Transformer Protection and Control RET630 Numerical transformer protection in medium voltage networks

Similar documents
Numerical motor protection in medium voltage networks Motor Protection and Control REM620

Relion 615 series Transformer Protection and Control RET615 Ver. 2.0 Technical Presentation

Substation Automation Products. Generator protection REG670/650 Relion 670 and 650 series

TWO-WINDING TRANSFORMER DIFFERENTIAL

Substation Automation Products. Transformer protection RET670/650 Relion 670 and 650 series

Substation Automation Products. Line differential protection RED670 Relion 670 series

Relion 615 series Line Differential Protection and Control RED615 Ver. 2.0 Technical Presentation

PROTECTION, AUTOMATION & CONTROL

Content REF615 Technical Presentation

Relion 615 series Feeder Protection and Control REF615 Ver. 2.0 Technical Presentation

Substation Automation Products. Bay control REC670/650 Relion 670 and 650 series

MiCOM P521. Fast feeder differential protection

Substation Automation Products. High impedance differential busbar protection REB650 Relion 650 series

MiCOM P521. Fast Feeder Differential Protection

Protection relays.

Directional or Non-Directional Earth-Fault Relay REJ 527. Product Guide

Relion 605 series. Self-powered feeder protection REJ603 Product Guide

MiCOM P122C Time-Overcurrent Protection

RELAYABLE POWER. AQ 200 series protection, control, measurement and monitoring IEDs

SR489 SR489. Generator Management Relay. Economical protection, metering, and monitoring functions for small and medium sized generators.

DTRV-EP. COMPLEX DIGITAL PROTECTION FOR 120 kv / MEDIUM VOLTAGE TRANSFORMERS. Application field

Bus Bar Protection Relay B-PRO 4000

Substation Automation Products. Line distance protection REL670/650 Relion 670 and 650 series

MiCOM P521. Fast Feeder Differential Protection. Protection Relays. MiCOM P521 CUSTOMER BENEFITS

Siprotec 7ST61 / 7ST63

DIGITAL RELAY OF PROTECTION AND AUTOMATION SERIES PC83 AND PC830

Voltage regulator. SPAU 341 C 1MRS MBG Issued: July 1998 Status: Revised Version: C/ Data subject to change without notice

GE Multilin 350 Feeder Protection Relay Specifications

A low-cost, economical solution for distribution feeder protection

RELAYABLE POWER. AQ 200 series protection, control, measurement and monitoring IEDs

Sensitive definite time or inverse time earth-fault stage for back-up residual earthfault

RELAYABLE POWER. AQ-200 series protection, control, measurement and monitoring IEDs

Recloser Controller for feeder protection and automation siemens.com/distribution-automation

DGSZV-EP DIGITAL GALVANIC LONGITUDINAL DIFFERENTIAL PROTECTION. Application field

Perfect protection smallest space

High-speed transformer differential protection for up to five terminals

Earth-fault Relay SPAJ 110 C. Product Guide

MiCOM P124 T&D. Self and Dual Powered Overcurrent Relays

Combined Overcurrent and Earth-fault Relay SPAJ 140 C. Product Guide

SIPROTEC 7SC80 Feeder Protection and Automation Answers for infrastructure and cities.

INTRODUCTION. The PL-50 MO and PM-250 families represent the. PM-250-H: Horizontal box. PM-250-V: Vertical box

Relion 615 series. Voltage Protection and Control REU615 Product Guide

MiCOM Agile P642, P643, P645

Transformer Protection Relay

Feeder protection relay SPAA 121 C. Product Guide

GRT100 FEATURES APPLICATION

High Impedance Protection Relay SPAE010, SPAE011. Product Guide

Feeder Protection Relay REF 610. Product Guide

MiCOM P124. Self and Dual Powered Overcurrent Relays. Protection Relays

Three phase and earth fault overcurrent relays

Advanced Line Differential Protection, Automation, and Control System. Combine subcycle line protection with traveling-wave fault locating

MiCOM P220, P225 and P226C

Feeder Protection REF615 Ver Technical Presentation. ABB Oy Distribution Automation. Prashant Ganoo Regional Product Marketing Manager

S o m e t h i n g b e t t e r t h a n p r o t e c t i v e r e l a y s. automation, control & communication

SYMAP R Plug in Variants FI, MI, 87M, TI Technical data

NPW800R RETROFITTING. Power and Volatge Protection Relay

MiCOM P721 & P723. Numerical High Impedance Differential Relay. Protection Relays. Customer Benefits

ELG4125: System Protection

Combined Overcurrent and Earth-fault Relay SPAJ 141 C. Product Guide

F6150. Power System Simulator For Testing Protection Relays and Schemes.

Relion 630 series. Load-shedding controller PML630 High performing load-shedding solution for industrial and utility power networks

WiAutoLink Frequently Asked Questions

Overcurrent and Arc Protection by Reyrolle Alexander Erokhin. 21, 2017 I Berlin

ACOS 300. Reliable protection for network and constructions in medium- and high voltage

Electrical Integration with Smart Communication

REL52002 Easergy P3U30, 4L, 4U, 16DI/8DO, Uaux: V, DI: V, RS-485

Residual overvoltage relay

MiCOM Agile P746. Grid Solutions. Key Benefits. Numerical Busbar Protection. A Combination of Speed, Security and Selectivity. About MiCOM P40 Agile

Sensitive Earth-fault Relay SPAJ 111 C. Product Guide

Advanced distribution feeder solution with integrated protection, monitoring, and control

REL52001 Easergy P3U30, 4L, 4U, 16DI/8DO, Uaux: V, DI: V, 2 x RJ-45

Relion 620 series. Transformer protection and control RET620 ANSI Product guide

Overcurrent and Earth-Fault Relay REJ 525. Technical Reference Manual

MiCOM P12x/y. Three phase and earth fault overcurrent relays

Power Systems Communications Implementation of IEC61850 in a Substation Environment

7SR23 DAD High Impedance Protection Relay Energy Management

ATV340D75N4E variable speed drive - 75kW- 400V - 3 phases - ATV340 Ethernet

Feeder Protection REF615 ANSI. Product Guide

Content FPC 200. USER MANUAL Mar Feeder F1 and F3 Motor M1 and M3 Busbar B2 and B3 Transformer T1 and T3

MiCOM P12x/y AREVA T&D. Three phase and earth fault overcurrent relays

SIPROTEC 5 V7.8 Protection, automation and monitoring for digital substations

SACE Emax 2 Specification guide

Function permission: yes/no. Operating range: 0.10 to 30 xin (step 0.01) Operating time: 0.02 to 300 s (step 0.01 s) Activation level 100%

Approval...6. Current Revision...7. Introduction... 8 About PJM Manuals... 8 About This Manual... 8 Using This Manual...9

MiCOM P111. Three phase and earth fault overcurrent relays

System Protection and Control Subcommittee

Busbar protection REB 670

Maximize protection. Sepam series 10, 20, 40, 60, 80. Modular range of digital protection relays

High impedance protection relay

VIP 40/45 VIP 400/410

SIPROTEC easy 7SJ45 Numerical Overcurrent Protection Relay Powered by CTs

SIPROTEC. Numerical Overhead Contact Line Protection for AC Traction Power Supply 7ST6. Preface. Introduction 1. Functions 2

Perfect protection smallest space

SIPROTEC 4 7SD61 Differential Protection Relay for Two Line Ends

C C CIRCUIT-BREAKERS Moulded-case (MCCB), general. 1. Introduction. 2. General description

Content FPC 400. USER MANUAL Apr Feeder F3 Motor M4 Busbar B3 Transformer T4

ATV340D18N4E variable speed drive - 18kW- 400V - 3 phases - ATV340 Ethernet

Maximize process uptime with the SEL-patented motor thermal model.

Numerical Protective and Management Relays

DIN Series MINIATURE CIRCUIT BREAKERS, RESIDUAL CURRENT CIRCUIT BREAKERS. Introducing the DIN Series High-quality, high-performance circuit breakers

Transcription:

GUIDEFORM SPECIFICATION Transformer Protection and Control RET630 Numerical transformer protection in medium voltage networks The freely configurable relay is intended for protection, control, measurement and supervision of medium-sized and large two-winding power transformers, including step-up transformers, and power generator-transformer blocks in utility and industrial power distribution systems. Mechanical and construction details The relay shall have compact dimensions not exceeding 4U in height for panel door mounting installations. The relay shall support flush, semi-flush, rack and wall mounting options. As flush mounted, the relay shall meet the IP40 (with detached HMI IP42) ingress protection requirements on the front side and IP20 on the rear side and connection terminals. To facilitate quick replacement, the relay shall have detachable connectors with secure current transformer (CT) shorting. It shall be possible to quickly replace the faulty unit with a spare without disturbing any of the wiring. The relay shall have an integrated human-machine interface (HMI) or alternatively be offered with a detached HMI. The detached HMI shall enable flexible installation for reduced wiring and weight impact on the panel door of the low voltage (LV) compartment. The power supply to the detached HMI shall be provided using Power over Ethernet (PoE) to avoid additional wiring for the auxiliary voltage. The HMI of the relay shall have a large graphical display with dimensions no less than 70 mm x 100 mm and 320 x 240 pixel resolution, allowing the display of at least 10 switching objects. The HMI shall also include 5 freely configurable push buttons. Protection and control functions Differential protection for two-winding transformers The relay shall have stabilized (biased) differential protection (87T) with two independently settable stages. The stabilized (biased) low-set stage shall provide fast fault clearance while remaining stable when high currents are passing through the protected zone, which increases current measurement errors. The instantaneous high-set stage shall provide very fast clearance of severe internal power transformer faults with a high differential current regardless of their harmonics content. The operate time of the instantaneous stage shall be less than 20 ms. The necessary adaptation to the current ratios and vector groups shall be made using software (with internally settable adaptation for CT ratio matching and vector group) and all current inputs (1A and 5A) shall allow direct connection to the main CT, i.e. no interposing current transformers for matching transformer group and main CTs ratio shall be required. The stabilized (biased) stage of the differential protection shall have an adjustable three-section restraint characteristic to manage measurement errors caused by CT errors and the tap changer position. The stabilized (biased) low-set of the differential protection shall be provided with a 2nd harmonic blocking to avoid tripping at magnetizing inrush when the transformer is energized either from the HV or LV-side and with a 5th harmonic restraint to avoid tripping at overexcitation. It shall be possible to set the blocking and unblocking levels for the 5th harmonic restraint to manage excessive overvoltage situations.

2 The second harmonic restraint, together with the waveform-based algorithms, shall ensure that the low-set stage does not operate due to transformer inrush currents, including inrush currents with low harmonic content. When switching the power transformer on to a fault within the protected zone, the 2nd harmonic restraint shall not delay the operation. In such a situation, the blocking, based on the 2nd harmonic of the differential current, shall be prevented by the waveform-based algorithm. The relay shall detect CT saturation conditions and prevent the differential protection from malfunctioning during external faults. The relay shall be able to eliminate the zerosequence current from the measured current. Elimination of the zero-sequence current shall be possible for either the HV or LV winding or both. Tap changer position compensation shall be included to enable more sensitive settings to be used. The correction of the transformation ratio due to changing tap changer positions shall be done automatically based on the tap changer position information. Restricted earth-fault protection The relay shall have both high-impedance (87NH) and low-impedance (87NL) restricted earth-fault protection, freely selectable for both the HV and LV-side. The restricted low-impedance earth-fault protection (87NL) shall be based on the numerically stabilized differential current principle and the neutral-current second harmonic shall be used for blocking the function in a transformer inrush situation. No external stabilizing resistor or non-linear resistors shall be required. The operating characteristics shall be according to the definite time. Backup protection The relay shall have three separate non-directional overcurrent (50/51) stages, freely settable between 0.05 and 40 times pu. The operation characteristic of the low and high-set stages shall be settable to either definite time (DT) or inverse definite minimum time (IDMT), supporting various types of inverse curves, including a user-definable one. The instantaneous stage shall support the peak-to-peak measurement mode and include a possibility to introduce a dedicated two-time setting value peak detection for fast operation in conditions when the current transformers have saturated. The number of overcurrent stages shall be available for the LV and HV-side respectively. It shall be possible to select the number of started phases for operation, either one, two or all three phases. The relay shall include two negative-sequence overcurrent protection (46) stages for both the HV and LV side, settable between 0.01 and 5 times pu. The relay shall include three-phase thermal overload protection (49T) and shall protect the transformer mainly from short-time overloads. The protection shall be able to utilize either one or two time constants, which shall be selectable. The relay shall have two-stage underimpedance protection (21GT) as backup protection against short circuits at the generator terminals or on the HV-side of a step-up transformer when used for generator transformer block differential protection. Underimpedance protection shall be applied instead of definite time voltagedependent overcurrent protection to obtain a limited protection zone and an optimum operating time. The relay shall have non directional earth-fault protection (51N) as backup protection for remote earth-faults and internal transformer earth faults.

3 Other protection The relay shall have overexitation (V/Hz) protection (24) to protect the generators and power transformers against an excessive flux density and saturation of the magnetic core. The relay shall have comprehensive voltage protection, including at least overvoltage (59), undervoltage (27), positive-sequence overvoltage(47o+), positive-sequence undervoltage (47U+), negative-sequence overvoltage (47O-) and residual overvoltage (59G) protection. It shall be possible to apply the protection on the HV or the LV side of the transformer. The relay shall have circuit breaker failure protection (51BF/51NBF) for both the HV and LVside of the transformer. The function shall have independent timers for repeated tripping of the same breaker and backup tripping of the upstream breaker. The function shall facilitate enhanced protection selectivity by avoiding tripping of the upstream breaker if the repeated tripping of the breaker closest to the fault is successful. The relay must have three-stage frequency protection, including at least overfrequency (81O), underfrequency (81U) and frequency rate-ofchange (81R) protection with rate-of-rise or rateof-fall freely selectable for each stage. Control functionality The relay shall include manual and automatic voltage regulation (90V) of power transformers with a motor-driven on-load tap-changer. The voltage regulator function shall have the following features: Parallel operation of up to four power transformers Parallel operation modes according to masterfollower, minimizing circulating current and negative reactance principles Support for necessary data exchange between relays using IEC 61850-8-1 GOOSE messaging when power transformers are running in parallel Line drop compensation for both single power transformers and transformers running in parallel - - Out-of-step supervision for followers in the master-follower mode - - Possibility to apply reduced set-point voltage setting in case of a temporary power shortage within the supplying network - - Both definite time (DT) and inverse definite minimum time (IDMT)- based time delay modes for the tap-changer step-timer. This allows either a fixed time delay or an inverse time delay, based on the difference between the measured and the target voltage level, to be applied for the steptimer. - - Fast lowering feature that is activated when a specific set voltage value is exceeded due to large load rejection. In this case, the voltage regulator drives the on-load tap-changer to reach the desired LV-side voltage as fast as possible. - - Blocking of the operation in an overcurrent situation - - Blocking of the operation in case the measured voltage is too low to be regulated by the tapchanger - - Supervision of the tap-changer response to the given control command and issuing of an alarm if the performance is not within the set performance limits The relay shall include a synchrocheck (25) function for circuit breaker closing. The function shall check voltage, frequency and angle conditions between two network parts before allowing the circuit breaker to close. - - To enable circuit breaker closing in case of two asynchronous networks, the function shall compensate for the measured slip frequency and the circuit breaker closing delay. - - The synchrocheck function shall perform an energizing check prior to connecting a dead section of the network to an energized one, to ensure safe reconnection of disconnected lines. - - In case of a fuse failure, it shall be possible to block the synchrocheck function. The relay shall support the control of at least 10 objects, including at least 2 circuit breakers and 8 disconnectors/earthing switches freely selectable for control or indication only.

4 Transformer monitoring The relay shall include online monitoring (26/49HS) for calculating the hot spot temperature of the transformer winding, the momentary aging rate of the insulation and the resultant loss of life caused by thermal stress. The hot spot temperature and the momentary aging rate shall be calculated based on the IEC 60076-7 or the IEEE C57.91-2011 standard, according to a user-defined setting. The calculation of the transformer s overall loss of life is measured in years. It shall be possible to apply this function both to new transformers and transformers already in use. Inputs and outputs The relay shall have a scalable amount of binary inputs and outputs. The number of binary inputs shall be scalable up to 50 and the number of binary outputs to 45. The relay shall have at least 3 trip output relays with integrated trip circuit supervision (TCS). The trip output relays shall be rated to make and carry 30 A for 0.5 s The threshold voltage of the relay s binary inputs shall be independently settable between 15...221 V DC. The binary inputs of the relay shall, when energized, utilize a higher inrush current to facilitate the breaking of possible dirt or sulfide from the surface of the activating contact. The relay shall optionally include 8 RTD/analog inputs and 4 ma outputs settable between -20 ma and +20 ma. The RTD/analog input shall support various options, e.g. RTDs, ma signals, voltages and resistance arrays. The RTD inputs shall support both 2-wire and 3-wire measurements for RTD and resistance modes. The phase current inputs and the residual current input of the relay shall be rated 1/5 A. The selection of 1 A or 5 A shall be software-based. For applications requiring sensitive earth-fault protection the relay shall offer an optional 0.1/0.5 A residual current input. The selection of 0.1 A or 0.5 A shall be software-based. Measurements, alarms and reporting The relay shall have three-phase current, residual current and voltage measurement with an accuracy of ±0.5%, and positive and negative sequence current and voltage measurement with an accuracy of ±1%. The relay shall support current and voltage phaseangle measurement viewing via the local HMI. To collect sequence-of-events (SoE) information, the relay must incorporate a non-volatile memory with a capacity of storing at least 1000 event codes with associated time stamps and userdefinable event texts with a minimum resolution of 1 ms. The relay shall include a numerical disturbance report containing information on the fault. The report shall incorporate the recording time, prefault and postfault time, prefault amplitude, prefault angle, fault amplitude and fault angle trip values. The report shall be stored in a non-volatile memory and be accessable via the local HMI. The relay shall have a disturbance recorder supporting a sampling frequency of 20 samples per cycle and featuring up to 40 analog and 64 binary signal channels. The relay shall support not less than 100 recordings with a sampling frequency of 20 samples per cycle, each recording 3.4 seconds in length, 10 analog channels and 64 binary channels.

5 Communication The relay must support IEC 61850 Edition 1. The relay must support, besides IEC 61850, simultaneous communication using one of the following communication protocols: IEC 60870-5- 103 or DNP3 (TCP). The relay shall have an Ethernet port with a galvanic (RJ-45) or an optical (LC) interface. The relay must have an Ethernet port (RJ45) on the front for local parametrization and data retrieval. The relay shall support up to five IEC 61850 (MMS) clients simultaneously. The relay must support IEC 61850 GOOSE messaging and meet the performance requirements for tripping applications (<10 ms) as defined by the IEC 61850 standard. The relay shall support sharing analog values, such as temperature, resistance and tap positions using IEC 61850 GOOSE messaging. The relay must support the SNTP (Simple Network Time Protocol) and IRIG-B (Inter-Range Instrumentation Group - Time Code Format B) time synchronization methods. Engineering and configurability The relay must have 4 independent settings groups for the relevant protection settings (start value and operate time). It must be possible to change protection setting values from one setting group values to another via the local HMI, using a binary input signal, and remotely through the communication link. The relay must have a web browser-based humanmachine interface (WHMI) that shall provide access to: Sequence-of-events (SoE) Device status Parameter settings Measurements Disturbance records Phasor diagram Programmable LED status The relay HMI and configuration tool shall have multilingual support. The relay HMI and configuration tool shall support both IEC and ANSI protection function codes. The relay shall have at least 15 freely configurable programmable three-color LEDs. The relay must have at least 4 user-configurable local HMI pages including measurements and single line diagram (SLD). The relay shall have a graphical configuration tool for the complete relay application including multilevel logic programming support, timers and flipflops. The relay configuration tool must include online visualization of the relay application state. It must be possible to keep the relay configuration tool up-to-date using an online update functionality. The relay configuration tool shall support viewing of relay events, disturbance reports and visualization of disturbance recordings. The relay configuration tool must include the complete relay documentation including operation and technical details. The relay configuration tool must include functionality for comparing the archived configuration to the configuration in the relay. The relay configuration tool must allow configuration of IEC 61850 vertical and horizontal communication including GOOSE. The relay configuration tool must support importing and exporting of valid IEC 61850 files (ICD, CID, SCD, IID). The relay configuration tool must be compatible with earlier relay versions. It shall be possible to freely assign current and voltage inputs to protection and measurement functions.

Type tests and other compliance requirements The relay shall have a continuous operational temperature range of -25 +55⁰C and transport and storage temperature range of -40...+85⁰C. The relay must fulfill mechanical tests IEC 60255-21-1, -2 and -3 according to Class 1 for vibrations, shock, bump and seismic compliance. The relay must fulfill the electromagnetic compatibility (EMC) tests according to IEC 60255-26. The relay must be tested according to the requirements of the IEC or an equivalent standard. Additional information For more information, please contact your local ABB representative or visit our website at: www.abb.com/substationautomation www.abb.com/mediumvoltage abb.com/mediumvoltage The information in this document is subject to change without notice and should not be construed as a commitment by ABB. ABB assumes no responsibility for any errors that may appear in this document. ABB is a registered trademark of the ABB Group. All other brand or product names mentioned in this document may be trademarks or registered trademarks of their respective holders. 1MRS758402 B Copyright 2018 ABB. All rights reserved.