Safety Technique. SAFEMASTER C Multifunction Safety Module BH 5910

Size: px
Start display at page:

Download "Safety Technique. SAFEMASTER C Multifunction Safety Module BH 5910"

Transcription

1 Safety Technique SAFEMASTER C Multifunction Safety Module BH Block Diagram A+ A S S S4 S S S S4 S S S S4 S S4 S4 S44 S4 PTC Galvanic separation Monitoring logic Monitoring logic Galvanic separation K K run K K Galvanic separation run K K According to - Performance Level (PL) e and category 4 to EN ISO 849-: 8 - SIL Claimed Level (SIL CL) to IEC/EN 66 - Safety Integrity Level (SIL ) to IEC/EN Category 4 to EN 954- Functions selectable via rotational switches to connect max.: - 8 circuits, single channel or - 4 circuits, -channel or - 4 light curtains or - light curtains and circuit or - 4 safety gates or - safety gates and circuit or - 4 pairs of -hand-buttons or Typ III A according to DIN EN 547 or - pairs of -hand-buttons Typ III C according to DIN EN 547 and circuit In addition selectable: - auto or manual reset (simulation input for gate monitor) - continuously monitored feedback circuit to monitor external contactors Cross fault detection Short circuit and broken wire detection Outputs: - NO or NO and s - semiconductor outputs short circuit proof and overload protected Under- and overvoltage detection and signalling LED indication for operation (RUN), channel / 45 mm width Approvals and Marking Canada / USA * A M84_a * see variants Table of Contents Content page Applications Protection of men and machines Features, Indication, Notes... Setting table... Operating modes, Manual and Auto start... Functions:...4 Light curtains...6 Light curtains Gate monitor...9 Gate monitor Hand-Safety...4 -Hand-Safety Circuit diagrams, Technical data...8 Standard type, Example of order, Flash codes for fault indication... Indication lower green LEDs K, K: On, when relays K and K are energized upper yellow LEDs run, run : Continuously on on fault free operation. Regular flashing when waiting for external action e.g. release of an button. Detected faults are indicated with special flashing sequences (see flash codes for fault indication) Terminal 48: Flashes, als long as starting condition is t fulfilled. Terminal 58: Flashes while waiting for start or simulation input (button). Continuous signal when relay enabled. Notes On BH 59. the - can only be used as monitoring contact. Changes of settings are only permitted when supply voltage is disconnected and have to be made by trained persons only. Before removing the front cover please touch ground potential. All technical data in this list relate to the state at the moment of edition. We reserve the right for technical improvements and changes at any time en / 45

2 Unit settings M99 plate ch ch The selection of the function of BH 59 is done via 4 rotational switches behind the front cover of the unit (see drawing on the left). The switches on the left set processor (ch ) and the switches on the right set processor (ch ). Both processors must have the same setting. On both upper switches () the function is selected, on both lower switches () the number of sensor circuits, control and operation mode and the feed back circiuit option is selected. M855 Inside view Switch Function Switch No / Sensors Control mode Operation mode Feedback circuit for external contacts button 6 6 channel channel channel channel channel channel channel channel Auto-Start Manual start Auto-Start Manual startt Auto-Start Manual startt Auto-Start Manual start Light curtains (LC) 4 Light curtains channel channel channel channel Auto-Start Manual startt Auto-Start Manual start Light curtains + ( button, -channel, manual start Light curtains channel channel channel channel Auto-Start Manual start Auto-Start Manual start Gate monitor Gate switches s s C/O contacts C/O contacts s C/O contacts, NO s C/O contacts s C/O contacts, NO without simulation button without simulation button 4 Gate monitor + ( button, -channel, manual start) 4 5 Gate switches s C/O contacts s s C/O contacts s 5 -hand safety button pairs s s s s s C/O contacts s s s C/O contacts 6 -hand safety + ( button, -channel, manual start) 4 5 button pairs s s C/O contacts s s C/O contacts 7 t permitted 8 t permitted en / 45

3 Operating Mode Auto start (with function and light curtain) On automatic restart the output contacts are activated when the input condition for the selected function is fulfilled. A start-button is only necessary in cases: - If the function light curtain, safety gate or -hand-safety is combined with. - If a function with feedback circuit is selected and the unit has to be reset after a detected fault without disconnection. Manual start (with function and light curtain) If the unit was deactivated by operating the safety function e.g. by pressing an e- button it only can be reset in manual mode by pressing the start button. After voltage failure the unit has to be reset also with the start button. The button has to be pressed t longer then sec. to allow the unit to energise. Feedback Circuit to Monitor External Contactors If the number of contacts has to be increased or a higher current has to be switched by contactors a feedback circuit with ors can be connected to terminals S4-S4 (see drawing ). This circuit allows to monitor the state of the external contactors. The BH 59 monitors continuously if the state of this input corresponds to the state of K and K. In the case of a fault K and K switch off or do t switch on at all. If the fault is removed, the BH 59 has to be reset with the start button. When operating the unit with feedback circuit the circuit has to be connected to terminal S4 and S4. If one of the functions light curtain, safety gate or -hand-safety is combined with the function always works with manual restart. When manual start is selected, the start button is always connected to terminals S4-S44. K start K A+ S S S4 S S S S4 S S S S4 S S4 S4 S44 S4 BH59 K K A- 48 machine enabling K K waiting for start L- M844_a Pic. :, -channel, with buttons, manual start and external contactors with feed back circuits (Switch : position, switch : position 4 or 5) en / 45

4 Stop (switch in position ) With switch the maximum number of e- loops is selected. Open (unused) inputs (S_/S_ and S_/S_4) have to be linked with a wire bridge. K and K can only be activated, if all e- buttons are released. The function diagrams show only the action of one e- button. We pretend that the others are closed. When the unit is used with -channel e- loops, it checks the state of the inputs. If both channels have different signals for more then 5 ms the outputs K and K are switched off and the unit gives failure code 7. This failure is stored and can only be reset by disconnecting the auxiliary supply. Function Diagrams Settings on switch Switch Number of loops Type of control Type of start Feedback circuit for external contactors 4 channel Auto-Start channel Manual start 8 channel Auto-Start 6 channel Manual start 4 channel Auto-Start 5 channel Manual start 6 6 channel Auto-Start 7 6 channel Manual start 8 position t allowed (failure code 5 9 position t allowed (failure code 5 Auxiliary voltage (A/A) K/K (-4, -4, -4) Output 48 () Output 58 (waiting for start) : off : on : flashing M848, -channel, auto start Auxiliary voltage (A/A) Start button (S4/S44) K/K (-4, -4, -4) Output 48 () Output 58 (waiting for start) : off : on : flashing M849, -channel, manual start Terminal designation A- Terminal S S S S4 S S S S4 S S S S4 S4 S4 S4 S44 loop, channel Semiconductor outputs loop, channel 4 Feedback circuit and/or manual start Feedback circuit or connection Start button Output Flashing signal Continuous signal 48 active or failure in feedback circuit or failure on start button 58 Wait for start button Relay K, K active Application Example A+ S S S4 S S S S4 S S S S4 S S4 S4 S44 S4 BH59 K K 48 machine enabling waiting for start L- M845_a Pic. :, -channel, with 4 e- loops, auto start (switch in position, switch in position ) en / 45

5 Stop, Application Examples A+ S S S4 S S S S4 S S S S4 S S4 S4 S44 S4 BH59 K K 48 machine enabling waiting for start L- M846_a Pic. :, -channel, with 8 e- loops, auto start; (switch in position, switch in position ) start A+ S S S4 S S S S4 S S S S4 S S4 S4 S44 S4 BH59 K K A- A- 48 machine enabling waiting for start L- M847_a Pic. 4:, -channel, with e- loops, manual start; (switch in position ; switch in position ) en / 45

6 Light Curtains (switch in position ) With switch the maximum number of LCs (Light curtains) is selected. Open (unused) inputs (S_/S_ and S_/S_4) have to be linked with a wire bridge. K and K can only be activated, if LC is interrupted. If both channels of an LC have different signals for more then 5 ms the outputs K and K are switched off and the unit gives failure code 7. This failure is stored and can only be reset by disconnecting the auxiliary supply. The BH 59 can be used on LCs of type 4 (IEC/EN ) or type with self test and crossfault monitoring. The following function diagrams show the function of one LC. We pretend that other connected LCs are t interrupted. Function Diagrams Auxiliary voltage (A/A) LC K/K (-4, -4, -4) Output 48 () Output 58 (waiting for start) : off : on : flashing M84 Light curtains, auto start Auxiliary voltage (A/A) LC Start button (S4/S44) K/K (-4, -4, -4) Output 48 () Output 58 (waiting for start) : off : on : flashing M84 Settings on switch Switch No. of Type of Type of Feedback circuit for LCs control start external contactors 4 -channel light curtains Auto-Start -channel light curtains Manual start -channel light curtains Auto-Start -channel light curtains Manual start 4-9 position t allowed (failure 5) Terminal designation transmitter Terminal S S S S4 S S S S4 S S S S4 S4 S4 S4 S44 t connected LC t connected LC t connected LC t connected LC t connected LC t connected LC t connected LC 4 t connected LC 4 Light curtains Sorties à semi-conducteurs link S-S without LCI link S-S4 without LC link S-S without LC link S-S4 without LC link S-S without LC link S-S4 without LC link S4-S4 without LC 4 link S4-S44 without LC 4 Feedback circuit and /or manual start Feedback circuit or connection Start button Output Flashing signal Continuous signal 48 One LC interrupted or failure in feedback circuit or in start circuit 58 Wait for start button Relay K, K active Light curtains, manual start Application Example LC LC LC LC 4 A+ S S S4 S S S S4 S S S S4 S S4 S4 S44 S4 A- transmitter transmitter transmitter BH59 K K 48 machine enabling waiting for start L- M84_a Pic. 5: Light curtains, with 4 LCs, auto start; (switch in position, switch in position ) en / 45

7 Light Curtains (switch in position ); Application Example LC LC A- transmitter transmitter start A+ S S S4 S S S S4 S S S S4 S S4 S4 S44 S4 BH59 K K 48 machine enabling waiting for start L- M84_a Pic. 6: Light curtains, with LCs, manual start; (switch in position, switch in position ) Light Curtains and Stop (switch in position ) In this function the unit is always set to LCs and e- loop. Open (unused) inputs (S/S and S/S4) have to be linked with a wire bridge. K and K can only be activated, if LC is interrupted and the e- loop is closed. After an e- or power failure the unit has to be reset with manual start. If both channels of an LC or e- loop have different signals for more then 5 ms the outputs K and K are switched off and the unit gives failure code 7. This failure is stored and can only be reset by disconnecting the auxiliary supply. Settings on switch Switch No. of Type of Type of Feedback circuit for LCs control start external contactors 4 -channel light curtains Auto-Start -channel light curtains Manual start -channel light curtains Auto-Start -channel light curtains Manual start 4-9 position t allowed (failure 5) Terminal designation Terminal S S S S4 S S S S4 S S S S4 S4 S4 S4 S44 Light curtains / t connected link S-S LC without LC t connected link S-S4 LC without LC t connected link S-S LC without LC t connected link S-S LC without LC Start button Feedback circuit for external contactors Feedback circuit Semiconductor outputs Output Flashing signal Continuous signal 48 One LC interrupted or button pressed or failure in feedback circuit or failure in start circuit 58 Wait for start button Relay K, K active en / 45

8 Light Curtains and Stop Auxiliary voltage (A/A) LC Start button (S4/S44) K/K (-4, -4, -4) Output 48 () Output 58 (waiting for start) : off : on : flashing M844 Auxiliary voltage (A/A) LC Start button (S4/S44) K/K (-4, -4, -4) Output 48 () Output 58 (waiting for start) : offl : on : flashing M845 Light curtains and, auto start Light curtains and, manual start LC LC A- transmitter transmitter start A+ S S S4 S S S S4 S S S S4 S S4 S4 S44 S4 BH59 K K 48 machine enabling waiting for start L- M846_a Pic. 7: Light curtains and, auto start or manual start (switch in position, switch in position or ) en / 45

9 Safety Gates (switch in position ) With switch the maximum number of gates is selected. Open (unused) inputs (S_/S_ and S_/S_4) have to be linked with a wire bridge. If gate inputs are t used the type of control has to be. K and K can only be activated, if all connected gates have been opened and closed again. Both gate contacts have to be operated within s. If the time difference is longer, the gate has to be opened before it can be closed again. When all gates are closed the unit can also be activated by an external connected Simulation button. If changeover contacts are used on the gate switches the switchover time has to be less then 5 ms. If it is longer the outputs K and K are switched off and the unit gives failure code 7. This failure is stored and can only be reset by disconnecting the auxiliary supply. Function Diagram Auxiliary voltage (A/A) Gate S (S/S) Settings on switch Switch Number of gates Number and type of gate switches Simulation button Feedback circuit for external contactors 4 s s C/O contacts C/O contacts 4 s 5 C/O contacts + 6 s 7 C/O contacts 8 s C/O contacts 9 + s must be closed when gate is closed, s must be open when gate is closed. Gate S (S/S4) Gate S (S/S) Gate S (S/S4) Gate S (S/S) Gate S (S/S4) Simulation button (S4/S44) K/K (-4, -4, -4) 48 (gate open or failure) 58 (all gates closed) : off : on : flashing M847 Gate monitor, gates with s for each gate, Simulation button Semiconductor outputs Output Flashing signal Continuous signal Open gate or failure in feedback 48 circuit or in start circuit 58 Gates are closed but starting conditions t fulfilled >s Gates are closed and contacts K, K are active Terminal designation Terminal S S S4 S S S S4 S S S S4 S S4 S4 S44 S4 Max. gates with NO gate contacts gate, S gate, S gate, S gate, S gate with C/O + NO gate contact gate, S gate, S gate, S gate, S gate, S gate, S gate, S gate, S Max. 4 gates with NO gate contacts gate, S gate, S gate, S gate, S gate, S gate, S gate, S gate, S t connected t connected t connected gate, S gate 4, S gate 4, S Max. gates with C/O gate contacts gate, S gate, S gate, S gate, S gate, S gate, S gate, S gate, S gate, S gate, S gate, S gate, S gate, S gate, S gate, S gate, S contact NO Feedback circuit Feedback circuit for external contacts simulation Simulation button en / 45

10 Safety Gates (switch in position ); Application Examples safety gate safety gate safety gate safety gate 4 open closed open closed open closed open closed S S S S S S S S A+ S S S4 S S S S4 S S S S4 S S4 S4 S44 S4 BH59 K K 48 machine enabling gate closed L- M848_a Pic. 8:Gate monitor, 4 gates with NO gate contacts each (switch in position ; switch in position ) safety gate safety gate closed open closed open S S S S A+ S S S4 S S S S4 S S S S4 S S4 S4 S44 S4 BH59 K K A- A- 48 machine enabling gate closed L- M849_a Pic. 9: Gate monitor, gates with changeover gate contacts each (switch in position ; switch in position ) en / 45

11 Safety Gates (switch in position ); Application Examples safety gate S safety gate S open closed open closed simulation S S S S A+ S S S4 S S S S4 S S S S4 S S4 S4 S44 S4 BH59 K K 48 machine enabling gate closed L- M844_a Pic. : Gate monitor, gates with NO gate contacts each, simulation button (switch in position ; switch in position 4) S safety gate closed open S S simulation A+ S S S4 S S S S4 S S S S4 S S4 S4 S44 S4 BH59 K K A- A- 48 machine enabling gate closed L- M844_a Pic. : Gate monitor, gate with changeover gate contacts, simulation button (switch in position ; switch in position 5) en / 45

12 Safety Gates and Stop (switch in position 4) With switch the maximum number of gates is selected. Open (unused) inputs (S_/S_ and S_/S_4) have to be linked with a wire bridge. K and K can only be activated, if the e- loop is closed and all connected gates have been opened and closed again. Both gate contacts have to be operated within s. If the time difference is longer, the gate has to be opened before it can be closed again. When all gates are closed the unit can also be activated by an external connected simulation button. After e- or power failure the unit can only be reset by manual start. If changeover contacts are used on the gate switches the switchover time has to be less then 5 ms. If it is longer the outputs K and K are switched off and the unit gives failure code 7. This failure is stored and can only be reset by disconnecting the auxiliary supply. Function Diagram Settings on switch Switch No. of gates Number and type of gate switches Simulation button Feedback circuit for external contactors s C/O contacts s s 4 C/O contacts 5 s 6-9 position t allowed (failure 5) s must be closed when gate is closed, s must be open when gate is closed. Terminal designation Auxiliary voltage (A/A) Gate S (S/S) Gate S (S/S4) Gate S (S/S) Simulation button (S4/S44) K/K (-4, -4, -4) 48 (gates open or ) 58 (all gates closed, e- loop closed) : off : on : flashing M844 Gate monitor and, gate with NO gate contacts and e- loop Terminal S S S4 S S S S4 S S S S4 S S4 S4 S44 S4 gate with NO gate contacts gate, S gate, S gate, S t connected gate with NO gate contacts gate, S gate, S gate, S gate, S button, Simulation or start button, channel, channel Simulation or start button gate with C/O gate contacts gate, S gate, S gate, S gate, S gate, S gate, S gate, S gate, S Feedback circuit for external contactors Feedback circuit Semiconductor outputs Output Flashing signal Continuous signal 48 Open gate, e- loop open or failure in feedback circuit or failure on simulation button 58 Gates are closed but starting conditions t fulfilled or loop has been opened and closed again. K, K can be activated with the simulation button Gates are closed and contacts K, K are active en / 45

13 Safety Gates and Stop (switch in position 4); Application Example safety gate S open S S closed simulation or start A+ S S S4 S S S S4 S S S S4 S S4 S4 S44 S4 BH59 K K A- 48 machine enabling gate closed, loop closed L- M844_a Pic. : Gate monitor and, gate with NO gate contacts and e- loop (switch position 4; switch position ) NE5. actuator NE5. actuator NE5. actuator 4 sensor sensor 4 sensor emergency simulation A(+) S S S4 S S S S4 S S44 S4 BH59 A(-) S S S4 S S4 S sensor sensor sensor 4 L- 4 actuator actuator actuator NE5. NE5. NE5. M848_g Pic. : Gate monitor and, safety gate monitoring with up to magnetic coded safety switches NE 5 + e- loop (switch position 4; switch position or ) en / 45

14 Two-Hand Control (switch in position 5) 4 pairs of -hand buttons Typ III A or pairs of -hand buttons Typ III C according to DIN EN 574 can be connected in this function. The number of connected button pairs has to be selected on the device. K and K can only be activated, if conditions are fulfilled: - First all button pairs have to be in initial position. - Both buttons of pair have to be pressed within.5 sec. - All connected pairs have to be operated within 5 s. If changeover contacts are used in the -hand buttons the switchover time has to be less then 5 ms. If it is longer the outputs K and K are switched off and the unit gives failure code 7. This failure is stored and can only be reset by disconnecting the auxiliary supply. Function Diagram Settings on switch Switch Number of button pairs Type of button contacts s s s 4 s 4 C/O contacts 5 C/O contacts 6 s 7 s 8 s 9 C/O contacts Feedback circuit for external contactors Auxiliary voltage (A/A) Button S (S/S) Button S (S/S4) Button S (S/S) Button S (S/S4) K/K (-4, -4, -4) 48 ( button activated) 58 (all buttons activated) : off : on : flashing <,5s,5s <5s Two-hand control, pairs of buttons with s each Set-Up Instructions 5s M8444 The device has to be connected as shown in the application examples. When connecting the push-buttons in parallel or in series the safe function of the relay is disabled. The buttons must be designed and installed in a way, that it is t possible to manipulate or to operate them without intention. The distance between push buttons and dangerous area must be chosen in a way that it is t possible to reach the dangerous area after release of one button before the dangerous movement comes to standstill. The safety distance "S" is calculated with the following formula: S = V x T + C a) moving speed of person V = 6 mm/s b) ping time of the machine T (s) c) Additional safety distance C = 5 mm Terminal designation Terminal S S S4 S S S S4 S S S S4 S S4 S4 S44 S4 Pair of buttons with s each Pair, button S Pair, button S Pair, button S Pair, button S Pair, button S Pair, button S Pair 4, button S Pair 4, button S Pair of buttons with Feedback circuit for C/O contacts each external contactors Pair, button S, Pair, button S, Pair, button S, Pair, button S, contact NF Pair, button S, Pair, button S, Pair, button S, Pair, button S, Pair, button S, Pair, button S, Pair, button S, Pair, button S, Pair, button S, Pair, button S, Feedback circuit Pair, button S, Ackwledge button Pair, button S, If the risc of accessing the dangerous area is prohibited while the push buttons are pressed e.g. by covering the buttons, C can be. The minimum distance has to be in this case mm. See also EN 574. Semiconductor outputs Output Flashing signal Continuous signal 48 Open gate, e- loop open or failure in feedback circuit or failure on simulation button 58 Press ackwledge button. All buttons in initial position. For a new start all buttons have to be activated according to the starting conditions. All buttons are activated, K, K are energized en / 45

15 Two-Hand Control (switch in position 5); Application Examples -hand -hand -hand S S S S S S A+ S S S4 S S S S4 S S S S4 S S4 S4 S44 S4 BH59 K K 48 machine enabling hand state machine enabled L- M8445_a Pic.4: -hand control, with pairs of buttons and s each (switch in position 5; switch in position ) Safety switches Typ III A according to DIN EN 574 S -hand -hand S S S A+ S S S4 S S S S4 S S S S4 S S4 S4 S44 S4 BH59 K K A- A- 48 machine enabling hand state machine enabled L- M8446_a Pic.5: -hand control, with pairs of buttons and changeover contacts each (switch in position 5; switch in position 5) Safety switches Typ III C according to DIN EN en / 45

16 Two-Hand Control and Stop (switch in position 6) pairs of -hand buttons can be connected in this function together with e- loop. The number of connected button pairs has to be selected on the device. K and K can only be activated, if 4 conditions are fulfilled: - First all button pairs have to be in initial position. - The e- contacts must be closed and manual start must be activated. - Both buttons of pair have to be pressed within.5 sec. - All connected pairs have to be operated within 5 sec. If changeover contacts are used in the -hand buttons the switchover time has to be less then 5 ms. If it is longer the outputs K and K are switched off and the unit gives failure code 7. This failure is stored and can only be reset by disconnecting the auxiliary supply. After e- or power failure the start button must always be activated. The e- loop must be closed and all -hand button pairs must be in initial position. Function Diagram Settings on switch Switch Number of button pairs Type of button contacts Feedback circuit for external contactors s s C/O contacts s 4 s 5 C/O contacts 6-9 position t allowed (failure 5) Terminal designation Auxiliary voltage (A/A) Button S (S/S) Button S (S/S4) Button S (S/S) Button S (S/S4) Start button (S4/S44) K/K (-4, -4, -4) 48 ( button activated) 58 (all buttons activated) Terminal S S S4 S S S S4 S S Pair of buttons with Pair of buttons with s each C/O contacts each button S, Pair, button S button S, button S, Pair, button S button S, button S, Pair, button S button S, button S, Pair, button S button S, loop and Start button Feedback circuit for external contactors : off : on : flashing M8447 S, channel -hand control and e-, with pairs of buttons with s each and e- loop Set-Up Instructions The device has to be connected as shown in the application examples. When connecting the push-buttons in parallel or in series the safe function of the relay is disabled. The buttons must be designed and installed in a way, that it is t possible to manipulate or to operate them without intention. S4 S S4 S4 S44 S4, channel t connected Start button Feedback circuit The distance between push buttons and dangerous area must be chosen in a way that it is t possible to reach the dangerous area after release of one button before the dangerous movement comes to standstill. The safety distance "S" is calculated with the following formula: S = V x T + C a) moving speed of person V = 6 mm/s b) ping time of the machine T (s) c) Additional safety distance C = 5 mm If the risc of accessing the dangerous area is prohibited while the push buttons are pressed e.g. by covering the buttons, C can be. The minimum distance has to be in this case mm. See also EN 574. Semiconductor outputs Output Flashing signal Continuous signal 48 loop open or starting conditions t fulfilled or failure in feedback circuit or on ackwledge button/start button. 58 Press ackwledge button. All buttons in initial position. For a new start all buttons have to be linked according to the starting conditions. All buttons are activated, K, K are energized en / 45

17 Two-Hand Control and Stop (switch in position 6); Application Example -hand -hand S S S S start A+ S S S4 S S S S4 S S S S4 S S4 S4 S44 S4 BH59 K K A- 48 machine enabling hand state machine enabled L- M8448_a Pic. 6: -hand control and e-, with pairs of buttons and s each (switch in position 6; switch in position ) -hand-safety switsches Type III A according to DIN EN en / 45

18 Circuit Diagrams Technical Data S S S S4 S Input S S S S4 K S S S S4 S K S S S4 S4 S4 S4 S44 A 48 S S4 S (+) A(+) A(-) A+ 48 A+ 58 Nominal voltage U N : Voltage range at max. 5 % residual ripple: Nominal consumption: DC 4 V Control voltage on S, S, S, S, S, S, S4, S4, 48, 58: DC V at U N Control current on S, S4, S, S4, S, S4, S4, S44: 4,5 ma at U N each Min. voltage at terminals S, S4, S, S4, S, S4 S4, S44: DC 6 V Fusing: internal with PTC,85...,5 U N max. 7 ma (Semiconductor outputs t connected) BH 59. A 58 S S4 S4 4 (-) 4 4 S S S4 S4 S44 S S S S4 S A 48 S S4 S (+) M896 Output Contacts BH 59.: BH 59.: Contact type: Operating time typ. at U N s s, The can only be used as indicator contact. Relay, forcibly guided S S S S4 K S S S S4 S K S S S4 S4 S4 S4 S44 BH 59. A(+) A(-) A 58 (-) S S4 S4 4 4 S S Connection Terminals 4 4 S4 S4 S44 A+ 48 A+ 58 M897 Terminal designation Signal designation A+ + / L A - / N S, S4, S, S4, S, S4. S4, S44 Inputs S, S, S, S, S, S, S4, S4 Outputs, 4,, 4,, 4 Forcibly guided s for release circuit, Forcibly guided s for monitoring 48, 58 Semiconductor monitoring output Function Manual start Auto start Light curtains Safety gates -hand control * ) TS = closing of gate 45 ms 45 ms 45 ms (Simulation) 54 ms (Activation) max. switch off time (reaction time) Function Light curtains Safety gates -hand control 8 ms 8 ms 8 ms 8 ms Start,6 s,6 s Restart 45 ms 45 ms 9 ms (TS)* ) Switching off when failure in feedback circuit: max. ms Nominal output voltage: AC 5 V DC: see limit curve for arc-free operation Switching of low loads: mv Thermal current I th : 5 A Switching capacity to AC 5 : A / AC V IEC/EN : A / AC V IEC/EN to DC at, Hz: 8 A / DC 4 V IEC/EN Electrical life to AC 5 at A, AC V: 5 switching cycles IEC/EN Permissible switching frequency: max. switching cycles / h Short circuit strength max. fuse rating: 6 A gl IEC/EN line circuit breaker: C 8 A Mechanical life: x 6 switching cycles Semiconductor Outputs Output (terminal 48 and 58): transistor outputs, switching + Nominal output voltage: DC 4 V, max. ma continuous current, max. 4 ma for,5 s internal short circuit, over temperature and overload protection en / 45

19 Technical Data Technical Data General Data Operating mode: Continuous operation Temperature range operation: ± C storage : C altitude: <. m Clearance and creepage distances rated impuls voltage / pollution degree: 4 kv / (basis insulation) IEC EMC Electrostatic discharge: 8 kv (air) IEC/EN 6-4- (according to test degree ) HF-irradiation: V / m IEC/EN 6-4- Fast transients on wires for power supply A-A: kv IEC/EN on signal and control wires: kv IEC/EN Surge voltages between wires for power supply: kv IEC/EN between wireand ground: kv IEC/EN HF-wire guided: V Interference suppression: Limit value class B EN 55 Degree of protection: according to IEC/EN (997) the unit has to be mounted in a control cabinet with protection class 54 Housing: IP 4 IEC/EN 6 59 Terminals: IP IeC/EN 6 59 Housing: Thermoplastic with V behaviour according to UL subject 94 Vibration resistance: according to IEC/EN (997) Amplitude,5 mm IEC/EN frequency Hz Shock proof: Acceleration: g Impulse length: 6 ms Number of shocks: per ax is on all axes Climate resistance: / 5 / 4 IEC/EN Terminal designation: EN 5 5 Wire connection: x,5 mm stranded wire with sleeve or x 4 mm solid or x,5 mm stranded wire with sleeve DIN 46 8-/-/-/-4 Wire fixing: Plus-minus terminal screws M,5 box terminals with wire protection Mounting: DIN rail IEC/EN 6 75 Weigth: g Safety Related Data for light curtains,safety gates or two-hand Values according to EN ISO 849-: Kategorie: 4 PL: e MTTF d :.5 a DC avg : 98.9 % d op : d/a (days/year) h op : h/d (hours/day) t Zyklus : 44 s/zyklus Values according to IEC/EN 66 / IEC/EN 658: SIL CL: IEC/EN 66 SIL IEC/EN 658 HFT *) : DC avg : 98.9 % SFF 99.6 % PFH D : 7.89 h - * ) HFT = Hardware-Failure Tolerance nfo UL-Data The values stated above are valid for the standard type. Safety data for other variants are available on request. The safety relevant data of the complete system has to be determined by the manufacturer of the system. The safety functions were t evaluated by UL. Listing is accomplished according to requirements of Standard UL 58, general use applications Nominal voltage U N : Ambient temperature: Switching capacity: Ambient temperature 5 C: Semiconductor outputs: Wire connection: nfo DC 4 V +5 C Pilot duty B 5A 5Vac G.P. 5A 4Vdc 4Vdc, ma 6 C / 75 C copper conductors only AWG - Sol Torque.8 Nm AWG - 4 Str Torque.8 Nm Technical data that is t stated in the UL-Data, can be found in the technical data section. Dimensions CCC-Data Width x height x depth: 45 x 84 x mm Thermal current I th : 4 A Safety Related Data for STOP Values according to EN ISO 849-: Category: 4 MTTF d : 8.9 a DC avg : 97.9 % d op : 65 d/a (days/year) h op : 4 h/d (hours/day) t Zyklus : 6 s/zyklus = /h (hour) Switching capacity to AC 5: A / AC V IEC/EN to DC : A / DC 4 V IEC/EN nfo Technical data that is t stated in the CCC-Data, can be found in the technical data section. Values according to IEC EN 66 / IEC EN 658: SIL CL: IEC EN 66 SIL IEC EN 658 HFT *) : DC avg : 97.9 % SFF 99.4 % PFH D : 5.57 h en / 45

20 Standard Type BH 59./MF DC 4 V Article number: 547 Output: s All functions selectable via rotational switches Nominal voltage U N : DC 4 V Width: 45 mm Ordering example BH 59. /MF DC 4 V Nominal voltage Contacts.: s.: s, Type Fault Indication by flashing code The failure codes are displayed by a flashing sequence of the upper yellow LEDs run, run. Flashing frequence: env.,5 s on,,5 s off, end od the sequence: env. s off. It is possible that the two processors show different failure codes. If a failure is displayed, the relays K and K are switched off. These failures are serious and do t allow further operation of the module. They are indicated only by the LEDs run and / or run of the module. The semiconductor outputs 48 and 58 are both switched off. The module can only be reset by switching the power supply off and on again. N o * ) Description Mesures et conseils Internal module failure (LEDs are continuously off) If both LEDs stay off, the module is defective and has to be repaired. Variants BH 59/6: Characteristic with UL-approval 5 Adjustment failure ) The settings of the channels are t identically. ) The selected setting is t permitted. Switching voltage U [ V] M77_a 6 Undervoltage detection ou Overvoltage detection ) Left LED is flashing: The supply voltage dropped below the permitted value (< approx..85 U N ) ) Right LED is flashing: The supply voltage went over the permitted value (> approx..5 U N + 5 % residual ripple) ) A short circuit has been detected on the inputs of the unit Switching current I[A] safe breaking, continuous arcing under the curve, max. switching cycle/s Limit curve for arc-free operation 7 Input failure 8 Failure on relays K or K ) The signals of a -channel sensor ( button, light curtain) are t identical. (Short circuit, broken wire, other defects). Check circuit and current. Module has to be repaired. 9 Internal module failure Internal module failure Please try to evaluate the circumstances that lead to this fault and check with the supplier or manufacturer. The module has to be repaired 4 *) No.: Number of flash pulses in a series E. DOLD & SÖHNE KG D-784 Furtwangen PO Box 5 Telephone (+49) 77 / 654- Telefax (+49) 77 / dold-relays@dold.com internet: en / 45

Safety Technique. SAFEMASTER Light Curtain Controller With Selectable Operating Modes BH 5902/01MF2

Safety Technique. SAFEMASTER Light Curtain Controller With Selectable Operating Modes BH 5902/01MF2 Safety Technique SAFEMASTER Light Curtain Controller With Selectable Operating Modes BH 5902/01MF2 0237093 Block Diagram A1+ A2 S12 S14 S21 S22 S24 S23 S44 S43 13 23 33 PTC monitoring logic 1 galvanic

More information

Safety Technique. SAFEMASTER C Multifunctional Safety Timer UG 6960

Safety Technique. SAFEMASTER C Multifunctional Safety Timer UG 6960 Safety Technique SAFEMASTER C Multifunctional Safety Timer UG 6960 0269008 Product Description The multifunction safety timer UG 6960 provides protection of men machines by enabling disabling a safety

More information

Safety Technique. SAFEMASTER C Multifunctional Safety Timer UG 6961

Safety Technique. SAFEMASTER C Multifunctional Safety Timer UG 6961 Safety Technique SAFEMASTER C Multifunctional Safety Timer UG 6961 0269009 Your Advantage Various delay functions adjustable at device - Release delay - Release delay retriggerable - On delay - Fleeting

More information

Installation / Control Technique

Installation / Control Technique Installation / Control Technique Interface Relay, Interface Relay System Input-Output Interface Relay IK 3070, I_ 3070 0633 IK 3070 Circuit Diagrams IS 3070 According to IEC/EN 61 810-1 Relay, triac or

More information

Monitoring technique. VARIMETER Voltage relay MK 9064N, MH 9064

Monitoring technique. VARIMETER Voltage relay MK 9064N, MH 9064 Monitoring technique VARIMETER Voltage relay MK 9064N, MH 9064 0269462 Your Advantages Preventive maintenance For better productivity Quicker fault locating Precise and reliable Min-, Max. value or window

More information

ENGLISH. Terminals 13, 14, 23, 24, 43, 44, 53, Web: Phone: Toll Free:

ENGLISH. Terminals 13, 14, 23, 24, 43, 44, 53, Web:   Phone: Toll Free: Operating Manual ENGLISH 0266691 PRSU/M2SI Multifunctional Downstream Device ORIGINAL Before installing, operating or maintaining the device, read underst this manual. DANGER Dangerous tension. Danger

More information

Monitoring Technique. VARIMETER PRO Multifunction Measuring Relay MK 9300N, MH 9300

Monitoring Technique. VARIMETER PRO Multifunction Measuring Relay MK 9300N, MH 9300 Monitoring Technique VARIMETER PRO Multifunction Measuring Relay MK 93N, MH 93 268581 Product description MK 93N MH 93 The universal measuring relays MK 93N / MH 93 of the VARIMETER PRO series monitor

More information

Monitoring Technique. VARIMETER PRO Multifunction Measuring Relay MK 9300N, MH 9300

Monitoring Technique. VARIMETER PRO Multifunction Measuring Relay MK 9300N, MH 9300 Monitoring Technique VARIMETER PRO Multifunction Measuring Relay MK 93N, MH 93 268581 Product Description MK 93N MH 93 The universal measuring relays MK 93N / MH 93 of the VARIMETER PRO series monitor

More information

H S11I1A I2A I3A I4A I5A I6A I7A I8A S21I1C I2C I3C I4C I5C I6C I7C I8C 14A I 15A I 16A 13A I 13B 14B 15B 16B M8540

H S11I1A I2A I3A I4A I5A I6A I7A I8A S21I1C I2C I3C I4C I5C I6C I7C I8C 14A I 15A I 16A 13A I 13B 14B 15B 16B M8540 Safety Technique SAFEMASTER Emergency Stop Monitor BH 5922, BL 5922 34656 BH 5922 BL 5922 Circuit Diagrams To monitor max. 16 singlechannel estop buttons or 8 2channel estop buttons button can be connected

More information

E-STOP relays, safety gate monitors

E-STOP relays, safety gate monitors Safety relay for monitoring E-STOP pushbuttons, safety gates and light barriers. Approvals Block diagram Unit features Positive-guided relay outputs: 6 safety contacts (N/O), instantaneous 4 auxiliary

More information

Installation / control / monitoring technique. CANopen PLC IL 5504, IN 5504 minimaster

Installation / control / monitoring technique. CANopen PLC IL 5504, IN 5504 minimaster Installation / control / monitoring technique CANopen PLC IL, IN minimaster 6 Circuit diagram CAN H Rab C CAN L C IL IN C CAN H Rab CAN L C According to IEC/EN 6 -, EN 78 Operation as master - Operation

More information

Installation / Control / Monitoring Technique

Installation / Control / Monitoring Technique Installation / Control / Monitoring Technique MINIMASTER CANopen PLC IL, IN 6 Your Advantages Compact CAN-operation Graphical programming Qquick and easy installation Various input- / output module digital

More information

Datasheet - SRB 301LC/B-24V

Datasheet - SRB 301LC/B-24V 27.01.2016-00:27:16h Datasheet - SRB 301LC/B-24V Guard door monitors and Safety control modules for Emergency Stop applications / General Purpose safety controllers (Series PROTECT SRB) / SRB 301LC/B Fit

More information

Installation / control / monitoring technique. CANopen PLC IL 5504, IN 5504 minimaster

Installation / control / monitoring technique. CANopen PLC IL 5504, IN 5504 minimaster Installation / control / monitoring technique CANopen PLC IL, IN minimaster 6 Circuit diagram CAN H Rab CAN H CAN CAN L GND C C CAN L C C Rab M88_a IL IN CAN H CAN H Rab CAN CAN L GND C C Rab CAN L C C

More information

Two-hand control unit

Two-hand control unit Unit features Safety features Gertebild ][Bildunterschrift_Zweihand Two-hand control unit for press controllers and safety circuits Approvals Gertemerkmale Positive-guided relay outputs: 3 safety contacts

More information

Positive-guided relay outputs: 3 safety contacts (N/O), instantaneous. 1 auxiliary contact (N/C), instantaneous

Positive-guided relay outputs: 3 safety contacts (N/O), instantaneous. 1 auxiliary contact (N/C), instantaneous Two-hand control unit for press controllers and safety circuits Approvals Unit features Positive-guided relay outputs: 3 safety contacts (N/O), instantaneous 1 auxiliary contact (N/C), instantaneous 1

More information

H S11I1A I2A I3A I4A I5A I6A I7A I8A S21I1C I2C I3C I4C I5C I6C I7C I8C 14A I 15A I 16A 13A I 13B 14B 15B 16B M8540

H S11I1A I2A I3A I4A I5A I6A I7A I8A S21I1C I2C I3C I4C I5C I6C I7C I8C 14A I 15A I 16A 13A I 13B 14B 15B 16B M8540 Safety technique Emergencystop monitor BH 5922, BL 5922 safemaster Profibus 34656 BH 5922 BL 5922 Circuit diagrams I3A I4A X2 I3B I4B I3A I4A I5A I6A I7A According to SILClaimed Level (SIL CL) 1 to EN

More information

Datasheet - SRB 402EM-24V

Datasheet - SRB 402EM-24V Print - Create PDF - Create EXCEL file 20.04.2011-18:31:35h Datasheet - SRB 402EM-24V Output expanders / SRB 402EM Expander module for contact expansion 4 safety contacts, STOP 0 2 Signalling outputs (Minor

More information

Power Electronics. Semiconductor relay / - contactor

Power Electronics. Semiconductor relay / - contactor Power Electronics Semiconductor relay / - contactor PH 9260 POWERSWITCH 0247349 Semiconductor relay PH 9260.91 Semiconductor contactor PH 9260.91/000/01 AC semiconductor relay / -contactor According to

More information

Safety technique. Emergency-stop monitor BH 5922, BL 5922 safemaster

Safety technique. Emergency-stop monitor BH 5922, BL 5922 safemaster Safety technique Emergencystop monitor BH 5922, BL 5922 safemaster 34656 Approvals and marking Applied for patent To monitor max. 8 singlechannel or 2channel estop buttons button can be connected directly

More information

Datasheet SRB301ST 24V (V.2)

Datasheet SRB301ST 24V (V.2) 26.10.2016 05:03:31h Datasheet SRB301ST 24V (V.2) Guard door monitors and Safety control modules for Emergency Stop applications / General Purpose safety controllers (Series PROTECT SRB) / SRB301ST Suitable

More information

Two-hand control unit

Two-hand control unit Unit features Safety features Gertebild Bildunterschrift_gertespezifisch Two-hand control device for safety circuits Approvals Gertemerkmale Positive-guided relay outputs: 2 safety contacts (N/O), instantaneous

More information

E-STOP relay, safety gate monitor

E-STOP relay, safety gate monitor Safety relay for monitoring E-STOP pushbuttons, safety gates and light barriers. Approvals Unit features Positive-guided relay outputs: 2 safety contacts (N/O), instantaneous 1 semiconductor output Connection

More information

PSR-MS60. Safety relay for emergency stop, safety door and light grid monitoring. Data sheet. 1 Description

PSR-MS60. Safety relay for emergency stop, safety door and light grid monitoring. Data sheet. 1 Description SILCL IEC 62061 Safety relay for emergency stop, safety door and light grid monitoring Data sheet 106171_en_01 PHOENIX CONTACT 2015-05-19 1 Description Intended Use The PSR-MS60 safety relay can be used

More information

Positive-guided relay outputs: 3 safety contacts (N/O), instantaneous. 1 auxiliary contact (N/C), instantaneous

Positive-guided relay outputs: 3 safety contacts (N/O), instantaneous. 1 auxiliary contact (N/C), instantaneous Gertebild Bildunterschrift Two-hand control device for safety circuits Approvals Zulassungen Unit features Gertemerkmale Positive-guided relay outputs: 3 safety contacts (N/O), instantaneous 1 auxiliary

More information

Safe timer relay/contact expansion modules

Safe timer relay/contact expansion modules Contact expander module for increasing the number of available contacts, Pulse-on timer relay for step-by-step control of movement sequences, Delay-on energisation timer for unlocking an interlock with

More information

Positive-guided relay outputs: 3 safety contacts (N/O), instantaneous. 1 auxiliary contact (N/C), instantaneous

Positive-guided relay outputs: 3 safety contacts (N/O), instantaneous. 1 auxiliary contact (N/C), instantaneous Safety relay for monitoring E-STOP pushbuttons. Approvals Unit features Positive-guided relay outputs: 3 safety contacts (N/O), instantaneous 1 auxiliary contact (N/C), instantaneous Safe separation of

More information

Technical data. Dimensions: see page 116. ): 4 kv Rated insulation voltage (U i Over-voltage category: Power supply. Rated operating voltage (Un):

Technical data. Dimensions: see page 116. ): 4 kv Rated insulation voltage (U i Over-voltage category: Power supply. Rated operating voltage (Un): Safety module CS AR-91, according to EN 81 Safety modules for the lift automatic floor levelling operation according to EN 81 Main functions For safety applications up to SIL 3 / PL e Choice between automatic

More information

SAFETY RELAY YRB-4EML-31S MAIN FEATURES

SAFETY RELAY YRB-4EML-31S MAIN FEATURES SAFETY RELAY TYPE 4 SAFETY PROTECTION DEVICE FOR SAFETY LIGHT CURTAINS/BARRIERS MAIN FEATURES For safety light curtains and access control barriers, emergency stop, door switch Safety Integrity Level (SIL)

More information

E-STOP relays, safety gate monitors

E-STOP relays, safety gate monitors Unit features Safety features Gertebild ][Bildunterschrift Safety relay for monitoring E-STOP pushbuttons and safety gates. Approvals Kein Gerätebild vorhanden Gertemerkmale Positive-guided relay outputs:

More information

E-STOP relays, safety gate monitors

E-STOP relays, safety gate monitors Unit features Safety gates Gertebild ][Bildunterschrift_NOT_Sch.tuer_Licht Safety relay for monitoring E-STOP pushbuttons, safety gates and light beam devices Approvals Gertemerkmale Positive-guided relay

More information

Technical data. Safety parameters: see page 333. DC maximum residual ripple: 10% Supply voltage tolerance: DC consumption: Control circuit

Technical data. Safety parameters: see page 333. DC maximum residual ripple: 10% Supply voltage tolerance: DC consumption: Control circuit Safety module CS DM-01 Technical data Housing PA 6.6 polyamide housing, self-extinguishing, V0 acc. to UL 94 Protection degree IP40 (housing), IP20 (terminal strip) Dimensions see page 283, design A Two-hand

More information

E-STOP relays, safety gate monitors

E-STOP relays, safety gate monitors Safety relay for monitoring E-STOP pushbuttons and safety gates. Approvals Unit features Positive-guided relay outputs: 3 safety contacts (N/O), instantaneous 2 safety contacts (N/O), delay-on de-energisation

More information

E-STOP relays, safety gate monitors

E-STOP relays, safety gate monitors Unit features Safety features Gertebild ][Bildunterschrift_NOT_Sch.tuer_Licht Safety relay for monitoring E-STOP pushbuttons, safety gates and light beam devices Approvals Gertemerkmale Positive-guided

More information

Contact protection relay

Contact protection relay Contact protection relay Ordering details SVR 450 08 F0000 The protects sensitive control contacts from excessive load. It can be used with latching function or without. Bounce time of control contacts

More information

E-STOP relay, safety gate monitor

E-STOP relay, safety gate monitor Unit features Safety features Gertebild ][Bildunterschrift Safety relay for monitoring E-STOP pushbuttons and safety gates. Approvals Gertemerkmale Positive-guided relay outputs: 7 safety contacts (N/O),

More information

E-STOP relays, safety gate monitors

E-STOP relays, safety gate monitors Safety relay for monitoring E-STOP pushbuttons and safety gates. Approvals Unit features Positive-guided relay outputs: 2 safety contacts (N/O), instantaneous 2 safety contacts (N/O), delay-on de-energisation

More information

E-STOP relays, safety gate monitors

E-STOP relays, safety gate monitors Gertebild ][Bildunterschrift Safety relay for monitoring E-STOP pushbuttons and safety gates. Approvals Unit features Gertemerkmale Relay outputs: 2 safety contacts (N/O), instantaneous 1 semiconductor

More information

Technical data. Housing Polyamide housing PA 66, self-extinguishing V0 acc. to UL 94. Supply Rated supply voltage (U n

Technical data. Housing Polyamide housing PA 66, self-extinguishing V0 acc. to UL 94. Supply Rated supply voltage (U n Safety module CS AT 0 Module for emergency stops, end position monitoring for movable guards with delayed contacts at the opening of the input channels, semiconductor outputs (e.g. light barriers and magnetic

More information

Two-hand control unit

Two-hand control unit Gertebild ][Bildunterschrift_Zweihand Two-hand control unit for press controllers and safety circuits Approvals Unit features Gertemerkmale Positive-guided relay outputs: 3 safety contacts (N/O), instantaneous

More information

Dold BH5928 Series 2-Channel Emergency Stop and Safety Gates with Delay

Dold BH5928 Series 2-Channel Emergency Stop and Safety Gates with Delay Dold Series 2-Channel Emergency Stop and Safety Gates with Delay -92-61-24-1 Part umber Price Marking Type Voltage Outputs Time Delay -92-61-24-1 2-channel E-STOP / GATE 24 VDC 3.O. time delay positive

More information

Safe monitoring relays

Safe monitoring relays Unit features Unit description Gertebild ][Bildunterschrift_Stillstandswchter Standstill monitor for safe standstill monitoring Approvals Zulassungen Gertemerkmale Positive-guided relay outputs: 2 safety

More information

Original operating instructions Safety relay with relay outputs G1501S / / 2016

Original operating instructions Safety relay with relay outputs G1501S / / 2016 Original operating instructions Safety relay with relay outputs G50S UK 8023637 / 00 02 / 206 Contents Preliminary note...4. Symbols used...4 2 Safety instructions...5 3 Items supplied...6 4 Functions

More information

E-STOP relays, safety gate monitors

E-STOP relays, safety gate monitors Safety relay for monitoring E-STOP pushbuttons, safety gates and light barriers. Approvals Unit features Positive-guided relay outputs: 7 safety contacts (N/O), instantaneous 2 auxiliary contacts (N/C),

More information

E-STOP relays, safety gate monitors

E-STOP relays, safety gate monitors Unit features Safety features Gertebild ][Bildunterschrift Safety relay for monitoring E-STOP pushbuttons and safety gates. Approvals Gertemerkmale Positive-guided relay outputs: 2 safety contacts (N/O),

More information

Vital. Safety controller. Approvals: Control of: Features: Entire safety system based on the dynamic safety circuit.

Vital. Safety controller. Approvals: Control of: Features: Entire safety system based on the dynamic safety circuit. Safety controller Vital Approvals: TÜV Nord Vital 1 TÜV Rheinland Vital and 3 Control of: Entire safety system based on the dynamic safety circuit. Features: Vital is based on a single channel safety concept

More information

Original operating instructions Safety relay with relay outputs with and without delay G1502S / / 2016

Original operating instructions Safety relay with relay outputs with and without delay G1502S / / 2016 Original operating instructions Safety relay with relay outputs with and without delay UK G50S 803638 / 00 0 / 06 Contents Preliminary note...4. Symbols used...4 Safety instructions...5 3 Items supplied...6

More information

E-STOP relays, safety gate monitors

E-STOP relays, safety gate monitors Unit features Safety features Gertebild ][Bildunterschrift_NOT_Sch.tuer_Licht Safety relay for monitoring E-STOP pushbuttons, safety gates and light beam devices Gertemerkmale Positive-guided relay outputs:

More information

Faults on the system Proximity switch connection technology:

Faults on the system Proximity switch connection technology: Speed monitor for connection to a base unit from the PNOZmulti modular safety system Approvals Unit features Monitoring of 2 independent axes Connection of 2 incremental encoders or 4 proximity switches

More information

Positive-guided relay outputs: 4 safety contacts (N/O), instantaneous

Positive-guided relay outputs: 4 safety contacts (N/O), instantaneous ohne Abbildung Contact expansion module for increasing the number of available contacts Approvals PZE X4.1P with universal power supply Unit features Positive-guided relay outputs: 4 safety contacts (N/O),

More information

PNOZ s1. Safety relays. Operating Manual EN-07

PNOZ s1. Safety relays. Operating Manual EN-07 Safety relays Operating Manual- Preface This document is the original document. All rights to this documentation are reserved by Pilz GmbH & Co. KG. Copies may be made for internal purposes. Suggestions

More information

Positive-guided relay outputs: 3 safety contacts (N/O), instantaneous

Positive-guided relay outputs: 3 safety contacts (N/O), instantaneous Gertebild ][Bildunterschrift Kontakterweiterungen Contact for increasing the number of available contacts Approvals Unit features Gertemerkmale Positive-guided relay outputs: 3 safety contacts (N/O), instantaneous

More information

SNO 4062K SNO 4062KM SNO 4062 K / KM. Circuit diagram. Applications. Function. Function (Continued)

SNO 4062K SNO 4062KM SNO 4062 K / KM. Circuit diagram. Applications. Function. Function (Continued) SNO 4062K SNO 4062 K / KM Basic unit for emergency stop and guard door applications Basic unit as per DIN EN 60204-1 and EN ISO 13849-1 for single or twin channel emergency stop monitoring. PL e and category

More information

Datasheet - SLB 200-C04-1R

Datasheet - SLB 200-C04-1R 14.02.2013-17:06:30h Datasheet - SLB 200-C04-1R Safety light barriers / Safety monitoring modules to monitor safety light barriers / SLB 200-C Up to 2 light barrier pairs SLB 200 can be connected 1 safety

More information

E-STOP relays, safety gate monitors

E-STOP relays, safety gate monitors Unit features Positive-guided relay outputs: 2 safety contacts (N/O), instantaneous Connection options for: E-STOP pushbutton Reset button LED indicator for: Switch status channel 1/2 Supply voltage See

More information

E-STOP relays, safety gate monitors

E-STOP relays, safety gate monitors Unit features Safety features Gertebild ][Bildunterschrift_NOT_Sch.tuer_Licht Safety relay for monitoring E-STOP pushbuttons, safety gates and light beam devices Gertemerkmale Positive-guided relay outputs:

More information

Safety relays PNOZsigma

Safety relays PNOZsigma Safety relays PNOZsigma Configuration guide, safety relays PNOZsigma Technical catalogue 3.2 November 2008 edition Why does Pilz offer more? Because the integrality of our business activities is what sets

More information

E-STOP relays, safety gate monitors

E-STOP relays, safety gate monitors Gertebild ][Bildunterschrift Safety relay for monitoring E-STOP pushbuttons and safety gates. Unit features Gertemerkmale Positive-guided relay outputs: 3 safety contacts (N/O), instantaneous Connection

More information

Safe monitoring relays

Safe monitoring relays monitor for safe standstill monitoring Approvals Block diagram Unit features Positive-guided relay outputs: 2 safety contacts (N/O), instantaneous 1 auxiliary contact (N/C), instantaneous LED indicator

More information

E-STOP relays, safety gate monitors

E-STOP relays, safety gate monitors Unit features Gertemerkmale Positive-guided relay outputs: 2 safety contacts (N/O), instantaneous Connection options for: E-STOP pushbutton Safety gate limit switch Reset button Light barriers LED indicator

More information

E-STOP relays, safety gate monitors

E-STOP relays, safety gate monitors Unit features Safety features Gertebild ][Bildunterschrift_nur_Not-Halt Safety relay for monitoring E-STOP pushbuttons Approvals Gertemerkmale Positive-guided relay outputs: 3 safety contacts (N/O), instantaneous

More information

E-STOP relays, safety gate monitors

E-STOP relays, safety gate monitors Unit features Safety features Gertebild ][Bildunterschrift Safety relay for monitoring E-STOP pushbuttons and safety gates. Approvals Gertemerkmale Positive-guided relay outputs: 3 safety contacts (N/O),

More information

AS-i Safety Relay Output Module with Diagnostic Slave and 1 EDM Input

AS-i Safety Relay Output Module with Diagnostic Slave and 1 EDM Input Safety + standard I/O in one module Safety relay output with galvanically isolated contact sets, approved up to 230 V IEC 61508 SIL 3, EN ISO 13849-1/PLe Kat 4, EN 62061 SIL 3 Protection category IP20

More information

Positive-guided relay outputs: 3 safety contacts (N/O), instantaneous. 1 auxiliary contact (N/C), instantaneous

Positive-guided relay outputs: 3 safety contacts (N/O), instantaneous. 1 auxiliary contact (N/C), instantaneous Unit features Safety features Gertebild ][Bildunterschrift_nur_Not-Halt Safety relay for monitoring E-STOP pushbuttons Approvals Gertemerkmale Positive-guided relay outputs: 3 safety contacts (N/O), instantaneous

More information

Can be configured in the PNOZmulti Configurator Semiconductor outputs: or 4 safety outputs in accordance with EN 954-1, Cat. 3

Can be configured in the PNOZmulti Configurator Semiconductor outputs: or 4 safety outputs in accordance with EN 954-1, Cat. 3 Products Expansion Gertebild mo1p modules PNOZmulti Verwendung/Bildunterschrift_multi_Modul Expansion module for connection to a base unit from the configurable control system PNOZmulti Approvals Unit

More information

VEO. V2UF230V10 Art.Nr.: TECHNICAL DATA

VEO. V2UF230V10 Art.Nr.: TECHNICAL DATA Continous voltage monitoring Mains fluctuation detection Detects voltage drop / short interruptions of at least 10ms Prevents undefined states in switching and control systems Generates reset pulse after

More information

PSR DC/ESP4/2X1/1X2

PSR DC/ESP4/2X1/1X2 PSR-...- 24DC/ESP4/2X1/1X2 Safety relay for emergency stop and safety door monitoring Data sheet 100516_en_05 PHOENIX CONTACT 2013-11-21 1 Description The safety relay can be used for emergency stop and

More information

Safety relay emergency stop/protective door, 24VDC/AC, 4 enabling paths

Safety relay emergency stop/protective door, 24VDC/AC, 4 enabling paths DATASHEET - ESR5-NO-41-24VAC-DC Safety relay emergency stop/protective door, 24VDC/AC, 4 enabling paths Part no. ESR5-NO-41-24VAC-DC Catalog No. 118701 EL-Nummer (Norway) 0004133317 Delivery program Product

More information

E-STOP relay, safety gate monitor

E-STOP relay, safety gate monitor Safety relay for monitoring E-STOP pushbuttons and safety gates. Approvals Unit features Positive-guided relay outputs: 2 safety contacts (N/O), instantaneous 1 semiconductor output Connection options

More information

SNO 4003 K plus. Areas of application for the unit. Connection circuit diagrams. Intended use. Competent persons. Equipment and functional description

SNO 4003 K plus. Areas of application for the unit. Connection circuit diagrams. Intended use. Competent persons. Equipment and functional description SNO 4003 K plus Safety relay for emergency stop and guard door applications SILCL2 in accordance with EN 62061 PL d, Category 3 in accordance with EN ISO 13849-1 Stop category 0 in accordance with DIN

More information

E-STOP relays, safety gate monitors

E-STOP relays, safety gate monitors Safety relay for monitoring E-STOP pushbuttons and safety gates. Approvals Unit features Positive-guided relay outputs: 5 safety contacts (N/O), instantaneous 1 auxiliary contact (N/C), instantaneous Connection

More information

E-STOP relays, safety gate monitors

E-STOP relays, safety gate monitors E-STOP relays, safety gate monitors Up to Category 2, EN 954-1 Unit features Positive-guided relay outputs: 2 safety contacts (N/O), instantaneous Connection options for: E-STOP pushbutton Reset button

More information

RM4TR31 three-phase network control relay RM4-T - range V

RM4TR31 three-phase network control relay RM4-T - range V Characteristics three-phase network control relay RM4-T - range 160..220 V Complementary [Us] rated supply voltage Control threshold undervoltage Control threshold overvoltage Output contacts Main Range

More information

MINI-PS AC/10-15DC/8

MINI-PS AC/10-15DC/8 Primary-Switched Power Supply, Narrow Design Data Sheet 08/2004 MINI POWER provides: An extra narrow design, with widths of 22.5 mm, 45 mm, and 67.5 mm (0.886, 1.772, and 2.657 in.) Global use due to a

More information

E-STOP relays, safety gate monitors

E-STOP relays, safety gate monitors Unit features Safety features Gertebild ][Bildunterschrift_nur_Not-Halt Safety relay for monitoring E-STOP pushbuttons Approvals Gertemerkmale Positive-guided relay outputs: 3 safety contacts (N/O), instantaneous

More information

E-STOP relays, safety gate monitors

E-STOP relays, safety gate monitors Gertebild ][Bildunterschrift Safety relay for monitoring E-STOP pushbuttons and safety gates. Approvals Unit features Gertemerkmale Positive-guided relay outputs: 2 safety contacts (N/O), instantaneous

More information

Electronic timer CT-ERD.12

Electronic timer CT-ERD.12 2CDC 251 092 F0t06 a Rotary switch for the preselection of the time range b Potentiometer with direct reading scale for the fine adjustment of the time delay c U: green LED V control supply voltage applied

More information

Contact expander modules

Contact expander modules Gertebild ][Bildunterschrift Kontakterweiterungen Contact expansion module for increasing the number of available contacts Approvals Zulassungen Unit features Gertemerkmale Positive-guided relay outputs:

More information

VEO. V2PF480Y/277VSY01 Art.Nr.: V2PF480Y/277VSY01P Art.Nr.: TECHNICAL DATA

VEO. V2PF480Y/277VSY01 Art.Nr.: V2PF480Y/277VSY01P Art.Nr.: TECHNICAL DATA Monitoring of phase sequence and phase loss Monitoring of asymmetry Supply voltage 208-480 V AC Supply circuit = measuring circuit 1 change-over contact Width 22,5 mm Control elements Asymmetry Status

More information

VEO. V2ZS V AC/DC Art.Nr.: V2ZS20P V AC/DC Art.Nr.: TECHNICAL DATA

VEO. V2ZS V AC/DC Art.Nr.: V2ZS20P V AC/DC Art.Nr.: TECHNICAL DATA 4 time ranges 4 transition times Supply voltage 12-240V AC/DC 2 normally open contacts Width 22,5 mm Control elements Fine adjustment star contactor Setting of time range star contactor Transit time Status

More information

Electronic timer CT-AHD.22

Electronic timer CT-AHD.22 2CDC 251 093 F0t06 a Rotary switch for the preselection of the time range b Potentiometer with direct reading scale for the fine adjustment of the time delay c U: green LED V control supply voltage applied

More information

Control elements. Fine adjustment. Status indication. 24 V DC typ. 0,25 W / 0,25 VA. 24 V DC typ. 0,03 W / 0,09 VA. 0,15 3 s. 0,5 10 h.

Control elements. Fine adjustment. Status indication. 24 V DC typ. 0,25 W / 0,25 VA. 24 V DC typ. 0,03 W / 0,09 VA. 0,15 3 s. 0,5 10 h. On-Delay 10 time ranges Supply voltage 24-240V AC/DC 1 change-over contact Width 22,5mm Control elements Fine adjustment Setting of time range Status indication LED U/t: Supply voltage LED R: Relay status

More information

RE7RB13MW adjustable off-delay timing relay s V AC DC - 2OC

RE7RB13MW adjustable off-delay timing relay s V AC DC - 2OC Characteristics adjustable off-delay timing relay - 0.05..1 s - 240 V AC DC - 2OC Main Range of product Product or component type Contacts type and composition Component name Time delay type Time delay

More information

PSR-PC50. SIL 3 coupling relay for safety-related switch on. Data sheet. 1 Description

PSR-PC50. SIL 3 coupling relay for safety-related switch on. Data sheet. 1 Description SIL 3 coupling relay for safety-related switch on Data sheet 105818_en_01 PHOENIX CONTACT 2014-08-18 1 Description The PSR-PC50 SIL coupling relay can be used for power adaptation and electrical isolation

More information

VEO. V2ZR V AC/DC Art.Nr.: V2ZR10P V AC/DC Art.Nr.: TECHNICAL DATA

VEO. V2ZR V AC/DC Art.Nr.: V2ZR10P V AC/DC Art.Nr.: TECHNICAL DATA Off-Delay 10 time ranges Supply voltage 24-240V AC/DC 1 change-over contact Width 22,5 mm Control elements Fine adjustment Setting of time range Status indication LED U/t: Supply voltage LED R: Relay status

More information

Positive-guided relay outputs: 4 safety contacts (N/O), instantaneous

Positive-guided relay outputs: 4 safety contacts (N/O), instantaneous Contact expander module for increasing the number of available contacts Approvals Unit features Positive-guided relay outputs: 4 safety contacts (N/O), instantaneous LED indicator for: Switch status channel

More information

PHOENIX CONTACT - 07/2006

PHOENIX CONTACT - 07/2006 Buffer module with maintenance-free capacitor-based power storage device INTERFACE Data sheet 102035_03_en PHOENIX CONTACT - 07/2006 Description Short-term mains interruptions are bridged by QUINT BUFFER,

More information

PNOZ s2. Safety relays. Operating Manual EN-07

PNOZ s2. Safety relays. Operating Manual EN-07 Safety relays Operating Manual- Preface This document is the original document. All rights to this documentation are reserved by Pilz GmbH & Co. KG. Copies may be made for internal purposes. Suggestions

More information

RE7YA12BU time delay relay for star-delta starter s - 24 V AC DC - 2OC

RE7YA12BU time delay relay for star-delta starter s - 24 V AC DC - 2OC Characteristics time delay relay for star-delta starter - 0.05..1 s - 24 V AC DC - 2OC Main Range of product Product or component type Contacts type and composition Component name Time delay type Time

More information

E-STOP relays, safety gate monitors

E-STOP relays, safety gate monitors Unit features Positive-guided relay outputs: 2 safety contacts (/O), instantaneous Connection options for: E-STOP pushbutton Reset button LED indicator for: Switch status channel 1/2 Supply voltage See

More information

BNS SERIES - COMPATIBLE SERIES AES SAFETY CONTROLLERS SELECTION CHART AVAILABLE STANDARD MODELS

BNS SERIES - COMPATIBLE SERIES AES SAFETY CONTROLLERS SELECTION CHART AVAILABLE STANDARD MODELS BNS SERIES - COMPATIBLE SERIES AES SAFETY CONTROLLERS SELECTION CHART AVAILABLE STANDARD MODELS Safety Controller Suitable for use with Coded-Magnet Sensor Part Numbers below BNS250... BNS33... BNS303...

More information

RM4TA32 three-phase network control relay RM4-T - range V

RM4TA32 three-phase network control relay RM4-T - range V Characteristics three-phase network control relay RM4-T - range 380..500 V Complementary [Us] rated supply voltage Output contacts Main Range of product Product or component type Relay type Product specific

More information

PNOZ s9. Safety relays. Operating Manual EN-08

PNOZ s9. Safety relays. Operating Manual EN-08 Safety relays Operating Manual- Preface This document is the original document. All rights to this documentation are reserved by Pilz GmbH & Co. KG. Copies may be made for internal purposes. Suggestions

More information

Electronic timer CT-ERS.12 ON-delayed with 1 c/o contact Data sheet

Electronic timer CT-ERS.12 ON-delayed with 1 c/o contact Data sheet 2CDC 251 056 F0t07 Features Rated control supply voltage 24-48 V DC, 24-240 V AC Single-function ON-delay timer One device includes 10 time ranges (0.05 s - 300 h) 1 c/o contact 2 LEDs for status indication

More information

RE22R2QGMR Star-Delta Timing Relay s 300h V AC/DC - 2C/O

RE22R2QGMR Star-Delta Timing Relay s 300h V AC/DC - 2C/O Characteristics Star-Delta Timing Relay - 0.05s 300h - 24 240V AC/DC - 2C/O Main Range of product Product or component type Discrete output type Device short name Nominal output current Complementary Contacts

More information

PSR-PS21. SIL coupling relay. Data sheet. 1 Description

PSR-PS21. SIL coupling relay. Data sheet. 1 Description SIL coupling relay Data sheet 106253_en_00 PHOENIX CONTACT 2015-03-13 1 Description Intended Use The SIL coupling relay can be used for power adaptation and electrical isolation in high and low-demand

More information

Zelio Control-modular measurement and control relays 1

Zelio Control-modular measurement and control relays 1 Presentation, description 1 106439 RM35 TM111MW Presentation Motor temperature measurement and 50MW and RM35 TM250MW monitor the following, on 3-phase supplies: correct sequencing of phases L1, L2 and

More information

Safety Switching Devices SNO 4003K. Basic device for Emergency-Stop and Safety Gate Applications PI E

Safety Switching Devices SNO 4003K. Basic device for Emergency-Stop and Safety Gate Applications PI E EN 60204-1 Stop category 0 EN 954-1 Safety category 4 Basic device to EN 60204-1 and EN 954-1 single E-stop monitoring. Manual or automatic start Application up to safety category 2 and stop category 0

More information

Power supply CP-C 24/5.0

Power supply CP-C 24/5.0 2CDC 271 064 F0004 Features Supply voltage ranges: 85-264 V AC, 100-350 V DC Output voltage adjustable from 22-28 V DC, default setting 24 V DC 0,5 % 5 A output current Open-circuit, overload and continous

More information

Safe timer relay/contact expansion modules

Safe timer relay/contact expansion modules Gertebild Bildunterschrift Contact expander module for increasing the number of available contacts, Pulse-on timer relay for step-by-step control of movement sequences, Delay-on energisation timer for

More information