Protocol interface AK-PI 300

Similar documents
Protocol interface AK-PI 200 REFRIGERATION AND AIR CONDITIONING. Manual

ELECTRONIC CONTROLS & SENSORS. AK-SC255 Fact Sheet Version R Software Software version 02_085

MAKING MODERN LIVING POSSIBLE AK-255 CO 2. Controller On-Site Installation Guide DANFOSS ELECTRONIC CONTROLS & SENSORS

AK-SC255 Fact Sheet & Recommended Accessories List

MCX08M2 Programmable controller

CI-tronic Reversing contactor Type RCI

Refrigeration and Air Conditioning Controls. Technical Leaflet. Monitoring, Control and Alarm System m2 REFRIGERATION AND AIR CONDITIONING

Modulating controlled actuator AME 11

ECL Comfort V a.c. and 24 V a.c.

Data sheet. MCX15B electronic controller MAKING MODERN LIVING POSSIBLE. REFRIGERATION & air CONDITIONING DIVISION. Danfoss Electronics spa

Service Tool AK-ST 500

Programmable controller MCX152V

SonoSelect and SonoSafe energy meters

1 IF-812 or IF-815 Terminal (Slave) 2 Intended Use. 3 Assembly and Installation _V IF-812/IF-815

1 IF-810 or IF-811 Terminal (Slave) 2 Intended Use. 3 Assembly and Installation _V IF-810/IF-811

RXTP ROOM TEMPERATURE

The ECL Apex 20 is operated by means of either a PC or the ECL Apex Web Panel. Temperature input signals are based on Pt 1000 or 0-10 V.

RST ROOM TEMPERATURE TRANSMITTER. Mounting and operating instructions

Capacity controller AK-PC 710. Manual

ENGINEERING TOMORROW. User Guide. BACnet MS/TP Communication with MBS UBR-01 Router. VLT HVAC Drive FC 102 VACON 100 HVAC. vlt-drives.danfoss.

M-Bus Central Unit. Use

PRELIMINARY. USB1 / USB2 USB host interface to read data via memory stick. Bus Out (system bus) For connection to a router

IntesisBox Modbus Server Panasonic

Danfoss Enterprise Manager AK-EM 800

USER MANUAL. Longo programmable controller LPC-2.MC8 Main module. Version 10

MVS RAIL ELECTRONIC FAN SPEED CONTROLLER. Mounting and operating instructions

Access Terminal IF-800

AC 800M for Compact Product Suite Outline of all modules

RXTH DUAL ROOM SENSOR / SWITCH

Wall-/Pipe Mounted Universal Process Indicator

IntesisBox. v.0.1. User Manual Issue Date: 12/2017 r1.3 EN

Installation guide. Data communication link to m2 - LON with EKC - LonWorks

CNVT-USB-RS485 MODBUS TO USB CONVERTER. Operating instructions

Programmable controller MCX06C

Programmable controller Type MCX06C

Installation Guide DEVIlink CC Central Controller

FGC LON System. Technical Specification

C160 Wall-/Pipe Mounted Universal Process Indicator

MCX06C Programmable controller

MODEL: GR8-EM. Communication Adaptor GR8 Series

Appearance Size (mm) Power supply voltage Model (W H D) 100 to 240 VAC K3SC to 240 VAC

Operating Manual. English. Digital-Analog Converter DACON8-UMB.

General information. Display. Supply voltage

Installation and User Guide

General Specifications

General information Engineering with Programming package. Display with display. Supply voltage 24 V DC Yes. Input current

AC 800M Controllers Outline of all modules

General information. Display. Supply voltage. Input current

SonoSelect 10 and SonoSafe 10 energy meters

Capacity controller for small CO2 refrigeration system AK-PC 772A

living connect and Danfoss Link CC wireless thermostat system. Total temperature control from one central point.

General information Engineering with Programming package. Display with display. Supply voltage 24 V DC Yes

General information. Display. Supply voltage. Input current

SonoMeter 30 Ultrasonic energy meter for heating and cooling applications

Capacity controller for small CO2 booster refrigeration system AK-PC 772 REFRIGERATION AND AIR CONDITIONING. Manual

/8 DIN Universal Process Indicator

Gas Controller System DGC-06

living connect and Danfoss Link CC wireless thermostat system. Total temperature control from one central point.

Designed for commercial, residential and industrial applications, guarantee rapid installation with few and easy connections.

Temperature Controller E5C4

Measuring transducers MI4x0 series Programmable transducers for RTD sensors MI450

VMU-MC and VMU-OC. Pulse concentrator. Benefits. Description

LNP-800AGH-24 Series. Features INTRODUCTION DIMENSIONS

Service Tool AK-ST 500

EXD-TEVI Economizer Controller for Tandem Compressors

MODEL: R2K-1 SEN TRONIC AG. R2K Series

PHS Series. PowerHUBB Node - Satellite

F150 Vision Controller with integrated PROFIBUS-DP unit. 9-pin female sub-d connector (RS-485 ProfiBus) Bus termination

Energy Management BUS Adapter Type VMU-B 01

Display. Supply voltage. Input current. Encoder supply. Output current. Power losses. Memory

Fieldgate SFG500. Technical Information. Intelligent Ethernet/PROFIBUS gateway

AK-SM 720 Boolean logic REFRIGERATION AND AIR CONDITIONING. User guide

VLT Line Filter MCC 107 EMC Filter Series VLT Midi Drive FC 280 (K1 K3)

OHIO SEMITRONICS, INC. AC MULTIFUNCTION PROGRAMMABLE TRANSDUCERS & -1000L

General information. Display. Supply voltage. Input current. Encoder supply. Output current

SCS (System Core Server) Model BCY44100M

General information. Display. Supply voltage. Input current

Energy Management BUS Adapter Type VMU-B

Display. Supply voltage. Input current. Encoder supply. Output current. Power losses. Memory

6GK6041-6AT Automation Technology > Industrial Communication > Industrial Ethernet > RUGGEDCOM Serial Device Servers > RUGGEDCOM RS416 managed

IntesisBox PA-AC-MBS-1

Comprehensive User/Group Security Restrict or allow access to myriad of points based on individual or group credentials

Energy Management Energy Transducer Type ET112

BD Controller 101N07xx Series 24 V DC with Tool4Cool LabEdition software Operating Instructions

General information. Display. Supply voltage. Input current. Encoder supply. Output current

M-bus web server. Meters and Energy Cost Allocation WTV676-HB6035

General information. Display. Supply voltage. Input current. Encoder supply. Output current

Energy meters Single phase electrical energy meters WM1-6 / WM1M6

Neon pr. ph/ ORP measurement. Applications. Description

MAKING MODERN LIVING POSSIBLE. Installation Guide. Twin Kit 086L

Danfoss commercial compressors Secop compressors produced for Danfoss Bluetooth Gateway

HPS-M -2 DIFFERENTIAL PRESSURE TRANSMITTER. Mounting and operating instructions

OP10. Pre-programmed, configurable controller for simple applications

6GK6091-0AT Automation Technology > Industrial Communication > Industrial Ethernet > RUGGEDCOM Serial Device Servers > RUGGEDCOM RS910 managed

P3-RS Remote Slave Module

General information. Display. Supply voltage. Input current

IntesisBox Modbus Server - BACnet/IP Client

6 Port Unmanaged Industrial Gigabit Ethernet Switch w/ 4 PoE+ Ports and Voltage Regulation - DIN Rail / Wall-Mountable

General information. Display. Supply voltage. Input current

EZ imarquee Specifications

Transcription:

User Guide Protocol interface AK-PI 300 ADAP-KOOL Refrigeration control systems

Introduction Function The AK-PI 300 is an intermediary link allowing Daikin type controllers to be operated via a System Manager, e.g. AK-SM 720 or similar. The actual operation of the controllers is carried out with an AK-ST 500. Daikin units include data communication, where communication is controlled by a Daikin Comm. box or a Daikin RTD-network. The three units: Outdoor unit, Booster unit and Indoor unit can be connected to the Comm. box and Indoor unit to RTDnetwork. Application The AK-PI 300 is used on systems where the system unit is an AK-SM 720 and where there is/are one or more Daikin type units. AK-PI 300 links communication to Daikin so that the system manager can present all the controllers on the system. Daikin units are presented on an equal footing together with LON RS 485 controllers and MODBUS controllers. All controllers can be viewed and operated from the system manager s network overview. The network list on the right shows two RTD-networks, and an outdoor unit. The outdoor unit is connected via a Comm. box. Principle The link between the system manager and the AK-PI 300 is via a TCP/IP. In this very simple connection the two units can be connected to each other via a crossed cable. This is where the IP addresses are set to static addresses. On larger systems or where there is also outgoing IP communication from the system, the connection must be made via a router. Here the IP addresses can be dynamic, but if there is communication to the system from outside, they must be static. If you are not sure whether you should select static or dynamic, abide by the following recommendation: Dynamic is the easiest. Here the router itself allocates an address for the system manager and another for the PI unit. But you should only select this solution if the system is closed without a connection for an external operation interface. With static you must obtain a couple of addresses yourself at the local IT department and you must also set the addresses yourself in the two units. This solution must always be used when the system is operated by an external service company, e.g. for log collection, alarm management or service. Contents Introduction... 2 Installation... 4 Requirements and terms... 6 Ordering... 8 Data... 8 2 Manual RS8GP102 Danfoss 12-2015 AK-PI 300

Number of Daikin units One Comm. box and three RTD units can be connected to a single AK-PI 300. If there are more, use 2 (x) AK-PI 300 units. Up to two AK-PI-300 units can be connected to a single system manager, i.e. up to 2 Comm. boxes and 6 RTD units. If there are two AK-PI 300 units, the connection to the system manager is led via a router or a switch. (Up to 32 outdoor units, 30 booster units and 64 indoor units can be connected to a single Comm. box. Up to 16 indoor units can be connected to a single RTD unit.) Addresses In principle there are three types of addresses: IP addresses Both the system manager and the AK-PI 300 must have an IP address set. The address can be either dynamic or static the desired value is selected with a setting. If static is chosen, an address must also be set. If the system can be accessed externally, the setting in the system manager AK-SM 720 must always be set to static so that the external connection always recognises the address and can communicate with the unit. (The IP address is set in a menu). Network addresses There must always be one and only one master system manager on a network. This is defined with the address setting = 1. This system manager controls the communication to all the other controllers on the network. The PI unit is perceived as a controller on the network and its address can be viewed in the IP list. (Up to two PI units can be connected to the system manager, which is master - i.e. has address =1) (You set the network address on the front of the system units and on the front of the PI units.) Set the system manager to address 1. If there are several system managers (slave network), set these to addresses 2 to 10. Each PI unit is set with a separate address. Select 12 or higher, e.g. 21. Interconnection When setting the system manager, a menu must also be set in which the relevant AK-PI 300 chooses the network. The system manager then knows the way to the different Daikin units. The system manager must be version 1.20 or later. Controller addresses All controllers on the same network must have different addresses. In other words, all controllers that are connected to a system manager on either: the LON communication the MODBUS communication the DANBUSS communication or Daikin communication. Start with the addresses on Daikin RTD-NET. Then for DANBUSS, if needed (via AK-PI 200). A Daikin Comm. box registers 3 addresses. After this, add the addresses on the Daikin Comm. box connections. (These address numbers can be offset. See next page.) The addresses on the LON and MOD buses can be set higher. No more than 200 controllers can be connected to a system manager. Daikin Outdoor: Address options 1 to 32 Daikin Booster: Address options 1 to 30 Daikin Indoor: Address options 1 to 64 DANBUSS communication: Address options 1 to 120 LON-communication: Address options 1 to 999 MOD-bus communication: Address options 1 to 247 Max. number of controllers: 200 pcs. AK-PI 300 Manual RS8GP102 Danfoss 12-2015 3

Installation Preparing addresses on the Daikin-network Note down which addresses the units have, e.g.: Outdoor = 6 Booster = 1 Indoor = 2 RTD = 9600 These must be adapted in order to prevent these addresses from conflicting with each other and other controller addresses on the network overview. Duplication of addresses is not permitted. Set a value for the Comm. box connections that will increase the address value so as to prevent duplication. E.g. 100, 200 and 300, as shown in the image on the right. The values constitute factory default settings. In the network overview they will subsequently be shown as offset by either: 100 for outdoor (displayed as 106) 200 for booster (displayed as 201) 300 for indoor (displayed as 302). Only via Comm. box Only via Comm. box Only via Comm. box Note The address of Comm. box will take up 3 addresses, the set address and the two subsequent ones. RTD can only run at 9600 baud. Omit indoor units on Comm. box: If an indoor unit is connected to both an RTD and outdoor unit, the scanning of indoor units on the Comm. box can be deselected. Otherwise, they will appear twice in the system. Preparing TCP/IP connection The AK-PI 300 must have a connection to the system manager both physically and with a software setting. This can take place in one of the following ways: 1. Connection a) Direct connection (only used if there is not an external connection via a router). The cable between the two units must be a crossed cable. (A static IP address is always used here.) b) Cables from the units are connected to a router or to a switch. (A dynamic or static IP address is used here.) 2. Setting a) Router - Dynamic: There are no settings in the router - Static: A static address range must be set in the router b) AK-SM 720 - Select static if the connection between the system unit and the AK-PI 300 is with a crossed cable or there is an external connection to the system. Then set the IP address (an IP address must be obtained from the local IT manager). - Select dynamic if it is a closed system and the two units are connected to a router or a switch. c) In the AK-PI 300 the IP address is set either to static or to dynamic. - Select static if the connection between the system unit and the AK-PI 300 is with a crossed cable. Then set the IP address (an IP address must be obtained from the local IT manager). - Select dynamic if it is a closed system and the two units are connected to a router or a switch. 3. If a router or switch is connected, it must be turned on. 1a) 1b) Crossed cable 4 Manual RS8GP102 Danfoss 12-2015 AK-PI 300

Preparing the system manager 1. Set its address on the front to 1 (there must always be a system manager with address 1 on a network (1=master)). If there are several networks and thus several system managers, they must have addresses 2 to 10. 2. Connect the controllers to the two data communications, LON and MODBUS. Switch on the controllers and set an address in each controller. Addresses may not be duplicated not even with addresses on the Daikin-NET, the Comm. box s 3 addresses or the addresses adjusted with an offset. 3. Apply power to the system manager 4. If a static IP address is used, this must be set 5. Enter the system manager's service PIN Preparing the AK-PI 300 1. Set its address on the front (e.g. to 12) (possible range = 11-999) 2. Apply the power 3. If a static IP address is used, this must be set 4. (You can activate the Service PIN function at this point. If you do, this means you do not have to start the scan function in the next point.) Perform the first scan 1. Start the scan function in the system manager wait for the results (the controllers on the LON and MODBUS communication will now be located and visible in the network overview). 2. Go to the next page of the network overview, which details the IP registrations. Check that the AK-PI 300 unit is registered. Interconnection Define which AK-PI 300 unit the system manager should recognise (several units can be registered but the system manager with address 1 can only control two units. 1. There is a menu in the system manager in which settings must be entered. Go to the Setup menu/protocol interface (the system manager must be version 1.20 or later). 2. Select the address of the AK-PI 300, which is to be connected to the system unit. Perform scan number 2 and locate the Daikin units Precondition: Daikin units must be connected to AK-PI 300 on the Modbus terminals. (This output is adapted to the Daikin Modbus Protocol and can only be used for Daikin units.) 1. Perform a new scan of the system manager. Wait for the results. (All controllers will now be located.) Se manualen for systemmanageren for yderligere installation. Daikin units AK-PI 300 Manual RS8GP102 Danfoss 12-2015 5

Requirements and terms Principle The installation of the data communication must be carried out as specified in the guide to the RC8AC. The terminations must be in order. Up to 1 Comm. box + 3 RTD-network units can be connected to a single AK-PI 300 unit. Up to two AK-PI 300 units can be connected to a single system manager. Only addresses on the Comm. box can be offset. Furthermore, address numbers on an RTD-network must not also be address numbers on an AK-SM 720 unit. Network addresses Here is a small summary of the networks and addresses that can occur: 11:001 is the master system manager 11:002 to 11:010 are slave networks controlled by 11:001 (the figure 11 keeps track of the networks and cannot be changed). 11:012 to 11:999 are addresses for units on the network. The units can be AK-PI 300 units or wireless units, or they can be controllers in which the data communication takes place via TCP/IP. 1: xxx will be controllers that are registered under the master system manager. 2: xxx will be controllers that are registered under slave network number 2. A Comm. box registers 3 addresses on the Daikin Modbus network: the one it is set with + the 2 subsequent ones. The units on an RTD-network must not have an address that coincides with these 3 addresses. 6 Manual RS8GP102 Danfoss 12-2015 AK-PI 300

The overview display will show the following: The address of the system manager that AK-PI 300 is connected to The status of the alarm transmission Date and time The quality of the Daikin communication signal The configuration display gives access to the following: The configuration lock is only used if a static IP address is to be set. Under "System setup" you can give the unit a name IP settings can be entered Examples of IP addresses AK-PI 300 Manual RS8GP102 Danfoss 12-2015 7

Ordering Type Function Application Language Code no. AK-PI 300 Protocol interface Intermediary link between system manager and units with Daikin data communication English, German, 080Z8526 Accessories Transformer module 230 V / 115 V to 24 V AK-PS 075 18 VA Supply 080Z0053 Data Supply voltage 24 V a.c. +/- 20% Power consumption AK-PI 300 12 VA Ambient temperature During transport -40 to 70 C During operation -20 to 55 C, 0 to 95% RH (non condensing) No shock influences / vibrations Enclosure Material PC / ABS Enclosure IP10, VBG 4 Approvals Mounting Weight EU low voltage directive and EMC requirements are complied with UL 873, For mounting on wall or DIN rail Approx. 600 g LVD tested according to EN 60730 EMC tested Immunity according to EN 61000-6-2 Emission according to EN 50081-1 UL file number: E166834 Danfoss can accept no responsibility for possible errors in catalogues, brochures and other printed material. Danfoss reserves the right to alter its products without notice. This also applies to products already on order provided that such alternations can be made without subsequential changes being necessary in specifications already agreed. All trademarks in this material are property of the respecitve companies. Danfoss and Danfoss logotype are trademarks of Danfoss A/S. All rights reserved. ADAP-KOOL 8 Manual RS8GP102 Danfoss 12-2015 AK-PI 300