The Infinity TCX 865 programmable Infinet terminal controller is a unique, low-cost VAV box

Similar documents
lighting control. Each controller switches up to 48 high voltage, 20-amp lighting circuits, using

Andover Continuum Infinet II i2865/866 VAV Controllers with Built-in Actuator

Andover ContinuumTM b3865/866 VAV Controllers with Built-in Actuator

using optional EMX 190 expansion modules), and makes access decisions based on its own distributed

Andover ContinuumTM Infinet II

Andover ContinuumTM Infinet II

BACnet. b3867 Terminal Controllers

Andover ContinuumTM. b3850 Series Terminal Controllers

Andover ContinuumTM Infinet II

BACnet. b3810 Series Local Controllers

Andover Continuum. Power Supplies with or without UPS

TCX 865. TCX 865 VAV Controller Family Installation Guide. Technical Manuals Online! - Controlling Tomorrow s World

SRQ24A. Technical data. Safety notes. Rotary actuator for ball valves Torque 16Nm Nominal voltage AC/DC 24V Control: Open-close Running time 9s

Functional data Nominal torque min. 180 in lb [20 NM] Communicative control Cloud: (call for clientapi )

Specification Sheet For electronically commutated motors

NKQB24-1, NKQX24-1 On/Off, Fail-Safe, Operation, Direct Coupled, 24V

Siemens BACnet Programmable TEC Dual Duct Two Air Velocity Sensors Controller

DS BAS 08/99 UNC 532

Standard Options. Model 4100 Position Indicating Meter. Three Phase Motor Control. Positran Transmitter

Power consumption In operation At rest For wire sizing. Torque Inhibiting torque. 150 s / C Sound power level Motor

Siemens BACnet Programmable TEC Dual Duct Two Air Velocity Sensors Controller

Siemens BACnet Programmable TEC Constant Volume

Functional data Communicative control Cloud: (call for clientapi ) Angle of rotation 90

Industrial Electric Actuators AC and DC Voltages Nm/ inch lbs

Siemens BACnet Programmable TEC VAV with Series Fan and 3-Stage Electric Heat Controller

Siemens BACnet VAV Actuator

Functional data Position indication reflective visual indicator (snap on) Communicative control Cloud: (call for clientapi )

Functional data Communicative control Cloud: (call for clientapi ) Angle of rotation 90

Andover ContinuumTM Infinet II

Siemens BACnet Programmable TEC Unit Conditioner (Fan Coil) Controller for Smoke Control

clarity 3 VAV Programmable Controller

Electrical data Nominal voltage AC/DC 24 V Nominal voltage frequency

FX Input/Output (I/O) Modules XM07 and XM14

Siemens BACnet Programmable TEC Unit Conditioner Controller

FXVMA Variable Air Volume (VAV) Box Controller

TC-9102 Terminal Controller

LM24A-MOD. Cable 1 m, 6 x 0.75 mm 2 RJ12 socket

Unitary Controller. Features. Description. Technical Specification Sheet Rev. 6, March, 2000

SORDS ELECTRIC ~ MA7200. Sensorless Vector AC Inverter.

ECP-VAV Series. ECP-VAV Series. 10-Point Single Duct VAV / VVT Free Programmable Controller. Applications. Features

NKQB24-1, NKQX24-1 On/Off, Electronic Fail-Safe, Direct Coupled, 24V

DS BAS /99 UNC 596 BUILDING AUTOMATION SYSTEM UNIVERSAL NETWORK CONTROLLER FEATURES

Siemens BACnet Programmable TEC Unit Conditioner (Fan Coil) Controller

Technical data sheet. Technical data

Power consumption In operation At rest For wire sizing

BACnet Terminal Box (VAV) Controller

Installation & Operation Guide

N05, N10 SERIES NON-SPRING RETURN DIRECT-COUPLED DAMPER ACTUATORS FOR MODULATING AND FLOATING CONTROL

Easy To Use OEMS Take Note

N20010-SER. NON-SPRING RETURN DAMPER ACTUATOR 20 Nm (177 lb-in) FOR ADJUSTABLE MODULATING CONTROL SPECIFICATIONS GENERAL FEATURES PRODUCT DATA

Rotary version, three-position control

RXB10.1. Room controller. Siemens Building Technologies Building Automation DESIGO RXB. for chilled ceilings and radiators with EIB bus communication

N0524/N1024, N POS/N POS

N05010/N10010 NON-SPRING RETURN DIRECT-COUPLED DAMPER ACTUATORS FOR MODULATING AND FLOATING / 2-POSITION CONTROL SPECIFICATIONS

XT-9100 Technical Bulletin

ACX Series. Access Controller for Ethernet

Display. Supply voltage. Input current. Encoder supply. Output current. Power losses. Memory

ECB-VAVS. Features and Benefits. Applications Cooling Only VAV Boxes Cooling with Reheat VAV Boxes Room Pressurization.

Compact Electric Actuators AC and DC Voltages 18 Nm/160 inch lbs

Functional data Factory settings Variable Setting Torque Inhibiting torque

PEAK TM. PEAK TM controllers. Mid-Market BAS Smart equipment controllers. HVAC/R controllers

VAV Modular Assembly (VMA) 1410/1420

DX-9100 Digital Controller, Version 2

Lab and Central Plant Controller

78 Series Electromechanical Relay Selection Guide

TAC Xenta 101-VF. 3-Speed Fan Coil Controller. TAC Xenta

9.5 nominal torque 4.5 W 16 VA. Min. 30 nominal voltage Min. 30 Nm. Reversible with switch By mounting. MIN (minimum position)

Electrical data Nominal voltage AC/DC 24 V Nominal voltage frequency

DS October MAXIM 1010 Controller

I/O Modules. user interface modules in a single controller location to meet your building s control and

General information Engineering with Programming package. Display with display. Supply voltage 24 V DC Yes. Input current

THERMOSTATS & CONTROLLERS

oom Pressurization Con

6ES7212-1BD30-0XB0. permissible range, lower limit (DC) permissible range, upper limit (DC)

IQM & IQML RANGE CONTROL AND MONITORING FACILITIES. Publication E420E issue 7/02

Inform IT Single Pen Circular Chart Recorder

Display. Supply voltage. Input current. Encoder supply. Output current. Power losses. Memory

Answers to Chapter 2 Review Questions. 2. To convert controller signals into external signals that are used to control the machine or process

General information. Display. Supply voltage. Input current. Encoder supply. Output current

General information. Display. Supply voltage. Input current

A CLOSER LOOK. Electronic Fail-Safe Series Direct Coupled Actuators. The Belimo Difference. Brushless DC Motor for Added Accuracy and Controllability

NF760 Batch Controller

General information Engineering with Programming package. Display with display. Supply voltage 24 V DC Yes

Electrical data Nominal voltage AC/DC 24 V Nominal voltage frequency

General information. Display. Supply voltage. Input current. Encoder supply. Output current

ABB Instrumentation. Specification DataFile COMMANDER 100. the-easy-to use 1. /8 DIN controller with extensive application capabilities

VAV compact controller KNX / PL-Link

AF24-MFT (-S) US Proportional damper actuator, Spring Return Fail-Safe, Multi-Function Technology

Siemens BACnet Programmable TEC Unit Vent Controller for Smoke Control

Cables. U.S. Registered Trademark EN0B-0341GE51 R0402 Copyright 2002 Honeywell Inc. All rights reserved

MAJOR VA Power Inverter

UNT1100 Series. Binary Output Jumpers AO2 AO1 AO3 AO4 AOCM AOCM AOCM AOCM AO1. AI Switches Job Information N2 Address. Ref N2+ N2- ADDR 0 = ALL OPEN

Power consumption In operation At rest For wire sizing. Torque Inhibiting torque. 150 s / C Sound power level Motor

VAV compact controller GDB181.1E/3 GLB181.1E/3

General information. Display. Supply voltage. Input current. Encoder supply. Power losses

General information. Display. Supply voltage. Input current

Electrical data Nominal voltage AC/DC 24 V Nominal voltage frequency

General information. Display. Supply voltage. Input current

Brief description. Type overview

DRTS 3 PLUS Advanced Protection Relay Test Set and Measurement System

Transcription:

Infinity TCX 865,866 VAV Controller with Built-in Actuator The Infinity TCX 865 programmable Infinet terminal controller is a unique, low-cost VAV box controller that comes equipped with a built-in damper actuator to streamline hardware installation and save commissioning time. The TCX 865, with two universal inputs; an airflow sensor; three Form A triac-based outputs; and an integrated damper actuator, is perfect for VAV applications requiring reheat control. Infinity's true peer-to-peer communications protocol provides the TCX 865 with the ability to instantly communicate with an Infinity network controller such as the CX 9200, as well as the entire network of Andover Infinet field controllers. Up to 254 TCX 865s can be networked to one CX series network controller. Metal oxide varistors and optocouplers on the TCX 865 provide 2500V isolation on each triac-based output, ensure noise-free operation and, in most cases, eliminate the need to install MOVs in the field. The TCX 866 model adds an additional universal input, plus a room sensor input, which supports Andover's new Smart Sensor, or any standard room temperature sensor. The TCX 866 also adds two analog outputs to control reheat valves, lighting ballast control, etc. F E A T U R E S Stand-alone VAV Control for System Reliability Built-in Damper Actuator Simplifies Hardware Installation Universal Inputs with Form A Outputs for Flexible VAV Control Peer-to-Peer Communications Provide Transparent Data Transfer Plain English Language Simplifies Programming On-Board Pressure Transducer for Airflow Measurement Actuator Clutch Feature Saves Commissioning Time View and Modify Information with Optional Andover Smart Sensor Interface

Infinity TCX 865, 866 VAV Control with Built-in Actuator COMMUNICATIONS Communication to the Infinity TCX 865 is handled via the Infinet bus, a twisted pair, half duplex RS-485 interface. Communication is accomplished with a token passing protocol which provides full transparent data transfer between all Infinity controllers on the network. INPUTS Input configuration consists of two full range Universal inputs that accept voltage, (0-5 VDC), digital (on/off), counter signals (up to 4 Hz), or temperature signals, plus an on-board air flow sensor. The TCX 866 model offers an additional universal input plus a room temperature input to support the Andover Smart Sensor, or any standard room temperature sensor. OUTPUTS The TCX 865 contains three Form A triac-based outputs for on/off or pulsed control of lighting, heat, and fan units. Two outputs can also be configured to provide one Tri-state Form K output and one Form A output, for bidirectional control of dampers and valves. Outputs are rated for AC loads only. The TCX 866 model also offers two analog outputs to control reheat valves, lighting ballast control, etc. DAMPER ACTUATOR The integrated Belimo damper actuator allows simple direct mounting of the TCX 865 directly over the existing damper shaft. This eliminates the need for separate mounting, wiring, and positioning of the damper motor. All TCX 865 controllers have built in software over-drive protection which senses repeated motor limit stall conditions and helps to prevent motor damage. Also, the actuator has a built-in clutch button to temporarily disengage the direct-drive gears during commissioning. The TCX 865 actuator may be preset for a limited range of motion using the mechanical "stops" provided. PROGRAMMING Every TCX 865 can be configured to meet the exact distributed control requirements of your application using Andover Controls powerful Plain English programming language. Programs can be activated within individual TCX 865s or any network controller. Programs are entered into a TCX 865 using an SX 8000 workstation, the LSX 280 Lap-Top Service Tool, or network controller. The program is then stored in, and executed by, the TCX 865. The on-board replaceable lithium battery keeps the TCX 865's programs and real-time clock backed up in the event of a power failure. Programming multiple TCX 865s is inherently easy with Plain English. A complete copy of one TCX 865 s programs can be loaded directly into other TCX 865s without changing any point names or programs. The SX 8000 workstation makes this process even easier with its unique drag-and-copy feature. SOFTWARE CAPABILITIES The dynamic memory of the TCX 865 can be allocated for any combination of Plain English control programs, scheduling, alarming, and data logging. Andover's object-oriented language with intuitive keywords provides easy operation and programming. In addition, Plain English s pre-defined and customized functions and powerful math capabilities reduce programming time for repetitive applications.

9" (228mm) 5.25" (133mm) Depth 2.5" (63.5mm) TCX 865 Dimensional Drawing TCX 866 Extra I/O Connections

S P E C I F I C A T I O N S ELECTRICAL Power: Power Consumption: Overload Protection: Real-Time Clock: 24 VAC, 50/60 Hz Note: Individual transformer at each controller required (not included). 10 VA Fused with 2 amp pico fuse. MOV protected. Battery-backed quartz clock, synchronized through Infinet by CX or CMX Network Controller. MECHANICAL Operating Environment: 32-120 F (0-48 C), 10-95% RH (non-condensing) Size: 9"H x 5 1/4" W x 2 1/2"D (228mm H x 133mm W x 63mm D) Weight: 1.78 lbs. Enclosure: UL open class, flammability rating of UL94-5V, IP 10. Optional terminal strip cover for NEMA-1 style, IP 20. BATTERY Battery Backup: Replaceable non-rechargeable, lithium battery. Provides 3 years typical accumulated power failure backup of RAM memory and real-time clock. COMMUNICATIONS Communications Interface: Communications Speed: Bus Length: Bus Media: Through Infinity CX or CMX Network Controllers or LSX 280 Lap-Top Service Tool. 1200 to 19.2k baud 4,000 ft. (1,220m) standard for Infinet, InfiLink amplification module allows extension to longer distances and is required after every group of 32 units on the network. Infinet: twisted, shielded pair, approved low capacitance cable Comm. Error Checking: International Standard CRC 16 INPUTS/OUTPUTS Inputs: Input Voltage Range: 2 universal inputs (TCX 866 has 3): Temperature -30 F to 230 F (-34 C to 110 C), Digital (on/off), Counter (up to 4Hz at 50% duty cycle, 125 ms. minimum pulse width), Voltage (0-5. 115 VDC) 1 airflow sensor (0 to 1" W.C.) 1 Smart Sensor or std. room sensor (32 F to 105 F) (0 C to 41 C) (TCX 866 only) 0-5.115 volts DC

S P E C I F I C A T I O N S (Cont'd) Input Impedance: 10k ohm to 5.120V Input Protection: Input Resolution: Input Accuracy: 24 VAC or 24 VDC temporarily on any single channel, ± 1000V transients. Tested according to IEC 1000-4-4 5.0 mv ± 15 mv (± 0.56 C from -23 C to +66 C or ± 1 F from -10 F to +150 F) Airflow Input: Range: 0 to 1" WC (0-249 Pa) Resolution: 0.005" WC (1.25 Pa) @ 23 C (73 F) Outputs: Accuracy: ± 0.05" WC (12.5 Pa) @ 23 C (73 F) 3 single pole single throw (SPST) Form A triacs; 1 integrated damper actuator 2 analog outputs (0-10V) -TCX 866 Output Rating: For SPST: Maximum: 0.5A, 24 VAC, +2000 volt transients (Tested according to IEC 1000-4-4) Minimum: 30 MA AC Optically-isolated triac outputs, DC loads not permitted For 0-10V: 5 ma maximum, 2K Ohm minimum impedance, +1000 volts transients (tested according to IEC 1000-4-4) Accuracy: For SPST: For 0-10V: 0.1 sec. for pulse width modulation 50 mv resolution/100mv accuracy Damper Actuator: Rated Torque: Range of Travel: Rotation Speed: 35 in-lb. (3.95 Nm) 0-95 degrees, with adjustable mechanical stops 1.0 degree/sec nominal Position Resolution: 0.1 degrees with a 1.0 degree min. positioner movement Actuator Output: 1.0 sec minimum pulse duration Shaft Accommodations: Accepts shafts 1/4" - 5/8" diameter (6.35mm - 15.9mm)

S P E C I F I C A T I O N S (Cont'd) CONNECTIONS Power: Male Spade (.250) Inputs: Outputs: Damper Shaft: Infinet Bus: Male Spade (.250) (Additional TCX 866 inputs use screw terminals) Male Spade (.250) (Additional TCX 866 outputs use screw terminals) 1/4" - 5/8" diameter (6.35mm - 15.9mm) Three-position barrier strip GENERAL Memory: 128K EPROM, 32K RAM, 128 Bytes EEPROM AGENCY LISTINGS UL/CUL 916, 916, UL864-UUKL, FCC, CE FCC, CE OPTIONS Terminal Strip Cover for NEMA 1-style enclosure, IP 20 Andover Controls Corporation World Headquarters 300 Brickstone Square Andover, Massachusetts 01810 USA Tel: 508 470 0555 Fax: 508 470 0946 http://www.andovercontrols.com Andover Controls Ltd. Smisby Road Ashby-de-la-Zouch Leicestershire LE65 2UG, England Tel: 01530 417733 Fax: 01530 415436 Andover Control GmbH Am Seerhein 8 D-78467 Konstanz, Germany Tel: 07531 99370 Fax: 07531 993710 Andover Controls Corporation 707 Chinachem Golden Plaza 77 Mody Road, Tsimshatsui East Kowloon, Hong Kong Tel: 2739 5497 Fax: 2739 7350 1997, Andover Controls Corporation. Data subject to change without notice. Consult Andover Product Installation Guides for exact installation instructions and specifications. #DS-TCX865-D