Digital On-Load Tap Changer Voltage Controller TAPCON 250 Operating Instructions (short version) BA 289
|
|
- Sherman Norris
- 6 years ago
- Views:
Transcription
1 Digital On-Load Tap Changer Voltage Controller Operating Instructions (short version) BA 289 Defined movement of the drive shaft REGULATING TRANSFORMER Changing the Transformer Ratio MOTOR-DRIVE Drive Shaft Actual voltage LOAD PROFILE Need of Power Changes Control pulse for changing the tap position Regulating circuit Power grid REFERENCE VOLTAGE LEVEL TAPCON Matching Actual and Reference Voltage
2 Contents 1 Safety Technical Data/Information General Information Connection User Interface Typical External Connections Parameters Accessories NOTE! The product may have been modified after this document went to press. We expressly reserve the right to make changes to the technical data, the design or the scope of delivery. In general, the information provided and the arrangements agreed during processing of the relevant offers and orders are binding. 2 Operating Instructions - short version
3 1 Safety 1.1 Safety labels The following safety labels relating to the operation of the are used in these operating instructions. These labels must be observed at all times! DANGER! Refers to an imminent danger that may result in death or severe injury. WARNING! Refers to a potentially hazardous situation that may result in death or severe injury. CAUTION! Refers to a potentially hazardous situation that may result in slight injury or material damage. NOTE! Contains important information and special notes. Special safety labels are used for certain hazards, such as electric shock. The following specific safety warnings are used in these operating instructions: DANGER! Fire hazard! DANGER! Risk of electric shock! Operating Instructions - short version
4 1.2 Safety instructions All warnings and safety instructions must be observed at all times! Danger of death and risk of injury! Not following the safety instructions may lead to accidents and severe personal injury. Please read these operating instructions before commissioning the equipment! Read the operating instructions before commissioning the. As operator, you are responsible for ensuring that users of the equipment have fully understood the operating and safety instructions. Always connect the to an electrical ground! To avoid shock hazard, the chassis must be connected to an electrical ground. When servicing the in a test area, the protective earth terminal must be attached to a seperate ground securely by use of a tool since it is not grounded by external connectors. Only suitably qualified personnel should work at the TAPCON 250! The contains high voltages which can cause serious injury or death! It is designed exclusively for application in electrical or energy systems and facilities operated by appropriately trained staff who are familiar with the installation, operation and maintenance of such products. Exercise due care when operating or servicing alone. Do not operate the in an explosive environment! Do not operate this equipment in the presence of flammable or explosive gases or fumes. To do so would risk a possible fire or explosion. Keep away from live circuits! Operating personnel must not remove the cover or expose the printed circuit board while power is applied. Dangerous voltages may exist even when power is disconnected. To avoid electrical shock, always disconnect 4 Operating Instructions - short version
5 power and discharge circuits before working on the unit. Do not modify the! Do not perform any unauthorized changes on the. Contact Reinhausen Manufacturing regarding any modification. If authorized modifications are to be attempted, be sure to follow replacement procedures carefully to assure that safety features are maintained. Avoid static charge! The contains MOS circuitry which can be damaged by improper test or rework procedures. Avoid static charge on work surfaces and service personnel. Use extreme caution during any diagnostic work! Any attempt to perform any diagnostic work or connection between points on the printed circuit board, unless services noted in the Operating Instructions is likely to cause damage or permanent failure to the. Operating Instructions - short version 5
6 2 Technical Data/Information 2.1 Environmental Temperature Operation IEC IEC High voltage IEEE C ,000 Vpk IEC ,500 VAC rms to ground for one minute with a leakage current not to exceed 15 ma (except communication ports, CAN bus terminals P1 and terminals P P2.37) Contact Discharge +/-8kV Air Discharge +/-15 kv Fast Transient Burst Electrostatic discharge test IEC V/m, ,000 MHz Immunity against HF fields IEC khz (1 min.) Fast transient disturbance test IEC ,000 Vpk Immunity against Surge IEC V, 150 khz MHz Immunity against HF on lines IEC F F (-25 C C)* * extended temperature range on demand Applicable Standards Dry Cold -40 F/ -40 C for 96 hours Dry Heat +176 F/ +80 C for 96 hours IEC Damp Heat 104 F/ +40 C for 96 hours, rel. air humidity 93% IEC Damp Heat, cyclic (12 h +12 h), 131 F/ 55 C, stress duration: 6 cycles Mold Resistance A conformal coating on the printed circuit is used to inhibit mold growth. 2.2 Transient Protection 1,000 A/m, 60 Hz, continuous Radiated electromagnetic withstand capability Immunity against magnetic fields All units are protected against electromagnetic radiated interference from portable communications transceivers. Operating Instructions - short version
7 2.3 Industrial Certifications TAPCON250 is a UL Listed (Industrial Control Equipment) device. 2.4 Technical Data Protective Housing Dimensions Weight Protective Housing 5.81 x 8.5 x 3.08 (W x H x D) (147.6 x 216 x 78.2 mm) approx. 6.2 lbs (2.8 kgs) 2.5 Warranty The is offered with an extended warranty. Operating Instructions - short version 7
8 3 General Information These operating instructions provide a quick overview of the main functions of the voltage controller, enabling you to put the device into operation very quickly. More comprehensive information about the configuration and operating principle of the voltage controller along with settings for special applications can be found in the following document: Operating instructions BA297 Digital On-Load Tap Changer Voltage Controller. 4 Connection The is powered by a measurement voltage from a potential source ranging from 85 to 140 VAC ( Hz) on pin P2.1(Line) and pin P2.3(Neutral). The voltage controller alternatively accepts an external 12 VDC power supply on terminal P3, [P3.1(+) and P3.2(-)], for continuous operation during an AC power outage. Assembly instructions Familiarize yourself with the inputs and outputs at the bottom of the voltage controller. Ensure proper grounding of the voltage controller by means of the chassis ground screw attached to the housing. This connection maintains the EMC characteristics of the device. Connect the voltage controller according to the wiring diagram, the connection diagram (see fig. 3; for detailed description see operating instructions BA297) and according to the wiring diagram of the respective motor-drive. Refer to specific adapter panel information provided separately for wiring details. 8 Operating Instructions - short version
9 5 User Interface Raise/Lower command LEDs Remote Manual Automatic operating modes Contrast Serial interface COM2 (Parameter Software only) Function keys Status LED Scroll arrow keys show measured values and navigate menus Enter Escape Menu Fig. 1: Front panel 5.1 Description of the front panel (see fig. 1) LEDs The LEDs indicate overcurrent, under voltage, overvoltage, parallel active, NORMset active and (4) assignable functions or modes. Function keys F1 F5 These soft keys are used to navigate the menu sub-groups or adjust specific parameter settings in the input screens. Status LED If the status LED is illuminated, the device is working properly. MENU key This key, when pressed, displays the initial menu screen. Operating Instructions - short version 9
10 ESC key The ESC key, when pressed, displays the previous higher menu level or returns to the operating display. Enter key Once a value or setting is changed in a specific parameter menu, this key must be pressed to enter the new parameter into the operating memory. Arrow keys In Auto and Manual mode, the arrow keys can be used for changing the Measured value display (see display layout, Fig. 2) and for navigating between the parameter screens within a menu sub-group. Automatic mode Indication only; this mode can be controlled separately by a 120VAC input (see fig. 3). Manual mode Indication only; this mode can be controlled separately by a 120VAC input (see fig. 3). Remote mode Indication only; this mode can be controlled separately by a 120 VAC input (see fig. 3). Raise/Lower keys The on-load tap-changer can be operated via the Raise/Lower keys (changing the step voltage). During Auto mode, the raise/lower command has to be confirmed with Enter in the upcoming display before the signals a raise/lower command. Changing the measured value display By default, the system deviation rate du is displayed first when the device is switched on. Deviation - du - current (A) - apparent power (VA) - active power (W) - reactive load (VAr) - phase angle (deg.) - Cos can also be displayed by pressing the scroll arrow keys. Serial interface COM 2 The COM2 port used to connect the voltage controller with a PC only for parameter settings. The TAPCON-trol system parameter software and interface cable are included with each controller. 10 Operating Instructions - short version
11 5.2 Description of the display (see fig. 2) Status line; displays menu items or error/alarm messages 2 Actual measured voltage level in V/kV 3 Reference or alternate voltage level in V/kV 4 Measured value display (voltage deviation and other values) 5 Tap changer operating position 6 Deviation from reference or alternate voltage level 7 Timing bar Fig. 2: LCD graphic display Operating Instructions - short version 11
12 6 External Connections 12 Operating Instructions - short version
13 Notes 1. Motor voltage may be 120 or 240 V to neutral, or 240 V phase-to-phase. 2. A ground connection has to be provided to the CT/VT s neutral connection, external to the control. WARNING! WARNING! When an adapter panel is not used, automatic shorting of CT inputs is not provided by the ; the customer must provide a method for shorting the CT s before the control is disconnected. When an adapter panel is not used, the has to be protected by an external fuse (0.375 A, slo-blo ) on pin P2.1. Fig. 3: Wiring scheme for definition of external connections Operating Instructions - short version 13
14 7 Parameters 7.1 NORMset Activating the NORMset function Menu => NORMset => NORMset Activation The term NORMset function stands for an automated control function which considerably simplifies the parameter setting of a voltage controller. The only requirement left to do for the operator when commissioning during the NORMset mode is to enter the reference voltage level and, if required, the CT/VT values and subsequently place the device into operation. All other parameters required for simple voltage regulation will be preassigned at the factory (e. g. bandwidth of 1 %). Should the actual value exceed the set bandwidth, an appropriate switching operation will be initiated at the on-load tap-changer. The voltage change ensuing from the switching operation corresponds to the transformer s tap voltage and is checked for plausibility by the controller, using the preset bandwidth. The bandwidth value is then corrected and optimized in accordance with the results determined by this function/mode. If the next system deviation occurs, the new bandwidth will be used as basis, which will be rechecked and readjusted, if necessary. Should the marginal conditions change, the controller will again optimize itself automatically. Specific settings such as LDC, parallel operation or position display among others are still applicable and can be changed in the standard mode. These settings will be taken into consideration during the NORMset mode of operation to optimize the voltage and the use of the tap changer. 14 Operating Instructions - short version
15 Setting the primary voltage NOTE! The parameters for undervoltage/ overvoltage and overcurrent are not set by the NORMset function. If required, these parameters have to be entered manually during commissioning/initiation. The NORMset function is deactivated during parallel operation. Menu => NORMset => Primary voltage Setting range: kv Setting the secondary voltage Menu => NORMset => Secondary voltage Setting range: V Operating Instructions - short version 15
16 Setting the reference voltage level 1 within NORMset Menu => NORMset => Reference voltage level 1 Setting range: V The setting of the reference voltage level 1 refers either to the secondary or to the primary voltage side of the voltage transformer connected to the TAPCON 250. The secondary voltage is displayed in Volt (V), the primary voltage in kilovolt (kv). If NORMset function is off for operation, the reference voltage level 1 can be set in the PARAMETER menu subgroup. This display requires the correct input of the CT/VT data in the following two menu windows. 7.2 CT/VT data Menu => Configuration The transformer ratios and measuring values of the voltage and current transformers applied can be set in the corresponding menus within the CONFIGURATION subgroup and use of the soft function keys F1 thru F5. Setting the primary VT voltage Menu => Configuration => Data of meas. Trf. => Primary voltage Setting range: kv 16 Operating Instructions - short version
17 Setting the secondary VT voltage Menu => Configuration => Data of meas. Trf. => Secondary voltage Setting range: V Setting the primary CT current Menu => Configuration => Data of meas. Trf. => Primary current Setting range: ,000 A Setting the phase angle relationship of current/voltage transformers This setting of the conventional measuring circuits is in accordance with fig. 4. Menu => Configuration => Data of meas. Trf. => Instr. transformer circuit Operating Instructions - short version 17
18 Fig. 4: Measurement circuits 18 Operating Instructions - short version
19 Setting the time and date Menu => Configuration => Continue => Memory Press the Right Arrow key (screen 06) six times to view the input field for the system time. Press the F4 function key to select the digit(s) you want to edit and then press the F1 and F5 keys to set the display forward or backward in one-step increments. The time format in HH:MM:SS is available in a 24-hour format. Press the Right Arrow key (screen 07) seven times to view the input field for the system date. Press the F4 function key to select the digit(s) you want to edit and then press the F1 and F5 keys to set the display forward or backward in one-step increments. The date format in DD.MM.YY can be set to any date between 01/01/2001 and 29/12/ Parallel operation settings (optional) Setting of parallel operation principle Menu => Configuration => Parallel operation => Parallel operation method Set the desired parallel operation principle by pressing the F1 and F5 function keys. Operating Instructions - short version 19
20 Setting options: Off = no parallel operation Circulating current = parallel operation following the current principle of minimum circulating reactive current Master = Master/Follower principle: the controller assumes Master function Follower = Master/Follower principle: the controller assumes Follower function Synchr.Auto = Master/Follower principle: with this setting, the controller with the lowest CAN address of all connected controllers is automatically selected as Master. XPA = Parallel operation with the TAPCON-XPA, external Paralleling Assistant, following the principle of minimum circulating reactive current with CT circuits connected between power transformers. Parallel control according to the Master/Follower principle requires no further settings other than the T1 and T2 delay times must be greater than 8 seconds. In each case, the voltage controllers engaged in parallel operation have to be connected either via the CAN bus interface (see fig. 4) or via the TAPCON- XPA (ANSI scheme). Note: Please remember that the CAN bus must be connected with a resistor of 120 Ω at both ends (at the first and last controller). The resistor is included in the scope of delivery. CAN Address To permit controller communication via CAN bus, each individual controller needs a separate identifier. Menu => Configuration => Parallel operation => CAN Address Assign a number as address to each controller by pressing the F1 or F5 function keys. The values assigned as CAN address may range between 1 and = no CAN bus communication 20 Operating Instructions - short version
21 7.4 Regulating parameters This specific sub-group contains all parameters required for the regulating functions. Menu => PARAMETER Example of Parameter Adjustment Setting the reference voltage level 1 Menu => Parameter => Regulation param. => Reference voltage level 1 Setting range: V Operating Instructions - short version 21
22 8 Accessories For further information on: Analog Input/Output extension Communication Interface Card with RS232, RS485, Modem/Ethernet and fiber optic connection Adapter Panels please contact Reinhausen Manufacturing or 22 Operating Instructions - short version
23 Fig. 5: Connection diagram Operating Instructions - short version 23
24 Reinhausen Manufacturing Inc. Phone: (+1)731/ North 9th Avenue Fax: (+1)731/ Humboldt, Tennessee 38343, USA BA en 0407/300 F Printed in USA
Voltage Controller TAPCON 250
www.reinhausen.com Voltage Controller TAPCON 250 Quick Reference Guide 2009 All rights reserved, Maschinenfabrik Reinhausen Unauthorised copying and distribution of this document and the utilisation and
More informationTAPCON 250 DIGITAL ON-LOAD TAP-CHANGER CONTROLLER FOR VOLTAGE REGULATING TRANSFORMERS.
TAPCON 250 DIGITAL ON-LOAD TAP-CHANGER CONTROLLER FOR VOLTAGE REGULATING TRANSFORMERS. WWW.REINHAUSEN.COM TAPCON 250 TAPCON 250 THE NEW GENERATION OF VOLTAGE CONTROLLERS. For more than 40 years voltage
More informationTAPCON 230 Voltage Regulator for Regulating Transformers
www.reinhausen.com TAPCON 230 Voltage Regulator for Regulating Transformers TAPCON Voltage regulators of the next generation TAPCON : a name which stands for a completely new range of voltage regulators
More informationTF501, TF521 Terminal Bases
Ordering Data DATA SHEET TF501, TF521 Terminal Bases 1 Ordering Data Part No. Scope of delivery Product life cycle status 1SAP 117 000 R0271 1SAP 317 000 R0271 1SAP 117 200 R0271 1SAP 317 200 R0271 TF501-CMS,
More informationTAPCON 240 Voltage Regulator for Regulating Transformers
www.reinhausen.com TAPCON 240 Voltage Regulator for Regulating Transformers TAPCON The next generation of voltage regulators TAPCON : a name which is synonymous for an entirely new and ground-breaking
More informationINSTRUCTION MANUAL TRIP CIRCUIT SUPERVISION RELAY GKAD1
INSTRUCTION MANUAL TRIP CIRCUIT SUPERVISION RELAY GKAD1 TOSHIBA Corporation 2004 All Rights Reserved. ( Ver. 1.6 ) Safety Precautions Before using this product, please read this chapter carefully. This
More informationModel 7705 Control Module
www.keithley.com Model 7705 Control Module User s Guide PA-696 Rev. D / October 2006 A G R E A T E R M E A S U R E O F C O N F I D E N C E Safety Precautions The following safety precautions should be
More informationTU531, TU532 Terminal Unit
Ordering Data DATA SHEET TU531, TU532 Terminal Unit 1 Ordering Data Part No. Description Product Life Cycle Phase *) 1SAP 217 200 R0001 1SAP 217 000 R0001 1SAP 417 000 R0001 TU531, terminal unit, 230 VAC,
More informationApplication Guide. M 2174B Moloney Replacement Adapter Panel
Application Guide M 174B Moloney Replacement Adapter Panel CONTROLS Replacement Panel M 174B Adapts M 001 Series Digital Tapchanger Control to Replace Moloney/Tempo LTC Control Panel Connects easily to
More informationPart No. Description Product Life Cycle Phase *) unit, 24 VDC, spring terminals. unit, 24 VDC, spring terminals, XC version
Ordering Data DATA SHEET TU520 Terminal Unit 1 Ordering Data Part No. Description Product Life Cycle Phase *) 1SAP 214 400 R0001 1SAP 414 400 R0001 TU520-ETH, PROFINET I/O terminal unit, 24 VDC, spring
More informationMultifunctional time delay relay MFT U31S, MFT U41SE
8 Functions, 8 time ranges Multivoltage: 24 Vac / dc 110... 240 Vac 2 output contacts MFT U31S Functions E Delay on E Delay on - version with control contact as opening contact A Delay off without auxiliary
More informationContent. Time delay relays mounting position. Multifunctional time delay relay Clock-pulse generator time delay relay... 3.
Content Time delay relays mounting position Multifunctional time delay relay... 3.2 Clock-pulse generator time delay relay... 3.10 Multifunctional clock-pulse generator relay... 3.14 Technical safety advice...
More informationekorrps MULTIFUNCTIONAL PROTECTION UNIT CONFIGURATION AND GENERAL CHARACTERISTICS LIB
MO-067-EN Operation Manual MULTIFUNCTIONAL PROTECTION UNIT CONFIGURATION AND GENERAL CHARACTERISTICS LIB Transformer Substations Secondary Distribution Switchgear Primary Distribution Switchgear Protection
More informationAnalog display for resistance current
www.reinhausen.com Analog display for resistance current Operating Instructions BA 2220061/01 NOTE The product may have been modified after this document went to press. We expressly reserve the right to
More informationHV-CS kv Edge Mount Triaxial Jack
Keithley Instruments 28775 Aurora Road Cleveland, Ohio 44139 1-800-935-5595 http://www.tek.com/keithley HV-CS-1589 3 kv Edge Mount Triaxial Jack Installation Information Description The Keithley Instruments
More informationAO523 Analog Input Module
Ordering Data DATA SHEET AO523 Analog Input Module 1 Ordering Data Part No. Description Product Life Cycle Phase *) 1SAP 250 200 R0001 1SAP 450 200 R0001 AO523, analog output module, 16 AO, U/I, 12 bits
More informationQUICK START GUIDE. vau4/3. Frequency converter. operating instructions /12
operating instructions QUICK START GUIDE Frequency converter vau4/3 28100241101 12/12 1 Safety information Warning of electrical shock! Danger to life! Electrical shock can cause serious injury or even
More informationACCESS 9340/9360 Meter Input/Output Module
Installation Manual PMIM-IOMOD-0208 ACCESS 9340/9360 Meter Input/Output Module 9340-60-I/O2222 and 9340-60-I/O26 HAZARD CATEGORIES AND SPECIAL SYMBOLS Read these instructions carefully and look at the
More informationType VRLTC tap changer
Report No. 1ZUA938502-AGC 2, Rev 0 Date: 6 November 2012 Type VRLTC tap changer Ruggedized electronics systems specification & type test data Product Style No Rating By Type VRLTC, on-tank, vacuum reactance
More informationModel 8020-KHV. Kelvin Keithley Triaxial Connector Card. Description / October 2014 *P * 1
Keithley Instruments 28775 Aurora Road Cleveland, Ohio 44139 1-800-935-5595 http://www.keithley.com Model 8020-KHV Kelvin Keithley Triaxial Connector Card Description The Model 8020-KHV Keithley HV Connector
More informationtapcon 230 user-friendly, FleXiBle and reliable. transformer control
tapcon 230 user-friendly, FleXiBle and reliable. transformer control Tapcon 230 tapcon 230 the new standard in voltage control. 2 Maschinenfabrik Reinhausen (MR) has been developing and manufacturing voltage
More informationAX521 Analog Input/Output Module
Ordering Data DATA SHEET AX521 Analog Input/Output Module 1 Ordering Data Part No. Description Product Life Cycle Phase *) 1SAP 250 100 R0001 1SAP 450 100 R0001 AX521, analog input/output module, 4 AI,
More informationDC532-XC, digital input/output module,
Ordering Data DATA SHEET DC532 Digital Input/Output Module 1 Ordering Data Part No. Description Product Life Cycle Phase *) 1SAP 240 100 R0001 1SAP 440 100 R0001 DC532, digital input/output module, 16
More informationCD522 Encoder, Counter and PWM Module
Ordering Data DATA SHEET CD522 Encoder, Counter and PWM Module 1 Ordering Data Part No. Description Product Life Cycle Phase *) 1SAP 260 300 R0001 1SAP 460 300 R0001 CD522, encoder & PWM module, 2 encoder
More informationThis 4200-RM Rack Mount Kit is for installation in 4200-CAB series cabinets only.
Keithley Instruments, Inc. 28775 Aurora Road Cleveland, Ohio 44139 (440) 248-0400 Fax: (440) 248-6168 www.keithley.com Model 4200-RM Rack Mount Kit Packing List Introduction NOTE This 4200-RM Rack Mount
More informationInteliPro. Protection Relay for Parallel Applications. Technical Specification
InteliPro Protection Relay for Parallel Applications Product description InteliPro is a highly flexible interconnection/mains decoupling protective relay with extensive protective functions. It meets the
More informationMC 11 EB-2 Power supply cabinet with external bus, AC version
MC 11 EB-2 Power supply cabinet with external bus, AC version USER/MAINTENANCE MANUAL 1 SLOT 0 SLOT 1 SLOT 2 SLOT 3 SLOT 4 SLOT 5 SLOT 6 SLOT 7 SLOT 8 SLOT 9 SLOT 10 SLOT 11 EB-2 (a) MC11 (b) (c) Figures
More informationModel 8020-STC. Kelvin Standard Triaxial Connector Card. Description / October 2014 *P * 1
Keithley Instruments 28775 Aurora Road Cleveland, Ohio 44139 1-800-935-5595 http://www.keithley.com Model 8020-STC Kelvin Standard Triaxial Connector Card Description The Model 8020-STC Kelvin Standard
More informationDC541 Digital Input/Output Module
Ordering Data DATA SHEET DC541 Digital Input/Output Module 1 Ordering Data Part No. Description Product Life Cycle Phase *) 1SAP 270 000 R0001 1SAP 470 000 R0001 DC541-CM, digital input/output module,
More informationDC522 Digital Input/Output Module
Ordering Data DATA SHEET DC522 Digital Input/Output Module 1 Ordering Data Part No. Description Product Life Cycle Phase *) 1SAP 240 600 R0001 1SAP 440 600 R0001 DC522, digital input/output module, 16
More informationAX522 Analog Input/Output Module
Ordering Data DATA SHEET AX522 Analog Input/Output Module 1 Ordering Data Part No. Description Product Life Cycle Phase *) 1SAP 250 000 R0001 1SAP 450 000 R0001 AX522, analog input/output module, 8 AI
More informationINSTALLATION DKM-409 NETWORK ANALYSER WITH HARMONIC MEASUREMENT AND SCOPEMETER. Before installation:
DKM-409 NETWORK ANALYSER WITH HARMONIC MEASUREMENT AND SCOPEMETER The DKM-409 is a precision instrument designed for displaying various AC parameters in 3-phase distribution panels. Thanks to its isolated
More informationMCCB-250 MOLDED-CASE CIRCUIT BREAKER TESTER
MCCB-250 MOLDED-CASE CIRCUIT BREAKER TESTER USER S MANUAL Vanguard Instruments Company, Inc. 1520 S. Hellman Ave. Ontario, California 91761, USA TEL: (909) 923-9390 FAX: (909) 923-9391 January 2015 Revision
More informationRedundancy unit CP-A RU
2CDC 271 010 F0t06 Features Decoupling of CP power supply units with 2 inputs, each up to 20 A per input / channel Output up to 40 A True redundancy by 100 % decoupling of two parallel connected power
More informationCM592 PROFIBUS Communication Module
Ordering Data DATA SHEET CM592 PROFIBUS Communication Module 1 Ordering Data Part No. Description Product Life Cycle Phase *) 1SAP 173 200 R0001 1SAP 373 200 R0001 CM592-DP, communication module PROFIBUS
More informationModel 2460-KIT. Screw Terminal Connector Kit. Description / September 2014 *P * 1
Keithley Instruments 28775 Aurora Road Cleveland, Ohio 44139 1-800-935-5595 http://www.keithley.com Model 2460-KIT Screw Terminal Connector Kit Description The Model 2460-KIT Screw Terminal Connector Kit
More informationAI531 Analog Input Module
Ordering Data DATA SHEET AI531 Analog Input Module 1 Ordering Data Part No. Description Product Life Cycle Phase *) 1SAP 250 600 R0001 AI531, analog input module, 8 AI, U/I/Pt100, TC, 15 bits + sign, 4-wires
More informationSIPROTEC easy 7SJ45 Numerical Overcurrent Protection Relay Powered by CTs
SIPROTEC easy 7SJ4 Numerical Overcurrent Protection Relay Powered by CTs Function overview Fig. /1 Description The SIPROTEC easy 7SJ4 is a numerical overcurrent protection relay which is primarily intended
More informationRT12-240V/2.4kW Rectifier Specification
The RT12-240V/2.4kW is a switched mode rectifier (SMR) module that delivers up to 2.4kW of output power (and up to 11A output current) into a 240V nominal DC system. The RT12 suits AC supply voltages between
More informationPHOENIX CONTACT - 01/2010. Features. DANGER OF EXPLOSION! Only remove equipment when it is disconnected and not in the potentially explosive area.
Uninterruptible power supply with integrated power supply unit INTERFACE Data sheet 104211_en_00 1 Description PHOENIX CONTACT - 01/2010 Features The MINI-DC-UPS provide an uninterruptible DC voltage both
More informationUniversal Power Supplies
, Features Universal input: 90 264 VAC or 120 30 VDC Active power factor correction (>0.95) High efficiency up to 93% Load share function for up to 3 units in parallel Adjustable output voltage EMI/EMC
More informationCVU-3K-KIT. 3 kv Bias Tee Kit. Description. Parts list / October 2014 *P * 1
Keithley Instruments 28775 Aurora Road Cleveland, Ohio 44139 1-800-935-5595 http://www.keithley.com CVU-3K-KIT 3 kv Bias Tee Kit Description The CVU-3K-KIT Bias Tee Kit consists of three bias tees for
More informationCVU-200-KIT. 200 V Bias Tee Kit. Description. Parts list / October 2014 *P A* 1
Keithley Instruments 28775 Aurora Road Cleveland, Ohio 44139 1-800-935-5595 http://www.keithley.com CVU-200-KIT 200 V Bias Tee Kit Description The CVU-200-KIT Bias Tee Kit consists of three 2600-RBT-200
More informationRT4F-110V/25A RECTIFIER
The RT4F-110V/25A is a hot-pluggable switched mode rectifier (SMR) module designed to provide up to 25A of output current into a 110V nominal system. Examples of such systems are 60 cells lead acid (136V
More informationModel 2380 Rack-Mount Kit
Keithley Instruments 28775 Aurora Road Cleveland, Ohio 44139 1-800-935-5595 http://www.tek.com/keithley Model 2380 Rack-Mount Kit Installation Instructions Introduction The Model 2380 Fixed Rack-Mount
More informationRT4F-48V/50A-WAC RECTIFIER
The RT4F-48V/50A-WAC is a switched mode rectifier (SMR) module designed to provide up to 58A of output current into a 48V nominal system, over a wide range of AC input voltage. This rectifier has been
More informationEnglish. Operating manual. Universal transmitter UT125. Save for later reference. Companies / brands of GHM
English Operating manual Universal transmitter UT125 Companies / brands of GHM www.ghm-messtechnik.de Save for later reference. Table of contents page 1. Intended use (areas of application)... 3 1.1 Safety
More informationModels 2601B, 2602B, and 2604B System SourceMeter Instruments Quick Start Guide
Models 2601B, 2602B, and 2604B System SourceMeter Instruments Quick Start Guide Safety precautions Observe the following safety precautions before using this product and any associated instrumentation.
More informationCM589 PROFINET Communication Module
Ordering Data DATA SHEET CM589 PROFINET Communication Module 1 Ordering Data Part No. Description Product Life Cycle Phase *) 1SAP 172 900 R0011 1SAP 372 900 R0011 1SAP 172 900 R0111 1SAP 372 900 R0111
More informationCI542 PROFIBUS Communication Interface Module
Ordering Data DATA SHEET CI542 PROFIBUS Communication Interface Module 1 Ordering Data Part No. Description Product Life Cycle Phase *) 1SAP 224 200 R0001 1SAP 424 200 R0001 CI542-DP, PROFIBUS DP bus module,
More informationCM579-PNIO PROFINET Communication Module
Ordering Data DATA SHEET CM579-PNIO PROFINET Communication Module 1 Ordering Data Part No. Description Product Life Cycle Phase *) 1SAP 170 901 R0101 1SAP 370 901 R0101 CM579-PNIO, PROFINET communication
More information2260B-RMK-Series Rack Mount Kit
Keithley Instruments, Inc. 28775 Aurora Road Cleveland, Ohio 44139 1-888-KEITHLEY http://www.keithley.com Assembly and Mounting Instructions Introduction The 2260B-RMK-Series Rack Mount Kit is suited for
More informationIPD163C. Single-Phase Multifunction Meter User Manual Version: V1. August 20, 2017
163C Single-Phase Multifunction Meter User Manual Version: V1 August 20, 2017 This manual may not be reproduced in whole or in part by any means without the express written permission from IPD. The information
More informationApplication Guide. M-2053 Adapter Panel
Application Guide M-2053 Adapter Panel CONTROLS Adapter Panel M 2053 Adapts M 2001 Series Digital Tapchanger Control for Surface Mounting Applications Connects easily to the M 2001 Series Digital Tapchanger
More informationModel 8010 High Power Device Test Fixture Interconnection Reference Guide
Model 8010 High Power Device Test Fixture Interconnection Reference Guide Safety precautions Observe the following safety precautions before using this product and any associated instrumentation. Although
More informationRT4B-110V/12A RECTIFIER
The RT4B-110V/12A is a switched mode rectifier (SMR) module designed to provide up to 12A of output current into a 110V nominal system. It can be used with or without a cooling fan. With a fan it runs
More informationMDM 011-Z1 Regen Resistor
MDM 011-Z1 Regen Resistor Date of creation: 10.04.2017 Version date: 10.04.2017 Article number: 09-402-011-Z1-E Publisher: SIGMATEK GmbH & Co KG A-5112 Lamprechtshausen Tel.: 06274/4321 Fax: 06274/4321-18
More informationPMT. Model Number: Model Number Input Voltage Range Output Voltage Output Current PMT-5V350W1A (Selectable by Switch)
PMT Highlights & Features AC input range selectable by switch Full Aluminium casing for light weight and corrosion resistant handling Built-in automatic fan speed control circuit Wide operating temperature
More information300 WATT, PFC, OPEN FRAME POWER SUPPLIES TABLE 1. OUTPUT RATINGS AND SPECIFICATIONS, RMW 300W SERIES
INSTRUCTION MANUAL KEPCO An ISO 9001 Company. 300 WATT, PFC, OPEN FRAME POWER SUPPLIES RMW 300W SERIES I INTRODUCTION SCOPE OF MANUAL. This instruction manual covers the installation and operation of the
More informationRT4F-120V/20A-WAC RECTIFIER
The RT4F-120V/20A-WAC is a switched mode rectifier/charger module designed to provide up to 20A of output current into a 120V nominal system. This charger has been designed for use in conjunction with
More informationP3-SCM. General Specifications
General Specifications Module Type Modules per Base Modules per Group I/O Points Used Field Wiring Connector Operating Temperature Storage Temperature Humidity Environmental Air Vibration Shock Field to
More informationPHOENIX CONTACT - 07/2006
Buffer module with maintenance-free capacitor-based power storage device INTERFACE Data sheet 102035_03_en PHOENIX CONTACT - 07/2006 Description Short-term mains interruptions are bridged by QUINT BUFFER,
More informationOperating instructions. Standstill monitor A / / 2011
Operating instructions Standstill monitor A300 UK 1 2 3 4 5 6 7 8 7390337 / 01 02 / 2011 1 2 3 4 5 6 7 8 switchpoint min max pulse/min power Made in Germany ifm electronic gmbh D 45127 Essen func. I II
More informationDM-918 OPERATIONS MANUAL AUTORANGING MULTIMETER
DM-918 OPERATIONS MANUAL AUTORANGING MULTIMETER SAFETY INFORMATION The following safety information must be observed to ensure maximum personal safety during the operation of this meter: This meter is
More informationCI504 PROFINET Communication Interface Module
Ordering Data DATA SHEET CI504 PROFINET Communication Interface Module 1 Ordering Data Part No. Description Product Life Cycle Phase *) 1SAP 221 300 R0001 1SAP 421 300 R0001 CI504-PNIO, PROFINET Bus Module
More informationModel 2600B-PM V Protection Module with 1 A Clamp. Description / April 2015 *PPA * 1
Keithley Instruments 28775 Aurora Road Cleveland, Ohio 44139 1-800-935-5595 http://www.keithley.com Model 2600B-PM-1 200 V Protection Module with 1 A Clamp Description The Model 2600B-PM-1 200 V Protection
More informationSPA-ZC 302. Profibus-DPV1/SPA Gateway. Product Guide. spa-zc302_rightco300
Profibus-DPV1/SPA Gateway SPA-ZC 302 Product Guide spa-zc302_rightco300 Issued: 25.11.2003 Status: Updated Version: D/16.05.2008 Data subject to change without notice Features Profibus DP Version 1 connectivity
More informationVoltage regulator. SPAU 341 C 1MRS MBG Issued: July 1998 Status: Revised Version: C/ Data subject to change without notice
Issued: July 1998 Status: Revised Version: C/08.10.2003 Data subject to change without notice Features Comprehensive voltage regulation for power transformers with on-load tapchangers in distribution substations
More informationSDM120 SERIES. SDM120 series User Manual. Single phase two wire DIN rail energy meter (One module)
SDM120 SERIES Single phase two wire DIN rail energy meter (One module) User manual ------------ 1.1 Safety instruction 1.2 Foreword 1.3 Performance criteria 1.4 Specifications 1.5 Basic errors 1.6 Dimension
More informationDescription. SIMATIC Sensors. RF systems Wide-range power supply unit for SIMATIC RF systems. Operating Instructions 11/2007 J31069-D0169-U001-A4-7618
1 SIMATIC Sensors RF systems Wide-range power supply unit for SIMATIC RF systems Operating Instructions 11/2007 J31069-D0169-U001-A4-7618 Safety Guidelines This manual contains notices you have to observe
More informationRugged MediaConverter
Rugged MediaConverter Installation Guide RuggedCom Inc. 30 Whitmore Road, Woodbridge, Ontario Canada L4L 7Z4 Web: http://www.ruggedcom.com/ Tel: (905) 856-5288 Fax: (905) 856-1995 Toll Free: (888) 264-0006
More informationInstalling the Tracer MP503 Input/Output Module Ordering number: ,
Installing the Tracer MP503 Input/Output Module Ordering number: 4950 0490, 4950 0590 Product overview The Tracer MP503 input/output (I/O) module is a field-installed device used to monitor inputs and
More informationINSTRUCTION SHEET. Eaton Logic Controller ELCB Controllers
2010-12-10 5011699201-PBB1 Eaton Logic Controller ELCB Controllers INSTRUCTION SHEET [Applicable Controllers] ELCB-PB10 ELCB-PB14 ELCB-PB20 ELCB-PB30 ELCB-PB40 IL05001005E 002-1310020-02 Thank you for
More informationPart No. Z , IA Jul OPERATION MANUAL. High Voltage Digitalmeter A
Part No. Z1-109-820, IA001705 Jul. 2016 OPERATION MANUAL High Voltage Digitalmeter 149-10A Use of Operation Manual Please read through and understand this Operation Manual before operating the product.
More informationMODEL CIO-EN MODBUS/TCP, MODBUS/RTU I/O MODULE
INSTALLATION INSTRUCTIONS Revision B1 Rapid City, SD, USA, 05/2009 MODEL CIO-EN MODBUS/TCP, MODBUS/RTU I/O MODULE BE SURE POWER IS DISCONNECTED PRIOR TO INSTALLATION! FOLLOW NATIONAL, STATE AND LOCAL CODES.
More informationRTU500 series Data Sheet Power Supply CP-E 24/2.5
Data Sheet Power Supply CP-E 24/2.5 Power Supply CP-E 24/2.5 Application The primary switch mode power supply offers two voltage input ranges. This enables the supply with AC or DC. Furthermore it is equipped
More informationH Series PLC. ! : Indicates Compulsion. EH-150 Analog input module EH-AXH8M Instruction manual. Safety precautions DANGER CAUTION COMPULSION
H Series PLC EH-150 Analog input module EH-AXH8M Instruction manual Thank you for purchasing a Hitachi Programmable Logic Controller. To operate it safely, please read this instruction manual and all the
More informationOperating instructions. Speed monitor D / / 2014
Operating instructions Speed monitor D200 80005257 / 00 05 / 2014 Contents 1 Preliminary note...4 1.1 Symbols used...4 1.2 Warning signs used...4 2 Safety instructions...5 2.1 General...5 2.2 Target group...5
More informationHITACHI. EH-150 series PLC EH-RTD8 Resistance Temperature Detective input module Instruction manual. Safety precautions
HITACHI EH-150 series PLC Resistance Temperature Detective input module Instruction manual Thank you for purchasing a Hitachi Programmable Logic Controller. To operate it safely, please read this instruction
More informationCM589 PROFINET Communication Module
Ordering Data DATA SHEET CM589 PROFINET Communication Module 1 Ordering Data Part No. Description Product Life Cycle Phase *) 1SAP 172 900 R0011 1SAP 372 900 R0011 1SAP 172 900 R0111 1SAP 372 900 R0111
More informationOperating instructions. Switching amplifier DN0210 DN / / 2015
Operating instructions Switching amplifier DN0210 DN0220 UK 80011079 / 00 01 / 2015 Contents 1 Preliminary note...4 1.1 Symbols used...4 1.2 Warning signs used...4 2 Safety instructions...5 2.1 General...5
More informationMini Digital Multimeter
User's Guide Mini Digital Multimeter Model MN15 99 Washington Street Melrose, MA 02176 Phone 781-665-1400 Toll Free 1-800-517-8431 Visit us at www.testequipmentdepot.com Back to the Extech MN15/MN16 Series
More informationModel 2657A-LIM-3 LO Interconnect Module
Keithley Instruments, Inc. 28775 Aurora Road Cleveland, Ohio 44139 1-888-KEITHLEY http://www.keithley.com Model 2657A-LIM-3 LO Interconnect Module User's Guide Description The Model 2657A-LIM-3 LO Interconnect
More informationSafety Standards. Model Number: Unit Weight:
MEA-250A24C Highlights & Features Meet Efficiency Level VI Safety Approvals to IEC 60601-1 3.1 Ed. & IEC 60950-1 Compliant with IEC 60601-1-2 3 th and 4 th Ed. Requirements IP22 ingress protection rating
More informationMonitoring technique. VARIMETER Voltage relay MK 9064N, MH 9064
Monitoring technique VARIMETER Voltage relay MK 9064N, MH 9064 0269462 Your Advantages Preventive maintenance For better productivity Quicker fault locating Precise and reliable Min-, Max. value or window
More informationRhino Buffer Module PSM24-BFM600S. Operating Instructions
Rhino Buffer Module PSM24-BFM600S Operating Instructions RHINO BUFFER MODULE PSM24-BFM600S Description The PSM24-BFM600S Buffer Module will hold the output voltage of a 24 VDC power supply after brownouts
More informationPM Series Power Meter
PM Series Power Meter Quick Setup Guide - PMC-1000, PMC- 1001, PMM-1000, PMB-1960 Safety Information DANGER! HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH Follow safe electrical work practices. See
More informationCI541 PROFIBUS Communication Interface Module
Ordering Data DATA SHEET CI541 PROFIBUS Communication Interface Module 1 Ordering Data Ordering No. Scope of delivery Product Life Cycle Phase *) 1SAP 224 100 R0001 1SAP 424 100 R0001 CI541-DP, PROFIBUS
More informationCM597 Ethernet Communication Module
Ordering Data DATA SHEET CM597 Ethernet Communication Module 1 Ordering Data Part No. Description Product Life Cycle Phase *) 1SAP 173 700 R0001 1SAP 373 700 R0001 CM597-ETH, communication module Ethernet
More informationUser s Guide. 600A AC Clamp Meter. Model 38387
User s Guide 600A AC Clamp Meter Model 38387 Safety International Safety Symbols This symbol, adjacent to another symbol or terminal, indicates the user must refer to the manual for further information.
More informationMCCB-500 MOLDED-CASE CIRCUIT BREAKER TESTER
MCCB-500 MOLDED-CASE CIRCUIT BREAKER TESTER USER S MANUAL Vanguard Instruments Company, Inc. 1520 S. Hellman Ave. Ontario, California 91761, USA TEL: (909) 923-9390 FAX: (909) 923-9391 January 2015 Revision
More informationQUICK SETUP GUIDE PMC-1000, PMC-1001, PMM-1000, PMB PM Series Power Meter. Safety Information. Equipment Maintenance and Service.
PM Series Power Meter QUICK SETUP GUIDE PMC-1000, PMC-1001, PMM-1000, PMB-1960 Safety Information DANGER! HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH Follow safe electrical work practices. See NFPA
More informationATS22D88S6U. ATS22D88S6U soft starter-ats22-control110v-power 208V(25hp)/230V(30hp)/460V(60hp)/575V(75hp) Product data sheet Characteristics.
Characteristics soft starter-ats22-control110v-power 208V(25hp)/230V(30hp)/460V(60hp)/575V(75hp) Main Range of product Altistart 22 Product or component type Product destination Product specific application
More informationAnalog output 520AOD01 Data sheet
RTU520 product line Analog output 520AOD01 Data sheet ERR RTU I/O bus Microcontroller RAM Flash Output register DC DC D D A A Adjustment Output range O1 O2 Adjustment Output range IOC UE Figure 1: Block
More informationATS22D75S6 soft starter-ats22-control 220V-power 230V(18.5kW)/ V(37kW)/500V(45kW)
Characteristics soft starter-ats22-control 220V-power 230V(18.5kW)/400...440V(37kW)/500V(45kW) Price* : 683.00 GBP Main Range of product Altistart 22 Product or component type Product destination Product
More informationDATASHEET. Ultra Capacitor Charger, UCC-4
DATASHEET Ultra Capacitor Charger, UCC-4 Easy installation Monitoring and surveillance of operation Balancing to save energy 90-450 V DC 3.5A Output Modular Ultra Capacitor system Document no.: 4921260003
More informationTRC-190 User s Manual
User s Manual Edition 3.2, May 2017 www.moxa.com/product 2017 Moxa Inc. All rights reserved. User s Manual The software described in this manual is furnished under a license agreement and may be used only
More informationTXP3500/4000 Series AC-DC Industrial PSU
TXP3500/4000 Series ACDC Industrial PSU The TXP3500/4000 series of Fan cooled power supplies convert a universal 3 phase AC I/p to an adjustable, wide range, simple o/p @ 3.5kW. Parallel operation is possible
More informationLXEM145 SERIES Lanx Australis single Phase KWh Meter 45Amp. User manual
LXEM145 SERIES Lanx Australis single Phase KWh Meter 45Amp Single phase two wire DIN rail energy meter (One module) 1.1 Safety instruction 1.2 Foreword 1.3 Performance criteria 1.4 Specifications 1.5 Basic
More informationTechnical specifications
Technical specifications General information Operating temperature -25 to 60 C Storage temperature -40 to 70 C Enclosure type Panel installation (DIN IEC 61554) Enclosure fixing Screw-type clamping technology
More information