCL-MX800-PAN MNL-800-101 TAC I/A Series MicroNet MN 800 Series Controller Installation Instructions Application

More information

BACnet PTEC Terminal Box (VAV) Controller. Control Applications. Product Numbers. Product Description. Warning/Caution Notation

BACnet PTEC Terminal Box (VAV) Controller. Control Applications. Product Numbers. Product Description. Warning/Caution Notation BACnet PTEC Terminal Box (VAV) Controller Generic Controller I/O Layout. See Wiring Diagram for application specific details. Control Applications 6600 through 6607 Product Description These instructions

More information

ECB-VAV Series & ECB-103 Controllers

ECB-VAV Series & ECB-103 Controllers Hardware Installation Guide ECB-VAV Series & ECB-103 Controllers Figure 1: From left to right: ECB-VAV and ECB-103 Product Description This document describes the hardware installation procedures for the

More information

RТTH DUAL ROOM SWITCH

RТTH DUAL ROOM SWITCH DUAL ROOM SWITCH FOR TEMPERATURE AND RELATIVE HUMIDITY Mounting and operating instructions Table of contents SAFETY AND PRECAUTIONS PRODUCT DESCRIPTION ARTICLE CODES INTENDED AREA OF USE TECHNICAL DATA

More information

LN Series Free Programmable LN-PRGxxx-12 Controllers

LN Series Free Programmable LN-PRGxxx-12 Controllers LN Series Free Programmable LN-PRGxxx-12 Controllers Installation Instructions LN-PRG203-12, LN-PRG300-12, LN-PRG4x0-12, LN-PRG6x0-12 Code No. LIT-12011796 Issued April 24, 2014 Supersedes January 30,

More information

CTR21, CTR22, CTR23, and CTR24 Wall Modules

CTR21, CTR22, CTR23, and CTR24 Wall Modules CTR21, CTR22, CTR23, and CTR24 Wall Modules FEATURES SPECIFICATION DATA The CTR21, CTR22, CTR23, and CTR24 family of wall modules include: Models with setpoint adjustment. Models with occupied/unoccupied

More information

Installation manual for for Schleifenbauer DPM3

Installation manual for for Schleifenbauer DPM3 Installation manual for for Schleifenbauer DPM3 Installatie handleiding voor Schleifenbauer DPM3 Installationsanleitung für Schleifenbauer DPM3 Guide d installation du Schleifenbauer DPM3 Installation

More information

RWD68U Universal Controller

RWD68U Universal Controller Document No. 155-738 RWD68U Universal Controller Description Features Product Number The Universal Controller is intended for heating, air conditioning, ventilation and refrigeration in comfort control

More information

Power supply module, bus connection module

Power supply module, bus connection module s 8 183 8183p01, p02 TX-I/O Power supply module, bus connection module TXS1.12F10 TXS1.EF10 Each I/O row begins with one of these devices TXS1.12F10 power supply module Up to 4 power supply modules can

More information

PXC Compact Unitary Equipment Controller (UEC)

PXC Compact Unitary Equipment Controller (UEC) Document No. 553-169 PXC Compact Unitary Equipment Controller (UEC) Product Description The PXC Unitary Equipment Controller (UEC) is an MS/TP device that can be configured as a programmable, stand-alone

More information

TOXALERT MODEL AIR 2000

TOXALERT MODEL AIR 2000 TOXALERT MODEL AIR 2000 NOTE: Toxalert s Model GVU-CO 2 Sensor is the same as the Air2000R. Microprocessor-based, Infrared Environmental CO 2 Sensor OPERATOR S MANUAL TOXALERT TM INTERNATIONAL INC. P.O.

More information

ECP-PTU Series. ECP-PTU Series. 14-Point High-Voltage Programmable Power Terminal Unit Controller. Applications. Features

ECP-PTU Series. ECP-PTU Series. 14-Point High-Voltage Programmable Power Terminal Unit Controller. Applications. Features ECP-PTU Series 14-Point High-Voltage Programmable Power Terminal Unit Controller Applications Control of equipment such as: roof top units, fan coils, heat pumps, ventilator units, terminal units, lighting

More information

LX Series Free Programmable Controllers

LX Series Free Programmable Controllers Code No. LIT-1900565 Issued November 5, 2012 LX-PRG203-1, LX-PRG300-1, LX-PRG4x0-1, LX-PRG5x0-1 LX Series Free Programmable Controllers Description The LX Series Free Programmable Controllers are microprocessor-based

More information

Please Read Instruction Carefully Before Installation! Figure 1: A/CO2-DUCT

Please Read Instruction Carefully Before Installation! Figure 1: A/CO2-DUCT Installation and Operation Instructions A/CO2-DUCT Series Please Read Instruction Carefully Before Installation! Figure 1: A/CO2-DUCT PRECAUTIONS REMOVE POWER BEFORE WIRING. NEVER CONNECT OR DISCONNECT

More information

This simple chassis houses one media-converter module and features an external AC power supply and also a terminal block for DC power input.

This simple chassis houses one media-converter module and features an external AC power supply and also a terminal block for DC power input. LMC5103A-R2 1-slot Multipower Desktop Chassis (Module Not Included) This simple chassis houses one media-converter module and features an external AC power supply and also a terminal block for DC power

More information

RXTH DUAL ROOM SENSOR / SWITCH

RXTH DUAL ROOM SENSOR / SWITCH DUAL ROOM SENSOR / SWITCH FOR TEMPERATURE AND RELATIVE HUMIDITY Mounting and operating instructions Table of contents SAFETY AND PRECAUTIONS 3 PRODUCT DESCRIPTION 4 ARTICLE CODES 4 INTENDED AREA OF USE

More information

RXB39.1. Room controller RXB. Communicating room controller for fan-coil applications FC-13

RXB39.1. Room controller RXB. Communicating room controller for fan-coil applications FC-13 s 3 875 RXB Room controller Communicating room controller for fan-coil applications FC-13 RXB39.1 The RXB39.1 room controller is used for temperature control in individual rooms. For 2-pipe or 4-pipe fan-coil

More information

Actuator Commissioning Tool

Actuator Commissioning Tool Document No. 129-287 Actuator Commissioning Tool Product Description The 985-047 Actuator Commissioning Tool provides a portable instrument for exercising, calibrating, and testing resistive, proportional

More information

TKL19 (RTUL19) Installation Manual. Tema1.0_L19_IM_1.0_EN Pagina 1 di 24

TKL19 (RTUL19) Installation Manual. Tema1.0_L19_IM_1.0_EN Pagina 1 di 24 TKL19 (RTUL19) Installation Manual Tema1.0_L19_IM_1.0_EN Pagina 1 di 24 CONTENTS 1.1 Wall Set Up for the Cable Trays... 3 1.2 Electrical Connections... 4 1.3 LONWORKS Data Cables... 6 1.4 Mounting the

More information

MicroTech II TM Remote I/O Panel Installation Manual

MicroTech II TM Remote I/O Panel Installation Manual Installation Manual IM 783-0 MicroTech II TM Remote I/O Panel Installation Manual Group: Controls Part Number: IM 783-0 Date: February 2004 Supersedes: New 2004 McQuay International Page 2 IM-783 Table

More information

EX-RC1 Remote I/O Adapter

EX-RC1 Remote I/O Adapter EX-RC1 Remote I/O Adapter The EX-RC1 interfaces between Unitronics Vision OPLCs and remote I/O Expansion Modules distributed throughout your system. The adapter is connected to a PLC via CANbus. Each adapter

More information

When any of the following symbols appear, read the associated information carefully. Symbol Meaning Description

When any of the following symbols appear, read the associated information carefully. Symbol Meaning Description Uni-I/O Wide Modules Installation Guide UIS-WCB1 Uni-I/O Wide is a family of Input/Output modules that are compatible with the UniStream control platform. Wide Modules are 1.5 times as wide as Uni-I/O

More information

LON Module for Variable Speed Drive

LON Module for Variable Speed Drive 5 193. LON Module for Variable Speed Drive SED2 Conforms to and is certified to the LONMARK Interoperability Guidelines enabling information sharing with other LONMARK products. LONMARK-compliant with

More information

INJ-24A Series Quick Installation Guide

INJ-24A Series Quick Installation Guide INJ-24A Series Quick Installation Guide Moxa High-Power PoE+ Injector Edition 4.1, August 2017 Technical Support Contact Information www.moxa.com/support Moxa Americas: Toll-free: 1-888-669-2872 Tel: 1-714-528-6777

More information

RST ROOM TEMPERATURE TRANSMITTER. Mounting and operating instructions

RST ROOM TEMPERATURE TRANSMITTER. Mounting and operating instructions Mounting and operating instructions Table of contents SAFETY AND PRECAUTIONS 3 PRODUCT DESCRIPTION 4 ARTICLE CODES 4 INTENDED AREA OF USE 4 TECHNICAL DATA 4 STANDARDS 4 OPERATIONAL DIAGRAM 5 WIRING AND

More information

clarity 3 Programmable Controller

clarity 3 Programmable Controller clarity 3 Programmable Controller BACnet General Purpose Controllers (B-AAC) DESCRIPTION Taco Clarity 3 FPC series controllers are designed to control building systems and HVAC equipment. The integrated

More information

Datasheet. ECB-PTU Series. 1/14. BACnet B-ASC Powered Terminal Unit Programmable Controllers. Overview

Datasheet. ECB-PTU Series.  1/14. BACnet B-ASC Powered Terminal Unit Programmable Controllers. Overview Datasheet BACnet B-ASC Powered Terminal Unit Programmable Controllers Overview Applications Meets the requirements of the following applications: Fan Coil Units Heat Pumps Chilled Beams Reversible Ceiling

More information

When any of the following symbols appear, read the associated information carefully. Symbol Meaning Description

When any of the following symbols appear, read the associated information carefully. Symbol Meaning Description Uni-I/O Modules Installation Guide UID-0808THS Uni-I/O is a family of Input/Output modules that are compatible with the UniStream control platform. This guide provides basic installation information for

More information

CDD Carbon Dioxide Transmitter

CDD Carbon Dioxide Transmitter Introduction The OSA CO2 transmitter uses Infrared Technology to monitor CO2 levels within a range of 0 2000 ppm and outputs a linear 4-20 ma or 0-5/0-10 Vdc signal. The enclosure is designed to operate

More information

Lonix Automation/BMS. Installation Manual.

Lonix Automation/BMS. Installation Manual. /BMS www.lonix.com 2 (12) INDEX 1 Introduction... 3 2 LonWorks Fieldbus in Lonix System... 3 2.1 Fieldbus Topology... 3 2.2 Fieldbus Termination... 4 2.3 Routers and Repeaters... 4 2.4 Fieldbus Cabling...

More information

Analog Input Installation Manual

Analog Input Installation Manual Analog Input Installation Manual August 2011 Part Number: 144-23917 Copyright 2011 Magnetek 1. Preface and Safety Magnetek manufactures products used as components in a wide variety of industrial systems

More information

CMSA-100 Manual. Cinema Media Server Automation

CMSA-100 Manual. Cinema Media Server Automation CMSA-100 Manual Cinema Media Server Automation 181 Bonetti Drive San Luis Obispo, CA 93401-7397 USA Phone: +1 805 549 0161 Fax: +1 805 549 0163 www.uslinc.com Table of Contents 1. Safety Notice... 3 2.

More information

See instructions to download and install the latest version of LinkBoxLON and the user's manual at

See instructions to download and install the latest version of LinkBoxLON and the user's manual at Safety Instructions WARNING Follow carefully this safety and installation instructions. Improper work may lead to serious harmful for your health and also may damage seriously the IntesisBox and/or any

More information

RXL24.1. Room controller RXL. Communicating controller for chilled ceiling and radiator applications CC-02

RXL24.1. Room controller RXL. Communicating controller for chilled ceiling and radiator applications CC-02 s 3 878 RXL Room controller RXL24.1 Communicating controller for chilled ceiling and radiator applications CC-02 The RXL24.1 room controller is used for temperature control in individual rooms. For chilled

More information

MicroTech II Remote I/O Panel Installation Manual

MicroTech II Remote I/O Panel Installation Manual MicroTech II Remote I/O Panel Installation Manual Installation Manual IM 783-2 Group: Controls Part Number: IM 783 Date: November 2006 Supersedes: IM 783-1 Table of Contents Notice... 3 Reference Documents...

More information

Sylk I/O Devices APPLICATION FEATURES PRODUCT DATA

Sylk I/O Devices APPLICATION FEATURES PRODUCT DATA Sylk I/O Devices APPLICATION PRODUCT DATA The Sylk IO devices are part of the Spyder family. The three IO devices are designed to seamlessly integrate with Spyder with relay controllers using only Sylk

More information

ECB-203 Series BACnet B-ASC 14-Point Programmable Controllers

ECB-203 Series BACnet B-ASC 14-Point Programmable Controllers Datasheet ECB-203 Series BACnet B-ASC 14-Point Programmable Controllers Overview Features & Benefits The ECB-203 Series controllers are microprocessor-based programmable controllers designed to control

More information

CDD4 Series Room CO2 Transmitter Installation Instructions

CDD4 Series Room CO2 Transmitter Installation Instructions CDD4 Series Room CO2 Transmitter Installation Instructions Introduction The CO2 transmitter uses Infrared Technology to monitor CO2 levels and outputs a linear 4-20 ma or 0-5/0-10 Vdc signal. Options include

More information

ETM-2050/ETM-2051 Service Manual

ETM-2050/ETM-2051 Service Manual Introduction Novar s Electronic Thermostat Modules (ETMs) are intelligent control modules that provide local, direct digital control of unitary, packaged, staged HVAC systems. This document: Describes

More information

BACnet PTEC Unit Conditioner/Fan Coil P. Controller. Control Applications. Accessories. Product Description. Warning/Caution Notation

BACnet PTEC Unit Conditioner/Fan Coil P. Controller. Control Applications. Accessories. Product Description. Warning/Caution Notation Installation Instructions BACnet PTEC Unit Conditioner/Fan Coil Controller Figure 1. BACnet PTEC Unit Conditioner/Fan Coil Controller. Control Applications 6540, 6541, 6550, 6551, 6552, 6553 and 6554 Product

More information

TECH/DATA SHEET. Application. Model Chart. Installation. slon-v1. slon-v2. slon VAV Controller

TECH/DATA SHEET. Application. Model Chart. Installation. slon-v1. slon-v2. slon VAV Controller TECH/DATA SHEET s-v1 s-v2 s VAV Controller Application Solidyne s s-v1 and s-v2 VAV Controllers are interoperable MARK -compliant variable air volume controllers. These controllers provide pressure independent

More information

TAC Xenta 101-VF. 3-Speed Fan Coil Controller. TAC Xenta

TAC Xenta 101-VF. 3-Speed Fan Coil Controller. TAC Xenta TAC Xenta TAC Xenta 101-VF 3-Speed Fan Coil Controller TAC Xenta 101-VF is a zone controller intended primarily for fan coil applications with the ability to control fans with multiple speeds, with one

More information

LON-module for MULTICAL 601

LON-module for MULTICAL 601 LON-module for MULTICAL 601 Type 67-00-24-000-000 i n s t a l l a t i o n Kamstrup A/S Industrivej 28, Stilling, DK-8660 Skanderborg TEL: +45 89 93 10 00 FAX: +45 89 93 10 01 info@kamstrup.com www.kamstrup.com

More information

TCNM-ACBB1 Installation Manual

TCNM-ACBB1 Installation Manual The TCNM-ACBB1 is a connection box that can be used as an accessory to facilitate system connections for installation and device replacement of several Banner family reading devices. System cabling is

More information

Temperature controller Ducted systems

Temperature controller Ducted systems 2 725 Temperature controller Ducted systems Standard model without zoning functions RRV851 Multifunctional controller used for central control of ducted HVAC systems in combination with a QAX850 master

More information

DLA. DMX512 Analyzer. DLA Users Manual SV2_00 B.lwp copyright ELM Video Technology, Inc.

DLA. DMX512 Analyzer. DLA Users Manual SV2_00 B.lwp copyright ELM Video Technology, Inc. DLA DMX512 Analyzer DLA DLA-HH 1 Table Of Contents IMPORTANT SAFEGUARDS... 2 DLA OVERVIEW... 3 CONNECTION... 3 OPERATION... 3 HARDWARE SETUP... 4 DLA-HH (PORTABLE) LAYOUT... 4 CHASSIS LAYOUT... 4 DLA MENU

More information

RXL24.1. Room controller RXL. Communicating controller for chilled ceiling and radiator applications CC-02

RXL24.1. Room controller RXL. Communicating controller for chilled ceiling and radiator applications CC-02 s 3 878 RXL Room controller RXL24.1 Communicating controller for chilled ceiling and radiator applications CC-02 The RXL24.1 room controller is used for temperature control in individual rooms. For chilled

More information

M1000 INTELLIGENT ZONE CONTROL SYSTEM

M1000 INTELLIGENT ZONE CONTROL SYSTEM HARDWARE GUIDE DIMENSIONS & SPECIFICATIONS REV. 5.2 M1000 INTELLIGENT ZONE CONTROL SYSTEM ROOFTOP CONTROLLER 2 Table of Contents GENERAL INFORMATION... 3 PL-M1000 Rooftop Controller...3 Description...3

More information

INSTRUCTION SHEET. Eaton Logic Controller ELCB Controllers

INSTRUCTION SHEET. Eaton Logic Controller ELCB Controllers 2010-12-10 5011699201-PBB1 Eaton Logic Controller ELCB Controllers INSTRUCTION SHEET [Applicable Controllers] ELCB-PB10 ELCB-PB14 ELCB-PB20 ELCB-PB30 ELCB-PB40 IL05001005E 002-1310020-02 Thank you for

More information

INSTALLATION MANUAL SLI 50 INVERTER

INSTALLATION MANUAL SLI 50 INVERTER INSTALLATION MANUAL SLI 50 INVERTER www.unipowerco.com Manual No. SLI-50-48-3 2016 UNIPOWER LLC All Rights Reserved UNIPOWER LLC 3900 Coral Ridge Drive, Coral Springs, Florida 33065, USA sales@unipowerco.com

More information

Suitable for a wide range of installations with wall-mount, flush-mount and hand-held remote control options.

Suitable for a wide range of installations with wall-mount, flush-mount and hand-held remote control options. TUC03 Configurable Terminal Unit Controller Product Bulletin The TUC03 Configurable Terminal Unit Controller is designed specifically to provide direct digital control of terminal unit applications with

More information

BACnet vs. Lonworks Specifications (Network Guide)

BACnet vs. Lonworks Specifications (Network Guide) Connections IP, MS/TP, Ethernet TCP/IP with Fox connections Topology BACnet p. 17-19 Lon pp. 39-40 Termination Requirements BACnet pp. 17-19 Lon pp. 39-40 Cable Requirements BACnet p. 16 Lon p. 41 Daisy

More information

QAX50.1 QAX50.5 QAX51.1 QAX51.5. Flexible room unit. Desigo RXC

QAX50.1 QAX50.5 QAX51.1 QAX51.5. Flexible room unit. Desigo RXC 1 648 Desigo RXC Flexible room unit for integrated operation of HVAC, lighting and blinds in individual rooms; with LONMARK -compatible bus communication QAX50.1 QAX50.5 QAX51.1 QAX51.5 Room temperature

More information

REDUNDANCY MODULE TSP-REM360 AND TSP-REM600

REDUNDANCY MODULE TSP-REM360 AND TSP-REM600 REDUNDANCY MODULE TSP-REM360 AND TSP-REM600 Operating Instructions Seite 1 Dimensions drawings: TSP-REM360 Weight: 0.882lb Gewicht: 0.40kg Seite 2 Dimensions drawings: TSP-REM600 Bottom view Top view Side

More information

FX Input/Output (I/O) Modules XM07 and XM14

FX Input/Output (I/O) Modules XM07 and XM14 Product Bulletin FX I/O Modules Issue Date July 6, 2009 FX Input/Output (I/O) Modules XM07 and XM14 The FX Input/Output (I/O) Modules provide additional physical input and output points for FX field controllers

More information

USER S MANUAL Power Supply for Backplane Vdc

USER S MANUAL Power Supply for Backplane Vdc USER S MANUAL Power Supply for Backplane 20-30 Vdc D F 5 6 M E smar www.smar.com Specifications and information are subject to change without notice. Up-to-date address information is available on our

More information

POE084824B. PoE 54V/8x0,3A/4x7Ah PoE buffer power supply for up to 8 IP camera. v.1.1 EN* Edition: 7 from

POE084824B. PoE 54V/8x0,3A/4x7Ah PoE buffer power supply for up to 8 IP camera. v.1.1 EN* Edition: 7 from POE084824B v.1.1 PoE 54V/8x0,3A/4x7Ah PoE buffer power supply for up to 8 IP camera. EN* Edition: 7 from 15.11.2017 Supersedes the edition: 6 from 22.11.2016 GREEN POWER CCTV PoE PSU features: DC 54V uninterruptible

More information

XT-9100 Technical Bulletin

XT-9100 Technical Bulletin System 9100 Technical Manual 636.4 Technical Bulletins Section Technical Bulletin Issue Date 0896 XT-9100 Technical Bulletin XT-9100 Extension Module/XP-910x Expansion Modules Page 3 Introduction 3 SX

More information

OHIO SEMITRONICS, INC. AC MULTIFUNCTION PROGRAMMABLE TRANSDUCERS & -1000L

OHIO SEMITRONICS, INC. AC MULTIFUNCTION PROGRAMMABLE TRANSDUCERS & -1000L AC PROGRAMMABLE TRANSDUCERS MODBUS OR LONWORKS DESCRIPTION The DMT-1000 is a programmable transducer with an RS-485 bus interface (MODBUS ). It supervises several variables of a poly-phase electrical power

More information

Operating instructions. Switching amplifier DN0210 DN / / 2015

Operating instructions. Switching amplifier DN0210 DN / / 2015 Operating instructions Switching amplifier DN0210 DN0220 UK 80011079 / 00 01 / 2015 Contents 1 Preliminary note...4 1.1 Symbols used...4 1.2 Warning signs used...4 2 Safety instructions...5 2.1 General...5

More information

AUDIO AND VIDEO DOOR ENTRY SYSTEM WITH NEXA CODED PANEL

AUDIO AND VIDEO DOOR ENTRY SYSTEM WITH NEXA CODED PANEL AUDIO AND VIDEO DOOR ENTRY SYSTEM WITH NEXA CODED PANEL 2 INTRODUCTION First and foremost we would like to thank you for purchasing this product. Our commitment to satisfying our customers can be seen

More information

TELN 1018 Automotive Four Channel Input Node Version 1.0

TELN 1018 Automotive Four Channel Input Node Version 1.0 Simple.Sensible.Smart TELN 1018 Automotive Four Channel Input Node Version 1.0 Users Manual January 1999 Techlon Instruments, Inc. P.O. Box 127 Topton, PA 19562 (610)682-9764 (610)682-9765 FAX E-mail:

More information