PoP ROOM: INSIDE AND OUTSIDE PLANT RULES & REGULATIONS

Size: px
Start display at page:

Download "PoP ROOM: INSIDE AND OUTSIDE PLANT RULES & REGULATIONS"

Transcription

1 PoP ROOM: INSIDE AND OUTSIDE PLANT RULES & REGULATIONS Version 14 November 19, 2014 Digital Realty

2 Table of Contents INTRODUCTION... 3 ACCESS TO THE POP ROOMS, ISP & OSP... 3 PoP- MoP Forms... 3 Who must submit a PoP- MoP?... 4 Scheduled Access... 5 Carrier Emergency Access... 5 After Hours Access... 5 SECURITY... 6 RULES FOR POP ROOMS... 6 PROHIBITED PRACTICES IN POP ROOMS... 7 RULES FOR CABLE INSTALLATIONS WITHIN POP ROOMS... 8 PROHIBITED PRACTICES REGARDING ISP & OSP... 9 ELECTRICAL DISTRIBUTION... 9 NEW CONDUIT INSTALLATIONS...10 PRE-ACTIVATION CHECK...10 CABINET AND RELAY RACK INSTALLATIONS...10 LABELING STANDARD...12 DELIVERY OF EQUIPMENT...13 EXHIBIT A: Datacenter Customer PoP-MoP...14 EXHIBIT B: Carrier PoP- MoP...18 Pop Room: Inside and Outside Plant Rules and Regulations Page 2

3 INTRODUCTION Digital Realty s Point of Presence (PoP) Rooms, Inside Plant (ISP) and Outside Plant (OSP) are classified as Mission Critical due to the central role they play in connecting Customers to Carriers and the outside world. All work performed in the PoP Rooms, ISP & OSP must be done in accordance with these Rules & Regulations. These requirements will contribute to providing a safe environment and facilitate the timely, secure and uninterrupted delivery of telecommunications services. It will allow for 24 X 7 X 365 access. ACCESS TO THE POP ROOMS, ISP & OSP 1. Only Customers or Carriers with pathway(s) or premises granted to them in a lease, PoP Room Rider or Carrier Access Contract/Carrier Service Agreement can request access to the PoP Rooms, ISP or OSP. 2. Customers and Carriers must request access to the PoP Rooms, ISP and OSP on behalf of their Vendors and Contractors. 3. Vendors and Contractors cannot request access directly. PoP- MoP Forms 1. There are two PoP-MoP forms: a. Customer PoP-MoP See Exhibit A Datacenter Customer PoP-MoP b. Carrier PoP-MoP See Exhibit B Carrier PoP-MoP 2. Establishes which entity Customer or Carrier--is requiring access to the PoP Room, ISP or OSP. 3. Requires that a Carrier requesting real time access due to an emergency must provide brief description of the emergency wiith name(s) of datacenter Customer(s) affected. 4. Requires full contact information for the senior person from the Customer or the Carrier coordinating and/or requiring access to the PoP, ISP or OSP. 5. Requires the names of everyone from the Customers or the Carrier requiring access to the PoP, ISP or OSP. 6. Requires full contact information for the senior person from the Vendor or Contractor requiring access to the PoP, ISP or OSP. 7. Requires the names of everyone from the Vendor or Contractor requiring access to the PoP, ISP or OSP. Pop Room: Inside and Outside Plant Rules and Regulations Page 3

4 8. Establishes where the work will be performed. a. PoP Room i. Customer or Carrier licensed pathway and/or premise: a) Rack, ¼ rack, quad cabinet or RU(s) ii. Common Area a) Vertical & horizontal ladder rack and fiber guide b) ISP & OSP iii. Customer pathway a) Ducts and conduits b) Innerduct or Maxcell sleeve. iv. Common area a) Man holes vaults, hand holes, junction and pull boxes, cab, etc. 9. Requires the date(s) and time(s) that access is required. Who must submit a PoP- MoP? 1. Customers and Carriers requesting access to the PoPs, ISP and/or OSP 2. Datacenter Customers submit Customer PoP-MoP a. For Customer s employees requesting access to the PoP Rooms or ISP b. On behalf of their Vendors or Contractors c. Customer s employees who are merely visiting and not working in the PoP Room or ISP only need to complete page 1 of the Customer-PoP-MoP 3. Carriers submit Carrier PoP-MoP a. Carrier employees requesting access to the PoP Rooms, ISP or OSP b. On behalf of their Vendors or Contractors 4. Remote Hands do not need to submit a PoP-MoP when performing cross-connects Pop Room: Inside and Outside Plant Rules and Regulations Page 4

5 Scheduled Access 1. The appropriate PoP-MoP must be fully completed and submitted by the Customer or Carrier 48 hours in advance of the requested access via a. Customer Portal, or b. to 2. The PoP-MoP must be approved by Building Management before access is granted. 3. An approved PoP- MoP is required for access to the PoP Room, ISP & OSP even if there will only be a visit and no work will be performed. Carrier Emergency Access 1. The Carrier PoP-MoP must be fully completed and submitted by the Carrier a. Via to Customer Portal, b. Via Customer to Customerservice@digitalrealty.com, c. Via hard copy to Building Management in business hours, or d. Via hard copy to Security after hours 2. A description of the emergency including any impact on other Customers is required. 3. The PoP-MoP must be approved by Building Management before access is granted. After Hours Access 1. The correct PoP-MoP must be fully completed and submitted by the Customer or Carrier a. Via to Customerservice@digitalrealtytrust.com, b. Via Customer Portal, or c. Via hard copy to Security 2. The PoP-MoP must be approved by Building Management before access is granted. Pop Room: Inside and Outside Plant Rules and Regulations Page 5

6 SECURITY 1. All persons accessing the PoP Rooms, ISP & OSP must be in possession of a valid Customer or visitor badge. 2. All Carriers, Vendors and Contractors requesting access to the PoP Rooms, ISP & OSP must show a Government issued ID to Security to obtain a visitors badge. 3. All Carriers Vendors and Contractors accessing the PoP Rooms, ISP & OSP must be escorted by Building Management or Security. 4. Building Management or Security escort will remain with the Customer, Carrier Vendor or Contractor for the duration of a visit or while work is being performed. 5. All persons entering a PoP Room will register their Customer or visitor badge at the card reader before entering. 6. Any person not complying with Security requirements will be denied access to, or ejected from the PoP Rooms, ISP & OSP. RULES FOR POP ROOMS 1. Customers are only authorized to work in the area(s) identified in an approved PoP- MoP. 2. Work must be performed in a professional manner; it must comply with industry standards and the standards set forth in the PoP Room, ISP & OSP Rules & Regulations. a. Building Management reserves the right to have the work removed or replaced in the event that it does not meet these standards. 3. Extreme care should be used at all time when working in a PoP Room. 4. Customers must remove any trash before they leave the PoP Room. 5. Customers are obliged to keep their space neat and clean. 6. At completion of the work and prior to activation (see Pre-Activation Check), the Customer must notify Building Management, so that the work can be inspected and verified against these Rules & Regulations and the approved PoP-MoP. 7. All incidents must be reported to Building Management immediately. Pop Room: Inside and Outside Plant Rules and Regulations Page 6

7 8. All incidents after hours must be reported to Security immediately. 9. Building Management will audit Customer equipment on a continual basis and shall notify Customers if corrections are required. PROHIBITED PRACTICES IN POP ROOMS 1. Working in areas (Customer/common area) not identified in the approved PoP-MoP. 2. Splicing outside of a Customer s or Carriers licensed area (cabinet, relay rack or ¼ relay racks). 3. Leaving slack loops anywhere but in a location approved in writing by Building Management 4. Deploying splice cans 5. Mounting anything on walls without specific written permission from Building Management or called out in a POP Rider, Carrier Access Contract or Carrier Service Agreement. 6. Tampering with the access control system, HVAC settings, airflow, cameras, fire alarms, smoke detectors and signage. 7. Tailgating: a. i.e. following someone into the PoP Room without registering a visitor s or Customer s badge. b. Opening the POP door to allow a person into the space without using biometric access device 8. Propping POP room door open for any reason. 9. Eating, drinking or smoking. 10. Taking photographs or video. 11. Using a PoP Room to store anything. a. Building Management or Security will dispose of any such articles. 12. Leaving any articles behind after hours. a. Building Management or Security will dispose of any such articles. Pop Room: Inside and Outside Plant Rules and Regulations Page 7

8 RULES FOR CABLE INSTALLATIONS WITHIN POP ROOMS 1. Signal Cable: Defined as any cable transmitting a signal over fiber, copper or coax. These cables must be installed on the bottom tier of ladder rack in the POP rooms. 2. All Signal cables must be plenum rated when entering from a Customer s suite or space. 3. All horizontal cabling will be attached to horizontal ladder rack, and all vertical cabling will be attached to a vertical ladder rack or cable management system. a. Inner-duct is not required in the POP rooms. b. If innerduct is required this will be ran on the bottom tier of ladder rack. c. All cabling and innerduct must waterfall over the side of the ladder rack and not through the rungs of the ladder. This must also not block or obstruct any equipment, device, outlet or cable management systems within the cabling footprint. d. All cabling must be fastened to vertical & horizontal ladder rack with #12 stitching/lace wax cord. Velcro may be used if installer cannot stitch/lace. e. Tie-Wraps are not allowed as a permanent fastening solution. Tie-wraps can only serve as a temporary solution during installation or build. 4. All fiber cross-connects, jumpers and patch cables must be run in POP room provided ADC FiberGuide System, where installed. These must not be run in innerduct and or on any ladder racking. 5. Any copper or coax cross-connects, jumpers and patch cables must run on the signal ladder rack. These must not be run in innerduct and must follow same rules cabling rules. a. Waterfall cables over the sides or ladder racks and not through rungs. b. Lace/stitch cables to ladder rack. c. Label as described below. 6. Building Management will audit Cable Installations & equipment installs on a continual basis and shall notify Customers or Carriers if any corrections are required. Pop Room: Inside and Outside Plant Rules and Regulations Page 8

9 RULES FOR ISP & OSP 1. Customers and Carriers are only authorized to work in the pathways and common areas identified in an approved PoP- MoP. 2. Work must be performed in a professional manner, it must comply with industry standards and the standards set forth in the PoP Room, ISP & OSP Rules & Regulations. a. Building Management reserves the right to have the work removed or replaced in the event that it does not meet these standards. 3. Customers and Carriers must take the utmost care not to damage other Customers AND Carriers facilities in common areas. 4. Building Management will audit Customer ISP & OSP on a continual basis and shall notify Customers if any corrections are required. PROHIBITED PRACTICES REGARDING ISP & OSP 1. Splice cases in man holes, hand holes and vaults. 2. Slack loops in man holes, hand holes and vaults. 3. Slack loops or splice cases in Property Campus entrance vaults 4. Cables blocking or impeding ducts or conduit points of entry 5. Installing cables in ducts or inner-ducts in higher ducts when there are available ducts or inner-ducts lower down in the duct bank stack. 6. Building Management reserves the right to have the work removed or replaced in the event that it does not meet these standards. ELECTRICAL DISTRIBUTION 1. Building Management will manage all electrical distribution requirements. 2. A PoP Room Rider, Carrier Access Contract or Carrier Service Agreement will need to be fully executed before any electrical circuit activation. Pop Room: Inside and Outside Plant Rules and Regulations Page 9

10 3. Customers must adhere to the existing power cabling standard. a. DC cabling cloth covered with red positive and black or gray for negative, and sized accordingly. b. Grounding-RHH/RHW or THHN, Type green. 4. Building Management will control all electrical breaker positions. 5. Distribution panels will remain locked at all times. 6. Coordination of breaker operation must be requested by Datacenter Customer or Carrier Customer and approved by Building Management prior to activation. 7. All AC and DC power cabling to cabinets and relay racks will be installed by an approved electrician and approved by Building Management. 8. Customers are responsible for connection or plug in of all power for equipment in the space. 9. Building Management will audit Electrical Distribution on a continual basis and shall notify Customers if any corrections are required. NEW CONDUIT INSTALLATIONS Building Management will manage all new conduit installations. PRE-ACTIVATION CHECK At the critical period between the time the Customer s cabling or installation is completed but before equipment is activated, the cabling or installation is to be checked by Building Management prior to the equipment activation (powered, energized or turned up). CABINET AND RELAY RACK INSTALLATIONS 1. Building Management will manage all cabinet and rack Installations. a. Building Management reserves the right to make an exception to this rule. 2. A Quad is defined as ¼ of an EIA-D compliant rack10 or 11 Rus. Pop Room: Inside and Outside Plant Rules and Regulations Page 10

11 Pop Room: Inside and Outside Plant Rules and Regulations Page 11

12 LABELING STANDARD 1. All signal cables and x-connects in the common area will be labelled. 2. Telecommunications labels will be black characters on orange. 3. Equipment a. Carrier Customers must identify their equipment in racks and cabinets with a label displaying their name. 4. Signal Cable a. Permanent labels are required for identification of Carrier Customer cable ownership. i. See approved materials below. b. Labels should be present every 10 feet. i. See approved materials below. 5. Cables between racks/cabinets/interconnection areas. a. Labels should be present at the beginning and end points of the cable. b. Labels should be present every 10 feet. c. Write on labels are allowed for the identification of circuits. d. Labels should include Customer name(s) or Suite #, cabinet/ rack number. i. See approved materials below. 5. ISP & OSP a. Permanent labels are required for identification of Carrier Customer cable ownership in maintenance holes and hand holes. i. See approved materials below. 6. Power Cables a. All power cabling will be labeled according to industry standards and completed by the Customer and/or their Contractor/Vendor. Pop Room: Inside and Outside Plant Rules and Regulations Page 12

13 7. Building Management will audit Customer labeling on a continual basis and shall notify Customers if any corrections are required. DELIVERY OF EQUIPMENT 1. Deliveries must go directly from the loading dock to the PoP Room for installation. 2. No staging area is provided. 3. Customers are required to ensure that delivery and moving companies provide the appropriate insurance certificates to Building Management before the delivery arrives. Pop Room: Inside and Outside Plant Rules and Regulations Page 13

14 EXHIBIT A: DATACENTER CUSTOMER POP-MOP Pop Room: Inside and Outside Plant Rules and Regulations Page 14

15 Pop Room: Inside and Outside Plant Rules and Regulations Page 15

16 Pop Room: Inside and Outside Plant Rules and Regulations Page 16

17 Pop Room: Inside and Outside Plant Rules and Regulations Page 17

18 EXHIBIT B: CARRIER POP- MOP Pop Room: Inside and Outside Plant Rules and Regulations Page 18

19 Pop Room: Inside and Outside Plant Rules and Regulations Page 19

20 Pop Room: Inside and Outside Plant Rules and Regulations Page 20

21 Pop Room: Inside and Outside Plant Rules and Regulations Page 21

22 Pop Room: Inside and Outside Plant Rules and Regulations Page 22

23 Pop Room: Inside and Outside Plant Rules and Regulations Page 23

Data Centers and Mission Critical Facilities Access and Physical Security Procedures

Data Centers and Mission Critical Facilities Access and Physical Security Procedures Planning & Facilities Data Centers and Mission Critical Facilities Access and Physical Security Procedures Attachment B (Referenced in UW Information Technology Data Centers and Mission Critical Facilities

More information

Centeris Data Centers - Security Procedure. Revision Date: 2/28/2018 Effective Date: 2/28/2018. Site Information

Centeris Data Centers - Security Procedure. Revision Date: 2/28/2018 Effective Date: 2/28/2018. Site Information Section 01 Document Information Creation Date: 12/1/2016 Centeris Data Centers - Security Procedure Revision Date: 2/28/2018 Effective Date: 2/28/2018 Section 02 Site Information Site Information Document

More information

SECTION COMMUNICATIONS OPTICAL FIBER BACKBONE CABLING

SECTION COMMUNICATIONS OPTICAL FIBER BACKBONE CABLING SECTION 27 13 23 COMMUNICATIONS OPTICAL FIBER BACKBONE CABLING PART 1 GENERAL 1.01 DESCRIPTION A. The work covered by this section of the Specifications includes all labor necessary to perform and complete

More information

Tarleton State University. Specifications

Tarleton State University. Specifications Tarleton State University Campus Communication Infrastructure Specifications Cabling Standards Summary This document identifies Tarleton State University communication infrastructure standards. The communication

More information

AT&T Switched Ethernet Service SM

AT&T Switched Ethernet Service SM Site Preparation Guide AT&T Switched Ethernet Service SM December 2016 2016 AT&T Intellectual Property. All rights reserved. AT&T, Globe logo, Mobilizing Your World and DIRECTV are registered trademarks

More information

FACILITY USER GUIDE. Colocation in Key Info s Agoura Court Data Center

FACILITY USER GUIDE. Colocation in Key Info s Agoura Court Data Center FACILITY USER GUIDE Colocation in Key Info s Agoura Court Data Center Page 1 of 11 Key Info Facilities User Guide v2.4 Table of Contents Welcome... 3 GETTING STARTED... 4 Colocation Access... 4 Proof of

More information

AT&T Dedicated Internet (ADI formerly known as MIS) and Private Network Transport (PNT)

AT&T Dedicated Internet (ADI formerly known as MIS) and Private Network Transport (PNT) AT&T Dedicated Internet (ADI formerly known as MIS) and Private Network Transport (PNT) Site Preparation Guide 2015 AT&T Intellectual Property. All rights reserved. AT&T, the AT&T logo and all other AT&T

More information

AT&T Dedicated Internet (ADI formerly known as MIS) and Private Network Transport (PNT)

AT&T Dedicated Internet (ADI formerly known as MIS) and Private Network Transport (PNT) AT&T Dedicated Internet (ADI formerly known as MIS) and Private Network Transport (PNT) Site Preparation Guide This guide is designed to assist local on-site contacts to understand what you will need to

More information

17. Microwave Collocation 17.1 General

17. Microwave Collocation 17.1 General Original Page 1 17.1 General 17.1.1 General A. Unless otherwise specified herein, general regulations contained in Sections 1 through 4 and Sections 14 and 15 apply in addition to the regulations contained

More information

Office of the Chief Information Officer Technical Note: IT-960-TN14 Effective: 05/25/2006 Last Revised: 02/17/2012 Issuing Office: OCIO

Office of the Chief Information Officer Technical Note: IT-960-TN14 Effective: 05/25/2006 Last Revised: 02/17/2012 Issuing Office: OCIO Cabling Standards Office of the Chief Information Officer Technical Note: IT-960-TN14 Effective: 05/25/2006 Last Revised: 02/17/2012 Issuing Office: OCIO 1. Purpose CABLING STANDARDS This technical note

More information

Data Center Access Policies and Procedures

Data Center Access Policies and Procedures Data Center Access Policies and Procedures Version 2.0 Tuesday, April 6, 2010 1 Table of Contents UITS Data Center Access Policies and Procedures!3 Introduction!3. Overview!3 Data Center Access!3 Data

More information

Physical and Environmental Security Standards

Physical and Environmental Security Standards Physical and Environmental Security Standards Table of Contents 1. SECURE AREAS... 2 1.1 PHYSICAL SECURITY PERIMETER... 2 1.2 PHYSICAL ENTRY CONTROLS... 3 1.3 SECURING OFFICES, ROOMS AND FACILITIES...

More information

Timico Data Centres: Access Policy

Timico Data Centres: Access Policy Timico Data Centres: Access Policy Timico Ltd 2012 Page: 1 of 6 1 Contents 1 Contents... 2 2 Version control... 2 3 Overview... 3 4 Introduction... 3 5 Rules of conduct... 3 6 Access request procedure...

More information

CCBC is equipped with 3 computer rooms, one at each main campus location:

CCBC is equipped with 3 computer rooms, one at each main campus location: Policy: Computer Room Procedures Policy: Draft 12/14/2009 1.0 Purpose The purpose of this document is to establish procedures for the Community College of Baltimore County (CCBC) Information Technology

More information

Computer Network Design Guide Existing Systems 1 / 6

Computer Network Design Guide Existing Systems 1 / 6 COMPUTER NETWORK DESIGN GUIDELINE FOR EXISTING SYSTEMS DOCUMENT NUMBER: 16765 APPLICATION: ELEMENTARY, MIDDLE AND HIGH SCHOOL DATE OF ISSUE: 11-27-06 - First Issued NOTES: The attached guideline should

More information

SECTION 15 KEY AND ACCESS CONTROLS

SECTION 15 KEY AND ACCESS CONTROLS 15.1 Definitions A. The definitions in this section shall apply to all sections of the part unless otherwise noted. B. Definitions: Access Badge / Card a credential used to gain entry to an area having

More information

UITS Data Center Access Policies and Procedures

UITS Data Center Access Policies and Procedures UITS Data Center Access Policies and Procedures Revision 5: 2/15/2017 2/15/17 Page 1 Author: Len Sousa, UConn/UITS Contents... 1 UITS Data Center Access Policies and Procedures... 1 1. Introduction...

More information

Data Center Colocation Service Level Agreement

Data Center Colocation Service Level Agreement Data Center Colocation Service Level Agreement Contents Terminology... 2 Service Description... 2 Power... 2 Conditioned Space... 3 Fire Suppression... 3 Service Reporting... 3 Hardware Replacement...

More information

Sabey Data Center Properties CONSOLIDATED WORK RULES

Sabey Data Center Properties CONSOLIDATED WORK RULES Sabey Data Center Properties CONSOLIDATED WORK RULES Contents Overview... 2 Building Security... 2 General... 2 Access Badge Display... 2 Security Rounds... 2 Access to Secure Spaces... 2 Emergency Exits...

More information

Target Interface / Construction Compliance Inspection Checklist

Target Interface / Construction Compliance Inspection Checklist TES A. Roads-Service, Lanes Common Items Trails and service roads provide adequate access to buildings for maintenance B. Testing Results-provided to the local government construction representative Data

More information

Communications Room Policy

Communications Room Policy Information Security Policies Communications Room Policy Author : David Rowbotham Date : 01/07/2014 Version : 1.1 Status : Initial Release MAG Information Security IT Policies Page: 1 1 Table of contents

More information

Data Centre Security. Presented by: M. Javed Wadood Managing Director (MEA)

Data Centre Security. Presented by: M. Javed Wadood Managing Director (MEA) Data Centre Security Presented by: M. Javed Wadood Managing Director (MEA) EPI history and global locations UK origin, 1987 Singapore office, 1999 9 EPI offices worldwide Global partner network spanning

More information

BROWARD COUNTY AVIATION DEPARTMENT INSIDE PLANT INFRASTRUCTURE SPECIFICATIONS

BROWARD COUNTY AVIATION DEPARTMENT INSIDE PLANT INFRASTRUCTURE SPECIFICATIONS BROWARD COUNTY AVIATION DEPARTMENT INSIDE PLANT INFRASTRUCTURE SPECIFICATIONS All noted standards apply to the current revisions applicable at the time of construction or intended construction. NO SUBSTITUTIONS

More information

Data Cabling / Low Voltage Technology Specifications

Data Cabling / Low Voltage Technology Specifications P19-02- Forsyth County Schools Data Cabling / Low Voltage Technology Specifications 1. General requirements 1.1 On premise connectivity All building closets (IDF) aside from the main closet (MDF) shall

More information

Physical and Environmental Security Policy Document Number: OIL-IS-POL-PES

Physical and Environmental Security Policy Document Number: OIL-IS-POL-PES Physical and Environmental Security Policy Document Number: OIL-IS-POL-PES Document Details Title Description Version 1.0 Author Classification Physical and Environmental Security Policy Physical and Environmental

More information

NZQA unit standard version 2 Page 1 of 5

NZQA unit standard version 2 Page 1 of 5 Page 1 of 5 Title Demonstrate knowledge of installation practices and procedures for telecommunications network equipment Level 3 Credits 10 Purpose This unit standard covers the installation of basic

More information

Open IX Data Center Technical Standards

Open IX Data Center Technical Standards Open IX Data Center Technical Standards Comments/Questions: dc group@open ix.org Last updated: November 1, 2013 Version: 1.0 Developed by: Open IX Data Center/MMR Standards Committee Gabe Cole RTE Group

More information

Open Access. Definitions

Open Access. Definitions Open-IX Data Center Technical Standards Version 2.0, January 1, 2018 Questions: dc-group@open-ix.org The purpose of the Open- IX Data Center Technical Standards document is to establish a recommended standard

More information

Classroom WiFi Network Infrastructure Plan

Classroom WiFi Network Infrastructure Plan Seattle Archdiocese Office for Catholic Schools Design for Classroom WiFi Network Modernization Guidelines for IT Physical Infrastructure Design and Specifications This document provides guidelines to

More information

Standard CIP-006-4c Cyber Security Physical Security

Standard CIP-006-4c Cyber Security Physical Security A. Introduction 1. Title: Cyber Security Physical Security of Critical Cyber Assets 2. Number: CIP-006-4c 3. Purpose: Standard CIP-006-4c is intended to ensure the implementation of a physical security

More information

SPECIFICATION STANDARD COPPER RISER AND INTRABUILDING CABLING

SPECIFICATION STANDARD COPPER RISER AND INTRABUILDING CABLING PART 1: GENERAL 1.01 SCOPE OF WORK A. The Designer and Contractor are responsible to be familiar with the provisions contained herein and with other Sections of this Specification as applicable to the

More information

SECTION FARE COLLECTION SYSTEM

SECTION FARE COLLECTION SYSTEM SECTION 17830 PART 1 - GENERAL 1.01 DESCRIPTION A. Section includes requirements for the Ticket Vending Machines (TVMs) and for the Clipper Network Card Interface Devices (CIDs) as a subsystem of the station

More information

Crisp Data Centre Standards 11 November 2008

Crisp Data Centre Standards 11 November 2008 Crisp Data Centre Standards 11 November 2008 This document outlines the standards that are enforced within the Crisp Data Centre, and as amended from time to time. Also specified are the responsibilities

More information

ANSI/TIA/EIA-568-B Cabling Standard

ANSI/TIA/EIA-568-B Cabling Standard 83 Pair Numbers and Color Coding The conductors in a UTP cable are twisted in pairs and color coded so that each pair of wires can be easily identified and quickly terminated to the appropriate pin on

More information

Ulster University Policy Cover Sheet

Ulster University Policy Cover Sheet Ulster University Policy Cover Sheet Document Title DATA CENTRE ACCESS POLICY 3.2 Custodian Approving Committee Data Centre & Operations Manager ISD Committee Policy approved date 2017 09 08 Policy effective

More information

SPECTRUM ENTERPRISE. Colocation Services Addendum

SPECTRUM ENTERPRISE. Colocation Services Addendum LEGAL SPECTRUM ENTERPRISE Colocation Services Addendum This Colocation Services Addendum ( Colocation Addendum ) governs the Spectrum Enterprise Colocation Service ( Colocation Service ) and constitutes

More information

CenturyLink Data Center North American Facility User Guide

CenturyLink Data Center North American Facility User Guide CenturyLink Data Center North American Facility User Guide page 1 of 18 NORTH AMERICAN FACILITY USER GUIDE Table of Contents 1.0 - Welcome... 3 1.1 - CenturyLink Data Center Facility Classifications...

More information

Copper Riser And Intrabuilding Cabling

Copper Riser And Intrabuilding Cabling Copper Riser And Intrabuilding Cabling PART 1: GENERAL The Contractor is held responsible to be familiar with the provisions contained herein and with other Sections of this Specification as applicable

More information

6. Secured Collocation Open Physical Environment (SCOPE) 6.1 Description

6. Secured Collocation Open Physical Environment (SCOPE) 6.1 Description 6.1 Description Page 1 Unless otherwise specified herein, general regulations contained in Part A, Sections 1 through 4 and Part E, Sections 1 and 2 apply in addition to the regulations contained in this

More information

n+2 DATA CENTER CONTROL POLICY

n+2 DATA CENTER CONTROL POLICY This Data Center Control Policy (the Control Policy ) forms a part of the Master Services Agreement between n+2 LLC ( n+2 ) and Client (the Agreement ), in which this Control Policy is incorporated by

More information

Meter Enclosure and Equipment Standards

Meter Enclosure and Equipment Standards Meter Enclosure and Equipment Standards (a) (b) General Requirements: CITY OF OCALA UTILITY SERVICES METER ENCLOSURE AND EQUIPMENT STANDARDS: (1) To avoid the costs associated with having to replace unacceptable

More information

Data Center Rules & Regulations

Data Center Rules & Regulations Data Center Rules & Regulations VERSION 7.1 AUGUST, 2013 TABLE OF CONTENTS SECTION 11102: TURN-KEY DATACENTER RULES & REGULATIONS... 3 THE PURPOSE OF THESE STANDARDS... 3 DEFINITION OF MISSION CRITICAL

More information

SECTION COMMUNICATIONS BACKBONE CABLING

SECTION COMMUNICATIONS BACKBONE CABLING (NOTE TO DESIGNER: These Specifications are basic minimum criteria to be met in preparing the final specifications for this section, which is the responsibility of the Designer.) PART 1 GENERAL 1.1 RELATED

More information

Technical Planning for Moving Into a Colocation Data Center

Technical Planning for Moving Into a Colocation Data Center Technical Planning for Moving Into a Colocation Data Center Jonathan Jew - J&M Consultants, Inc. Co-chair BICSI Data Center Subcommittee Secretary TIA TR-4 Telecommunications Cabling Systems Chair TIA

More information

v2.5 was updated May 10, v2.6 is an updated copy from March 1, 2017.

v2.5 was updated May 10, v2.6 is an updated copy from March 1, 2017. Changes in v2.6: v2.5 was updated May 10, 2016. v2.6 is an updated copy from March 1, 2017. Modifications to 4. Horizontal Pathways section with feedback incorporated from UofA Facilities and Operations

More information

AT&T Virtual Private Network Service (VPN) and AT&T VPN Express

AT&T Virtual Private Network Service (VPN) and AT&T VPN Express AT&T Virtual Private Network Service (VPN) and AT&T VPN Express Site preparation guide This guide is designed to assist local on-site contacts to understand what you will need to accomplish in preparation

More information

Technical Planning for Moving Into a Colocation Data Center

Technical Planning for Moving Into a Colocation Data Center Technical Planning for Moving Into a Colocation Data Center Jonathan Jew J&M Consultants, Inc. Co-chair BICSI Data Center Subcommittee Secretary TIA TR-4 Telecommunications Cabling Systems Chair TIA TR-4.6

More information

Standard CIP-006-3c Cyber Security Physical Security

Standard CIP-006-3c Cyber Security Physical Security A. Introduction 1. Title: Cyber Security Physical Security of Critical Cyber Assets 2. Number: CIP-006-3c 3. Purpose: Standard CIP-006-3 is intended to ensure the implementation of a physical security

More information

CERTIFICATION PLUS SM

CERTIFICATION PLUS SM CERTIFICATION PLUS SM SYSTEM WARRANTY PROGRAM Panduit Warranty Guide PROGRAM OUTLINE TABLE OF CONTENTS: MATERIALS PAGE # Program Outline 2 Table of Contents Warranty Information 3 Introduction & Installation

More information

AT&T Virtual Private Network Service (VPN) and AT&T VPN Express

AT&T Virtual Private Network Service (VPN) and AT&T VPN Express AT&T Virtual Private Network Service (VPN) and AT&T VPN Express Site Preparation Guide 2017 AT&T Intellectual Property. All rights reserved. AT&T, Globe logo, Mobilizing Your World and DIRECTV are registered

More information

HIPAA Security. 3 Security Standards: Physical Safeguards. Security Topics

HIPAA Security. 3 Security Standards: Physical Safeguards. Security Topics HIPAA Security SERIES Security Topics 1. Security 101 for Covered Entities 2. Security Standards - Administrative Safeguards 3. Security Standards - Physical Safeguards 4. Security Standards - Technical

More information

INTERNATIONAL STANDARD

INTERNATIONAL STANDARD INTERNATIONAL STANDARD ISO/IEC 18010 First edition 2002-05 Information technology Pathways and spaces for customer premises cabling ISO/IEC 2002 All rights reserved. Unless otherwise specified, no part

More information

Data Center Design and the ANSI/TIA-942 Standard

Data Center Design and the ANSI/TIA-942 Standard Data Center Design and the BICSI Regional Meeting Ellicott, MD Rick Foster RCDD,TLT Communications Infrastructure Group July 27, 2006 What is ANSI/TIA-942? Published by TIA in April 2005 Telecommunications

More information

The six major components of a structured wiring system are:

The six major components of a structured wiring system are: OBJECTIVES 1. Describe various ANSI/TIA/EIA standards for commercial buildings and residential settings. 2. Discuss the specific Technical Systems Bulletins that can affect telecommunications installations.

More information

SFTI & COLOCATION US US LIQUIDITY CENTER OPERATING POLICIES & PROCEDURES. June Version 12 STATUS. NYSE Group, Inc.

SFTI & COLOCATION US US LIQUIDITY CENTER OPERATING POLICIES & PROCEDURES. June Version 12 STATUS. NYSE Group, Inc. SFTI & COLOCATION US US LIQUIDITY CENTER OPERATING POLICIES & PROCEDURES June 2016 STATUS Version 12 NYSE Group, Inc. 2016 Page 1 About This Document The following documents should be read in conjunction

More information

NZQA unit standard version 3 Page 1 of 5. Demonstrate knowledge for telecommunications premises network cablers

NZQA unit standard version 3 Page 1 of 5. Demonstrate knowledge for telecommunications premises network cablers Page 1 of 5 Title Demonstrate knowledge for telecommunications premises network cablers Level 2 Credits 2 Purpose This unit standard is for people installing and maintaining telecommunications cables on

More information

Government of Prince Edward Island Structured Cabling Standards August 24, 2009

Government of Prince Edward Island Structured Cabling Standards August 24, 2009 Government of Prince Edward Island Structured Cabling Standards August 24, 2009 Emerging technologies dictate that it is no longer allowable to simply integrate various manufacturers components into a

More information

DATA CENTER COLOCATION BUILD VS. BUY

DATA CENTER COLOCATION BUILD VS. BUY DATA CENTER COLOCATION BUILD VS. BUY Comparing the total cost of ownership of building your own data center vs. buying third-party colocation services Executive Summary As businesses grow, the need for

More information

Security Integrator. Solutions. Your One Source for Physical Security, Network & Electrical. Solutions

Security Integrator. Solutions. Your One Source for Physical Security, Network & Electrical. Solutions Your One Source for Physical Security, Network & Electrical Solutions Security Integrator Solutions WESCO best-in-class supply chain solutions The latest technology from all industry-leading manufacturers

More information

FIBER OPTIC HARDWARE STEVE PAULOV

FIBER OPTIC HARDWARE STEVE PAULOV C H A P T E R 7 FIBER OPTIC HARDWARE STEVE PAULOV The main purpose for hardware is to protect and organize splice and termination points. Hardware can be divided into two categories; indoor and outdoor.

More information

AIMS CUSTOMER HAND BOOK THANK YOU FOR CHOOSING AIMS AS YOUR PREFERRED SERVICE PROVIDER.

AIMS CUSTOMER HAND BOOK THANK YOU FOR CHOOSING AIMS AS YOUR PREFERRED SERVICE PROVIDER. AIMS CUSTOMER HAND BOOK THANK YOU FOR CHOOSING AIMS AS YOUR PREFERRED SERVICE PROVIDER. It is our pleasure to provide you with the fullest of Informations to enable you to obtain the best from our services.

More information

Information Services IT Security Policies L. Network Management

Information Services IT Security Policies L. Network Management Information Services IT Security Policies L. Network Management Version 1.1 Last updated: 11th August 2010 Approved by Directorate: 2nd July 2009 Review date: 1st August 2011 Primary owner of security

More information

Standard CIP Cyber Security Physical Security

Standard CIP Cyber Security Physical Security A. Introduction 1. Title: Cyber Security Physical Security of Critical Cyber Assets 2. Number: CIP-006-3 3. Purpose: Standard CIP-006-3 is intended to ensure the implementation of a physical security program

More information

AIMS HOUSE RULES AND REGULATIONS

AIMS HOUSE RULES AND REGULATIONS AIMS HOUSE RULES AND REGULATIONS The security of the equipment and information in our data centres is of critical importance to the daily function of our customers operations. The following House Rules

More information

ANSI/TIA/EIA-568-B Cabling Standard NOTE

ANSI/TIA/EIA-568-B Cabling Standard NOTE 95 ANSI/TIA/EIA-569-A Though the ANSI/TIA/EIA-568-B Standard describes the subsystems of a structured cabling system, the TIA has published a more thorough document called ANSI/TIA/EIA-569-A Commercial

More information

Communications. UNM IT/Telecommunications Guide Specification Communications

Communications. UNM IT/Telecommunications Guide Specification Communications The material below covers specific information we definitely want to be included in the contract documents and may not be a completed specification section. This material is to be highlighted in your preliminary

More information

Los Angeles Community College District Design Standards

Los Angeles Community College District Design Standards LACCD Facilities Design Standards - Structural Cabling and Telecommunications Room Facilities Ver Approved: DTC February 0, 0 LACCD has developed the following Districtwide standard for IT infrastructure

More information

A - Campus Emergency Phone System

A - Campus Emergency Phone System University of New Hampshire University of New Hampshire Scholars' Repository Division 27 Communication Chapter 5 Technical Construction and Renovation Standards 2-26-2016 270742 - A - Campus Emergency

More information

NZQA registered unit standard version 2 Page 1 of 7. Demonstrate basic knowledge of electronic security data protocols and cabling

NZQA registered unit standard version 2 Page 1 of 7. Demonstrate basic knowledge of electronic security data protocols and cabling Page 1 of 7 Title Demonstrate basic knowledge of electronic security data protocols and cabling Level 3 Credits 15 Purpose This unit standard is for electronic security installers engaged in the installation

More information

TECHKNOW, INC. Kiosk Order Confirmation System INSTALLATION MANUAL. Revision Date: July 11, 2012 Part # Version 3.2

TECHKNOW, INC. Kiosk Order Confirmation System INSTALLATION MANUAL. Revision Date: July 11, 2012 Part # Version 3.2 document Page 1 of 18 TECHKNOW, INC Kiosk Order Confirmation System INSTALLATION MANUAL Revision Date: July 11, 2012 Part # Version 3.2 Techknow, Inc. 393 Mayfield Road Duncan, SC 29334 www.gotechknow.com

More information

CYBER SECURITY POLICY REVISION: 12

CYBER SECURITY POLICY REVISION: 12 1. General 1.1. Purpose 1.1.1. To manage and control the risk to the reliable operation of the Bulk Electric System (BES) located within the service territory footprint of Emera Maine (hereafter referred

More information

Mayhew Technology Solutions

Mayhew Technology Solutions Mayhew Technology Solutions Business Overview MTS offers design, engineering, and installation services for fiber optic, telecommunications, ISP, OSP, physical security, low voltage, and audio-visual systems.

More information

f) Telecommunications Equipment Rooms

f) Telecommunications Equipment Rooms SECTION 270000 - COMMUNICATIONS PART 1 - GENERAL 1.1 GENERAL REQUIREMENTS A. The Contractor is held responsible to be familiar with the provisions contained herein and with other Sections of this Specification

More information

Network Construction Guide Specification Telecommunications Infrastructure Standards V 2.6

Network Construction Guide Specification Telecommunications Infrastructure Standards V 2.6 Network Construction Guide Specification Telecommunications Infrastructure Standards 11-16-2018 V 2.6 Springfield Public Schools R12 Prepared by: Approved by: Released by: Springfield Public Schools R12

More information

Your One Source for Federal Solutions

Your One Source for Federal Solutions Your One Source for Federal Solutions GSA Contract Vehicles Dedicated Federal and Technical Teams Local Presence, International Network About WESCO The WESCO Federal Advantage Government Team Commitment

More information

PANGEN SYSTEM WARRANTY. Warranty Guide

PANGEN SYSTEM WARRANTY. Warranty Guide PANGEN SYSTEM WARRANTY Warranty Guide C2-10270 PANGEN SYSTEMWARRANTY GUIDE PROGRAM OUTLINE TABLE OF CONTENTS: MATERIALS PAGE # Program Outline 2 Table of Contents Warranty Information 3 Introduction &

More information

Cabling a Data Center to TIA-942 Standard

Cabling a Data Center to TIA-942 Standard Cabling a Data Center to TIA-942 Standard BICSI 2006 Winter Conference Wednesday, January 25 th 2006 at 9:15 am Gary J. Bernstein, RCDD HellermannTyton Corporation Agenda Overview of TIA-942 Data Center

More information

RFP Annex A Terms of Reference UNHCR HQ Data Centre Colocation Service

RFP Annex A Terms of Reference UNHCR HQ Data Centre Colocation Service RFP 2017 845 Annex A Terms of Reference UNHCR HQ Data Centre Colocation Service Version 1 Contents Project objectives... 1 Background... 1 Scope... 1 Timeframe and Cost... 4 Stakeholders, roles and responsibilities...

More information

SPECIAL INSTRUCTIONS FOR CAPACITORS COMPACT GENERATORS

SPECIAL INSTRUCTIONS FOR CAPACITORS COMPACT GENERATORS SPECIAL INSTRUCTIONS FOR CAPACITORS COMPACT GENERATORS (WITH CAPACITOR CHARGER BOARD A3517-02) The process depends on Generator and System configuration. This document applies to installation of Capacitors

More information

SPOS (Station Point of Sale) 200. SFTP (Station Fare Transaction Processor) 35. CQD (Card Query Device) 35. HCR (Handheld Card Reader) Cradles 120

SPOS (Station Point of Sale) 200. SFTP (Station Fare Transaction Processor) 35. CQD (Card Query Device) 35. HCR (Handheld Card Reader) Cradles 120 DESIGN GUIDELINES PRESTO INSTALLATION & CONNECTIVITY PAGE 1 of 4 ELECTRICAL CONNECTIVITY AND WIRING Communications Conduits Conduits designated for Presto equipment data wiring shall be clearly identified

More information

Rack Solutions RS-2. Free Standing Racks & Cabinets Wall Mount Racks, Cabinets, & Brackets Shelving Cable Management Accessories RS-5 RS-10 RS-12

Rack Solutions RS-2. Free Standing Racks & Cabinets Wall Mount Racks, Cabinets, & Brackets Shelving Cable Management Accessories RS-5 RS-10 RS-12 Rack Solutions Rack Solutions Rack Solutions Contents: RS-2 RS-5 RS-10 RS-12 RS-14 Free Standing Racks & Cabinets Wall Mount Racks, Cabinets, & Brackets Shelving Cable Management Accessories As a logical

More information

Security Integrator. Solutions. Your One Source for Physical Security, Network & Electrical. Solutions

Security Integrator. Solutions. Your One Source for Physical Security, Network & Electrical. Solutions Your One Source for Physical Security, Network & Electrical Solutions Security Integrator Solutions WESCO CSC best-in-class supply chain solutions The latest technology from all industry-leading manufacturers

More information

Chapter 1 Introduction to Outside Plant

Chapter 1 Introduction to Outside Plant Chapter 1 Introduction to Outside Plant Chapter 1 offers an overview of outside plant (OSP) fundamentals. An introduction to standardization and valuable resources for the OSP designer are also included

More information

peace of mind kit FAQ s Q: Is AccuPay bonded?

peace of mind kit FAQ s Q: Is AccuPay bonded? peace of mind kit At AccuPay, we take the trust you have placed in us very seriously. We understand that you depend on us to produce accurate payrolls as well as accurate tax returns and payments. With

More information

SCOPE OF SERVICES FIBER OPTIC NETWORK DESIGN CITY OF OVERLAND PARK, KANSAS

SCOPE OF SERVICES FIBER OPTIC NETWORK DESIGN CITY OF OVERLAND PARK, KANSAS 1.0 PROJECT ADMINISTRATION SCOPE OF SERVICES FIBER OPTIC NETWORK DESIGN CITY OF OVERLAND PARK, KANSAS Project Administration services shall consist of project management and other support services for

More information

CRM Control Panel and Weather Detection System CRM3 for DC actuators (part # 40821J) CRM4 for AC actuators (part # 40822K)

CRM Control Panel and Weather Detection System CRM3 for DC actuators (part # 40821J) CRM4 for AC actuators (part # 40822K) CRM Control Panel and Weather Detection System CRM3 for DC actuators (part # 40821J) CRM4 for AC actuators (part # 40822K) CRM Applications CRM includes a control relay box and a power supply; additional

More information

Page 1 of 15. Applicability. Compatibility EACMS PACS. Version 5. Version 3 PCA EAP. ERC NO ERC Low Impact BES. ERC Medium Impact BES

Page 1 of 15. Applicability. Compatibility EACMS PACS. Version 5. Version 3 PCA EAP. ERC NO ERC Low Impact BES. ERC Medium Impact BES 002 5 R1. Each Responsible Entity shall implement a process that considers each of the following assets for purposes of parts 1.1 through 1.3: i. Control Centers and backup Control Centers; ii. Transmission

More information

The Common Controls Framework BY ADOBE

The Common Controls Framework BY ADOBE The Controls Framework BY ADOBE The following table contains the baseline security subset of control activities (derived from the Controls Framework by Adobe) that apply to Adobe s enterprise offerings.

More information

Wire Communications Design jfm 07. An Inside Look at Outside Plant

Wire Communications Design jfm 07. An Inside Look at Outside Plant An Inside Look at Outside Plant BICSI Region Meeting 2007 Agenda What is CO-OSP? A close look at the 758-A standard Available Resources What is CO-OSP? Customer Owned Outside Plant Telecommunications infrastructure

More information

I. PURPOSE III. PROCEDURE

I. PURPOSE III. PROCEDURE A.R. Number: 2.11 Effective Date: 2/1/2009 Page: 1 of 5 I. PURPOSE This policy outlines the procedures that third party organizations must follow when connecting to the City of Richmond (COR) networks

More information

EUROPEAN LIQUIDITY CENTRE COLOCATION OPERATING POLICIES

EUROPEAN LIQUIDITY CENTRE COLOCATION OPERATING POLICIES EUROPEAN LIQUIDITY CENTRE COLOCATION OPERATING POLICIES Version 5.3 December 2017 ICE Data Services Limited PREFACE REFERENCES A reference in this document to: Authorised Trading Platform means a trading

More information

2.3 SCOPE OF WORK MATRIX TO BE INCLUDED IN DISTRICT PROJECTS

2.3 SCOPE OF WORK MATRIX TO BE INCLUDED IN DISTRICT PROJECTS NOCCCD Cabling Infrastructure Standards - Page 1 2.3 SCOPE OF WORK MATRI TO BE INCLUDED IN DISTRICT PROJECTS For each project, a Scope of Work Matrix is to be created by the construction manager and updated

More information

ICS Entrance Management Sign Installation Guide. Version 1.0

ICS Entrance Management Sign Installation Guide. Version 1.0 ICS Entrance Management Sign Installation Guide Version 1.0 Thank you for purchasing your new ICS Entrance Management System (EMS) from Innovative Control Systems, Inc. Installation Overview This document

More information

INTERIM COMMUNICATIONS INFRASTRUCTURE PLANNING GUIDELINES

INTERIM COMMUNICATIONS INFRASTRUCTURE PLANNING GUIDELINES INTERIM COMMUNICATIONS INFRASTRUCTURE PLANNING GUIDELINES University of California, Riverside Computing and Communications April XX, 2001 R1V6 TABLE OF CONTENTS Introduction and Background...3 Outside

More information

SPI PowerNet requirements for the non-contestable Interface Works at Deer Park Terminal Station

SPI PowerNet requirements for the non-contestable Interface Works at Deer Park Terminal Station SPI PowerNet requirements for the non-contestable Interface Works at Deer Park Terminal Station SPI PowerNet Reference: ZD23 Version: 1.1 Issue date: 15 May 2014 Contents 1 Scope... 3 2 Deer Park Terminal

More information

Installation Instructions

Installation Instructions 50ES, 50EZ, 50GL, 50GS, 50GX, 50JS, 50JX, 50JZ, 50SD, 50SZ, 50VL, 50VT, 50XP, 50XZ 601A, 602A, 602B, 604A, 604B, 604D, 607C, 701A, 702A, 702B, 704A, 704B, 704D, 707C PA1P, PA2P, PA3P, PH1P, PH2P, PH3P

More information

Atras Network Communications

Atras Network Communications Atras Network Communications Guide to Information and Communications Technology (ICT) Standards developed and published by the Telecommunications Industry Association (TIA) The Telecommunications Industry

More information

ANNEX. Organizational and technical measures

ANNEX. Organizational and technical measures ANNEX Organizational and technical measures The Data Processor has implemented the measures as described in this exhibit insofar as the respective measure contributes or is capable of contributing directly

More information

AUTHORITY FOR ELECTRICITY REGULATION

AUTHORITY FOR ELECTRICITY REGULATION SULTANATE OF OMAN AUTHORITY FOR ELECTRICITY REGULATION SCADA AND DCS CYBER SECURITY STANDARD FIRST EDITION AUGUST 2015 i Contents 1. Introduction... 1 2. Definitions... 1 3. Baseline Mandatory Requirements...

More information

Standard: Data Center Security

Standard: Data Center Security Standard: Data Center Security Page 1 Executive Summary The university data centers provide for the reliable operation of SJSU s computing systems, computing infrastructure, and communication systems.

More information