MPR 10. Digital Motor Protection Relay. P&B Engineering Belle Vue Works Boundary Street Manchester M12 5NG

Size: px
Start display at page:

Download "MPR 10. Digital Motor Protection Relay. P&B Engineering Belle Vue Works Boundary Street Manchester M12 5NG"

Transcription

1 MPR 10 Digital Motor Protection Relay P&B Engineering Belle Vue Works Boundary Street Manchester M12 5NG Tel: Fax:

2 Issue 3 8/10/98 Contents 1. INTRODUCTI APPLICATI FEATURES AND CHARACTERISTICS DESIGN CIRCUIT DIAGRAM Analogue Input Circuits Output Relays FRT PANEL Fault Indication REMOTE DATA COMMUNICATI FRT PANEL CIRCUIT DIAGRAM MOUNTING INFORMATI SERIAL NUMBER WORKING PRINCIPLES ANALOGUE CIRCUITS DIGITAL CIRCUITS POWER SUPPLY REQUIREMENTS FOR THE MAIN CURRENT TRANSFORMERS... 9 CT CLASS 3, 2.5VA OPERATI AND SETTING LAYOUT OF THE CTROL ELEMENTS SETTING PROCEDURE Overload Pre-Trip Alarm Earth Fault Current (Ie) Locked Rotor ( Stall ) Protection Undercurrent Setting (Iu) Negative Phase Sequence Protection Reset Full Load Current Setting (Iflc) t6x Setting Normal/Factory Mode OVERCURRENT TRIP INHIBIT SETTING VALUE CALCULATI RELAY CASE TEST AND MAINTENANCE TECHNICAL DATA MEASURING INPUT CIRCUITS AUXILIARY POWER SUPPLY SETTING RANGES AND STEPS THERMAL CURRENT / TIME CURVES OUTPUT CTACT RATINGS SYSTEM DATA HOUSING PUBLICATI CHANGES ORDER FORM

3 1. Introduction. The application of powerful microprocessors opens a new chapter for power system protective relaying. The digital processing of measured values and the ability to perform complex arithmetic and logic operations, give digital protection relays significant performance and flexibility improvements over their traditional analogue counterparts. Additional advantages - very small power consumption, adaptability, self-supervision, fault diagnosis through fault data recording, smaller physical construction and selectable relay characteristics - all combine to allow the implementation of accurate and highly reliable protection schemes at a significantly reduced financial burden. The development of microprocessor based protective relays and their introduction into the market has been stimulated by the recent trend to replace analogue with digital equipment. This modern trend has prompted the development of a new P&B protective relay family - the MR relay series. This comprehensive family of protection relays can satisfy the demands of even the most complex protection schemes: MRI - Overcurrent Relay (Independent time/i.d.m.t + earth + directional facilities) MRI-V - Voltage Dependent Overcurrent Relay MREF - Restricted Earth Fault Relay MRMF - Mains Failure Relay MRNS - Negative Sequence Relay MRRP - Power Relay MRCS - Check Synchronising Relay MRFF - Field Failure Relay The superiority of digital protective relaying over traditional analogue devices, as embodied by the MR relay family, is summarised by the following features: Integration of many protective functions in a single compact case High accuracy owing to digital processing Digital relay setting with very wide setting ranges and fine setting steps Comfortable setting procedure through extensive human - relay dialogue Measured values and fault data indication by means of alpha-numeric display Data exchange with DCS/SCADA by means of RS485 Operational reliability through self-supervision A similar but simplified range, with reduced functions and without display, is also available. The MIRI - overcurrent and earth fault relays, and the MIRV - undervoltage, overvoltage and neutral voltage displacement relays. To complement the MR series, a range of Auxiliary, Timing and Tripping devices are also available. The MPR range of motor protection relays embodies the developments in technology of the MRI, and MIRI as well as previous electronic motor protection relays, with the traditional knowledge and expertise developed over the long tradition of motor protection within P & B Engineering. Issue 3 8/10/98 Page 1 MPR10

4 2. Application. The MPR 10 is a universal digital adjustable motor protection relay. It serves as overload, negative phase sequence (unbalance), and general protection for synchronous and induction machines. With a large selection of adjustment possibilities, the MPR 10 is suitable for almost any type of machine. The protective functions of the MPR 10 are summarised as follows: Thermal overload protection with adjustable current/time curves. Thermal Overload prior alarm with separate output relay Locked rotor and stall protection. (definite time). Earth fault protection (definite time). Negative phase sequence protection (inverse time). Undercurrent protection (definite time). Setting and measured parameters available via RS485 serial link. 3. Features And Characteristics. High accuracy. Wide setting range. Universal power supply AC or DC. Selectable auto / manual reset of the output relays. Hot/cold thermal current/times with thermal memory and trip times dependent on prior loading. Locked rotor protection set at 3.5 times I FLC after the start time. Setting via front panel switches and potentiometers. Test functions activated with front panel push button. Complete digital processing of the sampled measured values Continuous self-supervision of software and hardware Setting Values and Measured Data are available via optional RS485 serial link. Din rail modules for back of panel mounting, allowing a considerable saving in front panel space. Issue 3 8/10/98 Page 2 MPR10

5 4. Design Circuit Diagram. L1 L2 L3 Supply A2 A1 P2 S2 1S1 P1 S1 1S2 2S1 2S2 3S1 3S2 I1 I2 IE POWER SUPPLY TRIP ALARM MPR Typical earthing shown. Diagram 1 Relay with two line current transformers and a core balance current transformer. L1 L2 L3 Supply A2 A1 P2 S2 1S1 P1 S1 1S2 2S1 2S2 3S1 3S2 I1 I2 IE POWER SUPPLY TRIP ALARM MPR Diagram 2 Relay with three line current transformers residually connected to provide earth fault and NPS protection. Issue 3 8/10/98 Page 3 MPR10

6 Analogue Input Circuits. The constantly monitored measuring values are galvanically decoupled, filtered and finally fed to the analogue/digital converter. The protection unit receives these analogue input signals of the phase currents I1 & I2 and Earth fault IE, via separate input transformers Output Relays. The MPR 10 has two output relays, with single pole change-over contacts as detailed in the previous diagram and summarised below: Tripping relay Alarm relay The trip relay is energised for ' trip' and de-energised for 'no trip'. The alarm relay is energised for 'no alarm' and de-energised for 'alarm'. Its action is the inverse of the trip relay to allow flexibility in plant wiring schemes. The trip relay will operate for 1 second if the test button is pressed Front Panel. The front panel of the MPR 10 comprises the following operation and indication elements: 8 Dip switches for selection of protection options. 6 Rotary switches for setting of parameters. 3 LEDs for indication. 1 Push button for reset and test functions. Issue 3 8/10/98 Page 4 MPR10

7 Fault Indication. When the relay alarms or trips the LEDS on the front panel will flash indicating the type of fault the relay is seeing, as shown in Diagram 3 below. The LED flashes a certain number of times very quickly, pauses then repeats the process. The LED will carry on indicating the fault until it has been cleared. For example the Trip LED flashing four times indicates that there is an unbalance fault on the relay. This then enables the user to clear the fault that is causing the trip. FUNCTI TRIP LED OVERLOAD LED LED THERMAL PICKUP OVERLOAD PRE-ALARM OVERLOAD TRIP WHEN MANUAL RESET POSSIBLE STALL PROTECTI EARTH FAULT UNDERLOAD UNBALANCE SHORT CIRCUIT INTERNAL FAULT Diagram 3 Tripping And Alarm Indications. Issue 3 8/10/98 Page 5 MPR10

8 5. Remote Data Communication. As an option, the MPR 10 may have a separate RS485 interface for remote data communication with a control centre. This then enables the user to view many of the parameters of the relay as well as well as assigning new values to the parameter. Auxilliary supply to the unit is in the range 19-55v DC only. For more information on the communications of an MPR10 contact P&B Engineering on Tel: The unit, which must be mounted adjacent to the protection relay, provides the following information: Status signals Self supervision alarm signal Actual measured values Relay settings Fault signalling 5.1. Front Panel. The front panel of the communications unit shows the following data: 2 LEDs displaying power status and communication activity A1 PE A2 A1 PE A2 RS XRS1 RS RS N G P N G P 1 Jumper to switch or the communication facilities of the unit Circuit Diagram. -ve Gnd +ve Input Supply 19-55v DC L- L+ P G N PE PE A1 A2 POWER SUPPLY A2 A1 L+ Output Supply 19-55v DC L- N G -ve Gnd +ve P MPR 10 COMMUNICATI UNIT Issue 3 8/10/98 Page 6 MPR10

9 5.3. Mounting Information. The Communications Unit is mounted next to the MPR10 as shown below. Also shown are the dimensions of the Unit A1 PE A2 A1 PE A2 RS XRS1 RS RS N G P N G P Positioning Of Communications Unit. 110 Din rail mounting: Top Hat Profile to BS5584:1978 (EN , DIN ) A1 PE A2 A1 PE A2 RS XRS1 RS RS N G P N G P 1S1 1S2 2S1 2S2 3S1 3S2 A1 TEST I> I>> I> In I>> In ti> ti>> A All dimensions are approximate and in mm 5.4. Serial Number. To set the serial number follow the procedure below. i) Set dip switch 8 to on and dip switch 7 to off. ii) Set dips 1 through 5 to the required comms ID. (0 = off, 1-31 = comms id). iii) Power up the unit. iv) Press the test/reset button. v) The alarm and overload LEDs will flash momentarily. vi) Power off the unit and reset the dip switches to their previous settings. Issue 3 8/10/98 Page 7 MPR10

10 6. Working Principles Analogue Circuits. The incoming currents and voltages from the external transformers are converted to internal signals in proportion to the current, via the internal input transducers and shunt resistors. The noise signals caused by inductive and capacitive coupling are suppressed by an analogue filter circuit. The analogue signals are fed to the A/D converter of the micro-processor and transformed to digital signals through sample-hold circuits. The analogue signals are sampled at a rate of 470Hz giving a sample time of 2.13mS for each measured value Digital Circuits. The essential component of the MPR 10 relay is a powerful micro-processor. All of the operations, from the analogue digital conversion to the relay trip decision, are carried out by the microprocessor. The relay has a thermal memory which operates using an I 2 t characteristic and a fixed hot / cold ratio of 50%. A motor running at FLC (Full Load Current - Iflc) in the steady state achieves a thermal capacity of 45%. At operating currents above 105% the relay will trip in a time proportional to current. That is a trip occurs at a thermal capacity of 100%. The thermal characteristics are adjustable through the potentiometer setting t6x. which is the time, in seconds, for the relay to trip at six times FLC (Iflc). The thermal current/time functions of the relay have the following special features:- 1. The change in thermal capacity during a start is stored and a reset after a trip is only allowed if there is this much capacity available. For example if during a start the thermal capacity rises from 75% to 95% a required start capacity of 20% is stored. After an overload trip the relay will not reset until the thermal capacity has dropped to less than (100%-20%) = 80%. To allow faster restarts there is a maximum value of 50% for the stored change in thermal capacity. 2. After a motor has tripped on thermal overload the thermal capacity available in the relay for a restart is increased at a rate according to the cooling time constant of the relay. The motor cannot be restarted until there is sufficient capacity, as above, available. 3. If the motor is started from cold and then stopped, an immediate restart would only be possible if there was sufficient thermal capacity available within the relay. The thermal capacity is retained even when the auxiliary supply is disconnected. Under special circumstances it is possible to 'defeat' this mechanism, that is reset the thermal capacity to zero, by holding the test button down as the auxiliary supply is applied. 4. There is a pre-trip alarm relay output available and may be switched on or off using the relay front panel setting switch (dip switch 1). The alarm output is set at 95% thermal capacity. The alarm is self reset, that is when the thermal capacity rises above 95% the alarm is switched on and when the thermal capacity drops below 95% the alarm is switched off. 5. On power up the thermal model is initialised to the value it had just prior to removal of the auxiliary supply. 6. The overload LED fitted to the front panel of the unit will be illuminated when the motor current is greater than 105% of FLC. This LED will also be illuminated when a thermal overload trip has occurred. Issue 3 8/10/98 Page 8 MPR10

11 6.3. Power Supply. The MPR10 needs a seperate auxiliary supply voltage. The relay has an integrated wide range power supply with voltage in the range:- Vaux = v AC Vaux = v DC The voltage does not need to be set Requirements For The Main Current Transformers. In order to ensure the correct operation of the MPR 10 range of relays, protection class CT's must be utilised. Instrument CT's are generally NOT a suitable alternative. CT's should be chosen such that saturation, or loss of accuracy does not occur within the settings and operation ranges of the relays. In the absence of known settings the following may be regarded as an approximate guide. For 1A secondary CT class 5P10 or 10P10 2.5VA (Allowing for up to 1.5Ω of secondary lead resistance) For 5A secondary CT class 5P10 or 10P10 2.5VA (Allowing for up to 0.8Ω of secondary lead resistance) with due regard to a suitable CT ratio and fault level capacity. For Core Balance CT (CBCT) CT class 3, 2.5VA 7. Operation And Setting Layout Of The Control Elements. All control elements required for the operation and adjustment of the MPR 10 are located on the front panel. They are divided according to function into the two following groups: DIP SWITCHES: Selection of the protection functions to be utilised. These are detailed in the table below: Normal operation dip switch functions. DIP Switch Function 1 Overload pre trip alarm ( / ). 2 Earth fault and locked rotor protection ( / ). 3 Undercurrent protection ( / ). 4 NPS protection ( / ). 5 Contactor ()/ Circuit breaker () feeder selection. 6 Overload reset auto () / man (). 7 Earth fault, nps and locked rotor reset auto () / man (). 8 Normal Operation () Issue 3 8/10/98 Page 9 MPR10

12 ROTARY SWITCHES: Individual setting of trip levels or time characteristics. These are detailed in the table below: Control settings. Potentiometer Function. 1. Iflc/Inom ratio coarse six steps 0.6, 0.7, 0.8, 0.9, 1.0, Iflc/Inom ratio fine variable from 0 to t 6x time coarse six steps 0, 5, 10, 15, 20, 25 seconds. (see note) 4. t6x time fine variable from 0 to 5 seconds. 5. Iuc/Iflc ratio variable from 40% to 80%. 6. I ef/ I flc ratio variable from 10% to 50%. NOTE When the t6x setting is set at its lowest setting ( 0.0 ) the actual setting assumed by the relay is 0.5 Seconds 7.2. Setting Procedure. In the following sections the setting of all relay parameters is described in detail: Overload Pre-Trip Alarm. The pre-trip alarm relay output may be switched on or off using the relay front panel setting switch ( DIP Switch 1). The alarm output is set at 95% thermal capacity. The alarm is self reset, that is when the thermal capacity rises above 95% the alarm is switched on and when the thermal capacity drops below 95% the alarm is switched off Earth Fault Current (Ie). This setting specifies the pickup level of Earth Fault Current as a percentage of Iset. The value is set by adjusting the potentiometer on the front panel. The earth fault protection function may be switched on or off using the relay front panel setting switch (dip switch 2). The action on earth fault is to trip. The earth fault trip level setting is variable between 10% and 50% of Inom. The earth fault current is detected by the connection of the earth fault input either to a core balance current transformer or to three line current transformers residually connected. If the earth fault current rises above the set level for a time greater than the set earth fault operating time the relay will trip. The earth fault protection is automatically or manually reset as determined by dip switch 7. The earth fault trip operates in a definite time of 1 second or instantaneously as determined by dip switch 5. The earth fault trip is instantaneous when dip switch 5 is on (Circuit breaker mode) and 1 second when dip switch 5 is set to off (contactor fed mode) Locked Rotor ( Stall ) Protection. Stalling protection is available and may be switched on or off using the relay front panel setting switch ( DIP Switch 2). Stalling protection is activated by detection of the end of the start time. Stall protection is set to trip at 3.5 times I flc. The locked rotor trip operates in a definite time of 1 second. The locked rotor protection is automatically or manually reset as determined by dip switch 7. Issue 3 8/10/98 Page 10 MPR10

13 Undercurrent Setting (Iu). The undercurrent protection function may be switched on or off using the relay front panel setting switch (dip switch 3). The action on undercurrent is to alarm. The undercurrent setting is variable between 40% and 80% of the motor FLC (Iflc) via the potentiometer on the relay front panel.. If after a start the average motor current drops below the set undercurrent level for a time greater than the set undercurrent time (3 sec.) the relay will alarm. The undercurrent protection is automatically reset Negative Phase Sequence Protection. The negative phase sequence protection function may be switched on or off using the relay front panel setting switch (dip switch 4). The action on negative phase sequence is to trip. The negative phase sequence pickup point is fixed at 15% of the motor FLC (Iflc). If the negative phase sequence current rises above the pick up value the relay will trip in a time determined by the curve below. The negative phase sequence protection is inhibited for motor currents of below 0.1 times and 2 times Inom. The negative phase sequence protection is automatically or manually reset as determined by dip switch 5. Phase loss will result in a trip occurring in 1.5 seconds. Secs %NPS Reset. When the relay has tripped it may be either manually or automatically reset according to the following table. Trip Reset Switch Overload Auto/man Switch 1,6 Earth fault Auto/man Switch 1,7 Locked rotor Auto/man Switch 1,7 NPS Auto/man Switch 1,7 Alarm Reset Switch Overload Auto - Undercurrent Auto - Issue 3 8/10/98 Page 11 MPR10

14 Automatic reset. When the fault condition is no longer present, for example the thermal capacity has dropped below its reset limit, the trip relay will reset allowing a restart. Manual reset. The trip condition is latched until the relay is reset by removal and re-application of the auxiliary supply or by pressing the reset button on the front panel. Note: a manual reset can only be effected if the trip condition is no longer present. Special condition reset. To effect a premature reset of an overload trip the 'Test' push button must be held down as the auxiliary power is restored Full Load Current Setting (Iflc). Determines the normal running full load current of the machine, this is set in terms of the CT ratio, thus if the CT has a primary rating of 200:1, and the machine has a FLC of 150A, Then Iflc should be set at 150/200 = t6x Setting. This setting specifies the time taken to trip at 6 times FLC, with respect to the cold characteristic curve, and therefore determines the basic thermal characteristic Normal/Factory Mode. This setting, selectable between Normal(off) or Factory (on) by use of the relay front panel setting switch ( DIP Switch 8). The functions of this are pre set, and should not be adjusted without consultation with P&B, this should be left in the Normal ( off ) position. Issue 3 8/10/98 Page 12 MPR10

15 7.3. Overcurrent Trip Inhibit. The relay can be switched to either contactor fed or circuit breaker fed through dip switch 5. In the case of contactor fed mode the MPR 10 relay trip outputs are inhibited for phase overcurrents above 7 times Iset, this is in order to provide full co-ordination between the fuse and the contactor, to ensure the fuse clears faults in excess of the contactor breaking capacity. For earth faults a one second delay is provided integral to the unit, this normally provides sufficient time for the fuse to clear any faults, at high or medium voltage however, there are a few occasions usually where impedance earthing is used, when this is not the case. In such circumstances a full co-ordination study is almost mandatory, and the following special connections may be used. L1 L2 L3 S2 P2 1S1 Supply A1 A2 P1 S1 L1 L2 L3 P2 Rstab 1S1 1S2 2S1 2S2 3S1 3S2 I3 IE I1 POWER SUPPLY TRIP ALARM MPR P1 S1 1S2 2S1 Typical earthing shown 2S2 Alternative connections for CBCT CBCT 3S1 3S2 Special CT connections for earth fault trip inhibit above 7 x Set 7.4. Setting Value Calculation. In order to ensure that protection relays form an integral part of any system, a full protection coordination study should normally be undertaken which considers both upstream and downstream equipment. Further details may be obtained by contacting P&B Engineering. 8. Relay Case. The MPR 10 is delivered in an individual case for Din rail mounting. Issue 3 8/10/98 Page 13 MPR10

16 9. Test And Maintenance. Currents may be supplied to the input transformers to test the behaviour of the relay. By switching on test currents and measuring the tripping time, the whole system can be accurately tested. All measuring input circuits of the MPR 10 are of static design and the relay functions are fully digitised. Thus, the MPR 10 has no particular demand on maintenance. 10. Technical Data Measuring Input Circuits. Rated Data Rated current, In Rated frequency, fn 1A or 5A 40-70Hz Power Consumption Current Circuits Thermal withstand For 1A Relays Half wave for 1 second for 10 seconds In = 1 A In = 5 A VA 270A 90A 30A 10A For 5A Relays Half wave 1350A for 1 second 450A for 10 seconds 150A Continuously Auxiliary Power Supply. Supply Voltage Vaux = v DC or v AC Power Consumption Quiescent Operating Approx. 4W Approx. 6W Issue 3 8/10/98 Page 14 MPR10

17 10.3. Setting Ranges And Steps. Function Parameter Setting range Step Tolerance Thermal curve Iflc t6x x In 0.5, sec 2% 1 sec 1% of setting ±1% or ±20ms under- Iu 10-50% x Iset 10% 1% of setting current Ie Ie 10-50% x In 10% In 1% of setting Thermal Current / Time Curves. The curves shown are the time/current operating characteristics for the MPR10 Thermal Overload protection. Curve 1 :Cold Curve Curve 2 :Hot Curve Overload Setting =105% Overload Setting = 105% Running From 100% FLC Hot/Cold Ratio = 50% t Multiples of FLC Issue 3 8/10/98 Page 15 MPR10

18 10.5. Output Contact Ratings. Number of relays = 2 Contacts = 1 change over contacts for trip signal. 1 change over contact for alarm. Maximum breaking capacity 250V AC / 1500VA / continuous current 5A for DC voltage: ohmic L/R = 4ms L/R = 7ms 110 V DC 0.5 A / 55 W 0.4 A / 40 W 0.2 A / 22 W 60 V DC 0.7 A / 42 W 0.5 A / 30 W 0.3 A / 17 W 24 V DC 6 A / 144 W 4.2 A / 100 W 2.5 A / 60 W Max. rated making current: mechanical life span: electrical life span: Contact material 64A(IEC65) operating cycles operating cycles at 220 V AC / 6A Silver Cadmium Oxide (AgCdO) System Data. Design standard = IEC 255-4, BS 142 Operating temperature range = 0 C to 70 C Storage temperature range = -25 C to 70 C Test Voltages to EN , EN Isolation Test = 2.5kV / 50Hz / 1 min. Impulse Test = 5kV, 1.2 / 50mS, 0.5J High frequency interference Test= 2.5kV / 1MHz Burst transient Test = 4kV / 2.5KHz, 15mS ESD Test = 8kV RFI Suppression Test = 10V/m, MHz, 1 Octave/ 3 min. EMI Suppression Test = 10V/m Mechanical Tests: Shock = IEC 41B (CO) 38, Class 1 Vibration = IEC 41B (CO) 35, Class 1 Degree of Protection = IP54 Weight = Approx. 250g. Issue 3 8/10/98 Page 16 MPR10

19 10.7. Housing. MPR 10 units are supplied in standard cases, Suitable for direct mounting on Din rail complying with BS-5584:1978. ( Top hat section ). All the terminals are situated at the top and bottom of the relay front panel, the screw terminals can accept one or two wires of up to 2.5mm 2. The unit may be sealed to prevent unauthorised adjustment, by passing a wire through the small loops moulded in the front facia, and crimping with a seal. 1S1 1S2 2S1 2S2 3S1 3S2 A1 TEST I> I>> I> In I>> In ti> ti>> A Din rail mounting: Top Hat Profile to BS5584:1978 (EN , DIN ) All dimensions are approximate and in mm Publication Changes. Form Issue 2 The auxilliary input to the MPR10 and its communication module has changed. From Issue 1 The use of a portable test case for the testing of a MPR10 is no longer required. All information subject to change without notice Publication number:- Issue 3 8/10/98 Issue 3 8/10/98 Page 17 MPR10

20 11. Order Form. QUANTITY MPR 10 Rated current 1A 1 5A 5 Optional Communication Module C PBSI Ltd Trading as P&B ENGINEERING Bell Vue Works, Boundary Street, Manchester. M12 5NG. Tel: Fax: Issue 3 8/10/98 Page 18 MPR10

MRI-V. Digital Multifunctional Relay for Voltage Controlled Overcurrent Protection. P&B Engineering Belle Vue Works Boundary Street Manchester M12 5NG

MRI-V. Digital Multifunctional Relay for Voltage Controlled Overcurrent Protection. P&B Engineering Belle Vue Works Boundary Street Manchester M12 5NG MRI-V Digital Multifunctional Relay for Voltage Controlled Overcurrent Protection P&B Engineering Belle Vue Works Boundary Street Manchester M12 5NG Tel: 0161 230 6363 Fax: 0161 230 6464 2/5/96 0 MRI-V

More information

XE2 DC current relay for loss of excitation protection. Manual XE2 (Revision A)

XE2 DC current relay for loss of excitation protection. Manual XE2 (Revision A) XE2 DC current relay for loss of excitation protection Manual XE2 (Revision A) Woodward Manual XE2 GB Woodward Governor Company reserves the right to update any portion of this publication at any time.

More information

XU1-E Earth fault voltage relay. (August 1996) Manual XU1-E (Revision New)

XU1-E Earth fault voltage relay. (August 1996) Manual XU1-E (Revision New) XU1-E Earth fault voltage relay (August 1996) Manual XU1-E (Revision New) Woodward Manual XU1-E GB Woodward Governor Company reserves the right to update any portion of this publication at any time. Information

More information

MRRP. Digital Reverse Power Relay. P&B Engineering Belle Vue Works Boundary Street Manchester M12 5NG Tel: Fax:

MRRP. Digital Reverse Power Relay. P&B Engineering Belle Vue Works Boundary Street Manchester M12 5NG Tel: Fax: MRRP Digital Reverse Power Relay P&B Engineering Belle Vue Works Boundary Street Manchester M12 5NG Tel: 0161 230 6363 Fax: 0161 230 6464 Contents CONTENTS... I 1. INTRODUCTION... 1 2. APPLICATIONS...

More information

High-Tech Range IRI1-ES- Sensitive Earth Fault Current Relay

High-Tech Range IRI1-ES- Sensitive Earth Fault Current Relay High-Tech Range IRI1-ES- Sensitive Earth Fault Current Relay IE ON RESET.5 X1 t IE X1.6%.2.4.8 1.6 X1.1s.2.4.8 1.6 X2 OFF ON S1 S2 IRI1-ES IRI1-ES C&S Electric Limited (Protection & Control Division) Contents

More information

IRI1-ES Sensitive Earth Fault Current Relay. Manual IRI1-ES (Revision A)

IRI1-ES Sensitive Earth Fault Current Relay. Manual IRI1-ES (Revision A) IRI1-ES Sensitive Earth Fault Current Relay Manual IRI1-ES (Revision A) Woodward Manual IRI1-ES GB Woodward Governor Company reserves the right to update any portion of this publication at any time. Information

More information

XU1-DC DC voltage relay. (June 1998) Manual XU1-DC (Revision New)

XU1-DC DC voltage relay. (June 1998) Manual XU1-DC (Revision New) XU1-DC DC voltage relay (June 1998) Manual XU1-DC (Revision New) Woodward Manual XU1-DC GB Woodward Governor Company reserves the right to update any portion of this publication at any time. Information

More information

Earth-fault Relay SPAJ 110 C. Product Guide

Earth-fault Relay SPAJ 110 C. Product Guide Issued: April 1999 Status: Updated Version: C/12.04.2006 Data subject to change without notice Features Low-set neutral overcurrent stage with definite time or inverse time characteristic High-set neutral

More information

DGSZV-EP DIGITAL GALVANIC LONGITUDINAL DIFFERENTIAL PROTECTION. Application field

DGSZV-EP DIGITAL GALVANIC LONGITUDINAL DIFFERENTIAL PROTECTION. Application field DGSZV-EP DIGITAL GALVANIC LONGITUDINAL DIFFERENTIAL PROTECTION The digital galvanic longitudinal differential protection of type DGSZV-EP is part of device family named EuroProt. This short description

More information

Combined Overcurrent and Earth-fault Relay SPAJ 140 C. Product Guide

Combined Overcurrent and Earth-fault Relay SPAJ 140 C. Product Guide Combined Overcurrent and Earth-fault Product Guide Issued: April 1999 Status: Updated Version: C/18.04.2006 Data subject to change without notice Features Three-phase, low-set phase overcurrent unit with

More information

XG2 Generator-/Mains Monitor. Manual XG2 (Revision A)

XG2 Generator-/Mains Monitor. Manual XG2 (Revision A) XG2 Generator-/Mains Monitor Manual XG2 (Revision A) Woodward Manual XG2 GB Woodward Governor Company reserves the right to update any portion of this publication at any time. Information provided by Woodward

More information

Combined Overcurrent and Earth-fault Relay SPAJ 141 C. Product Guide

Combined Overcurrent and Earth-fault Relay SPAJ 141 C. Product Guide Combined Overcurrent and Earth-fault Product Guide Issued: April 1999 Status: Updated Version: C/19.04.2006 Data subject to change without notice Features Three-phase, low-set phase overcurrent unit with

More information

Sensitive Earth-fault Relay SPAJ 111 C. Product Guide

Sensitive Earth-fault Relay SPAJ 111 C. Product Guide Issued: April 1999 Status: Update Version: C/12.04.2006 Data subject to change without notice Features Sensitive low-set neutral overcurrent stage with definite time characteristic High-set neutral overcurrent

More information

Feeder protection relay SPAA 121 C. Product Guide

Feeder protection relay SPAA 121 C. Product Guide Issued: April 1999 Status: Updated Version: C/06.03.2006 Data subject to change without notice Features Two-phase low-set phase overcurrent unit with definite time or inverse time characteristic Two-phase

More information

2C138. Sensitive Earth Fault Relay. Features. Application. Operation

2C138. Sensitive Earth Fault Relay. Features. Application. Operation Technical Bulletin 2C138 Sensitive Earth Fault Relay Features High sensitivity (0.1% of I n ) 2 nd & 3rd harmonic & HF noise suppression - tuned to 50 Hz Optional reset functions Instantaneous (Fast),

More information

Sensitive definite time or inverse time earth-fault stage for back-up residual earthfault

Sensitive definite time or inverse time earth-fault stage for back-up residual earthfault Issued: April 1999 Status: Updated Version: B/09.11.2001 Data subject to change without notice Features Sensitive restricted earth-fault protection stage for fast, selective earth-fault protection Sensitive

More information

Residual overvoltage relay

Residual overvoltage relay Page 1 Issued: April 1999 Status: New Data subject to change without notice Features Definite-time residual overvoltage earthfault protection and supervision Two independent operation stages, e.g. one

More information

INTRODUCTION. The PL-50 MO and PM-250 families represent the. PM-250-H: Horizontal box. PM-250-V: Vertical box

INTRODUCTION. The PL-50 MO and PM-250 families represent the. PM-250-H: Horizontal box. PM-250-V: Vertical box INTRODUCTION The PL-50 MO units are available in the next mechanical version: The PL-50 MO and PM-250 families represent the different solutions that Team Arteche offers for motor protection. Both families

More information

Electronic timer CT-AHS OFF-delayed with 2 c/o contacts Data sheet

Electronic timer CT-AHS OFF-delayed with 2 c/o contacts Data sheet 2CDC 251 113 F0004 CT-AHS 1 7 2 6 5 4 8 3 1 10 selectable time ranges, from 0.05 s to 300 h 2 Potentiometer with direct reading scale for the fine adjustment of the time delay 3 Sliding switch to set the

More information

SYMAP R Plug in Variants FI, MI, 87M, TI Technical data

SYMAP R Plug in Variants FI, MI, 87M, TI Technical data SYMAP R Plug in Variants FI, MI, 87M, TI Technical data 1 Product overview SYMAP R (Retrofit) is a digital protection relay for use in medium and high-voltage power systems. Because of its integrated protection

More information

C C CIRCUIT-BREAKERS Moulded-case (MCCB), general. 1. Introduction. 2. General description

C C CIRCUIT-BREAKERS Moulded-case (MCCB), general. 1. Introduction. 2. General description CIRCUIT-BREAKERS C C81-21 CIRCUIT-BREAKERS - Contents 1. Introduction 2. General description 3. Rated voltages 3.1 Rated operational voltage (U e ) 3.2 Rated impulse withstand voltage (U imp ) 3.3 Rated

More information

1S20. Arc Fault Monitor Relay. Features. Introduction. ARC Fault Protection

1S20. Arc Fault Monitor Relay. Features. Introduction. ARC Fault Protection Technical Bulletin Arc Fault Monitor Relay Features Compact, economic design Simple panel mounting for retrofit applications Two or three arc sensor inputs Two high speed tripping duty arc sense output

More information

Phase loss monitor CM-PBE Phasemonitor for over and undervoltage CM-PVE Ordering details

Phase loss monitor CM-PBE Phasemonitor for over and undervoltage CM-PVE Ordering details Phase loss monitor CM-PBE Phasemonitor for over and undervoltage CM-PVE 1SVR 550 882 F 9500 CM-PBE Yellow LED - state of relay voltage and single-phase supply voltage for phase failure Monitoring of neutral

More information

3 Pole Contactors with AC operating coils

3 Pole Contactors with AC operating coils 1 3 Pole Contactors with AC operating coils Characteristics General Characteristics Switching Current 9A ~ Rated insulation voltage (Ui) (Conforming to IEC 158-1) V 750 IEC 60947-4 V 1000 Conforming to

More information

Feeder protection relay

Feeder protection relay Page 1 Issued: April 1999 Status: New Data subject to change without notice Features Comprehensive numerical feeder protection relay consisting of two multi-function protection relay modules and a flexible

More information

Section 4 Ground-Fault Protection Devices

Section 4 Ground-Fault Protection Devices Multi 9 System Catalog Section 4Ground-Fault Protection Devices Section 4Ground-Fault Protection Devices Selection Table The Multi 9 System includes one UL Listed and three IEC rated product families that

More information

Feeder protection relay SPAA 341 C. Product Guide

Feeder protection relay SPAA 341 C. Product Guide Issued: April 1999 Status: Updated Version: D/07.03.2006 Data subject to change without notice Features Comprehensive numerical feeder protection relay consisting of two multi-function protection relay

More information

Electronic timer CT-EAS ON-delayed and OFF-delayed with 1 c/o contact Data sheet

Electronic timer CT-EAS ON-delayed and OFF-delayed with 1 c/o contact Data sheet 2CDC 251 116 F0004 1 5 2 4 3 6 Characteristics Single-function ON-delay and OFF-delay timer One device includes 10 time ranges, from 0.05 s to 300 h, for the adjustment of the time delay Remote potentiometer

More information

BN1-400 Mains decoupling relay. (February 2000) Manual BN1-400 (Revision New)

BN1-400 Mains decoupling relay. (February 2000) Manual BN1-400 (Revision New) BN1-400 Mains decoupling relay (February 2000) Manual BN1-400 (Revision New) Woodward Manual BN1-400 GB Woodward Governor Company reserves the right to update any portion of this publication at any time.

More information

SIPROTEC easy 7SJ45 Numerical Overcurrent Protection Relay Powered by CTs

SIPROTEC easy 7SJ45 Numerical Overcurrent Protection Relay Powered by CTs SIPROTEC easy 7SJ4 Numerical Overcurrent Protection Relay Powered by CTs Function overview Fig. /1 Description The SIPROTEC easy 7SJ4 is a numerical overcurrent protection relay which is primarily intended

More information

MRI1-IU - Voltage controlled time overcurrent relay

MRI1-IU - Voltage controlled time overcurrent relay MRI1-IU - Voltage controlled time overcurrent relay Contents 1 Introduction and application 2 Features and characteristics 3 Design 3.1 Connections 3.1.1 Analog input circuits 3.1.2 Output relays 3.1.3

More information

Reyrolle Protection Devices. 7SG117 Argus 7 Synchronising Relay. Answers for energy

Reyrolle Protection Devices. 7SG117 Argus 7 Synchronising Relay. Answers for energy Reyrolle Protection Devices 7SG117 Argus 7 Synchronising Relay Answers for energy 7SG117 Argus 7 Synchronising Relay Fig 1. Independent check & system synchronising settings Adjustable slip frequency,

More information

02/11/2015

02/11/2015 DIN Rail Mount 22.5 mm ETM2 Part number 84874023 Version ETM : Controls temperature of machines using built-in PTC probes Line break or probe short-circuit detection Version ETM2 / ETM22 : Fault latching

More information

Contact protection relay

Contact protection relay Contact protection relay Ordering details SVR 450 08 F0000 The protects sensitive control contacts from excessive load. It can be used with latching function or without. Bounce time of control contacts

More information

RT4B-110V/12A RECTIFIER

RT4B-110V/12A RECTIFIER The RT4B-110V/12A is a switched mode rectifier (SMR) module designed to provide up to 12A of output current into a 110V nominal system. It can be used with or without a cooling fan. With a fan it runs

More information

Electronic timer CT-VBS OFF-delayed without auxiliary voltage, for DC contactors Data sheet

Electronic timer CT-VBS OFF-delayed without auxiliary voltage, for DC contactors Data sheet Characteristics Single-function OFF-delay timer for DC contactors, without auxiliary voltage Width.5 mm CDC 5 6 F Approvals a culus f CCC CT-BS Circuit diagram Marker label Marks g c CE C-Tick Order data

More information

High Impedance Protection Relay SPAE010, SPAE011. Product Guide

High Impedance Protection Relay SPAE010, SPAE011. Product Guide SPAE010, SPAE011 SPAE010, SPAE011 1MRS750383-MBG Issued: April 1999 Status: Updated Version: D/21.03.2006 Data subject to change without notice Features High impedance type differential current earth-fault

More information

ISOMETER isopv with coupling device AGH-PV

ISOMETER isopv with coupling device AGH-PV Insulation monitoring device for unearthed AC, AC/DC and DC systems (IT systems) for photovoltaic plants up to AC 793 V/DC 1100 V Vorläufiges Datenblatt IsoPV_D00024_02_D_XXEN/07.2018 ISOMETER with coupling

More information

DGBV-EP DIGITAL GENERATOR AND GENERATOR-TRANSFORMER UNIT PROTECTION. Field of application

DGBV-EP DIGITAL GENERATOR AND GENERATOR-TRANSFORMER UNIT PROTECTION. Field of application DGBV-EP DIGITAL GENERATOR AND GENERATOR-TRANSFORMER UNIT PROTECTION Field of application The devices of the EuroProt complex protection family are modular devices. The modules are selected, assembled and

More information

Voltage regulator. SPAU 341 C 1MRS MBG Issued: July 1998 Status: Revised Version: C/ Data subject to change without notice

Voltage regulator. SPAU 341 C 1MRS MBG Issued: July 1998 Status: Revised Version: C/ Data subject to change without notice Issued: July 1998 Status: Revised Version: C/08.10.2003 Data subject to change without notice Features Comprehensive voltage regulation for power transformers with on-load tapchangers in distribution substations

More information

INSTRUCTION SHEET. Eaton Logic Controller ELCB Controllers

INSTRUCTION SHEET. Eaton Logic Controller ELCB Controllers 2010-12-10 5011699201-PBB1 Eaton Logic Controller ELCB Controllers INSTRUCTION SHEET [Applicable Controllers] ELCB-PB10 ELCB-PB14 ELCB-PB20 ELCB-PB30 ELCB-PB40 IL05001005E 002-1310020-02 Thank you for

More information

www. ElectricalPartManuals. com l Basler Electric MPS100 MOTOR PROTECTION SYSTEM ADVANTAGES WINDOWS SOFTWARE ADDITIONAL INFORMATION

www. ElectricalPartManuals. com l Basler Electric MPS100 MOTOR PROTECTION SYSTEM ADVANTAGES WINDOWS SOFTWARE ADDITIONAL INFORMATION The Motor Protection System is a microprocessor based digital relay which provides comprehensive motor protection including metering, communications, data recording and diagnostics. ADVANTAGES Extensive

More information

Type MVTT 14 and MVTT 15: Static Digital Time delay relays

Type MVTT 14 and MVTT 15: Static Digital Time delay relays Type MVTT 4 and MVTT 5: Static Digital Time delay relays Features 000/ setting range Time settings easily selected by means of thumbwheel switches Provide time delayed pick-up, or drop-off Compact construction

More information

5.1. Motor Protection and Monitoring. Contents. Product Overview. Monitoring Relays. D64R Series Digital Ground Fault Relays...

5.1. Motor Protection and Monitoring. Contents. Product Overview. Monitoring Relays. D64R Series Digital Ground Fault Relays... .1 Ground Fault Relays and Monitors Contents Description Current.................. Phase................... Voltage.................. Ground Fault Relays and Monitors D64R Series Digital Ground Fault Relays....

More information

NewCode. Comprehensive Motor Protection and Control Relay. Relay Field Input and Output LEDs. LED Fault Indicators

NewCode. Comprehensive Motor Protection and Control Relay. Relay Field Input and Output LEDs. LED Fault Indicators NewCode Comprehensive Motor Protection and Control Relay Relay Field Input and Output LEDs LED Fault Indicators Configurable Memory Module on a T-Bus IrDA and USB Connectors Profibus Address Indicator

More information

Overcurrent and Arc Protection by Reyrolle Alexander Erokhin. 21, 2017 I Berlin

Overcurrent and Arc Protection by Reyrolle Alexander Erokhin. 21, 2017 I Berlin Overcurrent and Arc Protection by Reyrolle Alexander Erokhin VAR Partner Day September 20-21, 21, 2017 I Berlin Reyrolle Product Range by SIEMENS Challenges We Meet for our Customers Easy-to-use protection

More information

GRD110 FEATURES APPLICATION

GRD110 FEATURES APPLICATION FEATURES Overcurrent protection for phase and earth faults with IDMTL or DTL. Three instantaneous elements with DTL. Programmable reset characteristics. Sensitive earth fault protection (SEF). Restricted

More information

RT4F-110V/25A RECTIFIER

RT4F-110V/25A RECTIFIER The RT4F-110V/25A is a hot-pluggable switched mode rectifier (SMR) module designed to provide up to 25A of output current into a 110V nominal system. Examples of such systems are 60 cells lead acid (136V

More information

BE1-50/51M TIME OVERCURRENT RELAY ADVANTAGES

BE1-50/51M TIME OVERCURRENT RELAY ADVANTAGES BE1-50/51M TIME OVERCURRENT RELAY The BE1-50/51M Time Overcurrent Relay provides economical overload and fault protection for generators, transformers, lines and motors. ADVANTAGES Self powered from 50/60Hz

More information

MIC-2 Multi-instrument DATA SHEET

MIC-2 Multi-instrument DATA SHEET Measurements All 3-phase AC measurements True RMS 4-Quadrant energy Power Quality Analysis Replaces analogue meters RS-485 Modbus RTU protocol TCP/IP Modbus (optional) Profibus DP (optional) I/O modules

More information

Reyrolle Protection Devices. 7SG13 Delta Protection and Control Relays. Answers for energy

Reyrolle Protection Devices. 7SG13 Delta Protection and Control Relays. Answers for energy Reyrolle Protection Devices 7SG13 Delta Protection and Control Relays Answers for energy 7SG13 Delta Protection and Control Relays User Interface 20 character x 2 line backlit LCD Menu navigation keys

More information

PROTECT Electronics Co. Ltd

PROTECT Electronics Co. Ltd Independent static overcurrent relay Document ID: 24-13-15848-00 Budapest, 2006 User s manual version information Version Datum Modification Compiled by.00 May 1995 First Hungarian version Póka.01 June

More information

FM2. Economical and compact feeder protection for low voltage feeders. Digital Energy Multilin. Monitoring & Metering. Protection and Control

FM2. Economical and compact feeder protection for low voltage feeders. Digital Energy Multilin. Monitoring & Metering. Protection and Control Key Benefits FM2 FEEDER Protection System Economical and compact feeder protection for low voltage feeders Comprehensive low voltage feeder management system - Integrated feeder protection and process

More information

Arc protection relay. Features Three-phase overcurrent function. Application

Arc protection relay. Features Three-phase overcurrent function. Application Arc protection relay REA 10_ Page 1 Issued: May 1999 Status: New Data subject to change without notice Features Three-phase overcurrent function Loop-type or radial sensor fibre for arc detection Two high-speed

More information

Bulletin 817 Thermistor Protection Relay

Bulletin 817 Thermistor Protection Relay 6 Bulletin 817 Accurate Temperature Monitoring for Critical Applications Automatic, Manual and Remote Reset Status Indicating LEDs DIN Rail or Panel Mounting Guarded Terminals IP20 1 N.O. and 1 N.C. Output

More information

For Transmission, Distribution and Machinery protection.

For Transmission, Distribution and Machinery protection. Founded in 1953, Microelettrica Scientifica has developed a wide range of products, divided into three main lines: For Transmission, Distribution and Machinery protection. A-Line Electronic analogic. M-Line

More information

Electronic timer CT-AWS Impulse-OFF with 2 c/o contacts Data sheet

Electronic timer CT-AWS Impulse-OFF with 2 c/o contacts Data sheet CDC 51 1 F000 1 7 6 5 8 Characteristics Single-function impulse-off timer One device includes 10 time ranges, from 0.05 s to 00 h, for the adjustment of the pulse time c/o contacts nd c/o contact can be

More information

Multifunction Transducer MT440

Multifunction Transducer MT440 Multifunction Transducer MT440 Voltage and current auto range measurements up to 600V, 12.5A Universal wide auxiliary power supply range 24 300 Vdc, 40 276 Vac Power accuracy class 0.5 (EN 60 688), Up

More information

D64RP18 INSTRUCTION MANUAL N.O. N.C V AC/DC TEST/ RESET

D64RP18 INSTRUCTION MANUAL N.O. N.C V AC/DC TEST/ RESET D64RP18 INSTRUCTION MANUAL N.O. N.O. CONTROL CIRCUIT N.C. N.C. CONTROL CIRCUIT 24-240V AC/DC L POWER SUPPLY N TEST/ RESET TEST/RESET PUSHBUTTON CT Wires EXTERNAL CORE BALANCE CT RATINGS PER IEC 60755 CT

More information

RT4F-120V/20A-WAC RECTIFIER

RT4F-120V/20A-WAC RECTIFIER The RT4F-120V/20A-WAC is a switched mode rectifier/charger module designed to provide up to 20A of output current into a 120V nominal system. This charger has been designed for use in conjunction with

More information

GS400. Electronic Auto-Ranging DIN Panel Mounted Positioner

GS400. Electronic Auto-Ranging DIN Panel Mounted Positioner GS400 Electronic Auto-Ranging DIN Panel Mounted Positioner Features * AC (115/230V) and DC (24V) versions available. * Accepts either current or voltage command signal and either current, voltage, or three

More information

Switching relay CT-IRS with 1, 2 or 3 c/o contacts Data sheet

Switching relay CT-IRS with 1, 2 or 3 c/o contacts Data sheet 1SVR 430 221 F7300 2 1 3 Characteristics Switching relay ON-delay approx. 10 ms 1, 2 or 3 c/o contacts Switching relay with gold-plated contacts Width 22.5 mm Approvals e f GOST CCC CT-IRS 1 U/R: green

More information

GPM500 Generator Protection Module

GPM500 Generator Protection Module GPM500 Generator Protection Module Generator Protection Module GPM500 The microprocessor based Generator Protection System GPM500 performs the protection and control of medium and low voltage generators

More information

Electronic timer CT-ERD.12

Electronic timer CT-ERD.12 2CDC 251 092 F0t06 a Rotary switch for the preselection of the time range b Potentiometer with direct reading scale for the fine adjustment of the time delay c U: green LED V control supply voltage applied

More information

SM100. On-Line Switchgear Condition Monitoring

SM100. On-Line Switchgear Condition Monitoring On-Line Switchgear Condition Monitoring On-Line Switchgear Condition Monitoring Introduction Weis is a specialist company with over 40 years of experience in the commissioning, testing & maintenance of

More information

2T105. Multi Range Digital Setting Time Delay Relay. Features. Application. Operation

2T105. Multi Range Digital Setting Time Delay Relay. Features. Application. Operation 2T15 Multi Range Digital Setting Time Delay Relay Technical Bulletin Features Four time ranges -.99s, -9.9s, -99s, -99s High accuracy & repeatability timing compensated for output relay delay Time settings

More information

Protection Relays PHASE & RESIDUAL OVERCURRENT

Protection Relays PHASE & RESIDUAL OVERCURRENT Protection Relays PHASE & RESIDUAL OVERCURRENT Application The relay type NA016 can be used in radial networks as feeder or power transformer protection. In solidly grounded systems the residual overcurrent

More information

DATA SHEET Selectable AC transducer, TAS-331DG

DATA SHEET Selectable AC transducer, TAS-331DG DATA SHEET Selectable AC transducer, TAS-331DG Measures power or reactive power on 3-phase AC networks Class 0.5 (IEC-688) measurement Supply and measuring voltage up to 690 V Easy configuration via PC

More information

BE1-51 BE1-51/27C BE1-51/27R TIME OVERCURRENT RELAY

BE1-51 BE1-51/27C BE1-51/27R TIME OVERCURRENT RELAY BE1-51 BE1-51/27C BE1-51/27R TIME OVERCURRENT RELAY The BE1-51 Series of Time Overcurrent Relays is microprocessor-based to provide versatile overload and fault protection on 50Hz or 60Hz systems. ADVANTAGES

More information

Millenium 3. General Characteristics. General environment characteristics for CB, CD, XD, XR and XE product types

Millenium 3. General Characteristics. General environment characteristics for CB, CD, XD, XR and XE product types Millenium 3 General Characteristics Millenium 3 Compact Range Millenium 3 Expandable Range Millenium 3 Communication Options Millenium 3 Range General environment characteristics for CB, CD, XD, XR and

More information

PROTECTION RELAYS THE ULTRA LINE NUMERICAL MULTIFUNCTION INTELLIGENT DEVICE FOR PROTECTION, SUPERVISION, METERING AND CONTROL

PROTECTION RELAYS THE ULTRA LINE NUMERICAL MULTIFUNCTION INTELLIGENT DEVICE FOR PROTECTION, SUPERVISION, METERING AND CONTROL MICROPROCESSOR PROTECTION RELAYS THE ULTRA LINE NUMERICAL MULTIFUNCTION INTELLIGENT DEVICE FOR PROTECTION, SUPERVISION, METERING AND CONTROL MICROELETTRICA SCIENTIFICA MANUFACTURES A COMPLETE RANGE OF

More information

T M. IRDH375 Series. Digital Ground Fault Monitor / Ground Detector For Ungrounded (Floating) AC/DC Systems. Technical Bulletin NAE / 09.

T M. IRDH375 Series. Digital Ground Fault Monitor / Ground Detector For Ungrounded (Floating) AC/DC Systems. Technical Bulletin NAE / 09. T M 1 IRDH375 Series Digital Ground Fault Monitor / Ground Detector For Ungrounded (Floating) AC/DC Systems Technical Bulletin NAE101051 / 09.013 IRDH375 Series Digital ground fault monitor / ground detector

More information

MiCOM P122C Time-Overcurrent Protection

MiCOM P122C Time-Overcurrent Protection Protection Relays 01 MiCOM P122C Time-Overcurrent Protection Customer Benefits 1A/5A software setting 4 function keys Compact unit for flush and wall-surface mounting Comprehensive measurements Disturbance

More information

VEO. V2ZR V AC/DC Art.Nr.: V2ZR10P V AC/DC Art.Nr.: TECHNICAL DATA

VEO. V2ZR V AC/DC Art.Nr.: V2ZR10P V AC/DC Art.Nr.: TECHNICAL DATA Off-Delay 10 time ranges Supply voltage 24-240V AC/DC 1 change-over contact Width 22,5 mm Control elements Fine adjustment Setting of time range Status indication LED U/t: Supply voltage LED R: Relay status

More information

7SR21 Non-Directional 7SR22 Directional Overcurrent Relay

7SR21 Non-Directional 7SR22 Directional Overcurrent Relay 7SR21 Non-Directional 7SR22 Directional Overcurrent Relay Document Release History This document is issue 2010/05. The list of revisions up to and including this issue is: 2010/05 Additional Comms modules

More information

DALI Professional Controller-4. Control unit Operating instructions

DALI Professional Controller-4. Control unit Operating instructions LI Professional Controller-4 Control unit Operating instructions Contents Safety... 4 General instructions 4 Safety instructions 4 Description... 5 Purpose and application 5 Configuration 5 Design 5 Connections

More information

RT4F-48V/50A-WAC RECTIFIER

RT4F-48V/50A-WAC RECTIFIER The RT4F-48V/50A-WAC is a switched mode rectifier (SMR) module designed to provide up to 58A of output current into a 48V nominal system, over a wide range of AC input voltage. This rectifier has been

More information

High impedance protection relay

High impedance protection relay High impedance protection relay Page 1 Issued: April 1999 Status: New Data subject to change without notice Features High impedance type differential current earth-fault protection, so called restricted

More information

Thermistor motor protection relays CM-MSS.22 and CM-MSS.23

Thermistor motor protection relays CM-MSS.22 and CM-MSS.23 Data sheet Thermistor motor protection relays CM-MSS.22 and CM-MSS.23 The thermistor motor protection relays CM-MSS.22 and CM-MSS.23 monitor the winding temperature of motors and protect them from overheating,

More information

Auxiliary Units for 7SR23 High Impedance Protection Energy Management

Auxiliary Units for 7SR23 High Impedance Protection Energy Management Reyrolle Protection Devices Auxiliary Units for High Impedance Protection Energy Management Siemens Protection Devices Limited 2 Auxiliary Units for High Impedance Protection Description 7XG15 High Impedance

More information

Company Directive ENGINEERING SPECIFICATION EE SPEC: 136

Company Directive ENGINEERING SPECIFICATION EE SPEC: 136 Company Directive ENGINEERING SPECIFICATION EE SPEC: 136 Ancillary Electrical Equipment for Use in Conjunction with Switchgear and Protection/Control Panels NOTE: The current version of this document is

More information

VEO. V2PF480Y/277VSY01 Art.Nr.: V2PF480Y/277VSY01P Art.Nr.: TECHNICAL DATA

VEO. V2PF480Y/277VSY01 Art.Nr.: V2PF480Y/277VSY01P Art.Nr.: TECHNICAL DATA Monitoring of phase sequence and phase loss Monitoring of asymmetry Supply voltage 208-480 V AC Supply circuit = measuring circuit 1 change-over contact Width 22,5 mm Control elements Asymmetry Status

More information

Products Portfolio. Pole mounted Vacuum Recloser

Products Portfolio. Pole mounted Vacuum Recloser Products Portfolio Pole mounted Vacuum Recloser Efacec Switchgear Efacec Switchgear is a leading company in Portugal and a worldwide reference in the development of solutions for power generation, transmission,

More information

Application Notes on Generator Protection Schemes

Application Notes on Generator Protection Schemes Application Notes on Generator Protection Schemes Single Line Diagram Examples 1. Introduction The application notes provide selected single line diagrams for the SIPROTEC 4 generator protection device

More information

Protector Trip Relays ENERGY DIVISION

Protector Trip Relays ENERGY DIVISION Protector Trip Relays ENERGY DIVISION Protector Trip Relays An extensive range of electronic control products providing continuous monitoring and protection of any electrical parameter. When the monitored

More information

Electronic timer CT-AHD.22

Electronic timer CT-AHD.22 2CDC 251 093 F0t06 a Rotary switch for the preselection of the time range b Potentiometer with direct reading scale for the fine adjustment of the time delay c U: green LED V control supply voltage applied

More information

Arc protection relay. Features Three-phase overcurrent function. Application

Arc protection relay. Features Three-phase overcurrent function. Application Arc protection relay REA 10_ Issued: May 1999 Status: Updated Version: B/12.11.2001 Data subject to change without notice Features Three-phase overcurrent function Loop-type or radial sensor fibre for

More information

TeSys IEC Contactors and Overload Relays

TeSys IEC Contactors and Overload Relays TeSys IEC Contactors and Overload Relays Making High-Fault Short-Circuit Current Ratings Simple Schneider Electric is an industry leader in IEC contactors and overload relays, and is recognized as the

More information

2V67-S Four Stage Over / Under Voltage Relay

2V67-S Four Stage Over / Under Voltage Relay Technical Bulletin 2V67-S Four Stage Over / Under Voltage Relay Features Large graphics display panel Instantaneous voltage display 20 to 130V PU setting range 0.1V setting resolution Adjustable pick up

More information

Quantum III. Compact DC Drive Package. Slitter DC Drive Package. Quantum III

Quantum III. Compact DC Drive Package. Slitter DC Drive Package. Quantum III Compact DC Drive Package The delivers a DC drive package that integrates the intelligence of the Mentor II with a space saving design that incorporates many accessories typically required in the North

More information

Circuit Breakers Type CTI 25M, CTI 45MB

Circuit Breakers Type CTI 25M, CTI 45MB Data sheet Circuit Breakers Type CTI 25M, CTI 45MB Circuit breakers for short circuit and overload protection of motor applications cover the current range 0.1 45 A (AC-3 rating). The product range is

More information

MiCOM P521. Fast feeder differential protection

MiCOM P521. Fast feeder differential protection 01 Fast feeder differential protection The relay provides high-speed two-ended current differential unit protection of overhead lines and underground cables in applications such as ring mains and parallel

More information

Reyrolle Protection Devices. 7SG118 Argus 8 Voltage & Frequency Relay. Answers for energy

Reyrolle Protection Devices. 7SG118 Argus 8 Voltage & Frequency Relay. Answers for energy Reyrolle Protection Devices 7SG118 Argus 8 Voltage & Frequency Relay Answers for energy 7SG118 Argus 8 Voltage and Frequency Relay Data Storage and Communication Serial communications conform to IEC60870-5-103

More information

2. Control Pin Functions and Applications

2. Control Pin Functions and Applications IMARY CONTROL ( PIN) Module Enable / Disable. The module can be disabled by pulling the below 2.3 V with respect to the Input. This should be done with an open-collector transistor, relay, or optocoupler.

More information

NPW800R RETROFITTING. Power and Volatge Protection Relay

NPW800R RETROFITTING. Power and Volatge Protection Relay RETROFITTING Power and Volatge Protection Relay NPW800R (R3 case) is dedicated to the refurbishment of CEE WTG 7000 relays (R3 case) providing the measurement of apparent (S), active (P) and reactive (Q)

More information

Chrome DIN Rail Power Supply 12V 9.96W 1 Phase (Class II & NEC Class 2) / DRC-12V10W1A

Chrome DIN Rail Power Supply 12V 9.96W 1 Phase (Class II & NEC Class 2) / DRC-12V10W1A Highlights & Features Protection Class II, Double Isolation (No Earth connection is required) Universal AC input voltage and full power up to 55 C Power will not de-rate for the entire input voltage range

More information

E-STOP relays, safety gate monitors

E-STOP relays, safety gate monitors Safety relay for monitoring E-STOP pushbuttons, safety gates and light barriers. Approvals Block diagram Unit features Positive-guided relay outputs: 6 safety contacts (N/O), instantaneous 4 auxiliary

More information

MIC-2 MKII & MIC-2 MKII DIN, Multi-instrument DATA SHEET

MIC-2 MKII & MIC-2 MKII DIN, Multi-instrument DATA SHEET & DIN, Multi-instrument DATA SHEET Measurements All 3-phase AC measurements True RMS 4-Quadrant energy Power Quality Analysis Replaces analogue meters RS-485 Modbus RTU protocol TCP/IP Modbus (optional)

More information

SECTION 16 LED DIAGNOSTIC FEATURES: EXPANSION UNITS: SCR-31P-i. SCR-73-i. SEU-31-i. SCR-31-42TD-i. SEU-31TD-i

SECTION 16 LED DIAGNOSTIC FEATURES: EXPANSION UNITS: SCR-31P-i. SCR-73-i. SEU-31-i. SCR-31-42TD-i. SEU-31TD-i SECTION 16 VIPER Safety Relays Type: SCR-i (with added diagnostics) SAFETY RELAY FUNCTION: IDEM s VIPER SCR-i range of Safety Relays have been designed in accordance with EN60204-1 for safety circuits

More information

MiCOM P521. Fast Feeder Differential Protection

MiCOM P521. Fast Feeder Differential Protection 01 Fast Feeder Differential Protection The relay provides high-speed two-ended current differential unit protection of overhead lines and underground cables in applications such as ring mains and parallel

More information