HIGH BAY PASSIVE INFRARED OCCUPANCY SENSOR Product Overview The HB3x0 series occupancy sensors are designed for automatic lighting control in high bay applications. All models contain a passive infrared (PIR) sensor. Sensitivity and time delay adjustments are set using DIP switches located on the sensor module. Each HB3x0 series sensor module accepts one of four interchangeable lenses, which provide different types of coverage for specific applications. Standard On/Off Models - HB3x0-B The Standard High Bay Sensors provide On/Off switching based on occupancy within a space. Surface Mount models do not come with Back Box (HBNB3). Cold location models are ideal for indoor cold environments. Daylighting Model - HB340D-B The Daylighting High Bay Sensor provides daylighting and On/Off control. The daylighting feature turns the luminaire off 3 minutes after the ambient light level goes above the adjustable setpoint (2 to 200fc) regardless of occupancy. This time delay helps avoid cycling the luminaire unnecessarily. A factory default 20% deadband on the lower end provides a slight delay before the lights turn ON. Lights turn ON only when ambient daylight goes below the setpoint and motion is detected. The daylighting model is designed to measure light levels by looking up toward a skylight, or down toward the task area. The daylighting feature can be disabled, refer to the installation instructions. Models Standard On/Off Models: HB340 (Surface Mount) HB300-B HB330-B HB340-B Daylighting Model: HB340D-B Specifications and Features Indoor use only Operating Temperature: 32 F to 158 F (0 C to 70 C) Operating Humidity: 5% to 95%, noncondensing Line voltage for direct connection to load and low voltage for connection to power pack Power consumption for line voltage models: HB340, HB330-B, HB340-B: 0.34W HB340D-B: 0.36W Power consumption for low voltage model: HB300-B: 10mA @ 24VDC Snap-in mounting hardware Weight: 6.4 oz (181 g) Easy mounting using knockout at end of fluorescent high bay luminaire Hardware choices for adjustability or static mount UL and cul listed Five year warranty Optical Four interchangeable lenses (HBL1, HBL2, HBL3, HBL4) Asymmetric 2-way and 360 lenses Lens choices for mounting between 8 and 40 feet, aisleway and open area lenses (lens required for operation) Materials ABS, flame retardant Impact resistant Recyclable Meets materials restrictions of RoHS Factory Defaults Time Delay: Sensitivity: Light Level: 15 minutes Medium HB3X0 SERIES 200fc (if applicable) 1
Coverage Ceiling 3 40 ft 4 3 3 HBL1 side coverage pattern 4 3 3 4 HBL1 top coverage pattern HBL1 Aisleway Lens 3 60 ft 8' 24' 11' 7' 3' 3' 7' 11' 24' HBL2 side coverage pattern HBL2 top coverage pattern HBL2 Low Bay Lens 5' Ceiling 15' 40 ft 18' 15' 12' 9' 6' 3' 3' 6' 9' 12' 15' 18' HBL3 side coverage pattern HBL3 top coverage pattern HBL3 Mid Bay Lens Coverage Side View 3 27' 3 12' 6' 3' 3' 6' 12' 60 ft 4 3 12' 6' 6' 12' 3 HBL4 side coverage pattern 27' 3 3 27' 12' 6' 3' 3' 6' 12' 27' 3 HBL4 top coverage pattern HBL4 High Bay Lens 2
Dimensions 1.265 (32.13mm) Light level trimpot for daylighting models DIP switches for time delay and sensitivity adjustments 2.75.635 (69.85mm) (16.12mm).85 (21.59mm) Dimensions of HB3x0 sensor module with back box and HBL1 lens module. 4.23 2.58 (65.53mm) PIR detector.68 (17.27mm) Dimensions of HB3x0 sensor module with back box and HBL2 or HBL3 lens module. 2.65 (67.31mm).75 (19.05mm) Dimensions of HB3x0 sensor module with back box and HBL4 lens module. 3
Installing and Mounting Instructions 1. Select a mounting configuration that ensures the sensor is positioned below the fixture edge and away from fluorescent lamps so that lamp heat does not affect the sensor. The sensor can either be directly mounted to the fixture housing (Figure 1) or to the extender module (HBEM3) (Figure 2). The latter enables offset mounting so sensor is positioned at or below the plane of the lamps. 2. Thread wires through extender module s chase nipples and into fixture for connection. Snap the extender module s sides together to protect wires. The short chase nipple snaps into sensor module while longer chase nipple snaps into any metal fixture or connection box with a standard 1/2 inch knockout. The caps on the extender module can be removed to allow moving chase nipples and to adjust the sensor height. 3. Determine if angular adjustment accessory (HBAA1 or HBAA2) is required. 4. Assemble all necessary mounting accessories and attach them to sensor module, ensuring that flying leads from power module are accessible. 5. Feed sensor leads through knockout to line voltage and load wires for the unit s application. Conceal all bare wire, and confirm all connections are secure. 6. Attach lens as shown in assembly drawing (Figure 3). HBEM3 Extender Module Figure 3. Figure 1. Rear mounting hole Side of fixture HBNB3 Box or HBNB3 Box CLOSE OPEN HB350 Sensor Module Alignment Guides Daylight Sensor Housing Lens below edge of fixture HB350 Sensor Module HBLx Lens Figure 2. Side of fixture HBEM3 Extender Module Rear mounting hole HBNB3 Box CLOSE Bottom edge of fixture OPEN HB350 Sensor Module Lens below edge of fixture 4
Wiring Diagrams HB300 Neutral Hot White Power Pack Load Blue (Common) (+24VDC) (Control Output) Blue HB330 and HB340 Phase A Phase B Phase A Load Phase B Load Load w/white stripes (347 VAC Neutral) w/white stripes (347 VAC Cap off) 5
Sequence of Operation The HB3x0 series occupancy sensor is designed to mount to a light fixture and control the load in the fixture based on occupancy. It can be wired to control all ballasts in the fixture, or to control half of the ballasts to provide high/low lighting control. When motion is detected within the sensor s coverage area, the sensor signals a relay to close, and lighting loads turn on automatically. When motion is no longer detected for the duration of the time delay setting, the relay opens and the lighting load is turned off. The sensor s sensitivity and time delay settings are factory preset at 100% and 15 minutes, respectively, which are suitable for most high bay applications. However, the values can be easily adjusted for specific applications using the DIP switches on the sensor module. Refer to the Installation Instructions for changing factory preset values, and for important start up instructions. Ordering Information Catalog # Master Pack Details Master Pack Quantity Inner Pack Details Case dimensions (inches) Inner Case dimensions (inches) Weight Pack Length Width Height (pounds) Quantity Length Width Height HB340 100 17.63 21.18 15.86 30.5 50 19.44 16.30 10.39 21.38 HB300-B 50 17.63 21.18 15.86 20.0 N/A N/A N/A N/A N/A HB330-B 50 17.63 21.18 15.86 22.2 N/A N/A N/A N/A N/A HB340-B 50 24.00 17.25 11.25 22.4 N/A N/A N/A N/A N/A HB340D-B 50 17.63 21.18 15.86 22.5 N/A N/A N/A N/A N/A HBEM3 240 18.00 21.50 16.5 22.22 120 17.10 20.63 7.60 17.8 HBAA-1 500 17.63 21.18 18.86 21.5 10 5.0 8.0 1.50 0.41 HBAA-2 500 14.0 17.50 16.50 21.6 10 5.0 8.0 1.50 0.41 HBNB3 100 17.63 21.18 15.86 16.0 50 8.34 20.62 15.28 8.4 BZ-50 40 13.58 13.46 9.06 15.0 10 6.30 13.0 3.93 3.55 Weight (pounds) Catalog # Color Description Voltage Load Capacity HB340 White High Bay Line Voltage Sensor, No Back Box, No Lens HB300-B White High Bay Low Voltage Sensor w/ Back Box, No Lens HB330-B White High Bay Line Voltage Sensor w/ Back Box, No Lens HB340-B White High Bay Line Voltage Sensor w/ Back Box, No Lens HB340D-B White High Bay Line Voltage Sensor w/ Back Box, Daylighting Feature HBEM3 White High Bay Extender Module HBAA-1 White HB Angle Fitting, Plastic/Plastic HBAA-2 White HB Angle Fitting, Plastic/Metal HBNB3 White HB Nipple Mounting Box 347/480 VAC 5 A ballast @ 347/480 VAC 24 VDC (requires power pack) 208/240 VAC 5 A ballast @ 240 VAC 347/480 VAC 5 A ballast @ 347/480 VAC 347/480 VAC 5 A ballast @ 347/480 VAC BZ-50 White Power Pack 120/230 (1P, L-N) /277 VAC 20 A ballast and tungsten or 1 hp motor Above models do not include lenses, please refer to OEM-105xx High Bay PIR Occupancy Sensor Lens Module datasheet for lens information. Compatible with all standard lenses and extender module. Bulk packaged products are shipped without individual boxes or installation instructions. Information supplied above is subject to change. Harmonization code: 8538908080. Country of origin: China. Pub. No. OEM-101 09/2016 6