C-DIAS Analogue Conversion Module CAM 011 for 3 x 0-10V DC inputs 2 x PT100 inputs and 1 x ±10V output

Similar documents
C-DIAS Analogue Conversion Module CAM 124 for eight 0 10V DC inputs and four 10V outputs

Technical Data. C-DIAS-MULTI l/o MODULE CIO 013

C-DIAS Analogue Output Module CAO 081 for eight 10V DC outputs

C-DIAS Temperature sensing module CAI x temp. inputs C 8 x digital outputs +24V

C-DIAS Analogue Output Module CAO 082 for eight ±10V DC respectively eight 0 20mA DC outputs

C-DIAS-Temperature Recording module CAI x Temp. inputs 50 C to +150 C

C-DIAS Digital Input Module CDI 161 with 16 inputs

C-DIAS Analog Module CAO 086 For eight ±10 V Outputs

C-DIAS Analog Input Module CAI 086 For eight, ±10V voltage inputs

Expansion Module HZS 541-1S

C-DIAS Serial Interface CSI 021

HZS Solar Module

HZS Internal Controller Expansion

Internal Buffer/Boiler Module HZS 534

PCD3.C90. Date Modification Asked by: Version E/A Bus Connector PCD2.K106 change to PCD3.K106 Müller.R 1.1

DIAS Interface Module VARAN DIV 511

VARAN Splitter Module VSV 041

AO 081 S-DIAS Analog Output Module

AI 046 S-DIAS Analog Input Module

ISE 021 S-DIAS Interface Module RS232 / RS485

VARAN Digital Combined Module VDM 086

Auxiliary Board MP-Bus HZS 562

Cube67 - Modular I/O station

VARAN Bus Coupler Module VBC 021 For connecting two VARAN bus systems

VARAN Splitter PROFINET VSP 044

TO 161 S-DIAS Digital Output Module

Protected VARAN Digital Mixed Module PVDM 086

GFK-2415A March Type of sensor connection

Profibus DP slave. dual ported RAM 2Kbyte. Maximum length for I/O data. Maximum length for output data. Status display

SI 021 S-DIAS SSI Interface Module

R1M-GH THERMOCOUPLE & DC INPUT MODULE MODEL. Remote I/O R1M Series. (16 points)

Processor module DCP 642

IB IL AO 2/SF... Inline terminal with two analog outputs. AUTOMATION Data sheet 6655_en_06. 1 Description

Modular controllers CECX

PCAN-MicroMod Analog 2 Application-specific PCAN-MicroMod Motherboard. User Manual. Document version ( )

IB ST 24 AO 4/EF. INTERBUS-ST analog output module, 4 outputs, 0-10 V, ±10 V, 0-20 ma, 4-20 ma. Data sheet. 1 Description

DM 161 S-DIAS Digital Mixed Module

DINALOG A 144 x 36 A1400 Light-Strip Indicator

SAI Active Universal Pro

Tachometers TC-4B-V TC-6A-V Electronic cam-operated switching devices FC-21-V... 50

AMC 8 & IOC 8T. Analog Monitoring Card Type AMC 8 and Input / Output Card Type IOC 8T FEATURES

Strain gauge Measuring Amplifier GSV-1A8. Instruction manual GSV-1A8, GSV-1A8USB, GSV-1A16USB

VARAN-INTERFACE VAC 012

Temperature measurement board, optically isolated, 16/8/4 channels for thermocouples, Pt100, RTD, 18-bit

This data sheet is only valid in association with the IL SYS INST UM E user manual.

VARAN Splitter Module VSV 043

TSY 041 Training System Extension Motion

General information Engineering with Programming package. Display with display. Supply voltage 24 V DC Yes

RSTI-EP Slice I/O. Analog Input Modules `EP-3164, EP-3264, EP-3124, EP-3368, EP-3468 EP-3664, EP-3704, EP GFK-2960F September 2018

General information. Display. Supply voltage. Input current. Encoder supply. Output current

NI REM Remote I/O Overview DATASHEET. Analog Output Module for Remote I/O

TM3TI4 module TM3-4 inputs temperature

Analog Input Module. ST-3xxx. User Manual CREVIS Co.,Ltd. Version FnIO S-Series

Linear Position Transducer HLT 1000-R2

General information. Display. Supply voltage. Input current. Encoder supply. Output current

Distributed Control I/O System ADAM-8000 Series

VARAN Splitter PROFINET VSP 042

USB-1616FS. Analog Input and Digital I/O. Specifications

TM3AI4 module TM3-4 analog inputs

Time Counters mini "h", DC Version

PCAN-MicroMod Mix 2 Application-specific PCAN-MicroMod Motherboard. User Manual. Document version ( )

TM3TM3 module TM3-2 temperature inputs and 1 analog output

TM5C12D6T6L compact I/O expansion block TM5-24 I/0-12 DI - 6 DO transistor - 4 AI - 2 AO

TM3TI8T module TM3-8 inputs temperature

Mix 2. Motherboard for the PCAN-MicroMod. User Manual

SITOP in the SIMATIC Design

General information. Display. Supply voltage. Input current. Encoder supply. Output current

Display. Supply voltage. Input current. Encoder supply. Output current. Power losses. Memory

Display. Supply voltage. Input current. Encoder supply. Output current. Power losses. Memory

Keyboard Unit Sigmatek

General information. Display. Supply voltage. Input current

OPERATION MANUAL - DS-MOD-

Measuring transducers MI4x0 series Programmable transducers for RTD sensors MI450

Rotary Measuring Technology Absolute singleturn encoder shaft version

P2-04DAL-2 Analog Output. Removable Terminal Block Specifications

I/O module, universal, digital, S0 inputs, modu533

RSTI-EP Slice I/O. Analog Input Modules `EP-3164, EP-3264, EP-3124, EP-3368, EP-3468 EP-3704, EP GFK-2960B November 2017

to 12a Added Standard and Electrical requirements for UL table 1.1

General information. Display. Supply voltage. Input current. Encoder supply. Power losses

1/32-DIN TEMPERATURE CONTROLLER INSTALLATION, WIRING AND OPERATION MANUAL FORM 3882

A16. Separate Construction with Cylindrical 16-dia. Body. Pushbutton Switch (Detachable) (Lighted/Non-Lighted) (Cylindrical 16-dia.

Process displays For current and voltage

16-Channel 16-Bit PMC Analog I/O Board

MIC-2 MKII, Multi-instrument DATA SHEET

Data Sheet T 6493 EN. TROVIS 6400 Automation System TROVIS 6493 Compact Controller. For panel mounting (front frame 48 x 96 mm/1.89 x 3.

Millenium II +: general characteristics

Specifications USB-1408FS

C-DIAS EtherNet/IP Slave CIP 022

LED Driver Compact fixed output

SystempaK (Digital/File Type) Dual Input Arithmetic Relay Module Model J-SCM 92/97

General information Engineering with Programming package. Display with display. Supply voltage 24 V DC Yes. Input current

General information Engineering with Programming package. Display with display. Supply voltage 24 V DC Yes. Input current

LAUREL ELECTRONICS, INC.

General information Engineering with Programming package. Display with display

General information. Display. Supply voltage. Input current

Your process requires the utmost attention Our new ACT20C signal conditioners support you in achieving this

JUMO MIDAS C08. OEM Pressure Transmitter Basic. Applications. Brief description. Special features. Customer benefits

Electronic Level Switch ENS 3000

LAUREL. Laureate Digital Panel Meter for Process and Ratiometric Signals ELECTRONICS, INC. Features. Description

CamCon DC16/IO. Digitronic Automationsanlagen GmbH. Input Output - extension

Transcription:

C-DIAS Analogue Conversion Module CAM 011 for 3 x 0-10V DC inputs 2 x PT100 inputs and 1 x ±10V output This analogue conversion module is a combination of analogue inputs and outputs. There are three analogue inputs for voltage measurement (0 10V / 4 wire), two analogue inputs for temperature measurement (PT100 / 4 wire) and one analogue output for voltage output (±10V). Additionally various states can be displayed via 5 LEDs. Technical Data Input channel specifications Number of channels Measuring range 3 (4 wire connection) 0 10V Measured value 0 16000 Open input delivers value 16383 Resolution Transformation time per channel 14 bit 1ms Input filter Cut-off frequency 1kHz (1ms) Low pass class 3 Reference output +10V / ±1% Loading capacity of the reference supply voltage per channel Precision of the analogue channel 2.5mA +/-0.5% of the maximum measured value 05.08.2011 Page 1

Eingang [V] Response Sprungantwort of des input Eingangsfilters 0-10V 0 10 12,00 12,00 10,00 10,00 8,00 8,00 6,00 6,00 4,00 4,00 2,00 2,00 0,00 0,00 0,00 250,00 500,00 750,00 1000,00 Zeit [µs] Ausgang [V] Eingang [V] Delay of the input filter 0 10 Verzögerung des Eingangsfilters 0-10V 12 12 10 10 8 8 6 6 4 4 2 2 0 0 0 0,5 1 1,5 2 2,5 3 3,5 4 4,5 5 Zeit [ms] Ausgang [V] Temperature measurement with thermal resistances Number of Channels 2 Measuring range -50 to +150 C Sensor area 80.31-157.31Ω Measure value Input resistance 0 to 16000 (open input delivers value16383) >1MΩ Common mode area ±20V Input filter 1s Suitable sensor PT 100 DIN IEC 751 Measuring precision ±0.75 % Reference output 1mA / ±1 % Eingang [ C] Sprungantwort des Eingangsfilters Response of input filter 12,00 150,00 10,00 100,00 8,00 6,00 50,00 4,00 0,00 2,00-50,00 0,00 0,00 250,00 500,00 750,00 1000,00 Zeit [ms] Ausgang [V] Eingang [ C] 450 400 350 300 250 200 150 100 50 0 Verzögerung des Eingangsfilters DAI402 und DAI403 Delay of the input filter ca.300 ms 0 0,5 1 1,5 2 2,5 3 3,5 4 4,5 5 Zeit [s] 12 10 8 6 4 2 0 Ausgang [V] Page 2 a 05.08.2011

Output channel specifications C-DIAS ANALOGUE CONVERSION MODULE CAM 011 Number of channels 1 Output voltage -10 to +10V DC Output value -2000 to +2000 Resolution Loading capacity of the output voltage Protection against short circuiting Transient time Refresh time of all channels Precision of the analogue output 14 bit (1,25mV / bit) >100KΩ Yes <50µs <1ms +/-0.4% of the magnitude of the output Electrical requirements Supply voltage +24V 18 30V DC (is supplied at connectors X1 X5) Bus supply +5V / +24V internal Current consumption on the C-DIAS bus (+5V supply) Typically 100mA Maximum 130mA Current consumption on the C-DIAS bus (+24V supply) Typically 100mA (without load on reference outputs) Voltage supervision Supply voltage +24V LED 5 illuminates at supply voltage <18V Miscellaneous Article number 12-017-011 Hardware version 2.x Standardization UL (E247993) 05.08.2011 Page 3 e

Environmental conditions Storage temperature Operating temperature Humidity EMV stability -20 +85 C 0 +60 C 0 95%, without condensation In accordance with EN 61000-6-2:2001 (industrial) Resistance to shocks EN 60068-2-27 150m/s² Protective system EN 60529 IP 20 Page 4 b 05.08.2011

Mechanical dimensions C-DIAS ANALOGUE CONVERSION MODULE CAM 011 104.10 (dimensioning incl. covers) 109.2 129 24.90 05.08.2011 Page 5

Pin assignment X1 Analogue input 0-10V X2 Analogue input 0-10V X3 Analogue input 0-10V X4 Analogue input temperature sensor (PT100) X5 Analogue input temperature sensor (PT100) X6 Analogue output -10...+10V X7 Supply +24V Analogue In Error: When there is not a signal on every input channel or the input voltage at one or more channels is >10V. Page 6 05.08.2011

X1 X3: Analogue inputs 0 10V C-DIAS ANALOGUE CONVERSION MODULE CAM 011 1 2 5 6 Pin Function 1 +10V-Ref OUT 2 Analogue IN + 3 AGND-1 4 Analogue IN - 5 GND 6 +24V-OUT X4, X5: Analogue inputs temperature sensor (PT100) 1 2 Pin Function 1 Reference OUT 2 Analogue IN + 3 AGND-1 4 Analogue IN - 5 GND 6 +24V-OUT 5 6 X6: Analogue output Pin 1 Pin Function 1 Analogue OUT 2 AGND-2 3 n.c. 4 AGND-2 The connection of the power supply happens with a 2-pole plug assigned as follows: X7: Supply plug 1 Pin Function 1 +24V supply 2 GND 05.08.2011 Page 7

Usable connectors X1-X5: 6-pole Weidmüller plug B2L3,5/6 X6: Connector with spring clamp: Phoenix Contact: FK-MCP 1,5/ 4-ST-3,5 Connector with screw clamp technique: Phoenix Contact: MC 1,5/ 4-ST-3,5 X7: Connector with spring clamp: Phoenix Contact: FK-MCP 1,5/ 2-ST-3,5 Connector with screw clamp technique: Phoenix Contact: MC 1,5/ 2-ST-3,5 The complete C-DIAS plug set CKL 041 with spring clamp is available from Sigmatek with the article number 12-600-041. Page 8 05.08.2011

Wiring instructions C-DIAS ANALOGUE CONVERSION MODULE CAM 011 The signals detected from the analogue module are very small in comparison with the digital signals. In order to guarantee trouble free functioning it is essential to stick to a meticulous wiring arrangement. The 0V supply voltage connection must follow the shortest path the common 0V terminal. The connecting wires to the sources of the analogue signals must be as short as possible and avoid lying in parallel to wires carrying digital signals. The signal carrying wires should be double or triple pole screened, or at least twisted together. Temperature measurement with thermistors 2-wire measurement 2-wire measurement is only advisable with short sensor leads since the resistance of the lead influences the measurement. Input + must be connected to the reference output and input with analogue GND. Input +/ Ref. Output 1 2 Input -/ Analogue GND 05.08.2011 Page 9 a

3-wire measurement This method can be employed when the earth lead has a large cross-section and therefore a correspondingly low resistance. Input must be connected to the analogue GND. Input + Ref. Output 1 2 Analogue GND/ Input - 4-wire measurement This type of connection provides the smallest measuring errors. Input + Ref. Output 1 2 Analogue GND Input - Page 10 a 05.08.2011

Voltage measurement with potentiometers (odometry) The input must be connected to the analogue GND connection. Ref OUT 1 2 Analogue IN + Analogue IN -/ AGND Active voltage source With voltage sources, which are not potential free, no connection must be made between input and GND or analogue GND. Analogue IN + 1 2 U Analogue IN -/ AGND 05.08.2011 Page 11 a

Status displays LED no. LED colour Meaning 1 green Sync 2 green Reference voltage OK 3 green Reference voltage ON 4 red Analogue IN error 5 red +24V Low level error Page 12 a 05.08.2011

Addressing Address Access Function $00, $20, $40, $60, $80, $A0, $C0, $E0 $02, $22, $42, $62, $82, $A2, $C2, $E2 $04, $24, $44, $64, $84, $A4, $C4, $E4 $06, $26, $46, $66, $86, $A6, $C6, $E6 $08, $28, $48, $68, $88, $A8, $C8, $E8 $0A, $2A, $4A, $6A, $8A, $AA, $CA, $EA $10, $30, $50, $70, $90, $B0, $D0, $F0 $16, $36, $56, $76, $96, $B6, $D6, $F6, $16, $36, $56, $76, $96, $B6, $D6, $F6, 16#18, 16#38, 16#58, 16#78, 16#98, 16#B8, 16#D8, 16#F8 READ WORD Analogue measurement value REFERENCE VOLTAGE READ WORD Analogue measurement value CHANNEL1 (0 10V) READ WORD Analogue measurement value CHANNEL2 (0...10V) READ WORD Analogue measurement value CHANNEL 3 (0...10V) READ WORD Analogue measurement value CHANNEL 4 (PT100 / -50..+150 C) READ WORD Analogue measurement value CHANNEL 5 (PT100 / -50..+150 C) WRITE WORD Value analogue output (-10..+10V) WRITE BYTE ADC-DAC configuration: Bit 7 10V-Reference switch on READ BYTE ADC-DAC status: Bit 0 10V-Reference OK Bit 7 10V-Reference switched on READ BYTE PLL status register Bit 1 = PLL online Bit 0 = PLL lock (PLL locked) 16#19, 16#39, 16#59, 16#79, 16#99, 16#B9, 16#D9, 16#F9 READ/ WRITE BYTE PLL Configuration register Bit 2 0: Period duration of PLL time base in ms 16#1A, 16#3A, 16#5A, 16#7A, 16#9A, 16#BA, 16#DA, 16#FA 16#1B, 16#3B, 16#5B, 16#7B, 16#9B, 16#BB, 16#DB, 16#FB READ BYTE reserved READ BYTE Xilinx Version 05.08.2011 Page 13

16#1C... 16#1F 16#3C... 16#3F.. 16#FC... 16#FF reserved for interface module (CIC) Matching data (organized byte-wise) Address Data Description $00 $xx Check sum $01 123 Identification $02 7 Module group 7=AM $03 1 Module version 1=CAM011 $04 6 Number of channels $05 $10 Hardware version $10=HW 1.0 $10 Serial number AI-Matching data 0 10Vref way $40 $xxxx Check sum $42 12345 Identification $44 19 Length of the following data block in WORD $46 5 Number of channels $48-488 AI1 Offset = 0 10Vref way $4A 16000 AI1 Multiplicand $4C 15761 AI1 Divisor $4E -487 AI2 Offset = 0 10Vref way $50 16000 AI2 Multiplicand $52 15718 AI2 Divisor $54-497 AI3 Offset = 0 10Vref way $56 16000 AI3 Multiplicand $58 15698 AI3 Divisor $5A -8287 AI4 Offset = PT100 50 C +150 C $5C 16000 AI4 Multiplicand $5E 7363 AI4 Divisor $60-8220 AI5 Offset = PT100 50 C +150 C $62 16000 AI5 Multiplicand $64 7309 AI5 Divisor Page 14 a 05.08.2011

$66 15257 AI6 Offset = Reference voltage value at the moment of matching $68 0 AI6 Multiplicand not used $6 0 AI6 Divisor not used Address Data Description AI-Matching data 0 10V $80 $xxxx Check sum $82 12345 Identification $84 19 Length of the following data block in WORD $86 5 Number of channels $88-488 AI1 Offset = 0 10V $8A 16000 AI1 Multiplicand $8C 15834 AI1 Divisor $8E -487 AI2 Offset = 0 10V $90 16000 AI2 Multiplicand $92 115791 AI2 Divisor $94-497 AI3 Offset = 0 10V $96 16000 AI3 Multiplicand $98 15771 AI3 Divisor $9A -8287 AI4 Offset = PT100 50 C +150 C $9C 16000 AI4 Multiplicand $9E 7360 AI4 Divisor $A0-8221 AI5 Offset = PT100 50 C +150 C $A2 16000 AI5 Multiplicand $A4 7305 AI5 Divisor $A6 15258 AI6 Offset = Reference voltage value at the moment of matching $A8 0 AI6 Multiplicand not used $AA 0 AI6 Divisor not used AO-Matching data +/-10V $C0 $xxxx Check sum $C2 12345 Identification $C4 4 Length of the following data block in WORD $C6 1 Number of channels $C8 2054 AO1 Offset $CA 4040 AO1 Multiplicand $CC 4000 AO1 Divisor 05.08.2011 Page 15

Check sum calculation of the EEPROM The check sum is calculated byte-wise It is calculated from the address following the check sum to the last address of the data block (both inclusive) This means, the length of the data block of the check sum to be calculated = 5 BYTE fixed. Calculation algorithm 1. Load pointer with address of the matching data L.DI# HWKENN (without check sum) ADD.DI 1 2. Length of data block L.CX 5 3. Load check sum with $FF L.AL $FF 4. Rotate check sum 1 bit to the left into Carry LP ROL.AL 1 5. Add up check sum with current WORD and Carry ADC.AL (DI) 6. Increase pointer on next WORD ADD.DI 1 7. Finished all addresses? NO ---> 4. YES ---> 8. LOOP LP 8. Check sum is ready Calculation AI/AO matching values AI Matching values (0 10Vref way and 0 10V absolute) Calculation of the matching values e.g. 0.000 Assigned to ADC 163d 10.000V or 10Vref assigned to ADC 14614d Matching data: OFFSET: -163 Value for 0 V at AI (0 163) GAIN Multiplicand: 16000 Delta X of gradient (Debit value of gradient) GAIN Divisor: 14451 Delta Y of gradient (Actual value of gradient 14614-163) Reference voltage matching data: OFFSET: 15336 Value at the moment of the comparison of the OFFSET (0% values) GAIN Multiplicand: 00000 Not used GAIN Divisor: 00000 Not used ATTENTION: Matching data for GAIN (100% values) must be already subject to a correction of the reference voltage! Page 16 05.08.2011

AI calculation in the user program C-DIAS ANALOGUE CONVERSION MODULE CAM 011 Read value from ADC Control of plausibility (e.g. break-down of sensor) Correction of reference voltage (if necessary in case of ramp procedure) Value = Value * value of reference voltage from EEPROM / reference voltage value Digital filter (if desired) Standardization of the measurement value Value = (Value + OFFSET) * MULTIPLICAND / DIVISOR (all from EEPROM) Scaling of the measurement value (if desired e.g. 0 16000d to 0 10000mV) Cold terminal compensation (only at thermo elements but not in mv and not in C) Linearization (at temperature sensor, thermo elements and the like) Standardization example: 0.000V amounts at ADC 163d (163 + -163) * 16000 / 14451 = 0 5.000V amounts at ADC 7555d (7389 + -163) *16000 / 14451 = 8000 10.000V amounts at ADC 14614d (14614 + -163) * 16000 / 14451 = 16000 AO matching data (+/-10V) Calculation of matching data e.g.: 8253d amounts 0.000V at analogue output 192d amounts -10.000V at analogue output 16313d amounts +10.000V at analogue output Matching data: OFFSET: 8253 Value for 0V at AO GAIN Multiplicand: 16121 Delta X of gradient (Actual value of gradient 16313-192) GAIN Divisor: 16000 Delta Y of gradient (Debit value of gradient) AO calculation in user program Bring output value to normed sector -10.000V corresponds 8000d 0.000V corresponds 0d +10.000V corresponds +8000d DAC writing Standardization example: 0.000V corresponds 0d amounts at DAC 8253d (0 * 16121 / 16000) + 8253-10.000V corresponds 8000d amounts at DAC 192d (-8000 *16121 / 16000) + 8253 +10.000V corresponds +8000d amounts at DAC 16313d (8000 * 16121 / 16000) + 8253 05.08.2011 Page 17

Check sum calculation of the matching values The check sum is calculated WORD-wise It is calculated from the address following the check sum to the last address of the data block (both inclusive). This means, the length of the data block of the check sum to be calculated = 2 WORD fixed (Identification and length of the data block) + number of the WORD as defined under the length of the data block. Calculation algorithm: 1. Load pointer with address of the matching data L.DI# ABGL (without check sum) ADD.DI 2 2. Calculate length of data block L.CX (DI+0002) (+2 WORD identification and data block length) ADD.CX 2 3. Load check sum with $FFFF L.AX $FFFF 4. Rotate check sum 1 bit to the left into Carry LP ROL.AX 1 5. Add up check sum with current WORD and Carry ADC.AX (DI) 6. Increase pointer on next WORD ADD.DI 2 7. Finished all addresses? NO ---> 4. YES ---> 8. LOOP LP 8. Check sum is ready Page 18 05.08.2011