TXM1.8RB. TX-I/O Blinds module

Similar documents
TXM1.8T. Triac module Used for Thermic and motor-driven actuators (AC 24 V) TX-I/O

Digital input modules

Resistance measuring module

Super universal modules

TXM1.8U TXM1.8U-ML. Universal modules TX-I/O

TXM1.8U TXM1.8U-ML. Universal modules TX-I/O

TXM1.8U TXM1.8U-ML. Universal modules TX-I/O

Power supply module, bus connection module

BACnet/IP Web Interface

9283P01. Extension module. Integration of existing PT-I/O modules in Desigo Used with PXC50...D, PXC100...D or PXC200...D

Island bus expansion module

Universal Modules. Synco 700. Extension modules for use with controls of the Synco 700 family. Use

Rotary version, three-position control

Interface converter for VAV compact controllers

Extension module Integration of existing PTM I/O modules in Desigo Used with PXC50...D, PXC100...D or PXC200...D

RMZ782B RMZ783B. Extension Modules. Building Technologies HVAC Products. Synco 700. for heating controller RMH760B

Web interface BACnet/IP

Rotary actuators for ball valves

M-bus web server. Meters and Energy Cost Allocation WTV676-HB6035

Air damper actuators

USB-KNX Interface OCI702. USB-KNX interface with cables and service bag

Room unit with PPS2 interface

SAX.. ACVATIX Electromotive actuators for valves. with a 20 mm stroke

QAX50.1 QAX50.5 QAX51.1 QAX51.5. Flexible room unit. Desigo RXC

BACnet router for BACnet/IP BACnet/LonTalk BACnet MS/TP

Fast running actuators for air dampers

RXM39.1. PL-Link IO Block. Desigo TRA. Use with PXC3 series room automation station

OCI Service tool. As of ACS790 V9.00. Service case with software and service interface

Handheld Tool for VAV compact and modular controllers

Airflow Pressure Sensor

Electromotoric actuators

VAV modular controller

VAV compact controller

Room unit with PPS2 interface

Touch Panels 10.1" and 15.6"

RMZ782B RMZ783B. Extension Modules. Building Technologies HVAC Products. Synco 700. for heating controller RMH760B

Extension module for lighting control

Room automation station

Room Temperature Controller

RXL24.1. Room controller RXL. Communicating controller for chilled ceiling and radiator applications CC-02

Air Damper Actuators Modbus RTU

Air Damper Actuators Modbus RTU

Network node WTT56.. A6V _en--_c Building Technologies

Impulse switching module

Room automation stations

RMZ790. Operator Unit. Building Technologies. Synco 700

QXA2000 QXA2001. Condensation Monitor QXA2001 QXA2000 AQX2000

Electromotive actuators for combi valves

Switching module for AC V and up to three load stages, with manual switching

Communication module to connect M-bus devices to POL6xx.xxx controllers.

Accessories and options

Semi flush-mounted room temperature controllers with LCD

s Climatix AHU ext. module 14 I/O POL955.XX/XXX Climatix

SEH62.1. Digital Time Switch

RXC39.5. Room controller. Building Technologies. Desigo RXC. Communicating room controller for fan-coil applications

Room sensors QFA4160 QFA41 D AQF4150 AQF3153. Symaro. for relative humidity and temperature with calibration certificates

AEW Pulse Adapter. Building Technologies

Electromotoric actuator

RXL24.1. Room controller RXL. Communicating controller for chilled ceiling and radiator applications CC-02

Touch Panels 10.1" and 15.6"

Duct Sensors. Building Technologies HVAC Products. Symaro. for relative humidity and temperature with calibration certificates

Electromotoric actuators

Mobile Data Collector

Compact room automation stations, BACnet/IP, AC 230 V

QUINT-PS/1AC/24DC/10. Extract from the online catalog. Order No.:

RXB39.1. Room controller RXB. Communicating room controller for fan-coil applications FC-13

QUINT-PS/ 1AC/24DC/ 5

LON Module for Variable Speed Drive

Immersion Temperature Sensors

Electromotoric actuators for stroke valves

Heating Circuit Controller

Compact actuating room automation stations, BACnet/IP, AC24 V (Actuating DXR)

Electromotoric actuators Torques up to 60 Nm Running times ¹) s. ¹) Predefined by the basic unit (LMV5...)

RXB10.1. Room controller. Siemens Building Technologies Building Automation DESIGO RXB. for chilled ceilings and radiators with EIB bus communication

Climatix programmable controller

Rotary actuator for ball valves KNX / PL-Link

Product and Applications Description. Application Programs. Note. instabus EIB Technical Product Information. June 2005

Product and functional description

QUINT-PS/ 1AC/24DC/20/CO

Room unit with PPS2 interface

Product and Applications Description. Example of Operation. Installation Instructions WARNING. Note. Application Programs

ERF910. RF Repeater. Synco living

Fume Hood Cable Sash Sensor

QVE3000.0xx QVE3100.0xx. Flow sensor. for liquids in DN10 25 pipes

Product and Applications Description. Note. Example of Operation. Installation Instructions. Application Programs WARNING

Product and Applications Description. Application Programs. Example of Operation. Installation Instructions. load circuit AC 230/400V L1 L2 L3 N

Extract from the online catalog

DESIGO RX Individual room controllers. for fan-coil systems, chilled ceilings and radiators, with LONMARK-compatible bus communications

Communication over Modbus protocol Connection with multiple controllers Application upgrade by using an SD 1) card or a USB stick

AEW36.2. Pulse Adapter. Building Technologies. Siemeca AMR

QUINT-PS AC/24DC/10

RMZ792. Bus Operator Unit. Building Technologies HVAC Products. Synco 700

Room unit with PPS2 interface

MINI-DC-UPS/12DC/4. Extract from the online catalog. Order No.:

RXL21.1 RXL22.1. Room controllers RXL. Communicating controllers for fan-coil applications FC-10, FC-11, FC12

Product and functional description

Miniature Circuit Breakers for Railway Applications

Product and functional description

PHOENIX CONTACT Features

Switching modules for AC 230 V, non-potential-free, single and double module

Transcription:

s 8 178 8178p01 TX-I/O Blinds module TXM1.8RB 8 non-floating relay outputs for... 4 blinds motors with 2 end switches, or 2 blinds motors with 3 end switches, or 2 blinds motors with 2 end switches + 1 blinds motor with 3 end switches Switching voltage AC 100...250 V Green status LED to indicate status for each I/O point Current measurement for each blinds motor for end position detection Compact design as per DIN, requiring little space Separation into terminal base and electronics unit for optimal handling Self-connecting bus for the easiest possible installation Isolating terminal function for fast commissioning Exchange of electronics unit within seconds without a need of rewiring, at full functionality of the remaining I/O modules Terminal strips are required to connect N and PE of the field devices Simple display concept Lit I/O status LEDs for the outputs when relays are active LEDs for fast fault diagnosis Double-sided labeling of all I/O points with label CM2N8178en_04 2017-06-29 Building Technologies

Functions The module supports the following I/O function: Signal type BO Blind Relay Description Maintained contact relay, for blinds control with 2 / 3 end switches See document "TX-I/O Functions and operation", CM110561, for a detailed description of this function. Compatibility For signal type support and functionality in the various building automation and control systems, see TX-I/O engineering and installation manual, CM110562. Ordering Type Stock number Designation TXM1.8RB S55661-J105 Blinds module Delivery Accessories Terminal base and electronics unit are assembled and delivered in a box. Address keys, printable label sheets and replacement label holders are available as accessories. See data sheet CM2N8170. Design and technology See the TX-I/O Engineering and installation manual, CM110562, for a description of the properties for all TX-I/O modules. Operating and display elements Connection terminals (No. 1 screwdriver for slotted or recessed-head * screws) with test plug socket (pins 1.8 to 2 mm) and terminal number. Signal designation Address key and module status LED I/O point numbers Output status LEDs (TXM1.8RB: green) * Combined slotted / recessed-head screws from mid-2012 2 / 8

Output status LEDs Module status LED Address key Terminal End position detection The output status LEDs indicate the relay status. The LEDs are also used for diagnostics. The module status LED illuminates the transparent address key. The LED (green) indicates the status for the entire module (contrary to the I/O point status). It can also be used for diagnostic purposes. The module only works with the address key. The module address is mechanically encoded in the address key. Swing out the address key when exchanging the electronics unit. The key remains in the terminal base. The relay contact lines are interconnected (in the electronics unit). Active mains power must be supplied separately to each terminal strip. Different phases for the different terminals strips are allowed. The end position of the blind is detected using a current measurement. Measurement reports "On" when the motor exceeds a minimum current / motor power (see technical data). Module labeling The electronics unit has a removable, transparent lid (label holder) allowing for insertion of the label. 2 1 8172z11 Disposal "The device is considered electronics device for disposal in terms of European Directive 2012/19/EU and may not be disposed of as domestic garbage. The device must be disposed of via the proper channels. Observe all local and applicable laws. Engineering, mounting, installation Please consult the following documents: Document TX-I/O Functions and operation TX-I/O Engineering and installation manual Number CM110561 CM110562 3 / 8

Mounting Allowed mounting positions TX-I/O devices can be mounted in any position: You must ensure, however, that sufficient ventilation is available to maintain the permissible ambient temperature (max. 50 C). Technical data Power supply (side bus connector) Operating voltage Safety extra-low voltage SELV or protection by extra-low voltage PELV per HD384 Max. power consumption (see CM110562 for supply design) DC 21.5... 26 V 1.4 W Protection Bus connector on side No protection against shortcut and incorrect wiring with AC / DC 24 V Switching outputs Number of switching outputs 8 (NO contacts) External supply line fusing Non-renewable fuse, slow Max. 10 A Miniature circuit breaker MCB Max. 13 A Tripping characteristic MCB B, C, D as per EN 60898 Contact data Switching voltage Max. AC 100 to 250 V Motor current Max. 3 A *) Switch-on current (max. 1 s) *) Max. 10 A *) Minimum current Min. 1 ma at AC 250 V Pickup/dropout time 7 ms / 3 ms typical Current measurement "On" I 0.2 A "Off" I 0.1 A Contact life for AC 250 V (guide values) Up to 2 A 1 x 10 5 switchings Up to 3 A 5 x 10 4 switchings Insulating strength Between relay outputs and system electronics (increased insulation) AC 3000 V, as per EN 60730-1 *) Caution: Some motor manufacturers do not comply with these specifications (very short switch-on current peaks >10 A). This is not always stated in the data sheets. For customer projects, clarify the type and properties of motors in an early phase. If in doubt, investigate or perform tests / measurements. This applies for blinds motors as well as linear actuators for window applications. Connection terminals Test plug socket (test terminals) 4 / 8 Mechanical design Wire Copper stranded wire without ferrules Stranded wire with ferrule (DIN 46228/1) Screwdriver Max. tightening torque Pin diameter Screw-type terminal 1 x 0.5 mm 2 to 4mm 2 or 2 x 0.6 mm dia. to 1.5 mm 2 1 x 0.5 mm 2 to 2.5 mm 2 or 2 x 0.6 mm dia. to 1.5 mm 2 1 x 0.25 mm 2 to 2.5 mm 2 or 2 x 0.6 mm dia. to 1.5 mm 2 No. 1 Screwdriver for slotted or recessed-head * screws with shaft diameter 4.5 mm * Combined slotted / recessedhead screws from mid-2012 0.6 Nm 1 x 1.8 to 2.0 mm

Classification per EN 60730 Operation of automatic controller Degree of pollution Mechanical design Housing protection type Degree of protection as per EN 60529 Front parts in DIN excerpt Terminal part Environmental conditions Operation Climatic conditions Temperature Relative humidity Mechanical conditions Transport / storage Climatic conditions Temperature Relative humidity Mechanical conditions Type 1 2 Devices suited for use with equipment of safety classes I and II IP30 IP20 As per IEC 60721-3-3 Class 3K5-5...50 C 5 95% r.h. Class 3M2 As per IEC 60721-3-2 Class 2K3-25...70 C 5 95% r.h. Class 2M2 Standards and directives Product standard EN 60730-1 EU conformity (CE) T10870xx *) Electromagnetic compatibility For residential, commercial and industrial environments RCM conformity (EMC) T10870en_C1 *) UL approbation UL 916 *) The documents can be downloaded from http://siemens.com/bt/download. Environmental compatibility Product environmental declaration (contains data on RoHS compliance, materials composition, packaging, environmental benefit, disposal) CM1E8178 Color Terminal base and electronics unit RAL 7035 (light-gray) Dimensions Housing as per DIN 43880, see dimensions Weight With/without packaging 208 / 229 g 5 / 8

Connection diagrams (example) Terminal assignment TXM1.8RB Output (1) (2) (3) (4) (5) (6) (7) (8) Supply line *) 11 28 NO contact 6 8 14 16 23 25 31 33 *) Different phases allowed for terminals 11 and 28 Blinds with 2 end switches 2 blinds can be connected per terminal strip AC 100...230V U (1) 6 (2) (3) (4) 8 14 16 11 U Blinds module L N Down2 M1 Up Down2 Up M2 8178z13 Blinds actuator M1, M2 Blinds motors Down2, Up End switch Blinds with 3 end switches 1 set of blinds can be connected per terminal strip (the 4 th terminal must remain free) AC 100...230V U (1) 6 8 (2) 11 (3) (4) 14 16 U Blinds module L N Down2 M1 Up Down1 8178z14 Blinds actuator M1 Blinds motor Down2, Up End position Down1 Center position STOP Note! Because of the current measurement, interposing relays for the control of several blinds in parallel are not admitted. Parallel operation of more than one blinds motor on the same terminal is not admissible! 6 / 8

Dimensions Dimensions in mm 90 67 45 22 44 70 77.5 7.1 98 108 64 3 8172M01 7 / 8

Published by: Siemens Switzerland Ltd. Building Technologies Division International Headquarters Gubelstrasse 22 6301 Zug Switzerland Tel. +41 41-724 24 24 www.siemens.com/buildingtechnologies Siemens Switzerland Ltd 2012 Delivery and technical specifications subject to change 8 / 8