Utility Implements Communications- Assisted Special Protection and Control Schemes for Distribution Substations
|
|
- Eleanore Alison McDowell
- 6 years ago
- Views:
Transcription
1 Utility Implements Communications- Assisted Special Protection and Control Schemes for Distribution Substations Michael. Duff City of College Station Payal Gupta, Dharmendra Prajapati, and Alex Langseth Schweitzer Engineering Laboratories, Inc City of College Station and SEL
2 Provides electric power to residential and commercial customers Is composed of City of College Station (COCS) College Station Utilities (CSU) ~20 miles of transmission lines ~458 miles of distribution lines 7 substations OpenStreetMap contributors
3 Traditional 13.2 kv Distribution Substation 138 Electromechanical kv ring bus relays Two No bus 138 differential kv / 13.8 kv power protection transformers Two No breaker buses electrically failure backup connected via normally No automatic source open tie breaker transfer Four feeders per bus Challenge coordinating supplied from main breaker for simultaneous fault conditions
4 13.2 kv Distribution Substation for Special Protection and Control Scheme (SPCS)
5 Information Flow Diagram
6 Communications Link Supervision for High-Speed Data Bits Transmit eceive TB1 TB2... TB8 B1 B2... B TB1 TB2... TB8 B1 B2... B8 Transmit eceive IEDs OK = 1 OK = 0 Status Description Communications channel good Communications channel bad Inverse (NOT) of OK is used to create digital alarm bit to alert operations of communications failure
7 Communications Link Supervision for High-Speed Data Bits IED-B IED-COM B-IED Logic Processors COM = 1 COM = 0 Status Description Communications channel good Communications channel bad Communications link supervision in logic processors only allows received data bits of good quality to be considered in algorithms
8 Different Schemes Implemented Fast bus tripping scheme for significantly reduced bus fault-clearing time Breaker failure protection scheme for shorter breaker failure clearing time Double-circuit feeder trip scheme for faster clearing of simultaneous faults without causing substation outage, and stall reclose logic for system availability Automatic source transfer scheme (ASTS) for higher power system availability
9 SCPS Six Major Design Criteria Dependability Security Selectivity esilience Speed Cost
10 Fast Bus Tripping Scheme Limitation of traditional bus protection philosophy Bus fault is cleared with time-delayed transformer backup protection Typical fault-clearing time is between 0.6 and 1.0 seconds Solution Bus differential protection is fast and secure, but has added cost Fast bus tripping scheme is fast and cost-effective
11 Fast Bus Tripping Scheme Fault on Bus 1
12 Fast Bus Tripping Scheme Fault on F1 Feeder Circuit
13 Limitation of traditional breaker failure protection philosophy Fault is cleared with upstream inverse-time overcurrent protection Long fault-clearing times lead to equipment damage or reduced equipment lifespan Solution Breaker Failure Protection Scheme Dedicated, fast breaker failure protection scheme using existing IEDs and communications backbone Low implementation cost with minimal wiring
14 B-BF T1 Breaker Failure Protection Scheme Fault on Bus 1 Breaker Fails Bus 1 M1 TB-BF TIE F1 F2 F3 F4 B-BF B-BF B-BF B-BF B-BF Logic Processor T1
15 Limitation of traditional system Simultaneous faults may cause coordination issues Main breaker 51 element may misoperate IED overcurrent pickup and time-dial settings must be adjusted (resulting in slower tripping) Solution Double Circuit Feeder Trip Scheme and Stall eclose Logic Double-circuit feeder trip scheme with low implementation cost Fast 51 element setting and improved service reliability
16 Double Circuit Feeder Trip Simultaneous Fault M1 M2 Bus 1 TIE Bus 2 F1 F2 F3 F4 F5 F6 F7 F8 TB-PU B-PU TB-PU B-PU B-PU B-PU B-PU B-PU B-PU B-PU Logic Processor T1 B-PU Logic Processor T2
17 Stall eclose Logic M1 M2 Bus 1 TIE Bus 2 F1 F2 F3 F4 F5 F6 F7 F8 TB-S B-S Logic Processor T1 Logic Processor T2
18 ASTS Limitation of traditional system Less power system availability with more disruption Long restoration times Solution ASTS that automatically switches from primary source to alternate source Short restoration times to improve power system availability
19 11 22 T1 T2 ASTS Transformer Fault TB-FAULT M1 Bus 1 TB-52A Bus 2 TIE TB-52A B-CLOSE M2 F1 F2 F3 F4 F5 F6 F7 F8 TB-52A TB-NO FAULT SCADA ASTS ENABLE Logic Processor T1 Logic Processor T2
20 Other Schemes Multiple SPCSs run in parallel and coordinate with each other as complete, integrated solution Other control logic is implemented to improve system availability and dependability Hot-line mode IED health alarm
21 Questions?
Utility Implements Communications-Assisted Special Protection and Control Schemes for Distribution Substations
Utility Implements Communications-Assisted Special Protection and Control Schemes for Distribution Substations Michael. Duff, City of College Station Payal Gupta, Dharmendra Prajapati, and Alex Langseth,
More informationHigh-Reliability Fault-Clearing System solution. Application Guide. Outdoor Distribution (15.5 kv through 38 kv) S&C ELECTRIC COMPANY
S&C Remote Supervisory V ista Outdoor Distribution (15.5 kv through 38 kv) Electric utility customers are increasingly concerned about the frequency and duration of outages they are experiencing, and are
More informationIdentify and understand the operation of common bus. After this presentation you will be able to: Identify common bus arrangements
Introduction to Bus Protection By Matt Horvath, P.E. November 6, 2018 Electrical Buses Physical and Electrical Junction A bus is a critical element of a power system, as it is the point of convergence
More informationProtection, Monitoring, and Control System for Distribution Substations ALARM HISTORY SYSTEM COMM. On-Line Documentation TRANSFORMER 12 MW
SEL Distribution Substation Protection and Automation System Protection, Monitoring, and Control System for Distribution Substations Data Sheet SYSTEM ONE-LINE RELAY TARGETS ALARM HISTORY SYSTEM COMM.
More informationPG&E 500 kv Protection Standard Design and Development
PG&E 500 kv Protection Standard Design and Development Davis Erwin, Rafael Pineda, and Monica Anderson Pacific Gas and Electric Company Eric Udren Quanta Technology, LLC Jordan Bell and Neal Jones Schweitzer
More informationMultifunction Relays and Protection Logic Processors in Distribution Substation Applications
Multifunction s and Protection Logic Processors in Distribution Substation Applications David Sánchez Escobedo, Eliseo Alcázar Ramírez, Oscar A. Márquez Villanueva, and Héctor J. Altuve Ferrer Schweitzer
More informationIMPROVING POWER SYSTEM RELIABILITY USING MULTIFUNCTION PROTECTIVE RELAYS
IMPROVING POWER SYSTEM RELIABILITY USING MULTIFUNCTION PROTECTIVE RELAYS Armando Guzmán Schweitzer Engineering Laboratories, Inc. Pullman, WA 99163 A reliable power system maintains frequency and voltage
More informationBREAKER FAILURE PROTECTION
0 th Annual HANDS-ON RELAY SCHOOL March 11-15, 201 REAKER FAILURE PROTECTION brent.c@relayapplication.com OUTLINE Protection System Failures and reaker Failures Protection versus Relaying Relay Schemes
More informationAdvanced Protection and Control for a Power System Serving Industrial Customers
Advanced Protection and Control for a Power System Serving Industrial Customers Marco F. Jorge Iberdrola Energía Monterrey David Sánchez, Héctor J. Altuve, and Jorge L. Soto Schweitzer Engineering Laboratories,
More informationSEL-487B. A Powerful Solution for Busbar Differential Protection. Bus Differential and Breaker Failure Relay
Bus Differential and Breaker Failure Relay A Powerful Solution for Busbar Differential Protection Features and Benefits Select the for the differential protection of busbar systems with up to 18 terminals.
More informationUpgrading From a Successful Emergency Control System to a Complete WAMPAC System for Georgian State Energy System
Upgrading From a Successful Emergency Control System to a Complete WAMPAC System for Georgian State Energy System Dave Dolezilek International Technical Director Schweitzer Engineering Laboratories SEL
More informationSystem Protection and Control Subcommittee
Power Plant and Transmission System Protection Coordination GSU Phase Overcurrent (51T), GSU Ground Overcurrent (51TG), and Breaker Failure (50BF) Protection System Protection and Control Subcommittee
More informationBus Differential and Breaker Failure Relay. Advanced bus protection with built-in breaker failure detection
SEL-487B Bus Differential and Breaker Failure Relay Advanced bus protection with built-in breaker failure detection Protect busbars with up to 21 terminals using high-speed, low-impedance bus differential
More informationBus Differential and Breaker Failure Relay. Advanced bus protection with built-in breaker failure detection
SEL-487B Bus Differential and Breaker Failure Relay Advanced bus protection with built-in breaker failure detection Protect busbars with up to 21 terminals using high-speed, low-impedance bus differential
More informationBusbar protection REB 670
Gunnar Stranne Busbar protection REB 670 Rio de Janeiro April 23-25, 2006 ABB Power Technologies AB 2 3 4 REB 500 is enabled for use with IEC61850 communication Benefits of REB 670 outstanding features
More informationAdvanced Line Differential Protection, Automation, and Control System. Combine subcycle line protection with traveling-wave fault locating
Advanced Line Differential Protection, Automation, and Control System Combine subcycle line protection with traveling-wave fault locating Subcycle differential and distance protection minimizes damage
More informationBus Protection Application Challenges
Bus Protection Application Challenges KN Dinesh Babu - Megger JC Theron, Lubomir Sevov GE Grid Solutions 2017 Texas A&M Protective Relay Conference Content Introduction Application Challenges Increase
More informationAdvanced Fuse-Saving Techniques. T. ROUSAN Ameren Illinois USA. J. JERMAKOWICZ S&C Electric Company USA
21, rue d Artois, F-75008 PARIS CIGRE US National Committee http : //www.cigre.org 2015 Grid of the Future Symposium Advanced Fuse-Saving Techniques T. ROUSAN Ameren Illinois USA J. JERMAKOWICZ S&C Electric
More informationA Current Based, Communication Assisted High Speed Protection System to Limit Arc Energy. Patrick Robinson Altelec Engineering
A Current Based, Communication Assisted High Speed Protection System to Limit Arc Energy Patrick Robinson Altelec Engineering Captured Arcing Fault Event Arc begins as phase A-C, 8ka peak, dies out then
More informationPPL EU Relay Standardization
PPL EU Relay Standardization John Sonnelitter Senior Engineer, Transmission Relay Engineering Richard Michael Jr. Support Engineer, Transmission Relay Engineering 9/18/2018 Background PPL EU is undergoing
More informationBlackstart Hardware-in-the-loop Relay Testing Platform
21, rue d Artois, F-75008 PARIS CIGRE US National Committee http : //www.cigre.org 2016 Grid of the Future Symposium Blackstart Hardware-in-the-loop Relay Testing Platform R. LIU R. SUN M. TANIA Washington
More informationRequests for Clarifications And Responses Order No. 754 Data Request The Study of Single Point of Failure
Requests for Clarifications And Responses Order No. 754 Data Request The Study of Single Point of Failure Revised: July 12, 2013 Introduction The following information includes requests for clarification
More informationPRC 001 R6 & R7.3 TFO s Notification Requirement
PRC 001 R6 & R7.3 TFO s Notification Requirement Diagram Information: 4 Substation Buses: SB1 is Substation Bus 1, SB2 is Substation Bus 2, SB3 is Substation Bus 3, and SB4 is Substation Bus 4. Terminals:
More informationLecture 6 Substation Automation Systems
Lecture 6 Substation Automation Systems 1 Course map 2 Contents of the Lecture Part 1 Substation Automation Components & Architectures Substation Automation Functions Communication within the Substation
More informationLightweight and flexible recloser control for single-phase applications
SEL-35S Kestrel Single-Phase ecloser Control Lightweight and flexible recloser control for single-phase applications Plug-and-work operation with popular single-phase reclosers simplifies new and retrofit
More informationRedundant Bus Protection Using High-Impedance Differential Relays. Josh LaBlanc
Redundant Bus Protection Using High-Impedance Differential Relays Josh LaBlanc Purpose Discuss the configuration of the bus under study, and touch on the needs for redundant protection on the bus. Briefly
More informationAuto-Changeover & Feeder Automation. Reclosers & Sectionalizers
Auto-Changeover & Feeder Automation Reclosers & Sectionalizers WHY AUTOMATE? COMPETITION SERVICE VALUE QUALITY RELIABILITY REGULATION RATES BASED ON RELIABITY & PERFORMANCE PENALTIES REGULATION SAIDI (System
More informationConfiguration and Interoperability Guide for IEC for the SEL-751 Feeder Protection Relay. July 10, 2015
Configuration and Interoperability Guide for IEC 60870-5-103 for the SEL-751 Feeder Protection Relay July 10, 2015 Contents 1 Interoperability... 3 1.1 Physical Layer... 3 Electrical Interface... 3 Optical
More informationBus Bar Protection Applications Seminar
Bus Bar Protection Applications Seminar April 3, 2006 College Station TX ZONE 1 23 24 ZONE 2 1 2 11 12 13 22 ZONE 1 ZONE 2 23 24 1 2 3 21 22 Presentation Outline Introduction to Bus Bar Protection Bus
More informationEE 868: Digital Techniques for Power System Protection. Laboratory Assignment #2 (Feb. 8 (12pm)) Overcurrent Relay Coordination
EE 868: Digital Techniques for Power System Protection 1 Objective Laboratory Assignment #2 (Feb. 8 (12pm)) Overcurrent Relay Coordination Rama Gokaraju Department of Electrical & Computer Engineering
More informationBus Differential and Breaker Failure Relay. Advanced bus protection with built-in breaker failure detection
SEL-487B Bus Differential and Breaker Failure Relay Advanced bus protection with built-in breaker failure detection Protect busbars with up to 21 terminals using high-speed, low-impedance bus differential
More informationELG4125: System Protection
ELG4125: System Protection System Protection Any power system is prone to 'faults', (also called short-circuits), which occur mostly as a result of insulation failure and sometimes due to external causes.
More information2012 Grid of the Future Symposium. Demonstration of Pulsecloser Applications and Benefits in Ameren s Distribution Automation Program
21, rue d Artois, F-75008 PARIS CIGRE US National Committee http : //www.cigre.org 2012 Grid of the Future Symposium Demonstration of Pulsecloser Applications and Benefits in Ameren s Distribution Automation
More informationApproval...6. Current Revision...7. Introduction... 8 About PJM Manuals... 8 About This Manual... 8 Using This Manual...9
PJM Manual 07: PJM Protection Standards Revision: 3 Effective Date: May 24, 2018 Prepared by System Planning Division Transmission Planning Department PJM 2018 Table of Contents Table of Contents Approval...6
More informationPRC Coordination of Protection Systems for Performance During Faults
PRC-027-1 Coordination of Protection Systems for Performance During Faults A. Introduction 1. Title: Coordination of Protection Systems for Performance During Faults 2. Number: PRC-027-1 3. Purpose: To
More informationSmall Generator Interconnection System Impact Study Report. Completed For Q0047
Small Generator Interconnection Completed For Q0047 Proposed Interconnection PacifiCorp s Existing Goshen Rigby 69 kv Line March 7, 2005 1.0 Description of the Generation Facility Q0047 ( Interconnection
More informationDTRV-EP. COMPLEX DIGITAL PROTECTION FOR 120 kv / MEDIUM VOLTAGE TRANSFORMERS. Application field
DTRV-EP COMPLEX DIGITAL PROTECTION FOR 120 kv / MEDIUM VOLTAGE TRANSFORMERS Application field The DTRV type of complex transformer protection is designed to protect 120 kv / medium voltage transformers,
More informationASPEN Software - Introduction
ASPEN Software - Introduction ASPEN is a very user-friendly software package that is capable of doing load-flow and shortcircuit studies, as well as relay application and coordination. Its simple graphical
More informationFAULT DETECTION ISOLATION AND RESTORATION ON THE FEEDER (FDIR): PICK YOUR TECHNOLOGY
FAULT DETECTION ISOLATION AND RESTORATION ON THE FEEDER (FDIR): PICK YOUR TECHNOLOGY Fahrudin Mekic Ken Alloway Cleber Angelo Robert Goodin ABB Inc. USA ABB Inc. USA ABB Inc. USA ABB Inc. USA fahrudin.mekic@us.abb.com.ken.alloway@us.abb.com
More informationPower System Protection Training
Power System Protection Training Contact us Today for a FREE quotation to deliver this course at your company?s location. https://www.electricityforum.com/onsite-training-rfq Refresh your knowledge of
More informationSOLKOR-N (7SR18) Feeder Differential Protection. Make the ight choice! Choose EYROLLE Protection
SOLKO-N (7S18) Feeder Differential Protection CLASSIFICATION OF UNIT TYPE POTECTION Summation Transformer, Circulating Current Protection B B 3 1 1 O O 3 1 1 SUMMATION TANSFOME SUMMATION TANSFOME O - Operating
More informationPower System Protection Laboratory Electric Power and Energy Engineering
Experiment no. 5 Overcurrent Protection of Transmission Line Power System Protection Laboratory Electric Power and Energy Engineering Dr. Jamal Thalji Eng. Saddam Ratrout Eng. Mageda El-Moubarak Content
More informationLecture 5 Substation Automation Systems. Course map
Lecture 5 Substation Automation Systems 1 Course map 2 1 Contents of the Lecture Part 1 Substation Automation Components Substation Automation Functions Communication within the Substation (Intro) Part
More informationSubstation to substation (ss2ss) GOOSE exchange for critical relay operations
CIGRÉ Canada 21, rue d Artois, F-75008 PARIS (CIGRE-130) Conference on Power Systems http : //www.cigre.org Vancouver, October 17-19, 2010 Substation to substation (ss2ss) GOOSE exchange for critical relay
More informationInternational Journal of Engineering Trends and Technology (IJETT) Volume 26 Number 2- August 2015
Microprocessor-Based Protective Applications in Nigeria Power System Protections J.O. Aibangbee #1, S.O. Onohaebi *2. # Department of Electrical &Computer Engineering, Bells University of Technology, Ota,
More informationIntelliTeam II Automatic Restoration System
No system is too complex to automate with... IntelliTeam II Automatic Restoration System Introduced in 1997, the IntelliTeam Automatic Restoration System was the first product of its kind. Using peer-to-peer
More informationSEL Time-Domain Link (TiDL ) Technology
SEL Time-Domain Link (TiDL ) Technology The simple, fast, and secure digital secondary system solution Increase safety by removing high-energy cables from areas where personnel typically work. Reduce the
More informationProtection, Automation, and Bay Control System. Advanced feeder protection and complete substation bay control in one economical system
SEL-451 Protection, Automation, and Bay Control System Advanced feeder protection and complete substation bay control in one economical system Customize distribution protection using multiple instantaneous,
More informationADVANCED. Protection Co-ordination. H.H. Sheik Sultan Tower (0) Floor Corniche Street Abu Dhabi U.A.E
ADVANCED Protection Co-ordination H.H. Sheik Sultan Tower (0) Floor Corniche Street Abu Dhabi U.A.E www.ictd.ae ictd@ictd.ae Course Introduction: Distribution Networks are designed to serve loads in a
More informationA low-cost, economical solution for distribution feeder protection
SEL-351A Protection System A low-cost, economical solution for distribution feeder protection Achieve sensitive and secure fault detection using comprehensive protection functions. Track breaker status
More information////// SUBSTATIONS. Control command and local Scada
////// SUBSTATIONS Control command and local GENERAL INFORMATION The solution provided by Sécheron for local control and monitoring of traction substations is a significant step in supporting operations
More informationIf You Cannot Test It, You Cannot Use It IEC GOOSE System Designed With Testing in Mind
If You Cannot Test It, You Cannot Use It IEC 61850 GOOSE System Designed With Testing in Mind Don Burkart, Consolidated Edison of New York William Edwards, Anne Atalay, and Stephen Snuggs, Schweitzer Engineering
More informationTo: Honorable Public Utilities Board Submitted by: From: Diosdado Hernandez, P. E. Approved by:
AGENDA ITEM NO.: 4.F.1 ADMINISTRATIVE REPORT NO.: 2018-50 To: Honorable Public Utilities Board Submitted by: /S/ Andre Basler AGM Engineering and Operations From: Diosdado Hernandez, P. E. Approved by:
More informationExercise 2. Single Bus Scheme EXERCISE OBJECTIVE DISCUSSION OUTLINE. The single bus scheme DISCUSSION
Exercise 2 Single Bus Scheme EXERCISE OBJECTIVE When you have completed this exercise, you will be familiar with electric power substations using the single bus scheme with bus section circuit breakers.
More informationWHAT IS A BUS? FUNDAMENTALS OF BUS PROTECTION. Kevin Wright Senior Protection Engineer Sacramento Municipal Utility District
WHAT IS A BUS? FUNDAMENTALS OF BUS PROTECTION Kevin Wright Senior Protection Engineer Sacramento Municipal Utility District 5 WHAT IS A BUS? All connections are at the same voltage. WHAT IS A BUS? All
More informationFlexible High-Speed Load Shedding Using a Crosspoint Switch
Flexible High-Speed Load Shedding Using a Crosspoint Switch Will Allen and Tony Lee Schweitzer Engineering Laboratories, Inc. Published in Wide-Area Protection and Control Systems: A Collection of Technical
More informationProtection, Automation, and Control System. Combine subcycle line protection with complete substation bay control
Protection, Automation, and Control System Combine subcycle line protection with complete substation bay control Subcycle distance protection minimizes damage and expensive repairs on transmission lines.
More informationRevised Generation Interconnection Impact Study Report. For. Queue Position 31 ( Interconnection Customer )
Revised Generation Interconnection Impact Study Report For Queue Position 31 ( Interconnection Customer ) September 22, 2004 1 Generation Interconnection System Impact Study Report I. Revision of Original
More informationSmart Distribution Technology
Smart Distribution Technology Presentation Agenda Alabama Power Company, A Southern Company Distribution Automation Supervisory Control And Data Acquisition (SCADA) Multiple Address System (MAS) communications
More information1 Description of Methodology for Volt / Var Optimization
Methodology for Volt / Var Optimization on a Substation Basis May 13th, 2011 Version 1.7 1 Methodology for Volt / Var Optimization (VVO) on a Substation Basis This use case discusses how the utility will
More informationThis webinar brought to you by the Relion product family Advanced protection and control IEDs from ABB
This webinar brought to you by the Relion product family Advanced protection and control IEDs from ABB Relion. Thinking beyond the box. Designed to seamlessly consolidate functions, Relion relays are smarter,
More informationDISTRIBUTION FEEDER FAULT ANALYSIS TILLAMOOK PEOPLE S UTILITY DISTRICT
DISTRIBUTION FEEDER FAULT ANALYSIS TILLAMOOK PEOPLE S UTILITY DISTRICT SCADA TO DG SITES DIGESTER MW AND MVAR INSTANTANEOUS READINGS FROM SEL 751 RELAY TRASK SUBSTATION LOADING DO NOT WANT TO FEED INTO
More informationFAST BUS PROTECTION USING IEC Cassandra Ha Goff
FAST BUS PROTECTION USING IEC 61850 By Cassandra Ha Goff Approved: Ahmed H. Eltom Professor of Electrical Engineering (Chair) Stephen D. Craven Adjunct Professor of Electrical Engineering (Committee Member)
More informationImproving Fault Response with Real-time Fault Location Analysis through Combined Outage and Advanced Distribution Management
Improving Fault Response with Real-time Fault Location Analysis through Combined Outage and Advanced Distribution Management David Lyons Georgia Power Brad Williams Oracle Kevin Costin - Oracle Southern
More informationSEL Protection and Communications Capabilities Integral to Power System Upgrade at Alberta s Dynamic Northlands Park
CASE STUDY Northlands Park Edmonton, Alberta, Canada SEL Protection and Communications Capabilities Integral to Power System Upgrade at Alberta s Dynamic Northlands Park A hub of sports, gaming, business,
More informationIowa State University
Iowa State University Cyber Security Smart Grid Testbed Senior Design, Final Report Dec 13-11 Derek Reiser Jared Pixley Rick Sutton Faculty Advisor: Professor Manimaran Govindarasu 1 Table of Contents
More informationStandard Development Timeline
Standard Development Timeline This section is maintained by the drafting team during the development of the standard and will be removed when the standard becomes effective. Description of Current Draft
More informationLandsnet-Icegrid. Requirements for protection and control systems. Principles for the Icelandic power transmission network.
Landsnet-Icegrid Requirements for protection and control systems. Principles for the Icelandic power transmission network. Introduction.... 4 System requirements... 6 Validity:... 6 Requirements for protection:...
More informationJehanpour Ranjkesh, Integrator Partner Seminar 2012 Station level product news Automation Controller COM600
Jehanpour Ranjkesh, Integrator Partner Seminar 2012 Station level product news Automation Controller COM600 Contents COM600 Product Overview Business Overview Product News Overview June 12-14, 2012 Slide
More informationGeneration Interconnection Impact Study Report. For. Interconnection Customer Q0022
Generation Interconnection Impact Study Report For Interconnection Customer Q0022 Prepared by: PacifiCorp Date: 10/29/2003 Generation Interconnection System Impact Study Report Interconnection Customer
More informationAdvanced Protection and Control Technologies for T&D Grid Modernization
Advanced Protection and Control Technologies for T&D Grid Modernization i-pcgrid Workshop San Francisco, CA March 31, 2016 Jeff Shiles, Principal Manager Protection & Automation Engineering Southern California
More informationAdvanced distribution feeder solution with integrated protection, monitoring, and control
Protection System Advanced distribution feeder solution with integrated protection, monitoring, and control Achieve sensitive and secure fault detection using comprehensive protection functions. Keep track
More informationSimplifying Protection System Design for Distribution Substations
Rich Hunt - GE Digital Energy, John Coursey, Stephen Hirsch - Orion New Zealand Limited Rich Hunt 903 Haddon Hall Drive Apex, NC 27502 (O) 919 367 7608 (F) 919 882 9962 richard.hunt@ge.com 1. Introduction
More informationSome previous important concepts
Almustansorya University College of Education Computer Science Department Communication and Computer Networks Class 4 (A/B) Lesson 6... Network Topology Abstract This lesson will mainly focus on the network
More informationAn Application of a Protective Relaying Scheme using the UCA/MMS Standard GER-4007
An Application of a Protective elaying Scheme using the UCA/MMS Standard GE-4007 New Communications Protocols An Application Of A Protective elaying Scheme Using the UCA/MMS Standard 1 Gustavo Brunello,
More informationLogic Programming for the DPU2000R Feeder Protection Relay
ABB Application Note Substation Automation and Protection Division Logic Programming for the DPU2000R Feeder Protection Relay DPU2000R AN-51D-99 The DPU2000R has extensive logic processing capability that
More informationAn Innovative Approach to Implementing SCADA into the Industrial Environment
Feature An Innovative Approach to Implementing SCADA into the Industrial Environment by Lynn Hamrick and David Charles ESCO Energy Services ESCO Energy Services Company recently implemented a Supervisory,
More informationIMP/ 001 / 014 Policy for the Protection of Distribution Networks
Version:- 1.1 Date of Issue:- July 2016 Page 1 of 39 IMP/ 001 / 014 Policy for the Protection of Distribution Networks 1. Purpose The purpose of this document is to detail the network protection philosophy
More informationANALYSIS OF PROTECTIVE SYSTEM FOR HIGH VOLTAGE LINES USING PROTOCOL IEC 61850
Available Online at www.ijcsmc.com International Journal of Computer Science and Mobile Computing A Monthly Journal of Computer Science and Information Technology IJCSMC, Vol. 3, Issue. 5, May 2014, pg.1164
More informationAmsterdam 27 September 2017 David MacDonald
Operations & Maintenance facilitating condition based and predictive maintenance to support cost-efficient operation and maximum life-cycle of next generation IEC 61850 systems Amsterdam 27 September 2017
More informationInnovative Distribution Feeder Protection and Control Schemes Using New Capabilities of Microprocessor Relays
Innovative Distribution Feeder Protection and Control Schemes Using New Capabilities of Microprocessor Relays Mohammad Vaziri PG&E 1. Abstract Farshid Vahedian Brojeni PG&E Eugene Shulman GE Multilin Manish
More informationi-pcgrid Workshop 2014 PG&E Order No. 754 Analysis: Protection
i-pcgrid Workshop 2014 PG&E Order No. 754 Analysis: Protection 1 Process PG&E Order No. 754 Analysis Receive Bus List from Planning that Meet the Criteria in Table A Protection Computes Actual Clearing
More informationFCIs reduce fault-locating times and improve reliability metrics, especially the Customer Average Interruption Duration Index (CAIDI).
1 Intelligent electronic devices (IEDs) are the preferred choice for modernizing the grid. Communication among networks of robust IEDs designed for protection, control, and monitoring (PCM) of the power
More informationLoop Automation. Technical Manual for the ADVC Controller Range
Loop Automation Technical Manual for the ADVC Controller Range Contents List of Figures 5 List of Tables 7 Acronyms 7 Symbols 7 Introduction 8 About this Manual 8 ADVC Controller Firmware Version 9 WSOS
More informationwww. ElectricalPartManuals. com Protective Relays HIGHLIGHTS PROTECTIVE FUNCTIONS ixp-420 Transformer Protection Relay
Protective Relays Electrical Apparatus ixp-420 Transformer Protection Relay 165-420 Figure 1: Edison Idea Relay The ixp-420 is a member of Cooper Power Systems Edison Idea line of protective relays. The
More informationComparing Protective-Relaying Commissioning and Test Philosophies and Methods
Comparing Protective-Relaying Commissioning and Test Philosophies and Methods Abstract This paper will discuss the differences in types of testing philosophies, test set units and different automated testing
More informationEntergy Development and Deployment of IEC Protection and Control Including Process Bus
Entergy Development and Deployment of IEC 61850 Protection and Control Including Process Bus Chan Y. Wong Entergy Transmission Eric A. Udren and Solveig Ward Quanta Technology, LLC Presented at CIGRÉ Grid
More informationFP-5000 Series Multi-functional Microprocessor-based Feeder Protective Relay
FP-5000 Series Multi-functional Microprocessor-based Feeder Protective Relay The power of fusion. 1874 1886 1893 1899 1906 1908 1911 1934 1962 1963 1976 1983 1990 1999 There s a certain energy at Eaton.
More informationFP-5000 Feeder Protection
Effective: April 2001 Page 1 New Information FP-00 Feeder Protection Contents Description Page FP-00 Description......... 2 Application Description...... 2 Features, Functions and Benefits..............
More informationSmall Generator Interconnection Facilities Study Report. Completed for Q0314 ( Interconnection Customer ) A Qualified Facility
Small Generator Interconnection Completed for Q0314 ( Interconnection Customer ) A Qualified Facility Proposed Interconnection PacifiCorp s 34.5-kV West Cedar Substation December 29, 2010 TABLE OF CONTENTS
More informationProtection relays.
Protection relays www.vamp.fi Vamp Ltd Vamp Ltd, with a strong experience of designing devices, is an independent supplier of relays and monitoring equipment. The company has an established reputation
More informationSacramen Sacr t amen o t Municipal Utility Dis t Dis rict t SMUD May Ma 10,
Sacramento Municipal Utility District SMUD May 10, 2010 1 SMUD Facts and Figures 900 Sq. Miles Service Area 585,500 Customers 1.4 million Area Population 10 Bulk Substations 473 Miles of Transmission Lines
More informationDIGITAL RELAY OF PROTECTION AND AUTOMATION SERIES PC83 AND PC830
DIGITAL RELAY OF PROTECTION AND AUTOMATION SERIES PC83 AND PC830 PC83 and PC830 series devices are designed to perform the relay protection functions and 6-154 kv networks automation, have different functionality
More informationASPEN Software - Introduction
ASPEN Software - Introduction ASPEN is a very user-friendly software package that is capable of doing load-flow and shortcircuit studies, as well as relay application and coordination. Its simple graphical
More informationRedundant Bus Protection Using High-Impedance Differential Relays
Redundant Bus Protection Using High-Impedance Relays Josh LaBlanc, Schweitzer Engineering Laboratories, Inc. (formerly of Minnesota Power) Michael J. Thompson, Schweitzer Engineering Laboratories, Inc.
More informationThis webinar brought to you by the Relion product family
This webinar brought to you by the Relion product family Relion. Thinking beyond the box. Designed to seamlessly consolidate functions, Relion relays are smarter, more flexible and more adaptable. Easy
More informationSmart Grid Protection through Self-Healing
Smart Grid Protection through Self-Healing Chathurika Chandraratne, R.T. Naayagi, Thillainathan Logenthiran School of Electrical and Electronic Engineering Newcastle University (Singapore) Singapore 567739
More informationCatching Falling Conductors in Midair Detecting and Tripping Broken Distribution Circuit Conductors at Protection Speeds
Catching Falling Conductors in Midair Detecting and Tripping Broken Distribution Circuit Conductors at rotection Speeds Karl Iliev San Diego Gas & Electric Company Eric Udren Quanta Technology, LLC Copyright
More informationWe will discuss two types of loss-of-potential (LOP) logic during this presentation:
1 We will discuss two types of loss-of-potential (LOP) logic during this presentation: Traditional LOP, which uses traditional voltage and current elements to detect an LOP condition. Advanced LOP, which
More informationAUTOMATION OF POWER DISTRIBUTION USING SCADA
1 2 ABSTRACT In every substation certain measurements, supervision, control, operation and protection functions are necessary. Traditionally these functions were performed manually by system operator from
More information