ELECTRICAL SAFETY INSPECTION REPORT

Size: px
Start display at page:

Download "ELECTRICAL SAFETY INSPECTION REPORT"

Transcription

1 ELECTRICAL SAFETY INSPECTION REPORT Al Islam Textile Industries Ltd. Ramjannessa Super Market (2 nd Floor), 142, Senanibash Road, Pallabi, Mirpur12, Dhaka 1221, Bangladesh. Factory List: 1. Al Islam Textile Industries Ltd. Inspected by: Yang Report Generated by: S M Tasdeek Inspected on May 06, 2014

2 SUMMARY The Al Islam Textile Industries Ltd. factory is operating in a four (G+3) storied building with a shed on top. Construction of the building was completed in the year The building was approved for industrial purpose. The Factory was surveyed for electrical safety by Woosun Energy and Construction Co., Ltd. (WEC). The purpose of the survey was to identify significant electrical safety issues and to provide recommendations for remediation based on applicable standards specified by the Accord. The scope of this initial electrical safety inspection was limited to the review and identification of major electrical safety issues. The inspection did not include identification of minor deficiencies, which will be further addressed as part of follow-up inspections. Table below summarizes the major electrical safety issues identified during the inspection. Recommendations have been provided to address each issue. An implementation schedule shall be developed by the factory to remediate each of the findings. The Specific timing of improvements, including any requested extensions due to design / installation constraints shall be submitted to the Accord for approval. Al Islam Textile Industries Ltd. Page 2 of 5

3 FINDINGS AND RECOMMENDATIONS Finding #: E- 1 SERVICE LINE HT cable dropping from OH line, not supported to the pole. HT cable dropping from HT pole must be firmly fixed to the pole with support and clamps. 3months DESCO pole Finding #: E- 2 SWITCH BOARD & PANELS Panel doors not connected with earth bond. Panel door(s) must be connected with earth bond connecting frame and door. Panel board Al Islam Textile Industries Ltd. Page 3 of 5

4 Finding #: E- 3 GENERATOR ROOM Cables terminating to generator output terminal box are laid on floor. Cable terminating at Generator output terminal box must be supported on riser and protected. Existing cables laid on floor may be installed in cable trench or on trays. 3 months Generator room Finding #: E- 4 EQUIPMENT & MACHINE Cables to machines/motor are laid on the floor Install the cables through rigid pipe (metallic) for the protection of the cable laid on floor. The pipe must be fixed/ clamped with saddle on floor at regular intervals Cable on the floor Finding #: E- 5 CABLE & CABLE SUPPORTS Cables terminating at distribution boards are not protected (and not supported), near panel. Cables terminating at distribution boards must be supported in cable tray and protected throughout its length till the panel base or top plate. 3 months Cable terminating in panel board Al Islam Textile Industries Ltd. Page 4 of 5

5 Finding #: E- 6 SWITCH BOARD & PANELS Cables connecting to bus bar without cable lugs. Cables connecting to bus bars must be connected firmly with cable lugs. Cable terminating to the bus bars must be fixed with proper size nuts and bolt with washers. Cable connecting to bus bar Finding #: E- 7 EQUIPMENT & MACHINE Leakage in IPS battery. Leakage in battery terminal must be checked and fixed regularly. Battery rack Finding #: E- 8 CABLE & CABLE SUPPORTS Cables are not covered in duct. Electric cables must be supported on cable duct with metal covers. Provide cover made of noncombustible material on duct for preventing any physical damage & ingress of dust and debris in future. Cable duct Al Islam Textile Industries Ltd. Page 5 of 5

ELECTRICAL SAFETY INSPECTION REPORT

ELECTRICAL SAFETY INSPECTION REPORT ELECTRICAL SAFETY INSPECTION REPORT CHITTAGONG FASHION WEAR LTD. SOUTH HALISHAHAR, CHITTAGONG, BANGLADESH Factory List: 1. Chittagong Fashion Wear Ltd. 2. H & W Apparels Inspected on May 5, 2014 SUMMARY

More information

INITIAL ELECTRICAL SAFETY ASSESSMENT - EXPANSION

INITIAL ELECTRICAL SAFETY ASSESSMENT - EXPANSION INITIAL ELECTRICAL SAFETY ASSESSMENT - EXPANSION Factory Name: ACS TEXTILES (BANGLADESH) LTD. Tetlabo, Barpa Rupgonj, Narayangonj Rupgonj Dhaka Bangladesh 26 Sep 2018 The Alliance for Bangladesh Worker

More information

SECTION PANELBOARDS

SECTION PANELBOARDS SECTION 16450 PART 1 - GENERAL 1.01 DESCRIPTION A. Section includes requirements for panelboards providing fault interrupting capability and overcurrent protective devices. 1.02 REFERENCE STANDARDS A.

More information

Copper Riser And Intrabuilding Cabling

Copper Riser And Intrabuilding Cabling Copper Riser And Intrabuilding Cabling PART 1: GENERAL The Contractor is held responsible to be familiar with the provisions contained herein and with other Sections of this Specification as applicable

More information

ICS Entrance Management Sign Installation Guide. Version 1.0

ICS Entrance Management Sign Installation Guide. Version 1.0 ICS Entrance Management Sign Installation Guide Version 1.0 Thank you for purchasing your new ICS Entrance Management System (EMS) from Innovative Control Systems, Inc. Installation Overview This document

More information

NEC Server Rack Configuration Guide

NEC Server Rack Configuration Guide NEC Server Rack Configuration Guide Introduction This document contains product and configuration information that will enable you to configure your system. The guide will ensure fast and proper configuration

More information

Office of the Chief Information Officer Technical Note: IT-960-TN14 Effective: 05/25/2006 Last Revised: 02/17/2012 Issuing Office: OCIO

Office of the Chief Information Officer Technical Note: IT-960-TN14 Effective: 05/25/2006 Last Revised: 02/17/2012 Issuing Office: OCIO Cabling Standards Office of the Chief Information Officer Technical Note: IT-960-TN14 Effective: 05/25/2006 Last Revised: 02/17/2012 Issuing Office: OCIO 1. Purpose CABLING STANDARDS This technical note

More information

Computer Network Design Guide Existing Systems 1 / 6

Computer Network Design Guide Existing Systems 1 / 6 COMPUTER NETWORK DESIGN GUIDELINE FOR EXISTING SYSTEMS DOCUMENT NUMBER: 16765 APPLICATION: ELEMENTARY, MIDDLE AND HIGH SCHOOL DATE OF ISSUE: 11-27-06 - First Issued NOTES: The attached guideline should

More information

A-100G6 - Basic frame assembly diagram

A-100G6 - Basic frame assembly diagram doepfer System A - 100 Rack system A-100 G A-100G6 - Basic frame assembly diagram Parts: 1 Rail with lip, and with tapped hole strip inserted (with M3 threads). 2 Rail with lip, with three M3 hexagon nuts

More information

SPECIFICATION STANDARD COPPER RISER AND INTRABUILDING CABLING

SPECIFICATION STANDARD COPPER RISER AND INTRABUILDING CABLING PART 1: GENERAL 1.01 SCOPE OF WORK A. The Designer and Contractor are responsible to be familiar with the provisions contained herein and with other Sections of this Specification as applicable to the

More information

IEC Installation Manual and User Manual for. BYD Photovoltaic Module

IEC Installation Manual and User Manual for. BYD Photovoltaic Module IEC Installation Manual and User Manual for BYD Photovoltaic Module BYD(Shanghai) Industrial Co.Ltd ADD:No.999 Xiangjing Road,Songjiang Shanghai, 201611, P.R.China TEL:+86-21-5777 8888 FAX:+86-21-5777

More information

Electrical Demand Specification (Reference SOP: )

Electrical Demand Specification (Reference SOP: ) Project: Equipment Description: Location: Equipment No.: Project No: Protocol No.: Content Index 1. GENERAL...3 Design Standards...3 1.1. Standards...3 2. DESIGN...3 2.1. Safety...3 2.2. Circuit protection...3

More information

sonnen Installation Practical

sonnen Installation Practical sonnen Installation Practical sonnen Components sonnenbatterie eco 8.0 Single Phase System Components 4 sonnenbatterie eco 8.0 Single Phase System Components 5 sonnenbatterie eco 8.0 Single Phase System

More information

BS EN Class H, BS 7430 UL467 (CR105) Tightening torque 15 Nm mm mm kg CR525

BS EN Class H, BS 7430 UL467 (CR105) Tightening torque 15 Nm mm mm kg CR525 Rod to tape clamp (type A) Nominal rod Max. conductor 1 2 12.7 mm 26 x 12 mm 0.1 kg CR10 8 16 mm 26 x 12 mm 0.1 kg CR10 4 20 mm 26 x 10 mm 0.1 kg CR10 8 16 mm 0 x 2 mm 0.16 kg CR108 4 20 mm 0 x 2 mm 0.16

More information

ANSI/TIA/EIA-568-B Cabling Standard NOTE

ANSI/TIA/EIA-568-B Cabling Standard NOTE 95 ANSI/TIA/EIA-569-A Though the ANSI/TIA/EIA-568-B Standard describes the subsystems of a structured cabling system, the TIA has published a more thorough document called ANSI/TIA/EIA-569-A Commercial

More information

CCBC is equipped with 3 computer rooms, one at each main campus location:

CCBC is equipped with 3 computer rooms, one at each main campus location: Policy: Computer Room Procedures Policy: Draft 12/14/2009 1.0 Purpose The purpose of this document is to establish procedures for the Community College of Baltimore County (CCBC) Information Technology

More information

References. References. Rating (A) Référence

References. References. Rating (A) Référence DIRECT OPERATION T O O R D E R EXTERNAL OPERATION picto_080_c_1_gb Switch body Direct Switch body + handle + Shaft + + OTHER ACCESSORIES External handle acces_128_a_1_cat acces_129_a_1_cat Direct handle

More information

Webb Core Cleanroom Wall System

Webb Core Cleanroom Wall System Webb Core Cleanroom Wall System PART 1 GENERAL 1.1 WORK INCLUDED A. This Section specifies the requirements necessary to furnish, install and complete a cleanroom wall system (CRW) including, but not limited

More information

ISOLATION RELAY RACK ISOLATION KIT 19 RACK MOUNT RELAY RACK ISOLATION KIT, SLOTTED UNEQUAL FLANGE RACK ISOLATION KIT 23 RACK MOUNT

ISOLATION RELAY RACK ISOLATION KIT 19 RACK MOUNT RELAY RACK ISOLATION KIT, SLOTTED UNEQUAL FLANGE RACK ISOLATION KIT 23 RACK MOUNT ISOLATION Info: 9070 = Isolation RELAY RACK ISOLATION KIT 19 RACK MOUNT 9070-1019 19" Rack Mount 23 RACK MOUNT 9070-1023 23" Rack Mount RELAY RACK ISOLATION (KIT) RELAY RACK ISOLATION KIT, SLOTTED 19 RACK

More information

Installation Guide for Mazak Mazatrol M - Plus, M-2, M32, T-Plus, T2

Installation Guide for Mazak Mazatrol M - Plus, M-2, M32, T-Plus, T2 1 Installation Guide for Mazak Mazatrol M - Plus, M-2, M32, T-Plus, T2 Tsubis Part Number: LCD12-0046 Power Down 1. Power down the controller. 2. Power down the complete machine by turning off the rear

More information

ATS-16 HV USER MANUAL. Automatic Transfer Switch 16A / 230Vac V090318

ATS-16 HV USER MANUAL. Automatic Transfer Switch 16A / 230Vac V090318 ATS-16 HV Automatic Transfer Switch 16A / 230Vac USER MANUAL V090318 SAFETY Intended use The ATS-16 HV device serves as a power source selector to provide improved power supply for connected loads. ATS-16

More information

PV Module Installation Instructions

PV Module Installation Instructions Name 1601A Page 1 / 8 Name 1601A Page 2 / 8 1 Introduction Thanks for purchasing PV modules of HT SOLAR ENERGY JOINT STOCK COMPANY This manual refers to PV modules manufactured and sold by HT Turkey. This

More information

Application Guideline for BOP Business Support Coordinator BANGLADESH in FY 2013

Application Guideline for BOP Business Support Coordinator BANGLADESH in FY 2013 Application Guideline for BOP Business Support Coordinator BANGLADESH in FY 2013 1 May, 2013 Kei Kawano Representative JETRO Dhaka The Japan External Trade Organization (JETRO) Dhaka Office will retain

More information

User s Manual. ACS550-PD 3R Irrigation Packaged Drive Supplement to ACS550-U1 User s Manual

User s Manual. ACS550-PD 3R Irrigation Packaged Drive Supplement to ACS550-U1 User s Manual User s Manual ACS550-PD 3R Irrigation Packaged Drive Supplement to ACS550-U1 User s Manual 2 ACS550-PD 3R Irrigation Packaged Drive ACS550 Drive Manuals GENERAL MANUALS ACS550-U1 User s Manual (1 200 HP)

More information

Obtaining Documentation and Submitting a Service Request, page xvii Safety Warnings, page xvii Safety Guidelines, page xx

Obtaining Documentation and Submitting a Service Request, page xvii Safety Warnings, page xvii Safety Guidelines, page xx Preface Obtaining Documentation and Submitting a Service Request, page xvii Safety s, page xvii Safety Guidelines, page xx Obtaining Documentation and Submitting a Service Request For information on obtaining

More information

EX- Documentation VA 450 / VA 452. thermal mass flow sensor

EX- Documentation VA 450 / VA 452. thermal mass flow sensor EX- Documentation VA 450 / VA 452 thermal mass flow sensor This document contains important information for the installation and operation of the flow sensor in explosive environments. Please read the

More information

Installation Instructions

Installation Instructions 50ES, 50EZ, 50GL, 50GS, 50GX, 50JS, 50JX, 50JZ, 50SD, 50SZ, 50VL, 50VT, 50XP, 50XZ 601A, 602A, 602B, 604A, 604B, 604D, 607C, 701A, 702A, 702B, 704A, 704B, 704D, 707C PA1P, PA2P, PA3P, PH1P, PH2P, PH3P

More information

SECTION ENCLOSED SWITCHES AND CIRCUIT BREAKERS

SECTION ENCLOSED SWITCHES AND CIRCUIT BREAKERS SECTION 262816 - ENCLOSED SWITCHES AND CIRCUIT BREAKERS PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division

More information

Control Box Setup - PRSalpha

Control Box Setup - PRSalpha 888-680-4466 ShopBotTools.com Control Box Setup - PRSalpha Copyright 2016 ShopBot Tools, Inc. page 1 Copyright 2016 ShopBot Tools, Inc. page 2 Parts List: Hooking Up a PRSalpha Gantry Tool Powering the

More information

VERAK IP. 19 Stand Alone Cabinet with IP65 Rating.

VERAK IP. 19 Stand Alone Cabinet with IP65 Rating. 19 Stand Alone Cabinet with IP65 Rating www.apw.eu.com Overview Material specification Frame: Steel 2.0 mm Panel mounting angles and reducing channels: Steel 2.0 mm Panel mount supports: Steel 1.5 mm Side

More information

Vertiv VR Rack 1.0 GENERAL

Vertiv VR Rack 1.0 GENERAL 1.1 SUMMARY Vertiv VR Rack Guide Specifications 1.0 GENERAL This specification defines the mechanical characteristics and requirements for the Vertiv VR Rack. A series of adaptive and scalable electronic

More information

1510 MOTOR CONTROLLERS

1510 MOTOR CONTROLLERS SECTION 262913- MOTOR CONTROLLERS PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of contract, including general and supplementary conditions and Division 1 specification section,

More information

Westell. Breaker Panel Technical Practice NPDRP1114

Westell. Breaker Panel Technical Practice NPDRP1114 030-000218 REV F 1114-03F June 29, 2017 Westell Breaker Panel Technical Practice NPDRP1114 FEATURES DIN rail panel accepts up to 6 DIN rail devices (one surge and 5 breakers) Specific configuration of

More information

Breaker Panel Technical Practice NPDRP1114

Breaker Panel Technical Practice NPDRP1114 030-000218 REV E 1114-03E January 30, 2013 Westell Breaker Panel Technical Practice NPDRP1114 FEATURES DIN rail panel accepts up to 6 DIN rail devices (one surge and 5 breakers) Specific configuration

More information

CONTROL PANEL WIRING SPECIFICATIONS

CONTROL PANEL WIRING SPECIFICATIONS CONTROL PANEL WIRING ISSUE STATUS FIRST REV DESCRIPTION DATE 001 1 ST ISSUE 22/04/2014 002 1 ST AMMENDMENT 10/03/2017 003 2 ND AMMENDMENT 08/09/2017 THIS DOCUMENT IS DESIGNED TO COVER ALL APPLICATIONS,

More information

User s Manual. ACS550-PD Stock 3R Irrigation Packaged Drive Supplement to ACS550-U1 User s Manual

User s Manual. ACS550-PD Stock 3R Irrigation Packaged Drive Supplement to ACS550-U1 User s Manual User s Manual ACS550-PD Stock 3R Irrigation Packaged Drive Supplement to ACS550-U1 User s Manual 2 ACS550-PD 3R Irrigation Packaged Drive ACS550 Drive Manuals GENERAL MANUALS ACS550-U1 User s Manual (1

More information

AIR TERMINALS: COPPER

AIR TERMINALS: COPPER AIR TERMINALS: COPPER A ADAPTER TYPE B LESS ADAPTER LA TYPE A B C A B C A B C 3 8 COPPER POINTS (CLASS I ONLY) 1 2 COPPER POINTS (CLASS I OR II) 5 8 COPPER POINTS (CLASS I OR II) THE 3 8 COPPER AND ALUMINUM

More information

DK-PS Rack. New generation DK-PS Rack for room climate control

DK-PS Rack. New generation DK-PS Rack for room climate control DK-PS Rack DK-PS Rack New generation DK-PS Rack for room climate control Rack as the support for IT equipment is the main component of the data center; Reliable,eficiency and flexible is the main requirement

More information

Section COMMUNICATION EQUIPMENT ROOM FITTINGS. Section Communications Cable Management and Ladder Rack

Section COMMUNICATION EQUIPMENT ROOM FITTINGS. Section Communications Cable Management and Ladder Rack PART 1 GENERAL 1.1 WORK INCLUDED Section 27 11 00 COMMUNICATION EQUIPMENT ROOM FITTINGS Section 27 11 23 Communications Cable Management and Ladder Rack A. Provide all labor, materials, and equipment for

More information

MASTERLINE Ultimate Hybrid High Voltage 4/12 (MLUH HV 4/12) blunt cut at BTS side

MASTERLINE Ultimate Hybrid High Voltage 4/12 (MLUH HV 4/12) blunt cut at BTS side INSTALLATION MANUAL HUBER+SUHNER AG Fiber Optics MASTERLINE Ultimate Hybrid High Voltage 4/12 (MLU HV 4/12) blunt cut at BTS side DOC-0000803885 Rev A June 18, 2018 Page 1 of 12 (MLUH HV 4/12) blunt cut

More information

National Light Sources Pty Ltd Electrical Accessories - Date 8th April, Coombes Drive, Penrith, NSW, 2750 Australia

National Light Sources Pty Ltd Electrical Accessories - Date 8th April, Coombes Drive, Penrith, NSW, 2750 Australia National Light Sources Pty Ltd 15 Coombes Drive, Penrith, NSW, 2750 Australia 15 Coombes Drive Penrith NSW 2750 Tel: 02-4732 5444 Fax: 02-4732 6600 Email: sales@nlslight.com.au Product list for Electrical

More information

ADDENDUM NO. 1 ITB-DOT BAT. You are hereby notified that the above referenced Invitation to Bid (ITB) is modified as shown below:

ADDENDUM NO. 1 ITB-DOT BAT. You are hereby notified that the above referenced Invitation to Bid (ITB) is modified as shown below: ADDENDUM NO. 1 ITB-DOT-15-16-5002-BAT To: All Prospective Proposers From: Ashley Henning District Five Contractual Services Date: March 25, 2016 RE: ITB-DOT-15-16-5002-BAT ITS Battery Installation You

More information

MBE Mounts and Adapters

MBE Mounts and Adapters MBE Mounts and Adapters MBE Series en Installation Guide MBE Mounts and Adapters Table of Contents en 3 Table of Contents 1 Important safety instructions 4 2 MBE Series Mounts and Adapters 6 2.1 Unpacking

More information

Target Interface / Construction Compliance Inspection Checklist

Target Interface / Construction Compliance Inspection Checklist TES A. Roads-Service, Lanes Common Items Trails and service roads provide adequate access to buildings for maintenance B. Testing Results-provided to the local government construction representative Data

More information

Distribution Substation Manual (DSM) Section 6: Miscellaneous

Distribution Substation Manual (DSM) Section 6: Miscellaneous Distribution Substation Manual (DSM) Section 6: Miscellaneous Standard Number: HPC-5DA-07-0006-2012 Document Control Author Name: Viswa Easwaran Position: Standards Engineer Document Owner Name: Justin

More information

Codian MSE 8000 Media Services Engine

Codian MSE 8000 Media Services Engine Codian MSE 8000 Media Services Engine Getting started Codian MSE 8000 Media Services Engine Getting started Copyright Codian 2008. All rights reserved. This Getting Started Guide may not be copied, photocopied,

More information

1993 Specifications CSJ SPECIAL SPECIFICATION ITEM Transportation Management Console

1993 Specifications CSJ SPECIAL SPECIFICATION ITEM Transportation Management Console 1993 Specifications CSJ 0598-01-057 1.0 Description SPECIAL SPECIFICATION ITEM 6398 Transportation Management Console This Item shall govern for the furnishing and installation of Transportation Management

More information

INSTITUTE OF TESTING AND CERTIFICATION (INDIA) PVT. LTD.

INSTITUTE OF TESTING AND CERTIFICATION (INDIA) PVT. LTD. (INDIA) VT. LTD. 5. INCOMING SULY CONDUCTOR TERMINATIONS AND DEVICES FOR DISCONNECTING AND SWITCHING OFF 5.1 Incoming supply conductor terminations The electrical equipment of the machine shall have only

More information

Spring Test 17 due 06/14/2013

Spring Test 17 due 06/14/2013 Spring Test 17 due 06/14/2013 Multiple Choice Identify the choice that best completes the statement or answers the question. 1. The NEC defines cable as a cylindrical assembly composed of a conductor centered

More information

DIGILOCK DK-AT SERIES LOCK SPECIFICATION - Applies to DK-ATS, DK-ATV and DK-ATH models

DIGILOCK DK-AT SERIES LOCK SPECIFICATION - Applies to DK-ATS, DK-ATV and DK-ATH models DIGILOCK DK-AT SERIES LOCK SPECIFICATION - Applies to DK-ATS, DK-ATV and DK-ATH models PART 1 GENERAL 1.1 SUMMARY Furnish Digilock electronic locks for installation on lockers, cabinets or containers as

More information

Specifications, Installation, and Operating Instructions

Specifications, Installation, and Operating Instructions Specifications, Installation, and Operating Instructions Model: Power Vantage AC Panel Protector CAUTION: The installation of a surge protection device () must be done by qualified electrical personnel.

More information

AT&T Virtual Private Network Service (VPN) and AT&T VPN Express

AT&T Virtual Private Network Service (VPN) and AT&T VPN Express AT&T Virtual Private Network Service (VPN) and AT&T VPN Express Site preparation guide This guide is designed to assist local on-site contacts to understand what you will need to accomplish in preparation

More information

HP UPS R/T3000 G2. Overview. Precautions. Kit contents. Installation Instructions

HP UPS R/T3000 G2. Overview. Precautions. Kit contents. Installation Instructions HP UPS R/T3000 G2 Installation Instructions Overview The HP UPS R/T3000 G2 features a 2U rack-mount with convertible tower design and offers power protection for loads up to a maximum of 3300 VA/3000 W

More information

SPECIAL INSTRUCTIONS FOR CAPACITORS COMPACT GENERATORS

SPECIAL INSTRUCTIONS FOR CAPACITORS COMPACT GENERATORS SPECIAL INSTRUCTIONS FOR CAPACITORS COMPACT GENERATORS (WITH CAPACITOR CHARGER BOARD A3517-02) The process depends on Generator and System configuration. This document applies to installation of Capacitors

More information

GPS tracker Voyager 5N (M)

GPS tracker Voyager 5N (M) GPS tracker Voyager 5N (M) Data sheet Device identification number 1. General Information 2 Voyager 5N (М) is a GPS tracker (hereinafter referred to as the device) used for monitoring of various irregular

More information

MICHIGAN DEPARTMENT OF TRANSPORTATION

MICHIGAN DEPARTMENT OF TRANSPORTATION MICHIGAN DEPARTMENT OF TRANSPORTATION SPECIAL PROVISION FOR GROUNDING, BONDING, LIGHTNING PROTECTION AND SURGE PROTECTION FOR INTELLIGENT TRANSPORTATION SYSTEM EQUIPMENT ITS:CLC 1 of 5 APPR:LWB:DBP:07-31-13

More information

Total Amount Carried Forward To Bill summary Page

Total Amount Carried Forward To Bill summary Page BILL 1: GROUND FLOOR Supply, Deliver, Install, Set to Work and Commission the Following. 1.01 4 Pair, 24 AWG UTP cable, CAT 6, 305 metres per roll. As siemon or equal &approved equivalent 1.02 CAT 6 Face

More information

Site Preparation CHAPTER

Site Preparation CHAPTER CHAPTER 3 Site Preparation This chapter describes the steps to take and the considerations you should keep in mind prior to installing the modules in an open rack. It also contains information that applies

More information

Improved power supply after Fukushima and OPC in Japanese BWRs

Improved power supply after Fukushima and OPC in Japanese BWRs BWR-club workshop on Robust Power in Uppsala Improved power supply after Fukushima and OPC in Japanese BWRs May 3 rd, 2017 Hitachi-GE Nuclear Energy, Ltd Masashi Sugiyama Hitachi-GE Nuclear Energy, Ltd.

More information

Free-Standing Type 12 Enclosures

Free-Standing Type 12 Enclosures Type 12 Enclosures Application Designed to protect electrical and electronic controls, components, and instruments in typical industrial environments. The UL Type 12 rating protects enclosed equipment

More information

AT&T Virtual Private Network Service (VPN) and AT&T VPN Express

AT&T Virtual Private Network Service (VPN) and AT&T VPN Express AT&T Virtual Private Network Service (VPN) and AT&T VPN Express Site Preparation Guide 2017 AT&T Intellectual Property. All rights reserved. AT&T, Globe logo, Mobilizing Your World and DIRECTV are registered

More information

Installation Notes TII Model 341 Protector

Installation Notes TII Model 341 Protector Installation Notes TII Model 341 Protector (ATT-IS PEC 32918) for MERLIN Communications System In Range Out of Building (IROB) Station Installation By Trained Technician Only WARNING: Failure to follow

More information

Delta Unifence Kit Installation Instructions

Delta Unifence Kit Installation Instructions Delta Unifence Kit Installation Instructions Please note this installation kit is designed for installation on the Delta Commercial Unifence (units made between 1993 and current). Accurate Technology manufactures

More information

ECP NORTROLL CABLETROLL 2350 FPI INSTALLATION AND COMMISSIONING PROCEDURE

ECP NORTROLL CABLETROLL 2350 FPI INSTALLATION AND COMMISSIONING PROCEDURE Network(s): Summary: ENGINEERING COMMISSIONING PROCEDURE ECP 11-0521 NORTROLL CABLETROLL 2350 FPI INSTALLATION AND COMMISSIONING PROCEDURE EPN, LPN, SPN This document details the installation, testing

More information

MPS-850 e-drum set. assembly instructions

MPS-850 e-drum set. assembly instructions MPS-850 e-drum set assembly instructions Musikhaus Thomann Thomann GmbH Hans-Thomann-Straße 1 96138 Burgebrach Germany Telephone: +49 (0) 9546 9223-0 E-mail: info@thomann.de Internet: www.thomann.de 16.10.2018,

More information

A/E REVIEW CHECKLIST TELECOMMUNICATIONS SYSTEMS

A/E REVIEW CHECKLIST TELECOMMUNICATIONS SYSTEMS A/E REVIEW CHECKLIST TELECOMMUNICATIONS SYSTEMS May 1, 2016 Reviewers should - Be aware that these checklists are not allinclusive but only provide important review items. Reviewers should - Use Checklists

More information

Internal Printer. Features.

Internal Printer. Features. Internal Printer Features Automatic Operation for o Fire o Fault o Alarms o Test On-Demand Option for Printing o Inputs o Outputs o Disablements o Event Log o Network Faults The operation and functions

More information

LARGE S URGE-PROTECTOR S HELTER

LARGE S URGE-PROTECTOR S HELTER LARGE S URGE-PROTECTOR S HELTER The weather-resistant Large Surge-Protector Shelter (simply referred to as the shelter in this manual) provides protection from the elements for Surge Protectors (not included)

More information

Title System Substation Commissioning Tests. Reference Number PCP 07 - (RIC Standard: EP SP)

Title System Substation Commissioning Tests. Reference Number PCP 07 - (RIC Standard: EP SP) Discipline Engineering Standard - NSW Category Electrical Title s Reference Number PCP 07 - (RIC Standard: EP 99 00 00 02 SP) Document Control Status Date Prepared Reviewed Endorsed Approved Mar 05 Standards

More information

Effective Date: September 2017 Void After: September Product: Lead Free Plumbing Products File No. 6142

Effective Date: September 2017 Void After: September Product: Lead Free Plumbing Products File No. 6142 IAPMO Research and Testing, Inc. is a product certification body which tests and inspects samples taken from the supplier's stock or from the market or a combination of both to verify compliance to the

More information

Data Cabling / Low Voltage Technology Specifications

Data Cabling / Low Voltage Technology Specifications P19-02- Forsyth County Schools Data Cabling / Low Voltage Technology Specifications 1. General requirements 1.1 On premise connectivity All building closets (IDF) aside from the main closet (MDF) shall

More information

Dell Networking S4810 Open Networking (ON) Getting Started Guide

Dell Networking S4810 Open Networking (ON) Getting Started Guide Dell Networking S4810 Open Networking (ON) Getting Started Guide Regulatory Model: S4810 Notes, Cautions, and Warnings NOTE: A NOTE indicates important information that helps you make better use of your

More information

Overview These instructions are presented as a guideline for installing and setting up the LX Series Breaker Control Panel.

Overview These instructions are presented as a guideline for installing and setting up the LX Series Breaker Control Panel. LX Breaker Control Panels Installation and Setup Procedure Hubbell Building Automation, Inc. 9601 Dessau Road Building One Suite 100 Austin, Texas 78754 512-450-1100 512-450-1215 Fax www.hubbell-automation.com

More information

Security at Fingertips.

Security at Fingertips. Security at Fingertips www.esslsecurity.com Installation Guide SF1000 Version: 2.0 Date: May 2014 All design and specification declared are subject to change without notice in advance. I. Use Instructions

More information

3M Cross-Connect Cabinet Riser Installation Guide

3M Cross-Connect Cabinet Riser Installation Guide 3M Cross-Connect Cabinet Riser Installation Guide Installing riser in stake, hand hole and pad-mount applications Instructions October 2016 78-0015-3063-9-B 2 October 2016 78-0015-3063-9-B Contents 1.

More information

7 Day Programmable Room Thermostat

7 Day Programmable Room Thermostat 7 Day Programmable Room Thermostat Model: TRT035N Installation & Operating Instructions 1. General Information These instructions should be read carefully and retained for further reference and maintenance.

More information

UNDERGROUND CONSTRUCTION MANUAL SERVICES

UNDERGROUND CONSTRUCTION MANUAL SERVICES UNDERGROUND CONSTRUCTION MANUAL ack to MAIN INDEX Go to SECTION INDEX CONSTRUCTION DESCRIPTION DWG CONSTRUCTION DESCRIPTION DWG Construction code guide - Underground service from overhead system 53 SERVICE

More information

INSTALLATION INSTRUCTIONS

INSTALLATION INSTRUCTIONS AFL TITAN RTD Multiport Terminal AFL TRIDENT Hardened Drop TABLE OF CONTENTS GENERAL... 2 SPECIFICATIONS... 2 PACKAGE CONTENTS... 3 REQUIRED TOOLS... 3 ADD-ON COMPONENTS... 3 TERMINAL MOUNTING STRAND...

More information

SOLAR Basic. Operating instructions for electronic high-security locks

SOLAR Basic. Operating instructions for electronic high-security locks SOLAR Basic Operating instructions for electronic high-security locks Gebäude Sicherheitstechnik Vertriebs GmbH, 34123 Kassel Solar-Basic (DE, EN, FR)-17000000 Rev. 1.3 / 01-2015 Table of contents General

More information

The University of Texas at Austin July 30, 2014 SECTION COMMUNICATIONS TERMINATION BLOCKS AND PATCH PANELS

The University of Texas at Austin July 30, 2014 SECTION COMMUNICATIONS TERMINATION BLOCKS AND PATCH PANELS SECTION 27 11 19 COMMUNICATIONS TERMINATION BLOCKS AND PATCH PANELS PART 1 - GENERAL 1.1 SUMMARY A. This section specifies the products and installation of communications termination blocks and patch panels

More information

E A54-UL 2012-AUGUST-29 XP POWER L L C SUITE E DYER RD SANTA ANA CA 92705

E A54-UL 2012-AUGUST-29 XP POWER L L C SUITE E DYER RD SANTA ANA CA 92705 CERTIFICATE OF COMPLIANCE Certificate Number 20120829-E139109 Report Reference Issue Date E139109-A54-UL 2012-AUGUST-29 Issued to: XP POWER L L C SUITE 150 1241 E DYER RD SANTA ANA CA 92705 This is to

More information

CERTIFICATE OF APPROVAL No CF 694 3M UK LTD

CERTIFICATE OF APPROVAL No CF 694 3M UK LTD CERTIFICATE OF APPROVAL No CF 694 This is to certify that, in accordance with TS00 General Requirements for Certification of Fire Protection Products The undermentioned products of 3M Centre, Cain Road,

More information

Independent Testing - For End User Confidence

Independent Testing - For End User Confidence Independent Testing - For End User Confidence QUALIFICATION TESTING OF SCREENED CATEGORY 5 (CAT. 5e) CONNECTING HARDWARE ACCORDING TO REQUIREMENTS OF PROPOSED CENELEC 2nd EDITION EN 50173, PROPOSED ISO/IEC

More information

NOTICE OF COMPLETION AND AUTHORIZATION TO APPLY THE UL MARK

NOTICE OF COMPLETION AND AUTHORIZATION TO APPLY THE UL MARK NOTICE OF COMPLETION AND AUTHORIZATION TO APPLY THE UL MARK 2017-05-26 Frank Lofrano IMS ENGINEERED PRODUCTS L L C 1 INNOVATION DR DES PLAINES, IL, 60016-3161, US Our Reference: File E490068, Vol 1 Order:

More information

Select 107 XLS User Instructions

Select 107 XLS User Instructions Select 107 XLS User Instructions A timeswitch allows you to set On and Off time periods. The timeswitch will allow you to set the On and Off time periods for either Hot water or Central heating to suit

More information

itac120m Series Intelligent Hot-Pluggable Phasing Miniature Switch Modules

itac120m Series Intelligent Hot-Pluggable Phasing Miniature Switch Modules itac120m Series Intelligent Hot-Pluggable Phasing Miniature Switch Modules Domestically Leading Hot-Pluggable and Phase Selecting Technologies Secondary PCB Connection Technology Contents I. Application

More information

SPI PowerNet requirements for the non-contestable Interface Works at Deer Park Terminal Station

SPI PowerNet requirements for the non-contestable Interface Works at Deer Park Terminal Station SPI PowerNet requirements for the non-contestable Interface Works at Deer Park Terminal Station SPI PowerNet Reference: ZD23 Version: 1.1 Issue date: 15 May 2014 Contents 1 Scope... 3 2 Deer Park Terminal

More information

CTO Server and Network Cabinets

CTO Server and Network Cabinets DeltaV Distributed Control System Product Data Sheet January 2018 CTO Server and Network Cabinets CTO Server and Network Cabinet. Delivers standard cabinet with 19 frame construction for your DeltaV networking

More information

Bombay Stock Exchange Limited

Bombay Stock Exchange Limited Bombay Stock Exchange Limited APPLICATION FOR NETWORK CONNECTIITY FOR CDSL OPEARTION To be filled in by the CDSL Member and submitted to CDSL 16 th Floor, P.J. Towers, Mumbai 400 001. 1. Participant details

More information

INTRINSICALLY SAFE Ex ia PSU TYPE AC36W

INTRINSICALLY SAFE Ex ia PSU TYPE AC36W Title INTRINSICALLY SAFE Ex ia PSU TYPE AC36W USER MANUAL Document Number 66-184-12 Issue 10 10 Update new logo and address 2017.10.18 CW CW PC 09 Added Um as 265V, Io up to 3.3A & IIB data 2017.08.21

More information

Line Interactive 1000VA/1400VA/2000VA Uninterruptible Power System

Line Interactive 1000VA/1400VA/2000VA Uninterruptible Power System USER MANUAL Line Interactive 1000VA/1400VA/2000VA Uninterruptible Power System 614-06762-00 IMPORTANT SAFETY INSTRUCTIONS SAVE THESE INSTRUCTIONS This manual contains important instructions for Line Interactive

More information

Desh Polytechnic College Mirpur-11, Dhaka-1216 Class Routine: 5th Semester (Civil Technology-64)

Desh Polytechnic College Mirpur-11, Dhaka-1216 Class Routine: 5th Semester (Civil Technology-64) Class Routine: 5th Semester (Civil Technology-64) Foundation Engineering (6451) Accounting (5851) All R-408(XYZ) Engineering- 1 (6453) Foundation Engineering (6451) Accounting (5851) All R-408(XYZ) Engineering-1

More information

BA684DF-P PROFIBUS PA Field mounting Fieldbus Display

BA684DF-P PROFIBUS PA Field mounting Fieldbus Display BA684DF-P PROFIBUS PA Field mounting Fieldbus Display Issue: 3 Issue: 3 8 th December 2011 2 CONTENTS 1. Description 1.1 Documentation 1.2 Version 3.0 firmware 2. Operation 2.1 Controls 3. System Design

More information

SW-PM POLE MOUNT BRACKET

SW-PM POLE MOUNT BRACKET SW-PM POLE MOUNT BRACKET INSTALLATION GUIDE V1.00 JULY 2017 The P.Audio SW-PM pole mount system is an easy to install and flexible system designed to allow the P.Audio SW series of enclosures to be mounted

More information

ENCLOSURE HEAT DISSIPATION

ENCLOSURE HEAT DISSIPATION ENCLOSURE HEAT DISSIPATION DATA CENTER SOLUTIONS A White Paper by Great Lakes Case & Cabinet Company www.werackyourworld.com 814.734.7303 Page 2 Introduction Dangerous heat levels inside an enclosure threaten

More information

3 BUTTERFLY VALVE MAINTENANCE MANUAL //

3 BUTTERFLY VALVE MAINTENANCE MANUAL // 3 BUTTERFLY VALVE MAINTENANCE MANUAL // MM008 REV01-27.08.13 IMPORTANT: PLEASE READ THE INSTRUCTIONS IN FULL PRIOR TO COMMENCING WORK ON THE VALVE. Manual Contents Valve Identification. General Assembly

More information

Wireless 7 Day Programmable Room Thermostat

Wireless 7 Day Programmable Room Thermostat Wireless 7 Day Programmable Room Thermostat Model: TRT037N Installation & Operating Instructions 1. General Information These instructions should be read carefully and retained for further reference and

More information

U.S. Price List and Part Selector Guide

U.S. Price List and Part Selector Guide TJC-L-207-022 Effective Date 02-2-207 (Supercedes Previous Versions) U.S. Price List and Part Selector Guide Price in U.S. Dollars AICKINSTRUT CHANNEL FRAMING - TYPES P (GRAY), V (BEIGE) AND E (GRAY) PRICE/LF

More information

MPS-600 e-drum set. assembly instructions

MPS-600 e-drum set. assembly instructions MPS-600 e-drum set assembly instructions Musikhaus Thomann e.k. Treppendorf 30 96138 Burgebrach Germany Telephone: +49 (0) 9546 9223-0 E-mail: info@thomann.de Internet: www.thomann.de 26.07.2012 Table

More information

Reservation QA Desk Review Procedure

Reservation QA Desk Review Procedure Reservation QA Desk Review Procedure A. Start the DESK Review: 1. Open the project s Reservation JRT. 2. Open blank Advanced DESK template 4-8-4-8. 3. Import JRT data into DESK template: Home >> Data >>

More information