Universal Serial/PROFIBUS DP Gateway GT200-DP-RS User Manual V6.1 SST Automation

Size: px
Start display at page:

Download "Universal Serial/PROFIBUS DP Gateway GT200-DP-RS User Manual V6.1 SST Automation"

Transcription

1 GT200-DP-RS V6.1 SST Automation

2 Catalog 1 About the Gateway Product Function Product Features Technical Specifications Related Products Quick Start Guide Power Wiring Wiring with PC Configuration Method Wiring with Serial Device Wiring PROFIBUS DP Interface Debug Hardware Descriptions Product Appearance Indicators LED Display and Button LED Display PROFIBUS DP Address Setting Button Interface Power Interface PROFIBUS DP Interface RS-485/RS-422 Interface RS-232 Interface Working Principle Modbus Master Modbus Slave Universal Mode Data Exchange Universal Protocol Software Instructions Notes before Configuring User Interface The Operation of Equipment View Equipment View Interface Operation Mode of Equipment View Operation Types of Equipment View The Operation of Configuration View Interface of Fieldbus Configuration View Interface of Subnet Configuration View

3 6.4.3 Interface of Node Configuration View Interface of Command Configuration View Notes View Conflict Detection Operation of Command List Operation of Memory Mapping Area Hardware Communication Serial Configuration Upload Configuration Download Configuration Load and Save Configuration Load Configuration Project Save Configuration Project Export EXCEL Debug Debug Interface of 4.X or 3.X Debug Interface of 5.x and above PROFIBUS DP Hardware Configuration Instructions Register GSD file DPRS2A.GSD-Configuration software configuration mode use DPRS2M.GSD-DP Hardware Configuration of Modbus master DPRS2S.GSD-DP Hardware Configuration of Modbus slave DPRS2T.GSD-DP Hardware Configuration of User Config Installation Machine Dimension Installation Method...69 Appendix A: Using STEP 7 to Set PROFIBUS DP Appendix B: How STEP7 Access Data of Gateway and Select Data Module How STEP7 Access Data of Gateway...78 How STEP7 Select Data Module

4 1 About the Gateway 1.1 Product Function The gateway GT200-DP-RS enables data to establish communication between the serial port and PROFIBUS DP (PROFIBUS DP master such as Siemens PLC). At the same time it can remotely obtain real-time I / O data, status and other information of the connected PLC and serial device via docking cloud platforms such as bokaiyun to achieve remote monitoring. The gateway can connect multiple devices with Modbus/RS-485/RS-232/RS-422 interface with PROFIBUS DP, meaning that Modbus/RS-485/RS-232/RS-422 network devices can be converted to PROFIBUS DP network devices. 1.2 Product Features Wide Application: Any devices with RS-485/RS-232/RS-422 can be connected to PROFIBUS DP network through GT200-DP-RS. For example Variable-frequency Drive with Modbus protocol interface, Motor starting protector, transmitters. Easy to use: Users don t need to know more knowledge about PROFIBUS and Modbus, and they can configure the gateway according to the user manual in a short time without complex programming. Transparent communication: Users can refer to mapping relations between PROFIBUS DP data area and Modbus data area to realize the transparent data communication between PROFIBUS DP and Modbus. 1.3 Technical Specifications 1. Act as a PROFIBUS DP slave at the side of PROFIBUS DP, while Modbus master, Modbus slave and Universal mode can be selected at serial side and serial interface can be selected RS-232, RS-485 or RS-422. The mapping of PROFIBUS DP and Modbus communication data area can achieve transparent communication of PROFIBUS and Modbus; 2. Serial: RS-485, RS-232, RS-422, half-duplex. Baud rate: 300, 600, 1200, 2400, 4800, 9600, 19.2 K, 38.4K, 57.6K and 115.2Kbps can be selected. Parity check mode: None, Odd Even, Mark and space can be selected; 4

5 3. As a Modbus master, it supports 01H, 02H, 03H, 04H, 05H, 06H, 0FH and 10H function codes. Use configuration software to configure: It can be configured up to 100 Modbus commands. 03H and 04H support "Word / Byte mapping". Through the high-byte or low-byte mapping of the registers can effectively utilize PROFIBUS DP input-byte; Support monitoring status of Modbus slave; Support clearing data or keep the last data when input-data is abnormal; Support re-transmitting data when response is timeout; Hardware configuration of PROFIBUS DP master (Abbr. DP master hardware configuration): Support configuring at most 48 Modbus commands; Support monitoring status of Modbus slave; Support clearing data or keep the last data when input-data is abnormal; Support re-transmitting data when response is timeout; 4. Modbus slave supports 01H, 02H, 03H, 04H, 05H, 06H 0FH and 10H function codes; 5. Support the control mode of character timeout and character number in universal mode, and have the function of sending automatically; 6. DP/V0 PROFIBUS DP communication capability, in accordance with EN50170; 7. As a PROFIBUS DP slave, baud rate is self-adaptive, and the maximum baud rate is 12Mbps; 8. PROFIBUS DP input-byte and output-byte number can be freely set and the maximum input and output bytes are: Max Input bytes 244 Bytes Max Output bytes 244 Bytes Max Input Bytes + Output Bytes 488Bytes 9. Support clearing data or keep the last data when input-data is abnormal; 10. Update firmware function; 11. Power: 24VDC (11V~30V), 80mA; 12. Working circumstance temperature: -4 ~140 (-20 ~60 ), Humidity: 5%~ 95% (non-condensing); 13. External dimensions (W*H*D): 0.98 in*3.94 in *3.54 in (25mm*100mm*90mm); 14. Installation: 35mm DIN RAIL; 15. Protection Level: IP20; 16. Test standard: In accordance with EMC test standard. 5

6 1.4 Related Products Other related products in SSTCOMM: GT100-DP-RS and so on. If you want to get more information about these products, please visit SSTCOMM website: 6

7 2 Quick Start Guide 2.1 Power Wiring The power is 24V DC, wiring method is shown as follow: 2.2 Wiring with PC Establish the connection the RS-232 interface of gateway with PC, the wiring method is shown as follow: 2.3 Configuration Method GT200-DP-RS V6.1 version product supports two methods to configure: One is through configuration software, the 7

8 other is through DP hardware configuration (this method is new added function of V6.X). It also supports USB and RS232 interface to configure. The LED Display of GT200-DP-RS will show in DP slave address and -U or -P alternately. When showing -U on LED Display, the gateway is in the Software configuration state; When showing -P, it means the gateway is in DP Hardware Configuration state. 1) When using Setting through configuration software, users can choose to use USB interface or RS-232 interface to configure. If users use USB interface to configure it, they can download and upload the configuration under run and configuration mode. USB interface can auto-detect and switch to the configuration mode. If users use RS-232 interface to configure the gateway, GT200-DP-RS should be entered into configuration mode and finish upload and download tasks. How to enter into configuration mode? Power on GT200-DP-RS, long press button for 5s, LED display shows CF blinking. Click the button again to enter into configuration mode, LED display shows CF on. Configuration software is named SST-MPG-CFG. Double click the application and install the configuration software SST-MPG-CFG. Users can finish the installation lightly according to the wizard. Power on GT200-DP-RS, long press button for 5s, LED display shows CF blinking. Click the button again to enter into configuration mode, LED display shows CF on. Open the software SST-MPG-CFG and users can configure GT200-DP-RS. 2) Use DP Hardware Configuration way, first of all, users should confirm that LED display is showing -P, if it shows -P, that means the gateway has been entered into DP Hardware Configuration status. Users can configure the gateway in DP hardware configuration, no need to upload/download configuration in the software; If the LED display shows -U, users should download the configuration that is DP Hardware Configuration in SST-MPG-CFG to let the gateway enter into this mode, then users can use DP Hardware way to configure the gateway. 8

9 2.4 Wiring with Serial Device After finishing configuration, wire communication interface, the wiring method of RS-232 is the same with "wiring with PC", the wiring method of RS-485 is shown as follow: The wiring method of RS-422 is shown as follow: 9

10 When RS-485 is in the communication of point to multi-point, to prevent the reflection and obstruction of signal, users need to use two terminal resistances in furthest ports of line, and the parameters are 120Ω 1/2W. Note: There is no terminal resistor inside RS-485 interface of GT200-DP-RS. 2.5 Wiring PROFIBUS DP Interface Suggest wiring PROFIBUS DP with standard PROFIBUS DP connector. The description of PROFIBUS DP interface has been shown in chapter Set the address of PROFIBUS DP through button on the panel. Under normal run mode, LED display shows the address of PROFIBUS DP. Register GSD file to PROFIBUS DP master configuration software (STEP7), and configure parameters. 10

11 PBF light being off and STA light being blinking show the connection with PROFIBUS DP master is successful! 2.6 Debug GT200-DP-RS supports three operating modes: Modbus Master, Modbus Slave and User Config. GT200-DP-RS supports debugging function in three modes. Quickly press the button for 3 times, GT200-DP-RS enter into debug mode, the LED display shows db always on. Notes: Under Software Configuration mode, the gateway can enter into Debug without DP master; Under DP Hardware Configuration mode, the Debug function is enabled when connecting DP master, it is disabled without DP master communication. 11

12 3 Hardware Descriptions 3.1 Product Appearance Power Interface Indicators Button USB Interface LED Display PROFIBUS DP Interface RS-232 Interface RS-485/RS-422 Interface Note: This picture is for reference only. Product appearance should accord to the real object. 12

13 3.2 Indicators GT200-DP-RS Indicators State Description Always Red PROFIBUS DP communication fails. PBF Close Communication is ok. PB Green Blinking PROFIBUS DP is communicating. STA Close PROFIBUS DP is not communicating. Green Blinking RS-485/422 port is sending data. TX RS-232/485 Close RS-485/422 port isn't sending data. /422 Green Blinking RS-485/422 port is receiving data. RX Close RS-485/422 port isn't receiving data. 3.3 LED Display and Button LED Display LED display is in the front of the product. There are three display conditions: 13

14 LED display CF db Number+ -P or -U alternate blinking Description The gateway is in the configuration mode. The gateway is in the debug mode. The gateway is in the run mode. The number shows the PROFIBUS DP slave address. -U shows the gateway is in the Software Configuration mode; -P shows the gateway is in the DP Hardware Configuration mode PROFIBUS DP Address Setting Button Configuration button on the front panel can be used to set the address of the PROFIBUS DP slave. Now, we have three operation ways to provide users. 1) Under normal working condition of the GT200-DP-RS, digital tube always displays the address of the current PROFIBUS DP address. Quickly press (double-click) the button twice in succession, the high bit starts flash, and the low bit always on, click the button to add 1 to start setting the PROFIBUS DP address high bit. Long-press the button for 2.5 seconds, the high bit is always on, and the low bit starts flash. Click the button to add 1to start setting the PROFIBUS DP address low bit. Then long-press the button for 2.5 seconds to save DP address. 2) Long press button for 5 seconds, LED display shows CF blinking, click button to enter into configuration state, the LED display shows CF on, users can upload and download the configuration under this mode. When it is done, long press 2.5 seconds to enter into the run mode, the LED display shows DP address. 3) Quick click the button for three times in 3s to enter into debug mode, the LED display shows db is always on. Users can do the serial debugging and other actions. When it is done, click the button three times in 3s to enter into the run mode, the LED display shows DP address. Notes: After entering into PROFIBUS DP address setting, the gateway will exit the address setting state automatically and keep showing the original address without any action button within 10 seconds. The settable range of PROFIBUS DP address is 0~99 (DEC). The operation instruction of button is shown as below: 14

15 3.4 Interface Power Interface GND NC 24V+ Pin Function 1 GND 2 NC(No Connect) 3 24V+, DC plus 24V PROFIBUS DP Interface 5 GND (Pin 5) PROFI_A (Pin 8) PROFI_B (Pin 3)

16 PROFIBUS DP interface uses DB9 male-connector, and the pins are defined as follow: Pin Function 3 PROFI_B, Data positive 4 RTS 5 GND 6 +5VOutput 8 PROFI_A, Data negative Bolt SHIELD, Bus cable shield ground PROFI_B (pin 3), PROFI_A (pin 8) and the shield GND (bolt) must be connected; RTS (pin 4) can be used to determine the direction of transmission by equipment; +5 V (Pin 6) and GND (Pin 5) are used for the bus terminal, and can also be used supply to fiber optic transceivers. The maximum output current of pin 5 and pin6 is 80mA RS-485/RS-422 Interface The RS-485 interface of GT200-DP-RS is standard, and the RS-485 characteristics of the product are shown as follows: 1. The basic characteristics of RS-485 transmission technology 1 Network topology: Linear bus, there are active bus termination resistors at both sides. 2 Transfer rate: 300 bps~115.2kbps. 3 Media: Shielded twisted-pair cable and also can cancel the shielding, depending on environmental conditions (EMC). 4Site number: 32 stations per subsection (without repeater), and can up to 127 stations (with RS-485 repeater). 5Plug connection: 3-pin pluggable terminal. 2. The main points on RS-485 transmission equipment installation 1All the equipment be connected with RS-485 bus; 2Subsection can be connected up to 32 sites; 3The farthest end of each bus has a termination resistor 120Ω 1/2W to ensure reliable operation of the network. Serial interface uses 5-pin pluggable terminal and users can wire it according to the wiring instructions on the panel. 16

17 Pin Function 1 R-, RS-422 Receive Negative 2 R+, RS-422 Receive Positive 3 GND 4 D-, RS-485/RS-422 Transmit Negative 5 D+, RS-485/RS-422Transmit Positive RS-232 Interface RS-232 interface uses a 3-pin pluggable open terminal, and its pin description is shown as follows: Pin Function 1 RX, Connect user device RS-232's RX 2 TX, Connect user device RS-232's TX 3 GND, Connect user device RS-232's GND 17

18 4 Working Principle 4.1 Modbus Master The data conversion between Modbus and PROFIBUS of GT200-DP-RS is established by mapping. GT200-DP-RS has two data buffers, one is PROFIBUS network input buffer; the other is PROFIBUS network output buffer. Command ID 1, 2, 3 and 4 of Modbus puts the data read from Modbus slave station into network input buffer for reading by PROFIBUS network; Command ID 5, 6, 15 and 16 of Modbus write the data from network output buffer into Modbus slave station. Input buffer Output buffer Modbus Device 1 Modbus Device 3 Modbus Device 2 Modbus Device 4 Support 01H, 02H, 03H, 04H, 05H, 06H, 0FH, 10H function codes, when using DP Hardware Configuration, users can configure 48 Modbus commands Module. When using Software Configuration, users can configure at most 100 Modbus commands in the software SST-MPG-CFG. 4.2 Modbus Slave The data conversion between Modbus of GT200-DP-RS Modbus Slave and PROFIBUS is established by mapping relation. GT200-DP-RS has two data buffers, one is PROFIBUS network input buffer, and the other is PROFIBUS network output buffer. Network input and output buffers are relative to PROFIBUS. Modbus write-register commands write data 18

19 into network input buffer for PROFIBUS network reading. Modbus read-register commands data from network output buffer, and transmit to Modbus master device through response messages. PROFIBUS PROFIBUS Input buffer Output buffer Modbus write commands: 06H 4xxxx (40001) 3xxxx (30001) Modbus read and 10H (40002) (30002) commands: 04H Modbus read commands: 03H (40003) (30003) Modbus write commands: 05H 0xxxx (00001) 1xxxx (10001) Modbus read and 0FH (00002) (10002) commands: 02H Modbus read commands: 01H (00003) (10003) Support Modbus register address area 3 (3xxxx), area 4 (4xxxx), area 0 (0xxxx) and area 1 (1xxxx); and area 3 supports 04H function code; area 4 supports 03H, 06H, and 10H function codes; area 0 supports 01H, 05H, and 0FH function codes; 1 area supports 02H function code. PROFIBUS DP input buffer being relative to Modbus side is Modbus master output, mapping to Modbus holding registers 4xxxx (10H and 06H commands are used to write data, 03H command is used to read back data) and loops 0xxxx (0FH and 05H commands are used to write data, 01H command is used to read back data). PROFIBUS DP output buffet being relative to Modbus side is Modbus master input, mapping to Modbus input registers 3xxxx (04H command is used to read data) and input bits 1xxxx (02H command is used to read data). 19

20 5 Universal Mode 5.1 Data Exchange This product provides data communication between PROFIBUS DP and RS-485/RS-232. The communication between PROFIBUS DP and RS-485/RS-232 is bidirectional. The output data of PROFIBUS DP can be sent to RS-485/RS-232 fieldbus through the interface of RS-485/RS-232 and the data received from RS-485/RS-232 is put into input data of PROFIBUS DP. Data exchange is shown as follows: PROFIBUS DP PROFIBUS output data PROFIBUS input data Eo i D1 D2 Di 0 Ei j D1 D2 Dj 0 GT200-DP-RS Serial output data Serial input data D1 D2 Di D1 Dj RS -485/RS -232 Above, "EO" is transaction number of PROFIBUS output data; "i" is serial data number included in output data being transmitted; "D1" to "Di" are data being transmitted by serial; "Ei" is transaction number of PROFIBUS input data; "j" is serial data number included in input data receiving form serial; "D1" to "Dj" are data receiving form serial. 20

21 5.2 Universal Protocol PROFIBUS DP output data format: [Transaction number][length of serial output data n][serial output data 1] [Serial output data n] [0x00] [0x00] n m Note: The number of PROFIBUS DP output byte should be greater than or equal to n + 1; M 0x00 are filling data (also for arbitrary number); n + m +1 should be equal to the number of PROFIBUS DP output-byte. Transaction number: When transmit output data; the transaction number must add 1 to show a new frame data. Example: If users select the number of PROFIBUS DP input byte and output-byte is 8-byte input and 8-byte output, length of serial output-data is 3, data are Current transaction number is 0. The format of output-data is: [01][03][01][02][03][00][00][00][00] PROFIBUS DP input data format: [Transaction number][length of serial input data n] [Serial input data 1] [Serial input data n] [0x00] [0x00] n m Note: The number of PROFIBUS DP input byte should be greater than or equal to n + 1; M 0x00 are filling data (also for arbitrary number); n + m +1 should be equal to the number of PROFIBUS DP input-byte. Transaction number: The transaction number adds 1 showing a new frame input data. Example: 21

22 If users select the number of PROFIBUS DP input-byte and output byte is 8-byte input and 8-byte output, length of serial input-data is 3, data are Current transaction number is 0. The format of input data is: [01][03][04][05][06][00][00][00][00] 22

23 6 Software Instructions 6.1 Notes before Configuring SST-MPG-CFG is a product based on Windows platform, and it can set related parameters and commands of Modbus and PROFIBUS DP of GT200-DP-RS. Double-click the icon to enter configuration interface: 6.2 User Interface SST-MPG-CFG interface include: title bar, menu bar, toolbar, status bar, equipment section, configuration section and notes section. Note: All the gray part in the software cannot be modified. 23

24 Menu bar Title bar Toolbar Equipment section: can choose the operating targets, including fieldbus or sub-network and add the nodes and commands. Configuration section: input configuration parameters, gray part cannot be modified, while white part can be modified. Notes section: The specific explanation to the nouns appearing in the configuration and devices to help users to understand and operate. Toolbar is shown as below: Functions separately from left to right are: new, save, open, add nodes, delete nodes, add commands, delete commands, upload configuration, download configuration, calculate mapping address, conflict detection, Export EXCEL, debug, edit base address and cancel edit address. New: Create a new configuration project Save: Save the current configuration Open: Open a configuration project Add Nodes: Add a Modbus slave node Delete Nodes: Delete a Modbus slave node 24

25 Add Commands: Add a Modbus command Delete Commands: Delete a Modbus command Upload Configuration: Read the configuration from the module and show it in the software Download Configuration: Download the configuration from the software to the module Calculate Mapping Address: Calculating mapping address automatically Conflict Detection: Detect whether there is conflict in memory data buffer of the gateway Export EXCEL: Export the current configuration to local hard disk and save it as.xls file Debug: For debugging Modbus communications, and defining the network fault Edit Base Address: Advanced function Cancel Base Address: Advanced function 25

26 6.3 The Operation of Equipment View Equipment View Interface Operation Mode of Equipment View The equipment view supports three types of operation: Edit Menu, Edit Toolbar and Right click edit Menu. 26

27 6.3.3 Operation Types of Equipment View 1) Add nodes: Right click on subnet or existing nodes, and then perform the operation of adding a new node. Then there is a new node named "new node" under subnet. 2) Delete nodes: Right click on the node to be deleted, and then perform the operation of deleting the node. The node and its all commands will be deleted. 3) Add commands: Right click on the node, and then perform the operation of adding command to add a command for the node. The dialog box will be shown as follow: Currently, it supports the commands: 01, 02, 03, 04, 05, 06, 15 and 16. Select the command: Double click the command 4) Delete commands: Right-click on the command and then perform the operation of deleting the command. 5) Rename nodes: Left click on the node to be renamed, and then the edit status will be shown and you can rename it. 6) Copy node: Left click on the existing node, choose the node and execute the operation of copying nodes (include all commands under the node) 7) Paste node: Left click and choose any existing node, execute operation of pasting node. Then under the subnet tree you can see a new node (include all commands under the node); Parameters of new node is default setting, it needs to be 27

28 reset. 6.4 The Operation of Configuration View Interface of Fieldbus Configuration View In the interface of device view, click fieldbus, and then the configuration view is shown as follows: Configurable items include: "Type of Protocol", "Size of PROFIBUS DP Input buffer", "Size of PROFIBUS DP Input buffer", "How to action after N successive response timeout", "Successive response timeout for N times", "PROFIBUS address", "Compatliblity mode" and "Parameter configuration options". Size of PROFIBUS DP Input buffer: Set in PROFIBUS DP master configuration software, cannot be modified; Size of PROFIBUS DP Input buffer: Set in PROFIBUS DP master configuration software, cannot be modified; How to action after N successive response timeout: Clear data or Hold data can be selected; Successive response timeout for N times: 2 to 254 can be selected; PROFIBUS address: Use the hardware to set the address or PROFIBUS address can be selected; Compatliblity mode: Open or Close can be selected; Parameter configuration options:setting through configuration software or Setting through Hardware Configuration of PROFIBUS DP can be selected. 28

29 6.4.2 Interface of Subnet Configuration View 1) Choose Modbus Master in protocol type Configurable parameters are shown as follows: Baud Rate, Data Bits, Check Bit, Stop bit, Transmission mode, Response timeout, Delay between Polls, Output Mode, Scan Rate, Status of Modbus Command Response, Communication interface, Time Interval between Character(Sending) and Time Interval between Character(Receiving). Interface of configuration view is shown as below: 29

30 Baud Rate: 300, 600, 1200, 2400, 4800, 9600, 19200, 38400, and bps optional Data bits: 8 Check Bit: none, odd, even, mark and space optional Stop bits: 1, 2 Transmission mode: RTU, ASCII optional Response timeout: When the Modbus master send commands, the time waiting for response from the slave, the range is 5~60000ms. Delay between polls: After one Modbus command has been sent and has received correct response, the delay time before next command being sent, the range is: 0 ~ 2500ms. Output Mode: Modbus writing command (output command) has 3 kinds of outputting modes: Cycle, Forbidden and Change of Value output. Cycle: The same with Modbus read command, and output according to the scanning ratio. Forbidden: Prohibit outputting Modbus write command. Change of Value: When the output data has changed, it outputs the write command and stop outputting after receiving 30

31 correct response. time. GT200-DP-RS Scan rate: Ratio of slow scan and fast scan. If the fast scan command sends 10 times, slow scan command sends 1 Status of Modbus Command Response: disable, 1byte, 2bytes, 3bytes, 4bytes, 5bytes, 6bytes, 7bytes, 8bytes, 9bytes, 10bytes, 11bytes, 12bytes and 13bytes can be selected. They locate in the first several bytes of PROFIBUS input data and show the status of Modbus commands. The bit 0 of the first byte shows the status of the first Modbus command and six bytes can show all status of 48 commands. The value of status is 0, when the communication is OK and the value is 1. RS-485) Communication interface: There are RS-232 and RS-485 to be selected. (Note: If using the RS-422, here select Time interval between Characters (Sending): Serial port of GT200-DP-RS will send every byte according to the time interval. The range of value is 0 to 600, and the unit is 0.1ms. If the value is 100, then the time interval is 100* 0.1 ms =10ms. (Note: The time interval does not contain/cover the frame interval of Modbus protocol) Time interval between Characters (Receiving): Serial port of GT200-DP-RS will use this time interval as the judge receiving end basis. The range of value is 0 to 600, and the unit is 0.1ms. If the value is 100, then the time interval is 100* 0.1 ms =10ms. (Note: The time interval does not contain/cover the frame interval of Modbus protocol) Note: The reference time of gateway receiving data and broking frame: Time interval between characters (Receiving) character time of Modbus protocol. Make sure that the response wait time is greater than time interval between characters character time. 2) Choose Modbus Slave in protocol type Configurable parameters are shown as follows: Baud Rate, Data Bits, Check Bit, Stops Bits, Slave Address, Transmission Mode, Communication Interface, Time interval between Character (Sending) and Time Interval between Character (Receiving). Interface of configuration view is shown as follow: 31

32 Baud Rate: 300, 600, 1200, 2400,4800, 9600, 19200, 38400, and bps optional. Data Bits: 8 Check Bit: none, odd, even, mark and space optional Stop Bits: 1, 2 Slave Address: range is 0~247. Transmission Mode: RTU, ASCII Communication Interface: There are RS-232 and RS-485 to be selected. (Note: If using the RS-422, here select RS-485) Time interval between Characters (Sending): Serial port of GT200-DP-RS will send every byte according to the time interval. The range of value is 0 to 600, and the unit is 0.1ms. If the value is 100, then the time interval is 100* 0.1 ms =10ms. (Note: The time interval does not contain/cover the frame interval of Modbus protocol) Time interval between Characters (Receiving): Serial port of GT200-DP-RS will use this time interval as the judge receiving end basis. The range of value is 0 to 600, and the unit is 0.1ms. If the value is 100, then the time interval is 100* 0.1 ms =10ms. (Note: The time interval does not contain/cover the frame interval of Modbus protocol) 32

33 3) Choose User Config in protocol type: Configurable parameters are shown as follows: Baud Rate, Data Bits, Check Bit, Stop Bits, Frame Type, Time interval between Characters, Frame Length, Enable Auto Sending, Period of Auto Sending, Enable CRC Check, Communication Interface, Time interval between Character (Sending) and Time interval between Character (Receiving). Interface of configuration view is shown as follow: Baud Rate: 300, 600, 1200, 2400, 4800, 9600, 19200, 38400, and bps optional Data Bits: 8 Check Bit: none, odd, even, mark and space optional Stop Bits: 1, 2 Frame Type: Time Interval between Characters, Frame length optional Time interval between characters: It is maximum time interval between characters and used to decide whether a frame is terminated or not. User input, the default is 10, and the range is 10 ~ 60000ms. Frame Length: User input, the default is 111 and the range is 1 ~ 223, only valid when the frame type is frame length. 33

34 Enable Auto Sending: There are Enable and Disable to be selected. Period of Auto Sending: User input, the default is 1000 and the range is 10 ~ 60000ms, only valid when the Enable Auto Sending is Enabled Enable CRC Check: Enable, Disable optional Communication Interface: RS-232, RS-485 optional. (Note: If using the RS-422, here select RS-485) Time interval between Characters (Sending): Serial port of GT200-DP-RS will send every byte according to the time interval. The range of value is 0 to 600, and the unit is 0.1ms. If the value is 100, then the time interval is 100* 0.1 ms =10ms. (Note: The time interval does not contain/cover the frame interval of Modbus protocol) Time interval between Characters (Receiving): Serial port of GT200-DP-RS will use this time interval as the judge receiving end basis. The range of value is 0 to 600, and the unit is 0.1ms. If the value is 100, then the time interval is 100* 0.1 ms =10ms. (Note: The time interval does not contain/cover the frame interval of Modbus protocol) Interface of Node Configuration View When the protocol type of subnet is "Modbus Master", in the interface of device view, left click a node, and then configuration interface is shown as follow: 34

35 In the moment, you can modify the Modbus slave node address in the configuration view interface Interface of Command Configuration View In the interface of device view, left click a command and then configuration interface is shown as follow: 35

36 Configurable parameters are shown as follows: Starting Address, Number of Data, Mapping Address (HEX), Mapping Bit (0~7) and Type of Scan Starting Address: The starting address of register or switching value or loop and so on in Modbus slave and the range is 0~ Notes: This address in SST-MPG-CFG is protocol address, when users input PLC address, it will pop up the below dialog box after entering. After clicking OK, the PLC address users input will be converted into protocol address. Following table shows the PLC address and corresponding protocol address examples: Command PLC address examples Corresponding protocol address Coil state 00001~ ~00009 Input state 10001~ ~00009 Holding register 40001~ ~00009 Input register 30001~ ~

37 Number of Data: number of register/switching value/coil in Modbus slave Mapping address (HEX): The starting address of data in memory buffer of the module. The address range of data mapping in the module memory: Read command: 0x0000~ 0x00F3 Write command: 0x4000 ~ 0x40F3 When write command is used exchanging locally, it also can use: 0x0000 ~ 0x00F3 Mapping bit (0-7): For the bit operation commands, the position range of start-bit byte is 0 ~ 7 Data filter: There are three kinds of types: full word, high byte, low byte. Every register has two bytes. Full word mapping is taking two bytes of register into gateway memory buffer; High byte mapping is taking the high byte of register into gateway memory buffer; Low byte mapping is taking the low byte of register into gateway memory buffer. Type of scan: There are two kinds of scanning mode: fast scan and slow scan. It is fit for requests of user about fast scan or slow scan of different commands. Slow scan is equal to fast scan being multiplied by scan ratio. (Configure it in the interface of subnet configuration interface) Byte Swap: There are three kinds of types: no swap, double-byte swap and four-byte swap. Modbus function code 03H, 04H, 06H and 10H support different byte swap types Notes View Notes view displays the explanation of configuration. The notes that show how to action after N successive response timeout is shown as follow: 37

38 6.5 Conflict Detection For the detection of whether there exists conflict of "the starting address of memory mapping", if conflict it can adjust in time. The interface is shown as follow: 38

39 6.5.1 Operation of Command List All the configuration commands can be shown at the command list. Each select box before command is used for checking the memory-mapping location of that command. Click on the command can select the check box, and in the memory-mapping area it can show the corresponding share of spatial location. Click the command again will remove the selected box and it doesn t show the mapping location. The function can be used to conflict detection of memory mapping area. 39

40 6.5.2 Operation of Memory Mapping Area Memory mapping area is divided two parts: input area and output area. Input-mapping address: 0x0000 ~ 0x3FFF; Output-mapping address: 0x4000 ~ 0x7FFF. Each box represents a byte address. Green: Read command show in the input-mapping area; no conflict; Yellow: Write command show when the mapping addresses in the input area; no conflict; Blue: When the address mapping area is located in the output area; no conflict. Red: Output area or input area, different commands occupy the same byte address, the byte is shown as red. For bit operation commands, the meanings of above shows are also applicable. Click the input-output regional grid, whether the grid is occupied or not is shown as follows: 40

41 6.6 Hardware Communication Hardware communications' menu items are shown as follow: Serial Configuration The software automatically scan the available serial port of system, and the available serial can be shown in serial list. After modifying all items, pressing "OK" to save your settings. Notes: Apart from the serial port number, the other parameters are fixed values: 19200, 8, N,

42 6.6.2 Upload Configuration Choose upload configuration, upload the gateway configuration information from the device to the software, the display interface is shown as follows: Note: Before uploading the configuration, please check whether the "serial port configuration" is the available port Download Configuration Choose download configuration, download the configurated gateway information to the gateway, the display interface 42

43 is shown as follows: GT200-DP-RS port. Note 1: Before downloading the configuration, please check whether the "serial port configuration" is the available Note 2: Before downloading the configuration, make sure that all configurations has been completed. 6.7 Load and Save Configuration Load Configuration Project Choosing "Open" can save a project Save Configuration Project Choosing "Save" can open a saved project before. 43

44 6.8 Export EXCEL Excel document helps users to examine the configuration related. Choose the icon, save the configuration as excel document and choose the right path. Double click to open excel document, three modes as "Modbus master", "Modbus slave", "Universal mode" are different from each other slightly. Modbus master: The document has three parts: "Command List", "Fieldbus", and "Subnet". Command list: Modbus command list 缺少图片 Fieldbus: Bus type and relevant parameters Subnet: Modbus subnet parameters As follows: Modbus slave: The document has two parts: "Subnet" and "Fieldbus". Subnet: Modbus subnet parameters Fieldbus: Bus type and relevant parameters As follows: Universal mode: The document has two parts: "Subnet" and "Fieldbus". 44

45 Subnet: Modbus subnet parameters Fieldbus: Bus type and relevant parameters As follows: 6.9 Debug This function is for debugging Modbus network communications, the interface is shown as follows: Click Debug button will show up the firmware select dialog box, choose the matched version: 45

46 6.9.1 Debug Interface of 4.X or 3.X Firmware Version of 4.X or 3.X only supports debug function in the protocol of "Modbus Master" Status: shows communication state with slave: response ok, response timeout, response abnormal and response error Slave Address: slave address in the configuration file (HEX) Starting Address: "Modbus register starting address" (HEX) in the configuration file Data/Exception Code: display the slave data or exception code (HEX) Memory mapping address: Starting address of data writing in the gateway Data: Data writing into the gateway When Modbus has no response or response timeout: 46

47 When Modbus responses are right: 47

48 packet. After filling the "Memory mapping address" and "Data" correctly, users can click on "Send" button to transmit the 48

49 User clicks on the "Save Content" button can save the received data to a computer's hard disk Debug Interface of 5.x and above Modbus master: 49

50 Status: shows communication state with slave: respond correctly, response timeout, respond abnormally and response error Slave Address: slave address in the configuration file (only master, HEX) Function Code (Command): Modbus command in the configuration file (only master, HEX) Starting Address:"Modbus register starting address" (HEX) in the configuration file (only master, HEX) Data/Exception Code: display the slave data or exception code (HEX) Notes: When the gateway is configured as Modbus master, it will show slave address, function code and starting address. Read Data: show the latest read data (HEX) Memory mapping address: Starting address of data writing in the gateway Data: Data writing into the gateway When users want to fill in correct "memory mapping address" and "data", you can click "send" button to send the 50

51 package out. Save Content/Stop Saving: the software supports saving data to local disk. When saving is over, users need to click "Stop Saving" to save it. Stop Displaying/Continue to Display: the software supports dynamic or static data debugging. Clear Data: click this button, it will clear the data in the debug interface. Stop debug and exit: click the button or the exit button to close the debug interface. Exit: Force quit. When Modbus has response timeout: When Modbus slave responses are right: 51

52 The debug interface of user config and Modbus slave: 52

53 The debug function of user config and slave is send input buffer data and output buffer data of PROFIBUS to the debug interface alternately, users can send debug data to simulate the input data of PROFIBUS. 53

54 7 PROFIBUS DP Hardware Configuration Instructions GT200-DP-RS V6.X version has four GSD files, "Software Configuration" has a corresponding GSD file, and DP Hardware Configuration has three corresponding GSD files. As follows: DPRS2V60A.GSD-Configuration software configuration mode use DPRS2V60M.GSD-DP Hardware Configuration of Modbus master DPRS2V60S.GSD-DP Hardware Configuration of Modbus slave DPRS2V60T.GSD-DP Hardware Configuration under universal mode It needs to import the GSD file in the PROFIBUS DP master configuration software, and then set the relevant parameters. Take the following Step7 configuration software as an example: 7.1 Register GSD file Figure 1: Open an existing project in STEP 7, under the Hardware configuration interface, click Options->Install GSD file, The popup interface is shown as Figure 2, select GSD file needs to be installed, click Install GSD File, and click Close after registering completely, close the register window. 54

55 In the menu, select Options -> Update Catalog, update the registered devices in the device catalog You can find the registered device in the right window /PROFIBUS DP/Additional Field Devices/General/Converter/, shown as Figure 4: 55

56 7.2 DPRS2A.GSD-Configuration software configuration mode use After registering DPRS2A.GSD completely, you can find GT200-DP-RS V6.0 device in the catalog.in the SST-MPG-CFG configuration mode, GT200-DP-RS achieves the functions of the three types of protocols, which are Modbus master, Modbus slave, Universal mode. and perform data exchange between serial port and DP master. In the Step7 configuration, GT200-DP-RS offers Module numbers up to 64, Max Input 244 bytes, Max Output 244 bytes, Max Input or Output 488Bytes. Module Integrity 4 Words Input,4 Words Output word 8 Words Input,8 Words Output word 24 Words Input,24 Words Output word 56 Words Input,56 Words Output word 1 Byte Input byte 1 Word Input word 2 Words Input word 4 Words Input word 8 Words Input word 16 Words Input word 56

57 32 Words Input word 64 Words Input word 2 Words Input Consistent length 4 Words Input Consistent length 8 Words Input Consistent length 16 Words Input Consistent length 1 Byte Output byte 1 Word Output word 2 Words Output word 4 Words Output word 8 Words Output word 16 Words Output word 32 Words Output word 64 Words Output word 2 Words Output Consistent length 4 Words Output Consistent length 8 Words Output Consistent length 16 Words Output Consistent length GT200-DP-RS supports data including word complete, byte complete, and length complete The user selects the data block as long as it is not less than the number of bytes transmitted. who can select one or more data block. 7.3 DPRS2M.GSD-DP Hardware Configuration of Modbus master After registering DPRS2M.GSD completely, you can find GT200-DP-RS Modbus Master V6.0 device in the catalog. That is to say GT200-DP-RS act as a Modbus master at the side of Modbus. 57

58 PROFIBUS DP slave property parameter: In configuration interface, double click GT200-DP-RS Modbus Master V6.0 in PROFIBUS DP network, the popup property interface is shown as follow: Configurable parameters include: Baud rate (bps): Configure serial baud rate, 300, 600, 1200, 2400, 4800, 9600, 19200, 38400, 57600, bps can be selected; Data bits, Parity bit, Stop bits: 8 None 1, 8 Odd 1, 8 Even 1, 8 Mark 1, 8 Space 1 and 8 None 2 can be selected; Protocol Type: If what you drag to the PROFIBUS DP bus is GT200-DP-RSModbus Master, the parameter is Modbus Master, if what you drag to the PROFIBUS DP bus is GT200-DP-RS Modbus Slave, the parameter is Modbus Slave. Response Timeout: It is available when Protocol Type is Modbus Master, 100, 200, 300, 400, 500, 600, 700, 800, 900, 1000, 1500, 2000, 3000, 4000, 5000ms can be selected. Delay Between Polls: It is available when Protocol Type is Modbus Master, No Delay, 50, 100, 150, 200, 300, 400, 500, 600, 700, 800, 900, 1000, 1500, 2000ms can be selected. Transmission Mode: Set Modbus transmission mode, RTU or ASCII can be selected. Write Mode: Set output mode, Change of value or Cycle can be selected. 58

59 Response Timeout Action: Enter Data, Clear / Hold Data, default state is Hold Data; Response Timeout for N times: the number of over times, the input range: 2-254, the default value is 3; Communication Interface: communication interface, RS485 and RS232 can be chosen, the default is RS485. Module Parameter GT200-DP-RS Modbus Master supports modules include: Control Module, Status Module, Exception Module, Read Module, Write Module. The module set as Modbus command is Read Module, Write Module, as follows: Read Module : (Modbus Read Command) Read 1-8 Bits(0xxxx)~Read Bits(0xxxx), Read 1-8 Bits(1xxxx)~Read Bits(1xxxx), Read 1 Words(4xxxx)~Read 64 Words (4xxxx), Read 2 Words(4xxxx)Consistent~Read 16 Words(4xxxx)Consistent, Read 1 Words(3xxxx)~Read 64 Words(3xxxx), Read 2 Words(3xxxx)Consistent~Read 16 Words(3xxxx)Consistent Write Module : (Modbus Write Command)Write Single Bits(0xxxx)~Write Bits(0xxxx), Write Single Words(4xxxx)~Write 64 Words(4xxxx), Write 2 Words(4xxxx)Consistent~Write 16 Words(4xxxx)Consistent~Write 64 Words(4xxxx), Write 2 Words(4xxxx)Consistent~Write 16 Words(4xxxx)Consistent (No. 3 area is the function code 04H; No. 4 area is the function code 03H, 06H, 10H; No. 0 area is the function code 01H, 05H, 0FH; No. 1 area is the function code 02H.) In configuration interface, double-click Module that is already dragged to the left bottom of the GT200-DP-RSrelevant table, the popup interface is shown as follow: 59

60 Configurable parameters include: Slave address: Set Modbus slave address which is needed to connect with GT200-DP-RS, 1 to 247 can be selected; Function: No need to set, every function code has its own module; Starting Address: Set register starting address, 0~65535 can be selected; No. of Points: Number of data, only those modules that are relevant with 01H, 02H, 0FH function codes need to set the number of data; Other Module like Control Module, Stats Module and Exception Module are shown below: Control Module:Control (8 Commands) ~ Control (48 Commands) As a Modbus master, users can control the transmission of Modbus command from the PROFIBUS terminal, the provided 6 control Module can be selected, every GT200-DP-RS only can be configured one control Module. Notes: if no need of the control Modbus command, the control Module is no need to configure, Modbus command can send automatically. Control (8 Commands) ~ Control (48 Commands): Select one kind control from 6, every bit of the control block control 1 Modbus command. When the enable is needed, set 1 to the corresponding bit; otherwise, set

61 a) Control (8 Commands): Control the transmitting of the 8 commands which is after the slots occupied by the Control Module, it occupies 1 byte of the output area. b) Control (16 Commands): Control the transmitting of the 16 commands which is after the slots occupied by the Control Module, it occupies 2 bytes of the output area. c) Control (24 Commands): Control the transmitting of the 24 commands which is after the slots occupied by the Control Module, it occupies 3 bytes of the output area. d) Control (32 Commands): Control the transmitting of the 32 commands which is after the slots occupied by the Control Module, it occupies 4 bytes of the output area. e) Control (40 Commands): Control the transmitting of the 40 commands which is after the slots occupied by the Control Module, it occupies 5 bytes of the output area. f) Control (48commands): Control the transmitting of the 48 commands which is after the slots occupied by the Control Module, it occupies 6 bytes of the output area. Notes: When users add the control block, the control block should be added in front of the slots which occupied by Read Module and Write Module. For example: If users need to configure 7 commands (7 read/write data block) during actual using process, then you can select control block Control (8 Commands), which means the control commands numbers of the selected Control Module should be equals or more than the numbers of the configured commands. Assume the data block of PROFIBUS DP master slots is shown as below: After powering on the gateway, if the communication of PROFIBUS DP is normal (STA green light blinking), users need to evaluate the output address QB0 to enable the required sending command. If only the 2nd (Read 1-8bits (1xxxx) ) 61

62 and the fourth (Read 8 Words (3xxxx) ) command need to be configured by enable, set 1 to the 2nd bit and 4th bit of the first byte in output area. That means evaluate the output address QB0 as 9 ( ). Status Module: Status (8 Commands) ~ Status (48 Commands), Exception Codes As a Modbus master, PROFIBUS side can monitor the status of Modbus commands, and provide two kinds of method to monitor Modbus commands status: Status (8 Commands) ~ Status (48 Commands): Select one kind status from 6, and every bit means the status of every Modbus command respectively. The value is 1 when response is correct, and when times of abnormal response, timeout or error count up to 3 the value is 0. The count clears when response is right. a) Status (8 Commands): Monitoring 8 commands b) Status (16 Commands): Monitoring 16 commands c) Status (24 Commands): Monitoring 24 commands d) Status (32 Commands): Monitoring 32 commands e) Status (40 Commands): Monitoring 40 commands f) Status (48 Commands): Monitoring 48 commands Exception codes: 1 word Module, can monitor the executive condition of Modbus commands High byte indicates Modbus command index 0~47, low byte indicates abnormal code or error code. When response is correct, error code is 0, when response is abnormal or overtime or error, the highest bit of high byte is set to 1. Abnormal code come from devices, the error code is 0xFF when response overtime or error. 7.4 DPRS2S.GSD-DP Hardware Configuration of Modbus slave After registering DPRS2S.GSD completely, you can find GT200-DP-RS Modbus Master V6.0 device in the catalog. That is to say GT200-DP-RS act as a Modbus slave at the side of Modbus. 62

63 PROFIBUS DP slave property parameter: In configuration interface, double click GT200-DP-RS Modbus Slave V6.0 in PROFIBUS DP network, the popup property interface is shown as follow: Configurable parameters include: Baud rate (bps): Configure serial baud rate, 300, 600, 1200, 2400, 4800, 9600, 19200, 38400, 57600, bps can be selected; Data bits, Parity bit, Stop bits: 8 None 1, 8 Odd 1, 8 Even 1, 8 Mark 1, 8 Space 1 and 8 None 2 can be selected; 63

64 Protocol Type: If what you drag to the PROFIBUS DP bus is GT200-DP-RSModbus Master, the parameter is Modbus Master, if what you drag to the PROFIBUS DP bus is GT200-DP-RS Modbus Slave, the parameter is Modbus Slave. selected. Slave Address: When Protocol Type is Modbus Slave, configure the slave address of GT200-DP-RS, 1~247 can be Transmission Mode: Set Modbus transmission mode, RTU or ASCII can be selected. Communication Interfaces: RS458 and RS232 can be selected, the defautl is RS485.. Module Parameter GT200-DP-RS Modbus slave supports modules include: Status Module, Input Module, Output Module. The module set as Modbus command is Input module and Output Module, as follows: Input Module : (Modbus Read Command) 8 Bits Input(0xxxx)~128 Bits Input(0xxxx), 1 Word Input (4xxxx)~64 Words Input (4xxxx), 2 Words Input(4xxxx)Consistent~16 Words Input(4xxxx)Consistent Output Module : (Modbus 写命令 )8 Bits Input(1xxxx)~128 Bits Input(1xxxx), 1 Word Input(3xxxx)~64 Words Input(3xxxx), 2 Words Input(3xxxx)Consistent~16 Words Input(3xxxx)Consistent (No. 3 area is the function code 04H; No. 4 area is the function code 03H, 06H, 10H; No. 0 area is the function code 01H, 05H, 0FH; No. 1 area is the function code 02H.) In configuration interface, double-click Module that is already dragged to the left bottom of the GT200-DP-RSrelevant table, the popup interface is shown as follow: 64

65 10H(16).: Function: When draging one Module, the function is fixed. It means this function includes 03H (3), 06H (6) and Other Module: Stats Module is shown below: Status Module: As modbus slave, PROFIBUS can monitor Modbus network status, PROFIBUS side can provide Modbus network status Module, which occupies one byte. When slave receives one correct request, the status byte add DPRS2T.GSD-DP Hardware Configuration of Universal Mode After registering DPRS2T.GSD completely, you can find GT200-DP-RS Modbus Serial V6.0 device in the catalog. That is to say GT200-DP-RS executes the function of universal mode, which can connect self-defined protocol serial devices

66 PROFIBUS DP slave property parameter: In configuration interface, double click GT200-DP-RS Modbus Slave V6.0 in PROFIBUS DP network, the popup property interface is shown as follow: Configurable parameters include: Baud rate (bps): Configure serial baud rate, 300, 600, 1200, 2400, 4800, 9600, 19200, 38400, 57600, bps can 66

67 be selected; Data bits,parity bit,stop bits:configuration data bits, test mode and stop bits, 8 None 1, 8 Odd 1, 8 Even 1, 8 Mark 1, 8 Space 1, 8 None 2 Optional; Protocol Type:Serial, which means "universal mode", cannot be changed; Receiving Frame Type : There are two control modes for serial receive data. "Time Interval Between Characters" (character timed out) and "Frame Length" (character number)are available. Character timeout: by judging the time interval between characters and characters to determine the end of a frame of serial data; number of characters: by determining the number of characters to determine the end of a frame of serial data. Interval Between Characters (ms): Character Timeout: The maximum time interval between characters and characters in general mode. Frame Length: Number of characters: In general mode, the serial port receives the number of data frame characters. Valid only if the control mode is a number of characters. Enable Auto Sending(ms): Auto send, with "On" and "Off" optional, the default is "off". "Open": send the serial data, according to the automatic send cycle to send serial data. "Off", according to the general mode output rule output data. Period of Auto Sending (ms): Automatic transmission period, the serial port automatically send data cycle. Valid only when "Enable Auto Sending (ms): Auto Send" is on. Enable CRC Check: CRC check, with "On" and "Off" optional, the default is "off". "Open": when serial send data, it will automatically add two bytes of CRC checksum; when serial data receive dataf, it will automatically determine if the CRC check code is normal, and in the PROFIBUS input data automatically remove the two bytes of CRC Check code. Communication Interface: communication interface, RS485 and RS232 optional, the default is RS485. Communication Interface: communication interface, RS485 and RS232 optional, the default is RS485. Input Data Effective Length: PROFIBUS input valid data length, with "on" and "off" optional, the default is "off". "ON": The first byte of the PROFIBUS input data is used to indicate the length of the serial data frame received. "Off": No byte represent data length in the PROFIBUS input data. Module parameter GT200-DP-RS works as a common mode, supports Module include: Input Module and Output Module. Input Module is used to store the contents of the GT200-DP-RS read from the serial device, Output Module is used to store the data 67

68 content of the PROFIBUS DP master output to the serial device. Only set the PROFIBUS DP input / output address, no other parameters need to be set. 68

69 8 Installation 8.1 Machine Dimension Size: 0.98 in (width)*3.94 in (height)*3.54 in (depth) 8.2 Installation Method Using 35mm DIN RAIL 69

70 70

71 Appendix A: Using STEP 7 to Set PROFIBUS DP The following show how to use STEP7 to configure GT200-DP-RS: First of all, copy *. Gsd file to the following path: Step7\S7data\gsd\ 1. Open SIMATIC Manager ; Figure 1: 2. Open File, and then New, create a new project; Figure 2: Figure 1 Figure 2 3. Click Insert, Station and then SIMATIC 300 Station; Figure

72 4. Open S7 PLC hardware configuration Figure 3 Open SIMATIC 300(1) and then double-click Hardware; Figure 4 Figure 4 5. In the menu, select Options and Install GSD file, Update GSD in the device catalog 72

73 Figure 5 6. Here you can find your equipment in the right side of the window ; Figure

74 Figure 6 7. Set PLC rack, click the "Hardware Catalog \ SIMATIC 300 \ RACK-300 \ Rail"; Figure

75 Figure 7 8. Set CPU module and select the corresponding device type and the occupied slots. 9. Create PROFIBUS DP network and set up PROFIBUS DP: Click New and then Network settings, select DP; select a baud rate such as 187.5Kbps, then "OK". Double-click it; Figure

76 10. Select PROFIBUS DP Master address; Figure 9: Figure

77 11. Put configuration into PROFIBUS DP network, and map the input and output data block into other controller s memory; Figure 10: Drag the data to Figure 10 Operation is divided into two steps, the first step is dragging GT200-DP-RS into the network configuration on the upper left, the mouse will change shape, and that is to say, it can be placed. The second step is dragging data block into the data mapping table at the bottom left, mapping to the PLC memory. Note: PROFIBUS input and output bytes of GT200-DP-RSare set in PROFIBUS master configuration software. The max number of modules is 64 when configuring Step7. The max number of input bytes is 244, the max number of output bytes is 244 and the max number of input bytes add output bytes is 488. Note: The address must be the same with the settings of module switch! 12. Compile and download into PLC. 77

Modbus/ PROFIBUS DP Gateway PM-160

Modbus/ PROFIBUS DP Gateway PM-160 Modbus/ PROFIBUS DP Gateway PM-160 REV 3.2 SiboTech Automation Co., Ltd. Technical Support: +86-21-5102 8348 E-mail: support@sibotech.net Table of Contents 1 About This Document... 3 1.1 General... 3 1.2

More information

Catalog 1 Product Overview General Important User Information About the Gateway Function Features Tec

Catalog 1 Product Overview General Important User Information About the Gateway Function Features Tec PROFIBUS DP / Modbus TCP Gateway EP-321MP User Manual REV 1.2 Sibotech Automation Co., Ltd Technical Support: 021-5102 8348 E-mail:support@sibotech.net Catalog 1 Product Overview... 4 1.1 General...4 1.2

More information

HART / EtherNet/IP Gateway GT200-HT-EI User Manual V 1.0 REV A SST Automation

HART / EtherNet/IP Gateway GT200-HT-EI User Manual V 1.0 REV A SST Automation HART / EtherNet/IP Gateway GT200-HT-EI V 1.0 REV A SST Automation E-mail: SUPPORT@SSTCOMM.COM WWW.SSTCOMM.COM Catalog 1 Product Overview... 4 1.1 Product Function...4 1.2 Product Features... 4 1.3 Technical

More information

HART/ Modbus TCP Gateway GT200-HT-MT User Manual V 1.2 REV A SST Automation

HART/ Modbus TCP Gateway GT200-HT-MT User Manual V 1.2 REV A SST Automation HART/ Modbus TCP Gateway GT200-HT-MT User Manual V 1.2 REV A SST Automation E-mail: SUPPORT@SSTCOMM.COM WWW.SSTCOMM.COM Catalog 1 Product Overview... 4 1.1 Product Function...4 1.2 Product Features...

More information

HART/ MODBUS Gateway HTM-611. User Manual REV

HART/ MODBUS Gateway HTM-611. User Manual REV HAT/ MODBUS Gateway HTM611 EV 1.6 SiboTech Automation Co., Ltd. Technical Support: +86215102 8348 Email: support@sibotech.net HAT/ Catalog 1 Product Overview... 4 1.1 Product Function... 4 1.2 Product

More information

Embedded Modbus TCP Module GS11-MT. User Manual REV 1.1. SST Automation.

Embedded Modbus TCP Module GS11-MT. User Manual REV 1.1. SST Automation. Embedded Modbus TCP Module GS11-MT User Manual REV 1.1 SST Automation E-mail: SUPPORT@SSTCOMM.COM WWW.SSTCOMM.COM Catalog 1 About the Embedded Module... 4 1.1 General...4 1.2 Features... 4 1.3 Specifications...4

More information

Table of Contents 1 ABOUT THIS DOCUMENT GENERAL COPYRIGHT INFORMATION TERMS ABOUT THE GATEWAY PRODUCT FUNCTIO

Table of Contents 1 ABOUT THIS DOCUMENT GENERAL COPYRIGHT INFORMATION TERMS ABOUT THE GATEWAY PRODUCT FUNCTIO DeviceNet/PROFIBUS-DP Adapter - User Manual REV 4.0 SiboTech Automation Co., Ltd. Technical Support: +86-21-5102 8348 E-mail:gt@sibotech.net Table of Contents 1 ABOUT THIS DOCUMENT...2 1.1 GENERAL... 2

More information

PROFIBUS DP/CAN Gateway PCA-100. User Manual

PROFIBUS DP/CAN Gateway PCA-100. User Manual PCA-100 REV 4.0 SiboTech Automation Co., Ltd. Technical Support: 021-5102 8348 E-mail: support@sibotech.net Catalog 1 Introduction... 2 1.1 About This Instruction... 2 1.2 Copyright... 2 1.3 Related Products...

More information

SST Automation

SST Automation EtherNet / CAN Gateway GT200-MT-CA REV 1.0 SST Automation E-mail: SUPPORT@SSTCOMM.COM WWW.SSTCOMM.COM Catalog 1 About This Document... 4 1.1 General...4 1.2 Important Information... 4 1.3 Related Products...

More information

VPGate Manual PROFIBUS to serial

VPGate Manual PROFIBUS to serial VPGate Manual PROFIBUS to serial Important information Purpose of the Manual This user manual provides information how to work with the VPGate PROFIBUS to serial. Document Updates You can obtain constantly

More information

i-7550 PROFIBUS to RS-232/422/485 Converter User's Manual High Quality, Industrial Data Acquisition, and Control Products

i-7550 PROFIBUS to RS-232/422/485 Converter User's Manual High Quality, Industrial Data Acquisition, and Control Products i-7550 PROFIBUS to RS-232/422/485 Converter User's Manual High Quality, Industrial Data Acquisition, and Control Products i-7550 PROFIBUS to RS-232/422/485 Converter User's Manual (Version 1.01) PAGE:1

More information

Document Name: User Manual for SC10MK, Modbus RTU to Modbus TCP Converter

Document Name: User Manual for SC10MK, Modbus RTU to Modbus TCP Converter Document Name: User Manual for SC10MK, Modbus RTU to Modbus TCP Converter Login for the first time, please use http://192.168.1.100 To key in user name and password is for identifying authorization. Default

More information

Motortronics VirtualSCADA VS2-MT Communication Gateway VS2-MT User Manual Revision

Motortronics VirtualSCADA VS2-MT Communication Gateway VS2-MT User Manual Revision Motortronics VirtualSCADA VS2-MT Communication Gateway VS2-MT User Manual Revision 1.03.00 Motortronics / Phasetronics 1600 Sunshine Drive Clearwater, Florida 33765 Tel: 727-573-1819 Fax: 727-573-1803

More information

USB to RS-232/RS422/485. US-101-I USB To Serial Operation Manual

USB to RS-232/RS422/485. US-101-I USB To Serial Operation Manual USB to RS-232/RS422/485 US-101-I USB To Serial Operation Manual First Edition, Jun 2008 Table of Contents 1. Introduction 2 2. Package checklist 3 3. Product Specification 4 4. Product Panel Views Description

More information

GE Grid Solutions. P485 Modbus to Profibus Converter. Instruction Manual. GE publication code: A2 (GEK A) LISTED * A2*

GE Grid Solutions. P485 Modbus to Profibus Converter. Instruction Manual. GE publication code: A2 (GEK A) LISTED * A2* GE Grid Solutions P485 Modbus to Profibus Converter Instruction Manual GE publication code: 1601-0237-A2 (GEK-113190A) LISTED *1601-0237-A2* Copyright 2017 GE Multilin Inc. All rights reserved. P485 Modbus

More information

SDM-6RO. Expansion Module 6 relay outputs. Manufactured for

SDM-6RO. Expansion Module 6 relay outputs. Manufactured for Version 1.0 5.02.2014 Manufactured for Thank you for choosing our product. This manual will help you with proper support and proper operation of the device. The information contained in this manual have

More information

G0307 Modbus to PA Gateway User Manual

G0307 Modbus to PA Gateway User Manual G0307 Modbus to PA Gateway User Manual Microcyber Corporation Caution 1. Please don t take off/install temperature board set at random. 2. Please check if the power of gateway meets the power request in

More information

This manual may not be reproduced in whole or in part by any means, without written permission of Accuenergy.

This manual may not be reproduced in whole or in part by any means, without written permission of Accuenergy. Copyright 2008 V1.10 This manual may not be reproduced in whole or in part by any means, without written permission of Accuenergy. The information contained in this document is believed to be accurate

More information

EQ-DCM User Manual Revision 1.02 Sep 10, 2013

EQ-DCM User Manual  Revision 1.02 Sep 10, 2013 EQ-DCM User Manual www.equustek.com Revision 1.02 Sep 10, 2013 Contents INTRODUCTION...5 ABOUT THIS MANUAL... 5 INTENDED AUDIENCE... 5 HARDWARE SPECIFICATIONS...6 PHYSICAL SPECIFICATIONS... 6 HARDWARE

More information

Industrial Serial Device Server

Industrial Serial Device Server 1. Quick Start Guide This quick start guide describes how to install and use the Industrial Serial Device Server. Capable of operating at temperature extremes of -10 C to +60 C, this is the Serial Device

More information

User Manual A08. User Manual

User Manual A08. User Manual A08 TABLE OF CONTENTS TABLE OF CONTENTS... 1 1. INTRODUCTION... 2 1.1. Key Features... 3 1.2. OS Requirement... 4 1.3. Specification... 4 1.4. Packing List... 4 2. OVERVIEW... 5 2.1. LED Definition...

More information

ECAN-240. (Modbus TCP to 2-port CAN Bus Gateway User manual) ECAN-240 Modbus TCP to 2-port CAN Bus Gateway User Manual, Version 1.0.

ECAN-240. (Modbus TCP to 2-port CAN Bus Gateway User manual) ECAN-240 Modbus TCP to 2-port CAN Bus Gateway User Manual, Version 1.0. ECAN-240 (Modbus TCP to 2-port CAN Bus Gateway User manual) ECAN-240 Modbus TCP to 2-port CAN Bus Gateway User Manual, Version 1.0.0 Page: 1 Table of Contents Table of Contents -----------------------------------------------------------------------------2

More information

RS485 MODBUS Module 8AO

RS485 MODBUS Module 8AO Version 1.3 12/02/2013 Manufactured for Thank you for choosing our product. This manual will help you with proper support and proper operation of the device. The information contained in this manual have

More information

GW-7228 J1939/Modbus RTU Slave Gateway

GW-7228 J1939/Modbus RTU Slave Gateway GW-7228 J1939/Modbus RTU Slave Gateway User s Manual www.icpdas.com GW-7228 J1939/Modbus RTU Slave Gateway User s Manual (Ver 1.2, May/2011) ------------- 1 Warranty All products manufactured by ICP DAS

More information

RS485 MODBUS Module 6RO

RS485 MODBUS Module 6RO Version 2.0 12/02/2013 Manufactured for Thank you for choosing our product. This manual will help you with proper support and proper operation of the device. The information contained in this manual have

More information

MGate 4101-MB-PBS Series

MGate 4101-MB-PBS Series MGate 4101-MB-PBS Series 1-port Modbus RTU/ASCII-to-PROFIBUS slave gateways Features and Benefits Protocol conversion between Modbus and PROFIBUS Supports PROFIBUS DP V0 slave Supports Modbus RTU/ASCII

More information

isma-b-mg-ip User Manual Global Control 5 Sp. z o.o. Poland, Warsaw

isma-b-mg-ip User Manual Global Control 5 Sp. z o.o. Poland, Warsaw isma-b-mg-ip User Manual Global Control 5 Sp. z o.o. Poland, Warsaw www.gc5.pl Table of content 1 Introduction... 4 1.1 Revision history... 5 1.2 Safety rules... 5 1.3 Technical specifications... 6 1.4

More information

USER MANUAL FOR FIOA-0402-U-16

USER MANUAL FOR FIOA-0402-U-16 USER MANUAL FOR FIOA-0402-U-16 COPYRIGHT NOTICE This manual is a publication of Renu Electronics Pvt. Ltd. and is provided for use by its customers only. The contents of the manual are copyrighted by Renu

More information

RS-FX-N01 wind transmitter user's Guide (485type)

RS-FX-N01 wind transmitter user's Guide (485type) RS-FX-N01 wind transmitter user's Guide (485type) Issue:. V1. 0 1 2 Context 1. Introduction...4 2. Installation instructions... 5 3. Configure the software installation and use...7 4. Communication Protocol...

More information

Gateway 1400 Reference Manual

Gateway 1400 Reference Manual Profibus-DP Gateway 1400 Reference Manual Copyright All Rights Reserved. No part of this document may be copied, reproduced, republished, uploaded, posted, transmitted, distributed, stored in or introduced

More information

RS485 MODBUS Module 8I8O

RS485 MODBUS Module 8I8O Expansion Module 8 digital inputs, 8 digital outputs Version 2.2 12/01/2014 Manufactured for Thank you for choosing our product. This manual will help you with proper support and proper operation of the

More information

Technical Documentation

Technical Documentation AGILiGATE PROFIBUS - MODBUS Technical Documentation Parc d activités Giraudeau Tel: +33 (0)2 47 76 10 20 6, rue Auguste Perret Fax: +33 (0)2 47 37 95 54 37000 TOURS Email: info@agilicom.fr FRANCE Web:

More information

USER S MANUAL. PH232Ex1. #1 RS-232 Serial Port to Ethernet, Terminal Server/Client. Doc No: PH232Ex1-UM-001 IPEX. (IP Electronix)

USER S MANUAL. PH232Ex1. #1 RS-232 Serial Port to Ethernet, Terminal Server/Client. Doc No: PH232Ex1-UM-001 IPEX. (IP Electronix) USER S MANUAL PH232Ex1 Doc No: PH232Ex1-UM-001 #1 RS-232 Serial Port to Ethernet, Terminal Server/Client IPEX (IP Electronix) Contents 1. INTRODUCTION... 3 2. SPECIFICATIONS... 3 3. PACKAGE CHECKLIST...

More information

SDM-8AO. Expansion Module 8 analog outputs. Manufactured for

SDM-8AO. Expansion Module 8 analog outputs. Manufactured for Version 1.0 16.05.2014 Manufactured for Thank you for choosing our product. This manual will help you with proper support and proper operation of the device. The information contained in this manual have

More information

GW-7238D J1939 to Modbus TCP Server / RTU Slave Gateway

GW-7238D J1939 to Modbus TCP Server / RTU Slave Gateway GW-7238D J1939 to Modbus TCP Server / RTU Slave Gateway User s Manual www.icpdas.com 1 Warranty All products manufactured by ICP DAS are under warranty regarding defective materials for a period of one

More information

R1M-GH THERMOCOUPLE & DC INPUT MODULE MODEL. Remote I/O R1M Series. (16 points)

R1M-GH THERMOCOUPLE & DC INPUT MODULE MODEL. Remote I/O R1M Series. (16 points) Remote I/O R1M Series THERMOCOUPLE & DC INPUT MODULE (16 points) MODEL MODEL & SUFFIX CODE SELECTION R1MGH2T MODEL Modbus protocol I/O TYPE GH2 : Thermocouple or DC input, 16 points FIELD TERMINAL TYPE

More information

Flex Series User Guide

Flex Series User Guide User Programmable Current 4..20mA Digital RS485 Dual & Single Axis Up to 360º 2016 Flex Series User Guide Sensor Installation, Wiring, Flexware App Instructions Page 1 of 33 Page 2 of 33 Table of Contents

More information

The I-7530A-MR Modbus RTU to CAN Converter

The I-7530A-MR Modbus RTU to CAN Converter The I-7530A-MR Modbus RTU to CAN Converter User s Manual Warranty All products manufactured by ICP DAS are under warranty regarding defective materials for a period of one year from the date of delivery

More information

RS 485 Mini Modbus 1AO

RS 485 Mini Modbus 1AO RS 485 Mini Modbus 1AO Version 1.0 14/08/2014 Manufactured for Thank you for choosing our product. This manual will help you with proper support and proper operation of the device. The information contained

More information

NCOM SERIAL DEVICE SERVER 1XX SERIES USER S MANUAL

NCOM SERIAL DEVICE SERVER 1XX SERIES USER S MANUAL NCOM SERIAL DEVICE SERVER 1XX SERIES USER S MANUAL 2017-07-07 Edition Titan Electronics Inc. Web: www.titan.tw Contents 1. INTRODUCTION... 4 1.1 Key Features... 5 1.2 Specifications... 6 2. PANEL LAYOUT

More information

USER S MANUAL. PH485Ex1. #1 RS-485 Serial Port to Ethernet, Terminal Server/Client. Doc No: PH485Ex1-UM-001 IPEX. (IP Electronix)

USER S MANUAL. PH485Ex1. #1 RS-485 Serial Port to Ethernet, Terminal Server/Client. Doc No: PH485Ex1-UM-001 IPEX. (IP Electronix) USER S MANUAL PH485Ex1 Doc No: PH485Ex1-UM-001 #1 RS-485 Serial Port to Ethernet, Terminal Server/Client IPEX (IP Electronix) Contents 1. INTRODUCTION... 3 2. SPECIFICATIONS... 3 3. PACKAGE CHECKLIST...

More information

RS-FS-N01 Wind speed transmitter user's Guide (485type)

RS-FS-N01 Wind speed transmitter user's Guide (485type) RS-FS-N01 Wind speed transmitter user's Guide (485type) Issue: V1.0 1 2 Context 1. Introduction... 4 2. Installation instructions...5 3. Configure the software installation and use... 6 4. Communication

More information

Copyright Extract from Conditions of Sale Safety Warning

Copyright Extract from Conditions of Sale Safety Warning KD420 User Manual Copyright 2004-2013 KK Systems Ltd. No reproduction of any part of this document, in any form, is allowed without prior written permission from KKSystems Ltd. All other copyrights and

More information

NCOM SERIAL DEVICE SERVER 4XX SERIES USER S MANUAL

NCOM SERIAL DEVICE SERVER 4XX SERIES USER S MANUAL NCOM SERIAL DEVICE SERVER 4XX SERIES USER S MANUAL 2017-07-07 Edition Titan Electronics Inc. Web: www.titan.tw Contents 1. INTRODUCTION... 4 1.1 Key Features... 5 1.2 Specifications... 6 2. PANEL LAYOUT

More information

Installation and Setup. In This Chapter... Installing the H0 PSCM The Profibus Network Configuring the Module

Installation and Setup. In This Chapter... Installing the H0 PSCM The Profibus Network Configuring the Module Installation and Setup 1 2 In This Chapter.... Installing the H0 PSCM The Profibus Network Configuring the Module 2 2 Installing the H0 PSCM Remove the Slot Cover The first step in installing the option

More information

CAS IKS Gateway (Modbus RTU/TCP and HTML) Manual

CAS IKS Gateway (Modbus RTU/TCP and HTML) Manual CAS-2700-42 IKS to Modbus RTU Gateway CAS 2700-42 IKS Gateway (Modbus RTU/TCP and HTML) Manual CAS 2700-42 IKS Gateway Manual Page 1 of 34 BLANK PAGE CAS 2700-42 IKS Gateway Manual Page 2 of 34 Contents

More information

RS485 MODBUS Module 16I-M

RS485 MODBUS Module 16I-M Version 2.0 12/02/2013 Manufactured for Thank you for choosing our product. This manual will help you with proper support and proper operation of the device. The information contained in this manual have

More information

PAC BI-DP BIM and 8701-CA-BI Carrier

PAC BI-DP BIM and 8701-CA-BI Carrier June 2013 PAC8000 8507-BI-DP BIM and 8701-CA-BI Carrier PROFIBUS DP Bus Interface Module and Carrier The 8507-BI-DP Bus Interface Module (BIM) provides the communications link between the PAC8000 series

More information

Copyright: December 2017 Nidec Issue: E

Copyright: December 2017 Nidec Issue: E General Information The manufacturer accepts no liability for any consequences resulting from inappropriate, negligent or incorrect installation or adjustment of the optional parameters of the equipment

More information

MODBUS RTU MODULE INSTRUCTIONS. for use with WSIQ2/WSE

MODBUS RTU MODULE INSTRUCTIONS. for use with WSIQ2/WSE INSTRUCTIONS MODBUS RTU MODULE for use with WSIQ2/WSE WorldWide Electric Corporation Phone: 1-8-88-2131 Fax: 1-8-711-1616 www.worldwideelectric.net Product Compatibility This communications module is suitable

More information

Installation and Programming Manual. Niobrara Research & Development Corporation P.O. Box 3418 Joplin, MO USA

Installation and Programming Manual. Niobrara Research & Development Corporation P.O. Box 3418 Joplin, MO USA DUCM DF1 Manual DUCM DF1 Installation and Programming Manual This manual describes the DUCM application for interfacing DF1 slaves to a Modbus or RNIM serial network. Effective: February 16, 2017 Niobrara

More information

USB to RS-232/RS422/485. URK-228-I USB To Serial Operation Manual

USB to RS-232/RS422/485. URK-228-I USB To Serial Operation Manual USB to RS-232/RS422/485 URK-228-I USB To Serial Operation Manual First Edition, Feb 2012 Table of Contents 1. Introduction 2 2. Package checklist 3 3. Product Specification 4 4. Product Panel Views Description

More information

T1K MODBUS Base Controller Specifications

T1K MODBUS Base Controller Specifications Base Controller 1 2 In This Chapter.... Base Controller Setting the DIP Switches Setting the Rotary Address Switches Port Pin out and Wiring RJ12 Serial Port Pin out and Wiring 2 2 Base Controller General

More information

This is the procedure to use the Clone module as a serial converter: To enable communication you must set the following parameters in the drive.

This is the procedure to use the Clone module as a serial converter: To enable communication you must set the following parameters in the drive. AC10 Clone module 1002-00-00 There are a number of different ways in which the Clone Module can be used with AC10 drive. It can be used to Clone a drive or it can be used as a USB to serial converter to

More information

Chapter 1. Introduction. Additional Documentation

Chapter 1. Introduction. Additional Documentation Chapter 1 Introduction This chapter is an introduction to the PACSystems RX3i Serial Communications modules: Introduction to PACSystems RX3i Serial Communications Modules Introduction to Installing Serial

More information

Modbus/DeviceNet Gateway MD-210 User Manual

Modbus/DeviceNet Gateway MD-210 User Manual Modbus/DeviceNet Gateway MD-210 EV 1.2 April,2009 Sibotech Automation Co., Ltd Technical Support: +86-021-5102 8348 E-mail: support@sibotech.net Table of Contents 1 About This Document...4 1.1 General...

More information

Real Time Clock with Temperature Sensor and RS485/Modbus Comunications

Real Time Clock with Temperature Sensor and RS485/Modbus Comunications Real Time Clock with Temperature Sensor and RS485/Modbus Comunications April 29, 2014 Power 8 20 VDC @ less than 100 MA. Battery connect jumper RS485 Bus Load Jumpers Model: RTC-TI2C Page 1 of 6 Features:

More information

INDEX. Document Name : User Manual for SC10EJ Serial to Ethernet Converter

INDEX. Document Name : User Manual for SC10EJ Serial to Ethernet Converter Document Name : User Manual for SC10EJ Serial to Ethernet Converter Page 1 of 10 INDEX 1. Technical Specifications 1 2. Modes of Operation 1 3. Configuring the SC10 EJ : Through Serial Port 2 a. Configuring

More information

GW-7553-CPM PROFIBUS/CANopen GATEWAY. User's Manual

GW-7553-CPM PROFIBUS/CANopen GATEWAY. User's Manual GW-7553-CPM PROFIBUS/CANopen GATEWAY User's Manual High Quality, Industrial Data Acquisition, and Control Products GW-7553-CPM PROFIBUS/CANopen GATEWAY User Manual (Version 1.00, Apr/2016) PAGE: 1 Warranty

More information

HART 710. User s Manual Version HART-710 User Manual (Version 1.00, July/2010) PAGE: 1

HART 710. User s Manual Version HART-710 User Manual (Version 1.00, July/2010) PAGE: 1 TM HART 710 User s Manual Version 1.00 HART-710 User Manual (Version 1.00, July/2010) PAGE: 1 Warranty All products manufactured by ICP DAS are under warranty regarding defective materials for a period

More information

D485 Modbus to DeviceNet Converter Instruction Manual

D485 Modbus to DeviceNet Converter Instruction Manual GE Consumer & Industrial D485 Modbus to DeviceNet Converter Instruction Manual Manual P/N: 1601-0235-A1 Manual Order Code: GEK-113195 Copyright 2005 GE Multilin GE Multilin 215 Anderson Avenue, Markham,

More information

The PROFIBUS and PROFINET Company. COMbricks Modules. Copyright 2013 PROCENTEC. All rights reserved.

The PROFIBUS and PROFINET Company. COMbricks Modules. Copyright 2013 PROCENTEC. All rights reserved. Modules SCOPE Repeater Module Name 1 Channel RS 485 SCOPE Repeater Type 1 Order code 101 201210 Description 1 Channel RS 485 PROFIBUS SCOPE repeater module with integrated quality oscilloscope for 12 Mbps

More information

VPGate Manual PROFINET to Serial

VPGate Manual PROFINET to Serial VPGate Manual PROFINET to Serial Content 1. PROPERTIES... 5 1.1 General properties... 5 1.2 Electrical properties... 7 1.3 Mechanical properties... 8 2. Hardware installation... 9 2.1 Connector technology...

More information

SMART RELAY SRW 01 V4.0X

SMART RELAY SRW 01 V4.0X Motors Automation Energy Transmission & Distribution Coatings SMART RELAY SRW 01 V4.0X Profibus DP Communication Manual Profibus DP Communication Manual Series: SRW 01 Firmware Version: V4.0X Language:

More information

+ (5~27 VDC) GND. Bluetooth V4.2 BLE RS-422/485 Serial Adapter. Model: BLE-485C. 1. Package content: BLE RS-422/485 adapter

+ (5~27 VDC) GND. Bluetooth V4.2 BLE RS-422/485 Serial Adapter. Model: BLE-485C. 1. Package content: BLE RS-422/485 adapter Bluetooth V4.2 BLE RS-422/485 Serial Adapter 1. Package content: BLE RS-422/485 adapter Model: BLE-485C Package Contents: BLE 422/485 adapter x 1 Screw x2, Screw nut x 2 A4 User manual x 1 Mini USB Cable

More information

The I-7530A RS-232/485/422 to CAN Converter

The I-7530A RS-232/485/422 to CAN Converter The I-7530A RS-232/485/422 to CAN Converter User s Manual Warranty All products manufactured by ICP DAS are under warranty regarding defective materials for a period of one year from the date of delivery

More information

RS-232/422/485 to Copper or Fiber. Ethernet Converter. User s Manual

RS-232/422/485 to Copper or Fiber. Ethernet Converter. User s Manual RS-232/422/485 to Copper or Fiber Ethernet Converter User s Manual Table Of Contents TABLE OF CONTENTS... 1 INTRODUCTION... 3 PRODUCT OVERVIEW... 3 PRODUCT FEATURES... 3 PACKING LIST... 4 LED INDICATORS...

More information

HRT-710. User s Manual Version HRT-710 User Manual (Version 1.23, Dec/2012) PAGE: 1

HRT-710. User s Manual Version HRT-710 User Manual (Version 1.23, Dec/2012) PAGE: 1 TM HRT-710 User s Manual Version 1.23 HRT-710 User Manual (Version 1.23, Dec/2012) PAGE: 1 Warranty All products manufactured by ICP DAS are under warranty regarding defective materials for a period of

More information

Anybus-CC CFW-11. User s Manual. Phone: Fax: Web: -

Anybus-CC CFW-11. User s Manual. Phone: Fax: Web:  - Anybus-CC CFW-11 User s Manual Anybus-CC User s Manual Series: CFW-11 Language: English Document Number: 0899.5750 / 06 Publication Date: 09/2013 CONTENTS CONTENTS... 3 ABOUT THE MANUAL... 6 ABBREVIATIONS

More information

RS485 MODBUS Module 8I8RO

RS485 MODBUS Module 8I8RO Expansion Module 8 digital inputs, 8 relay outputs Version 1.0 3.12.2014 Manufactured for Thank you for choosing our product. This manual will help you with proper support and proper operation of the device.

More information

RMx621. Appendix to the operating manual

RMx621. Appendix to the operating manual Appendix to the operating manual RMx621 DP-slave module ( PROFIBUS-coupler ) from V2.01.00 Connecting the RMx621 to PROFIBUS DP via the RS485 serial interface using the external module (HMS AnyBus Communicator

More information

G0313 Modbus to FF Gateway User Manual

G0313 Modbus to FF Gateway User Manual G0313 Modbus to FF Gateway User Manual Microcyber Corporation Caution 1. Please don t take off/install gateway at random. 2. Please check if the power of gateway meets the power request in the User Manual.

More information

MGate 4101-MB-PBS Modbus Serial-to-PROFIBUS Slave Gateway User s Manual

MGate 4101-MB-PBS Modbus Serial-to-PROFIBUS Slave Gateway User s Manual Modbus Serial-to-PROFIBUS Slave Gateway User s Manual Edition 5.0, February 2017 www.moxa.com/product 2017 Moxa Inc. All rights reserved. Modbus Serial-to-PROFIBUS Slave Gateway User s Manual The software

More information

+ (5~27 VDC) GND. Bluetooth V4.2 BLE RS-232 Serial Adapter. Model: BLE-232D-E. 1. Package content: BLE RS-232 adapter

+ (5~27 VDC) GND. Bluetooth V4.2 BLE RS-232 Serial Adapter. Model: BLE-232D-E. 1. Package content: BLE RS-232 adapter 1. Package content: BLE RS-232 adapter Bluetooth V4.2 BLE RS-232 Serial Adapter Model: BLE-232D-E Package Contents: BLE RS-232 adapter x 1 A4 User manual x 1 Mini USB Cable x 1 White Box: 11 x 6 x 5 (cm)

More information

DKG-210 UNIVERSAL INTERNET GATEWAY UNIT

DKG-210 UNIVERSAL INTERNET GATEWAY UNIT DKG-210 UNIVERSAL INTERNET GATEWAY UNIT AC & DC SUPPLY VERSIONS DESCRIPTION The DKG-210 is designed for internet monitoring and control of industrial devices using different protocols through the RAINBOW

More information

SDM-8I8O. Expansion Module 8 digital inputs, 8 digital outputs. Manufactured for

SDM-8I8O. Expansion Module 8 digital inputs, 8 digital outputs. Manufactured for Version 1.2 20.01.2014 Manufactured for Thank you for choosing our product. This manual will help you with proper support and proper operation of the device. The information contained in this manual have

More information

MGate TM EIP3000 DF1 to EtherNet/IP Gateway User s Manual

MGate TM EIP3000 DF1 to EtherNet/IP Gateway User s Manual MGate TM EIP3000 DF1 to EtherNet/IP Gateway User s Manual First Edition, June 2009 www.moxa.com/product 2009 Moxa Inc. All rights reserved. Reproduction without permission is prohibited. MGate EIP3000

More information

HDLC-USB. Portable Protocol Converter. Rev. Dec 25, Datasheet. Website:

HDLC-USB. Portable Protocol Converter. Rev. Dec 25, Datasheet.   Website: HDLC-USB Portable Protocol Converter Rev. Dec 25, 2017 HDLC-USB Datasheet Email: yacer@yacer.cn Website: www.yacer.cn 1 Overview... 3 1.1 Introduction... 3 1.2 Features... 3 1.3 Applications... 3 1.4 Technical

More information

High Performance FieldBus cards

High Performance FieldBus cards Profibus card VLT 5000/6000...2 Interbus card VLT 5000... 4 DeviceNet card VLT 5000... 6 Modbus+ card VLT 5000...8 Lonworks card VLT 5000/6000 Free Topology... 10 Lonworks cards VLT 5000/6000 78 kbps and

More information

tsh-700 Series User Manual

tsh-700 Series User Manual tsh-700 Series User Manual Tiny Serial Port Sharer Aug. 2017 Ver. 1.6 WARRANTY All products manufactured by ICP DAS are warranted against defective materials for a period of one year from the date of delivery

More information

RMx621 /FML621. Appendix to the operating manual

RMx621 /FML621. Appendix to the operating manual Appendix to the operating manual RMx621 /FML621 DP-slave module ( PROFIBUS-coupler ) from V2.01.00 Connecting the RMx621 /FML621 to PROFIBUS DP via the RS485 serial interface using the external module

More information

Modbus Gateway User's Manual ADM-5850G

Modbus Gateway User's Manual ADM-5850G Modbus Gateway User's Manual ADM-5850G Functional introduction The Modbus protocol is the most widely used protocol in the electronic industrial equipment, and now it has become a general industrial standard.

More information

ICP PANEL-TEC PEX3000 II

ICP PANEL-TEC PEX3000 II ICP PANEL-TEC PEX3000 II MODBUS PORT EXPANDER INSTALLATION AND OPERATION GUIDE REVISION HISTORY Revision Date Author Comments 000 29 Aug 2008 Keira Majors Initial release. 001 16 Sep 2008 David Walker

More information

BridgeWay. PROFIBUS to DeviceNet Gateway User Manual. Part No. AB7605. Publication PUB-AB

BridgeWay. PROFIBUS to DeviceNet Gateway User Manual. Part No. AB7605. Publication PUB-AB BridgeWay PROFIBUS to DeviceNet Gateway User Manual Part No. AB7605 Pyramid Solutions 1850 Research Drive, Suite 300 Troy, Michigan 48083 Phone 248-524-3890 Web www.pyramid-solutions.com Publication PUB-AB7605-005

More information

SATEL I-LINK 100 MB I/O-converter User Guide, Version 1.1

SATEL I-LINK 100 MB I/O-converter User Guide, Version 1.1 TABLE OF CONTENTS TABLE OF CONTENTS... 1 IMPORTANT NOTICE... 2 PRODUCT CONFORMITY... 3 WARRANTY AND SAFETY INSTRUCTIONS... 4 1 GENERAL... 5 1.1 SATEL I-LINK 100 MODBUS I/O- CONVERTER... 5 2 SPECIFICATIONS...

More information

EGW1-IA3-MB User s Manual

EGW1-IA3-MB User s Manual www.exemys.com Rev. 0 1 Products are in constant evolution to satisfy our customer needs. For that reason, the specifications and capabilities are subject to change without prior notice. Updated information

More information

USER MANUAL FOR GS100/GS1003G

USER MANUAL FOR GS100/GS1003G USER MANUAL FOR GS100/GS1003G 1 Table of Contents 1. INTRODUCTION... 3 2. FEATURES... 3 3. OPERATION... 3 4.CONNECTION DETAILS... 4 5.CONFIGURATION... 5 5.1 Hyper Terminal Setting... 5 5.2 GS100 Configuration...

More information

TABLE OF CONTENTS. Communication Functions

TABLE OF CONTENTS. Communication Functions TABLE OF CONTENTS Chapter 1: Chapter 2: Chapter 3: Chapter 4: General Features....................................................... 1-1 Functions......................................................

More information

PACSystems* RX3i IC695CMM002-EG and IC695CMM002CA-EG IC695CMM004-EG, IC695CMM004CA-EG, and IC695CMM004LT-EG

PACSystems* RX3i IC695CMM002-EG and IC695CMM002CA-EG IC695CMM004-EG, IC695CMM004CA-EG, and IC695CMM004LT-EG September 2017 PACSystems* RX3i IC695CMM002-EG and IC695CMM002CA-EG IC695CMM004-EG, IC695CMM004CA-EG, and IC695CMM004LT-EG Serial Communications Modules PACSystems* RX3i Serial Communications modules expand

More information

3-7 Tiny Serial-to-Ethernet Device Server & Modbus Gateway

3-7 Tiny Serial-to-Ethernet Device Server & Modbus Gateway Tiny Serial-to-Ethernet Device Server & Modbus Gateway - Tiny Serial-to-Ethernet Device Server & Modbus Gateway tds-00 Series tds-12 tds-00 series tdsm-12 Tiny Serial-to-Ethernet Device Server Features

More information

EtherSeries Modbus Gateway EMB-2 User s Guide

EtherSeries Modbus Gateway EMB-2 User s Guide EtherSeries Modbus Gateway EMB-2 User s Guide Revised March 25, 2004 Firmware Version 1.4 FCC Statement This device complies with the limits for a Class B digital device, pursuant to Part 15 of the FCC

More information

ELC-CODNETM. Effective December Users Manual

ELC-CODNETM. Effective December Users Manual Effective December Users Manual Introduction This is an OPEN-TYPE device and therefore should be installed in an enclosure free of airborne dust, excessive humidity, shock and vibration. The enclosure

More information

RS-485 Products. ICP Electronics Australia Pty Ltd Communication Cards for PC/IPC P 2-1

RS-485 Products. ICP Electronics Australia Pty Ltd Communication Cards for PC/IPC P 2-1 2.1 Communication Cards for PC/IPC P 2-1 2.2 Communication Modules for PAC P 2-2 2.3 Converter/Repeater/Hub/Splitter P 2-3 2.4 Termination Resistor/DC Bias Voltage P 2-5 2.5 I/O Modules P 2-6 2.6 I/O Units

More information

PCI Express 4-Port Industrial Serial I/O Cards

PCI Express 4-Port Industrial Serial I/O Cards PCI Express 4-Port Industrial Serial I/O Cards The PCIe-400i and PCIe-400i-SI PCI Express 4-port industrial serial I/O cards are plug & play high-speed serial I/O expansion cards for the PCI Express bus.

More information

HDLC-ETH. Serial Ethernet Converter. Rev. Dec 20, Datasheet. Website:

HDLC-ETH. Serial Ethernet Converter. Rev. Dec 20, Datasheet.   Website: HDLC-ETH Serial Ethernet Converter Rev. Dec 20, 2017 HDLC-ETH Datasheet Email: yacer@yacer.cn Website: www.yacer.cn 1 Overview... 3 1.1 Introduction... 3 1.2 Features... 3 1.3 Applications... 3 1.4 Technical

More information

IntesisBox Modbus Server Fidelio IP

IntesisBox Modbus Server Fidelio IP IntesisBox Modbus Server Fidelio IP User Manual r1 eng Issue Date: 10/04/2014 Intesis Software S.L. All Rights Reserved. Information in this document is subject to change without notice. The software described

More information

IntesisBox Modbus Server KILSEN KSA-7xx. User s Manual 08/2013 r1.2 eng

IntesisBox Modbus Server KILSEN KSA-7xx. User s Manual 08/2013 r1.2 eng IntesisBox Modbus Server KILSEN KSA-7xx User s Manual 08/2013 r1.2 eng Intesis Software S.L. 2013 All rights reserved. Information in this document is subject to change without notice. The software described

More information

1. Introduction. 2. Installation MODBUS INTERFACE

1. Introduction. 2. Installation MODBUS INTERFACE 5551.C 8473.C MODBUS INTERFACE PIM-MB-1 Modbus Interface 1. Introduction AuCom soft starters can be controlled and monitored across an RS485 serial communication network using the Modbus RTU and AP ASCII

More information

MODBUS PLUS TO SIEMENS G110/G120/MM440 APPLICATION

MODBUS PLUS TO SIEMENS G110/G120/MM440 APPLICATION ICP PANEL-TEC MICROBRIDGE INSTALLATION AND OPERATION GUIDE MODBUS PLUS TO SIEMENS G110/G120/MM440 APPLICATION Revision History Revision Date Author Comments 000 3 May 2010 David Walker Initial release.

More information

Quick Start Guide PN/CAN Gateway Layer 2. Version. 2 en. ab FW

Quick Start Guide PN/CAN Gateway Layer 2. Version. 2 en. ab FW Version 2 en ab FW 1.02 Quick Start Guide PN/CAN Gateway Layer 2 www.helmholz.de Content 1. Introduction 3 2. Preparation of the PN/CAN Gateway 3 3. Configure PN/CAN Gateway 4 4. PN/CAN Gateway settings

More information