DIGITAL RELAY OF PROTECTION AND AUTOMATION SERIES PC83 AND PC830

Size: px
Start display at page:

Download "DIGITAL RELAY OF PROTECTION AND AUTOMATION SERIES PC83 AND PC830"

Transcription

1 DIGITAL RELAY OF PROTECTION AND AUTOMATION SERIES PC83 AND PC830 PC83 and PC830 series devices are designed to perform the relay protection functions and kv networks automation, have different functionality with common design features and main technical characteristics. DESIGN Structurally, the PC83 and PC830 are performed in the form of a block frame with functionally completed modules - "Typical Elements of Substitution" (TES). Each TES is a single board design with built-in front of the connection through the backplane to the inside circuit device and the terminal at the rear for external connections. Connectors and terminals for external connections are fixed to the vertical metal plate, which is the completion of TES and at the same time part of the rear wall of the device. GENERAL FEATURES OF PC83, PC830 SERIES Flexible modular design, standardization of modules, high maintainability. Extended operating temperature range (from -40⁰C to + 70⁰C). Advanced voltage supply range (from 48V to 450V) AC / DC. One service software for all devices. Average lifetime (25 years).* * Subject to timely conduct routine maintenance devices. 1

2 FUNCTIONS AND FEATURES OF РС83 AND РС830 RELAYS Function Code ANSI 1 Transformer differential protection 87P 2 Overexcitation (block differential protection by the 5th harmonic) 24 3 Monitoring the magnetizing current (block differential protection by the 2nd harmonic) 4 Phase distance protection with any of the three characteristics: polygon, circle(ellipse), sector of circle 21P 5 Power swing blocking 68 6 Load encroachment 7 Blocking distance protection at voltage circuits faults 8 Phase directional overcurrent protection 67P 9 Phase instantaneous/time overcurrent protection 50/51P 10 Overcurrent protection with voltage restraint 51V 11 Ground distance protection with any of the three characteristics: polygon, circle (ellipse), the sector of the circle 21G 12 Single-phase directional overcurrent protection (2 analog inputs of free appointment) Neutral directional overcurrent protection 67N 14 Instantaneous/time overcurrent protection of zero sequence at the measured current 50/51G 15 Instantaneous/time overcurrent protection of zero sequence at the rated current 50/51N 16 Sensitive overcurrent protection of zero sequence for electrical power networks with compensated neutral 50/51NC 17 Overvoltage protection 3Uo or start of ground protection from the measured 3Uo 59N 18 Negative sequence overcurrent protection Phase undervoltage protection Phase overvoltage protection Negative sequence overvoltage protection Synchrocheck Underfrequency 81U 24 Overfrequency 81О 25 Breaker failure 50BF 26 Auto recloser Blocking, self-retaining Breaker close/trip circuit monitoring TSC 29 Voltage circuits monitoring VTS 30 Arc protection with fiber optic sensor and the current monitoring 31 Fault location (km) 32 Automatic voltage control for tap changer and supervision 33 Central alarm system s logics 34 Ethernet communication port (optional optical or electrical). Protocol IEC-61850, MODBUS TCP 35 RS 485 port, USB, communication via Modbus RTU 36 Event log, alarm log, disturbance recorder 37 Digital Inputs, pcs 38 Relay Outputs, pcs 39 Analog inputs (current), pcs 40 Analog inputs (voltage), pcs 41 LEDs: alarms, failures and user-programmable, pcs 42 The number of setting groups 43 The option to switch setting groups in the direction of power 2

3 FUNCTIONS AND FEATURES OF РС83 AND РС830 RELAYS РС83-АВ2 РС83-ДТ2 РС83-А2М РС83-А2.0 РС83-В1 РС83-В4 РС83-С РС830-ДЗ РС830-ДТ3 (РС830-Т2) РС830-В2 1 2 steps 2 steps zones steps steps 4 steps 3 steps + 6 steps zones 12 2 steps 13 2 steps 2 steps 2 steps steps с steps steps 18 2 steps 2 steps 2 steps 2 steps 2 steps 2 steps 19 2 steps 2 steps 2 steps 4 steps 20 2 steps 2 steps 21 2 steps 2 steps steps 24 2 steps steps 2 steps 2 steps 2 steps 2 steps 2 steps step 1 step 1 step /13/18 8/13/18 8/13/18 6/ /22 11/22 11/ /12/16 8/12/16 8/12/16 8/ /20 10/20 10/ (7)

4 ADVANTAGES DIGITAL RELAY OF SERIES PC83 Integrated solutions for the entire substation AC and DC power supply, versions with an additional performance power-current and deshunting Cold start period ms Voltage loss hold-up ms duration Low power consumption, size and weight Low Price PURPOSE Protection, automation, control, alarm, measurement, telemechanization and data transmission for substations and connections kv. KEY FEATURES OF РС83 Transformer differential protection. Automatic CT ratio matching and vector group compensation. Instantaneous Differential. Transformer differential protection. Phase directional overcurrent protection. Neutral directional overcurrent protection. Phase overvoltage protection. Phase undervoltage protection. Negative sequence overvoltage protection. Overvoltage protection 3Uo or start of ground protection from the measured 3Uo. Negative sequence overcurrent protection. Logical busbar protection. Acceleration of overcurrent protection. Breaker failure. 2 settings group. Automatic switching-in of reserve. Automatic recloser. Automatic voltage control for tap changer and supervision. Event log, alarm log, disturbance recorder. Fault location (km). Arc protection with fiber optic sensor and the current monitoring. MEASURING, RECORDING, ALARM Measurement of voltages and currents of phases. Measurement of voltage and zero-sequence current. Measurement of angles between the phase currents, voltages, as well as currents and voltages of zero sequence. Digital Oscilloscope at 60 s (record format COMTRADE), fault recorder on 100 events, the event log on 200 events. Calendar and clock with nonvolatile power. Continuous self-diagnostics of the device, nonvolatile storage of the fact of wearing-out of protection and alarm. Non-volatile alarm. 4

5 TECHNICAL SPECIFICATIONS OF РС83 Phase directional overcurrent protection Automatic recloser Pickup level, А Pickup level, А 0, Angle of maximum sensitivity, о The width of the zone, о The width of the zone, о The width of the zone, о Pickup delay, s Pickup delay, s Biased differential protection Negative sequence overcurrent protection Pickup level at the beginning of the zone of action, А 0,5 5 Pickup level, А 0,5 20 The braking rate 0,1 0,9 Pickup delay, s Equalization coefficient 0,25 4 Phase undervoltage protection Pickup delay, s 0 1 Pickup level, V Transformer differential protection Pickup delay, s 0,1 25 Pickup level, А 5 60 Phase overvoltage protection Pickup delay, s 0 1 Pickup level, V Auto recloser Pickup delay, s 0,1 25 Preparation time, s U0мах, U2мах Pickup delay of the 1 cycle, s 1 25 Pickup level, V Pickup delay of the 2 cycle, s 1 60 Pickup delay, s 0,1 25 Digital inputs Output relays Logical unit level 0,65Un Maximum continious current 8 А Breaking capacity (AC) 8A/250V Consumption, not more, ma 2,5 Breaking capacity (DC) FRONT PANEL AND CONTROLS 8A/24V; 1A/50V; 0,4A/250V ON and OFF buttons for controlling the switch. Four menu navigation buttons. Reset button for confirmation the alarm and return to the previous menu. Enter button to confirm the changes made. 18 two-color LEDs. 5

6 EXAMPLE OF EQUIPPING THE KV SUBSTATION WITH PC83 DEVICES Line 35 (110) kv 1-st. busbar 35 (110) kv VOLTAGE TRANSFORMER 35 (110) KV TAP CHANGER 1-st. busbar 10 kv VOLTAGE TRANSFORMER 10 KV Line 10 kv RESERVE LOGICAL BUSBAR PROTECTION LOGICALL BUSBAR PROTECTION CENTRAL ALARM Line 35 (110) kv TAP CHANGER RESERVE LOGICAL BUSBAR PROTECTION LOGICAL BUSBAR PROTECTION Line 10 kv 2-nd. busbar 35 (110) kv VOLTAGE TRANSFORMER 35 (110) KV 2-nd. busbar 10 kv VOLTAGE TRANSFORMER 10 KV 6

7 DIGITAL RELAY OF SERIES PC830 FEATURES PC830 Series differs from PC83 by its enhanced functionality and has increased quantity of discrete inputs to 22 and output relays - to 20, supports new communication interfaces (electric or optical Ethernet) and new interchange protocols (IEC-61850, MODBUS TCP), using the internal logics of devices provides user with more freedom to perform various tasks. THE SERIES CONSISTS OF: Distance Protection PC830-ДЗ. Differential Protection of three-winding transformer PC830-ДТ3. Differential Protection of two-winding transformer PC830-ДТ2. Voltage protection device with function Underfrequency - Overfrequency РС830-В2. EXAMPLE OF EQUIPPING THE 110 kv SUBSTATION WITH PC830 DEVICES Line 110 кв Voltage transformer supervision Distance and overcurrent line protection TV TV РС830-В2 РС830-Д3 Bus sectionalizer circuit breaker protection 110 кv РС830-Д3 To second busbar110 кv Т1 РС830-Д3 Transformer overcurrent and distance protection Transformer differential protection 10 kv 35 kv РС830-ДТ3 7

8 KEY FEATURES OF PC830 Transformer differential protection of three-winding transformer. Automatic CT ratio matching and vector group compensation. Instantaneous differential. Load encroachment. Phase distance protection. Ground distance protection. Phase directional overcurrent protection. Instantaneous/time overcurrent protection of zero sequence. Negative sequence overcurrent protection. Phase undervoltage protection. Phase overvoltage protection. Overvoltage protection 3Uo or start of ground protection from the measured 3Uo. Negative sequence overvoltage protection. Underfrequency - overfrequency control. Logical busbar protection. Acceleration of overcurrent protection. Power swing blocking. Blocking distance protection at voltage circuits faults. Breaker failure. Automatic recloser. Breaker close/trip circuit monitoring. 6 settings group. Fault location (km). Event log, alarm log, disturbance recorder. Synchrocheck. Negative sequence overvoltage protection. Functionality of each device of PC830 series is presented in the table on p DISTANCE PROTECTION FEATURES OF PC830-ДЗ DEVICE Each of the distance protection stages can have one of three kinds of characteristics on complex plane: MHO sector, MHO, a polygon. MHO sector characteristic MHO (ellipse) characteristic polygon characteristic jx jx Z reach settings Xy jx z reach settings Z reach settings 0.5φ zone φ zone φ reach φ reach φ reach R R -0.5R 1 R 1 R 8

9 TECHNICAL SPECIFICATIONS OF PC830 Phase distance protection Ground distance protection Pickup level Zrs, Ohm 0,1 100,0 Pickup level Zrs, Ohm 0,1 100,0 Pickup level R 1, Ohm 0,1 100,0 Pickup level R 1, Ohm 0,1 100,0 Pickup level Xy, Ohm 0,1 100,0 Pickup level Xy, Ohm 0,1 100,0 Angle of maximum sensitivity φ о Angle of maximum sensitivity φ о reach reach The width of the working zone φ o The width of the working zone φ о The compression ratio of the ellipse 0,1 1,0 The compression ratio of the ellipse 0,1 1,0 Pickup delay, s 0 60,0 Pickup delay, s 0 60,0 Phase directional overcurrent protection Instantaneous/time overcurrent protection of zero sequence Pickup level, А 0,3 120 Pickup level, А 0,3 120 Angle of maximum sensitivity, о Angle of maximum sensitivity, о The width of the zone, о The width of the zone, о Pickup delay, s 0 60 Pickup delay, s 0 60 Biased differential protection of three-winding transformer Negative sequence overcurrent protection Pickup level in the beginning of the zone, А 0,5 5 Pickup level, А 0,5 20 Breaking coefficient 0,1 0,9 Pickup delay, s 0 60 Equalization coefficients 0,25 4 Phase undervoltage protection Pickup delay, s 0 1 Pickup level, V Transformer differential protection Pickup delay, s 0 60 Pickup level, А 5 60 Phase overvoltage protection Pickup delay, s 0 1 Pickup level, V Automatic recloser Pickup delay, s 0 60 Preparation time, s U0мах, U2мах Pickup delay of 1 cycle, s 1 25 Pickup level, V 5 50 Pickup delay of 2 cycle, s 1 60 Pickup delay, s 0 60 Underfrequency (4 lines) Overfrequency Pickup level, Hz Pickup level, Hz Pickup delay, s 0 60 Pickup delay, s 1 60 Digital inputs Output relays Level of logical unit 0,65Uн Maximum continious current 8 А Breaking capacity (AC) 8A/250V Consumption, not higher, mа 2,5 8A/24V; Breaking capacity (DC) 1A/50V; 0,4A/250V 9

10 CONFIGURATION, PROGRAMMING OF INTERNAL LOGICS, SETPOINTS All operations on configuration of devices before commissioning can be carried out using the keyboard of Digital relay or using a special software CODIS. When working with the program all the settings and digital relay setpoints can be saved as a file for later modifying or uploading into the device. In emulation mode of CODIS software the digital relay setpoint file can be created and saved even in the absence of the device. "Measurement and control" mode CODIS allows you to display on your computer screen the current values of currents, voltages, their vector diagram. To view the oscillograms there is RZA Oscilog software. AN EXAMPLE OF ONE OF THE CODIS WINDOWS 10

11 OVERALL AND MOUNTING DIMENSIONS РС83 РС830 front view left side view front view left side view top view cutout in panel top view cutout in panel Body type Size А, mm Size В, mm Size С, mm Size D, mm M1 Module M2 Module mass, kg K none none 2 K DIRL AD, DIRL 3 11

12 RECOMMENDED USE OF DIGITAL RELAYS Use РС83-А2.0 РС83-А2М РС83-АВ2 РС83-ДТ2 РС83-В1 РС83-В4 РС83-С РС830-ДЗ РС830-ДТ3 РС830-ДТ2 РС830-В2 Radial line feeder 6(10) кv + + Ring line feeder 6 (10) kv + Bus sectionalizer 6(10) кv + + Main switch 6(10) кv + + Main switch 35 кv + Voltage transformer 6-35 кv + Voltage transformer кv + Radial line feeder 35 kv + Bus sectionalizer circuit breaker 35 kv + Ring line feeder 35 kv + + Back-up protection of transformer kv, control of HVbreaker Differential protection of two-winding transformer 35 kv + + Voltage control for tap changer kv + Central alarm + Bus sectionalizer circuit breaker 110 (150) kv + Radial or ring line feeder 110 (150) kv + Differential protection of three-winding transformer (150) kv Differential protection of two-winding transformer 110 kv + + Synchrocheck + Automatic load transfer + + Ukraine, 03680, Kyiv city, Ivan Lepse blvd, 4, building 1 tel.: +38 (044) fax: +38 (044) info@rzasystems.kiev.ua 12

PROTECTION, AUTOMATION & CONTROL

PROTECTION, AUTOMATION & CONTROL PROTECTION, AUTOMATION & CONTROL 1. DTIVA The members of the DTIVA product line are configured to protect and control the elements of not solidly grounded radial networks. Here the application of Petersen

More information

Microprocessor protection and automation devices

Microprocessor protection and automation devices Microprocessor protection and automation devices THE ТЭМП 2501 MICROPROCESSOR PROTECTION TERMINALS It is well known that microprocessor protection devices have indisputable advantages over electromechanical

More information

TWO-WINDING TRANSFORMER DIFFERENTIAL

TWO-WINDING TRANSFORMER DIFFERENTIAL E3-TR PROTECTION WITH AUTOMATIC VOLTAGE Because of the control, measuring and monitoring functions implemented, the IED can also be used as a bay control unit. The EuroCAP configuration tool, which is

More information

Substation Automation Products. Generator protection REG670/650 Relion 670 and 650 series

Substation Automation Products. Generator protection REG670/650 Relion 670 and 650 series Substation Automation Products Generator protection REG670/650 Relion 670 and 650 series A new protection standard for your valuable assets Based on ABB s extensive experience, REG670 and REG650 IEDs (Intelligent

More information

Siprotec 7ST61 / 7ST63

Siprotec 7ST61 / 7ST63 Siprotec / Numerical overhead contact line protection for AC traction power supply siemens.de/rail-electrification The numerical overhead contact line protection relay Siprotec / is a selective and quick

More information

NPW800R RETROFITTING. Power and Volatge Protection Relay

NPW800R RETROFITTING. Power and Volatge Protection Relay RETROFITTING Power and Volatge Protection Relay NPW800R (R3 case) is dedicated to the refurbishment of CEE WTG 7000 relays (R3 case) providing the measurement of apparent (S), active (P) and reactive (Q)

More information

GE Multilin 350 Feeder Protection Relay Specifications

GE Multilin 350 Feeder Protection Relay Specifications GE Multilin 350 Feeder Protection Relay Specifications The feeder protection relay shall provide primary protection of medium voltage distribution feeders. The relay shall be equipped with the following

More information

Protection relays.

Protection relays. Protection relays www.vamp.fi Vamp Ltd Vamp Ltd, with a strong experience of designing devices, is an independent supplier of relays and monitoring equipment. The company has an established reputation

More information

Substation Automation Products. Transformer protection RET670/650 Relion 670 and 650 series

Substation Automation Products. Transformer protection RET670/650 Relion 670 and 650 series Substation Automation Products Transformer protection RET670/650 Relion 670 and 650 series For reliable protection and control of all types of power transformers and reactors The RET670/650 IEDs (Intelligent

More information

Feeder protection relay SPAA 121 C. Product Guide

Feeder protection relay SPAA 121 C. Product Guide Issued: April 1999 Status: Updated Version: C/06.03.2006 Data subject to change without notice Features Two-phase low-set phase overcurrent unit with definite time or inverse time characteristic Two-phase

More information

DGSZV-EP DIGITAL GALVANIC LONGITUDINAL DIFFERENTIAL PROTECTION. Application field

DGSZV-EP DIGITAL GALVANIC LONGITUDINAL DIFFERENTIAL PROTECTION. Application field DGSZV-EP DIGITAL GALVANIC LONGITUDINAL DIFFERENTIAL PROTECTION The digital galvanic longitudinal differential protection of type DGSZV-EP is part of device family named EuroProt. This short description

More information

SR489 SR489. Generator Management Relay. Economical protection, metering, and monitoring functions for small and medium sized generators.

SR489 SR489. Generator Management Relay. Economical protection, metering, and monitoring functions for small and medium sized generators. SR489 Generator Management Relay Economical protection, metering, and monitoring functions for small and medium sized generators. 1 Product Highlights Inputs / Outputs Generator Protection Power Metering

More information

Bus Bar Protection Relay B-PRO 4000

Bus Bar Protection Relay B-PRO 4000 Bus Bar Protection Relay B-PRO 4000 Product Overview The IEC 61850 station bus embedded B-PRO 4000 relay provides complete bus and substation differential protection (low impedance) with CT saturation

More information

REL52002 Easergy P3U30, 4L, 4U, 16DI/8DO, Uaux: V, DI: V, RS-485

REL52002 Easergy P3U30, 4L, 4U, 16DI/8DO, Uaux: V, DI: V, RS-485 Characteristics Easergy P3U30, 4L, 4U, 16DI/8DO, Uaux: 48-230V, DI: 220-230V, RS-485 Main Range of product Product or component type Relay application Device short name [Us] rated supply voltage Type of

More information

Overcurrent and Arc Protection by Reyrolle Alexander Erokhin. 21, 2017 I Berlin

Overcurrent and Arc Protection by Reyrolle Alexander Erokhin. 21, 2017 I Berlin Overcurrent and Arc Protection by Reyrolle Alexander Erokhin VAR Partner Day September 20-21, 21, 2017 I Berlin Reyrolle Product Range by SIEMENS Challenges We Meet for our Customers Easy-to-use protection

More information

SEL-487B. A Powerful Solution for Busbar Differential Protection. Bus Differential and Breaker Failure Relay

SEL-487B. A Powerful Solution for Busbar Differential Protection. Bus Differential and Breaker Failure Relay Bus Differential and Breaker Failure Relay A Powerful Solution for Busbar Differential Protection Features and Benefits Select the for the differential protection of busbar systems with up to 18 terminals.

More information

Transformer Protection and Control RET630 Numerical transformer protection in medium voltage networks

Transformer Protection and Control RET630 Numerical transformer protection in medium voltage networks GUIDEFORM SPECIFICATION Transformer Protection and Control RET630 Numerical transformer protection in medium voltage networks The freely configurable relay is intended for protection, control, measurement

More information

Transformer Protection Relay

Transformer Protection Relay Transformer Protection Relay T-PRO Product Overview The IEC 61850 station bus embedded T-PRO relay provides complete three-phase multi-winding transformer protection and overload protection, DFR-quality

More information

A low-cost, economical solution for distribution feeder protection

A low-cost, economical solution for distribution feeder protection SEL-351A Protection System A low-cost, economical solution for distribution feeder protection Achieve sensitive and secure fault detection using comprehensive protection functions. Track breaker status

More information

Recloser Controller for feeder protection and automation siemens.com/distribution-automation

Recloser Controller for feeder protection and automation siemens.com/distribution-automation SIPROTEC 7SC80 Control Controller for feeder protection and automation siemens.com/distribution-automation SIPROTEC 7SC80 Control Designed for feeder automation applications This solution allows very fast

More information

SIA-B. Overcurrent & Earth Fault Protection Relay for Secondary Distribution. Dual & Self Powered / Standard CTs. Main characteristics

SIA-B. Overcurrent & Earth Fault Protection Relay for Secondary Distribution. Dual & Self Powered / Standard CTs. Main characteristics SIA-B Overcurrent & Earth Fault Protection Relay for Secondary Distribution Dual & Self Powered / Standard CTs Main characteristics The SIA-B is an protection relay with self powered and dual powered (Self-powering

More information

RELAYABLE POWER. AQ 200 series protection, control, measurement and monitoring IEDs

RELAYABLE POWER. AQ 200 series protection, control, measurement and monitoring IEDs RELAYABLE POWER AQ 200 series protection, control, measurement and monitoring IEDs Contents AQ 200 series protection and control IEDs 3 AQ 200 benefits 3 AQ 200 protection functions 4 AQ 200 control and

More information

Earth-fault Relay SPAJ 110 C. Product Guide

Earth-fault Relay SPAJ 110 C. Product Guide Issued: April 1999 Status: Updated Version: C/12.04.2006 Data subject to change without notice Features Low-set neutral overcurrent stage with definite time or inverse time characteristic High-set neutral

More information

InteliPro. Protection Relay for Parallel Applications. Technical Specification

InteliPro. Protection Relay for Parallel Applications. Technical Specification InteliPro Protection Relay for Parallel Applications Product description InteliPro is a highly flexible interconnection/mains decoupling protective relay with extensive protective functions. It meets the

More information

Protection, Automation, and Control System. Combine subcycle line protection with complete substation bay control

Protection, Automation, and Control System. Combine subcycle line protection with complete substation bay control Protection, Automation, and Control System Combine subcycle line protection with complete substation bay control Subcycle distance protection minimizes damage and expensive repairs on transmission lines.

More information

U lity network. system Q sys. Interconnected P sys. P load Q load. P gen Q gen. Generator network

U lity network. system Q sys. Interconnected P sys. P load Q load. P gen Q gen. Generator network SIL-G Feeder & Generator Protection Relay RC FLSH Main characteristics The SIL-G is a relay for primary distribution which can protect a feeder by means of current and voltage functions. It is also provided

More information

Substation Automation Products. Line differential protection RED670 Relion 670 series

Substation Automation Products. Line differential protection RED670 Relion 670 series Substation Automation Products Line differential protection RED670 Relion 670 series For maximum reliability of your power system The RED670 IED (Intelligent Electronic Device) is designed for protection,

More information

Substation Automation Products. Line distance protection REL670/650 Relion 670 and 650 series

Substation Automation Products. Line distance protection REL670/650 Relion 670 and 650 series Substation Automation Products Line distance protection REL670/650 Relion 670 and 650 series For maximum reliability of your power system REL670 and REL650 line distance protection IEDs (Intelligent Electronic

More information

SIPROTEC 7SC80 Feeder Protection and Automation Answers for infrastructure and cities.

SIPROTEC 7SC80 Feeder Protection and Automation Answers for infrastructure and cities. www.siemens.com/protection SIPROTEC 7SC80 Feeder Protection and Automation Answers for infrastructure and cities. designed for feeder automation applications This solution allows very fast fault detection

More information

REL52001 Easergy P3U30, 4L, 4U, 16DI/8DO, Uaux: V, DI: V, 2 x RJ-45

REL52001 Easergy P3U30, 4L, 4U, 16DI/8DO, Uaux: V, DI: V, 2 x RJ-45 Characteristics Easergy P3U30, 4L, 4U, 16DI/8DO, Uaux: 48-230V, DI: 220-230V, 2 x RJ-45 Main Range of product Product or component type Relay application Configuration type (Cortec) [Us] rated supply voltage

More information

750/760 Feeder Management Relay Instruction Manual

750/760 Feeder Management Relay Instruction Manual GE Digital Energy 750/760 Feeder Management Relay Instruction Manual Software Revision: 7.4x Manual P/N: 1601-0120-AK Manual Order Code: GEK-106471T GE Digital Energy 650 Markland Street Markham, Ontario

More information

Advanced Line Differential Protection, Automation, and Control System. Combine subcycle line protection with traveling-wave fault locating

Advanced Line Differential Protection, Automation, and Control System. Combine subcycle line protection with traveling-wave fault locating Advanced Line Differential Protection, Automation, and Control System Combine subcycle line protection with traveling-wave fault locating Subcycle differential and distance protection minimizes damage

More information

Synchro-check relay. Application

Synchro-check relay. Application Issued: April 1999 Status: Updated Version: B/08.11.2001 Data subject to change without notice Features Two identical operation stages allowing the closing conditions of two separate circuit breakers to

More information

Advanced distribution feeder solution with integrated protection, monitoring, and control

Advanced distribution feeder solution with integrated protection, monitoring, and control Protection System Advanced distribution feeder solution with integrated protection, monitoring, and control Achieve sensitive and secure fault detection using comprehensive protection functions. Keep track

More information

Sensitive Earth-fault Relay SPAJ 111 C. Product Guide

Sensitive Earth-fault Relay SPAJ 111 C. Product Guide Issued: April 1999 Status: Update Version: C/12.04.2006 Data subject to change without notice Features Sensitive low-set neutral overcurrent stage with definite time characteristic High-set neutral overcurrent

More information

Perfect protection smallest space

Perfect protection smallest space www.siemens.com/energy/protection Perfect protection smallest space The SIPROTEC Compact device range redefines protection technology Answers for energy. SIPROTEC Compact is the ideal solution for almost

More information

Residual overvoltage relay

Residual overvoltage relay Page 1 Issued: April 1999 Status: New Data subject to change without notice Features Definite-time residual overvoltage earthfault protection and supervision Two independent operation stages, e.g. one

More information

2 ms arc-flash protection and feeder relay in one platform

2 ms arc-flash protection and feeder relay in one platform Feeder Protection Relay 2 ms arc-flash protection and feeder relay in one platform Combine light sensor inputs with high-speed overcurrent protection to achieve secure arc-flash protection in as fast as

More information

Function permission: yes/no. Operating range: 0.10 to 30 xin (step 0.01) Operating time: 0.02 to 300 s (step 0.01 s) Activation level 100%

Function permission: yes/no. Operating range: 0.10 to 30 xin (step 0.01) Operating time: 0.02 to 300 s (step 0.01 s) Activation level 100% Operating range: 0.10 to 30 xin (step 0.01) 50P(2) Activation level 100% Deactivation level 95% Timer accuracy: 30 ms Operating range: 0.10 to 30 xin (step 0.01) 50N/G(2) Activation level 100% Deactivation

More information

ATV310H075N4E variable speed drive ATV kw - 1 hp V - 3 phase

ATV310H075N4E variable speed drive ATV kw - 1 hp V - 3 phase Characteristics variable speed drive ATV310-0.75 kw - 1 hp - 380...460 V - 3 phase Main Range of product Altivar Easy 310 Product or component type Product specific application Assembly style Device short

More information

ENhanced TEChnology. Solid insulated vacuum recloser for power distribution system thru 15kV, 27kV, 38kV. Ver.

ENhanced TEChnology.  Solid insulated vacuum recloser for power distribution system thru 15kV, 27kV, 38kV. Ver. ENhanced TEChnology www.entecene.co.kr Solid insulated vacuum recloser for power distribution system thru 15kV, 27kV, 38kV Ver. 081226 General features We, ENTEC introduce a Solid Insulated Vacuum Recloser

More information

Feeder/ Motor Protection Relay VAMP 40

Feeder/ Motor Protection Relay VAMP 40 Feeder/ Motor Protection Relay Feeder/motor protection relay Main characteristics Complete protection Comprehensive selection of protection functions for distribution network overhead line feeders, cable

More information

RELAYABLE POWER. AQ-200 series protection, control, measurement and monitoring IEDs

RELAYABLE POWER. AQ-200 series protection, control, measurement and monitoring IEDs RELAYABLE POWER AQ-200 series protection, control, measurement and monitoring IEDs Contents AQ-200 series protection and control IEDs 3 AQ-200 benefits 3 Arcteq innovation: ultra-accurate measurement technology

More information

Substation Automation Products. High impedance differential busbar protection REB650 Relion 650 series

Substation Automation Products. High impedance differential busbar protection REB650 Relion 650 series Substation Automation Products High impedance differential busbar protection REB650 Relion 650 series One IED for a wide range of high impedance differential protection applications ABB introduces a new,

More information

Voltage regulator. SPAU 341 C 1MRS MBG Issued: July 1998 Status: Revised Version: C/ Data subject to change without notice

Voltage regulator. SPAU 341 C 1MRS MBG Issued: July 1998 Status: Revised Version: C/ Data subject to change without notice Issued: July 1998 Status: Revised Version: C/08.10.2003 Data subject to change without notice Features Comprehensive voltage regulation for power transformers with on-load tapchangers in distribution substations

More information

Relion 615 series Transformer Protection and Control RET615 Ver. 2.0 Technical Presentation

Relion 615 series Transformer Protection and Control RET615 Ver. 2.0 Technical Presentation Relion 615 series Transformer Protection and Control RET615 Ver. 2.0 Technical Presentation Distribution Automation May 13, 2010 1MRS756901 A Slide 1 Content RET615 Technical Presentation highlights May

More information

Protection, Automation, and Bay Control System. Advanced feeder protection and complete substation bay control in one economical system

Protection, Automation, and Bay Control System. Advanced feeder protection and complete substation bay control in one economical system SEL-451 Protection, Automation, and Bay Control System Advanced feeder protection and complete substation bay control in one economical system Customize distribution protection using multiple instantaneous,

More information

Product Sheet ECO. Types ECG, AMF Technical data. product sheet eco ecg-amf - technical data gb v1.0.docx

Product Sheet ECO. Types ECG, AMF Technical data.  product sheet eco ecg-amf - technical data gb v1.0.docx ECO Types ECG, AMF Technical data Product overview ECO ECG and ECO AMF are microprocessor controlled devices for use in low voltage single genset applications for standby power generation. The front-side

More information

Power Systems Communications Implementation of IEC61850 in a Substation Environment

Power Systems Communications Implementation of IEC61850 in a Substation Environment Power Systems Communications Implementation of IEC61850 in a Substation Environment 26 October 2009 Reference VEE4700-01 Revision 0 Document Control Document ID: DOCUMENT1 Rev No Date Revision Details

More information

Bus Differential and Breaker Failure Relay. Advanced bus protection with built-in breaker failure detection

Bus Differential and Breaker Failure Relay. Advanced bus protection with built-in breaker failure detection SEL-487B Bus Differential and Breaker Failure Relay Advanced bus protection with built-in breaker failure detection Protect busbars with up to 21 terminals using high-speed, low-impedance bus differential

More information

Protection Relays PHASE & RESIDUAL OVERCURRENT

Protection Relays PHASE & RESIDUAL OVERCURRENT Protection Relays PHASE & RESIDUAL OVERCURRENT Application The relay type NA016 can be used in radial networks as feeder or power transformer protection. In solidly grounded systems the residual overcurrent

More information

Bus Differential and Breaker Failure Relay. Advanced bus protection with built-in breaker failure detection

Bus Differential and Breaker Failure Relay. Advanced bus protection with built-in breaker failure detection SEL-487B Bus Differential and Breaker Failure Relay Advanced bus protection with built-in breaker failure detection Protect busbars with up to 21 terminals using high-speed, low-impedance bus differential

More information

High-speed transformer differential protection for up to five terminals

High-speed transformer differential protection for up to five terminals Transformer Protection Relay High-speed transformer differential protection for up to five terminals Advanced differential protection and three restricted earth fault (REF) elements minimize damage and

More information

S o m e t h i n g b e t t e r t h a n p r o t e c t i v e r e l a y s. automation, control & communication

S o m e t h i n g b e t t e r t h a n p r o t e c t i v e r e l a y s. automation, control & communication S o m e t h i n g b e t t e r t h a n p r o t e c t i v e r e l a y s IEDs with embedded protection, measurement, automation, control & communication digital processing multifunction Monitoring and metering

More information

Bus Differential and Breaker Failure Relay. Advanced bus protection with built-in breaker failure detection

Bus Differential and Breaker Failure Relay. Advanced bus protection with built-in breaker failure detection SEL-487B Bus Differential and Breaker Failure Relay Advanced bus protection with built-in breaker failure detection Protect busbars with up to 21 terminals using high-speed, low-impedance bus differential

More information

RELAYABLE POWER. AQ 200 series protection, control, measurement and monitoring IEDs

RELAYABLE POWER. AQ 200 series protection, control, measurement and monitoring IEDs RELAYABLE POWER AQ 200 series protection, control, measurement and monitoring IEDs Contents AQ 200 series protection and control IEDs 3 AQ 200 benefits 3 AQ 200 protection functions 4 AQ 200 control and

More information

Combined Overcurrent and Earth-fault Relay SPAJ 141 C. Product Guide

Combined Overcurrent and Earth-fault Relay SPAJ 141 C. Product Guide Combined Overcurrent and Earth-fault Product Guide Issued: April 1999 Status: Updated Version: C/19.04.2006 Data subject to change without notice Features Three-phase, low-set phase overcurrent unit with

More information

DTRV-EP. COMPLEX DIGITAL PROTECTION FOR 120 kv / MEDIUM VOLTAGE TRANSFORMERS. Application field

DTRV-EP. COMPLEX DIGITAL PROTECTION FOR 120 kv / MEDIUM VOLTAGE TRANSFORMERS. Application field DTRV-EP COMPLEX DIGITAL PROTECTION FOR 120 kv / MEDIUM VOLTAGE TRANSFORMERS Application field The DTRV type of complex transformer protection is designed to protect 120 kv / medium voltage transformers,

More information

NEO 3000 Substation System THE FAMILY OF EQUIPMENT DEDICATED FOR POWER UTILITIES. Energy Sector

NEO 3000 Substation System THE FAMILY OF EQUIPMENT DEDICATED FOR POWER UTILITIES. Energy Sector THE FAMILY OF EQUIPMENT DEDICATED FOR POWER UTILITIES Introduction The supply of electrical energy occupies an important position in the life of modern society. Operation of commerce, industry, transport,

More information

Perfect protection smallest space

Perfect protection smallest space www.siemens.com/siprotec Perfect protection smallest space The SIPROTEC Compact device range redefines protection technology Answers for infrastructure and cities. SIPROTEC Compact is the ideal solution

More information

ATV310HU30N4E variable speed drive ATV310-3 kw - 4 hp V - 3 phase

ATV310HU30N4E variable speed drive ATV310-3 kw - 4 hp V - 3 phase Characteristics variable speed drive ATV310-3 kw - 4 hp - 380...460 V - 3 phase Complementary Product destination Main Range of product Altivar Easy 310 Product or component type Product specific application

More information

Substation Automation Products. Bay control REC670/650 Relion 670 and 650 series

Substation Automation Products. Bay control REC670/650 Relion 670 and 650 series Substation Automation Products Bay control REC670/650 Relion 670 and 650 series For optimized control and reliable operation of your switchyard The REC670 and REC650 Bay control IEDs (Intelligent Electronic

More information

7SR242 Duobias Multi-Function 2-Winding Transformer Protection Relay

7SR242 Duobias Multi-Function 2-Winding Transformer Protection Relay 7SR242 Duobias Multi-Function 2-Winding Transformer Protection Relay Document Release History This document is issue 2010/06. The list of revisions up to and including this issue is: 2010/06 Additional

More information

e 2 TANGO -400 Overcurrent Relay K Catalogue EN

e 2 TANGO -400 Overcurrent Relay K Catalogue EN e 2 TANGO -400 Overcurrent Relay K-33.1.3 Catalogue EN We Create Ideas With Power! e 2 TANGO-400 protection relay is a solution developed by ELEKTROMETAL ENERGETYKA SA R&D department consisting of engineers

More information

2 ms arc-flash protection and feeder relay in one platform

2 ms arc-flash protection and feeder relay in one platform Feeder Protection Relay 2 ms arc-flash protection and feeder relay in one platform Directly monitor and control your system using the 5-inch, 800 480 color touchscreen display. Prevent insulation damage

More information

Content FPC 400. USER MANUAL Apr Feeder F3 Motor M4 Busbar B3 Transformer T4

Content FPC 400. USER MANUAL Apr Feeder F3 Motor M4 Busbar B3 Transformer T4 Content FPC 400 USER MANUAL Apr 2017 Feeder F3 Motor M4 Busbar B3 Transformer T4 1 USER MANUAL FPC 400-4/2017 Content Preface Copyright Copyright Iskra d.d. Ljubljana, Slovenia 2016. All rights reserved.

More information

Combined Overcurrent and Earth-fault Relay SPAJ 140 C. Product Guide

Combined Overcurrent and Earth-fault Relay SPAJ 140 C. Product Guide Combined Overcurrent and Earth-fault Product Guide Issued: April 1999 Status: Updated Version: C/18.04.2006 Data subject to change without notice Features Three-phase, low-set phase overcurrent unit with

More information

Content REF615 Technical Presentation

Content REF615 Technical Presentation Distribution Automation Relion 615 series Feeder Protection and Control Ver. 2.0 Technical Presentation March 30, 2010 1MRS756407 E Slide 1 Content Technical Presentation highlights March 30, 2010 Slide

More information

Relion 615 series Feeder Protection and Control REF615 Ver. 2.0 Technical Presentation

Relion 615 series Feeder Protection and Control REF615 Ver. 2.0 Technical Presentation Relion 615 series Feeder Protection and Control REF615 Ver. 2.0 Technical Presentation Distribution Automation May 13, 2010 1MRS756407 E Slide 1 Content REF615 Technical Presentation highlights May 13,

More information

g Energy Multilin Voltage Regulator Controller DGCV KEy BENEFITS APPLICATIONS FEATURES Metering & Monitoring Voltage Regulation Communications

g Energy Multilin Voltage Regulator Controller DGCV KEy BENEFITS APPLICATIONS FEATURES Metering & Monitoring Voltage Regulation Communications Multilin Voltage Regulator DGCV KEy BENEFITS Increases grid efficiency by optimizing voltage regulation Through deployment of the Volt/VAR system, the Multilin DGCV: - Enables up to a 6% reduction in energy

More information

DRTS 33. The new generation of advanced test equipments for Relays, Energy meters, Transducers and Power quality meters

DRTS 33. The new generation of advanced test equipments for Relays, Energy meters, Transducers and Power quality meters The new generation of advanced test equipments for Relays, Energy meters, Transducers and Power quality meters Testing all relay technologies: electromechanical, solid state, numerical and IEC61850 Manual

More information

Content FPC 200. USER MANUAL Mar Feeder F1 and F3 Motor M1 and M3 Busbar B2 and B3 Transformer T1 and T3

Content FPC 200. USER MANUAL Mar Feeder F1 and F3 Motor M1 and M3 Busbar B2 and B3 Transformer T1 and T3 Content FPC 200 USER MANUAL Mar 2017 Feeder F1 and F3 Motor M1 and M3 Busbar B2 and B3 Transformer T1 and T3 1 USER MANUAL FPC 200-3/2017 Content Preface Copyright Copyright Iskra d.d. Ljubljana, Slovenia

More information

TFS 2100 Traveling Wave Fault Location System

TFS 2100 Traveling Wave Fault Location System Traveling Wave Fault Location System The most accurate overhead transmission and distribution line fault locator Accuracy: ±150m typical regardless the line length Unaffected by fault resistance Suitable

More information

Metering Devices, Protective Relays, Software and Connectivity. Pre-Wired Control Power, Voltage and CT Inputs

Metering Devices, Protective Relays, Software and Connectivity. Pre-Wired Control Power, Voltage and CT Inputs .3 Features and Benefits Saves installation time and cost One part number to order; no need to worry that any part has been left out Pick the meter or meters you need as it is designed to fit various Eaton

More information

MiCOM P521. Fast feeder differential protection

MiCOM P521. Fast feeder differential protection 01 Fast feeder differential protection The relay provides high-speed two-ended current differential unit protection of overhead lines and underground cables in applications such as ring mains and parallel

More information

www. ElectricalPartManuals. com Protective Relays HIGHLIGHTS PROTECTIVE FUNCTIONS ixp-420 Transformer Protection Relay

www. ElectricalPartManuals. com Protective Relays HIGHLIGHTS PROTECTIVE FUNCTIONS ixp-420 Transformer Protection Relay Protective Relays Electrical Apparatus ixp-420 Transformer Protection Relay 165-420 Figure 1: Edison Idea Relay The ixp-420 is a member of Cooper Power Systems Edison Idea line of protective relays. The

More information

GPM500 Generator Protection Module

GPM500 Generator Protection Module GPM500 Generator Protection Module Generator Protection Module GPM500 The microprocessor based Generator Protection System GPM500 performs the protection and control of medium and low voltage generators

More information

Using the Bitronics 70 Series to Improve Local Monitoring and Control

Using the Bitronics 70 Series to Improve Local Monitoring and Control Automate a Substation and Preserve the Electromechanical Relay Investment Part Two of Four Using the Bitronics 70 Series to Improve Local Monitoring and Control Paul Grabowski - Bitronics Senior Application

More information

Mehta Tech, Inc. TRANSCAN IED For Multi-Function, Multi-Speed Recording

Mehta Tech, Inc. TRANSCAN IED For Multi-Function, Multi-Speed Recording Mehta Tech, Inc. TRANSCAN IED For Multi-Function, Multi-Speed Recording Two independent, simultaneously operating recorders in one package Triggering on input quantities and calculated values, such as

More information

Relion 615 series Line Differential Protection and Control RED615 Ver. 2.0 Technical Presentation

Relion 615 series Line Differential Protection and Control RED615 Ver. 2.0 Technical Presentation Relion 615 series Line Differential Protection and Control RED615 Ver. 2.0 Technical Presentation ABB Oy Distribution Automation July 1, 2009 1MRS756504 B Slide 1 Contents RED615 Technical Presentation

More information

DRTS 33. The new generation of advanced three phase relay test set

DRTS 33. The new generation of advanced three phase relay test set The new generation of advanced three phase relay test set Testing all relay technologies: electromechanical, solid state, numerical and IEC61850 Local control with color display Simultaneously available:

More information

7SR21 Non-Directional 7SR22 Directional Overcurrent Relay

7SR21 Non-Directional 7SR22 Directional Overcurrent Relay 7SR21 Non-Directional 7SR22 Directional Overcurrent Relay Document Release History This document is issue 2010/05. The list of revisions up to and including this issue is: 2010/05 Additional Comms module

More information

MiCOM P521. Fast Feeder Differential Protection

MiCOM P521. Fast Feeder Differential Protection 01 Fast Feeder Differential Protection The relay provides high-speed two-ended current differential unit protection of overhead lines and underground cables in applications such as ring mains and parallel

More information

Products Portfolio. Pole mounted Vacuum Recloser

Products Portfolio. Pole mounted Vacuum Recloser Products Portfolio Pole mounted Vacuum Recloser Efacec Switchgear Efacec Switchgear is a leading company in Portugal and a worldwide reference in the development of solutions for power generation, transmission,

More information

DRTS 64. The new generation of advanced test equipment for Relays, Energy meters, Transducers and Power quality meters.

DRTS 64. The new generation of advanced test equipment for Relays, Energy meters, Transducers and Power quality meters. The new generation of advanced test equipment for Relays, Energy meters, Transducers and Power quality meters Testing all relay technologies: electromechanical, solid state, numerical and IEC61850 Manual

More information

ATV930U30M3 variable speed drive - ATV930-3kW - 200/240Vwith braking unit - IP21

ATV930U30M3 variable speed drive - ATV930-3kW - 200/240Vwith braking unit - IP21 Characteristics variable speed drive - ATV930-3kW - 200/240Vwith braking unit - IP21 Main Range of product Product or component type Device application Device short name Variant Product destination Mounting

More information

BF

BF BE1-11i INTERTIE PROTECTION SYSTEM DEVICE FUNCTIONS The BE1-11i Intertie Protection System is a multifunction numeric relay providing the protection and control requirements outlined in IEEE 1547-2003

More information

ATV12HU22M3 variable speed drive ATV12-2.2kW - 3hp V - 3ph - with heat sink

ATV12HU22M3 variable speed drive ATV12-2.2kW - 3hp V - 3ph - with heat sink Characteristics variable speed drive ATV12-2.2kW - 3hp - 200..240V - 3ph - with heat sink Main Range of product Altivar 12 Product or component type Product destination Product specific application Assembly

More information

ATV12P075M3 variable speed drive ATV kW - 1hp V - 3ph - on base plate

ATV12P075M3 variable speed drive ATV kW - 1hp V - 3ph - on base plate Characteristics variable speed drive ATV12-0.75kW - 1hp - 200..240V - 3ph - on base plate Main Range of product Altivar 12 Product or component type Product destination Product specific application Assembly

More information

SYMAP R Plug in Variants FI, MI, 87M, TI Technical data

SYMAP R Plug in Variants FI, MI, 87M, TI Technical data SYMAP R Plug in Variants FI, MI, 87M, TI Technical data 1 Product overview SYMAP R (Retrofit) is a digital protection relay for use in medium and high-voltage power systems. Because of its integrated protection

More information

VAMP 50 series. with native IEC and arc flash protection

VAMP 50 series. with native IEC and arc flash protection VAMP 50 series with native EC 61850 and arc flash protection V VAMP 50 series protection relays VAMP 50 family low and mid range relay series with EC 61850 The VAMP 50 series protection relay family is

More information

Numerical motor protection in medium voltage networks Motor Protection and Control REM620

Numerical motor protection in medium voltage networks Motor Protection and Control REM620 Guideform Specification 1MRS758530 A Numerical motor protection in medium voltage networks Motor Protection and Control REM620 The configurable motor management relay is intended for protection, control,

More information

ABB Inc. Substation Automation and Protection Division Coral Springs, FL Allentown, PA. Multi-Zoned Distance

ABB Inc. Substation Automation and Protection Division Coral Springs, FL Allentown, PA. Multi-Zoned Distance ABB ABB Inc. Substation Automation and Protection Division Coral Springs, FL Allentown, PA Descriptive Bulletin September 21 Multi-Zoned Distance Device umber:21/21, 21B, 21P/21P, 2, 27, /, BF, 1/1, Q/1Q,

More information

Data Sheet. Digital Multifunctional Power Meter with LCD Display and Optional Modules WPM D

Data Sheet. Digital Multifunctional Power Meter with LCD Display and Optional Modules WPM D WPM 770 Data Sheet 679.D.141.02 Digital Multifunctional Power Meter with LCD Display and Application The digital Weigel Power Meters WPM 770 have been designed to display the electrical parameters in low

More information

SIPROTEC 4 7SD61 Differential Protection Relay for Two Line Ends

SIPROTEC 4 7SD61 Differential Protection Relay for Two Line Ends Line Differential Protection / SD61 SIPROTEC 4 SD61 Differential Protection Relay for Two Line Ends Description The SD610 relay is a differential protection relay suitable for all types of applications

More information

SACE Emax 2 Specification guide

SACE Emax 2 Specification guide SACE Emax 2 Specification guide Specification Number: 26 01 20.17 Product Name: LOW VOLTAGE POWER CIRCUIT BREAKERS PART 1 GENERAL NOTE: ( ) Indicates option or a selection is to be made for quantity or

More information

Maximize process uptime with the SEL-patented motor thermal model.

Maximize process uptime with the SEL-patented motor thermal model. SEL-710 Motor Protection Relay Maximize process uptime with the SEL-patented motor thermal model. Optimize motor performance with separate thermal models for the stator and rotor. Monitor stator and ambient

More information

Protection, Monitoring, and Control System for Distribution Substations ALARM HISTORY SYSTEM COMM. On-Line Documentation TRANSFORMER 12 MW

Protection, Monitoring, and Control System for Distribution Substations ALARM HISTORY SYSTEM COMM. On-Line Documentation TRANSFORMER 12 MW SEL Distribution Substation Protection and Automation System Protection, Monitoring, and Control System for Distribution Substations Data Sheet SYSTEM ONE-LINE RELAY TARGETS ALARM HISTORY SYSTEM COMM.

More information

THE INTEGRATED TESTING SOLUTION

THE INTEGRATED TESTING SOLUTION Test & Data Management Software TDMS protective relays energy meters transducers power quality CT-VT-PT transformers ground grid circuit breakers batteries surge arresters THE INTEGRATED TESTING SOLUTION

More information

750/760 Feeder Management Relay

750/760 Feeder Management Relay g GE Industrial Systems 750/760 Feeder Management Relay Instruction Manual Firmware Rev: 5.X Manual P/N: 1601-0044-AP (GEK-106293D) Copyright 2006 GE Multilin 760 STATUS SYSTEM STATUS OUTPUT STATUS RELAY

More information