Thermocouple Input Module Channel Isolated Thermocouple/Micro Voltage Input Module User's Manual. Q64TD Q64TDV-GH GX Configurator-TI (SW1D5C-QTIU-E)

Size: px
Start display at page:

Download "Thermocouple Input Module Channel Isolated Thermocouple/Micro Voltage Input Module User's Manual. Q64TD Q64TDV-GH GX Configurator-TI (SW1D5C-QTIU-E)"

Transcription

1 Thermocouple Input Module Channel Isolated Thermocouple/Micro Voltage Input Module User's Manual Q64TD Q64TDV-GH GX Configurator-TI (SW1D5C-QTIU-E)

2

3 SAFETY PRECAUTIONS (Read these precautions before using this product.) Before using this product, please read this manual and the relevant manuals carefully and pay full attention to safety to handle the product correctly. The precautions given in this manual are concerned with this product only. For the safety precautions of the programmable controller system, refer to the user s manual for the CPU module used. In this manual, the safety precautions are classified into two levels: " WARNING" and " CAUTION". Under some circumstances, failure to observe the precautions given under " CAUTION" may lead to serious consequences. Observe the precautions of both levels because they are important for personal and system safety. Make sure that the end users read this manual and then keep the manual in a safe place for future reference. [Design Precautions] WARNING Do not write any data to the system area of the buffer memory in the intelligent function module. Also, do not use any use prohibited signals as an output signal from the programmable controller CPU to the intelligent function module. Doing so may cause malfunction of the programmable controller system. CAUTION Do not install the control lines or communication cables together with the main circuit lines or power cables. Keep a distance of 100mm or more between them. Failure to do so may result in malfunction due to noise. A - 1 A - 1

4 [Installation Precautions] CAUTION Use the programmable controller in an environment that meets the general specifications in the user s manual for the CPU module used. Failure to do so may result in electric shock, fire, malfunction, or damage to or deterioration of the product. To mount the module, while pressing the module mounting lever located in the lower part of the module, fully insert the module fixing projection(s) into the hole(s) in the base unit and press the module until it snaps into place. Incorrect mounting may cause malfunction, failure or drop of the module. When using the programmable controller in an environment of frequent vibrations, fix the module with a screw. Tighten the screws within the specified torque range. Undertightening can cause drop of the screw, short circuit or malfunction. Overtightening can damage the screw and/or module, resulting in drop, short circuit, or malfunction. Shut off the external power supply (all phases) used in the system before mounting or removing the module. Failure to do so may result in damage to the product. A module can be replaced online (while power is on) on any MELSECNET/H remote I/O station or in the system where a CPU module supporting the online module change function is used. Note that there are restrictions on the modules that can be replaced online, and each module has its predetermined replacement procedure. For details, refer to the relevant chapter in this manual. Do not directly touch any conductive and electronic component of the module. Doing so can cause malfunction or failure of the module. [Wiring Precautions] WARNING After wiring, attach the included terminal cover to the module before turning it on for operation. Failure to do so may result in electric shock. CAUTION Individually ground the FG terminal of the programmable controller with a ground resistance of 100 or less. Failure to do so may result in electric shock or malfunction. Tighten the terminal screws within the specified torque range. Undertightening can cause short circuit, fire, or malfunction. Overtightening can damage the screw and/or module, resulting in drop, short circuit, or malfunction. Prevent foreign matter such as dust or wire chips from entering the module. Such foreign matter can cause a fire, failure, or malfunction. A protective film is attached to the top of the module to prevent foreign matter, such as wire chips, from entering the module during wiring. Do not remove the film during wiring. Remove it for heat dissipation before system operation. Use applicable solderless terminals and tighten them with the specified torque. If any solderless spade terminal is used, it may be disconnected when the terminal screw comes loose, resulting in failure. Keep a distance of 100mm or more between a thermocouple and the main circuit line or AC control lines. Also, keep the thermocouple away from a circuit that includes harmonics, such as a highvoltage circuit and a load circuit of an inverter. If not, the thermocouple is more likely to be affected by noise, surges, and induction. A - 2 A - 2

5 [Startup and Maintenance Precautions] WARNING Do not touch any terminal while power is on. Doing so will cause electric shock or malfunction. Shut off the external power supply (all phases) used in the system before cleaning the module or retightening the terminal screws, connector screws, or module fixing screws. Failure to do so may result in electric shock or cause the module to fail or malfunction. Undertightening can cause drop of the screw, short circuit or malfunction. Overtightening can damage the screw and/or module, resulting in drop, short circuit, or malfunction. CAUTION Do not disassemble or modify the modules. Doing so may cause failure, malfunction, injury, or a fire. Shut off the external power supply (all phases) used in the system before mounting or removing the module. Failure to do so may cause the module to fail or malfunction. A module can be replaced online (while power is on) on any MELSECNET/H remote I/O station or in the system where a CPU module supporting the online module change function is used. Note that there are restrictions on the modules that can be replaced online, and each module has its predetermined replacement procedure. For details, refer to the relevant chapter in this manual. After the first use of the product, do not mount/remove the module to/from the base unit, and the terminal block to/from the module more than 50 times (IEC compliant). Exceeding the limit of 50 times may cause malfunction. Before handling the module, touch a conducting object such as a grounded metal to discharge the static electricity from the human body. Failure to do so may cause the module to fail or malfunction. [Disposal Precaution] CAUTION When disposing of this product, treat it as industrial waste. A - 3 A - 3

6 CONDITIONS OF USE FOR THE PRODUCT (1) Mitsubishi programmable controller ("the PRODUCT") shall be used in conditions; i) where any problem, fault or failure occurring in the PRODUCT, if any, shall not lead to any major or serious accident; and ii) where the backup and fail-safe function are systematically or automatically provided outside of the PRODUCT for the case of any problem, fault or failure occurring in the PRODUCT. (2) The PRODUCT has been designed and manufactured for the purpose of being used in general industries. MITSUBISHI SHALL HAVE NO RESPONSIBILITY OR LIABILITY (INCLUDING, BUT NOT LIMITED TO ANY AND ALL RESPONSIBILITY OR LIABILITY BASED ON CONTRACT, WARRANTY, TORT, PRODUCT LIABILITY) FOR ANY INJURY OR DEATH TO PERSONS OR LOSS OR DAMAGE TO PROPERTY CAUSED BY the PRODUCT THAT ARE OPERATED OR USED IN APPLICATION NOT INTENDED OR EXCLUDED BY INSTRUCTIONS, PRECAUTIONS, OR WARNING CONTAINED IN MITSUBISHI'S USER, INSTRUCTION AND/OR SAFETY MANUALS, TECHNICAL BULLETINS AND GUIDELINES FOR the PRODUCT. ("Prohibited Application") Prohibited Applications include, but not limited to, the use of the PRODUCT in; Nuclear Power Plants and any other power plants operated by Power companies, and/or any other cases in which the public could be affected if any problem or fault occurs in the PRODUCT. Railway companies or Public service purposes, and/or any other cases in which establishment of a special quality assurance system is required by the Purchaser or End User. Aircraft or Aerospace, Medical applications, Train equipment, transport equipment such as Elevator and Escalator, Incineration and Fuel devices, Vehicles, Manned transportation, Equipment for Recreation and Amusement, and Safety devices, handling of Nuclear or Hazardous Materials or Chemicals, Mining and Drilling, and/or other applications where there is a significant risk of injury to the public or property. Notwithstanding the above, restrictions Mitsubishi may in its sole discretion, authorize use of the PRODUCT in one or more of the Prohibited Applications, provided that the usage of the PRODUCT is limited only for the specific applications agreed to by Mitsubishi and provided further that no special quality assurance or fail-safe, redundant or other safety features which exceed the general specifications of the PRODUCTs are required. For details, please contact the Mitsubishi representative in your region. A - 4 A - 4

7 REVISIONS Print Date Manual Number Revision Nov., 2000 Jun., 2001 Feb., 2002 Feb., 2003 Sep., 2003 May, 2004 Oct., 2004 The manual number is given on the bottom left of the back cover. SH (NA) A First printing SH (NA) B Addition Selection 2.1, 2.2 Correction Conformation to the EMC Directive and Low Voltage Instruction, About the Generic Terms and Abbreviations, Product Structure, Section 3.1.1, Section 5.2, 5.2.1, 5.2.2, SH (NA) C Q64TDV-GH was added as a new model. Addition Section 3.1.2, 3.2.1, 3.2.3, 3.4.2, , , , , Section 5.6.3, Chapter 7, Section 8.2.8, Appendix 4 to 6 Correction SAFETY PRECAUTIONS, About the Generic Terms and Abbreviations, Chapter 1, Section 1.1, Section 2.1, 2.2, Section 3.1.1, 3.2, 3.2.2, 3.3.1, 3.3.2, 3.4.1, to 3.4.9, to , , , Section 4.2, 4.3, 4.4.1, 4.4.2, 4.5 to 4.7, Section 5.1, 5.2.1, 5.2.2, 5.4, 5.5, 5.6.1, 5.6.2, Chapter 6, Chapter 8, Section 8.1, 8.2.1, to 8.2.7, 8.2.9, Appendix 7 SH (NA) D Addition Section 1.2, Section Correction SAFETY PRECAUTIONS, Section 2.1, Section 3.1.1, 3.1.2, 3.2, 3.3.1, 3.3.2, 3.4.1, 3.4.2, 3.4.4, 3.4.7, 3.4.8, to , , Section 4.3, 4.5, 4.6, Section 5.1, 5.2.1, 5.2.2, 5.3.2, 5.3.3, 5.4, 5.5, to 5.6.3, Section 6.1, 6.1.1, 6.1.2, 6.2, 6.2.1, 6.2.2, 7.3.1, 7.3.3, 7.3.4, 7.3.6, 7.4, Section 8.1, 8.2.1, 8.2.5, Appendix 4.1, Appendix 5.2, Appendix 5.3 SH (NA) E Addition Section 3.4.1, 3.4.2, , Section 4.5, 4.6 Correction Section 3.1.1, 3.1.2, 3.3.1, 3.3.2, to , Section 4.5, 4.6, Section 5.1, 5.2.1, 5.3.1, 5.3.2, 5.5, to 5.6.4, Section 6.1.1, 6.2.1, Chapter 7, Section 7.3.4, 7.3.6, 7.4, Appendix 5.2, Appendix 5.3, Appendix 7 SH (NA) F Correction Section 2.2, Section , Section 7.1, to SH (NA) G Correction SAFETY PRECAUTIONS, Section 2.1, Section 3.1.1, Section 4.1, Section 6.2, A - 5 A - 5

8 Print Date Manual Number Revision Sep., 2005 SH(NA) H Addition Section 3.2.4, , , Appendix 4.2 Correction Conformation to the EMC Directive and Low Voltage Instruction, Section 1.2, Section 2.1, 2.2, Section 3.1.1, 3.1.2, 3.2, 3.2.3, 3.3.1, 3.3.2, 3.4.1, 3.4.2, 3.4.6, , , Section 5.1, 5.2.2, Section 6.1.1, 6.2.1, 6.2.2, Section 8.2.9, Appendix 4.1 Feb., 2006 SH(NA) I Addition Appendix 5.1 Correction SAFETY PRECAUTIONS, Section 1.2, Section 2.2, Section , Section 7.3.3, 7.3.5, Appendix 5, INDEX Section number changed Appendix 5.1 Appendix 5.2, Appendix 5.2 Appendix 5.3, Appendix 5.3 Appendix 5.4 Mar., 2006 SH(NA) J Correction Section Oct., 2007 SH(NA) K Correction Jan., 2008 May, 2008 Sep., 2011 About the Generic Terms and Abbreviations, Section 1.1, Section 2.1, Section 3.1.1, Section 3.2.4, Section 3.3.2, Section 3.4.1, Section 3.4.2, Section 3.4.3, Section , Section , Section , Section 6.2.1, Section 6.2.2, Section 7.4, Appendix 7 SH(NA) L Correction SAFETY PRECAUTIONS, CONTENTS, About the Generic Terms and Abbreviations, Section 2.2, Section 2.3, Section 4.1, Section SH(NA) M Correction SAFETY PRECAUTIONS, Compliance with the EMC and Low Voltage Directives, About the Generic Terms and Abbreviations, Section 2.1, Section 2.3, Section 3.4.1, Section , Section 4.1, Section 5.2.1, Section 5.3, Section 7.1, Appendix 1 to 3 SH(NA) N Addition CONDITIONS OF USE FOR THE PRODUCT Correction SAFETY PRECAUTIONS, COMPLIANCE WITH EMC AND LOW VOLTAGE, Section 6.1, 6.1.2, WARRANTY A - 6 A - 6

9 Print Date Manual Number Revision May, 2015 May, 2016 SH(NA) O Addition SAFETY PRECAUTIONS, COMPLIANCE WITH EMC AND LOW VOLTAGE DIRECTIVES, ABOUT THE GENERIC TERMS AND ABBREVIATIONS, PACKING LIST, Chapter 1, Chapter 2, Section 2.1, Section 2.4, Section 3.1.1, Section 3.1.2, Section 3.2, Section 3.2.1, Section 3.2.3, Section 3.2.4, Section 3.3.1, Section 3.3.2, Section 3.4.1, Section 3.4.2, Section 3.4.4, Section 3.4.6, Section 3.4.7, Section 3.4.8, Section , Section , Section , Section 4.1, Section 4.3, Section 4.5, Section 4.6, Section 5.2.1, Section 5.2.2, Section 5.4, Section 5.5, Section 5.6.1, Section 5.6.2, Section 5.6.3, Section 6.1, Section 6.1.1, Section 6.1.2, Section 6.2, Section 6.2.1, Section 6.2.2, Chapter 7, Section 7.5, Section 8.1, Section 8.2.7, Section 8.2.8, Section 8.2.9, Appendix 1.2, Appendix 2.2, Appendix 2.3, Appendix 2.4, Appendix 4 Section number changed Appendix 4 Appendix 1, Appendix 4.1 Appendix 1.1, Appendix 4.2 Appendix 1.2, Appendix 5 Appendix 2, Appendix 5.1 Appendix 5.2, Appendix 5.3 Appendix 2.3, Appendix 5.4 Appendix 2.4, Appendix 6 Appendix 3, Appendix 7 Appendix 4 SH(NA) P Addition Section 2.3, Section 4.3, Section 4.4.2, Section 3.2.1, Appendix 4 Japanese Manual Version SH Q This manual confers no industrial property rights or any rights of any other kind, nor does it confer any patent licenses. Mitsubishi Electric Corporation cannot be held responsible for any problems involving industrial property rights which may occur as a result of using the contents noted in this manual MITSUBISHI ELECTRIC CORPORATION A - 7 A - 7

10 INTRODUCTION Thank you for purchasing the series programmable controller. Before using the equipment, please read this manual carefully to develop full familiarity with the functions and performance of the Q series programmable controller you have purchased, so as to ensure correct use. Please forward a copy of this manual to the end user. CONTENTS SAFETY PRECAUTIONS... A- 1 CONDITIONS OF USE FOR THE PRODUCT... A- 4 REVISIONS... A- 5 INTRODUCTION... A- 8 CONTENTS... A- 8 COMPLIANCE WITH EMC AND LOW VOLTAGE DIRECTIVES... A- 12 ABOUT THE GENERIC TERMS AND ABBREVIATIONS... A- 13 PACKING LIST... A OVERVIEW 1-1 to Features Added Functions SYSTEM CONFIGURATION 2-1 to Applicable Systems About Use of the Q64TD/Q64TDV-GH in the Redundant System How to Check the Function Version, Product Information, and Software Version Precautions for System Configuration SPECIFICATIONS 3-1 to Performance Specifications Specifications of Q64TD Specifications of Q64TDV-GH Function List Micro voltage input/output conversion characteristic (Q64TDV-GH only) Temperature conversion system (Q64TD) Temperature/micro voltage conversion system (Q64TDV-GH) Conversion setting for disconnection detection function I/O Signals Transferred to/from CPU I/O signal list I/O signal details Buffer Memory Buffer memory assignment (Q64TD) Buffer memory assignment (Q64TDV-GH) Conversion enable/disable setting (Un\G0) CH time/count averaging setting (Un\G1 to 4) Averaging processing specification (Un\G9) Conversion completion flag (Un\G10) CH measured temperature value/micro voltage value (Un\G11 to 14) Error code (Un\G19) A - 8 A - 8

11 3.4.9 Setting range (Q64TD) (Un\G20) Setting range 1 (Q64TDV-GH) (Un\G20) Setting range 2 (Q64TDV-GH) (Un\G21) Warning output enable/disable setting (Un\G47) Warning output flag (Un\G48) Disconnection detection flag (Un\G49) CH scaling value (Un\G50 to 53) CH scaling range upper/lower limit values (Un\G62 to 69) CH scaling width upper/lower limit values (Un\G78 to 85) CH warning output upper/lower limit values (Un\G86 to 101) CH offset/gain temperature value (Q64TD)/CH offset/gain setting value (Q64TDV-GH) (Un\G118 to 125) Conversion setting for disconnection detection (Un\G148) Conversion setting value for disconnection detection (Un\G150 to 153) Mode switching setting (Un\G158 to 159) Factory default offset/gain value/user range settings offset/gain value/user range settings thermal EMF offset/gain value (Un\G160 to 191) SETUP AND PROCEDURES BEFORE OPERATION 4-1 to Handling Precautions Setup and Procedures before Operation Part Names and Settings Wiring Wiring instructions External wiring Switch Setting for Intelligent Function Module Offset/Gain Setting Cold Junction Temperature Compensation Yes/No Setting UTILITY PACKAGE (GX Configurator-TI) 5-1 to Utility Package Functions Installing and Uninstalling the Utility Package Handling precautions Operating environment Utility Package Operation Common utility package operations Operation overview Starting the Intelligent function module utility Initial Setting Auto Refresh Settings Monitoring/Test Monitor/test screen Offset/gain setting operation (Function version C or later) Offset/gain setting operation (Function version B) OMC (Online Module Change) refresh data A - 9 A - 9

12 6 PROGRAMMING 6-1 to Programs Used in Normal System Configuration Program example when utility package is used Program example when utility package is not used Programs Used on Remote I/O Network Program example when utility package is used Program example when utility package is not used ONLINE MODULE CHANGE 7-1 to Online Module Change Conditions Online Module Change Operations Online Module Change Procedure When factory default is used and initial setting was made with GX Configurator-TI When factory default is used and initial setting was made with sequence program When user range setting is used and initial setting was made with GX Configurator-TI (other system is available) When user range setting is used and initial setting was made with GX Configurator-TI (other system is unavailable) When user range setting is used and initial setting was made with sequence program (other system is available) When user range setting is used and initial setting was made with sequence program (other system is unavailable) Range Reference Table Precautions for Online Module Change TROUBLESHOOTING 8-1 to Error Code List Troubleshooting RUN LED is extinguished RUN LED flickers ERROR LED flickers ERROR LED is lit Disconnection detection flag (XC) has turned on Measured temperature value/micro voltage conversion value cannot be read Measured temperature value is abnormal Micro voltage conversion value is abnormal Checking the Q64TD/Q64TDV-GH status using GX Developer system monitor APPENDICES App.- 1 to App.-14 Appendix 1 Upgrading of Q64TD/Q64TDV-GH Functions...App.- 1 Appendix 1.1 Comparison between Q64TD and Q64TDV-GH Functions...App.- 1 Appendix 1.2 When the Q64TD/Q64TDV-GH has Product Information which First 5 Digits are or Earlier...App.- 2 A - 10 A - 10

13 Appendix 2 Dedicated Instruction...App.- 3 Appendix 2.1 Dedicated Instruction List and Available Device...App.- 3 Appendix 2.2 G(P).OFFGAN...App.- 4 Appendix 2.3 G(P).OGLOAD...App.- 6 Appendix 2.4 G(P).OGSTOR...App.- 9 Appendix 3 Differences between Q64TD and Q64TDV-GH... App.-13 Appendix 4 External Dimension Diagram... App.-14 INDEX Index- 1 to Index- 2 A - 11 A - 11

14 COMPLIANCE WITH EMC AND LOW VOLTAGE DIRECTIVES (1) Method of ensuring compliance To ensure that Mitsubishi programmable controllers maintain EMC and Low Voltage Directives when incorporated into other machinery or equipment, certain measures may be necessary. Please refer to one of the following manuals. QCPU User's Manual (Hardware Design, Maintenance and Inspection) Safety Guidelines (This manual is included with the CPU module or base unit.) The CE mark on the side of the programmable controller indicates compliance with EMC and Low Voltage Directives. (2) Additional measures No additional measures are necessary for the compliance of this product with EMC and Low Voltage Directives. A - 12 A - 12

15 ABOUT THE GENERIC TERMS AND ABBREVIATIONS Unless otherwise specified, this manual uses the following generic terms and abbreviations. Generic term/abbreviation Q64TD Q64TDV-GH Personal computer GX Developer GX Works2 GX Configurator-TI QCPU (Q mode) Process CPU Redundant CPU Personal computer Windows Vista Windows XP Windows 7 Description Abbreviation for the Q64TD thermocouple input module Abbreviation for the Q64TDV-GH channel isolated thermocouple/micro voltage input module IBM PC/AT or compatible computer with DOS/V. Product name of the software package for the MELSEC programmable controllers Abbreviation for thermocouple input module setting/monitor tool, GX Configurator-TI (SW1D5C-QTIU-E) Generic term for the Q00JCPU, Q00UJCPU, Q00CPU, Q00UCPU, Q01CPU, Q01UCPU, Q02CPU, Q02HCPU, Q02PHCPU, Q02UCPU, Q03UDCPU, Q03UDVCPU, Q03UDECPU, Q04UDHCPU, Q04UDVCPU, Q04UDPVCPU, Q04UDEHCPU, Q06HCPU, Q06PHCPU, Q06UDHCPU, Q06UDVCPU, Q06UDPVCPU, Q06UDEHCPU, Q10UDHCPU, Q10UDEHCPU, Q12HCPU, Q12PHCPU, Q12PRHCPU, Q13UDHCPU, Q13UDVCPU, Q13UDPVCPU, Q13UDEHCPU, Q20UDHCPU, Q20UDEHCPU, Q25HCPU, Q25PHCPU, Q25PRHCPU, Q26UDHCPU, Q26UDVCPU, Q26UDPVCPU, Q26UDEHCPU, Q50UDEHCPU, Q100UDEHCPU Generic term for the Q02PHCPU, Q06PHCPU, Q12PHCPU, and Q25PHCPU Generic term for the Q12PRHCPU and Q25PRHCPU IBM PC/AT or compatible computer with DOS/V. Generic term for the following: Microsoft Windows Vista Home Basic Operating System, Microsoft Windows Vista Home Premium Operating System, Microsoft Windows Vista Business Operating System, Microsoft Windows Vista Ultimate Operating System, Microsoft Windows Vista Enterprise Operating System Generic term for the following: Microsoft Windows XP Professional Operating System, Microsoft Windows XP Home Edition Operating System Generic term for the following: Microsoft Windows 7 Starter Operating System, Microsoft Windows 7 Home Premium Operating System, Microsoft Windows 7 Professional Operating System, Microsoft Windows 7 Ultimate Operating System, Microsoft Windows 7 Enterprise Operating System Note that the 32-bit version is designated as "32-bit Windows 7", and the 64-bit version is designated as "64-bit Windows 7". PACKING LIST The product package contains the following. Model Product Quantity Q64TD Q64TD thermocouple input module 1 Q64TDV-GH Q64TDV-GH channel isolated thermocouple/micro voltage input module 1 SW1D5C-QTIU-E GX Configurator-TI Version 1 (Single license product) (CD-ROM) 1 SW1D5C-QTIU-EA GX Configurator-TI Version 1 (Volume license product) (CD-ROM) 1 A - 13 A - 13

16 MEMO A - 14 A - 14

17 1 OVERVIEW 1 OVERVIEW This user's manual provides the specifications, handling instructions, programming procedures and others of the Q64TD thermocouple input module (abbreviated to the Q64TD) and Q64TDV-GH channel isolated thermocouple/micro voltage input module (abbreviated to the Q64TDV-GH) used with the series CPU module (hereafter abbreviated to the CPU). The Q64TD is a module designed to convert thermocouple input values from outside the programmable controller into 16-bit signed binary measured temperature values and 16-bit signed binary scaling values (ratios). 1 1: Refer to Section for details of the scaling values. In addition to the temperature measurement functions of the Q64TD, the Q64TDV-GH has a function that converts a micro voltage signal into a 16-bit, signed binary data. 1: Refer to Section for details of the scaling value

18 1 OVERVIEW 1.1 Features 1 (1) Channels isolated Both the Q64TD and Q64TDV-GH are channel isolated modules. (2) 4 channels of temperatures measured by one module One Q64TD module can measure temperatures of four channels. It can also convert the detected temperature values into scaling values (ratios (%)). (3) Micro voltages of four channels can be converted on one module (Q64TDV-GH only) One Q64TDV-GH module can make micro voltage conversion of four channels. It can also convert the detected micro voltage conversion values into scaling values (ratio values (%)). (4) Setting of conversion enable/disable You can make a conversion enable/disable setting for each channel. Disabling unused channels for conversion reduces sampling time. It also prevents unnecessary disconnection detection on unused channels. (5) Thermocouples conforming to JIS Standards usable You can use eight different thermocouples (K, E, J, T, B, R, S, N) conforming to the JIS Standards. You can also select the thermocouple type for each channel using GX Developer. (6) Disconnection detection The disconnection of a thermocouple or compensation conductor can be detected on each channel. (7) Selection of sampling processing/time averaging processing/count averaging processing As a conversion processing method, you can choose sampling processing, time averaging processing or count averaging processing on each channel. (8) Pt100 temperature-measuring resistor for cold junction temperature compensation The Pt100 temperature-measuring resistor connected makes cold junction temperature compensation automatically. (9) Setting of Pt100 cold junction temperature compensation enable/disable Disabling cold junction temperature compensation with Pt100 temperaturemeasuring resistor enables cold junction temperature compensation to be made outside the module. By providing a precision ice bath externally, the thermoelectromotive force generated at the tip of the thermocouple can be led to the Q64TD/Q64TDV-GH without any change, improving the cold junction temperature compensation accuracy. (10) Error compensation by offset/gain value setting Error compensation can be made by setting offset and gain values on each channel. As the offset and gain values, you can make selection from user range setting and factory default setting

19 1 OVERVIEW 1.2 Added Functions (11) Warning output If the temperature detected is outside the preset measurement range, a warning can be output for each channel. (12) Online module change A module can be replaced without stopping the system. Furthermore, original specifications can be transferred to the replacement module by using a sequence program and by executing the following. (Note that this is for modules of the same model only.) Inheritance of offset/gain settings to the new Q64TD/Q64TDV-GH after online module change Transfer of offset/gain settings to the other Q64TD/Q64TDV-GH mounted on the other slot (13) Easy setting with GX Confogurator-TI The use of GX Configurator-TI, which is sold separately, reduces sequence programming since Q64TD/Q64TDV-GH settings can be configured on the screen. In addition, setting status and operating status of modules can be checked easily. The following is a function added for the Q64TD/Q64TDV-GH. Item Applicable module Function overview Online module change Mode switching that does not require CPU to be reset Conversion setting for disconnection detection Function version C or later Function version C or later First 5 digits of product information are or later You can change the module without stopping the system. The CPU of function version C or later is required. Using the mode switching setting (buffer memory addresses 158, 159: Un\G158, Un\G159) and operating condition setting request (Y9), the module is switched between the normal mode and offset/gain setting mode without the CPU being reset. Using the dedicated instruction (G(P).OFFGAN), the module is switched between the normal mode and offset/gain setting mode without the CPU being reset. Using GX Configurator-TI, the module is switched between the normal mode and offset/gain setting mode without the CPU being reset. For values to be stored in the CH measured temperature value/micro voltage conversion value (buffer memory addresses 11 to 14: Un\G11 to 14) in the case of disconnection detection, any of "Value immediately before disconnection", "Up scale (maximum value of measured temperature range + 5% of measured temperature range)", "Down scale (minimum value of measured temperature range 5% of measured temperature range)" or "Given value" can be selected. Reference section Chapter 7 Section Appendix 2.2 Section Section POINT (1) For function comparison by function versions, refer to Appendix 1.1. (2) For Q64TD/Q64TDV-GH with product information (first five digits) of or earlier or or later, refer to Appendix 1.2. (3) For how to check the function version and product information, refer to Section

20 2 SYSTEM CONFIGURATION 2 SYSTEM CONFIGURATION 2.1 Applicable Systems This chapter explains the system configuration of the Q64TD/Q64TDV-GH. 2 This section describes the applicable systems. (1) Applicable modules and base units, and No. of modules (a) When mounted with a CPU module For the applicable CPU modules and base units, and the number of mountable modules, refer to the user s manual for the CPU module used. When mounting the Q64TD/Q64TDV-GH with a CPU module, observe the following precautions. When mounting the Q64TD/Q64TDV-GH with a Redundant CPU, use the Q64TD/Q64TDV-GH with a serial No. (first five digits) of or later. Depending on the combination with other modules or the number of mounted modules, power supply capacity may be insufficient. Consider the power supply capacity before mounting modules, and if the power supply capacity is insufficient, change the combination of the modules. Mount the modules within the number of I/O points of a CPU module. The modules can be mounted on any slots within the usable number of slots. REMARK For use of a C Controller module, refer to the C Controller Module User s Manual. (b) Mounting to a MELSECNET/H remote I/O station For the applicable MELSECNET/H remote I/O station and base units, and the number of mountable modules, refer to the Q Corresponding MELSECNET/H Network System Reference Manual (Remote I/O network). (2) Support of the multiple CPU system When using the Q64TD/Q64TDV-GH in a multiple CPU system, refer to the following manual first. QCPU User's Manual (Multiple CPU System) (3) Compatibility with online module change To make an online module change, use the Q64TD/Q64TDV-GH of function version C or later. Refer to Chapter

21 2 SYSTEM CONFIGURATION (4) Q64TD-compatible software packages Relation between the system containing the Q64TD and software package is shown in the following table. GX Developer or GX Works2 is necessary when using the Q64TD. Q00J/Q00/Q01CPU Single CPU system Version 7 or later Multiple CPU system Version 8 or later Q02/Q02H/Q06H/ Single CPU system Version 4 or later Q12H/Q25HCPU Multiple CPU system Version 6 or later Q02PH/Q06PHCPU Single CPU system Version 8.68W or Multiple CPU system later Q12PH/Q25PHCPU Single CPU system Multiple CPU system Version 7.10L or later Q12PRH/Q25PRHCPU Redundant system Version 8.45X or later Q00UJ/Q00U/Q01UCPU Q02U/Q03UD/ Q04UDH/Q06UDHCPU Q10UDH/Q20UDHCPU Q13UDH/Q26UDHCPU Q03UDE/Q04UDEH/ Q06UDEH/Q13UDEH/ Q26UDEHCPU Q10UDEH/Q20UDEHCPU CPU module other than the above Single CPU system Multiple CPU system Version 8.76E or later Single CPU system Multiple CPU system Version 8.48A or later Single CPU system Multiple CPU system Version 8.76E or later Single CPU system Multiple CPU system Version 8.62Q or later Single CPU system Version 8.68W or Multiple CPU system later Single CPU system Multiple CPU system Version 8.76E or later Single CPU system Multiple CPU system Cannot be used Software Version GX Developer GX Configurator- 1 2 TI GX Works2 Version 1.10L or later Version 1.00A or later Version 1.13P or later Version 1.14Q or later Refer to the GX Works2 Version1 Operating Manual (Common). Version 1.24AA or later Cannot be used If installed in a MELSECNET/H remote I/O station Version 6 or later Version 1.00A or later 1 The product of Version 1.14Q or earlier is not compatible with "normal mode - offset/gain setting mode switching" and "OMC refresh data". Use the product of Version 1.15R or later. 2 The product of Version 1.20W or earlier is not compatible with "Conversion setting for disconnection detection function". Use the product of Version 1.21X or later

22 2 SYSTEM CONFIGURATION Q00J/Q00/Q01CPU Q02/Q02H/Q06H/ Q12H/Q25HCPU Q02PH/Q06PHCPU Q12PH/Q25PHCPU (5) Q64TDV-GH-compatible software packages Relation between the system containing the Q64TDV-GH and software package is shown in the following table. GX Developer or GX Works2 is necessary when using the Q64TDV-GH. Single CPU system Multiple CPU system Single CPU system Multiple CPU system Single CPU system Multiple CPU system Single CPU system Multiple CPU system GX Developer Version 7 or later Version 8 or later Version 4 or later Version 6 or later Version 8.68W or later Version 7.10L or later Q12PRH/Q25PRHCPU Redundant system Version 8.45X or later Q00UJ/Q00U/Q01UCPU Q02U/Q03UD/ Q04UDH/Q06UDHCPU Q10UDH/Q20UDHCPU Q13UDH/Q26UDHCPU Q03UDE/Q04UDEH/ Q06UDEH/Q13UDEH/ Q26UDEHCPU Q10UDEH/Q20UDEHCPU CPU module other than the above Single CPU system Multiple CPU system Single CPU system Multiple CPU system Single CPU system Multiple CPU system Single CPU system Multiple CPU system Single CPU system Multiple CPU system Single CPU system Multiple CPU system Single CPU system Multiple CPU system Version 8.76E or later Version 8.48A or later Version 8.76E or later Version 8.62Q or later Version 8.68W or later Version 8.76E or later Cannot be used Software Version GX Configurator- 1 2 GX Works2 TI Version 1.13P or later Version 1.14Q or later Version 1.24AA or later Cannot be used If installed in a MELSECNET/H remote I/O station Version 6 or later Version 1.13P or later Refer to the GX Works2 Version1 Operating Manual (Common). 1 The product of Version 1.14Q or earlier is not compatible with "OMC refresh data". Use the product of Version 1.15R or later. 2 The product of Version 1.20W or earlier is not compatible with "Conversion setting for disconnection detection function". Use the product of Version 1.21X or later. POINT (1) The Q64TD of function version A is not available. The Q64TDV-GH of function version B is not available. The products of function version C include the functions of the products of function version A and B. (2) Depending on the version of GX Configurator-TI, applicable system, CPU module and functions of the Q64TD/Q64TDV-GH vary. (3) When using GX Works2, refer to the following. GX Works2 Version1 Operating Manual (Common) GX Works2 Version1 Operating Manual (Intelligent Function Module)

23 2 SYSTEM CONFIGURATION 2.2 About Use of the Q64TD/Q64TDV-GH in the Redundant System This section describes the case when the Q64TD/Q64TDV-GH is used in the redundant system. (1) Dedicated instruction The dedicated instruction cannot be used. (2) GX Configurator-TI When using GX Developer to access the Redundant CPU through the intelligent function module on the extension base unit, GX Configurator-TI cannot be used. Connect a personal computer to the Redundant CPU with a communication path indicated below. 1 2 Main base unit Extension base unit (GX Configurator-TI cannot be used.) 1 2 Direct connection to the CPU Connection through an intelligent function module on the main base unit (Through Ethernet module, MELSECNET/H module, or CC-Link module)

24 2 SYSTEM CONFIGURATION 2.3 How to Check the Function Version, Product Information, and Software Version This section describes how to check the function version and product information of the Q64TD/Q64TDV-GH and the GX Configuration-TI software version. (1) Checking the function version and serial number The function version and serial number of the Q64TD/Q64TDV-GH can be checked on the rating plate, front of the module, or system monitor of GX Developer. (a) Checking on the rating place The rating plate is on the side of the Q64TD/Q64TDV-GH. (b) Checking on the front of the module The function version and serial number on the rating plate are also shown on the front (bottom part) of the module

25 2 SYSTEM CONFIGURATION (c) Checking on the system monitor (Product Information List) To display the system monitor, select [Diagnostics] [System monitor] Product Inf. List of GX Developer. 1). Displaying product number For the Q64TD/Q64TDV-GH, "-" is displayed since the product number display is not supported. POINT The serial No. on the rating plate and front of the module may be different from the serial No. displayed on the product information list of GX Developer. The serial No. on the rating plate and front of the module indicates the management information of the product. The serial No. displayed on the product information list of GX Developer indicates the function information of the product. The function information of the product is updated when a new function is added

26 2 SYSTEM CONFIGURATION (2) Checking the software version of GX Configurator- TI The software version of GX Configurator-TI can be checked by selecting [Help] [Product information] of GX Developer. Software version (In the case of GX Developer Version 7)

27 2 SYSTEM CONFIGURATION 2.4 Precautions for System Configuration The Q64TD/Q64TDV-GH measures a temperature on the basis of the temperature of a terminal block. Therefore, depending on a system configuration (especially for the case when two or more the Q64TD/Q64TDV-GH are mounted side by side, or when the Q64TD/Q64TDV-GH is mounted next to the power supply module or the CPU module), the temperature distribution of the terminal block becomes inhomogeneous because of the effect of heat emitted from each module, thus the measured temperature error may become large. In such case, use a terminal block converter module and a dedicated cable shown below to prevent the error caused by the heat emission. The following table lists the dedicated cable and the terminal block converter module. Product name Model Manufacturer Thermocouple input dedicated cable with Q terminal block FA-CBLQ64TD** (**: Cable length) Mitsubishi Electric Terminal block converter module for Engineering Co., Ltd. FA-TB20TD thermocouple input For inquiries related to the products or your order, please consult your local Mitsubishi Electric sales office or representative

28 2 SYSTEM CONFIGURATION MEMO

29 3 SPECIFICATIONS 3 SPECIFICATIONS 3.1 Performance Specifications Specifications of Q64TD The following are the performance specifications of the Q64TD/Q64TDV-GH. (1) Performance specification list Item Number of channels Measured temperature Output value Scaling value Standard with which thermocouple conforms Usable thermocouples, measured temperature range accuracies, and effect from wiring resistance of 1 Cold junction temperature compensation accuracy Specifications 4 channels 16-bit, signed binary (-2700 to 18200: Value to the first decimal place 10 times) 16-bit, signed binary JIS C Refer to Section (2) Accuracy As per calculation expression marked 1 Resolution B,R,S,N : 0.3 K,E,J,T : 0.1 Conversion speed 40ms/channel 2 Number of analog input points channels + Pt100 connection channel/module 3 Isolation Specific isolated area Between thermocouple input and programmable controller power supply Between thermocouple input channels Between cold junction temperature compensation channel and programmable controller power supply Isolation method Transformer isolation Transformer isolation No insulation Dielectric withstand voltage 1780VrmsAC /3 cycles (Altitude 2000m) Isolation resistance 100M or more using 500VDC isolation resistance tester 10M or more using 500VDC isolation resistance tester Wire break detection Yes (Each channel independent) 3 E 2 PROM write count Number of occupied I/O points Connection terminals Max. 100 thousand times 16 points (I/O assignment: Intelligent 16 points) 18-point terminal block Applicable wire size 0.3 to 0.75mm 2 Applicable crimping terminals R1.25-3(Sleeved crimping terminals are unusable) Internal current consumption (5VDC) 0.50A Weight kg Outline dimensions 98(H) 27.4(W) 112(D)mm 1: Calculate the accuracy in the following method. (Accuracy) = (conversion accuracy) + (temperature characteristic) (operating ambient temperature variation) + (cold junction temperature compensation accuracy) An operating ambient temperature variation indicates a deviation of the operating ambient temperature from the 25 5 range.example: When the thermocouple used is B (Refer to Section (2)), the operating ambient temperature is 35, and the measured temperature is 1000, the accuracy is: ( 2.5 ) + ( 0.4 ) (35-30 ) + ( 1 ) = 5.5

30 3 SPECIFICATIONS 2: The conversion speed is a period from when a temperature is input and converted into a corresponding digital value until the value is stored into the buffer memory. When two or more channels are used, the conversion speed is "40ms number of conversion enabled channels". 3: For output in the case of disconnection detection, select any of "Value immediately before disconnection", "UP scale (maximum value of measured temperature range + 5% of measured temperature range)", "Down scale (minimum value of measured temperature range 5% of measured temperature range)" or "Given value". (see Section )

31 3 SPECIFICATIONS Usable Thermocouple Type B R S K E J T Measured Temperature 1 Range (2) Usable thermocouples, measured temperature range accuracies, and effect from wiring resistance of 1 This section explains the usable thermocouples, measured temperature range accuracies, and effect from wiring resistance of 1. Conversion Accuracy (At operating ambient temperature 25 5 ) Temperature Characteristic (Per operating ambient temperature variation of 1 ) Max. Temperature Error at Ambient Temperature 55 Effect from wiring resistance of to to / 800 to / 1700 to to to / 300 to / 1600 to to to / 300 to / 1600 to to to to Larger value of 0.5 and 0.5% of measured temperature Larger value of 0.5 and 0.25% of measured temperature Larger value of 0.06 and 0.2% of measured temperature Larger value of 0.06 and 0.02% of measured temperature / / 1200 to to to to Larger value of 0.5 and 0.5% of measured temperature Larger value of 0.5 and 0.25% of measured temperature Larger value of 0.06 and 0.15% of measured temperature Larger value of 0.06 and 0.02% of measured temperature / / 900 to to to Larger value of 0.5 and 0.25% of measured temperature Larger value of 0.06 and 0.02% of measured temperature / 750 to to to to Larger value of 0.5 and 0.5% of measured temperature Larger value of 0.5 and 0.25% of measured temperature Larger value of 0.06 and 0.1% of measured temperature Larger value of 0.06 and 0.02% of measured temperature / / 350 to

32 3 SPECIFICATIONS Usable Thermocouple Type N Measured Temperature 1 Range Conversion Accuracy (At operating ambient temperature 25 5 ) Temperature Characteristic (Per operating ambient temperature variation of 1 ) Max. Temperature Error at Ambient Temperature 55 Effect from wiring resistance of to to 0 0 to Larger value of 0.5 and 0.5% of measured temperature Larger value of 0.5 and 0.25% of measured temperature Larger value of 0.06 and 0.2% of measured temperature Larger value of 0.06 and 0.02% of measured temperature / / 1250 to : If a value entered from the thermocouple is outside the measured temperature range given in the table, it is handled as the maximum/minimum value of the measured temperature range. 2: The accuracies only in the temperature ranges of Class 1 to 3 (shaded areas) in JIS C apply. 3: Temperature measurement can be made, but accuracy is not guaranteed. 4: Means temperature error per of wiring resistance of the thermocouple. Check the wiring resistance value and calculate the temperature error in the system. In case of a temperature error that exceeds the measurement range of the system, compensate the measured temperature value using the offset/gain setting. (Refer to Section 4.6.)

33 3 SPECIFICATIONS Specifications of Q64TDV-GH Item Number of channels Output Measured temperature value Micro voltage conversion value Scaling value Standard with which thermocouple conforms Usable thermocouples, measured temperature range accuracies, and effect from wiring resistance of 1 Cold junction temperature compensation accuracy (1) Performance specifications Specifications 4 channels 16-bit, signed binary (-2700 to 18200: Value to the first decimal place 10 times) 16-bit signed binary ( to 25000) 16-bit, signed binary JIS C Refer to Section (2) Thermocouple input accuracy As per calculation expression marked 1 Micro voltage input range -100mV to +100mV (input resistance 2M or more) Micro voltage input accuracy Refer to Section (3) Resolution Thermocouple input B:0.7 R,S:0.8 K,T:0.3 E:0.2 J:0.1 N:0.4 Micro voltage input Sampling period 20ms/channel 2 Conversion speed Sampling period 3 3 Number of analog input points Absolute maximum input V 4 channels + Pt100 connection channel/module 5V Isolation Specific isolated area Between thermocouple input/micro voltage input and programmable controller power supply Between thermocouple input/micro voltage input channels Between cold junction temperature compensation channel and programmable controller power supply Isolation method Transformer isolation Transformer isolation Dielectric withstand voltage 1780VrmsAC/3 cycles (Altitude 2000m) Isolation resistance 100M or more using 500VDC isolation resistance tester 10M or more using 500VDC isolation resistance tester No insulation Wire break detection Yes (Each channel independent) 4 E 2 PROM write count Number of occupied I/O points Connection terminals Max. 100 thousand times 16 points (I/O assignment: Intelligent 16 points) 18-point terminal block Applicable wire size 0.3 to 0.75mm 2 Applicable crimping terminals Internal current consumption (5VDC) Weight R1.25-3(Sleeved crimping terminals are unusable) 0.50A 0.25kg Outline dimensions 98(H) 27.4(W) 112(D)mm

34 3 SPECIFICATIONS 1: Calculate the accuracy in the following method. (Accuracy) = (conversion accuracy) + (temperature characteristic) (operating ambient temperature variation) + (cold junction temperature compensation accuracy) An operating ambient temperature variation indicates a deviation of the operating ambient temperature from the 25 5 range. Example: When the thermocouple used is B (Refer to Section (2)), the operating ambient temperature is 35, and the measured temperature is 1000, the accuracy is: ( 3.5 ) + ( 0.4 ) (35-30 ) + ( 1 ) = 6.5 2: A period until a thermocouple input value/micro voltage input value is converted into a measured temperature value/micro voltage conversion value. 3: A period until a thermocouple input value/micro voltage input value is converted into a measured temperature value/micro voltage conversion value and the resultant value is stored into the buffer memory. The conversion speed is a delay time that occurs during sampling processing. It is independent of averaging processing. Example: When two channels are enabled for conversion (Conversion speed) = (sampling period) 3 = (20ms 2 channels) 3 = 120ms Input 1) Input 2) Conversion processing CH1 CH2 CH1 CH2 CH1 CH2 CH1 CH2 CH1 CH2 Buffer memory Conversion speed Conversion speed Input 1) Input 2) 4: For output in the case of disconnection detection, select any of "Value immediately before disconnection", "Up scale (maximum value of measured temperature range + 5% of measured temperature range)", "Down scale (minimum value of measured temperature range 5% of measured temperature range)" or "Given value". (see Section )

35 3 SPECIFICATIONS Usable Thermocouple Type Measured Temperature Range 1 (2) Usable thermocouples, measured temperature range accuracies, and effect from wiring resistance of 1 This section explains the usable thermocouples, measured temperature range accuracies, and effect from wiring resistance of 1. Conversion Accuracy (At operating ambient temperature 25 5 ) Temperature Characteristic (Per operating ambient temperature variation of 1 ) Max. Temperature Error at Ambient Temperature 55 Effect from wiring resistance of to B R S 600 to / to / 1700 to to to / to / 1600 to to to / to / 1600 to to K E J T -200 to / to / 0 to / 1200 to to to / to / 900 to to to / to / 750 to to to / to / 350 to N -270 to to / 0 to / 0 to / 1250 to : If a value entered from the thermocouple is outside the measured temperature range given in the table, it is handled as the maximum/minimum value of the measured temperature range. 2: The accuracies only in the temperature ranges of Class 1 to 3 (shaded areas) in JIS C apply. 3: Temperature measurement can be made, but accuracy is not guaranteed. 4: Means temperature error per Ω of wiring resistance of the thermocouple. Check the wiring resistance value and calculate the temperature error in the system. In case of a temperature error that exceeds the measurement range of the system, compensate the measured temperature value using the offset/gain setting. (Refer to Section 4.6.)

36 3 SPECIFICATIONS Input Type (3) Micro voltage input range, accuracies, and effect from wiring resistance of 1 The following table lists a micro voltage input range, accuracies, and the effect from wiring resistance of 1. Measurable Voltage Range (At 25 5 operating ambient temperature) Conversion Accuracy (At 0 to 55 operating ambient temperature) Effect from wiring resistance of 1 1 Micro voltage input -100 to 100mV 0.2mV 0.8mV 0.064μV/ 1: Means error per of wiring resistance. Check the wiring resistance value and calculate the error in the system. In case of an error that exceeds the measurement range of the system, compensate the micro voltage conversion value using the offset/gain setting. (Refer to Section 4.6.)

37 3 SPECIFICATIONS 3.2 Function List The following table lists the Q64TD/Q64TDV-GH functions. Item Description Refer To Temperature conversion function Micro voltage conversion function (Q64TDV-GH only) Temperature conversion system (Q64TD) Temperature/micro voltage conversion system (Q64TDV-GH) Conversion enable/disable function Input type selection function Disconnection detection function Conversion setting for disconnection detection function Pt100 cold junction temperature compensation yes/no setting function Warning output function Scaling function Offset/gain setting function This function allows temperature data to be imported by connecting a thermocouple. Temperature data are 16-bit signed binary (-2700 to 18200) and stored into buffer memory. This function converts a -100mV to +100mV micro voltage into a 16-bit, signed binary ( to 25000) and stores it into the buffer memory. (1) Sampling processing A temperature input value is converted into a temperature one by one on each channel and a measured temperature value is output after every conversion. (2) Averaging processing Temperature conversion is averaged by count or time on each channel and an averaged value is stored. (1) Sampling processing A temperature/micro voltage input value is converted one by one on each channel and a measured temperature value is output after every conversion. (2) Averaging processing Temperature conversion is averaged by count or time on each channel and an averaged value/micro voltage conversion value is stored. This function specifies whether temperature/micro voltage conversion is enabled or disabled on each channel. Setting temperature/micro voltage conversion enable/disable reduces the processing time of unused channels. In addition, it prevents unnecessary disconnection detection of unused channels. Section Section Section Section Section This function sets the input type per channel. Section 4.5 This function detects the disconnection of the connected thermocouple/micro voltage signal cable on each channel. For values to be stored in the CH measured temperature value/micro voltage value (buffer memory addresses 11 to 14: Un\G11 to 14) in the case of disconnection detection, any of "Value immediately before disconnection", "Up scale (maximum value of measured temperature range + 5% of measured temperature range)", "Down scale (minimum value of measured temperature range 5% of measured temperature range)" or "Given value" can be selected. This function determines whether cold junction temperature compensation is made or not using the Pt100 attached to the terminals. Use this function to measure temperatures with higher accuracy than the cold junction temperature compensation accuracy ( 1 ) of the Pt100 that is attached to the Q64TD/Q64TDV-GH. The cold junction temperature compensation accuracy can be improved by disabling the cold junction temperature compensation of the Pt100 and providing a precision ice bath externally. This function outputs a warning when the measured temperature value/micro voltage conversion value is equal to or more than the warning output upper limit value or is equal to or less than the warning output lower limit value. This function can convert a measured temperature value/micro voltage conversion value into a preset range ratio (%) and import it into buffer memory. This function compensates for an error of a measured temperature value or changes the conversion characteristic of a micro voltage conversion value. Section Section Section 4.7 Section Section Section Section Section Section Section 4.6 Online module change A module change is made without the system being stopped. Chapter

38 3 SPECIFICATIONS Micro voltage input/output conversion characteristic (Q64TDV-GH only) A micro voltage input/output conversion characteristic indicates the slope of a straight line that connects an offset value and gain value when an external micro voltage signal is converted into a digital value. Offset value A micro voltage input value whose digital output value will be Gain value A micro voltage input value whose digital output value will be The following indicates the micro voltage input/output conversion characteristic as set at the factory (offset value: -100mV, gain value: 100mV) Digital output value mV 0mV 100mV Micro voltage input value POINT (1) Use the module within the micro voltage input range and digital output range. Outside those ranges, the maximum resolution and accuracy may not fall within the ranges of the performance specifications. (Avoid using the dotted line areas in the chart.) (2) Do not input voltage of 5V or higher, or -5V or lower. Doing so may damage the elements

39 3 SPECIFICATIONS Temperature conversion system (Q64TD) There are two temperature conversion systems, sampling processing and averaging processing. (1) Sampling processing A temperature input value is converted into a measured temperature value successively and the digital output value is stored into the buffer memory. Sampling processing time varies with the number of used channels (number of channels set to enable temperature conversion). (Processing time) = (number of used channels) (40ms) [Example] Sampling time is 120ms when three channels, channels 1, 2 and 4, are enabled for conversion. 3 channels 40ms = 120ms (2) Averaging processing The temperatures of the channels specified for averaging processing are converted by the preset count or for the preset period of time, the sum of the resultant values except the maximum and minimum values is averaged, and the result is stored into the buffer memory. Averaging processing requires at least 2 times of conversion processing excluding the maximum and the minimum values. (a) Time averaging processing The processing count within the preset time varies with the number of used channels (number of channels set to enable temperature conversion). (Processing count) = (preset time) (number of used channels) (40ms) Setting range of preset time is 160 to 5000ms. When setting a value out of the setting range, an error (error code 20 ) occurs. [Example] The sampling count is 4.75 when four channels, channels 1, 2, 3 and 4, are enabled for conversion and the preset time is 760ms. 760ms (4 channels 40ms) = 4.75 Since the fractional portion of an indivisible value is dropped, the sampling count is 4 times. (b) Count averaging processing The time taken to store a count-averaged value into buffer memory varies with the number of used channels (number of channels set to enable temperature conversion). (Processing time) = (preset count) (number of used channels) (40ms) Setting range of preset count is 4 to times. When setting a value out of the setting range, an error (error code 30 ) occurs. [Example] An average value is output ever 320ms when two channels, channels 3 and 4, are enabled for conversion and the preset count is 4. 4 times (2 channels 40ms) = 320ms

40 3 SPECIFICATIONS Temperature/micro voltage conversion system (Q64TDV-GH) Temperature/micro voltage conversion can either be made by sampling processing or averaging processing. (1) Sampling processing A temperature/micro voltage input value is converted successively and a digital output value is stored into the buffer memory. The conversion speed changes depending on the number of channels used (number of channels set for conversion enable). (Conversion speed) = (sampling period) 3 = {(number of used channels) (20ms)} 3 [Example] When 2 channels are enabled for conversion (Conversion speed) = (sampling period) 3 = (20ms 2 channels) 3 = 120ms Input 1) Input 2) Conversion processing CH1 CH2 CH1 CH2 CH1 CH2 CH1 CH2 CH1 CH2 Buffer memory Conversion speed Conversion speed Input 1) Input 2) (2) Averaging processing The input value of the channel specified for averaging processing is converted by the preset number of times or for the preset period of time, the sum of the resultant values except the maximum and minimum values is averaged, and the average value is stored into the buffer memory. Averaging processing requires at least 2 times of conversion processing excluding the maximum and the minimum values. (a) Time averaging processing The number of processings performed within the preset time changes depending on the number of channels used (number of channels set for conversion enable). (preset time) (Processing count) = (number of used channels) (20ms) Setting range of preset time is 80 to 2500ms. When setting a value out of the setting range, an error (error code 20 ) occurs. [Example] When four channels, channels 1, 2, 3 and 4, are enabled for conversion and the preset time is 760ms, the sampling count is ms (4 channels (20ms) = 9.5 If the result cannot be divided, its fractional portion is rounded down and the sampling count is 9 times

41 3 SPECIFICATIONS (b) Count averaging processing The time when the count-based average value is stored into the buffer memory changes depending on the number of channels used (number of channels set for conversion enable). (Processing time) = (preset count) (number of used channels) (20ms) Setting range of preset count is 4 to 62500ms. When setting a value out of the setting range, an error (error code 30 ) occurs. [Example] When two channels, channels 3 and 4, are enabled for conversion and the preset count is 4, the average value is output per 160ms. 4 times (2 channels 20ms) = 160ms

42 3 SPECIFICATIONS Conversion setting for disconnection detection function (1) For values to be stored in the CH measured temperature value/micro voltage value (buffer memory addresses 11 to 14: Un\G11 to 14) in the case of disconnection detection, any of "Value immediately before disconnection", "Up scale (maximum value of measured temperature range + 5% of measured temperature range)", "Down scale (minimum value of measured temperature range 5% of measured temperature range)" or "Given value" can be selected. Setting is available for each channel. (2) This function can be utilized only for channels where temperature conversion is enabled. (3) When Up scale (1H) or Down scale (2H) is set, an Up scale value (maximum value of measured temperature range + 5% of measured temperature range) or a Down scale value (minimum value of measured temperature range 5% of measured temperature range) of the individual range is stored respectively. Input type Set value Measurement range Up scale Down scale Thermocouple K to Thermocouple E to Thermocouple J to Thermocouple T to Thermocouple B 4 0 to Thermocouple R 5-50 to Thermocouple S 6-50 to Thermocouple N to Micro voltage input to For the Up scale and Down scale of the micro voltage input, the maximum and minimum of the micro voltage conversion values are applied. (4) When Given value(3h) is selected, set a value for the CH conversion setting for disconnection detection (buffer memory addresses 150 to 153: Un\G150 to 153) in units of 0.1. The value set in the area is stored in CH measured temperature value/micro voltage value when disconnection is detected

43 3 SPECIFICATIONS 3.3 I/O Signals Transferred to/from CPU I/O signal list This section describes the I/O signal assignment and signal functions. The following are the I/O signals of the Q64TD/Q64TDV-GH. The I/O numbers (X/Y) given in this chapter and later assume that the first I/O number of the Q64TD is set to 0. Input Signal (Signal Direction: Programmable controller CPU Q64TD/Q64TDV-GH) Output Signal (Signal Direction: Programmable controller CPU Q64TD/Q64TDV-GH) Device No. Signal name Device No. Signal name X0 Module Ready Y0 Reserved X1 CH1 Offset/Gain Setting Status Signal Y1 CH1 Offset Setting Request X2 CH2 Offset/Gain Setting Status Signal Y2 CH1 Gain Setting Request X3 CH3 Offset/Gain Setting Status Signal Y3 CH2 Offset Setting Request X4 CH4 Offset/Gain Setting Status Signal Y4 CH2 Gain Setting Request X5 Y5 CH3 Offset Setting Request X6 1 Y6 CH3 Gain Setting Request Reserved X7 Y7 CH4 Offset Setting Request X8 Y8 CH4 Gain Setting Request X9 Operating Condition Setting Completion Signal Y9 Operating Condition Setting Request XA Offset/Gain Setting Mode Status Flag YA User Range Write Request XB Reserved 1 XC Disconnection Detection Flag YC Reserved XD Warning Output Signal YD XE Conversion Completion Flag YE XF Error Flag YF Error Clear Request YB 1 1 POINT The reserved signals marked 1 are used by the system and are unavailable for the user. Should they be turned on/off in a sequence program, we cannot guarantee the functions of the Q64TD/Q64TDV-GH. REMARK Between the Q64TD/Q64TDV-GH whose first 5 digits of product information are or earlier and those of or later, the Conversion Completion Flag (XE) operation is different. For details, refer to Appendix

44 3 SPECIFICATIONS I/O signal details The following are details of the Q64TD/Q64TDV-GH I/O signals. (1) Input signals Device No. Signal Name Description (1) If the module is in the normal mode at power-on or resetting of the programmable controller CPU, this signal turns on to start conversion processing as soon as it gets ready for conversion. (2) When this signal (X0) is off in the normal mode, conversion processing is not performed. In the X0 Module Ready X1 X2 CH Offset/Gain X3 Setting Status Signal X4 offset/gain setting mode, conversion processing is performed if this signal (X0) is off. (3) This signal (X0) turns off when: The module is in the offset/gain setting mode; The Q64TD/Q64TDV-GH is in a watchdog timer error 1; or The module can be changed during online module change (1) This signal is used as an interlock condition to turn on/off the CH Offset Setting Request (Y1, Y3, Y5, Y7)/CH Gain Setting Request (Y2, Y4, Y6, Y8) when offset/gain setting is made. (2) When the CH Offset Setting Request (Y1, Y3, Y5, Y7) or CH Gain Setting Request (Y2, Y4, Y6, Y8) is turned from ON to OFF in the offset/gain setting mode, this signal (X1 to 4) corresponding to the user range setting, conversion-enabled channel turns on. CH Offset/Gain Setting Status Signal (X1 to 4) CH Offset Setting Request (Y1, Y3, Y5, Y7) CH Offset/Gain Setting Status Signal (X1 to 4) CH Gain Setting Request (Y2, Y4, Y6, Y8) X9 Operating Condition Setting Completion Signal (1) This signal is used as an interlock condition to turn on/off the Operating Condition Setting Request (Y9) when the "Conversion enable/disable setting", "CH time/count averaging setting", "Averaging processing specification", "Warning output enable/disable setting", "Scaling range upper/lower limit value", "CH scaling width upper/lower limit value", "CH warning output upper/lower limit value", "Conversion setting for disconnection detection" or "CH Conversion setting value for disconnection detection" is changed. (2) Conversion processing is not performed when this signal (X9) is off. (3) This signal (X9) turns off when: The Module Ready (X0) is off in the normal mode; or The Operating Condition Setting Request (Y9) is on. Module Ready(X0) Operating Condition Setting Completion Signal (X9) Operating Condition Setting Request (Y9) Conversion enable/disable setting (buffer memory addresses 0: Un\G0) Conversion disable Conversion enable Conversion Completion Flag (XE) 1 Occurs if program operation is not completed within the intended time due to a hardware fault of the Q64TD/Q64TDV-GH. The RUN LED of the Q64TD/Q64TDV- GH goes off when a watchdog timer error occurs

45 3 SPECIFICATIONS Device No. Signal Name Description [In offset/gain setting mode] (1) This signal is used as an interlock condition to turn ON/OFF the User range write request (YA) when the value at completion of offset/gain setting adjustment is registered. (2) See Section 4.6 regarding the offset/gain settings. Module ready (X0) OFF XA Offset/Gain Setting Mode Status Flag Offset/gain setting mode status flag (XA) User range write request (YA) [In normal mode] (1) This signal is used as an interlock condition to turn ON/OFF the User range write request (YA) when the user range is restored. (2) Refer to Chapter 7 for the user range restoration. Module ready (X0) ON Offset/gain setting mode status flag (XA) XC XD Disconnection Detection Flag Warning Output Signal User range write request (YA) (1) The input circuit for the thermocouple of the conversion-enabled channel turns ON the Disconnection Detection Flag (XC) when any input signal line including the thermocouple/micro voltage signal line is disconnected. For the channel where disconnection is detected, a value based on the Conversion setting for disconnection detection (buffer memory address 148: Un\G148) is stored in the CH measured temperature value/micro voltage conversion value (buffer memory addresses 11 to 14: Un\G11 to 14). Conversion of the channels not disconnected is continued. (2) For temperature conversion values to be stored when the Disconnection Detection Flag (XC) turns ON, any of "Value immediately before disconnection", "Up scale (maximum value of measured temperature range + 5% of measured temperature range)", "Down scale (minimum value of measured temperature range 5% of measured temperature range)" or "Given value" can be selected. (Refer to Section ) (3) Removing the cause of disconnection and turning ON the Error Clear Request (YF) turns OFF the Disconnection Detection Flag (XC). (4) When the line connection is recovered, the temperature conversion value update is restarted independently of the Disconnection Detection Flag (XC) reset. (1) This signal turns on when the measured temperature value/micro voltage conversion value has fallen out of the temperature range set in the warning output upper/lower limit values (buffer memory addresses 86 to 101: Un\G86 to 101) on any of the channels enabled for conversion. (2) This signal turns off automatically as soon as the measured temperature value/micro voltage conversion value returned to within the ranges on all channels enabled for conversion

46 3 SPECIFICATIONS Device No. Signal Name Description (1) This signal (XE) turns on when the measured temperature value/micro voltage conversion value of all channels enabled for conversion are stored into buffer memory after power-on or hardware reset. (2) When averaging processing is performed, this signal also turns on when the measured temperature value/micro voltage conversion value are stored into buffer memory after completion of averaging processing. (3) This signal (XE) varies as described below depending on whether the Operation Condition Setting Completed Signal (X9) has turned on or off. When the Operation Condition Setting Completed Signal (X9) has turned on (stop conversion) 1) Temperature conversions of the enabled channels are started. 2) After the measured temperature value/micro voltage conversion value are stored into XE buffer memory, the Conversion completion flags (buffer memory address 10: Un\G10) are Conversion turned on. Completion Flag 3) This signal (XE) is turned on after the measured temperature value/micro voltage conversion value of all channels enabled for conversion are stored into buffer memory. When the Operation Condition Setting Completed Signal (X9) has turned off (conversion stop) 1) The Conversion completion flags (buffer memory address 10: Un\G10) of all channels are turned off. 2) This signal (XE) is turned off. Note that if conversion is stopped, the measured temperature value/micro voltage conversion value stored in buffer memory are held at the data immediately before the stop. (4) This signal (XE) does not turn on when all channels are disabled for conversion. (5) Read measured temperature value/micro voltage conversion value using this signal or the Conversion completion flag (buffer memory address 10: Un\G10) as an interlock. (1) This signal (XF) turns on when an error occurs. (2) To clear the error code, turn on the Error Clear Request (YF). Error code (buffer memory addresses 19:Un\G19) Error occurs XF Error Flag Error Flag (XF) Error clear request (YF)

47 3 SPECIFICATIONS (2) Output signals Device No. Signal name Description (1) This signal is made valid in the offset/gain setting mode. (2) This signal corrects the measured temperature value/micro voltage conversion Y1 Y3 CH Offset Y5 Setting Request Y7 Y2 Y4 CH Gain Y6 Setting Request Y8 Operating Y9 Condition Setting Request YA User Range Write Request YF Error Clear Request value to be an offset value when it is on. (3) When this signal turns on while the Gain Setting Request on the same channel is on or they turn on simultaneously, an error will occur and the operation in (2) not performed. (4) For the on/off timing, refer to the field of the CH Offset/Gain Setting Status Signal (X1 to 4). (1) This signal is made valid in the offset/gain setting mode. (2) This signal corrects the measured temperature value/micro voltage conversion value to be a gain set value when it is on. (3) When this signal turns on while the Offset Setting Request on the same channel is on or they turn on simultaneously, an error will occur and the operation in (2) not performed. (4) For the on/off timing, refer to the field of the CH Offset/Gain Setting Status Signal (X1 to 4). (1) This signal is turned on when the "Conversion enable/disable setting", "CH time/count averaging setting", "Averaging processing specification", "Warning output enable/disable setting", "CH scaling range upper/lower limit value", "CH scaling width upper/lower limit value", "CH warning output upper/lower limit value", "Mode switching setting", "Conversion setting for disconnection detection" or "CH Conversion setting value for disconnection detection" is made valid. (2) When this signal turns on, the Disconnection Detection Flag (XC) and Warning Output Signal (XD) turn off. (3) For the on/off timing, refer to the field of the Operation Condition Setting Completed Signal (X9). [In offset/gain setting mode] (1) This turns ON when the value for the adjusted offset/gain settings are registered in E 2 PROM. (2) Refer to the section of Offset/Gain Setting Mode Status Flag (XA) for ON/OFF timing. Refer to Section 4.6 for offset/gain settings. [In normal mode] (1) This signal turns ON when the user range is restored. (2) Refer to the section of Offset/Gain Setting Mode Status Flag (XA) for ON/OFF timing. Refer to Chapter 7 for user range restoration. (1) This signal is turned on when the Error Flag (XF) and Disconnection Detection Flag (XC) are cleared. However, the set value error of the intelligent function module switch setting cannot be cleared. Correct the set value. (2) For the on/off timing, refer to the field of the Error Flag (XF)

48 3 SPECIFICATIONS POINT When the User range write request (YA) is turned ON in the normal mode with conversion enabled, the Q64TD/Q64TDV-GH restores the user range. Offset/gain setting mode status flag (XA) User range write request (YA) User range restoration processing Conversion completion flag (Buffer memory address 10: Un\G10) During restoration Restoration completed Measured temperature value/micro voltage value (Buffer memory addresses 11 to 14: Un\G11 to 14) During user range restoration: Conversion stop, Conversion completion flag (buffer memory addresses 10: Un\G10) OFF, measured temperature value/micro voltage value held as previously. After user range restoration: Conversion resumed (when user range setting is used, conversion is resumed at the restored offset/gain setting value.)

49 3 SPECIFICATIONS 3.4 Buffer Memory Buffer memory assignment (Q64TD) This section describes the assignment of the Q64TD buffer memory. POINT Do not write data from system area or sequence program to the buffer memory area where writing is disabled. Doing so may cause malfunction. Table 3.1 Buffer memory assignment (Q64TD) (1/3) Address Hex. Dec. Description R/W 1 Reference 00H 0 Conversion enable/disable setting R/W 2 Section H 1 CH1 time/count averaging setting R/W 2 02H 2 CH2 time/count averaging setting R/W 2 03H 3 CH3 time/count averaging setting R/W 2 Section H 4 CH4 time/count averaging setting R/W 2 05H 5 to to System area 08H 8 09H 9 Averaging processing specification R/W 2 Section AH 10 Conversion completion flag R Section BH 11 CH1 measured temperature value R 0CH 12 CH2 measured temperature value R 0DH 13 CH3 measured temperature value R Section EH 14 CH4 measured temperature value R 0FH 15 to to System area 12H 18 13H 19 Error code R Section H 20 Setting range R Section H 21 to to System area 2EH 46 2FH 47 Warning output enable/disable setting R/W 2 Section H 48 Warning output flag R Section H 49 Disconnection detection flag R Section H 50 CH1 scaling value R 33H 51 CH2 scaling value R 34H 52 CH3 scaling value R Section H 53 CH4 scaling value R 36H 54 to to System area 3DH 61 3EH 62 CH1 scaling range lower limit value R/W 2 3FH 63 CH1 scaling range upper limit value R/W 2 40H 64 CH2 scaling range lower limit value R/W 2 Section H 65 CH2 scaling range upper limit value R/W

50 3 SPECIFICATIONS Table 3.1 Buffer memory assignment (Q64TD) (2/3) Address Hex. Dec. Description R/W 1 Reference 42H 66 CH3 scaling range lower limit value R/W 2 43H 67 CH3 scaling range upper limit value R/W 2 44H 68 CH4 scaling range lower limit value R/W 2 Section H 69 CH4 scaling range upper limit value R/W 2 46H 70 to to System area 4DH 77 4EH 78 CH1 scaling width lower limit value R/W 2 4FH 79 CH1 scaling width upper limit value R/W 2 50H 80 CH2 scaling width lower limit value R/W 2 51H 81 CH2 scaling width upper limit value R/W 2 52H 82 CH3 scaling width lower limit value R/W 2 Section H 83 CH3 scaling width upper limit value R/W 2 54H 84 CH4 scaling width lower limit value R/W 2 55H 85 CH4 scaling width upper limit value R/W 2 56H 86 CH1 warning output lower lower limit value R/W 2 57H 87 CH1 warning output lower upper limit value R/W 2 58H 88 CH1 warning output upper lower limit value R/W 2 59H 89 CH1 warning output upper upper limit value R/W 2 5AH 90 CH2 warning output lower lower limit value R/W 2 5BH 91 CH2 warning output lower upper limit value R/W 2 5CH 92 CH2 warning output upper lower limit value R/W 2 5DH 93 CH2 warning output upper upper limit value R/W 2 5EH 94 CH3 warning output lower lower limit value R/W 2 Section FH 95 CH3 warning output lower upper limit value R/W 2 60H 96 CH3 warning output upper lower limit value R/W 2 61H 97 CH3 warning output upper upper limit value R/W 2 62H 98 CH4 warning output lower lower limit value R/W 2 63H 99 CH4 warning output lower upper limit value R/W 2 64H 100 CH4 warning output upper lower limit value R/W 2 65H 101 CH4 warning output upper upper limit value R/W 2 66H 102 to to System area 75H H 118 CH1 offset temperature set value R/W 2 77H 119 CH1 gain temperature set value R/W 2 78H 120 CH2 offset temperature set value R/W 2 79H 121 CH2 gain temperature set value R/W 2 7AH 122 CH3 offset temperature set value R/W 2 Section BH 123 CH3 gain temperature set value R/W 2 7CH 124 CH4 offset temperature set value R/W 2 7DH 125 CH4 gain temperature set value R/W 2 7EH 126 to to System area 93H

51 3 SPECIFICATIONS Table 3.1 Buffer memory assignment (Q64TD) (3/3) Address Hex. Dec. Description R/W 1 Reference 94H 148 Conversion setting for disconnection detection R/W 2 Section H 149 System area 96H 150 CH1 Conversion setting for disconnection detection R/W 2 97H 151 CH2 Conversion setting for disconnection detection R/W 2 98H 152 CH3 Conversion setting for disconnection detection R/W 2 Section H 153 CH4 Conversion setting for disconnection detection R/W 2 9AH 154 to to System area 9DH 157 9EH 158 9FH 159 Mode switching setting R/W Section A0H 160 CH1 factory default offset value 3 R/W A1H 161 CH1 factory default gain value 3 R/W A2H 162 CH1 user range settings offset value 3 R/W A3H 163 CH1 user range settings gain value 3 R/W A4H 164 CH1 user range settings offset value (L) 3 A5H 165 (H) R/W A6H 166 CH1 user range settings gain value (L) 3 A7H 167 (H) R/W A8H 168 CH2 factory default offset value 3 R/W A9H 169 CH2 factory default gain value 3 R/W AAH 170 CH2 user range settings offset value 3 R/W ABH 171 CH2 user range settings gain value 3 R/W ACH 172 CH2 user range settings offset value (L) 3 ADH 173 (H) R/W AEH 174 CH2 user range settings gain value (L) 3 AFH 175 (H) R/W B0H 176 CH3 factory default offset value 3 R/W B1H 177 CH3 factory default gain value 3 R/W Section B2H 178 CH3 user range settings offset value 3 R/W B3H 179 CH3 user range settings gain value 3 R/W B4H 180 CH3 user range settings offset value (L) 3 B5H 181 (H) R/W B6H 182 CH3 user range settings gain value (L) 3 B7H 183 (H) R/W B8H 184 CH4 factory default offset value 3 R/W B9H 185 CH4 factory default gain value 3 R/W BAH 186 CH4 user range settings offset value 3 R/W BBH 187 CH4 user range settings gain value 3 R/W BCH 188 CH4 user range settings offset value (L) 3 BDH 189 (H) R/W BEH 190 CH4 user range settings gain value (L) 3 BFH 191 (H) R/W C0H 192 to to System area

52 3 SPECIFICATIONS 1 Indicates whether reading from and writing to a sequence program are enabled. R : Read enabled W : Write enabled 2 Data must be written to buffer memory under the interlock conditions (buffer memory write conditions) of the following I/O signals. Operation condition setting Buffer memory write conditions Setting request switch Operation Operation condition condition setting completed setting request signal Offset setting Buffer memory write conditions Offset setting switch Offset setting request Offset/gain setting completed signal Gain setting Buffer memory write conditions Gain setting switch Gain setting request Offset/gain setting completed signal 3 This area is related with the user range save/restore function and allows users to re-set the offset/gain values easily in the case of online module change

53 3 SPECIFICATIONS Buffer memory assignment (Q64TDV-GH) The assignment of the Q64TDV-GH buffer memory will be explained. POINT Do not write data from system area or sequence program to the buffer memory area where writing is disabled. Doing so may cause malfunction. Table 3.2 Buffer memory assignment (Q64TDV-GH) (1/3) Address Hex. Dec. Description R/W 1 Reference 00H 0 Conversion enable/disable setting R/W 2 Section H 1 CH1 time/count averaging setting R/W 2 02H 2 CH2 time/count averaging setting R/W 2 03H 3 CH3 time/count averaging setting R/W 2 Section H 4 CH4 time/count averaging setting R/W 2 05H 5 to to System area 08H 8 09H 9 Averaging processing specification R/W 2 Section AH 10 Conversion completion flag R Section BH 11 CH1 measured temperature value/micro voltage conversion value R 0CH 12 CH2 measured temperature value/micro voltage conversion value R 0DH 13 CH3 measured temperature value/micro voltage conversion value R Section EH 14 CH4 measured temperature value/micro voltage conversion value R 0FH 15 to to System area 12H 18 13H 19 Error code R Section H 20 Setting range 1 R Section H 21 Setting range 2 R Section H 22 to to System area 2EH 46 2FH 47 Warning output enable/disable setting R/W 2 Section H 48 Warning output flag R Section H 49 Disconnection detection flag R Section H 50 CH1 scaling value R 33H 51 CH2 scaling value R 34H 52 CH3 scaling value R Section H 53 CH4 scaling value R 36H 54 to to System area 3DH 61 3EH 62 CH1 scaling range lower limit value R/W 2 3FH 63 CH1 scaling range upper limit value R/W 2 40H 64 CH2 scaling range lower limit value R/W 2 Section H 65 CH2 scaling range upper limit value R/W

54 3 SPECIFICATIONS Table 3.2 Buffer memory assignment (Q64TDV-GH) (2/3) Address Hex. Dec. Description R/W 1 Reference 42H 66 CH3 scaling range lower limit value R/W 2 43H 67 CH3 scaling range upper limit value R/W 2 44H 68 CH4 scaling range lower limit value R/W 2 Section H 69 CH4 scaling range upper limit value R/W 2 46H 70 to to System area 4DH 77 4EH 78 CH1 scaling width lower limit value R/W 2 4FH 79 CH1 scaling width upper limit value R/W 2 50H 80 CH2 scaling width lower limit value R/W 2 51H 81 CH2 scaling width upper limit value R/W 2 52H 82 CH3 scaling width lower limit value R/W 2 Section H 83 CH3 scaling width upper limit value R/W 2 54H 84 CH4 scaling width lower limit value R/W 2 55H 85 CH4 scaling width upper limit value R/W 2 56H 86 CH1 warning output lower lower limit value R/W 2 57H 87 CH1 warning output lower upper limit value R/W 2 58H 88 CH1 warning output upper lower limit value R/W 2 59H 89 CH1 warning output upper upper limit value R/W 2 5AH 90 CH2 warning output lower lower limit value R/W 2 5BH 91 CH2 warning output lower upper limit value R/W 2 5CH 92 CH2 warning output upper lower limit value R/W 2 5DH 93 CH2 warning output upper upper limit value R/W 2 5EH 94 CH3 warning output lower lower limit value R/W 2 Section FH 95 CH3 warning output lower upper limit value R/W 2 60H 96 CH3 warning output upper lower limit value R/W 2 61H 97 CH3 warning output upper upper limit value R/W 2 62H 98 CH4 warning output lower lower limit value R/W 2 63H 99 CH4 warning output lower upper limit value R/W 2 64H 100 CH4 warning output upper lower limit value R/W 2 65H 101 CH4 warning output upper upper limit value R/W 2 66H 102 to to System area 75H H 118 CH1 offset setting value R/W 2 77H 119 CH1 gain setting value R/W 2 78H 120 CH2 offset setting value R/W 2 79H 121 CH2 gain setting value R/W 2 7AH 122 CH3 offset setting value R/W 2 Section BH 123 CH3 gain setting value R/W 2 7CH 124 CH4 offset setting value R/W 2 7DH 125 CH4 gain setting value R/W 2 7EH 126 to to System area 93H H 148 Conversion setting for disconnection detection R/W 2 Section H 149 System area

55 3 SPECIFICATIONS Table 3.2 Buffer memory assignment (Q64TDV-GH) (3/3) Address Hex. Dec. Description R/W 1 Reference 96H 150 CH1 Conversion setting for disconnection detection R/W 2 97H 151 CH2 Conversion setting for disconnection detection R/W 2 98H 152 CH3 Conversion setting for disconnection detection R/W 2 Section H 153 CH4 Conversion setting for disconnection detection R/W 2 9AH 154 to to System area 9DH 157 9EH 158 9FH 159 Mode switching setting R/W Section A0H 160 CH1 factory default offset value 3 R/W A1H 161 CH1 factory default gain value 3 R/W A2H 162 CH1 user range settings offset value 3 R/W A3H 163 CH1 user range settings gain value 3 R/W A4H 164 CH1 user range settings thermal EMF offset value (L) 3 A5H 165 (H) R/W A6H 166 CH1 user range settings thermal EMF gain value (L) 3 A7H 167 (H) R/W A8H 168 CH2 factory default offset value 3 R/W A9H 169 CH2 factory default gain value 3 R/W AAH 170 CH2 user range settings offset value 3 R/W ABH 171 CH2 user range settings gain value 3 R/W ACH 172 CH2 user range settings thermal EMF offset value (L) 3 ADH 173 (H) R/W 3 AEH 174 CH2 user range settings thermal EMF gain value (L) R/W AFH 175 (H) Section B0H 176 CH3 factory default offset value 3 R/W B1H 177 CH3 factory default gain value 3 R/W B2H 178 CH3 user range settings offset value 3 R/W B3H 179 CH3 user range settings thermal EMF gain value 3 R/W B4H 180 CH3 user range settings thermal EMF offset value (L) 3 B5H 181 (H) R/W B6H 182 CH3 user range settings gain value (L) 3 B7H 183 (H) R/W B8H 184 CH4 factory default offset value 3 R/W B9H 185 CH4 factory default gain value 3 R/W BAH 186 CH4 user range settings offset value 3 R/W BBH 187 CH4 user range settings gain value 3 R/W BCH 188 CH4 user range settings thermal EMF offset value (L) 3 BDH 189 (H) R/W BEH 190 CH4 user range settings thermal EMF gain value (L) 3 BFH 191 (H) R/W C0H 192 to to System area

56 3 SPECIFICATIONS 1 Indicates whether reading from and writing to a sequence program are enabled. R : Read enabled W : Write enabled 2 Data must be written to buffer memory under the interlock conditions (buffer memory write conditions) of the following I/O signals. Operating condition setting Buffer memory write conditions Setting request switch Operating Operating condition condition setting completion setting request signal Offset setting Buffer memory write conditions Offset setting switch Offset setting request Offset/gain setting completion signal Gain setting Buffer memory write conditions Gain setting switch Gain setting Offset/gain setting request completion signal 3 This area is related with the user range save/restore function and allows users to re-set the offset/gain values easily in the case of online module change

57 3 SPECIFICATIONS Conversion enable/disable setting (Un\G0) (1) You can make setting to enable/disable temperature conversion on each channel. (2) Specifying unused channels as "conversion disabled" prevents unnecessary disconnection detection and also reduces sampling time. (3) At power-on or reset, the conversion enable/disable setting is set to 000FH (all channels disabled). b15 b14 b13 b12 b11 b10 b9 b8 b7 b6 b5 b4 b3 b2 b1 b CH4 CH3 CH2 CH1 [Example] 0: Conversion enabled 1: Conversion disabled b15 b14 b13 b12 b11 b10 b9 b8 b7 b6 b5 b4 b3 b2 b1 b Channels 1 and 2 are conversion enabled. (4) The Operating Condition Setting Request (Y9) must be turned on/off to make the conversion enable/disable setting valid

58 3 SPECIFICATIONS CH time/count averaging setting (Un\G1 to 4) (1) Set the averaging time or averaging count for each channel when averaging processing is selected. (buffer memory address 9: Un\G9). (2) Setting can be made within the following ranges. Time averaging processing: 160 to 5000ms (Q64TD) 80 to 2500ms (Q64TDV-GH) Count averaging processing: 4 to times 1 If you set any value outside the range, it will result in an error and the previous setting will not be updated. 1: when setting times or more in the sequence program, set the count in hexadecimal. For instance, set F424H to specify times. (3) This setting will be invalid if sampling is specified in the averaging processing specification (buffer memory address 9: Un\G9). (4) At power-on or reset, this area is set to 0000H (averaging time 0/averaging count 0). (5) The Operating Condition Setting Request (Y9) must be turned on/off to make this setting valid. (6) Refer to Section for details of sampling processing/time averaging processing/count averaging processing Averaging processing specification (Un\G9) (1) To select sampling or averaging processing, write values to the buffer memory address 9 (Un\G9). (2) When you selected averaging processing, choose time averaging or count averaging. (3) The default is set to sampling processing for all channels. b15 b14 b13 b12 b11 b10 b9 b8 b7 b6 b5 b4 b3 b2 b1 b CH4 CH3 CH2 CH CH4 CH3 CH2 CH1 Example Setting of channels 1: Averaging processing 0: Sampling processing Selection of time/count 1: Time averaging 0: Count averaging (4) The Operating Condition Setting Request (Y9) must be turned on/off to make this setting valid. To specify count averaging for channels 1, time averaging for channels 2 and sampling processing for other channels, store 0302H (770) into the buffer memory address 9 (Un\G9). b15 b14 b13 b12 b11 b10 b9 b8 b7 b6 b5 b4 b3 b2 b1 b H (770) CH4 CH3 CH2 CH1 CH4 CH3 CH2 CH

59 3 SPECIFICATIONS Conversion completion flag (Un\G10) (1) You can check whether the channels specified for conversion enable succeeded in normal conversion. (2) You can make check on each channel using the conversion completion flag. (3) The conversion completion flag is cleared when the Operating Condition Setting Request (Y9) is turned from ON to OFF. (4) The Conversion Completion Flag (XE) turns on when conversions of all conversion-enabled channels are completed. When conversion enable/disable setting is turned from 1 (disable) to 0 (enable) After the measured temperature value/micro voltage conversion voltage is stored into the buffer memory, the conversion completion flag of the corresponding channel is turned to 1. When the conversion enable/disable setting is turned from 0 (enable) to 1 (disable) The conversion completion flag of the corresponding channel is turned to 0. b15 b14 b13 b12 b11 b10 b9 b8 b7 b6 b5 b4 b3 b2 b1 b CH4 CH3 CH2 CH1 1: Conversion completed 0: During conversion or unused (5) Read measured temperature value/micro voltage conversion value using this area or the Conversion completion flag (XE) as an interlock. REMARK Between the Q64TD/Q64TDV-GH whose first 5 digits of product information are or earlier and those of or later, the Conversion Completion Flag (Un\G10) operation is different. For details, refer to Appendix

60 3 SPECIFICATIONS CH measured temperature value/micro voltage value (Un\G11 to 14) (1) Thermocouple input (a) The "thermal EMF value" input from the thermocouple is converted into a "temperature value" to detect a temperature. (b) The value of the measured temperature to the first decimal place is multiplied by 10 and the result is stored into buffer memory in 16-bit signed binary. (The second decimal place and on are rounded down.) (c) A negative measured temperature value is displayed as two's complement. (d) At power-on or reset, all channels are set to 0. [Example 1] At the measured temperature value of is stored. b15 b14 b13 b12 b11 b10 b9 b8 b7 b6 b5 b4 b3 b2 b1 b [Example 2] At the measured temperature value of is stored. b15 b14 b13 b12 b11 b10 b9 b8 b7 b6 b5 b4 b3 b2 b1 b (2) Micro voltage input (a) A micro voltage of -100mV to +100mV is converted into a 16-bit, signed binary value of to 25000, and the result is stored. (b) A negative micro voltage conversion value is displayed as two's complement. (c) At power-on or reset, all channels are set to 0. [Example 1] At the micro voltage input value of mV is stored. b15 b14 b13 b12 b11 b10 b9 b8 b7 b6 b5 b4 b3 b2 b1 b [Example 2] At the micro voltage input value of mV is stored. b15 b14 b13 b12 b11 b10 b9 b8 b7 b6 b5 b4 b3 b2 b1 b POINT Read measured temperature value/micro voltage conversion value using the Conversion completion flag (XE) or the Conversion completion flag (buffer memory address 10: Un\G10) as an interlock

61 3 SPECIFICATIONS Error code (Un\G19) Setting range (Q64TD) (Un\G20) (1) When the Q64TD/Q64TDV-GH has detected a set value or operation procedure error, the corresponding error code is stored. (2) The error code is stored as a 16-bit binary value. (3) When an error occurs, the "ERROR LED" of the Q64TD/Q64TDV-GH is lit. (4) The following are main checking details. Timing Description Check on the intelligent function module switch settings of At start GX Developer When Operating Condition Setting Check on averaging processing specification Request (Y9) has turned from ON to Check on averaging time and averaging count OFF Check on warning output upper/upper limit values Check on offset/gain setting Check on preset CH offset temperature value/ch gain When Offset Setting Request (Y1, Y3, temperature value Y5, Y7) or Gain Setting Request (Y2, Check whether Offset Setting Request (Y1, Y3, Y5, Y7) and Y4, Y6, Y8) is turned on Gain Setting Request (Y2, Y4, Y6, Y8) are not turned on at the same time. Check whether the same data was written consecutively or When User Range Write Request (YA) has turned from ON to OFF 1 not. Check whether the pass data has been set or not. Check whether the same data was written consecutively or When G(P).OGSTOR instruction is not. executed in sequence program 1 Check whether a different model has been mounted or not by an online module change. 1 Supported by the module of function version C or later. (5) When two or more errors occurred, the error code of the error found first is stored and latter errors are not stored. However, you can confirm the latter errors in the error history of the detailed module information of GX Developer. (6) Giving the Error Clear Request (YF) clears the error code and turns off the lit "ERROR LED". (7) Clearing the error stores 0. (1) The settings of the "thermocouple type" and "offset/gain setting" are stored. (2) Use the intelligent function module switches of GX Developer to make settings of the "thermocouple type" and "offset/gain setting". Refer to Section 4.5 for details of the setting method. b15 b14 b13 b12 b11 b10 b9 b8 b7 b6 b5 b4 b3 b2 b1 b0 CH4 CH3 CH2 CH1 b3 b2 b1 b0 Set value of offset/gain setting Offset/Gain Setting Set Value Factory default 0 User range setting 1 Set value of thermocouple type Thermocouple Type Set Value K 0 E 1 J 2 T 3 B 4 R 5 S 6 N

62 3 SPECIFICATIONS Setting range 1 (Q64TDV-GH) (Un\G20) (1) The setting of the "input type" is stored. (2) Use the intelligent function module switches of GX Developer to make the setting of the "input type". Refer to Section 4.5 for details of the setting method. b15 b14 b13 b12 b11 b10 b9 b8 b7 b6 b5 b4 b3 b2 b1 b0 CH4 CH3 CH2 CH1 b3 b2 b1 b0 Set value of input type Input Type Thermocouple K Thermocouple E Thermocouple J Thermocouple T Thermocouple B Thermocouple R Thermocouple S Thermocouple N Micro voltage input Set Value Setting range 2 (Q64TDV-GH) (Un\G21) (1) The setting of the "offset/gain setting" is stored. (2) Use the intelligent function module switches of GX Developer to make the setting of the "offset/gain setting". Refer to Section 4.5 for details of the setting method. b15 b14 b13 b12 b11 b10 b9 b8 b7 b6 b5 b4 b3 b2 b1 b0 CH4 CH3 CH2 CH1 b3 b2 b1 b Set value of offset/gain setting Offset/Gain Setting Set Value Factory default 0 User range setting

63 3 SPECIFICATIONS Warning output enable/disable setting (Un\G47) (1) This area is used to set whether a warning will be output or not per channel. (2) At power-on or reset, the warning output enable/disable setting is set to 000FH (all channels disabled). b15 b14 b13 b12 b11 b10 b9 b8 b7 b6 b5 b4 b3 b2 b1 b CH4 CH3 CH2 CH1 0: Warning output enable 1: Warning output disable [Example] b15 b14 b13 b12 b11 b10 b9 b8 b7 b6 b5 b4 b3 b2 b1 b Warning output flag (Un\G48) Channels 1 and 2 are warning output enabled. (3) The Operating Condition Setting Request (Y9) must be turned on/off to make the warning output enable/disable setting valid. (1) When CH measured temperature value/micro voltage conversion value (buffer memory addresses 11 to 14: Un\G 11 to 14) is outside the range set for the CH warning output upper/lower limit value (buffer memory addresses 86 to 101: Un\G86 to 101), the warning output flag of the corresponding channel turns to 1. (2) You can check whether the warning given is the upper or lower limit value warning on each channel. (3) When the measured temperature value/micro voltage conversion value returned to within the measurement range, the flag is automatically reset. (4) If a warning is detected on any of the channels enabled for conversion, the Warning Output Signal (XD) turns on. (5) The warning output flag is cleared when the Operation Condition Setting Request (Y9) is turned on. b15 b14 b13 b12 b11 b10 b9 b8 b7 b6 b5 b4 b3 b2 b1 b CH4 upper limit value CH4 lower limit value CH3 upper limit value CH3 lower limit value CH2 upper limit value CH2 lower limit value CH1 upper limit value CH1 lower limit value 0: Normal 1: Out-of-range POINT Refer to Section for details of the warning output

64 3 SPECIFICATIONS Disconnection detection flag (Un\G49) (1) The disconnection detection flag of the corresponding channel turns to 1 when the disconnection of the thermocouple, compensation conductor or micro voltage signal cable is detected. (2) Disconnection detection is made on only the channels set for conversion enable. (3) Disconnection is detected on each channel. (4) For a channel where disconnection is detected, a value based on the Conversion setting for disconnection detection (buffer memory address 148: Un\G148) is stored in the CH measured temperature value/micro voltage value (buffer memory addresses 11 to 14: Un\G11 to 14). Conversion of the channels not disconnected is continued. b15 b14 b13 b12 b11 b10 b9 b8 b7 b6 b5 b4 b3 b2 b1 b CH4 CH3 CH2 CH1 0: Normal 1: Disconnection (5) The disconnection detection flag is cleared when the Operation Condition Setting Request (Y9) or Error Clear Request (YF) is turned on. Clearing of the disconnection detection flag using the Error Clear Request (YF) is supported by the module of function version C or later. (6) The relationships between disconnection detection and conversion enable/disable setting are indicated below. Connection Status Conversion Enable/Disable Setting Disconnection Detection Flag Without disconnection + - Conversion enable Conversion disable OFF + Conversion enable ON With disconnection - Conversion disable OFF + Conversion enable ON Without connection - Conversion disable OFF POINT Any channel where no thermocouple, compensation conductor or micro voltage signal cable is connected must be set to "conversion disable". Not doing so will turn on the disconnection detection flag. For measured temperature values/micro voltage conversion values to be stored when the Disconnection Detection Flag (XC) turns ON, any of "Value immediately before disconnection", "Up scale (maximum value of measured temperature range + 5% of measured temperature range)", "Down scale (minimum value of measured temperature range 5% of measured temperature range)", or "Given value" can be selected. (Refer to Section ) After disconnection detection, update of measured temperature values/micro voltage conversion values resumes if the connection is re-established. Refer to Section 4.4 for the wiring of the thermocouple, compensation conductor or micro voltage signal cable. Refer to Section for the troubleshooting of disconnection detection

65 3 SPECIFICATIONS CH scaling value (Un\G50 to 53) (1) The measured temperature value/micro voltage conversion value within the scaling range set for the CH scaling range upper/lower limit values (buffer memory address 62 to 69: Un\G62 to 69) is scaled to the scaling width set for the CH scaling width upper/lower limit values (buffer memory address 78 to 85: Un\G78 to 85) and the result is stored. (2) The following is how to calculate the scaling value. Scaling value = (Scaling width upper limit value - Scaling width lower limit value) Measured temperature value/ micro voltage conversion value - Scaling range lower limit value Scaling range upper limit value - Scaling range lower limit value [Example] To scale a temperature to a percent When the CH1 measured temperature value of 360 (measured temperature value = 3600) is scaled at the following settings, Scaling range: -100 to 500 (lower limit value = -1000, upper limit value = 5000) Scaling width: 0 to 100% (lower limit value = 0, upper limit value = 100) Scaling value= 3600-(-1000) (100-0) +0= Fractional portion is rounded off (-1000) =Scaling width lower limit value =77[%] Stored into buffer memory address 50. POINT (1) If the upper limit value is less than the lower limit value in the settings of the CH scaling range upper/lower limit values (buffer memory address 62 to 69: Un\G62 to 69) or CH scaling width upper/lower limit values (buffer memory address 78 to 85: Un\G78 to 85), it will not result in an error and the scaling value will be output using the above calculation expression to make calculation. (2) If the temperature/micro voltage measured is outside the range set by the upper and lower limit values of the scaling range, the value set as the upper or lower limit value of the scaling width is stored into the buffer memory CH scaling range upper/lower limit values (Un\G62 to 69) (1) Set the scaling range of the temperature measurement value/micro voltage conversion value on each channel. The setting for the measured temperature value is in 0.1 increments. (2) 0 is set at power-on or reset. (3) The scaling range that may be set is to (4) Scaling will not be made if the upper limit value and lower limit value are equal. (5) The Operating Condition Setting Request (Y9) must be turned on/off to make the setting valid

66 3 SPECIFICATIONS CH scaling width upper/lower limit values (Un\G78 to 85) (1) Set the scaling width on each channel. (2) 0 is set at power-on or reset. (3) The scaling range that may be set is to (4) Set the upper and lower limit values to 0 when scaling will not be made. (5) The Operating Condition Setting Request (Y9) must be turned on/off to make the setting valid CH warning output upper/lower limit values (Un\G86 to 101) (1) Set the warning output range of the measured temperature value/micro voltage conversion value on each channel. The setting for the measured temperature value is in 0.1 increments. (2) The warning output range can be set in four levels of the warning output upper upper value, upper lower value, lower upper value and lower lower value. (3) When the detected measured temperature value is higher than or equal to the warning output upper upper limit value, or lower than or equal to the warning output lower lower limit value (when the value enters the warning output range), a warning occurs. When a warning occurs, "1" is stored to the bit of the corresponding channel in the warning output flag (buffer memory address 48: Un\G48), and the warning output signal (XD) turns ON. (4) After a warning occurrence, when the temperature value is lower than the warning output upper lower limit value or higher than the warning output lower upper limit value (when the value returns to within the setting range), the warning is cleared. When the warning is cleared, "0" is stored to the bit of the corresponding channel in the warning output flag (buffer memory address 48: Un\G48). The warning output signal (XD) turns OFF only when the values for all channels return to within the setting range. Temperature Upper upper limit value Upper lower limit value Warning output Warning output range section Out of warning output range section Included Warning clear Lower upper limit value Lower lower limit value Warning output Warning clear Time

67 3 SPECIFICATIONS (5) At power-on or reset, the minimum and maximum values of the accuracy guarantee range of the input type set as the input type (set using GX Developer) are stored. The upper upper limit value is set to be equal to the upper lower limit value, and the lower upper limit value equal to the lower lower limit value. Input type Lower upper limit value Settings at Power-On or Reset Lower lower Upper upper limit value limit value Upper lower limit value Available Temperature Range(Accuracy guarantee range) Thermocouple K to (-2000 to 12000) Thermocouple E to (-2000 to 9000) Thermocouple J to (-400 to 7500) Thermocouple T to 4000 (-2000 to 3500) Thermocouple B to (-6000 to 17000) Thermocouple R to (-0 to 1600) Thermocouple S to (-0 to 1600) Thermocouple N to (-2000 to 12500) Micro voltage input to ( to 25000) (6) When the settings below are applied, an error (error code 6 ) occurs. Then the error flag (XF) turns ON and the operation is carried out with the setting before the error occurrence. (a) Setting a value out of the above settable range. (b) Setting a value that does not satisfy the following condition: Warning output lower lower limit value lower upper limit value upper lower limit value upper upper limit value (7) If the lower upper limit value is equal to the upper lower limit value, an error does not occur and the warning output is made invalid. (8) The Operating Condition Setting Request (Y9) must be turned on/off to make the setting valid

68 3 SPECIFICATIONS CH offset/gain temperature value (Q64TD)/CH offset/gain setting value (Q64TDV-GH) (Un\G118 to 125) (1) Offset/gain setting (error compensation) is a function designed to compensate for the value at any two points (offset value/gain value) within the operating range when the proper measured temperature value/micro voltage conversion value is not available at a system start or when the input type is changed. (2) When the Offset Setting Request/Gin Setting Request (Y1 to 8) is turned on in the offset/gain setting mode, the measured temperature value/micro voltage conversion value is corrected to be the set value written to this area. (Setting for measured temperature value in 0.1 increments) [Example] To set to Store 800. (3) Error compensation is made by reading the measured temperature value/micro voltage conversion value of the buffer memory using a sequence program and monitoring the values on the peripheral device. (4) The following are the relationships between the measured temperature value/ micro voltage conversion value and offset value/gain value relative to the input temperature. (a) Thermocouple input 80[ ] 79.7 Gain value Measured temperature value is corrected to be input temperature. Measured temperature value -50[ ] 0 80[ ] Input temperature Measured temperature value is corrected to be input temperature. Offset value [ ] Characteristic before error compensation Characteristic after error compensation (b) Micro voltage input Gain value Micro voltage conversion value is corrected to be gain setting. Micro voltage conversion value 75[mV] 0 100[mV] Micro voltage input value Micro voltage conversion value is corrected to be offset setting. Offset value Characteristic before error compensation Characteristic after error compensation

69 3 SPECIFICATIONS (5) At power-on or reset, the minimum and maximum values in the accuracy guarantee range of the input type set as Input type (set using GX Developer) are stored. Refer to Section for the accuracy guarantee range. POINT High accuracy is ensured for the offset and gain values when the minimum and maximum values within the operating range are used to make error compensation. Make offset/gain value setting while simultaneously reading the measured temperature value/micro voltage conversion value. Always set the offset and gain values so that they will satisfy the following conditions. An error will occur if the conditions are not satisfied. Condition 1: Within the input enabled range Condition 2: (Gain value) - (offset value) > 0.1 [ ] (for temperature input) or (Gain value) - (offset value) > 4 [ V] (for micro voltage input) By giving the user range write request, the offset and gain values are stored into the E 2 PROM of the Q64TD/Q64TDV-GH and will not be erased at power-off. For thermocouple input, error compensation may also be made using a standard DC voltage generator or like instead of inputting a temperature directly to the thermocouple. Power value of standard DC voltage generator = Thermoelectromotive force value of thermocouple used as offset/gain value relative to input temperature Conversion setting for disconnection detection (Un\G148) (1) Select the value to be stored in the CH measured temperature value/micro voltage value (buffer memory address 11 to 14: Un\G11 to 14) in the case of disconnection detection. b15 b14 b13 b12 b11 b10 b9 b8 b7 b6 b5 b4 b3 b2 b1 b0 CH4 CH3 CH2 CH1 Setting value 0H 1H 2H 3H Value to be stored in the CH measured temperature value in the case of disconnection detection. Value immediately before disconnection Up scale (maximum value of measured temperature range + 5% of measured temperature range) Down scale (minimum value of measured temperature range - 5% of measured temperature range) Given value (set a value for the CH conversion setting for disconnection state value)(refer to Section )

70 3 SPECIFICATIONS (2) This is set to 0H (Value immediately before disconnection) when the module is powered up or reset. (3) The Operating Condition Setting Request (Y9) must be turned on/off to make the setting valid. (4) Do not set any value outside the setting range. If it is set, the module operation cannot be guaranteed

71 3 SPECIFICATIONS Conversion setting value for disconnection detection (Un\G150 to 153) (1) If Given value (3H) is set in the Conversion setting for disconnection detection (buffer memory address 148: Un\G148), when disconnection is detected, the value set in this area is stored in the CH measured temperature value/micro voltage value (buffer memory addresses 11 to 14: Un\G11 to 14). If any of 0H to 2H is set in the Conversion setting for disconnection detection, setting of this area is ignored. (2) The setting range is from to (0000H to FFFFH). (Setting in 0.1 increments.) [Example] To set to Store 3. (3) This is set to 0 when the module is powered up or reset. (4) The Operating Condition Setting Request (Y9) must be turned on/off to make the setting valid Mode switching setting (Un\G158 to 159) Used to change between the normal mode and offset/gain setting mode. You can change the mode without resetting the programmable controller CPU. (1) Set the value of the mode to which you want to switch. (2) After setting the value, turn the operating condition setting request (Y9) from OFF to ON to shift the mode. (3) When the mode is switched, this area is cleared to zero and the operating condition setting completion flag (X9) turns off. After making sure that the operating condition setting completion flag (X9) has turned off, turn off the operating condition setting request (Y9). Mode to Be Shifted to Set Value Buffer memory address 158 Buffer memory address 159 Normal mode 0964H 4144H Offset/gain setting mode 4144H 0964H POINT If the value written is other than the above, mode switching is not performed and only the operating condition is changed

72 3 SPECIFICATIONS Factory default offset/gain value/user range settings offset/gain value/user range settings thermal EMF offset/gain value (Un\G160 to 191) (1) This area is related with the user range save/restore function and allows users to re-set the offset/gain values easily in the case of online module change. (2) When the offset/gain values of the user range setting are restored, the used data are stored. The data are stored (saved) when: Initial setting write is performed by the utility; The operating condition is set (Y9 turns from OFF to ON 1) The offset/gain values are written in the offset/gain setting mode (YA turns from OFF to ON). 1 The data are not saved when values have been written to the mode switching setting area (buffer memory addresses 158, 159: Un\G158, Un\G159). (3) When restoring the offset/gain values of the user range setting, set the data saved here similarly into the corresponding area of the module where the data will be restored. (4) Buffer memory saving recording procedure for online module change 1) Turn the operating condition setting request (Y9) from OFF to ON. 2) Compare the Factory default offset/gain value/user range settings offset/gain value/user range settings thermal EMF offset/gain value (buffer memory addresses 160 to 191: Un\G160 to Un\G191) with the range reference values. Refer to Section 7.4 for the range reference values. 3) If the values are proper, record the Factory default offset/gain value/user range settings offset/gain value/user range settings thermal EMF offset/gain value. (5) Refer to Chapter 7 for details of online module change. POINT This area is not used for the offset/gain settings. For the offset/gain settings, refer to section

73 3 SPECIFICATIONS MEMO

74 4 SETUP AND PROCEDURES BEFORE OPERATION 4 SETUP AND PROCEDURES BEFORE OPERATION 4.1 Handling Precautions (1) Do not drop the module or subject it to heavy impact. (2) Do not remove the PCB of the module from its case. Doing so may cause the module to fail. (3) Be careful not to let foreign particles such as swarf or wire chips enter the module. They may cause a fire, mechanical failure or malfunction. 4 (4) The top surface of the module is covered with a protective film to prevent foreign objects such as wire burrs from entering the module during wiring. Do not remove this film until the wiring is complete. Before operating the system, be sure to remove the film to provide adequate ventilation. (5) Tighten the screws such as module fixing screws within the following ranges. Loose screws may cause short circuits, failures, or malfunctions. Screw location Module fixing screw (M3 screw) Terminal block screw (M3 screw) Terminal block mounting screw (M3.5 screw) 1 Tightening torque range 0.36 to 0.48 N.m 0.42 to 0.58 N.m 0.66 to 0.89 N.m 1 The module can be easily fixed onto the base unit using the hook at the top of the module. However, it is recommended to secure the module with the module fixing screw if the module is subject to significant vibration. (6) To mount the module, while pressing the module mounting lever located in the lower part of the module, fully insert the module fixing projection(s) into the hole(s) in the base unit and press the module until it snaps into place. Incorrect mounting may cause malfunction, failure or drop of the module. When using the programmable controller in an environment of frequent vibrations, fix the module with a screw

75 4 SETUP AND PROCEDURES BEFORE OPERATION 4.2 Setup and Procedures before Operation Start Module mounting Mount the Q64TD/Q64TDV-GH in the specified slot. Wiring Wire external devices to the Q64TD/Q64TDV-GH. Intelligent function module switch settings Perform settings using GX Developer (see Section 4.5). 4 Use user range settings? Use factory default settings Use user range settings Offset/gain setting If user range settings are used, perform the offset and gain settings (see Section 4.6). Use the utility package? NO YES Initial setting and automatic refresh setting The program can be simplified if the utility package is used for setting (see Chapter 5). Programming and debugging Create and check the sequence program

76 4 SETUP AND PROCEDURES BEFORE OPERATION 4.3 Part Names and Settings The name of each part of the 64TD/Q64TDV-GH is listed below. Terminal Block Layout Terminal number Signal name 1 RTD + 2 Empty 3 RTD - 4 Empty 5 Empty 6 CH1 SLD 7 CH2 SLD 8 CH1 + 9 CH CH1-11 CH2-12 CH CH CH3-15 CH4-16 CH3 SLD 17 CH4 SLD 18 FG Number Name and Appearance Description Indicates the operating status of the Q64TD/Q64TDV-GH. On : Operating normally. 1) RUN LED Flicker : Offset/gain setting mode Off : 5V power switched off, watchdog timer error occurred, or online module change enabled Indicates the error status of the Q64TD/Q64TDV-GH. On : Error occurrence 2) ERROR LED Flicker : Switch setting error Switch 5 was set to other than 0 in intelligent function module switch setting of GX Developer. Off : Operating normally. 3) Terminal block Used for wiring of the thermocouple, etc. 4) Cold junction temperature compensation resistor Used for cold junction temperature compensation using Pt100. 5) Serial number display Displays the serial number of the Q64TD/Q64TDV-GH

77 4 SETUP AND PROCEDURES BEFORE OPERATION 4.4 Wiring Wiring instructions The wiring precautions and examples of module connection are provided below. In order to optimize the functions of the Q64TD/Q64TDV-GH and ensure system reliability, external wiring that is protected from noise is required. Please observe the following precautions for external wiring: External wiring (1) Use separate cables for the AC control circuit and Q64TD/Q64TDV-GH's external input signals to avoid the influence of AC side surges and inductions. (2) Always place the thermocouple/micro voltage signal cable at least 100mm away from the main circuit cables and AC control lines. Fully keep it away from high-voltage cables and circuits which include harmonics, such as an inverter's load circuit. Not doing so will make the module more susceptible to noises, surges and inductions. (3) Insulation-sleeved crimping terminals cannot be used with the terminal block. It is recommended to fit mark tubes or insulation tubes to the wire connection parts of the crimping terminals. (1) Thermocouple 1 As cables, always use shielded compensation conductors. Also, wire the shielded cables as short as possible. 2 Always connect to the earth terminal of the control box

78 4 SETUP AND PROCEDURES BEFORE OPERATION (2) Micro voltage signal 1 As cables, always use shielded conductors. Also, wire the shielded cables as short as possible. 2 Always connect to the earth terminal of the control box

79 4 SETUP AND PROCEDURES BEFORE OPERATION 4.5 Switch Setting for Intelligent Function Module The settings for the intelligent function module are performed using the I/O assignment settings for GX Developer. (1) Setting item The intelligent function module switches consist of switches 1 to 5 and are set using 16 bit data. When the intelligent function module switches are not set, the default value for switches 1 to 5 is 0. Setting Item Switch 1 Input type setting CH4 CH3 CH2 CH1 H Input type Set value Thermocouple K 0 Thermocouple E 1 Thermocouple J 2 Thermocouple T 3 Thermocouple B 4 Thermocouple R 5 Thermocouple S 6 Thermocouple N 7 Micro voltage input 1 8 Switch 2 Switch 3 Offset/gain setting CH4 CH3 CH2 CH1 H Offset/gain setting Set value Factory default 0 User range setting 1 Empty Switch 4 Switch 5 0 : Fixed 1: Micro voltage input can be set on the Q64TDV-GH only. 2: Setting any value within the setting range activates the same operation. In the setting range of 1H to FH, set 1 for example

80 4 SETUP AND PROCEDURES BEFORE OPERATION (2) Operating procedure Start the settings with GX Developer assignment setting screen. (a) I/O assignment setting screen Set the following for the slot in which the Q64TD/Q64TDV-GH is mounted. The type setting is required; set other items as needed. Type : Select "intelli." Model name : Enter the module model name. Points : Select 16 points. Start XY : Enter the start I/O number for the Q64TD/Q64TDV-GH. Detailed setting : Specify the "H/W error time PLC operation mode" and "Control PLC" for the Q64TD/Q64TDV-GH. It is unnecessary to set the "Error time output mode" because this setting is invalid for the Q64TD/Q64TDV-GH. (b) Switch setting for intelligent function module screen Click on [Switch setting] on the I/O assignment setting screen to display the screen shown at left, then set switches 1 to 5. The switches can easily be set if values are entered in hexadecimal. Change the entry format to hexadecimal and then enter the values

81 4 SETUP AND PROCEDURES BEFORE OPERATION 4.6 Offset/Gain Setting Perform offset/gain settings in the procedure given in Section 4.6 (1) or Section 4.6 (2). When the industrial shipment setting is used, offset/gain setting is not necessary. If the utility package is installed, perform the offset/gain settings according to the procedure described in Section or Section (1) Offset/gain setting for thermocouple input

82 4 SETUP AND PROCEDURES BEFORE OPERATION (2) Offset/gain setting for the micro voltage input

83 4 SETUP AND PROCEDURES BEFORE OPERATION 1 The mode switching (normal mode to offset/gain setting mode to normal mode) method is given below. Dedicated instruction (G.OFFGAN)... Refer to Section 4.6 (3), (a) Setting made to mode switching setting (buffer memory addresses 158, 159: Un\G158, Un\G159) and turning the operation condition setting request (Y9) from OFF to ON... Refer to Section 4.6 (3), (b) Intelligent function module switch setting... Refer to Section 4.5, Section 4.6 (3), (c) (After intelligent function module switch setting, reset the programmable controller CPU or switch power OFF, then ON.) 2 Do not perform the following during the steps marked 2 If any of the following is performed, the data in E 2 PROM will have a problem and the Q64TD/Q64TDV-GH may not operate normally. Powering off the programmable controller CPU Resetting the programmable controller CPU POINT Check the offset and gain values in the actual operating status. By turning on the User Range Write Request (YA), the offset and gain values are stored into the E 2 PROM and will not be erased at power-off. Make offset/gain setting within the measured temperature guarantee range (refer to Section (2), Section (2)) or within the measurable voltage range (refer to Section (3)). If setting is made outside the measured temperature guarantee range or measurable voltage range, the resolution and accuracy may not fall within the ranges of the performance specifications. Set the offset and gain values within the ranges where the following conditions are satisfied. (Gain value) - (offset value) > 0.1 [ ] (for temperature input) or (Gain value) - (offset value) > 4 [ V] (for micro voltage input) Offset/gain setting may be made for two or more channels at the same time. Do not set the offset and gain values concurrently. Doing so will cause an error, lighting up the ERROR LED. If an error occurs during offset/gain setting, setting can be continued on another channel or the like. However, since the error remains occurring, turn on the Error Clear Request (YF) when you want to clear the error. At the time of offset/gain setting, turn ON the user range write request (YA) to write the values to the E 2 PROM. Data can be written to the E 2 PROM up to 100 thousand times. To prevent accidental write to the E 2 PROM, an error will occur and the error code (buffer memory address 19: Un\G19) will be stored if write is performed 26 consecutive times. (Refer to Section ) 1 If an error (error code: 40 ) occurs during offset/gain setting, re-set the correct offset/gain value. The offset/gain value of the channel where the error has occurred is not written to the Q64TD/Q64TDV-GH. ( 1 indicates the corresponding channel number.) The module ready (X0) turns from OFF to ON when the offset/gain setting mode is switched to the normal mode by the setting of the dedicated instruction (G(P).OFFGAN) or mode switching setting (buffer memory addresses 158, 159: Un\G158, Un\G159). Note that initial setting processing will be executed if there is a sequence program that will perform initial setting when the module ready (X0) turns on. Also, for only the Q64TD, the error is cleared when the mode is switched. The factory default offset/gain values, user range settings offset/gain values and user range settings thermal EMF offset/gain values (buffer memory addresses 160 to 255: Un\G160 to 255) are related with the user range save/restore function and allow users to re-set the offset/gain values easily in the case of online module change. These areas are not used for the offset/gain setting

84 4 SETUP AND PROCEDURES BEFORE OPERATION (3) Program examples The program in the dotted area of (a) is common to (a), (b) and (c). In this example, the I/O signals for Q64TD/Q64TDV-GH are X/Y0 to X/YF. Offset request... M0 Gain request... M1 Write request... M2 Mode switching... M3 Offset/gain temperature set value... D0 Dedicated instruction (G.OFFGAN) set value storage device... D1 (a) When dedicated instruction (G.OFFGAN) is used to change mode The following program example is designed to shift to the offset/gain setting mode using the dedicated instruction (G.OFFGAN) and write the offset and gain values of CH1 to the Q64TD/Q64TDV-GH

85 4 SETUP AND PROCEDURES BEFORE OPERATION (b) When switching the mode using the setting of the mode switching setting (buffer memory addresses 158, 159: Un\G158, Un\G159) and operating condition setting request (Y9) Switch to the offset/gain setting mode. Sets 4144H to buffer memory address 158. Sets 964H to buffer memory address 159. Turns ON operating condition setting request (Y9). Turns OFF operating condition setting request (Y9) Common program Switches to normal mode Sets 964H to buffer memory address 158. Sets 4144H to buffer memory address 159. Turns ON operating condition setting request (Y9). Turns OFF operating condition setting request (Y9). Processing normal mode (c) When switching the mode by making intelligent function module switch setting Only the common program is necessary

86 4 SETUP AND PROCEDURES BEFORE OPERATION 4.7 Cold Junction Temperature Compensation Yes/No Setting The Q64TD/Q64TDV-GH can perform the following two different cold junction temperature compensations by making intelligent function module switch setting (switch 4) to select whether a cold junction temperature compensation will be made or not using the Pt100 temperature-measuring resistor. (1) Pt100 temperature-measuring resistor is used to perform cold junction temperature compensation (cold junction temperature compensation set for "Yes") A cold junction temperature compensation using the Pt100 temperaturemeasuring resistor attached to the Q64TD/Q64TDV-GH is made automatically. Q64TD Object whose temperature is to be measured RUN ERROR Pt Compensation conductor (copper) Thermocouple (2) Cold junction temperature compensation is performed externally (cold junction temperature compensation set for "No") Use this compensation when you want to make temperature measurement at so high accuracy that the cold junction temperature compensation accuracy using the Pt100 temperature-measuring resistor attached to the Q64TD/Q64TDV-GH cannot be ignored as an error. By providing a precision ice bath externally, the thermoelectromotive force generated at the tip of the thermocouple can be led to this module without any change, improving the cold junction temperature compensation accuracy. Q64TD Object whose temperature is to be measured RUN Pt100 ERROR Copper Compensation conductor (copper) Thermocouple Ice bath POINT The ice bath is designed to connect the thermocouple and conductor in the pot whose internal temperature is controlled to be 0 C. Hence, the thermoelectromotive force at the contact portion of the thermocouple and conductor will be 0mV, preventing the generation of extra thermoelectromotive force which can cause errors. Use the accessory Pt100 temperature-measuring resistor as it is connected

87 5 UTILITY PACKAGE (GX Configurator-TI) 5 UTILITY PACKAGE (GX Configurator-TI) 5.1 Utility Package Functions Table 5.1 shows a list of the utility package functions. Table 5.1 Utility Package (GX Configurator-TI) Function List Function Description (1) Make initial setting for operating the Q64TD/Q64TDV-GH channel-by-channel. Set the values of the items which require initial setting. Conversion Enable/Disable Setting Warning Output Upper Lower Limit Value Sampling Averaging Processing Selection Warning Output Upper Upper Limit Value Time/Count Averaging Selection Scaling Range Lower Limit Value Time/Count Averaging Setting Scaling Range Upper Limit Value Warning Output Enable/Disable Setting Scaling Width Lower Limit Value Initial setting Thermocouple Type (Q64TD) Scaling Width Upper Limit Value Setting Range (Q64TDV-GH) Conversion setting for disconnection detection Warning Output Lower Lower Limit Value Conversion setting value for disconnection Warning Output Lower Upper Limit Value detection (2) The data for which initial setting has been completed is registered in the parameters for the programmable controller CPU, and automatically written to the Q64TD/Q64TDV-GH when the programmable controller CPU changes to the RUN status. (1) Set the automatically refreshed Q64TD/Q64TDV-GH buffer memory channel-by-channel. Conversion Completion Flag Error Code CH Measured Temperature Value (Q64TD) Setting Range (Q64TD) CH Measured Temperature Value/ Micro Signal Range 1 (Q64TDV-GH) Voltage Conversion Value (Q64TDV-GH) Warning Output Flag Automatic refresh Disconnection Detection Flag CH Scaling Value (2) The values stored in the Q64TD/Q64TDV-GH buffer memory where automatic refresh setting was made are automatically read or written when the END instruction of the programmable controller CPU is executed. Reference section Section 5.4 Section

88 5 UTILITY PACKAGE (GX Configurator-TI) Function Description Monitors and tests the buffer memory and I/O signals for the Q64TD/Q64TDV-GH. Module Ready Operating Condition Setting Completion Signal Operating Condition Setting Request Offset/gain Setting Mode Status Flag User Range Write Request Disconnection Detection Signal (1) CH Monitor/Test Conversion Enable/Disable Setting Sampling/Averaging Processing Selection Time/Count Averaging Selection Time/Count Averaging Setting Conversion Completion Flag Measured Temperature Value (Q64TD) Measured Temperature Value/Micro Voltage Conversion Value (Q64TDV-GH) Error Code Thermocouple Type (Q64TD) Setting Range 1 (Q64TDV-GH) Warning Output Enable/Disable Setting Warning Output Flag Lower Limit Value (Q64TD) Warning Output Flag Upper Limit Value Warning Output Signal Conversion Completion Flag Error Signal Error Clear Request Warning Output Lower Lower Limit Value Warning Output Lower Upper Limit Value Warning Output Upper Lower Limit Value Warning Output Upper Upper Limit Value Disconnection Detection Flag Scaling Value Scaling Range Lower Limit Value Scaling Range Upper Limit Value Scaling Width Lower Limit Value Scaling Width Upper Limit Value Conversion setting for disconnection detection 2 Conversion setting value for disconnection detection 2 Reference section 5 Monitor/test (2) Offset/Gain Setting Mode Switching Setting Mode Switching Setting Status CH Thermocouple Type (Q64TD) CH Setting Range 1 (Q64TDV-GH) CH Offset Temperature Setting Value (Q64TD) CH Offset Setting Value (Q64TDV-GH) CH Offset Setting Request CH Gain Temperature Setting Value (Q64TD) (3) X/Y Monitor/Test CH Gain Setting Value (Q64TDV-GH) CH Gain Setting Request CH Measured Temperature Value (Q64TD) CH Measured Temperature Value/Micro Voltage Conversion Value (Q64TDV-GH) User Range Write Request Offset/Gain Setting Mode Status Flag Section 5.6 Xn0: Module Ready Xn1: CH1 Offset/Gain Setting Status Signal Xn2: CH2 Offset/Gain Setting Status Signal Xn3: CH3 Offset/Gain Setting Status Signal Xn4: CH4 Offset/Gain Setting Status Signal Xn9: Operating Condition Setting Completion Signal XnA: Offset/Gain Setting Mode Status Flag XnC: Disconnection Detection Flag XnD: Warning Output Signal XnE: Conversion Completion Flag (4) OMC refresh CH Factory default offset/gain value CH User range settings thermal EMF offset/gain value OMC refresh data write request XnF: Error Flag Yn1: CH1 Offset Setting Request Yn2: CH1 Gain Setting Request Yn3: CH2 Offset Setting Request Yn4: CH2 Gain Setting Request Yn5: CH3 Offset Setting Request Yn6: CH3 Gain Setting Request Yn7: CH4 Offset Setting Request Yn8: CH4 Gain Setting Request Yn9: Operating Condition Setting Request YnA: User Range Write Request YnF: Error Clear Request CH User range settings offset/gain value OMC refresh data read request POINT 1 To make initial and automatic refresh settings, a maximum of 76 bytes are required for the intelligent function module parameters per module. 2 Monitoring only is available. The tests are not executable

89 5 UTILITY PACKAGE (GX Configurator-TI) 5.2 Installing and Uninstalling the Utility Package Handling precautions For how to install or uninstall the utility package, refer to "Method of installing the MELSOFT Series" included in the utility package. The following explains the precautions on using the GX Configurator-TI: (1) For safety Since GX Configurator-TI is add-in software for GX Developer, read "Safety Precautions" and the basic operating procedures in the GX Developer Operating Manual. (2) About installation The GX Configurator-TI is add-in software for GX Developer Version 4 or later. Therefore, GX Configurator-TI must be installed on the personal computer that has already GX Developer Version 4 or later installed. (3) Screen error of Intelligent function module utility Insufficient system resource may cause the screen to be displayed inappropriately while using the Intelligent function module utility. If this occurs, close the Intelligent function module utility, GX Developer (program, comments, etc.) and other applications, and then start GX Developer and Intelligent function module utility again. (4) To start the Intelligent function module utility (a) In GX Developer, select "QCPU (Q mode)" for PLC series and specify a project. If any PLC series other than "QCPU (Q mode)" is selected, or if no project is specified, the Intelligent function module utility will not start. (b) Multiple Intelligent function module utilities can be started. However, [Open parameters] and [Save parameters] operations under [Intelligent function module parameter] are allowed for one Intelligent function module utility only. Only the [Monitor/test] operation is allowed for the other utilities (5) Switching between two or more Intelligent function module utilities When two or more Intelligent function module utility screens cannot be displayed side by side, select a screen to be displayed on the top of others using the task bar

90 5 UTILITY PACKAGE (GX Configurator-TI) (6) Number of parameters that can be set in GX Configurator-TI When multiple intelligent function modules are mounted, the number of parameter settings must not exceed the following limit. When intelligent function modules are installed to: Maximum number of parameter settings Initial setting Auto refresh setting Q00J/Q00/Q01CPU Q02/Q02H/Q06H/Q12H/Q25HCPU Q02PH/Q06PH/Q12PH/Q25PHCPU Q12PRH/Q25PRHCPU Q00UJ/Q00U/Q01UCPU Q02UCPU Q03UD/Q04UDH/Q06UDH/ Q10UDH/Q13UDH/Q20UDH/ Q26UDH/Q03UDE/Q04UDEH/ Q06UDEH/Q10UDEH/Q13UDEH/ Q20UDEH/Q26UDEHCPU CPU module other than the above N/A N/A MELSECNET/H remote I/O station For example, if multiple intelligent function modules are installed to the MELSECNET/H remote I/O station, configure the settings in GX Configurator-TI so that the number of parameter settings for all the intelligent function modules does not exceed the limit of the MELSECNET/H remote I/O station. Calculate the total number of parameter settings separately for the initial setting and for the auto refresh setting. The number of parameters that can be set for one module in GX Configurator-TI is as shown below. Target module Initial setting Auto refresh setting Q64TD 6 (Fixed) 13 (Max.) Q64TDV-GH 6 (Fixed) 13 (Max.) Example) Counting the number of parameter settings in Auto refresh setting This one row is counted as one setting. Blank rows are not counted. Count up all the setting items on this screen, and add the total to the number of settings for other intelligent function modules to get a grand total

91 5 UTILITY PACKAGE (GX Configurator-TI) Operating environment This section explains the operating environment of the personal computer that runs GX Configurator-TI. Item Description Installation (Add-in) target 1 Add-in to GX Developer Version 4 (English version) or later 2 4 Computer A personal computer with any of the operating systems below CPU Required memory Refer to the next page "Operating system and performance required for personal computer". Hard disk For installation 65 MB or more space 3 For operation 10 MB or more Display dots or more resolution 3 Microsoft Windows 95 Operating System (English version) Operating system Microsoft Windows 98 Operating System (English version) Microsoft Windows Millennium Edition Operating System (English version) Microsoft Windows NT Workstation Operating System Version 4.0 (English version) Microsoft Windows 2000 Professional Operating System (English version) Microsoft Windows XP Professional Operating System (English version) Microsoft Windows XP Home Edition Operating System (English version) Microsoft Windows Vista Home Basic Operating System (English version) Microsoft Windows Vista Home Premium Operating System (English version) Microsoft Windows Vista Business Operating System (English version) Microsoft Windows Vista Ultimate Operating System (English version) Microsoft Windows Vista Enterprise Operating System (English version) Microsoft Windows 4 7 Starter Operating System (English version) Microsoft Windows 4 7 Home Premium Operating System (English version) Microsoft Windows 4 7 Professional Operating System (English version) Microsoft Windows 4 7 Ultimate Operating System (English version) Microsoft Windows 4 7 Enterprise Operating System (English version) 1: Install GX Configurator-TI in GX Developer Version 4 or higher in the same language. GX Developer (English version) and GX Configurator-TI (Japanese version) cannot be used in combination, and GX Developer (Japanese version) and GX Configurator-TI (English version) cannot be used in combination. 2: GX Configurator-TI is not applicable to GX Developer Version 3 or earlier. 3: When Windows Vista or Windows 7 is used, resolution of dots or more is recommended. 4: When 32-bit Windows 7 is used, add GX Configurator-TI Version 1.28AE or later in GX Developer Version 8.91V or later. When 64-bit Windows 7 is used, add GX Configurator-TI Version 1.28AE or later in GX Developer Version 8.98C or later

92 5 UTILITY PACKAGE (GX Configurator-TI) Operating system and performance required for personal computer Operating system Performance required for personal computer CPU Memory Windows 95 Pentium 133MHz or more 32MB or more Windows 98 Pentium 133MHz or more 32MB or more Windows Me Pentium 150MHz or more 32MB or more Windows NT Workstation 4.0 Pentium 133MHz or more 32MB or more Windows 2000 Professional Pentium 133MHz or more 64MB or more Windows XP Pentium 300MHz or more 128MB or more Windows Vista Pentium 1GHz or more 1GB or more Windows 7 Pentium 1GHz or more 1 GB or more (32-bit) 2 GB or more (64-bit) POINT The following functions cannot be used when the computer is running under Windows XP, Windows Vista, and Windows 7. This product may not perform properly, when these functions are used. Activating the application with Windows compatible mode Simplified user switch-over Remote desktop Large font size (Advanced setting of Display Properties) DPI setting other than 100% 64-bit edition *1 Windows XP Mode Windows Touch *1 This function can be used for Windows 7. A user with USER authority or higher can access GX Configurator-TI for Windows Vista

93 5 UTILITY PACKAGE (GX Configurator-TI) 5.3 Utility Package Operation Common utility package operations (1) Control keys Special keys that can be used for operation of the utility package and their applications are shown in the table below. Key Esc Tab Ctrl Delete Back Space Application Cancels the current entry in a cell. Closes the window. Moves between controls in the window. Used in combination with the mouse operation to select multiple cells for test execution. Deletes the character where the cursor is positioned. When a cell is selected, clears all of the setting contents in the cell. Deletes the character where the cursor is positioned. Moves the cursor. Page Up Page Down Enter Moves the cursor one page up. Moves the cursor one page down. Completes the entry in the cell. (2) Data created with the utility package The following data or files that are created with the utility package can be also handled in GX Developer. Figure 5.1 shows respective data or files are handled in which operation. <Intelligent function module parameter> (a) This represents the data created in Auto refresh setting, and they are stored in an intelligent function module parameter file in a project created by GX Developer. Project Program Parameter PLC Parameter Network Parameter Intelligent Function Module Parameter

94 5 UTILITY PACKAGE (GX Configurator-TI) (b) Steps 1) to 3) shown in Figure 5.1 are performed as follows: <Text files> 1) From GX Developer, select: [Project] [Open project] / [Save]/ [Save as] 2) On the intelligent function module selection screen of the utility, select: [Intelligent function module parameter] [Open parameters] / [Save parameters] 3) From GX Developer, select: [Online] [Read from PLC] / [Write to PLC] "Intelligent function module parameters" Alternatively, from the intelligent function module selection screen of the utility, select: [Online] [Read from PLC] / [Write to PLC] (a) A text file can be created by clicking the Make text file button on the initial setting, Auto refresh setting, or Monitor/Test screen. The text files can be utilized to create user documents. GX Developer /GX Configurator-TI Project Disk Project 1) A 2) A Personal computer B QCPU Q25HCPU MODE. RUN. ERR. USER. BAT. BOOT. A 3) A: Intelligent function module parameters B: Data saved by "Make text file" USB RS-232 Figure 5.1 Correlation chart for data created with the utility package

95 5 UTILITY PACKAGE (GX Configurator-TI) Operation overview GX Developer screen Screen for selecting a target intelligent function module [Tools] [Intelligent function utility] [Start] Refer to Section Initial setting Enter "Start I/O No.", and select "Module type" and "Module model name". Auto refresh 1) Initial setting screen Automatic refresh setting screen Refer to Section 5.4. Refer to Section

96 5 UTILITY PACKAGE (GX Configurator-TI) 1) [Online] [Monitor/Test] Selecting monitor/test module screen Monitor/Test screen Select a module to be monitored/tested. Refer to Section

97 5 UTILITY PACKAGE (GX Configurator-TI) Starting the Intelligent function module utility [Operating procedure] Intelligent function module utility is started from GX Developer. [Tools] [Intelligent function utility] [Start] [Setting screen] [Explanation of items] (1) Activation of other screens Following screens can be displayed from the intelligent function module utility screen. (a) Initial setting screen "Start I/O No. 1 " " Module type" "Module model name" Initial setting (b) Auto refresh setting screen "Start I/O No. 1 " " Module type" "Module model name" Auto refresh (c) Select monitor/test module screen [Online] [Monitor/Test] 1 Enter the start I/O No. in hexadecimal. (2) Command buttons Delete Exit Deletes the initial setting and auto refresh setting of the selected module. Closes this screen

98 5 UTILITY PACKAGE (GX Configurator-TI) (3) Menu bar (a) File menu Intelligent function module parameters of the project opened by GX Developer are handled. [Open : Reads a parameter file. parameters] [Close : Closes the parameter file. If any data are modified, a parameters] dialog asking for file saving will appear. [Save : Saves the parameter file. parameters] [Delete : Deletes the parameter file. parameters] [Exit] : Closes this screen. (b) Online menu [Monitor/ Test] : Activates the Select monitor/test module screen. [Read from PLC] : Reads the intelligent function module parameters from the CPU module. [Write to PLC] : Writes the intelligent function module parameters to the CPU module. POINT (1) Saving intelligent function module parameters in a file Since intelligent function module parameters cannot be saved in a file by the project saving operation of GX Developer, save them on the shown module selection screen for intelligent function module parameter setting. (2) Reading/writing intelligent function module parameters from/to a programmable controller CPU using GX Developer (a) Intelligent function module parameters can be read from and written into the programmable controller CPU after having been saved in a file. (b) Set the target programmable controller CPU in GX Developer: [Online] [Transfer setup]. (c) When the Q64TD/Q64TDV-GH is installed to the remote I/O station, use "Read from PLC" and "Write to PLC". (3) Checking the required utility While the start I/O is displayed on the Intelligent function module utility setting screen, " " may be displayed for the model name. This means that the required utility has not been installed or the utility cannot be started from GX Developer. Check the required utility, selecting [Tools] - [Intelligent function utility] - [Utility list...] in GX Developer

99 5 UTILITY PACKAGE (GX Configurator-TI) 5.4 Initial Setting [Purpose] Make initial setting for operating the Q64TD/Q64TDV-GH on each channel. Refer to Section 5.1 for the initial setting parameter types. Parameter setting in the initial setting window omits parameter setting through a sequence program. [Operating procedure] 1 "Start I/O No." "Module type" "Module model name" Initial setting 1 Enter the start I/O No. in hexadecimal. [Setting screen] [Explanation of items] (1) Setting contents Set whether temperature conversion is enabled or disabled and the temperature conversion method for each channel. (2) Command button Make text file End setup Cancel Creates a file containing the screen data in text file format. Saves the set data and ends the operation. Cancels the setting and ends the operation. POINT Initial settings are stored in the intelligent function module parameters. After being written to the CPU module, the initial setting is made effective by either (1) or (2). (1) Cycle the RUN/STOP switch of the CPU module: STOP RUN STOP RUN. (2) With the RUN/STOP switch set to RUN, turn off and then on the power or reset the CPU module. When using a sequence program to write the initial settings, when the CPU is switched from STOP to RUN the initial settings will be written, So ensures that programming is carried out to re-execute the initial settings

100 5 UTILITY PACKAGE (GX Configurator-TI) 5.5 Auto Refresh Settings [Purpose] Configure the Q64TD/Q64TDV-GH's buffer memory for automatic refresh. [Operating procedure] 1 "Start I/O No. " "Module type" "Module model name" Auto refresh 1 Enter the start I/O No. in hexadecimal. [Setting screen] [Explanation of items] (1) Items Model side Buffer size : Displays the buffer memory size of the setting item that can be transferred (fixed at one word). Model side Transfer word count : Displays the number of words to transfer the CPU device from the head device (fixed at one word). Transfer direction : " " indicates that data are written from the device to the buffer memory. " " indicates that data are loaded from the buffer memory to the device. PLC side Device : Enter a CPU module side device that is to be automatically refreshed. Applicable devices are X, Y, M, L, B, T, C, ST, D, W, R, and ZR. When using bit devices X, Y, M, L or B, set a number that can be divided by 16 points (examples: X10, Y120, M16, etc.) Also, buffer memory data are stored in a 16- point area, starting from the specified device number. For example, if X10 is entered, data are stored in X10 to X1F

101 5 UTILITY PACKAGE (GX Configurator-TI) (2) Command buttons Make text file End setup Cancel Creates a file containing the screen data in text file format. Saves the set data and ends the operation. Cancels the setting and ends the operation. POINT Auto refresh settings are stored in the intelligent function module parameters. After being written to the CPU module, the auto refresh settings are made effective by either (1) or (2). (1) Cycle the RUN/STOP switch of the CPU module: STOP RUN STOP RUN. (2) With the RUN/STOP switch set to RUN, turn off and then on the power or reset the CPU module. Auto refresh settings cannot be changed through a sequence program. Although, processing that is equivalent to auto refresh can be added using the FROM/TO instruction in a sequence program

102 5 UTILITY PACKAGE (GX Configurator-TI) 5.6 Monitoring/Test Monitor/test screen [Purpose] Start buffer memory monitoring/testing, I/O signal monitoring/testing, offset/gain settings (refer to Section 5.6.2, 5.6.3) and pass data (refer to Section 5.6.4) from this screen. [Operating procedure] "Select monitor/test module" screen "Start I/O No." "Module type" "Module model name" Monitor/test 1 Enter the start I/O No. in hexadecimal. The screen can also be started from System monitor of GX Developer Version 6 or later. Refer to the GX Developer Operating Manual for details. [Setting screen] 1 1) CH Monitor/Test Offset/Gain Setting

103 5 UTILITY PACKAGE (GX Configurator-TI) 1) X/Y Monitor/Test OMC refresh

104 5 UTILITY PACKAGE (GX Configurator-TI) [Explanation of items] (1) Items Setting item Current value Setting value : Displays I/O signals and buffer memory names. : Monitors the I/O signal states and present buffer memory values. : Enter or select the data to be written into the buffer memory for test operation. (2) Command buttons Current value display Make text file Start monitor / Stop monitor Execute test Close Displays the current value of the item selected. (This is used to check the text that cannot be displayed in the current value field. However, in this utility package, all items can be displayed in the display fields). Creates a file containing the screen data in text file format. Selects whether or not to monitor current values. Performs a test on the selected items. To select more than one item, select them while holding down the Ctrl key. Closes the currently open screen and returns to the previous screen. (3) Example of using "Execute test" The following is an example to change sampling processing to count averaging processing in 10 times. (a) Set "Averaging" in the setting value field for Sampling/Averaging processing selection. (b) Set a count value in the setting value field for "Time/Count averaging setting". At this point, the set data have not been written to the Q64TD/Q64TDV-GH. (c) Select the setting value fields that were specified in steps (a) and (b) while holding down the Ctrl key. (d) Click Execute test to execute data writing. Once the writing is completed, the written values are displayed in the current value fields

105 5 UTILITY PACKAGE (GX Configurator-TI) Offset/gain setting operation (Function version C or later) Perform the offset/gain setting operation in the following sequence. (1) Using a user range setting Specify a user range setting for Switch 2 of the intelligent function module switch setting. (Refer to Section 4.5.) (2) Switch to the offset/gain setting screen Display the offset/gain setting screen using the operation described in Section (3) Switch to the offset/gain setting mode Set "Offset/gain setting mode" in the Setting value field of Mode Switching Setting and click the Execute test button to perform write. On completion of write, the indication in the Current value field of Mode Switching Setting Status changes to "Offset/gain setting mode". (4) Adjustment of the offset and gain values (a) Offset value adjustment 1) Set the offset value Enter the desired value into the Setting value field for CH Offset Setting Value, and click the Execute test button. 2) Determine the offset value Select "Request" from the Setting value field for CH Offset Setting Request, and click the Execute test button. After making sure that CH offset/gain setting status signal (X1, X2, X3, X4) has turned off, select "OFF" from the Setting value field for CH Offset Setting Request, and click the Execute test button. (b) Gain value adjustment 1) Set the gain value Enter the desired value into the Setting value field for CH Gain Setting Value, and click the Execute test button. 2) Determine the gain value Select "Request" from the Setting value field for CH Gain Setting Request, and click the Execute test button. After making sure that CH offset/gain setting status signal (X1, X2, X3, X4) has turned off, select "OFF" from the Setting value field for CH Gain Setting Request, and click the Execute test button. (c) To set the offset/gain for more than one channel, repeat steps (a) and (b)

106 5 UTILITY PACKAGE (GX Configurator-TI) (5) Write the offset/gain setting values to the module Write the offset/gain settings to the module after completing the settings for all channels using the user range setting. Note that if settings are written while offset/gain settings are incomplete, the status at that point will be written to the module. (a) How to write the values 1) Write to the Q64TD/Q64TDV-GH Select "Request" from the Setting value field for User Range Write POINT Request, and click the Execute test button. 2) Confirm the execution of writing Confirm that the indication of the Current value field for Offset/gain Setting Mode Status Flag changes from "Completed" to "Writing ". 3) Finish writing Select "OFF" from the Setting value field for User Range Write Request, and click the Execute test button. While the set data of the steps (a)1) to (a)2) above are written to the module, do not perform the operations below. If they are performed, the data inside E 2 PROM will have a problem, and the Q64TD/Q64TDV-GH may not operate normally. Powering off the programmable controller CPU Resetting the programmable controller CPU (b) Error handling Confirm that the ERR. LED for the Q64TD/Q64TDV-GH is off. If the ERR. LED is lit, click on Close, check the error code on the monitor screen, and then perform the offset/gain settings again. (6) Switch to the normal mode Set "Normal mode" in the Setting value field of Mode Switching Setting and click the Execute test button to perform write. On completion of write, the indication in the Current value field of Mode Switching Setting Status changes to "Normal mode"

107 5 UTILITY PACKAGE (GX Configurator-TI) Offset/gain setting operation (Function version B) Perform the offset/gain setting operation in the following sequence. (1) Switch to the offset/gain setting mode Change switch 4 for intelligent function module switch setting to the offset/gain setting mode and switch 2 to the user range setting. (Refer to Section 4.5) (2) Switch to the offset/gain setting screen Display the offset/gain setting screen using the operation described in Section (3) Adjustment of the offset and gain values (a) Set the offset value Enter the desired value into the Setting value field for CH Offset Setting Value, and click the Execute test button. (b) Determine the offset value Select "Request" from the Setting value field for CH Offset Setting Request, and click the Execute test button. After making sure that CH offset/gain setting status signal (X1, X2, X3, X4) has turned off, select "OFF" from the Setting value field for CH Offset Setting Request, and click the Execute test button. (c) Set the gain value Enter the desired value into the Setting value field for CH Gain Setting Value, and click the Execute test button. (d) Determine the gain value Select "Request" from the Setting value field for CH Gain Setting Request, and click the Execute test button. After making sure that CH offset/gain setting status signal (X1, X2, X3, X4) has turned off, select "OFF" from the Setting value field for CH Gain Setting Request, and click the Execute test button. (e) To set the offset/gain for more than one channel, repeat steps (a) to (d). (4) Write the offset/gain setting values to the module Write the offset/gain settings to the module after completing the settings for all channels using the user range setting. Note that if settings are written while offset/gain settings are incomplete, the status at that point will be written to the module. (a) How to write the values 1) Write to the Q64TD/Q64TDV-GH Select "Request" from the Setting value field for User Range Write Request, and click the Execute test button. 2) Confirm the execution of writing Confirm that the indication of the Current value field for Offset/gain Setting Mode Status Flag changes from "Completed" to "Writing "

108 5 UTILITY PACKAGE (GX Configurator-TI) POINT 3) Finish writing Select "OFF" from the Setting value field for User Range Write Request, and click the Execute test button. While the set data of the steps (a)1) to (a)2) above are written to the module, do not perform the operations below. If they are performed, the data inside E 2 PROM will have a problem, and the Q64TD/Q64TDV-GH may not operate normally. Powering off the programmable controller CPU Resetting the programmable controller CPU (b) Error handling Confirm that the ERR. LED for the Q64TD/Q64TDV-GH is off. If the ERR. LED is lit, click on Close, check the error code on the monitor screen, and then perform the offset/gain settings again. (5) Switch to the normal mode Specify the normal mode for Switch 4 of the intelligent function module switch setting. (Refer to Section 4.5.)

109 5 UTILITY PACKAGE (GX Configurator-TI) OMC (Online Module Change) refresh data Perform operation in the following sequence to save/restore the user range. (1) Switch to the OMC refresh data screen Perform the operation in Section to display the OMC refresh data screen. (2) User range saving (a) Change the Setting value field of Online Module Change read request to "Request", and click the Execute test button. When read is completed, the values are displayed in the Current value fields of CH Factory default offset/gain value/user range settings offset/gain value/user range settings offset/gain thermal EMF value. (b) Compare the values with those in the range reference table, and take a note of the values if they are correct. Refer to Section 7.4 for the range reference table. (3) User range restoration (a) Set the noted values into the Setting value fields of CH Factory default offset/gain value/user range settings offset/gain value/user range settings thermal EMF offset/gain value. (b) Select all the Setting value fields of CH Factory default offset/gain input value/user range settings offset/gain value/user range settings thermal EMF offset/gain value, and click the Execute test button. When write is completed, the set values are displayed in the Current value fields of them. (c) Change the Setting value field of online module change write request to "Request", and click the Execute test button. Make sure that the indication in the Current value field of online module change write request changes from "Request" to "OFF" on completion of write

110 6 PROGRAMMING 6 PROGRAMMING This chapter describes Q64TD/Q64TDV-GH programs. When applying any of the program examples introduced in this chapter to the actual system, verify the applicability and confirm that no problems will occur in the system control. 6.1 Programs Used in Normal System Configuration System configuration used to describe programs (1) System configuration 6 (2) Program conditions This program reads the digital values of temperature conversions made on CH1 to CH3 of the Q64TD. Sampling processing is to be set for CH1, and average processing of 500-count timing and 1000ms-interval is for CH2 and CH3 respectively. If a write error occurs, the corresponding error code appears in BCD. Disconnection detection is processed on CH1 only. (a) Initial settings Temperature conversion enabled channel... CH1 to CH3 Sampling channel...ch1 Count-averaging channel... CH2 Time-averaging channel... CH3 (b) Devices used by user Measured temperature value read command signal (Turned on when user wants to read a measured temperature value)... X10 Disconnection detection reset signal... X11 Error reset signal (Turned on when user wants to make error reset)... X12 Error code display (BCD 3 digits)... Y40 to Y4B Conversion completion flag... M0 to M2 Module ready check flag... M100 Measured temperature value (16-bit)... D1 to D3 (D11 to D13) Disconnection detection flag... D4, M10 Error code storage... D5 POINT (1) Refer to Section 3.3 for the I/O signals (X0 to XF, Y0 to YF). (2) Perform the disconnection detection reset operation after the connection is reestablished

111 6 PROGRAMMING Program example when utility package is used (1) Operation of utility package (a) Initial setting (Refer to Section 5.4) Set sampling processing for CH1, and averaging processing of 500-count timing and 1000ms-interval for CH2 and CH3 respectively. (b) Automatic refresh settings (Refer to Section 5.5) Set devices to store CH1 to CH3 Measured temperature values, error code, and disconnection detection flag. 6 (c) Write of intelligent function module parameters (Refer to Section 5.3.3) Write the intelligent function module parameters to the CPU module. Perform this operation on the parameter setting unit selection screen

112 6 PROGRAMMING (2) Program example Program example when utility package is not used

113 6 PROGRAMMING 6.2 Programs Used on Remote I/O Network System configuration used to describe programs (1) System configuration (2) Program conditions This program was written for the CPU on the remote master station to read the digital values of temperature conversions made on CH1 to CH3 of the Q64TD. Sampling processing is to be set for CH1, and average processing of 500-count timing and 1000ms-interval is for CH2 and CH3 respectively. If a write error occurs, the corresponding error code appears in BCD. Disconnection detection is processed on CH1 only. (3) Initial settings Temperature conversion enabled channel... CH1 to CH3 Sampling channel... CH1 Count averaging channel... CH2 Time averaging channel... CH3 CH2 averaging count times CH3 averaging time ms (1s) (4) Devices used by user Initial setting request signal... X20 Measured temperature value read command signal (Turned on when user wants to read a measured temperature value)... X21 Disconnection detection reset signal... X22 Error reset signal (Turned on when user wants to make error reset)... X23 Error code display (BCD 3 digits)... Y30 to Y3B Conversion completion flag... W0, M0 to M2 CH1 to 3 measured temperature value (16-bit)... D1 to D3 (W1 to W3) Disconnection detection flag... W4, M20 Error code storage... W

114 6 PROGRAMMING POINT (1) Refer to Section 3.3 for the I/O signals (X120 to X12F, Y120 to Y12F). (2) Perform the disconnection detection reset operation after the connection is reestablished. (3) For details on the MELSECNET/H remote I/O network, refer to the Q Corresponding MELSECNET/H Network System Reference Manual (Remote I/O network)

115 6 PROGRAMMING Program example when utility package is used (1) Operation of GX Developer (a) Setting of CPU parameters Network type First I/O No. :0000H Network No. :1 Total number of (slave) stations :1 Mode :Online Network range assignment : :MNET/H (remote master) Refresh parameters: (2) Operation of utility package Perform operation on the remote I/O station side. Operate the utility package on the remote I/O station side. Set the following in the Intelligent function module parameter setting module select area. Start I/O No. : 20 Module type : Thermocouple Input Module Module model name: Q64TD / Q64TDV-GH (a) Initial setting (Refer to Section 5.4) Set sampling processing for CH1, and averaging processing of 500-count timing and 1000ms-interval for CH2 and CH3 respectively

116 6 PROGRAMMING (b) Automatic refresh settings (Refer to Section 5.5) Set devices to store CH1 to CH3 Measured temperature values, error code, and disconnection detection flag. (c) Write of intelligent function module parameters (refer to Section 5.3.3) The intelligent function module parameters are written to the remote I/O station. Perform this operation on the parameter setting unit selection screen. (3) Program example POINT To write the intelligent function module parameters, set the target remote I/O station from [Online] - [Transfer setup] on GX Developer. They can be written by: Directly connecting GX Developer to the remote I/O station. Connecting GX Developer to another device such as a CPU module and passing through the network

117 6 PROGRAMMING Program example when utility package is not used POINT The dedicated instructions used for reading/writing the buffer memory of the intelligent function module on a remote I/O station (REMTO and REMFR) are the execution type for which several scans are needed. Therefore, transmissions of the execution results are not synchronized with the I/O signal operations. When reading a measured temperature value on an Q64TD after changing the operating condition during operation, be sure to read the Conversion completed flag (buffer memory address 10) at the same time. Also, for the case of changing the operating condition, insert an interlock to prevent the execution of the REMFR instruction. (1) Operation of GX Developer (Setting of CPU parameters) Network type : MNET/H (remote master) First I/O No : 0000H Network No : 1 Total number of (slave) stations : 1 Mode : Online Network range assignment : Refresh parameters:

118 6 PROGRAMMING (2) Program example

119 6 PROGRAMMING

120 7 ONLINE MODULE CHANGE 7 ONLINE MODULE CHANGE When changing a module online, read the following manual. QCPU User's Manual (Hardware Design, Maintenance and Inspection) This chapter describes the specifications of an online module change. (1) Perform an online module change by operating GX Developer. (2) To ensure ease of offset/gain re-setting, there is a user range save/restoration function that is performed by executing the dedicated instruction or read/write from/to buffer memory. 7 POINT (1) Perform an online module change after making sure that the system outside the programmable controller will not malfunction. (2) To prevent an electric shock and malfunction of operating modules, provide means such as switches for powering off each of the external power supply and external devices connected to the module to be replaced online. (3) After the module has failed, data may not be saved properly. Referring to Section , therefore, prerecord the data to be saved (Factory default offset/gain value/user range settings offset/gain value/user range settings thermal EMF offset/gain value in the buffer memory). (4) It is recommended to perform an online module change in the actual system in advance to ensure that it would not affect the other modules by checking the following: Means of cutting off the connection to external devices and its configuration are correct. Switching ON/OFF does not bring any undesirable effect. (5) Do not install/remove the module to/from the base unit, or the terminal block to/from the module more than 50 times after the first use of the product. (IEC compliant) Failure to do so may cause malfunction. (Note) The dedicated instruction cannot be executed during an online module change. When using the dedicated instruction to execute save/restoration, therefore, execute save/restoration in the other system 1. If the other system is unavailable, execute restoration by performing write to the buffer memory. 1 If the module is mounted on the remote I/O station, execute save/restoration in the other system mounted on the main base unit. (Save/restoration cannot be executed in the other system mounted on the remote I/O station.)

121 7 ONLINE MODULE CHANGE 7.1 Online Module Change Conditions The CPU, MELSECNET/H remote I/O module, Q64TD/Q64TDV-GH, GX Developer and base unit given below are needed to perform an online module change. (1) CPU The Process CPU or Redundant CPU is required. For precautions for multiple CPU system configuration, refer to the QCPU User's Manual (Multiple CPU System). For precautions on redundant system configuration, refer to the QnPRHCPU User's Manual (Redundant System). (2) MELSECNET/H remote I/O module The module of function version D or later is necessary. (3) Q64TD/Q64TDV-GH The module of function version C or later is necessary. (4) GX Developer GX Developer of Version 7.10L or later is necessary. GX Developer of Version 8.18U or later is required to perform an online module change on the remote I/O station. (5) Base unit 1) When the slim type main base unit (Q3 SB) is used, an online module change cannot be performed. 2) When the power supply module unnecessary type extension base unit (Q5 B) is used, online module change cannot be performed for the modules on all the base units connected

122 7 ONLINE MODULE CHANGE 7.2 Online Module Change Operations The following gives the operations performed for an online module change. CPU operation : Executed : Not executed X/Y refresh FROM/TO instruction 1 Dedicated instruction Device test GX Configurator Initial setting parameter Monitor/ test (User operation) (Intelligent function module operation) 1 Access to the intelligent function module device (U \G ) is included. 2 In the absence of the operation marked 2, the operation of the intelligent function module is the operation performed prior to that

123 7 ONLINE MODULE CHANGE 7.3 Online Module Change Procedure There are the following online module change procedures depending on whether the user range setting has been made or not, whether the initial setting of GX Configurator- TI has been made or not, and whether the other system exists or not. Range setting Initial setting Other system Reference section Factory setting GX Configurator-TI Section Factory setting Sequence program Section User range setting GX Configurator-TI Present Section User range setting GX Configurator-TI Absent Section User range setting Sequence program Present Section User range setting Sequence program Absent Section When factory default is used and initial setting was made with GX Configurator-TI (1) Conversion disable (a) Set conversion enable/disable setting (buffer memory address 0: Un\G0) for all channel conversion disable and turn Operating Condition Setting Request (Y9) from OFF to ON to stop conversion. After confirming that conversion has stopped with the Conversion Completion Flag (buffer memory address 10: Un\G10), turn off Operating Condition Setting Request (Y9)

124 7 ONLINE MODULE CHANGE (2) Dismounting of module (a) After choosing [Diagnosis] - [Online module change] on GX Developer to enter the "Online module change" mode, double-click the module to be changed online to display the "Online module change" screen. (b) Click the "Execution" button to enable a module change. If the following error screen appears, click the [OK] button, dismount the module, and mount a new module. (c) After confirming that the "RUN" LED of the module has turned off, remove the external wiring and dismount the module. POINT (1) If you have removed the wiring together with the terminal block, the measured temperature values may vary within the accuracy range due to the error of the specific cold junction compensation resistor. (2) Always dismount the module. If you execute mounting confirmation without dismounting the module, the module will not start properly and the "RUN" LED will not be lit

125 7 ONLINE MODULE CHANGE (3) Mounting of new module (a) Mount a new module to the same slot and install the external wiring. (b) After mounting the module, click the [Execution] button and make sure that the "RUN" LED is lit. Module Ready (X0) remains OFF. (4) Operation check (a) To make an operation check, click the [Cancel] button to cancel control resumption. (b) Click the [OK] button to leave the "Online module change" mode

126 7 ONLINE MODULE CHANGE (c) Click the [Close] button to close the System monitor screen. (d) Monitor CH measured temperature value/micro voltage conversion value (buffer memory addresses 11 to 14: Un\G11 to 14) to check that proper conversion has been made

127 7 ONLINE MODULE CHANGE (5) Resumption of control (a) After choosing [Diagnosis] - [Online module change] on GX Developer to redisplay the "Online module change" screen, click the [Execution] button to resume control. Module READY (X0) turns ON. (b) The "Online module change completed" screen appears

128 7 ONLINE MODULE CHANGE When factory default is used and initial setting was made with sequence program (1) Conversion disable (a) Set conversion enable/disable setting (buffer memory address 0: Un\G0) for all channel conversion disable and turn Operating Condition Setting Request (Y9) from OFF to ON to stop conversion. After confirming that conversion has stopped with the Conversion Completion Flag (buffer memory address 10: Un\G10), turn off Operating Condition Setting Request (Y9)

129 7 ONLINE MODULE CHANGE (2) Dismounting of module (a) After choosing [Diagnosis] - [Online module change] on GX Developer to enter the "Online module change" mode, double-click the module to be changed online to display the "Online module change" screen. (b) Click the "Execution" button to enable a module change. If the following error screen appears, click the [OK] button, dismount the module, and mount a new module

130 7 ONLINE MODULE CHANGE (c) After confirming that the "RUN" LED of the module has turned off, remove the external wiring and dismount the module. POINT (1) If you have removed the wiring together with the terminal block, the measured temperature values may vary within the accuracy range due to the error of the specific cold junction compensation resistor. (2) Always dismount the module. If you execute mounting confirmation without dismounting the module, the module will not start properly and the "RUN" LED will not be lit. (3) Mounting of new module (a) Mount a new module to the same slot and install the external wiring. (b) After mounting the module, click the [Execution] button and make sure that the "RUN" LED is lit. Module Ready (X0) remains OFF. (4) Operation check (a) To make an operation check, click the [Cancel] button to cancel control resumption

131 7 ONLINE MODULE CHANGE (b) Click the [OK] button to leave the "Online module change" mode. (c) Click the [Close] button to close the System monitor screen. (d) (e) Enable the conversion of the channel to be used through conversion enable/disable setting (buffer memory address 0: Un\G0), and monitor CH measured temperature value/micro voltage conversion value (buffer memory addresses 11 to 14: Un\G11 to 14) to check that proper conversion has been made. Since the new module is in a default status, it must be initialized by a sequence program after control resumption. Before performing initialization, check whether the contents of the initialization program are correct or not. 1) Normal system configuration The sequence program should perform initialization on the leading edge of Module READY (X9) of the Q64TD/Q64TDV-GH. When control resumption is executed, Module READY (X0) turns ON and initialization is performed. (If the sequence program performs initialization only one scan after RUN, initialization is not performed.) 2) When used on remote I/O network Insert a user device that will execute initialization at any timing (initialization request signal) into the sequence program. After control resumption, turn ON the initialization request signal to perform initialization. (If the sequence program performs initialization only one scan after a data link start of the remote I/O network, initialization is not performed.)

132 7 ONLINE MODULE CHANGE (5) Resumption of control (a) After choosing [Diagnosis] - [Online module change] on GX Developer to redisplay the "Online module change" screen, click the [Execution] button to resume control. Module READY (X0) turns ON. (b) The "Online module change completed" screen appears

133 7 ONLINE MODULE CHANGE When user range setting is used and initial setting was made with GX Configurator-TI (other system is available) (1) Conversion disable (a) Set conversion enable/disable setting (buffer memory address 0: Un\G0) for all channel conversion disable and turn Operating Condition Setting Request (Y9) from OFF to ON to stop conversion. After confirming that conversion has stopped with the Conversion Completion Flag (buffer memory address 10: Un\G10), turn off Operating Condition Setting Request (Y9)

134 7 ONLINE MODULE CHANGE (2) Dismounting of module (a) After choosing [Diagnosis] - [Online module change] on GX Developer to enter the "Online module change" mode, double-click the module to be changed online to display the "Online module change" screen. (b) Click the "Execution" button to enable a module change. If the following error screen appears, the user range cannot be saved. Click the [OK] button, and perform the operation in Section (2)(c) and later

135 7 ONLINE MODULE CHANGE (c) After confirming that the "RUN" LED of the module has turned off, remove the external wiring and dismount the module. POINT (1) If you have removed the wiring together with the terminal block, the measured temperature values may vary within the accuracy range due to the error of the specific cold junction compensation resistor. (2) Always dismount the module. If you execute mounting confirmation without dismounting the module, the module will not start properly and the "RUN" LED will not be lit. (3) Mounting of new module (a) Mount the dismounted module and new module to the other system. (b) Using the G.OGLOAD instruction, save the user range setting values to the CPU device. Refer to Appendix 2.3 for the G.OGLOAD instruction. (c) Using the G.OGSTOR instruction, restore the user range setting values to the module. Refer to Appendix 2.4 for the G.OGSTOR instruction. (d) Dismount the new module from the other system, mount it to the slot from where the old module was dismounted in the original system, and install the external wiring. (e) After mounting the module, click the [Execution] button and make sure that the "RUN" LED is lit. Module Ready (X0) remains OFF

136 7 ONLINE MODULE CHANGE (4) Operation check (a) To make an operation check, click the [Cancel] button to cancel control resumption. (b) Click the [OK] button to leave the "Online module change" mode. (c) Click the [Close] button to close the System monitor screen

137 7 ONLINE MODULE CHANGE (d) Monitor CH measured temperature value/micro voltage conversion value (buffer memory addresses 11 to 14: Un\G11 to 14) to check that proper conversion has been made. (5) Resumption of control (a) After choosing [Diagnosis] - [Online module change] on GX Developer to redisplay the "Online module change" screen, click the [Execution] button to resume control. Module READY (X0) turns ON. (b) The "Online module change completed" screen appears

138 7 ONLINE MODULE CHANGE When user range setting is used and initial setting was made with GX Configurator-TI (other system is unavailable) (1) Conversion disable (a) Set "Disable" in the Setting value field of Conversion Enable/Disable Setting on the CH Monitor/Test screen of GX Configurator-TI, and click the Execute test button. (b) After making sure that "Disable" is displayed in the Current value field of Conversion Enable/Disable Setting, set "Request" in the Setting value field of Operation Condition Setting Request on the Monitor screen, and click the [Execute test] button to stop conversion. Monitor the Conversion Completion Flag (buffer memory address 10: Un\G10) and confirm that conversion has stopped

139 7 ONLINE MODULE CHANGE (c) POINT If the saved buffer memory contents are not yet prerecorded, record them in the following procedure. 1) Display the OMC refresh data screen of GX Configurator-TI. 2) Make a OMC refresh data read request. (Refer to Section 5.6.4) 3) Compare the current values of the Factory default offset/gain value/user range settings offset/gain value/user range settings thermal EMF offset/gain value with those of the range reference table. Refer to Section 7.4 for the range reference table. 4) If the values are proper, take a note of the Factory default offset/gain value/user range setting offset/gain value/user range settings thermal EMF offset/gain value If the buffer memory values compared with the reference table are not proper, save and restoration of the user range cannot be executed. Before executing module control resumption, make offset/gain setting in the GX Configurator-TI. (Refer to Section ) Note that if module control is resumed without offset/gain setting being made, operation will be performed with the default values. (2) Dismounting of module (a) After choosing [Diagnosis] - [Online module change] on GX Developer to enter the "Online module change" mode, double-click the module to be changed online to display the "Online module change" screen

140 7 ONLINE MODULE CHANGE (b) Click the "Execution" button to enable a module change. If the following error screen appears, the user range cannot be saved. Click the [OK] button, and perform the operation in this section (2) (c) and later. (c) After confirming that the "RUN" LED of the module has turned off, remove the external wiring and dismount the module. POINT (1) If you have removed the wiring together with the terminal block, the measured temperature values may vary within the accuracy range due to the error of the specific cold junction compensation resistor. (2) Always dismount the module. If you execute mounting confirmation without dismounting the module, the module will not start properly and the "RUN" LED will not be lit. (3) Mounting of new module (a) Mount a new module to the same slot and install the external wiring. (b) After mounting the module, click the [Execution] button and make sure that the "RUN" LED is lit. Module Ready (X0) remains OFF

141 7 ONLINE MODULE CHANGE (4) Operation check (a) To make an operation check, click the [Cancel] button to cancel control resumption. (b) Click the [OK] button to leave the "Online module change" mode. (c) Click the [Close] button to close the System monitor screen. (d) On the OMC refresh data screen of GX Configurator-TI, set the prerecorded values and make a OMC refresh data write request. (Refer to Section )

142 7 ONLINE MODULE CHANGE (e) Monitor CH measured temperature value/micro voltage conversion value (buffer memory addresses 11 to 14: Un\G11 to 14) to check that proper conversion has been made. (5) Resumption of control (a) After choosing [Diagnosis] - [Online module change] on GX Developer to redisplay the "Online module change" screen, click the [Execution] button to resume control. Module READY (X0) turns ON. (b) The "Online module change completed" screen appears

143 7 ONLINE MODULE CHANGE When user range setting is used and initial setting was made with sequence program (other system is available) (1) Conversion disable (a) Set conversion enable/disable setting (buffer memory address 0: Un\G0) for all channel conversion disable and turn Operating Condition Setting Request (Y9) from OFF to ON to stop conversion. After confirming that conversion has stopped with the Conversion Completion Flag (buffer memory address 10: Un\G10), turn off Operating Condition Setting Request (Y9)

144 7 ONLINE MODULE CHANGE (2) Dismounting of module (a) After choosing [Diagnosis] - [Online module change] on GX Developer to enter the "Online module change" mode, double-click the module to be changed online to display the "Online module change" screen. (b) Click the "Execution" button to enable a module change. If the following error screen appears, the user range cannot be saved. Click the [OK] button, and perform the operation in Section (2)(c) and later

145 7 ONLINE MODULE CHANGE (c) After confirming that the "RUN" LED of the module has turned off, remove the external wiring and dismount the module. POINT (1) If you have removed the wiring together with the terminal block, the temperature measurement values may vary within the accuracy range due to the error of the specific cold junction compensation resistor. (2) Always dismount the module. If you execute mounting confirmation without dismounting the module, the module will not start properly and the "RUN" LED will not be lit. (3) Mounting of new module (a) Mount the dismounted module and new module to the other system. (b) Using the G(P).OGLOAD instruction, save the user range setting values to the CPU device. Refer to Appendix 2.3 for the G(P).OGLOAD instruction. (c) Using the G(P).OGSTOR instruction, restore the user range setting set values to the module. Refer to Appendix 2.4 for the G(P).OGSTOR instruction. (d) Dismount the new module from the other system, mount it to the slot from where the old module was dismounted in the original system, and install the external wiring. (e) After mounting the module, click the [Execution] button and make sure that the "RUN" LED is lit. Module Ready (X0) remains OFF

146 7 ONLINE MODULE CHANGE (4) Operation check (a) To make an operation check, click the [Cancel] button to cancel control resumption. (b) Click the [OK] button to leave the "Online module change" mode. (c) Click the [Close] button to close the System monitor screen. (d) Enable the conversion of the channel to be used through conversion enable/disable setting (buffer memory address 0: Un\G0), and monitor CH measured temperature value/micro voltage conversion value (buffer memory addresses 11 to 14: Un\G11 to 14) to check that proper conversion has been made

147 7 ONLINE MODULE CHANGE (e) Since the new module is in a default status, it must be initialized by a sequence program after control resumption. Before performing initialization, check whether the contents of the initialization program are correct or not. 1) Normal system configuration The sequence program should perform initialization on the leading edge of Module READY (X9) of the Q64TD/Q64TDV-GH. When control resumption is executed, Module READY (X0) turns ON and initialization is performed. (If the sequence program performs initialization only one scan after RUN, initialization is not performed.) 2) When used on remote I/O network Insert a user device that will execute initialization at any timing (initialization request signal) into the sequence program. After control resumption, turn ON the initialization request signal to perform initialization. (If the sequence program performs initialization only one scan after a data link start of the remote I/O network, initialization is not performed.) (5) Resumption of control (a) After choosing [Diagnosis] - [Online module change] on GX Developer to redisplay the "Online module change" screen, click the [Execution] button to resume control. Module READY (X0) turns ON. (b) The "Online module change completed" screen appears

148 7 ONLINE MODULE CHANGE When user range setting is used and initial setting was made with sequence program (other system is unavailable) (1) Conversion disable (a) Set "Disable" in the conversion enable/disable setting (buffer memory address 0: Un\G0) for all channels and turn Operating Condition Setting Request (Y9) from OFF to ON to stop conversion. After confirming that conversion has stopped with the Conversion Completion Flag (buffer memory address 10: Un\G10), turn off Operating Condition Setting Request (Y9). (b) If the saved buffer memory contents are not yet prerecorded, record them in the following procedure. 1) Turn Operating Condition Setting Request (Y9) form OFF to ON. 2) Compare the Factory default offset/gain value/user range settings offset/gain value/user range settings thermal EMF offset/gain value (buffer memory addresses 160 to 191: Un\G160 to Un\G191) with the range reference table. Refer to Section 7.4 for the range reference table. 3) If the values are proper, take a note of them. POINT If the buffer memory values compared with the reference table are not proper, save and restoration of the user range cannot be executed. Before executing module control resumption, follow the flowchart in Section 4.6 and make offset/gain setting in the device test of GX Developer. Perform mode switching by making the setting of the mode switching setting (buffer memory addresses 158, 159: Un\G158, Un\G159) and turning Operating Condition Setting Request (Y9) from OFF to ON. Note that if module control is resumed without offset/gain setting being made, operation will be performed with the default values

149 7 ONLINE MODULE CHANGE (2) Dismounting of module (a) After choosing [Diagnosis] - [Online module change] on GX Developer to enter the "Online module change" mode, double-click the module to be changed online to display the "Online module change" screen. (b) Click the "Execution" button to enable a module change. If the following error screen appears, the user range cannot be saved. Click the [OK] button, and perform the operation in this section (2) (c) and later

150 7 ONLINE MODULE CHANGE (c) POINT After confirming that the "RUN" LED of the module has turned off, remove the external wiring and dismount the module. (1) If you have removed the wiring together with the terminal block, the measured temperature values may vary within the accuracy range due to the error of the specific cold junction compensation resistor. (2) Always dismount the module. If you execute mounting confirmation without dismounting the module, the module will not start properly and the "RUN" LED will not be lit. (3) Mounting of new module (a) Mount a new module to the same slot and install the external wiring. (b) After mounting the module, click the [Execution] button and make sure that the "RUN" LED is lit. Module Ready (X0) remains OFF. (4) Operation check (a) To make an operation check, click the [Cancel] button to cancel control resumption. (b) Click the [OK] button to leave the "Online module change" mode

151 7 ONLINE MODULE CHANGE (c) Click the [Close] button to close the System monitor screen. (d) (e) (f) (g) Choose [Online] - [Debug] - [Device test] on GX Developer and set the values prerecorded in Section (2) to the buffer memory. Turn the user range write request (YA) from OFF to ON to restore the user set values to the module. After confirming that the offset/gain setting mode status flag (XA) is ON, turn OFF the user range write request (YA). Enable the conversion of the channel to be used through conversion enable/disable setting (buffer memory address 0: Un\G0), and monitor CH measured temperature value/micro voltage conversion value (buffer memory addresses 11 to 14: Un\G11 to 14) to check that proper conversion has been made. Since the new module is in a default status, it must be initialized by a sequence program after control resumption. Before performing initialization, check whether the contents of the initialization program are correct or not. 1) Normal system configuration The sequence program should perform initialization on the leading edge of Module READY (X9) of the Q64TD/Q64TDV-GH. When control resumption is executed, Module READY (X0) turns ON and initialization is performed. (If the sequence program performs initialization only one scan after RUN, initialization is not performed.) 2) When used on remote I/O network Insert a user device that will execute initialization at any timing (initialization request signal) into the sequence program. After control resumption, turn ON the initialization request signal to perform initialization. (If the sequence program performs initialization only one scan after a data link start of the remote I/O network, initialization is not performed.)

152 7 ONLINE MODULE CHANGE (5) Resumption of control (a) After choosing [Diagnosis] - [Online module change] on GX Developer to redisplay the "Online module change" screen, click the [Execution] button to resume control. Module READY (X0) turns ON. (b) The "Online module change completed" screen appears

153 7 ONLINE MODULE CHANGE 7.4 Range Reference Table Address (Decimal) CH1 CH2 CH3 CH4 The range reference tables are given below. Description Factory default offset value Reference value Digital offset value set prior to shipment (Reference value 8000H) Factory default gain value Digital gain value set prior to shipment (Reference value EB85H) User range settings offset value Digital value for user-set offset value (Refer to (3).) User range settings gain value Digital value for user-set gain value (Refer to (4).) User range settings thermal EMF offset value (L) User range settings thermal EMF offset value (H) User range settings thermal EMF gain value (L) User range settings thermal EMF gain value (H) Thermoelectromotive force or offset set voltage for user-set offset set temperature ( V unit) (Refer to (5).) Thermoelectromotive force or gain set voltage for userset gain set temperature ( V unit) (Refer to (6).) (1) Compare the factory default offset value with the reference value 8000H. (2) Compare the factory default gain value with the reference value EB85H. (3) Compare the user range settings offset value with the value obtained by the following formula Digital value = User range settings thermal EMF offset value ( V) (4) Compare the user range settings gain value with the value obtained by the following formula Digital value = User range settings thermal EMF gain value ( V) (5) Obtain a value that corresponds to the offset setting temperature set by the user from the chart of standard thermal electromotive force that is compliant with JIS C , IEC584-1, and IEC Compare the value with the user range settings thermal EMF offset value. (6) Obtain a value that corresponds to the offset setting temperature set by the user from the chart of standard thermal electromotive force that is compliant with JIS C , IEC584-1, and IEC Compare the value with the user range settings thermal EMF gain value. POINT The chart of standard thermal electromotive force compliant with JIS C and IEC584-1, or IEC584-2 needs to be arranged by the user

154 7 ONLINE MODULE CHANGE (Example) When offset/gain setting is made at the offset set temperature of C and the gain set temperature of C with an E type thermocouple connected Value type Set temperature Thermal EMF Set value Input value Offset value C V = 5138 Gain value C V = Precautions for Online Module Change The following are the precautions for online module change. (1) Always perform an online module change in the correct procedure. A failure to do so can cause a malfunction or failure. (2) If an online module change is made with the user range setting, the accuracy after that will fall to about less than 1/3 of the accuracy before that. Re-set the offset/gain values as necessary. (3) During an online module change, do not perform the operations below. If they are performed, the Q64TD/Q64TDV-GH may not operate normally. (a) Powering off the programmable controller CPU (b) Resetting the programmable controller CPU

155 8 TROUBLESHOOTING 8 TROUBLESHOOTING 8.1 Error Code List Error Code (Decimal) 6 10 This chapter explains the natures of errors which may occur during use of the Q64TD/Q64TDV-GH and troubleshooting. If an error occurs during reading/writing data from/to a programmable controller CPU, the Q64TD/Q64TDV-GH writes the corresponding error code to the buffer memory address 19 (Un\G19). Description The input type setting is other than 0 to 7 (Q64TD)/0 to 8 (Q64TDV-GH) in the intelligent function module switch setting. indicates the channel number set incorrectly. 111 A module error at a start The offset/gain setting is other than 0 and 1 in the intelligent function module switch setting. indicates the channel number set incorrectly. 2 The G(P).OGSTOR instruction was executed in the offset/gain setting mode. 1 The G(P).OGSTOR instruction was executed consecutively. At the time of offset/gain setting, a set value was written to the E 2 PROM 26 or more times. The G(P).OGSTOR instruction was executed for the model that differs from the model for which the G(P).OGLOAD 1 instruction had been executed. The G(P).OGSTOR instruction had been executed before the G(P).OGLOAD instruction was executed. 1 The averaging time setting is outside the setting range. indicates the channel number set incorrectly. 1 The averaging count setting is outside the setting range. indicates the channel number set incorrectly. Gain value - offset value 0.1 [ C] (for temperature input) or 1 gain value - offset value 4 [ V] (for micro voltage input). indicates the channel number set incorrectly Remedy Make a correct setting in the intelligent function module switch setting. (Refer to Section 4.5.) Switch power off, then on again. If the error recurs, the module may have failed. Please consult your local Mitsubishi representative. Make a correct setting in the intelligent function module switch setting. (Refer to Section 4.5.) Do not execute the G(P).OGSTOR instruction in the offset/gain setting mode. Execute the G(P).OGSTOR instruction only once for one module. At the time of offset/gain setting, write a set value only once at one time. Execute the G(P).OGLOAD and G(P).OGSTOR instructions for the same model. Set a correct value at the buffer memory address 1 to 4 (Un\G1 to 4). (Refer to Section ) Set a correct value at the buffer memory address 1 to 4 (Un\G1 to 4). (Refer to Section ) Set a correct value in buffer memory, or measure and check the voltage at the thermocouple/micro voltage input terminal. When the offset setting request (Y1, Y3, Y5, Y7) or gain setting request (Y2, Y4, Y6, Y8) is turned on in the offset/gain Make a correct setting in the intelligent function module setting mode, the offset/gain of the intelligent function module switch setting. (Refer to Section 4.5.) switch setting on that channel is not user range setting. indicates the channel number set incorrectly. When the offset setting request (Y1, Y3, Y5, Y7) or gain setting request (Y2, Y4, Y6, Y8) is turned on in the offset/gain Check the measured range and set the offset/gain value setting mode, the "offset value" or "gain value" of that channel within the range. (Refer to Section 3.1.1, ) is outside the measured range. indicates the channel number set incorrectly. The offset setting request and gain setting request were turned on simultaneously in the offset/gain setting mode. indicates the channel number set incorrectly. The warning output upper/lower limit value setting is outside the measurable range specified for the input type. indicates the channel number set incorrectly. indicates any of the following statuses. 0: The lower lower limit value is lower than the measurement range. 1: The upper upper limit value is higher than the measurement range. 2: Lower lower limit value > lower upper limit value 3: Lower upper limit value > upper lower limit value 4: Upper lower limit value > upper upper limit value Reexamine the sequence program so that they do not turn on simultaneously. Set a correct value at the buffer memory address 86 to 101 (Un\G86 to 101). (Refer to Section )

156 8 TROUBLESHOOTING POINT For the Q64TD, the code of the first error found by the Q64TD is stored when two or more errors occur. The latter errors are not stored. In addition, the error is cleared by mode switching. For the Q64TDV-GH, the code of the latest error found by the Q64TDV-GH is stored when two or more errors occur. The errors marked 1 can be cleared by turning on the error clear request (YF). The error marked 2 is not written to the buffer memory address 19 (Un\G19). It is written to the completion status area (S) + 1 of the G(P).OGSTOR instruction. 8.2 Troubleshooting RUN LED is extinguished Check that power is supplied. Check Item Check that the capacity of the power supply module is sufficient. Check for a watchdog timer error. Check whether the modules are loaded normally on the base unit. Is a module change enabled during an online module change? Remedy Confirm that the supply voltage of the power supply module is within the rated range. Calculate the current consumption of the CPU, I/O, intelligent function and other modules loaded on the base unit, and make sure that the power supply capacity is enough. Reset the programmable controller CPU and verify that it is lit. If the RUN LED does not light even after doing this, the module may be malfunctioning. Please consult your local Mitsubishi representative. Check the module loading status. Refer to Chapter 7 and take corrective action RUN LED flickers 8 Check Item Check whether the module is in the offset/gain setting mode or not ERROR LED flickers Remedy After making offset/gain setting, return to the normal mode. Check Item Check whether the switch 5 of the intelligent function module switches is "other than 0" ERROR LED is lit Remedy Set the switch 5 of the intelligent function module switches for 0. (Refer to Section 4.5) Check for an error. Check Item Remedy Check the error code and take the action given in Section

157 8 TROUBLESHOOTING Disconnection detection flag (XC) has turned on Check Item Check whether the thermocouple, compensation conductor or micro voltage signal cable is connected incompletely or not. Check for loose terminal screws. Check the connected thermocouple, compensation conductor or micro voltage signal cable for wire break. Check whether the channel where no thermocouple or micro voltage signal cable is connected is set to conversion enable. Remedy Connect the thermocouple, compensation conductor or micro voltage signal cable securely. Retighten the terminal screws within the specified torque range. Make continuity check on the thermocouple, compensation conductor or micro voltage signal cable, and change the thermocouple, compensation conductor or micro voltage signal cable if its wire is broken. Check the channels which are set to conversion enable and the channels where thermocouples or micro voltage signal cables are connected, and set to conversion enable correctly Measured temperature value/micro voltage conversion value cannot be read Check Item Check whether the used channel has been set for conversion disable. Check whether the programmable controller CPU is set for STOP. Remedy Set it for conversion enable in sequence program. Set the programmable controller CPU for RUN Measured temperature value is abnormal Check Item Check whether the connected thermocouple or compensation conductor differs from the setting. Check whether the connected thermocouple or compensation conductor is connected reversely. Check for noise in the thermocouple input. Check the Pt100 temperature-measuring resistor for making cold junction temperature compensation for wire break or disconnection from the terminal block. Check whether the cold junction temperature compensation yes/no setting is correct. Check whether conversion is made with the other thermocouple set after setting of the offset/gain value Is the measured temperature value greatly affected by a temperature error due to wiring resistance of the thermocouple? Remedy Set the thermocouple type connected to the switch 1 in the intelligent function module switch setting. Connect the thermocouple or compensation conductor correctly. Check influence from the ground and adjacent devices, and take action to prevent noise. Confirm that the Pt100 temperature-measuring resistor is connected to the terminal block and there is continuity, and if not, connect or change the Pt100 temperature-measuring resistor. Set the switch 4 to the correct position in the intelligent function module switch setting. (Refer to Section 4.5) Make offset/gain setting again after changing the thermocouple. Check the wiring resistance value of the thermocouple and calculate the temperature error in the system. (Refer to Section (2) for the Q64TD and Section (2) for the Q64TDV-GH.) If the temperature error is large, the error may be affecting the measured temperature value. Compensate the measured temperature value using the offset/gain setting. (Refer to Section 4.6.)

158 8 TROUBLESHOOTING Micro voltage conversion value is abnormal Check Item Check whether the input type set is a thermocouple or not. Check the micro voltage signal cable for noise. After offset/gain value setting, the other signal cable was connected. Is the micro voltage conversion value greatly affected by an error due to wiring resistance? Remedy Set the switch for micro voltage input in the intelligent function module switch setting. Check influence from grounding and adjacent equipment, and take noise reduction measures. Make offset/gain setting again with the newly connected signal cable. Check the wiring resistance value and calculate the error in the system. (Refer to Section (3).) If the error is large, the error may be affecting the micro voltage conversion value. Compensate the micro voltage conversion value using the offset/gain setting. (Refer to Section 4.6.)

159 8 TROUBLESHOOTING Checking the Q64TD/Q64TDV-GH status using GX Developer system monitor When the Q64TD/Q64TDV-GH detail information is selected in GX Developer system monitor, error code can be checked. (1) Operating GX Developer [Diagnostics] [System monitor] "Select Q64TD/Q64TDV-GH" Module Detailed Information (2) Module Detail Information (a) Checking the function version and product information The function version and product information of the Q64TD/Q64TDV-GH is displayed in the product information field. (b) Checking the error code The error code stored in buffer memory address 19 (Un\G19) of the Q64TD/Q64TDV-GH is displayed in the Present Error field. (When the Error History button is pressed, the contents displayed in the Present Error field are displayed in the No. 1 field.)

160 8 TROUBLESHOOTING (3) H/W information (a) H/W LED information The LED ON status is displayed. No. LED name Status 1 RUN LED 0000H : Indicates that LED is unlit. 2 ERROR LED 0001H : Indicates that LED is lit (b) H/W SW information The status of the intelligent function module switch setting is displayed. No. Switch setting for intelligent function module 1 Switch 1 2 Switch 2 3 Switch 3 4 Switch 4 5 Switch

RTD Input Module Channel Isolated RTD Input Module User's Manual. -Q64RD -Q64RD-G -GX Configurator-TI (SW1D5C-QTIU-E)

RTD Input Module Channel Isolated RTD Input Module User's Manual. -Q64RD -Q64RD-G -GX Configurator-TI (SW1D5C-QTIU-E) RTD Input Module Channel Isolated RTD Input Module User's Manual -Q64RD -Q64RD-G -GX Configurator-TI (SW1D5C-QTIU-E) SAFETY PRECAUTIONS (Read these precautions before using this product.) Before using

More information

Channel Isolated Thermocouple Input Module User's Manual. -Q68TD-G-H01 -Q68TD-G-H02 -GX Configurator-TI (SW1D5C-QTIU-E)

Channel Isolated Thermocouple Input Module User's Manual. -Q68TD-G-H01 -Q68TD-G-H02 -GX Configurator-TI (SW1D5C-QTIU-E) Channel Isolated Thermocouple Input Module User's Manual -Q68TD-G-H01 -Q68TD-G-H02 -GX Configurator-TI (SW1D5C-QTIU-E) SAFETY PRECAUTIONS (Read these precautions before using this product.) Before using

More information

Digital-Analog Converter Module User's Manual. -Q62DAN -Q62DA -Q64DAN -Q64DA -Q68DAVN -Q68DAV -Q68DAIN -Q68DAI -GX Configurator-DA (SW2D5C-QDAU-E)

Digital-Analog Converter Module User's Manual. -Q62DAN -Q62DA -Q64DAN -Q64DA -Q68DAVN -Q68DAV -Q68DAIN -Q68DAI -GX Configurator-DA (SW2D5C-QDAU-E) Digital-Analog Converter Module User's Manual -Q62DAN -Q62DA -Q64DAN -Q64DA -Q68DAVN -Q68DAV -Q68DAIN -Q68DAI -GX Configurator-DA (SW2D5C-QDAU-E) SAFETY PRECAUTIONS (Always read these precautions before

More information

Channel Isolated Digital-Analog Converter Module User's Manual. -Q62DA-FG -GX Configurator-DA (SW2D5C-QDAU-E)

Channel Isolated Digital-Analog Converter Module User's Manual. -Q62DA-FG -GX Configurator-DA (SW2D5C-QDAU-E) Channel Isolated Digital-Analog Converter Module User's Manual -Q62DA-FG -GX Configurator-DA (SW2D5C-QDAU-E) SAFETY PRECAUTIONS (Read these precautions before using this product.) Before using this product,

More information

Channel Isolated Digital-Analog Converter Module User's Manual. -Q66DA-G -GX Configurator-DA (SW2D5C-QDAU-E)

Channel Isolated Digital-Analog Converter Module User's Manual. -Q66DA-G -GX Configurator-DA (SW2D5C-QDAU-E) Channel Isolated Digital-Analog Converter Module User's Manual -Q66DA-G -GX Configurator-DA (SW2D5C-QDAU-E) SAFETY PRECAUTIONS (Read these precautions before using this product.) Before using this product,

More information

MELSEC-Q High Speed Analog-Digital Converter Module User's Manual -Q64ADH

MELSEC-Q High Speed Analog-Digital Converter Module User's Manual -Q64ADH MELSEC-Q High Speed Analog-Digital Converter Module User's Manual -Q64ADH SAFETY PRECAUTIONS (Read these precautions before using this product.) Before using this product, please read this manual and

More information

MELSEC-Q Current Transformer Input Module User's Manual -Q68CT

MELSEC-Q Current Transformer Input Module User's Manual -Q68CT MELSEC-Q Current Transformer Input Module User's Manual -Q68CT SAFETY PRECAUTIONS (Read these precautions before using this product.) Before using this product, please read this manual and the relevant

More information

SAFETY PRECAUTIONS. (Always read these instructions before using this product.)

SAFETY PRECAUTIONS. (Always read these instructions before using this product.) SAFETY PRECAUTIONS (Always read these instructions before using this product.) Before using this product, please read this manual and the relevant manuals introduced in this manual carefully and pay full

More information

MELSEC-L Analog Input/Output Module User's Manual -L60AD2DA2

MELSEC-L Analog Input/Output Module User's Manual -L60AD2DA2 MELSEC-L Analog Input/Output Module User's Manual -L60AD2DA2 SAFETY PRECAUTIONS (Read these precautions before using this product.) Before using this product, please read this manual and the relevant

More information

Load Cell Input Module User's Manual -Q61LD

Load Cell Input Module User's Manual -Q61LD Load Cell Input Module User's Manual -Q61LD SAFETY PRECAUTIONS (Read these precautions before using this product.) Before using this product, please read this manual and the relevant manuals carefully

More information

MODBUS Interface Module User's Manual. -QJ71MB91 -GX Configurator-MB (SW1D5C-QMBU-E)

MODBUS Interface Module User's Manual. -QJ71MB91 -GX Configurator-MB (SW1D5C-QMBU-E) MODBUS Interface Module User's Manual -QJ71MB91 -GX Configurator-MB (SW1D5C-QMBU-E) SAFETY PRECAUTIONS (Always read these instructions before using this product.) Before using this product, please read

More information

Loop Control Module User's Manual. -Q62HLC -GX Configurator-TC (SW0D5C-QTCU-E)

Loop Control Module User's Manual. -Q62HLC -GX Configurator-TC (SW0D5C-QTCU-E) Loop Control Module User's Manual -Q62HLC -GX Configurator-TC (SW0D5C-QTCU-E) SAFETY PRECAUTIONS (Read these precautions before using this product.) Before using this product, please read this manual

More information

SAFETY PRECAUTIONS. (Always read these instructions before using this product.)

SAFETY PRECAUTIONS. (Always read these instructions before using this product.) SAFETY PRECAUTIONS (Always read these instructions before using this product.) Before using this product, please read this manual and the relevant manuals introduced in this manual carefully and pay full

More information

Analog-Digital Converter Module. Mitsubishi Programmable Logic Controller. Q64AD Q68ADV Q68ADI GX Configurator-AD (SW0D5C-QADU-E)

Analog-Digital Converter Module. Mitsubishi Programmable Logic Controller. Q64AD Q68ADV Q68ADI GX Configurator-AD (SW0D5C-QADU-E) Analog-Digital Converter Module User's Manual Mitsubishi Programmable Logic Controller Q64AD Q68ADV Q68ADI GX Configurator-AD (SW0D5C-QADU-E) SAFETY PRECAUTIONS (Always read these instructions before using

More information

CC-Link/LT Master Module User's Manual -QJ61CL12

CC-Link/LT Master Module User's Manual -QJ61CL12 CC-Link/LT Master Module User's Manual -QJ61CL12 SAFETY PRECAUTIONS (Read these precautions before using this product.) Before using this product, please read this manual and the relevant manuals carefully

More information

4Mpps Capable High-Speed Counter Module User's Manual. -QD64D2 -GX Configurator-CT (SW0D5C-QCTU-E)

4Mpps Capable High-Speed Counter Module User's Manual. -QD64D2 -GX Configurator-CT (SW0D5C-QCTU-E) 4Mpps Capable High-Speed Counter Module User's Manual -QD64D2 -GX Configurator-CT (SW0D5C-QCTU-E) SAFETY PRECAUTIONS (Read these precautions before use.) Before using this product, please read this manual

More information

MELSEC iq-r Channel Isolated Thermocouple Input Module/Channel Isolated RTD Input Module User's Manual (Startup) -R60TD8-G -R60RD8-G

MELSEC iq-r Channel Isolated Thermocouple Input Module/Channel Isolated RTD Input Module User's Manual (Startup) -R60TD8-G -R60RD8-G MELSEC iq-r Channel Isolated Thermocouple Input Module/Channel Isolated RTD Input Module User's Manual (Startup) -R60TD8-G -R60RD8-G SAFETY PRECAUTIONS (Read these precautions before using this product.)

More information

MELSEC iq-r Analog-Digital Converter Module User's Manual (Startup) -R60AD4 -R60ADV8 -R60ADI8

MELSEC iq-r Analog-Digital Converter Module User's Manual (Startup) -R60AD4 -R60ADV8 -R60ADI8 MELSEC iq-r Analog-Digital Converter Module User's Manual (Startup) -R60AD4 -R60ADV8 -R60ADI8 SAFETY PRECAUTIONS (Read these precautions before using this product.) Before using MELSEC iq-r series programmable

More information

AS-i Master Module User's Manual. -QJ71AS92 -GX Configurator-AS (SW1D5C-QASU-E)

AS-i Master Module User's Manual. -QJ71AS92 -GX Configurator-AS (SW1D5C-QASU-E) AS-i Master Module User's Manual -QJ71AS92 -GX Configurator-AS (SW1D5C-QASU-E) SAFETY PRECAUTIONS (Always read these instructions before using this equipment.) Before using this product, please read this

More information

MELSEC iq-r Digital-Analog Converter Module User's Manual (Startup) -R60DA4 -R60DAV8 -R60DAI8

MELSEC iq-r Digital-Analog Converter Module User's Manual (Startup) -R60DA4 -R60DAV8 -R60DAI8 MELSEC iq-r Digital-Analog Converter Module User's Manual (Startup) -R60DA4 -R60DAV8 -R60DAI8 SAFETY PRECAUTIONS (Read these precautions before using this product.) Before using the MELSEC iq-r series

More information

CC-Link IE Controller Network Interface Board User's Manual (For SW1DNC-MNETG-B)

CC-Link IE Controller Network Interface Board User's Manual (For SW1DNC-MNETG-B) CC-Link IE Controller Network Interface Board User's Manual (For SW1DNC-MNETG-B) -Q80BD-J71GP21-SX -Q80BD-J71GP21S-SX -Q81BD-J71GP21-SX -Q81BD-J71GP21S-SX SAFETY PRECAUTIONS (Be sure to read these instructions

More information

Digital-Analog Converter Module User's Manual -CL2DA2-B

Digital-Analog Converter Module User's Manual -CL2DA2-B Digital-Analog Converter Module User's Manual -CL2DA2-B SAFETY PRECAUTIONS (Read these precautions before using this product.) Before using this product, please read this manual and the relevant manuals

More information

DC I/O Conversion Module FA-TB32XY

DC I/O Conversion Module FA-TB32XY DC I/O Conversion Module FA-TB32XY User's Manual Thank you for purchasing FA Goods product. Before using, please read this User s Manual and the relevant manuals carefully to ensure correct use. SAFETY

More information

MELSEC iq-r DeviceNet Master/Slave Module User's Manual (Application) -RJ71DN91

MELSEC iq-r DeviceNet Master/Slave Module User's Manual (Application) -RJ71DN91 MELSEC iq-r DeviceNet Master/Slave Module User's Manual (Application) -RJ71DN91 SAFETY PRECAUTIONS (Read these precautions before using this product.) Before using this product, please read this manual

More information

MELSEC iq-r EtherNet/IP Network Interface Module User's Manual (Application) -RJ71EIP91

MELSEC iq-r EtherNet/IP Network Interface Module User's Manual (Application) -RJ71EIP91 MELSEC iq-r EtherNet/IP Network Interface Module User's Manual (Application) -RJ71EIP91 SAFETY PRECAUTIONS (Read these precautions before using this product.) Before using this product, please read this

More information

DC I/O Conversion Module

DC I/O Conversion Module DC I/O Conversion Module,FA-TB32XYH User's Manual Thank you for purchasing FA Goods product. Before using, please read this User s Manual and the relevant manuals carefully to ensure correct use. SAFETY

More information

FL-net(OPCN-2) Interface Module

FL-net(OPCN-2) Interface Module FL-net(OPCN-2) Interface Module User s Manual (Hardware) QJ71FL71-T-F01 QJ71FL71-B5-F01 QJ71FL71-B2-F01 Thank you for purchasing the Mitsubishi programmable controller MELSEC-Q series. Prior to use, please

More information

MELSEC iq-r Channel Isolated Analog-Digital Converter Module User's Manual (Startup) -R60AD8-G -R60AD16-G

MELSEC iq-r Channel Isolated Analog-Digital Converter Module User's Manual (Startup) -R60AD8-G -R60AD16-G MELSEC iq-r Channel Isolated Analog-Digital Converter Module User's Manual (Startup) -R60AD8-G -R60AD16-G SAFETY PRECAUTIONS (Read these precautions before using this product.) Before using this product,

More information

MELSEC iq-r CPU Module User's Manual (Startup)

MELSEC iq-r CPU Module User's Manual (Startup) MELSEC iq-r CPU Module User's Manual (Startup) -R00CPU -R01CPU -R02CPU -R04CPU -R04ENCPU -R08CPU -R08ENCPU -R08PCPU -R08PSFCPU -R08SFCPU -R16CPU -R16ENCPU -R16PCPU -R16PSFCPU -R16SFCPU -R32CPU -R32ENCPU

More information

MELSEC iq-r Online Module Change Manual

MELSEC iq-r Online Module Change Manual MELSEC iq-r Online Module Change Manual SAFETY PRECAUTIONS (Read these precautions before using this product.) Before using MELSEC iq-r series programmable controllers, please read the manuals for the

More information

ERNT-AQTX10 ERNT-AQT68AD-GH. User s Manual. Mitsubishi General-Purpose Programmable Logic Controller Renewal Tool Conversion Adapter.

ERNT-AQTX10 ERNT-AQT68AD-GH. User s Manual. Mitsubishi General-Purpose Programmable Logic Controller Renewal Tool Conversion Adapter. Mitsubishi General-Purpose Programmable Logic Controller Renewal Tool Conversion Adapter Model ERNT-AQT68AD-GH User s Manual ERNT-AQTX10 Model ERNT-AQT68AD-GH 50CM-D180033-A(0810)MEE SAFETY PRECAUTIONS

More information

MELSEC iq-r PROFIBUS-DP Module User's Manual (Application) -RJ71PB91V

MELSEC iq-r PROFIBUS-DP Module User's Manual (Application) -RJ71PB91V MELSEC iq-r PROFIBUS-DP Module User's Manual (Application) -RJ71PB91V SAFETY PRECAUTIONS (Read these precautions before using this product.) Before using this product, please read this manual and the

More information

High Speed Data Communication Module User's Manual. -QJ71DC96 -SW1DNN-DCUTL-E (High Speed Data Communication Module Tool)

High Speed Data Communication Module User's Manual. -QJ71DC96 -SW1DNN-DCUTL-E (High Speed Data Communication Module Tool) High Speed Data Communication Module User's Manual -QJ71DC96 -SW1DNN-DCUTL-E (High Speed Data Communication Module Tool) SAFETY PRECAUTIONS (Read these precautions before using this product.) Before using

More information

MELSEC iq-r Channel Isolated Digital-Analog Converter Module User's Manual (Startup) -R60DA8-G -R60DA16-G

MELSEC iq-r Channel Isolated Digital-Analog Converter Module User's Manual (Startup) -R60DA8-G -R60DA16-G MELSEC iq-r Channel Isolated Digital-Analog Converter Module User's Manual (Startup) -R60DA8-G -R60DA16-G SAFETY PRECAUTIONS (Read these precautions before using this product.) Before using this product,

More information

Q Corresponding MELSECNET/H Network System Reference Manual (Remote I/O network)

Q Corresponding MELSECNET/H Network System Reference Manual (Remote I/O network) Q Corresponding MELSECNET/H Network System Reference Manual (Remote I/O network) -QJ71LP21 -QJ71LP21-25 -QJ71LP21S-25 -QJ71LP21G -QJ71LP21GE -QJ71BR11 -QJ72LP25-25 -QJ72LP25G -QJ72LP25GE -QJ72BR15 SAFETY

More information

SAFETY PRECAUTIONS. (Read these precautions before using this product.)

SAFETY PRECAUTIONS. (Read these precautions before using this product.) SAFETY PRECAUTIONS (Read these precautions before using this product.) Before using this product, please read this manual and the relevant manuals carefully and pay full attention to safety to handle the

More information

Safety Programmable Controller. User's Manual. Safety Relay Module SH(NA) ENG Version C INDUSTRIAL AUTOMATION MITSUBISHI ELECTRIC

Safety Programmable Controller. User's Manual. Safety Relay Module SH(NA) ENG Version C INDUSTRIAL AUTOMATION MITSUBISHI ELECTRIC MITSUBISHI ELECTRIC Safety Programmable Controller User's Manual Safety Relay Module 01 11 2008 SH(NA)-080746ENG Version C MITSUBISHI ELECTRIC INDUSTRIAL AUTOMATION SAFETY PRECAUTIONS (Always read these

More information

MELSEC iq-r CC-Link System Master/Local Module User's Manual (Startup) -RJ61BT11

MELSEC iq-r CC-Link System Master/Local Module User's Manual (Startup) -RJ61BT11 MELSEC iq-r CC-Link System Master/Local Module User's Manual (Startup) -RJ61BT11 SAFETY PRECAUTIONS (Read these precautions before using this product.) Before using this product, please read this manual

More information

MELSEC iq-r CC-Link System Master/Local Module User's Manual (Startup) -RJ61BT11

MELSEC iq-r CC-Link System Master/Local Module User's Manual (Startup) -RJ61BT11 MELSEC iq-r CC-Link System Master/Local Module User's Manual (Startup) -RJ61BT11 SAFETY PRECAUTIONS (Read these precautions before using this product.) Before using this product, please read this manual

More information

CC-Link IE Field Network Interface Board User's Manual (For SW1DNC-CCIEF-B) -Q80BD-J71GF11-T2 -Q81BD-J71GF11-T2

CC-Link IE Field Network Interface Board User's Manual (For SW1DNC-CCIEF-B) -Q80BD-J71GF11-T2 -Q81BD-J71GF11-T2 CC-Link IE Field Network Interface Board User's Manual (For SW1DNC-CCIEF-B) -Q80BD-J71GF11-T2 -Q81BD-J71GF11-T2 SAFETY PRECAUTIONS (Read these precautions before using this product.) Before using this

More information

MELSEC Communication Protocol Reference Manual

MELSEC Communication Protocol Reference Manual MELSEC Communication Protocol Reference Manual SAFETY PRECAUTIONS (Read these precautions before using this product.) Before using this product, please read this manual and the relevant manuals carefully

More information

SAFETY PRECAUTIONS. (Read these precautions before using this product.)

SAFETY PRECAUTIONS. (Read these precautions before using this product.) SAFETY PRECAUTIONS (Read these precautions before using this product.) Before using this product, please read this manual and the relevant manuals carefully and pay full attention to safety to handle the

More information

MELSEC iq-r DeviceNet Master/Slave Module User's Manual (Startup) -RJ71DN91

MELSEC iq-r DeviceNet Master/Slave Module User's Manual (Startup) -RJ71DN91 MELSEC iq-r DeviceNet Master/Slave Module User's Manual (Startup) -RJ71DN91 SAFETY PRECAUTIONS (Read these precautions before using this product.) Before using this product, please read this manual and

More information

MELSEC iq-r MES Interface Module User's Manual (Application) -RD81MES96 -SW1DND-RMESIF-E(MX MESInterface-R)

MELSEC iq-r MES Interface Module User's Manual (Application) -RD81MES96 -SW1DND-RMESIF-E(MX MESInterface-R) MELSEC iq-r MES Interface Module User's Manual (Application) -RD81MES96 -SW1DND-RMESIF-E(MX MESInterface-R) SAFETY PRECAUTIONS (Read these precautions before using this product.) Before using this product,

More information

Programmable Controller Analog Terminal Block Conversion Module FA1-TBS40ADGN, FA1-TBS40ADDG, FA1-TBS40DAG User's Manual

Programmable Controller Analog Terminal Block Conversion Module FA1-TBS40ADGN, FA1-TBS40ADDG, FA1-TBS40DAG User's Manual Programmable Controller Analog Terminal Block Conversion Module FA1-TBS40ADGN, FA1-TBS40ADDG, FA1-TBS40DAG User's Manual Thank you for purchasing FA Goods product. Before using, please read this User s

More information

SAFETY PRECAUTIONS. (Read these precautions before using this product.)

SAFETY PRECAUTIONS. (Read these precautions before using this product.) SAFETY PRECAUTIONS (Read these precautions before using this product.) Before using this product, please read this manual and the relevant manuals carefully and pay full attention to safety to handle the

More information

SAFETY PRECAUTIONS. (Read these precautions before using this product.)

SAFETY PRECAUTIONS. (Read these precautions before using this product.) SAFETY PRECAUTIONS (Read these precautions before using this product.) Before using this product, please read this manual and the relevant manuals carefully and pay full attention to safety to handle the

More information

MELSEC iq-r Ethernet/CC-Link IE User's Manual (Startup) -RJ71EN71 -RJ71GP21-SX -RJ71GF11-T2 -R04CPU -R08CPU -R16CPU -R32CPU -R120CPU

MELSEC iq-r Ethernet/CC-Link IE User's Manual (Startup) -RJ71EN71 -RJ71GP21-SX -RJ71GF11-T2 -R04CPU -R08CPU -R16CPU -R32CPU -R120CPU MELSEC iq-r Ethernet/CC-Link IE User's Manual (Startup) -RJ71EN71 -RJ71GP21-SX -RJ71GF11-T2 -R04CPU -R08CPU -R16CPU -R32CPU -R120CPU SAFETY PRECAUTIONS (Read these precautions before using this product.)

More information

Additional Explanation for A851GOT Graphic Operation Terminal

Additional Explanation for A851GOT Graphic Operation Terminal Additional Explanation for A851GOT Graphic Operation Terminal GRAPHIC OPERATION TERMINAL Mitsubishi Graphic Operation Terminal SAFETY PRECAUTIONS (Always read these instructions before using this equipment.)

More information

MELSEC-L Flexible High-Speed I/O Control Module User's Manual

MELSEC-L Flexible High-Speed I/O Control Module User's Manual MELSEC-L Flexible High-Speed I/O Control Module User's Manual -LD40PD01 -Flexible High-Speed I/O Control Module Configuration tool (SW1DNN-FLEXIOP-E) SAFETY PRECAUTIONS (Read these precautions before

More information

Digital-Analog Converter Module type AJ65SBT62DA. User's Manual

Digital-Analog Converter Module type AJ65SBT62DA. User's Manual Digital-Analog Converter Module type AJ65SBT62DA User's Manual SAFETY PRECAUTIONS (Read these precautions before using this product.) Before using this product, please read this manual and the relevant

More information

CC-Link IE Field Network Basic Reference Manual

CC-Link IE Field Network Basic Reference Manual CC-Link IE Field Network Basic Reference Manual SAFETY PRECAUTIONS (Read these precautions before using Mitsubishi Electric programmable controllers.) Before using Mitsubishi Electric programmable controllers,

More information

MELSEC iq-r High Speed Data Logger Module User's Manual (Application) -RD81DL96 -SW1DNN-RDLUTL (High Speed Data Logger Module Tool)

MELSEC iq-r High Speed Data Logger Module User's Manual (Application) -RD81DL96 -SW1DNN-RDLUTL (High Speed Data Logger Module Tool) MELSEC iq-r High Speed Data Logger Module User's Manual (Application) -RD81DL96 -SW1DNN-RDLUTL (High Speed Data Logger Module Tool) SAFETY PRECAUTIONS (Read these precautions before using this product.)

More information

MELSEC-Q/L Ethernet Interface Module User's Manual (Application) -QJ71E QJ71E71-B5 -QJ71E71-B2 -LJ71E71-100

MELSEC-Q/L Ethernet Interface Module User's Manual (Application) -QJ71E QJ71E71-B5 -QJ71E71-B2 -LJ71E71-100 MELSEC-Q/L Ethernet Interface Module User's Manual (Application) -QJ71E71-100 -QJ71E71-B5 -QJ71E71-B2 -LJ71E71-100 SAFETY PRECAUTIONS (Read these precautions before using this product.) Before using this

More information

MELSEC iq-r High Speed Data Logger Module User's Manual (Startup) -RD81DL96 -SW1DNN-RDLUTL (High Speed Data Logger Module Tool)

MELSEC iq-r High Speed Data Logger Module User's Manual (Startup) -RD81DL96 -SW1DNN-RDLUTL (High Speed Data Logger Module Tool) MELSEC iq-r High Speed Data Logger Module User's Manual (Startup) -RD81DL96 -SW1DNN-RDLUTL (High Speed Data Logger Module Tool) SAFETY PRECAUTIONS (Read these precautions before using this product.) Before

More information

MELSECNET/H Interface Board User's Manual (For SW0DNC-MNETH-B) -Q80BD-J71LP Q80BD-J71LP21S-25 -Q81BD-J71LP Q80BD-J71LP21G -Q80BD-J71BR11

MELSECNET/H Interface Board User's Manual (For SW0DNC-MNETH-B) -Q80BD-J71LP Q80BD-J71LP21S-25 -Q81BD-J71LP Q80BD-J71LP21G -Q80BD-J71BR11 NET/H Interface Board User's Manual (For SW0DNC-MNETH-B) -Q80BD-J71LP21-25 -Q80BD-J71LP21S-25 -Q81BD-J71LP21-25 -Q80BD-J71LP21G -Q80BD-J71BR11 SAFETY PRECAUTIONS (Be sure to read these instructions before

More information

MELSEC iq-r Temperature Control Module User's Manual (Startup) -R60TCTRT2TT2 -R60TCTRT2TT2BW -R60TCRT4 -R60TCRT4BW

MELSEC iq-r Temperature Control Module User's Manual (Startup) -R60TCTRT2TT2 -R60TCTRT2TT2BW -R60TCRT4 -R60TCRT4BW MELSEC iq-r Temperature Control Module User's Manual (Startup) -R60TCTRT2TT2 -R60TCTRT2TT2BW -R60TCRT4 -R60TCRT4BW SAFETY PRECAUTIONS (Read these precautions before using this product.) Before using this

More information

MELSEC iq-r HART-Enabled Analog-Digital Converter Module User's Manual (Startup) -R60ADI8-HA -SW1DNN-HARTCDTM-BD (CommDTM for R60ADI8-HA)

MELSEC iq-r HART-Enabled Analog-Digital Converter Module User's Manual (Startup) -R60ADI8-HA -SW1DNN-HARTCDTM-BD (CommDTM for R60ADI8-HA) MELSEC iq-r HART-Enabled Analog-Digital Converter Module User's Manual (Startup) -R60ADI8-HA -SW1DNN-HARTCDTM-BD (CommDTM for R60ADI8-HA) SAFETY PRECAUTIONS (Read these precautions before using this product.)

More information

SAFETY PRECAUTIONS (Always read these instructions before using this equipment.)

SAFETY PRECAUTIONS (Always read these instructions before using this equipment.) SAFETY PRECAUTIONS (Always read these instructions before using this equipment.) Before using this product, please read this manual and the relevant manuals introduced in this manual carefully and pay

More information

GX Configurator-SC Version 2 Operating Manual (Protocol FB support function) -SW2D5C-QSCU-E

GX Configurator-SC Version 2 Operating Manual (Protocol FB support function) -SW2D5C-QSCU-E GX Configurator-SC Version 2 Operating Manual (Protocol FB support function) -SW2D5C-QSCU-E SAFETY PRECAUTIONS (Always read these instructions before using this equipment.) Before using this product,

More information

SAFETY PRECAUTIONS. (Always read these precautions prior to use.)

SAFETY PRECAUTIONS. (Always read these precautions prior to use.) EQ-V68D1 EQ-V68D2 SAFETY PRECAUTIONS (Always read these precautions prior to use.) Before using this product, please read this manual and the relevant manuals introduced in this manual carefully and pay

More information

MELSEC iq-r CC-Link System Master/Local Module User's Manual (Application) -RJ61BT11

MELSEC iq-r CC-Link System Master/Local Module User's Manual (Application) -RJ61BT11 MELSEC iq-r CC-Link System Master/Local Module User's Manual (Application) -RJ61BT11 SAFETY PRECAUTIONS (Read these precautions before using this product.) Before using this product, please read this

More information

SLMP Reference Manual

SLMP Reference Manual SLMP Reference Manual SAFETY PRECAUTIONS (Read these precautions before using this product.) Before using this product, please read this manual carefully and pay full attention to safety to handle the

More information

MELSEC iq-r AnyWireASLINK Master Module User's Manual (Application) -RJ51AW12AL

MELSEC iq-r AnyWireASLINK Master Module User's Manual (Application) -RJ51AW12AL MELSEC iq-r AnyWireASLINK Master Module User's Manual (Application) -RJ51AW12AL COPYRIGHT This document is protected by the law of copyright, whereby all rights established therein remain with the company

More information

Mitsubishi Electric General-purpose Programmable Controllers MELSEC-A/QnA (Large), AnS/QnAS (Small) Transition Examples. Apr.

Mitsubishi Electric General-purpose Programmable Controllers MELSEC-A/QnA (Large), AnS/QnAS (Small) Transition Examples. Apr. Mitsubishi Electric General-purpose Programmable Controllers MELSEC-A/QnA (Large), AnS/QnAS (Small) Transition Examples Apr. 08 Edition Safety Precautions When replacing A (Large Type)/AnS (Small Type)

More information

MELSEC iq-r EtherNet/IP Network Interface Module User's Manual (Startup) -RJ71EIP91

MELSEC iq-r EtherNet/IP Network Interface Module User's Manual (Startup) -RJ71EIP91 MELSEC iq-r EtherNet/IP Network Interface Module User's Manual (Startup) -RJ71EIP91 SAFETY PRECAUTIONS (Read these precautions before using this product.) Before using this product, please read this manual

More information

MX Sheet Version 2 Operating Manual (Introduction) -SW2DNC-SHEET-E

MX Sheet Version 2 Operating Manual (Introduction) -SW2DNC-SHEET-E MX Sheet Version 2 Operating Manual (Introduction) -SW2DNC-SHEET-E SAFETY PRECAUTIONS (Read these precautions before using this product.) Before using this product, please read this manual and the relevant

More information

MELSEC iq-r PROFIBUS-DP Module User's Manual (Startup) -RJ71PB91V

MELSEC iq-r PROFIBUS-DP Module User's Manual (Startup) -RJ71PB91V MELSEC iq-r PROFIBUS-DP Module User's Manual (Startup) -RJ71PB91V SAFETY PRECAUTIONS (Read these precautions before using this product.) Before using this product, please read this manual and the relevant

More information

SAFETY PRECAUTIONS. (Read these precautions before using this product.)

SAFETY PRECAUTIONS. (Read these precautions before using this product.) SAFETY PRECAUTIONS (Read these precautions before using this product.) Before using MELSEC-Q, -L, or -F series programmable controllers, please read the manuals included with each product and the relevant

More information

GX Simulator Version 7 Operating Manual -SW7D5C-LLT-E

GX Simulator Version 7 Operating Manual -SW7D5C-LLT-E GX Simulator Version 7 Operating Manual -SW7D5C-LLT-E SAFETY PRECAUTIONS (Read these precautions before using this product.) Before using this product, please read this manual and the relevant manuals

More information

MELSEC-L CPU Module User's Manual (Function Explanation, Program Fundamentals)

MELSEC-L CPU Module User's Manual (Function Explanation, Program Fundamentals) MELSEC-L CPU Module User's Manual (Function Explanation, Program Fundamentals) -L02SCPU -L02SCPU-P -L02CPU -L02CPU-P -L06CPU -L06CPU-P -L26CPU -L26CPU-P -L26CPU-BT -L26CPU-PBT SAFETY PRECAUTIONS (Read

More information

SAFETY PRECAUTIONS. (Read these precautions before using this product.)

SAFETY PRECAUTIONS. (Read these precautions before using this product.) SAFETY PRECAUTIONS (Read these precautions before using this product.) Before using this product, please read this manual and the relevant manuals carefully and pay full attention to safety to handle the

More information

PX Developer Version 1 Operating Manual (JoyWatcherSuite Interaction) -SW1D5C-FBDQ-E -SW1D5C-FBDQMON-E

PX Developer Version 1 Operating Manual (JoyWatcherSuite Interaction) -SW1D5C-FBDQ-E -SW1D5C-FBDQMON-E PX Developer Version 1 Operating Manual (JoyWatcherSuite Interaction) -SW1D5C-FBDQ-E -SW1D5C-FBDQMON-E SAFETY PRECAUTIONS (Always read these instructions before using this product.) Before using this

More information

SAFETY PRECAUTIONS. (Read these precautions before using this product.)

SAFETY PRECAUTIONS. (Read these precautions before using this product.) SAFETY PRECAUTIONS (Read these precautions before using this product.) Before using this product, please read this manual and the relevant manuals carefully and pay full attention to safety to handle the

More information

HITACHI. EH-150 series PLC EH-RTD8 Resistance Temperature Detective input module Instruction manual. Safety precautions

HITACHI. EH-150 series PLC EH-RTD8 Resistance Temperature Detective input module Instruction manual. Safety precautions HITACHI EH-150 series PLC Resistance Temperature Detective input module Instruction manual Thank you for purchasing a Hitachi Programmable Logic Controller. To operate it safely, please read this instruction

More information

MODBUS Interface Module

MODBUS Interface Module MODBUS Interface Module User's Manual Mitsubishi Programmable Logic Controller QJ71MB91 GX Configurator-MB (SW1D5C-QMBU-E) SAFETY PECAUTIONS (Always read these instructions before using this product.)

More information

SAFETY PRECAUTIONS. (Read these precautions before using this product.)

SAFETY PRECAUTIONS. (Read these precautions before using this product.) SAFETY PRECAUTIONS (Read these precautions before using this product.) Before using this product, please read this manual and the relevant manuals carefully and pay full attention to safety to handle the

More information

Setting/Monitoring Tools for the C Controller Module Version 4 Operating Manual -SW4PVC-CCPU-E

Setting/Monitoring Tools for the C Controller Module Version 4 Operating Manual -SW4PVC-CCPU-E Setting/Monitoring Tools for the C Controller Module Version 4 Operating Manual -SW4PVC-CCPU-E SAFETY PRECAUTIONS (Read these precautions before using this product.) Before using this product, please

More information

Q Corresponding MELSECNET/H Network System Reference Manual (PLC to PLC network)

Q Corresponding MELSECNET/H Network System Reference Manual (PLC to PLC network) Q Corresponding MELSECNET/H Network System Reference Manual (PLC to PLC network) -QJ71LP21 -QJ71LP21-25 -QJ71LP21S-25 -QJ71LP21G -QJ71LP21GE -QJ71BR11 -QJ71NT11B SAFETY PRECAUTIONS (Read these precautions

More information

MELSEC iq-r OPC UA Server Module User's Manual (Startup) -RD81OPC96 -SW1DND-ROPCUA-E (MX OPC UA Module Configurator-R)

MELSEC iq-r OPC UA Server Module User's Manual (Startup) -RD81OPC96 -SW1DND-ROPCUA-E (MX OPC UA Module Configurator-R) MELSEC iq-r OPC UA Server Module User's Manual (Startup) -RD81OPC96 -SW1DND-ROPCUA-E (MX OPC UA Module Configurator-R) SAFETY PRECAUTIONS (Read these precautions before using this product.) Before using

More information

SAFETY PRECAUTIONS (Read these precautions before using this product.)

SAFETY PRECAUTIONS (Read these precautions before using this product.) SAFETY PRECAUTIONS (Read these precautions before using this product.) Before using this product, please read this manual and the relevant manuals carefully and pay full attention to safety to handle the

More information

SAFETY PRECAUTIONS (Read these precautions before using.)

SAFETY PRECAUTIONS (Read these precautions before using.) SAFETY PRECAUTIONS (Read these precautions before using.) Before using this product, please read this manual and the relevant manuals introduced in this manual carefully and pay full attention to safety

More information

MELSEC-L Serial Communication Module User's Manual (Basic) -LJ71C24 -LJ71C24-R2

MELSEC-L Serial Communication Module User's Manual (Basic) -LJ71C24 -LJ71C24-R2 MELSEC-L Serial Communication Module User's Manual (Basic) -LJ71C24 -LJ71C24-R2 SAFETY PRECAUTIONS (Read these precautions before using this product.) Before using this product, please read this manual

More information

MELSEC iq-r CC-Link IE Field Network Remote Head Module User's Manual (Startup) -RJ72GF15-T2

MELSEC iq-r CC-Link IE Field Network Remote Head Module User's Manual (Startup) -RJ72GF15-T2 MELSEC iq-r CC-Link IE Field Network Remote Head Module User's Manual (Startup) -RJ72GF15-T2 SAFETY PRECAUTIONS (Read these precautions before using this product.) Before using this product, please read

More information

MELSEC iq-r I/O Module User's Manual

MELSEC iq-r I/O Module User's Manual MELSEC iq-r I/O Module User's Manual -RX10 -RX10-TS -RX28 -RX40C7 -RX40C7-TS -RX41C4 -RX41C4-TS -RX42C4 -RX40PC6H -RX40NC6H -RX41C6HS -RX61C6HS -RX70C4 -RX71C4 -RX72C4 -RY10R2 -RY10R2-TS -RY18R2A -RY20S6

More information

SAFETY PRECAUTIONS (Always read these instructions before using this product.)

SAFETY PRECAUTIONS (Always read these instructions before using this product.) SAFETY PRECAUTIONS (Always read these instructions before using this product.) Before using this product, thoroughly read this manual and the relevant manuals introduced in this manual and pay careful

More information

SAFETY PRECAUTIONS (Always read these instructions before using this equipment.)

SAFETY PRECAUTIONS (Always read these instructions before using this equipment.) SAFETY PRECAUTIONS (Always read these instructions before using this equipment.) Before using this product, please read this manual and the relevant manuals introduced in this manual carefully and pay

More information

MELSEC iq-r C Controller Module/C Intelligent Function Module Programming Manual (Data Analysis)

MELSEC iq-r C Controller Module/C Intelligent Function Module Programming Manual (Data Analysis) MELSEC iq-r C Controller Module/C Intelligent Function Module Programming Manual (Data Analysis) SAFETY PRECAUTIONS (Read these precautions before using this product.) Before using C Controller module

More information

QA65B/QA68B Extension Base Unit

QA65B/QA68B Extension Base Unit QA65B/QA68B Extension Base Unit User s Manual Thank you for buying the Mitsubishi general-purpose programmable controller MELSEC-Q Series Prior to use, please read both this manual and detailed manual

More information

SAFETY PRECAUTIONS. (Read these precautions before using this product.)

SAFETY PRECAUTIONS. (Read these precautions before using this product.) SAFETY PRECAUTIONS (Read these precautions before using this product.) Before using this product, please read this manual and the relevant manuals carefully and pay full attention to safety to handle the

More information

H Series PLC. ! : Indicates Compulsion. EH-150 Analog input module EH-AXH8M Instruction manual. Safety precautions DANGER CAUTION COMPULSION

H Series PLC. ! : Indicates Compulsion. EH-150 Analog input module EH-AXH8M Instruction manual. Safety precautions DANGER CAUTION COMPULSION H Series PLC EH-150 Analog input module EH-AXH8M Instruction manual Thank you for purchasing a Hitachi Programmable Logic Controller. To operate it safely, please read this instruction manual and all the

More information

Programmable Controller. User's Manual (Multiple CPU System) QCPU SH(NA) ENG Version H INDUSTRIAL AUTOMATION MITSUBISHI ELECTRIC

Programmable Controller. User's Manual (Multiple CPU System) QCPU SH(NA) ENG Version H INDUSTRIAL AUTOMATION MITSUBISHI ELECTRIC MITSUBISHI ELECTRIC Programmable Controller User's Manual (Multiple CPU System) QCPU 01 12 2008 SH(NA)-080485ENG Version H MITSUBISHI ELECTRIC INDUSTRIAL AUTOMATION SAFETY PRECAUTIONS (Read these precautions

More information

SAFETY PRECAUTIONS. (Read these precautions before using this product.)

SAFETY PRECAUTIONS. (Read these precautions before using this product.) SAFETY PRECAUTIONS (Read these precautions before using this product.) Before using this product, please read this manual and the relevant manuals carefully and pay full attention to safety to handle the

More information

MELSEC iq-r PROFINET IO Controller Module User's Manual (Startup) -RJ71PN92

MELSEC iq-r PROFINET IO Controller Module User's Manual (Startup) -RJ71PN92 MELSEC iq-r PROFINET IO Controller Module User's Manual (Startup) -RJ71PN92 SAFETY PRECAUTIONS (Read these precautions before using this product.) Before using this product, please read this manual and

More information

CC-Link IE Field Network Waterproof Remote IO-Link Module User's Manual -NZ2GF12A-60IOLH8

CC-Link IE Field Network Waterproof Remote IO-Link Module User's Manual -NZ2GF12A-60IOLH8 CC-Link IE Field Network Waterproof Remote IO-Link Module User's Manual -NZ2GF12A-60IOLH8 COPYRIGHT This document is protected by the law of copyright, whereby all rights established therein remain with

More information

Transition from MELSEC-I/OLINK to AnyWire DB A20 Handbook

Transition from MELSEC-I/OLINK to AnyWire DB A20 Handbook Transition from MELSEC-I/OLINK to AnyWire DB A20 Handbook Dec. 2018 Edition SAFETY PRECAUTIONS (Read these precautions before using this product.) Before using products introduced in this handbook, please

More information

CW Configurator Operating Manual -SW1DND-RCCPU-E

CW Configurator Operating Manual -SW1DND-RCCPU-E CW Configurator Operating Manual -SW1DND-RCCPU-E SAFETY PRECAUTIONS (Read these precautions before using this product.) Before using this product, please read this manual and the relevant manuals carefully,

More information

MELSEC iq-r MES Interface Module User's Manual (Startup) -RD81MES96 -SW1DND-RMESIF-E(MX MESInterface-R)

MELSEC iq-r MES Interface Module User's Manual (Startup) -RD81MES96 -SW1DND-RMESIF-E(MX MESInterface-R) MELSEC iq-r MES Interface Module User's Manual (Startup) -RD81MES96 -SW1DND-RMESIF-E(MX MESInterface-R) SAFETY PRECAUTIONS (Read these precautions before using this product.) Before using this product,

More information

Output Terminal Module

Output Terminal Module Output Terminal Module FA-TH16YRA11/11S/20/20S/20SL/21/21S,FA-TH16YRAC20S, FA-TH16YRAB20SL,FA-TH16YSR11S/20S/21S, FA-TH16YTL11S/21S,FA-TH16YTH11S,FA-TH16YTR20S, FA-TH16Y2TR20,FA-THE16YTH11S,FA-THE16YTR20S

More information

GX Works2 Beginner's Manual (Structured Project) -SW1DND-GXW2-E -SW1DNC-GXW2-E

GX Works2 Beginner's Manual (Structured Project) -SW1DND-GXW2-E -SW1DNC-GXW2-E GX Works2 Beginner's Manual (Structured Project) -SW1DND-GXW2-E -SW1DNC-GXW2-E SAFETY PRECAUTIONS (Always read these instructions before using this product.) Before using this product, thoroughly read

More information