MIC-2 MKII, Multi-instrument DATA SHEET Measurements All 3-phase AC measurements True RMS 4-Quadrant energy Power Quality Analysis Replaces analogue meters RS-485 Modbus RTU protocol TCP/IP Modbus (optional) Profibus DP (optional) I/O modules optional Analogue Input/Output Digital Input/Output Relay Accuracy Multi-instrument only U, I and f class 0.2 Harmonic Class 5 Other values class 0.5 Harmonic accuracy 1 % when MIC-2 MKII FCT and MIC-2 MKII FCT DIN is including flexible current transformer Variants MIC-2 MKII front-mounted MIC-2 MKII DIN-mounted MIC-2 MKII FCT, flexible current transformer input, front-mounted MIC-2 MKII FCT DIN, flexible current transformer input, DIN-mounted Intelligent Suitable for 2 and 3-phase network topologies Installation Compact dimensions Simple wiring Utility software Data logging Remote reading Easy setting up Alarms Up to 16 configurable alarms Document no.: 4921210156C
Application The MIC-2 MKII multi-instrument is a microprocessorbased measuring unit providing measurement of most electrical quantities on a 2- or 3-phase electric energy distribution network. The measurements are shown on the built-in display.*1 MIC-2 MKII can be used as a data logging device for an intelligent Power Distribution System or Plant Automation System. All measurements are monitored and data is available via the RS-485 Modbus port. Other communication types as Ethernet (Web page, TCP/IP Modbus and emails transfer) and Profibus DP are available options. True RMS values are measured with/without neutral and with both balanced and unbalanced load. A large number of standard analogue instruments can be replaced by the MIC-2 MKII in all electrical measuring applications. The MIC-2 MKII contains all necessary measuring circuits and presents all values on a display with white backlight. The display has 4-digits resolution for all measurements. The backlight duration is selectable. *1 Operating the MIC-2 MKII is very easy. It is a flexible and logical measuring unit that enables the user to easily adapt the instrument to individual applications. Password protection of KWh counter reset and change of settings is possible. Measured and calculated values Voltage True RMS each phase, line-to-line voltage and average. Current Each phase, average and neutral. Active power (P) Each phase, total power. Reactive power (Q) Each phase, total power. Apparent power (S) Each phase total power. Power factor Each phase and total power factor. Frequency Actual frequency Load nature Inductive/Capacitive/Resistive. THD (up to 63 rd harmonics) Voltage THD of each phase, current THD of each phase. Maximum Demand Demand of Active (P), Reactive (Q) and Apparent (S) power. Energy counter Import and export of energy, inductive and capacitive of reactive energy. Apparent energy. Energy pulse output (optional) Two ports of pulse output (assign to any energy (P, Q and S) counter. Statistics Max/min of voltage, current, Power (P, Q, S) total, PF total, Frequency, Unbalance factor and THD values with time stamps. Running hour indication. Unbalance factor Voltage and current. Based on the positive and the negative sequence Connection The MIC-2 MKII can be used in 2- and 3-phase network topologies with/without neutral and with both balanced and unbalanced load, including the US split phase system. The voltage and current input wiring modes are set separately in the parameter setting process. Please refer to the wiring diagram section in the MIC-2 MKII Installation Instructions for more details. Options Ethernet - TCP/IP Modbus Profibus DP/VO Input/Output Analogue input (AI) Analogue output (AO) Digital input/output (DI/DO) Relay output (RO) I/O Module DI DO RO AI AO AXM-IO1 6 2 AXM-IO2 4 2 2 AXM-IO3 4 2 2 AXM-IO1 has a 24 V DC power supply for DI. A maximum of 1 communication and 2 input/output modules can be used for each MIC-2 MKII. via RS-485 com port and AXM-NET module. Normal refresh time Modbus 1 sec. Refresh time harmonic values 4 sec. The 100 ms. refresh time Modbus parameter address list is only supported by the RS-485 communication port. Please see the Installations Instructions. *1 Only MIC-2 MKII and MIC-2 MKII FCT DEIF A/S Page 2 of 8
Technical specifications, MIC-2 MKII and MIC-2 MKII DIN Voltage inputs Nominal voltage UN Overload capacity VT primary VT secondary Fuse Current inputs Nominal current IN Overload capacity CT primary CT secondary Load Frequency Nominal frequency fn Measuring point Accuracy Multi-instrument only Voltage 0.2 % Current 0.2 % Power 0.5 % Power factor 0.5 % Frequency 0.2 % Energy 0.5 % Harmonic 5.0 % L- L 480 V AC (cat III) L-L 690 V AC (cat II) 0 to 1.2 x UN 1500 V continuous 3250 V for 1min 220 V to 500 kv 100 V to 400 V 1 A slow blow 5 A AC 0 to 10 A 20 A continuous 100 A for 1 s 5 A to 50 ka 5 A 0.5 VA 50/60 Hz 45 Hz to 65 Hz V1 phase voltage Standard IEC 60051 Auxiliary power supply Universal AC/DC power supply Supply voltage 100 to 240 L-N / +/-10 % 100 to 415 L-L V AC +/-10 % 50/60 Hz 100 300 V DC Data rate 1200 (9600) to 38400 bits/s Environmental conditions Operation temperature -25 to 70 C Storage temperature -40 to 85 C Standard IEC 60068-2-2 IEC 60068-2-1 Humidity, relative Standard Connections Measuring inputs Screw torque Other Wire max. Screw torque Mounting Panel mounted Panel cutout 5-97 % RH condensing IEC 60068-2-6 Db Current input fixed block, wire max. 5 mm² 0.5 Nm/5.5 lb-inch Pluggable block 1.5 mm² 0.25 Nm/2.5 lb-inch Max. 6 mm thick 92 x 92 mm +0.8 mm (3.62 x 3.62 ) or 4 round Protection Front IP52 (EN 60529) Rear IP30 (EN 60529) Safety IEC/EN 61010-1, UL 61010-1 300 V installation cat. III, pollution degree 2 600 V installation cat. II, pollution degree 2 Weight MIC-2 MKII MIC-2 MKII DIN 320 g (0.8 lbs.) 280 g (0.7 lbs.) Consumption Fuse RS-485 Modbus RTU Number of devices Cable type Maximum cable length 5 VA 1 A slow blow Max. 32 units Belden 3105 A or equivalent (twisted pair and shielded) up to 1000 m EMC IEC/EN 61000-6-2 IEC/EN 61000-6-4 Vibration 3 to 13.2 Hz: 2 mmpp 13.2 to 100 Hz: 0.7 g To IEC 60068-2-6 To IACS UR E10 DEIF A/S Page 3 of 8
Technical specifications, MIC-2 MKII FCT and MIC-2 MKII FCT DIN Voltage inputs Nominal voltage UN Overload capacity VT primary VT secondary Fuse L- L 480 V AC (cat III) L-L 690 V AC (cat II) 0 to 1.2 x UN 1500 V continuous 3250 V for 1min 220 V to 500 kv 100 V to 400 V 1 A slow blow FCT, Flexible Current Transformer input 100 mv Only to be used with DEIF accessory flexible current transformer. See Technical Specification, Flexible Current Transformer Frequency Nominal frequency fn Measuring point 50/60 Hz 45 Hz to 65 Hz V1 phase voltage Accuracy Multi-instrument only Voltage 0.2 % Current 0.2 % Power 0.5 % Power factor 0.5 % Frequency 0.2 % Energy 0.5 % Harmonic 1.0 % *3 *3 Harmonic accuracy 1 % when MIC-2 MKII FCT and MIC-2 MKII FCT DIN is including flexible current transformer. Standard IEC 60051 Auxiliary power supply Universal AC/DC power supply Supply voltage 100 to 240 L-N / +/-10 % 100 to 415 L-L V AC +/-10 % 50/60 Hz 100 to 300 V DC Environmental conditions Operation temperature -25 to 70 C Storage temperature -40 to 85 C Standard IEC 60068-2-2 IEC 60068-2-1 Humidity, relative Standard Connections Measuring inputs Screw torque Other Wire max. Screw torque Mounting Panel mounted Panel cut out 5-95 % RH condensing IEC 60068-2-30 Db Current input fixed block, wire max. 5 mm² 0.5 Nm/5.5 lb-inch Pluggable block 1.5 mm² 0.25 Nm/2.5 lb-inch Max. 6 mm thick 92 x 92 mm +0.8 mm (3.62 x 3.62 ) or 4 round Protection Front IP52 (EN 60529) Rear IP30 (EN 60529) Safety IEC/EN 61010-1, UL 61010-1 300 V installation cat. III, pollution degree 2 600 V installation cat. II, pollution degree 2 Weight MIC-2 MKII FCT MIC-2 MKII FCT DIN 320 g (0.8 lbs.) 280 g (0.7 lbs.) Consumption Fuse 5 VA 1 A slow blow EMC IEC/EN 61000-6-2 IEC/EN 61000-6-4 RS-485 Modbus RTU Number of devices Max. 32 units Cable type Belden 3105 A or equivalent (twisted pair and shielded) Maximum cable length up to 1000 m Baud rate 1200 (9600) to 38400 bps Vibration 3 to 13.2 Hz: 2 mmpp 13.2 to 100 Hz: 0.7 g To IEC 60068-2-6 To IACS UR E10 DEIF A/S Page 4 of 8
Technical specifications, FCT - Flexible Current Transformer Flexible Current Transformer Variant FCT1200 FCT3000 FCT6000 5 A 1200 A 12.5 A 3000 A 25 A 6000 A Window size 106 mm 178 mm 271 mm Coil length 400 mm 600 mm 900 mm External diameter 143 mm 207 mm 302 mm Frequency Range Maximum measurements error 20 Hz 5 khz (Coil only) 1 % (of final range value). MIC-2 MKII FCT and MIC-2 MKII FCT DIN including Flexible Current Transformer. Conductor Position sensitivity Influence of external fields Lead Mounting +/- 2 % max +/- 2 % max White-positive, brown-negative, bare-shield must be connected to functional earth; 24AWG Coil to be fastened to the busbar or cable with tie wrap. Wire lead must also be fastened securely. Insulation category Polarity Measuring principle CAT III 1000 V/CAT IV 600 V Arrow towards load (current flow direction). Rogowski 100 mv Operating temperatures -20 C - 70 C Storage temperature -40 C - 70 C Temperature drift +/- 0.07 % within operating temperature range Material Testing voltage Coil diameter Wire lead length Orange thermoplastic rubber, flame retardant UL 94 V-0 rated 7400 V AC @ 50/60 Hz for 1 minute 15.5 mm 2 meters. Extension of wire lead is not approved DEIF A/S Page 5 of 8
Unit dimensions in mm (inches) MIC-2 MKII DIN Panel cutout: H x W = 92 x 92 mm (3.622 x 3.622 ) DEIF A/S Page 6 of 8
Technical specifications optional modules modules Ethernet TCP/IP module AXM-NET 10 M/100 M self-adaptable, RJ45 Jack TCP/IP Modbus protocol, HTTP Web page browse E-mail sending on time interval or on event. Profibus module AXM-PROFI Profibus-DP/V0 Input Byte (typical): 32 bytes Output Byte (typical): 32 bytes EN50170 vol.2 compliance Profibus slave mode, baud rate self-adaptable up to 12M I/O modules AXM-IO1 AXM-IO2 AXM-IO3 6 digital inputs (DI), 2 relay output (RO), 24 V DC isolated voltage output 4 digital inputs (DI), 2 digital outputs (DO), 2 analogue output (AO) 4 digital inputs (DI), 2 relay output (RO), 2 analogue input (AI) Digital Input (DI) Input voltage range 20~160 V AC/DC Input current (max) 2 ma 1 voltage level 15 V 0 voltage level 5 V Switch response time <1 ms Pulse frequency (max) 100 Hz, 50 % duty ratio (5 ms ON and 5 ms OFF) Power supply for digital input (DI) Output voltage 24 V DC Output current 42 ma Load (max) 21 DI Digital Output (DO) (Photo-MOS) Voltage range 0~250 V AC/DC Load current 100 ma (Max) Output frequency 25 Hz, 50 % Duty Ratio (20 ms ON, 20 ms OFF) Isolation voltage 2500 V Relay Output (RO) Switching voltage (max) 250 V AC, 30 V DC Load current 3 A Set time 10 ms (Max) Contact resistance 100 mω (Max) Isolation voltage 2500 V Mechanical life 1.5 x 10 7 Analogue Input (AI) Input range, 0~20 ma/4~20 ma Accuracy 0.2 % Temperature drift 50 ppm/ C typical Isolation voltage 500 V Impedance: 100 Ω Analogue Output (AO) Output range, 0~20 ma/4~20 ma Accuracy 0.5 % Response time 300 ms The max load resistance is 500 Ω Temperature drift 50 ppm/ C typical Isolation voltage 500 V Note: Predefined output, see Option I-O module 4189320032 UK, for more information. Consumption AXM-NET: 1 W AXM-PROFI: 1 W AXM-IO1: 1 W AXM-IO2: 1.3 W AXM-IO3: 0.8 W Environmental conditions Operation temperature -25 to 70 C Storage temperature -40 to85 C Standard IEC 60068-2-2 IEC 60068-2-1 Humidity, relative Standard 5-97 % RH condensing IEC 60068-2-6 Db Safety IEC/EN 61010-1, UL 61010-1 300 V installation cat. III, pollution degree 2 600 V installation cat. II, pollution degree 2 Weight AXM-NET: 65 g AXM-PROFI: 65 g AXM-IO1: 90 g AXM-IO2: 80 g AXM-IO3: 85 g EMC IEC/EN 61000-6-2 IEC/EN 61000-6-4 DEIF A/S Page 7 of 8
Available accessories Type Description Item no. Accessory for MIC-2 MKII Bracket for DIN rail mounting 2232700011 Accessory for MIC-2 MKII FCT & DIN FCT1200 Flexible current transformer 1211029016 Accessory for MIC-2 MKII FCT & DIN FCT3000 Flexible current transformer 1211029017 Accessory for MIC-2 MKII FCT & DIN FCT6000 Flexible current transformer 1211029018 Order specifications Optional modules: MIC-2 Multi - instrument module I/O module 1 I/O module 2 MIC-2 MKII DEIF no. 1211020021 EAN no. 5703727116133 MIC-2 MKII FCT DEIF no. 1211020023 EAN no. 5703727113019 MIC-2 MKII DIN DEIF no. 1211020022 EAN no. 5703727116140 AXM-NET TCP/IP Modbus com. DEIF no. 1211020016 EAN no. 5703727109746 AXM-PROFI PROFI-BUS DP/VO DEIF no. 1211020017 EAN no. 5703727109753 AXM-IO1 DEIF no. 1211020013 EAN no. 5703727109760 AXM-IO2 DEIF no. 1211020014 EAN no. 5703727109777 AXM-IO3 DEIF no. 1211020015 EAN no. 5703727109784 AXM-IO1 (2) DEIF no. 1211020018 EAN no. 5703727110001 AXM-IO2 (2) DEIF no. 1211020019 EAN no. 5703727110018 AXM-IO3 (2) DEIF no. 1211020020 EAN no. 5703727110025 MIC-2 MKII FCT DIN DEIF no. 1211020024 EAN no. 5703727113026 A maximum of 1 communication and 2 input/output modules can be used for each MIC-2 MKII.