VAV Modular Assembly (VMA) 1410/1420

Similar documents
UNT1100 Series. Binary Output Jumpers AO2 AO1 AO3 AO4 AOCM AOCM AOCM AOCM AO1. AI Switches Job Information N2 Address. Ref N2+ N2- ADDR 0 = ALL OPEN

Variable Air Volume Modular Assembly (VMA) 1400 Series

TC-9102 Terminal Controller

FXVMA Variable Air Volume (VAV) Box Controller

Variable Air Volume Modular Assembly (VMA) 1200 Series Overview and Engineering Guidelines

CCS ZEC400 VAV Controllers

AS-CVTPROx00-0 Zone Bus/N2 Bus Interface Converter

BAC-9000 Series VAV Controller Installation Guide

HE-6800 Series Humidity Transmitters with Temperature Sensor

ZEC310 Zone Damper and BYP200 Bypass Damper Controllers

TECH/DATA SHEET. Application. Model Chart. Installation. slon-v1. slon-v2. slon VAV Controller

VMA1610 and VMA1620 Variable Air Volume Controllers Installation Instructions

Custom Controller Installation Instructions

TEC Terminal Box (VAV) Controller

Onboard Inputs and Outputs. Remote User Interface. Integral LCD User Interface

BACnet PTEC Terminal Box (VAV) Controller. Control Applications. Product Numbers. Product Description. Warning/Caution Notation

Siemens BACnet Programmable TEC VAV with Series Fan and 3-Stage Electric Heat Controller

Installation & Operation Guide

FX Input/Output (I/O) Modules XM07 and XM14

FX-DIS1710 Local Controller Display Installation Instructions Part No , Rev. B Issued April 2016

VMA Programmable VAV Box Controllers Catalog Page Code No. LIT Issued February 2018

XT-9100 Technical Bulletin

Cables. U.S. Registered Trademark EN0B-0341GE51 R0402 Copyright 2002 Honeywell Inc. All rights reserved

LN Series Remote Input/Output (I/O) Modules

P216 Series Condenser Fan Speed Controller

BACnet Terminal Box (VAV) Controller

MNL-V1RVx MNL-V2RVx. Application. Model Chart. TAC I/A Series MicroNet Variable Air Volume Controllers Installation Instructions

Suitable for a wide range of installations with wall-mount, flush-mount and hand-held remote control options.

TM-2100 Series Room Command Module

PP-8516 & PP Electronic Static Pressure Controllers and Transmitters for Cental Air Supply Systems General Instructions

Andover Continuum Infinet II i2865/866 VAV Controllers with Built-in Actuator

FX06 Field Controller

Smart Equipment Controls (SEC)

N20010-SER. NON-SPRING RETURN DAMPER ACTUATOR 20 Nm (177 lb-in) FOR ADJUSTABLE MODULATING CONTROL SPECIFICATIONS GENERAL FEATURES PRODUCT DATA

Modular Room Control (MRC) Series Expansion Board

FX14 Field Controller

Functional data Communicative control Cloud: (call for clientapi ) Angle of rotation 90

FX-PCX Expansion Input/Output Modules Catalog Page Code No. LIT Issued April 17, 2015

N05, N10 SERIES NON-SPRING RETURN DIRECT-COUPLED DAMPER ACTUATORS FOR MODULATING AND FLOATING CONTROL

Field selectable application type and room module series, via dip-switches on controller

Siemens BACnet Programmable TEC Dual Duct Two Air Velocity Sensors Controller

Input/Output Module (IOM) Series Controllers Catalog Page Code No. LIT Issued June 2018

Lab and Central Plant Controller

S66 Series Electronic Fan Speed Control

T7560A,B,C Digital Wall Module

Andover ContinuumTM b3865/866 VAV Controllers with Built-in Actuator

RWD68U Universal Controller

LX Series Free Programmable LX-PRG6x0-11 Controllers and LX Series Input/Output (I/O) Extension Modules

Siemens BACnet Programmable TEC Dual Duct Two Air Velocity Sensors Controller

T7560A1036 Digital Wall Module

Input/Output Module (IOM) Series Catalog Page

System 450 Series Modular Controls

clarity 3 VAV Programmable Controller

VMA Programmable VAV Box Controllers Catalog Page

Zone Pressure Touch (ZPT) Sensor - Standard Range

TM-2100 Series Room Command Module

PROLON INSTALLATION AND START UP GUIDE

CCS Handheld VAV Balancing Tool Technical Bulletin

The Infinity TCX 865 programmable Infinet terminal controller is a unique, low-cost VAV box

Compact actuating room automation stations, BACnet/IP, AC24 V (Actuating DXR)

Siemens BACnet Programmable TEC Constant Volume

TEC VAV with 0-10V AO Heat. Modulation and CO2 Monitoring. Controller. Control Applications. Product Description. Accessories.

ASI Systems ML5740A Series

VAV compact controller GDB181.1E/3 GLB181.1E/3

ASI Systems ML5720A Series

BA/BS4S Temperature Sensor Installation & Operating Instructions

Zone Pressure Touch Sensor - Standard Range

TAC Xenta 101-VF. 3-Speed Fan Coil Controller. TAC Xenta

MAXIMA+ Series Rotary Level Indicator

Free Energy Band RCC30U Room Temperature Controller for Four-pipe Fan Coil Unit

Siemens BACnet VAV Actuator

Dual Duct Controller - One Air Velocity

DWYER INSTRUMENTS, INC. Series AVUL Air Velocity Transmitter. Specifications - Installation and Operating Instructions.

N20, N34 Series Non-Spring Return Direct Coupled Actuators

P216. Condenser fan speed controller. Product bulletin. Features

MAXIMA + Series ROTARY LEVEL CONTROL

Hardware Installation. Tracer MP581 Programmable Controller CNT-SVN01C-EN

Powermite 599 MT Series SAS Electronic Valve Actuator 24 Vac or 24 Vdc, Proportional Control

Functional data Position indication reflective visual indicator (snap on) Communicative control Cloud: (call for clientapi )

rcc.1081 Installation Instructions

LN Series Communicating Sensors

TEC Zoning Control System for Stand-Alone and BACnet MS/TP Networked Applications

Actuator Commissioning Tool

Technical data sheet

SEZ7000 Series. Wireless Commercial Zoning System

LN Series Free Programmable LN-PRG6x0-12 Controllers and LN Series Input/Output (I/O) Extension Modules

TEC Unit Conditioner Controller

Tracer Controls. Tracer MP501 Controller BAS-PRC008-EN. January 2005

TC-8900 Controller Units with PM-8900 Power Modules

em4 Accessories Digital expansions

oom Pressurization Con

Airflow Pressure Sensor

Spyder Lon Programmable, VAV/Unitary Controllers

Electrical Actuators

TCNM-ACBB1 Installation Manual

Zone Pressure Touch (ZPT) Sensor with Attached Tube (-AT) - Low Pressure Range Unit Installation and Operation Instructions

Siemens BACnet Programmable TEC Unit Conditioner (Fan Coil) Controller for Smoke Control

System 450 Series Modular Controls

Series P215PR/RM Direct- and Remote-Mount Pressure-Actuated Condenser Fan Speed Controllers for Single-Phase Motors

LTEC Heat Pump DDC Controller

Transcription:

Installation Instructions Issue Date June 9, 2004 VAV Modular Assembly (VMA) 1410/1420 Application The Variable Air Volume (VAV) Modular Assembly (VMA) 1400 Series consists of configurable digital controllers. Both the VMA1410 and 1420 have a pressure sensor and actuator in a prewired unit. For additional information, refer to the Variable Air Volume Modular Assembly (VMA) 1400 Series Overview and Engineering Guidelines Technical Bulletin (LIT-6363120) and the Variable Air Volume Modular Assembly (VMA) 1400 Series Application Note (LIT-6375125). Use HVAC PRO software to program these controllers. (Use EURO PRO in Europe.) Installation Set the N2 addresses using the following instructions before mounting the VMA. Setting N2 Addresses There are two ways to set the N2 addresses for VAV boxes: hardware addressing or software addressing. Hardware addresses take priority over software addresses. If software addressing is used, the hardware address of each VMA must be disabled by setting the N2 address (DIP) switch to 0 or to 255. Hardware Addressing In hardware addressing, the N2 address DIP switches on the side of the VMA are manually set to the appropriate address (Figure 1). The N2 hardware address equals the sum of the values beside each DIP switch that is set to ON. For example, if the first DIP switch (1) and the fifth DIP switch (16) are both set to ON, the N2 hardware address for that controller is 17 (1 + 16 = 17). Use Addresses 1-253 (254 is reserved and should not be used by any N2 device on the same N2 trunk). Software Addressing In software addressing, use HVAC PRO software Release 8.01 or later to set the N2 address of each VMA over the Zone Bus. The VMA must be at firmware Revision B12 or later in order to use software addressing. To use software addressing: 1. Set DIP switches to address 0 or 255 and install the VMAs. If the DIP switches are set to any other value during power up, the controller defaults to hardware addressing. N2 Address DIP Switches To CCW End Stop To CW End Stop O O F N F 128 64 32 1684 Mounting Screw 2 1 Shoulder Washer example: 16 + 1 = 17 Phone Jack Port (Sensor) Gear Release (Push Down) Mounting Slot packsl1f Figure 1: VMA1410/1420 Controller 2004 Johnson Controls, Inc. 1 Part No. 24-8740-1, Rev. D www.johnsoncontrols.com

2. Supply power to the units. 3. Program each address through the Zone Bus using a laptop, AS-CBLPRO-2 or AS-CVTPROx00-0 converter, and HVAC PRO software Release 8.01 or later. Select either Controller Information or VMA Balancer Tool from the Action menu in HVAC PRO software. If you select Controller Information, select Single Device. 4. Select Zone Bus. The Controller Information screen or VMA Balancer Tool screen appears. 5. Select an N2 address from the drop-down list. 6. Click Set Address. 7. Wait for the new address to appear in the N2 Address field of the Controller Information screen or Balancer Tool screen. Alternately, program each address through the Zone Bus using a Palm compatible handheld device and the VMA1400 Balancing Tool (VBT) software. Refer to the Auxiliary Gear Technical Bulletin (LIT-6363080) and Using the VMA1400 Balancing Tool (VBT) Software Technical Bulletin (LIT-6363092). Refer to the Testing and Receiving Data from Controllers chapter (LIT-63750416) of the HVAC PRO User s Guide for more information. Mounting For additional information, refer to the Mounting and Wiring Variable Air Volume Modular Assembly (VMA) 1400 Series Controllers Technical Bulletin (LIT-6363125). To mount the VMA1410/1420: 1. Set the N2 address DIP switches to the appropriate address before mounting the VMA. Make sure the switches are pressed fully to the required position. See the Setting N2 Addresses section in this document. 2. Place the VMA in the proper mounting position on the damper shaft so that the wiring connections are easily accessible. Make sure the VMA base is parallel to the VAV box. If needed, use a spacer to offset tipping of the VMA caused by shaft bushings. IMPORTANT: When the air supply to the VAV box is below 50 F (10 C), make sure that any condensation on the VAV box, particularly on the damper shaft, does not enter the electronics. Mount the VMA vertically above the damper shaft to allow any shaft condensation to fall away from the VMA controller. Additional measures may be required in some installations. 3. Secure the self-drilling No. 10 screw into the VMA mounting slot with a power screwdriver and 100 mm (4-inch) extension socket. Otherwise, use a punch to mark the position of the shoulder washer, and then drill a hole into the VAV box through the mark using a 3.5 mm (9/64 in.) drill bit. Insert the mounting screw, and tighten against the washer. IMPORTANT: Do not overtighten the screws, or the threads may strip. If mounting to the VAV box, make sure the screws do not interfere with damper blade movement. 4. Locate the damper position using typical marking on the end of the damper shaft (see Figure 2). Figure 2: Typical Damper Shaft End Icons 5. Note the direction, Clockwise (CW) or Counterclockwise (CCW), required to close the damper. Grasp the damper shaft firmly with pliers and either manually close the damper for 90 boxes or manually open the damper for 45 or 60 boxes. 6. Push down and hold the gear release lever (see Figure 1), and turn the VMA coupler until it contacts the mechanical end-stop at either the fully closed (90 boxes) or fully open (45 or 60 boxes) position. 7. If the damper for a 90 box closes CCW, rotate the coupler to the CCW mechanical limit. If the damper for a 90 box closes CW, rotate the coupler to the CW mechanical limit. The open end-stop is automatically set for 90 boxes. Hard stops must be provided for 45 and 60 boxes at both fully closed and fully open damper positions. By installing the VMA at the fully open position, the VMA provides the open stop for 45 and 60 boxes. The closed damper seal provides the fully closed stop. packsli4 2 VAV Modular Assembly (VMA) 1410/1420 Installation Instructions

8. Tighten the square coupler bolt to the shaft using an 8 mm (5/16 in.) wrench or 10 mm (3/8 in.) 12-point socket. Tighten to 17 to 21 N m (150 to 180 lb in [14 lb ft]). 9. Loop the pneumatic tubing to include a trap for condensation. Attach the tubing from the VMA to the VAV box pickup. The HI (red) tubing is connected to the inlet or high-pressure side and the clear tubing to the low side (see Figure 3). 10. Push the gear release lever, and turn the actuator coupling manually to ensure that the actuator can rotate from full closed to full open positions without binding. 11. Complete the mounting by rotating the damper to the full open position.! CAUTION: Risk of Equipment Damage. Rotate the damper to full open position before starting the air handler. Failure to rotate the damper to the full-open position may result in damage to the VAV box when the air handler is started. Approved 5/7/2004 Wiring! CAUTION: Risk of Electrical Shock. Disconnect supply power to the VMA1410/1420 before attempting to adjust the DIP-switch. Failure to disconnect the supply power may result in electrical shock.approved 8/26/2003 To wire the VMA: 1. Terminate wiring per engineering drawings. 2. Install the N2 Bus to the Network Control Module (NCM) or N30/N31 controller in a daisy chain only (see Figure 3). 3. Ensure the N2 address DIP switches are set to the appropriate hardware address (0 or 255 if using software addressing). 4. Connect power to the VMA. 5. Download, commission, and balance the VMA. Table 1: VMA Wiring List Point Description Range Input or Load Impedance (ohms) AI-1* Zone Temperature 1 K ohm Nickel, Silicon, or Platinum 2.25 K ohm NTC (Negative Temperature Coefficient) AI-2* Zone Setpoint 1.6 K ohm 2-wire potentiometer AI-3* AI-4* Humidity Transmitter Perimeter Temperature or Supply Air Temperature Continued on next page... Voltage Current 10 K 5 VDC 0.5 ma Cable Length Wire Size in mm or mm 2 (AWG) 1.5 mm 2 ( 10 K 5 VDC 0.5 ma 10 K 5 VDC 0.5 ma 1.5 mm 2 ( 0 to 10 VDC 1.1 M 16.5 VDC 15 ma 1 K ohm Nickel, Silicon, or Platinum 2.25 K ohm NTC 10 K 5 VDC 0.5 ma 1.5 mm 2 ( 10 K 5 VDC 0.5 ma VAV Modular Assembly (VMA) 1410/1420 Installation Instructions 3

Point (Cont.) Description Range Input or Load Impedance (ohms) Voltage Current Cable Length Wire Size in mm or mm 2 (AWG) AI-5* BI-1* BI-2* BI-3* AO-1* AO-2* BO-1, 2, 3, 4, 5^ SM-1^ N2 Bus*^ Zone Bus* Room Sensor Cable* +15 VDC* 24 VAC Power In^ Velocity Pressure (internal) Temporary Occupied Comfort (occupied) Window, Off (shutdown) Proportional Heat/ Humidity/Fan Speed Proportional Heat/ Humidity/Fan Speed Fan/Box Heat/ Baseboard Heat/Electric Heat/Lighting Stepper Motor (internal) Networking Bus Local Room Sensor Bus AI-1, AI-2, BI-1, Zone Bus, and +15 VDC DC Output Supply AC Supply Voltage * Isolated from 24 VAC. ^ Note: 0-1.5 in. W.C. (0.5 to 4.5 VDC) 0-5 VDC, 3.1 V trigger 0-15 VDC, 2.5 V trigger 0-15 VDC, 2.5 V trigger 250 K 5 VDC 0.020 ma Internal NA 440 5 VDC 10 ma 47 K 17 VDC 0.3 ma 47 K 17 VDC 0.3 ma 0-10 VDC 1 K-10 M 10 VDC 10 ma 0-10 VDC 1 K-10 M 10 VDC 10 ma 24 VAC @25-500 ma ±34 VDC 2-phase ±5 V transmit, ±0.2 V receive 48-1000 30 VAC 1.5 mm 2 ( 1.5 mm 2 ( 60 m (200 ft) 0.6 mm (24) 100 ma 1.5 mm 2 ( 60 m (200 ft) 0.6 mm (24) 1.5 mm 2 ( 100 ma 500 ma 30 m (100 ft) 1.5 mm 2 ( 500 ma 6 m (20 ft) 0.6 mm (24) 72-100 40 VDC 250 ma Internal NA 200 5 VDC 100 ma 1500 m (5000 ft) ±0-5 VDC >3000 5 VDC 100 ma See Zone Bus above. Isolated from AI, BI, AO, Zone Bus, 15 VDC. All field terminals are power limited. 14-18 VDC 1 K-10 M 18 VDC 35 ma 20-30 VAC 12-48 30 VAC 417 ma (100 VA cable length) 7.5 m (25 ft) 15 m (50 ft) 30 m (100 ft) 0.6 mm (24) eightconductor phone cable 1.5 mm 2 ( 60 m (200 ft) 0.6 mm (24) 67 m (222 ft) 6 mm 2 (10) 42 m (140 ft) 4 mm 2 (12) 27 m (88 ft) 2.5 mm 2 (14) 17 m (55 ft) 1.5 mm 2 (16) 11 m (35 ft) 1.5 mm 2 ( 4 VAV Modular Assembly (VMA) 1410/1420 Installation Instructions

Class2 Energy Limited Transformer Primary 24 VAC 2-wire Proportional Valve Actuator 3-wire Incremental Valve Actuator 24 VAC HI (Red) LO Pneumatic Tubing (Differential Pressure) ( BI-1 (19) COM (20) BI-2 (21) COM (22) BI-3 (23) COM (24) +15 VDC* (25) +15 VDC (26) AI-1 (27) COM (28) AI-2 (29) COM (30) AI-3* (31) COM* (34) ZB+ (35) ZB- (Europe) SHLD REF N2- N2+ Wiringis Coupler Coupler Bolt Set Screw CCW End Stop COM Optional National Electrical Code (NEC) if More than 150 VAC Primary Fan Relay 3-wire Baseboard Heat open close open close (1) 24 VAC (2) 24 VAC (3) Earth Gnd. (Optional) (4) BO-1* (5) BCOM* (6) BO-2* (7) BCOM* (9) BCOM* (11) BCOM* (12) BO-5* (13) BCOM* (14) AO-1* (15) COM* (16) AO-2* (17) COM* LED Visual Response Flashes at 1 second rate Irregular flashing 4 times per second Rapid flashing 20 times per second Not lit Action During initialization After communications established Needs core code download. No power or +15V shorted Optional N2 Shield To Next N2 Device CW End Stop TMZ1600 Wiring TE-6700 Screw Numbers 6 5 3 4 8 8 6 5 1 2 4 3 7 TB1-1 TB2-7 TB2-8 TB1-3 TB1-4 TB1-2 TB2-5 TB2-6 TE-7000 Screw Numbers (Europe) * Included on VMA1420 only. To NCM N2 Bus 24-18 AWG Figure 3: Typical VMA1410/1420 Wiring Interface VAV Modular Assembly (VMA) 1410/1420 Installation Instructions 5

Technical Specifications Product Name Variable Air Volume Modular Assembly (VMA) Product Code Number Cooling Only Models Cooling with Reheat and/or Fan Powered Models Supply Voltage Power Consumption Optional 24 VAC Fuse Current Ambient Operating Conditions Ambient Storage Conditions Terminations Optional Terminations Single Unit AP-VMA1410-0 AP-VMA1420-0 Bulk Pack AP-VMA1410-0D AP-VMA1420-0D Buy American AP-VMA1410-0G 20-30 VAC at 50 or 60 Hz AP-VMA1420-0G 10 VA maximum (relay and valve requirements not included) VMA1410 = 0.6 ampere, VMA1420 = 2.0 ampere 0 to 50 C (32 to 122 F) -40 to 70 C (-40 to 158 F) 6.3 mm (1/4 in.) spade lugs except communications, which are screw terminals 2 or 3 position screw terminals that plug onto spade lugs (optional accessories) 2-position screw terminal: AP-TBK1002-0 3-position screw terminal: AP-TBK1003-0 Replacement N2 Communications Bus terminal: AP-TBK4N2-0 Controller Addressing DIP switch set (1-253) Address 254 is reserved (0 or 255 is used for software addressing). Software addressable with HVAC PRO Release 8.01 or later Communications Bus Mounting Actuator Rating Standards Compliance N2 Bus between VMA controller and supervisory controller (3-wire) Zone Bus between VMA controller and room sensor (8-pin phone jack or wire to spade lugs or optional plug-on terminals) Mounts to damper shaft using single set screw and to duct with single mounting screw. 4 N m (35 lb in) minimum Minimum shaft length = 44 mm (1 3/4 in.) IEEE 472, IEEE518, IEEE587 Category A/B, ANSI C62.41 FCC Part 15, Subpart J, Class A/B CISPR 22, Class B UL 916 UL 864 (UUKL) UL 94-5VB CSA 22.2 No. 205 IEC-950, IEC 801 CE Directive (89/336/EEC, EN50081-1, EN50082-2) FCC Part 15 Label - Note: This equipment has been tested and found to comply with the limits for a Class A digital device pursuant to Part 15 of FCC Rules. These limits are designed to provide reasonable protection against harmful interference when this equipment is operated in a commercial environment. This equipment generates, uses, and can radiate radio frequency energy and, if not installed and used in accordance with the instruction manual, may cause harmful interference to radio communications. Operation of this equipment in a residential area is likely to cause harmful interference, in which case the user will be required to correct the interference at their own expense. Controls Group 507 E. Michigan Street P.O. Box 423 Milwaukee, WI 53201 Published in U.S.A. www.johnsoncontrols.com 6 VAV Modular Assembly (VMA) 1410/1420 Installation Instructions