Technical Specification Minipower Plus

Similar documents
ALL PSU Ltd ROTATION+ 6kVA - 10kVA PARALLEL ON LINE DOUBLE CONVERSION

Technical Data Sheets Uninterruptible Power Supply LP11 Series UPS kva

PowerWAVE 5000/TP. (10 50 kva) Technical Specification

1PH RACK 19 SINGLE PHASE UPS Rev. 11 SR 6kVA 10kVA

DPA UPSCALE TM RI kw Technical Specifications

Single phase UPS. Applications. Highlights. 1ph from 450 VA to 10 kva. Home Office Computers and peripherals Networks and servers Small data centers

Uninterruptible Power Supplies

UPS. centric Hot scalable modular 3-phase UPS Delivers 25 up to 200 kva/kw INFINITE POWER. Mission Critical Applications

THOR Modular. Modular UPS system. Online double-conversion Scalable Decentralized Parallel. Modular. 10, 20, 30, 40kVA modules kVA systems

Conceptpower DPA TM S kva Technical Specifications

GAMATRONIC, A SolarEdge Division.

Intelligent On-Line UPS

Higher Availability: Self-diagnostics. Automatically tests unit electronics and batteries. Designed to simplify maintenance and troubleshooting.

MAJOR VA Power Inverter

ATS-16 HV USER MANUAL. Automatic Transfer Switch 16A / 230Vac V090318

PowerWAVE (6-10kVA) Technical Specification

SmartOnline SVTX Series 3-Phase 380/400/415V 30kVA 27kW On-Line Double-Conversion UPS, Tower, Extended Run, SNMP Option

Socomec Netys PR RT U P S TOWER / RACK MOUNT

LEVELUPS T3. SERIES kva ONLINE UPS 3:3 PHASE VFI TYPE. Highest Reliability and Robust Protection for Industrial Loads

g GE Power Quality Digital Energy GT Series On-Line, Double Conversion Uninterruptible Power Supply 1000, 1500, 2200, 3000 VA UL-version

Sentinel Dual High Power

Liebert GXT3 5kVA-10kVA UPS Compact UPS Systems For High Power Network Rack Applications. AC Power For Business-Critical Continuity

Keor HPE UPS THREE-PHASE UPS. from 60 to 200 kw GLOBAL SPECIALIST IN ELECTRICAL AND DIGITAL BUILDING INFRASTRUCTURES

UPS TRIFASE kVA Rev. 8 Serie TPH IGBT

Conceptpower DPA TM Technical Specifications

SmartOnline 10kVA On-Line, Double-Conversion UPS, 6U Rack/Tower, 3-Phase input, 1-Phase output

Est ComPower Mini. Compact UPS kva

the Centric 300 An advanced modular UPS up to 1800kVA/kW

Premium Online Series

Evolution 650/650 Rack 1U 850/850 Rack 1U 1150/1150 Rack 1U 1550/1550 Rack 1U Installation and user manual Pulsar Series

Pulsar EXtreme 2000/3000 VA

LEVELUPS T3 3 UPS. SERIES kva ONLINE UPS 3:3 PHASE VFI TYPE. Highest Reliability with Embedded Isolation Transformer

SmartOnline V 10kVA 7kW Online, Double-Conversion UPS, 6U Rack/Tower, Extended Run, Pre-installed SNMP port, RS232, 3 Phase in-single Phase out

Product Snapshot. The Powerware Uninterruptible Power System. Product Focus

PHASE ONE Series 700: Uninterruptible Power Supply (UPS) Systems

1. Introduction External description Front and Rear Panel The LCD screen Alarm Conditions...6

Keor HPE UPS. THREE-PHASE UPS from 60 to 300 kw GLOBAL SPECIALIST IN ELECTRICAL AND DIGITAL BUILDING INFRASTRUCTURES

Est FlexiPower Maxi. Modular UPS kw

UPS Sentry MPS. SENTRY MPS is also compatible with different battery technologies: openvase lead acid and AGM and Gel VRLA, NiCd.

SmartOnline 240/208/120V 8kVA 5.6kW On-Line Double-Conversion UPS, Extended Run, SNMP, Webcard, 4U Rack/Tower, Split-Phase input, Bypass Switch

Powerstar PS3204rm2u True online 2KVA /1800W (19.7 deep)

SmartOnline 208/240V 3kVA 2.4kW Double-Conversion UPS, 3U Rack/Tower, Extended Run, SNMPWEBCARD Option, DB9 Serial

Postfach 2327, Offenburg * Helmholtzstr. 13, Offenburg. Technical Data. Model protecto ER

10 kva 3/1 15 kva 3/1 20 kva 3/1 10 kva 3/3 15 kva 3/3 20 kva 3/3 30 kva 3/3 40 kva 3/3 UOUS SERV WARRANTY

APC Matrix-UPS 3kVA 208V/240V In 120/208/240V Out

RT4F-48V/50A-WAC RECTIFIER

SmartOnline SVX Series 120kVA Modular, Scalable 3-Phase, On-line Double-Conversion 400/230V 50/60Hz UPS System

PowerWAVE 6000 Series kva Technical Specification

UPS Series. features: uninterruptible power supply. what great systems are built on.

Product Specifications

MUST900 Modular UPS. Datacenter & servers. Internet centers. Local Area Networks (LAN) Telecommunication devices. Emergency application

SmartPro LCD 120V 1500VA 900W Line- Interactive UPS, AVR, 2U Rack/Tower, LCD, USB, DB9 Serial, 8 Outlets

UPS Emergency Bed Power Unit

POWERVAR SECURITY PLUS SERIES DETAILED UPS SPECIFICATION (8kVA 10kVA)

SmartOnline 208/120V or 240/120V 16kVA 11.2kW On-Line Double-Conversion UPS, Extended Run, SNMP, Webcard, 8U Rack/Tower, USB, DB9 Serial

SmartOnline SV Series 40kVA Medium-Frame Modular Scalable 3-Phase On-Line Double- Conversion 208/120V 50/60 Hz UPS System, 2 Battery Modules

RT4F-110V/25A RECTIFIER

SmartOnline SV Series 20kVA Small-Frame Modular Scalable 3-Phase On-Line Double- Conversion 208/120V 50/60 Hz UPS System, No SVBM Battery Module

SmartOnline V 3kVA 2.5kW On-Line Double-Conversion UPS, Extended Run, SNMP, Webcard, 2U Rack/Tower, USB, DB9 Serial

TME Modular Series UPS System kva/kw - 208/220 VAC

T2003 uninterruptible power supply. 10kVA to 50kVA

SMARTONLINE E3 UPS SYSTEMS

SmartOnline 120V 3kVA 2.7kW Double- Conversion UPS, 2U Rack/Tower, Extended Run, Network Card Slot, LCD, USB, DB9 Serial

RT4F-120V/20A-WAC RECTIFIER

SmartOnline V 1kVA 800W On-Line Double-Conversion UPS, Extended Run, SNMP, Webcard, 2U Rack/Tower, USB, DB9 Serial

Eaton 9EHD Industrial UPS

SmartOnline Expandable Rack / Tower UPS System Online, double-conversion protection for mission critical applications

SmartOnline V 3kVA 2.7kW On-Line Double-Conversion UPS, Extended Run, SNMP, Webcard, 3U Rack, LCD display, USB, DB9 Serial

MASTERELITE MULTITEC MRM/MRT MRM 10-20kVA single/single phase or three/single phase MRT 10-30kVA three/three phase

SmartOnline V 3kVA 2.7kW On-Line Double-Conversion UPS, Extended Run, SNMP, Webcard, 2U Rack, LCD display, USB, DB9 Serial

SmartOnline 120V 2.2kVA 1.6kW Double- Conversion UPS, 2U Rack/Tower, Extended Run, Network Card Slot, USB, DB9 Serial

RT12-240V/2.4kW Rectifier Specification

Emerson Network Power provides customers with technical support. Users may contact the nearest Emerson local sales office or service center.

SmartOnline SVX Series 90kVA 400/230V 50/60Hz Modular Scalable 3-Phase On-Line Double- Conversion Medium-Frame UPS System, 5 Battery Modules

Liebert GXT4 UPS, 5kVA-10kVA Intelligent, Reliable UPS Protection

3 Uninterruptible Power Systems

SmartOnline 208/230V 1kVA 900W Double- Conversion UPS, 2U, Extended Run, SNMP Card Option, LCD, USB, DB9, ENERGY STAR

U P S USER S MANUAL IMPORTANT SAFETY INSTRUCTIONS SAVE THESE INSTRUCTIONS. Uninterruptible Power System. Line Interactive (Network) UPS

APC Symmetra LX. GUIDE SPECIFICATIONS FOR 4kVA-16kVA Uninterruptible Power System

SmartOnline 120V 3kVA 2.7kW Double- Conversion UPS, 3U Rack/Tower, Extended Run, WEBCARDLX Network Interface, LCD, USB, DB9

MODULAR UPS SYSTEM KVA

Installation and user manual English Français Deutsch Italiano Español Nederlands Pulsar Series

MODULYS GP Unique, fully modular and redundant solution Green Power 2.0 range from 25 to 600 kva/kw

Single phase UPS. Applications. Highlights. 1ph from 450 VA to 10kVA

Distributed by. Keor T UPS THREE-PHASE UPS. from 10 to 120 kva GLOBAL SPECIALIST IN ELECTRICAL AND DIGITAL BUILDING INFRASTRUCTURES

SmartOnline 230V 2kVA 1800W On-Line Double- Conversion UPS, Tower, Extended Run, Network Card Options, LCD, USB, DB9

SmartOnline 120V 1.5kVA 1.2kW Double- Conversion UPS, 2U Rack/Tower, Extended Run, Network Card Options, USB, DB9 Serial

SmartOnline 208/240 & 120V 20kVA 18kW, Double-Conversion UPS, N+1, 14U, Network Card Slot, USB, DB9, Bypass Switch

Modular UPS S KVA

OmniSmart 1500VA 2U Rack/Tower Line-Interactive 120V UPS with LCD display and USB port

SmartPro 120V 1.5kVA 1.35kW Line-Interactive Sine Wave UPS, 2U Rack/Tower, WEBCARDLX Network Interface, LCD, USB, 8 Outlets

APC Easy UPS 1 Ph Online Rack Mount Models

Liebert GXT MT kva

IMPORTANT SAFETY INSTRUCTIONS SAVE THESE INSTRUCTIONS

Powerware 9120 UPS. Product Snapshot. Features

Symmetra LX APC Symmetra LX 8kVA Scalable to 16kVA N+1 Rack-mount, 208/240V Input, 208/240V and 120V Output

AIS 3000 APC AIS kVA 400V w/3 Batt. Modules Exp. To 4, Start-Up 5X8, Internal Maintenance Bypass

SmartOnline 6kVA On-Line Double-Conversion UPS, 6U Rack/Tower, V Hardwire output

SmartPro LCD 120V 1200VA 700W Line- Interactive UPS, AVR, 2U Rack/Tower, LCD, USB, DB9 Serial, 8 Outlets

3 Uninterruptible Power Systems

Transcription:

Technical Specification Minipower Plus Pioneering solutions for total power protection

MINIpowerUPS SYSTEM DESCRIPTION Using a unique modular construction, the MINIpowerUPS model range represents a completely new generation of low power single-phase UPS systems that incorporate the latest technological developments in power engineering. High reliability, upgrade ability, low operating costs and excellent electrical performance are just some of the highlights of this innovative UPS solution. This system s advanced double conversion Voltage and Frequency Independent (VFI) topology fully satisfies the highest availability and environmentally-friendly requirements compliant with the most stringent safety, EMC and other important UPS standards. It is certified to International Standard ISO 9001/EN 29001 and ISO 14001. The MINIpowerUPS is a truly modular system based on 1250VA power modules. Depending on the model, the MINIpowerUPS cabinet can contain up to four or eight power modules operating in parallel to provide a 5kVA or 10kVA rated UPS system. MINIpowerUPS 5000 model range The MINIpowerUPS 5000 is available in both Rack-mounted and Tower versions and uses up to four 1250VA power modules to offer a system output rating of 1250VA, 2500VA, 3750VA or 5000VA. Each power module requires three batteries which are housed within the UPS cabinet to provide a completely selfcontained UPS system. An optional external battery cabinet can be connected to the UPS to extend the system s autonomy time if required. MINIpowerUPS 10000 model range The MINIpowerUPS 10000 is available in a tower version only and uses between four and eight 1250VA power modules to offer a system output of 5000VA, 6250VA, 7500VA, 8750VA or 10000VA. In this model range the batteries are contained in a separate battery cabinet which is similar in design and appearance to the UPS cabinet and is usually positioned adjacent to the UPS cabinet to form a matching suite. If required, additional battery cabinets can be connected to the existing battery cabinet to extend the system s autonomy time. System expansion Thanks to the advanced MINIpowerUPS system design, if a cabinet is not fully populated with power modules when purchased, additional modules and batteries can be added at a later time to expand the system up to its full capacity as required. Where increased autonomy is required several battery cabinets (up to 10) can be piggy-backed onto the basic system using a simple daisy chained inter-cabinet power cables. KEY FEATURES Compact size, small foot print Easy to replace UPS power modules Flexible battery management High efficiency Low power factor at partial and full load (p.f.>0.99 @20% load) Blade-server-friendly power; full power from 0.9 lead to 0.8 lag Ergonomic design Technology Synchronised Bypass Computer Interface Remote Control Integral batteries, saving on expensive floor space Cost effective upgrading and reduced downtime for repair Advanced management of battery charging and preventive failure diagnostics avoids premature deterioration of battery life. Up to 92% ac-ac efficiency at 100% load Cost savings during installation and the entire life cycle (TCO) No de-rating required with leading PF loads Easy serviceability PWM high frequency both for input stage and output stage. Microprocessor control logic. Automatic static and manual (optional). Intervenes in case of overload and operating anomaly. Standard serial RS232 for interfacing with personal computer using diagnostics software. Optional scheduling of UPS switch ON/OFF and display of main UPS signals. 2 335-02-00 MINIpowerUPS Technical Specification Dated 05/08/14

GENERAL SPECIFICATIONS This Technical Specification provides detailed information concerning the mechanical, electrical and environmental performance of the MINIpowerUPS intended to support and give answers to tender and end-user requirements. Mechanical Characteristics MINIpowerUPS 5000 MINIpowerUPS 10000 Configuration accommodates Up to four 1250VA power modules Up to 12V, 9Ah batteries (3 per module) Between four and eight 1250VA power modules Up to 24, 9Ah batteries (3 per module) housed in matching battery cabinet Cabinet type Tower or 19 inch rack mounted Tower cabinet only Size (mm) (WxDxH) Tower: 270 x 475 x 570 270 x 475 x 570 x 2 cabinets 19" Rack: 483.5 x 266 x 600 (6U) Weight UPS Cabinet (Kg.) 23.5 34 43 53 24+50 26.5 29 31.5 34 Weight Battery Cabinet (Kg.) 50 57.5 65 72.5 380 Electrical Input MINIpowerUPS 5000 MINIpowerUPS 10000 Nominal Input Voltage 230V Input Voltage Range 184V to 264V with nominal load 100V to 264V with 50% nominal load Frequency 50 or 60Hz ± 2% auto-sensing and/or selected by operator Current (Nom.) 4.6A 8.9A 13.2A 17.7A 17.7A 22.4A 26.9A 31.25A 36.6A Current (Max.) 5.75A 11.2A 16.6A 22.2A 22.2A 27.8A 33.25A 38.9A 44.5A Current Distortion <3% THD Power Factor > 0.99 at 20% nominal load Inrush Current 100% of nominal current Phases Single Line Fuse 25AF 32 + 32 AFF Battery Charger 0.8A rms (direct from mains) Output Waveform MINIpowerUPS 5000 MINIpowerUPS 10000 Mains Operation Battery Operation Topology Sine wave Sine wave No break, on line UPS with passing neutral and double conversion 335-02-00 MINIpowerUPS Technical Specification Dated 05/08/14 3

Output Characteristics MINIpowerUPS 5000 MINIpowerUPS 10000 (Operating on mains) Nominal Output Voltage 230 V ± 1% Nominal Output frequency 50 Hz / 60Hz synchronised (auto-sensing and/or as selected by operator) Output Current with linear load and 0.7 pf (A rms) 5.37 10.75 16.25 21.6 21.6 27.2 32.6 38 43.5 Crest Factor 3.5 Output VA 1250 2500 3750 5000 5000 6250 7500 8750 10000 Output W with 0.7 pf linear/non-linear load 875 1750 2625 3500 3500 4375 5250 6125 7000 THD Overload Capacity Phases AC-AC conversion efficiency with linear load pf=1 and charged batteries < 0.5% with nominal load and < 1% with 0.7 pf nominal non-linear load 300% for 1s, 200% for 5s and 150% for 30s without By-pass intervention Single 80% with 50% load 85% with 75% load 92% with 100% load Output Characteristics MINIpowerUPS 5000 MINIpowerUPS 10000 (Operating on battery) Nominal Output Voltage 230 V ± 1% Nominal Output frequency 50 Hz / 60Hz synchronised (auto-sensing and/or as selected by operator) Output VA 1250 2500 3750 5000 5000 6250 7500 8750 10000 Output W with 0.7 pf linear/non-linear load 875 1750 2625 3500 3500 4375 5250 6125 7000 THD < 1% Overload Capacity 160% for 15s Allowable load pf 0.7-1.0 DC-AC conversion efficiency 80% efficient with loads from 50% to 100% (with linear load pf=1 and charged batteries) WARNING: There is a danger of explosion should the batteries be replaced with the wrong type. Dispose of used batteries as per the instructions and precautions detailed on the battery label. Battery Operation MINIpowerUPS 5000 1250 2500 3750 5000 Percentage load 50 80 100 50 80 100 50 80 100 50 80 100 *Standard autonomy (min) 20 11 8 20 11 8 20 11 8 20 11 8 Recharge time to 90% charge 5-6 hours according to level of discharge Battery specifications 3 x 12V 9Ah, sealed, lead-acid, maintenance free batteries connected in series for each power module Reserve signals 32.2 V to 36V, programmable Minimum voltage for battery 27V to 31.5V with automatic selection depending on applied load, or as programmed by operator. operation during discharge Average battery life 3-6 years according to use and working temperature. The UPS batteries are subject to a reduction in capacity depending on their age. For example, the reduction of capacity of a 4-year-old battery can be as much as 40%, resulting in a proportional reduction of UPS autonomy time when running on battery power. *Approximate autonomy in minutes with fully charged batteries 4 335-02-00 MINIpowerUPS Technical Specification Dated 05/08/14

Battery MINIpowerUPS 10000 Operation 5000/2 6250/2 7500/2 8750/2 10000/2 Percentage load 50 80 100 50 80 100 50 80 100 50 80 100 50 80 100 *Standard Autonomy 20 11 8 20 11 8 20 11 8 20 11 8 20 11 8 Recharge time to 5-6 hours according to level of discharge 90% charge Battery specifications Reserve signals Minimum voltage for battery operation during discharge 3 x 12V 9Ah, sealed, lead-acid, maintenance free batteries connected in series for each power module 32.2 V to 36V, programmable 27V to 31.5V with automatic selection depending on applied load, or as programmed by operator. Average battery life 3-6 years according to use and working temperature The UPS batteries are subject to a reduction in capacity depending on their age. For example, the reduction of capacity of a 4-year-old battery can be as much as 40%, resulting in a proportional reduction of UPS autonomy time when running on battery power. *Approximate autonomy in minutes with fully charged batteries Bypass Operation Type Switchover time MINIpowerUPS 5000 MINIpowerUPS 10000 Static and electromechanical Zero Reference MINIpowerUPS 5000 MINIpowerUPS 10000 Standards Safety Conforms to standard EN 62040-1-1 Electromagnetic compatibility Immunity: Conforms to standard EN 50091-2 (class A) Emissions: Conforms to standard EN 50091-2 (class B) Typical Performance Conforms to standard EN 62040-3 Communication Options Power Management Display (PMD) RS232 Comms Port on 9-pin D-type connector Customer Interface (Logic level output) on 9-pin and 15-pin D-type connectors LCD display showing operating and alarm status (with event history) For monitoring integration in network management and service Environmental MINIpowerUPS 5000 MINIpowerUPS 10000 Storage Altitude Storage Temperature Operating Temperature Relative Humidity Protection Audible Noise 10.000 metres -20 C to +50 C 0 C to +40 C 20-80% non-condensing IP 21 (IEC529) < 40dBA at 1 metre 335-02-00 MINIpowerUPS Technical Specification Dated 05/08/14 5

POWER MANAGEMENT DISPLAY (PMD) The user-friendly control panel comprises three areas: Alpha-numeric LCD Display Normally provides indication of the UPS operating mode together with the input/output supply parameters and the battery state of charge (SOC). It can also display error messages and UPS set-up data via the control menuing system Operator Keypad Provides keys to navigate through the UPS control menu system together with an ON/OFF button. Operating status indicator The area behind the mimic diagram is illuminated by a multi-coloured led to indicate the UPS operating status. Alpha-numeric LCD Display Panel A multi-function LCD Display provides a simple communications interface that enables the operator to monitor important UPS operating parameters and alarm warnings. It also allows the operator to undertake various control operations such transferring the load between the inverter and bypass. The display is menu-driven using the UP/DOWN and ENTER buttons. UPS On Mains Normal operating status when the input mains voltage is present. On Battery There is no mains power and the UPS is running on its batteries. On By-pass The UPS internal bypass circuit has been turned on and the UPS output is connected directly to the UPS input mains supply. IN xxxv Indicates the UPS input voltage and the RMS power (W) taken from the mains. This indication is not displayed during battery operation. OUT xxxv/x,xkw (xx%) Indicates the output voltage and power. The power is shown in kw and also as the percentage of the total power that the UPS is able to supply. Batt. xx,x Indicates the battery state of charge in a bar graph format together with a numerical indication of the available autonomy time (in minutes). 6 335-02-00 MINIpowerUPS Technical Specification Dated 05/08/14

LCD Display Panel summary: Displays the input and output voltage, current, frequency and power Displays an Event register which stores a date/time stamped history of the 99 most recent alarms and events Enables battery run time monitoring Enables selection of commands such as UPS Start-up and Shut-down, Load transfer from inverter to bypass and vice-versa Provides diagnostic facilities (service mode only) In conjunction with the operator keys, provides UPS adjustments and functional testing facilities (service mode only) Operator Keypad ESCape Key Exit a function without modifying it Go up one menu level Exit the main menu and return to the status display Silence the buzzer SCROLL UP Key Select previous function Increase a value Select a new item within the function (e.g. go from DISABLED to ENABLED) SCROLL DOWN Key Select next function Reduce a value Select a new item within the function (e.g. go from ENABLED to DISABLED) ENTER (SELECT) Key Confirm a value Access an item in the menu Go down a menu level ON/OFF UPS ON/OFF pushbutton 335-02-00 MINIpowerUPS Technical Specification Dated 05/08/14 7

COMMUNICATIONS OPTIONS Three D-type connectors are fitted on the UPS back panel to facilitate connection to a range of external communication options. The RS232 Interface can be connected to various shutdown and monitoring software applications whereas the Logic Level interfaces are generally used to drive a more simplified remote alarms monitor panel. Shutdown and monitoring Software RS232 Interface Remote Control and Logic Level Interface Four monitoring systems are available for use with the MINIpowerUPS UPS system: WAVEMON can be used for monitoring and automatic shutdown SNMP can be used for monitoring only PowerREPORTER can be used to automatically email UPS monitored parameters and alarm events to Uninterruptible Power Supplies Ltd. for appropriate response RELAY INTERFACE BOARD provides volt free contacts for connecting to a remote alarm monitor WAVEMON UPS monitoring software WAVEMON is designed to operate with many of the Uninterruptible Power Supplies Ltd. UPS systems and features both monitoring and automatic server/ups shutdown facilities. The system comprises a bespoke software package which is installed on a local PC and communicates with the UPS over a standard RS232 cable connected to the RS232 port on the UPS back panel. The interconnecting RS232 cable can be up to 15m in length and may be connected/disconnected whilst the UPS is running. The main characteristics of WAVEMON are: On-screen autonomy time/battery time countdown On-screen server log off and shutdown procedure Time and date stamp event log Extensive logging of all UPS activity and power quality data Allow alarm warnings to be monitored remotely via email Scheduled UPS service mode and other systems status Graphical user interface for Windows-compatible platforms Automatic unattended local shutdown Special modules for MS-Office software to close and save open documents Compatible with all optional modules like UPSDIALER, SNMP adaptors, temperature sensors, etc. SNMP ADAPTER for network management/remote monitoring Simple Network Management Protocol (SNMP) is a world-wide standardised communication protocol that can be used to monitor any network-connected device via a simple control language. The monitored results are displayed in a web browser. When this facility is used in conjunction with the MINIpowerUPS, an external SNMP adapter is used which is connected to the RS232 connector on the UPS back panel. The SNMP adapter is then connected to the network by means of a standard RJ-45 terminated Ethernet connector, and the UPS-Management software agent installed in the SNMP adapter monitors the UPS operating parameters and outputs its data in SNMP format to the connected network. 8 335-02-00 MINIpowerUPS Technical Specification Dated 05/08/14

UPS Ethernet Terminal External SNMP Adapter The external SNMP adapter is enclosed in a small box which must be powered from a backed-up supply supported by the UPS output so that its power is maintained in the event of a mains failure. A suitable plug-top power supply is included with the option kit. Note: It is the customer s responsibility to provide a suitable, backed-up mains supply for the adapter. In order to use this adapter the operating system you are using must be SNMP-compatible. We offer our software with SNMP functionality together with NetWare, OS/2, all Windows NT systems on INTEL and ALPHA. The SNMP adapter requires a PC with terminal connections and, for normal operation, at least one Ethernet network connection. PowerREPORTER management software PowerREPORTER is a remote monitoring and management service which is a part of the premium power protection concept. ThePowerREPORTER application: Provides affordable, continuous monitoring over mission-critical facilities and offers peace-of-mind by detecting and warning of any potential system problems before they become a crisis. I Acquires key performance parameters and productivity information in real-time to enable you to better understand machine performance and faster troubleshoot downtime events Gives total transparent information concerning all actions performed on the system, such as all critical status changes, coordination of equipment service, reporting of all alarms with priorities Key features Redundant and secure communication Alarm acknowledgment Priority driven Management (with escalation) Comprehensive management system Reception and management of alarm calls from UPS Storage of UPS Data in a database exportable in a CSV-format for easy handling in Excel Unlimited number of UPS that can be managed User administration with passwords and permission-level Administration of Log file Data logging with statistical analysis and diagnostics, report Visualization of the UPS data Current status Measured values for single or three phase Recording function including graphs with zooming capabilities for selected measured values Display of event log file Display of UPS Parameters Web Server functionality, for data access from any Web Browser 335-02-00 MINIpowerUPS Technical Specification Dated 05/08/14 9

Logic Level Interface The outputs from the Logic Level Interface (9-pin and 15-pin) connectors are normally used to drive a basic remote alarms panel. The available output signals are shown below: 9-pin 15-pin 1 5 Input ON/OFF (Max. voltage +15V, equivalent to the ON/OFF button on the front control panel) 2 4 +15V (max 30mA) 3 3 AUTONOMY RESERVE (active high 15V, max 5mA) 4 2 UPS RUN ON BATTERY (active high 15V, max 5mA) 5 1 GND (common) 6 15 GENERAL ALARM (Open collector active low, max 50mA) 7 14 AUTONOMY RESERVE (Open collector active-low, max 50mA) 8 GND (common) 9 12 UPS RUN ON BATTERY (Open collector active-low, max 50mA) 7 OVERLOAD (Open collector active-low, max 50mA) Relay Interface Board An optional Relay Interface Board is available to act as an interface between the UPS and a remote alarms panel. This option contains three changeover relays that are controlled by the UPS Logic Level outputs to provide volt free signalling to the remote panel. The board is contained in an ABS box which is fitted to the UPS back panel and connected to the 9-pin D-type connector on the back of the UPS by means of the supplied 0.6m ribbon cable. The board s outputs can be wired to provide indication of: UPS on Mains UPS on Battery General UPS fault detected Low battery (UPS has been operating on battery power and the remaining autonomy time is low.) Note: All relay contacts are rated at 150Vdc / 125Vac and 1A. INSTALLATION PLANNING The following guidelines should be taken into account when planning a suitable UPS location and environment. Location considerations summary The UPS equipment must be installed and transported in a upright position. The floor at the installed location and en-route from the off-loading point must be able to safely take the weight of the UPS and battery equipment. The floor material where the UPS is to be located should be non-flammable. Local fire protection standards must be respected. The location must be vibration free. Environmental considerations summary Ensure the humidity (< 90% non-condensing) and temperature (+15 C to +25 C) are within prescribed limits. An ambient temperature of 20 C is recommended to achieve a long battery life. Any prescribed air cooling flow must be available. Ensure the air conditioning system can provide a sufficient amount of air cooling to keep the room at, or below, the maximum desired temperature. Ensure no dust or corrosive/explosive gases are present. 10 335-02-00 MINIpowerUPS Technical Specification Dated 05/08/14

CLEARANCES Tower cabinets The MINIpowerUPS 5000/10000 UPS Tower cabinet is compact and mounted on wheeled castors so that it can be easily moved to its intended operating location. As shown in the illustration alongside, the UPS and battery cabinets require a minimum of 200 mm clearance at the rear and either side to permit adequate cooling airflow. However, in each case full rear access is required for cabling, and side access is necessary for maintenance and repair. For this reason it is recommended that the cabinets are located so that they can be wheeled forward to provide the necessary side and rear access when required. X BATT. CAB. Front Y* V UPS Front Y* X This recommendation must be taken into consideration when cabling the equipment so that a sufficient cable length is provided to allow for the prescribed cabinet movement. A space of 900 mm is shown at the front of the cabinets. This allows adequate room for the safe passage of personnel during normal operation and also sufficient space for the cabinets to be pulled forward for access, as described above. Ensure that the cabinet is located in an area where the ventilation grills are unlikely to be accidentally covered. Access Space V 200 mm X 200 mm Y* 200 mm Z 900 mm Z Rack-mounted cabinets The MINIpowerUPS Rack-mounted cabinet is designed to fit into a standard 19 inch rack and is 6U high. The cabinet is fitted through the front of the rack, supported on suitable rails and secured in position by means of two screws on each side of the front of the assembly. All MINIpowerUPS 5000 Rack-mounted UPS cabinets contain the UPS batteries; however a matching rack-mounted battery cabinet is available if an extended battery facility is required. Where used, the separate battery cabinet (also 6U) and UPS cabinet should preferably be fitted in the same rack and positioned immediately adjacent to each other. Due to the weight of the assembly it is usual to mount the UPS cabinet in the bottom of the rack and the optional battery cabinet (where used) mounted immediately above it. There is no minimum space requirement above or below the UPS cabinet when it is in-situ, but a minimum of 200mm must be provided at the rear of the unit to allow for adequate cooling air flow and facilitate cabling. As the UPS cabinet is 600mm deep this implies a minimum rack depth of 800mm. As rear access is required for cabling, sufficient space should be provided behind the rack to permit easy passage recommended 900mm. A similar space is required at the front of the rack to enable the UPS cabinet to be handled while it is being installed. Z Y 19" Rack UPS Front Access Space X 900 mm Y 200 mm Z 900 mm X 335-02-00 MINIpowerUPS Technical Specification Dated 05/08/14 11

UPS POWER CABLING The UPS input and output cables are fitted to a single power connector that plugs into a receptacle located on the rear of the UPS cabinet. A ready-cabled connector of approximately 600mm in length, and terminated with an input plug and outlet socket suitable for the UPS capacity rating, is provided with the equipment. Where a separate battery cabinet is employed a purpose-made cable is also supplied suitable for connecting the battery cabinet to the UPS. Note: The UPS must be installed to prescribed IEC or local regulations (e.g. BS7671:2008). Extended battery cabinet connections Additional battery cabinets can be connected to the UPS system to further extend the available autonomy time. Where an extended battery cabinet is used, the standard cabinet inter-connect cables are replaced by splitter cables that can be effectively daisy chained to connect any number of cabinets together. When several cabinets are connected as shown, the battery charger within the UPS cabinet may inadequate to fully charge all the additional batteries. In this case an independent battery charger is fitted to each extended battery cabinet which must be connected to a mains supply using a standard IEC power cord. A C A B B Standard cable Splitter cable UPS Cabinet Batt. Cab. 1 Batt. Cab. 2 Batt. Cab. 3 Maintenance bypass option A Maintenance Bypass option is available which allows the load equipment to be powered from the raw mains supply when the UPS is totally powered down. Where the option is used, the Maintenance Bypass switch is built into the UPS power connector and requires no modification to the UPS. When the Maintenance Bypass switch is closed, the UPS power connector can be disconnected from the UPS whilst maintaining the (raw) load supply. This allows the completed UPS cabinet to be swapped out for repair if required without disturbing the load supply. 12 335-02-00 MINIpowerUPS Technical Specification Dated 05/08/14