Meter Bus Intelligent Communication
Data Transmission System The M-Bus system (Meter Bus) is a data transmission system for acquiring, evaluating, optimizing and controlling energy and process data (e.g. electricity meter, heat meter, water meter, gas meter, etc).
Applications Power Generation Power Distribution local Power Generator Consumers Hotels, etc. Commercial Industry M-Bus Repeater PSTN (analog) M-Bus UniMod 01/I ISDN (digital) M-Bus M-Bus M-Bus M-Bus UniMod 01/ISDN GSM (900/1800MHz) UniMod GSM4 Communication Network UniMod Radio M-Bus Master RS232 UniMod Ethernet LAN UniMod Ethernet Modem SIGLON RS232 PC Software
M-Bus (Fieldbus) Development since 1992 - University of Padeborn: Prof. Ziegler - Techem (German energy service provider) - Texas Instruments: M-Bus chip TSS721 European standards: - EN 1434 (Heat meters) - EN 13757 (based on EN 61334-4-1 / IEC 60870-5) Structure: - Physical layer: hardware - Logical layer: software, application, data transmission Internet: www.m-bus.com, user group
Features (I) Simple twisted-pair cable (2 wire bus) e.g. telephone cable (J-YSTY 2 x 0.8mm/0.5mm²) Polarity exchangeable Protected against polarity reversal (resistant to short circuits) Integrated power supply for units (optionally: max. 3.3V / 0.6mA per unit) Support of battery-powered units Each segment connects up to 250 units Max. 250 units (meters) / 1000m Max. distance for 1 unit: 10km Large bus segments with repeaters All protocols are possible (IEC62056-21 / IEC1107, IEC60870, VDEW, DLMS, SCTM, Modbus...) Adequate rate of data transmission: 300-38400 Baud (mixed baud rate possible)
Features (II) Possible galvanic isolation (optocoupler) One-chip solution is available Compliance with all standards: EMC, ESD and EMI (CE mark) High safety level of data transmission and immunity to interference Line, star and tree topology
Advantages Low connection and cabling costs No licence costs It supplies the units with power The M-Bus conforms to standards EN 1434 / IEC 60870-5 Development by the M-Bus user group Used for heat, electricity, gas, water Various components can be provided: masters, repeaters, converters Modular structure Data transmission with type, unit, resolution
Segment Configuration The number of terminals (units) that can be connected to a repeater and the structure of the segments within an extended M-Bus system is determined by the type of cable and the baud rate.
M-Bus Lengths per Segment - Examples Sizing Plant type Maximum distance Total cable length Cable diameter Number of M-bus slaves Maximum rate of transmission Small residential building 350 m 1000 m 0.8 mm 250 9,600 Baud Large residential building 350 m 4,000 m 0.8 mm 250 2,400 Baud 64 9,600 Baud Small district 1,000 m 4,000 m 0.8 mm 64 2,400 Baud Medium district 3,000 m 5,000 m 1.5 mm2 64 2,400 Baud Large district 5,000 m 7,000 m 1.5 mm2 16 300 Baud Point to point connection 10,000 m 10,000 m 1.5 mm2 1 300 Baud
Data Transmission
Data Acquisition Hexadecimal: 00 hex to FF hex (corresp. 0 to 255) SND: 10 40 00 40 16 RCV: E5 SND: 68 0B 0B 68 73 FD 52 78 56 34 12 FF FF FF FF D2 16 RCV: E5 SND: 10 7B FD 78 16 RCV: 68 D7 D7 68 08 00 72 78 56 34 12 25 08 25 02 00 04 00 00 84 C0 80 00 06 91 A0 FC 01 C4 C0 80 00 06 91 A0 FC 01 84 C1 80 00 06 91 A0 FC 01 C4 C1 80 00 06 91 A0 FC 01 84 C2 80 00 06 91 A0 FC 01 C4 C2 80 00 06 91 A0 FC 01 84 C3 80 00 06 91 A0 FC 01 84 80 C0 00 06 FF B5 4F 03 C4 80 C0 00 06 FF B5 4F 03 84 81 C0 00 06 FF B5 4F 03 C4 81 C0 00 06 FF B5 4F 03 84 82 C0 00 06 FF B5 4F 03 C4 82 C0 00 06 FF B5 4F 03 84 83 C0 00 06 FF B5 4F 03 84 80 80 00 6D 11 88 05 27 C4 80 80 00 6D 0F 88 05 27 84 81 80 00 6D 2D 87 1D 26 C4 81 80 00 6D 1E 87 1D 26 84 82 80 00 6D 0F 87 1D 26 C4 82 80 00 6D 00 87 1D 26 84 83 80 00 6D 2D 86 1D 26 1F 01 01 01 01 01 15 00 1F 01 51 FA 16 SND: 10 5B FD 58 16 RCV: 68 D7 D7 68 08 00 72 78 56 34 12 25 08 25 02 00 00 00 00 84 C0 80 00 06 91 A0 FC 01 C4 C0 80 00 06 91 A0 FC 01 84 C1 80 00 06 91 A0 FC 01 C4 C1 80 00 06 91 A0 FC 01 84 C2 80 00 06 91 A0 FC 01 C4 C2 80 00 06 91 A0 FC 01 84 C3 80 00 06 91 A0 FC 01 84 80 C0 00 06 FF B5 4F 03 C4...
Telegram Formats
M-Bus Segment M-Bus Master: the control center of an M-Bus system is formed by the M-Bus master. It consists of an M-Bus repeater connected to a normal commercially availably PC (via RS232). M-Bus Repeater: each M-Bus segment is terminated with a repeater and connects up to 250 terminals. Repeaters can be cascaded. M-Bus Converter is used to adapt physically two interfaces and to separate them galvanicly. The following conversions are available: M-Bus RS232 M-Bus RS485 M-Bus CS (20mA) M-Bus Fiber optic
M-Bus Devices M-Bus Master and M-Bus Repeater for up to 250 devices (used for large segments) M-Bus Mini-Master and M-Bus Mini-Repeater for up to 10 or 25 devices (used for small segments) Metcom T X for up to 25 devices (used for medium size segments)
Accessory Units M-Bus LOG: 2 pulse inputs Internal clock Load profile Modems UniMod: GSM, PSTN, ISDN, LAN Modems Metcom T: GSM, PSTN, ISDN, LAN Data Logger: DATAREG DLX DLM6
Application (M-Bus) Heat meter Water meter M-Bus communication 2 wire cable 0.8mm 2 Electricity meter M-Bus Master
Application (M-Bus, pulse) Heat meter Electricity meter (Ferraris) Water meter Electricity meter (digital) Pulse M-Bus LOG M-Bus communication Modem UniMod
Application (M-Bus, RS232, pulse) Heat meter Water meter Electricity meter (digital) Pulse M-Bus LOG RS232 M-Bus communication Modem Metcom T
Software: Siglon (I) Automated acquisition of meter data load profiles or demand values with time setting, counter reset. Client - Server architecture with multi user capability. Each terminal can be customized for each task: meter management, sales, energy supply etc. Multi utility: all energy types can be processed: gas, water, heat or electricity and... Uses standard databases (e.g. MS SQL Server) Rights management for each task (technician, dealer, sales, procurement etc.). Capable of adapting to the processes of a deregulated utility. Export of the data can be easy customized (format, contents, sequence, protocols, communication means). SIGLON helps to manage meters (manufacturer, identification number, serial number, certification period, etc.). Creation and handling of physical and virtual metering points. Future extensions supported by modular design.
Software: Siglon (II)
Software: Siglon (III)