Relion 615 series Line Differential Protection and Control RED615 Ver. 2.0 Technical Presentation

Size: px
Start display at page:

Download "Relion 615 series Line Differential Protection and Control RED615 Ver. 2.0 Technical Presentation"

Transcription

1 Relion 615 series Line Differential Protection and Control RED615 Ver. 2.0 Technical Presentation ABB Oy Distribution Automation July 1, MRS B Slide 1

2 Contents RED615 Technical Presentation highlights July 1, 2009 Slide 2

3 July 1, 2009 Slide 3

4 Relion 615 series RED615 RED615 is a member of ABB s Relion product family and part of its 615 protection and control product series The 615 series IEDs are characterized by their compactness and withdrawable design Other members of the 615 product series: REF615 REM615 RET615 July 1, 2009 Slide 4

5 Description RED615 is a phase-segregated two-end line differential protection and control IED (intelligent electronic device) designed for utility and industrial power systems, including looped and meshed distribution networks with or without decentralized power generation July 1, 2009 Slide 5

6 Selective protection for a dedicated zone Unit protection for applications calling for absolutely selective protection for a dedicated zone Main application area: twoterminal protection for cable or overhead line feeders Phase segregated protection algorithm Protection communication using a dedicated optical link Designed for IEC July 1, 2009 Slide 6

7 A pre-configured IED Three standard configurations available Possibility to add, delete and change signal connections for binary inputs, binary outputs and between function blocks using PCM600 The number and type of function blocks is fixed July 1, 2009 Slide 7

8 Standard configurations Standard configuration A Line differential protection Standard configuration B Line differential protection with directional earth-fault protection Standard configuration C Line differential protection with non-directional earth-fault protection July 1, 2009 Slide 8

9 Standard configurations, page 1(3) Standard configuration A B C Protection functions Line differential protection and related measurements, stabilized and instantaneous stages Three-phase non-directional overcurrent, low stage, instance 1 Three-phase non-directional overcurrent, high stage, instance 1 Three-phase non-directional overcurrent, high stage, instance 2 Three-phase non-directional overcurrent, instantaneous stage, instance 1 Non-directional earth-fault protection, low stage (SEF), instance Non-directional earth-fault protection, low stage, instance Non-directional earth-fault protection, high stage, instance Non-directional earth-fault protection, instantaneous stage, instance Directional earth-fault protection, low stage (SEF), instance Directional earth-fault protection, low stage, instance Directional earth-fault protection, high stage, instance Transient / intermittent earth-fault protection - - = included, = optional at the time of order July 1, 2009 Slide 9

10 Standard configurations, page 2(3) Standard configuration A B C Protection functions, cont d Non-directional (cross-country) earth-fault protection, using calculated I o - - Negative sequence overcurrent protection, instance 1 Negative sequence overcurrent protection, instance 2 Phase discontinuity protection - Three-phase thermal protection for feeders, cables and distribution transformers - Binary signal transfer Circuit-breaker failure protection Three-phase inrush current detector Master trip, instance 1 Master trip, instance 2 Control functions Circuit-breaker control Disconnector position indication, instance 1 Disconnector position indication, instance 2 = included, = optional at the time of order July 1, 2009 Slide 10

11 Standard configurations, page 3(3) Standard configuration A B C Control functions, cont d Disconnector position indication, instance 3 Earthing switch indication Auto-reclosing - O O Condition monitoring Circuit-breaker condition monitoring - Trip circuit supervision, instance 1 Trip circuit supervision, instance 2 Current circuit supervision Protection communication supervision Measurement Disturbance recorder Three-phase current measurement Sequence current measurement Residual current measurement - Residual voltage measurement - - = included, = optional at the time of order July 1, 2009 Slide 11

12 July 1, 2009 Slide 12

13 Why line differential protection? Application examples Case Overcurrent protection challenges Solution Fault current contribution from more than one source (direction) Protection co-ordination Varying fault current levels Load currents magnitudes close to fault current levels Selective protection scheme still required Protection co-ordination based on definite or inverse time delays might result in too high accumulated time delays within the chain of protection devices Difficult to find protection setting parameters that would suit all cases Difficult to separate fault conditions from normal loading RED615 RED615 RED615 RED615 July 1, 2009 Slide 13

14 Line differential protection application examples Application examples Parallel feeders Looped feeder construction Doubled feeders Two interconnected feeders between a primary substation Reserve connections or meshed type of network Distributed generation Power generation at the remote end of the feeder Weak grid supplying relatively long distribution lines July 1, 2009 Slide 14

15 Unit protection with overcurrent back-up protection Application examples The phase currents of CT core #2 are summated externally to the IED, and used as CT supervision (MCS3I) reference current The two lowest overcurrent stages are used for remote back-up protection The two highest overcurrent stages are blocked under normal conditions and released in case of protection communication failure Binary signal transfer, 8 signals for user definable purpose (BST) Protection communication supervision (PCS) Standard configuration A July 1, 2009 Slide 15

16 Unit protection with directional earth-fault protection Application examples Standard configuration B The cable CT I 0 input is used for directional earth-fault protection and for CT supervision (MCS3I) reference current Non-directional earth-fault protection stage, based on calculated I 0,, for cross-country earthfault protection Auto-reclosing option for overheadlines Thermal overload protection for feeders The two lowest overcurrent stages are used for remote back-up protection Two highest overcurrent stages are blocked under normal conditions and released in case of protection communication failure Binary signal transfer, 8 signals for user definable purpose (BST) Protection communication supervision (PCS) July 1, 2009 Slide 16

17 Unit protection with non-directional earth-fault protection Application examples Standard configuration C The fourth CT (I 0 ) input is used for nondirectional earth-fault protection and for CT supervision (MCS3I) reference current The same phase CT cores can be used for main protection and for earth-fault protection (external summation), but in that case the CT supervision shall not be used Auto-reclosing option for overheadlines Thermal overload protection for feeders The two lowest overcurrent stages are used for remote back-up protection Two highest overcurrent stages are blocked under normal conditions and released in case of protection communication failure Binary signal transfer, 8 signals for user definable purpose (BST) Protection communication supervision (PCS) July 1, 2009 Slide 17

18 615 series Supported ABB solutions, page 1(2) Application examples Supported ABB solutions Station Automation COM600 MicroSCADA Pro Version 3.3 or later 9.2 SP1 or later The 615 series IEDs together with COM600 constitute a genuine IEC solution for reliable power distribution in utility and industrial power systems The native IEC support offer: Fast software based communication Continuous supervision of the integrity of the protection and communication system Inherent flexibility for reconfiguration and upgrades ABB s Connectivity Package concept enables: Streamlining of the system engineering and IED configuration Easy integration with COM600 and MicroSCADA Pro July 1, 2009 Slide 18

19 615 series Supported ABB solutions, page 2(2) Application examples Industrial example The 615 series IEDs complemented with COM600 offer several benefits: Enhanced substation level functionality using the data content of the bay level IEDs A web HMI providing single-line mimic diagrams for switchgear bay solutions COM600 can be used as a local data warehouse for technical documentation and for network data Extensive reporting and analyzing of network fault situations Seamless connectivity to MicroSCADA Pro and System 800xA Utility example July 1, 2009 Slide 19

20 July 1, 2009 Slide 20

21 Hardware modules [X000] module with optional station bus ports [X100] Power supply and binary output module [X110] Binary I/O module [X120] Basic analog input module [X130] Additional binary I/O module (option) July 1, 2009 Slide 21

22 module variants [X000] Line differential protection link: 100BASE-FX with a fibre-optic LC connector, multi mode or single mode Station bus : 100BASE-TX with a RJ-45 connector Serial (RS-485): Screw terminal connector 2-wire or 4-wire connection Serial (ST connector) Glass fibre July 1, 2009 Slide 22

23 Power supply and binary output modules [X100] Power supply : 48 V 250 V DC, 100 V 240 V AC Four power output contacts capable of direct CB operation Two contacts with integrated trip circuit supervision; also to be used with double-pole operation Two signal output contacts (1 changeover, 1 normally open) IRF output for self-supervision signalling July 1, 2009 Slide 23

24 Binary I/O module [X110] 8 binary inputs 6 inputs, grouped in pairs of two 2 inputs, separated (potential free) 4 binary outputs 3 outputs, changeover contacts 1 output, normally open Selectable binary input thresholds ( V DC) July 1, 2009 Slide 24

25 Basic analog input modules [X120] Four analog current inputs (I 0,I L1, I L2, and I L3 ), user selectable 1 A or 5 A I 0 used as current circuit supervision reference current One voltage input U 0 (std. conf B) alt. a fourth binary input with dedicated ground Three binary inputs (common ground), thresholds selectable Both for ring and pin type wire terminals Max. wire 1 x 6 mm 2 or 2 x 2.5 mm 2 July 1, 2009 Slide 25

26 Input / output overview Standard configuration Analog inputs Binary inputs/outputs CT VT BI BO A 4-12 (18) 1) 10 (13) 1) B (17) 1) 10 (13) 1) C 4-12 (18) 1) 10 (13) 1) 1) With optional binary I/O module ( ) July 1, 2009 Slide 26

27 highlights July 1, 2009 Slide 27

28 Line differential protection Stabilized low stage and instantaneous high stage The protection algorithm calculation is performed both in the local and the remote IED Direct intertrip between line ends ensures simultaneous tripping of the local and the remote CB Detection (blocking) for inrush conditions based on the second harmonic Possibility to introduce either definite or inverse time delay for the stabilized low stage July 1, 2009 Slide 28

29 Line differential protection, cont d Small tapped loads can be included inside the LD protection zone LD protection selectivity towards the protections on the LV-side of the power transformer can be achieved by introducing a time delay for the low set stage Faults on the feeder with low fault impedance (=> high fault current) cleared by the high set stage Reach of the instantaneous high stage Reach of the stabilized low stage with inverse time delay July 1, 2009 Slide 29

30 Line differential protection, cont d Current transformer ratio correction factor Maximum ratio difference 1:5 Local and remote current transformers secondary side star-point selection Both end on the busbar side or on the line side (by default) One end on the busbar side and the other end on the line side July 1, 2009 Slide 30

31 Current circuit supervision Comparing calculated I 0 to a measured I 0 (I_REF) from a different core or from a core balance current transformer Will block line differential and negative sequence overcurrent protection by default if the calculated and the measured I 0 values do not match Operation is indicated by an alarm LED Enabled on load current levels Can be switched OFF if required, or if there is no connected reference current measurement July 1, 2009 Slide 31

32 Disturbance recorder 12 analog channels and 64 binary channels Triggering by: Analog or binary channel Manual or periodic command Recording modes: Wave form or trend Selectable sampling rate, 32/16/8 samples per cycle Max 2 X 10 sec using the highest sampling rate and maximum number of recorded channels July 1, 2009 Slide 32

33 Operation traceability Non-volatile memory for: Setting values Configuration Trip lock-out Disturbance recorder data Up to 50 event codes Recorded data of the four latest events with time stamp Operation indications and alarm LEDs show the status of the IED July 1, 2009 Slide 33

34 Self-supervision Continuous monitoring of: Memory circuits (RAM, ROM, EEPROM) CPU operation and program execution Internal supply voltages Internal trip path continuity External trip circuit (TCS) Light sensor inputs software configuration July 1, 2009 Slide 34

35 Control functions Control of one circuit breaker Dedicated push-buttons for opening and closing of the CB Interlocking schemes July 1, 2009 Slide 35

36 Access control Individual user accounts with role-based access control Four access levels: viewer, operator, engineer and administrator level Applies to: Front-panel user interface Web-browser based user interface PCM600 Administrator programmable passwords July 1, 2009 Slide 36

37 July 1, 2009 Slide 37

38 615 series Designed for IEC Native support for IEC communication between devices in substations IEC enables GOOSE (Generic Object Oriented Substation Event) horizontal communication between IEDs RED615 can simultaneously report events to five different clients on the station bus RED615 also supports: Modbus TCP/IP and RTU / ASCII DNP3 TCP/IP and serial IEC July 1, 2009 Slide 38

39 615 series IEC GOOSE communication Network control centre MicroSCADA Pro Station Automation COM600 Station bus IEC Standardized horizontal communication enables interoperability between any IEDs supporting GOOSE communication Used for transmitting binary process data to peer IEDs within a substation Ethernet technology offers a fast and reliable station bus for the transfer of data The publisher-subscriber principle allows the IEDs to send and/or receive time critical data July 1, 2009 Slide 39

40 615 series GOOSE communication benefits Expandability and flexibility: Flexible modifications without changing the wiring between the IEDs No IED I/Os are needed for the transer of data between the IEDs Reduced wiring between the IEDs Possible to add functionality like interlocking schemes between the cubicles in existing switchgear (retrofit) Supervised data transfer (connection and data quality) RED615 meets the GOOSE performance requirements for tripping applications in distribution substations, as defined by the IEC standard July 1, 2009 Slide 40

41 GOOSE - Breaker failure protection IED A GOOSE message On detecting a fault on the outgoing feeder IED B sends a trip command to CB B and initiates the CB failure protection function CB B fails to open The CB failure protection function of IED B sends a trip command to IED A using GOOSE The use of GOOSE communication eliminates the need for dedicated wiring CB failure protection can be added without renewing the wiring and with minimum disturbance to the process IED C IED B July 1, 2009 Slide 41

42 Protection communication IED 2 Fibre optic communication link IED 1 Physical communication link: A dedicated pair of optical single mode or multimode fibres Optical LC Distance: < 2 km (multi mode), 2-20 km (single mode) Protection communication supervision: Continuous supervision of sending and receiving of messages In the event of a communication failure an alarm is issued and the LD protection is blocked July 1, 2009 Slide 42

43 Protection communication, cont d IED 2 Fibre optic communication link IED 1 The communication link is used for both the LD protection communication and the binary signal transfer (BST) The current phasor data, for each phase, is exchanged between the terminals 8 times per cycle (20 ms at 50 Hz) Simultaneous tripping of both the local and the remote circuit breaker 8 user definable binary signals can be transferred between the terminals July 1, 2009 Slide 43

44 Protection synchronisation No external time-synchronization devices (GPS) are needed propagation delay measuring of symmetrical communication links Sampling differential time calculation algorithm Synchro-phasors in common time reference July 1, 2009 Slide 44

45 Binary signal transfer (BST) Binary information transfer between the line ends (the two IEDs located apart from each other) using the protection communication link Typically used for interlocking and intertripping schemes For user definable purposes, (8 signals) duplex communication Fast communication between two RED615 IEDs (< 5 ms) Fully user configurable using the signal matrix tool in PCM600 July 1, 2009 Slide 45

46 Binary signal transfer, example 1 Protection communication BI BSTGGIO Output 1 BSTGGIO Output 1 Output 8 Input 8 Output 8 Input 8 Input 1 BO Input 1 July 1, 2009 Slide 46

47 Binary signal transfer, example 2 Protection communication BI BSTGGIO Output 1 BSTGGIO Output 1 Output 8 Input 8 Block Output 8 Input 8 I> Input 1 PHLPTOC Input 1 July 1, 2009 Slide 47

48 Binary signal transfer, example 3 Protection communication Start BSTGGIO Output 1 BSTGGIO Output 1 3I> PHLPTOC Output 8 Input 8 Block Output 8 Input 8 3I>> Input 1 PHHPTOC 1 Input 1 July 1, 2009 Slide 48

49 Supported station communication protocols Interfaces / Protocols Ethernet (RJ-45) Serial (RS-485 / RS-232) + IRIG-B Serial (fibre ST) +IRIG-B IEC IEC DNP3 TCP/IP - - DNP3 serial - Modbus TCP/IP - - Modbus RTU/ASCII - = supported, - = not supported July 1, 2009 Slide 49

50 Station time synchronization Ethernet-based time synchronization: SNTP (Simple Network Time Protocol) With special time synchronization wiring: IRIG-B (Inter-Range Instrumentation Group - Time Code Format B) Remote-end station time reference: Line-differential Time stamp resolution: 1 ms July 1, 2009 Slide 50

51 Front port communication RJ45 Ethernet connector IED configuration using PCM600 IED access using the webbrowser-based HMI LED indication on the local HMI during data transfer Both crossover and regular cables can be used July 1, 2009 Slide 51

52 July 1, 2009 Slide 52

53 615 series Patented and compact plug-in design Speeds up installation, maintenance and testing of the protection Contributes to a shortened MTTR (mean time to recover) Allows the cases to be installed and wired before the plug-in units are delivered Mechanical coding system for preventing insertion of a wrong plug-in unit in a case Sealable pull-out handle to prevent accidental (or unauthorized) withdrawal of the plug-in unit July 1, 2009 Slide 53

54 615 series IED case and plug-in unit Height: frame 177 mm, case 164 mm Width: frame 177 mm (4U), case 160 mm Depth: case 155 mm IP classification IP54 IP20 When panelmounted Rear side July 1, 2009 Slide 54

55 615 series Flush and semi-flush mounting Flush mounting The same cut-out on the cubicle front as for the 610 series IEDs (height: ±1, width: ±1) Semi-flush mounting With a 50 mm rising frame July 1, 2009 Slide 55

56 615 series Semi-flush and wall mounting Semi-flush mounting in a 25 angle With special accessories Wall mounting The IED can be tilted for easy access to the connectors July 1, 2009 Slide 56

57 615 series Panel and rack mounting Mounting using a 19 mounting panel One or two IEDs Mounting with an RTXP test switch in a 19 rack For routine testing purposes July 1, 2009 Slide 57

58 July 1, 2009 Slide 58

59 615 series Three dedicated LEDs: Ready, Start,Trip 4 x 16 character display (LCD) CB Control, OPEN and CLOSE buttons 11 programmable LEDs ENTER button CLEAR button Front communication port MENU button ESC button Navigation buttons LOCAL/REMOTE button, HELP AUTHORIZATION July 1, 2009 Slide 59

60 615 series Display Large LCD, mono-spaced 10 x 20 characters, variable width 8 x 8 (or more) characters Small LCD, mono-spaced 4 x 20 characters, variable width 4 x 8 (or more) characters Background light with power-saving mode Option: Small LCD Large LCD July 1, 2009 Slide 60

61 Display readouts IEC naming, classic IEC symbols or ANSI codes: (LNPLDF, 3ΔI >, 87L) Fault indications Four fault recordings with time stamp Measurements: Currents Historical data July 1, 2009 Slide 61

62 Display readouts, cont d Name or code of protected objects Settings in 4 setting groups Configurations such as protocol settings etc. Product information, serial number, software version, identification etc. July 1, 2009 Slide 62

63 July 1, 2009 Slide 63

64 PCM600 Web-browser-based user interface RED615 Connectivity Package, including the line differential characteristics tool Version 2.0 SP2 or later IE 7.0 or later 2.5 or later July 1, 2009 Slide 64

65 PCM600 Protection and control IED Manager A common tool for new and existing protection IEDs and terminals IED-specific connectivity packages enable the use PCM600 for different ABB protection IEDs and terminals Supports IEC GOOSE messaging configuration (PCM600 Engineering Pro) IED interaction using: Corporate LAN/WAN The IED s communication port July 1, 2009 Slide 65

66 PCM600 All tools needed to manage RED615 are included in PCM600: Signal matrix Signal monitoring IED parameter setting Disturbance recorder handling and viewing IEC (GOOSE) communication configuration Modbus communication configuration DNP3 communication configuration IEC communication configuration Access control management July 1, 2009 Slide 66

67 PCM600 Power system overview PCM600 offers the possibility to create a tree-structure representing your individual power system, including: Project name Substations Voltage levels Bays IEDs/terminals July 1, 2009 Slide 67

68 615 series Web-browser based user interface Local or remote IED access using an IE 7.0 (or later) web browser Disabled by default, enabled by PCM600 or the local front-panel interface Functions: Viewing of alarm LEDs and event lists Saving of event data Parameter setting Signal monitoring Measurement viewing Phasor diagram viewing Reading of disturbance records User access level authentication July 1, 2009 Slide 68

69 Differential characteristics tool Included in the connectivity package Visual presentation of the differential protection characteristics Possibility to read fault records from the IED and present them on the characteristic Writing of parameters to the IED using the local HMI, the web-browser based HMI or PCM600 July 1, 2009 Slide 69

70 July 1, 2009 Slide 70

71 Product summary Phase segregated line differential protection with two stages IEC station communication including GOOSE messaging Binary signal transfer between the IEDs in the substations (located apart from each other) Extensive supervision on protection communication and CT secondary connections All I/Os are fully matrixed, thus enabling optimal use Rapid set-up and commissioning, preconfigured IEDs Versatile tools July 1, 2009 Slide 71

72 Selection and ordering data, digit 1-3 July 1, 2009 Slide 72

73 Selection and ordering data, digit 4-8 July 1, 2009 Slide 73

74 Selection and ordering data, digit 9-11 July 1, 2009 Slide 74

75 Selection and ordering data, digit 9-11 cont d July 1, 2009 Slide 75

76 Selection and ordering data, digit July 1, 2009 Slide 76

77 Selection and ordering data, ordering code July 1, 2009 Slide 77

78 Product pages on the web July 1, 2009 Slide 78

79 Please visit our website for the latest product information July 1, 2009 Slide 79

80

Relion 615 series Feeder Protection and Control REF615 Ver. 2.0 Technical Presentation

Relion 615 series Feeder Protection and Control REF615 Ver. 2.0 Technical Presentation Relion 615 series Feeder Protection and Control REF615 Ver. 2.0 Technical Presentation Distribution Automation May 13, 2010 1MRS756407 E Slide 1 Content REF615 Technical Presentation highlights May 13,

More information

Content REF615 Technical Presentation

Content REF615 Technical Presentation Distribution Automation Relion 615 series Feeder Protection and Control Ver. 2.0 Technical Presentation March 30, 2010 1MRS756407 E Slide 1 Content Technical Presentation highlights March 30, 2010 Slide

More information

Relion 615 series Transformer Protection and Control RET615 Ver. 2.0 Technical Presentation

Relion 615 series Transformer Protection and Control RET615 Ver. 2.0 Technical Presentation Relion 615 series Transformer Protection and Control RET615 Ver. 2.0 Technical Presentation Distribution Automation May 13, 2010 1MRS756901 A Slide 1 Content RET615 Technical Presentation highlights May

More information

Feeder Protection REF615 Ver Technical Presentation. ABB Oy Distribution Automation. Prashant Ganoo Regional Product Marketing Manager

Feeder Protection REF615 Ver Technical Presentation. ABB Oy Distribution Automation. Prashant Ganoo Regional Product Marketing Manager ABB Oy Distribution Automation Prashant Ganoo Regional Product Marketing Manager Feeder Protection REF615 Ver. 1.1 Technical Presentation 9/26/2008-1 - 1MRS756407 C Self Introduction Prashant Ganoo B.E.(ELECT),

More information

Electrical Integration with Smart Communication

Electrical Integration with Smart Communication Electrical Integration with Smart Communication New possibilities with Industrial Ethernet ABB Group September 24, 2009 Slide 1 Unified Integration Approach MES and Business Systems Knowledge Portals as

More information

Substation Automation Products. Line differential protection RED670 Relion 670 series

Substation Automation Products. Line differential protection RED670 Relion 670 series Substation Automation Products Line differential protection RED670 Relion 670 series For maximum reliability of your power system The RED670 IED (Intelligent Electronic Device) is designed for protection,

More information

Substation Automation Products. High impedance differential busbar protection REB650 Relion 650 series

Substation Automation Products. High impedance differential busbar protection REB650 Relion 650 series Substation Automation Products High impedance differential busbar protection REB650 Relion 650 series One IED for a wide range of high impedance differential protection applications ABB introduces a new,

More information

Substation Automation Products. Line distance protection REL670/650 Relion 670 and 650 series

Substation Automation Products. Line distance protection REL670/650 Relion 670 and 650 series Substation Automation Products Line distance protection REL670/650 Relion 670 and 650 series For maximum reliability of your power system REL670 and REL650 line distance protection IEDs (Intelligent Electronic

More information

Substation Automation Products. Bay control REC670/650 Relion 670 and 650 series

Substation Automation Products. Bay control REC670/650 Relion 670 and 650 series Substation Automation Products Bay control REC670/650 Relion 670 and 650 series For optimized control and reliable operation of your switchyard The REC670 and REC650 Bay control IEDs (Intelligent Electronic

More information

Substation Automation Products. Generator protection REG670/650 Relion 670 and 650 series

Substation Automation Products. Generator protection REG670/650 Relion 670 and 650 series Substation Automation Products Generator protection REG670/650 Relion 670 and 650 series A new protection standard for your valuable assets Based on ABB s extensive experience, REG670 and REG650 IEDs (Intelligent

More information

Feeder Protection REF615. Product Guide

Feeder Protection REF615. Product Guide Product Guide Contents 1 Description.............................. 3 2 Standard configurations................. 3-4 3 Protection functions.................... 4-5 4 Application...........................

More information

Substation Automation Products. Transformer protection RET670/650 Relion 670 and 650 series

Substation Automation Products. Transformer protection RET670/650 Relion 670 and 650 series Substation Automation Products Transformer protection RET670/650 Relion 670 and 650 series For reliable protection and control of all types of power transformers and reactors The RET670/650 IEDs (Intelligent

More information

Relion 615 series. Feeder Protection and Control REF615 Product Guide

Relion 615 series. Feeder Protection and Control REF615 Product Guide Relion 615 series Feeder Protection and Control Product Guide Contents 1. Description...3 2. Standard configurations...3 3. Protection functions...8 4. Application...16 5. Supported ABB solutions...22

More information

Laurent Sowazi, EPMV-DA/ Africa Channel Partner event, 2016 ABB Distribution Automation Making Grids Smarter. ABB November 23, 2016

Laurent Sowazi, EPMV-DA/ Africa Channel Partner event, 2016 ABB Distribution Automation Making Grids Smarter. ABB November 23, 2016 Laurent Sowazi, EPMV-DA/ Africa Channel Partner event, 2016 ABB Distribution Automation Making Grids Smarter Slide 1 Distribution Automation Footprint Global deliveries Finland (Vaasa) Home market deliveries

More information

TWO-WINDING TRANSFORMER DIFFERENTIAL

TWO-WINDING TRANSFORMER DIFFERENTIAL E3-TR PROTECTION WITH AUTOMATIC VOLTAGE Because of the control, measuring and monitoring functions implemented, the IED can also be used as a bay control unit. The EuroCAP configuration tool, which is

More information

Transformer Protection and Control RET630 Numerical transformer protection in medium voltage networks

Transformer Protection and Control RET630 Numerical transformer protection in medium voltage networks GUIDEFORM SPECIFICATION Transformer Protection and Control RET630 Numerical transformer protection in medium voltage networks The freely configurable relay is intended for protection, control, measurement

More information

Relion 615 series. Line Differential Protection and Control RED615 Product Guide

Relion 615 series. Line Differential Protection and Control RED615 Product Guide Relion 615 series Line Differential Protection and Control Product Guide Contents 1. Description...3 2. Standard configurations...3 3. Protection functions...6 4. Application...8 5. Supported ABB solutions...13

More information

Relion 615 series. Feeder Protection and Control REF615 Product Guide

Relion 615 series. Feeder Protection and Control REF615 Product Guide Relion 615 series Feeder Protection and Control Product Guide Contents 1. Description...3 2. Standard configurations...3 3. Protection functions...7 4. Application...9 5. Supported ABB solutions...12 6.

More information

Relion 630 series. Load-shedding controller PML630 High performing load-shedding solution for industrial and utility power networks

Relion 630 series. Load-shedding controller PML630 High performing load-shedding solution for industrial and utility power networks Relion 630 series Load-shedding controller PML630 High performing load-shedding solution for industrial and utility power networks Integrated load-shedding and protection solution The PML630 is a freely-configurable

More information

Grid Automation Controller COM600 How it fits into the Smart Grid?

Grid Automation Controller COM600 How it fits into the Smart Grid? ABB Oy Distribution Automation Grid Automation Controller How it fits into the Smart Grid? May 27, 2014 Slide 1 1MRS756763 E Content Technical Presentation May 27, 2014 Slide 2 Description Grid Automation

More information

Relion 630 series. Load Shedding Controller PML630 Product Guide

Relion 630 series. Load Shedding Controller PML630 Product Guide Relion 630 series Load Shedding Controller Product Guide Contents 1. Description...3 2. Power management systems...3 3. Application...3 4. Communication...4 5. Network architecture...4 6. Terminology in

More information

Jehanpour Ranjkesh, Integrator Partner Seminar 2012 Station level product news Automation Controller COM600

Jehanpour Ranjkesh, Integrator Partner Seminar 2012 Station level product news Automation Controller COM600 Jehanpour Ranjkesh, Integrator Partner Seminar 2012 Station level product news Automation Controller COM600 Contents COM600 Product Overview Business Overview Product News Overview June 12-14, 2012 Slide

More information

Power Products. Protection and Control IED Manager PCM600 Product Guide

Power Products. Protection and Control IED Manager PCM600 Product Guide Power Products Protection and Control IED Manager Product Guide Contents 1. Description............................ 3 2. Tool variants........................... 3 3. Connectivity packages...................

More information

Bus Bar Protection Relay B-PRO 4000

Bus Bar Protection Relay B-PRO 4000 Bus Bar Protection Relay B-PRO 4000 Product Overview The IEC 61850 station bus embedded B-PRO 4000 relay provides complete bus and substation differential protection (low impedance) with CT saturation

More information

MiCOM P122C Time-Overcurrent Protection

MiCOM P122C Time-Overcurrent Protection Protection Relays 01 MiCOM P122C Time-Overcurrent Protection Customer Benefits 1A/5A software setting 4 function keys Compact unit for flush and wall-surface mounting Comprehensive measurements Disturbance

More information

Lars Frisk, Frantz Kruger, Integrator Partner Seminar 2012 Bay level product news Relion & supporting products

Lars Frisk, Frantz Kruger, Integrator Partner Seminar 2012 Bay level product news Relion & supporting products Lars Frisk, Frantz Kruger, Integrator Partner Seminar 2012 Bay level product news Relion & supporting products Bay level product news Relion & Relion supporting products Relion for generation, transmission

More information

Feeder Protection Relay REF 610. Product Guide

Feeder Protection Relay REF 610. Product Guide Product Guide Contents 1 Description.............................. 3 2 Protection functions....................... 3 3 Measurement............................ 4 4 Disturbance recorder......................

More information

Sensitive Earth-fault Relay SPAJ 111 C. Product Guide

Sensitive Earth-fault Relay SPAJ 111 C. Product Guide Issued: April 1999 Status: Update Version: C/12.04.2006 Data subject to change without notice Features Sensitive low-set neutral overcurrent stage with definite time characteristic High-set neutral overcurrent

More information

Earth-fault Relay SPAJ 110 C. Product Guide

Earth-fault Relay SPAJ 110 C. Product Guide Issued: April 1999 Status: Updated Version: C/12.04.2006 Data subject to change without notice Features Low-set neutral overcurrent stage with definite time or inverse time characteristic High-set neutral

More information

Recloser Controller for feeder protection and automation siemens.com/distribution-automation

Recloser Controller for feeder protection and automation siemens.com/distribution-automation SIPROTEC 7SC80 Control Controller for feeder protection and automation siemens.com/distribution-automation SIPROTEC 7SC80 Control Designed for feeder automation applications This solution allows very fast

More information

This webinar brought to you by the Relion product family Advanced protection and control IEDs from ABB

This webinar brought to you by the Relion product family Advanced protection and control IEDs from ABB This webinar brought to you by the Relion product family Advanced protection and control IEDs from ABB Relion. Thinking beyond the box. Designed to seamlessly consolidate functions, Relion relays are smarter,

More information

Numerical motor protection in medium voltage networks Motor Protection and Control REM620

Numerical motor protection in medium voltage networks Motor Protection and Control REM620 Guideform Specification 1MRS758530 A Numerical motor protection in medium voltage networks Motor Protection and Control REM620 The configurable motor management relay is intended for protection, control,

More information

MiCOM P521. Fast feeder differential protection

MiCOM P521. Fast feeder differential protection 01 Fast feeder differential protection The relay provides high-speed two-ended current differential unit protection of overhead lines and underground cables in applications such as ring mains and parallel

More information

SIPROTEC 7SC80 Feeder Protection and Automation Answers for infrastructure and cities.

SIPROTEC 7SC80 Feeder Protection and Automation Answers for infrastructure and cities. www.siemens.com/protection SIPROTEC 7SC80 Feeder Protection and Automation Answers for infrastructure and cities. designed for feeder automation applications This solution allows very fast fault detection

More information

RELAYABLE POWER. AQ 200 series protection, control, measurement and monitoring IEDs

RELAYABLE POWER. AQ 200 series protection, control, measurement and monitoring IEDs RELAYABLE POWER AQ 200 series protection, control, measurement and monitoring IEDs Contents AQ 200 series protection and control IEDs 3 AQ 200 benefits 3 AQ 200 protection functions 4 AQ 200 control and

More information

DS Agile C264. Grid Solutions. Dual-bay Modular Substation Controller. Multi-function Controller. Automation and Control. Advanced Communication

DS Agile C264. Grid Solutions. Dual-bay Modular Substation Controller. Multi-function Controller. Automation and Control. Advanced Communication GE Grid Solutions DS Agile C264 Dual-bay Modular Substation Controller The DS Agile C264 substation controller is a sophisticated solution supporting multiple applications and functions for substation

More information

Feeder Protection REF615 ANSI. Product Guide

Feeder Protection REF615 ANSI. Product Guide Product Guide Contents 1 Description............................. 3 2 Standard configurations................ 3-4 3 Protection functions................... 4-5 4 Application.......................... 6-7

More information

SEL-487B. A Powerful Solution for Busbar Differential Protection. Bus Differential and Breaker Failure Relay

SEL-487B. A Powerful Solution for Busbar Differential Protection. Bus Differential and Breaker Failure Relay Bus Differential and Breaker Failure Relay A Powerful Solution for Busbar Differential Protection Features and Benefits Select the for the differential protection of busbar systems with up to 18 terminals.

More information

SIPROTEC 5 V7.8 Protection, automation and monitoring for digital substations

SIPROTEC 5 V7.8 Protection, automation and monitoring for digital substations SIPROTEC 5 V7.8 Protection, automation and monitoring for digital substations siemens.com/siprotec5 SIPROTEC 5 Table of content Introduction New functions of V7.8 SIPROTEC 5 - the core of Digital Substation

More information

Relion 615 series. Feeder protection and control REF615 ANSI Product guide

Relion 615 series. Feeder protection and control REF615 ANSI Product guide Relion 615 series Feeder protection and control Product guide Contents 1 Description............................. 3 2 Standard configurations................ 4-5 3 Protection functions...................

More information

Feeder protection relay SPAA 121 C. Product Guide

Feeder protection relay SPAA 121 C. Product Guide Issued: April 1999 Status: Updated Version: C/06.03.2006 Data subject to change without notice Features Two-phase low-set phase overcurrent unit with definite time or inverse time characteristic Two-phase

More information

RELAYABLE POWER. AQ-200 series protection, control, measurement and monitoring IEDs

RELAYABLE POWER. AQ-200 series protection, control, measurement and monitoring IEDs RELAYABLE POWER AQ-200 series protection, control, measurement and monitoring IEDs Contents AQ-200 series protection and control IEDs 3 AQ-200 benefits 3 Arcteq innovation: ultra-accurate measurement technology

More information

Non-conventional instrument transformers Advanced GIS substations with IEC LE process bus

Non-conventional instrument transformers Advanced GIS substations with IEC LE process bus Non-conventional instrument transformers Advanced GIS substations with IEC 61850-9-2LE process bus Content Towards the digital GIS substations Optimized substation design NCIT for gas-insulated switchgears

More information

A low-cost, economical solution for distribution feeder protection

A low-cost, economical solution for distribution feeder protection SEL-351A Protection System A low-cost, economical solution for distribution feeder protection Achieve sensitive and secure fault detection using comprehensive protection functions. Track breaker status

More information

RED615 ANSI Line differential protection and control

RED615 ANSI Line differential protection and control DESCRIPTIVE BULLETIN RED615 ANSI Line differential protection and control RED615 is a phase-segregated, twoend line differential protection and control relay for protection, control, measurement and supervision

More information

1) IED Protection and Control Manager PCM 600 Tool (SEP-601) The following subjects will be studied:

1) IED Protection and Control Manager PCM 600 Tool (SEP-601) The following subjects will be studied: 1) IED Protection and Control Manager PCM 600 Tool (SEP-601) PCM 600 Introduction and Overview Application Configuration Tool (CAP 531) Signal Matrix Tool, SMT Graphical Display Editor, GDE Parameter Setting

More information

Overcurrent and Arc Protection by Reyrolle Alexander Erokhin. 21, 2017 I Berlin

Overcurrent and Arc Protection by Reyrolle Alexander Erokhin. 21, 2017 I Berlin Overcurrent and Arc Protection by Reyrolle Alexander Erokhin VAR Partner Day September 20-21, 21, 2017 I Berlin Reyrolle Product Range by SIEMENS Challenges We Meet for our Customers Easy-to-use protection

More information

Protection relays.

Protection relays. Protection relays www.vamp.fi Vamp Ltd Vamp Ltd, with a strong experience of designing devices, is an independent supplier of relays and monitoring equipment. The company has an established reputation

More information

Busbar protection REB 670

Busbar protection REB 670 Gunnar Stranne Busbar protection REB 670 Rio de Janeiro April 23-25, 2006 ABB Power Technologies AB 2 3 4 REB 500 is enabled for use with IEC61850 communication Benefits of REB 670 outstanding features

More information

SIPROTEC 5 Application Note. Breaker-and-a-half solutions. SIP5-APN-002, Edition 2.

SIPROTEC 5 Application Note. Breaker-and-a-half solutions. SIP5-APN-002, Edition 2. -and-a-half solutions SIP5-APN-002, Edition 2 www.siemens.com/protection SIPROTEC 5 Application Note -and-a half solutions SIP5-APN-002, Edition 2 -and-a-half solution Content 1 -and-a-half solutions 3

More information

Synchro-check relay. Application

Synchro-check relay. Application Issued: April 1999 Status: Updated Version: B/08.11.2001 Data subject to change without notice Features Two identical operation stages allowing the closing conditions of two separate circuit breakers to

More information

Sensitive definite time or inverse time earth-fault stage for back-up residual earthfault

Sensitive definite time or inverse time earth-fault stage for back-up residual earthfault Issued: April 1999 Status: Updated Version: B/09.11.2001 Data subject to change without notice Features Sensitive restricted earth-fault protection stage for fast, selective earth-fault protection Sensitive

More information

Combined Overcurrent and Earth-fault Relay SPAJ 141 C. Product Guide

Combined Overcurrent and Earth-fault Relay SPAJ 141 C. Product Guide Combined Overcurrent and Earth-fault Product Guide Issued: April 1999 Status: Updated Version: C/19.04.2006 Data subject to change without notice Features Three-phase, low-set phase overcurrent unit with

More information

Session Five: IEC61850 Based Process Bus Protection Solution for Remote Located Power Transformers

Session Five: IEC61850 Based Process Bus Protection Solution for Remote Located Power Transformers Session Five: IEC61850 Based Process Bus Protection Solution for Remote Located Power 1. Abstract Dinesh Mithanthaya Design Manager, Horizon Power Higher capacity substation power transformers ( 5MVA),are

More information

Type SDR reclosers plus controllers and type B-2 recloser bypass switch assembly usa.siemens.com/mediumvoltage

Type SDR reclosers plus controllers and type B-2 recloser bypass switch assembly usa.siemens.com/mediumvoltage Overhead solutions Type SDR reclosers plus controllers and type B-2 recloser bypass switch assembly usa.siemens.com/mediumvoltage Overhead switching products Brochure Your outdoor overhead distribution

More information

Combined Overcurrent and Earth-fault Relay SPAJ 140 C. Product Guide

Combined Overcurrent and Earth-fault Relay SPAJ 140 C. Product Guide Combined Overcurrent and Earth-fault Product Guide Issued: April 1999 Status: Updated Version: C/18.04.2006 Data subject to change without notice Features Three-phase, low-set phase overcurrent unit with

More information

SOLKOR-N (7SR18) Feeder Differential Protection. Make the ight choice! Choose EYROLLE Protection

SOLKOR-N (7SR18) Feeder Differential Protection. Make the ight choice! Choose EYROLLE Protection SOLKO-N (7S18) Feeder Differential Protection CLASSIFICATION OF UNIT TYPE POTECTION Summation Transformer, Circulating Current Protection B B 3 1 1 O O 3 1 1 SUMMATION TANSFOME SUMMATION TANSFOME O - Operating

More information

Relion 615 series. Feeder Protection and Control REF615 Product Guide

Relion 615 series. Feeder Protection and Control REF615 Product Guide Relion 615 series Feeder Protection and Control Product Guide Contents 1. Description...3 2. Standard configurations...3 3. Protection functions...8 4. Application...16 5. Supported ABB solutions...22

More information

Relion 611 series. Busbar and Multipurpose Differential Protection and Control REB611 Product Guide

Relion 611 series. Busbar and Multipurpose Differential Protection and Control REB611 Product Guide Relion 611 series Busbar and Multipurpose Differential Protection and Control Product Guide Contents 1. Description...3 2. Standard configuration...3 3. Protection functions...5 4. Application...5 5. Supported

More information

MiCOM P521. Fast Feeder Differential Protection

MiCOM P521. Fast Feeder Differential Protection 01 Fast Feeder Differential Protection The relay provides high-speed two-ended current differential unit protection of overhead lines and underground cables in applications such as ring mains and parallel

More information

7SR21 Non-Directional 7SR22 Directional Overcurrent Relay

7SR21 Non-Directional 7SR22 Directional Overcurrent Relay 7SR21 Non-Directional 7SR22 Directional Overcurrent Relay Document Release History This document is issue 2010/05. The list of revisions up to and including this issue is: 2010/05 Additional Comms module

More information

Power Systems Communications Implementation of IEC61850 in a Substation Environment

Power Systems Communications Implementation of IEC61850 in a Substation Environment Power Systems Communications Implementation of IEC61850 in a Substation Environment 26 October 2009 Reference VEE4700-01 Revision 0 Document Control Document ID: DOCUMENT1 Rev No Date Revision Details

More information

Voltage regulator. SPAU 341 C 1MRS MBG Issued: July 1998 Status: Revised Version: C/ Data subject to change without notice

Voltage regulator. SPAU 341 C 1MRS MBG Issued: July 1998 Status: Revised Version: C/ Data subject to change without notice Issued: July 1998 Status: Revised Version: C/08.10.2003 Data subject to change without notice Features Comprehensive voltage regulation for power transformers with on-load tapchangers in distribution substations

More information

REL52002 Easergy P3U30, 4L, 4U, 16DI/8DO, Uaux: V, DI: V, RS-485

REL52002 Easergy P3U30, 4L, 4U, 16DI/8DO, Uaux: V, DI: V, RS-485 Characteristics Easergy P3U30, 4L, 4U, 16DI/8DO, Uaux: 48-230V, DI: 220-230V, RS-485 Main Range of product Product or component type Relay application Device short name [Us] rated supply voltage Type of

More information

Distribution Automation, India Product portfolio

Distribution Automation, India Product portfolio Distribution Automation, India Product portfolio Distribution Automation Product portfolio Main protection for MV / LV switchgear Generator / Generator-Transformer protection for machines < 40 MW Fast

More information

Current Matters. The Device issue. Siemens Protection Devices Ltd. In-depth looks at some of our best and most versatile products to date

Current Matters. The Device issue. Siemens Protection Devices Ltd. In-depth looks at some of our best and most versatile products to date Offshore Spotlight ENERGY Issue 02 Oct 2013 www.siemens.com/reyrolle Current Matters Siemens Protection Devices Ltd Protecting your electrical assets... today and tomorrow The Device issue In-depth looks

More information

Feeder protection relay SPAA 341 C. Product Guide

Feeder protection relay SPAA 341 C. Product Guide Issued: April 1999 Status: Updated Version: D/07.03.2006 Data subject to change without notice Features Comprehensive numerical feeder protection relay consisting of two multi-function protection relay

More information

Siprotec 7ST61 / 7ST63

Siprotec 7ST61 / 7ST63 Siprotec / Numerical overhead contact line protection for AC traction power supply siemens.de/rail-electrification The numerical overhead contact line protection relay Siprotec / is a selective and quick

More information

Advanced distribution feeder solution with integrated protection, monitoring, and control

Advanced distribution feeder solution with integrated protection, monitoring, and control Protection System Advanced distribution feeder solution with integrated protection, monitoring, and control Achieve sensitive and secure fault detection using comprehensive protection functions. Keep track

More information

RELAYABLE POWER. AQ 200 series protection, control, measurement and monitoring IEDs

RELAYABLE POWER. AQ 200 series protection, control, measurement and monitoring IEDs RELAYABLE POWER AQ 200 series protection, control, measurement and monitoring IEDs Contents AQ 200 series protection and control IEDs 3 AQ 200 benefits 3 AQ 200 protection functions 4 AQ 200 control and

More information

NEO 3000 Substation System THE FAMILY OF EQUIPMENT DEDICATED FOR POWER UTILITIES. Energy Sector

NEO 3000 Substation System THE FAMILY OF EQUIPMENT DEDICATED FOR POWER UTILITIES. Energy Sector THE FAMILY OF EQUIPMENT DEDICATED FOR POWER UTILITIES Introduction The supply of electrical energy occupies an important position in the life of modern society. Operation of commerce, industry, transport,

More information

REL52001 Easergy P3U30, 4L, 4U, 16DI/8DO, Uaux: V, DI: V, 2 x RJ-45

REL52001 Easergy P3U30, 4L, 4U, 16DI/8DO, Uaux: V, DI: V, 2 x RJ-45 Characteristics Easergy P3U30, 4L, 4U, 16DI/8DO, Uaux: 48-230V, DI: 220-230V, 2 x RJ-45 Main Range of product Product or component type Relay application Configuration type (Cortec) [Us] rated supply voltage

More information

MiCOM P111. Three phase and earth fault overcurrent relays

MiCOM P111. Three phase and earth fault overcurrent relays Three phase and earth fault overcurrent relays The relays are suitable for all the application where overcurrent and/or earth-fault protection are required. Thanks to its favorable price vs technical features

More information

PRODUCT GUIDE. RER620 Advanced recloser protection & control

PRODUCT GUIDE. RER620 Advanced recloser protection & control PRODUCT GUIDE RER620 Advanced recloser protection & control 2 RER620 ADVANCED RECLOSER PROTECTION & CONTROL Table of contents 003 004 1. Description 004 006 2. Standard configurations 006 007 3. Protection

More information

GE Multilin 350 Feeder Protection Relay Specifications

GE Multilin 350 Feeder Protection Relay Specifications GE Multilin 350 Feeder Protection Relay Specifications The feeder protection relay shall provide primary protection of medium voltage distribution feeders. The relay shall be equipped with the following

More information

Communication Gateway COM 610. Product Guide

Communication Gateway COM 610. Product Guide Communication Gateway COM 610 Product Guide Issued: September 2004 Status: Updated Version: D/17.10.2006 Data subject to change without notice Features Protocol conversion gateway for substation automation:

More information

MiCOM P124 T&D. Self and Dual Powered Overcurrent Relays

MiCOM P124 T&D. Self and Dual Powered Overcurrent Relays PROTECTION MiCOM P124 Self and Dual Powered Overcurrent Relays MiCOM P124 are numerical relays designed to offer complete overcurrent protection without requiring any external auxiliary supply. They can

More information

7SR242 Duobias Multi-Function 2-Winding Transformer Protection Relay

7SR242 Duobias Multi-Function 2-Winding Transformer Protection Relay 7SR242 Duobias Multi-Function 2-Winding Transformer Protection Relay Document Release History This document is issue 2010/06. The list of revisions up to and including this issue is: 2010/06 Additional

More information

MiCOM P721 & P723. Numerical High Impedance Differential Relay. Protection Relays. Customer Benefits

MiCOM P721 & P723. Numerical High Impedance Differential Relay. Protection Relays. Customer Benefits 01 MiCOM P721 & P723 Numerical High Impedance Differential Relay The new P72x high impedance differential protection series provides an independent and simple high impedance differential protection solution

More information

Feeder protection relay

Feeder protection relay Page 1 Issued: April 1999 Status: New Data subject to change without notice Features Comprehensive numerical feeder protection relay consisting of two multi-function protection relay modules and a flexible

More information

Utilization of IEC GOOSE messaging in protection applications in distribution network

Utilization of IEC GOOSE messaging in protection applications in distribution network 9AKK106930A2259 Utilization of IEC 61850 GOOSE messaging in protection applications in distribution network Yogesh Bhamare Head-Product Management, Distribution Automation, ABB Limited, Vadodara, India

More information

Lecture 5 Substation Automation Systems. Course map

Lecture 5 Substation Automation Systems. Course map Lecture 5 Substation Automation Systems 1 Course map 2 1 Contents of the Lecture Part 1 Substation Automation Components Substation Automation Functions Communication within the Substation (Intro) Part

More information

DRTS 64. The new generation of advanced test equipment for Relays, Energy meters, Transducers and Power quality meters.

DRTS 64. The new generation of advanced test equipment for Relays, Energy meters, Transducers and Power quality meters. The new generation of advanced test equipment for Relays, Energy meters, Transducers and Power quality meters Testing all relay technologies: electromechanical, solid state, numerical and IEC61850 Manual

More information

SACE Emax 2 Specification guide

SACE Emax 2 Specification guide SACE Emax 2 Specification guide Specification Number: 26 01 20.17 Product Name: LOW VOLTAGE POWER CIRCUIT BREAKERS PART 1 GENERAL NOTE: ( ) Indicates option or a selection is to be made for quantity or

More information

PROTECTION, AUTOMATION & CONTROL

PROTECTION, AUTOMATION & CONTROL PROTECTION, AUTOMATION & CONTROL 1. DTIVA The members of the DTIVA product line are configured to protect and control the elements of not solidly grounded radial networks. Here the application of Petersen

More information

SYMAP R Plug in Variants FI, MI, 87M, TI Technical data

SYMAP R Plug in Variants FI, MI, 87M, TI Technical data SYMAP R Plug in Variants FI, MI, 87M, TI Technical data 1 Product overview SYMAP R (Retrofit) is a digital protection relay for use in medium and high-voltage power systems. Because of its integrated protection

More information

MiCOM P521. Fast Feeder Differential Protection. Protection Relays. MiCOM P521 CUSTOMER BENEFITS

MiCOM P521. Fast Feeder Differential Protection. Protection Relays. MiCOM P521 CUSTOMER BENEFITS MiCOM 01 MiCOM Fast Feeder Differential Protection The MiCOM relay provides high-speed two-ended current differential unit protection of overhead lines and underground cables in applications such as ring

More information

Lecture 6 Substation Automation Systems

Lecture 6 Substation Automation Systems Lecture 6 Substation Automation Systems 1 Course map 2 Contents of the Lecture Part 1 Substation Automation Components & Architectures Substation Automation Functions Communication within the Substation

More information

Advanced Line Differential Protection, Automation, and Control System. Combine subcycle line protection with traveling-wave fault locating

Advanced Line Differential Protection, Automation, and Control System. Combine subcycle line protection with traveling-wave fault locating Advanced Line Differential Protection, Automation, and Control System Combine subcycle line protection with traveling-wave fault locating Subcycle differential and distance protection minimizes damage

More information

DGSZV-EP DIGITAL GALVANIC LONGITUDINAL DIFFERENTIAL PROTECTION. Application field

DGSZV-EP DIGITAL GALVANIC LONGITUDINAL DIFFERENTIAL PROTECTION. Application field DGSZV-EP DIGITAL GALVANIC LONGITUDINAL DIFFERENTIAL PROTECTION The digital galvanic longitudinal differential protection of type DGSZV-EP is part of device family named EuroProt. This short description

More information

DRTS 33. The new generation of advanced three phase relay test set

DRTS 33. The new generation of advanced three phase relay test set The new generation of advanced three phase relay test set Testing all relay technologies: electromechanical, solid state, numerical and IEC61850 Local control with color display Simultaneously available:

More information

Relion 615 series. Voltage Protection and Control REU615 Product Guide

Relion 615 series. Voltage Protection and Control REU615 Product Guide Relion 615 series Product Guide Contents 1. Description...3 2. Standard configurations...3 3. Protection functions...6 4. Application...8 5. Supported ABB solutions...10 6. Control...12 7. Measurement...12

More information

Relion 620 series. Feeder Protection and Control REF620 Product Guide

Relion 620 series. Feeder Protection and Control REF620 Product Guide Relion 620 series Feeder Protection and Control Product Guide Contents 1. Description...3 2. Default configurations...3 3. Protection functions...10 4. Application...10 5. Supported ABB solutions...15

More information

SIPROTEC 7SC805. Merging Unit for conventional instrument transformer. Products for digital substations.

SIPROTEC 7SC805. Merging Unit for conventional instrument transformer. Products for digital substations. Products for digital substations SIPROTEC 7SC805 Merging Unit for conventional instrument transformer Integrated PRP, HSR www.siemens.com/processbus built to create digital substations based on IEC 61850-9-2

More information

Residual overvoltage relay

Residual overvoltage relay Page 1 Issued: April 1999 Status: New Data subject to change without notice Features Definite-time residual overvoltage earthfault protection and supervision Two independent operation stages, e.g. one

More information

ABB Substation Automation Products Relion 670 series Ver. 2.0, IEC & ANSI What s new?

ABB Substation Automation Products Relion 670 series Ver. 2.0, IEC & ANSI What s new? ABB Substation Automation Products Relion 670 series Ver. 2.0, IEC & ANSI What s new? Relion 670 series Ver. 2.0 Relion Product Family 605 610 615 620 630 650 670 Relion 670 series Ver. 2.0 Relion Product

More information

VIP 40/45 VIP 400/410

VIP 40/45 VIP 400/410 40/45 400/410 Selection guide 01 PM100573 40/45 PM100576 400/410 self-powered integrated protection relay Optimised performance for transformer, incomer, feeder and bus riser protection Complete engineered

More information

Landsnet-Icegrid. Requirements for protection and control systems. Principles for the Icelandic power transmission network.

Landsnet-Icegrid. Requirements for protection and control systems. Principles for the Icelandic power transmission network. Landsnet-Icegrid Requirements for protection and control systems. Principles for the Icelandic power transmission network. Introduction.... 4 System requirements... 6 Validity:... 6 Requirements for protection:...

More information

7SR21 Non-Directional 7SR22 Directional Overcurrent Relay

7SR21 Non-Directional 7SR22 Directional Overcurrent Relay 7SR21 Non-Directional 7SR22 Directional Overcurrent Relay Document Release History This document is issue 2010/05. The list of revisions up to and including this issue is: 2010/05 Additional Comms modules

More information

Products Portfolio. Pole mounted Vacuum Recloser

Products Portfolio. Pole mounted Vacuum Recloser Products Portfolio Pole mounted Vacuum Recloser Efacec Switchgear Efacec Switchgear is a leading company in Portugal and a worldwide reference in the development of solutions for power generation, transmission,

More information